3-Attachment B Drawings Central PH4 3.13.26.pdf
PDF 22 MB Posted
- Solicitation number
- 2026-06
- Issued by
- Jackson County, Amity City, Oregon
About this file
This file contains architectural and engineering construction drawings for the Central Hall - Phase 4 Second Floor Tenant Improvements project at Southern Oregon University (SOU) located at 1250 Siskiyou Boulevard in Ashland, Oregon. The project encompasses approximately 12,828 square feet of interior renovation work on the second floor, including new wood frame partitions, casework, architectural finishes, mechanical systems (HVAC branch ducting and terminal units), plumbing fixtures and piping, electrical infrastructure including subpanels and lighting systems, and fire suppression system extensions. The scope of work also includes one bid alternate for a rooftop solar photovoltaic system. The drawing set is dated March 12, 2026, and classified as 100% Construction Documents suitable for construction bidding, recordation, conveyance, and permit issuance. The project involves comprehensive coordination across multiple trades including structural, mechanical, electrical, and plumbing systems, with detailed specifications for wall assemblies, interior finishes, door and window schedules, reflected ceiling plans, building sections, and system-specific plans for HVAC, plumbing, and electrical installations.
The construction documents include detailed specifications requiring all work to conform to the 2022 Oregon Structural Specialty Code, 2025 Oregon Energy Efficiency Specialty Code, 2022 Oregon Mechanical Specialty Code, 2023 Oregon Electrical Specialty Code, 2023 Oregon Plumbing Specialty Code, and applicable fire codes and standards including NFPA 13, NFPA 72, and NFPA 24. The project is funded by Southern Oregon University through its capital improvement program. General contractors are required to field-verify existing conditions, coordinate with all trades, maintain structural integrity during construction, provide necessary access and security for the site, and deliver comprehensive operation and maintenance documentation. The contractor bears responsibility for locating and protecting existing utilities, providing all required backing and blocking for fixtures and equipment, installing fire-rated and smoke-sealed access panels where required, and completing the work in compliance with all applicable building codes and manufacturer specifications without causing disruption to existing building operations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SYMBOLS LEGEND - GENERAL
A101
N
DETAIL NUMBER
DETAIL
SHEET NUMBER
A101
A101
SECTION NUMBER
WALL CROSS SECTION
SHEET NUMBER
SECTION NUMBER
BUILDING CROSS SECTION
SHEET NUMBER
A101
A101
ELEVATION NUMBER
EXTERIOR ELEVATION
SHEET NUMBER
ELEVATION NUMBER
INTERIOR ELEVATION
SHEET NUMBER
A
GRID LINE
TOP TO BOTTOM: LETTERS
LEFT TO RIGHT: NUMBERS
ROOM IDENTIFICATION
ROOM NUMBER
ROOM NAME
AREA
NORTH ARROW
ARROW INDICATES PLAN NORTH
NO: CORRESPONDS TO ROOM
LETTER: DOOR
IDENTIFICATION
DOOR IDENTIFICATION
A
KEYNOTE
A
WINDOW IDENTIFICATION
KEYNOTE NUMBER
WINDOW TYPE
R-1
RELITE IDENTIFICATION
RELITE TYPE
XXXXX
ASSEMBLY IDENTIFICATION
ASSEMBLY TYPE. SEE
ASSEMBLIES SHEET FOR
MORE INFORMATION.
L-1
O.F.C.I. ITEM
ITEM NUMBER
24D / L 0'-1"
CABINET DIMENSION
W.I.C. CABINET TYPE NUMBER
CABINET LENGTH
CABINET DEPTH
LEVEL NAME
100'-0"
LEVEL IDENTIFICATION
LEVEL NAME
LEVEL ELEVATION
CENTERLINE
LOUVER IDENTIFICATION
LOUVER NUMBER
SEE INDIVIDUAL SHEETS FOR ADDITIONAL LEGENDS AND SYMBOLS
RIDGE
VALLEY
SLOPE
STEP IN ELEVATION
100'-0"
SPOT ELEVATION
X" / 12" SURFACE SLOPE
1 DRAWING REVISION
REVISION NUMBER. SEE
REVISION SCHEDULE ON
TITLEBLOCK
MATERIALS LEGEND - GENERAL
EARTH BATT INSULATION
NOTE: ALL METERIAL SYMBOLS ABOVE MAY NOT NECESSARILY BE USED IN THIS PROJECT. SEE INDIVIDUAL
SHEETS FOR ADDITIONAL LEGENDS AND SYMBOLS.
GRAVEL / ROCK
SAND / GROUT
CONCRETE
CMU
EXISTING WALL
WALL TO BE DEMOLISHED
BRICK
NEW WALL
RIGID INSULATION
ALUMINUM
STEEL
DIMENSIONAL LUMBER
BLOCKING / SHIM
FINISH WOOD
PLYWOOD
ISSUE DATE:
PROJECT NO.:
SHEET:
REVISIONS
T hi s do cu m en t, a nd t he id ea s an d de si gn s in co rp or at ed h er ei n, a s an in st ru m en t of p ro fe ss io na l s er vi ce , i s th e pr op er ty o f K is tle r
S m al l +
W hi te A rc hi te ct s an d is n ot t o be u se d, in w ho le o r in p ar t, fo r an y ot he r pr oj ec t w ith ou t th e w rit te n au th or iz at io n of
K S
W A rc hi te ct s.
K
S W
A rc hi te ct s, L
LC
143 N 1ST STREET
ASHLAND, OR 97520
TEL.: 541.488.8200
THESE DRAWINGS MAY
BE USED FOR:
CONSTRUCTION
BIDDING
RECORDATION
CONVEYANCE
ISSUANCE OF A PERMIT
FOR CONSTRUCTION
/1
/2
:0 :2
A
M
G0.1
1.20.26
25-021
100% CD
S
IS
K
IY
O U
B O
U L
E V
A R
D A
S H
L A
N D
O R
E G
O N
S O
U
C E
N T
R A
L H
A L
L
P H
A S
E
GENERAL
INFORMATION
SOU - CENTRAL HALL - PHASE 4
S E
C O
N D
F L O
O R
T E
N A
N T
I M
P R
O V
E M
E N
T S
ABV ABOVE
AC ASHPHALTIC CONCRETE
ACT ACOUSTIC CEILING TILE
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
ASW AREA SEPARATION WALL
BD BOARD
BLDG BUILDING
B.O. BOTTOM OF
BM BEAM
BS BACKSPLASH
CAB CABINET
CFCI CONTRACTOR FURNISHIED
CONTRACTOR INSTALLED
CH COAT HOOK
CJ CONTROL JOINT
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONT CONTINUOUS
CORR CORRIDOR
CPT CARPET
CR CLASSROOM
CT CERAMIC TILE
CTB COMPUTER TERMINAL BOARD
CTSK COUNTERSINK
CURT CURTAIN/ DRAPERY
DBL DOUBLE
DIA DIAMETER
DIMS DIMENSIONS
DF DRINKING FOUNTAIN
DS DOWNSPOUT
DW DISHWASHER
DP DISABLED PERSON
(E) EXISTING
EA EACH
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EM ENTRANCE MATTING
EMT ELECTRICAL METALLIC TUBING
EPT EPOXY PAINT
EQ EQUAL
(E) EXISTING
EJ EXPANSION JOINT
EXT EXTERIOR
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER & CABINET
FF FINISHED FLOOR
FFE FINISHED FLOOR ELEVATION
FG FINISH GRADE
FHSMS FLAT HEAD SHEET METAL SCREWS
FHMB FLAT HEAD MACHINE BOLT
ABBREVIATIONS - GENERAL
FIN FINISH (ED)
FND FEMININE NAPKIN DISPENSER
F.O. FACE OF
F.O.C. FACE OF CONCRETE / FACE OF COLUMN
F.O.F. FACE OF FINISH
F.O.M. FACE OF MASONRY
F.O.S. FACE OF STUD / STRUCTURE
FP FIREPLACE
FR FIRE RESISTANT
FRP FIBERGLASS REINFORCED PANEL
FRMG FRAMING
FRZR FREEZER
FTG FOOTING
GA GUAGE
GA GYPSUM ASSOCIATION
GALV GALVANIZED
GB GYPSUM BOARD
GWB GYPSUM WALL BOARD
GI GALVANIZED IRON
GS GALVANIZED STEEL
HS HALL STATION (ELEVATOR)
H HIGH
HDBD HARDBOARD
HDR HEADER
HDWD HARDWOOD
HGT HEIGHT
HR HOUR
HVAC HEATING/VENTILATION/AIR CONDITIONING
HW HOT WATER
HC HANDICAP
INSUL INSULATION
IR INSIDE RADIUS
JST JOIST
KS KNEE SPACE
LAV LAVATORY
LPG LIQUID PROPANE GAS
M MIRROR
MAX MAXIMUM
MB MARKER BOARD
MDL MODEL
MECH MECHANICAL
MED MEDIUM
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MPH MILES PER HOUR
MTL METAL
MW MICROWAVE
(N) NEW
NIC NOT IN CONTRACT
O/ OVER
OCC OCCUPANCY
OPNG OPENING
OC ON CENTER
OD OUTSIDE DIAMETER
NOTE: ABBREVIATIONS BELOW MAY NOT INCLUDE ALL FOUND IN THE DRAWINGS
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED OWNER INSTALLED
P PAINT
PLAM PLASTIC LAMINATE
PLWD PLYWOOD
PSF POUNDS PER SQ. FOOT
PWC PLASTIC WALL COVERING
PWP PLASTIC WALL PANEL
PT PRESSURE TREATED
RD ROOF DRAIN
REF REFRIGERATOR
RM ROOM
RO ROUGH OPENING
SD SOAP DISPENSER
SEP SEPARATION
SF SQUARE FEET
SQ FT SQUARE FEET
SHTG SHEATHING
SHT SHEET
SIM SIMILAR
SM SHEET METAL
SMS SHEET METAL SCREWS
SPECS SPECIFICATIONS
STB SINGAL TERMINAL BACKBOARD
STL STEEL
STR STRUCTURAL
SS SOLID SURFACE
SST STAINLESS STEEL
TPD TOILET PAPER DISPENSER
TRSFR TRANSFORMER/TRANSFER
TS TUBE STEEL
TTB TELEPHONE TERMINAL BACKBOARD
TVB DATA TERMINAL BACKBOARD
TYP TYPICAL
TH THRESHOLD
TO TOP OF
TC TOP OF CONCRETE / CURB
TW TOP OF WALL
UL UNDERWRITER'S LABORATORY
UTIL UTILITY
UNO UNLESS NOTED OTHERWISE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VWC VINYL WALL COVERING
WBG WALL BUMPER GUARD
WC WATER CLOSET
WD WOOD
WDW WINDOW
WH WATER HEATER
WTP WATER TREATMENT PLANT
WF WIDE FLANGE
WS WOOD SCREW
W.I.C. WOODWORK INSTITUTE
W/ WITH
NOTES - GENERAL
1. CONTRACTOR TO FIELD VERIFY ALL CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING WITH ANY WORK.
2. DIMENSIONS TAKE PRECEDENCE OVER DRAWING. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT OF ANY DISCPREPANCIES PRIOR TO PROCEEDING WITH
WORK. DIMENSIONS ARE TAKEN TO FOC, FOF, FOM, FOS, OR GRID, UNO.
