3-Drawings - John Marshall HS Coffee Shop.pdf
PDF 13 MB Posted
- Attached to
- John Marshall High School Coffee Shop
- Solicitation number
- Bid #052126
- Issued by
- Olmsted County, Minnesota
About this file
John Marshall High School Coffee Shop - Construction Document Summary
This is a comprehensive construction document set prepared by CRW Architecture + Design Group for Rochester Public Schools (ISD #535) regarding the renovation of an existing cafeteria room at John Marshall High School (1510 14th Street NW, Rochester, Minnesota 55901) to create a new coffee shop. The project involves mechanical scope including removal of an existing hood and unused vent, relocation of existing finned tube radiation, and modifications to water, waste, and vent piping systems. The electrical scope encompasses demolition of existing wall devices, installation of new devices to support food service equipment, removal and reinstallation of ceiling fixtures, and installation of a new electrical panel dedicated to the coffee shop. The construction documents were issued in three phases: Design Development (DD) Issue dated April 7, 2026; 90% Construction Documents (CD) dated April 21, 2026; and 100% CD dated April 30, 2026. The documents include architectural floor plans, reflected ceiling plans, demolition plans, mechanical plans, plumbing plans, fire protection plans, electrical plans, and comprehensive food service equipment plans with detailed specifications.
The project involves multiple design and engineering disciplines coordinated by CRW Architecture + Design Group (contact: Emma Sunnarborg, 507-206-6201), with mechanical design by Short Elliot Hendrickson Inc. (contact: Ben Wolf, 507-288-6464) and Dunham Engineering (contacts: Mike Szuberski, 507-424-6868; Blythe Waldemar, 507-424-6852), and food service design by Boelter (contact: Dennis Hahn, 612-851-2309). The project requires compliance with the 2020 Minnesota State Building Code, 2020 Minnesota Accessibility Code, 2020 Minnesota Conservation Code for Existing Buildings, 2020 Minnesota Fire Code, and 2024 Minnesota Commercial Energy Code. Construction scope includes extensive demolition, new construction of temporary and permanent walls, installation of ceramic floor tile, rubber sheet flooring, fiber reinforced panels, stainless steel guards and transitions, and complete food service equipment rough-ins. Permits required include demolition, sidewalk, driveway approach, electrical utility, gas utility, cable television, telephone, sewer and water connection, site grading, zoning and building review, and signage permits, with responsibility assigned to the contractor or owner as noted in the permit schedule.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N O
R T
H
14TH ST NW
T H
A V
E N
W
T H
A V
E N
W
7TH ST NW
SITE
OWNER
ELECTRICAL DESIGN
MECHANICAL DESIGN
ARCHITECT
STRUCTURAL ENGINEER
ROCHESTER PUBLIC SCHOOLS
CONSTRUCTION SERVICES DEPARTMENT
3935 HIGHWAY 14 EAST
ROCHESTER, MINNESOTA 55904
CONTACT: BILL BURT
PHONE NUMBER: (507) 328-4505
EMAIL: wiburt@rochesterschools.org
CRW ARCHITECTURE + DESIGN GROUP
211 11TH AVENUE NORTHWEST
ROCHESTER, MINNESOTA 55901
CONTACT: EMMA SUNNARBORG
PHONE NUMBER: (507) 206-6201
EMAIL: esunnarborg@crwarchitecture.com
SHORT ELLIOT HENDRICKSON INC.
3428 LAKERIDGE PLACE NW, #1OO
ROCHESTER, MINNESOTA 55901
CONTACT: BEN WOLF, PE.
PHONE NUMBER: (507) 288-6464
EMAIL: bwolf@sehinc.com
DUNHAM ENGINEERING
421 FIRST AVENUE SW - SUITE 201W
ROCHESTER, MINNESOTA 55902
CONTACT: MIKE SZUBERSKI
PHONE NUMBER: (507) 424-6868
EMAIL: mike.szuberski@dunhameng.com
DUNHAM ENGINEERING
421 FIRST AVENUE SW - SUITE 201W
ROCHESTER, MINNESOTA 55902
CONTACT: BLYTHE WALDEMAR
PHONE NUMBER: (507) 424-6852
EMAIL: blythe.waldemar@dunhameng.com
FOOD SERVICE DESIGN
BOELTER
7120 NORTHLAND TERRACE N
MINNEAPOLIS, MN 55428
CONTACT: DENNIS HAHN
PHONE NUMBER: (612) 851-2309
EMAIL: dhahn@boelter.com
PROJECT SITE
JOHN MARSHALL HIGH SCHOOL
1510 14TH ST NW
ROCHESTER, MINNESOTA 55901
NO
W
O
RK IN
S
HADED A
REA
NO WORK IN SHADED AREA
CONSTRUCTION
ACCESS
AREA OF WORK
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
CONSTRUCTION DOCUMENT SET
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.46.21 www.crwarchitecture.com
CLIENT
1 DD Issue 4/7/2026
2 90% CD Issue 4/21/2026
3 100% CD Issue 4/30/2026
A u to d e s k D o c s
/R P
S J o h n
M a rs h a ll
H S
C o ff e e S h o p /2
-0
J o h n M a rs h a ll H
S C o ff e e
S h o p
.r v t
/3
/2
:2 :0
P
M
G0.00
Jason Woodhouse
44421 4/30/2026
COVER SHEET
R O
C H
E S
T E
R
M
IN
N E
S O
T A
IS
D
JO
H N
M A
R S
H A
LL
H
IG
H
S C
H O
O L
C O
F F
E E
S H
O P
26-015
4/30/2026
LG
JW
ISD #535 JOHN MARSHALL HIGH
SCHOOL COFFEE SHOP
ROCHESTER, MINNESOTA
PLANS ISSUED:4/30/2026
G0.00 COVER SHEET
G0.01 GENERAL INFORMATION SHEET
G0.02 CODE SUMMARY
AD1.01 DEMO PLANS
A1.00 FLOOR AND RCP PLAN
A2.00 ENLARGED FLOOR PLAN
A2.01 DETAILS
M0.00 MECHANICAL SYMBOLS AND ABBREVIATIONS
M1.01 MAIN LEVEL MECHANICAL PLANS
ME1.00 MECHANICAL AND ELECTRICAL SCHEDULES
F1.01 FIRE PROTECTION PLAN
P1.00 UNDERFLOOR PLUMBING PLANS
P1.01 MAIN LEVEL PLUMBING PLANS
P2.00 PLUMBING RISERS AND DETAILS
E0.00 ELECTRICAL SYMBOLS AND ABBREVIATIONS
E1.00 ELECTRICAL PLANS
E2.00 ELECTRICAL RISER DIAGRAM
ED1.00 ELECTRICAL DEMOLITION PLANS
FS001 COVER SHEET
FS100 FOODSERVICE EQUIPMENT PLAN & SCHEDULE
FS400 FOODSERVICE DETAILS
FS401 FOODSERVICE DETAILS
FS500 FOODSERVICE ROUGH-IN PLAN & SCHEDULE
SHEET INDEXSITE LOCATION MAP
BUILDING LEGEND
PLAN NORTH
N O
R T
H
NORTH
NOT TO SCALE
TRUE NORTH
NO. REVISIONS DATE
SCHEDULE OF REQUIRED PERMITS
DESCRIPTION OF PERMIT TYPE
PERMIT ARRANGED FOR AND
PAID FOR BY:
= NOT APPLICABLE= BY OWNER= BY CONTRACTOR
12. SIGNAGE PERMIT
11. FOOTING & FOUNDATION PERMIT
(IF PHASED PERMIT REQUESTED)
10. ZONING & BUILDING REVIEW & PERMIT
9. SITE GRADING PERMIT
8. SEWER & WATER CONNECTION PERMIT
7. TELEPHONE PERMIT
6. CABLE TELEVISION PERMIT
5. GAS UTILITY PERMIT
4. ELECTRICAL UTILITY PERMIT
3. DRIVEWAY APPROACH PERMIT
2. SIDEWALK PERMIT (IF APPLICABLE)
1. DEMOLITION PERMIT
A
B
C
D
E
F
P
O
N
M
L
K
J
H
G
R
S
T
U
V
W I
STANDARD ABBREVIATIONS
W/O.
W.C.
WD.
WDW.
WT.
W.W.F.
W.W.M.
VAR.
V.C.T.
U.L.
UNFIN.
U.N.O.
T.&G.
TEMP.
THK.
T.O.
T.V.
TYP.
SCHD.
SECT.
S.F.
SHT.
SHTG.
SIM.
SIM.REV.
SPEC.
STD.
STL.
STOR.
STRUCT.
SUSP.
SYM.
R.D.
REBAR
REF.
REINF.
REQ.
REV.
RM.
R.O.
PC.
PERF.
P.LAM.
PLYW.
O.C.
OF.D.
O.H.D.
OPNG.
OPP.
O.S.B.
N.I.C.
NO. / #
NOM.
N.T.S.
MAINT.
MATL.
MAX.
MECH.
MEMB.
MEZZ.
MFR.
MIN.
MIR.
MISC.
M.O.
MTD.
MTL.
LAM.
LAV.
L.F.
KIT.
JAN.
I.D.
IN.
INFO.
INSUL.
INT.
H.C.
HCP.
HDR.
HDWD
HDWR.
H.M.
HORIZ
HR.
HT./HGT.
GA
GALV.
G.C.
GYP. BD.
F.D.
FDN.
F.E.
F.E.CAB.
F.F.E.
FLR.
F.O.
F.R.P.
FT.
FTG.
FURN.
F.V.
DBL.
DEPT.
DET.
D.F.
DIA./ Ø
DIAG.
DIM.
DISP.
DN.
DR.
DS.
DWG.
C.I.P.
C.J.
C/L / ℄
CLG.
CLR.
C.M.U.
COL.
COMP.
CONC.
CONST.
CONT.
COORD.
CORR.
CPT.
CT.
BD.
BLDG.
BM.
B.O
BRG.
ACC.
A.C.T.
ADD.
ADJ.
A.F.F.
ALT.
APPROX.
ARCH.
AVG.
EA.
E.I.F.S.
E.J.
ELEC.
ELEV.
ENTR.
EQ.
EQUIP.
EXP.
EXIST.
