3-ESH 2020-440 H (1-2) - Drawing Set.pdf
PDF 24 MB Posted
- Attached to
- BID - DSHS - ESH - EL & WL : Fire & Smoke Ctrl Retro-Comm REBID - Department of Social & Health Services
- Solicitation number
- 2020-440 H (1-2)
- Issued by
- Washington
About this file
This document is a comprehensive set of architectural and mechanical drawings for a fire and smoke control retrofit project at Eastern State Hospital in Medical Lake, Washington, involving the Department of Social and Health Services (DSHS) and the Department of Enterprise Services. The project focuses on addressing existing fire safety and smoke control deficiencies in the Eastlake and Westlake Buildings, specifically targeting the shared plenum return between corridors and patient rooms, which currently violates healthcare occupancy requirements per NFPA 101 Section 19.3.6.2.1. The scope includes decommissioning the existing smoke control system, adding smoke dampers at corridor plenum return locations and in areas considered hazardous, and modifying fire alarm and HVAC system controls across multiple building levels (basement, first, second, and third floors).
The project involves extensive retrofitting of mechanical systems, including installing new Ruskin smoke dampers with 24V power and end switches, modifying ductwork, adding fire alarm output control modules, and implementing new control sequences for building automation systems. The drawings detail specific requirements for each floor, including smoke compartment modifications, damper installations, and fire/smoke barrier improvements. The retrofit is designed to enhance life safety by improving smoke containment, separating hazardous areas, and ensuring proper fire alarm and HVAC system responses during potential emergency events. The project appears to be a rebid, suggesting previous solicitations may have been unsuccessful, and includes alternate bid scopes to provide flexibility in implementation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1-DES Online Bidding Vendor Submission Instructions.pdf | ||
| 2-ESH 2020-440 H (1-2) - Spec Book.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COVER SHEET
G-001
JTT
SDK
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
850 MAPLE ST
MEDICAL LAKE, WA 99022
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
2020-440 H (1-2)
192591
8/22/25
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
www.coffman.com ph 509.328.2994
221 N. Wall Street, Suite 500 Spokane, WA 99201
ESH - EL & WL FIRE AND SMOKE CONTROL RETRO-COMMISSION
EASTERN STATE HOSPITAL
EASTLAKE BUILDING AND WESTLAKE BUILDING
850 MAPLE ST,
MEDICAL LAKE, WA 99022
MECHANICAL ENGINEER
Coffman Engineers 221 N Wall St, Suite 500 Spokane, WA 99201 509-328-2994 Scott Knecht, PE
VICINITY MAP
For: Department of Social and Health Services Owner: Department of Enterprise Services, Facilities Professional Services
ARCHITECT
ALSC Architects 203 N Washington, Suite 400 Spokane, WA 99201 509-838-8568 Todd Keller, AIA
SHEET INDEX
Sheet Number Sheet Title
G-001 COVER SHEET
A-100 OVERALL PLAN, PARTIAL PLANS, DOOR ELEVATION AND DETAILS
A-110 F WARD SMOKE BARRIER PLAN, UL DETAILS
A-111 UL ASSEMBLIES
M-001 GENERAL MECHANICAL NOTES, LEGENDS, AND SHEET INDEX
MD-101 EL LEVEL 1 NORTH DEMO
MD-102 EL LEVEL 2 NORTH DEMO
MD-103 EL LEVEL 3 NORTH DEMO
MD-104 EL BASEMENT SOUTH DEMO
MD-105 EL PENTHOUSE
M-201 EL BASEMENT SOUTH - ALTERNATE BID 1
M-202 EL BASEMENT MIDDLE - ALTERNATE BID 1
M-203 EL BASEMENT NORTH - ALTERNATE BID 1
M-204 EL LEVEL 1 SOUTH
M-205 EL LEVEL 1 MIDDLE
M-206 EL LEVEL 1 NORTH
M-207 EL LEVEL 2 SOUTH
M-208 EL LEVEL 2 MIDDLE
M-209 EL LEVEL 2 NORTH
M-210 EL LEVEL 3 SOUTH
M-211 EL LEVEL 3 MIDDLE
M-212 EL LEVEL 3 NORTH
M-501 MECHANICAL DETAILS
M-701 MECHANICAL SCHEDULES
FX-001 FIRE ALARM NOTES AND MATRIX
5-15-258-22-25
REBID
ESH - EL & WL FIRE AND SMOKE CONTROL RETRO-COMMISSION REBID
RN1-018
R N
-0
B R
N
-0
RAMP UP
UP
UP
UP
UP
UP
UP
RN1-018
R N
-0
B R
N
-0
RAMP UP
UP
UP
UP
UP
UP
UP
A-100
B3
LIGHT FIXT
2x2 EXIST HVAC DUCT
ABOVE CLG TO REMAIN
(DIAGONAL HATCH)
NEW POSITION
FOR SA GRILLE
NEW SMOKE BARRIER
WALL WITH DBL EGRESS
DOORS, FULL HT TO
STRUCTURE ABOVE
EXIST CEILING SPEAKER,
RELOCATE 2' WEST & 2'
SOUTH
FS = FIRE SPRINKLER
FA = FIRE ALARM
SD = SMOKE DETECTOR
REMOVE PORTION OF
EXIST ROUND HVAC DUCT
BACK TO RELOCATED
GRILLE POSITION (DASHED
LINES)
EXIST SA GRILLE,
RELOCATE TO WEST
SIDE OF CROSS
CORRIDOR DOORS
NEW POSITION
FOR SPEAKER
EXIST THRU-
WALL RA
OPENING
ABOVE CEILING
FS
FS
FA
SD
LIGHT FIXT
2x2
A6
A-100
A-100
B4
A-100
B5
A-100
B6
A-100
B3
PAIR 3'-8" x 7'-0" DBL
EGRESS HM DOORS
NON-RATED CLOSE
FITTING
REMOVE & REINSTALL
EXIST WALL GUARDS,
MODIFY FOR NEW WALL
/4
A-100
B6
SIM
CORRIDOR
S2-C004
CORRIDOR
S2-C003
CORRIDOR
S2-C002
S -C
PARALLEL ARM
CLOSER WITH
HOLD OPEN TIED
TO FIRE ALARM
24"x30"
VISION
PANEL
EXIST WALL
GUARDS, TYP EA
SIDE OF HALL
EXIST PIPES & CONDUITS
ABOVE CEILING
HVAC DUCT
FS PIPE
±9'-6"
CONC SLAB
±7'-10"
CEILING
18x40 SST
KICK PLATE
LC
10" 24" 10"
A6
A-100
PROVIDE FIRE STOPPING IN NEW
SMOKE BARRIER AT ALL
PENETRATIONS, TYP.
A-100
B1
A-100
B2
4"
EXIST CONC
WALL, VER
3 1/2" x 20
GA STUDS
5/8" GYP BD
1/2" FRT PLYWD
REINSTALL WALL
GUARDS
HM DOOR FRAME,
GROUT FILLED
/4
VER EXIST
WALL DEPTH
3 1/2" x 20
GA STUDS
5/8" GYP BD
1/2" FRT PLYWD
REINSTALL WALL
GUARDS
HM DOOR FRAME,
GROUT FILLED
4"
/4
REMOVE & SALVAGE
EXIST WALL GUARDS,
UPPER AND LOWER
REMOVE PORTION OF
EXIST MTL STUD WALL
WITH 1/2" PLYWD, 1/2"
GYP BD, & VENEER
PLASTER
A S
R E
Q U
IR
E
D
EXIST MTL STUD
WALL TO REMAIN
V E
R
±7'-2"
T.O. FRAME
/8
FIRE STOPPING
3 1/2" x 20
GA STUDS
5/8" GYP BD
J-MOLD
EXIST NON-RATED
ACOUST CLG PANEL,
REVISED FOR NEW
WALL CONSTRUCTION
HM DOOR FRAME,
GROUT FILLED
5 3/4"
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
REBID
2020-440 H (1-2)
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
WESTLAKE
BUILDING
850 MAPLE ST,
MEDICAL LAKE, WA 99022
2022-050
A-100
OVERALL
PLAN,
PARTIAL
PLANS, DOOR
ELEVATION
AND DETAILS
JTS
TMK
8/22/25
SCALE: 1/2" = 1'-0"B2
PARTIAL BASEMENT RCP
SCALE: 1/2" = 1'-0"B1
PARTIAL BASEMENT PLAN
N O
R T
H
N O
R T
H
SCALE: 1/2" = 1'-0"B3
DOOR ELEV @ CORRIDOR S2-C003
SCALE: 1/32" = 1'-0"A1
OVERALL BASEMENT FLOOR PLAN
SCALE: 3" = 1'-0"B5
N DOOR JAMB
SCALE: 3" = 1'-0"B4
S DOOR JAMB
SCALE: 3" = 1'-0"B6
EXIST WALL DEMO
N O
R T
H
SCALE: 3" = 1'-0"A6
DOOR HEAD
EASTLAKE
G201
G200
G255
G280G282 G281
G251
G272G267
G267T
G268
G269
G270
G271
G250
G254
G265
G266
G264
G261
G263
G262
F281F282
F280
F283
F241
F250
F236
F251
F242 F243
F276
F275F274
F285 F284
F260
F258
F273 F272
F272T
F271
F223
F222
F286
F270
F269
F221
F220 F259
F219
F253
F233
F254
F255
F200
F201
F203T F202
F203
F204
F204T F205T
F205
F218
F206
F217
F268 F267
F266
F216
F265
F257
F215 F264
F263
F262
F207
F208T
F207T
F208
F209
F210T
F209T
F210
F211
F212T
F211T
F212
F213
F213T
F214
F261
G260
F278 F279
F277 G253
F251 F251
VESTIBULE
SWITCHBOARD
CORRIDOR
MAIL ROOMOFFICE OFFICE
CORRIDOR
YELLOW CONFERENCE
ON-DUTY
RESIDENCE
TOILET
GPU MAILROOM
OFFICE
WOMENS TOILET
MENS TOILET
CORRIDR
CORRIDOR
STOR.
STOR.
OFFICE
OFFICE
DISASTER
SUPPLY
TOILET
TOILETTOILET
LAB. OFFICE
LAB. OFFICE
OFFICE
CORRIDOR
CHAPEL
CORRIDOR
TOILET TOILET
SPEECH / HEARING
LAB. OFFICEMALL CONFERENCE
LABORATORY LABORATORY
CORRIDOR
CORRIDOR
HOUSEKEEPING
STORAGE
DRESSING
ROOM
TOILET
X-RAY
ELEC.
LAUNDRY
LABORATORY
DARK ROOM
X-RAY OFFICE
PATIENT BATH
ISOLATION
CORRIDOR
MEDS ROOM
CORRIDOR
BEAUTY SHOP
CORRIDOR
CORRIDOR
STORAGE
PATIENT TOILET
TOILET ANTE
EQUIPMENT STORAGE
EQUIPMENT STORAGE
TOILET TOILET
EQUIPMENT STORAGE
NURSE STATION
SOLARIUM
CONFERENCE
STORAGE STORAGE
STORAGE
GALLEY
STORAGE
CORRIDOR
OFFICE DARK RM
DENTAL LAB.
