About this file

This document is an amendment to a federal solicitation for Underground and Above Ground Storage Tank Inspection/Testing Services for the VA Boston Healthcare System. The amendment provides responses to industry questions, an updated Statement of Work, and a revised Price/Cost Schedule.

The key details are:

  • The VA Boston Healthcare System has a requirement for inspection and testing services for underground and aboveground storage tanks at its Brockton, West Roxbury, and Jamaica Plain locations. This includes annual testing, 3-year inspections, and 5-year permit renewals.
  • The contractor must submit applications for state and local permits on behalf of the VA.
  • Pricing is requested for annual services such as automatic tank gauge testing, UST testing inspections, AST annual inspections, fuel conditioning, and hydrostatic testing of sumps and spill buckets.
  • Quotes are due by 11:00 AM EST on 6/28/2024.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5. PROJECT NUMBER (if applicable)

CODE 7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO. 1. CONTRACT ID CODE

FACILITY CODE CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30 PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243

(Type or print) (Type or print)

(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code)

(If other than Item 6)

(Specify type of modification and authority)

(such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer)

1 17

36C241

Department of Veterans Affairs Network Contracting Office 1 (NCO 1) VA Boston Healthcare System 940 Belmont Street Brockton MA 02301-5596

Department of Veterans Affairs Network Contracting Office 1 (NCO 1) VA Boston Healthcare System 940 Belmont Street Brockton MA 02301-5596

To all Offerors/Bidders 36C24124Q0617

06-25-2024 X

X X

See CONTINUATION Page

X 1

Amendment 0002: Underground and Above Ground Storage Tank Inspection/Testing Services at VA Boston Healthcare System

1. The purpose of this amendment is to provide responses to industry questions.

2. The purpose of this amendment is to provide an updated Statement of Work (SOW).

3. The purpose of this amendment is to provide a revised Price/Cost Schedule.

4. Please submit quotes to Subrena Magee | subrena.magee@va.gov NLT 11:00AM EST on 6.28.2024.

Issa J. Shawki Contracting Officer

RFQ 36C24124Q0617

Industry Q &A

Question 1: When would the first 3-year hydrostatic testing be needed for each UST?

Answer 1: October 2026

Question 2: When is the next 3rd party inspection due for each UST?

Answer 2: Brockton: 2/13/2025, West Roxbury: 3/21/2025, Jamaica Plain: 4/16/2025

Question 3: Is this a brand name contract OR is there is (was) an incumbent performing these services?

Answer 3: There was an incumbent performing the MassDEP UST/AST regulatory requirements. This is a new contract which includes fuel oil analysis and tank cleanings.

Question 4: If not brand new, could you please provide the current/previous contract number?

Answer 4: Department of Veterans Affairs Contract No: 36C24123P1242 for the MassDEP UST/AST regulatory requirements.

Question 5: One of the UST Tanks listed for WR SOW has been removed according to the UST registry. Please confirm and update the tank list.

Bldg. 10 Grounds #11 Removed (2017) 2,500 UST

Answer 5: Correct. Bldg. 10 Grounds 2,500 UST was removed in 2017. SOW has been corrected/updated.

Question 6: The two Boiler Tanks for WR are listed as 20,000 gal, in the SOW. The UST registry shows them as 25,000 gal. each. Please confirm the correct size.

Answer 6: Correct. The two Boiler Tanks for WR are 25,000-gal double-walled fiberglass reinforced USTs which maintain the No. 2 fuel oil for the five boilers located in Building 8. SOW has been corrected/updated.

Question 7: The VA Brockton Grounds Diesel 4,000 gal. UST is listed as a 3,000 gal. UST in the registry. Please confirm the correct size.

Answer 7: Grounds Diesel is 4,000 gal. Grounds gasoline is 3,000 gal.

Question 8: When are the next 3-year UST testing due for each location:

Answer: See Response for Answer 2

Questions 9: The new MassDEP 2024 requirements been completed? (Install dates for all equipment/components-Spill buckets, sumps).

Answer 9: Yes.

Question 10: When are the next 3-year Hydrostatic testing of sumps & Spill buckets due for each location?

Answer 10: See answer 1.

Question 11: When is the annual Stage 1 testing due for W. Roxbury & Brockton?

Answer 11: W. Roxbury May 2024, Brockton August 2024.

Question12: When are the next AST Use Permits (5yr.) due for Jamaica Plain?

Answer 12: 5/3/2026

Question 13: When are the next Annual ATG tests due for each location/tank?

