Summary of Aluminum Box Culvert Plans for Moyer Road Culvert Replacement
This document is a comprehensive set of technical construction plans and specifications prepared by Contech Engineered Solutions for the manufacture and installation of an aluminum box culvert (ALBC) structure in West Hanover Township, Dauphin County, Pennsylvania. The project involves the installation of a single #4R1 aluminum box culvert with a 10-foot span, 4-foot-10-inch rise, and 40-foot-6-inch length, designed to comply with AASHTO LRFD bridge design specifications and ASTM standards for corrugated aluminum alloy structural plate. The structure includes fish baffles (6 required), a full aluminum invert plate system, corrugated headwalls at both inlet and outlet ends measuring 13 feet-6 inches in width, reinforcing ribs, and associated deadman anchors. The design is based on HL-93 vehicle live loads, minimum soil cover of 1.5 feet, maximum cover of 2.5 feet, and assumes a design net allowable bearing capacity of 4,000 PSF and engineered backfill material unit weight of 120 pounds per cubic foot.
The plans establish critical construction procedures including assembly tolerances requiring the structure's span and rise to be within 2 percent of plan dimensions and length within 1 percent. Engineered backfill material must meet AASHTO soil classifications A-1, A-2-4, or A-2-5 per AASHTO M-145, placed in 8-inch loose lifts and compacted to 90 percent density using hand-operated equipment within 1 foot laterally of the structure's widest section. The specifications require electrochemical properties for backfill and water with pH between 4 and 9 and resistivity exceeding 500 ohm-cm, with geotextile protection required in multiple applications to prevent fine infiltration. Pre-construction conferences, periodic structure shape monitoring during backfill placement, and compliance with restrictions on construction equipment weight (maximum 10 tons static mass within 5 feet of the structure until minimum cover is achieved) are mandatory. The document prohibits the use, reproduction, or copying of the drawings without prior written permission from Contech Engineered Solutions and requires immediate notification to the manufacturer if unexpected site soil conditions are encountered or if construction vehicles heavier than the design live load must cross the structure.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2-2026.10.13 SLEEPY HOLLOW AND MOYER RD CULVERTS.pdf | ||
| 1-2026.10.13 sealed WHT Culverts Project Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES:
1. THIS SPECIFICATION COVERS THE MANUFACTURE AND INSTALLATION OF THE
ALUMINUM BOX CULVERT (ALBC) STRUCTURE AS DETAILED IN THE PLANS. ANY
INSTALLATION INFORMATION PROVIDED HEREIN SHALL BE REVIEWED AND APPROVED
BY THE ENGINEER. CHANGES AND DISCREPANCIES MUST BE FORWARDED TO THE
MANUFACTURER TO BE INCORPORATED IN A REVISED DRAWING SET.
2. THE ENGINEER SHALL VERIFY THAT THE PROPOSED STRUCTURE IS APPROPRIATE FOR
THE SITE CONDITIONS AND THE DESIGN PARAMETERS ARE CONSISTENT WITH THE
PROJECT REQUIREMENTS. ALL ASPECTS OF THE STRUCTURE DESIGN AND SITE
LAYOUT NOT EXPLICITLY INCLUDED IN THESE DRAWINGS SHALL BE PROVIDED OR
COORDINATED BY THE ENGINEER. THIS MAY INCLUDE BUT IS NOT LIMITED TO:
FOUNDATIONS, BACKFILL, END TREATMENTS, HYDRAULIC ANALYSIS AND SCOUR
ANALYSIS AS REQUIRED.
3. CONTECH PRODUCT DRAWINGS MAY NOT BE USED, REPRODUCED, COPIED, OR
ISSUED TO A THIRD PARTY WITHOUT THE PRIOR WRITTEN PERMISSION OF CONTECH
ENGINEERED SOLUTIONS.
4. ALL DIMENSIONS ARE TO THE INSIDE CREST OF THE CORRUGATION PROFILE UNLESS
NOTED OTHERWISE AND ARE SUBJECT TO MANUFACTURING TOLERANCES.
5. THE STRUCTURE GEOMETRY, DESIGN, AND MATERIALS AS SHOWN IN THESE
DRAWINGS ONLY APPLY TO THE ALBC, DESIGNED AND FABRICATED BY CONTECH
ENGINEERED SOLUTIONS (CONTECH). ALTERNATIVE SYSTEMS SHALL BE FULLY
DESIGNED AND APPROVED PRIOR TO BIDDING, WITH SEALED DRAWINGS AND
CALCULATIONS PROVIDED TO DEMONSTRATE COMPLIANCE WITH THE SAME
GEOMETRY, DESIGN, AND MATERIAL REQUIREMENTS AS SHOWN HEREIN.
6. CIRCUMFERENTIAL PLATE LENGTHS ARE IN TERMS OF N = 9.625 INCHES.
7. FOR WATER CONVEYANCE APPLICATIONS THE STRUCTURE MUST MEET HYDRAULIC
REQUIREMENTS OF THE SITE AS DETERMINED BY THE ENGINEER. SHEET PILING,
INLET AND OUTLET APRONS, CUTOFF WALLS, RIP RAP, AND/OR OTHER MEASURES
SHALL BE INSTALLED AS NECESSARY TO PREVENT LOSS OF ENGINEERED BACKFILL
AND/OR FOUNDATION SOILS DUE TO SCOUR. THE EXTENT, SIZE, AND LOCATION OF
SCOUR PROTECTION SHALL BE DETERMINED BY THE ENGINEER.
8. PERIMETER DRAINAGE, SURFACE DRAINAGE, AND GRADING AROUND THE STRUCTURE
SHALL BE DESIGNED, SPECIFIED, SUPPLIED, AND INSTALLED BY OTHERS.
DESIGN PARAMETERS
1. DESIGN BY CONTECH ENGINEERED SOLUTIONS IS BASED ON THE FOLLOWING DESIGN
CRITERIA:
VEHICLE LIVE LOAD:HL-93
MINIMUM COVER: 1.5'
MAXIMUM COVER: 2.5'
UNIT WEIGHT OF ENGINEERED BACKFILL = 120 LBS/FT³.
2. ENGINEERED BACKFILL MATERIAL SHALL COMPLY WITH THE ENGINEERED BACKFILL
MATERIAL REQUIREMENTS SHOWN IN THESE DRAWINGS.
3. DESIGN COVER AND LATERAL EXTENT OF ENGINEERED BACKFILL ZONE SHALL BE AS
SHOWN IN THESE DRAWINGS AND REQUIRED BY THE DESIGN STANDARDS
REFERENCED IN THESE NOTES.
4. REFERENCE AASHTO LRFD SECTION 12.6.1 FOR SEISMIC DESIGN CONSIDERATIONS.
5. STRUCTURE DESIGN BASED ON SITE SOIL INFORMATION PROVIDED IN CONTRACT
DOCUMENTS. IF UNEXPECTED SITE SOIL CONDITIONS ARE ENCOUNTERED, CONTECH
MUST BE NOTIFIED TO DETERMINE IF DESIGN CHANGES ARE NEEDED.
6. TEMPORARY CONSTRUCTION VEHICLE LOADING HEAVIER THAN THE DESIGN VEHICLE
LIVE LOAD SHALL NOT BE PERMITTED TO CROSS OVER THE STRUCTURE WITHOUT THE
APPROVAL OF CONTECH. IT IS THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY
CONTECH OF THE SIZE, TYPE AND WEIGHT OF ANY CONSTRUCTION VEHICLES
INTENDED TO CROSS OVER THE STRUCTURE.
