26185 Drawings.pdf

PDF 3 MB Posted

Attached to
551/26185. KMM; MSP Police Training Academy - ADA Lift
Solicitation number
RFQ 171 260000000440 2
Issued by
Grand Traverse County, Lansing City, Michigan

About this file

This is a set of architectural and electrical construction drawings for the Michigan State Police (MSP) Training Academy, specifically for an ADA lift installation project located at 7426 N. Canal Road, Lansing, Michigan 48913. The project scope involves providing barrier-free access to the stage area of the existing auditorium through installation of a two-stop vertical platform lift. The drawings were issued for bids on August 10, 2026, and include comprehensive architectural plans (covering demolition, floor plans, and building sections), electrical specifications, and detailed construction documents prepared by Hobbs + Black Associates, Inc. (Architect of Record) and Matrix Consulting Engineering, Inc. (Electrical Engineer). The project is classified as a Level 2 alteration under the Michigan Rehabilitation Code, with construction type II-B, and maintains existing building height and area limitations with no structural changes required.

The electrical work includes installation of new power and lighting circuits, conduit routing, outlet placement, and integration with existing electrical systems, with the new ADA lift controller requiring a 20-ampere, 120-volt branch circuit connection to existing panel EPD1. The project scope encompasses demolition of portions of existing metal guard rails and channel stringers, temporary wall and door construction to isolate the work area during occupancy, relocation of existing light fixtures, and restoration of removed carpet tile flooring. All work must comply with the 2021 Michigan Building Code, 2021 Michigan Rehabilitation Code, 2023 National Electrical Code, and applicable ASME and NFPA standards. The building will remain occupied during construction and renovation operations, requiring daily cleaning and debris removal by the contractor to maintain clear exits and protect existing finishes.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONSULTANT

SHEET TITLE

PROJECT NUMBER

SHEET NUMBER

PROJECT

Copyright 2021, Hobbs + Black Associates, Inc.C

ALL RIGHTS RESERVED

H G F E D C B A

H G F E D C B A

Sheet Size - 24x36

DATE ISSUED

DRAWN BY

CHECKED BY

A u to d e s k D o c s /2

-3

M

S P

T ra in in g A c a d e m y A

D A

L if t P

H

-7

/2

-A

R C

H -M

S P

T ra in in g A c a d e m y A

D A

L if t P

H

-7

-2

.r v t

G-000

26-325

COVER SHEET

A U

D

IT

O R

IU

M

A D

A L

IF

T

N C

A N

A L

R D

L A

N S

IN

G

M

I

M S

P T

R A

IN

IN

G A

C A

D E

M Y

7426 N. CANAL RD.

LANSING, MI 48913

DTMB FILE NO.: 551/26185.KMM

ISSUED FOR BIDS

08/10/2026

MSP TRAINING ACADEMY

AUDITORIUM ADA LIFT

ELECTRICAL ENGINEER

MATRIX CONSULTING ENGINEERING, INC.

544 CHERBOURG DRIVE

LANSING, MI 48917

PHONE: (517) 487-2511

ARCHITECT OF RECORD

HOBBS + BLACK ASSOCIATES, INC.

117 E. ALLEGAN ST.

LANSING, MI 48933

PHONE: (517) 484-4870

LOCATION MAP VICINITY MAP

PROJECT LOCATION PROJECT LOCATION

NORTH NORTH

H+B PROJECT NO.: 26-325

ISSUED FOR BIDS 08/10/2026

UPUP

2021 MICHIGAN REHABILITATION CODE

2021 MICHIGAN BUILDING CODE

2023 NATIONAL ELECTRICAL CODE

2013 ASME A17.1 SAFETY CODE FOR ELEVATORS AND ESCALATORS

2016 NFPA 13, 2016 (NFPA 72, 2013 NFPA 17A, 2013 NFPA 96)

NATIONAL FIRE ALARM AND SIGNALING CODE (NFPA 72-16)

AUTOMATIC SPRINKLER SYSTEMS (NFPA-13-16)

APPLICABLE CODES

USE AND OCCUPANCY CLASSIFICATION (CHAPTER 3):

USE GROUP: B

CONSTRUCTION TYPE: II B

INCIDENTAL USES (CHAPTER 5; SECTION 509): NONE

CODE

MICHIGAN REHABILITATION CODE - LEVEL 2 ALTERATION

SHAFT ENCLOSURES NOT REQUIRED PER SECTION 802.2.2.1, EXCEPTION 5.2

CONSTRUCTION TYPE (CHAPTER 6; TABLE 601):

II-B NON-COMBUSTIBLE

GENERAL BUILDING HEIGHTS AND AREAS (CHAPTER 5):

GENERAL BUILDING HEIGHT AND AREA LIMITATIONS (SECTION 402.4.1.2, 503; TABLE 503, 504, 506, 507):

ALLOWABLE HEIGHT: 4 STORIES, 75 FEET

EXISTING HEIGHT: 2 STORIES, 36 FEET - NO CHANGE

ALLOWABLE BUILDING AREA PER STORY: UNLIMITED - NO CHANGE

MEANS OF EGRESS (CHAPTER 10):

1. EXISTING NO CHANGE

PROJECT SCOPE

TO PROVIDE BARRIER FREE ACCESS FOR CONVENIENCE TO THE STAGE AREA OF THE EXISTING AUDITORIUM BY

MEANS OF A 2-STOP VERTICAL LIFT (PLATFORM LIFT).

