3-C2 - ELECTRICAL CONTRACT DRAWINGS-SEALED.pdf

PDF 702 KB Posted

Attached to
Hanover Trolley Trail - Route 116 Trailhead
Solicitation number
Not on record
Issued by
Blair County, Pennsylvania

About this file

This electrical contract drawing document pertains to the Route 116 Trailhead project for the Hanover Trolley Trail, managed by the York County Rail Trail Authority in Pennsylvania. The project involves the installation of electrical infrastructure including a 100-ampere, 208Y/120-volt, three-phase service with a surface-mounted panelboard and meter base. The work encompasses the installation of two swing-type gate operators with battery backup systems, complete with remote controls, safety sensors, keypads, and photoeye entrapment sensors. Additional electrical work includes trenching and conduit installation to connect to an existing utility pole, grounding systems with copper-clad steel ground rods, and the installation of underground electrical lines with concrete encasement in specified areas. The contract period is ninety calendar days, with sealed bids due May 29, 2026, at 10:00 AM via the PennBid Program. A bid bond equal to 10% of the maximum bid is required, and the project is subject to Pennsylvania Prevailing Wage Act requirements.

The electrical specifications require all materials to be new, UL-listed, and compliant with the National Electrical Code and Pennsylvania Uniform Construction Code. Key equipment manufacturers specified include Mill-Bank for the meter/load center enclosure (Model CP3B), Liftmaster for gate operators (Model CSW24UL), Linear for keypads (Model AK-11), and Optex for safety sensors. The contractor is responsible for all labor, materials, equipment, trenching, permit acquisition, and scheduling inspections with authorities having jurisdiction. Contract closeout requirements include system cleaning, preparation of two operation and maintenance manuals, equipment startup, and demonstration and training for the owner's personnel. No pricing information, set-asides, or funding sources are specified in the drawing document itself, as this is a technical specification rather than a bid summary document.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SYMBOL AND ABBREVIATION SCHEDULE

SYMBOL DESCRIPTIONABBR.

PANELBOARD, 120/208V, 208V OR 240V, SURFACE OR FLOOR MOUNTEDPNLBD

OR PNL

UNDERGROUND ELECTRICAL LINEUE

KEYPADKP

UTILITY METERMU

GROUND ROD LOCATIONGR

AMPEREA

ABOVE FINISHED FLOORAFF

AMERICAN WIRE GAUGEAWG

ELECTRICALELEC

GROUNDG, GND,

GRD

THOUSAND CIRCULAR MILSKCMIL

NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATIONNEMA

MAIN CIRCUIT BREAKERMCB

NATIONAL ELECTRICAL CODENEC

POLEP

VOLTSV

WIREW

MOUNTING HEIGHT SCHEDULE

TOP PROTECTIVE DEVICE TO BE 72" ABOVE FINISHED FLOORPANELBOARDS

NOTES (FOR MOUNTING HEIGHT SCHEDULE):

1. UNLESS INDICATED OTHERWISE, DEVICE MOUNTING HEIGHTS ARE TO CENTER LINE OF DEVICE.

2. REFER TO FLOOR PLANS FOR DEVICES MOUNTED AT HEIGHTS DIFFERING FROM HEIGHTS SCHEDULED.

DEVICES INDICATED ON FLOOR PLANS WITH A 'C' NOTATION SHALL BE MOUNTED AT COUNTER HEIGHT.

3. MOUNTING HEIGHTS OF ALL DEVICES SHALL COMPLY WITH ICC/ANSI A117.1. THIS INCLUDES ALL

FORWARD AND SIDE REACH REQUIREMENTS FOR BOTH UNOBSTRUCTED AND OBSTRUCTED REACH

RANGES AS APPLICABLE.

CONTACT:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

SEAL:

PROJECT:

PROJECT NUMBER:

DATE:

DRAWING TITLE:

DRAWING NUMBER:

COPYRIGHT © 2024

4/

/2

9:

:0

AM

H:

\R

EV

IT

\A J2

6_ M

EP

_C

EN

TR

AL

_R

_f al ve yH

CU

.rv t

L.E.L.