ACCORDING/ACCORDION
ACOUSTICAL CEILING TILE
ADDENDUM
ADJUSTABLE/ADJACENT
ABOVE FINISHED FLOOR
ALTERNATE/ALTERATION
APPROXIMATE
ARCHITECT/ARCHITECTURAL
AVERAGE
BOARD
BUILDING
BEAM
BOTTOM OF
BEARING
DOUBLE
DEPARTMENT
DETAIL
DRINKING FOUNTAIN
DIAMETER
DIAGONAL
DIMENSION
DISPOSAL
DOWN
DOOR
DOWNSPOUT
DRAWING
EACH
EXTERIOR INSUL. FINISH SYSTEM
EXPANSION JOINT
ELECTRICAL
ELEVATOR / ELEVATION
ENTRANCE
EQUAL
EQUIPMENT
EXPANSION
EXISTING
CAST IRON PIPE/CAST IN PLACE
CONTROL JOINT
CENTER-LINE
CEILING
CLEAR
CONCRETE MASONRY UNITS
COLUMN
COMPOSITE/COMPOSITION
CONCRETE
CONSTRUCTION
CONTINUOUS
COORDINATE
CORRIDOR
CARPET
CERAMIC TILE
FLOOR DRAIN
FOUNDATION
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FINISH FLOOR ELEVATION
FLOOR
FACE OF
FIBERGLASS REINFORCED PANEL
FOOT OR FEET
FOOTING
FURNACE/FURNISH
FIELD VERIFY
GAUGE
GALVANIZED
GENERAL CONTRACTOR
GYPSUM BOARD
HOLLOW CORE
HANDICAP
HEADER
HARDWOOD
HARDWARE
HOLLOW METAL
HORIZONTAL
HOUR
HEIGHT
INSIDE DIMENSION
INCHES
INFORMATION
INSULATION
INTERIOR
LAMINATED
LAVATORY
LINEAL FOOT
KITCHEN
JANITOR
MAINTENANCE/MAINTAIN
MATERIAL
MAXIMUM
MECHANICAL
MEMBRANE
MEZZANINE
MANUFACTURER
MINIMUM/MINUTE
MIRROR
MISCELLANEOUS
MASONRY OPENING
MOUNTED
METAL
NOT IN CONTRACT
NUMBER
NOMINAL
NOT TO SCALE
ON CENTER
OVERFLOW DRAIN
OVERHEAD DOOR
OPENING
OPPOSITE
ORIENTED STRAND BOARD
PRECAST
PERFORATED
PLASTIC LAMINATE
PLYWOOD
ROOF DRAIN
REINFORCING BAR
REFERENCE/REFRIGERATOR
REINFORCED
REQUIRED
REVISION/REVERSE
ROOM
ROUGH OPENING
SCHEDULE
SECTION
SQUARE FEET
SHEET
SHEATHING
SIMILAR
SIMILAR REVERSE
SPECIFICATION
STANDARD
STEEL
STORAGE
STRUCTURE/STRUCTURAL
SUSPENDED
SYMBOL
TONGUE AND GROOVE
TEMPERED/TEMPORARY/TEMPERATURE
THICK
TOP OF
TELEVISION
TYPICAL
UNDERWRITERS LABORATORIES, INC.
UNFINISHED
UNLESS NOTED OTHERWISE
VARIES
VINYL-COMPOSITION TILE
WITHOUT
WATER CLOSET
WOOD
WINDOW
WEIGHT
WELDED WIRE FABRIC
WELDED WIRE MESH
O.F.C.I. OWNER FURNISHED
CONTRACTOR INSTALLED
GRAPHIC SYMBOLS
100A
ROOM TAG
Room Name
DOOR TAG
WINDOW TAG1t
WALL PARTITION TYPE
FIRE EXTINGUISHER CABINET
A101
SIM
F.E.C
F.E
ELEVATION NUMBER
SHEET NUMBER
BUILDING SECTION NUMBER
SHEET NUMBER
FIRE EXTINGUISHER CABINET
INTERIOR ELEVATION MARK
ELEVATION MARKER
A1.100
Ref
Ref
R e fR e f
XX
2h
A101
Ref
1Ref 1 Ref
Ref
Name Elevation
WALL TYPE PATTERNS
EXISTING WALL CONSTRUCTION
EXIST. WALL TO BE REMOVED
SOUND BATT INSULATION
NEW MASONARY WALL
NEW POUR CONCRETE WALL
MOUNTING NOTES:
ADA COMPLIANT
ADA COMPLIANT
STD. ADA COMPLIANT (DUAL)
ADA COMPLIANT
ADA COMPLIANTTYPICAL MOUNTING HEIGHTS FORTYPICAL
MOUNTING HT. FOR
ADA COMPLIANT
FRONT APPROACH ADA COMPLIANT
ADA COMPLIANT
ADA COMPLIANT
TYPICAL LOCATION FOR
ADA COMPLIANT
TYPICAL SIZE, SPACING &
MOUNTING OF
SIDEWALL
VERTICAL
AND
HORIZONTAL
GRAB BARS
PER 2/A0.1
30" CLEAR
S
T D
M
T G
H
G H
T
DIRECTION
OF
APPROACH
PLAN VIEW FRONT ELEVATION SIDE ELEVATION
FRONT ELEVATION SECTION
FRONT ELEVATION SIDE ELEVATION
FRONT ELEVATION SIDE ELEVATION
SIDE VIEW
'PUSH' SIDE
OF DOOR
'PULL' SIDE
OF DOOR
FRONT VIEW PLAN VIEW
PROTRUDING
DISPENSER
BELOW GRAB BAR
RECESSED DISPENSER
TOILET
MOUNT
TYP. TOILET PARTITION
TYPICAL
URINAL
SCREEN
COAT HOOK(S)
TOILET PAPER
DISPENSER -
SEE DETAILS
TO
RIGHT
GRAB BARS GRAB BARS
PAPER
TOWEL
DISPENSE
R
PAPER
TOWEL
DISPENSE
RSOAP
DISP.
CLEAR FLOOR AREA TO
REMAIN CLEAR OF
OBSTRUCTIONS FOR
WHEELCHAIR TO FIXTURE
ACCESS
30"x48" MIN. CLEAR FLOOR
SPACE REQUIRED (ANY
ORIENTATION) FOR ACCESSIBLE
STALL ENTRY/EXITING,
ADJACENT TO DOOR
ALWAYS REQUIRED
FRONT VIEW ADA
COMPLIANT
ELEVATOR
BUTTONS & SIGNALS
ELEVATO
R
DOORS
*-54" MAX. FOR
EXISTING
BUTTONS
OUTLETS
CLEAR
FLOOR
AREA
CLEAR
FLOOR
AREA
SEE 7/A0.1 FOR
KNEE
& TOE CLEARANCE
INFO.
ADA COMPLIANT
PIPE
WRAP AT EXPOSED
PIPES -TYP.
URINAL
FIXTURE
(T R
A S
H
48"
CLEAR
LAVATORY PROVIDED W/
INSULATED EXPOSED
PLUMBING PIPE COVERS
(NOT
SHOWN)
BRACKETCABINET
MOUNT
30"x48" CLEAR
FLOOR
SPACE (ADA
MINIMUM)
ROOM SIGNAGE, SEE
SPEC
FOR DESCRIPTION AND
SIZE
DOOR FRAME
HAND
DRYER
REQUIRED ONLY
WHEN BOTH A
LATCHSET AND
CLOSER IS USED
COUNTER TOP
SINK TO BE
ACCESSIBLE
BABY
CHANGING
TO TOP OF DECK
WHEN OPEN
CONTROL
S/
SWITCHES
ACCESSIBL
E
TOILET
FIXTURE
NOTE:
G.C. TO PROVIDE ANCHORAGE
TO
WALL W/ ADEQUATE
BLOCKING- ADA DESIGN HEIGHT TO
BE
PROVIDED AS REQUIRED
1" CLOSET
ROD
(SEE SPEC.)
3/4" P.LAM SHELF
W/
P.LAM WALL
SUPPORTS
MIRROR TO
MATCH VANITY
LENGTH
2'-0"x3'-0" MIRROR
CENTERED ON
LAV.
ACCESSIBLE
C U
P S
HANDRAIL HANDRAIL (GRAB
BAR)
1. THIS SHEET IS FOR GENERAL INFORMATION AND REFERENCE ONLY. ANY
JOB SPECIFICDRAWINGS IN THESE CONTRACT DOCUMENTS ARE TO TAKE
PRECEDENCE OVER SIMILAR DRAWINGS SHOWN ON THIS SHEET.
2. IF DISCREPANCIES ARE FOUND BETWEEN STANDARD OR GENERAL
DETAILS AND JOB SPECIFIC DETAILS INCLUDED IN THIS SET, PLEASE
CONTACT THE ARCHITECT FOR CLARIFICATION.
3. ALL CONDITIONS SHOWN ON THIS SHEET MAY NOT BE PRESENT WITHIN
THESE CONTRACT DOCUMENTS
4. ALL CLEARANCES AND MOUNTING HEIGHTS ARE INTENDED TO COMPLY
WITH CURRENT ACCESSIBILITY CODE.
END PANEL
(WHERE
APPLICABLE)
PER MN. CODE SECTION 1012 -
HANDRAILS SHALL RETURN TO A
WALL, GUARD OR THE WALKING
SURFACE OR SHALL BE
CONTINUOUS TO THE HANDRAIL
OF AN ADJACENT STAIR FLIGHT
OR RAMP RUN OR SHALL COMPLY
WITH THE DIAGRAM AT RIGHT.
ROUND-OVER CONC.
TOP (SMOOTH FINISH)
6" DIA. STEEL PIPE BOLLARD
FILL PIPE SOLID W/ CONC.
PRIME AND PAINT PIPE,
COLOR TO BE SELECTED
BY
ARCHITECT FROM
STANDARD
FINISHES
GRADE
18" DIA. CONC. PIER
6" CLEAN
GRANULAR
MATERIAL AT BASE
ACCESSIBLE TOILET ELEVATIONS
LAVATORY PLAN & ELEVATION
DRINKING FOUNTAIN
AMBULATORY TOILET STALL
LATCH SIDE DOOR CLEARANCES
COAT ROD & SHELF/ COAT HOOKS
BOLLARD DETAIL
ELEVATOR SIGNALS
FIRE EXTINGUISHER
VANITY ELEVATION & SECTION
ACCESSIBLE REACH LIMITATIONS
ACCESSIBLE TOILET PLAN
URINAL PLAN & ELEVATION
RESTROOM SIGNAGE
STAIR TREAD/RISERS & HANDRAILS
DISPENSER INSTALLATION LOCATIONS
60"
WALL SPACE
42" MIN. CLEAR 16"-18"
M
IN
C
L E
A R
O R
M
IN
C
L E
A R
60" CLEAR
36" MIN. 6"
MIN.
24"
MIN.
12"
16''-18"
T O
S E
A T
M
IN
MAX
12" 42" MIN.
54"
39"-41"
M
IN
MIN.
24"
42" MAX.
-1
/2
M
IN
P
E R
.3
M
IN
MIN.
24"
42" MAX.
36"
M
IN
M A
X
M
IN
MIN.
32"
17"-19"
36" CLEAR
M
A X
M A
X
O F
C A
L L B
U T
T O
N S
M
A X
H
E
IG
H T
H E
IG
H
T O
F S
IG
N
A L
S
M
IN
A
D A
M T
G H
G H
T
T O
L
IP
CLEAR
30"
M A
X
U .N
.O
C L E
A R
M
IN
48" MIN. CLEAR
MAX.
17" - 25"
M
A X
M
IN
MIN.
8"
18"
M
IN
" 2
M
IN
M
IN
M
IN
M
IN
6"
M A
X
T O
P O
F E
X T
IN
G
U
IS
H E
R
M A
X
TOIL
M
IN
M A
X
M
A X
T O
S P
O U
T
T O
S P
O U
T
FLOOR SPACE
30" CLR
M
IN
M
A X
T O
S P
O U
T
8" MIN.
M
IN
FLOOR SPACE
48" MIN.CLR
MAX
6"
1 1/4"-2"
1 1/2" MIN
1 1/4"-2"
1 1/2" MIN
" M A
X
11" MIN.
2" MAX.
MIN.
12"
A D
A M
A X
T
O C
E N
T E
R O
F R
O D
12"
14"
T
O T
H E
T O
P O
F S
H E
L F
SEE PLAN
MIN.
12"
CLEAR
18" MIN.
CLEAR
32" MIN.