DENTAL OFFICE
CORRIDOR
E WARD STORAGE
TOILET
TOILET
D WARD STORAGE
HMH STORAGE
TOILET
TOILET
EQUIPMENT STORAGE
HOUSEKEEPING
STORAGE
TOILET
TOILET
HOUSEKEEPING
STORAGE
HOUSEKEEPING
STORAGE
TOILET
JAN.
DENTAL OPERATORY
STORAGE
AUDIOLOGY OFFICE
SOUND
BOOTH
CORRIDOR
CORRIDOR CORRIDOR
102103
114115
112116
123123
127128
1-HOUR SMOKE BARRIER W/ 20 MON OPENINGS
LEGEND - WALL RATINGS
SEE UL ASSEMBLIES ON SHEET A-111 FOR
FIRESTOPPING DETAILS
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
REBID
2020-440 H (1-2)
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
WESTLAKE
BUILDING
850 MAPLE ST,
MEDICAL LAKE, WA 99022
2022-050
A-110
F WARD
SMOKE
BARRIER
PLAN, UL
DETAILS
TMK
TMK
8/22/25
PLAN NOTES
NUMBER DESCRIPTION
100 SEAL WALL TO DECK ALONG ENTIRE WALL WITH FIRESTOPPING
101 FIRE SEAL THREE CONDUIT PENETRATIONS WITH FIRESTOPPING
102 FIRE TAPE DRYWALL JOINTS
103 SEAL WALL TO BEAM THAT HAS EXISTING FIREPROOFING WITH FIRESTOPPING
104 ADD FIRESTOPPING TO 4 INCH PIPE, 1 INCH PIPE AND 1 INCH CABLE
PENETRATION
105 ADD RETAINING ANGLE TO DUCT, INFILL BETWEEN DUCT AND DECK TO
COMPLETE SMOKE BARRIER.
106 ADD RETAINING ANGLE TO DUCT, REMOVE FIRESTOPPING.
107 REPAIR DAMAGED DRYWALL AT CONDUIT PENETRATION
108 SEAL DRYWALL TO DECK, ADD FIRESTOPPING TO MULTIPLE CONDUIT
PENETRATIONS. SEAL WALL TO BEAM THAT HAS EXISTING SPRAY APPLIED
FIREPROOFING.
109 FIRE TAPE CORNER JOINT
110 FILL CABLE SLEEVES WITH FIRESTOPPING
111 SEAL THREE CONDUITS WITH FIRESTOPPING
112 FIRE TAPE DRYWALL JOINTS AND SEAL WALL TO DECK ENTIRE LENGTH OF
WALL.
113 SEAL DRYWALL AROUND ANGLE IRON
114 SEAL DRYWALL TO DECK AND COLUMN. SEAL THROUGH FLOOR PENETRATION
AT EXPANSION JOINT.
115 ADD FIRESTOPPING AT THREE PIPES AND ONE ANGLE IRON.
116 ADD RETAINING ANGLES TO TWO DUCTS
117 ADD FIRESTOPPING TO 3 PIPES, ADD RETAINING ANGLES TO ONE DUCT, SEAL
WALL TO DECK ENTIRE LENGTH OF WALL, SEAL WALL TO BEAM THAT HAS
EXISTING SPRAY APPLIED FIREPROOFING.
118 REMOVE FIRESTOPPING FROM RETAINING ANGLES, ADD RETAINING ANGLES
TO DUCT ONE SIDE, FILL VOID ABOVE DUCT TO COMPLETE WALL TO DECK.
119 FIRE TAPE DRYWALL JOINTS ALONG ENTIRE WALL, SEAL WALL TO DECK, SEAL
WALL TO BEAM THAT HAS EXISTING SPRAY APPLIED FIREPROOFING.
120 REMOVE FIRESTOPPING FROM DUCT RETAINING ANGLES, ADD RETAINING
ANGLE TO ONE SIDE OF DUCT, COMPLETE DRYWALL ABOVE DUCT TO DECK.
121 FIRE TAPE DRYWALL JOINT ALONG ENTIRE WALL, SEAL WALL TO DECK, SEAL
WALL TO BEAM THAT HAS EXISTING SPRAY APPLIED FIREPROOFING.
122 SEAL MULTIPLE CONDUIT PENETRATIONS AND ANGLE IRON PENETRATIONS
WITH FIRESTOPPING.
123 FIRE TAPE DRYWALL JOINTS ALONG ENTIRE WALL, SEAL WALL TO DECK
ALONG ENTIRE WALL, SEAL WALL TO BEAM THAT HAS EXISTING SPRAY
APPLIED FIREPROOFING.
124 REMOVE FIRESTOPPING FROM RETAINING ANGLES
125 ADD RETAINING ANGLES TO DUCT
126 ADD FIRESTOPPING TO MULTIPLE CONDUIT PENETRATIONS.
127 ADD RETAINING ANGLES TO DUCT, SECURE LOOSE DRYWALL TO SIDE AND
ABOVE DUCTWORK
128 SEAL JOINTS AND PENETRATIONS
129 PROPERLY REPAIR SMOKE BARRIER WHERE DRYWALL PATCHES EXIST
130 COMPLETE SMOKE BARRIER BETWEEN BEAM AND WALL.
131 ADD RETAINING ANGLES TO DUCTWORK
132 SEAL 20+/- PIPE AND CONDUIT PENETRATIONS WITH FIRESTOPPING
133 ALONG ENTIRE WALL SEAL WALL TO DECK AND BEAMS THAT HAVE EXISTING
SPRAY APPLIED FIREPROOFING
134 REPAIR AND FINISH DRYWALL IN CORNER TO MAINTAIN SMOKE BARRIER
135 ADD FIRESTOPPING BETWEEN TOP TRACK OF WALL AND BEAM
136 SEAL WALL TO VERTICAL BEAM WITH FIRESTOPPING
137 FIRE TAPE CORNER JOINT AND DRYWALL JOINTS, SEAL DRYWALL TO DECK
AND BEAM WITH FIRESTOPPING, ADD RETAINING ANGLES TO TWO SIDES OF
DUCT AND REPAIR ANGLE FALLING OFF THE BOTTOM, REMOVE FIRESTOPPING
FROM RETAINING ANGLES.
138 ADD RETAINING ANGLES AROUND 6 DUCT PENETRATIONS, SEAL MULTIPLE
PENETRATIONS WITH FIRESTOPPING AND SEAL WALL TO DECK AND BEAMS.
139 SEAL APPROXIMATELY 12 FEET OF WALL TO DECK, ADD RETAINING ANGLES TO
TWO DUCT PENETRATIONS, SEAL 10 +/- PENETRATIONS WITH FIRESTOPPING
140 SEAL DRYWALL TO DECK, FIRE TAPE DRYWALL JOINTS
141 ADD RETAINING ANGLES TO LARGE DUCT
142 SEAL 15 PENETRATIONS WITH FIRESTOPPING
143 SEAL WALL TO DECK WITH FIRESTOPPING BOTH SIDES
144 SEAL TOP TRACK TO DECK WITH FIRESTOPPING. REPAIR EXISTING DRYWALL
PATCHES WITH COMPLIANT SMOKE BARRIER REPAIRS.
145 SEAL WALL TO DECK AND BEAM ALONG ENTIRE WALL. WALL IS OFFSET FROM
BEAM APPROX. 8".
146 ADD DRYWALL WHERE NOT CONTINUOUS BEHIND BEAM BRACING
147 FIRE TAPE DRYWALL JOINTS, ADD FIRESTOPPING TO APPROX 5
PENETRATIONS.
SCALE: 1/8" = 1'-0"1
F WARD PARTIAL MAIN LEVEL PLAN
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
REBID
2020-440 H (1-2)
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
WESTLAKE
BUILDING
850 MAPLE ST,
MEDICAL LAKE, WA 99022
2022-050
A-111
UL
ASSEMBLIES
TMK
TMK
8/22/25
GENERAL
MECHANICAL
NOTES, LEGENDS,
AND SHEET
INDEX
M-001
JTT
SDK
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
EASTLAKE
BUILDING
850 MAPLE ST
MEDICAL LAKE, WA 99022
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
2020-440 H (1-2)
192591
8/22/25
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
www.coffman.com ph 509.328.2994
221 N. Wall Street, Suite 500 Spokane, WA 99201ABBR
STANDARD ABBREVIATIONS
DESCRIPTION ABBR DESCRIPTION
A/E ARCHITECT/ENGINEER
AAV AUTOMATIC AIR VENT
ACH AIR CHANGES PER HOUR
AD ACCESS DOOR
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARCH ARCHITECT/ARCHITECTURAL
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
BAS BUILDING AUTOMATION SYSTEM
BD BACKDRAFT DAMPER
BFP BACK FLOW PREVENTER
BG BELOW GROUND
BHP BRAKE HORSEPOWER
BLDG BUILDING
BOD BOTTOM OF DUCT
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CC COOLING COIL
CFM CUBIC FEET PER MINUTE
CI CAST IRON
CLG CEILING
CMU CONCRETE MASONRY UNIT
CO CLEANOUT
CONC CONCRETE
COND CONDENSER
CONN CONNECT/CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION
COP COEFFICIENT OF PERFORMANCE
CW COLD WATER
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
DB DECIBEL or DRY BULB
DDC DIRECT DIGITAL CONTROL
DEMO DEMOLISH
DIA/Ø DIAMETER
DIM DIMENSION
DN DOWN
DWG DRAWING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC ELECTRICAL CONTRACTOR
EDB ENTERING DRY BULB
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
EG EXHAUST GRILLE
ELEC ELECTRIC/ELECTRIAL
ELEV ELEVATION
EMCS ENERGY MANAGEMENT CONTROL
SYSTEM
ENCL ENCLOSURE
EQUIP EQUIPMENT
ESP EXTERNAL STATIC PRESSURE
EWB ENTERING WET BULB
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
F FAHRENHEIT
FCO FLOOR CLEANOUT
FD FLOOR DRAIN or FIRE DAMPER
FDC FIRE DEPARTMENT CONNECTION
FF FINAL FILTER
FLA FULL LOAD AMPS
FLR FLOOR
FP FIRE PROTECTION
FPM FEET PER MINUTE
FPI FINS PER INCH
FPS FEET PER SECOND
FS FLOOR SINK
FSD FIRE-SMOKE DAMPER
FT FEET or FLASH TANK
FV FACE VELOCITY
GA GAGE or GAUGE
GAL GALLONS
GALV GALVANIZED STEEL
GC GENERAL CONTRACTOR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HB HOSE BIBB