L.E.L.

C.G.M.

426005.00

E001

SYMBOL AND

ABBREVIATION

SCHEDULE

04/15/2026

C.G.M.

ROUTE 116

TRAILHEAD

HANOVER TROLLEY

TRAIL

GENERAL NOTES:SPECIFICATIONS:

SUBMITTALS:

PROVIDE SUBMITTAL DATA FOR THE FOLLOWING:

• PANELBOARDS

• METERBASES

• GATE OPENERS AND ACCESSORIES

• GATE

CONDUCTORS AND CABLES:

GENERAL: LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND USE. ROHS COMPLIANT. COMPLY WITH WIRE

AND CABLE MARKING ACCORDING TO UL'S "WIRE AND CABLE MARKING AND APPLICATION

GUIDE."

BUILDING WIRE: COPPER, COMPLYING WITH ASTM B 3 FOR BARE ANNEALED COPPER AND

WITH ASTM B 8 FOR STRANDED CONDUCTORS. THHN/THWN-2 CONDUCTOR INSULATION,

COMPLYING WITH UL 83.

CONNECTORS: UL LISTED FACTORY-FABRICATED CONNECTORS AND SPLICES OF SIZE,

AMPACITY RATING, MATERIAL, TYPE, AND CLASS FOR APPLICATION AND SERVICE

INDICATED.

GROUNDING AND BONDING:

COMPLY WITH UL 467 FOR GROUNDING AND BONDING MATERIALS AND EQUIPMENT.

CONDUCTORS: INSTALL SOLID CONDUCTOR FOR NO. 10 AWG AND SMALLER, AND

STRANDED CONDUCTORS FOR NO. 8 AWG AND LARGER UNLESS OTHERWISE INDICATED.

INSULATED CONDUCTORS: COPPER WIRE OR CABLE INSULATED FOR 600V UNLESS

OTHERWISE REQUIRED BY APPLICABLE CODE OR AUTHORITIES HAVING JURISDICTION.

BARE COPPER CONDUCTORS: SOLID CONDUCTORS: ASTM B 3

STRANDED CONDUCTORS: ASTM B 8, BONDING CABLE: 28 KCMIL, 14 STRANDS OF

NO. 17 AWG CONDUCTOR, 1/4 INCH IN DIAMETER

BONDING CONDUCTOR: NO. 4 OR NO. 6 AWG, STRANDED CONDUCTOR

GROUND ROD CLAMPS: MECHANICAL TYPE, COPPER OR COPPER ALLOY, TERMINAL WITH

HEX HEAD

GROUND ROD: COPPER-CLAD STEEL ROD, 8’-0” LONG MINIMUM, 5/8” DIAMETER.

METAL CONDUIT, TUBING, AND FITTINGS:

MINIMUM RACEWAY SIZE: 3/4 INCH.

RIGID METAL CONDUIT (RMC): COMPLY WITH ANSI C80.1, UL6.

LIQUIDTIGHT FLEXIBLE METAL CONDUIT (LFMC) AND FITTINGS: COMPLY WITH UL 360,

FLEXIBLE STEEL CONDUIT WITH PVC JACKET.

FITTINGS: COMPLY WITH NEMA FB 1 AND UL 514B.

RMC IMC FITTINGS: THREADED, COMPLY WITH NEMA FB 2.10.

LFMC FITTINGS: COMPLY WITH NEMA FB 2.20.

NONMETALLIC CONDUIT AND TUBING:

RIGID NONMETALLIC CONDUIT (RNC): COMPLY WITH NEMA TC 2 AND UL 651, SCHEDULE 40

PVC.

FITTINGS: COMPLY WITH NEMA TC 3.

SOLVENTS AND ADHESIVES: AS RECOMMENDED BY CONDUIT MANUFACTURER.