Answer 13: August 2024 for all three sites.

Question 14: What month are the annual fuel conditioning services due for each location?

Answer 14: No official due dates required. The VA would like them done during the spring or fall.

Question 15: Do you need STI inspections on all AST tanks to meet your SPCC plan regulations?

Answer 15: No.

Question 16: The SOW #3- for annual fuel conditioning – a. bottom pump services to remove sludge & water. By definition, Bottom pump only removes bulk water from the tank. Do you also want the fuel filtered? (Best practice to ensure fuel quality)?

Answer 16: Best practice to ensure fuel quality.

Question 17: Line Item clarifications:

Line items 0002, 1002, 2002, 3002, 4002: UST testing inspections has a quantity of 12. I counted 14 UST tanks across all locations. Are you requesting pricing per tank?

Answer: VA Boston was previously charged one UST price for both the Brockton Boiler Plant UST’s and the West Roxbury Boiler Plant UST’s. If individual UST tanks need to be priced, then the correct count is 14.

Question 18: Line items 0002, 1002, 2002, 3002, 4002: And if UST testing is only every 3-years, why is it a line item every year? Should we quote for every year, even if services are not due?

Answer: Yes, please quote for every year. The vendor shall only invoice for each UST that requires testing.

Question 19: Line Items 0005, 1005, 2005, 3005, 4005: Hydrostatic Testing of all Sumps & Spill buckets has a quantity of 12. Does this mean that there is a combined total of 12 (sumps & Spill buckets), across all locations?

Answer: SOW has been correct to reflect a total of 14 UST’s. Hydrostatic Testing of all Sumps & Spill buckets should be built into one price per UST. Every UST has one sump and one spill bucket.

Question 20: Line Items 0005, 1005, 2005, 3005, 4005: And if Hydrostatic testing is only every 3-years, why is it a line item every year? Should we quote for every year, even if services are not due?

Answer: Yes, the same as question 18.

Question 21: Line Items 0006, 1006, 2006, 3006, 4006: Completing AST use permits has a quantity of 2, however there are 3-tanks that require a Use permit. Is this quantity correct?

Answer: No. SOW corrected to reflect 3-tanks.

Question 22: Line Items 0006, 1006, 2006, 3006, 4006: Why is pricing requested every year if services are only needed every 5 years?

Answer: Yes, the same as question 18. This allows the VA some flexibility in case any UST’s or AST’s are added or removed.

Question 23: Line items 0007, 1007, 2007, 3007, 4007: Completing annual fuel conditioning and testing of fuel services has a quantity of 34. I counted 38 tanks across all locations. Are you requesting pricing per tank?

Answer: Yes. SOW corrected to 38 tanks across all locations.

Question 24: On the Price/Cost Schedule: For the Fuel Testing/Conditioning – The fuel treatments are dependent on the fuel analysis, and there is 1 price line for both events. Should I be pricing the out assuming all tanks will need treatments/bottom pumps out? If so, the price will be high and will not be competitive.

Answer 24: The SOW and Price/Cost Schedule has been adjusted.

Statement of Work

Underground and Above Ground Storage Tank Inspection/Testing Services

VA Boston Healthcare System

Scope of Work

1. The Contractor shall provide tank inspection/testing services for the listed inventory below. VA Boston Healthcare System (VABHS) has three facilities that have above and below ground storage tanks. All Underground Storage Tanks (UST) have Veeder Root or equivalent Automatic Tank Gauge (ATG) monitoring systems.

2. The Contractor shall submit state and local permits applications with associated fees on behalf of VABHS to required state/local regulators. These will include aboveground storage tanks (AST) user permits, inspections and permits to maintain existing underground storage tanks.

3. The Contractor will perform Annual Fuel Conditioning and Testing of fuel storage tanks located at the Boston Healthcare System, Brockton, West Roxbury, and Jamaica Plain Division.

a. Provide bottom pump services to remove any sludges and water accumulated in the tank.

b. Fuel treatments needed to prohibit any microbial growth and support fuel stability.

c. Provide written results of the condition of caps, gaskets, fittings, and vents.

d. Perform sampling and analysis of all tanks per ASTM Standards, NFPA 110-2010: 8.3.8, with a certified report provided to the VA of the following tests at a minimum:

1) Visual Appearance

2) Water

3) Microbial Growth

4) Particulate Contamination

5) Water & Sediment

4. The Contractor shall leave each work site clean based on the work that was performed, no oily rags, absorbents, or other debris will be left on site. Provide inventory of waste shipment to VA.

