3-K2M Harvey Building Spalling Detail Sheet S1.0.pdf
PDF 864 KB Posted
- Solicitation number
- RFS-610
- Issued by
- Monroe County, Florida
About this file
This document is a technical architectural engineering drawing set (Sheet S1.0) from K2M Design focused on spalling repair details for concrete structural elements. The drawing provides comprehensive technical specifications for repairing reinforcing steel in concrete structures, including detailed elevation views and cross-sectional diagrams for Type II Repair (Cosmetic Coating), cleaning of reinforcing steel, and repair techniques for sections with steel section loss. The document includes multiple detailed technical illustrations showing methods for exposing and undercutting reinforcing steel, cleaning oxidized bars, applying protective coatings, and addressing concrete structural degradation.
The technical drawing set is sealed by two licensed professionals - Steven S. Grasley (License #73110) and Scott C. Maloney (License #AR93161), both with expiration dates of 2/28/2027. The document appears to be part of a construction or renovation project, likely for a public or institutional building in Monroe County, as indicated by the document header. The drawings provide precise engineering specifications for concrete repair techniques, including minimum coating depths (20 mil DFT), methods for handling oxidized and unoxidized reinforcing bars, and guidelines for replacing sections of reinforcing steel when section loss exceeds 25%.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2-Structural Report K2M - 7.28.25.pdf | ||
| 1-RFS Harvey Govt Ctr Spalling FINAL.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A A
CLEANING OF REINFORCING STEEL
1.
2.
3.
4.
LIGHT/MEDIUM CORROSION IS DEFINED AS PORTIONS OF THE REINFORCEMENT WITH
SURFACE CORROSION AND LOCAL PITTING THAT RESULTS IN LESS THAN 20% OF
SECTION LOSS OF THE STEEL. HEAVY CORROSION IS ANY CORROSION RESULTING IN
SECTION LOSS GREATER THAN 20%
CLEAN ALL EXISTING REINFORCEMENT WITH LIGHT/MEDIUM OR HEAVY CORROSION TO
REMOVE ALL CORROSION SCALE AND EXPOSE BARE STEEL. ALL SURFACES OF THE
REINFORCEMENT SHALL BE CLEANED. DETERMINE SECTION LOSS AFTER
REINFORCEMENT IS CLEANED TO DETERMINE IF SUPPLEMENTAL REINFORCEMENT IS
REQUIRED.
FOLLOW THE BONDING AGENT MANUFACTURER CLEANING RECOMMENDATIONS FOR
ALL REPAIRS. ALL SCALE SHOULD BE REMOVED FROM THE BAR AS NECESSARY TO
PROMOTE MAXIMUM BOND OF REPLACEMENT MATERIAL. OIL-FREE ABRASIVE BLAST IS
THE PREFERRED METHOD. A TIGHTLY BONDED LIGHT OXIDE BUILD-UP ON THE SURFACE
MAY RESULT FROM HIGH-PRESSURE WATERBLASTING, WITH OR WITHOUT ABRASIVE.
THIS IS USUALLY NOT DETRIMENTAL TO BOND, UNLESS A PROTECTIVE COATING IS
BEING APPLIED TO THE BAR SURFACE, IN WHICH CASE THE COATING MANUFACTURER'S
RECOMMENDATIONS FOR SURFACE PREPARATION SHOULD BE FOLLOWED.
REINFORCEMENT SHOULD BE CLEANED AND DRY BEFORE COATING WITH CORROSION
INHIBITOR AND BONDING AGENT.
NO CORROSION
ORIGINAL MILL SCALE
CORROSION
LIGHT/MEDIUM
CORROSION
HEAVY
CLEANING REQUIRED
CLEANING UNDERSIDE OF BAR
CONCRETE
PATH OF
ABRASIVES
CAREFULLY REMOVE EXIST.
CONC. AROUND BAR TO REACH
UNDAMAGED PORTION OF BAR
EXIST. BOTTOM
OXIDIZED BAR
PROVIDE NEW HORIZONTAL BAR.
IF LOSS OF SECTION IS 25% OR
MORE MATCH EXIST. (TYP.)
ELEVATED SLAB DETAIL
BAR
UNOXIDIZED OXIDIZED BAR
BAR
UNOXIDIZED
REPAIR OF REINFORCING STEEL
DUE TO SECTION LOSS
IF REBAR HAS LOST MORE THAN 25% OF ITS CROSS SECTION (20% IF 2 OR MORE CONSECUTIVE PARALLEL BARS ARE AFFECTED)
CONSULT THE ENGINEER.