RACEWAY APPLICATIONS:

OUTDOORS: USE THE FOLLOWING WIRING METHODS:

EXPOSED: RMC.

CONCEALED: RMC OR IMC.

UNDERGROUND: RNC, 1 INCH MINIMUM, CONCRETE ENCASE UNDER ROADWAYS,

DRIVEWAYS, AND MACADAM AREAS WITH MINIMUM 3 INCHES OF CONCRETE ON 3 SIDES.

UNDERGROUND, SERVICE ENTRANCE: RNC, CONCREATE ENCASE WHERE REQUIRED BY

UTILITY. PROVIDE RMC LONG RADIS SWEEPS WHEN REQUIRED BY UTILITY.

FINAL CONNECTION TO VIBRATING EQUIPMENT (INCLUDING TRANSFORMERS AND

HYDRAULIC, PNEUMATIC, ELECTRIC SOLENOID, OR MOTOR-DRIVEN EQUIPMENT): LFMC.

BOXES AND FITTINGS:

PULL AND JUNCTION BOXES (INTERIOR, EXPOSED, DRY, DAMP OR WET LOCATIONS): CAST-

METAL BOXES, COMPLY WITH NEMA FB 1 AND UL 1773, CAST ALUMINUM WITH GASKETED

COVER, NEMA 250 TYPE 3R.

OUTLET AND DEVICE BOXES (INTERIOR, EXPOSED, DRY, DAMP OR WET LOCATIONS): CAST-

METAL BOXES, NEMA FB 1, CAST ALUMINUM WITH GASKETED COVER, NEMA 250 TYPE 3R.

EXTERIOR PULL BOXES AND HANDHOLES:

CAST METAL BOXES: CAST ALUMINUM WITH GASKETED COVER WITH NONSKID FINISH.

POLYMER CONCRETE HANDHOLES: WEATHERPROOF, MOLDED POLYMER CONCRETE UNIT

WITH HEAVY-DUTY COVER AND NONSKID FINISH. UL LISTED. PROVIDE LOGO TO READ

‘ELECTRIC'.

MANUFACTURER: QUAZITE OR APPROVED EQUAL.

LOAD CENTER:

LISTINGS: COMPLY WITH NEMA PB 1. RATED FOR SERVICE ENTRANCE.

OVERCURRENT PROTECTIVE DEVICES: PLUG-IN CIRCUIT BREAKERS, REPLACEABLE

WITHOUT DISTURBING ADJACENT UNITS.

ENCLOSURE: NEMA 3R, LOCKABLE

BUS: COPPER (INCLUDING NEUTRAL AND GROUND BUS).

EQUIPMENT GROUND BUS: ADEQUATE FOR FEEDER AND BRANCH-CIRCUIT EQUIPMENT

GROUND CONDUCTORS; BONDED TO BOX.

LOAD BALANCING: MEASURE LOAD BALANCING AND MAKE CIRCUIT CHANGES.

FULLY RATED, NO SERIES RATING ALLOWED.

MANUFACTURERS: EATON/CUTLER HAMMER, GENERAL ELECTRIC, SIEMENS-ITE, OR

SQUARE D.

WIRING DEVICES AND COMPONENTS:

HEAVY-DUTY SPECIFICATION GRADE OR INDUSTRIAL SPECIFICATION GRADE.

MANUFACTURERS: LEVITON, HUBBELL, EATON, OR PASS AND SEYMOUR.

GFCI RECEPTACLES: 125 V, 20 A: COMPLY WITH NEMA WD 1, NEMA WD 6, UL 498, UL 943

CLASS A, AND FS W-C-596. FEED-THROUGH TYPE WITH INDICATOR LIGHT FOR

MALFUNCTION OR IMPROPER GFCI PROTECTION.

