33310521Q0004 Combined Synopsis/Solicitation Attachment I – Specifications
BACKGROUND INFORMATION
The John F. Kennedy Center for the Performing Arts (Center) is a trust instrumentality of the U.S. Government and a living Presidential memorial. The Center fulfills its obligation as a living memorial to the late President through the presentation of performing arts programming and through education activities both in the District of Columbia and around the country. The largest cultural facility of its kind, it is the nation’s busiest arts facility presenting more than 2,000 performances each year. It currently consists of one building encompassing approximately 1,500,000 square feet of usable floor space and is situated on 17 acres of land overlooking the Potomac River. A 65,000 square foot addition to the facility called the REACH was added to the Federal footprint in September 2019.
The Center houses nine theaters, production support areas, two public restaurants, nine function/special event rooms, five public galleries/halls/foyers, approximately 50,000 square feet of administrative offices and a large parking facility. It attracts over three million visitors annually. The facility operates 365-days per year and support systems in the building often operate at capacity in excess of 14-hours per day.
The site of Center is bounded by:
• North: The South curbs of New Hampshire Avenue and F Street
• East: The Western most retaining walls and curbs of the Inner Loop Freeway
• South: The Northernmost retaining walls and curbs of the Theodore Roosevelt
Bridge
• West: The Easternmost retaining walls and curbs of the Rock Creek Parkway
To fulfill its mission, the Center has a series of lighting consoles and dimmers manufactured by Electronic Theater Controls (ETC) in all of its performance spaces and many public spaces including the REACH and Grand Foyer Millennium stages. The Center requires an upgrade to the circuit breaker panel in the Center’s Opera House. As a result, a new ETC IQ48 sensor IQ main-feed panel is required.
SCOPE OF WORK
The work covered under this Section shall include the materials and equipment necessary for the Contractor to furnish only the Theatrical Lighting control system and associated distribution equipment herein specified. It shall also include the services of qualified field engineer/technicians authorized by the manufacturer of the system who shall review the installation to ensure its proper operation and provide owner training.
The Theatrical Lighting control systems shall be furnished by a factory authorized Contractor certified to design, program and service the systems. The Contractor shall be responsible for coordination between the electrical installation and other trades installing theatrical equipment, system startup, and warranty repair.
Attachment I – Specifications
The Contractor shall furnish all necessary equipment as hereinafter detailed for a complete and functional Theatrical Lighting control system. It shall be the responsibility of the Contractor providing the system to assure that the intended function is furnished.
The system specified herein shall consist of a relay-per-circuit high density power control system, distribution equipment, and all required interconnecting wiring.
QUALITY ASSURANCE
This Contractor shall furnish submittals for all components of the lighting control system in accordance with Division 1 of these Specifications. The submittals should include, but not be limited to the following:
Manufacturer's catalog data for all equipment and components that shall include all technical data to demonstrate conformance with these Specifications.
Complete physical drawings of all items of equipment showing dimensions, metal gauges, etc.
Complete load schedules which shall clearly indicate actual connected loads and control channel assignment (where applicable), cross-reference of internal equipment identifications to circuit numbers shown on the Drawings, and all other scheduled information which shall relate the equipment to the project requirements. The schedules shall also clearly identify those circuits that are on the emergency lighting transfer system.
Complete internal and interconnection wiring diagrams showing number, size, and types of conductors between equipment and from equipment to loads, and feeder quantity and sizes.
• All materials used shall be new and of good quality conforming to these specifications and the successfully reviewed submittals. Any material not successfully reviewed by the Owner or Architect/Engineer that is incorporated in the work, used, or delivered to the site, shall be immediately removed upon the order of the Owner or Architect/Engineer and replaced to the satisfaction of the Owner and Architect/Engineer at this Contractor's expense.
• The Theatrical Lighting control system equipment specified herein shall be the sole responsibility of a single manufacturer. The manufacturer shall have been producing theatrical lighting and SCR/RELAY type lighting power systems for at least fifteen (15) years.
• All work shall be in accordance with good engineering practices. All equipment for this system shall be listed by Underwriter's Laboratories, Inc. (UL), bear the UL label, and shall be installed in accordance with all requirements of the National Electrical Code (NEC), state and local codes, and these Specifications.
SPECIFICATIONS
The Contractor shall provide the following items:
System: New IQ Panel #1
Attachment I – Specifications
DRd Enclosures and Accessories Qty. Model Part Number Description 1 IQ48 7131A1061 Sensor IQ Mains Feed Wall Mount panel to Contain: 3 phase 120/208V; 400A;
48 Pole breaker sub panel with no breakers 3 - 2x250MCM Main Lugs w/option for main breaker 1 - 2x350MCM Neutral Lugs
40 IQ SM B20 CB852-2 Sensor IQ 120V 20A single pole intelligent breaker with relay; includes reporting for current, breaker trip, and relay state.
