36C24123Q0689_1.docx
DOCX document 17 KB Posted
- Attached to
- J041--Cooling Tower Controller Replacement & Maintenance SDVOSB Set Aside Federal contract opportunity
- Solicitation number
- 36C24123Q0689
About this file
This combined synopsis/solicitation from the Department of Veterans Affairs seeks fixed-price proposals for the installation and maintenance of cooling tower controls at the West Haven Veterans Affairs Medical Center in Connecticut. Offerors must be certified service-disabled veteran-owned small businesses. Proposals are due by June 9, 2023 and award is anticipated to occur by June 23, 2023. The government will evaluate proposals based on price, past performance references, and technical qualifications to demonstrate experience providing similar HVAC services. Offerors must complete the attached price schedule and past performance worksheet and submit them with their proposal, along with representations and certifications in SAM. The performance period is expected to start on June 23, 2023.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 852.219-75 VA Notice of Limitations on Subcontracting.docx | DOCX document | |
| Attachment 2_Cost-Price Schedule.xlsx | XLSX spreadsheet | |
| Attachment 1_PWS.pdf | ||
| 36C24123Q0689.docx | DOCX document | |
| Wage Determination_2015-4127.pdf | ||
| Attachment 3_Past Performance Worksheet.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Amendment to a Previous Combined Solicitation
Amendment to a Previous Combined Solicitation
| SUBJECT* |
| Cooling Tower Controller Replacement & Maintenance SDVOSB Set Aside |
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 03104 |
| SOLICITATION NUMBER* |
| 36C24123Q0689 |
| RESPONSE DATE/TIME/ZONE |
| 06-09-2023 3:00 PM EASTERN TIME, NEW YORK, USA |
| ARCHIVE |
| 60 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
| SET-ASIDE |
| SDVOSBC |
| PRODUCT SERVICE CODE* |
| J041 |
| NAICS CODE* |
| 238220 |
| CONTRACTING OFFICE ADDRESS |
| Department of Veterans Affairs |
VAMC Manchester
718 Smyth Road Manchester NH 03104
POINT OF CONTACT*
Contract Specialist David Valenzuela david.valenzuela2@va.gov
PLACE OF PERFORMANCE
| ADDRESS |
| See PWS. |
POSTAL CODE
COUNTRY
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
AGENCY CONTACT’S EMAIL ADDRESS
EMAIL DESCRIPTION
DESCRIPTION
** AMENDMENT A00001 – Cooling Tower Controller Replacement and Maintenance – West Haven VAMC
– Contractor Site Visit Questions and Government Responses ** Please confirm receipt of this amendment in your solicitation response
1. How long have the absorbers been dormant and have they been tested to insure they function properly now?
a. Units are currently being brought online to test for functionality. Service reports are available from Joel C./Plant Supervisor. Service work is being provided by Broad this week (week of June 5th) to setup the building 19/ CHP Plant’s chilled water system for the cooling season. Per work on Tuesday, June 6, 2023, basket strainers were found to be plugged and have been cleaned. Building 19 chilled water system (chillers, cooling towers) will be exercised before end of week to assess and improve flow and improve operational efficiency as required. Board has provided past pre and post cooling season services for the building 19/ CHP Plant in August 2021, Oct 2022, April 2022, and July 2022.
2. What process (if any) was used to put the absorbers into long term storage?
a. Long term storage was performed by Broad USA the manufacture of absorber.
3. What documentation was done with putting the absorbers into long term storage and does the VA (or a Contractor) have this documentation?
a. See answers to question #1.
4. Is there any documentation on the condition of the bromide and/or has the bromide been tested in the past or recently?
a. BRASCO In August of 2022 conducted a checks and test of the Cooling Tower and Bromide for quality and/or biological… record on file in CHP Plant.
5. Have the chiller tubes been punched or have Eddy Currents been performed?
a. The chiller tubes have not been punched. Board checked but did not punch. Per the check this week, flow through absorption cooling unit deemed to be OK. Full system operation/flow is scheduled before end of this week. See answer to question #1.
6. Is there currently water in the chiller barrels?
a. It will be filled by end of the week of June 5th.
7. If so, has that water been tested in the past or recently?
a. N/A
8. Are there original start-up sheets available for the absorbers?
a. Yes (on the HDMI). Board’s O&M Manual(s) available on site and/or through vendor.
9. Does the ‘warranty’ being asked for in the bid document refer to labor, equipment or bot.
a. Equipment