WEATHERPROOF "WHILE IN USE" COVER: SHALL BE PROVIDED FOR ALL RECEPTACLES

INSTALLED IN WET LOCATIONS PER NATIONAL ELECTRICAL CODE. THERMOPLASTIC CLEAR

COVER RATED NEMA 3R "WHILE IN USE".

METER ENCLOSURES

ACCEPTABLE TO LOCAL UTILITY COMPANY.

PEDESTAL MOUNTED METER/LOAD CENTER ENCLOSURE.

SINGLE METER, RINGLESS SOCKET WITH LEVER BYPASS. 200A-120/240V-1PH-3W , 5 JAW .

INTEGRATED

PANEL W ITH (1) 200A MAIN DISCONNECT. (1) SW ITCHED 16 CIRCUIT LOAD CENTER W ITH

INTEGRATED DIN

RAIL MOUNTED TIME CLOCK, PHOTOCELL AND HAND-OFF-AUTO SW ITCH. (1) UN-SW

ITCHED 16 CIRCUIT

LOAD CENTER. 22KAIC INTERRUPTING CAPACITY (VERIFY W ITH UTILITY). PROVIDE

SUMMERLAND GRAY

FINISH.

MODEL: CP3B

MANUFACTURERS: MILL-BANK.

DRIVE BARRIER PIPE GATES

GATE DIMENSIONS: CLEAR OPENING PER GATE LEAF: 13'-0" WIDE. OVERALL GATE HEIGHT:

4'-0". DESING TO ALLOW FOR ATTACHMENT OF GATE OPENERS AND 90 DEGREE OPENING.

MATERIALS: GATE FRAME FABRICATED FROM 6-5/8" O.D. SCHEDULE 40 STEEL PIPE.

INCLUDE DIAGONAL PIPE BRACING FOR STRUCTURAL RIGIDITY. HINGE POST TO BE

CONSTRUCTED OF COMPATIBLE SCHEDULE 40 STEEL PIPE SIZED AS REQUIRED FOR

STRUCTURAL SUPPORT.

HARDWARE: PROVIDE HEAVY-DUTY INDUSTRIAL HINGES, WELDED PER MANUFACTURER

RECOMMENDATIONS, SUITABLE FOR REPEATED VEHICULAR ACCESS USE. INCLUDE

PROVISIONS AS REQUIRED TO CHAIN GATE SHUT.

FINISH: ALL STEEL SURFACES TO RECEIVE SAFETY-YELLOW POWDER-COAT FINISH,

SAFETY MARKINGS: APPLY CONTINUOUS RED-AND-WHITE REFLECTIVE SAFETY STRIPING

ALONG THE FULL LENGTH OF THE GATE ON BOTH THE ENTRANCE AND EXIT SIDES.

REFLECTIVE MARKINGS SHALL COMPLY WITH APPLICABLE MUTCD VISIBILITY STANDARDS.

GATE OPERATORS

OPERATORS: PROVIDE TWO (2) SWING-TYPE GATE OPERATORS. BATTERY BACKUP, TWO

(2) 7AH BATTERIES CAPABLE OF APPROXIMATELY 146 CYCLES AND UP TO 24 DAYS

STANDBY OPERATION. PROVIDE A 90-DEGREE OPENING IN APPROXIMATELY 15 SECONDS,

ACCEPT 120/240V INPUT POWER, RATED FOR A 1,200-POUND GATE AT 12'-0" LENGTH.

MANUFACTURER: LIFTMASTER, MODEL: CSW24UL

ACCESSORIES: PROVIDE FIVE (5) REMOTE CONTROLS FOR WIRELESS ACCESS;

ENTRAPMENT SENSOR: LIFTMASTER LMRP01 PHOTO EYE SENSOR; SHADOW/SAFETY

LOOP: LIFTMASTER LOOPDETLM LOOP DETECTOR MODULE WITH COMPLETE IN-GROUND

LOOP CABLE; FREE EXIT / SAFETY SENSOR: OPTEX OVS-02GT SENSOR.