8 IQ B20 CB1026-2 Sensor IQ 120V 20A single pole breaker; includes reporting for current, breaker trip, and relay state.
Unison Paradigm Control and Accessories Qty. Model Part Number Description
1 IQ DOOR
120-48S 7131A1551 Door for surface mounted 120V Sensor IQ 48 panel
System: New IQ Panel #2 DRd Enclosures and Accessories Qty. Model Part Number Description 1 IQ48 7131A1061 Sensor IQ Mains Feed Wall Mount panel to Contain: 3 phase 120/208V; 400A;
48 Pole breaker sub panel with no breakers 3 - 2x250MCM Main Lugs w/option for main breaker 1 - 2x350MCM Neutral Lugs
18 IQ SM B20 CB852-2 Sensor IQ 120V 20A single pole intelligent breaker with relay; includes reporting for current, breaker trip, and relay state.
28 IQ B20 CB1026-2 Sensor IQ 120V 20A single pole breaker; includes reporting for current, breaker trip, and relay state.
2 IQ B30 CB1027-2 Sensor IQ 120V 30A single pole breaker; includes reporting for current, breaker trip, and relay state.
Attachment I – Specifications
Unison Paradigm Control and Accessories
Qty. Model Part Number Description
1 IQ DOOR
120-48S 7131A1551 Door for surface mounted 120V Sensor IQ 48 panel
System: Ern2 - Rack 1 Unison Paradigm Control and Accessories Qty. Model Part Number Description 1 P-ACP 7180A1029 Paradigm Architectural Control Processor 1 P-SPM-E 7182A1701 Paradigm Station Power Module - supports 63 stations and (1) 500m wire segment 1 ERn2-R-120 7180A1013 ERn2 Rack Mount 120V Enclosure 3 P-TS7-PE 7184A1532 Paradigm 7" Portable Ethernet Touchscreen Unison Paradigm and Heritage Stations Qty. Model Part Number Description
2 UH10002-11 7181A2202-
1A Cream 1-gang faceplate assembly to accept the following: 1 - On Select Switch 1 - Off Select Switch
2 UH10002 7181B2005 1-gang, 2-button electronics assembly Unison Locking Covers, Remotes and Accessories Qty. Model Part Number Description 2 BB-2S 7081A2004-2 2-gang surface-mount back-box 2 LBB-1 1064A2002-1 1-gang Hinged Cover Locking Backbox
2 SLD-1 1064A2008-1
C. Adder – Custom Faceplate
I. Unison Paradigm Control Station Faceplates to consist of:
Qty. Part Number Description 2 QUOTE-20004 UH10002-_Z - Custom metal 1-gang faceplate assembly to include the following: 2 -
Select Switches Custom/standard nomenclature to be
The aforementioned items shall conform to the following, at a minimum:
Intelligent Breaker System
• The Intelligent breaker system shall be 120V Sensor IQ as manufactured by ETC, Inc.
• Breaker Panels shall be UL508, UL67, and UL924 Listed, and shall be so labeled when delivered
• Breakers shall be UL489 listed and shall be labeled when delivered
Qty. Part Number Description
1 QUOTE-30014 9300 Series - Surface Mount Pigtail Box with: 8 - 18" pigtails and 20A Edison (5-20R) connectors wired on 8 - 20A circuits 4 - 18" pigtails and 20A Stage Pin (2P&G/GPC) connectors wired on 4 - 20A circuits
Attachment I – Specifications
• Breaker Panels shall consist of a main enclosure with 48 pole breaker subpanels, integral control electronics for low voltage terminations and provision for accessory cards
• Up to three accessory cards shall be supported per breaker panel
Mechanical
• The panel shall be constructed of 16-gauge galvannealed steel. All panel components shall be properly treated or finished in fine-textured, scratch resistant paint
• Breaker panels shall be capable of being mounted on the surface of a wall or recessed mounted
• Breaker panels shall be available in 48 pole configurations o 48 pole (with provision to add main breaker) o 64 inches high, 20” wide and 5.25” deep (with front panel attached)
• Choice of panel covers shall be available for surface or recess mount applications. This outer panel shall ship complete with a locking door to limit access to electronics and breakers
• Optional center-pin reject security screws shall be available for all accessible screws
• Optional recess mount doors shall extend 1” beyond all panel edges to hide wall cut-out
• The unit shall provide interior cover over the control electronics and accessory cards to allow access only to class 2 wiring and prevent direct access to class 1 line voltage components
• The panel shall support up to 48 single pole branch circuits o Branch circuits shall range from 15A to 30A capable of holding full rated load for minimum of three hours continuously
• Breakers shall provide manual switching control while power is unavailable to the panel such that critical lighting can be set to an on state, without the need for power to the panel
• Breaker output lugs shall accept 10-14 AWG dual conductor wire
• Breaker output lug shall support solid or stranded 6-14 AWG class B, C, or K copper wire
• Control wiring for DMX, station bus, and Emergency input terminations shall land on a removable headers for contractor installation
User Interface
• The user interface shall contain an LCD display with button pad to include 0-9 number entry, up, down back arrow navigation and enter
• Test shortcut button shall be available for local activation of preset, sequence and set level overrides
• The user interface shall have a power status LED indicator (Blue), a DMX status LED indicator (Green), a network status LED indicator (Green) and an LED indicator (red) for errors
• Interface shall allow the backlight to timeout and shall provide user editable options to shut off backlight completely as well as adjust screen contrast
• Ethernet interface (when installed) shall default to automatic IP through link local and DHCP. Upon receiving IP address, the address of the Network Interface Card (NIC) shall display in the about menu. Static address and settings shall also be possible
• The control interface shall support a USB memory stick interface for uploads of configurations and software updates.