M
IN
M A
X
DRINKING
FOUNTAI
N
EQ EQ
CONCRETE
MASONARY UNIT
BRICK
MASONARY
TYPICAL FILL PATTERN
PLYWOOD
CONTINIUS WOOD
FRAMING
CONCRETE
SAND
INTERRUPED
WOOD FRAMING
FINISHED WOOD
EARTH
RIGID
INSULATION
GRAVEL FILL
BATT
INSULATION
STEEL
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.46.21 www.crwarchitecture.com
CLIENT
1 DD Issue 4/7/2026
2 90% CD Issue 4/21/2026
3 100% CD Issue 4/30/2026
A u to d e s k D o c s
/R P
S J o h n
M a rs h a ll
H S
C o ff e e S h o p /2
-0
J o h n M a rs h a ll H
S C o ff e e
S h o p
.r v t
/3
/2
:5 :1
P
M
G0.01
Jason Woodhouse
44421 4/30/2026
GENERAL INFORMATION
SHEET
R O
C H
E S
T E
R
M
IN
N E
S O
T A
IS
D
JO
H N
M A
R S
H A
LL
H
IG
H
S C
H O
O L
C O
F F
E E
S H
O P
26-015
4/30/2026
LG
JW
1. UNLESS SPECIFICALLY NOTED OTHERWISE, ALL DETAILS, SECTIONS,
NOTES, ETC. ARE TO BE CONSIDERED AS BEING TYPICAL AT ALL SIMILAR
LOCATIONS OR CONDITIONS. IN THESE DOCUMENTS, DETAILS, NOTES, ETC.
ARE NOT INDICATED OR REFERENCED AT ALL POSSIBLE APPLICABLE
LOCATIONS.
2. THE SPECIFICATIONS AS PREPARED BY CRW ARCHITECTURE + DESIGN
GROUP SHALL BE CONSIDERED A PART OF THESE DOCUMENTS AS IF BOUND
HEREIN.
3. THE CONTRACTOR SHALL NOTIFY ALL APPROPRIATE ENGINEERING
DEPARTMENTS AND UTILITY COMPANIES 72 HOURS PRIOR TO CONSTRUCTION.
ALL NECESSARY PRECAUTIONS SHALL BE TAKEN TO AVOID DAMAGE TO ANY
EXISTING UTILITY.
4. BEFORE BIDDING, FABRICATION OR BEGINNING WORK, CONTRACTOR
SHALL VISIT PROJECT SITE, REVIEW ALL CONSTRUCTION DOCUMENTS AND
UNDERSTAND THEM IN THEIR ENTIRETY. THE CONSTRUCTION DOCUMENTS
MUST BE VIEWED IN THEIR ENTIRETY AS COMPLETE SETS.
5. BEFORE BIDDING, FABRICATION OR BEGINNING WORK, CONTRACTOR
SHALL VISIT PROJECT SITE AND FIELD VERIFY ALL EXISTING CONDITIONS,
DIMENSIONS, ETC.
6. CONTRACTOR SHALL IMMEDIATELY REPORT ANY DISCREPANCIES,
CONTRADICTIONS OR QUESTIONS REGARDING THE CONTRACT DOCUMENTS
OR EXISTING CONDITIONS TO THE ARCHITECT IMMEDIATELY FOR
RESOLUTION.
7. CONTRACTOR SHALL IMMEDIATELY REPORT ANY CODE VIOLATIONS IN THE
CONTRACT DOCUMENTS TO THE ARCHITECT FOR RESOLUTION.
8. DO NOT SCALE DRAWINGS. IN ALL CASES STATED DIMENSIONS TAKE
PRECEDENCE. CONTACT ARCHITECT IMMEDIATELY FOR ADDITIONAL
REQUIRED DIMENSIONS. GENERAL CONTRACTOR SHALL VERIFY ALL
DIMENSIONS, VERIFY AND COORDINATE WITH EXISTING CONDITIONS AND
COORDINATE THE WORK, TIMING AND PHASING OF ALL TRADES.
9. ALL DEMOLITION, NEW CONSTRUCTION, SITE WORK AT INTERIOR AND
EXTERIOR OF BUILDING SHALL BE IN CONFORMANCE WITH ALL APPLICABLE
CODE REQUIREMENTS, INCLUDING BUT NOT LIMITED TO, CURRENT BUILDING
CODE
10. ALL FINISH MATERIALS SHALL CONFORM TO APPLICABLE FLAME SPREAD
AND SMOKE GENERATED REQUIREMENTS.
11. ALL FIRE RATED WALLS SHALL BE CONSTRUCTED PER APPROVED U.L. OR
OTHER ACCEPTABLE TESTING AGENCY REQUIREMENTS TO MEET OR EXCEED
STATED FIRE RATINGS. ALL PENETRATIONS OF FIRE RATED BUILDING
ELEMENTS SHALL BE SIMILARLY CONSTRUCTED PER LOCAL BUILDING CODE
TO MAINTAIN REQUIRED FIRE RATINGS.
12. IF AT ANY TIME THE CONTRACTOR ENCOUNTERS OR UNCOVERS
ASBESTOS CONTAINING BUILDING MATERIALS OR OTHER POSSIBLE
HAZARDOUS OR TOXIC MATERIALS, IT'S PRESENCE SHALL BE IMMEDIATELY
REPORTED TO ARCHITECT AND BUILDING OWNER.
13. CONTRACTOR SHALL FOLLOW OSHA AND OTHER APPLICABLE SAFETY
REQUIREMENTS DURING ALL WORK INCLUDING BUT NOT LIMITED TO
DEMOLITION, REPAIR AND CONSTRUCTION.
14. ALL EXISTING MATERIALS TO REMAIN WHICH ARE DISTURBED OR
DAMAGED AND ALL OTHER CUTTING SHALL BE PATCHED BACK AS REQUIRED
TO LIKE NEW CONDITION, TO MATCH ADJACENT SURFACES AND TO MAKE
SUCH REPAIR IMPERCEPTIBLE.
15. BEFORE DEMOLITION, FABRICATION OR CONSTRUCTION, CONTRACTOR
SHALL VERIFY THAT NO CONFLICTS EXIST IN LOCATIONS OR CLEARANCE
REQUIREMENTS OF STRUCTURAL, MECHANICAL, ELECTRICAL, PLUMBING,
TELECOMMUNICATIONS, TELEPHONE, DATA OR FIRE PROTECTION SYSTEMS
AND THEIR ELEMENTS.
16. FIREBLOCKING, FIRESTOPS, DRAFTSTOPPING SHALL BE INSTALLED AS
REQUIRED BY CURRENT LOCAL BUILDING CODE REQUIREMENTS. TYPICAL AS
REQUIRED AT PARTITIONS, CONCEALED COMBUSTIBLE SPACES, CONCEALED
COMBUSTIBLE ATTIC SPACES, FLOOR PENETRATIONS, PENETRATIONS
THROUGH FIRE RATED PARTITIONS OR OTHER STRUCTURES AS REQUIRED BY
CURRENT CODE.
17. CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL TEMPORARY SHORING
OR BRACING AND FOR THE DESIGN, CONSTRUCTION, STABILITY AND SAFETY
OF ALL TEMPORARY STRUCTURES, ENCLOSURES AND SCAFFOLDING.
18. CONTRACTOR SHALL COORDINATE THE TIMING, PHASING AND EXECUTION
OF ALL CUTTING AND PATCHING FOR THE EFFICIENT AND TIMELY COMPLETION
OF WORK.
19. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR TEMPORARY
PROTECTION AT ANY OPENINGS IN FLOORS, ROOFS, WALLS, ETC.
20. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR DETERMINING
ERECTION PROCEDURE AND CONSTRUCTION SEQUENCE IN ORDER TO
ENSURE THE SAFETY OF THE BUILDING, WORKMEN AND VISITORS.
21. CONTRACTOR SHALL SAFELY AND LEGALLY REMOVE AND DISPOSE OF ALL
MATERIALS NOT SCHEDULED TO BE SALVAGED OR RE-INSTALLED.
22 CONTRACTOR SHALL MAINTAIN A STAMPED, APPROVED SET OF
CONSTRUCTION DOCUMENTS WITH APPROVAL LETTER AND CURRENT SHOP
DRAWINGS. DOCUMENTS ON SITE SHALL BE KEPT UP TO DATE.
23. MATERIAL OR PRODUCT SUBSTITUTIONS SHALL FOLLOW THE
SUBSTITUTION REQUIREMENTS OF DIVISION 01 OF THE PROJECT
SPECIFICATIONS DOCUMENT.
24. SHOP DRAWINGS OR OTHER SUBMITTALS SHALL FOLLOW THE SUBMITTAL
REQUIREMENTS OF DIVISION 01 OF THE PROJECT SPECIFICATIONS
DOCUMENT.
25. THE FIRE PROTECTION CONTRACTOR AND PLUMBING CONTRACTOR
SHALL CONFIRM ALL FLOW TEST INFORMATION WITH THE LOCAL FIRE
DEPARTMENT AND WATER DEPARTMENT AS REQUIRED.
26. GENERAL CONTRACTOR SHALL PROVIDE APPROVED KEY BOXES AS
REQUIRED BY LOCAL FIRE MARSHALL. INSTALL AT LOCATIONS AS REQUIRED
BY THE FIRE MARSHALL.
27. VERIFY MINIMUM SLOPES TO DRAIN AS INDICATED ON THE DRAWINGS
PRIOR TO THE START OF CONSTRUCTION. NOTIFY THE ARCHITECT
IMMEDIATELY UPON DISCOVERY OF ANY DISCREPANCIES.
28. FIELD VERIFY ELEVATIONS, FLOW LINES, EXISTING CONDITIONS, AND
POINTS OF CONNECTION OF SITE IMPROVEMENTS WITH EXISTING UTILITIES
PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES ARE TO BE
IMMEDIATELY CALLED TO THE ATTENTION OF THE ARCHITECT AND CIVIL
ENGINEER.
29. PROVIDE POSITIVE DRAINAGE OF SURFACE WATER AWAY FROM THE
BUILDING AT ALL LOCATIONS TO AVOID PONDING OF WATER AT BUILDING OR
ON PAVEMENT. DRAINAGE SLOPE FOR ALL PAVED SURFACES SHALL BE 1%
MINIMUM. MAXIMUM ALLOWABLE CROSS SLOPE AT ALL WALKS AND
HANDICAP ACCESSIBLE WALKS AND RAMPS SHALL BE 2%.
30. REPAIR EXISTING PUBLICLY OWNED FACILITIES OR STRUCTURES
DAMAGED OR ALTERED DURING DEMOLITION OR CONSTRUCTION TO THE
SATISFACTION OF THE LOCAL MUNICIPALITY.
31. EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE, CONTRACTOR SHALL
ENSURE THAT ALL FINISH MATERIALS SHALL BE APPLIED TO BE FLUSH WITH
ADJACENT SURFACES AND JOINTS.
32. CONTRACTOR TO PROVIDE AND INSTALL BLOCKING, DOUBLE STUDS,
AND/OR ANCHOR PLATES AS NECESSARY TO SUPPORT EQUIPMENT,
PLUMBING FIXTURES, CASEWORK, CABINETS, GRAB BARS, TOILET ROOM
ACCESSORIES, SIGNAGE, HANDRAILS, ETC.
33. CONTRACTOR SHALL VERIFY ALL EQUIPMENT LOCATIONS, DIMENSIONS,
AND ALL REQUIRED CLEARANCES OF ALL EQUIPMENT. COORDINATE WITH
DRAWINGS, SPECIFICATIONS, EQUIPMENT MANUALS AND CUT SHEETS. VERIFY
THAT STRUCTURAL LOADS ARE ACCEPTABLE.