CONTROL FEATURES: TIMER: TORK OR LIFTMASTER SEVEN-DAY PROGRAMMABLE TIMER

WITH HOLIDAY SCHEDULING FOR AUTOMATIC OPEN/CLOSE CONTROL; KEYPAD: LINEAR

AK-11 FOR KEYPAD ENTRY ACCESS.

MOUNTING: OPERATORS: CONCRETE MOUNTING PAD FOR EACH SWING GATE OPERATOR,

MINIMUM 24" X 24" PLAN DIMENSIONS, REINFORCED, WITH TOP OF PAD A MINIMUM OF 8"

ABOVE FINISHED GRADE AND FINAL PAD HEIGHT AS REQUIRED TO ACHIEVE PROPER

ALIGNMENT BETWEEN OPERATOR ACTUATOR ARM AND GATE ATTACHMENT POINT. PAD

SHALL BE LEVEL, NON-FLEXING, AND SIZED/ANCHORED TO RESIST OPERATOR TORQUE

UNDER FULL LOAD. COORDINATE FINAL OPERATOR ELEVATION AND ARM GEOMETRY WITH

GATE FABRICATOR PRIOR TO SETTING ANCHORS TO ENSURE 90° OPENING, CORRECT

THROW, AND CLEARANCES FOR ARM TRAVEL AND COVER REMOVAL. CONDUIT SHALL

ENTER FROM BELOW PAD; PROVIDE SLEEVES AS REQUIRED; FREE EXIT / SAFETY SENSOR:

2” SQUARE POST,4’-0” HIGH, BLACK POWER COAT FINISH, FOUNDATION AS REQUIRED;

KEYPAD: GOOSENECK POST WITH 1’-0” EXTENSION AND 48-54” HEIGHT TO BE

COORDINATED IN FIELD. KEYPAD RAIN HOOD. BLACK POWER COAT FINISH, FOUNDATION

AS REQUIRED;

PHOTOEYE / ENTRAPMENT SENSOR: WELDED BRACKET TO GATE SUPPORT POSTS,

DESIGNED TO PROVIDE FLAT SURFACE FOR SENSOR MOUNTING. YELLOW POWER COAT

TO MATCH GATE PAINT.

GENERAL REQUIREMENTS:

COMPLIANCE: PENNSYLVANIA UNIFORM CONSTRUCTION CODE, CURRENT EDITION.

PERMITS AND INSPECTIONS: SECURE ALL PERMITS AND SCHEDULE INSPECTIONS

REQUIRED BY AUTHORITIES HAVING JURISDICTION.

COORDINATION: DRAWINGS ARE DIAGRAMMATIC AND ARE GENERALLY INDICATIVE OF THE

WORK TO BE INSTALLED BUT MAY NOT INDICATE ALL BENDS, FITTINGS, OBSTRUCTIONS,

AND SUPPORTS REQUIRED TO MEET DESIGN INTENT.

COORDINATE CONSTRUCTION OF CONTRACTED WORK WITH WORK SHOWN ON ALL

CONTRACT DOCUMENTS AND WORK BY OTHER TRADES. COST ASSOCIATED WITH

CONSTRUCTION MODIFICATIONS AS A RESULT OF LACK OF COORDINATION SHALL BE

CORRECTED BY THE CONTRACTOR AT NO ADDITIONAL COST.

CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING EXISTING CONDITIONS,

DEMOLITION REQUIREMENTS, AND DIMENSIONS DURING BIDDING BEFORE PROCEEDING

WITH WORK.

COMPLY WITH OWNER’S REGULATIONS FOR USE OF PREMISES.

