This document is a Statement of Work (SOW) for the construction of a 2-story modular office building for the 305 MXS at a U.S. Air Force installation. The vendor shall furnish and assemble all required materials to construct the 18' x 28' modular building, which must be installed in a specific location and elevated 6-8" off the floor. Key requirements include 4" thick insulated walls, electrical and data connections, windows, doors, HVAC systems, stairway with landing, and finished flooring and ceilings. The SOW provides detailed specifications for the framing, walls, doors, windows, electrical, HVAC, roofing, and flooring components. The vendor shall be responsible for transporting waste material to the base recycle center upon completion. This SOW is associated with Solicitation Number FA448424Q0019 for the "305 Modular Office" requirement, issued by the Department of the Air Force's Air Mobility Command. Any questions should be directed to the listed Contracting Specialist and Contracting Officer.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Statement of Work 305 MXS 2-Story Modular Office The scope of work is as follows in the Statement of Work. The vendor shall furnish and assemble all material outlined below to construct a modular building. No alteration, additions or deletions shall be made to the contract unless prior approval is given in writing by the Contracting Officer (CO). The building must be installed in the northern corner of bldg. 2201 outside of the yellow aircraft spacing lines and elevated 6-8” off the floor. It must have an 18’ x 28’ footprint, built with 2 floors. Each floor must be 10’ tall with a 1’ drop ceiling to provide space for LED lighting, electrical systems and fire suppression systems. The walls will be 4” thick, insulated and provide routing and connections for 8 (2 plug) electrical and Cat5E data plugs sets on both floors (refer to drawings for location). The first floor requires 2 doors, one on the western wall and one place on the southern wall. Both doors will have a glass windows and lever lock handles. The first floor requires windows on the western and southern side of the construction. The second floor requires windows along the western and southern sides and 8 data/electrical connections point sets. The HVAC systems on each floor must be a wall mounted unit that rests along the eastern wall. The second floor requires stairs with a landing at the top. All walls, floors and ceilings will be of a finished material. At the completion of construction, the construction team will need to transport all waste material from the build site to the base recycle center approximately ½ mile away.

Vendor must provide the following specifications for the building:

1. GENERAL REQUIREMENTS

a. Frame and Wall systems w/ Electrical raceways/channels

b. Door w/Glass & Lever Lock

c. Fixed Windows

d. Steel Roof Deck

e. 10’ Tall IBC Stairway w/Landing

f. Steel Base w/Subfloor & Vinyl Tile

2. DATA

a. Cat5E Data Jack (Dual Port)

3. ELECTRICAL

a. Dedicated Modular Outlet

b. Modular C.B Box

c. Modular Light Switch

d. Modular Light Fixture

e. Modular Receptacle

4. HVAC

a. Drain Kit for HVAC Units

b. HVAC System

5. Wall Panels

a. 26ea. 4' x 10' x 4" Wall Panel - Interior Wall Make-Up: Gray 1/2" Vinyl Clad Gypsum, Foam Core, Exterior Wall Make-Up: Gray 1/2" Vinyl Clad Gypsum

b. 3ea. 4' x 10' x 4" - Door Panel - (A) Interior Wall Make-Up: Gray 1/2" Vinyl Clad Gypsum, Foam Core, Exterior Wall Make-Up: Gray 1/2" Vinyl Clad Gypsum

c. 16ea. 4' x 40" x 4" - Wall Kick - Interior Wall Make-Up: Gray 1/2" Vinyl Clad Gypsum, Foam Core, Exterior Wall Make-Up: Gray 1/2" Vinyl Clad Gypsum

d. 16ea 4' x 38" x 4" - Wall Top - Interior Wall Make-Up: Gray 1/2" Vinyl Clad Gypsum, Foam Core, Exterior Wall Make-Up: Gray 1/2" Vinyl Clad Gypsum

6. Framing

a. 20ea. Aluminum Fascia - 12' x 2" x 3" - Clear Satin

b. 8ea. Aluminum Corner Post - 10' x 4" - Clear Satin

c. 12ea. Aluminum H-Post - 10' x 4" - Clear Satin

d. 20ea. Aluminum Floor Track - 12' x 4" - Clear Satin

e. 10ea. Aluminum Top Cap - 12' x 4" - Clear Satin

f. 10ea. Aluminum Top Cap Fascia Combo - 12' x 4" - Clear Satin

g. 12ea. Aluminum Splice for Top Cap - 6" x 4" - Clear Satin

7. Doors

a. 2ea. Door - Painted 18 Gauge Steel - 3'-0" x 6'-8" x 1-3/4" - Painted Left Hand Steel Frame

b. 1ea. Door - Painted 18 Gauge Steel - 3'-0" x 6'-8" x 1-3/4" - Painted Right Hand Steel Frame

c. 3ea. Door Lever - Grade 2 Locking

d. 3ea. Vision Lite - 20" x 24" Clear Satin Frame - 3/16" Clear Tempered Glass

e. 25 Powder Coat - V-Tex Gray

8. Windows

a. 3ea Window - 36" x 40" Solid Frame - 3/16" Clear Tempered Glass

b. 13ea Window - 48" x 40" Solid Frame - 3/16" Clear Tempered Glass

c. Raceways/Electrical channels

d. 1ea 10' High - 4" Blank Raceway - No Box

e. 2ea 10' High - 4" Pre-Wired Raceway - Includes: Blank Cutouts w/ Covers - Blank

f. 16ea. 10' High - 4" Pre-Wired Raceway - Includes: Duplex - Ivory

g. 1ea. 10' High - 4" Pre-Wired Raceway - Includes: Switch - Ivory

h. 2ea. 10' High - 4" Pre-Wired Raceway - Includes: 3-Way Switch - Ivory

i. 14ea. 10' High - 4" Raceway - Includes: Single Data Jack - Ivory - No Box

j. 2ea. 10' High - 4" Pre-Wired Raceway - Includes: 230V HVAC 60" and 115v - Ivory