Functional
• Panel setup shall be user programmable. The control interface shall provide the following breaker setup features (per circuit):
o Type (1 pole, 2 pole, or 3 pole) o Name o Circuit Number o DMX address o sACN address (network enabled panels only) o Space Number o Circuit Modes
Normal (priority and HTP based activation and dimming) Latch-lock Fluorescent
DALI
o On threshold level o Off threshold level o Include in UL924 emergency activation o Allow Manual
• Breaker panels shall support discrete addressing of each breaker. Panels that are restricted to use of start address with sequential addressing, and cannot assign each 0-10V output control to any internal circuit shall not be acceptable
• The panel shall be capable of switching 6 poles on or off at once, or in a user-selectable delay per breaker using a period of 0.1 to 60 seconds, in 0.1 second increments
• Control electronics shall report the following information per branch circuit:
o Breaker state (On/Off) o Breaker state (Open/Closed) o Current draw (In Amps) o Voltage o Energy usage
• Built in Control shall include:
o Ability to record up to 16 presets in each space from the control panel, connected control stations, or timed events o Presets shall be programmable by recording current levels (as set by DMX or connected control stations), by entering levels on the control panel directly, manually selecting breaker state on each breaker, or a combination of these methods. From the control panel, stations, or timed events it shall be possible to record values for up to 16 zones per space o Up to 8 spaces in a single rack for total of up to 16 spaces shall be supported per system or system subnet o Indication of an active preset shall be visible on the control panel display o One 16-step sequence per space for power up and power down routines o The panel shall have a UL924-listed contact input for use in Emergency Lighting systems. The panel shall respond to the contact input by setting included breakers to “on”, while setting non-emergency breakers “off”. Each breaker can be selected for activation upon contact input o Upon Data loss the system shall provide options to hold last look infinitely or hold for a configured time period set by the installing technician then fade/switch to the input of the next available priority o Control electronics shall respond directly to control stations for zone, preset, and sequence control. Systems that require secondary control systems for this functionality are not acceptable o After power loss, electronics shall be capable of holding the system in its previous state until new level data (DMX, architectural presets, sequences and zones, or local overrides) is received to make each breaker change state
• The control of lighting and associated systems via timed and Astronomical clock controls o The breaker panel shall allow the activation of presets, sequence, and zone programming of up to 50 time clock events via a built in real and astronomical time clock o System time events shall be programmable via the control panel Time clock events shall be assigned to system day types. Standard day types include: everyday, weekday, weekend, Sunday, Monday, Tuesday, Wednesday, Thursday, Friday and Saturday
Time clock events shall be activated based on sunrise, sunset, time of day or periodic event
System shall automatically compensate for regions using a fully configurable daylight saving time
Presets shall be assigned to events at the time clock
• The time clock shall support event override o It shall be possible to override the timed event schedule form the face panel of the time clock
• The time clock shall support timed event hold o It shall be possible to hold a timed event from the face panel of the processor o Timed event hold shall meet California Title 24 requirements
• The panel shall receive ESTA DMX512-A control protocol. Addressing shall be set via the user interface button keypad with any circuit patched to any DMX control address o 2,500V of optical isolation shall be provided between the DMX512 inputs and the control electronics as well as between control and power components o The breakers shall respond to control changes (DMX or Stations) in less than 25 milliseconds. DMX512 update speed shall be 40Hz o Setting changes shall be able to be made across all, some, or just one selected breaker in a single action from the face panel o DMX data loss shall allow for levels/breakers to be held for ever or for a specified time before switching to a lower priority source
• Initial Panel setup o The breaker panel shall automatically detect the type of breaker or dimmer installed in each location without need for manual configuration of the physical arrangement o Quick rack setup shall be available to apply address settings across all circuits for rack number, DMX Start Address, sACN universe, and sACN start address o Emergency Setup Menu shall provide optional delays when emergency is activated or deactivated, and option to turn off non-emergency circuits shall be available. Record function shall allow circuits that are turned on to be added to the emergency setting
• Electrical o Breaker Panels shall be available to support power input from:
o 120/208V three phase 4-wire plus ground
• Conduit Entry:
o Feeders:
Top or upper 6” of either side Bottom or lower 6” of either side Feeders shall enter through the top or bottom according to the orientation of the enclosure.
Feeder entry shall be nearest to the location of the feeder lugs or main breaker.