HC HEATING COIL
HEPA HIGH EFFICIENCY PARTICULATE AIR
HG HOT GAS
HP HORSEPOWER
HR HOUR
HTG HEATING
HVAC HEATING, VENTILATION, AND AIR
CONDITIONING
HW HOT WATER
HWC HOT WATER CIRCULATION
HX HEAT EXCHANGER
HZ HERTZ
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
IE INVERT ELEVATION
IEEC INTERNATIONAL ENERGY
EFFICIENCY CODE
IFC INTERNATIONAL FIRE CODE
IMC INTERNATIONAL MECHANICAL CODE
IN INCHES
INSUL INSULATION
KW KILOWATT
KWH KILOWATT HOUR
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LDB LEAVING DRY BULB
LWB LEAVING WET BULB
LWT LEAVING WATER TEMPERATURE
MAV MANUAL AIR VENT
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
MCA MINIMUM CIRCUIT AMPS
MC MECHANICAL CONTRACTOR
MCC MOTOR CONTROL CENTER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM or MINUTES
MISC MISCELLANEOUS
MOCP MAXIMUM OVER CURRENT
PROTECTION
NA NOT APPLICABLE
NC NORMALLY CLOSED or NOISE
CRITERIA
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NPT NATIONAL PIPE THREAD
NTS NOT TO SCALE
OBD OPPOSED BLADE DAMPER
OC ON CENTER
OD OUTSIDE DIAMETER
ORD OVERFLOW ROOF DRAINAGE
OA or OSA OUTSIDE (SUPPLY) AIR
PD PRESSURE DROP
PG PROPYLENE GLYCOL
PH/Ø PHASE
PLBG PLUMBING
POC POINT OF CONNECTION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAGE
PT PRESSURE TEMPERATURE
RA RETURN AIR
REQD REQUIRED
REV REVISION(S)
RO REVERSE OSMOSIS
RPBP REDUCED PRESSURE BACKFLOW
PREVENTER
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SD SMOKE DETECTOR or SMOKE
DAMPER
SEER SEASONAL ENERGY EFFICIENCY
RATIO
SENS SENSIBLE
SF SUPPLY FAN or SQUARE FEET
SIM SIMILAR
SM SHEET METAL
SMACNA SHEET METAL AND AIR
CONDITIONING CONTRACTORS
NATIONAL ASSOCIATION
SP STATIC PRESSURE
SPEC SPECIFICATION or SPECIFIED
SQ SQUARE
SQ FT SQUARE FEET
SS STAINLESS STEEL
STD STANDARD
TAB TEST, ADJUSTMENT & BALANCE
TC TEMPERATURE CONTROLS
TEMP TEMPERATURE
TP TRAP PRIMER or TEST PLUG
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
UPC UNIFORM PLUMBING CODE
V VENTS OR VOLTS
VAC VACUUM or VOLTAGE ALTERNATING
CURRENT
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THRU ROOF
WB WET BULB
WC WATER CLOSET
WCO WALL CLEANOUT
WH WATER HEATER
WHA WATER HAMMER ARRESTOR
W/ WITH
W/O WITHOUT
ZVB ZONE VALVE BOX
SD
H
T
AHU-1
P1-1
GENERAL LEGEND
SYMBOL DESCRIPTION
THIN LINEWORK INDICATES EXISTING
MEDIUM LINEWORK INDICATES NEW
THERMOSTAT OR TEMPERATURE SENSOR (WALL MOUNTED)
HUMIDISTAT OR HUMIDITY SENSOR (WALL MOUNTED)
DETAIL SYMBOL: A = IDENTIFYING NUMBER
B = SHEET WHERE DETAIL IS SHOWN
SECTION SYMBOL: A = IDENTIFYING LETTER
B = SHEET WHERE SECTION IS SHOWN
SECTION CUT LINE INDICATOR
THICK DASHED LINEWORK INDICATES
EXISTING TO BE DEMOLISHED
KEYED REFERENCE NOTE SPECIFIC TO LOCATION INDICATED
POINT OF CONNECTION (POC)
PLUMBING FIXTURE TAG (REFER TO SCHEDULE)
MECHANICAL EQUIPMENT TAG (REFER TO SCHEDULES)
REVISION CLOUD AND REVISION NUMBER
SMOKE DETECTOR
GENERAL NOTE APPLIES TO ENTIRE SHEETX.
EXISTING(E)
NEW(N)
RELOCATE(REL)
NEW LOCATION(NL)
CO2 CO2 SENSOR
GENERAL NOTES
2021 WA STATE ENERGY CODE NOTES
1. DOCUMENTS DESCRIBED IN SECTION C103.6, INCLUDING RECORD DOCUMENTS, MANUALS,
COMPLIANCE DOCUMENTATION, AND SYSTEM OPERATION TRAINING, SHALL BE PROVIDED TO THE
BUILDING OWNER OR OWNER'S AUTHORIZED AGENT WITHIN 90 DAYS OF THE DATE OF RECEIPT
OF THE CERTIFICATE OF OCCUPANCY.
2. HVAC SYSTEMS SHALL BE BALANCED AS REQUIRED BY SECTION C408.2.2.
3. PROVIDE BALANCING DEVICES IN ALL BRANCH DUCTS AS REQUIRED BY SECTION C408.2.2.1.
4. COMMISSIONING (MECHANICAL SYSTEMS) SHALL BE PROVIDED AND A REPORT SHALL BE
SUBMITTED TO THE OWNER AS REQUIRED BY SECTION C408. PROVIDE A COMMISSIONING PLAN
PER C408.1.2.
5. MECHANICAL EQUIPMENT AND CONTROLS SHALL BE COMMISSIONED PER SECTION C408.2.
SYSTEM TESTING SHALL BE PERFORMED IN ACCORDANCE WITH SECTION C408.2.3.
CODES & AUTHORITIES HAVING JURISDICTION (AHJ)
THIS LIST IS FOR REFERENCE ONLY AND MAY NOT CONTAIN ALL CODES REQUIRED FOR THIS PROJECT OR LIST ALL AUTHORITIES HAVING JURISDICTION. CONTACT STATE, COUNTY AND CITY BUILDING
DEPARTMENT FOR A FULL AND ACCURATE LIST.
· 2021 INTERNATIONAL BUILDING CODE
· 2021 UNIFORM PLUMBING CODE
· 2020 NATIONAL ELECTRIC CODE
· 2021 WASHINGTON STATE ENERGY CODE
· 2021 INTERNATIONAL MECHANICAL CODE
· CODE AMENDMENTS SPECIFIC TO THE LOCAL & REGIONAL JURISDICTIONS
· STATE, COUNTY, CITY CODE AGENCIES & OFFICIALS
· 2014 FACILITY GUIDELINES INSTITUTE
HVAC DUCTWORK LEGEND
DUCTWORK
24x12 S/A
RECTANGULAR DUCT
SIZE (INCHES) FIRST
DIMENSION IS SIDE OF
DUCT SHOWN
DUCT SIZE
DUCT SYSTEM ABBREVIATION
(NOT ALWAYS BE SHOWN)
INSULATED DUCT
SOUND LINED DUCT
24x12ø
24ø ROUND DUCT
18ø24x12 CHANGE IN DUCT SIZE
AND/OR SHAPE
SUPPLY AIR (SA)
OUTSIDE AIR (OSA)
RECTANGULAR DUCT
TURNED UP/SECTION
ROUND/FLAT OVAL DUCT
TURNED UP/SECTION
RECTANGULAR DUCT
TURNED DOWN/AWAY
ROUND/FLAT OVAL DUCT
TURNED DOWN/AWAY
RETURN AIR (RA)
RECTANGULAR DUCT
TURNED UP/SECTION
ROUND/FLAT OVAL DUCT
TURNED UP/SECTION
RECTANGULAR DUCT
TURNED DOWN/AWAY
ROUND/FLAT OVAL DUCT
TURNED DOWN/AWAY
EXHAUST AIR (EA)
RECTANGULAR DUCT
TURNED UP/SECTION
ROUND/FLAT OVAL DUCT
TURNED UP/SECTION
RECTANGULAR DUCT
TURNED DOWN/AWAY
ROUND/FLAT OVAL DUCT
TURNED DOWN/AWAY
DAMPERS
VOLUME/BALANCING
DAMPER
FIRE DAMPER (FD)
SMOKE DAMPER (SD)
FIRE/SMOKE DAMPER
(FSD)
MOTORIZED FIRE/SMOKE
DAMPER
DUCT SYSTEM ABBREVIATIONS
SUPPLY AIRSA
OUTSIDE AIROSA
COMBUSTION AIRCA
RETURN AIRRA
TRANSFER AIRTA
EXHAUST AIREA
FLEXIBLE DUCT
DUCT SYMBOLS
DUCT END CAP
DUCT ACCESS DOOR
AD
SUPPLY AIR (SA)
TERMINAL
RETURN AIR (RA) OR
TRANSFER AIR (TA) TERMINAL
EXHAUST AIR (EA) TERMINAL
X
CFM
AIRFLOW DIRECTION
SOUND ATTENUATOR
DUCT SIZES SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS OF DUCT. DUCT SIZE
SHOWN DOES NOT INCLUDE INSULATION OR LINING UNLESS NOTED OTHERWISE. SEE
BELOW FOR DUCT SIZE TAG LEGEND.
GRILLE, REGISTER, OR OPEN
DUCT
AIR TERMINAL
IDENTIFICATION
FLAT OVAL DUCT SIZE
(INCHES) FIRST
DIMENSION IS SIDE OF
DUCT SHOWN
M S
S
S
AOM ALARM OUTPUT
CONTROL MODULE
FIRE ALARM SCOPE DESCRIPTION
THE PURPOSE OF THIS PROJECT IS TO ADDRESS EXISTING CONDITIONS WITHIN THE EAST
LAKE BUILDING AT EASTERN STATE HOSPITAL. THE BUILDING CURRENTLY FEATURES A
SHARED PLENUM RETURN BETWEEN THE CORRIDOR AND PATIENT ROOMS / HAZARDOUS
AREAS, WHICH IS PROHIBITED IN EXISTING HEALTHCARE OCCUPANCIES PER NFPA 101
SECTION 19.3.6.2.1.
PER COFFMAN'S FIRE PROTECTION AND LIFE SAFETY ASSESSMENT REPORT, THE EXISTING
SMOKE CONTROL SYSTEM DOES NOT PROVIDE EXHAUST FROM THE FIRE FLOOR NOR
PRESSURIZATION TO THE ADJACENT AREAS AND DOES NOT MEET THE DEFINITION OF AN
NFPA 92 SMOKE CONTROL SYSTEM; THEREFORE, COFFMAN RECOMMENDS
DECOMMISSIONING THE EXISTING SMOKE CONTROL SYSTEM, ELEVATOR PRESSURIZATION
SYSTEM, AND ADDING SMOKE DAMPERS AT THE FOLLOWING LOCATIONS. TO CORRIDOR
PLENUM RETURN LOCATIONS, THE RETURN FROM AREAS THAT ARE CONSIDERED
HAZARDOUS IN ACCORDANCE WITH NFPA 101 SEC. 19.3.2.1, AND EXISTING SHAFTS WITH
UNPROTECTED OPENINGS.