GENERAL NOTES
FDFD
FD
FD
FD
FD
FD
FD
FD
FD FD
FD
FDFD
FD
R E
F F
R Z
REF
21"42" x
21"48" x
CODE PLAN LEGEND:
2 HR. FIRE WALL
SMOKE TIGHT CONSTRUCTION
OCCUPANCY INFORMATION:
ROOM NAME
TOTAL OCCUPANT LOAD
ROOM
1 HR. FIRE BARRIER
331 OCCUPANT LOAD THROUGH EXIT
EXISTING 2-HOUR FIRE WALL FOR AREA
SEPARATION - UNCHANGED
EXIT
EXIT
EXIT
EXIT
EXIT
EXIT
EXIT
TEMPORARY CONSTRUCTION WALL
BY CONTRACTOR
TEMPORARY EGRESS DOOR WITH EXIT SIGN
BY CONTRACTOR
EXIT
COFFEE SHOP
4-104A
KITCHEN
GYM
EXISTING 2-HOUR FIRE WALL FOR
AREA SEPARATION - UNCHANGED
8139 SF
543 Occ.
CAFETERIA
4-104
2020 MINNESOTA STATE BUILDING CODE
2020 MINNESOTA ACCESSIBILITY CODE
2020 MINNESOTA CONSERVATION CODE FOR EXISTING BUILDINGS
2020 MINNESOTA FIRE CODE
2024 MINNESOTA COMMERCIAL ENERGY CODE
PROPOSED PROJECT SUMMARY
THE PROJECT CONSISTS OF RENOVATING AN EXISTING ROOM WITHIN THE
CAFETERIA TO CREATE A NEW COFFEE SHOP.
MECHANICAL SCOPE INCLUDES REMOVAL OF AN EXISTING HOOD AND UNUSED
VENT, AS WELL AS ASSOCIATED WATER AND GAS PIPING WITHIN THE DESIGNATED
COFFEE SHOP AREA. RELOCATING OF EXISTING FINNED TUBE RADIATION AND
MODIFICATIONS TO THE EXISTING WATER, WASTE, AND VENT PIPING SYSTEMS, AND
THEIR REQUIRED ACCESSORIES.
ELECTRICAL SCOPE INCLUDES DEMOLITION OF EXISTING WALL DEVICES,
INSTALLATION OF NEW DEVICES TO SUPPORT FOOD SERVICE EQUIPMENT,
REMOVAL AND REINSTALLATION OF CEILING FIXTURES, AND INSTALLATION OF A
NEW ELECTRICAL PANEL DEDICATED TO THE COFFEE SHOP.
USE AND OCCUPANCY CLASSIFICATION
A. THE EXISTING USE AND OCCUPANCIES WILL REMAIN UNCHANGED AND INCLUDE
GROUP B, GROUP E, GROUP A-1 (AUDITORIUM), GROUP A-2 (CAFETERIA/KITCHEN),
GROUP A-3 (GYMNASIUM), GROUP A-4 (POOL) AND ACCESSORY STORAGE SPACES.
B. THE EXISTING BUILDING IS CLASSIFIED AS A SEPARATED, MIXED-USE, MULTISTORY
BUILDING AND WILL REMAIN UNCHANGED. PER TABLE 508.4 SEPARATIONS ARE NOT
REQUIRED BETWEEN GROUP A AND E OCCUPANCIES.
BUILDING HEIGHTS AND AREAS
THERE ARE NO CHANGES TO BUILDING HEIGHTS OR AREAS AS PART OF THIS PROJECT
TYPES OF CONSTRUCTION
TYPE II-B - UNCHANGED
FIRE AND SMOKE PROTECTION FEATURES
A. BUILDING ELEMENT FIRE RESISTANCE
FIRE WALLS 2-HR SEE PLAN
FIRE BARRIERS
FIRE AREAS 2-HR SEE PLAN
SHAFT ENCLOSURES 1-HR SEE PLAN
INCIDENTAL USES 1-HR RATED CONSTRUCTION OR FULLY SPRINKLERED W/ SMOKE TIGHT CONSTRUCTION - SEE PLAN
BOILER ROOM FULLY SPRINKLERED W/ SMOKE TIGHT CONSTRUCTION
FIRE PARTITIONS
CORRIDOR WALLS 0-HR
ELEVATOR LOBBY NOT REQUIRED
INTERIOR FINISHES
A. GROUP E , SPRINKLERED
BUILDING ELEMENT FINISH CLASSIFICATION
EXIT ENCLOSURES/EXIT PASSAGEWAYS B
CORRIDORS: GROUP A OCC B
CORRIDORS: GROUP B, E, S OCC C
ROOMS AND ENCLOSED SPACES C
FLOOR FINISHES CLASS II
FIRE PROTECTION SYSTEMS
A. SPRINKLER SYSTEM REQUIRED & PROVIDED - NO CHANGES AS PART OF THIS PROJECT EXCEPT THE MODIFICATIONS AS
NEEDED TO ACCOMMODATE NEW SOFFITS, BULKHEADS, EQUIPMENT AND CEILINGS.
B. FIRE ALARM SYSTEM REQUIRED & PROVIDED
C. PORTABLE EXTINGUISHERS REQUIRED & PROVIDED
MEANS OF EGRESS
A. THERE ARE NO CHANGES IN OCCUPANCY TYPES, OCCUPANT LOADS, AND EXIT PATHS AS PART OF THIS PROJECT
B. THE PROJECT WILL REQUIRE TEMPORARY EMERGENCY EGRESS ONLY DOORS THROUGH THE TEMPORARY CONSTRUCTION BARRIERS TO MAINTAIN REQUIRED EGRESS AS THE CAFETERIA WILL BE USED DURING CONSTRUCTION.
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.46.21 www.crwarchitecture.com
CLIENT
1 DD Issue 4/7/2026
2 90% CD Issue 4/21/2026
3 100% CD Issue 4/30/2026
A u to d e s k D o c s
/R P
S J o h n
M a rs h a ll
H S
C o ff e e S h o p /2
-0
J o h n M a rs h a ll H
S C o ff e e
S h o p
.r v t
/3
/2
:2 :5
P
M
G0.02
Jason Woodhouse
44421 4/30/2026
CODE SUMMARY
R O
C H
E S
T E
R
M
IN
N E
S O
T A
IS
D
JO
H N
M A
R S
H A
LL
H
IG
H
S C
H O
O L
C O
F F
E E
S H
O P
26-015
4/30/2026
LG
JW
1/8" = 1'-0"
FIRST LEVEL CODE PLAN NORTH
CODE INFORMATION:
J
P
P
J
1 REMOVE EXISTING CMU WALL CONSTRUCTION TO THE DECK IN
ITS ENTIRETY AND DISPOSE OF PROPERLY.
DEMOLITION NOTES:
GENERAL DEMOLITION NOTES:
1. DASHED LINES REPRESENT EXISTING ITEMS TO BE REMOVED. U.N.O
2. PROVIDE ALL WORK TO COMPLETE DEMOLITION AS MAY BE REQUIRED
TO ACCOMPLISH WORK AS SHOWN ON THE DRAWINGS UNLESS NOTED
OTHERWISE. ALL AS INDICATED OR REQUIRED RELATING TO THE
EXISTING BUILDING AND NOT OTHERWISE ASSIGNED IS INCLUDED
UNDER THE RESPONSIBILITY OF THE CONTRACTOR.
3. CONTRACTOR TO VERIFY EXISTING ELECTRICAL & PLUMBING
LOCATIONS PRIOR TO DEMOLITION. EXISTING PLUMBING AND
ELECTRICAL MAY REQUIRE MODIFICATION TO ACCOMPLISH THE NEW
DESIGN AS SHOWN ON THESE PLANS.
4. MECHANICAL, ELECTRICAL AND PLUMBING CONTRACTORS SHALL
TERMINATE ALL APPROPRIATE SERVICES TO EXISTING CONSTRUCTION
WHICH ARE TO BE PERMANENTLY DISCONNECTED. THEY SHALL
FURTHER MAKE ALL TEMPORARY SERVICE TERMINATIONS INDICATED
OR REQUIRED TO ACCOMPLISH THE DEMOLITION AND/OR NEW
REVISED OR REPLACED SERVICES AS PART OF WORK UNDER ALL
CONTRACTS. ALL PERMANENT TERMINATIONS SHALL BE REMOVED
BACK TO THE SOURCE. NO VACANT SERVICES SHALL BE LEFT IN
PLACE.
5. CONTRACTORS ARE TO BE RESPONSIBLE FOR REMOVING AND
HAULING OF ALL DEMOLITION DEBRIS.
6. AT CONCLUSION OF DEMOLITION, ALL SURFACES SHALL BE READY TO
RECEIVE NEW FINISHES.
7. OWNER TO REMOVE/ RELOCATE ALL FURNITURE, FIXTURES AND
EQUIPMENT PRIOR TO START OF CONSTRUCTION, COORDINATE
PROJECT SCHEDULE WITH GENERAL CONTRACTOR.
2 REMOVE EXISTING DOOR, DOOR FRAME AND HARDWARE IN ITS
ENTIRETY AND DISPOSE OF PROPERLY.
3 REMOVE EXISTING QUARRY FLOOR TILE AND BASE IN ITS
ENTIRETY AND DISPOSE OF PROPERLY. PREP FLOOR FOR NEW
FLOOR FINISH INSTALLATION.
4 CUT AND REMOVE SLAB FOR INSTALLATION OF NEW SANITARY
LINE. COORD. FINAL LOCATION WITH PLUMBING PLANS.
5 REMOVE AND DISPOSE OF EXISTING WALL BASE IN ITS ENTIRETY
AND DISPOSE OF PROPERLY.
6 REMOVE AND DISPOSE OF EXISTING QUARTZ TILE FLOOR FINISH
IN HATCHED REGION OR UNTIL THE RED AND QHITE QUARTZ
FLOORING MEET, PREPARE FLOOR FOR NEW TILE INSTALLATION.
7 REMOVE AND DISPOSE OF EXISTING CASEWORK IN ITS ENTIRETY
AND DISPOSE OF PROPERLY.
8 REMOVE AND SALVAGE EXISTING PAPER TOWEL AND SOAP
DISPENSERS TO OWNER.
9 REMOVE AND DISPOSE OF EXISTING MIRROR IN ITS ENTIRETY
AND DISOPOSE OF PROPERLY.
10 REMOVE AND DISPOSE OF EXISTING HAND SINK IN ITS ENTIRETY
AND DISPOSE OF PROPERLY.
11 REMOVE AND DISPOSE OF EXISTING FLOOR SINK IN ITS ENTIRETY
AND DISPOSE OF PROPERLY. INFILL FLOOR AND PREP FOR NEW
FLOOR FINSIH.
12 REMOVE AND SALVAGE EXISTING SIGNAGE TO OWNER.
COFFEE SHOP
4-104A
CAFETERIA
4-104
20' - 7"
TUNNEL BELOW
DEMOLITION NOTES:
GENERAL DEMOLITION NOTES:
1. DASHED LINES REPRESENT EXISTING ITEMS TO BE REMOVED. U.N.O.
2. PROVIDE ALL WORK TO COMPLETE DEMOLITION AS MAY BE REQUIRED
TO ACCOMPLISH WORK AS SHOWN ON THE DRAWINGS UNLESS NOTED
OTHERWISE. ALL AS INDICATED OR REQUIRED RELATING TO THE
EXISTING BUILDING AND NOT OTHERWISE ASSIGNED IS INCLUDED
UNDER THE RESPONSIBILITY OF THE CONTRACTOR.