• Load:
o Load wiring shall enter through the top or bottom of the enclosure through the surface nearest to the breaker sub panel o Load wiring may also enter through left and/or right side provided a low voltage chase is not required through the same area. If class 2 chase is required, a field installable barrier panel shall be provided upon request. The side of the panel where the barrier has been installed shall not permit load wiring
• Low Voltage:
o Top or upper 6” of either side o Bottom or lower 6” of either side o For low voltage conduit entry at the breaker end of the cabinet, conduits shall be located at the outer 3” of the top/bottom panel
• Breaker o Bus connection type: Stab on o 1, 2, or three poles o UL489 listed o 20 amp, or 30 amp o 22,000 SCCR; 65,000A series rated with main breaker o High inrush trip curve (matches all Sensor breakers) o Maintains trip curve through entire thermal range o Guaranteed not to trip at full load o Load lugs accept 6-14awg load wiring o Multi-conductor listed output terminal o Integral mechanically held air gap relay o Manual control of relay state using breaker handle w/o power o Integral current sensing o Integral position and trip sensing o Control and status provided by contact pads directly at bottom of the breaker case o No external wires or connections required for control or feedback o The breaker shall be capable of switching up to 30A
• The breaker panel shall support a maximum feed size o 400 Amps at 48 circuits
• Breaker panels shall support main circuit breaker options:
o Main breaker options shall be optional and available for purchase upon request o Main breakers shall be field installable o Main breakers shall be available in up to 400A for 48 circuit panels at 120V o Series SCCR ratings apply as follows with appropriate main breaker:
22,000A or 64,000 at 120/208V o Main breakers shall allow the following range of wire sizes:
Up to 300kcmil at 100A and 200A Up to 2x250kcmil at 400A o Main Lug input shall support up to 2x250kcmil o Breaker panel shall support a 500kcmil main lug option for 48-circuit panels
• Breaker remote switching ratings o Mechanical 1,000,000 cycles o 24A Resistive 100,000 cycles o 16A Ballast (HID) 75,000 cycles o 15A Electronic (LED) 100,000 cycles o 15A Tungsten 45,000 cycles o 30FLA; 180 LRA Motor Load 50,000 cycles\ o Tested duty cycle: 12 operations (6 cycles) per minute o Decreasing duty cycle significantly increases switch life o Isolation: 4000V RMS} o Current reporting accuracy: 5% o Latching state mechanical relay
• Thermal o The panel shall be convection cooled. Panels that require the use of cooling fans shall not be acceptable o The panel shall operate safely in an environment having an ambient temperature between 32ºF (0ºC) and 104ºF (40C), and humidity between 5-95% (non-condensing)
• Provide the following Sensor IQ 48 Intelligent Breaker System Panels:
o Panel #1: Sensor IQ48 with Surface Mount Door containing:
Forty (40) IQ SM B20 20A single pole intelligent breaker with relay Eight (8) IQ B20 20A single pole breaker
Panel #1 IQ48
# BREAKER DESCRIPTION # BREAKER DESCRIPTION
48 SM B20 OFF SR WORKS 47 SM B20 GRID WORKS
46 SM B20 OFF SR WORKS 45 SM B20 GRID WORKS
44 SM B20 OFF SR WORKS 43 SM B20 GRID WORKS
42 SM B20 OFF SR WORKS 41 SM B20 GRID WORKS
40 SM B20 OFF SR WORKS 39 SM B20 GRID WORKS
38 SM B20 OFF SR WORKS 37 SM B20 GRID WORKS
36 SM B20 OFF SR WORKS 35 SM B20 GRID WORKS
34 SM B20 OFF SR WORKS 33 SM B20 GRID WORKS
Attachment I – Specifications
32 SM B20 UP CENT WORKS 31 SM B20 GRID WORKS
30 SM B20 UP CENT WORKS 29 SM B20 LARGE PIT ND
28 SM B20 UP CENT WORKS 27 SM B20 LARGE PIT ND
26 SM B20 UP CENT WORKS 25 SM B20 SMALL PIT ND
24 SM B20 UP CENT WORKS 23 SM B20 PIT ENTER WORKS
22 SM B20 OFF SL WORKS 21 SM B20 PIT SR BACK WALL
20 SM B20 OFF SL WORKS 19 SM B20 PIT SL BACK WALL
SM B20
OFF SL WORKS 17
SM B20 PIT CENTER BACK
WALL
16 SM B20 OFF SL WORKS 15 SM B20
14 SM B20 OFF SL WORKS 13 SM B20
12 SM B20 OFF SL WORKS 11 SM B20
10 SM B20 OFF SL WORKS 9 SM B20
B20 SL DRESSING RM
WORKS 7
B20 UNDER PIT WORKS
LRG
B20 SR DRESSING RM
WORKS 5
B20 UNDER PIT WORKS
SMALL
4 B20 COND CAMERA 3 B20 UNDER STAGE WORKS
2 B20 1 B20 UNDER STAGE WORKS
o Panel #2: Sensor IQ48 with Surface Mount Door containing:
Eighteen (18) IQ SM B20 20A single pole intelligent breaker with relay Twenty-eight (28) IQ B20 20A single pole breaker Two (2) IQ B30 30A single pole breaker
Panel #2 IQ48
# BREAKER DESCRIPTION # BREAKER DESCRIPTION
48 SM B20 LOCK RAIL WORKS 47 SM B20 SR BOX WORKS
