This document set comprises product specification sheets and technical data for industrial cables and connector coating systems.

The AmerCable 37-119 Flexible Power Cable (DLO) is a single-conductor portable power cable rated for 2000 volts at 90°C, manufactured in sizes from 14 AWG to 1111 kcmil. The cable features flexible-stranded, tin-coated annealed copper conductors with ethylene-propylene rubber (EPR) insulation and a flame-retardant, oil and sunlight-resistant chlorinated polyethylene (CPE) outer jacket. It is rated RHH and RHW-2 for sizes 2/0 and higher and is UL listed for sunlight resistance and marine shipboard cable use (4/0 and larger, special order only). The cable meets flame resistance standards FT-4/IEEE1202 and UL VW-1, complies with UL 1685 smoke release requirements (marked ST-1), and meets hazardous waste regulations per 40 CFR 261 for characteristic lead content. Ampacity ratings range from 35 amps (14 AWG) to 1119 amps (1111 kcmil). AmerCable offers factory-installed connector options to reduce installation time and costs. Contact information: (870) 862-4919, (800) 643-1516, or fax (870) 862-9613.

The LSTHOF-150 is a three-conductor cable with 3/0 AWG bare copper conductors (760 strands of 0.0140 strand size), rated 180 amps at 50°C, featuring EPR insulation and halogen-free, low-smoke (LSZH) cross-linked polyolefin (XLPO) jacket with a maximum outside diameter of 1.820 inches. TRI Applied Technologies' NCC 209™ is a next-generation, two-component modified epoxy metal pretreatment system (35 mils ± 10 mils thickness) developed for the U.S. Navy to prevent cathodic delamination of submarine connectors. The system reduces VOC exposure, offers improved reliability at lower cost, and is applicable to harsh industrial, subsea, and down-hole environments. Technical contact: Vince Newton, (703) 944-4763, vnewton@tri-austin.com.

View the file

Other files

File Type Posted
SPMYM226Q0217.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

37-119

Flexible Power Cable • DLO 2000 Volts • 90°C Diesel Locomotive Cable • Low Smoke (Sizes 2/0 and higher) • EP/CPE • RHH, RHW-2

Manufactured by AmerCable Incorporated • (870) 862-4919 • (800) 643-1516 • Fax (870) 862-96132

Application AmerCable’s 2000V Diesel Locomotive Cable (DLO) is a single conductor portable power cable suitable for use in applications needing great flexibility, excellent wearability and good flex life. Applications include locomotive and car equipment, motor and generator leads, battery leads, shipyards, telecommunications power, heavy earth moving equipment, renewable energy and other heavy duty flexing applications.

Features � A two layer composite of flame retardant, oil and sunlight resistant Chlorinated Polyethylene (CPE) outer layer and Ethylene- Propylene rubber (EPR) inner layer. The composite design provides significant diameter reductions compared to designs using full thickness jackets.

� Suitable for continuous operating temperatures of 90°C, wet or dry

� Rated RHH, RHW-2; 2/0 – 1111 kcmil listed and marked “for CT use”

� UL listed as Sunlight Resistant

� UL listed as Marine Shipboard Cable (4/0 and larger) – Special order only

� Insulation and jacket meet hazardous waste regulations, per Code of Federal Regulations 40 Section 261 (40CFR261) for characteristic lead content

� Flame Resistance: FT-4/IEEE1202 for 2/0 – 1111 kcmil and UL VW-1

� Meets smoke release and other require-ments of Vertical Cable Tray Test UL 1685 and is marked “ST-1” for 2/0 – 1111 kcmil

� Extremely flexible stranding used for increased flexibility and ease of installation

Insulation Ethylene-Propylene rubber

(EPR)

Jacket Flame retardant, oil and sunlight resistant Chlorinated Polyethylene (CPE)

See below for jacket color options (Special order)

Conductor Flexible-stranded, tin-coated annealed copper

SSeparator Suitable separator tape provides easy stripping of insulation

Ratings & Approvals � ICEA S-95-658/ NEMA WC-70: Nonshielded Power

Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy

� UL Standard 44: Thermoset Insulated Wires & Cables, Types RHH, RHW-2. UL VW-1

� UL Standard 1685: Vertical Tray Fire propagation and Smoke Release Test for Electrical and optical Fiber Cables. (UL,ST-1)

� ASTM B-33: Standard Specification for Tinned Soft or Annealed Copper Wire for Electrical Purposes

� ASTM B-172: Standard Specification for Rope-Lay-Stranded Copper Conductors having Bunch-Stranded Members, for Electrical Conductors