IF REPAIRS ARE REQUIRED TO THE STEEL REINFORCEMENT THE FOLLOWING METHODS SHOULD BE USED:
1. COMPLETE BAR REPLACEMENT ADDITION OF SUPPLEMENTAL BAR OVER AFFECTED SECTION.
2. NEW BAR MAY BE MECHANICALLY SPLICED TO OLD BAR OR PLACED PARALLEL TO AND APPROXIMATELY 3/4" FROM EXISTING BAR.
3. LAP LENGTH SHALL BE DETERMINED IN ACCORDANCE WITH ACI 318, AND STRUCTURAL GENERAL NOTES.
EXIST.
REBAR
NEW SPLICED
REBAR
CORROSION
LIGHT/MEDIUM
CORROSION
HEAVY
SEE NOTES
ACI REQUIRED LAP
CLEANED REINFORCEMENT RECOMMENDED CLEARANCE
�3/4" MAX.
CORROSION
LIGHT/MEDIUM
SEE NOTES
ACI REQUIRED LAP
TYPE II REPAIR
(COSMETIC COATING) ELEVATION VIEW
SURFACE OF CONCRETE
CLEAN EXPOSED REINF. STEEL AND
COAT EXPOSED BARS WITH
REINFORCEMENT PROTECTION
MATERIAL MIN 20 MIL DFT COATING
EX
PO
SE
D
RE
IN
F.
S
TE
EL
LIN
EA
R
FE
ET
O
F
TYPICAL CONCRETE REPAIR
ELEVATION AT COLUMN
CLEAN OXIDIZED, EXPOSED
EXIST. REINFORCING AS
REQUIRED (TYP.)(FIELD VERIFY)
DO NOT CUT OR DAMAGE
EXISTING REINFORCING.
EXIST. CONCRETE BEAM
EXIST. COLUMN
FIELD VERIFY AND PREPARE
REPAIR AREA AS REQUIRED.
PROVIDE NEW COLUMN
VERTICAL, IF LOSS OF SECTION
IS 25% OR MORE. MATCH EXIST.
(TYP.)(FIELD VERIFY)
PROVIDE #4 BENT BAR IF LOSS
OF SECTION IS 25% OR MORE
AS REQUIRED
SECTION A-A
EXIST. COLUMN
VERTICAL (TYP.)
NEW VERTICAL
AS REQUIRED
EXIST. CONCRETE
COLUMN
DRILL AND INSTALL NEW #4 TIES w/
EPOXY ADHESIVE SYSTEM TO
ANCHOR BAR INTO EXIST. COLUMN
6"
�3"
APPLY SIKA TOP 123 PLUS
MORTAR (FOLLOW
MANUFACTURER'S INSTRUCTIONS)
SEE NOTE 4 BELOW
UNDAMAGED CONCRETE
EXIST. UNCORRODED REBAR
TIGHTLY BONDED TO CONCRETE
EXIST. CONCRETE SURFACES PREPARED
TO RECEIVE REPAIR MATERIAL
EXIST. CORRODED REBAR, TYP.
TYPICAL EXPOSING AND UNDERCUTTING
REINFORCING STEEL DETAIL
SECTION THROUGH CONCRETE MEMBER
APPLICABLE TO HYDRODEMOLITION, HYDROMILLING, AND PNEUMATIC, HYDRAULIC
AND ELECTRIC BREAKERS
CAUTION! BEFORE STARTING REMOVALS, REVIEW EFFECT OF REMOVALS ON
STRUCTURAL INTEGRITY. PROVIDE SHORING OF MEMBER AS NECESSARY.
PARTICULAR CARE SHALL BE EXERCISED AT SLAB/BEAM CONNECTIONS TO COLUMNS.
1.
2.
3.
4.
5.
REMOVE LOOSE OR DELAMINATED CONCRETE ABOVE CORRODED REBAR.
ONCE INITIAL REMOVALS ARE MADE, PROCEED WITH UNDERCUTTING OF
ALL EXPOSED CORRODED REBAR. UNDERCUTTING WILL PROVIDE
CLEARANCE FOR UNDER BAR CLEANING, FULL BAR CIRCUMFERENCE
BONDING TO SURROUNDING CONCRETE, AND WILL SECURE THE PATCH
STRUCTURALLY.
UNDERCUTTING OF EXISTING REBAR: PROVIDE MINIMUM 3/4" CLEARANCE
BETWEEN EXPOSED BARS AND SURROUNDING CONCRETE OR 1/4" MORE
THAN THE LARGEST AGGREGATE IN CONCRETE REPAIR MATERIAL,
WHICHEVER IS GREATER.