3. CONTRACTOR IS SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS AND METHODS AND SHALL MAINTAIN THE STRUCTURAL INTEGRITY OF ANY CONSTRUCTION UNITS UNTIL ALL FINAL LATERAL AND VERTICAL CARRYING SYSTEMS ARE COMPLETED.
4. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION AND COORDINATION OF SUBCONTRACTORS WORK, COMPLIANCE WITH CONTRACT DOCUMENTS, ACCURATE LOCATION OF STRUCTURAL MEMBERS, AND OPENINGS FOR MECHANICAL, ELECTRICAL, AND MISCELLANEOUS EQUIPMENT. CONTRACTORS TO VERIFY ALL DIMENSIONS AND OPENING SIZES (CLEARANCES REQUIRED FROM MFR PRIOR TO CONSTRUCTION AND INSTALLATION OF EQUIPMENT, FURNISHINGS, ACCESSORIES ETC).
5. DETAILS NOTED AS "TYPICAL" OR "TYP" APPLY IN ALL CASES WHETHER OR NOT SPECIFICALLY REFERENCED. DETAILS THAT ARE SPECIFICALLY REFERENCED SHALL TAKE PRECEDENCE OVER "TYPICAL" OR "TYP." DETAILS. SPECIFIC DETAILS AND NOTES SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND DETAILS.
6. CONTRACTOR IS RESPONSIBLE FOR THE COMPLETE SECURITY OF THE SITE WHILE THE JOB IS IN PROGRESS AND UNTIL JOB COMPLETION.
7. CONTRACTOR IS RESPONISBLE FOR LOCATING ALL EXISTING UTILITIES WHETHER SHOWN HEREON OR NOT AND TO PROTECT THEM FROM DAMAGE. THE CONTRACTOR SHALL BEAR ALL EXPENSES OF REPAIR OR REPLACEMENT OF UTILITIES OR OTHER PROPERTY DAMAGED BY OPERATIONS IN CONJUNCTION
WITH THE EXECUTION OF THE WORK.
8. SEPARATE ALL METALS FROM DIS-SIMILAR METALS WITH BITUMINOUS TAPE.
9. DOORS NOT LOCATED BY DIMENSION SHALL BE CENTERED IN WALL OR SHALL BE LOCATED FOUR INCHES FROM FINISH WALL TO HINGE SIDE OF DOOR.
10. SCREWS ATTACHING GYPSUM BOARD TO RESILIENT CHANNELS SHALL NOT MAKE CONTACT AT THE METAL STUDS BEYOND.
11. CONTRACTOR TO PROVIDE BACKING OR BLOCKING AS REQUIRED FOR MOUNTING ALL GRAB BARS, SHELVES, EQUIPMENT, HAND RAILS, ACCESSORIES, CABINETS ETC. INCLUDING ITEMS INDICATED AS NIC.
12. CONTRACTOR TO PROVIDE ALL ACCESS PANELS AS REQUIRED. LOCATION, FINISH, AND TYPE SHALL BE APPROVED BY ARCHITECT PRIOR TO OBTAINING AND INSTALLING. ACCESS PANEL LOCATIONS NOT APPROVED BY ARCHITECT SHALL BE SUBJECT TO MODIFICATION AT NO ADDITIONAL COST. PROVIDE RATED PANELS (MATCHING ASSEMBLY RATING) WHERE REQUIRED TO PENETRATE A RATED ASSEMBLY. ACCESS PANELS IN SHAFT WALLS, RATED FLOOR/CEILINGS
OR RATED ROOF/CEILINGS SHALL BE SMOKE SEALED.
13. AUTOMATIC FIRE SPRINKLER PLANS SHALL BE SUBMITTEED TO THE FIRE MARSHALL FOR REVIEW AND APPROVAL. DESIGN AND INSTALLATION SHALL CONFORM TO NFPA 13, NFPA 13R, NFPA 24 AND NFPA 71 STANDARDS. INSTALLATION OF THE SPRINKLER SYSTEM SHALL NOT BE STARTED UNTIL COMPLETE PLANS AND SPECIFICATIONS (INCLUDING WATER SUPPLY INFORMATION) HAVE BEEN APPROVED BY THE FIRE MARSHAL HAVING JURISDICTION. THE SYSTEM
MUST BE TESTED IN THE PRESENCE OF THE ENFORCING AUTHORITY.
14. SMOKE/FIRE DAMPERS SHALL BE FIRE MARSHAL APPROVED AND INSTALLED STRICTLY IN ACCORDANCE WITH THE MFR'S INSTRUCTIONS. MFR'S INSTRUCTIONS SHALL BE MADE AVAILABLE TO THE INSPECTING AUTHORITY. DETAILS SHOWN ARE FOR REFERENCE ONLY. FIRE DAMPER ACCESS DOORS SHALL BE PROVIDED WHERE AIR DUCTS PENETRATE FIRE RATED WALLS OR CEILINGS AS PER OSSC CHAPTER 7.
GENERAL
G0.1 GENERAL INFORMATION
G0.2 ADA COMPLIANCE
G0.3 ADA COMPLIANCE
G0.5 CODE SUMMARY
G0.6 CODE SUMMARY
ARCHITECTURAL
A0.1 SITE PLAN
A1.1 ASSEMBLIES - INTERIOR
A2.1 SECOND FLOOR DEMOLITION PLAN
A3.1 SECOND FLOOR PLAN - DIMENSIONS
A3.1.2 SECOND FLOOR PLAN - NOTES
A3.1.3 SECOND FLOOR PLAN - FURNITURE &
EQUIPMENT
A3.1.4 SECOND FLOOR PLAN - FINISH
A3.1.5 ENLARGED RESTROOM PLAN
A3.3 ATTIC FLOOR PLAN
A3.4 ROOF PLAN
A5.1 SECOND FLOOR REFLECTED CEILING PLAN
A7.1 BUILDING SECTIONS
A7.2 BUILDING SECTIONS
A7.3 BUILDING SECTIONS
A9.1 EXTERIOR DETAILS
A10.0 INTERIOR ELEVATION TAG PLAN
A10.1 INTERIOR ELEVATIONS
A10.2 INTERIOR ELEVATIONS
A10.3 INTERIOR ELEVATIONS
A10.4 INTERIOR ELEVATIONS
A10.5 INTERIOR ELEVATIONS
A10.6 INTERIOR ELEVATIONS
A10.7 INTERIOR ELEVATIONS
A11.1 ROOM FINISH AND DOOR SCHEDULES
A11.3 WINDOW & CURTAIN WALL TYPES
A12.1 CABINET DETAILS
A12.2 INTERIOR DETAILS
A12.3 INTERIOR DETAILS
A12.4 INTERIOR DETAILS
A12.5 INTERIOR DETAILS
OWNER
SOUTHERN OREGON UNIVERSITY
CONTACT: JIM MCNAMARA
351 WALKER AVE.
ASHLAND, OR 97520
(541) 821-1294 (P) mcnamaraj@sou.edu
ARCHITECT CIVIL ENGINEER LANDSCAPE ARCHITECT STRUCTURAL ENGINEER MECHANICAL ENGINEER ELECTRICAL ENGINEER PLUMBING ENGINEER
KSW ARCHITECTS
CONTACT: RAY KISTLER
66 WATER STREET, STE 101
ASHLAND, OR 97520
(541) 488-8200 (P) raymondk@kswarchitects.com
ARCSINE ENGINEERING
CONTACT: JOHN KELLER
1236 DISK DRIVE
MEDFORD, OR. 97501
(541) 842-4188 (P)
JKELLER@ARC-SINE.COM
ARCSINE ENGINEERING
CONTACT: ED PHILLIPS
950 EXECUTIVE WAY
REDDING, CA. 96002
(530) 222-7204 (P)
EPHILLIPS@ARC-SINE.COM
ARCSINE ENGINEERING
CONTACT: CHRIS HEIDL
1236 DISK DRIVE
MEDFORD, OR. 97501
(541) 842-4188 (P)
CHEIDL@ARC-SINE.COM
N
VICINITY MAP
SISKIYOU BLVD
S
M O
U N
T A
IN
A
V E
MECHANICAL
M0.0 MECHANICAL LEGEND AND NOTES
M0.1 MECHANICAL SCHEDULES
M3.1 SECOND FLOOR MECHANICAL PLAN
M3.2 ATTIC MECHANICAL PLAN - EAST
M3.3 ATTIC MECHANICAL PLAN - WEST
M4.1 ATTIC MECHANICAL PIPING PLAN
PLUMBING
P0.0 LEGEND AND GENERAL NOTES
P0.1 SCHEDULES
P1.0 SECOND FLOOR PLUMBING PLAN
ELECTRICAL
E0.0 LEGEND AND GENERAL NOTES
E2.0 ONE-LINE DIAGRAM AND LOAD SUMMARY
E2.1 PANELBOARD SCHEDULES
E3.0 SITE POWER PLAN
E4.0 BASEMENT POWER PLAN
E4.1 SECOND FLOOR POWER PLAN
E5.0 SECOND FLOOR LIGHTING PLAN
E6.0 SECOND FLOOR SPECIAL SYSTEMS PLAN
E7.0 DETAILS
E7.1 DETAILS
E7.2 DETAILS
E7.3 DETAILS
BID ALTERNATES
DRAWING INDEX
SECOND FLOOR TENANT IMPROVEMENTS
N/A N/A N/A
#1 ADD GRID-TIED ROOFTOP SOLAR PHOTOVOLTAIC SYSTEM 1
FLOOR SURFACES (302) & CHANGES IN LEVEL (303)
NOTE: THESE DIAGRAMS ARE BASED ON THE INFORMATION CONTAINED IN THE ICC/ANSI
A117.1-2009 MANUAL AND CHAPTER 11 OF THE OSSC 2014. THEY ARE REPRESENTATIVE OF THE
GENERAL REQUIREMENTS THAT APPLY TO THIS PROJECT. THEY ARE NOT REPRODUCTIONS OF
ALL OF THE INFORMATION CONTAINED IN THE ANSI MANUAL. REFER TO THE ANSI MANUAL FOR
COMPLETE INFORMATION AND REQUIREMENTS.
