3-C2 - ELECTRICAL CONTRACT DRAWINGS-SEALED.pdf
PDF 702 KB Posted
- Attached to
- Hanover Trolley Trail - Route 116 Trailhead
- Solicitation number
- Not on record
- Issued by
- Blair County, Pennsylvania
About this file
This electrical contract drawing document pertains to the Route 116 Trailhead project for the Hanover Trolley Trail, managed by the York County Rail Trail Authority in Pennsylvania. The project involves the installation of electrical infrastructure including a 100-ampere, 208Y/120-volt, three-phase service with a surface-mounted panelboard and meter base. The work encompasses the installation of two swing-type gate operators with battery backup systems, complete with remote controls, safety sensors, keypads, and photoeye entrapment sensors. Additional electrical work includes trenching and conduit installation to connect to an existing utility pole, grounding systems with copper-clad steel ground rods, and the installation of underground electrical lines with concrete encasement in specified areas. The contract period is ninety calendar days, with sealed bids due May 29, 2026, at 10:00 AM via the PennBid Program. A bid bond equal to 10% of the maximum bid is required, and the project is subject to Pennsylvania Prevailing Wage Act requirements.
The electrical specifications require all materials to be new, UL-listed, and compliant with the National Electrical Code and Pennsylvania Uniform Construction Code. Key equipment manufacturers specified include Mill-Bank for the meter/load center enclosure (Model CP3B), Liftmaster for gate operators (Model CSW24UL), Linear for keypads (Model AK-11), and Optex for safety sensors. The contractor is responsible for all labor, materials, equipment, trenching, permit acquisition, and scheduling inspections with authorities having jurisdiction. Contract closeout requirements include system cleaning, preparation of two operation and maintenance manuals, equipment startup, and demonstration and training for the owner's personnel. No pricing information, set-asides, or funding sources are specified in the drawing document itself, as this is a technical specification rather than a bid summary document.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SYMBOL AND ABBREVIATION SCHEDULE
SYMBOL DESCRIPTIONABBR.
PANELBOARD, 120/208V, 208V OR 240V, SURFACE OR FLOOR MOUNTEDPNLBD
OR PNL
UNDERGROUND ELECTRICAL LINEUE
KEYPADKP
UTILITY METERMU
GROUND ROD LOCATIONGR
AMPEREA
ABOVE FINISHED FLOORAFF
AMERICAN WIRE GAUGEAWG
ELECTRICALELEC
GROUNDG, GND,
GRD
THOUSAND CIRCULAR MILSKCMIL
NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATIONNEMA
MAIN CIRCUIT BREAKERMCB
NATIONAL ELECTRICAL CODENEC
POLEP
VOLTSV
WIREW
MOUNTING HEIGHT SCHEDULE
TOP PROTECTIVE DEVICE TO BE 72" ABOVE FINISHED FLOORPANELBOARDS
NOTES (FOR MOUNTING HEIGHT SCHEDULE):
1. UNLESS INDICATED OTHERWISE, DEVICE MOUNTING HEIGHTS ARE TO CENTER LINE OF DEVICE.
2. REFER TO FLOOR PLANS FOR DEVICES MOUNTED AT HEIGHTS DIFFERING FROM HEIGHTS SCHEDULED.
DEVICES INDICATED ON FLOOR PLANS WITH A 'C' NOTATION SHALL BE MOUNTED AT COUNTER HEIGHT.
3. MOUNTING HEIGHTS OF ALL DEVICES SHALL COMPLY WITH ICC/ANSI A117.1. THIS INCLUDES ALL
FORWARD AND SIDE REACH REQUIREMENTS FOR BOTH UNOBSTRUCTED AND OBSTRUCTED REACH
RANGES AS APPLICABLE.
CONTACT:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SEAL:
PROJECT:
PROJECT NUMBER:
DATE:
DRAWING TITLE:
DRAWING NUMBER:
COPYRIGHT © 2024
4/
/2
9:
:0
AM
H:
\R
EV
IT
\A J2
6_ M
EP
_C
EN
TR
AL
_R
_f al ve yH
CU
.rv t
L.E.L.