BUILDING CODE DATA

93'-5" TO EXIT

EXISTING

CLASSROOM

EXISITNG

CLASSROOM

EXISTING

CLASSROOM

EXISTING

CLASSROOM

EXISTING

CLASSROOM

EXISTING

AUDITORIUM

EXISTING

STORAGE

ROOM

EXISTING

ELECTRICAL

ROOM

EXISTING

TOILET

EXISTING

TOILET

EXISTING

GYMNASIUM

EXISTING

POOL

EXISTING

CLASSROOM

EXISTING

LOBBY

EXISTING

COORIDOR

EXISTING

STAGE

E X

T

R A

M P

D O

W N

CONSULTANT

SHEET TITLE

PROJECT NUMBER

SHEET NUMBER

PROJECT

Copyright 2021, Hobbs + Black Associates, Inc.C

ALL RIGHTS RESERVED

H G F E D C B A

H G F E D C B A

Sheet Size - 24x36

DATE ISSUED

DRAWN BY

CHECKED BY

A u to d e s k D o c s /2

-3

M

S P

T ra in in g A c a d e m y A

D A

L if t P

H

-7

/2

-A

R C

H -M

S P

T ra in in g A c a d e m y A

D A

L if t P

H

-7

-2

.r v t

G-010

26-325

CODE DATA

A U

D

IT

O R

IU

M

A D

A L

IF

T

N C

A N

A L

R D

L A

N S

IN

G

M

I

M S

P T

R A

IN

IN

G A

C A

D E

M Y

NORTH

SCALE - 1/16" = 1'-0"

CODE DATA FLOOR PLAN

_GENERAL

G-000 COVER SHEET

G-010 CODE DATA

ARCHITECTURAL

D-110 DEMOLITION FLOOR PLANS AND SECTION

ARCHITECTURAL

A-100 FLOOR PLAN

A-110 ENLARGED LOWER LEVEL FLOOR PLAN AND MAIN LEVEL

FLOOR PLAN

A-300 BUILDING SECTIONS

ELECTRICAL

E-100 ELECTRICAL COVER SHEET

E-101 ELECTRICAL SPECIFICATIONS

E-300 ELECTRICAL DEMOLITION TEMPLATE

E-400 LIGHTING AND POWER NEW

E-900 ELECTRICAL SCHEDULES

INDEX OF DRAWINGS

UP

DN

U PU P

G4

D-110

G4

D-110

EXISTING

STAIRWELL

EXISTING

STORAGE

ROOM

G4

D-110

G4

D-110

A-300

F4 8" 4'-5" 5'-3"

EXISTING

STAIRWELL

EXISTING

STORAGE

ROOM EXISTING RAILING

TO REMAIN.

TEMPORARY PARTITION

FROM FLOOR TO

UNDERSIDE OF CEILING

TEMPORARY

DOOR

LEVEL 1

ELEV = 100' - 0"

B.O. CEILING

ELEV = 107' - 4"

LOWER LEVEL

ELEV = 88' - 8"

LEVEL .5

ELEV = 96' - 6"

8"4'-5"5'-3"

GENERAL DEMOLITION NOTES:

1. CONTRACTOR SHALL NOT ALTER

THE STRUCTURAL INTEGRITY OF

THE BUILDING WITHOUT WRITTEN

APPROVAL OF THE ARCHITECT.

2. CONTRACTOR SHALL MAINTAIN

ALL EXITS CLEAR OF ANY

OBSTRUCTIONS.

3. THE BUILDING WILL BE

OCCUPIED DURING DEMOLITION

AND RENOVATION OPERATIONS.

THE CONTRACTOR SHALL CLEAN ALL

CONSTRUCTION AREAS AND

REMOVE ALL DEBRIS DAILY.

4. FILL OPENINGS IN SURFACES

THAT REMAIN. ALL SURFACES THAT

REMAIN, THAT ARE ADJACENT TO

REMOVED WORK, SHALL BE

PATCHED TO MATCH EXISTING

CONDITION.

5. ALL LOOSE ITEMS (FURNITURE,

EQUIPMENT, ETC.) IN STAIRWAY

WILL BE REMOVED BY OWNER

PRIOR TO DEMOLITION

ACTIVITIES.

6. PROTECT ALL FINISHES TO

REMAIN (FLOORING, WALLS, PAINT,

ETC.) DURING DEMOLITION AND

RENOVATION ACTIVITIES.

DEMOLITION KEY NOTES:

SAW CUT AND REMOVE PORTION

OF EXISTING METAL GUARD RAIL

AND CHANNEL STRINGER.

EXISTING LIGHT FIXTURE TO BE

RELOCATED, SEE ELECTRICAL.

EXISTING FLOORING (CARPET

TILE) TO BE REMOVED AS

REQUIRED DURING DEMOLITION

AND REINSTALLED AFTER

CONSTRUCTION IS COMPLETE.

AREA OF WORK

TEMPORARY CONSTRUCTION NOTES:

TEMPORARY WALL

• 3 5/8" METAL STUDS @ 2'-0" ON

CENTER.

• 5/8" GYPSUM BOARD (ONE SIDE)

TEMPORARY DOOR AND FRAME

• PROVIDE WOOD OR METAL DOOR

WITH SELF CLOSING HINGES AND

LATCH TO MINIMIZE DUST AND

NOISE DURING DEMOLITION AND

CONSTRUCTION OPERATIONS.