� MSHA P-184

www. amercable.com • e-mail: industrial@amercable.com 3

Industrial Cables

37-119 • Single Conductor Portable Power Cable • DLO

201 14 19 0.045 0.015 0.214 31 35 202 12 19 0.045 0.015 0.233 41 40 203 10 37 0.045 0.015 0.257 58 55 204 8 168 0.055 0.030 0.349 77 80 205 6 61 0.055 0.030 0.365 124 105 207 4 133 0.055 0.030 0.460 203 140 209 2 259 0.055 0.030 0.534 265 190 210 1 224 0.065 0.045 0.623 415 220 211 1/0 266 0.065 0.045 0.668 489 260 212 2/0 323 0.065 0.045 0.689 562 300 213 3/0 418 0.065 0.045 0.771 757 350 214 4/0 532 0.065 0.045 0.822 894 405 215 262 646 0.075 0.065 0.957 1091 467 216 313 777 0.075 0.065 1.008 1245 522 217 373 925 0.075 0.065 1.074 1486 591 218 444 1110 0.075 0.065 1.143 1749 652 219 535 1332 0.090 0.065 1.257 2099 728 220 646 1591 0.090 0.065 1.361 2464 815 221 777 1924 0.090 0.065 1.439 2899 904 222 929 2318 0.090 0.065 1.685 3501 1005 223 1111 2745 0.130 0.065 1.850 4166 1119

* Ampacity – Calculated with at 90°C conductor temperature and 30°C ambient air, per 2008 NEC, Table 310.17

• Cable diameters are subject to +/-5% manufacturing tolerance

Approx.

Weight lbs. per 1,000 ft.

*Ampacity 90°C

Part No.

37-119-

Size

AWG/

kcmil

Minimum Wires per Conductor

Nominal Insulation Thickness in.

Nominal Jacket

Thickness in.

Nominal Outside

Diameter in.

Order Your DLO Cable with

Factory Installed Connectors

SAVE

TIME

SAVE

MONEY

LSTHOF-150

Attributes Values

No. of Cond. 3

Ampacity (50C) 180

Approx LBS/MFT 0.00

AWG Size 3/0

Cond. Material Bare Copper

Conductor Stranding 760/.014

Insul. Material Ethylene Propylene Rubber (EPR)

Jacket Material Halogen-Free (LSZH) Cross-Linked Polyolefin (XLPO)

Max O.D. (in) 1.820

Metal Tubes S

Mil-Spec M24643/3

No. of Strands 760

Nylon Tubes 8B

Strand Size 0.0140

1800 Central Commerce Ct., Ste. 900 Round Rock, TX 78664 | tri-appliedtech.com

TRI NCC 209™

Recently developed by TRI for the U.S. Navy to fight cathodic delamination (premature bond failure) of submarine connectors, TRI’s NCC 209™ ’s metal pretreatment system is ideal for use in harsh environments such as industrial, subsea and down-hole operations. NCC 209™ firmly adheres rubbers to metals so they can survive chemical exposure and high-pressure, extreme temperature conditions.

In independent third part testing, the new NCC 209™ out performs all other NCC systems in standard overmolds with peel strengths well beyond any previously seen. The result is a bond that can survive the harshest corrosive environments over an extended service life.

NEW OVERMOLD SYSTEM

•New NCC (Non-Conductive Coating) for both Navy and commercial applications
•Reduces exposure to harmful VOC’s and hazardous materials
•Reduces the number of failure points that exist in the currently approved overmold systems
•Increased reliability, reduced costs, improved application methods

NCC 209 SPECIFICATIONS

•2 component modified epoxy
•Thickness is 35 mils + or -10 mils
•Max temperature in process is 130C
•Standard undercut request is 10 mils
•Indefinite shelf life if stored correctly
•Cleaning and prep standard solvents are acceptable

TRI NCC 209™

TRI Next Generation NCC provides:

• Improved cathodic protection

• Ease of processing

• Applicable to NLOS locations

• Lower cost

• Higher density (less porosity)

A Product of TRI Applied Tech

TRI Applied Technologies is the product arm for TRI Austin. Applied Technologies provides commercialization strategies, product production, sales support, and marketing efforts for products developed by TRI Austin.

M-24231 Plug Sleeves Coated with NCC 209™

TO LEARN IF TRI NCC 209™

CAN HELP YOU WITH YOUR

APPLICATION, CONTACT:

VINCE NEWTON

DIR. SALES AND MARKETING

703.944.4763 vnewton@tri-austin.com tri-appliedtech.com

COMPARING OLD NCC STACK TO NEW TRI NCC 209™

Castable Polyurethane PR-1547 or EN-1556

Primer PR-420 or AD-1146

Seal Coat

Metal Substrate

Ceramic Layer Metal Matching Layer

Castable Polyurethane PR-1547 or EN-1556

Primer PR-420 or AD-1146

NCC 209™

Metal Substrate

TRI-109-2

Castable

Hydrophobic Polyurethane

NCC 209™

Metal Substrate

A Product of TRI Applied Tech

684386225BK01 - BK03 SALIENT CHARACTERISTICS (37-119 DLO).pdf