9. Roof

a. 10ea. 20 Gauge 3W-Deck - Dust Cover - 3' x 17'-11" T-Bar Ceiling

b. 142ea. Ceiling Cross Tee 4' - White

c. 210ea. Ceiling Wire - 12 Gauge @ 4' Ft - Includes: Pretied Clip

d. 24ea. Ceiling Main Tee 12' - White HD

e. 20ea. Ceiling Wall Angle 12' – White

f. 150 Ceiling Tile - Standard Fissured - 2' x 4' – White

g. 3ea. R-19 Insulation Batts - 2' x 4' - 144 Sq Ft/Bundle Lights

h. 12ea. 2' x 4' LED Flat Panel Light 3500/4000/5000K Adjustable

10. Wiring

a. 1ea. Electrical Whip Assembly: 100 Ft - 3/8" Flex Metal Clad Single Wire

b. 12ea. Electrical Whip Assembly: 13 Ft - 3/8" Flex Metal Clad Single Wire

c. 3ea. Electrical Whip Assembly: 20 Ft - 3/8" Flex Metal Clad Single Wire

d. 2ea. Chase Nipple - 3/4"

e. 2ea. Lock Nut - 3/4"

f. 6ea. Circuit Breaker: 20 Amp 1-Pole

g. 2ea. Ground Bar Kit - 5 Terminals

h. 2ea. Interior Load Center - 125 Amp 6 Space Single Phase

i. 2ea. Circuit Breaker: 20 Amp 2 Pole

11. Hardware

a. 500ea. #10 x 5/8" Tek Screws Satin -Zinc

b. 117ea. #12 x 1" Tek Screw - Galvanized - ICC Approved

c. 90ea. #12 Hex Head Tek Screw - 2" Zinc

d. 220ea. 5/8" - 11 Nut Grade 5

e. 220ea. 5/8"-11 X 2" Machine Bolt Grade 5

f. 24ea. Wedge Anchors - 5/8" x 6" - HILTI

g. 1,100ea. Flat Tek Screw - #12 x 2 3/4 - Phillips

h. 100ea. #12 x 1" Tek Screw - Galvanized - ICC Approved

12. Mechanical

a. 2ea HVAC Wall Unit - 18000 BTU - Amana with Heat Strip

b. 2ea. HVAC Aluminum Kit - 2" Large 26-1/16" x 16-15/16" – Amana

13. Steel

a. 1ea. 3-1/2" x 6" Steel Angle - 20' GR

b. 2ea. 6" x 1/2" Steel Flat Bar - 20' GR

c. 3ea. 6" x 6" Steel Tube - 24' GR

d. 1ea. 10" X 1/2" Steel Flat Bar - 20'

e. 16ea. Punched Cee Purlin - 12 Gauge Galvanized - 8 Pieces 13' 1-1/2" Long

f. 4ea. Punched Cee Purlin - 12 Gauge Galvanized - 8 Pieces 14' Long

g. 4ea. Punched Cee Purlin - 12 Gauge Galvanized - 8 Pieces 17'-3" Long

h. 4ea. Punched Cee Purlin - 12 Gauge Galvanized - 8 Pieces 17'-3" Long

14. Flooring

a. 42ea. Vinyl Plank Flooring - 6" x 36" - Color: Winding Brook - 24 Sq Ft Per Box

b. 10ea. Cove Base Adhesive - 20'

c. 1ea. Applicator Tool

d. 2ea. Cove Base - 4" Steel Gray (120' Roll)

e. 36ea. 48" x 96" x 1-1/8" Plywood Full Face

15. Stair and Landing

a. 1ea. Stairway with Landing & Handrail - 3' Wide IBC Stairway - 135-1/2" TOD w/ 5' x 5' Landing – Yellow

16. Installation (All Performed by Factory Trained Installers)

a. 10' High Wall(s)

b. Door(s)

c. Window(s)

d. 20ga Roof Deck - Dust Cover

e. Plywood

f. Grid Ceiling & Tiles

g. R-19 Insulation

h. Connection to Beam

i. Cee Purlins

j. Column(s)

k. Vinyl Plank Flooring

l. Cove Base

m. Stairway w/ Landing

n. Wall Mount HVAC

17. Miscellaneous

a. Round trip travel included in quote pricing for all service requirements (subject to change due to airfare)

b. Lodging expenses included in quote pricing for all service requirements (subject to change due to availability)

c. Equipment rental included in quote pricing for all service requirements (subject to change due to availability)

d. Transport of goods to worksite included in quote pricing

e. Trash to be disposed of in customers dumpster

f. Final electrical hookup to power source to be performed by customer/Base Civil Engineering

g. Fire suppression system to be installed by customer/Base Civil Engineering

h. Customer is responsible for furnishing space

Marked Drawing Attached: See the project drawings attached to this SOW.

image1.png

File details come from the government source that posted it. Updated .