L.E.L.
C.G.M.
426005.00
E001
SYMBOL AND
ABBREVIATION
SCHEDULE
04/15/2026
C.G.M.
ROUTE 116
TRAILHEAD
HANOVER TROLLEY
TRAIL
GENERAL NOTES:SPECIFICATIONS:
SUBMITTALS:
PROVIDE SUBMITTAL DATA FOR THE FOLLOWING:
• PANELBOARDS
• METERBASES
• GATE OPENERS AND ACCESSORIES
• GATE
CONDUCTORS AND CABLES:
GENERAL: LISTED AND LABELED AS DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND USE. ROHS COMPLIANT. COMPLY WITH WIRE
AND CABLE MARKING ACCORDING TO UL'S "WIRE AND CABLE MARKING AND APPLICATION
GUIDE."
BUILDING WIRE: COPPER, COMPLYING WITH ASTM B 3 FOR BARE ANNEALED COPPER AND
WITH ASTM B 8 FOR STRANDED CONDUCTORS. THHN/THWN-2 CONDUCTOR INSULATION,
COMPLYING WITH UL 83.
CONNECTORS: UL LISTED FACTORY-FABRICATED CONNECTORS AND SPLICES OF SIZE,
AMPACITY RATING, MATERIAL, TYPE, AND CLASS FOR APPLICATION AND SERVICE
INDICATED.
GROUNDING AND BONDING:
COMPLY WITH UL 467 FOR GROUNDING AND BONDING MATERIALS AND EQUIPMENT.
CONDUCTORS: INSTALL SOLID CONDUCTOR FOR NO. 10 AWG AND SMALLER, AND
STRANDED CONDUCTORS FOR NO. 8 AWG AND LARGER UNLESS OTHERWISE INDICATED.
INSULATED CONDUCTORS: COPPER WIRE OR CABLE INSULATED FOR 600V UNLESS
OTHERWISE REQUIRED BY APPLICABLE CODE OR AUTHORITIES HAVING JURISDICTION.
BARE COPPER CONDUCTORS: SOLID CONDUCTORS: ASTM B 3
STRANDED CONDUCTORS: ASTM B 8, BONDING CABLE: 28 KCMIL, 14 STRANDS OF
NO. 17 AWG CONDUCTOR, 1/4 INCH IN DIAMETER
BONDING CONDUCTOR: NO. 4 OR NO. 6 AWG, STRANDED CONDUCTOR
GROUND ROD CLAMPS: MECHANICAL TYPE, COPPER OR COPPER ALLOY, TERMINAL WITH
HEX HEAD
GROUND ROD: COPPER-CLAD STEEL ROD, 8’-0” LONG MINIMUM, 5/8” DIAMETER.
METAL CONDUIT, TUBING, AND FITTINGS:
MINIMUM RACEWAY SIZE: 3/4 INCH.
RIGID METAL CONDUIT (RMC): COMPLY WITH ANSI C80.1, UL6.
LIQUIDTIGHT FLEXIBLE METAL CONDUIT (LFMC) AND FITTINGS: COMPLY WITH UL 360,
FLEXIBLE STEEL CONDUIT WITH PVC JACKET.
FITTINGS: COMPLY WITH NEMA FB 1 AND UL 514B.
RMC IMC FITTINGS: THREADED, COMPLY WITH NEMA FB 2.10.
LFMC FITTINGS: COMPLY WITH NEMA FB 2.20.
NONMETALLIC CONDUIT AND TUBING:
RIGID NONMETALLIC CONDUIT (RNC): COMPLY WITH NEMA TC 2 AND UL 651, SCHEDULE 40
PVC.
FITTINGS: COMPLY WITH NEMA TC 3.
SOLVENTS AND ADHESIVES: AS RECOMMENDED BY CONDUIT MANUFACTURER.