UTILITY SERVICES: NOTIFY OWNER, ARCHITECT, AUTHORITIES HAVING JURISDICTION, AND

ENTITIES OWNING OR CONTROLLING WIRES, CONDUITS, PIPES, DUCTS, AND OTHER

SERVICES AFFECTED BY THE WORK BEFORE COMENCING OPERATIONS. DISCONNECT AND

CAP PIPES, DUCTS, AND OTHER SERVICES AS REQUIRED BY AUTHORITIES HAVING

JURISDICTION AND AS REQUIRED FOR THE WORK. MAINTAIN EXISTING SERVICES UNLESS

OTHERWISE INDICATED. KEEP IN SERVICE AND PROTECT AGAINST DAMAGE DURING

OPERATIONS. PROVIDE TEMPORARY SERVICES DURING INTERRUPTIONS TO EXISTING

UTILITIES. DO NOT INTERRUPT UTILITIES SERVING FACILITIES OCCUPIED BY OWNER OR

OTHERS UNLESS PERMITTED UNDER THE FOLLOWING CONDITIONS AND THEN ONLY AFTER

ARRANGING FOR TEMPORARY UTILITY SERVICES. NOTIFY ARCHITECT AND BUILDING

OWNER/OPERATOR NOT LESS THAN ONE WEEK IN ADVANCE OF PROPOSED UTILITY

INTERRUPTIONS. OBTAIN ARCHITECT AND BUILDING OWNER/OPERATOR’S WRITTEN

PERMISSION BEFORE PROCEEDING WITH UTILITY INTERRUPTIONS.

JOB SITE SAFETY: TEMPORARY SHORING AND CONSTRUCTION METHODS ARE THE SOLE

RESPONSIBILITY OF THE CONTRACTOR.

INSTALLATION: PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY FOR

COMPLETION OF WORK. ALL EQUIPMENT SHALL BE UL LISTED FOR INTENDED SERVICES.

MATERIALS: PROVIDE MATERIALS THAT ARE NEW, OF THE BEST OF THEIR RESPECTIVE

KINDS, WITHOUT IMPERFECTIONS OR BLEMISHES, AND PROTECTED FROM THE ELEMENTS

PRIOR TO CONSTRUCTION.

INSTALL ALL EQUIPMENT IN ACCORDANCE WITH EQUIPMENT MANUFACTURER’S

INSTRUCTIONS.

PROVIDE STRUCTURAL STEEL MEMBERS AS REQUIRED FOR SUPPORT OF EQUIPMENT AND

MATERIALS. PROVIDE ALL HANGERS AND SUPPORTS, AS SPECIFIED, DETAILED, OR IN

ACCORDANCE WITH ACCEPTED INDUSTRY STANDARDS.

CONTRACT CLOSEOUT: CLEAN ALL SYSTEMS AND EQUIPMENT READY FOR OWNER’S USE.

PREPARE AND DELIVER TWO OPERATION AND MAINTENANCE MANUALS CONSISTING OF

ALL SYSTEMS AND COMPONENTS. PERFORM START-UP OF EQUIPMENT AND

DEMONSTRATE INTENDED PERFORMANCE AND SEQUENCE OF OPERATION IN PRESENCE

OF OWNER. PROVIDE TRAINING SESSION FOR OWNER’S PERSONNEL FOR OPERATION OF

EQUIPMENT.

NEW WORK:

PROVIDE FEEDERS AND BRANCH CIRCUITS WITH SOLID CONDUCTORS FOR NO. 10 AWG

AND SMALLER AND STRANDED CONDUCTORS FOR NO. 8 AWG AND LARGER.

PROVIDE SEPARATE UNSHARED NEUTRAL CONDUCTOR(S) FOR ALL BRANCH CIRCUITS

UTILIZING A NEUTRAL AND ALL FEEDERS REQUIRING A NEUTRAL. SHARING OF NEUTRAL

CONDUCTORS BETWEEN ANY CIRCUIT (BRANCH OR FEEDER) IS NOT PERMITTED.

MULTIWIRE BRANCH CIRCUITS ARE NOT PERMITTED.

PROVIDE EVERY CONDUIT CONTAINING 120V OR GREATER WIRING WITH SEPARATE

INSULATED GROUND WIRE RATED FOR 600V, UNLESS NOTED OTHERWISE.