7. STANDARD HIGHWAY LOADS THAT MEET PERMISSIBLE DESIGN LOAD LIMITS FOR AN
ALBC ARE NOT ALLOWED ON THE STRUCTURE UNTIL IT IS BACKFILLED COMPLETELY
AND PAVEMENT IS IN PLACE.
8. IT IS RECOMMENDED THAT UNPAVED ROADS INCORPORATE AT LEAST 6" MORE THAN
MINIMUM ALLOWABLE COVER DEPTH TO ALLOW FOR RUTTING.
HAUNCH REINFORCING RIB
RIB SPLICE
CROWN REINFORCING RIB
INVERT CORNERS OF HAUNCH
PLATES PAINTED RED
RECEIVING CHANNEL
SEE DETAIL J
TOEWALL BOTH ENDS
15N - MK. C
INVERT PLATE 10'-0"
4' -1
0"
JSC
CHECKED:
DRAWN:
DESIGNED:
APPROVED:
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
SHEET NO.:
OF 18
3/9/2026 DATE:PROJECT No.:
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
MOYER ROAD CULVERT REPLACEMENT - WEST HANOVER TOWNSHIP
1REVISION DESCRIPTIONDATEMARK BY
700 Tech Drive, Winchester, KY 40391
859-744-3339 859-744-9665 FAX
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE THICKNESS: .125 (H)/.125(C)
REINFORCING RIB SPACING: AS SHOWN
REINFORCING RIB TYPE: AS SHOWN
NUMBER OF STRUCTURES: 1
ALUMINUM BOX CULVERT
MOYER ROAD CULVERT REPLACEMENT - WEST HANOVER TOWNSHIP
DAUPHIN COUNTY, PENNSYLVANIA
STRUCTURE CROSS-SECTION
REFER TO SHEET 17 FOR MINIMUM LIMITS OF ENGINEERED BACKFILL ENVELOPE
1. DESIGN AND MANUFACTURING STANDARDS
1.1 STANDARDS - ALL STANDARDS REFER TO THE CURRENT ASTM / AASHTO EDITION UNLESS
OTHERWISE NOTED.
1.2 AASHTO M219 - STANDARD SPECIFICATION FOR CORRUGATED ALUMINUM ALLOY STRUCTURAL
PLATE FOR FIELD-BOLTED PIPE, PIPE-ARCHES AND ARCHES
1.3 AASHTO LRFD BRIDGE DESIGN SPECIFICATIONS SECTION 12.
1.4 AASHTO LRFD BRIDGE CONSTRUCTION SPECIFICATIONS - SECTION 26.
1.5 ASTM B864 - STANDARD SPECIFICATION FOR CORRUGATED ALUMINUM BOX CULVERTS.
2. DEFINITIONS
2.1 ENGINEER - IN THESE NOTES THE WORD “ENGINEER” SHALL MEAN THE ENGINEER OF RECORD OR
OWNER'S DESIGNATED ENGINEERING REPRESENTATIVE.
2.2 MANUFACTURER - IN THESE NOTES THE WORD “MANUFACTURER” SHALL MEAN THE
MANUFACTURER OF THE ALBC, CONTECH ENGINEERED SOLUTIONS @ PHONE 800/338-1122.
2.3 CONTRACTOR - IN THESE NOTES THE WORD “CONTRACTOR” SHALL MEAN THE FIRM OR
CORPORATION UNDERTAKING THE EXECUTION OF ANY INSTALLATION WORK UNDER THE TERMS OF
THESE SPECIFICATIONS.
3. ALUMINUM BOX CULVERT (ALBC) STRUCTURE ASSEMBLY
3.1 ASSEMBLY OF THE ALBC SHALL BE IN ACCORDANCE WITH SECTION 26 OF AASHTO LRFD
CONSTRUCTION SPECIFICATIONS (LATEST EDITION, WITH INTERIMS) AND ANY SUPPLEMENTAL
RECOMMENDATIONS PROVIDED BY THE MANUFACTURER.
3.2 ALL PLATES AND ACCESSORIES SHALL BE UNLOADED AND HANDLED WITH REASONABLE CARE.
PLATES SHALL NOT BE ROLLED OR DRAGGED OVER GRAVEL ROCK AND SHALL BE PREVENTED FROM
STRIKING ROCK OR OTHER HARD OBJECTS DURING PLACEMENT IN TRENCH OR ON BEDDING.
3.3 FOR STRUCTURES SET ON CONCRETE FOOTINGS, PLATE ASSEMBLY CAN BEGIN AFTER PLACEMENT
OF STRUCTURE FOOTINGS HAS BEEN APPROVED BY THE ENGINEER. VERIFICATION OF PROPER
SPACING, ALIGNMENT, AND ORIENTATION OF THE FOUNDATIONS IS STRONGLY RECOMMENDED
PRIOR TO BEGINNING PLATE ASSEMBLY. ANY MODIFICATIONS TO THE FOUNDATIONS SHALL BE
MADE PRIOR TO BEGINNING PLATE ASSEMBLY.
3.4 WHEN A METAL FOUNDATION IS USED, THE SOIL BEDDING REQUIRES A MINIMUM OF 6 INCHES OF
LOOSE GRANULAR MATERIAL WITH A MAXIMUM PARTICLE SIZE OF ONE HALF THE CORRUGATION
DEPTH. THE PROPER WIDTH OF THE BEDDING MATERIAL REQUIRED SHALL CONFORM TO THE
PROJECT PLANS AND SPECIFICATIONS.
BEDDING PREPARATION SHOULD BE APPROVED BY THE ENGINEER PRIOR TO ASSEMBLY. THE BED
SHOULD BE CONSTRUCTED TO UNIFORM LINE AND GRADE. IT SHOULD BE FREE OF ROCK
FORMATIONS, PROTRUDING STONES, FROZEN LUMPS, ROOTS AND OTHER FOREIGN MATTER.
3.5 THE SPAN AND RISE OF THE STRUCTURE SHOULD BE CHECKED FREQUENTLY DURING THE EARLY
STAGES OF ASSEMBLY TO VERIFY THAT ASSEMBLY TOLERANCES ARE BEING ACHIEVED AND TO
ALLOW FOR ADJUSTMENTS TO PROCEDURES, IF NECESSARY, BEFORE ASSEMBLY IS COMPLETE.
3.6 CUT PLATES FOR SKEWED ENDS SHOULD BE ATTACHED AFTER THE MAIN BARREL OF A STRUCTURE
HAS BEEN ASSEMBLED. WHEN CAST-IN-PLACE CONCRETE COLLARS OR HEADWALLS ARE TO BE
CONSTRUCTED, THE CONTRACTOR MUST ALLOW FOR FORMWORK TO BE ERECTED ON THE END OF
THE STRUCTURE. FORMING AGAINST A SKEWED CORRUGATION PROFILE IS COMPLEX AND SHOULD
BE ACCOUNTED FOR BY THE FORMING CONTRACTOR WHEN PLANNING PROCEDURES AND
METHODS FOR FORMWORK CONSTRUCTION. IN SOME CASES, FIELD TRIMMING OF THE
STRUCTURE MAY BE NECESSARY. SPECIAL BRACING AND/OR SCAFFOLDING (DESIGN BY OTHERS) IS REQUIRED TO SUPPORT SKEWED ENDS UNTIL ADEQUATE COMPRESSIVE STRENGTH IS ACHIEVED AS
REQUIRED BY THE COLLAR/HEADWALL DESIGNER.
3.7 NUTS SHALL BE PLACED WITH THE ROUNDED FACE IN CONTACT WITH THE PLATES UNLESS NOTED OTHERWISE. NUTS CAN BE ON EITHER THE INSIDE OR OUTSIDE OF THE STRUCTURE TO FACILITATE
ASSEMBLY.