PROTRUDING OBJECTS (307)
/2
M
A X
FIG. 302.2
CARPET ON FLOOR SURFACES
FIG. 303.2
VERTICAL CHANGE IN LEVEL
/4
M
A X
FIG. 303.3
BEVELED CHANGES IN LEVEL
(B)
/4
/2
(A)
/4
M
A X
1 1
/2
M A
X
TURNING SPACE (304)
FIG. 304.3
SIZE OF TURNING SPACE
67 IN MIN
(A) CIRCULAR
60" MIN
M
IN
M
IN
12" MIN
36" MIN
12' MIN
M
IN
(B) T-SHAPED
CLEAR FLOOR SPACE (305)
(A) FORWARD
30" MIN
M
IN
(B) PARRALLEL
M
IN
48" MIN
FIG. 305.5
POSITION OF CLEAR FLOOR SPACE
(A) FORWARD APPROACH
36" MIN
X
(B) PARRALLEL APPROACH
X
60" MIN
FIG. 305.7
MANEUVERING CLEARANCE IN AN ALCOVE
KNEE AND TOE CLEARANCE (306)
(A) ELEVATION (B) PLAN
6" MAX
M
IN
17" - 25"
M
IN
FIG. 306.2
TOE CLEARANCE
(A) ELEVATION (B) PLAN
M
IN
25" MAX
M
IN
FIG. 306.3
KNEE CLEARANCE
8" MIN
M
IN
11" MIN
X
4" MAX
X
FIG. 307.2
LIMITS OF PROTRUDING OBJECTS
FIG. 307.4
REDUCED VERTICAL CLEARANCE
M A
X
X
REACH RANGES (308)
M
IN
M A
X
FIG. 308.2.1
UNOBSTRUCTED FORWARD REACH
M A
X
FIG. 308.2.2
OBSTRUCTED HIGH FORWARD REACH
(A)
M A
X
20" MAX
M A
X
(B)
M A
X
20" - 25"
FIG. 308.3.1
UNOBSTRUCTED SIDE REACH
FIG. 308.3.2
OBSTRUCTED HIGH SIDE REACH
M
IN
M A
X
10" MAX
10" MAX
(A)
M A
X
M A
X
10" - 24"
(B)
M A
X
M A
X
CLEAR WIDTH (403.5)
FIG. 403.5
CLEAR WIDTH OF AN ACCESSIBLE ROUTE
M
IN
M
IN
24" MAX 48" MAX 24" MAX
M A
X
M A
X
FIG. 403.5.1
CLEAR WIDTH AT 180 DEGREE TURN
M
IN
42" MIN 42" MIN
X < 48"
M
IN
36" MIN 36" MIN
X < 48"
(A)
180 DEGREE TURN
(A)
180 DEGREE TURN
(EXCEPTION)
32" MIN
32" MIN 32" MIN 36" MIN
FIG. 404.2.2
CLEAR WIDTH OF DOORWAYS
(A)
HINGED DOOR
(B)
SLIDING DOOR
(C)
FOLDING DOOR
(D)
DOORWAY W/O DOOR
FIG. 404.2.3.3
MANEUVERING CLEARANCE AT SLIDING AND FOLDING DOORS
(A)
FRONT APPROACH
(B)
POCKET OR HINGE APPROACH
(C)
STOP OR LATCH APPROACH
M
IN
M
IN
22" MIN 4
M
IN
24" MIN
STAIRWAYS (504) AND HANDRAILS (505)
DOORS AND DOORWAYS (404)
FIG. 404.2.3.2
MANEUVERING CLEARANCE AT MANUAL SWINGING DOORS
18" MIN
M
IN
(A) FRONT APPROACH, PULL SIDE
M
IN
* IF BOTH CLOSER AND LATCH ARE PROVIDED
(B) FRONT APPROACH, PUSH SIDE
12" MIN*
36" MIN 6
M
IN
(C) HINGE APPROACH, PULL SIDE
42" MIN
M
IN
(D) HINGE APPROACH, PULL SIDE
22" MIN
M
IN
* IF BOTH CLOSER AND LATCH PROVIDED
** 48 MIN IF BOTH CLOSER AND LATCH
PROVIDED
(E) HINGE APPROACH, PUSH SIDE
24" MIN
M
IN
*54 MIN IF CLOSER PROVIDED
(F) LATCH APPROACH, PULL SIDE
12" MIN*
M
IN
* 48 MIN IF CLOSER PROVIDED
(G) LATCH APPROACH, PUSH SIDE
24" MIN
RADIUS
1/2" MAX
(A) VERTICAL RISER (B) CURVED NOSING
1 1/2" MAX
(C) BEVELED NOSING
1 1/2" MAX
(C) BEVELED NOSING
30° MAX
FIG. 504.5
STAIR NOSINGS
FIG. 505.4
HANDRAIL HEIGHT
(A) STAIRS (B) RAMPS FIG. 505.10.2
TOP HANDRAIL
EXTENSION
AT STAIRS
12" MIN
12" MIN
FIG. 505.10.1
TOP AND BOTTOM HANDRAIL EXTENSION AT RAMPS
FIG. 505.7
HANDRAIL CROSS-SECTION
1 1/4" - 2" 1 1/2" MIN 1 1/2" MIN
4" - 6 1/4"
PERIMETER
2 1/4" MAX 1 1/2" MIN
-7
11" MIN
FIG. 505.10.3
BOTTOM HANDRAIL
EXTENSION
AT STAIRS
X X
X = TREAD
DEPTH
DRINKING FOUNTAINS (602)
5" MAX 15" MIN
(A) PLAN
M A
X
W H
E E
L C
H A
IR
A
C C
E S
S
IB
L E
S T
A N
D
IN
G
P E
R S
O N
S
5" MAX
15" MIN
(B) ELEVATION
FIG 602.5
DRINKING FOUNTAIN SPOUT LOCATION
PAPER
TOWER
DISPENSER
SANITARY
NAPKIN
DISPENSER
FIRE ALARM
PULL
STATION
M A
X H
E
IG
H T
O A
E R
A B
A R
T S
SEAT
COVER
DISPENSER
TOWEL
BAR
ROBE
HOOK
HAND
TOWEL
BAR
SOCKET/
SWITCH
HORN/
STROBE
STROBES ROOM
SIGNAGE
M
IN
M A
X
THERMOSTAT/
SECURITY/
FIRE ALARM
3" MAX
PROJECTIO
N
M
A X
CEILING
WALL MOUNTED DEVICES AND APPLIANCES
SOCKET
ABOVE
COUNTER
M A
X
FEC
T O
H A
N D
L E
M A
X
(4
M
IN
B
T
T O
M L
IN
F T
B
R A
IL
L E
C E
L L
C
N
T R
O L S
M A
X
P
S O
C K
E T
T O
B O
T T
M
S
C
K E
T
SOCKET/
SWITCH
SOCKETT
O
T O
P S
O C
K E
T
T O
P U
L L
M A
X
M
IM
CLEAR WIDTH (403.5)
DOORS AND DOORWAYS (404)
M
IN
(A) FRONT APPROACH (B) SIDE APPROACH
M
IN
FIG. 404.2.3.4
MANUEVERING CLEARANCE AT DOORWAYS WITHOUT DOORS
18" MIN
M
IN
FIG. 404.2.3.5
MANUEVERING CLEARANCE AT RECESSED DOORS
(A) PULL SIDE
X
M
IN
X
(B) PUSH SIDE
M
IN12" MIN
X
(C) PUSH SIDE, DOOR
PROVIDED W/ CLOSER AND
LATCH
ISSUE DATE:
PROJECT NO.:
SHEET:
REVISIONS
T hi s do cu m en t, a nd t he id ea s an d de si gn s in co rp or at ed h er ei n, a s an in st ru m en t of p ro fe ss io na l s er vi ce , i s th e pr op er ty o f K is tle r
S m al l +
W hi te A rc hi te ct s an d is n ot t o be u se d, in w ho le o r in p ar t, fo r an y ot he r pr oj ec t w ith ou t th e w rit te n au th or iz at io n of
K S
W A rc hi te ct s.
K
S W
A rc hi te ct s, TEL.: 541.488.8200
THESE DRAWINGS MAY
BE USED FOR:
CONSTRUCTION
BIDDING
RECORDATION
CONVEYANCE
ISSUANCE OF A PERMIT
FOR CONSTRUCTION
/1
/2
:0 :2
A
M
G0.2
1.20.26
25-021
100% CD
S
IS
K
IY
O U
B O
U L
E V
A R
D A
S H
L A
N D
O R
E G
O N
S O
U
C E
N T
R A
L H
A L
L
P H
A S
E
ADA
COMPLIANCE
S E
C O
N D
F L O
O R
T E
N A
N T
I M
P R
O V
E M
E N
NOTE: THESE DIAGRAMS ARE BASED ON THE INFORMATION CONTAINED IN THE ICC/ANSI
A117.1-2009 MANUAL AND CHAPTER 11 OF THE OSSC 2014. THEY ARE REPRESENTATIVE OF THE
GENERAL REQUIREMENTS THAT APPLY TO THIS PROJECT. THEY ARE NOT REPRODUCTIONS OF
ALL OF THE INFORMATION CONTAINED IN THE ANSI MANUAL. REFER TO THE ANSI MANUAL FOR
COMPLETE INFORMATION AND REQUIREMENTS.
16" - 18" 17" - 19"
(A)
ACCESSIBLE
WATER CLOSETS
(B)
AMBULATORY
WATER CLOSETS
FIG 604.2
WATER CLOSET LOCATION
60" MIN
M
IN
FIG 604.3
SIZE OF CLEARANCE FOR WATER CLOSET
FIG 604.4
WATER CLOSET SEAT HEIGHT
SEAT HEIGHT
FIG 604.5.1
SIDE WALL GRAB BAR FOR WATER CLOSET
12" MAX
42" MIN
M
IN
54" MIN
39" - 41"
FIG 604.5.2
REAR WALL GRAB BAR FOR WATER
CLOSET
24" MIN 12" MIN
36" MIN
FIG 604.9.2
WHEELCHAIR ACCESSIBLE
TOILET COMPARTMENTS
60" MIN
W A
L L
-H U
N G
M
IN
F L O
O R
-M O
U N
T E
D
M
IN
FIG 604.9.3.1
WHEELCHAIR ACCESSIBLE COMPARTMENT DOOR OPENINGS
4" MAX
56" MIN
OR
M
IN
(A) FRONT
APPROACH
(B) SIDE WALL OR
PARTITION
M A
X
W A
L L
H U
N G
M
IN
F L O
O R
M O
U N
T E
D
M
IN
M A
X
FIG. 606.3
HEIGHT OF LAVATORIES AND SINKS
M A
X
T O
B .O
M
IR
R
O R
M A
X
MIRROR
FIG. 605.2
HEIGHT OF URINALS
(A)
WALL HUNG TYPE
M A
X
(B)
STALL TYPE
FIG 604.9.3.1 (C)
WHEELCHAIR ACCESSIBLE COMPARTMENT DOOR OPENINGS - ALTERNATE
M
IN
56" MIN
59" MIN
(WALL MOUNTED W.C.) - ADULT
(FLOOR MOUNTED W.C.) - ADULT
WALL & FLOOR MOUNTED W.C. - CHILDREN
DOOR SHALL NOT SWING
INTO THE REQUIRED
MINIMUM AREA OF THE
COMPARTMENT
A
D U
L T
C H
IL
D
R E
N
FIG 604.9.5
WHEELCHAIR ACCESSIBLE COMPARTMENT TOE CLEARANCE
PARTITION
6"
M
IN
(A) ELEVATION
ADULT
PARTITION
6"
M
IN
(B) ELEVATION
CHILDREN
6"
(C)
PLAN
M
IN
FIG 604.10
AMBULATORY ACCESSIBLE COMPARTMENT
17"-19"
M
IN
36" 12" - 18"
FIG. 604.11.2
CHILDREN'S WATER CLOSET LOCATION
FIG 604.11.4
CHILDREN'S WATER CLOSET HEIGHT
NOTE: FOR ADULT DIMENSIONS SEE FIG. 604.4
FIG 604.11.7
CHILDREN'S DISPENSER OUTLET LOCATION
/2
M
IN
24" MIN
42" MAX
NOTE: FOR ADULT DIMENSIONS SEE FIG. 604.7
FIG. 607.2
CLEARANCE FOR BATHTUBS
LENGTH OF TUB
M
IN
H E
D
N
W
L L
BACK WALL
C O
N T
R
D W
A L L
(A) WITHOUT PERMANENT SEAT
LENGTH OF TUB
M
IN
H E
L L
BACK WALL
C O
N T
R
D W
A L L
(B) WITH PERMANENT SEAT
12" MIN
FIG. 607.4.1
GRAB BARS FOR BATHTUBS W/
PERMANENT SEATS
FIG. 607.4.2
GRAB BARS FOR BATHTUBS W/O
PERMANENT SEATS
H E
L L
C O
N T
R
D W
A L L
(B) PLAN
M
IN
M A
X
12" MAX 24" MIN 24" MAX
M
IN
H E
L L
C O
N T
R
D W
A L L
(B) PLAN
12" MAX 15" MAX
M A
X
M
IN
-3
-6
M
IN
(A) ELEVATION(A) ELEVATION
-3
-6
M
IN
WATER CLOSETS AND TOILET COMPARTMENTS (604), URINALS (605), AND LAVATORIES (606)
FIG. 607.5
LOCATION OF BATHTUB CONTROLS
BATHTUBS (607)
SHOWER COMPARMENTS (608)
FIG 608.2.1
TRANSFER-TYPE SHOWER
COMPARTMENT SIZE AND CLEARANCE
48" MIN
M
IN
36"
BACK WALL
C O
N T
R
L L
S E
L L
FIG 608.2.2
STANDARD ROLL-IN-TYPE SHOWER
COMPARTMENT SIZE AND CLEARANCE
BACK WALL
S
ID
L L
S
L L
60" MIN
M
IN
M
IN
FIG 608.3.1
GRAB BARS IN TRANSFER-TYPE SHOWERS
18"
BACK WALL
C O
N T
R
L L
S E
L L
M A
X
FIG 608.2.3
ALTERNATE ROLL-IN-TYPE SHOWER
COMPARTMENT SIZE AND CLEARANCE
S
L L
E
L L
60" MIN
SEAT
WALL
24"-36" 36" MIN
FIG 608.3.2
GRAB BARS IN STANDARD
ROLL-IN-TYPE SHOWER
M
IN
WITH SEAT
M A
X
6" MAX
FIG 608.3.3
GRAB BARS IN ALTERNATE
ROLL-IN-TYPE SHOWER
SEAT WALL
M A
X
6" MAX 6" MAX
FIG 608.4.1
TRANSFER-TYPE SHOWER
CONTROLS & HANDSHOWER LOCATION
15" MAX
M A
X
M
IN
CONTROL
WALL
FIG. 608.4.2
STANDARD ROLL-IN-TYPE
SHOWER CONTROL AND
HANDSHOWER LOCATION
BACK
WALL 4
M A
X
G R
A B
B A
R
A B
O V
E
16" MIN
27" MAX
FIG. 608.4.3
ALTERNATE ROLL-IN-TYPE SHOWER CONTROL AND HANDSHOWER LOCATION
(A)
END WALL
(ELEVATION)
M A
X
M
IN
END
WALL
MAX
27"
(B)
BACK WALL
(ELEVATION)
M A
X
M
IN
BACK
WALL
15" MAX15" MAX
SEAT WALL
END
WALL
SIDE
WALL
BACK WALL
(C)
WITH SEAT
(PLAN)
SEATS (610)
FIG. 609.2
SIZE OF GRAB BARS
(A)
CIRCULAR
1 1/4" - 2" 1 1/2".