CONSULTANT

SHEET TITLE

PROJECT NUMBER

SHEET NUMBER

PROJECT

Copyright 2021, Hobbs + Black Associates, Inc.C

ALL RIGHTS RESERVED

H G F E D C B A

H G F E D C B A

Sheet Size - 24x36

DATE ISSUED

DRAWN BY

CHECKED BY

A u to d e s k D o c s /2

-3

M

S P

T ra in in g A c a d e m y A

D A

L if t P

H

-7

/2

-A

R C

H -M

S P

T ra in in g A c a d e m y A

D A

L if t P

H

-7

-2

.r v t

D-110

26-325

DEMOLITION

FLOOR PLANS

AND SECTION

A U

D

IT

O R

IU

M

A D

A L

IF

T

N C

A N

A L

R D

L A

N S

IN

G

M

I

M S

P T

R A

IN

IN

G A

C A

D E

M Y

SCALE - 1/4" = 1'-0"D-110 A-100

D1

ENLARGED DEMOLITION

FLOOR PLAN - LOWER

LEVEL

SCALE - 1/4" = 1'-0"D-110 A-100

D4

ENLARGED DEMOLITION

FLOOR PLAN - MAIN LEVEL

SCALE - 1/4" = 1'-0"D-110 D-110

G4 DEMOLITION SECTION

NORTH

SCALE - 1" = 80'-0"

KEY PLAN

UPUP

D-110

D4

Sim

D-110

D1

Sim

A-110

D1

Sim

A-110

G4

Sim

EXISTING

STORAGE

ROOM

EXISTING

ELECTRICAL

ROOM

EXISTING

STAIRWELL

CONSULTANT

SHEET TITLE

PROJECT NUMBER

SHEET NUMBER

PROJECT

Copyright 2021, Hobbs + Black Associates, Inc.C

ALL RIGHTS RESERVED

H G F E D C B A

H G F E D C B A

Sheet Size - 24x36

DATE ISSUED

DRAWN BY

CHECKED BY

A u to d e s k D o c s /2

-3

M

S P

T ra in in g A c a d e m y A

D A

L if t P

H

-7

/2

-A

R C

H -M

S P

T ra in in g A c a d e m y A

D A

L if t P

H

-7

-2

.r v t

A-100

26-325

FLOOR PLAN

A U

D

IT

O R

IU

M

A D

A L

IF

T

N C

A N

A L

R D

L A

N S

IN

G

M

I

M S

P T

R A

IN

IN

G A

C A

D E

M Y

NORTH

SCALE - 1/16" = 1'-0"

FLOOR PLAN

UP

DN

DN

DN

U PU P

C1

A-300

C1

A-300

EXISTING STAIRS TO REMAIN

NEW PLATFORM LIFT

RAMP PER

MANUFACTURES

STANDARD

F1

A-300

F1

A-300

INDICATES CMU

WALL BELOW STAIRS

EXISTING

CMU WALL

5'-1 1/2"

INDICATES STRINGER ABOVE

EXISTING

STORAGE

ROOM EXISTING

STAIRWELL

A-300

H1

H4

4'-2"

PLATFORM LIFT CALL STATION

RELOCATED

LIGHT FIXTURE

EXISTING LIGHT FIXTURE TO REMAIN

C1

A-300

C1

A-300

EXISTING STAIRS

NEW PLATFORM LIFT

F1

A-300

F1

A-300

V .I

.F

C L E A R

INDICATES CMU WALL

BELOWV.I.F.

5'-0" CLEAR

A-300

F4

5'-3"4'-5"8"

EXISTING

STAIRWELL

EXISTING

STORAGE

ROOM

EXISTING

STORAGE

ROOM

EXISTING

ELECTRICAL

ROOM

EXISTING WALL SCONCE

TO REMAIN - TYPICAL.

REINSTALL EXISTING

CARPET TILE REMOVED

DURING DEMOLITION.

ANY PENETRATIONS

FROM CONDUIT RUNS IN

EXISTING WALLS TO BE

SEALED TO MAINTAIN

ANY EXISTING FIRE

RATINGS.

TEMPORARY PARTITION

FROM FLOOR TO

UNDERSIDE OF CEILING

TEMPORARY

DOOR

AREA OF WORK

TEMPORARY CONSTRUCTION NOTES:

TEMPORARY WALL

• 3 5/8" METAL STUDS @ 2'-0" ON

CENTER.

• 5/8" GYPSUM BOARD (ONE SIDE)

TEMPORARY DOOR AND FRAME

• PROVIDE WOOD OR METAL DOOR

WITH SELF CLOSING HINGES AND

LATCH TO MINIMIZE DUST AND

NOISE DURING DEMOLITION AND

CONSTRUCTION OPERATIONS.