CONCRETE REMOVALS SHALL EXTEND ALONG THE REBAR TO LOCATIONS
THAT ARE FREE OF BOND INHIBITING CORROSION, AND WHERE THE BAR IS
WELL BONDED TO SURROUNDING CONCRETE.
IF UNCORRODED REBAR IS EXPOSED DURING THE UNDERCUTTING
PROCESS, CARE SHALL BE TAKEN NOT TO DAMAGE THE BAR'S BOND TO
SURROUNDING CONCRETE. IF BOND BETWEEN BAR AND CONCRETE IS
BROKEN, UNDERCUTTING OF THE BAR WILL BE REQUIRED.
ANY REINFORCEMENT WHICH IS LOOSE SHALL BE SECURED IN PLACE BY
TYING TO OTHER SECURED BARS OR BY OTHER APPROVED METHODS.
DESIGN CRITERIA
APPLICABLE BUILDING CODE: 2023 FLORIDA BUILDING CODE, BUILDING (2023 FBC)
SPALLING REPAIR GUIDELINES :
THE FOLLOWING IS OFFERED FOR GENERAL INFORMATION AND GUIDANCE TO THE
CONTRACTOR AND BUILDING OWNER(S). DURING REPAIRS, CONDITIONS MAY BE EXPOSED
WHICH REQUIRE FURTHER INSPECTION BY THE ENGINEER AND MORE SPECIFIC INSTRUCTIONS
FOR PROPER REPAIR.
1) ALL WORK SHALL COMPLY WITH APPLICABLE CODES INCLUDING, BUT NOT LIMITED TO FBC
2023 PLUS SUPPLEMENTS, ASCE 7-22, AND ACI 318.
2) THE CONTRACTOR MAKING THE REPAIRS SHALL BE RESPONSIBLE FOR THE MEANS,
METHODS, TECHNIQUES, SEQUENCE, PROCEDURES, AND ALL SAFETY ASPECTS OF THE
CONSTRUCTION.
3) THE CONTRACTOR SHALL PROTECT ALL UTILITIES, BUILDING COMPONENTS, AND
PROPERTY ADJACENT TO THE REPAIR AREAS. THE CONTRACTOR SHALL BE RESPONSIBLE
TO REPAIR OR REPLACE ANY DAMAGE AT THEIR EXPENSE.
4) REMOVE ALL NON-STRUCTURAL ITEMS ATTACHED TO THE AREA OF REPAIR TO ALLOW
FULL ACCESS TO THE REPAIR.
5) TEMPORARY SHORING SHALL BE INSTALLED, IF REQUIRED, TO SUPPORT LOADS
SUPPORTED BY THE STRUCTURAL ELEMENT BEING REPAIRED. EACH POST SHORE SHALL
BE CAPABLE OF SUPPORTING AT LEAST FIVE THOUSAND POUNDS INDEFINITELY AND SHALL
BE PLACED IN A PROPER MANNER. TEMPORARY SHORING IS THE CONTRACTOR'S
RESPONSIBILITY. THE CONTRACTOR SHALL ENGAGE A LICENSED PROFESSIONAL
ENGINEER TO DESIGN TEMPORARY SHORING. PROVIDE SHORING PLAN, SHORING
SEQUENCE, AND CALCULATIONS SUBMITTAL SIGNED AND SEALED BY A LICENSED
ENGINEER IN THE PROJECT LOCATION.
6) REPAIR PROCEDURE IS AS FOLLOWS:
(a) SOUND CONCRETE SURFACES TO LOCATE CONCEALED SPALLING AND DELAMINATION.
(b) REMOVE ALL SPALLED AND CRACKED CONCRETE FROM ALL SURFACES OF THE
STRUCTURAL COMPONENT DOWN TO UNDAMAGED CONCRETE AND REMOVE ALL
CONCRETE IN CONTACT WITH CORRODED STEEL REINFORCEMENT (REBAR) AND
UNDERCUT BELOW THE EXISTING REBAR AS REQUIRED. REMOVE CONCRETE BY
CHIPPING. ALL HORIZONTAL STRUCTURAL (BEAMS AND SLABS) SHOULD BE SHORED
PRIOR TO SELECTIVE DEMOLITION UNLESS DEEMED NOT REQUIRED BY THE
ENGINEER.