FIRE ALARM GENERAL NOTES
5-15-258-22-25
11,385 SF
SMOKE COMPARTMENT
6,990 SF
SMOKE
COMPARTMENT
"1N2" SEGMENT
1N1 - CORE
"1N3" SEGMENT
"1N3/N3" CORE
AHU-5
AHU-2
1P3-16
1P3-15
1N3-10
1N3-10
M S
S M
M S
M S
M S
M S
S
S
S
S
SS S S
SS
SS
SS
S
S
S
S
SS
S
S
DH
DH
DH
DH
THIS IS NOT AN EXIT STAIR
FACP GAMEWELL
FACP GAMEWELL
EL LEVEL 1
NORTH DEMO
MD-101
JTT
SDK
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
EASTLAKE
BUILDING
850 MAPLE ST
MEDICAL LAKE, WA 99022
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
2020-440 H (1-2)
192591
8/22/25
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
www.coffman.com ph 509.328.2994
221 N. Wall Street, Suite 500 Spokane, WA 99201
1 EL LEVEL 1 NORTH DEMO
SCALE: 3/32"=1'-0"
N
EASTERN STATE HOSPITAL
FIRST FLOOR KEY PLAN
1S1 1A
1S2
1N1 1N2
1N3
1SE
KEY NOTES
1. REMOVE FIRE ALARM OUTPUT CONTROL MODULES FOR ZONE A, B, AND C.
THEN REMOVE THE SMOKE CONTROL SEQUENCE FROM THE DDC
CONTROLS FOR AHU 5, 6, AND 7.
2. WIRE DAMPER OPEN, REMOVE MOTORIZED ACTUATOR, DEMO
ELECTRICAL BACK TO SOURCE, AND DEMO PURPLE CONTROL WIRES
BACK TO DDC CONTROLS LOCATED INSIDE THE AHU MECHANICAL ROOM.
LABEL DAMPER AS "ABANDONED - NOT IN USE"
GENERAL DEMO NOTES
A. NOT USED.
2-HOUR OCCUPANCY SEPARATION OR
3-HOUR FIRE WALL, 3-HR OPENINGS
LEGEND - WALL RATINGS
SHAFT ENCLOSURE, 90-MIN OPENINGS
1-HOUR FIRE BARRIER:
NON-RATED SMOKE PARTITION PROVIDED TO HAZARDOUS
= NEW HEALTHCARE AT HAZARDOUS LOCATIONS
HAZARDOUS LOCATIONS (SEE KEY NOTES 6 & 7)
SMOKE BARRIER AT SMOKE COMPARTMENTS:
= 1-HR AT NEW HEALTHCARE WITH 20-MIN OPENINGS
NOTE: THIS ONLY OCCURS BETWEEN BLDGS
= EXISTING HEALTHCARE FOR VARIOUS HAZARDS
= 30-MIN AT EXISTING HEALTHCARE W/ SELF-CLOSING DOORS
(ELEVATOR MACHINE ROOM, ELECTRICAL ROOMS,
2-HOUR FIRE/SMOKE BARRIER AT INTERFACE OF SHAFT
ENCLOSURE AND SMOKE COMPARTMENT
NON-PATIENT-CARE SUITE
AREAS IN EXISTING HEALTHCARE
GARAGE, AND LAUNDRY COLLECTION)
PATIENT-CARE SUITE
(E) 1P3-11
(E) 1P3-14
(E) 1P3-20
6,990 SF
SMOKE COMPARTMENT
SMOKE
COMPARTMENT
"2N2" SEGMENT
"2N3" SEGMENT
2N1 CORE
"2N3/N3" CORE
202 T-STATS
AH-3
AHU-6
2N3-XX 1a?
2P3-23
2P3-16
2P3-17
M S
S M
M S
M S
M S
M S
SS S
S
S
S SS
S
S
S
THIS IS NOT AN EXIT STAIR
DH
DH
DH
DH
DH
DH
FACP GAMEWELL
FACP GAMEWELL
EL LEVEL 2
NORTH DEMO
MD-102
JTT
SDK
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
EASTLAKE
BUILDING
850 MAPLE ST
MEDICAL LAKE, WA 99022
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
2020-440 H (1-2)
192591
8/22/25
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
www.coffman.com ph 509.328.2994
221 N. Wall Street, Suite 500 Spokane, WA 99201
1 EL LEVEL 2 NORTH DEMO
SCALE: 3/32"=1'-0"
N
EASTERN STATE HOSPITAL
SECOND FLOOR KEY PLAN
2S1 2A
2S2
2N1 2N2
2N3
2-HOUR OCCUPANCY SEPARATION OR
3-HOUR FIRE WALL, 3-HR OPENINGS
LEGEND - WALL RATINGS
SHAFT ENCLOSURE, 90-MIN OPENINGS
1-HOUR FIRE BARRIER:
NON-RATED SMOKE PARTITION PROVIDED TO HAZARDOUS
= NEW HEALTHCARE AT HAZARDOUS LOCATIONS
HAZARDOUS LOCATIONS (SEE KEY NOTES 6 & 7)
SMOKE BARRIER AT SMOKE COMPARTMENTS:
= 1-HR AT NEW HEALTHCARE WITH 20-MIN OPENINGS
NOTE: THIS ONLY OCCURS BETWEEN BLDGS
= EXISTING HEALTHCARE FOR VARIOUS HAZARDS
= 30-MIN AT EXISTING HEALTHCARE W/ SELF-CLOSING DOORS
(ELEVATOR MACHINE ROOM, ELECTRICAL ROOMS,
2-HOUR FIRE/SMOKE BARRIER AT INTERFACE OF SHAFT
ENCLOSURE AND SMOKE COMPARTMENT
NON-PATIENT-CARE SUITE
AREAS IN EXISTING HEALTHCARE
GARAGE, AND LAUNDRY COLLECTION)
PATIENT-CARE SUITE
KEY NOTES
1. REMOVE FIRE ALARM OUTPUT CONTROL MODULES FOR ZONE A, B, AND C.
THEN REMOVE THE SMOKE CONTROL SEQUENCE FROM THE DDC
CONTROLS FOR AHU 5, 6, AND 7.
2. WIRE DAMPER OPEN, REMOVE MOTORIZED ACTUATOR, DEMO
ELECTRICAL BACK TO SOURCE, AND DEMO PURPLE CONTROL WIRES
BACK TO DDC CONTROLS LOCATED INSIDE THE AHU MECHANICAL ROOM.
LABEL DAMPER AS "ABANDONED - NOT IN USE"
GENERAL DEMO NOTES
A. NOT USED.
(E) 2P3-3
(E) 2P3-15
(E) 2P3-21
6,990 SF
SMOKE
COMPARTMENT
"3N2" SEGMENT
3N1 CORE
"3N3" SEGMENT
"3N3/N3" CORE
AH-7
3P3-16
3P3-17
M S
S M
M S
M S
M S
M S
S
SS
S
S
S S
S
S
S
S
SS
S
S
THIS IS NOT AN EXIT STAIR
DH
DH
DH
DH
S
FACP GAMEWELL
FACP GAMEWELL
EL LEVEL 3
NORTH DEMO
MD-103
JTT
SDK
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
EASTLAKE
BUILDING
850 MAPLE ST
MEDICAL LAKE, WA 99022
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
2020-440 H (1-2)
192591
8/22/25
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
www.coffman.com ph 509.328.2994
221 N. Wall Street, Suite 500 Spokane, WA 99201
1 EL LEVEL 3 NORTH DEMO
SCALE: 3/32"=1'-0"
2-HOUR OCCUPANCY SEPARATION OR
3-HOUR FIRE WALL, 3-HR OPENINGS
LEGEND - WALL RATINGS
SHAFT ENCLOSURE, 90-MIN OPENINGS
1-HOUR FIRE BARRIER:
NON-RATED SMOKE PARTITION PROVIDED TO HAZARDOUS
= NEW HEALTHCARE AT HAZARDOUS LOCATIONS
HAZARDOUS LOCATIONS (SEE KEY NOTES 6 & 7)
SMOKE BARRIER AT SMOKE COMPARTMENTS:
= 1-HR AT NEW HEALTHCARE WITH 20-MIN OPENINGS
NOTE: THIS ONLY OCCURS BETWEEN BLDGS
= EXISTING HEALTHCARE FOR VARIOUS HAZARDS
= 30-MIN AT EXISTING HEALTHCARE W/ SELF-CLOSING DOORS
(ELEVATOR MACHINE ROOM, ELECTRICAL ROOMS,
2-HOUR FIRE/SMOKE BARRIER AT INTERFACE OF SHAFT
ENCLOSURE AND SMOKE COMPARTMENT
NON-PATIENT-CARE SUITE
AREAS IN EXISTING HEALTHCARE
GARAGE, AND LAUNDRY COLLECTION)
N
EASTERN STATE HOSPITAL
THIRD FLOOR KEY PLAN
3S
3N1 3N23AS3S1 3AN3A
3S
PATIENT-CARE SUITE
KEY NOTES
1. REMOVE FIRE ALARM OUTPUT CONTROL MODULES FOR ZONE A, B, AND C.
THEN REMOVE THE SMOKE CONTROL SEQUENCE FROM THE DDC
CONTROLS FOR AHU 5, 6, AND 7.
2. WIRE DAMPER OPEN, REMOVE MOTORIZED ACTUATOR, DEMO
ELECTRICAL BACK TO SOURCE, AND DEMO PURPLE CONTROL WIRES
BACK TO DDC CONTROLS LOCATED INSIDE THE AHU MECHANICAL ROOM.