3. CONTRACTOR TO VERIFY EXISTING ELECTRICAL & PLUMBING
LOCATIONS PRIOR TO DEMOLITION. EXISTING PLUMBING AND
ELECTRICAL MAY REQUIRE MODIFICATION TO ACCOMPLISH THE NEW
DESIGN AS SHOWN ON THESE PLANS.
4. MECHANICAL, ELECTRICAL AND PLUMBING CONTRACTORS SHALL
TERMINATE ALL APPROPRIATE SERVICES TO EXISTING CONSTRUCTION
WHICH ARE TO BE PERMANENTLY DISCONNECTED. THEY SHALL
FURTHER MAKE ALL TEMPORARY SERVICE TERMINATIONS INDICATED
OR REQUIRED TO ACCOMPLISH THE DEMOLITION AND/OR NEW
REVISED OR REPLACED SERVICES AS PART OF WORK UNDER ALL
CONTRACTS. ALL PERMANENT TERMINATIONS SHALL BE REMOVED
BACK TO THE SOURCE. NO VACANT SERVICES SHALL BE LEFT IN
PLACE.
5. CONTRACTORS ARE TO BE RESPONSIBLE FOR REMOVING AND
HAULING OF ALL DEMOLITION DEBRIS.
6. AT CONCLUSION OF DEMOLITION, ALL SURFACES SHALL BE READY TO
RECEIVE NEW FINISHES.
7. SEE SEPARATE MECHANICAL, ELECTRICAL & PLUMBING DRAWINGS
FOR ADDITIONAL DEMOLITION ITEMS.
8. SEE SEPARATE SITE WORK DRAWINGS FOR ADDITIONAL DEMOLITION
ITEMS.
9. OWNER TO REMOVE/ RELOCATE ALL OFFICE SUPPLIES/EQUIPMENT
PRIOR TO START OF CONSTRUCTION, COORDINATE PROJECT
SCHEDULE WITH GENERAL CONTRACTOR.
10. EXISTING GYP. BD. CEILINGS TO REMAIN AND BE PROTECTED FROM
DAMAGE U.N.O.
11. REMOVE ACT CEILINGS IN THEIR ENTIRETY (U.N.O.) AND DISPOSE OF
PROPERLY.
CEILING LEGEND:
ACTGYP
1 REMOVE AND DISPOSE OF EXISTING ACOUSTICAL TILE AND GRID
IN ITS ENTIRETY.
2 REMOVE EXSTING AWNING AND SALVAGE TO OWNER.
3 REMOVE AND DISPOSE OF EXISTING HOOD. SEE MECH.
4 REMOVE AND DISPOSE OF EXISTING CEILING HUNG SIGNAGE IN
ITS ENTIRETY.
COFFEE SHOP
4-104A
CAFETERIA
4-104
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.46.21 www.crwarchitecture.com
CLIENT
1 DD Issue 4/7/2026
2 90% CD Issue 4/21/2026
3 100% CD Issue 4/30/2026
A u to d e s k D o c s
/R P
S J o h n
M a rs h a ll
H S
C o ff e e S h o p /2
-0
J o h n M a rs h a ll H
S C o ff e e
S h o p
.r v t
/3
/2
:5 :1
P
M
AD1.01
Jason Woodhouse
44421 4/30/2026
DEMO PLANS
R O
C H
E S
T E
R
M
IN
N E
S O
T A
IS
D
JO
H N
M A
R S
H A
LL
H
IG
H
S C
H O
O L
C O
F F
E E
S H
O P
26-015
4/30/2026
LG
JW
1/4" = 1'-0"
FIRST LEVEL - AREA 4C NORTH
1/4" = 1'-0"
FIRST LEVEL DEMOLITION CEILING PLAN - AREA 4C
NORTH
R E
F F
R Z
REF
21" 42"x
21" 48"x
1. ALL WORK SHALL BE PERFORMED IN COMPLIANCE WITH ALL
REQUIREMENTS OF THE OWNER. EACH TRADE CONTRACTOR SHALL
BE RESPONSIBLE FOR INITIATING, MAINTAINING AND SUPERVISING
ALL SAFETY PROCEDURES, PRECAUTIONS AND PROGRAMS IN
CONNECTION WITH THEIR WORK.
2. THE GENERAL CONTRACTOR SHALL FILE FOR AND OBTAIN ALL
REQUIRED PERMITS, LETTERS OF SATISFACTORY COMPLETION AND
CERTIFICATES OF OCCUPANCY FROM THE LOCAL BUILDING
OFFICIALS.
3. ALL EQUIPMENT SHOWN AS DASHED IS BY THE OWNER. ELECTRICAL
CONTRACTOR TO VERIFY POWER REQUIREMENTS FOR OWNER'S
EQUIPMENT. MECHANICAL CONTRACTOR TO VERIFY PLUMBING AND
HVAC REQUIREMENTS OF OWNER'S EQUIP.
4. REFER TO THE MECHANICAL, ELECTRICAL DRAWINGS FOR
ADDITIONAL WORK REQUIRED UNDER THIS CONTRACT.
5. THE GENERAL CONTRACTOR AND/OR MECHANICAL CONTRACTOR
SHALL COORDINATE ALL MECHANICAL WORK WITH THE OWNER'S
REPRESENTATIVE AND ALL OTHER TRADES.
6. THE GENERAL CONTRACTOR AND/OR ELECTRICAL CONTRACTOR
SHALL COORDINATE ALL ELECTRICAL WORK WITH THE OWNER'S
REPRESENTATIVE AND ALL OTHER TRADES.
GENERAL NOTES:
1 LINE OF NEW GYP. BD. BULKHEAD ABOVE.
PLAN NOTES:
2 INSTALL NEW RB-1 WALL BASE.
3 TEMPORARY EMERGENCY EXIT DOOR.
4 STAINLESS STEEL END WALL GUARD BY FSC. SEE FOOD
SERVICE PLANS.
5 STAINLESS STEEL CORNER GUARD, SEE FINISH MATERIAL
INDEX.
6 TEMPORARY WALL CONSTRUCTED OF LT. GA. METAL
FRAMING WITH GYP. BD. EACH SIDE AND BATT INSULATION
FROM FLOOR TO ROOF DECK ABOVE
7 INSTALL STAINLESS STEEL REDUCER TRANSITION WHERE
KITCHEN FLOOR FINISH AND EXISTING FLOOR FINISH MEET.
8 SIDE FOLDING SECURITY GRILLE, SEE SPEC.
9 PROVIDE FLOOR LEVELER TO ENSURE THERE IS NO SLOPING.
10 PATCH AND REPAIR TILE WHERE FLOOR CUTTING OCCURED,
MATCH EXISTING.
11 PATCH COMPOSITE SLAB OVER TUNNEL WHERE FLOOR
DRAINS ARE REMOVED AND LEVEL SLOPED FLOOR AROUND
DRAIN.
12 NEW FLOOR DRAIN - SEE MECHANICAL
COFFEE SHOP
4-104A
A2.00
A2.00 2
CAFETERIA
4-104
A2.00
A2.01
T
T
T
BOYS
4-100G
19' - 11" 4' - 0"
8' - 11"A.F.F.1
8' - 6"A.F.F.
1' - 3" 3' - 0" 3' - 0" 3' - 0" 3' - 0"
"3
SLIP TRACK AT TOP
OF WALL TO SOFFIT
SLIP TRACK AT TOP
OF WALL TO SOFFIT
CAULK JOINT AT CEILING SOFFIT TO WALL EACH END
TOOTH IN NEW CMU WHERE
EXISTING DUCT WAS REMOVED
J4
1. MECHANICAL AND ELECTRICAL INFORMATION SHOWN IS
INTENDED ONLY TO COMMUNICATE DESIGN INTENT. REFER TO
MECHANICAL AND ELECTRICAL DRAWINGS FOR DETAILED
INFORMATION. NOTIFY ARCHITECT/ENGINEER OF ANY
DISCREPANCIES NOTED PRIOR TO COMMENCEMENT OF WORK.
2. COORDINATE ALL CEILING MOUNTED EQUIPMENT SUPPORTS,
DEVICE LOCATIONS, CLEARANCES, ETC. WITH EQUIPMENT
INSTALLERS AND SUPPLIERS PRIOR TO INSTALLATION.
3. ACOUSTICAL PANEL CEILING GRIDS OR PANELS SHALL BE
CENTERED IN ROOMS UNLESS OTHERWISE NOTED OR
DIMENSIONED.
4. ALL CEILING MOUNTED ITEMS (LIGHT FIXTURES, SPRINKLER
HEADS, ETC.) SHALL BE CENTERED IN ACOUSTICAL CEILING
PANELS OR GYPSUM BOARD SOFFITS UNLESS OTHERWISE NOTED
OR DIMENSIONED.
5. SPACE LIGHT FIXTURES EVENLY IN ROOMS, BAYS, SPACES, ETC.
AND CENTER BETWEEN EXPOSED STRUCTURAL ELEMENTS
WHERE APPROPRIATE.
6. DIMENSIONS TO CEILING-INSTALLED ITEMS ARE TO CENTERLINE
OF FIXTURE OR EQUIPMENT UNLESS NOTED OTHERWISE.
7. LOCATE CONTROL JOINTS IN GYPSUM BOARD CEILINGS, SOFFITS,
BULKHEADS, AND FASCIAS AS INDICATED ON DRAWINGS OR AS
SPECIFIED AND TO ALIGN WITH THOSE IN WALLS BELOW. VERIFY
PROPOSED LAYOUT WITH ARCHITECT PRIOR TO INSTALLATION.
8. PAINT ALL CONDUITS, DUCTWORK, SUPPORTS, HANGERS, ETC.
THAT WILL REMAIN EXPOSED TO VIEW. MATCH COLOR INDICATED
FOR STRUCTURE UNLESS NOTED OTHERWISE.
9. ALL NEW CEILING HEIGHT IS NOTED ON PLAN.
10. EXISTING GYP BD CEILINGS TO REMAIN - PATCH AND PAINT AS
NEEDED TO COORD. W/ NEW WORK. SEE ELECTRICAL AND
MECHANICAL.
11. ACT CEILING WILL INTALL AS "EXISTING", EXCEPT NOTED ON THE
PLAN.
GENERAL CEILING NOTES:
1 ACOUSTICAL CEILING TILE #1 - 24"x24"
CEILING PLAN NOTES:
CEILING LEGEND:
ACTGYP
2 5/8" GYPSUM BOARD SOFFIT - PAINT - SEE FINISH SCHEDULE
3 PENDANT LIGHTS. SEE ELEC.
4 CEILING MOUNTED TRACK FOR SIDE FOLDING SECURITY
GRILLE, SEE SPEC.