3.8 BOLTS AND NUTS SHALL CONFORM TO THE REQUIREMENTS OF ASTM A-307 and/or ASTM A-449.
RECOMMENDED TORQUE RANGE ON THE BOLTS IS 100 TO 150 FT-LBS.
3.9 INSIDE SPAN AND RISE OF THE ASSEMBLED STRUCTURE AFTER BOLTING SHALL BE WITHIN 2% OF
THE PLAN DIMENSIONS. THE STRUCTURE LENGTH SHALL BE WITHIN 1%.
4. ENGINEERED BACKFILL ENVELOPE
4.1 ENGINEERED BACKFILL MATERIAL SHALL BE PLACED WITHIN THE ENGINEERED BACKFILL ENVELOPE
TO THE MINIMUM WIDTH AND WITHIN THE COVER LIMITS SHOWN ON THESE DRAWINGS. THE
ENGINEERED BACKFILL ENVELOPE SHALL NOT BE ALTERED WITHOUT WRITTEN APPROVAL FROM
CONTECH.
4.2. IN-SITU SOILS BELOW AND ADJACENT TO THE ENGINEERED BACKFILL ENVELOPE SHALL PROVIDE A
FIRM SURFACE AGAINST WHICH TO COMPACT THE ENGINEERED BACKFILL MATERIAL. THE
GEOTECHNICAL ENGINEER SHALL EVALUATE THE IN-SITU SOILS AND DETERMINE THE TYPE AND DEGREE OF ANY SOIL IMPROVEMENTS REQUIRED. THESE MAY INCLUDE BENCHING OR SLOPING OF THE SIDE SOILS. BACKFILL PLACEMENT MAY NOT BEGIN UNTIL THE GEOTECHNICAL ENGINEER HAS
APPROVED THE IN-SITU SOILS AND ANY REQUIRED IMPROVEMENTS.
4.3. A DRAINED CONDITION WAS ASSUMED FOR THE ENGINEERED BACKFILL ENVELOPE. DESIGN AND
SUPPLY OF A SUBSURFACE DRAINAGE SYSTEM (IF NEEDED) SHALL BE PROVIDED BY OTHERS.
4.4. IF REQUIRED BY THE GEOTECHNICAL ENGINEER, A GEOTEXTILE OR GRADED SOIL FILTER MAY BE USED BETWEEN THE ENGINEERED BACKFILL AND IN-SITU SOIL TO PREVENT MIGRATION OF FINES
AND POSSIBLE INTERNAL EROSION OF THE SOIL.
5. ENGINEERED BACKFILL MATERIAL REQUIREMENTS
5.1 THE DESIGN OF ALBC STRUCTURES RELIES ON COMPACTED SOIL PROPERTIES PROVIDED BY THE
ENGINEERED BACKFILL MATERIALS. THE CORRECT SELECTION AND PLACEMENT OF COMPACTED
ENGINEERED BACKFILL MATERIAL IS CRITICAL TO THE PERFORMANCE OF ALBC STRUCTURES.
5.2 THE ENGINEERED BACKFILL MATERIAL SHALL NOT BE ADVERSELY AFFECTED BY WETTING, DRYING, SATURATION, FREEZE/THAW, VIBRATIONS, OR FLOWING WATER.
5.3 BACKFILL MATERIALS SHALL CONFORM TO PROPERTIES REFERENCED IN THE PROJECT
SPECIFICATIONS OR THE PROPERTIES DESCRIBED HEREIN, WHICHEVER IS MORE STRINGENT.
5.4 ALBC NUMBERS 1 THROUGH 87 SHALL BE BACKFILLED USING CLEAN WELL GRADED GRANULAR MATERIAL THAT MEETS THE REQUIREMENTS FOR SOIL CLASSIFICATIONS A-1, A-2-4, A-2-5, OR A-3
MODIFIED PER AASHTO M-145.
A-3 MATERIAL MAY NOT CONTAIN FINE BEACH SANDS, WINDBLOWN SANDS, STREAM DEPOSITED
SAND, ETC. EXHIBITING FINE, ROUNDED PARTICLES.
ALBC NUMBERS 88 THROUGH 143 SHALL BE BACKFILLED USING CLEAN WELL GRADED GRANULAR
MATERIAL THAT MEETS THE REQUIREMENTS FOR SOIL CLASSIFICATIONS A-1, A-2-4 OR A-2-5 PER
AASHTO M-145.
REFER TO BACKFILL DETAILS FOR SOIL CLASSIFICATION TABLE. OPEN GRADED OR GAP GRADED MATERIALS ARE NOT PREFERRED. THE BACKFILL MATERIAL SHOULD BE FREE OF FROZEN LUMPS, FOREIGN MATERIAL OR ORGANIC DECOMPOSABLE MATERIALS. WHEN USING A-2 MATERIALS, MOISTURE CONTENT MUST BE BETWEEN -3% AND +2% OPTIMUM AS DEFINED BY AASHTO T 180.
5.5 GRAIN SIZE DISTRIBUTION (GRADATION) OF THE ENGINEERED BACKFILL MATERIAL SHALL SATISFY:
Cu GREATER THAN OR EQUAL TO 3 AND Cc BETWEEN 0.7 AND 3, WHERE Cu = COEFFICIENT OF UNIFORMITY = D60/D10 AND Cc = COEFFICIENT OF CURVATURE = (D30)²/(D60XD10). DXX IS THE PARTICLE SIZE CORRESPONDING TO XX% FINER ON THE CUMULATIVE PARTICLE SIZE DISTRIBUTION
CURVE (ASTM D2487).
Cu REQUIREMENTS ARE WAIVED FOR CRUSHER RUN SCREENED AGGREGATES. Cc REQUIREMENTS
ARE WAIVED FOR BACKFILL MATERIAL CONTAINING MORE THAN 60% GRAVEL (> #4 SIEVE).
5.6 ABRASION LOSS SHALL NOT EXCEED 45% AS DETERMINED BY THE LOS ANGELES ABRASION TEST
(ASTM C131).
5.7 HUMIC (DECAYING) ORGANIC MATTER SHALL NOT EXCEED 1.0% (DRY WEIGHT BASIS).
5.8 ELECTROCHEMICAL REQUIREMENTS FOR SOIL AND WATER IN CONTACT WITH BOTH THE INSIDE
AND OUTSIDE OF THE ALBC STRUCTURE ARE AS FOLLOWS:
- PH = 4 TO 9
- RESISTIVITY > 500 OHM-CM
5.9 IF THE ELECTROCHEMICAL PROPERTIES OF THE BACKFILL OR WATER FALL OUTSIDE OF THE
RECOMMENDED RANGE, A SECONDARY PROTECTION SYSTEM MAY BE NEEDED TO ACHIEVE THE
DESIGN SERVICE LIFE. SECONDARY PROTECTION SYSTEMS (IF REQUIRED) SHALL BE DESIGNED AND
PROVIDED BY OTHERS.
5.10 THE SELECTION AND EVALUATION OF PROPOSED ENGINEERED BACKFILL MATERIAL IS THE RESPONSIBILITY OF THE CONTRACTOR. THE PROPOSED ENGINEERED BACKFILL MATERIAL SHALL
MEET OR EXCEED THE REQUIREMENTS OF THESE SPECIFICATIONS.
6. ENGINEERED BACKFILL PLACEMENT PROCEDURE
6.1 CONTECH RECOMMENDS THAT A PRECONSTRUCTION CONFERENCE IS HELD PRIOR TO
COMMENCEMENT OF WORK TO REVIEW AND DISCUSS THE RECOMMENDED PROCEDURES FOR
BACKFILLING, AND STRUCTURE SHAPE MEASUREMENTS. ANY CONTRACTOR WITH RESPONSIBILITY
FOR BACKFILLING OR CONSTRUCTION OF END TREATMENTS MUST BE REPRESENTED AT THIS
MEETING. IT IS RECOMMENDED THAT THE ENGINEER AND ANY THIRD PARTY INVOLVED IN
COMPACTION TESTING OR OTHER QUALITY CONTROL MEASURES ALSO ATTEND.
