36C24218Q0523-00002000.docx

DOCX document 18 KB Posted

Attached to
ALBANY Boiler/Chiller plant water treatment (VA-18-00062523)
Solicitation number
36C24218Q0523
Issued by

About this file

36C24218Q0523 00002 36C24218Q0523 00002.docx

View the file

Other files

File Type Posted
36C24218Q0523-00001000.docx DOCX document
36C24218Q0523-000.docx DOCX document
36C24218Q0523-001.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5. PROJECT NUMBER (if applicable)

CODE

7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER

3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE

OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO.

1. CONTRACT ID CODE

FACILITY CODE

CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office.

is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

BY

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER

16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30

PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer) 00002 05-29-2018

NONE

Department of Veterans Affairs Samuel S . Stratton VA Medical Center 113 Holland Avenue (2-90NCA) Albany

NY

12208-3410 Department of Veterans Affairs Samuel S . Stratton VA Medical Center Network Contracting Activity 113 Holland Avenue (2-90NCA) Albany

NY

12208-3410 To all Offerors/Bidders

36C24218Q0523 05-29-2018

X X The purpose of this solicitation amendment is to respond to RFI's submitted regarding the SOW for work to be performed. The questions and responses are provided on page 2 of this document.

In order to allow for individuals to account for these changes, the close date of the solicitation has been extended to Wednesday June 6, 2018 at 4pm EST.

New RFI's will not be accepted after Thursday May 31, 2018 at 12pm Noon.

ANTHONY MURRAY

CONTRACTING OFFICER

Contractors who are interested in the solicitation posed the following questions.

RFI 1:

WE are interested in bidding this. Can you please tell me how to acquire plans and specs?

RFI 1 Response: We do not have plans of specs for this currently available.

RFI 2: (with responses) A.2 states “Solid Products”…..A.5 mentions liquid products for boilers. I believe there is currently a mix for the boiler especially the amine is liquid. Please clarify solid vs liquid products. Solid for everyday use. Liquid and powder chemicals to layup boiler wet and to treat quickly condensate and boilers.

A.5 states….. liquid Amine as needed to help protect the condensate return lines and maintain return pH 7.5 - 8.0…. We were told during a walkthrough that the amine is used only to treat the steam lines in the boiler plant and does not feed to the steam lines to the building. For purposes of this bid are we treating just the steam lines in the boiler plant as is currently done or expanding the treatment now to the building? Currently Amine is to treat the chiller plant steam to the heat exchangers.

Who owns the current dry product feeders? MIS of America

Who owns the existing cooling tower blowdown/chemical feed controllers? MIS of America

RFI 3:

Scope of Work Section A there is a conflict of information.

Under item 2. – it states all tower and boiler chemicals shall be solid products.

Then under Item 5. – it discusses the need for boiler de-scaler, liquid amine, liquid alkalinity booster, and liquid phosphate.

Please clarify which type of chemicals will be required.

RFI 3 Response: The need for de-scaler, liquid amine, liquid alkalinity booster, and liquid phosphate is to layup a boiler when not in use and to bring a boiler quickly back into the proper chemical range if the said boiler fall out of chemistry parameters.

Also… bromine tablets are needed for tower water treatment for quick disinfection and/or for use in the brominators.