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.46.21 www.crwarchitecture.com
CLIENT
1 DD Issue 4/7/2026
2 90% CD Issue 4/21/2026
3 100% CD Issue 4/30/2026
A u to d e s k D o c s
/R P
S J o h n
M a rs h a ll
H S
C o ff e e S h o p /2
-0
J o h n M a rs h a ll H
S C o ff e e
S h o p
.r v t
/3
/2
:5 :0
P
M
A1.00
Jason Woodhouse
44421 4/30/2026
FLOOR AND RCP PLAN
R O
C H
E S
T E
R
M
IN
N E
S O
T A
IS
D
JO
H N
M A
R S
H A
LL
H
IG
H
S C
H O
O L
C O
F F
E E
S H
O P
26-015
4/30/2026
LG
JW
1/4" = 1'-0"
FIRST LEVEL PLAN - AREA 4C
NORTH
1/4" = 1'-0"
FIRST LEVEL CEILING PLAN - AREA 4C
NORTH
F F
R Z
REF
21" 42" x
21" 48" x
1. ALL WORK SHALL BE PERFORMED IN COMPLIANCE WITH ALL
REQUIREMENTS OF THE OWNER. EACH TRADE CONTRACTOR SHALL
BE RESPONSIBLE FOR INITIATING, MAINTAINING AND SUPERVISING
ALL SAFETY PROCEDURES, PRECAUTIONS AND PROGRAMS IN
CONNECTION WITH THEIR WORK.
2. THE GENERAL CONTRACTOR SHALL FILE FOR AND OBTAIN ALL
REQUIRED PERMITS, LETTERS OF SATISFACTORY COMPLETION AND
CERTIFICATES OF OCCUPANCY FROM THE LOCAL BUILDING
OFFICIALS.
3. ALL EQUIPMENT SHOWN AS DASHED IS BY THE OWNER. ELECTRICAL
CONTRACTOR TO VERIFY POWER REQUIREMENTS FOR OWNER'S
EQUIPMENT. MECHANICAL CONTRACTOR TO VERIFY PLUMBING AND
HVAC REQUIREMENTS OF OWNER'S EQUIP.
4. REFER TO THE MECHANICAL, ELECTRICAL DRAWINGS FOR
ADDITIONAL WORK REQUIRED UNDER THIS CONTRACT.
5. THE GENERAL CONTRACTOR AND/OR MECHANICAL CONTRACTOR
SHALL COORDINATE ALL MECHANICAL WORK WITH THE OWNER'S
REPRESENTATIVE AND ALL OTHER TRADES.
6. THE GENERAL CONTRACTOR AND/OR ELECTRICAL CONTRACTOR
SHALL COORDINATE ALL ELECTRICAL WORK WITH THE OWNER'S
REPRESENTATIVE AND ALL OTHER TRADES.
GENERAL NOTES:
1 LINE OF NEW GYP. BD. BULKHEAD ABOVE.
PLAN NOTES:
2 INSTALL NEW RB-1 WALL BASE.
3 TEMPORARY EMERGENCY EXIT DOOR.
4 STAINLESS STEEL END WALL GUARD BY FSC. SEE FOOD
SERVICE PLANS.
5 STAINLESS STEEL CORNER GUARD, SEE FINISH MATERIAL
INDEX.
6 TEMPORARY WALL CONSTRUCTED OF LT. GA. METAL
FRAMING WITH GYP. BD. EACH SIDE AND BATT INSULATION
FROM FLOOR TO ROOF DECK ABOVE
7 INSTALL STAINLESS STEEL REDUCER TRANSITION WHERE
KITCHEN FLOOR FINISH AND EXISTING FLOOR FINISH MEET.
8 SIDE FOLDING SECURITY GRILLE, SEE SPEC.
9 PROVIDE FLOOR LEVELER TO ENSURE THERE IS NO SLOPING.
10 PATCH AND REPAIR TILE WHERE FLOOR CUTTING OCCURED,
MATCH EXISTING.
11 PATCH COMPOSITE SLAB OVER TUNNEL WHERE FLOOR
DRAINS ARE REMOVED AND LEVEL SLOPED FLOOR AROUND
DRAIN.
12 NEW FLOOR DRAIN - SEE MECHANICAL
A2.00 2
A2.00
J4.F
J4.FJ4.F
J4.F
J4.F
2' - 4" 8' - 9" 12' - 10"
23' - 11"
19' - 11" 4' - 0"
/4
/4
A2.01
20' - 8" 3' - 3"
T
J4
J4 34"h
6' - 9 1/4" 5' - 0" 4' - 9 3/4"
/4
/8
4 4
7' - 11 1/8" 12' - 5"
C F
T -1
E X
IS
T
RBS-1EXIST.
COFFEE SHOP
4-104A
CAFETERIA
4-104
T
T
/4
/4
/4
1' - 6" 4 1/4"
EXIST.
R B
S -1
C F
T -1
MIN.
12"
NOTE: GC TO PROVIDE FIRE-
TREATED PLYWD BLOCKING AS
REQUIRED AT EQUIPMENT NOTED
IN FOOD SERVICE PLANS AND
DETAILS
BOYS
4-100G
FINISH MATERIAL INDEX:
ACOUSTICAL MATERIALS
ACT-1 MANUFACTURER: USG,
PRODUCT: KITCHEN LAY-IN PANELS 3210
SIZE: 24"x24"
EDGE: SQUARE
COLOR: WHITE
GRID: 15/16"
CERAMIC FLOOR TILE
CFT-1 DISTRIBUTOR: ERGON
PATTERN: GRAINSTONE, ROUGH GRAIN
SIZE: 60 CM X 60 CM
COLOR: GREY
INSTALL: STACKED
CONTACT: M2i Ltd.; Michael Montorsi: mmontorsi@m2iltd.com
SCHLUTER TRANSITIONS
SCH-1: RENO-V, WHERE NEW FLOOR TILE AND EXISTING
FLOOR MEET
SCH-3: DECO, WHERE THE NEW FLOOR TILE AND NEW COFFEE
SHOP FLOORING MEET
RUBBER SHEET FLOOR
RBS-1 MANUFACTURER: ECO-GRIP
PRODUCT: SLIP RESISTANT SAFETY FLOOR
SIZE: 60"X96"
COLOR: PEWTER
BASE: ROUTED COVED
SCHLUTER TRANSITIONS
SCH-2: RENO-RAMP /-K, WHERE THE NEW COFFEE SHOP
FLOORING AND EXISTING FLOOR MEET
RESILIENT BASE
RB-1 MANUFACTURER: JOHNSONITE
PROFILE: COVED
HEIGHT: 4"
COLOR: BURNT UMBER 63
FIBER REINFORCED PANELS
FRP-1 MANUFACTURER: MARLITE
PRODUCT: SYMMETRIX SMARTSEAM
PATTERN: 6"x3" SUBWAY HORIZONTAL
COLOR: WHITE PANEL W/ GREY GROOVES
PANEL SIZE: 4' X 8'
PAINTS AND COATING
PT-1 MANUFACTURER: SHERWIN WILLIAMS
COLOR: PURE WHITE SW 7005 (FIELD)
PT-2 MANUFACTURER: SHERWIN WILLIAMS
COLOR: CUSTOM COLOR MATCH, RGB: 221 31 38 (ACCENT)
PT-3 MANUFACTURER: SHERWIN WILLIAMS
COLOR: DOVETAIL SW 7018 (ACCENT AND H.M.
DOOR FRAME)
PLASTIC LAMINATES *FOOD SERVICE
PLAM-1 MANUFACTURER: FORMICA
PATTERN: GRAPHITE ELM 5769-NG
QUARTZ *FOOD SERVICE
QTZ-1 MANUFACTURER: DALTILE
PATTERN: SIMPLY GREY OQ30
THICKNESS: 3CM
WALL/CORNER GUARDS *FOOD SERVICE
WG-1 STAINLESS STEEL END WALL GUARD, 2" WINGS X H" * FIELD
VERIFY (FULL HEIGHT OF WALL)
CG-1 STAINLESS STEEL CORNER GUARD, 2" WINGS X H" * FIELD
VERIFY (FULL HEIGHT OF WALL)
KITCHEN EQUIPMENT, SEE
FOOD SERVICE PLANS FOR
FURTHER INFORMATION
PAINT EXISTING ALCOVE
WALLS AND CEILING
PT-1
PAINT EXISTING WALL PT-1
RB-1 WALL BASE
EXISTING MECH.
TO REMAIN
EXIST ROOM SIGN
TO REMAIN
EXISTING CMU WALL TO
REMAIN
PAINT EXISTING
DOOR FRAME, PT-3
EXIST.
4' - 0 +/-
/4
/4
/4
A2.01
PAINT EXISTING CMU
WALL PT-1
PAINT EXISTING CMU
WALL PT-1
PAINT NEW GYP. BD.
SOFFIT PT-3
PAINT SIGNAGE LEDGE AND
SOFFIT CEILING PT-2
KITCHEN EQUIPMENT, SEE
FOOD SERVICE PLANS FOR
FURTHER INFORMATION
SIGNAGE BY OWNER,
PROVIDE ADDITIONAL WALL
BLOCKING FOR MOUNTING
PLAM-1 VERTICAL,
SEE FOOD SERVICE
PLANS FOR FURTHER
INFORMATION
QTZ-1 COUNTERTOPS,
SEE FOOD SERVICE
PLANS FOR FURTHER
INFORMATION
55" DISPLAY PROVIDED
AND INSTALLED BY
OWNER
3' - 3" +/-
EQ. 16' - 1 1/2" EQ.
RB-1 WALL BASE
20' - 8" +/-
PAINT END OF FURRED
WALL PT-1
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.46.21 www.crwarchitecture.com
CLIENT
1 DD Issue 4/7/2026
2 90% CD Issue 4/21/2026
3 100% CD Issue 4/30/2026
A u to d e s k D o c s
/R P
S J o h n
M a rs h a ll
H S
C o ff e e S h o p /2
-0
J o h n M a rs h a ll H
S C o ff e e
S h o p
.r v t
/3
/2
:5 :1
P
M
A2.00
Jason Woodhouse
44421 4/30/2026
ENLARGED FLOOR PLAN
R O
C H
E S
T E
R
M
IN
N E
S O
T A
IS
D
JO
H N
M A
R S
H A
LL
H
IG
H
S C
H O
O L
C O
F F
E E
S H
O P
26-015
4/30/2026
ERS
JW
1/2" = 1'-0"
COFFEE SHOP - ENLARGED PLAN
ROOM FINISH SCHEDULE
Room # Room Title Floor Base
Walls Ceilings(See R.C.P.)
CommentsNorth South East West Type Finish Clg. Ht.
4-104 CAFETERIA EXIST./CFT-1 EXIST./RB-1 EXIST. EXIST./PT-1 EXIST./PT-1 EXIST. EXIST. EXIST. EXIST. PAINT CAFETERIA FACING COFFEE SHOP WALLS AND SOUTH WALL WHERE CMU WAS INFILLED.
4-104A COFFEE SHOP RBS-1 RBS-1 FRP-1/PT-1 FRP-1/PT-1 FRP-1/PT-1 FRP-1/PT-1 ACT-1/GYP. BD. --/PT-2 8'-11"/8'-6" SOFFIT SEE ROUTED COVE DETAIL FOR KITCHEN BASE, 3/A2.01. FRP PANELS, 4'X8' PT-1 ABOVE
NORTH
1/4" = 1'-0"
COFFEE SHOP - MICROWAVE CENTER
1/4" = 1'-0"
COFFEE SHOP - ORDER COUNTER
W6x6 - W1.4xW1.4 WWF NEW CONC. SLAB AND
VAPOR BARRIER - BY G.C.