CONSULTANT

SHEET TITLE

PROJECT NUMBER

SHEET NUMBER

PROJECT

Copyright 2021, Hobbs + Black Associates, Inc.C

ALL RIGHTS RESERVED

H G F E D C B A

H G F E D C B A

Sheet Size - 24x36

DATE ISSUED

DRAWN BY

CHECKED BY

A u to d e s k D o c s /2

-3

M

S P

T ra in in g A c a d e m y A

D A

L if t P

H

-7

/2

-A

R C

H -M

S P

T ra in in g A c a d e m y A

D A

L if t P

H

-7

-2

.r v t

A-110

26-325

ENLARGED

LOWER LEVEL

FLOOR PLAN

AND MAIN

LEVEL FLOOR

PLAN

A U

D

IT

O R

IU

M

A D

A L

IF

T

N C

A N

A L

R D

L A

N S

IN

G

M

I

M S

P T

R A

IN

IN

G A

C A

D E

M Y

SCALE - 1/4" = 1'-0"A-110 A-100

G4

ENLARGED FLOOR PLAN

LOWER LEVEL

SCALE - 1/4" = 1'-0"A-110 A-100

D1

ENLARGED FLOOR PLAN

MAIN LEVEL

NORTH

SCALE - 1" = 80'-0"

KEY PLAN

NORTH

NORTH

LEVEL 1

ELEV = 100' - 0"

B.O. CEILING

ELEV = 107' - 4"

LOWER LEVEL

ELEV = 88' - 8"

LEVEL .5

ELEV = 96' - 6"

F1

A-300

F1

A-300

NEW PLATFORM

LIFT

EXISTING GYPSUM

BOARD CEILING

EXISTING

STRINGER AND

GUARD RAIL TO

REMAIN

EXISTING

STRINGER AND

GUARD RAIL TO

REMAIN

EXISTING CMU

WALL

LEVEL 1

ELEV = 100' - 0"

B.O. CEILING

ELEV = 107' - 4"

LOWER LEVEL

ELEV = 88' - 8"

C1

A-300

C1

A-300

LEVEL .5

ELEV = 96' - 6"

RAMP PER MANUFACTURES STANDARDS

EXISTING STRINGER GUARD RAIL TO REMAIN

NEW PLATFORM LIFT

EXISTING GYPSUM BOARD CEILING

EXISTING GYPSUM BOARD CEILING

A-300

C4

EXISTING CMU

WALL BEYOND

EXISTING CMU WALL BEYOND

EXISTING DOOR TO REMAIN

NEW WIRE MOLD

EQ EQ

ELECTRICAL DISCONNECT

(COORDINATE LOCATION WITH

ELECTRICAL REQUIREMENTS)

LEVEL 1

ELEV = 100' - 0"

EXISTING PIPE

GUARDRAIL TO

REMAIN

EXISTING CHANNEL

STRINGER TO REMAIN

EXISTING PIPE

GUARDRAIL TO

REMAIN

EXISTING CHANNEL

STRINGER TO REMAIN

NEW PIPE POST TO

MATCH EXISTING

8"4'-5"5'-3"

SAW CUT TOP

PORTION OF CHANNEL

STRINGER

REMOVE

PORTION OF

PIPE GUARDRAIL

NEW LIFT

DOOR

NEW LIFT CONTROLS

MOUNTED IN DOOR FRAME

1"

C4

A-300

1/4" WELD PLATE CAP

1/4" WELD

PLATE CAP

NOTE

PAINT EXISTING AND NEW HANDRAIL AND

CHANNEL STRINGER AT TOP LANDING TO MATCH

EXISTING HANDRAIL COLOR AND GLOSS.

LEVEL 1

ELEV = 100' - 0"

1"

1"

1 1/2"

REMOVE PORTION OF

PIPE HANDRAIL

SAW CUT AND REMOVE

PORTION OF

EXISTING STEEL

CHANNEL STRINGER

EXISTING CONCRETE

SLAB TO REMAIN

EXISTING BULK HEAD

TO REMAIN

1/4" WELD PLATE CAP

1/4" WELD

PLATE CAP

LOWER LEVEL

ELEV = 88' - 8"

4'-8"

PLATFORM LIFT CALL

STATION

EXISTING CMU

EXISTING BASE TO

REMAIN

WIRE MOLD - SEE

ELECTRICAL

LOWER LEVEL

ELEV = 88' - 8"

EXISTING STAIR

TO REMAIN

BRACE PLATFORM

LIFT TO EXISTING

WALL AS REQUIRED BY

MANUFACTURER.