RACEWAY APPLICATIONS:
OUTDOORS: USE THE FOLLOWING WIRING METHODS:
EXPOSED: RMC.
CONCEALED: RMC OR IMC.
UNDERGROUND: RNC, 1 INCH MINIMUM, CONCRETE ENCASE UNDER ROADWAYS,
DRIVEWAYS, AND MACADAM AREAS WITH MINIMUM 3 INCHES OF CONCRETE ON 3 SIDES.
UNDERGROUND, SERVICE ENTRANCE: RNC, CONCREATE ENCASE WHERE REQUIRED BY
UTILITY. PROVIDE RMC LONG RADIS SWEEPS WHEN REQUIRED BY UTILITY.
FINAL CONNECTION TO VIBRATING EQUIPMENT (INCLUDING TRANSFORMERS AND
HYDRAULIC, PNEUMATIC, ELECTRIC SOLENOID, OR MOTOR-DRIVEN EQUIPMENT): LFMC.
BOXES AND FITTINGS:
PULL AND JUNCTION BOXES (INTERIOR, EXPOSED, DRY, DAMP OR WET LOCATIONS): CAST-
METAL BOXES, COMPLY WITH NEMA FB 1 AND UL 1773, CAST ALUMINUM WITH GASKETED
COVER, NEMA 250 TYPE 3R.
OUTLET AND DEVICE BOXES (INTERIOR, EXPOSED, DRY, DAMP OR WET LOCATIONS): CAST-
METAL BOXES, NEMA FB 1, CAST ALUMINUM WITH GASKETED COVER, NEMA 250 TYPE 3R.
EXTERIOR PULL BOXES AND HANDHOLES:
CAST METAL BOXES: CAST ALUMINUM WITH GASKETED COVER WITH NONSKID FINISH.
POLYMER CONCRETE HANDHOLES: WEATHERPROOF, MOLDED POLYMER CONCRETE UNIT
WITH HEAVY-DUTY COVER AND NONSKID FINISH. UL LISTED. PROVIDE LOGO TO READ
‘ELECTRIC'.
MANUFACTURER: QUAZITE OR APPROVED EQUAL.
LOAD CENTER:
LISTINGS: COMPLY WITH NEMA PB 1. RATED FOR SERVICE ENTRANCE.
OVERCURRENT PROTECTIVE DEVICES: PLUG-IN CIRCUIT BREAKERS, REPLACEABLE
WITHOUT DISTURBING ADJACENT UNITS.
ENCLOSURE: NEMA 3R, LOCKABLE
BUS: COPPER (INCLUDING NEUTRAL AND GROUND BUS).
EQUIPMENT GROUND BUS: ADEQUATE FOR FEEDER AND BRANCH-CIRCUIT EQUIPMENT
GROUND CONDUCTORS; BONDED TO BOX.
LOAD BALANCING: MEASURE LOAD BALANCING AND MAKE CIRCUIT CHANGES.
FULLY RATED, NO SERIES RATING ALLOWED.
MANUFACTURERS: EATON/CUTLER HAMMER, GENERAL ELECTRIC, SIEMENS-ITE, OR
SQUARE D.
WIRING DEVICES AND COMPONENTS:
HEAVY-DUTY SPECIFICATION GRADE OR INDUSTRIAL SPECIFICATION GRADE.
MANUFACTURERS: LEVITON, HUBBELL, EATON, OR PASS AND SEYMOUR.
GFCI RECEPTACLES: 125 V, 20 A: COMPLY WITH NEMA WD 1, NEMA WD 6, UL 498, UL 943
CLASS A, AND FS W-C-596. FEED-THROUGH TYPE WITH INDICATOR LIGHT FOR
MALFUNCTION OR IMPROPER GFCI PROTECTION.
