3-Jefferson WWTP-HVAC Upgrades.pdf
PDF 5 MB Posted
- Attached to
- Treatment Plant Upgrades
- Solicitation number
- US.263198
- Issued by
- York County, Pennsylvania
About this file
This document is a bidding package for Treatment Plant Upgrades issued by the Jefferson Codorus Joint Sewer Authority in York County, Pennsylvania. The project encompasses equipment and valve replacements at various locations throughout the plant, HVAC replacements for the laboratory and blower room, door repair, and light replacement. The work is divided into two contracts: Contract No. 1 for General Construction and Contract No. 2 for Electrical Construction. Sealed bids will be received online through the PennBid Program until 10:00 a.m. on Tuesday, January 5, 2027, with public opening and electronic reading of bids occurring at the same time and date. A pre-bid conference is scheduled for Wednesday, December 9, 2026, at 10:00 a.m. at the Jefferson Borough Office located at 48 Baltimore Street, Codorus, PA 17311; bidder attendance is optional. The contract term is one hundred twenty (120) calendar days. Bidding documents are available online at no cost through the PennBid website.
Each bidder must submit a bid bond from an acceptable surety or a certified check payable to the Jefferson Codorus Joint Sewer Authority equal to 5% of the maximum bid. Bidders are required to provide evidence of their qualifications to perform the work. The project is subject to the Pennsylvania Prevailing Wage Act (Act No. 442, P.L. 987, as amended) and applicable federal and state statutes regarding environmental pollution prevention and natural resource preservation. Contract awards will be determined at a regularly scheduled meeting of the Authority. The Jefferson Codorus Joint Sewer Authority has authorized C.S. Davidson, Inc., to act on their behalf in opening bids.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
717-577-4744 | www.jegoodce.com
10709 Susquehanna Trail, Glen Rock, PA 17327
JE GOOD Consulting Engineers, LLC Sheet Title
Project Name
Jefferson WWTP - HVAC Upgrades
Floor Plan - Demo & New Work
Project Number:
26.0044
Date
Bulletin Drawing
10.29.2026
SKE-1
ELECTRICAL SPECIFICATIONS
1. CONDUIT:
1.1. INTERIOR EXPOSED WHERE NOT SUBJECT TO DAMAGE: EMT
1.2. INTERIOR EXPOSED WHERE SUBJECT TO DAMAGE: RMC
1.3. INTERIOR CONCEALED: EMT
1.4. EXTERIOR EXPOSED WHERE NOT SUBJECT TO DAMAGE: RMC
1.5. INTERIOR EXPOSED WHERE SUBJECT TO DAMAGE: RMC
1.6. CONNECTIONS TO VIBRATING EQUIPMENT OR MOTORS: LFMC
2. CONDUCTORS:
2.1. POWER: THHN/THWN-2 INSULATION, COPPER, STRANDED. MINIMUM
SIZE #12 AWG
2.2. CONTROLS: THHN/THWN-2 INSULATION, COPPER, STRANDED.
MINIMUM SIZE #14 AWG
2.3. CONDUCTOR COLORS:
2.3.1. 208Y/120V - BLACK, RED, BLUE, WHITE, GREEN. SOLID COLORS
2.3.2. 480Y/277V - BROWN, ORANGE, YELLOW, GRAY, GREEN/YELLOW
STRIPE
DESCRIPTIONSYMBOL
ELECTRICAL LEGEND
MOTOR TERMINATION
FUSED DISCONNECT SWITCH
NON-FUSED DISCONNECT SWITCH
JUNCTION BOX - MOTOR OPERATED DAMPER
NORMALLY OPEN CONTACT
SWITCH, MOTOR RATED
OVERLOAD (O/L)
VARIABLE FREQUENCY DRIVE
MOD
ELECTRICAL SCOPE OF WORK
DEMOLITION:
1. SELECTIVE DEMOLITION INDICATED.
NEW WORK:
1. PROVIDE ELECTRICAL INSTALLATION AND EQUIPMENT INDICATED FOR HEAT PUMP (HP-1) INDOOR AIR-HANDLER AND OUTDOOR CONDENSING UNIT.
2. PROVIDE ELECTRICAL ELECTRICAL INSTALLATION AND EQUIPMENT INDICATED FOR BLOWER ROOM EXHAUST FANS EF-1 AND EF-2. INTERLOCK WITH LOUVER
PER WIRING DIAGRAM. COORDINATE AND PROVIDE FIELD WIRING WITH INTERLOCKS.
3. PROVIDE VFD'S PER SCHEDULE. PROVIDE SUBMITTAL FOR REVIEW. PROVIDE O&M MANUAL WITH OWNER TRAINING.
JE GOOD Consulting Engineers, LLC Sheet Title
Project Name
Jefferson WWTP - HVAC Upgrades
DAMPER CONTROL WIRING
Project Number:
26.029
Date
Bulletin Drawing
10.29.2026
SKE-2
M
H
O/L
(FIELD SIZE FOR
DAMPER)
MANUAL
MOTOR STARTER
SWITCH
N.O AUX
CONTACT IN
FAN EF-1
VFD
DAMPER MOTOR
N
DAMPER CONTROL WIRING DIAGRAM
MODIFY EXISTING 120V-1PH
CIRCUIT TO PB-13 TO EXTEND TO DAMPER.