(B) (C)
NONCIRCULAR
2" MAX4" - 4.8" PERIMETER
FIG. 609.3
SPACING OF GRAB BARS
/2
M
IN
M
IN
1 1/2".
GRAB BARS (609)
NOTE: FOR ADULT DIMENSIONS SEE FIG.604.5.1
(A) SIDE WALL VIEW
12" MAX
42" MIN
M
IN
54" MIN
34" - 36"
NOTE: FOR ADULT DIMENSIONS SEE 604.5.2
(B) REAR WALL VIEW
24" MIN 12" MIN
36" MIN
FIG 609.4.2
POSITION OF CHILDREN'S GRAB BARS
604.5.1
604.5.2
(B) PERMANENT SEAT(A) REMOVABLE IN-TUB SEAT
15" -16" 15" MIN
H E
L L
FIG. 610.2
BATHTUB SEATS
FIG. 610.3.1
RECTANGULAR SHOWER
COMPARTMENT SEAT
FIG. 610.3.2
L-SHAPED SHOWER
COMPARTMENT SEAT
2 1/2" MAX 3
M A
X
/2
M
A X
15" - 16"
2 1/2" MAX 3
M A
X
/2
M A
X
15" - 16"
22" - 23"
M A
X
(a) Top Loading (b) Front Loading
FIG. 611.4
HEIGHT OF LAUNDRY EQUIPMENT
WASHING MACHINES AND CLOTHES DRYERS (611)
Offset 24 inches maximum from center of door opening
24"
FIG. 611.2
CLEAR FLOOR SPACE
ISSUE DATE:
PROJECT NO.:
SHEET:
REVISIONS
T hi s do cu m en t, a nd t he id ea s an d de si gn s in co rp or at ed h er ei n, a s an in st ru m en t of p ro fe ss io na l s er vi ce , i s th e pr op er ty o f K is tle r
S m al l +
W hi te A rc hi te ct s an d is n ot t o be u se d, in w ho le o r in p ar t, fo r an y ot he r pr oj ec t w ith ou t th e w rit te n au th or iz at io n of
K S
W A rc hi te ct s.
K
S W
A rc hi te ct s, TEL.: 541.488.8200
THESE DRAWINGS MAY
BE USED FOR:
CONSTRUCTION
BIDDING
RECORDATION
CONVEYANCE
ISSUANCE OF A PERMIT
FOR CONSTRUCTION
/1
/2
:0 :2
A
M
G0.3
1.20.26
25-021
100% CD
S
IS
K
IY
O U
B O
U L
E V
A R
D A
S H
L A
N D
O R
E G
O N
S O
U
C E
N T
R A
L H
A L
L
P H
A S
E
ADA
COMPLIANCE
S E
C O
N D
F L O
O R
T E
N A
N T
I M
P R
O V
E M
E N
ISSUE DATE:
PROJECT NO.:
SHEET:
REVISIONS
T hi s do cu m en t, a nd t he id ea s an d de si gn s in co rp or at ed h er ei n, a s an in st ru m en t of p ro fe ss io na l s er vi ce , i s th e pr op er ty o f K is tle r
S m al l +
W hi te A rc hi te ct s an d is n ot t o be u se d, in w ho le o r in p ar t, fo r an y ot he r pr oj ec t w ith ou t th e w rit te n au th or iz at io n of
K S
W A rc hi te ct s.
K
S W
A rc hi te ct s, TEL.: 541.488.8200
THESE DRAWINGS MAY
BE USED FOR:
CONSTRUCTION
BIDDING
RECORDATION
CONVEYANCE
ISSUANCE OF A PERMIT
FOR CONSTRUCTION
/1
/2
:0 :2
A
M
G0.5
1.20.26
25-021
100% CD
S
IS
K
IY
O U
B O
U L
E V
A R
D A
S H
L A
N D
O R
E G
O N
S O
U
C E
N T
R A
L H
A L
L
P H
A S
E
CODE
SUMMARY
S E
C O
N D
F L O
O R
T E
N A
N T
I M
P R
O V
E M
E N
T S
BUILDING OCCUPANCY
APPLICABLE OCCUPANCY CLASSIFICATION GROUPS: B
OCCUPANCY SEPARATION (TABLE 508.4):
NO SEPARATION REQUIRED
CHAPTER 3
FIRE PROTECTION
FIRE EXTINGUISHERS: 75'-0" MAX TRAVEL DISTANCE TO EXTINGUISHER (PER OFC TABLE
906.3 - CLASS A HAZARD)
CHAPTER 9
AUTOMATIC SPINKLER SYSTEM
STANDPIPE SYSTEM
FIRE ALARM SYSTEM
SMOKE DETECTION SYSTEM
REQUIRED PROPOSED TYPE/CLASS
NO PER 903.2 YES NFPA 13
NO PER 905.3 NO CLASS I
YES PER 907.2.2 EXISTING NFPA 72
NO PER 907.2.2 NO NFPA 72
*PER IFC 90702.9 - FIRE ALARM SYSTEM IS REQUIRED TO MONITOR THE FIRE SPRINKLER
SYSTEM. NOTIFICATION DEVICES ARE TO ACTIVATE UPON FIRE SPRINKLER WATER
FLOW. ONE MANUAL FIRE ALARM BOX IS REQUIRED AT AN APPROVED LOCATION.
* EXISTING STRUCTURE. NO CHANGE OF OCCUPANCY OR ADDITION OF FIRE AREA IS
PROPOSED.
* FIRE SPRINKLER PIPING TO BE INSTALLED AT SECOND FLOOR, PREVIOUSLY STUBBED
TO THIS FLOOR, ALL OTHER AREAS ARE COMPLETE.
SHAFT ENCLOSURES
NO SHAFTS ARE PROPOSED FOR THE PROJECT
PENETRATIONS
NO FIRE RATED ASSEMBLIES ARE PROPOSED, THREFORE NO PENETRATION
REQUIREMENTS ANTICIPATED
SECTION 714
VERTICAL OPENINGS
712.1 GENERAL
EACH VERTICAL OPENING SHALL COMPLY IN ACCORDANCE WITH ONE OF THE
PROTECTION METHODS IN SECTIONS 712.1.1 THROUGH 712.1.16.
712.1.6 DUCTS AND AIR TRANSFER OPENINGS
PENETRATIONS BY DUCTS AND AIR TRANSFER OPENINGS SHALL BE PROTECTED IN
ACCORDANCE WITH SECTION 717. GREASE DUCTS SHALL BE PROTECTED IN
ACCORDANCE WITH THE MECHANICAL CODE.
SECTION 712
DUCTS AND AIR TRANSFER OPENINGS
717.1 GENERAL
THE PROVISIONS OF THIS SECTION SHALL GOVERN THE PROTECTION OF DUCT
PENETRATIONS AND AIR TRANSFER OPENINGS IN ASSEMBLIES REQUIRED TO BE
PROTECTED AND DUCT PENETRATIONS IN NONFIRE-RESISTANCE-RATED FLOOR
ASSEMBLIES.
717.1.2.1 DUCTS THAT PENETRATE NONFIRE-RESISTANCE-RATED ASSEMBLIES
THE SPACE AROUND A DUCT PENETRATING A NONFIRE-RESISTANCE-RATED FLOOR
ASSEMBLY SHALL COMPLY WITH SECTION 717.6.3.
717.6.3 NONFIRE-RESISTANCE-RATED FLOOR ASSEMBLIES
DUCT SYSTEMS CONSTRUCTED OF APPROVED MATERIALS IN ACCORDANCE WITH THE
MECHANICAL CODE THAT PENETRATE NONFIRE-RESISTANCE-RATED FLOOR
ASSEMBLIES SHALL BE PROTECTED BY ANY OF THE FOLLOWING METHODS:
3. IN FLOOR ASSEMBLIES COMPOSED OF NONCOMBUSTIBLE MATERIALS, A
SHAFT SHALL NOT BE REQUIRED WHERE THE DUCT CONNECTS NOT MORE
THAN THREE STORIES, THE ANNULAR SPACE AROUND THE PENETRATING DUCT
IS PROTECTED WITH AN APPROVED NONCOMBUSTIBLE MATERIAL THAT RESISTS
THE FREE PASSAGE OF FLAME AND THE PRODUCTS OF COMBUSTION AND A
FIRE DAMPER IS INSTALLED AT EACH FLOOR LINE.