FACE OF EXISTING

CMU WALL

NEW PLATFORM LIFT

CONSULTANT

SHEET TITLE

PROJECT NUMBER

SHEET NUMBER

PROJECT

Copyright 2021, Hobbs + Black Associates, Inc.C

ALL RIGHTS RESERVED

H G F E D C B A

H G F E D C B A

Sheet Size - 24x36

DATE ISSUED

DRAWN BY

CHECKED BY

A u to d e s k D o c s /2

-3

M

S P

T ra in in g A c a d e m y A

D A

L if t P

H

-7

/2

-A

R C

H -M

S P

T ra in in g A c a d e m y A

D A

L if t P

H

-7

-2

.r v t

A-300

26-325

BUILDING

SECTIONS

A U

D

IT

O R

IU

M

A D

A L

IF

T

N C

A N

A L

R D

L A

N S

IN

G

M

I

M S

P T

R A

IN

IN

G A

C A

D E

M Y

SCALE - 1/4" = 1'-0"A-300 A-110

C1 SECTION

SCALE - 1/4" = 1'-0"A-300 A-110

F1 SECTION

SCALE - 3/4" = 1'-0"A-300 A-110

F4 RAILING ELEVATION

SCALE - 3/4" = 1'-0"A-300 A-300

C4 RAILING DETAIL

SCALE - 1/4" = 1'-0"A-300 A-110

H4

LOWER LEVEL EAST

ELEVATION

SCALE - 1/4" = 1'-0"A-300 A-110

H1

LOWER LEVEL WEST

ELEVATION

TS

FS

DC

AV

V

A

V

J

SD

DOOR CONTROLS, COORDINATE WITH SECURITY, AUTO AND MANUAL CONTROLS

FR

J

FD

F

HD

DD

OS OS

PC

OS

DO ADA DOOR CONTROL OPENER, COORDINATE WITH DOOR REQUIREMENTS

SPEAKER FOR PA SYSTEM.S

1LN1-1

BRANCH CIRCUIT HOMERUN. PROVIDE PHASE, NEUTRAL AND GROUND

CONDUCTORS FOR EACH INDICATED CIRCUIT OR MULTI WIRE BRANCH

AS REQUIRED. PROVIDE SWITCH LEGS FOR SWITCH CIRCUITING AS

REQUIRED. PROVIDE EQUIPMENT GROUND WIRE IN ALL BRANCH CIRCUIT

RACEWAYS/CIRCUITS. PROVIDE SEPARATE ISOLATED GROUND WIRE TO

ALL ISOLATED GROUND DEVICES.

PANEL NAME

POLE NUMBERS

B

CIRCUIT DESIGNATIONS

LIGHTING

EXISTING ELECTRICAL ITEM TO BE REMOVED, UON.

EXISTING ELECTRICAL ITEM TO REMAIN

EXISTING ELECTRICAL ITEM TO BE REMOVED AND PROVIDED WITH A

BLANK COVERPLATE

EXISTING ELECTRICAL CIRCUIT TO BE REMOVED SHOWN ONLY WHERE

CLARIFICATION BETWEEN EXISTING TO REMAIN AND REMOVED ITEMS IS

REQUIRED

SIZE

CONDUIT

MAX QUANTITY OF

CONDUCTORS PER CONDUIT

CONDUCTOR SIZE

12 10 8

1 INCH 9 TO 13 7 TO 11 4 TO 5

CONDUIT RISER UP

CONDUIT RISER DOWN

INDICATES CIRCUIT CONTINUATION

STUB INTO ACCESSIBLE CORRIDOR CEILING SPACE UNLESS OTHERWISE NOTED

CONDUIT SEAL FITTING FOR HAZARDOUS AREAS

CONDUIT SLEEVE

CAP END OF CONDUIT

CABLE OR CORD CONNECTED

GENERAL NOTES

NOTE A: OUTLETS IN FINISHED OR SHELL SPACES SHALL BE MOUNTED AT +18" UON.

NOTE B: OUTLETS LOCATED AT COUNTERS SHALL BE LOCATED 18"AFF IN KNEE SPACE IF

PROVIDED OR 4" ABOVE COUNTER OR BACK SPLASH AS APPLICABLE IF NO KNEE SPACE IS

PROVIDED UON.

NOTE C: WHERE ASTERISK (*) IS INDICATED NEXT TO OUTLET AT WORK

COUNTER, OUTLET SHALL BE LOCATED ABOVE COUNTER RATHER THAN IN KNEE

SPACE.

STANDARD TELECOMMUNICATIONS OUTLET - PROVIDE EXTRA DEEP DOUBLE GANG

BOX WITH SINGLE GANG MUD RING AND (1) 1" CONDUIT TO ABOVE

FINISHED CEILING, MOUNTED AT 18" AFF, UON. PROVIDE PLASTIC BUSHING AT THE

ENDS OF THE CONDUITS. DATA DEVICES AND WIRING PROVIDED BY OTHERS, UON.

THE FOLLOWING SUBSCRIPTS ARE USED TO INDICATE THE

VARIOUS (NON-STANDARD) TYPES OF OUTLETS

B BLANK (ROUGH-IN TO ACCESSABLE CEILING SPACE) WITH BLANK COVERPLATE

F FIBER

AMPERES

AMP FUSE OR AMP FRAME

AVAILABLE FAULT CURRENT (SYMMETRICAL)

ABOVE FINISHED FLOOR

AMPERE INTERRUPTING CAPACITY

ASYMMETRICAL

AMP TRIP

AUTOMATIC TRANSFER SWITCH

AMERICAN WIRE GAUGE

CONDUIT

CAPACITY OR CAPACITOR

COMMUNITY ANTENNA TELEVISION

CIRCUIT BREAKER

CLOSED CIRCUIT TELEVISION

CIRCUIT

CONDUIT ONLY

CONNECT OR CONNECTION

COPPER

DISCONNECT

DOUBLE POLE SINGLE THROW

ELECTRIC WATER COOLER (COORDINATE ACCESSIBILITY OF GFCI)

ELECTRIC OR ELECTRICAL

ELEVATION OR ELEVATOR

EMERGENCY

ELECTRICAL METAL TUBING

FIXTURE

FULL LOAD AMPERES

FLUORESCENTFLUOR.

FLA

FIXT.

EMT

EMERG, EM

ELEV

ELEC

EWC

DPST

DISC.

CU

CONN.

C.O.

CKT ,CCT

CCTV

CB

CATV

CAP.

C

AWG

ATS

AT

ASYM.

AIC.

A.F.F.

AFC

AF

A, AMP

AMMETERAM.