46 SM B20 LOCK RAIL WORKS 45 SM B20 SL BOX WORKS
44 SM B20 PIN RAIL WORKS 43 SM B20 US BOX WORKS
42 SM B20 PIN RAIL WORKS 41 SM B20
SM B20 LOADING BRIDGE
WORKS 39
SM B20
SM B20 LOADING BRIDGE
WORKS 37
WORKS 35
WORKS 33
WORKS 31
B20
RADIO CHARGER 29
B30 DMX RACK 30A
SWITCH
B20
SL BOX BM WORKS 27
B30 DMX RACK 30A
SWITCH
Attachment I – Specifications
26 B20 SR BOX BM WORKS 25 B20 HOUSE CURTAIN PWR
B20 SL OLD SOUND
CIRCUIT 23
B20
COVE WORKS
22 B20 SL DMX REC 21 B20 SR DMX REC
20 B20 19 B20 TRAP ROOM WORKS
18 B20 17 B20 16 B20 15 B20 14 B20 13 B20
12 B20 SR 20A STAGE PIN 11 B20 SR 20A STAGE PIN
10 B20 SR 20A STAGE PIN 9 B20 SR 20A STAGE PIN
8 B20 SR 20A EDISON 7 B20 SR 20A EDISON
6 B20 SR 20A EDISON 5 B20 SR 20A EDISON
4 B20 SR 20A EDISON 3 B20 SR 20A EDISON
2 B20 SR 20A EDISON 1 B20 SR 20A EDISON
Unison Ern Series Control Enclosures
• Control Enclosures o The control enclosure shall be the Unison ERn Series Control Enclosure as manufactured by Electronic Theatre Controls, Inc.
• Mechanical o The External Processing enclosure shall be a surface mounted panel constructed of 18 gauge formed steel panels with a hinged, lockable full-height door containing an integral electrostatic air filter The enclosure door shall have an opening to allow limited access to the control module face panel Enclosures shall be convection cooled without the use of fans.
• Control Enclosures shall be sized to accept one Control Processors and one Station Power Modules, including various options and accessories
• All enclosure components shall be properly treated and finished o Exterior surfaces shall be finished in fine textured, scratch resistant, powder based epoxy paint
• Enclosure(s) shall also be available in a 19” rack mounted (RM) version o Rack-mounted version shall have an independent enclosure suspension kit, with a full height, locking door/cover attached to the kit o Rack-mounted version shall have an opening to access the control module face panel, and openings to view indicators on option modules
• Enclosure dimensions and weights (without modules) shall not exceed ERn2-RM - 19" W 11"H 10" D, 20 lb.
• Top, bottom, and side knockouts shall facilitate conduit entry
• Enclosures shall be designed to allow easy insertion and removal of all control and option modules without the use of tools o Supports shall be provided for precise alignment of modules into power and signal connector blocks o With modules removed, enclosures shall provide clear front access to all power and control wire terminations.
• Electrical o External Processing enclosures shall be available in 120 volt, single-phase configurations o External Processing enclosures shall be completely pre-wired by the manufacturer. The contractor shall provide input and control wiring o External Processing enclosures shall be designed to support the following wire terminations:
AC (single phase) Echelon link power (Belden 8471 or equivalent) 24Vdc (2- 16AWG Wire) DMX512A Port A (In or Out) (Belden 9729) DMX512A Port B (In or Out) (Belden 9729) RS232 Serial In/Out (Belden 9729) Unshielded Twisted Pair (UTP) Category 5 Ethernet Contact Closure In (14AWG to 26AWG Wire) Contact Closure Out (14AWG to 26AWG Wire)
• Contact Closure Out shall provide 1A @ 30vDC
• Station Power Modules o Station power supply modules shall provide LinkPower for stations and 1.5A@24VDC of Auxiliary (AUX) power o Station power module shall support over-current/short protection for LinkPower and Aux. LinkPower shall support fault detection on each leg of the balanced data bus
• All control wire connections shall be terminated via factory provided connectors
• Thermal o Ambient room temperature: 0-40°C / 32-104°F o Ambient humidity: 10-90% non-condensing
• Provide one (1) ERn2-R-120 Rack Mounted Unison Control Enclosure
Control Processor Modules
• The Architectural Control Processor shall be the Unison Paradigm P-ACP Series Control Processor as manufactured by Electronic Theatre Controls, Inc.
• The Architectural Control Processor (ACP) assembly shall be designed for use in ERn Series Control Enclosures
• The processor shall utilize microprocessor based, solid state technology to provide multi-scene lighting and building control o ACP shall support functions such as station programming, macro sequencing, electronic lockout, room combine and astronomical time clock events. ACP station processor shall allow configuration of the control system via the menus.
