QUESTIONS N ANSWERS.pdf
PDF 201 KB Posted
- Attached to
- J044--Boiler Maintenance Federal contract opportunity
- Solicitation number
- 36C24125Q0110
About this file
This file contains questions and answers related to technical specifications for a boiler maintenance contract at White River Junction VAMC. The Q&A provides detailed information about three boilers: two 15,000 PPH Industrial Water Tube boilers (SP-110s-1A-40 and SP-NOS-1A-40) and one 6,000 PPH Flex Tube boiler (FLX-100-800-150ST). The document specifies plant pressure settings of 70 PSI with safety reliefs at 130-135 PSI, Hawk 5000/4000 series burners, and various meters/controls including Endress+Hauser flow meters, Fluid Components gas meters, and Cleaver Brooks O2 sensors. The VA will supply up to $10K in parts, and Coastal Inspection Services will perform cleaning and inspection services. The document includes an image of an Allen-Bradley control module that appears to be part of the boiler control system.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24125Q0110 0001.docx | DOCX document | |
| 36C24125Q0110.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
QUESTIONS:
1. Make / model and Horsepower of each boiler, water tube or fire tube style?
2. Steam pressure?
3. Is the VA supplying all parts to be replaced?
4. Make / Model of each burner
5. Make / Model of burner controls and flame safeguards
6. Make / Model of Plant Wide Controller
7. Make / Model of Steam, feed water, gas, oil, etc. meters that are required to be calibrated.
8. Brand of SCADA?
9. Is the boilers integrated with a BMS?
10. Is the VA opening and closing the boilers annually?
11. Who will perform the cleaning and inspection?
12. Does JRCS need to supply any gaskets for the boilers?
ANSWERS:
1. Makes/Models
A. Boiler#1 Make: SP-110s-1A-40, S/N: SP-4387, 15,000 PPH, Industrial Water Tube.
B. Boiler#2 Make: SP-NOS-1A-40, S/N: SP-4388, 15,000 PPH, Industrial Water Tube.
C. Boiler#3 Make: FLX-100-800-150ST, SN: 010492-1-1, 6,000PPH Flex Tube
2. Safety pressures are all 130# and 135# safety reliefs, Plant pressure runs at 70#.
3. Up to $10K
4. Model/S/N
A. Hawk 5000, #1 Make: EL-210, SN: 58912-715, B. Hawk 5000, #2 Make: EL-210, SN: 58912-715, C. Hawk 4000 #3 Make:VLA-80, SN: 59268-715,
5. Model: BLV512, Fireye YB-110-YB-230, Flame scanner: ProFlame ZPF-130
6.
7. Make/Model
A. Steam: Endress+Hauser ProWIRL F, Model: 73F1H-SK4AA1AB4AW
B. F/W: Endress+Hauser ProMag P, Model: 50P40-ELOA1AA0BBAW
C. Gas: Fluid Components International, Model ST51-4P110001
D. Oil: Contoil, Model: VZF RC 130/16
E. O2: Cleaver Brooks, Model: ZR202G
8. Cleaver Brooks
9. Halfway
10. Yes,
11. Coastal Inspection Services
12. No
File details come from the government source that posted it. Updated .