EC ELECTRICAL CONTRACTOR

HIGH INTENSITY DISCHARGE

HAND-OFF-AUTO

HORSEPOWER

HIGH PRESSURE SODIUM

HERTZ

INTERMEDIATE METAL CONDUIT

ISOLATED GROUND

INCANDESCENT

KILOVOLT AMPERES

KILOWATT

KILOWATT HOUR

LIGHTING

LOW VOLTAGE

MASTER ANTENNA TELEVISION

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MANHOLE, METAL HALIDE OR MOUNTING HEIGHT

MAIN LUGS ONLY

NORMALLY CLOSED

NON FUSIBLE

NORMALLY OPEN

NOT TO SCALE

OVERLOADS

POLE

PULLBOX

PHASE

PANEL

PAIR

POWER

RECEPTACLE

RIGID GALVANIZED STEELRGS

REC

PWR.

PR

PNL

PB

P

OL

NTS

N.O.

NF

N.C.

MLO

MH

MCC

MCB

MATV

LV

LTG

KWH

KW

KVA

KAIC

INCAND.

I.G.

IMC

HZ.

HPS

HP

HOA

HID

GRC,GCR

GFCI

GFI

GALVANIZED RIGID CONDUIT

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT INTERRUPTER

GROUND

JUNCTION BOXJB

NATIONAL ELECTRICAL CODEN.E.C.

N.I.C. NOT IN CONTRACT

POLYVINYL CHLORIDEPVC

GRD,GND,G

THOUSAND AMPERE INTERRUPTING CAPACITY

TELEPHONE

TRANSFORMER

TELEPHONE TERMINAL BACKBOARD

TELEVISION

TYPICAL

UNDERGROUND

UNLESS OTHERWISE NOTED

VOLT

VOLT AMPERES

VOLTAGE DROP

VOLT METER

WATTS OR WIRE

WITH

WITHOUT

WEATHERPROOFWP

W/O W/ W

VM

VD

VA

V

UON

UG

TYP

TV

TTB

XFMR

TEL

SOL

SPDT

SPKR

SPST

SOLENOID

SINGLE POLE DOUBLE THROW

SPEAKER

SINGLE POLE SINGLE THROW

SW.

SWBD

SYM

SWITCH

SWITCHBOARD

SYMMETRICAL

EXPLOSION PROOFXP

ABBREVIATIONS

EMERGENCY POWER OFFEPO

DURESS ALARM

DOOR BELLDB

DA

GEN GENERATOR

GENERAL

MOUNTING HEIGHTS TO BE AS INDICATED, UON. MOUNTING HEIGHTS ARE TO

CENTER OF DEVICE FROM FINISHED FLOOR OR GRADE, UON. SEE SPECIFICATION

DIV 26 FOR ADDITIONAL REQUIREMENTS.

KEY NOTE REFERENCE SYMBOL. DENOTES "SEE KEY NOTE NO. 2"

FOOT ON DEVICE INDICATES WALL MOUNTED

POWER AND DIAGRAMS

DEMOLITION AND REMODEL

SEE SPECIFICATONS FOR LIMITATIONS

ON QUANTITY OF CURRENT CARRYING

CONDUCTORS PER CONDUIT

TELECOMMUNICATION

PH OR ∅

1 TO 35 TO 65 TO 83/4 INCH

NOTE A: UPPER CASE ALPHANUMERIC SUBSCRIPT DENOTES FIXTURE TYPE. SEE

SCHEDULE(S)

NOTE B: LOWER CASE LETTER SUBSCRIPT PROVIDED ADJACENT TO SWITCHING

DEVICE AND ASSOCIATED LIGHT FIXTURE(S) WHERE REQUIRED FOR CLARIFICATION.

CEILING LIGHT OUTLET WITH FIXTURE CONNECTED TO NORMAL SOURCE

DIRECTIONAL AIMED FIXTURE AIM IN DIRECTION OF ARROW

WALL BRACKET LIGHT OUTLET WITH FIXTURE CONNECTED TO NORMAL SOURCE

RECESSED LIGHT OUTLET WITH FIXTURE CONNECTED TO NORMAL SOURCE

WALL BRACKET LIGHT OUTLET WITH FIXTURE CONNECTED TO NORMAL SOURCE

UNDERCABINET/ COUNTER LIGHT OUTLET OR STRIP LIGHT OUTLET WITH

FIXTURE CONNECTED TO NORMAL SOURCE

EXIT LIGHT OUTLET WITH FIXTURE - SHADING INDICATES LOCATION OF FACE(S).

ARROWS INDICATE DIRECTIONAL ARROWS WHERE REQUIRED. WALL MOUNTED

SIGNS AT +90" CENTERED ABOVE DOOR WHERE APPLICABLE

EMERGENCY LIGHT FIXTURE WITH INTEGRAL BATTERY SOURCE AND HEADS

TRACK LIGHT OUTLET WITH FIXTURE. TYPE INDICATED, QUANTITY AND LENGTH

AS SHOWN OR SCHEDULED

LIGHTING STANDARD WITH POST-TOP FIXTURE

CEILING LIGHT OUTLET WITH FIXTURE CONNECTED TO EMERGENCY SOURCE

WALL SCONCE LIGHT OUTLET WITH FIXTURE CONNECTED TO EMERGENCY

SOURCE

LIGHT OUTLET WITH FIXTURE CONNECTED TO EMERGENCY SOURCE

LINEAR WALL LIGHT OUTLET WITH FIXTURE CONNECTED TO EMERGENCY

SOURCE

SURFACE / STRIP LIGHT OUTLET WITH FIXTURE CONNECTED TO EMERGENCY

SOURCE

NO SUBSCRIPT - SINGLE POLE

TE

L

LV

OS

XP

DOUBLE POLE

THREE WAY

FOUR WAY

MANUAL STARTER WITH THERMAL ELEMENT

PILOT LIGHT

LOW VOLTAGE/DIGITAL SWITCH

WALL SWITCH OCCUPANCY SENSOR, DUAL TECHNOLOGY.