SECTION 717
SECTION 713
FIRE-RESISTANT JOINT SYSTEMS SECTION 715
NO FIRE RATED ASSEMBLIES ARE PROPOSED, THREFORE NO FIRE-RESISTANT JOINT
SYSTEMS ARE ANTICIPATED
OPENING PROTECTIVES SECTION 716
NO FIRE RATED ASSEMBLIES ARE PROPOSED, THREFORE NO OPENING PROTECTIVES
ARE ANTICIPATED
CONCEALED SPACES SECTION 718
FIREBLOCKING AND DRAFTSTOPPING SHALL BE INSTALLED IN COMBUSTIBLE
CONCEALED LOCATIONS IN ACCORDANCE WITH THIS SECTION. FIREBLOCKING SHALL
COMPLY WITH SECTION 718.2. DRAFTSTOPPING IN FLOOR/CEILING SPACES AND ATTIC
SPACES SHALL COMPLY WITH SECTIONS 718.3 AND 718.4, RESPECTIVELY.
PLUMBING FIXTURES CHAPTER 29 AND PLUMBING CODE
CLASSIFICATION LAVATORIES DRINKING
FOUNTAINS
U
GENDER
NEUTRAL
WC
FM
EDUCATIONAL
SUBTOTAL
URINALS
M
2.31
WATER
CLOSETS
FM
6.01
ROUNDED TOTAL 3377
OCC
LOAD
PROPOSED 36
32.31
1513 129
* URINALS MAY REPLACE WATER CLOSETS AT A
RATIO OF 1 URINAL PER 2/3 WATER CLOSET.
REQUIRED FIXTURES:
601 / 50 = 12.02 = 12 WATER CLOSETS
601 / 50 = 12.02 = 12 LAVATORIES
1 DRINKING FOUNTAIN PER FLOOR
6.01
6.01 6.01
6.01 6.01
6.01 6.01
LAV
2 2
PROJECT INFORMATION
PERMIT APPLICANT: KSW ARCHITECTS LLC.
ON BEHALF OF SOUTHERN OREGON UNIVERSITY
PROJECT ADDRESS: 1250 SISKIYOU BOULEVARD
ASHLAND, OR 97520
JACKSON COUNTY
PROJECT AGENT: JIM McNAMARA
351 WALKER AVENUE
ASHLAND, OR 97520
JACKSON COUNTY
PROJECT NARRATIVE:
THE PROPOSED PROJECT IS A RENOVATION TO SOUTHERN OREGON UNIVERSITY'S
CENTRAL HALL. CENTRAL HALL IS A CONCRETE AND WOOD BUILDING BUILT IN 1950. A
MAJOR RENOVATION OCCURED IN 1967.
THE PROJECT INCLUDES INTERIOR RENOVATION OF THE SECOND FLOOR. THIS
INCLUDES NEW INTERIOR PARTITIONS, NEW FURRING AND INSULATION TO EXISTING
CONCRETE WALLS, NEW INTERIOR FINISHES, NEW PLUMBING FIXTURES, NEW
MECHANICAL DUCTWORK AND TERMINATIONS, AND NEW ELECTRICAL FIXTURES. THE
BASEMENT AND FIRST FLOOR HAVE BEEN PREVIOUSLY RENOVATED.
EXISTING BUILDING - CONSTRUCTION TYPE: V-B (SPRINKLERED)
BUILDING CONSTRUCTION:
ZONING INFORMATION
BASE ZONE: SOUTHERN OREGON UNIVERSITY (SO)
OVERLAY ZONES: NONE
SPECIAL DISTRICTS: SOUTHERN OREGON UNIVERSITY (SOU)
MAP & TAX LOT: 391E10CC 5700
ACERAGE: 21.36 ACRES
MEANS OF EGRESS
EGRESS WIDTH PER OCCUPANT SERVED (PER 1005.3):
STAIRWAYS: (0.3"/OCC) = REFER TO BUILDING EXITING TABLE
EXCEPTION #1: (0.2"/OCC) FOR BUILDINGS WITH AUTOMATIC SPRINKLER SYSTEM
OTHER EGRESS COMPONENTS: (0.2"/OCC) = REFER TO BUILDING EXITING TABLE
EXCEPTION #1: (0.15"/OCC) FOR BUILDINGS WITH AUTOMATIC SPRINKLER SYSTEM
EXIT ACCESS STAIRWAY WIDTH (1009.3.2):
48" MINIMUM STAIRWAY WIDTH REQUIRED
EXCEPTION #1: 48" BETWEEN HANDRAILS IS NOT REQUIRED IN FULLY SPRINKLED
BUILDINGS.
STAIRWAY WIDTH AND CAPACTITY (1011.2):
MINIMUM WIDTH REQUIRED IS 44"
CHAPTER 10
NUMBER OF EXITS (1015):
TWO EXITS REQUIRED PER TABLE 1015.1
ILLUMINATED EXIT SIGNS: REQUIRED PER 1013.3
EXIT ACCESS (1006.2.1):
COMMON PATH OF EGRESS TRAVEL FOR GROUP B: 100'-0"
EXIT ACCESS TRAVEL DISTANCE (1017):
OCC B (WITH SPRINKLER SYSTEM) = 300'-0"
EXIT ACCESS STAIRWAYS AND RAMPS (1019):
1019.3 - OCCUPANCIES OTHER THAN I-2 AND I-3.
IN OTHER THAN GROUP I-2 AND I-3 OCCUPANCIES, FLOOR OPENINGS CONTAINING EXIT
ACCESS STAIRWAYS OR RAMPS THAT DO NOT COMPLY WITH ONE OF THE CONDITIONS
LISTED IN THIS SECTION SHALL BE ENCLOSED WITH A SHAFT ENCLOSURE
CONSTRUCTED IN ACCORDANCE WITH SECTION 713.
#4: EXIT ACCESS STAIRWAYS AND RAMPS IN BUILDINGS EQUIPPED THROUGHOUT WITH
AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1, WHERE
THE AREA OF THE VERTICAL OPENING BETWEEN STORIES DOES NOT EXCEED TWICE
THE HORIZONTAL PROJECTED AREA OF THE STAIRWAY OR RAMP AND THE OPENING IS
PROTECTED BY A DRAFT CURTAIN AND CLOSELY SPACED SPRINKLERS IN
ACCORDANCE WITH NFPA 13.
EXIT ACCESS ILLUMINATION REQUIREMENT:
EGRESS LIGHTING REQUIRED ALONG THE EGRESS PATH TO THE R.O.W. PER SECTION
1008.3.5.
PERFORMANCE REQUIREMENTS:
AVERAGE OF 1fc WITH A MINIMUM OF 0.1fc AT ANY POINT ON THE EGRESS PATH AT FLOOR LEVEL, LIGHT LEVEL MAY DECLINE TO AVERAGE OF 0.6fc WITH A MINUMN OF 0.06fc AT ANY POINT ON THE EGRESS PATH AT FLOOR LEVEL AFTER 90 MINUTES OF
OPERATION ON EMERGENCY POWER.
MAXIMUM TO MINIMUM ILLUMINATION UNIFORMITY RATIO OF 40 TO 1 SHALL NOT BE
EXCEEDED.
EXITING TABLE
BASEMENT FIRST FLOOR SECOND FLOOR
EXIT BN = .15 x 90 = 13.5" EXIT 1N = .15 x 95 = 14.25" EXIT 2E = .15 x 74 = 11.1" EXIT BE = .2 x 90 = 18.0" EXIT 1E = .15 x 141 = 21.15" EXIT 2SA = .2 x 74 = 14.8" EXIT BS = .2 x 89 = 17.8" EXIT 1S = .15 x 160 = 24.0" EXIT 2SB = .2 x 74 = 14.8"
EXIT 1W: .15 x 96 = 14.4" EXIT 2W: = .15 x 74 = 11.1"
CORRIDORS (1020):
1020.1 CONSTRUCTION:
CORRIDORS SHALL BE FIRE-RESISTANCE RATED IN ACCORDANCE WITH TABLE 1020.1.
THE CORRIDOR WALL REQUIRED TO BE FIRE-RESISTANCE RATED SHALL COMPLY WITH
SECTION 708 FOR FIRE PARTITIONS.
TABLE 102.1 CORRIDOR FIRE-RESISTANCE RATING
OCCUPANCY - B
OCCUPANT LOAD SERVED BY CORRIDOR - GREATER THAN 30
REQUIRED FIRE-RESISTANCE RATING, WITH SPRINKLER SYSTEM - O HOURS
1020.2 WIDTH AND CAPACTY:
THE REQUIRED CAPACTY OF CORRIDORS SHALL BE DETERMINED AS SPECIFIED IN
SECTION 1005.1, BUT THE MINIMUM WIDTH SHALL BE NOT LESS THAN THAT SPECIFIED IN
TABLE 1020.2.
TABLE 1020.2 MINIMUM CORRIDOR WIDTH
OCCUPANCY - ANY FACILITY NOT LISTED IN THIS TABLE MINIMUM WIDTH - 44 INCHES
1020.4 DEAD ENDS:
WHERE MORE THAN ONE EXIT OR EXIT ACCESS DOORWAY IS REQUIRED, THE EXIT
ACCESS SHALL BE ARRANGED SUCH THAT DEAD-END CORRIDORS DO NOT EXCEED 20
FEET IN LENGTH.
EXCEPTIONS:
2. IN OCCUPANCIES IN GROUP B, E, F, I-1, M, R-1, R-2, S AN U, WHERE THE BUILDING IS
EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
WITH SECTION 903.3.1.1, THE LENGTH OF THE DEAD-END CORRIDORS SHALL NOT
EXCEED 50 FEET.
BUILDING CONSTRUCTION
CONSTRUCTION TYPE: V-B
CHAPTER 5, 6 & 7
BUILDING HEIGHT (PER TABLE 504.3) 60' 37'-6" EXISTING
ALLOWABLE PROPOSED
NUMBER OF STORIES (PER TABLE 504.4)
NOTE: AUTOMATIC SPRINKLER SYSTEM SHALL BE IN ACCORDANCE WITH SECTION
903.3.1.1 (NFPA 13) Fire Sprinklers are Proposed for this Project
3 3 EXISTING
FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (TABLE 601)
BUILDING ELEMENT
STRUCTURAL FRAME
BEARING WALLS - EXTERIOR
INTERIOR
NOTE:
NONBEARING WALLS AND PARTITIONS
FLOOR CONSTRUCTION
ROOF CONSTRUCTION
FIRE RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS
BASED ON FIRE SEPARATION DISTANCE (TABLE 602)
FIRE SEPARATION DISTANCE PROVIDED 31'-0"
NORTH
TYPE V-B
a. DISTANCE IS TO CENTER OF RIGHT OF WAY
b. DISTANCE IS TO ASSUMED PROPERTY LINE BETWEEN BUILDINGS
c. DISTANCE IT TO ADJACENT PARKING LOT
0-HR
b 87'-6"
EAST
0-HR
b 54'-0"
SOUTH
0-HR
50'-0"
WEST
0-HR
c
MAXIMUM AREA OF EXTERIOR WALL OPENINGS (TABLE 705.8)
FIRE SEPARATION DISTANCE PROVIDED
NORTH
MAXIMUM AREA OF UNPROTECTED
OPENINGS (BUILDING SPRINKLERED)
NO LIMIT
b
EAST SOUTH
NO LIMIT
a
WEST
c
TYPE - VB
0 - HR
0 - HR
0 - HR
0 - HR
0 - HR
0 - HR
0 - HR
0 - HR
0 - HR
0 - HR
TYPE - VB
REQUIRED PROPOSED
1 - HR
0 - HR
31'-0" 87'-6" 54'-0" 50'-0" a b
NO LIMITNO LIMIT
a. DISTANCE IS TO CENTER OF RIGHT OF WAY
b. DISTANCE IS TO ASSUMED PROPERTY LINE BETWEEN BUILDINGS
c. DISTANCE IT TO ADJACENT PARKING LOT
DRAFT STOPS IN ATTICS SECTION 718.4
EXCEPTION: BUILDINGS EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER
SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1.