DOWEL INTO EXISTING SLAB
AT 3'-0" o.c. - MIN. 1 PER SIDE
COMPACTED GRANULAR FILL
W/ NEW VAPOR BARRIER - SEAL
TO EXIST. VAPOR BARRIER
EXIST. COMPACTED GRANULAR
FILL W/ VAPOR BARRIER
S T
A N
D A
R D
H E
IG
H
T
ECO-GRIP FLOORING
ROUTED COVE
ECO-GRIP ADHESIVE
ECO-GRIP FLOORING
ECO-GRIP BASE CAP
ECO-GRIP SEALANT
STAINLESS STAPLE OR
POWDER-COATED
STEEL FASTENER
FRP OR STAINLESS PANEL
ECO-GRIP FLOORING
1 1/2" PHILLIPS #10 STAINLESS STEEL
SCREW WITH LEAD ANCHOR
16 GAUGE, 2" WIDE STAINLESS
STEEL COLLAR ROUTED INTO
THE ECO-GRIP FLOORING
ECO-GRIP SEALANT USED
BETWEEN DRAIN COLLAR AND
ECO-GRIP FLOORING
ECO-GRIP EPOXY ADHESIVE
ECO-GRIP FLOORING
ECO-GRIP EPOXY FLOORING
ECO-GRIP SEALANT
SUBSTRATE
KICKBOARD
PAN FLASHING
METAL THRESHOLD
J4
• 5/8" GYPSUM BOARD
• 3-5/8" STUDS AT 24" o.c.
• 5/8" GYPSUM BOARD
WALL
TYPE
'AS INDICATED IN DIAGRAM ABOVE'
TYPICAL INTERIOR PARTITION, METAL FRAMED
PROPRIETARY DESIGN FIRE RATING/TEST:(WHERE APPLICABLE)
1/2 HOUR RATING - GA FILE NO. WP 0703
TEST: UL R3501, 12CA09542, 03-28-12,
UL Design W411
GYPSUM WALLBOARD, METAL STUDS
Fire Design:
One layer 5/8” proprietary gypsum wallboard applied parallel or at right angles to each side of 3-5/8", 15 mil steel studs 24" o.c. iwth 1" Type S screws 8" o.c.
Vertical joints centered over studs and staggered one stud cavity each side. Horizontal joints need not be staggered or backed.
(NLB)
Thickness: 4-7/8” (Fire and Sound)
Approx. Weight:
Fire Test: UL R3501, 12CA09542, 03-28-12, UL Design W411
5 psf (Fire and Sound)
STC SOUND RATING/TEST:
STC: 45 - 49
SOUNT TEST: NGC 2014005,
02-18-14
J4 A
J4
4 7/8"
'J4' PARTITIONS TO RECEIVE
SOUND BATT INSULATION NOTED
J4 A
GA FILE NO.
WP 0703
PROPRIETARY 1/2 HOUR FIRE
J6 'AS INDICATED IN DIAGRAM ABOVE W/ 2x6 STUDS IN LIEU OF 2x4 STUDS' (SEE EXPLANATORY NOTE 17 OF GA-600-2024)
J4.f 'AS INDICATED IN DIAGRAM ABOVE MINUS 5/8" GYPSUM BOARD ON ONE SIDE' J6.f 'AS INDICATED IN DIAGRAM ABOVE MINUS 5/8" GYPSUM BOARD ON ONE SIDE AND W/ 2x6 STUDS IN LIEU OF 2x4 STUDS'
(SEE EXPLANATORY NOTE 17 OF GA-600-2024)
45 TO 49 STC
SOUND
Sound Design:
Sound tested with 3-1/2" glass fiber insulation friction fit into stud cavity.
PROPRIETARY GYPSUM PANEL PRODUCTS
National Gypsum Company
- 5/8" Gold Bond® High Strength Fire-Shield 30® Gypsum Board
Sound Test: NGC 2014005, 02-18-14
FIRST LEVEL
100' - 0"
AREA 4 ROOF DECK
113' - 11 3/4"
4' - 1 3/8" 6"
EXIST. TECTUM ROOF DECK
EXIST. STEEL BAR JOISTS
3-5/8" x 18 GA. MIN. AT 16" O.C. METAL
STUD, EXTEND FRAMING TO
STRUCTURE ABOVE
(DESIGNATION: 362S162-43)
5/8" GYP. BD.
3-5/8" METAL STUD
5/8" GYP. BD.
ACT-1 CEILING
SEE PLAN
3 5/8" x 16 GA. TRACK - 3" LEGS
(DESIGNATION : 362T300-54)
METAL CLIP TRACK
A2.01
EXTEND FRAMING TO STRUCTURE
ABOVE, LATERALLY BRACE EVERY
8'-0" O.C.
SUPPORT CROSS MEMBER ON
BOTTOM JOIST CHORD NEAR PANEL
POINT - SECURE WITH
MANUFACTURERS'S STANDARD CLIP
(2) LAYERS 5/8" GYP. BD.
LATERALLY BRACE SOFFIT AT 4'-0" ON
CENTER WITH 3 5/8" x 18 GA STUD -
ALTERNATE BRACE DIRECTIONS
(4) #12 TEK SCREWS EACH BRACE CONNECTION
3 1/2" x 18 GA. METAL STUDS AT 16" O.C.
3"x3"x16GA ANGLE - (1) #12 TEK SCREW
TO EACH STUD AND TO LATERAL
MEMBER
6" x 16 GA. STUD (600S162-54) LATERAL
WITHIN 12" OF EACH JOIST BOTTOM
CHORD PANEL POINT
CORNER GUARD BY FSC
CORNER GUARD BY FSC
/2
STEEL BRACKET AT 16" O.C.
3x3 STEEL TUBE
3 5/8" x 18 GA. METAL STUDS AT 16" O.C.
SECURITY GRILLE TRACK
SECURITY GRILLE POCKET
SECURITY GRILLE
EXISTING TECTUM ROOF CONSTRUCTION
3-5/8" METAL STUD
3" METAL LEGS - 16 GA. TRACK
16 GA C.R. BRIDGING
CHANNEL AS REQ'D BY
MANUFACTURER FOR
HEIGHT LIMITS
ELEV.= 13' - 8 3/4"±
AREA 4 ROOF DECK
VERIFY
(2) #12 TEK SCREWS TRACK TO
EACH DECK FLUTE
(1) #12 TEK SCREWS EACH STUD TO
TRACK
PLAN TEMPORARY CONSTRUCTION WALL
T
1 LAYER GYP. BOARD - WOOD STUD WITH
BATT INSULATION - VAPOR BARRIER
EXTEND FROM FLOOR TO ROOF DECK
SHEET NUMBER
ISSUE/REVISION HISTORY
CHECKED BY
DRAWN BY
DATE
PROJECT
NUMBER
NUMBER DATE
OF SHEETS
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION, OR REPORT WAS
PREPARED BY ME OR UNDER MY
DIRECT SUPERVISION AND THAT I
AM A DULY LICENSED ARCHITECT
UNDER THE LAWS OF THE STATE OF
MINNESOTA.
© 2026 CRW architecture + design group
No. ISSUED FOR DATE
211 11th ave nw rochester, mn 55901
p. 507.206.6201
f. 507.206.46.21 www.crwarchitecture.com
CLIENT
1 DD Issue 4/7/2026
2 90% CD Issue 4/21/2026
3 100% CD Issue 4/30/2026
A u to d e s k D o c s
/R P
S J o h n
M a rs h a ll
H S
C o ff e e S h o p /2
-0
J o h n M a rs h a ll H
S C o ff e e
S h o p
.r v t
/3
/2
:5 :1
P
M
A2.01
Jason Woodhouse
44421 4/30/2026
DETAILS
R O
C H
E S
T E
R
M
IN
N E
S O
T A
IS
D
JO
H N
M A
R S
H A
LL
H
IG
H
S C
H O
O L
C O
F F
E E
S H
O P
26-015
4/30/2026
LG
JW
3" = 1'-0"
SLAB ON GRADE INFILL DETAIL
6" = 1'-0"
ROUTED COVE DETAIL
6" = 1'-0"
FLOOR DRAIN DETAIL
6" = 1'-0"
FLOOR TRANSITION TO EXTERIOR DOOR
1" = 1'-0"
SOFFIT DETAIL
1 1/2" = 1'-0"
METAL STUD AT EXISTING CONSTRUCTION
MECHANICAL SYMBOLS LEGEND
DESIGNATIONSSYMBOLDESIGNATIONSSYMBOLDESIGNATIONSSYMBOL DESIGNATIONSSYMBOL
PLUMBING
ACID VENT
ACID WASTE
DEIONIZED WATER SUPPLY
FILTERED WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER (TEMP. INDICATED)
DOMESTIC RECIRC. HOT WATER
HARD COLD WATER
OVERFLOW STORM DRAIN
REVERSE OSMOSIS WATER
SANITARY VENT
SANITARY WASTE
SOIL DRAINAGE TILE
SOFTENED COLD WATER
SOFTENED HOT WATER
TEMPERED WATER
STORM DRAIN
WELL WATER
AV
AW
DIS
140 HW
HARD
SDT
RO
V
W
SCW
SHW
TW
OSD
SD
WW
NPCW NON-POTABLE COLD WATER
NPHW NON-POTABLE HOT WATER
FW
HW
RHW
GW GREASE WASTE
DOMESTIC COLD WATERCW
CLEAR WATER VENTCWV
CLEAR WATER WASTECWW
DOM. RECIRC. HOT WATER (TEMP. INDICATED)140 RHW
PUMPED ACID WASTEPAW
PUMPED STORM DRAINPSD
PUMPED WASTEPW
COMPRESSED AIR (PSI INDICATED)10#A
MECHANICAL PIPING
BOILER FEED
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
FUEL OIL SUPPLY
FUEL OIL RETURN
FUEL OIL VENT
FUEL OIL FILL
GLYCOL SUPPLY
GLYCOL RETURN
HEAT RECOVERY SUPPLY
HEAT RECOVERY RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
LIQUEFIED PETROLEUM GAS
NATURAL GAS (PSI INDICATED)
PUMPED CONDENSATE
RADIATION WATER SUPPLY
RADIATION WATER RETURN
REFRIGERANT LIQUID
BF
CWS
CWR
CD
FOS
GS
GR
HRS
HRR
HWR
HWS
LPG
2#G
FOF
PC
RADS
CS
CR
FOR
FOV
RADR
RL
REFRIGERANT SUCTION
REFRIGERANT HOT GAS BYPASS
REHEAT WATER SUPPLY
REHEAT WATER RETURN
REMOTE RADIATOR SUPPLY
REMOTE RADIATOR RETURN
SECONDARY HEATING WATER SUPPLY
SECONDARY HEATING WATER RETURN
SNOW MELT SUPPLY
SNOW MELT RETURN
STEAM SUPPLY (PSI INDICATED)
STEAM CONDENSATE (PSI INDICATED)
RRS
RS
RHG
RHR
RHS
RRR
SHWS
SHWR
SMS
SMR
10#STM
10#SC
PIPE FITTINGS
ELBOW DOWN
PIPE CAP
ELBOW UP
TEE, OUTLET UP
TEE, OUTLET DOWN
CONNECTION, TOP
ECCENTRIC REDUCER
CONCENTRIC REDUCER
MEDICAL GAS
MEDICAL VACUUM
WASTE ANESTHETIC GAS DISPOSAL
CARBON DIOXIDE
OXYGEN
NITROGEN
NITROUS OXIDE
MEDICAL AIR
WAGD
CO2
O
N
MV
N2O
MA
PIPE UNION
PIPE FLANGE
ELBOW
TEE
FIRE PROTECTION
DFP
F FIRE PROTECTION
FIRE PROTECTION (DRY SYSTEM)
POST INDICATOR VALVE (PIV)
RECESSED FIRE DEPT CABINET
SURFACE MOUNTED FIRE DEPT CABINET
FIRE PROTECTION RISER
UPRIGHT SPRINKLER HEAD W/GUARD
PENDANT SPRINKLER HEAD
UPRIGHT SPRINKLER HEAD
SIDEWALL SPRINKLER HEAD
BUTTERFLY VALVE W/TAMPER SWITCH
DETECTOR CHECK W/BYPASS METER
GRADE FIRE DEPT CONNECTION
FLUSH FIRE DEPT CONNECTION
FIRE DEPT VALVE W/CAP AND CHAIN
O.S. & Y. VALVE W/TAMPER SWITCH
DRY PIPE VALVE
PREACTION VALVE
TS
FDVC
FDVC
FDV
TS
ANNOTATION
(4)A-12"ø
GRILLE, REGISTER, &
DIFFUSER IDENTIFICATION
QUANTITY
CFM
TYPE
SIZE
X X
X X
X X
X X
DETAIL NUMBER
SHEET NUMBER
SECTION NUMBER
SHEET NUMBER
EQUIP DESIGNATION
EQUIP NUMBER
POINT OF CONNECTION, NEW TO EXISTING
POINT OF DISCONNECTION
FTR/RP 01
6'-5"
0.5
HYDRONIC FINNED TUBE
RADIATION & RADIANT
PANEL IDENTIFICATION
TYPE ACTIVE
ELEMENT
LENGTHGPM
EBR 01
6'-5"
ELECTRIC BASEBOARD
RADIATION
IDENTIFICATION
ACTIVE
ELEMENT
LENGTH
ZONE VALVE BOXZVB
AREA ALARM PANELAAP
COMBINATION AREA/MASTER ALARM
PANEL
CAP
TYPE
INTERRUPTIBLE GASIG
PROCESS AND LABORATORY
LABORATORY AIR
LABORATORY VACUUM
ARGON
PROCESS WASTE
NITROGEN
HOUSE VACUUM
LV
AR
PRW
LA
N
HV
PROCESS VACUUMPV
INSTRUMENT AIRIA
ATMOSPHERIC STEAM SUPPLY
ATMOSPHERIC STEAM CONDENSATE
ATM STM
ATM SC
CONNECTION, BOTTOM
DARK DASHED LINE WEIGHT INDICATES
EXISTING ITEM TO BE DEMOLISHED.