LABEL DAMPER AS "ABANDONED - NOT IN USE"
GENERAL DEMO NOTES
A. NOT USED.
(E) 3P3-5
(E) 3P3-15
(E) 3P3-21
13551 SF
7797 SF
SMOKE COMPARTMENT
SMOKE COMPARTMENT
"0S1" SEGMENT
"0S2" SEGMENT
FSU ADMISSIONS
AH-10
S
SSS
FACP SIMPLEX
EL BASEMENT
SOUTH DEMO
MD-104
MRN
TAH
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
EASTLAKE
BUILDING
850 MAPLE ST
MEDICAL LAKE, WA 99022
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
2020-440 H (1-2)
192591
8/22/25
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
www.coffman.com ph 509.328.2994
221 N. Wall Street, Suite 500 Spokane, WA 99201
1 EL BASEMENT SOUTH DEMO
SCALE: 3/32"=1'-0"
N BASEMENT KEY PLAN
EASTERN STATE HOSPITAL
0S1 0SA
0S2
0N1 0N2
0N3
0SE
KEY NOTES
1. NOT USED.
GENERAL DEMO NOTES
A. NOT USED.
2-HOUR OCCUPANCY SEPARATION OR
3-HOUR FIRE WALL, 3-HR OPENINGS
LEGEND - WALL RATINGS
SHAFT ENCLOSURE, 90-MIN OPENINGS
1-HOUR FIRE BARRIER:
NON-RATED SMOKE PARTITION PROVIDED TO HAZARDOUS
= NEW HEALTHCARE AT HAZARDOUS LOCATIONS
HAZARDOUS LOCATIONS (SEE KEY NOTES 6 & 7)
SMOKE BARRIER AT SMOKE COMPARTMENTS:
= 1-HR AT NEW HEALTHCARE WITH 20-MIN OPENINGS
NOTE: THIS ONLY OCCURS BETWEEN BLDGS
= EXISTING HEALTHCARE FOR VARIOUS HAZARDS
= 30-MIN AT EXISTING HEALTHCARE W/ SELF-CLOSING DOORS
(ELEVATOR MACHINE ROOM, ELECTRICAL ROOMS,
2-HOUR FIRE/SMOKE BARRIER AT INTERFACE OF SHAFT
ENCLOSURE AND SMOKE COMPARTMENT
NON-PATIENT-CARE SUITE
AREAS IN EXISTING HEALTHCARE
GARAGE, AND LAUNDRY COLLECTION)
PATIENT-CARE SUITE
(E) FAN
UP TO ROOF COWL
EL PENTHOUSE
MD-105
JTT
SDK
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
EASTLAKE
BUILDING
850 MAPLE ST
MEDICAL LAKE, WA 99022
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
2020-440 H (1-2)
192591
8/22/25
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
www.coffman.com ph 509.328.2994
221 N. Wall Street, Suite 500 Spokane, WA 99201
1 EL PENTHOUSE
SCALE: 1/2"=1'-0"
GENERAL NOTES
KEY NOTES
1. DEMO EXISTING SMOKE PRESSURIZATION FAN, CONTROLS, AND
ELECTRICAL BACK TO SOURCE.
2. DEMO DUCTWORK TO ROOF AND CAP WATER TIGHT.
3. DEMO FIRE ALARM OUTPUT CONTROL MODULES AND REMOVE ELEVATOR
PRESSURIZATION SEQUENCE FROM FIRE ALARM SYSTEM PROGRAMMING.
1. DEMO THE FIRE FIGHTERS OVERRIDE PANEL (USED FOR MANUAL
ELEVATOR PRESSURIZATION) THAT IS LOCATED IN THE SWITCHBOARD
ROOM AT THE HOSPITAL MAIN ENTRANCE. PATCH AND PAINT WALLS AND
CEILINGS TO MATCH EXISTING.
13551 SF
7797 SF
SMOKE COMPARTMENT
SMOKE COMPARTMENT
"0S1" SEGMENT
"0S2" SEGMENT
FSU ADMISSIONS
AH-10
S
SSS
FACP SIMPLEX
LOCATION OF NEW
CORRIDOR DOOR
S
S
S
S
SS
S
S
S
S
S
S
AOM
AOM
AOM
AOM
AOM
AOM
AOM
AOM
AOM
AOM
AOM AOM
18x10
18x10
18x10
18x10
40x14
18x10
32x10
16x10
18x10
18x10
36x16 18x10
1 EL BASEMENT SOUTH - ALTERNATE BID 1
SCALE: 3/32"=1'-0"
EL BASEMENT
SOUTH -
ALTERNATE BID 1
M-201
JTT
SDK
N BASEMENT KEY PLAN
EASTERN STATE HOSPITAL
0S1 0SA
0S2
0N1 0N2
0N3
0SE
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
EASTLAKE
BUILDING
850 MAPLE ST
MEDICAL LAKE, WA 99022
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
2020-440 H (1-2)
192591
8/22/25
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
www.coffman.com ph 509.328.2994
221 N. Wall Street, Suite 500 Spokane, WA 99201
2-HOUR OCCUPANCY SEPARATION OR
3-HOUR FIRE WALL, 3-HR OPENINGS
LEGEND - WALL RATINGS
SHAFT ENCLOSURE, 90-MIN OPENINGS
1-HOUR FIRE BARRIER:
NON-RATED SMOKE PARTITION PROVIDED TO HAZARDOUS
= NEW HEALTHCARE AT HAZARDOUS LOCATIONS
HAZARDOUS LOCATIONS (SEE KEY NOTES 6 & 7)
SMOKE BARRIER AT SMOKE COMPARTMENTS:
= 1-HR AT NEW HEALTHCARE WITH 20-MIN OPENINGS
NOTE: THIS ONLY OCCURS BETWEEN BLDGS
= EXISTING HEALTHCARE FOR VARIOUS HAZARDS
= 30-MIN AT EXISTING HEALTHCARE W/ SELF-CLOSING DOORS
(ELEVATOR MACHINE ROOM, ELECTRICAL ROOMS,
2-HOUR FIRE/SMOKE BARRIER AT INTERFACE OF SHAFT
ENCLOSURE AND SMOKE COMPARTMENT
NON-PATIENT-CARE SUITE
AREAS IN EXISTING HEALTHCARE
GARAGE, AND LAUNDRY COLLECTION)
GENERAL NOTES
A. PROVIDE AND INSTALL A NEW FIRE ALARM OUTPUT CONTROL MODULE
WITHIN 3 FEET OF EACH NEW SMOKE DAMPER.
B. SHUT DOWN HVAC UNITS IN ACCORDANCE WITH THE INTERNATIONAL
MECHANICAL CODE AND FIRE ALARM MATRIX.
C. SMOKE DAMPERS MUST BE PROGRAMMED TO CLOSE ON ANY ALARM
AND IN ACCORDANCE WITH THE FIRE ALARM MATRIX.
D. PROVIDE ALL NECESSARY DUCT TRANSITIONS, FLANGES, AND GASKETS
TO INSTALL AND SEAL NEW DAMPERS IN EXISTING DUCTWORK.
E. CEILING TILES ARE SECURED WITH SECURITY CLIPS AND MUST BE
REMOVED AND REPLACED WHEN ACCESS IS NEEDED. CONTRACTOR
SHALL REPLACE ANY DAMAGED TILES AND CLIPS. ALL TILES MUST BE
SECURED IN PATIENT SPACES AT THE END OF EACH SHIFT BEFORE
PATIENTS ARE ALLOWED BACK IN THE SPACE.
F. AN ESCORT PROVIDED BY EASTERN STATE HOSPITAL IS REQUIRED AT
ALL TIMES.
G. ALL WORK SHALL BE CLEANED AND SECURED AT THE END OF THE SHIFT
SO THAT A PATIENT CAN SAFELY RETURN TO THEIR ROOM.
H. SEAL ALL PENETRATIONS IN EXISTING FIRE PARTITIONS AT THE TIME
THAT THE PENETRATION IS IDENTIFIED/CREATED. HILTI PRODUCTS ONLY.
CONTRACTOR SHALL COMPLY WITH ALL FACILITY REQUIREMENTS FOR
DOCUMENTING AND COMPLETING FIRE STOPPING. ALL NEW WORK
PENETRATIONS AND THOSE RELATED TO DEMOLISHING OF EXISTING
DUCTS/DAMPERS SHALL BE SEALED. ANY EXISTING PENETRATIONS
FOUND DURING THE PROJECT THAT ARE NOT FIRE SEALED SHALL BE
ADDED TO A LOG INDICATING THE LOCATION AND TYPE OF PENETRATION
NEEDING ADDRESSED. THE LOG SHOULD BE TURNED OVER TO THE
ENGINEER OF RECORD AT THE END OF EACH WEEK.
I. PROVIDE AND INSTALL 24" X 24" FIRE RATED ACCESS PANELS THAT LOCK
IN ALL LOCATIONS WHERE NEEDED FOR ACCESS TO NEW SMOKE
DAMPERS.
J. FIELD VERIFY ALL (E) DUCT SIZES PRIOR TO ORDERING DAMPERS.
KEY NOTES
1. PROVIDE AND INSTALL MINIMUM 3 FEET OF 26 GAUGE NON FLEXIBLE
DUCT FROM THE RETURN AIR CEILING GRILLE TO ACCOMMODATE A NEW
SMOKE DAMPER. PROVIDE AND INSTALL A NEW DUCT DETECTOR AND
FIRE ALARM OUTPUT CONTROL MODULE WITHIN 3 FEET OF THE NEW
SMOKE DAMPER.
2. PROVIDE AND INSTALL A NEW SMOKE DAMPER, DUCT DETECTOR, AND
FIRE ALARM OUTPUT CONTROL MODULE WITHIN 3 FEET OF THE NEW
SMOKE DAMPER.
OP3-53
OP3-54
OP3-55
OP3-57
OP3-58
OP3-59
OP3-61
OP3-62
OP3-63
OP3-64
OP3-65
OP3-66
PATIENT-CARE SUITE
5462 SF
SMOKE COMPARTMENT"0A" SEGMENT
"0N1" SEGMENT
SS
S
S
DH
DH
DH
S
S
S
S
AOM
AOM
AOM
AOM
AOM
S
18x10
18x10 16x10 21x10
48x4
26x12
1 EL BASEMENT MIDDLE - ALTERNATE BID 1
SCALE: 3/32"=1'-0"
EL BASEMENT
MIDDLE -
ALTERNATE BID 1
M-202
JTT
SDK
N BASEMENT KEY PLAN
EASTERN STATE HOSPITAL
0S1 0SA
0S2
0N1 0N2
0N3
0SE
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
EASTLAKE
BUILDING
850 MAPLE ST
MEDICAL LAKE, WA 99022
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
2020-440 H (1-2)
192591
8/22/25
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
www.coffman.com ph 509.328.2994
221 N. Wall Street, Suite 500 Spokane, WA 99201
2-HOUR OCCUPANCY SEPARATION OR
3-HOUR FIRE WALL, 3-HR OPENINGS
LEGEND - WALL RATINGS
SHAFT ENCLOSURE, 90-MIN OPENINGS
1-HOUR FIRE BARRIER:
NON-RATED SMOKE PARTITION PROVIDED TO HAZARDOUS
= NEW HEALTHCARE AT HAZARDOUS LOCATIONS
HAZARDOUS LOCATIONS (SEE KEY NOTES 6 & 7)
SMOKE BARRIER AT SMOKE COMPARTMENTS:
= 1-HR AT NEW HEALTHCARE WITH 20-MIN OPENINGS
NOTE: THIS ONLY OCCURS BETWEEN BLDGS
= EXISTING HEALTHCARE FOR VARIOUS HAZARDS
= 30-MIN AT EXISTING HEALTHCARE W/ SELF-CLOSING DOORS
(ELEVATOR MACHINE ROOM, ELECTRICAL ROOMS,
2-HOUR FIRE/SMOKE BARRIER AT INTERFACE OF SHAFT
ENCLOSURE AND SMOKE COMPARTMENT
NON-PATIENT-CARE SUITE
AREAS IN EXISTING HEALTHCARE
GARAGE, AND LAUNDRY COLLECTION)
2OP3-20
OP3-19
OP3-18
OP3-51
OP3-52
PATIENT-CARE SUITE
GENERAL NOTES
A. PROVIDE AND INSTALL A NEW FIRE ALARM OUTPUT CONTROL MODULE
WITHIN 3 FEET OF EACH NEW SMOKE DAMPER.