DRAFTSTOPPING SHALL BE INSTALLED IN ATTICS AND CONCEALED
ROOF SPACES, SUCH THAT ANY HORIZONTAL AREA DOES NOT EXCEED
3,000 SQUARE FEET.
ALLOWABLE AREA CHAPTER 5
LEVEL
PROPOSED BUILDING AREAS (SF)
B
TOTALB OCC
6,808 SF
6,437 SF
12,828 SF
TOTAL 20,020 SF 40,400 SF
6,775 SF
ALLOWED (Aa)
ALLOWABLE AREA PER FLOOR (TABLE 503):
CONST
TYPE
OCCUPANCY
TYPE
ALLOWABLE AREA
PER STORY
NOTES
V-B B 27,000 SF
27,000 SF
81,000 SF
14,296 SF
13,276 SF 27,000 SF
27,000 SF
UNDESIGNATED
7,488 SF
6,839 SF
5,758 SF
20,085 SF
BUILDING SEPARATIONS
APPLICABLE OCCUPANCY CLASSIFICATION GROUPS: B, S-1
OCCUPANCY SEPARATION (TABLE 508.4):
OCCUPANCY
B TO S-1
REQUIRED SEPARATION (SPRINKER SYSTEM PROVIDED PER 903.3.1.1)
0 HR (NO SEPARATION REQUIREMENT)
CHAPTER 5
ENERGY CONSERVATION ASHRAE 90.1 (2022)
ROOF
AREA OR
PERIMETER
EXTERIOR WALL
NOTES: BUDGET U-FACTORS ARE CODE REQUIREMENTS.
BUILDING
COMPONENTS
CLIMATE ZONE: 4C
BUILDING SPACE CONDITIONING TYPE: COMMERCIAL
AVERAGE FENESTRATION %: EXISTING - NO CHANGE
NEW WALL INSULATION TO MEET CODE
EXISTING --
R-11.5
FLOOR: SLAB
CAVITY
R-VALUE
CONT
R-VALUE
PROPOSED
U-FACTOR
BUDGET
U-FACTOR
-- .520
.021
.104
--WINDOWS -- .450
EXISTING
EXISTING
EXISTING .087
EXISTING
GOVERNING CODES
THE DESIGN OF THIS PROJECT IS BASED ON THE FOLLOWING CODES:
2022 OREGON STRUCTURAL SPECIALTY CODE
INCLUDING CHAPTER 34 - EXISTING BUILDINGS
2025 OREGON ENERGY EFFICIENCY SPECIALTY CODE
ASHRAE STANDARD 90.1-2022
2022 OREGON MECHANICAL SPECIALTY CODE
2023 OREGON ELECTRICAL SPECIALTY CODE
2023 OREGON PLUMBING SPECIALTY CODE
2022 OREGON FIRE CODE
NFPA 72: NATIONAL FIRE ALARM CODE, 2025 ED.
NFPA 13: AUTOMATIC SPRINKLER SYSTEMS, 2025 ED
RISK CATEGORY
TABLE 1604.5: RISK CATEGORY OF BUILDINGS AND OTHER STRUCTURES
RISK CATEGORY NATURE OF OCCUPANCY
III BUILDINGS AND OTHER STRUCTURES THAT REPRESENT A
SUBSTANTIAL HAZARD TO HUMAN LIFE IN THE EVENT OF
FAILURE, INCLUDING BUT NOT LIMITED TO:
BUILDINGS AND OTHER STRUCTURES CONTAINING
EDUCATIONAL OCCUPANCIES FOR STUDENTS ABOVE
THE 12TH GRADE WITH AN OCCUPANT LOAD
GREATER THAN 500.
SECTION 1604.5
OSSC CHAPTER 34 EXISTING BUILDINGS
COMPLIANCE METHOD SELECTED: SECTION 301.3:
3403.1.3.1 - PRESCRIPTIVE COMPLIANCE METHOD: YES
ALTERATIONS, ADDITIONS AND CHANGES OF OCCUPANCY COMPLYING WITH SECTION 3405 SHALL BE CONSIDERED IN COMPLIANCE WITH
THE PROVISIONS OF THIS CHAPTER.
3403.1.3.2 - WORK AREA COMPLIANCE METHOD: NO
ALTERATIONS, ADDITIONS AND CHANGES OF OCCUPANCY COMPLYING WITH THE APPLICABLE REQUIREMENTS OF SECTIONS 3406 THROUGH
3412 SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS OF THIS CHAPTER.
3403.1.3.3 - PERFORMANCE COMPLIANCE METHOD: NO
ALTERATIONS, ADDITIONS AND CHANGES OF OCCUPANCY COMPLYING WITH SECTION 3413 SHALL BE CONSIDERED IN COMPLIANCE WITH
THE PROVISIONS OF THIS CHAPTER.
SECTION 3405 PRESCRIPTIVE COMPLIANCE METHOD
3405.1 GENERAL
3405.1.1 SCOPE
THE PROVISIONS OF THIS SECTION SHALL CONTROL THE ALTERATION, ADDITION AND CHANGE OF OCCUPANCY OF EXISTING BUILDINGS AND STRUCTURES, INCLUDING HISTORIC BUILDINGS AND STRUCTURES AS REFERENCED IN SECTION 3403.1.3.1.
3405.1.1.1 COMPLIANCE WITH OTHER METHODS
ALTERATIONS, ADDITIONS AND CHANGES OF OCCUPANCY TO EXISTING BUILDINGS AND STRUCTURES SHALL COMPLY WITH THE PROVISIONS OF
THIS CHAPTER OR WITH ONE OF THE METHODS PROVIDED IN SECTION 3404.1.3.
3405.1.2 FIRE-RESISTANCE RATINGS
WHERE APPROVED BY THE BUILDING OFFICIAL, IN BUILDINGS WHERE AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 HAS BEEN ADDED, AND THE BUILDING IS NOW SPRINKLERED THROUGHOUT, THE REQUIRED FIRE-RESISTANCE RATINGS OF BUILDING ELEMENTS AND MATERIALS SHALL BE PERMITTED TO MEET THE REQUIREMENTS OF THE CURRENT BUILDING CODE. THE BUILDING IS REQUIRED TO MEET THE OTHER APPLICABLE REQUIREMENTS OF THIS CODE FOR NEW CONSTRUCTION.
PLANS, INVESTIGATION AND EVALUATION REPORTS, AND OTHER DATA SHALL BE SUBMITTED INDICATING WHICH BUILDING ELEMENTS AND MATERIALS THE APPLICANT IS REQUESTING THE BUILDING OFFICIAL TO REVIEW AND APPROVE FOR DETERMINATION OF APPLYING THE CURRENT BUILDING CODE FIRE-RESISTANCE RATINGS. SUBMITTED EVALUATION REPORTS SHALL IDENTIFY ANY SPECIAL CONSTRUCTION FEATURES THAT IMPACT REQUIRED FIRE-RESISTANCE RATINGS, INCLUDING: FIRE-RESISTANCE-RATED ASSEMBLIES AND SMOKE- RESISTIVE ASSEMBLIES; CONDITIONS OF OCCUPANCY; MEANS OF EGRESS CONDITIONS; APPROVED MODIFICATIONS; APPROVED ALTERNATIVE MATERIALS, DESIGN AND METHODS OF CONSTRUCTION; AND EQUIPMENT APPLYING TO THE BUILDING.
3405.2 ADDITIONS - DOES NOT APPLY
3405.3 ALTERATIONS - APPLIES
3405.3.1 GENERAL
ALTERATIONS TO ANY BUILDING OR STRUCTURE SHALL COMPLY WITH THE REQUIREMENTS OF THIS CODE FOR NEW CONSTRUCTION.
ALTERATIONS SHALL BE SUCH THAT THE EXISTING BUILDING OR STRUCTURE IS NOT LESS COMPLIANT WITH THE PROVISIONS OF THIS CODE FOR NEW CONSTRUCTION THAN THE EXISTING BUILDING OR STRUCTURE WAS PRIOR TO THE ALTERATION.
3405.3.2 FLOOD HAZARD AREAS - DOES NOT APPLY
3405.3.3 EXISTING STRUCTURAL ELEMENTS CARRYING GRAVITY LOAD - DOES NOT APPLY
ANY EXISTING GRAVITY LOAD-CARRYING STRUCTURAL ELEMENT FOR WHICH AN ALTERATION CAUSES AN INCREASE IN DESIGN GRAVITY LOAD OF MORE THAN 5 PERCENT SHALL BE REPLACED OR ALTERED AS NEEDED TO CARRY THE DESIGN GRAVITY LOADS REQUIRED BY THIS CODE FOR NEW STRUCTURES. ANY EXISTING GRAVITY LOAD-CARRYING STRUCTURAL ELEMENT WHOSE GRAVITY LOAD-CARRYING CAPACITY IS DECREASED AS PART OF THE ALTERATION SHALL BE SHOWN TO HAVE THE CAPACITY TO RESIST THE APPLICABLE DESIGN GRAVITY LOADS
REQUIRED BY THIS CODE FOR NEW STRUCTURES.
3405.3.4 EXISTING STRUCTURAL ELEMENTS CARRYING LATERAL LOAD - DOES NOT APPLY
EXCEPT AS PERMITTED BY SECTION 3405.3.13, WHERE THE ALTERATION INCREASES DESIGN LATERAL LOADS, RESULTS IN A PROHIBITED STRUCTURAL IRREGULARITY AS DEFINED IN ASCE 7, OR DECREASES THE CAPACITY OF ANY EXISTING LATERAL LOAD-CARRYING STRUCTURAL ELEMENT, THE STRUCTURE OF THE ALTERED BUILDING OR STRUCTURE SHALL MEET THE REQUIREMENTS OF SECTIONS 1609 AND 1613.
REDUCED SEISMIC FORCES SHALL BE PERMITTED.
3405.3.5 THROUGH 3405.3.12 - RESERVED
3405.3.13 VOLUNTARY LATERAL FORCE-RESISTING SYSTEM ALTERATIONS - DOES NOT APPLY
STRUCTURAL ALTERATIONS THAT ARE INTENDED EXCLUSIVELY TO IMPROVE THE LATERAL FORCE-RESISTING SYSTEM AND ARE NOT REQUIRED BY OTHER SECTIONS OF THIS CHAPTER SHALL NOT BE REQUIRED TO MEET THE REQUIREMENTS OF SECTION 1609 OR 1613, PROVIDED THAT ALL
OF THE FOLLOWING APPLY:
1. THE CAPACITY OF EXISTING STRUCTURAL SYSTEMS TO RESIST FORCES IS NOT REDUCED.
2. NEW STRUCTURAL ELEMENTS ARE DETAILED AND CONNECTED TO EXISTING OR NEW STRUCTURAL ELEMENTS AS REQUIRED BY THIS
CODE FOR NEW CONSTRUCTION.
3. NEW OR RELOCATED NONSTRUCTURAL ELEMENTS ARE DETAILED AND CONNECTED TO EXISTING OR NEW STRUCTURAL ELEMENTS
AS REQUIRED BY THIS CODE FOR NEW CONSTRUCTION.
