This file contains questions and answers related to technical specifications for a boiler maintenance contract at White River Junction VAMC. The Q&A provides detailed information about three boilers: two 15,000 PPH Industrial Water Tube boilers (SP-110s-1A-40 and SP-NOS-1A-40) and one 6,000 PPH Flex Tube boiler (FLX-100-800-150ST). The document specifies plant pressure settings of 70 PSI with safety reliefs at 130-135 PSI, Hawk 5000/4000 series burners, and various meters/controls including Endress+Hauser flow meters, Fluid Components gas meters, and Cleaver Brooks O2 sensors. The VA will supply up to $10K in parts, and Coastal Inspection Services will perform cleaning and inspection services. The document includes an image of an Allen-Bradley control module that appears to be part of the boiler control system.

View the file

Other files for this federal contract opportunity

Other files attached to J044--Boiler Maintenance, newest first.
File Type Posted
36C24125Q0110 0001.docx DOCX document
36C24125Q0110.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

QUESTIONS:

1. Make / model and Horsepower of each boiler, water tube or fire tube style?

2. Steam pressure?

3. Is the VA supplying all parts to be replaced?

4. Make / Model of each burner

5. Make / Model of burner controls and flame safeguards

6. Make / Model of Plant Wide Controller

7. Make / Model of Steam, feed water, gas, oil, etc. meters that are required to be calibrated.

8. Brand of SCADA?

9. Is the boilers integrated with a BMS?

10. Is the VA opening and closing the boilers annually?

11. Who will perform the cleaning and inspection?

12. Does JRCS need to supply any gaskets for the boilers?

ANSWERS:

1. Makes/Models

A. Boiler#1 Make: SP-110s-1A-40, S/N: SP-4387, 15,000 PPH, Industrial Water Tube.

B. Boiler#2 Make: SP-NOS-1A-40, S/N: SP-4388, 15,000 PPH, Industrial Water Tube.

C. Boiler#3 Make: FLX-100-800-150ST, SN: 010492-1-1, 6,000PPH Flex Tube

2. Safety pressures are all 130# and 135# safety reliefs, Plant pressure runs at 70#.

3. Up to $10K

4. Model/S/N

A. Hawk 5000, #1 Make: EL-210, SN: 58912-715, B. Hawk 5000, #2 Make: EL-210, SN: 58912-715, C. Hawk 4000 #3 Make:VLA-80, SN: 59268-715,

5. Model: BLV512, Fireye YB-110-YB-230, Flame scanner: ProFlame ZPF-130

6.

7. Make/Model

A. Steam: Endress+Hauser ProWIRL F, Model: 73F1H-SK4AA1AB4AW

B. F/W: Endress+Hauser ProMag P, Model: 50P40-ELOA1AA0BBAW

C. Gas: Fluid Components International, Model ST51-4P110001

D. Oil: Contoil, Model: VZF RC 130/16

E. O2: Cleaver Brooks, Model: ZR202G

8. Cleaver Brooks

9. Halfway

10. Yes,

11. Coastal Inspection Services

12. No