B. SHUT DOWN HVAC UNITS IN ACCORDANCE WITH THE INTERNATIONAL
MECHANICAL CODE AND FIRE ALARM MATRIX.
C. SMOKE DAMPERS MUST BE PROGRAMMED TO CLOSE ON ANY ALARM
AND IN ACCORDANCE WITH THE FIRE ALARM MATRIX.
D. PROVIDE ALL NECESSARY DUCT TRANSITIONS, FLANGES, AND GASKETS
TO INSTALL AND SEAL NEW DAMPERS IN EXISTING DUCTWORK.
E. CEILING TILES ARE SECURED WITH SECURITY CLIPS AND MUST BE
REMOVED AND REPLACED WHEN ACCESS IS NEEDED. CONTRACTOR
SHALL REPLACE ANY DAMAGED TILES AND CLIPS. ALL TILES MUST BE
SECURED IN PATIENT SPACES AT THE END OF EACH SHIFT BEFORE
PATIENTS ARE ALLOWED BACK IN THE SPACE.
F. AN ESCORT PROVIDED BY EASTERN STATE HOSPITAL IS REQUIRED AT
ALL TIMES.
G. ALL WORK SHALL BE CLEANED AND SECURED AT THE END OF THE SHIFT
SO THAT A PATIENT CAN SAFELY RETURN TO THEIR ROOM.
H. SEAL ALL PENETRATIONS IN EXISTING FIRE PARTITIONS AT THE TIME
THAT THE PENETRATION IS IDENTIFIED/CREATED. HILTI PRODUCTS ONLY.
CONTRACTOR SHALL COMPLY WITH ALL FACILITY REQUIREMENTS FOR
DOCUMENTING AND COMPLETING FIRE STOPPING. ALL NEW WORK
PENETRATIONS AND THOSE RELATED TO DEMOLISHING OF EXISTING
DUCTS/DAMPERS SHALL BE SEALED. ANY EXISTING PENETRATIONS
FOUND DURING THE PROJECT THAT ARE NOT FIRE SEALED SHALL BE
ADDED TO A LOG INDICATING THE LOCATION AND TYPE OF PENETRATION
NEEDING ADDRESSED. THE LOG SHOULD BE TURNED OVER TO THE
ENGINEER OF RECORD AT THE END OF EACH WEEK.
I. PROVIDE AND INSTALL 24" X 24" FIRE RATED ACCESS PANELS THAT LOCK
IN ALL LOCATIONS WHERE NEEDED FOR ACCESS TO NEW SMOKE
DAMPERS.
J. FIELD VERIFY ALL (E) DUCT SIZES PRIOR TO ORDERING DAMPERS.
KEY NOTES
1. PROVIDE AND INSTALL MINIMUM 3 FEET OF 26 GAUGE NON FLEXIBLE
DUCT FROM THE RETURN AIR CEILING GRILLE TO ACCOMMODATE A NEW
SMOKE DAMPER. PROVIDE AND INSTALL A NEW DUCT DETECTOR AND
FIRE ALARM OUTPUT CONTROL MODULE WITHIN 3 FEET OF THE NEW
SMOKE DAMPER.
2. REPLACE EXISTING FIRE DAMPER WITH A NEW SMOKE DAMPER. PROVIDE
AND INSTALL A NEW DUCT DETECTOR AND FIRE ALARM OUTPUT
CONTROL MODULE WITHIN 3 FEET OF THE NEW SMOKE DAMPER.
16983 SF
7690 SF
SMOKE COMPARTMENT
SMOKE
COMPARTMENT
"0N2" SEGMENT
"0N3" SEGMENT
APU ADMISSIONS
AHU-1
AH-4
ELEVATOR
CONTROL
RELAY'S
SS
SSS
S
S
S
DH
DH
THIS IS NOT AN EXIT STAIR
FACP GAMEWELL
FACP GAMEWELL
S
S
S
S
S
S
S
S
S
S
AOM
AOM
AOM AOM
AOM
AOM
AOM
AOM
AOM
AOM
S
AOM
24x5
50x10
12x10
1 EL BASEMENT NORTH - ALTERNATE BID 1
SCALE: 3/32"=1'-0"
EL BASEMENT
NORTH -
ALTERNATE BID 1
M-203
JTT
SDK
N BASEMENT KEY PLAN
EASTERN STATE HOSPITAL
0S1 0SA
0S2
0N1 0N2
0N3
0SE
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
EASTLAKE
BUILDING
850 MAPLE ST
MEDICAL LAKE, WA 99022
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
2020-440 H (1-2)
192591
8/22/25
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
www.coffman.com ph 509.328.2994
221 N. Wall Street, Suite 500 Spokane, WA 99201
2-HOUR OCCUPANCY SEPARATION OR
3-HOUR FIRE WALL, 3-HR OPENINGS
LEGEND - WALL RATINGS
SHAFT ENCLOSURE, 90-MIN OPENINGS
1-HOUR FIRE BARRIER:
NON-RATED SMOKE PARTITION PROVIDED TO HAZARDOUS
= NEW HEALTHCARE AT HAZARDOUS LOCATIONS
HAZARDOUS LOCATIONS (SEE KEY NOTES 6 & 7)
SMOKE BARRIER AT SMOKE COMPARTMENTS:
= 1-HR AT NEW HEALTHCARE WITH 20-MIN OPENINGS
NOTE: THIS ONLY OCCURS BETWEEN BLDGS
= EXISTING HEALTHCARE FOR VARIOUS HAZARDS
= 30-MIN AT EXISTING HEALTHCARE W/ SELF-CLOSING DOORS
(ELEVATOR MACHINE ROOM, ELECTRICAL ROOMS,
2-HOUR FIRE/SMOKE BARRIER AT INTERFACE OF SHAFT
ENCLOSURE AND SMOKE COMPARTMENT
NON-PATIENT-CARE SUITE
AREAS IN EXISTING HEALTHCARE
GARAGE, AND LAUNDRY COLLECTION)
2 ON-8
ON-1D
ON-17A
OP3-2OP3-3
OP3-45
OP3-46
OP3-47
OP3-48
OP3-49
OP3-50
PATIENT-CARE SUITE
GENERAL NOTES
A. PROVIDE AND INSTALL A NEW FIRE ALARM OUTPUT CONTROL MODULE
WITHIN 3 FEET OF EACH NEW SMOKE DAMPER.
B. SHUT DOWN HVAC UNITS IN ACCORDANCE WITH THE INTERNATIONAL
MECHANICAL CODE AND FIRE ALARM MATRIX.
C. SMOKE DAMPERS MUST BE PROGRAMMED TO CLOSE ON ANY ALARM
AND IN ACCORDANCE WITH THE FIRE ALARM MATRIX.
D. PROVIDE ALL NECESSARY DUCT TRANSITIONS, FLANGES, AND GASKETS
TO INSTALL AND SEAL NEW DAMPERS IN EXISTING DUCTWORK.
E. CEILING TILES ARE SECURED WITH SECURITY CLIPS AND MUST BE
REMOVED AND REPLACED WHEN ACCESS IS NEEDED. CONTRACTOR
SHALL REPLACE ANY DAMAGED TILES AND CLIPS. ALL TILES MUST BE
SECURED IN PATIENT SPACES AT THE END OF EACH SHIFT BEFORE
PATIENTS ARE ALLOWED BACK IN THE SPACE.
F. AN ESCORT PROVIDED BY EASTERN STATE HOSPITAL IS REQUIRED AT
ALL TIMES.
G. ALL WORK SHALL BE CLEANED AND SECURED AT THE END OF THE SHIFT
SO THAT A PATIENT CAN SAFELY RETURN TO THEIR ROOM.
H. SEAL ALL PENETRATIONS IN EXISTING FIRE PARTITIONS AT THE TIME
THAT THE PENETRATION IS IDENTIFIED/CREATED. HILTI PRODUCTS ONLY.
CONTRACTOR SHALL COMPLY WITH ALL FACILITY REQUIREMENTS FOR
DOCUMENTING AND COMPLETING FIRE STOPPING. ALL NEW WORK
PENETRATIONS AND THOSE RELATED TO DEMOLISHING OF EXISTING
DUCTS/DAMPERS SHALL BE SEALED. ANY EXISTING PENETRATIONS
FOUND DURING THE PROJECT THAT ARE NOT FIRE SEALED SHALL BE
ADDED TO A LOG INDICATING THE LOCATION AND TYPE OF PENETRATION
NEEDING ADDRESSED. THE LOG SHOULD BE TURNED OVER TO THE
ENGINEER OF RECORD AT THE END OF EACH WEEK.
I. PROVIDE AND INSTALL 24" X 24" FIRE RATED ACCESS PANELS THAT LOCK
IN ALL LOCATIONS WHERE NEEDED FOR ACCESS TO NEW SMOKE
DAMPERS.
J. FIELD VERIFY ALL (E) DUCT SIZES PRIOR TO ORDERING DAMPERS.
KEY NOTES
1. PROVIDE AND INSTALL MINIMUM 3 FEET OF 26 GAUGE NON FLEXIBLE
DUCT FROM THE RETURN AIR CEILING GRILLE TO ACCOMMODATE A NEW
SMOKE DAMPER. PROVIDE AND INSTALL A NEW DUCT DETECTOR AND
FIRE ALARM OUTPUT CONTROL MODULE WITHIN 3 FEET OF THE NEW
SMOKE DAMPER.
2. REPLACE EXISTING FIRE DAMPER WITH A NEW SMOKE DAMPER. PROVIDE
AND INSTALL A NEW DUCT DETECTOR AND FIRE ALARM OUTPUT
CONTROL MODULE WITHIN 3 FEET OF THE NEW SMOKE DAMPER.
9,170 SF
7,085 SF
SMOKE COMPARTMENT
SMOKE COMPARTMENT
"1S2" SEGMENT
"1S1" SEGMENT
AHU-15
AHU-11
S
S
S
S
S
S
S S
S
S
S
S
S
S
S
DH
S
S
DH
FACP SIMPLEX
S
S
SS
S
AOM
AOM
AOM AOM
AOM
18x10
18x1018x10 18x10
18x10
1 EL LEVEL 1 SOUTH
SCALE: 3/32"=1'-0"
EL LEVEL 1
SOUTH
M-204
JTT
SDK
N
EASTERN STATE HOSPITAL
FIRST FLOOR KEY PLAN
1S1 1A
1S2
1N1 1N2
1N3
1SE
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
EASTLAKE
BUILDING
850 MAPLE ST
MEDICAL LAKE, WA 99022
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
2020-440 H (1-2)
192591
8/22/25
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
www.coffman.com ph 509.328.2994
221 N. Wall Street, Suite 500 Spokane, WA 99201
2-HOUR OCCUPANCY SEPARATION OR
3-HOUR FIRE WALL, 3-HR OPENINGS
LEGEND - WALL RATINGS
SHAFT ENCLOSURE, 90-MIN OPENINGS
1-HOUR FIRE BARRIER:
NON-RATED SMOKE PARTITION PROVIDED TO HAZARDOUS
= NEW HEALTHCARE AT HAZARDOUS LOCATIONS
HAZARDOUS LOCATIONS (SEE KEY NOTES 6 & 7)
SMOKE BARRIER AT SMOKE COMPARTMENTS:
= 1-HR AT NEW HEALTHCARE WITH 20-MIN OPENINGS
NOTE: THIS ONLY OCCURS BETWEEN BLDGS
= EXISTING HEALTHCARE FOR VARIOUS HAZARDS
= 30-MIN AT EXISTING HEALTHCARE W/ SELF-CLOSING DOORS
(ELEVATOR MACHINE ROOM, ELECTRICAL ROOMS,
2-HOUR FIRE/SMOKE BARRIER AT INTERFACE OF SHAFT
ENCLOSURE AND SMOKE COMPARTMENT
NON-PATIENT-CARE SUITE
AREAS IN EXISTING HEALTHCARE
GARAGE, AND LAUNDRY COLLECTION)
1 1 1
1P3-39
1P3-401P3-411P3-42
1P3-43
PATIENT-CARE SUITE
GENERAL NOTES
A. PROVIDE AND INSTALL A NEW FIRE ALARM OUTPUT CONTROL MODULE
WITHIN 3 FEET OF EACH NEW SMOKE DAMPER.