4. THE ALTERATIONS DO NOT CREATE A STRUCTURAL IRREGULARITY AS DEFINED IN ASCE 7 OR MAKE AN EXISTING STRUCTURAL
IRREGULARITY MORE SEVERE.
3405.3.14 SMOKE COMPARTMENTS - DOES NOT APPLY
3405.3.15 RESERVED
3405.3.16 ENHANCED CLASSROOM ACOUSTICS - DOES NOT COMPLY
IN GROUP E OCCUPANCIES, WHERE THE WORK AREA EXCEEDS 50 PERCENT OF THE BUILDING AREA, ENHANCED CLASSROOM ACOUSTICS
SHALL BE PROVIDED IN ALL CLASSROOMS WITH A VOLUME OF 20,000 CUBIC FEET (565 M3) OR LESS. ENHANCED CLASSROOM ACOUSTICS SHALL
COMPLY WITH THE REVERBERATION TIME IN SECTION 808 OF ICC A117.1.
3405.3.17 LOCKING ARRANGEMENTS IN EDUCATIONAL OCCUPANCIES - WORK WILL COMPLY
IN GROUP E OCCUPANCIES, GROUP B EDUCATIONAL OCCUPANCIES AND GROUP I-4 OCCUPANCIES, EGRESS DOORS WITH LOCKING
ARRANGEMENTS DESIGNED TO KEEP INTRUDERS FROM ENTERING THE ROOM SHALL COMPLY WITH SECTION 1010.2.8.
3405.3.18 TWO-WAY COMMUNICATION SYSTEMS - DOES NOT APPLY
3405.4 FIRE ESCAPES - DOES NOT APPLY
3405.5 WINDOWS AND EMERGENCY ESCAPE OPENINGS - DOES NOT APPLY
3405.6 CHANGE OF OCCUPANCY - DOES NOT APPLY
UP
DN
UP
DN
DN
DN
UP
DN
UPUP
DN
DN
DN
DNDN
UP
PROPERTY LINE
1/2 HOUR FIRE PARTITION - 1/3 HOUR DOOR
1 HOUR FIRE PARTITION - 1/3 HOUR DOOR
1 HOUR FIRE BARRIER - 1 OR 3/4 HOUR DOOR
2 HOUR FIRE BARRIER - 1 1/2 HOUR DOOR
3 HOUR FIRE BARRIER - 3 HOUR DOOR
EXTERIOR EGRESS PATH TO R.O.W. WITH
TRAVEL WIDTH REQUIRED (PROVIDE MINIMUM
ILLUMIATION FOR EXITING)
INTERIOR EGRESS PATH OF TRAVEL WITH
TRAVEL WIDTH REQUIRED (PROVIDE MINIMUM
ILLUMINATION FOR EXITING)
LEGEND - CODE SUMMARY
FE
MH
AREA TAG
OCCUPANT LOAD TAG
BUILDING EXIT
CEILING MOUNTED LIGHTED EXIT SIGN -
SHADING INDICATES LIGHTED FACE(S)
ARROW INDICATES DIRECTION ARROW ON
SIGN
WALL MOUNTED LIGHTED EXIT SIGN
FIRE EXTINGUISHER
SMOKE DETECTOR
MAGNETIC HOLD
OPEN
MANUAL PULL
STATION
ACCESSIBLE ENTRANCE
STANDPIPE
ACCESSIBLE ROUTE OF TRAVEL
COMMON PATH OF EGRESS TRAVEL (PER 1006.2.1)
EXIT ACCESS DISTANCE (PER 1017)
C.P. XX'-XX"
E.A. XX'-XX"
AREA (SF)
OCCUPANCY TYPE
OCCUPANT LOAD FACTOR
# OF OCCUPANTS
X HR RATED SHAFT (WALL CONSTRUCTION TO MEET
FIRE BARRIER REQUIREMENTS)
XX"
XX"
AREA:
OT:
OLF:
OCC:
AREA NAME
150 SF
X-X
XXX
XX
BN
BE
BS
CORRIDOR
HALL
HALL
HALL
FE
FE
HALL
HALL
MAX TRAVEL DISTANCE = 148'
M
IN. SEPARATIO
N DISTANCE IS 18'-4"
55'-9"
40'-7"
AREA:
OT:
OLF:
OCC:
964 SF
CLASSROOM
B
AREA:
OT:
OLF:
OCC:
246 SF
STORAGE
B
AREA:
OT:
OLF:
OCC:
132 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
128 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
292 SF
WEAPONS SIM
B
AREA:
OT:
OLF:
OCC:
160 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
131 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
133 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
116 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
124 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
128 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
103 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
119 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
126 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
93 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
94 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
121 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
121 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
154 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
85 SF
WORK RM.
B
AREA:
OT:
OLF:
OCC:
125 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
139 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
360 SF
CONFERENCE
B
AREA:
OT:
OLF:
OCC:
263 SF
STORAGE
B
AREA:
OT:
OLF:
OCC:
519 SF
TESTING
B
AREA:
OT:
OLF:
OCC:
226 SF
STUDY
B
AREA:
OT:
OLF:
OCC:
225 SF
RECEPTION
B
AREA:
OT:
OLF:
OCC:
127 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
99 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
101 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
102 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
99 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
101 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
101 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
122 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
33 SF
P. TEST
B
AREA:
OT:
OLF:
OCC:
34 SF
P. TEST
B
AREA:
OT:
OLF:
OCC:
34 SF
P. TEST
B
AREA:
OT:
OLF:
OCC:
34 SF
P. TEST
B
AREA:
OT:
OLF:
OCC:
123 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
98 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
145 SF
OFFICE
B
AREA: 410 SF
MECHANICAL
AREA: 215 SF
WOMEN RR
AREA: 215 SF
MEN RR
AREA: 63 SF
ELEV.
AREA: 63 SF
ELEV. ROOM
AREA: 46 SF
STOR.
AREA: 76 SF
STOR.
AREA: 116 SF
I.S.
AREA: 89 SF
ELEC. RM.
AREA: 42 SF
JAN.
AREA: 83 SF
STAFF
AREA: 48 SF
TOILET
AREA: 149 SF
ROTC PREP.
AREA: 18 SF
STOR.
AREA:
OT:
OLF:
OCC:
117 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
118 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
118 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
118 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
123 SF
WAITING
B
AREA:
OT:
OLF:
OCC:
123 SF
WORK ROOM
B
AREA:
OT:
OLF:
OCC:
123 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
123 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
100 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
103 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
151 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
156 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
156 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
116 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
116 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
116 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
116 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
518 SF
WRITING LAB
B
AREA:
OT:
OLF:
OCC:
444 SF
CLASSROOM
B
AREA:
OT:
OLF:
OCC:
131 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
113 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
146 SF
OFFICE
B
AREA: 39 SF
JAN.
AREA: 61 SF
ELEC.
AREA: 45 SF
I.S. DN
AREA: 278 SF
WOMEN RR
AREA: 282 SF
MEN RR
CORRIDOR
LOBBY
LOBBY
CORRIDOR
ELEV.
FE
FE
89 90
55 55
MAX TRAVEL DISTANCE = 110'
44"
44"
1W
1E
1S
1N
AREA:
OT:
OLF:
OCC:
329 SF
CONFERENCE ROOM
B
AREA:
OT:
OLF:
OCC:
119 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
117 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
119 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
172 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
75 SF
WAITING
B
AREA:
OT:
OLF:
OCC:
121 SF
WORK ROOM
B
AREA:
OT:
OLF:
OCC:
128 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
121 SF
RECEPTION
B
AREA: 179 SF
FACULTY
AREA:
OT:
OLF:
OCC:
121 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
87 SF
WAITING
B
AREA:
OT:
OLF:
OCC:
119 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
114 SF
OFICE
B
AREA:
OT:
OLF:
OCC:
158 SF
WORK ROOM
B
AREA:
OT:
OLF:
OCC:
559 SF
MATH LAB
B
AREA: 290 SF
MATH LIBRARY
AREA:
OT:
OLF:
OCC:
101 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
103 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
234 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
155 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
1210 SF
CLASSROOM
B
AREA:
OT:
OLF:
OCC:
543 SF
STUDENT LOUNGE
B
AREA:
OT:
OLF:
OCC:
719 SF
CLASSROOM
B
AREA:
OT:
OLF:
OCC:
328 SF
STUDENT LOUNGE
B
AREA:
OT:
OLF:
OCC:
353 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
153 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
154 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
100 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
127 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
127 SF
OFFICE
B
AREA:
OT:
OLF:
OCC:
264 SF
CONFERENCE
B
AREA:
OT:
OLF:
OCC:
338 SF
RECEPTION
B
AREA:
OT:
OLF:
OCC:
234 SF
CONFERENCE
B
AREA:
OT:
OLF:
OCC:
1094 SF
CLASSROOM
B
AREA: 25 SF
ELEC.
AREA: 154 SF
STAFF LOUNGE
AREA: 28 SF
JAN.
AREA: 92 SF
I.T.
AREA: 109 SF
MEN RR
AREA: 110 SF
WOMEN RR
CORRIDOR
HALL
CORRIDOR
OPEN TO
BELOW
ELEV.
74FE
MIN
. S
EPARATIO
N D
IS
TANCE IS
17'-4
49'-5
39'-9"
MAX TRAVEL DISTANCE = 123'
FE
2W
2E
2SB 2SA
AREA: 44 SF
TOILET
AREA:
OT:
OLF:
OCC:
941 SF
OPEN STUDY
B
AREA:
OT:
OLF:
OCC:
1171 SF
FLEX OFFICE
B
ISSUE DATE:
PROJECT NO.:
SHEET:
REVISIONS
T hi s do cu m en t, a nd t he id ea s an d de si gn s in co rp or at ed h er ei n, a s an in st ru m en t of p ro fe ss io na l s er vi ce , i s th e pr op er ty o f K is tle r
S m al l +
W hi te A rc hi te ct s an d is n ot t o be u se d, in w ho le o r in p ar t, fo r an y ot he r pr oj ec t w ith ou t th e w rit te n au th or iz at io n of
K S
W A rc hi te ct s.
K
S W
A rc hi te ct s, TEL.: 541.488.8200
THESE DRAWINGS MAY
BE USED FOR:
CONSTRUCTION
BIDDING
RECORDATION
CONVEYANCE
ISSUANCE OF A PERMIT
FOR CONSTRUCTION
/1
/2
:0 :3
A
M
G0.6
1.20.26
25-021
100% CD
S
IS
K
IY
O U
B O
U L
E V
A R
D A
S H
L A
N D
O R
E G
O N
S O
U
C E
N T
R A
L H
A L
L
P H
A S
E
CODE
SUMMARY
S E
C O
N D
F L O
O R
T E
N A
N T
I M
P R
O V
E M
E N
T S
CODE SUMMARY - LEVEL 1
OCC
TYPE NAME AREA
OCC
L.F.
