Question and Answers.pdf

PDF 106 KB Posted

Attached to
J091--Underground Fuel Tank Cleaning and Filtration
Solicitation number
36C24124Q0223
Issued by

About this file

This solicitation requests quotes for annual fuel tank filtration and cleaning services at the White River Junction VA Medical Center. The contractor shall inspect and filter six tanks on an annual basis, consisting of three above ground storage tanks containing No. 2 fuel oil and diesel fuel, and three underground storage tanks containing diesel fuel. Services include visual inspections, fuel sampling and laboratory analysis to meet NFPA and joint commission standards, fuel filtering through a 1 micron bag filter and coalescer to remove particulates and water, and treatment with stabilizing and biocidal agents. Quotes are due by January 29, 2024 and the contract will have a one-year base period and four one-year options. Evaluation criteria include price, past performance references, and technical approach to meeting requirements.

View the file

Other files

File Type Posted
36C24124Q0223 0001.docx DOCX document
36C24124Q0223.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. In the SOW item one it states perform annual tank inspection, treatment, and fuel filtering on 3 aboveground storage tanks. Then in item 2 it says Aboveground storage tanks shall be inspected in years 2024 and 2027. Can you please verify what is to be yearly and what is to be done in 2024 and 2027 only for aboveground storage tanks? Also are these external inspections only? The AGST should be inspected every three years. The tanks should be visually inspected every three years and have fuel samples done in the off years to keep them in compliance. The 2024 and 2027 visual inspections are external.

2. Item 4 states perform inspection, treatment, and fuel filtering on 3 underground storage tanks with no schedule, but item 3 states inspections are yearly. Am I correct to assume all tasks are yearly? What is the scope of the inspection? Underground tanks are yearly, UST should be visually inspected, fuel filtered and treated with a fuel additive ( ILFC 1032 ) or a similar product.

3. Do they have prior fuel sample analysis results, if so can they share? Prior results are kept on file, they are not sharable.

4. Do they have an idea of amount of standing water in each tank? no

5. Does each tank have adequate openings to allow easy setup of polishing equipment. (2) open 4” ports (1) at each end of the tank? yes I suggest a walkthrough.

6. Can they provide a detailed spec on the ILFC 1032 fuel stabilizer they are calling for.

7. https://www.cgrs.com/wp-content/uploads/2017/02/ILFC-Ten-32-1032-Tank-Treatment-

1.pdf

8. How much fuel is in each tank? Typically top off is recommended to assure all surface areas are treated? Levels vary according to each tank, top off of tanks prior to treatment is possible.

9.

Tank #

Location

Size

Type of Fuel

Type of Tank

1996-1

1,200 gallons

Diesel

UST

1996-2 12,000 gallons Diesel UST

1996-3 20,000 gallons

Diesel

UST

2-3 Bldg. 54 30,000 gallons No. 2 fuel oil AST

2-4 Bldg. 54 30,000 gallons No. 2 fuel oil AST

88-1 Bldg. 88 3,000 gallons Diesel AST https://www.cgrs.com/wp-content/uploads/2017/02/ILFC-Ten-32-1032-Tank-Treatment-1.pdf https://www.cgrs.com/wp-content/uploads/2017/02/ILFC-Ten-32-1032-Tank-Treatment-1.pdf

ILFC-Ten-32-1032-T ank-Treatment-1.pdf