The file's text, extracted by GovTribe without its formatting.
Statement of Work
1. Purpose and Scope The Contractor shall supply and deliver heating oil and diesel fuel to the Togus VA Medical Center (VAMC) and identified off-campus locations. Deliveries shall support residential heating, emergency generators, and a diesel-driven fire pump. Fuel delivery and any required maintenance services are subject to clarification as noted separately.
2. Period and Locations of Performance The period of performance for this requirement is twelve (12) months, beginning December 4, 2026, and ending December 3, 2027 (base period). This requirement includes one (1) option period, which may be exercised at the Government’s discretion in accordance with the terms of the contract.
Delivery locations are identified below and in Attachment 1, Campus Map (rough locations). Eight heating-oil fill pipes are outdoors and accessible by standard delivery truck. Unless otherwise noted, tanks are VA-owned.
3. Heating Oil Requirements The Contractor shall schedule heating-oil deliveries using heating degree days and shall also accept will-call orders when unusually cold weather or other circumstances increase consumption. Emergency heating-oil orders shall be fulfilled within 24 hours after placement.
| Location |
| Tank capacity |
| FY26 usage |
| Quarters 15 |
| 275 gal |
| 907 gal |
| Quarters 16 |
| 275 gal |
| 834 gal |
| Quarters 17 |
| 275 gal |
| 979 gal |
| Quarters 18 |
| 275 gal |
| 895 gal |
| Quarters 19 |
| 275 gal |
| 928 gal |
| Quarters 20 |
| 275 gal |
| 1,117 gal |
| Quarters 27 |
| 275 gal |
| 916 gal |
| Quarters 32 |
| 275 gal |
| 994 gal |
4. Diesel Fuel Requirements The Contractor shall provide diesel fuel for emergency generators and the fire pump. For routine generator top-offs, the VA point of contact will request deliveries during regular business hours and schedule them before tanks become empty. Routine diesel orders shall be fulfilled within 72 hours of placement.
During power outages, the Contractor shall respond to emergency diesel orders within three hours of placement and remain available for fueling as frequently as every four hours until the outage ends.
| Equipment |
| Location |
| Tank information |
| G-4 / G-8 |
| Building 200, Room 195 |
| Shared 2,000-gal tank |
| G-5 |
| Outside near Building 249 |
| Not specified |
| G-7 |
| Inside Building 238 |
| Not specified |
| G-9 / G-10 |
| Building 244, Room 100 |
| Shared 2,000-gal tank |
| G-11 |
| Outside near Building 210 |
| 475-gal tank |
| P-1 |
| Large portable; currently near Salt Shed |
| Not specified |
| P-3 |
| Small portable; near Salt Shed |
| Not specified |
| P-4 |
| Small portable; near Building 249 |
| Not specified |
| P-6 |
| 35 State Hospital Dr., Bangor, ME 04401 |
| Not specified |
| P-7 |
| 15 Challenger Dr., Lewiston, ME 04240 |
| Not specified |
| P-8 |
| Portable; location not specified |
| Not specified |
| FP-1 (fire pump) |
| Building 200, Room 195A |
| 275-gal tank |
The Contractor shall fill fire-pump tank FP-1 every two months unless otherwise directed. The Contractor shall ensure the tank remains at least three-quarters full for NFPA compliance.
5. Delivery Records and Invoicing For each shipment or delivery, the Contractor shall provide documentation identifying the supplier, delivery date, and quantity delivered to each location. Invoices shall either be separate for each tank/building or provide an itemized breakdown by tank on a consolidated invoice.
6. Spill Prevention and Response The Contractor shall submit a comprehensive Spill Prevention and Response Plan for VA approval. The plan shall address spill prevention and containment, confirm driver training, and establish communication procedures for spills of 10 gallons or more. It shall include emergency telephone numbers for the Contractor, remediation companies, and appropriate state and federal authorities.
7. Government Information and Records The Contractor shall comply with applicable federal and VA records-management, privacy, and information-protection requirements, including the statutes and regulations cited in the original SOW: 44 U.S.C. chapters 21, 29, 31, and 33; 5 U.S.C. §§ 552 and 552a; and 36 CFR Parts 1222 and 1228.
All records, deliverables, electronic information, and supporting documentation produced under the contract are Government property, with the Government retaining the rights described in the original SOW. The Contractor shall create and maintain only contract-authorized Government records; safeguard sensitive information; preserve records regardless of format or completion status; and not retain, use, sell, disseminate, remove, or destroy protected information or records except as authorized. Disposal requires prior written Contracting Officer approval. The Contractor shall provide sufficient technical documentation to enable Government use of delivered data.