6.2 ANY IMPROVEMENT OF THE SUBGRADE AND EMBANKMENT SOILS REQUIRED BY THE
GEOTECHNICAL ENGINEER SHALL BE COMPLETED AND APPROVED PRIOR TO BEGINNING
PLACEMENT OF ENGINEERED BACKFILL MATERIAL.
6.3 THE ENGINEERED BACKFILL MATERIAL SHALL BE PLACED UNIFORMLY ON BOTH SIDES OF THE
STRUCTURE IN LAYERS OF 8 INCHES OR LESS (BEFORE COMPACTION).
6.4 BACKFILL SHALL BE COMPACTED TO THE MINIMUM DENSITY INDICATED IN THESE DRAWINGS.
DEPENDING ON THE COMPACTION EQUIPMENT AND ENGINEERED BACKFILL MATERIAL USED, IT
MAY BE NECESSARY TO DECREASE THE LIFT THICKNESS AND/OR MOISTURE CONDITION THE LOOSE
SOIL TO ACHIEVE THE SPECIFIED MINIMUM LEVEL OF COMPACTION.
6.5 IF THE ENGINEERED BACKFILL MATERIAL DOES NOT PRODUCE A PROCTOR CURVE AND/OR IS NOT CONDUCIVE TO TRADITIONAL FIELD-TESTING METHODS, QUALITATIVE METHODS OF EVALUATING
COMPACTION MAY BE USED. SUCH METHODS SHALL BE EVALUATED AND APPROVED BY THE
GEOTECHNICAL ENGINEER AND A COPY OF THE METHOD BE PROVIDED TO THE DESIGNER.
6.6 THE DIFFERENCE IN BACKFILL LEVELS ON THE TWO SIDES OF THE STRUCTURE AT ANY TRANSVERSE
SECTION SHALL NOT EXCEED 24 INCHES WITHOUT PRIOR APPROVAL FROM CONTECH.
6.7 CONSTRUCTION EQUIPMENT USED WITHIN 5 FEET LATERALLY OF THE WIDEST PART OF THE STRUCTURE, UP TO THE MINIMUM DESIGN COVER HEIGHT ABOVE THE STRUCTURE, SHALL HAVE A STATIC MASS OF 10 TONS OR LESS. IT MAY BE POSSIBLE TO USE HEAVIER EQUIPMENT IF IT CAN BE
DEMONSTRATED THAT THE STRUCTURE SHAPE IS NOT ADVERSELY AFFECTED. ENGINEERED
BACKFILL MATERIAL PLACED WITHIN 1 FOOT LATERALLY OF THE WIDEST PART OF THE STRUCTURE
SHALL BE COMPACTED USING HAND OPERATED EQUIPMENT UNTIL THE MINIMUM COVER HEIGHT
IS REACHED. OVER-COMPACTION OF ENGINEERED BACKFILL IN THIS ZONE SHOULD BE AVOIDED, AS THIS CAN CONTRIBUTE TO EXCESSIVE DEFLECTION OF SOME STRUCTURES. AREAS CLOSEST TO THE
STRUCTURE SHALL BE COMPACTED RUNNING PARALLEL TO THE LENGTH OF THE STRUCTURE.
6.8 ONCE THE BACKFILL ELEVATION REACHES THE MIDDLE OF THE HAUNCH CURVE (DEPENDING ON
RELATIVE MOVEMENT DURING THE BACKFILL PROCESS), PLACE AND COMPACT ENGINEERED
BACKFILL MATERIAL IN RADIAL LIFTS OVER THE TOP OF THE STRUCTURE USING EQUIPMENT AS DESCRIBED ABOVE. THE FIRST RADIAL LIFT SHOULD BE THICKER AND PROVIDE A MINIMUM 12
INCHES OF COVER BETWEEN THE STRUCTURE AND COMPACTION EQUIPMENT. EQUIPMENT
SHOULD RUN PERPENDICULAR TO THE LONGITUDINAL AXIS OF THE STRUCTURE. NO EQUIPMENT
SHALL BE ALLOWED OVER THE STRUCTURE THAT WOULD EXCEED THE DESIGN LOAD AT THE
MINIMUM DESIGN HEIGHT OF COVER. NO CONSTRUCTION EQUIPMENT SHALL BE ALLOWED TO
PARK ON TOP OF A PARTIALLY BACKFILLED STRUCTURE.
6.9 AT NO TIME SHALL THE ENGINEERED BACKFILL MATERIAL BE DUMPED OR PUSHED AGAINST THE STRUCTURE WALL(S) SO AS TO CHANGE THE SHAPE OR ALIGNMENT OF THE STRUCTURE. MATERIAL
SHALL NOT BE DUMPED ON TOP OF THE STRUCTURE AT ANY TIME. TRUCKS MAY UNLOAD IN
ROUGH LAYERS NO CLOSER THAN 5 FEET FROM THE WIDEST PART OF THE STRUCTURE.
6.10 THE STRUCTURE SHALL BE CHECKED PERIODICALLY DURING BACKFILLING TO ENSURE THE FINAL
SHAPE OF THE STRUCTURE MEETS DESIGN REQUIREMENTS AND IS CONSISTENT WITH THE
ASSEMBLY TOLERANCES AS STATED IN THESE NOTES. IF DEFLECTION OF THE STRUCTURE IS
GREATER THAN EXPECTED, BACKFILLING SHALL BE HALTED AND BACKFILL PLACEMENT AND
COMPACTION PROCEDURES MODIFIED TO CORRECT THE STRUCTURE SHAPE. IT MAY BE
NECESSARY TO REMOVE SOME OF THE BACKFILL TO CORRECT EXCESSIVE DEFLECTION.
7. CONSTRUCTION OBSERVATIONS AND TESTING
7.1. OBSERVATION AND TESTING SHALL BE PERFORMED DURING CONSTRUCTION TO VERIFY
COMPLIANCE WITH THESE DRAWINGS, APPLICABLE PROJECT DOCUMENTS, AND STANDARDS
REFERENCED IN THESE NOTES.
7.2. THE CONTRACTOR IS RESPONSIBLE FOR QUALITY CONTROL PROCEDURES, VERIFICATION
MEASUREMENTS, ADEQUATE SUPERVISION, PROGRESS TESTING, EVALUATION OF PROPOSED
ENGINEERED BACKFILL MATERIALS, AND/OR OTHER MEASURES AS NEEDED TO ENSURE THAT THE
COMPLETED PROJECT COMPLIES WITH THESE DRAWINGS AND NOTES.
7.3. THE PROJECT OWNER (OR THEIR DESIGNATED REPRESENTATIVE) IS RESPONSIBLE FOR PROJECT
OVERSIGHT AND FINAL ACCEPTANCE OF THE CONSTRUCTED STRUCTURE. THE OWNER MAY
ACCEPT THE CONTRACTOR'S QUALITY CONTROL PROGRAM OR ADOPT AN INDEPENDENT QUALITY
ASSURANCE PROGRAM TO VERIFY COMPLIANCE.