B. SHUT DOWN HVAC UNITS IN ACCORDANCE WITH THE INTERNATIONAL
MECHANICAL CODE AND FIRE ALARM MATRIX.
C. SMOKE DAMPERS MUST BE PROGRAMMED TO CLOSE ON ANY ALARM
AND IN ACCORDANCE WITH THE FIRE ALARM MATRIX.
D. PROVIDE ALL NECESSARY DUCT TRANSITIONS, FLANGES, AND GASKETS
TO INSTALL AND SEAL NEW DAMPERS IN EXISTING DUCTWORK.
E. CEILING TILES ARE SECURED WITH SECURITY CLIPS AND MUST BE
REMOVED AND REPLACED WHEN ACCESS IS NEEDED. CONTRACTOR
SHALL REPLACE ANY DAMAGED TILES AND CLIPS. ALL TILES MUST BE
SECURED IN PATIENT SPACES AT THE END OF EACH SHIFT BEFORE
PATIENTS ARE ALLOWED BACK IN THE SPACE.
F. AN ESCORT PROVIDED BY EASTERN STATE HOSPITAL IS REQUIRED AT
ALL TIMES.
G. ALL WORK SHALL BE CLEANED AND SECURED AT THE END OF THE SHIFT
SO THAT A PATIENT CAN SAFELY RETURN TO THEIR ROOM.
H. SEAL ALL PENETRATIONS IN EXISTING FIRE PARTITIONS AT THE TIME
THAT THE PENETRATION IS IDENTIFIED/CREATED. HILTI PRODUCTS ONLY.
CONTRACTOR SHALL COMPLY WITH ALL FACILITY REQUIREMENTS FOR
DOCUMENTING AND COMPLETING FIRE STOPPING. ALL NEW WORK
PENETRATIONS AND THOSE RELATED TO DEMOLISHING OF EXISTING
DUCTS/DAMPERS SHALL BE SEALED. ANY EXISTING PENETRATIONS
FOUND DURING THE PROJECT THAT ARE NOT FIRE SEALED SHALL BE
ADDED TO A LOG INDICATING THE LOCATION AND TYPE OF PENETRATION
NEEDING ADDRESSED. THE LOG SHOULD BE TURNED OVER TO THE
ENGINEER OF RECORD AT THE END OF EACH WEEK.
I. PROVIDE AND INSTALL 24" X 24" FIRE RATED ACCESS PANELS THAT LOCK
IN ALL LOCATIONS WHERE NEEDED FOR ACCESS TO NEW SMOKE
DAMPERS.
J. FIELD VERIFY ALL (E) DUCT SIZES PRIOR TO ORDERING DAMPERS.
KEY NOTES
1. PROVIDE AND INSTALL MINIMUM 3 FEET OF 26 GAUGE NON FLEXIBLE
DUCT FROM THE RETURN AIR CEILING GRILLE TO ACCOMMODATE A NEW
SMOKE DAMPER. PROVIDE AND INSTALL A NEW DUCT DETECTOR AND
FIRE ALARM OUTPUT CONTROL MODULE WITHIN 3 FEET OF THE NEW
SMOKE DAMPER.
6,045 SF
"1A" SEGMENT
"1N1" SEGMENT
S
S
S
S
S
S
S
S
AOM
AOM
AOM
30x8
12x6 16Ø
1 EL LEVEL 1 MIDDLE
SCALE: 3/32"=1'-0"
EL LEVEL 1
MIDDLE
M-205
JTT
SDK
N
EASTERN STATE HOSPITAL
FIRST FLOOR KEY PLAN
1S1 1A
1S2
1N1 1N2
1N3
1SE
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
EASTLAKE
BUILDING
850 MAPLE ST
MEDICAL LAKE, WA 99022
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
2020-440 H (1-2)
192591
8/22/25
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
www.coffman.com ph 509.328.2994
221 N. Wall Street, Suite 500 Spokane, WA 99201
2-HOUR OCCUPANCY SEPARATION OR
3-HOUR FIRE WALL, 3-HR OPENINGS
LEGEND - WALL RATINGS
SHAFT ENCLOSURE, 90-MIN OPENINGS
1-HOUR FIRE BARRIER:
NON-RATED SMOKE PARTITION PROVIDED TO HAZARDOUS
= NEW HEALTHCARE AT HAZARDOUS LOCATIONS
HAZARDOUS LOCATIONS (SEE KEY NOTES 6 & 7)
SMOKE BARRIER AT SMOKE COMPARTMENTS:
= 1-HR AT NEW HEALTHCARE WITH 20-MIN OPENINGS
NOTE: THIS ONLY OCCURS BETWEEN BLDGS
= EXISTING HEALTHCARE FOR VARIOUS HAZARDS
= 30-MIN AT EXISTING HEALTHCARE W/ SELF-CLOSING DOORS
(ELEVATOR MACHINE ROOM, ELECTRICAL ROOMS,
2-HOUR FIRE/SMOKE BARRIER AT INTERFACE OF SHAFT
ENCLOSURE AND SMOKE COMPARTMENT
NON-PATIENT-CARE SUITE
AREAS IN EXISTING HEALTHCARE
GARAGE, AND LAUNDRY COLLECTION)
KEY NOTES
1. PROVIDE AND INSTALL MINIMUM 3 FEET OF 26 GAUGE NON FLEXIBLE
DUCT FROM THE RETURN AIR CEILING GRILLE TO ACCOMMODATE A NEW
SMOKE DAMPER. PROVIDE AND INSTALL A NEW DUCT DETECTOR AND
FIRE ALARM OUTPUT CONTROL MODULE WITHIN 3 FEET OF THE NEW
SMOKE DAMPER.
2. REPLACE EXISTING FIRE DAMPER WITH A NEW SMOKE DAMPER. PROVIDE
AND INSTALL A NEW DUCT DETECTOR AND FIRE ALARM OUTPUT
CONTROL MODULE WITHIN 3 FEET OF THE NEW SMOKE DAMPER.
3. PROVIDE AND INSTALL MINIMUM 3 FEET OF 26 GAUGE NON FLEXIBLE
DUCT FROM THE DIFFUSER TO ACCOMMODATE A NEW COMBINATION
FIRE/SMOKE DAMPER. PROVIDE AND INSTALL A NEW DUCT DETECTOR
AND FIRE ALARM OUTPUT CONTROL MODULE WITHIN 3 FEET OF THE NEW
FIRE/SMOKE DAMPER.
(E) 1P3-01c 1P3-01C
1P3-37
1P3-38
PATIENT-CARE SUITE
GENERAL NOTES
A. PROVIDE AND INSTALL A NEW FIRE ALARM OUTPUT CONTROL MODULE
WITHIN 3 FEET OF EACH NEW SMOKE DAMPER.
B. SHUT DOWN HVAC UNITS IN ACCORDANCE WITH THE INTERNATIONAL
MECHANICAL CODE AND FIRE ALARM MATRIX.
C. SMOKE DAMPERS MUST BE PROGRAMMED TO CLOSE ON ANY ALARM
AND IN ACCORDANCE WITH THE FIRE ALARM MATRIX.
D. PROVIDE ALL NECESSARY DUCT TRANSITIONS, FLANGES, AND GASKETS
TO INSTALL AND SEAL NEW DAMPERS IN EXISTING DUCTWORK.
E. CEILING TILES ARE SECURED WITH SECURITY CLIPS AND MUST BE
REMOVED AND REPLACED WHEN ACCESS IS NEEDED. CONTRACTOR
SHALL REPLACE ANY DAMAGED TILES AND CLIPS. ALL TILES MUST BE
SECURED IN PATIENT SPACES AT THE END OF EACH SHIFT BEFORE
PATIENTS ARE ALLOWED BACK IN THE SPACE.
F. AN ESCORT PROVIDED BY EASTERN STATE HOSPITAL IS REQUIRED AT
ALL TIMES.
G. ALL WORK SHALL BE CLEANED AND SECURED AT THE END OF THE SHIFT
SO THAT A PATIENT CAN SAFELY RETURN TO THEIR ROOM.
H. SEAL ALL PENETRATIONS IN EXISTING FIRE PARTITIONS AT THE TIME
THAT THE PENETRATION IS IDENTIFIED/CREATED. HILTI PRODUCTS ONLY.
CONTRACTOR SHALL COMPLY WITH ALL FACILITY REQUIREMENTS FOR
DOCUMENTING AND COMPLETING FIRE STOPPING. ALL NEW WORK
PENETRATIONS AND THOSE RELATED TO DEMOLISHING OF EXISTING
DUCTS/DAMPERS SHALL BE SEALED. ANY EXISTING PENETRATIONS
FOUND DURING THE PROJECT THAT ARE NOT FIRE SEALED SHALL BE
ADDED TO A LOG INDICATING THE LOCATION AND TYPE OF PENETRATION
NEEDING ADDRESSED. THE LOG SHOULD BE TURNED OVER TO THE
ENGINEER OF RECORD AT THE END OF EACH WEEK.
I. PROVIDE AND INSTALL 24" X 24" FIRE RATED ACCESS PANELS THAT LOCK
IN ALL LOCATIONS WHERE NEEDED FOR ACCESS TO NEW SMOKE
DAMPERS.
