S06 Submittal for Unit 2C-AHU01.pdf

PDF 2 MB Posted

Attached to
Z2DA-- 689A4-24-200 NEWINGTON 2C DUCTWORK CORRECTIONS (VA-24-00051581)
Solicitation number
36C24124Q0349
Issued by

About this file

This document appears to be an equipment submittal for an air handling unit (AHU) proposed for the Newington VA Medical Center modernization project. The submittal provides detailed technical specifications and dimensional data for the AHU, including the various module configurations, fan sizing, coil details, and other components. The AHU will have a capacity of 33,810 CFM and includes features such as a hot water heating coil, chilled water cooling coil, 85% efficient cartridge filters, and a steam humidifier. The submittal is dated August 9, 1995 and was prepared for the Walter D. Sullivan Company, the contractor for the Newington VA Medical Center modernization project.

The related federal contract opportunity is a Request for Quote (RFQ) for Project 689A4-24-200, Newington 2C Ductwork Corrections, at the VA Connecticut Healthcare System, Newington Campus. This project appears to be separate from the equipment submittal, but may be related to the broader modernization efforts at the Newington VA Medical Center.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

The Trane Company TRA FE A Division of American Standard Inc. I 3600 Pammel Creek Road La Crosse WI 54601-7599

Equipment Submittal

Date:

August 9, 1995

Prepared For Ordering Information

• Owner. Dept Of Veterans Affairs Trane Job No.: B2-09259

• Architect.Stecker, LaBau, Arneill, McManus Trane Order No.:

Engineer Henningson, Durham, & Richardson Customer P.O. No.: VBL-BILL C.

Sold 'To: Job Name:

WALTER D. SULLIVAN COMPANY NEWINGTON V.A. MEDICAL CENTER

614 WEST MAIN STREET

MODERNIZATION

NEW BRITAIN, CT 06050

Item Qty. Description AIR HANfI IN( IINIT Tag 2C-AHU1

A 1 Size 66 Horizontal Draw Thru Modular Climate Changer Configured As Follows:

Position No. Description

1. Mixing module with top opening with damper, and access door.

2. Mixing module with top & back openings with damper, and access door.

3. Filter module with 2 inch pleated media 30% eff. Pre-filter (2C-AF1A) and 12 inch 85% eff.

Cartridge filter (2C-AF1 B).

4. Small horizontal coil module with hot water coil (2C-HC1).

5. Medium-large access module with 25 7/8 inch door.

6. Medium-large horizontal coil module with chilled water coil (2C-CC1) and sloped/pitched drain pan.

7. Medium access module with 15 3/8 inch door.

8. Supply fan module with 36.5 inch AF fan (2C-SF1) and 60 HP motor.

9. Custom 24 inch access, module with 18 inch door.

10.Custom 60 inch module with sound attenuator.

11.Custom 36 inch module with steam humidifier (2C-SH1) and 24 inch access door.

12. Discharge plenum with top opening.

Trane Sales Office — Sales Engineer

HARTFORD/ALAN C. ROMANIELLO

678-1761

Drawings in this submittal package describe the equipment we propose to furnish for this project and are submitted for approval to manufacture.

1-30.195-3-(293) Supersedes 1-30.195-3-(1088)

Approved By:

VAMC MODERNIZATION

NEWINGTON, CT.

Date 08/09/95

Time 07:44:11

Height I Length

Mixing Box Double Wall nsulation 2" 1.501b Solid

. Mixing Box Double Wall nsulation 2" 1.501b Solid

. Cartridge Filter Double Wall edia Type 12.000inches 85% Efficient Clean pressure drop condition used for fan selection Factory Supplied Media sulation 2" 1.501b Solid

869 10.03 1137.0192.00149.0011724

3 1461 10.54 1137.0192.00 1 29.50 1837

1. Hot Water Coil Double Wall 163.0 1537 10.14 I 13709200 114.50 11269

Type 2 row hot water W prima-flo alum fin, @ 80FPF & 0.020inches tubes

Airflow Type Standard Elevation 0 ft

Airflow 33810 CFM EWT 180.00 °F No turbulators fitted

EAT 0.10 °F LWT 136.57 °F

LAT 63.22 °F WFR 109.00 GPM

Cap 2314.5 MBH WPD 1.75 ftwg

Fluid 10 % Ethy glycol WTD 43.43 °F

Wet coil weight 730 lb Water Volume 16.3 GAL

Dry coil weight 594 lb Foul Factor 0.0000 hr ft2 F/BTU

Insulation 2" 1.501b Solid Water Velocity 151 FPM

Module Size SMALL

5. Access Double Wall 174.7 1453 10.00 1137 29.50 1694

Insulation 2" 1.501b Solid Module Size MED-LAR E

6. Chilled Water Coil Double Wall 163.0 537 0.75 137.0 92.00 29.50 313C

Type 8 row cooling WD prima-flo alum fin, @ 97FPF & 0.020inches tubes Airflow Type Standard