INTERCEPT AND EXTEND EXISTING CONDUIT
AND WIRE.
N.O AUX
CONTACT IN
FAN EF-2
VFD
VARIABLE FREQUENCY DRIVE SCHEDULE
DESIGNATION VOLTAGE PHASE HP DISC. AMPS NEMA ENCL. AUX CONTACTSPOLES CONTROLS BASIS MFG. BASIS CATALOG. NOTES
VFD-EF-1 240V 1 0.5 30A 1 1-N.O. & 1-N.C.2 HOA SCHNEIDER ALTIVAR 12 INTERNAL CB DISCONNECT
VFD-EF-2 240V 1 0.5 30A 1 1-N.O. & 1-N.C.2 HOA SCHNEIDER ALTIVAR 12 INTERNAL CB DISCONNECT
PANEL: "PA" AMP: 600 VOLT: 277/480
PHASE: 3 4 WIRE + GND
MOUNTING: SURFACE MAIN: 600 MCB AIC: 18K AMPS RMS SYM
ENCLOSURE: NEMA 1
Branch Circuit KVA Load Trip Ckt. Ckt. Trip KVA Load Branch Circuit Load Description A B C Poles No. Phase No. Poles A B C Load Description
EX TRF-PB (45KVA) 16.76 70/3 1 A 2 80/3 15.00 EX EC: WET WELL
** 15.53 ** 3 B 4 ** 15.00 ** ** 10.87 ** 5 C 6 ** 15.00 **
EX EC: BLOWER ROOM HEATER 5.00 30/3 7 A 8 50/3 5.00 EX EC: UV BUILDING
** 5.00 ** 9 B 10 ** 5.00 ** ** 5.00 ** 11 C 12 ** 5.00 **
EX EC: MUFFIN MONSTER 1.33 20/3 13 A 14 20/3 2.67 EX EC: SLUDGE PUMP
** 1.33 ** 15 B 16 ** 2.67 ** ** 1.33 ** 17 C 18 ** 2.67 **
EX EC: UTILITY PUMP 4.43 20/3 19 A 20 30/3 6.65 EX EC: SCREEN PANEL
** 4.43 ** 21 B 22 ** 6.65 ** ** 4.43 ** 23 C 24 ** 6.65 **
SPACE 0.00 PS/1 25 A 26 PS/1 0.00 SPACE
SPACE 0.00 PS/1 27 B 28 PS/1 0.00 SPACE
SPACE 0.00 PS/1 29 C 30 PS/1 0.00 SPACE
SPACE 0.00 PS/1 31 A 32 PS/1 0.00 SPACE
SPACE 0.00 PS/1 33 B 34 PS/1 0.00 SPACE
SPACE 0.00 PS/1 35 C 36 PS/1 0.00 SPACE
SPACE 0.00 PS/1 37 A 38 PS/1 0.00 SPACE
SPACE 0.00 PS/1 39 B 40 PS/1 0.00 SPACE
SPACE 0.00 PS/1 41 C 42 PS/1 0.00 SPACE
A SUB 350/3 51.93 EX EC: SBR CONTROL PANEL
B FEED ** 51.93 **
C CB ** 51.93 **
27.52 26.29 21.64 << PHASE SUB-TOTALS >> 29.32 29.32 29.32 MECH EQUIPMENT CIRCUIT BRKRS
SHALL BE HACR RATED.
PROVIDE THE FOLLOWING:
319.21 KVA CONNECTED LOAD
PHASE A 56.84 kVA 383.96 AMP TOTAL CONNECTED LOAD PHASE B 55.61 kVA 396.22 kVA TOTAL DEMAND LOAD PHASE C 50.96 kVA 478.62 AMP TOTAL DEMAND LOAD
PANELBOARD SPECIFIC NOTES:
1. PROVIDE NEW CIRCUIT BREAKER INDICATED IN AVAILABLE SPACE. MATCH EXISITNG PANEL MANUFACTURER, TYPE, AND AIC RATING.
717-577-4744 | www.jegoodce.com 10709 Susquehanna Trail, Glen Rock, PA 17327
JE GOOD Consulting Engineers, LLCSheet Title
Project Name
Jefferson WWTP - HVAC Upgrades
PANELBOARD "PA" SCHEDULE
Project Number:
26.029
Date
Bulletin Drawing
10.29.2026
SKE-3
JE GOOD Consulting Engineers, LLC Sheet Title
Project Name
Jefferson WWTP - HVAC Upgrades
PANELBOARD "PB" SCHEDULE
Project Number:
26.029
Date
Bulletin Drawing
10.29.2026
SKE-4
PANEL: "PB" AMP: 150 VOLT: 120/208
PHASE: 3 4 WIRE + GND
MOUNTING: SURFACE MAIN: 150 MCB AIC: 10k AMPS RMS SYM
ENCLOSURE: NEMA 1
Branch Circuit KVA Load Trip Ckt. Ckt. Trip KVA Load Branch Circuit Load Description A B C Poles No. Phase No. Poles A B C Load Description
EX LIGHTS 1.16 20/1 1 A 2 20/1 0.36 EX REC: LAB
EX LIGHTS 0.56 20/1 3 B 4 20/1 0.54 EX REC: LAB
EX REC: STORAGE 0.54 20/1 5 C 6 20/1 0.54 EX REC: BATH ROOM
EX MH: CHEM ROOM 1.50 20/1 7 A 8 20/1 0.54 EX REC: BLOWER RM
EX EC: FLOW METER 0.30 20/1 9 B 10 20/1 0.72 EX REC: BLOWER RM
EX EC: CHEM PUMPS 0.54 20/1 11 C 12 20/1 0.50 EX EC: DIALER
NOTE 3 MAS: BLOWER RM EF-1 0.12 20/1 13 A 14 20/1 0.70 EX LTG: TANK LIGHTS
EX ENC: WINCH REC @ TANK 1.50 20/1 15 B 16 20/1 0.90 EX REC: TANK NORTH
EX MH: ELEC\ ROOM 1.50 20/1 17 C 18 20/1 0.54 EX REC: TANK SOUTH
EX MH: BATHROOM 1.50 20/1 19 A 20 45/2 4.17 MAS: HP-INDOOR NOTE 1
EX MH: STORE ROOM 1.50 20/1 21 B 22 ** 4.17 **
EX MAS: WATER HEATER 1.50 20/2 23 C 24 20/2 1.13 MAS: HP-OUTDOOR NOTE 2
** 1.50 ** 25 A 26 ** 1.13 **
EX MAS: ELEC RM EF 0.50 20/1 27 B 28 20/1 0.50 EX UNKNOWN LOAD
EX EC: GEN BATT HEATER 0.20 20/1 29 C 30 20/1 0.50 EX LTS: SCREEN
EX EC: GEN BATT CHARGER 1.20 20/1 31 A 32 20/1 1.92 EX MH: CHEM LINE HEAT
EX EC: AC CHEM PUMP 1.92 20/1 33 B 34 20/1 1.92 SPARE
EX MAS: WELL PUMP 0.96 20/2 35 C 36 20/1 1.92 EX MH: INFLUENT HEAT TAPE
** 0.96 ** 37 A 38 20/1 0.00 EX MH: EFFLUENT HEAT TAPE
NOTE 4 MAS: EF-1 0.25 15/2 39 B 40 15/2 0.25 MAS: EF-2 NOTE 4
** 0.25 ** 41 C 42 ** 0.25 **
7.94 6.53 5.49 << PHASE SUB-TOTALS >> 8.82 9.00 5.38 MECH EQUIPMENT CIRCUIT BRKRS
SHALL BE HACR RATED.
PROVIDE THE FOLLOWING:
43.16 KVA CONNECTED LOAD
PHASE A 16.76 kVA 119.79 AMP TOTAL CONNECTED LOAD
PHASE B 15.53 kVA 51.15 kVA TOTAL DEMAND LOAD
PHASE C 10.87 kVA 127.49 AMP TOTAL DEMAND LOAD
PANELBOARD SPECIFIC NOTES:
1. REMOVE EXISTING 80A/2P CIRCUIT BREAKER AND PROVIDE NEW CIRCUIT BREAKER INDICATED IN AVAILABLE SPACE MADE AVAILABLE BY REMOVAL.
MATCH EXISTING PANEL MANUFACTURER, TYPE, AND AIC RATING.
2. REMOVE EXISTING 30A/2P CIRCUIT BREAKER AND PROVIDE NEW CIRCUIT BREAKER INDICATED IN AVAILABLE SPACE MADE AVAILABLE BY REMOVAL.
MATCH EXISTING PANEL MANUFACTURER, TYPE, AND AIC RATING.
3. MODIFIED CIRCUIT LOAD. CIRCUIT BREAKER TO REMAIN AS IS.
4. PROVIDE CIRCUIT BREAKER INDICATED IN AVAILABLE SPACE. MATCH EXISTING PANEL MANUFACTURER, TYPE, AND AIC RATING.
| Sketch - Jefferson WWTP HVAC (100%) rev3 (SKM-1) |
| Sketch - Jefferson WWTP HVAC (100%) rev3 (SKM-2) |
| Sketch - Jefferson WWTP HVAC (100%) rev3 (SKM-3) |
| Sketch - Jefferson WWTP HVAC (100%) rev3 (SKM-4) |
| Sketch - Jefferson WWTP HVAC (100%) rev3 (SKM-5) |