See software section for additional system details o When used in a dimming enclosure, the ACP shall allow access to dimming control menus including the status screen, dimming configuration screen, backup menu, test menu and configuration menu
• One ACP shall be rated to drive 1024 channels of control, 1024 zones, 64 rooms, 512 presets, 63 button or button/fader stations and 6 Touchscreen Stations
• ACP module electronics shall be convection cooled
• The ACP shall provide front-panel RJ45 jack, Secure Digital (SD) card slot, and
Universal Serial Bus (USB) Port for configuration and data exchange
• Architectural Lighting System configuration and program information shall be stored in flash memory, which does not require battery backup
• The ACP shall be contained in a plug-in assembly and require no discrete wiring connections; all wiring shall be terminated into Dimming or Control Enclosure o The ACP shall support the following communications
Echelon LinkPower 10/100BaseTX, auto MDI/MDIX, 802.3af compliant Ethernet networking with TCP/IP, ESTA BSR E1.17 Advanced Control Networks (ACN) and ESTA BSR E1.31 (sACN) Protocols
EIA-232 serial protocol ESTA DMX512A, configurable as input or output ports Dry contact closure inputs Dry contact closure outputs, rated at 1A@30VDC
• Provide one (1) P-ACP Paradigm Architectural Control Processor
Station Processor Modules
• The Station Power Module (SPM) shall be the Unison Paradigm P-SPM-E Series Station Power Module as manufactured by Electronic Theatre Controls, Inc.
o The SPM assembly shall be designed for use in ERn Rack Enclosures
• The SPM shall convert input power into low-voltage (Class II) power with data line and a secondary auxiliary low-voltage line to energize button, button/fader, touchscreen, and interface devices for multi-scene lighting and building control
• The SPM, in conjunction with a matching Architectural Control Processor (ACP), shall support Echelon LinkPower communications with remote devices, including button, button/fader, touchscreen and interface stations, and shall interoperate with LonMARK-approved third-party devices o The LinkPower network shall utilize polarity-independent, low-voltage Class II twisted pair wiring, type Belden 8471 (unshielded) or Belden 8719 (shielded) or equivalent. One # 14 AWG drain wire will be required for system not using grounded metal conduit o The LinkPower network shall be topology free. Network wiring may be bus, loop, home run, star or any combination of these o Link power wiring shall permit a total wire run of 1640 ft. (500m) o Link power wiring between stations shall not exceed 1313 ft. (400m) o The SPM shall support auxiliary power for certain remote devices, including touchscreen and interface stations, as required by the device The auxiliary power network shall utilize polarity-dependent, low-voltage
Class II wiring, consisting of two # 16 AWG wires Auxiliary wiring shall permit a total wire run of 1640 ft. (500m) The SPM shall supply 1.25 amps at 24v DC continuously o ACP module electronics shall be convection cooled o Each SPM shall:
Supply power for up to 63 button stations.
Supply auxiliary power for a similar number of interface stations.
Supply auxiliary power for up to four Touchscreen stations, when a like number of other stations are deducted from the total o Provide one (1) P-SPM-E Paradigm Station Power Module
Portable Touchscreen Control Stations
• The Portable Touchscreen Control Stations shall be the Unison Paradigm Portable Touchscreen P-LCD Series Control Stations as manufactured by Electronic Theatre Controls, Inc.
• General o Portable Touchscreen stations shall support default and fully graphical control pages o Portable Touchscreen stations shall operate using graphic buttons, faders and other images on at least 30 separate programmable control pages o Portable Touchscreen stations shall also allow programming of page pass-code, lock out and visibility levels o Portable Touchscreen stations shall support location awareness to automatically load the configuration required dependent on the connection point to the system
• Mechanical o Portable Touchscreen stations shall consist of a seven inch, backlit liquid crystal display (LCD) with a minimum resolution of 800 by 400 pixels and 24-bit color depth with a touch interface o The Portable Touchscreen enclosure and cover shall be constructed of aluminum and finished in a fine-texture powder coat paint o The enclosure shall provide a hinged cover with two positions for the Touchscreen: closed and operating o The Portable Touchscreen shall have a protective cover for removable media ports The protective cover shall be hinged The Touchscreen cover shall be operational with the media cover in the open or closed position
• The Portable Touchscreen shall include an attached cable with 6-pin Amphenol connector and strain relief to interface with Portable Connector Stations o Attached Cable shall be 15’ in length constructed of ultra-flexible material o Extension cables up to 100’ in length shall be available to extend the cable length to a maximum of 115’ total length
• Electrical o Portable Touchscreens shall be powered entirely by the System network o Portable Touchscreens shall connect to the System using the Unison control station Echelon® Link power network over the attached cable Echelon® Link power network
• Link power shall utilize low-voltage Class II unshielded twisted pair, type Belden 8471 or equivalent, and one #14 ESD drain wire (when not installed in grounded metal conduit)
• Touchscreen stations shall also require (2) #16 AWG stranded wires for 24Vdc operating power. 24Vdc wiring shall be topology free
• Network wiring may be bus, loop, home run, star or any combination of these
• Functional o System
The Portable Touchscreen shall support configuration upload from a Paradigm Processor as proxy
The Touchscreen shall support configuration or firmware upload from local removable media
It shall be possible to connect multiple Portable Touchscreen station to the system at one time o Setup Mode There shall be a setup display that is separate from any user-defined configuration It shall be possible to view and modify connectivity settings It shall be possible to view status information It shall be possible to view and modify LCD screen settings It shall be possible to perform Touchscreen calibration It shall be possible to view and modify audio settings The appearance of the setup display shall be standard and not editable The setup display may be invoked from within the user-defined configuration and/or physical button on the Portable Touchscreen There shall be a default protected method to invoke the setup display o Configurations It shall be possible to have multiple configurations stored within an LCD
Station The Portable Touchscreen shall automatically load the required configuration based on connection point to the system Only one configuration may be active on the LCD Station It shall be possible for Portable Touchscreen Stations connected via the
Echelon® Link power network to select a configuration automatically based on the configuration of the physical connection.