WEATHERPROOF "WHILE IN USE" COVER: SHALL BE PROVIDED FOR ALL RECEPTACLES
INSTALLED IN WET LOCATIONS PER NATIONAL ELECTRICAL CODE. THERMOPLASTIC CLEAR
COVER RATED NEMA 3R "WHILE IN USE".
METER ENCLOSURES
ACCEPTABLE TO LOCAL UTILITY COMPANY.
PEDESTAL MOUNTED METER/LOAD CENTER ENCLOSURE.
SINGLE METER, RINGLESS SOCKET WITH LEVER BYPASS. 200A-120/240V-1PH-3W , 5 JAW .
INTEGRATED
PANEL W ITH (1) 200A MAIN DISCONNECT. (1) SW ITCHED 16 CIRCUIT LOAD CENTER W ITH
INTEGRATED DIN
RAIL MOUNTED TIME CLOCK, PHOTOCELL AND HAND-OFF-AUTO SW ITCH. (1) UN-SW
ITCHED 16 CIRCUIT
LOAD CENTER. 22KAIC INTERRUPTING CAPACITY (VERIFY W ITH UTILITY). PROVIDE
SUMMERLAND GRAY
FINISH.
MODEL: CP3B
MANUFACTURERS: MILL-BANK.
DRIVE BARRIER PIPE GATES
GATE DIMENSIONS: CLEAR OPENING PER GATE LEAF: 13'-0" WIDE. OVERALL GATE HEIGHT:
4'-0". DESING TO ALLOW FOR ATTACHMENT OF GATE OPENERS AND 90 DEGREE OPENING.
MATERIALS: GATE FRAME FABRICATED FROM 6-5/8" O.D. SCHEDULE 40 STEEL PIPE.
INCLUDE DIAGONAL PIPE BRACING FOR STRUCTURAL RIGIDITY. HINGE POST TO BE
CONSTRUCTED OF COMPATIBLE SCHEDULE 40 STEEL PIPE SIZED AS REQUIRED FOR
STRUCTURAL SUPPORT.
HARDWARE: PROVIDE HEAVY-DUTY INDUSTRIAL HINGES, WELDED PER MANUFACTURER
RECOMMENDATIONS, SUITABLE FOR REPEATED VEHICULAR ACCESS USE. INCLUDE
PROVISIONS AS REQUIRED TO CHAIN GATE SHUT.
FINISH: ALL STEEL SURFACES TO RECEIVE SAFETY-YELLOW POWDER-COAT FINISH,
SAFETY MARKINGS: APPLY CONTINUOUS RED-AND-WHITE REFLECTIVE SAFETY STRIPING
ALONG THE FULL LENGTH OF THE GATE ON BOTH THE ENTRANCE AND EXIT SIDES.
REFLECTIVE MARKINGS SHALL COMPLY WITH APPLICABLE MUTCD VISIBILITY STANDARDS.
GATE OPERATORS
OPERATORS: PROVIDE TWO (2) SWING-TYPE GATE OPERATORS. BATTERY BACKUP, TWO
(2) 7AH BATTERIES CAPABLE OF APPROXIMATELY 146 CYCLES AND UP TO 24 DAYS
STANDBY OPERATION. PROVIDE A 90-DEGREE OPENING IN APPROXIMATELY 15 SECONDS,
ACCEPT 120/240V INPUT POWER, RATED FOR A 1,200-POUND GATE AT 12'-0" LENGTH.
MANUFACTURER: LIFTMASTER, MODEL: CSW24UL
ACCESSORIES: PROVIDE FIVE (5) REMOTE CONTROLS FOR WIRELESS ACCESS;
ENTRAPMENT SENSOR: LIFTMASTER LMRP01 PHOTO EYE SENSOR; SHADOW/SAFETY
LOOP: LIFTMASTER LOOPDETLM LOOP DETECTOR MODULE WITH COMPLETE IN-GROUND
LOOP CABLE; FREE EXIT / SAFETY SENSOR: OPTEX OVS-02GT SENSOR.
