This document contains an RFI log for a federal solicitation to complete repairs at buildings at the Harwood Research Center. The solicitation number is 36C24124B0018 from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1. The work includes repointing and repairing brick buildings constructed in 1951. The RFI log addresses questions from potential offerors regarding the scope of work such as requirements for removing ductwork and electrical equipment, specifications to follow, estimated quantities for concrete repairs, wastewater containment needs, and acceptable repointing depths.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT 04
RFI Log
4 pages
30 January 2024
Providence, Rhode Island VA Health Care System (650)
“Repair & Repoint Buildings at the Harwood Research Center”
Construction
Request for Information (RFI) Log
“Repoint & Repair Buildings at the Harwood Research Center”
Project: 650-24-106
30 JAN 2024
Providence, Rhode Island VA Health Care System (650)
RFI
Number
Date Question Answer
1. 1/27/2024
The specs call out to remove and reinstall existing leader and radon pipes. However, do we also need to remove ductwork, electrical generator switch and all electrical wires to be able to repoint the brick underneath?
No. Have mason “tightly” work around those utility items. But when finally applying sealer to masonry, wand sealant well at areas behind these utilities that were not accessible to repointing with multiple coats.
2. 1/29/2024
The specs call out to remove and reinstall existing leader and radon pipes. However, do we also need to remove ductwork, electrical generator switch and all electrical wires to be able to repoint the brick underneath?
See answer to RFI number one.
3. 1/29/2024
On page 8 of the solicitation section “b) Submittals”, it states that at the time of bidding the contractor needs to submit manufacturers literature, brick and concrete masonry samples, certificates, certifications and MSDS sheets. Please confirm these submissions would be required after award and not part of the bid process.
Required after award.
4. 1/30/2024 Is there a plan holders or bid list available?
No. There is, however, an “Interested Vendor List” via the solicitation on SAM.gov. However, this is a voluntary list and may contain companies not eligible to bid for this contract. There is also a site-walk sign-in sheet that will be posted, along with the answer to these RFIs, that has the names of companies who attended the site walk, and presumably are interested in the project. It is advised that all interested parties attend site visits to future projects for networking purposes.
5. 1/30/2024 Would a site visit be possible still at this time?
No. Section IB-VII of the “Instructions to All Bidders”, found on page 49 of the solicitation, states that no other site visits will be conducted.
6. 1/30/2024
The project documents did not include any specifications. Can you please provide specifications including products used as basis of design and application processes to perform the work.
Section B.4 of the Statement of Work (found on page 7 of the solicitation) provides a link to the Technical Information Libaray (TIL), a collection of all VA specifications, standards, regulations and manuals.
Contractors shall adhere to all regulations, regardless of whether or not each individual specification is pointed out.
Nevertheless, in an effort to ensure mutual understanding of the requirements, the following specifications have been deems ‘most applicable’. These will be provided as an attachment for bidder’s convenience:
Spec. sections:
VA 01 20 00-Unit prices VA 03 01 00 - Maintenance of Concrete VA 04 01 00 – Maintenance of Masonry
This does not alieviet the awardee’s responsibility to adhere to all specifications, codes, regulations that are applicable with federal work on VA installations.
7. 1/30/2024 What year was the research building constructed
8. 1/30/2024 What year was the maintenance building constructed
9. 1/30/2024 Is a mortar analysis required on the two buildings?
Yes, see spec. section 03 01 00 Paragraph 1.4 submittals.
10. 1/30/2024
Is there a square of lineal foot estimate going to be given for the concrete foundation repairs?
Refer to specification 03 01 00 for extent of crack repair and parging required by contract. Unit pricing is also being called for if additional repairs are found to be required.
11. 1/30/2024 Is there a capture of wastewater from the washing the buildings a requirement?
No.
12. 1/30/2024
Project documents require repointing 1/3 of the brick depth. This would be approximately 1/ ¼ inches deep. Typical repointing is 2 or 2 ½ times the joint thickness, or roughly ¾ of an inch. Please confirm 1 ¼ inch depth is what's excepted.
¾” Deep Minimum will be acceptable.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
42.
43.
44.
45.
46.
47.
48.
49.
50.
51.
52.
53.
54.
55.
56.
57.
58.
59.
60.
61.
62.
63.
64.
65.
66.
67.
68.
69.
70.
71.
72.
73.
74.
75.