(c) CLEAN EXPOSED STEEL REINFORCEMENT TO REMOVE ALL CORROSION AND SCALE
AND CLEAN THE NEWLY EXPOSED CONCRETE SURFACES. REMOVE ALL LOOSE
MATERIAL, WET CONCRETE, TRACES OF OIL, GREASE, LAITANCE, FORM TREATMENTS,
ETC.
(d) COMPLETELY COAT THE EXPOSED STEEL REINFORCEMENT WITH A CORROSION
INHIBITOR SUCH AS CORROSEAL TO ISOLATE THE BARS FROM THE NEW REPAIR
CONCRETE MATERIAL THAT WILL BE USED.
(e) ADD ANCHORS, STIRRUPS, ETC., AS NECESSARY TO PROVIDE FOR PROPER
ATTACHMENTS OF THE REPAIR MATERIAL AS DETAILED IN THE SPECIFIC REPAIR
INSTRUCTIONS OR DESIGN.
(f) USE APPROVED BONDING AGENT TO IMPROVE COLD JOINT BOND BETWEEN ALL
EXPOSED OLD SURFACES AND THE NEW CONCRETE OR PATCHING MATERIAL.
(g) APPLY PATCHING MATERIAL TO MATCH THE EXISTING CONCRETE.
7) THE BONDING AND PATCHING AGENT SHALL BE SPEED CRETE REDLINE OR EQUIVALENT
AND SHALL BE APPLIED ACCORDING TO THE MANUFACTURER ’S RECOMMENDATIONS.
8) ALL CRACKS LESS THAN 1/16" WIDE, NOT IDENTIFIED BY THE ENGINEER ARE CONSIDERED
NONSTRUCTURAL MINOR CRACKS. NONSTRUCTURAL MINOR CRACKS SHOULD BE OPENED
TO REMOVE LOOSE MATERIAL AND MAY BE EPOXY INJECTED WITH A HIGH MODULUS
EPOXY RESIN CONFORMING TO ASTM C881.
9) IF ANY STEEL REINFORCEMENT IS FOUND TO BE DEGRADED BY MORE THAN 30% OF ITS
ORIGINAL DIAMETER, NEW STEEL REINFORCEMENT SHALL BE SPLICED TO REPLACE THE
COMPROMISED BAR. SEE REPAIR OF REINFORCING STEEL DUE TO SECTION LOSS DETAIL.
10) FORMS SHALL BE CONSTRUCTED TO MATCH THE EXISTING FINISHED SHAPE UNLESS
SPECIFIED OTHERWISE.
11) ANY CONCRETE REPAIR MATERIAL USED IN THE REPAIR SHALL HAVE A 28-DAY
COMPRESSIVE STRENGTH OF 5,000 PSI MINIMUM AND SHALL CONTAIN OR BE
PREMANUFACTURED WITH CORROSION INHIBITOR ADMIXTURE.
12) THE CONTRACTOR SHALL CONTACT THE ENGINEER FOR FURTHER DESIGN DETAIL IF
THERE IS BELIEVED TO BE ANY NEED FOR A SPECIAL ADMIXTURE OR PROCEDURE DURING
THE REPAIR.
13) CONTACT K2M DESIGN, INC. FOR FURTHER GUIDANCE IF THE ABOVE INSTRUCTIONS
CANNOT BE ACHIEVED OR RESULT IN A CONFLICT.
APPLICABLE TO PROJECT VERIFICATION AND INSPECTION TASK CONTINUOUS DURING TASK LISTED PERIODICALLY DURING TASK LISTED REFERENCED STANDARD (a) APPLICABLE CODE REFERENCE
X 1. INSPECTION OF REINFORCING STEEL, INCLUDING PRE-STRESSING TENDONS
AND PLACEMENT -- X ACI 318: 20, 25.2, 25.3, 26.6.1-26.6.3
X
2. REINFORCING BAR WELDING
a. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM A706;
b. INSPECT SINGLE PASS FILLET WELDS MAXIMUM 5/16”: AND c INSPECT ALL OTHER WELDS
-- X AWS D1.4
ACI 318:26.6.4 --
3. INSPECTION OF ANCHORS CAST IN CONCRETE ACI 318: 17.8.2
ACI 318: 17.8.2.4 --
X 5. VERIFYING USE OF REQUIRED DESIGN MIX -- X ACI 318: 19, 26.4.3, 26.4.4 1904.1, 1904.2
X
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR
STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TEST, AND
DETERMINE THE TEMPERATURE OF THE CONCRETE
X --
ASTM C 31
ASTM C 172
ACI 318: 26.5, 26.12
X 7. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER APPLICATION TECHNIQUES X -- ACI 318: 26.5 --
X 8. INSPECTION FOR MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND
TECHNIQUES -- X ACI 318: 26.5.3 -26.5.5
X -- ACI 318: 26.10 --
X --
10. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS -- X ACI 318: 26.9 --
13. VERIFICATION OF IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING OF
TENDONS IN POST-TENSIONED CONCRETE AND PRIOR TO REMOVAL OF SHORES
AND FORMS FROM BEAMS AND STRUCTURAL SLABS
-- X ACI 318: 26.11.2 --
14. INSPECT FORMWORK FOR SHAPE, LOCATION, AND DIMENSIONS OF
CONCRETE MEMBER BEING FORMED -- X ACI 318: 26.11.1.2 (b) --
(a) WHERE APPLICABLE, SEE SECTION 1705.13.