CONTROL FEATURES: TIMER: TORK OR LIFTMASTER SEVEN-DAY PROGRAMMABLE TIMER
WITH HOLIDAY SCHEDULING FOR AUTOMATIC OPEN/CLOSE CONTROL; KEYPAD: LINEAR
AK-11 FOR KEYPAD ENTRY ACCESS.
MOUNTING: OPERATORS: CONCRETE MOUNTING PAD FOR EACH SWING GATE OPERATOR,
MINIMUM 24" X 24" PLAN DIMENSIONS, REINFORCED, WITH TOP OF PAD A MINIMUM OF 8"
ABOVE FINISHED GRADE AND FINAL PAD HEIGHT AS REQUIRED TO ACHIEVE PROPER
ALIGNMENT BETWEEN OPERATOR ACTUATOR ARM AND GATE ATTACHMENT POINT. PAD
SHALL BE LEVEL, NON-FLEXING, AND SIZED/ANCHORED TO RESIST OPERATOR TORQUE
UNDER FULL LOAD. COORDINATE FINAL OPERATOR ELEVATION AND ARM GEOMETRY WITH
GATE FABRICATOR PRIOR TO SETTING ANCHORS TO ENSURE 90° OPENING, CORRECT
THROW, AND CLEARANCES FOR ARM TRAVEL AND COVER REMOVAL. CONDUIT SHALL
ENTER FROM BELOW PAD; PROVIDE SLEEVES AS REQUIRED; FREE EXIT / SAFETY SENSOR:
2” SQUARE POST,4’-0” HIGH, BLACK POWER COAT FINISH, FOUNDATION AS REQUIRED;
KEYPAD: GOOSENECK POST WITH 1’-0” EXTENSION AND 48-54” HEIGHT TO BE
COORDINATED IN FIELD. KEYPAD RAIN HOOD. BLACK POWER COAT FINISH, FOUNDATION
AS REQUIRED;
PHOTOEYE / ENTRAPMENT SENSOR: WELDED BRACKET TO GATE SUPPORT POSTS,
DESIGNED TO PROVIDE FLAT SURFACE FOR SENSOR MOUNTING. YELLOW POWER COAT
TO MATCH GATE PAINT.
GENERAL REQUIREMENTS:
COMPLIANCE: PENNSYLVANIA UNIFORM CONSTRUCTION CODE, CURRENT EDITION.
PERMITS AND INSPECTIONS: SECURE ALL PERMITS AND SCHEDULE INSPECTIONS
REQUIRED BY AUTHORITIES HAVING JURISDICTION.
COORDINATION: DRAWINGS ARE DIAGRAMMATIC AND ARE GENERALLY INDICATIVE OF THE
WORK TO BE INSTALLED BUT MAY NOT INDICATE ALL BENDS, FITTINGS, OBSTRUCTIONS,
AND SUPPORTS REQUIRED TO MEET DESIGN INTENT.
COORDINATE CONSTRUCTION OF CONTRACTED WORK WITH WORK SHOWN ON ALL
CONTRACT DOCUMENTS AND WORK BY OTHER TRADES. COST ASSOCIATED WITH
CONSTRUCTION MODIFICATIONS AS A RESULT OF LACK OF COORDINATION SHALL BE
CORRECTED BY THE CONTRACTOR AT NO ADDITIONAL COST.
CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING EXISTING CONDITIONS,
DEMOLITION REQUIREMENTS, AND DIMENSIONS DURING BIDDING BEFORE PROCEEDING
WITH WORK.
COMPLY WITH OWNER’S REGULATIONS FOR USE OF PREMISES.