5. The Contractor is responsible for all labor, materials, tools, and special equipment required to perform the work.

6. The Contractor shall check in with the Engineering Dept. and be escorted by a VA staff member at all times.

7. The Contractor shall comply with all applicable records management laws and regulations, as well as National Archives and Records Administration (NARA) records policies, including but not limited to the Federal Records Act (44 U.S.C. chs. 21, 29, 31, 33), NARA regulations at 36 CFR Chapter XII Subchapter B, and those policies associated with the safeguarding of records covered by the Privacy Act of 1974 (5 U.S.C. 552a). These policies include the preservation of all records, regardless of form or characteristics, mode of transmission, or state of completion.

In accordance with 36 CFR 1222.32, all data created for Government use and delivered to, or falling under the legal control of, the Government are Federal records subject to the provisions of 44 U.S.C. chapters 21, 29, 31, and 33, the Freedom of Information Act (FOIA) (5 U.S.C. 552), as amended, and the Privacy Act of 1974 (5 U.S.C. 552a), as amended and must be managed and scheduled for disposition only as permitted by statute or regulation. In accordance with 36 CFR 1222.32, the Contractor shall maintain all records created for Government use or created in the course of performing the contract and/or delivered to, or under the legal control of the Government and must be managed in accordance with Federal law. Electronic records and associated metadata must be accompanied by sufficient technical documentation to permit understanding and use of the records and data.

VHA and its contractors are responsible for preventing the alienation or unauthorized destruction of records, including all forms of mutilation. Records may not be removed from the legal custody of VHA or destroyed except in accordance with the provisions of the agency records schedules and with the written concurrence of the Head of the Contracting Activity. Willful and unlawful destruction, damage, or alienation of Federal records is subject to the fines and penalties imposed by 18 U.S.C. 2701. In the event of any unlawful or accidental removal, defacing, alteration, or destruction of records, the Contractor must report to VHA. The agency must report promptly to NARA in accordance with 36 CFR 1230. The Contractor shall immediately notify the appropriate Contracting Officer upon discovery of any inadvertent or unauthorized disclosures of information, data, documentary materials, records, or equipment.

Disclosure of non-public information is limited to authorized personnel with a need-to-know as described in the [contract vehicle]. The Contractor shall ensure that the appropriate personnel, administrative, technical, and physical safeguards are established to ensure the security and confidentiality of this information, data, documentary material, records, and/or equipment is properly protected. The Contractor shall not remove material from Government facilities or systems, or facilities or systems operated or maintained on the Government’s behalf, without the express written permission of the Head of the Contracting Activity. When information, data, documentary material, records, and/or equipment is no longer required, it shall be returned to VHA control, or the Contractor must hold it until otherwise directed.

Items returned to the Government shall be hand-carried, mailed, emailed, or securely electronically transmitted to the Contracting Officer or address prescribed in the [contract vehicle]. Destruction of records is EXPRESSLY PROHIBITED unless in accordance with Paragraph (4). The Contractor is required to obtain the Contracting Officer's approval prior to engaging in any contractual relationship (sub-contractor) in support of this contract requiring the disclosure of information, documentary material, and/or records generated under, or relating to, contracts. The Contractor (and any sub-contractor) is required to abide by Government and VHA guidance for protecting sensitive, proprietary information, classified, and controlled unclassified information. The Contractor shall only use Government IT equipment for purposes specifically tied to or authorized by the contract and in accordance with VHA policy. The Contractor shall not create or maintain any records containing any non-public VHA information that is not specifically tied to or authorized by the contract. The Contractor shall not retain, use, sell, or disseminate copies of any deliverable that contains information covered by the Privacy Act of 1974 or that which is generally protected from public disclosure by an exemption to the Freedom of Information Act. The VHA owns the rights to all data and records produced as part of this contract. All deliverables under the contract are the property of the U.S. Government for which VHA shall have unlimited rights to use, dispose of, or disclose such data contained therein as it determines to be in the public interest. Any Contractor rights in the data or deliverables must be identified as required by FAR 52.227-11 through FAR 52.227-20. Training. All Contractor employees assigned to this contract who create, work with, or otherwise handle records are required to take VHA-provided records management training. The Contractor is responsible for confirming training has been completed according to agency policies, including initial training and any annual or refresher training.