Elevation 0 ft

Airflow 33810 CFM EWT 43.00 °F Fitted turbulators

EDB 82.00 °F LWT 56.36 °F

EWB 67.00 °F WFR 229.00 GPM

LDB 52.40 °F WPD 10.02 ftwg

LWB 52.00 °F WTR 13.36 °F

Scap 1103.3 MBH Water Volume 63.2 GAL Tcap 1529.3 MBH Dry coil weight 1841 lb Fluid Hot/cold water Wet coil weight 2369 lb Insulation 2" 1.501b Solid Foul Factor 0.0000 hr ft2 F/BTU Water Velocity 158 FPM Module Size MED-LARGE

Overall dimensional data

Size Width Height Length Weight inches inches inches lb

MCC Selection & Pricing V3.14

TRANS VA M C MODERNIZATION

Date 08/09/95 C

Time 07:44:17

NEWINGTON, CT. Page 3of7 uwner V.A. Contractor VVAL I tK U. iULLIVAN CO.

Architect o to WALTER D. SULLIVAN CO.

Engineer Tags

Trane Job Unit ¢e MCC Size 66

Quantity

F. Area Vel. P.D. Width Height Length Weight inwg inc he inc he Inc he lb

7.Access Double Wall

74.7 453 0.00 137.0 92.00 19.00 596

Insulation 2" 1.501b Solid Module Size MEDIUM

O

8. Supply Fan Double Wall 16.5 2044 0.00 137.0 92.00 84.00 4111

Type 66b 36.500inches AF fan with 3O.0 HP T-frame ODP High Efficient E+3

FlowType Standard Elevation 0 ft

Airflow 33810 CFM Speed 1204 RPM No Inlet-guide vanes

ESP 2.80 inwg BHP(*) 49.8 HP motor: 460/60/3

ASP inwg Max BHP 55.9 HP

TSP 6.60 inwg Mech. E. 76 %

Des. T. 70.00 'F Static. E. 74 %

Min. T. -10.00 'F Insulation 2" 1.501b Solid

Out. Vel. 2044 FPM (') BHP Includes 5% Drive Losses

9. Custom Module Double Wall 0.0 0 0.00 137.0 92.00 24.00 550

Insulation 2" 1.501b Solid tv Module Tag ACCESS TO SOU;,VD AITN.

10.Custom Module Double Wall 0.0 0 0.15 137.0 92.00 60.00 2000

Module Tag SOUND ATTENUATOR_

11.Custom Double Wall Module 0.0 0 0.05 137.0 92.00 36.00 1100

Module Tag HUMIDIFIER

12.Discharge Plenum Double Wall 16.5 2052 0.47 137.0 92.00 49.00 1117 ti

L F 3iE ~E 3~

49.0 49.0 29.4.9.29.59.08 84.0 4.0 60.0 36.0 49.0

F 473.0

3 5 6 78 9 10 11 12 if _

<42`~~ 42. rrI

__ I

T~wF VA M C MODERNIZATION Date 08/09/95 Time 07:44:31

NEWINGTON, CT. Page 6 of7 ne

Plan View Measurements in inches Legend Mod 1: Mixing Box

Door: Left Top Blade : Parallel Back Blade : Parallel Bottom Blade : Parallel Media Type: None Mod 2: Mixing Box

Door: Left Top Blade : Parallel Back Blade : Parallel Bottom Blade : Parallel Media Type: None Mod 3: Cartridge Filter *** Shipping split Door: Left Media Type: 12" Cartridge Filter Efficiency: 85 %

Elevation

Module Size: Small W / rows: 2/FPF: 80 Drain Pan: None

Door: Left Module Size: Medium Larg Drain Pan: None

1~ 2~ 3 5 6 78 9 10 11 12'

Module Size: Medium Larg WD / rows: 8 / FPF: 97 Drain Pan: Left

*** Shipping split Door: Left Module Size: Medium Drain Pan: None

E 18.5

Mod 6: Supply ran *** Shipping split Door: Left Motor Size: 50.0 HP T-frame ODP High Efficient vvetgnt

MCC

Page 1
Page 2
Page 3
Page 4