UTILITY SERVICES: NOTIFY OWNER, ARCHITECT, AUTHORITIES HAVING JURISDICTION, AND
ENTITIES OWNING OR CONTROLLING WIRES, CONDUITS, PIPES, DUCTS, AND OTHER
SERVICES AFFECTED BY THE WORK BEFORE COMENCING OPERATIONS. DISCONNECT AND
CAP PIPES, DUCTS, AND OTHER SERVICES AS REQUIRED BY AUTHORITIES HAVING
JURISDICTION AND AS REQUIRED FOR THE WORK. MAINTAIN EXISTING SERVICES UNLESS
OTHERWISE INDICATED. KEEP IN SERVICE AND PROTECT AGAINST DAMAGE DURING
OPERATIONS. PROVIDE TEMPORARY SERVICES DURING INTERRUPTIONS TO EXISTING
UTILITIES. DO NOT INTERRUPT UTILITIES SERVING FACILITIES OCCUPIED BY OWNER OR
OTHERS UNLESS PERMITTED UNDER THE FOLLOWING CONDITIONS AND THEN ONLY AFTER
ARRANGING FOR TEMPORARY UTILITY SERVICES. NOTIFY ARCHITECT AND BUILDING
OWNER/OPERATOR NOT LESS THAN ONE WEEK IN ADVANCE OF PROPOSED UTILITY
INTERRUPTIONS. OBTAIN ARCHITECT AND BUILDING OWNER/OPERATOR’S WRITTEN
PERMISSION BEFORE PROCEEDING WITH UTILITY INTERRUPTIONS.
JOB SITE SAFETY: TEMPORARY SHORING AND CONSTRUCTION METHODS ARE THE SOLE
RESPONSIBILITY OF THE CONTRACTOR.
INSTALLATION: PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY FOR
COMPLETION OF WORK. ALL EQUIPMENT SHALL BE UL LISTED FOR INTENDED SERVICES.
MATERIALS: PROVIDE MATERIALS THAT ARE NEW, OF THE BEST OF THEIR RESPECTIVE
KINDS, WITHOUT IMPERFECTIONS OR BLEMISHES, AND PROTECTED FROM THE ELEMENTS
PRIOR TO CONSTRUCTION.
INSTALL ALL EQUIPMENT IN ACCORDANCE WITH EQUIPMENT MANUFACTURER’S
INSTRUCTIONS.
PROVIDE STRUCTURAL STEEL MEMBERS AS REQUIRED FOR SUPPORT OF EQUIPMENT AND
MATERIALS. PROVIDE ALL HANGERS AND SUPPORTS, AS SPECIFIED, DETAILED, OR IN
ACCORDANCE WITH ACCEPTED INDUSTRY STANDARDS.
CONTRACT CLOSEOUT: CLEAN ALL SYSTEMS AND EQUIPMENT READY FOR OWNER’S USE.
PREPARE AND DELIVER TWO OPERATION AND MAINTENANCE MANUALS CONSISTING OF
ALL SYSTEMS AND COMPONENTS. PERFORM START-UP OF EQUIPMENT AND
DEMONSTRATE INTENDED PERFORMANCE AND SEQUENCE OF OPERATION IN PRESENCE
OF OWNER. PROVIDE TRAINING SESSION FOR OWNER’S PERSONNEL FOR OPERATION OF
EQUIPMENT.
NEW WORK:
PROVIDE FEEDERS AND BRANCH CIRCUITS WITH SOLID CONDUCTORS FOR NO. 10 AWG
AND SMALLER AND STRANDED CONDUCTORS FOR NO. 8 AWG AND LARGER.
PROVIDE SEPARATE UNSHARED NEUTRAL CONDUCTOR(S) FOR ALL BRANCH CIRCUITS
UTILIZING A NEUTRAL AND ALL FEEDERS REQUIRING A NEUTRAL. SHARING OF NEUTRAL
CONDUCTORS BETWEEN ANY CIRCUIT (BRANCH OR FEEDER) IS NOT PERMITTED.
MULTIWIRE BRANCH CIRCUITS ARE NOT PERMITTED.
PROVIDE EVERY CONDUIT CONTAINING 120V OR GREATER WIRING WITH SEPARATE
INSULATED GROUND WIRE RATED FOR 600V, UNLESS NOTED OTHERWISE.