7.4. OBSERVATIONS AND TESTING PRIOR TO STRUCTURE ASSEMBLY & BACKFILL SHALL INCLUDE BUT
NOT BE LIMITED TO:
- EVALUATION OF FOUNDATION SOILS BELOW FOOTINGS AND THE ENGINEERED BACKFILL
ENVELOPE
- VERIFICATION OF PROPER ALIGNMENT, DIMENSIONS, AND PLACEMENT OF FOUNDATIONS
- VERIFICATION OF PROPER SHAPING, PLACEMENT, AND PREPARATION OF BEDDING SOILS
(STRUCTURES WITH INVERTS)
- VERIFICATION OF PROPER PREPARATION OF EMBANKMENT SOILS ADJACENT TO THE ENGINEERED
BACKFILL ENVELOPE
- EVALUATION AND APPROVAL OF ENGINEERED BACKFILL MATERIALS
- VERIFICATION OF PROPER PLACEMENT OF GEOTEXTILES (WHEN REQUIRED)
7.5 OBSERVATIONS AND TESTING DURING ASSEMBLY & BACKFILLING SHALL INCLUDE BUT NOT BE
LIMITED TO:
- STRUCTURE ALIGNMENT
- PLATE TIGHTNESS OBSERVATIONS
- BOLT TORQUE MEASUREMENTS
- INITIAL STRUCTURE SHAPE MEASUREMENTS (PRIOR TO STARTING BACKFILLING)
- PERIODIC STRUCTURE SHAPE MEASUREMENTS (DURING BACKFILLING)
- ENGINEERED BACKFILL MATERIAL SAMPLING AND TESTING
- OBSERVATIONS OF PROPER FILL PLACEMENT AND COMPACTION PROCEDURES.
7.6 CONTECH MAY REQUIRE ADDITIONAL OBSERVATIONS AND/OR TESTING WHICH MAY INCLUDE, BUT
NOT BE LIMITED TO, FULL TIME SHAPE MONITORING, ADDITIONAL SOIL TESTING, AND SITE
EVALUATIONS DEPENDING ON THE STRUCTURE GEOMETRY, DESIGN, AND/OR OTHER PROJECT
SPECIFIC FACTORS.
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
2REVISION DESCRIPTIONDATEMARK BY
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE THICKNESS: .125 (H)/.125(C)
REINFORCING RIB SPACING: AS SHOWN
REINFORCING RIB TYPE: AS SHOWN
NUMBER OF STRUCTURES: 1
3/4" DIA. x 10'-0"
ANCHOR ROD (TYPICAL)
FLOW
PLAN VIEW
10'-0" SPAN
OVERALL LENGTH = 40'-9"
ALUMINUM BOX CULVERT
#4: 10'-0" SPAN x 4'-10" RISE
13'-6"
HEADWALL
13'-6"
HEADWALL
4'-6"
DEADMAN ANCHOR
ALUMINUM STRUCTURAL PLATE 0.150"
(1'-8" x 2' 4-3/4")
3/4" DIA. x 12'-6" ANCHOR ROD (TYPICAL)
90°
4'-6"
DEADMAN ANCHOR
ALUMINUM STRUCTURAL PLATE 0.150"
(1'-8" x 2' 4-3/4")
3/4" DIA. x 12'-6" ANCHOR ROD (TYPICAL)
4'-6"
DEADMAN ANCHOR
ALUMINUM STRUCTURAL PLATE 0.150"
(1'-8" x 2' 4-3/4")
3/4" DIA. x 12'-6" ANCHOR ROD (TYPICAL)
90°
4'-6"
DEADMAN ANCHOR
ALUMINUM STRUCTURAL PLATE 0.150"
(1'-8" x 2' 4-3/4")
3/4" DIA. x 12'-6" ANCHOR ROD (TYPICAL)
NOTE:
SHADED AREA REPRESENTS CRITICAL BACKFILL ZONES.
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
3REVISION DESCRIPTIONDATEMARK BY
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE THICKNESS: .125 (H)/.125(C)
REINFORCING RIB SPACING: AS SHOWN
REINFORCING RIB TYPE: AS SHOWN
NUMBER OF STRUCTURES: 1
FISH BAFFLE PLAN
6" 6"7'-6" 8'-3" 8'-3" 7'-6"
40'-9" GROSS STRUCTURE LENGTH
C STRUCTUREL
FLOW
9' -9
(T
YP
8'-3"
FISH BAFFLE
(6 REQUIRED)
9'-9"
2'-0"1'-6" 1'-6"
3"
3"3"
3"
FISH BAFFLE ELEVATION
2'-11 4"2'-11
4"
BAFFLE PLATE - 0.250" THICK x 12" TALL ALUMINUM PLATE
SHOP WELDED TO TYPE IV ALUMINUM REINFORCING RIB
CORRUGATED ALUMINUM
INVERT PLATE
TYPE IV ALUMINUM REINFORCING RIB
SHOP PUNCHED
TYPICAL ALUMINUM BAFFLE DETAIL
4" DIA. x 1 12" BOLTS @ 9 58" C/C
TYPE IV ALUMINUM REINFORCING RIB
BOLTED TO ALUMINUM INVERT PLATE.
HOLES IN RIB AND INVERT PLATE ARE
SHOP PUNCHED.
FLOW
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
4REVISION DESCRIPTIONDATEMARK BY
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE THICKNESS: .125 (H)/.125(C)
REINFORCING RIB SPACING: AS SHOWN
REINFORCING RIB TYPE: AS SHOWN
NUMBER OF STRUCTURES: 1
15N PLATE
.100 THK.
SHOP NOTCH PANELS
FLOW
312'-51 8" 10'-31
2"
1'-013 16"
1'-013 16"
4 C 5 C 6 C 7 8
ALBC - INVERT PLATES PLAN VIEW
NOTE: USE 1-1/4" LG. BOLTS ON OVERLAPPING SEAM
17'-11" MK. RC1 17'-11" MK. RC1 4'-5"
MK. RC2
17'-11" MK. RC1 17'-11" MK. RC1 4'-5"
MK. RC3
K K A A
FISH BAFFLE
(6 REQUIRED)
RECEIVING CHANNEL
RECEIVING CHANNEL
RECEIVING
CHANNEL
INVERT PLATE
.100 THK
1 1/4" BOLT
10'-3 1/2" - TO CENTER OF RECEIVING
CHANNEL SLOTS
SPRING CLIP (OPTIONAL)
4" NUT
ALIGN
HOLES
NOTE:
BEGIN INVERT ASSEMBLY AT OUTLET END. SEE
ASSEMBLY GUIDE INCLUDED WITH THE MATERIAL
SHIPMENT FOR FURTHER INSTRUCTIONS.
FOUNDATION NOTES:
1. THE ENGINEER SHALL VERIFY THAT THE PROPOSED FOUNDATION IS APPROPRIATE FOR THE
SITE CONDITIONS AND THE DESIGN PARAMETERS ARE CONSISTENT WITH THE PROJECT
REQUIREMENTS. THE FOUNDATION DESIGN CONSIDERS STRUCTURAL REQUIREMENTS OF THE
FOUNDATION ONLY. HYDRAULIC ANALYSIS AND SCOUR ANALYSIS, AS REQUIRED, SHALL BE
PERFORMED OR COORDINATED BY THE ENGINEER.
2. PRIOR TO CONSTRUCTION, CONTRACTOR MUST VERIFY ALL ELEVATIONS SHOWN WITH THE
ENGINEER.
3. FOUNDATION DESIGN IS BASED ON SITE SOIL INFORMATION PROVIDED TO CONTECH AND
DESCRIBED IN THE DESIGN PARAMETERS BELOW. FOUNDATION BEARING SOILS, INCLUDING
ANY SOIL IMPROVEMENTS REQUIRED, SHALL BE EVALUATED AND APPROVED BY OTHERS
PRIOR TO FOUNDATION CONSTRUCTION. IF UNEXPECTED SOIL CONDITIONS ARE
ENCOUNTERED, OR THE BEARING REQUIREMENTS CANNOT BE ACHIEVED, CONTECH MUST BE
NOTIFIED TO DETERMINE IF FOOTING DESIGN CHANGES ARE NEEDED.