EXPLOSION PROOF

DIMMER, COMPATIBLE WITH FIXTURE.D

M MOTOR RATED

SWITCH AT +48" U.O.N.

THE FOLLOWING SUBSCRIPTS ARE USED TO INDICATE VARIOUS TYPES

OF SWITCHES.

EXTERIOR PHOTOCELL. ON/OFF WITH ADJUSTABLE SET-POINT.

TIME CLOCK AT +48"

CEILING / DIRECTIONAL / DIRECTIONAL WALL MOUNTED

OCCUPANCY SENSOR DUAL TECHNOLOGY, WITH

REQUIRED POWER PACKS.

LIGHTING STANDARD POLE FIXTURE, PROVIDE QUANTITY OF HEADS

AND ORIENTATION AS INDICATED

BOLLARD FIXTURE

PENDANT LIGHT FIXTURE CONNECTED TO NORMAL SOURCE

PENDANT LIGHT FIXTURE CONNECTED TO EMERGENCY

SOURCE

LINEAR PENDANT/SUSPENDED LIGHT FIXTURE CONNECTED TO NORMAL SOURCE

LINEAR PENDANT/SUSPENDED LIGHT FIXTURE CONNECTED TO EMERGENCY

SOURCE

WP WEATHERPROOF, EXTRA DUTY, WITH STEEL IN-USE COVER.

CL CLOCK MOUNTED AT +84", REGRESSED SINGLE RECEPTACLE, WITH CLOCK HANGER.

A.

B.

C.

D.

E.

NOTE:

OUTLETS IN FINISHED OR SHELL SPACES SHALL BE MOUNTED AT +18" UON.

OUTLETS IN GARAGE, MECHANICAL, AND ELECTRICAL SPACES SHALL BE

MOUNTED AT 48" UON.

OUTLETS SHALL BE TAMPER PROOF, WHERE REQUIRED PER CODE.

OUTLETS SHALL HAVE AFCI PROTECTION, WHERE REQUIRED PER CODE.

OUTLETS SHALL HAVE GFCI PROTECTION, WHERE REQUIRED PER CODE.

THE FOLLOWING SUBSCRIPTS ARE USED TO INDICATE DIFFERENT TYPES

OF RECEPTACLES

20A, 125V, 2 POLE, 3 WIRE GROUNDING DUPLEX RECEPTACLE, NEMA 5-20R

20A, 125V, 2 POLE, 3 WIRE GROUNDING SINGLE RECEPTACLE, NEMA 5-20R

20A, 125V, 2 POLE, 3 WIRE GROUNDING DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R

PIGTAIL TO SWITCH DENOTES TOP HALF OF RECEPTACLE SWITCHED.

SURFACE RECEPTACLE STRIP. TYPE AND LENGTH AS INDICATED.

208 VOLT PANELBOARD AT +72" TO TOP

480 VOLT PANELBOARD AT +72" TO TOP

CABLE TRAY OR WIREWAY

CIRCUIT BREAKER. AMP/POLES AS INDICATED

FUSE. SIZE AS INDICATED

FUSIBLE SWITCH. AMP/POLES/FUSE SIZE AS INDICATED

AUTOMATIC TRANSFER SWITCH +72" TO TOP OR FLOOR MOUNTED.

DISCONNECT STABS FOR DRAWOUT TYPE EQUIPMENT

TRANSFORMER

GROUND CONNECTION

MOTOR CONNECTION, HP AS INDICATED

GENERATOR

START-STOP PUSHBUTTON STATION AT +48"

GROUND BUS ON STANDOFFS

CONTROL PANEL:

EQUIPMENT OR TERMINAL CABINET AT +72" TO TOP

POWER SUPPLY

PUSHBUTTON STATION AT +48"

SAFETY SWITCH AT +54". CHARACTERISTICS AS INDICATED BY FRAME/POLES.

MAGNETIC MOTOR STARTER AT +54". CHARACTERISTICS AS INDICATED BY

FRAME SIZE/POLES/NEMA SIZE.

COMBINATION MAGNETIC MOTOR STARTER WITH DISCONNECT AT +54".

CHARACTERISTICS AS INDICATED BY FRAME/FUSE/POLES/NEMA SIZE

ADJUSTABLE FREQUENCY DRIVE WITH INTEGRAL CIRCUIT BREAKER DISCONNECT

MAGNETIC CONTACTOR AT +54". AMPS/POLES/CONTACT VOLTS/ COIL VOLTS AS

INDICATED.

SEPARATELY MOUNTED, ENCLOSED MOLDED CASE CIRCUIT BREAKER AT +48".

FLUSH MOUNTED IN FINISHED AREAS. AMP/POLES AS INDICATED.

FUSED SAFETY SWITCH AT +54". CHARACTERISTICS AS INDICATED BY

FRAME/FUSESIZE/POLES.

J

S

TC

G

AFD

PS

FACP

FAA

FIXED VIDEO SURVEILANCE CAMERA

FIRE DETECTION AND ALARM

SECURITY

MANUAL STATION AT +48"

VISUAL NOTIFICATION APPLICANCE

WALL MOUNTED AUDIBLE NOTIFICATION APPLIANCE

ELECTROMECHANICAL DOOR RELEASE. COORDINATE WITH DOOR MANUFACTURER.