ALL SINGLE PHASE CIRCUITS ARE (2)#12, (1)#12G, 3/4”C AND ALL THREE PHASE CIRCUITS
ARE (3)#12, (1)#12G, 3/4"C UNLESS OTHERWISE NOTED.
FOR EACH PANELBOARD OR MODIFIED PANELBOARD, PROVIDE A TYPED DIRECTORY.
INDICATE SOURCE OF POWER FOR PANEL, ROOM AND ROOM NUMBER, EQUIPMENT
SERVED, SPARE, OR PROVISIONAL SPACE, AS APPLICABLE. MOUNT DIRECTORY INSIDE
PANELBOARD DOOR.
PROVIDE ALL LUGS AND TERMINATIONS RATED FOR 75 DEGREES C.
REVISIONS
SEAL:
4/16/2026
UE
UE
<E> UTILITY POLE
25344202
METER BASE
PANEL L1A
E601
PROPOSED
UTILITY POLE
E601
25' - 0"
CONTACT:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SEAL:
PROJECT:
PROJECT NUMBER:
DATE:
DRAWING TITLE:
DRAWING NUMBER:
COPYRIGHT © 2024
4/
/2
9:
:0
AM
H:
\R
EV
IT
\A J2
6_ M
EP
_C
EN
TR
AL
_R
_f al ve yH
CU
.rv t
L.E.L.
L.E.L.
C.G.M.
426005.00
E101
SITE PLAN -
ELECTRICAL
04/15/2026
C.G.M.
ROUTE 116
TRAILHEAD
HANOVER TROLLEY
TRAIL
SCALE: 1/16" = 1'-0"
SITE PLAN - ELECTRICAL1
N
REVISIONS
L1A
100A, MCB
240Y/120V, 1Ø, 3W
10 KAIC
(3)#1 AL
(1)#6 ALG
3"C.
(3)#1 AL
(1)#6 ALG
3"C.
UE
UE
GR
GR
KEYPAD
PHOTO
EYE/ENTRAPMENT
SENSOR
REFLECTOR
18/4
STRANDED
OPERATOR
SHADOW/SAFETY LOOP
GATE SWING ARC
SWING
GATE(TYPICAL)
OPERATOR
18/4
TWISTED/SHIELDED18/4
STRANDED
UE
CONCRETE PEDESTAL
FREE
EXIT/SAFETY
SENSOR
20'
- 0
2' - 2 1
/32
6' - 0"PANEL/METER BASE
1' - 9 3
1/3 2"
30' - 0"
UE
POST
UE
L1A-2
L1A-1
(2) 1" CONDUIT
UE
METER BASE
TO UTILITY
MIN. 3" (TYPICAL)
MIN. 3" (TYPICAL)
3'- 0"
MIN. 3"
(TYPICAL) 7.5" (TYPICAL)
1'- 0"
WARNING TAPE
FINISHED GRADE
3"C. PVC
SCH 40
(TYPICAL)
ACTIVE
SPARE
'-0
TH
RE
E
SI
DE
S
5'-0"
MIN.
#4/O BARE
COPPER
GROUND ROD. BURY SO THAT
TOP OF ROD IS 2'-0" B.F.G.
(TYPICAL)
EXOTHERMIC
CONNECTOR (TYPICAL)
1 1/2" RGS CONDUIT
BLDG
TO RESPECTIVE
GROUND BAR
FINISHED GRADE
GROUND CONDUCTOR
(SEE PLAN DWG FOR SIZE
AND TYPE)
"CLEAN" SAND
HIGH DENSITY GREEN
POLYETHYLENE
INSPECTION WELL
BUNDY HYTAIL TYPE
GKG434 CONNECTORS
OR EQUAL
3/4" X 10'-0" COPPERCLAD
PLATED STEEL GROUND ROD
4" 6"
METER
ELECTRICAL PANEL
60"
NOTES:
1. PROVIDE TRENCHING, WIRE, AND CONDUIT TO UTILITY POLE. REFER TO DUCT BANK DETAIL AND
SINGLE LINE DIAGRAM FOR ADDITIONAL INFORMATION. PROVIDE 30'-0" SCH 80 CONDUIT FOR
UTILITY POLE RISER AND REQUIRED CONDUCTOR LENGTH FOR TERMINATION TO UTILITY
EQUIPMENT BY UTILITY.