J. FIELD VERIFY ALL (E) DUCT SIZES PRIOR TO ORDERING DAMPERS.
6,990 SF
SMOKE
COMPARTMENT
"1N2" SEGMENT
1N1 - CORE
"1N3" SEGMENT
"1N3/N3" CORE
AHU-5
AHU-2
M S
S M
M S
M S
M S
M S
S
S
S
S
SS S S
SS
SS
SS
S
S
S
S
SS
S
S
DH
DH
DH
DH
THIS IS NOT AN EXIT STAIR
FACP GAMEWELL
FACP GAMEWELL
S
S
S
AOM
AOM
AOM
S
S
S
S
S
AOM
AOM
AOM
AOM
AOM
AOM
AOM
DH
DH
DH
S
AOM
AOM
AOM
22x10
38x14
5Ø
10x8
10x8
18x10
1 EL LEVEL 1 NORTH
SCALE: 3/32"=1'-0"
EL LEVEL 1
NORTH
M-206
JTT
SDK
N
EASTERN STATE HOSPITAL
FIRST FLOOR KEY PLAN
1S1 1A
1S2
1N1 1N2
1N3
1SE
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
EASTLAKE
BUILDING
850 MAPLE ST
MEDICAL LAKE, WA 99022
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
2020-440 H (1-2)
192591
8/22/25
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
www.coffman.com ph 509.328.2994
221 N. Wall Street, Suite 500 Spokane, WA 99201
2-HOUR OCCUPANCY SEPARATION OR
3-HOUR FIRE WALL, 3-HR OPENINGS
LEGEND - WALL RATINGS
SHAFT ENCLOSURE, 90-MIN OPENINGS
1-HOUR FIRE BARRIER:
NON-RATED SMOKE PARTITION PROVIDED TO HAZARDOUS
= NEW HEALTHCARE AT HAZARDOUS LOCATIONS
HAZARDOUS LOCATIONS (SEE KEY NOTES 6 & 7)
SMOKE BARRIER AT SMOKE COMPARTMENTS:
= 1-HR AT NEW HEALTHCARE WITH 20-MIN OPENINGS
NOTE: THIS ONLY OCCURS BETWEEN BLDGS
= EXISTING HEALTHCARE FOR VARIOUS HAZARDS
= 30-MIN AT EXISTING HEALTHCARE W/ SELF-CLOSING DOORS
(ELEVATOR MACHINE ROOM, ELECTRICAL ROOMS,
2-HOUR FIRE/SMOKE BARRIER AT INTERFACE OF SHAFT
ENCLOSURE AND SMOKE COMPARTMENT
NON-PATIENT-CARE SUITE
AREAS IN EXISTING HEALTHCARE
GARAGE, AND LAUNDRY COLLECTION)
KEY NOTES
1. PROVIDE AND INSTALL MINIMUM 3 FEET OF 26 GAUGE NON FLEXIBLE
DUCT FROM THE RETURN AIR CEILING GRILLE TO ACCOMMODATE A NEW
SMOKE DAMPER. PROVIDE AND INSTALL A NEW DUCT DETECTOR AND
FIRE ALARM OUTPUT CONTROL MODULE WITHIN 3 FEET OF THE NEW
SMOKE DAMPER.
2. REPLACE EXISTING FIRE DAMPER WITH A NEW SMOKE DAMPER. PROVIDE
AND INSTALL A NEW DUCT DETECTOR AND FIRE ALARM OUTPUT
CONTROL MODULE WITHIN 3 FEET OF THE NEW SMOKE DAMPER.
3. PROVIDE AND INSTALL A NEW DOOR HOLDER AND FIRE ALARM OUTPUT
CONTROL MODULE. REINSTALL THE AUTOMATIC DOOR CLOSER.
4. PROVIDE AND INSTALL A NEW FIRE ALARM OUTPUT CONTROL MODULE
WITHIN 3 FEET OF THE EXISTING FIRE/SMOKE DAMPER.
5. REPLACE EXISTING FIRE DAMPER WITH A NEW SMOKE DAMPER. PROVIDE
AND INSTALL MINIMUM 3 FEET OF 26 GAUGE NON FLEXIBLE DUCT FROM
THE RETURN AIR CEILING GRILLE TO ACCOMMODATE A NEW SMOKE
DAMPER. PROVIDE AND INSTALL A NEW DUCT DETECTOR AND FIRE
ALARM OUTPUT CONTROL MODULE WITHIN 3 FEET OF THE NEW SMOKE
DAMPER.
1N1-1A
1P3-16
1P3-21
1P3-15
1P3-11
1P3-01I 1P3-34
1P3-35
1P3-36
PATIENT-CARE SUITE
(E) 1P3-19
(E) 1P3-18
(E) 1P3-17
GENERAL NOTES
A. PROVIDE AND INSTALL A NEW FIRE ALARM OUTPUT CONTROL MODULE
WITHIN 3 FEET OF EACH NEW SMOKE DAMPER.
B. SHUT DOWN HVAC UNITS IN ACCORDANCE WITH THE INTERNATIONAL
MECHANICAL CODE AND FIRE ALARM MATRIX.
C. SMOKE DAMPERS MUST BE PROGRAMMED TO CLOSE ON ANY ALARM
AND IN ACCORDANCE WITH THE FIRE ALARM MATRIX.
D. PROVIDE ALL NECESSARY DUCT TRANSITIONS, FLANGES, AND GASKETS
TO INSTALL AND SEAL NEW DAMPERS IN EXISTING DUCTWORK.
E. CEILING TILES ARE SECURED WITH SECURITY CLIPS AND MUST BE
REMOVED AND REPLACED WHEN ACCESS IS NEEDED. CONTRACTOR
SHALL REPLACE ANY DAMAGED TILES AND CLIPS. ALL TILES MUST BE
SECURED IN PATIENT SPACES AT THE END OF EACH SHIFT BEFORE
PATIENTS ARE ALLOWED BACK IN THE SPACE.
F. AN ESCORT PROVIDED BY EASTERN STATE HOSPITAL IS REQUIRED AT
ALL TIMES.
G. ALL WORK SHALL BE CLEANED AND SECURED AT THE END OF THE SHIFT
SO THAT A PATIENT CAN SAFELY RETURN TO THEIR ROOM.
H. SEAL ALL PENETRATIONS IN EXISTING FIRE PARTITIONS AT THE TIME
THAT THE PENETRATION IS IDENTIFIED/CREATED. HILTI PRODUCTS ONLY.
CONTRACTOR SHALL COMPLY WITH ALL FACILITY REQUIREMENTS FOR
DOCUMENTING AND COMPLETING FIRE STOPPING. ALL NEW WORK
PENETRATIONS AND THOSE RELATED TO DEMOLISHING OF EXISTING
DUCTS/DAMPERS SHALL BE SEALED. ANY EXISTING PENETRATIONS
FOUND DURING THE PROJECT THAT ARE NOT FIRE SEALED SHALL BE
ADDED TO A LOG INDICATING THE LOCATION AND TYPE OF PENETRATION
NEEDING ADDRESSED. THE LOG SHOULD BE TURNED OVER TO THE
ENGINEER OF RECORD AT THE END OF EACH WEEK.
I. PROVIDE AND INSTALL 24" X 24" FIRE RATED ACCESS PANELS THAT LOCK
IN ALL LOCATIONS WHERE NEEDED FOR ACCESS TO NEW SMOKE
DAMPERS.
J. FIELD VERIFY ALL (E) DUCT SIZES PRIOR TO ORDERING DAMPERS.
9,170 SF
SMOKE COMPARTMENT
SMOKE COMPARTMENT
"2S2" SEGMENT
"2S1" SEGMENT
AHU-16
AHU-12
S
S
S
S
S
S
DH
DH
S
S S
S
S
S
S
S
S
S
S
S
S
FACP SIMPLEX
S
SS
S
S
S
AOM
AOM
AOM
AOM AOM
AOM
18x10
18x1018x10
18x10
18x10
1 EL LEVEL 2 SOUTH
SCALE: 3/32"=1'-0"
EL LEVEL 2
SOUTH
M-207
JTT
SDK
N
EASTERN STATE HOSPITAL
SECOND FLOOR KEY PLAN
2S1 2A
2S2
2N1 2N2
2N3
REV DATE DESCRIPTION
PROJ. NO.
DRAWN
CHECKED
DATE
COFFMAN ENGINEERS INC.C
EASTERN STATE
HOSPITAL
EASTLAKE
BUILDING
850 MAPLE ST
MEDICAL LAKE, WA 99022
ESH - EL & WL: FIRE
AND SMOKE CONTROL
RETRO-COMMISSION
2020-440 H (1-2)
192591
8/22/25
SHEET TITLE:
SHEET NO:
A
B
C
D
A
B
C
D
E
E
2 3 4 5 6
2 3 4 5 6
BID DOCUMENTS
www.coffman.com ph 509.328.2994
221 N. Wall Street, Suite 500 Spokane, WA 99201
2-HOUR OCCUPANCY SEPARATION OR
3-HOUR FIRE WALL, 3-HR OPENINGS
LEGEND - WALL RATINGS
SHAFT ENCLOSURE, 90-MIN OPENINGS
1-HOUR FIRE BARRIER:
NON-RATED SMOKE PARTITION PROVIDED TO HAZARDOUS
= NEW HEALTHCARE AT HAZARDOUS LOCATIONS
HAZARDOUS LOCATIONS (SEE KEY NOTES 6 & 7)
SMOKE BARRIER AT SMOKE COMPARTMENTS:
= 1-HR AT NEW HEALTHCARE WITH 20-MIN OPENINGS
NOTE: THIS ONLY OCCURS BETWEEN BLDGS
= EXISTING HEALTHCARE FOR VARIOUS HAZARDS
= 30-MIN AT EXISTING HEALTHCARE W/ SELF-CLOSING DOORS
(ELEVATOR MACHINE ROOM, ELECTRICAL ROOMS,
2-HOUR FIRE/SMOKE BARRIER AT INTERFACE OF SHAFT
ENCLOSURE AND SMOKE COMPARTMENT
NON-PATIENT-CARE SUITE
AREAS IN EXISTING HEALTHCARE
GARAGE, AND LAUNDRY COLLECTION)
1 1
2P3-46
2P3-47
2P3-48 2P3-492P3-50
2P3-51
PATIENT-CARE SUITE
GENERAL NOTES
A. PROVIDE AND INSTALL A NEW FIRE ALARM OUTPUT CONTROL MODULE
WITHIN 3 FEET OF EACH NEW SMOKE DAMPER.
B. SHUT DOWN HVAC UNITS IN ACCORDANCE WITH THE INTERNATIONAL
MECHANICAL CODE AND FIRE ALARM MATRIX.
C. SMOKE DAMPERS MUST BE PROGRAMMED TO CLOSE ON ANY ALARM
AND IN ACCORDANCE WITH THE FIRE ALARM MATRIX.
D. PROVIDE ALL NECESSARY DUCT TRANSITIONS, FLANGES, AND GASKETS
TO INSTALL AND SEAL NEW DAMPERS IN EXISTING DUCTWORK.
E. CEILING TILES ARE SECURED WITH SECURITY CLIPS AND MUST BE
REMOVED AND REPLACED WHEN ACCESS IS NEEDED. CONTRACTOR
SHALL REPLACE ANY DAMAGED TILES AND CLIPS. ALL TILES MUST BE
SECURED IN PATIENT SPACES AT THE END OF EACH SHIFT BEFORE
PATIENTS ARE ALLOWED BACK IN THE SPACE.
F. AN ESCORT PROVIDED BY…