ALL SINGLE PHASE CIRCUITS ARE (2)#12, (1)#12G, 3/4”C AND ALL THREE PHASE CIRCUITS

ARE (3)#12, (1)#12G, 3/4"C UNLESS OTHERWISE NOTED.

FOR EACH PANELBOARD OR MODIFIED PANELBOARD, PROVIDE A TYPED DIRECTORY.

INDICATE SOURCE OF POWER FOR PANEL, ROOM AND ROOM NUMBER, EQUIPMENT

SERVED, SPARE, OR PROVISIONAL SPACE, AS APPLICABLE. MOUNT DIRECTORY INSIDE

PANELBOARD DOOR.

PROVIDE ALL LUGS AND TERMINATIONS RATED FOR 75 DEGREES C.

REVISIONS

SEAL:

4/16/2026

UE

UE

<E> UTILITY POLE

25344202

METER BASE

PANEL L1A

E601

PROPOSED

UTILITY POLE

E601

25' - 0"

CONTACT:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

SEAL:

PROJECT:

PROJECT NUMBER:

DATE:

DRAWING TITLE:

DRAWING NUMBER:

COPYRIGHT © 2024

4/

/2

9:

:0

AM

H:

\R

EV

IT

\A J2

6_ M

EP

_C

EN

TR

AL

_R

_f al ve yH

CU

.rv t

L.E.L.

L.E.L.

C.G.M.

426005.00

E101

SITE PLAN -

ELECTRICAL

04/15/2026

C.G.M.

ROUTE 116

TRAILHEAD

HANOVER TROLLEY

TRAIL

SCALE: 1/16" = 1'-0"

SITE PLAN - ELECTRICAL1

N

REVISIONS

L1A

100A, MCB

240Y/120V, 1Ø, 3W

10 KAIC

(3)#1 AL

(1)#6 ALG

3"C.

(3)#1 AL

(1)#6 ALG

3"C.

UE

UE

GR

GR

KEYPAD

PHOTO

EYE/ENTRAPMENT

SENSOR

REFLECTOR

18/4

STRANDED

OPERATOR

SHADOW/SAFETY LOOP

GATE SWING ARC

SWING

GATE(TYPICAL)

OPERATOR

18/4

TWISTED/SHIELDED18/4

STRANDED

UE

CONCRETE PEDESTAL

FREE

EXIT/SAFETY

SENSOR

20'

- 0

2' - 2 1

/32

6' - 0"PANEL/METER BASE

1' - 9 3

1/3 2"

30' - 0"

UE

POST

UE

L1A-2

L1A-1

(2) 1" CONDUIT

UE

METER BASE

TO UTILITY

MIN. 3" (TYPICAL)

MIN. 3" (TYPICAL)

3'- 0"

MIN. 3"

(TYPICAL) 7.5" (TYPICAL)

1'- 0"

WARNING TAPE

FINISHED GRADE

3"C. PVC

SCH 40

(TYPICAL)

ACTIVE

SPARE

'-0

TH

RE

E

SI

DE

S

5'-0"

MIN.

#4/O BARE

COPPER

GROUND ROD. BURY SO THAT

TOP OF ROD IS 2'-0" B.F.G.

(TYPICAL)

EXOTHERMIC

CONNECTOR (TYPICAL)

1 1/2" RGS CONDUIT

BLDG

TO RESPECTIVE

GROUND BAR

FINISHED GRADE

GROUND CONDUCTOR

(SEE PLAN DWG FOR SIZE

AND TYPE)

"CLEAN" SAND

HIGH DENSITY GREEN

POLYETHYLENE

INSPECTION WELL

BUNDY HYTAIL TYPE

GKG434 CONNECTORS

OR EQUAL

3/4" X 10'-0" COPPERCLAD

PLATED STEEL GROUND ROD

4" 6"

METER

ELECTRICAL PANEL

60"

NOTES:

1. PROVIDE TRENCHING, WIRE, AND CONDUIT TO UTILITY POLE. REFER TO DUCT BANK DETAIL AND

SINGLE LINE DIAGRAM FOR ADDITIONAL INFORMATION. PROVIDE 30'-0" SCH 80 CONDUIT FOR

UTILITY POLE RISER AND REQUIRED CONDUCTOR LENGTH FOR TERMINATION TO UTILITY

EQUIPMENT BY UTILITY.