2. PROVIDE (2) 3" CONDUIT CAPPED AND CONCRETE ENCASED IN GROUND.
3. PROVIDE (3) 12 GAUGE CHANNELS, (2) SPRING NUTS PER CHANNEL, HEX NUT, AND LOCK WASHER
SECURELY MOUNTED TO SUPPORT POSTS.
3'-0" Min.
DETECTABLE
WARRING RIBBON
12" 24" Min.
of cover
RNC SCH 80
12" Min.
CONDUIT STRAP
SEE NOTE 2
SEE NOTE 3
ALL HARDWARE SHALL BE BONDED
AND GROUNDED PER NEC
CONCRETE ENCASED
POSTS (3' Min.) INTO
GROUND
COUNTERPOISE
1 REFER TO STRUCTURAL PLANS FOR FOUNDATIONS.
2 REFER TO SPECIFICATIONS FOR GATE CONSTRUCTION DETAILS.
3 PROVIDE ADJUSTABLE MOUNTING BRACKET TO MOUNT FREE EXIT / SAFETY SENSOR
AT 30 DEGREE ANGLE. ADJUST IN FIELD AS REQUIRED.
4 PROVIDE #6 BARE COPPER AND GROUND ROD FOR EACH PEDESTAL MOUNTED
OPERATOR.
5 INSTALL SHADOW LOOP / SAFETY LOOP AS PER MANUFACTURERS INSTRUCTIONS.
CONTACT:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SEAL:
PROJECT:
PROJECT NUMBER:
DATE:
DRAWING TITLE:
DRAWING NUMBER:
COPYRIGHT © 2024
4/
/2
9:
:0
AM
H:
\R
EV
IT
\A J2
6_ M
EP
_C
EN
TR
AL
_R
_f al ve yH
CU
.rv t
L.E.L.
L.E.L.
C.G.M.
426005.00
E601
SINGLE LINE
DIAGRAM AND
DETAILS
04/15/2026
C.G.M.
ROUTE 116
TRAILHEAD
HANOVER TROLLEY
TRAIL
SCALE: 1/4" = 1'-0"
ENLARGED GATE PLAN1
SCALE: 1/8" = 1'-0"
SINGLE LINE DIAGRAM2
SCALE: NONE
TYPICAL DUCTBANK DETAIL3
SCALE: NONE
TYPICAL GROUNDING COUNTERPOISE DETAIL4
SCALE: NONE
GROUND WELL DETAIL "B"5
SCALE: 1/8" = 1'-0"
PANEL/METER BASE DETAIL6
NOTES:
N
TOTAL DEMAND LOAD: 3000
TOTAL CONNECTED LOAD: 3000
3,000 VA 0 VA 0 VA
19 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 20
17 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 18
15 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 16
13 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 14
11 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 12
9 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 10
7 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 8
5 PREPARED SPACE -- 1 -- -- 1 -- PREPARED SPACE 6
3 SPARE 20 A 1 0 0 1 20 A SPARE 4
1 LIFT MASTER GATE 20 A 1 1,500 1,500 1 20 A LIFT MASTER GATE 2
CKT N DESCRIPTION AMP P A B C P AMP DESCRIPTION N CKT
100 A SQUARE D, QO
LOCATION: MAIN BREAKER: PANEL TYPE:
SURFACE 100 A 20
MOUNTING: BUS AMP: TOTAL POLES:
L1A 208Y/120V, 3Ø, 4 WIRE 10,000
PANEL DESIGNATION: VOLTAGE: MIN. AIC: NOTES:
REVISIONS