OCC
LOAD
# OF
EXITS
(1015.1)
COMMON
PATH DIST
(1014.3)
EXIT ACCESS
DIST (1016.2) COMMENTS
ELEC. 61 SF 1
I.S. 45 SF 1
JAN. 39 SF 1
MEN RR 282 SF 1
WOMEN RR 278 SF 1
B
B CLASSROOM 444 SF 20 23 1
B CONFERENCE
ROOM
329 SF 20 17
B FACULTY 179 SF 150 2
B MATH LAB 559 SF 20 28
B MATH LIBRARY 290 SF 150 2 1
B OFFICE 117 SF 150 1 1
B OFFICE 118 SF 150 1 1
B OFFICE 118 SF 150 1 1
B OFFICE 118 SF 150 1 1
B OFFICE 103 SF 150 1 1
B OFFICE 101 SF 150 1 1
B OFFICE 123 SF 150 1 1
B OFFICE 123 SF 150 1 1
B OFFICE 100 SF 150 1 1
B OFFICE 103 SF 150 1 1
B OFFICE 151 SF 150 2 1
B OFFICE 156 SF 150 2 1
B OFFICE 156 SF 150 2 1
B OFFICE 116 SF 150 1 1
B OFFICE 116 SF 150 1 1
B OFFICE 116 SF 150 1 1
B OFFICE 116 SF 150 1 1
B OFFICE 131 SF 150 1 1
B OFFICE 113 SF 150 1 1
B OFFICE 146 SF 150 1 1
B OFFICE 119 SF 150 1
B OFFICE 117 SF 150 1
B OFFICE 119 SF 150 1
B OFFICE 172 SF 150 2
B OFFICE 128 SF 150 1
B OFFICE 121 SF 150 1
B OFFICE 119 SF 150 1
B OFICE 114 SF 150 1
B RECEPTION 121 SF 150 1
B WAITING 123 SF 15 9 1
B WAITING 75 SF 15 6
B WAITING 87 SF 15 6
B WORK ROOM 123 SF 150 1 1
B WORK ROOM 121 SF 150 1
B WORK ROOM 158 SF 150 2
B WRITING LAB 518 SF 20 26 1
B
CODE SUMMARY - BASEMENT
OCC
TYPE NAME AREA
OCC
L.F.
OCC
LOAD
# OF
EXITS
(1015.1)
COMMON
PATH DIST
(1014.3)
EXIT ACCESS
DIST (1016.2) COMMENTS
ELEC. RM. 89 SF
ELEV. 63 SF 1
ELEV. ROOM 63 SF 1
I.S. 116 SF
JAN. 42 SF
MECHANICAL 410 SF 1
MEN RR 215 SF 1
ROTC PREP. 149 SF
STAFF 83 SF
STOR. 46 SF
STOR. 76 SF
STOR. 18 SF
TOILET 48 SF
WOMEN RR 215 SF 1
B
B CLASSROOM 964 SF 20 49 1
B CONFERENCE 360 SF 20 18
B OFFICE 132 SF 150 1
B OFFICE 128 SF 150 1
B OFFICE 160 SF 150 2
B OFFICE 131 SF 150 1
B OFFICE 133 SF 150 1
B OFFICE 116 SF 150 1
B OFFICE 124 SF 150 1
B OFFICE 128 SF 150 1
B OFFICE 103 SF 150 1
B OFFICE 119 SF 150 1
B OFFICE 126 SF 150 1
B OFFICE 93 SF 150 1
B OFFICE 94 SF 150 1
B OFFICE 121 SF 150 1
B OFFICE 121 SF 150 1
B OFFICE 154 SF 150 2
B OFFICE 125 SF 150 1
B OFFICE 139 SF 150 1
B OFFICE 127 SF 150 1
B OFFICE 99 SF 150 1
B OFFICE 101 SF 150 1
B OFFICE 102 SF 150 1
B OFFICE 99 SF 150 1
B OFFICE 101 SF 150 1
B OFFICE 101 SF 150 1
B OFFICE 122 SF 150 1
B OFFICE 123 SF 150 1
B OFFICE 98 SF 150 1
B OFFICE 145 SF 150 1
B P. TEST 33 SF 150 1
B P. TEST 34 SF 150 1
B P. TEST 34 SF 150 1
B P. TEST 34 SF 150 1
B RECEPTION 225 SF 150 2
B STORAGE 246 SF 300 1 1
B STORAGE 263 SF 300 1
B STUDY 226 SF 20 12
B TESTING 519 SF 20 26
B WEAPONS SIM 292 SF 150 2
B WORK RM. 85 SF 150 1
CODE SUMMARY - LEVEL 2
OCC
TYPE NAME AREA
OCC
L.F.
OCC
LOAD
# OF
EXITS
(1015.1)
COMMON
PATH DIST
(1014.3)
EXIT ACCESS
DIST (1016.2) COMMENTS
ELEC. 25 SF 1
I.T. 92 SF 1
JAN. 28 SF 1
MEN RR 109 SF 1
STAFF LOUNGE 154 SF 1
TOILET 44 SF 1
WOMEN RR 110 SF 1
B
B CLASSROOM 1210 SF 20 61 2
B CLASSROOM 719 SF 20 36 1
B CLASSROOM 1094 SF 20 55 2
B CONFERENCE 264 SF 20 14 1
B CONFERENCE 234 SF 20 12 1
B FLEX OFFICE 1171 SF 150 8 1
B OFFICE 234 SF 150 2 1
B OFFICE 155 SF 150 2 1
B OFFICE 353 SF 150 3 1
B OFFICE 153 SF 150 2 1
B OFFICE 154 SF 150 2 1
B OFFICE 100 SF 150 1 1
B OFFICE 127 SF 150 1 1
B OFFICE 127 SF 150 1 1
B OPEN STUDY 941 SF 20 48 1
B RECEPTION 338 SF 150 3 1
B STUDENT
LOUNGE
543 SF 20 28 1
B STUDENT
LOUNGE
328 SF 20 17 1
TN
1/16" = 1'-0" 1
CODE SUMMARY - BASEMENT
TN
1/16" = 1'-0" 2
CODE SUMMARY - LEVEL 1
TN
1/16" = 1'-0" 3 CODE SUMMARY - Level 2
B
B
FLOOR TOTAL
B
FLOOR TOTAL
BASEMENT OCCUPANT NUMBER 149
FIRST FLOOR OCCUPANT NUMBER 156
SECOND FLOOR OCCUPANT NUMBER 296
TOTAL BUILDING OCCUPANTS 601
149FLOOR TOTAL
EXISTING BUILDING
36" x 36" x 24" H
CONCRETE PEDESTAL
FOR "CHARGEPOINT"
EV CHARGER, PROVIDE
ELEC. CONDUITS AND
ANCHOR BOLTS IN
PEDESTAL FOR
CHARGER
INSTALLATION, CENTER
ON PARKING STRIPE
FENCED CONTRACTOR
STAGING AREA
TEMP. STAIRS
DOWN TO
PARKING LOT
PROVIDE SCAFFOLD
PLATFORM FOR
CONTRACTOR ACCESS
TO SECOND FLOOR
CONSTRUCTION ZONE.
MAINTAIN PEDESTRIAN
ACCESS UNDER
PLATFORM.
PRESERVE SOU
ACCESS TO
GROUND FLOOR
DURING
CONSTRUCTION
TEMPORARILY
REMOVE SECTION
OF GUARDRAIL FOR
CONSTRUCTION
ACCESS
6' CHAIN-LINK FENCED
CONTRACTOR STAGING
AREA
CONTRACTOR
ACCESS GATE
CONTRACTOR
ACCESS GATE
MAINTAIN SOU
ACCESS TO ADA
AND SERVICE
PARKING SPACES
SIDEWALKS & FIRST
FLOOR BUILDING
ENTRY TO REMAIN
OPEN
SIDEWALKS TO
REMAIN OPEN
ISSUE DATE:
PROJECT NO.:
SHEET:
REVISIONS
T hi s do cu m en t, a nd t he id ea s an d de si gn s in co rp or at ed h er ei n, a s an in st ru m en t of p ro fe ss io na l s er vi ce , i s th e pr op er ty o f K is tle r
S m al l +
W hi te A rc hi te ct s an d is n ot t o be u se d, in w ho le o r in p ar t, fo r an y ot he r pr oj ec t w ith ou t th e w rit te n au th or iz at io n of
K S
W A rc hi te ct s.
K
S W
A rc hi te ct s, TEL.: 541.488.8200
THESE DRAWINGS MAY
BE USED FOR:
CONSTRUCTION
BIDDING
RECORDATION
CONVEYANCE
ISSUANCE OF A PERMIT
FOR CONSTRUCTION
/1
/2
:0 :1
A
M
A0.1
1.20.26
25-021
100% CD
S
IS
K
IY
O U
B O
U L
E V
A R
D A
S H
L A
N D
O R
E G
O N
S O
U
C E
N T
R A
L H
A L
L
P H
A S
E
SITE PLAN
S E
C O
N D
F L O
O R
T E
N A
N T
I M
P R
O V
E M
E N
T S
TN
1/16" = 1'-0" 1
SITE - PLAN
GENERAL NOTES - SITE PLAN
A. SITE PLAN KEYNOTES APPLY TO SHEET A0.1 ONLY.
B. REFERENCE MECHANICAL AND ELECTRICAL DRAWINGS FOR
ADDITIONAL SITEWORK DEMOLITION INFORMATION.
5X - WOOD FURRED6X - WOOD PARTITION
IM
P T
WOOD - ACOUSTICAL PARTITION
NOTES:
1) STC 46 (BASED ON NGC 2018106) AT ACOUSTICAL WALLS.
D
IM
P T
WOOD - ACOUSTICAL PARTITION
D
IM
P T
WOOD - ACOUSTICAL PARTITION
NOTES:
1) STC 54 (BASED ON TEST NGC 2011066) AT ACOUSTICAL WALLS.
WOOD - STUD FURRED EXT. WALL
6X - WOOD PARTITION
09 21 16 - 5/8" TYPE X
ACOUSTICAL GYPSUM BOARD
09 21 16 - 5/8" TYPE X
ACOUSTICAL GYPSUM BOARD
09 21 16 - 5/8" TYPE X
ACOUSTICAL GYPSUM BOARD
09 21 16 - 5/8" TYPE 'X'
GYPSUM BOARD
07 21 00 - ACOUSTICAL
INSULATION
07 21 00 - ACOUSTICAL
INSULATION
07 21 10 - 2 3/4" MINERAL
WOOL INSULATION - MIN. R-4.2
PER INCH
NOTES:
1) STC 56 (BASED ON NGC 2010080) AT ACOUSTICAL WALLS.
U301 - INSTALLATION INSTRUCTIONS
Base layer 5/8 in. Type 'X' Gypsum Board applied vertically or horizontally to each side of 2x4 wood studs at 16 in. o.c. with 1-7/8 in. long 6d coated nails at 6 in. o.c., Face layer 5/8 in. Type 'X' Gypsum Board applied vertically or horizontally with 2-3/8 in. long 8d coated nails at 8 in. o.c., Vertical joints located over studs. Joints staggered each layer and side.
U301 - INSTALLATION INSTRUCTIONS with Optional Resilient Channels Base layer 5/8 in. Type 'X' Gypsum Board applied vertically to one side of 2x4 wood studs at 16 in. o.c. with 1-1/4 in. Type W screws at 8 in. o.c., Face layer 5/8 in. Type 'X' Gypsum Board applied with 2 in. Type W screws at 8 in. o.c., Resilient channels at 24 in. o.c.
applied horizontally to opposite side with 1-1/4 in. Type W screws. Base layer 5/8 in. Type 'X' Gypsum Board applied vertically to channels with 1 in. Type S screws at 24 in. o.c., Face layer 5/8 in. Type 'X' Gypsum Board applied with 1-5/8 in. Type S screws at 12 in.
o.c., Vertical joints located over studs.
This is the start of the file's text. The full file is on GovTribe.