Where multiple configurations are stored there shall be a setup menu to allow selection of a configuration
Each configuration shall be identified as a different Station within the System o Operation The Unison Paradigm Control System shall be designed to allow control of lighting and associated systems via Touchscreen controls. System shall allow the control of presets, sequences, macros and time clock events
• System presets shall be programmable via Button, Button/Fader or Touchscreen stations, or LightDesigner software o Presets shall have a discrete fade time, programmable from zero to 84,600 seconds with a resolution of one hundred milliseconds o Presets shall be selectable via Touchscreen stations
• System macros and sequences shall be programmable via
LightDesigner system software o Macro and sequence steps shall provide user selectable steps, and allow the application of conditional logic o Macro and sequences shall be activated by button, time clock event or LightDesigner software
• System time clock events shall be programmable via the
Touchscreen, LightDesigner system software, the processor user interface, or the internal web server o Time clock events shall be assigned to system day types.
Standard day types include: anyway, weekday, weekend, Sunday, Monday, Tuesday, Wednesday, Thursday, Friday and Saturday. System shall support programming of additional custom or special day types o Time clock events shall be activated based on sunrise, sunset, time of day or periodic event. System shall automatically compensate for regions using a fully configurable daylight saving time
• A Color picker, supporting Hue, Saturation and Brightness (HSB) color selection shall be available for color selection of color changing fixtures and provide visual feedback of the current color produced by the associated fixture o The color picker shall be provided with a default layout that requires no user configuration o The Color Picker shall provide RGB faders in addition to the default HSB color wheel for color selection o Color picker values shall allow for numerical value input in addition to color wheel and fader control o The color picker shall be compatible with color mixing systems that use up to seven discrete color control channels
Portable Touchscreen stations shall be designed to operate standard default or custom system functions. Components shall operate default functions unless re-assigned via LightDesigner, the Windows-based configuration program
• Optional button functions include: preset selection, manual mode activation, record mode activation, station lockout, raise, lower, macro activation, and cue light, or room join/separate
• Optional fader functions include master control, individual channel control, fade rate control or preset master control
Portable Touchscreen stations shall allow programming of station and component electronic lockout levels via LightDesigner
It shall be possible to adjust LCD contrast and brightness.
It shall be possible to program the station to dim during periods of inactivity
Provide three (3) P-TS7-PE Unison Paradigm Portable Touchscreen with NET Connect/Ethernet
Stations
• The Lighting Control Stations shall be the Unison Heritage UH Series Control Stations as manufactured by Electronic Theatre Controls, Inc.
• Mechanical o Unison Heritage Button Stations shall operate using up to two programmable buttons.
o All button stations shall be available with ivory faceplates and buttons
Manufacturer's standard colors shall conform to the RAL CLASSIC Standard o Stations shall have indicators lights at each button Indicators shall be comprised of red, green and blue LED's Indicator color and state (steady On, Blink, Off) shall be configured in software, and shall operate relative to the button or fader it is associated with o All faceplates shall be designed for surface mounting o Station faceplates shall be constructed of ABS plastic and shall use no visible means of attachment o Station faceplates shall be indelibly marked for each button function o The manufacturer shall supply back boxes for all surface mounted stations
• Functional o The Unison Paradigm Control System shall be designed to allow control of lighting and associated systems via Button and Interface or Astronomical time clock controls. System shall allow the programming of presets, sequences, macros and time clock events.
o Station Button and Interface) control components shall be designed to operate standard default or custom system functions. Components shall operate default functions unless re-assigned via LightDesigner, the Windows-based configuration program.
o Stations shall allow programming of station and component electronic lockout levels via LightDesigner
• Electrical o Unison control station wiring shall be an Echelon® Link power network
Link power shall utilize low-voltage Class II unshielded twisted pair, type Belden 8471 or equivalent, and one #14 ESD drain wire (when not installed in grounded metal conduit).
Touchscreen and Interface stations shall also require (2) #16 AWG stranded wires for 24Vdc operating power. 24Vdc wiring shall be topology free.
Network wiring may be bus, loop, home run, star or any combination of these.