DESIGN PARAMETERS:
DESIGN LIVE LOAD: HL-93
DESIGN MAXIMUM FILL HEIGHT: 2.5'
DESIGN METHOD: LOAD FACTOR DESIGN PER AASHTO SPECIFICATION
DESIGN MINIMUM NET ALLOWABLE BEARING CAPACITY: 4,000 PSF * (ASSUMED)*
*AT THE TIME OF DESIGN, A GEOTECHNICAL REPORT FOR THE PROJECT SITE WAS NOT
AVAILABLE. IT IS THE ENGINEER'S, OWNER'S AND/OR THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THAT THE ACTUAL SITE CONDITIONS AT THE TIME OF CONSTRUCTION ARE CONSISTENT
WITH THE ASSUMED ALLOWABLE SOIL BEARING PRESSURE WITH A GEOTECHNICAL
INVESTIGATION FROM A QUALIFIED GEOTECHNICAL ENGINEER.
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
5REVISION DESCRIPTIONDATEMARK BY
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE THICKNESS: .125 (H)/.125(C)
REINFORCING RIB SPACING: AS SHOWN
REINFORCING RIB TYPE: AS SHOWN
NUMBER OF STRUCTURES: 1
18" (T
YP)
RECEIVING CHANNEL
SCALLOP PLATE
CLIPS
PLACEMENT DETAIL
(NOT TO SCALE)
MATERIAL: SPRING STEEL
FINISH: GALVANIZED
OF STRUCTURE
TO INSIDE
(USED ON STRUCTURES WITH
FULL ALUMINUM INVERTS)
NOTE: THIS CLIP IS USED AS A "PUSH-ON"
RETAINER FOR THE SCALLOP PLATE.
THE THREADED PORTION IS NOT
UTILIZED. BOLTS ARE NOT SUPPLIED
AND ARE NOT NECESSARY.
Ø7/8" BOLT
HOLES
ALUMINUM RECEIVING CHANNEL
DETAIL "J"
REFER TO BOLT CHART
SHEET 9
INSIDE OF ALBC
HAUNCH PLATE
SCALLOP
CLIP
SCALLOP
PLATE
GEOTEXTILE
INVERT PLATE
RECEIVING CHANNEL
SECURE RECEIVING CHANNEL TO INVERT / SUPPLEMENTAL PLATE USING
1 1/4" BOLT (NOT PICTURED. INSERT BOLT FROM BENEATH INVERT OR
USE SPRING CLIPS TO HOLD IN PLACE
INSIDE SURFACE
FLOW
SECTION A-A
TYPICAL OVERLAPPING SEAM DETAIL
4" STRUCTURAL PLATE BOLT & NUT
WITH SPRING CLIP (OPTIONAL) BEDDING MATERIAL
5" MINIMUM THICKNESS
SEE SPECIFICATIONS
ROUNDED FACE OF NUT
ALWAYS FACES BOLT HEAD
AS SHOWN
PLACEMENT DETAIL
(NOT TO SCALE)
13"
RECEIVING CHANNEL
TO INSIDE
OF STRUCTURE
18"
CRITICAL
4"
13"
4"
18"
TYPICAL
RECEIVING CHANNEL
ALUMINUM RECEIVING CHANNEL
ISOMETRIC VIEW
FRONT VIEW SIDE VIEW
3/8"
16 GA
11/16"
1 11/16"
15/16"
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
6REVISION DESCRIPTIONDATEMARK BY
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE THICKNESS: .125 (H)/.125(C)
REINFORCING RIB SPACING: AS SHOWN
REINFORCING RIB TYPE: AS SHOWN
NUMBER OF STRUCTURES: 1
NOTES:
1. SCALLOPED CLOSURE PLATES ARE CLIPPED TO THE OUTSIDE OF THE RECEIVING
CHANNEL TO MINIMIZE BACKFILL INFILTRATION IN THE VALLEYS OF THE
CORRUGATED INVERT PLATE BELOW THE RECEIVING CHANNEL.
2. THE USE OF A GEOTEXTILE IS REQUIRED TO PREVENT THE INFILTRATION
OF THE BACKFILL THROUGH THE UNFILLED BOLT HOLES AND THE SPACE BETWEEN
THE INVERT PLATE AND THE SCALLOP PLATE. A ROLL OF GEOTEXTILE IS PROVIDED
FOR THIS PURPOSE.
NOTES:
1. SCALLOPED CLOSURE PLATES ARE CLIPPED TO THE OUTSIDE OF THE RECEIVING
CHANNEL TO MINIMIZE BACKFILL INFILTRATION IN THE VALLEYS OF THE
CORRUGATED INVERT PLATE BELOW THE RECEIVING CHANNEL.
2. THE USE OF A GEOTEXTILE IS REQUIRED TO PREVENT THE INFILTRATION
OF THE BACKFILL THROUGH THE UNFILLED BOLT HOLES AND THE SPACE BETWEEN
THE INVERT PLATE AND THE SCALLOP PLATE. A ROLL OF GEOTEXTILE IS PROVIDED
FOR THIS PURPOSE.
PLATE LAPPING DETAIL
2 PLATE STRUCTURE
NOTE:
BEGIN SHELL ASSEMBLY AT INLET END. SEE
ASSEMBLY GUIDE INCLUDED WITH THE MATERIAL
SHIPMENT FOR FURTHER INSTRUCTIONS.
MARK CORNERS RED
MARK CORNERS RED
LIP (11
2")LIP (11
2") CENTERLINE LENGTH = 40'-6"
OVERALL LENGTH = 40'-9"
FLOW
10N PLATE
.125 THK.
10N PLATE
.125 THK.
A A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
CROWN
CENTERLINE
ALBC - DEVELOPED PLAN (OUTSIDE VIEW)
10'-0" SPAN x 4'-10" RISE
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
7REVISION DESCRIPTIONDATEMARK BY
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE THICKNESS: .125 (H)/.125(C)
REINFORCING RIB SPACING: AS SHOWN
REINFORCING RIB TYPE: AS SHOWN
NUMBER OF STRUCTURES: 1
REFER TO BOLT LENGTH
USAGE DETAIL - SHEET 9
MARK CORNERS RED
MARK CORNERS RED
LIP (11
2")LIP (11
2") CENTERLINE LENGTH = 40'-6"
OVERALL LENGTH = 40'-9"
FLOW
HR1 - 2 PCS. x 75.375" LG.
TYPE II HAUNCH LOCATE WHERE SHOWN
HR2 - 2 PCS. x 75.375" LG.
TYPE II HAUNCH LOCATE WHERE SHOWN
CR3 - 2 PCS. x 27.5" LG.
TYPE IV CROWN LOCATE WHERE SHOWN
HR4 - 8 PCS. x 75.375" LG.
TYPE II HAUNCH @54" LOCATE WHERE SHOWN
HR5 - 8 PCS. x 75.375" LG.
TYPE II HAUNCH @54" LOCATE WHERE SHOWN
CR6 - 18 PCS. x 47" LG.
TYPE IV CROWN @18" LOCATE WHERE SHOWN
HR2
HR1
CR3
RIB SPLICE
(16 REQUIRED)
RIB SPLICE
10N PLATE
.125 THK.
10N PLATE
.125 THK.
A A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
CROWN
CENTERLINE
ALBC - DEVELOPED PLAN (OUTSIDE VIEW)
10'-0" SPAN x 4'-10" RISE
CR7 - 8 PCS. x 27.5" LG.