8. All services shall be performed in accordance with local, state, and federal tank inspection/testing regulations and guidelines. Testing/Inspection reports shall be provided to VABHS within 5 working days of performing the service. Services shall be scheduled within 5 working days of notification from VABHS. Services shall be conducted between the hours of 8am – 4pm Monday – Friday excluding federal holidays. Contractor shall contact the facility GEMS Coordinator to schedule all inspections. The Authorization & Accreditation (A&A) requirements do not apply, and that a Security Accreditation Package is not required.

VABHS – West Roxbury 1400 VFW Parkway

West Roxbury, MA 02132

1. Bldg 8 (Boiler Plant) – 2 x 25,000-gal diesel UST

a. Testing: ATG – Annual

b. Inspection: Third Party UST – every 3 years

c. Hydrostatic testing of Sumps and Spill Buckets – every 3 years

2. Bldg 10 (Grounds) – 250-gal gasoline and 1,250-gal diesel AST

a. Testing: ATG Annual

b. Stage I: Annual

3. Bldg 2 – 4000-gal diesel UST

a. Testing: ATG – Annual

b. Inspection: Third Party UST – every 3 years

c. Hydrostatic testing of Sumps and Spill Buckets – every 3 years

4. Bldg 1 – 3000-gal diesel UST

a. Testing: ATG – Annual

b. Inspection: Third party UST – every 3 years

c. Hydrostatic testing of Sumps and Spill Buckets – every 3 years

5. Annual Fuel Conditioning and Testing of the following fuel storage tanks:

Tank Location Capacity

Bldg. 1 AST Base Tank 4,000 Diesel

Bldg. 1 UST 4,000 Diesel

Bldg. 2 Gen 1 UST 4,000 Diesel

Bldg. 2 Gen 2 AST Base Tank 4,000 Diesel

Bldg. 3 Gen 1 AST Base Tank 9,000 Diesel

Bldg. 3 Gen 2 AST Base Tank 9,000 Diesel Bldg. 8 AST Base Tank 3,500 Diesel

Boiler Tank #1 UST 20,000 Diesel

Boiler Tank #2 UST 20,000 Diesel

Bldg. 20 AST Base Tank 1,500 Diesel

Bldg. 21 AST Base Tank 3,500 Diesel

Grounds AST Fueling Station 250 Gas

Grounds AST Fueling Station 1,250 Diesel

VABHS – Brockton 940 Belmont Street

Brockton, MA 02301

1. Bldg 67 – 4000-gal diesel UST

a. Testing: ATG - Annual

b. Inspection: Third Party UST – every 3 years

c. Hydrostatic testing of Sumps and Spill Buckets – every 3 years

2. Bldg 68 – 2500-gal diesel UST

a. Testing: ATG – Annual

b. Inspection: Third Party UST – every 3 years

c. Hydrostatic testing of Sumps and Spill Buckets – every 3 years

3. Bldg 69 – 2500-gal diesel UST

a. Testing: ATG – Annual

b. Inspection: Third Party UST – every 3 years

c. Hydrostatic testing of Sumps and Spill Buckets – every 3 years

4. Bldg 70 – 2500-gal diesel UST

a. Testing: ATG – Annual

b. Inspection: Third Party UST – every 3 years

c. Hydrostatic testing of Sumps and Spill Buckets – every 3 years

5. Boiler Plant – 2 x 30000-gal diesel UST

a. Testing: ATG – Annual

b. Inspection: Third Party UST – every 3 years

c. Hydrostatic testing of Sumps and Spill Buckets – every 3 years

6. Grounds – 3000-gal gasoline UST, 4000-gal diesel UST

a. Testing: ATG – Annual

b. Inspection: Third Party UST – every 3 years

c. Stage I: Annual

d. Hydrostatic testing of Sumps and Spill Buckets – every 3 years

7. Annual Fuel Conditioning and Testing of the following fuel storage tanks:

Tank Location Capacity

Bldg 67 UST 4000-gal Diesel

Bldg 68 UST 2500-gal Diesel

Bldg 69 UST 2500-gal Diesel

Bldg 70 UST 2500-gal Diesel

Boiler Plant UST 2 x 30000-gal Diesel

Grounds UST 3000-gal Gasoline

Grounds UST 4000-gal Diesel

Bldg 3 AST Base Tank 7448-gal Diesel

Bldg 3 AST Base Tank 555-gal Diesel

Bldg 25 AST Base Tank 215-gal Diesel

Bldg 34 AST Base Tank 706-gal Diesel

Bldg 32 AST Base Tank 1398-gal Diesel

Bldg 45 AST Base Tank 4 x 3575-gal Diesel

VABHS – Jamaica Plain

150 South Huntington Avenue Jamaica Plain, MA 02130

1. Bldg 1A – 11000-gal liquid nitrogen AST

a. Inspection: AST Inspection –Annual

b. Permit Submittal: AST Use Permit – every 5 Years.