GENERAL
LIGHT SOLID LINE WEIGHT INDICATES
EXISTING ITEM TO REMAIN.
DARK SOLID LINE WEIGHT INDICATES
NEW ITEM OR NEW LOCATION.
ROUND
12x12
12ø 12/12
RECTANGULAR (WxH)
FLAT-OVAL (W/H)
DUCT
DIMENSIONS
LIQUID NITROGENLN
MASTER ALARM PANELMAP
XXXX #-## EXISTING EQUIP NUMBER
EXISTING EQUIP DESIGNATION
MECHANICAL ABBREVIATIONS
AD AREA DRAIN
AFF ABOVE FINISHED FLOOR
AFMS AIR FLOW MEASURING STATION
AHU AIR HANDLING UNIT
ANB ACID NEUTRALIZING BASIN
AP ACCESS PANEL
ARCH ARCHITECT
AS AIR SEPARATOR
BD BUTTERFLY DAMPER
B/G BELOW GRADE
BTU BRITISH THERMAL UNIT
BWV BACKWATER VALVE
CCF HUNDRED CUBIC FEET
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CL CENTER LINE
CLG CEILING
CO CLEAN OUT
CONTR CONTRACTOR
CONV CONVECTOR
CUH CABINET UNIT HEATER
CW COLD WATER
DB DECIBEL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIFF DIFFUSER
DISCH DISCHARGE
DMPR DAMPER
DN DOWN
DR DRAIN
DSN DOWNSPOUT NOZZLE
DWG DRAWING
EAT ENTERING AIR TEMPERATURE
EDR EQUIVALENT DIRECT RADIATION
EP ELECTRIC-PNEUMATIC
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXP EXPANSION
F FAHRENHEIT
FC FAN COIL
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FHC FIRE HOSE CABINET
FHR FIRE HOSE RACK
FLR FLOOR
FLEX FLEXIBLE
FM FIRE MAIN
FPM FEET PER MINUTE
FPS FEET PER SECOND
FT FEET OR FOOT
F&T FLOAT AND THERMOSTATIC
FTG FOOTING
FTR FINNED TUBE RADIATION
FV FACE VELOCITY
GA GAUGE
GAL GALLON
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
HB HOSE BIBB
HD HEAD
HOA HANDS-OFF-AUTOMATIC
HTG HEATING
HTR HEATER
HVAC HEATING, VENTILATION,
AND AIR CONDITIONING
HYD HYDRANT
HW HOT WATER
GCO GRADE CLEANOUT
INSUL INSULATION
KW KILOWATT
LAT LEAVING AIR TEMPERATURE
LAV LAVATORY
LWT LEAVING WATER TEMPERATURE
MBH BTU PER HOUR (THOUSANDS)
MCF THOUSAND CUBIC FEET
MH MANHOLE
NC NOISE CRITERIA OR
NORMALLY CLOSED
NEG NEGATIVE
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP OR DIFFERENCE
PE PNEUMATIC-ELECTRIC
PLBG PLUMBING
PRV PRESSURE REDUCING VALVE
OR POWER ROOF VENTILATOR
PSIA POUNDS/SQ INCH ABSOLUTE
PSIG POUNDS/SQ INCH GAUGE
PVC POLY VINYL CHLORIDE
RA RETURN AIR
RCP REINFORCED CONCRETE PIPE
RD ROOF DRAIN
RECIRC RECIRCULATING
REG REGISTER
RET RETURN
RH RELATIVE HUMIDITY
RHT REHEAT
RHC REHEAT COIL
RHW RECIRCULATED HOT WATER
RM ROOM
RPM REVOLUTIONS PER MINUTE
RPZ
REDUCED ZONE BACKFLOW
PREVENTER
SA SUPPLY AIR
SAN SANITARY
SCFM CFM, STANDARD CONDITIONS
SD SMOKE DAMPER
SP STATIC PRESSURE
SPECS SPECIFICATIONS
SUP SUPPLY
SQ SQUARE
STM STEAM
TD TEMPERATURE DIFFERENCE
TEMP TEMPERATURE
TONS TONS OF REFRIGERATION
T-STAT THERMOSTAT
TYP TYPICAL
UB UP-BLAST
UG UNDERGROUND
UH UNIT HEATER
UR URINAL
V SANITARY VENT
VD VOLUME DAMPER
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W SANITARY WASTE
W/ WITH
WC WATER CLOSET
WCO WALL CLEANOUT
WH WALL HYDRANT
W/O WITHOUT
WTR WATER
GR GRILLE
VAV VARIABLE AIR VOLUME
VTR VENT THROUGH ROOF
INV INVERT
RLF RELIEF
ISO ISOLATION EXHAUST
GEXH GREASE EXHAUST
RH ROOF HYDRANT
YCO YARD CLEANOUT
ZDL ZERO DEADLEG VALVE
AUTOMATIC AIR VENT
AUTOMATIC CONTROL VALVE, 2-WAY
AUTOMATIC CONTROL VALVE, 3-WAY
STRAINER W/BLOWDOWN
CAP AND VALVE
PIPE SPECIALTIES
FLEXIBLE CONNECTION
PIPE ANCHOR
ALIGNMENT GUIDE
STRAINER
PRESSURE REDUCING VALVE
(SETTING AS NOTED, PSI)
EXPANSION JOINT
MANUAL AIR VENT
PRESSURE RELIEF/SAFETY
VALVES(SETTING AS NOTED, PSI)
DRAIN VALVE
REDUCED PRESSURE ZONE BACK
FLOW PREVENTER
DIAPHRAGM
REFRIGERANT SIGHT GLASS
GAS PRESSURE REGULATOR VALVE
BACKWATER VALVE
REFRIGERANT DRYER
FLOW DIRECTION
FLOW DIRECTION W/PITCH
DUPLEX STRAINER
PUMP
THERMOMETER
PRESSURE/TEMPERATURE TEST PORT
STEAM TRAP (TYPE INDICATED)
FLOW SWITCH
PRESSURE GAUGE W/PIGTAIL &
PETCOCK
PRESSURE SWITCH
FLOOR DRAIN
DRAIN ABOVE
FLOOR SINK
WALL HYDRANT
HOSE BIBB
WALL CLEANOUT
ROOF DRAIN
MANHOLE
HB
A
M
FS
PS
GAS COCK VALVE
WH
DEIONIZED WATER RETURNDIR
CLEAN DRY AIRCDA
REVERSE OSMOSISRO
CONTROLS
AQUA STAT
TAMPERPROOF THERMOSTAT
HUMIDISTAT OR R.H. SENSOR
REFRIGERANT SENSOR
SMOKE DETECTOR
SPACE TEMPERATURE SENSOR
STATIC PRESSURE SENSOR
ROOM PRESSURE MONITOR
THERMOSTAT
THERMOSTAT W/GUARD
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
DIFFERENTIAL PRESSURE SENSOR
TEMPERATURE SENSOR
A
CO2
CO
H
R
P
SD
TS
SP
PS
T
T
T
DP
TS
P
DUCTWORK
SUPPLY AIR OR OUTDOOR AIR
RETURN AIR
EXHAUST AIR
STANDARD BRANCH, NO SPLITTER -
SUPPLY FLOW TO RIGHT -
RETURN/EXHAUST FLOW TO LEFT
BELLMOUTH WITH BALANCING
DAMPER
FLEXIBLE DUCT
TURNING VANES
FLEXIBLE CONNECTION
MANUAL VOLUME DAMPER
MOTORIZED DAMPER
TYPE:
FD = FIRE DAMPER
SD = SMOKE DAMPER
FSD = COMBINATION FIRE/SMOKE
DAMPER
CRD = CEILING RADIATION DAMPER
ORIENTATION:
SUPPLY GRILLE OR REGISTER
RETURN DUCT UP, NEGATIVE
PRESSURE
SUPPLY DIFFUSER/REGISTER
BLANKOFF INDICATED
RETURN OR EXHAUST GRILLE OR
REGISTER
SUPPLY DUCT UP, POSITIVE
PRESSURE
EXHAUST DUCT UP, NEGATIVE
PRESSURE
RETURN GRILLE/REGISTER
EXHAUST GRILLE/REGISTER
LINEAR DIFFUSER
CONCENTRIC DUCT TRANSITION
ECCENTRIC DUCT TRANSITION
RECTANGULAR-TO-ROUND DUCT
TRANSITION
VAV BOX
REHEAT COIL
VAV BOX W/ REHEAT COIL
DUCT OFFSETS
DUCT CUTLINE
M
XXX
RETURN DUCT DN, NEGATIVE
PRESSURE
SUPPLY DUCT DN, POSITIVE
PRESSURE
EXHAUST DUCT DN, NEGATIVE
PRESSURE
DROPRISE
VERTICAL
XXX
XXX
XXX
ACTUATOR (AS
APPLICABLE)
HORIZONTAL
BLADE/CURTAIN
FIRE, SMOKE, AND
COMBINATION
FIRE/SMOKE DAMPERS
TYPE
ORIENTATION
AIRFLOW MEASURING STATIONAFMS
VAV BOX W/ DUCT SILENCER
VENTURI TYPE AIR…
This is the start of the file's text. The full file is on GovTribe.