TYPE IV CROWN @54" LOCATE WHERE SHOWN
FR8 - 2 PCS. x 8.25" LG.
TYPE II FILLER LOCATE WHERE SHOWN
FR8 - 2 PCS. x 8.25" LG.
TYPE II FILLER LOCATE WHERE SHOWN
FR9
FR8
31 2"
8"
11 8"
4"
1 4"
2"
1 2"
TYPE IV RIB
1 2"
3"
4"
2"
1 4"
4"
TYPE II RIB
NOTE:
1. REFER TO SHEET 9 FOR ADDITIONAL DETAIL.
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
8REVISION DESCRIPTIONDATEMARK BY
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE THICKNESS: .125 (H)/.125(C)
REINFORCING RIB SPACING: AS SHOWN
REINFORCING RIB TYPE: AS SHOWN
NUMBER OF STRUCTURES: 1
NOTES:
1. FOR PROPER BOLT SIZE USAGE, REFER TO THE FOLLOWING:
2 PLATE 3 PLATE
0.125" THK. PLATE 1 1/4" 1 1/4"
PLATE ONLY
1 PLATE 2 PLATE 3 PLATE
0.125" THK. PLATE 1 1/4" 1 1/2" 1 1/2"
PLATE W/ TYPE II OR TYPE IV REINFORCING RIB OR RECEIVING CHANNEL
BOLT LENGTH USAGE DETAIL
1'-41 2"
RIB SPLICE
RIB SPLICE
TYPE IV
CROWN RIB
4" NUT
TYPE II
HAUNCH RIB
4" x 11
2" BOLT
RIB SPLICE
ATTACHMENT TO TYPE IV RIB
TYPE IV
CROWN RIB
TYPE II
HAUNCH RIB
RIB SPLICE
NOTE:
THE ORIENTATION OF THE RIBS IS NOT CRITICAL,
BUT SHOULD BE KEPT CONSISTENT ALONG THE
LENGTH OF THE STRUCTURE.
RIB SPLICE
ISOMETRIC VIEW
A A
B1
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
9REVISION DESCRIPTIONDATEMARK BY
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE THICKNESS: .125 (H)/.125(C)
REINFORCING RIB SPACING: AS SHOWN
REINFORCING RIB TYPE: AS SHOWN
NUMBER OF STRUCTURES: 1
3 PLATE W/ TYPE IV RIB
2" BOLTS
2 PLATE W/ TYPE IV RIB
2" BOLTS
1 PLATE W/ TYPE IV RIB
1 1/2" BOLTS
3 PLATE WITHOUT RIB
1 1/4" BOLTS
2 PLATE WITHOUT RIB
1 1/4" BOLTS
1 PLATE W/ TYPE II RIB
1 1/4" BOLTS
2 PLATE W/ TYPE II RIB
1 1/2" BOLTS
USE 1 1/2" BOLTS
AT RIB SPLICE
PLATE SEAM
PLATE SEAM
2 PLATE W/ TYPE IV RIB
2" BOLTS
ALBC - INLET EXPANDED END VIEW
SHOP NOTCH
END PANEL
SHOP NOTCH END PANEL
13'-6"
HEADWALL WIDTH
2"
2'-3"
2"
4'-6"
WING
PANEL
3' -0
8' -6
WALE BEAM
x 4'-6" LG.
HW CAP MK HC1
x 22'-9" LG.
4'-6"
END
PANEL
4'-6"
CENTER
PANEL
4'-6"
END
PANEL
12 13
4'-6"
WING
PANEL
2"
2'-3"
2"
3' -0
8' -6
WALE BEAM
x 4'-6" LG.
WALE BEAM
x 13'-6" LG.
F
F
B
B
B
BD
D
NOTES:
1. WALL PANEL NUMBERS ARE MARKED ON THE SOIL SIDE.
2. BOLT HEADWALL TO REINFORCING RIB AT END OF STRUCTURE.
3. SEE SHEETS 12-16 FOR REFERENCED SECTIONS AND ADDITIONAL DETAILS.
4. ALL 2'-3" DIMENSIONS ARE RELATIVE TO SECTION B-B.
5. ALL 4 1/2" DIMENSIONS ARE RELATIVE TO SECTION F-F.
6. ○ DENOTES BOLTS CONNECTION
7. ● DENOTES ANCHOR ROD CONNECTION
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
10REVISION DESCRIPTIONDATEMARK BY
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE THICKNESS: .125 (H)/.125(C)
REINFORCING RIB SPACING: AS SHOWN
REINFORCING RIB TYPE: AS SHOWN
NUMBER OF STRUCTURES: 1
ALBC - OUTLET EXPANDED END VIEW
SHOP NOTCH
END PANEL
SHOP NOTCH END PANEL
13'-6"
HEADWALL WIDTH
2"
2'-3"41 2"
4'-6"
WING
PANEL
3' -0
8' -6
WALE BEAM
x 4'-6" LG.
HW CAP MK HC2
x 22'-9" LG.
4'-6"
END
PANEL
4'-6"
CENTER
PANEL
4'-6"
END
PANEL
17 18
4'-6"
WING
PANEL
2"
2'-3"41 2"
3' -0
8' -6
WALE BEAM
x 4'-6" LG.
WALE BEAM
x 13'-6" LG.
F
F
B
B
B
BD
D
NOTES:
1. WALL PANEL NUMBERS ARE MARKED ON THE SOIL SIDE.
2. BOLT HEADWALL TO REINFORCING RIB AT END OF STRUCTURE.
3. SEE SHEETS 12-16 FOR REFERENCED SECTIONS AND ADDITIONAL DETAILS.
4. ALL 2'-3" DIMENSIONS ARE RELATIVE TO SECTION B-B.
5. ALL 4 1/2" DIMENSIONS ARE RELATIVE TO SECTION F-F.
6. ○ DENOTES BOLTS CONNECTION
7. ● DENOTES ANCHOR ROD CONNECTION
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
11REVISION DESCRIPTIONDATEMARK BY
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE THICKNESS: .125 (H)/.125(C)
REINFORCING RIB SPACING: AS SHOWN
REINFORCING RIB TYPE: AS SHOWN
NUMBER OF STRUCTURES: 1
2' -1
/1
6"
(IN
LE
T)
2" WHEN HEADWALLS ARE ORDERED FOR BOTH ENDS,
THE LENGTH OF STRUCTURE MUST BE A MULTIPLE OF 9"
0.150" (END) / 0.125" (CENTER)
THICK PLATE
CORRUGATED
HEADWALL
REINFORCING RIB
FIELD DRILL HOLES FOR
ATTACHMENT OF THE
HEADWALL PLATE TO
THE END REINFORCING RIB
(ATTACH TO EVERY OTHER
CORRUGATION CREST ON
THE HEADWALL PANEL)
END OF
STRUCTURE
HEADWALL
CAP
Ø3 4" x 10'-0" ANCHOR ROD
(HOLE THROUGH PLATE TO
BE FIELD DRILLED, RIB TO BE
SHOP PUNCHED)
GEOTEXTILE
(NOTE #4)
CORRUGATED
PLATE
SECTION D-D
HEADWALL ATTACHMENT TO
CROWN OF STRUCTURENOTES:
1) REVERSE CROWN RIBS AT THIS CORRUGATION IF NECESSARY FOR PROPER ANCHOR
ROD ATTACHMENT PLATE ORIENTATION.
2) NO SPLICE PLATES ARE USED FOR THE TYPE IV REINFORCING RIBS ATTACHED TO
THE CORRUGATED HEADWALL.
3) REINFORCING RIBS AT EACH END OF STRUCTURE MUST BE ORIENTED SUCH THAT
THE HEADWALL CAN BE PLACED BEHIND THEM AS SHOWN.