Network insulation displacement connectors shall be provided with all stations o Provide two (2) UH10002 Ivory Unison Heritage 2-Button Button Stations with the following accessories:
Two (2) 2-gang Surface Mount Back Boxes Two (2) 1-gang Hinged Cover Locking Back Boxes Two (2) 1-gang Surface Mount Hinged Locking Doors
• Optional Custom Faceplate Adder o Two (2) Custom Metal 1-gang faceplate assembly to include (2) select switches, and custom/standard nomenclature to be determined
Power Distribution – Pigtail Boxes
• General o Connectors shall be available as 20A grounded stage pin, and 20A “U” ground
(dual rated “T-slot”); other connectors shall be available as specified o Pigtails shall be three-wire type “SOW” rubber jacketed cable sized for the maximum circuit ampacity.
o Pigtails with 20 amp stage pin connectors shall be terminated using 12 gauge 4 way indent crimp (with inspection window) type where the wire is inserted and crimped directly in the socket o Terminations for pigtail connectors shall utilize feed- through terminals individually labeled with corresponding circuit numbers 20 amp circuits shall use screwless tension clamp terminals listed for 20 –
8 gauge wire.
Terminals that place a screw directly on the wire are not acceptable o Pigtail boxes shall be supplied with appropriate brackets and hardware for mounting Standard mounting options shall include pipe or wall mounting Brackets shall be made from ASTM A 36 steel Hardware shall be ASTM A307 grade 5
• Physical o Pigtail boxes shall be 6.25” H x 3.3” D and fabricated from 18 gauge galvanized steel and finished in black fine-texture powder coat paint Covers shall be fabricated from 16-gauge galvanized steel o Pigtail boxes shall be available in any length specified in increments of 3-inches with a maximum length of up to 3-feet o Pigtails shall be spaced on 18” centers, or as otherwise specified o Outlets shall be mounted on individual 3” panels o Circuits shall be labeled with 1.25” lettering
Circuit labeling options shall include:
• Circuits shall be labeled on the front side of the connector strip with white lettering on black background labels.
• Circuits shall be labeled on front and back sides of the connector strip with white lettering on black background labels.
• Circuits shall be labeled on the front side of the connector strip with engraved lamicoid labels utilizing white lettering on black background labels.
• Circuits shall be labeled on the front and rear sides of the connector strip with engraved lamicoid labels utilizing white lettering on black background labels.
• Circuits shall be labeled on one side of the connector strip using individual circuit cover plates with lettering engraved in the cover and filled with the specified color.
• Circuits shall be labeled using specified labeling per plans and drawings o Pigtail boxes shall support optional LED indicators to indicate the presence of power at each local circuit. The indicator shall be red in color and mounted in pigtail box The LED indicator shall be mounted in the lower right corner of the outlet panel The LED indicator shall be mounted in the bottom of the pigtail box directly below the outlet panel The LED indicator shall be mounted in the cover plate directly below the circuit label for pigtail circuits
• Provide one (1) custom surface mount pigtail box: 9300 Series with: 8 - 18" pigtails and
20A Edison (5-20R) connectors wired on 8 - 20A circuits 4 - 18" pigtails and 20A Stage Pin (2P&G/GPC) connectors wired on 4 - 20A circuits
DELIVERY
The Contractor shall delivery all equipment specified herein no later than 10-days after award.
This delivery due date includes the required installation and demonstration services identified below.
The Contractor shall delivery all equipment in accordance with the approved Shop Drawings, Manufacturer’s instructions, and referenced quality standards as indicated herein.
INSTALLATION
The Contractor shall install stage controls, where shown, in accordance with manufacturer’s written instructions and with recognized industry practice to ensure that stage lighting equipment complies with applicable requirements of NEW and UL standards and with the applicable portions of NECA’s “Standard of Installation” and Trade Standards specified herein and before.
DEMONSTRATION
Operation and Maintenance Training
• A sign-in sheet shall be provided to maintain a record of attendees, in addition to a training sign off containing signatures from both an authorized trainer and end user.
• Provide links to additional support documentation, including but not limited to:
o Links to ETC video libraries and databases including product support articles, dimming compatibility charts, and software downloads o Distribute technical support hotlines and guidelines:
ETC Technical Support 24-hour hotline for emergencies with guaranteed response within fifteen minutes of initial contact, versus non-emergency hot line
Troubleshooting with ETC Local ETC service center provider within fifty miles of job site
FIELD QUALITY CONTROL
Final Inspection:
• Final inspection will be made by the Kennedy Center personnel following load testing.
• If inspection reveals any component of construction, fabrication, or installation to not be in strict accordance with the Contract Documents, approval will be withheld. Contractor shall be given thirty (30) days to replace rejected items with those conforming to specification requirements.
• At the time of the final inspection the Contractor shall furnish sufficient workers to operate equipment and to perform such adjustments and tests as may be required by the Theatre Consultant and COTR. Equipment that fails to meet with the specifications shall be repaired or replaced with suitable equipment and the inspection shall be rescheduled under the same conditions previously specified.
WARRANTY
The Contractor shall warrant the equipment in accordance with FAR 52.212-4(o). The warranty commence date shall begin on the date of energization sign off for orders which include energization performed by an authorized service provider (Kennedy Center personnel). A signed System Startup Sign Off shall initiate system warranty period.
The warranty duration shall be two (2) years.