(b) SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR ISSUED BY AN APPROVED SOURCE IN ACCORDANCE WITH 17.8.2 ACI 318, OR OTHER QUALIFICATION PROCEDURES. WHERE SPECIFIC REQUIREMENTS ARE NOT PROVIDED, SPECIAL INSPECTION REQUIREMENTS SHALL BE SPECIFIED BY THE REGISTERED DESIGN PROFESSIONAL AND SHALL BE
APPROVED BY THE BUILDING OFFICIAL PRIOR TO THE COMMENCEMENT OF THE WORK.
TABLE 3: REQUIRED VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION
X --
-- X
X
X
-- X --
4. INSPECTION OF ANCHORS POST INSTALLED IN HARDENED CONCRETE MEMBERS
a. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATION TO RESIST SUSTAINED TENSION LOADS.
b. MECHANICAL ANCHORS OR ADHESIVE ANCHORS NOT DEFINED IN 4.a.
9. INSPECTION OF PRESTRESSED CONCRETE FOR:
a. APPLICATION OF PRESTRESSING FORCES AND
b. GROUTING OF BONDED PRESTRESSING TENDONS
ACI 318: 17.8.2
11. FOR PRECAST CONCRETE DIAPHRAGM CONNECTIONS OR REINFORCEMENT AT JOINTS
CLASSIFIED AS MODERATE OR HIGH DEFORMABILITY ELEMENTS (MDE OR HDE) IN
STRUCTURES ASSIGNED TO SEISMIC DESIGN CATEGORY C, D, E, OR F, INSPECT SUCH
CONNECTIONS AND REINFORCEMENT IN THE FIELD FOR:
a. INSTALLATION OF THE EMBEDDED PARTS
b. COMPLETION OF THE CONTINUITY OF REINFORCEMENT ACROSS JOINTS c COMPLETION OF CONNECTIONS IN THE FIELD
X
X X
ACI 318: 26.13.1.3
ACI 550.5
12. INSPECT INSTALLATION TOLERANCES OF PRECAST CONCRETE DIAPHRAGM CONNECTIONS
FOR COMPLIANCE WITH ACI 550.5 -- X ACI 318: 26.13.1.3 --
X www.k2mdesign.com
Architecture, Engineering, Interior Design, Facility Asset Management
Building Relationships Based on Trust and Results
Cleveland | Indianapolis | Key Largo | Key West | Marathon | Charlotte | Columbus | NW Arkansas | Tampa
ARCHITECT:
©2025 by K2M Design, Inc.
Date:
Sheet Number:
Title:
Drawn By:
Drawing Size
Checked By:
Project #:
24X36
Submissions:
Seal:
NOTE: This item has been digitally signed and sealed. Digital signatures must be verified on electronic files. Reproduced copies of digitally signed, dated, and sealed documents are not considered signed and sealed.
Steven S. Grasley, License #73110 Expiration Date 2/28/2027
COA #30945
Scott C. Maloney, License #AR93161 Expiration Date 2/28/2027
COA #AA26001059
\\K 2M
SR
V-
N
FS
\U
EM
Pr of ile
\tp er ki ns
\P ro fil e\
D oc um en ts \2
H ar ve y Bu ild in g Sp al lin g-st ru c-
R
_t pe rk in s4 4V
H M
.rv t
8/ 1/
2:
:2
PM
H ar ve y
Bu ild in g
- S pa llin g
R ep ai rs
T ru m an
A ve
, K ey
W es t, FL
M on ro e
C ou nt y
SPALLING REPAIR
DETAILS
TKP Checker
25810
S1.0 7/30/2025
S im on to n St
, K ey
W es t, FL
No. Description Date
S1.0 - SPALLING REPAIR DETAILS