4) GEOTEXTILE PREVENTS INFILTRATION OF THE BACKFILL BETWEEN THE HEADWALL AND
STRUCTURE. A ROLL OF GEOTEXTILE IS PROVIDED FOR THIS PURPOSE.
2' -6
(O U
TL
ET
1' -0
TYPE WALE BEAM
4" x 1-12" STEEL BOLTS & NUTS
ANCHOR ROD
ATTACHMENT PLATE
FIELD DRILL
AND BOLT
DETAIL D1-D1
NOTE #1
2' -3
(IN
LE
T)
2' -4
/1
6"
(O
U
TL
ET
4" GALVANIZED NUT
4" GALVANIZED BOLT
4" DIA. ANCHOR ROD
4" GALVANIZED NUT
FIELD DRILL HOLE
IN TYPE IV RIB
TYPE IV ARAP
TYPE IV CROWN RIB
DETAIL D1-D1
TYPE IV ANCHOR ROD
7"
ATTACHMENT PLATE
(ARAP)
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
12REVISION DESCRIPTIONDATEMARK BY
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE THICKNESS: .125 (H)/.125(C)
REINFORCING RIB SPACING: AS SHOWN
REINFORCING RIB TYPE: AS SHOWN
NUMBER OF STRUCTURES: 1
4"±
BOTTOM HOLE
IN HEADWALL PLATE
4"±
FIELD-DRILL THE HEADWALL CAP
TO MATCH THE BOTTOM HOLE IN
THE HEADWALL PLATE.
FIELD-DRILL THE HEADWALL PLATE FOR
WALE BEAM ATTACHMENT.
USE A 2 X 4 TO ACHIEVE THE 1 7
16" GAP,
THEN REMOVE THE WOOD BLOCK
ONCE THE HEADWALL CAP IS
FASTENED.
TOP OF HEADWALL PLATE
HEADWALL PLATE
16"
8 9/16"± (INLET)
11 9/16"±(OUTLET)
HEADWALL
(CAP AND WALE BEAM ATTACHMENT)
X X
Y Y
WALE BEAM
4" x 1-12" STEEL BOLTS, FLAT WASHERS AND NUTS
(FIELD DRILLED)
OUTSIDE FACE OF WALL
& HEADWALL CAP
C WALL PANELL
HEADWALL/WINGWALL CAP
AT ATTACHMENT TO PANEL
DETAIL SECTION X-X
Ø3 4" x 10'-0" ANCHOR ROD
(FIELD DRILLED)
4" x 1-12" STEEL BOLTS & NUTS
(FIELD DRILLED)
WALE BEAM
C WALL PANELL
TYPICAL ANCHOR ROD ATTACHMENT
AT HEADWALL SECTION Y-Y
4" x 1-12" STEEL BOLTS & NUTSFACE SIDE
SOIL SIDE
℄OF PLATE SEAM
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
13REVISION DESCRIPTIONDATEMARK BY
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE THICKNESS: .125 (H)/.125(C)
REINFORCING RIB SPACING: AS SHOWN
REINFORCING RIB TYPE: AS SHOWN
NUMBER OF STRUCTURES: 1
TYPICAL PANEL LAP DETAIL
HEADWALL CAP
HEADWALL PLATE
C WALL PANEL
L
4" x 1-1/2" x STEEL BOLTS, FLAT
WASHERS AND NUTS
(FIELD DRILLED)
Ø3 4" x 10'-0" ANCHOR ROD
(FIELD DRILLED)
HEADWALL PLATE
WALE BEAM
HEADWALL CAP
C WALL PANEL
L
BACKFILL SIDE
FRONT OF WALL
WALE NUT
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
14REVISION DESCRIPTIONDATEMARK BY
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE THICKNESS: .125 (H)/.125(C)
REINFORCING RIB SPACING: AS SHOWN
REINFORCING RIB TYPE: AS SHOWN
NUMBER OF STRUCTURES: 1
HEADWALL / WINGWALL CAP AT ATTACHMENT TO PANEL DETAIL
SECTION X-X (ISOMETRIC VIEW)
TYPICAL ANCHOR ROD ATTACHMENT AT HEADWALL
SECTION Y-Y (ISOMETRIC VIEW)
1' -8
"9"
8' -6
" W
AL
L H
G T
5' -6
" T O
BO
TT
O M
O F
W
AL
L
HOLE THROUGH PLATE
TO BE FIELD DRILLED (TYP.)
Ø3/4" x 12'-6" ANCHOR ROD
DEADMAN ANCHOR ALUMINUM
STRUCTURAL PLATE
0.150" (1'-8" x 2'-4 3/4") (TYP.)
0.150"
THICK PLATE
REINFORCING
RIB
REFER TO SECTION X-X FOR WINGWALL CAP ATTACHMENT
SECTION B-B
SINGLE DEADMAN ANCHOR
ATTACHMENT
3' -0
" T O
TO
P
O F
C
AP
SEE DETAIL "G"
SEE DETAIL "H"
4" x 2" STEEL BOLT
HOLE THROUGH
WINGWALL PANEL
TO BE FIELD DRILLED
WALE
BEAM
WALE
NUT
SECURE ANCHOR ROD
WITH 34" NUT
DETAIL H
SECURE ANCHOR ROD
WITH 34" NUT
DETAIL G
8"
21 4"
THREADED FOR
4" ANCHOR ROD
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
15REVISION DESCRIPTIONDATEMARK BY
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE THICKNESS: .125 (H)/.125(C)
REINFORCING RIB SPACING: AS SHOWN
REINFORCING RIB TYPE: AS SHOWN
NUMBER OF STRUCTURES: 1
SECTION F-F
WALE BEAM ATTACHMENT
WALE NUT
TOE WALL ELEVATION
K
K
11'-23 4"
8"(13) SPACES @ 9 5/8"
DEPTH
2.50"
9" PITCH
2.2 5"
RAD.
T = THICKNESS
1-1/4"+T/2
NEUTRAL AXIS
ALUMINUM STRUCTURAL PLATE
SECTION K-K
3"
2' -3
INVERT
3/4"Ø x 11
4" BOLTS
@ 9-5/8" O.C.
TOEWALL
C :\U
SE
R
S\
JO
H N
.C
AR
PE
N
TE
R
\O N
ED
R
IV
E
- T H
E Q
U
IK
R
ET
E C
O M
PA
N
IE
S\
D O
C U
M
EN
TS
\8
4-
0-
AL
BC
-C
O N
-A .D
W G
/1
0/
0:
A M
865254 SEQ. No.:
010ALUMINUM BOX CULVERT
DAUPHIN COUNTY, PENNSYLVANIA
#4R1 - 10'-0" SPAN X 4'-10" RISE
16REVISION DESCRIPTIONDATEMARK BY
The design and information shown on this drawing is provided as a service to the project owner, engineer and contractor by Contech Engineered Solutions LLC ("Contech"). Neither this drawing, nor any part thereof, may be used, reproduced or modified in any manner without the prior written consent of Contech. Failure to comply is done at the user's own risk and Contech expressly disclaims any liability or responsibility for such use.
If discrepancies between the supplied information upon which the drawing is based and actual field conditions are encountered as site work progresses, these discrepancies must be reported to Contech immediately for re-evaluation of the design. Contech accepts no liability for designs based on missing, incomplete or inaccurate information supplied by others.
www.ContechES.com
CONTRACT
CONTECH
DRAWING
FOR APPROVAL
STRUCTURAL PLATE
TYPE: BOX
SIZE: 4R1
SPAN: 10'-0"
RISE: 4'-10"
LENGTH @ ℄: 40'-6"
SKEW
BEVEL
INLET OUTLET PLATE…