2. Bldg 1A- Generator 4000-gal diesel UST

a. Testing: ATG – Annual

b. Inspection: Third Party UST – every 3 years

c. Hydrostatic testing of Sumps and Spill Buckets – every 3 years

3. Boiler Plant – (2) 40000-gal diesel AST’s

a. Testing: ATG – Annual

b. Inspection: AST Inspection – Annually

c. Permit Submittal: AST Use Permit – every 5 years.

4. Boiler Plant 1000-gal diesel AST

a. Testing: ATG -annual

5. Boiler Plant – Generator 10000-gallon UST

a. Testing: ATG – Annual

b. Inspection: Third Party UST – every 3 years

c. Hydrostatic testing of Sumps and Spill Buckets – every 3 years

6. Annual Fuel Conditioning and Testing of the following fuel storage tanks:

Tank Location Capacity

Bldg 1A UST 4000-gal Diesel

Boiler Plant UST 10000-gal Diesel

Boiler Plant AST Horizontal Tanks (2) 40,000-gal Diesel

Boiler Plant AST Convault Tank 1,000-gal Diesel

Boiler Plant AST Base Tank 3,500-gal Diesel

Building 9 AST Base Tank 515-gal Diesel

Bldg.2/3/3A PG AST Base Tank 1,200-gal Diesel

A.1 PRICE/COST SCHEDULE

ITEM INFORMATION

ITEM

NUMBER

DESCRIPTION OF

SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

15.00 EA __________________ __________________

The contractor shall provide all labor, equipment, materials and supervision to complete Automatic Tank Gauge Testing (ATG) in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, and Inspection - Fire Fighting, Rescue, and Safety Equipment;

Environmental Protection Equipment and Materials

14.00 EA __________________ __________________

supervision for UST Testing Inspections in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing,

2.00 EA __________________ __________________

supervision to complete AST Annual Inspections in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete Stage 1 Inspections in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete Hydrostatic Testing of all Sumps & Spill Buckets in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing,

3.00 EA __________________ __________________

supervision completing AST Use Permits in accordance to the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing,

38.00 EA __________________ __________________

supervision in completing Annual Fuel Conditioning and Testing of Fuel in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete Automatic Tank Gauge Testing (ATG) in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision for UST Testing Inspections in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting

Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete AST Annual Inspections in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete Stage 1 Inspections in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete Hydrostatic Testing of all Sumps & Spill Buckets in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision completing AST Use Permits in accordance to the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision in completing Annual Fuel Conditioning and Testing of Fuel in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete Automatic Tank Gauge Testing (ATG) in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision for UST Testing Inspections in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete AST Annual Inspections in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete Stage 1 Inspections in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete Hydrostatic Testing of all Sumps & Spill Buckets in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision completing AST Use Permits in accordance to the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision in completing Annual Fuel Conditioning and Testing of Fuel in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete Automatic Tank Gauge Testing (ATG) in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision for UST Testing Inspections in accordance with the attached Statement of Work (SOW).

Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete AST Annual Inspections in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete Stage 1 Inspections in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete Hydrostatic Testing of all Sumps & Spill Buckets in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision completing AST Use Permits in accordance to the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision in completing Annual Fuel Conditioning and Testing of Fuel in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete Automatic Tank Gauge Testing (ATG) in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision for UST Testing Inspections in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete AST Annual Inspections in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete Stage 1 Inspections in accordance with the attached Statement of Work (SOW).

Services

PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision to complete Hydrostatic Testing of all Sumps & Spill Buckets in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision completing AST Use Permits in accordance to the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, supervision in completing Annual Fuel Conditioning and Testing of Fuel in accordance with the attached Statement of Work (SOW).

PRINCIPAL NAICS CODE: 541620 - Environmental Consulting Services PRODUCT/SERVICE CODE: H942 - Other Quality Control, Testing, GRAND TOTAL __________________

A.1 PRICE/COST SCHEDULE
ITEM INFORMATION

File details come from the government source that posted it. Updated .