2. PROVIDE (2) 3" CONDUIT CAPPED AND CONCRETE ENCASED IN GROUND.

3. PROVIDE (3) 12 GAUGE CHANNELS, (2) SPRING NUTS PER CHANNEL, HEX NUT, AND LOCK WASHER

SECURELY MOUNTED TO SUPPORT POSTS.

3'-0" Min.

DETECTABLE

WARRING RIBBON

12" 24" Min.

of cover

RNC SCH 80

12" Min.

CONDUIT STRAP

SEE NOTE 2

SEE NOTE 3

ALL HARDWARE SHALL BE BONDED

AND GROUNDED PER NEC

CONCRETE ENCASED

POSTS (3' Min.) INTO

GROUND

COUNTERPOISE

1 REFER TO STRUCTURAL PLANS FOR FOUNDATIONS.

2 REFER TO SPECIFICATIONS FOR GATE CONSTRUCTION DETAILS.

3 PROVIDE ADJUSTABLE MOUNTING BRACKET TO MOUNT FREE EXIT / SAFETY SENSOR

AT 30 DEGREE ANGLE. ADJUST IN FIELD AS REQUIRED.

4 PROVIDE #6 BARE COPPER AND GROUND ROD FOR EACH PEDESTAL MOUNTED

OPERATOR.

5 INSTALL SHADOW LOOP / SAFETY LOOP AS PER MANUFACTURERS INSTRUCTIONS.

CONTACT:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

SEAL:

PROJECT:

PROJECT NUMBER:

DATE:

DRAWING TITLE:

DRAWING NUMBER:

COPYRIGHT © 2024

4/

/2

9:

:0

AM

H:

\R

EV

IT

\A J2

6_ M

EP

_C

EN

TR

AL

_R

_f al ve yH

CU

.rv t

L.E.L.

L.E.L.

C.G.M.

426005.00

E601

SINGLE LINE

DIAGRAM AND

DETAILS

04/15/2026

C.G.M.

ROUTE 116

TRAILHEAD

HANOVER TROLLEY

TRAIL

SCALE: 1/4" = 1'-0"

ENLARGED GATE PLAN1

SCALE: 1/8" = 1'-0"

SINGLE LINE DIAGRAM2

SCALE: NONE

TYPICAL DUCTBANK DETAIL3

SCALE: NONE

TYPICAL GROUNDING COUNTERPOISE DETAIL4

SCALE: NONE

GROUND WELL DETAIL "B"5

SCALE: 1/8" = 1'-0"

PANEL/METER BASE DETAIL6

NOTES:

N

TOTAL DEMAND LOAD: 3000

TOTAL CONNECTED LOAD: 3000

3,000 VA 0 VA 0 VA

19 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 20

17 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 18

15 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 16

13 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 14

11 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 12

9 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 10

7 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 8

5 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 6

3 SPARE 20 A 1 0 0 1 20 A SPARE 4

1 LIFT MASTER GATE 20 A 1 1,500 1,500 1 20 A LIFT MASTER GATE 2

CKT N DESCRIPTION AMP P A B C P AMP DESCRIPTION N CKT

100 A SQUARE D, QO

LOCATION: MAIN BREAKER: PANEL TYPE:

SURFACE 100 A 20

MOUNTING: BUS AMP: TOTAL POLES:

L1A 208Y/120V, 3Ø, 4 WIRE 10,000

PANEL DESIGNATION: VOLTAGE: MIN. AIC: NOTES:

REVISIONS