SPRINKLER OR STANDPIPE FLOW ALARM SWITCH CONNECTION

VALVE TAMPER SWITCH

AIR PRESSURE MONITOR SWITCH FOR PRE-ACTION OR DRY PIPE SPRINKLER

SYSTEM

SMOKE DETECTOR - PHOTO ELECTRIC AREA BEAM

AUTOMATIC HEAT DETECTOR

CONTROL PANEL AT +72" TO TOP

FIRE ALARM ANNUNCIATOR PANEL AT +72" TO TOP

FIRE SUPPRESSION SYSTEM ABORT SWITCH STATION AT +48"

DUCT SMOKE DETECTOR

THE FOLLOWING SUBSCRIPTS ARE USED TO INDICATE THE VARIOUS TYPE

OF HEAT DETECTORS

NO SUBSCRIPT - FIXED TEMPERATURE (155 DEGREE U.O.N.)

R/F COMBINATION RATE OF RISE FIXED TEMPERATURE (135 DEGREE U.O.N.)

XP EXPLOSION PROOF, FIXED TEMPERATURE (135 DEGREE U.O.N.) CLASS 1,

GROUP C

NOTE: WALL MOUNT VISUAL AND COMBINATION AUDIO/VISUAL NOTIFICATION

APPLIANCES AT +80" AFF TO BOTTOM OF FACE PLATE U.O.N.

WALL MOUNTED COMBINATION AUDIBLE/VISUAL NOTIFICATION APPLIANCE

CEILING MOUNTED VISUAL NOTIFICATION APPLIANCE

CEILING MOUNTED COMBINATION AUDIBLE/VISUAL NOTIFICATION APPLIANCE

DOS WALL SWITCH OCCUPANCY SENSOR W/ DIMMER, DUAL TECHNOLOGY.

DH DAYLIGHT HARVESTING SENSOR. ANALOG 0-10V OUTPUT WITH

INTEGRAL MOTION SENSOR.

H HORIZONTAL MOUNTING

U DUAL USB INCLUDED WITH RECEPTACLE TYPE SHOWN.

TYPICAL SYMBOLOGY:

250V, 2 POLE, 3 WIRE GROUNDING SINGLE RECEPTACLE, SIZE AND TYPE AS NOTED.

RECEPTACLES WITH GROUND FAULT CIRCUIT INTERRUPTOR

RECEPTACLES MOUNTED 4" ABOVE COUNTER OR BACK SPLASH AS APPLICABLE, UON.

RECEPTACLES WITH GFCI AND MOUNTED 4" ABOVE COUNTER OR BACK SPLASH AS

APPLICABLE.

CEILING MOUNTED RECEPTACLE. TYPE AS INDICATED ABOVE.

CEILING MOUNTED GFCI RECEPTACLES, TYPE AS INDICATED ABOVE.

FLUSH FLOOR MOUNTED RECEPTACLE, TYPE AS INDICATED ABOVE.

COMBINATION POWER/ COMMUNICATIONS FLOOR BOX, TYPE AND COMMUNICATIONS

DEVICE AS INDICATED.

FLUSH FLOOR MOUNTED RECEPTACLE, GFCI, TYPE AS INDICATED ABOVE.

PEDESTAL MOUNTED RECEPTACLE, TYPE AS INDICATED ABOVE.

SPECIAL PURPOSE RECEPTACLE. SUBSCRIPT DENOTES NEMA TYPE.

JUNCTION BOX. 4" SQUARE, UON. WALL AND CEILING MOUNTED.

J JUNCTION BOX. 4" SQUARE, UON. WALL AND CEILING MOUNTED.

CB

DOOR POSITION SWITCH

CONNECTION TO ELECTRIC OR PNEUMATIC DOOR LOCK

CR CARD READER AT +48"

FLOOR MOUNTED.

CEILING MOUNTED.

MOUNTED 48" AFF, UON.

MOUNTED 72" AFF, UON.

TELEPHONE AT 44" AFF, UON.T

TELEVISION, MOUNTED AT NOTED HEIGHT.TV

## THE FIRST NUMBER INDICATES THE NUMBER OF CAT6 CABLES.

THE SECOND NUMBER INDICATES THE TO QUANTITY OF JACK LOCATIONS.

AV

A CEILING MOUNTED AUDIBLE NOTIFICATION APPLIANCE

DH MAGNETIC DOOR HOLDER. COORDINATE MOUNTING HEIGHT WITH DOOR

MANUFACTURER.

FIRE/ SMOKE DAMPER

CO COMBINATION CARBON MONOXIDE / SMOKE DETECTOR WITH ANNUNCIATION

SEE PLANS AND NOTES FOR DEVICES INTEND FOR REUSE AND / OR REPURPOSING.

F

FUSEDf

CLOCK - SEE SPECIFICATIONS FOR REQUIREMENTS.C

WIRELESS DEVICE

M ELECTRIC METER

GENERAL NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE

LATEST ACCEPTED EDITION OF THE NATIONAL ELECTRICAL

CODE, NEC, AND ALL STATE AND LOCAL CODES.

COORDINATE THE INSTALLATION OF ALL ELECTRICAL

EQUIPMENT AND CONNECTIONS WITH ARCHITECTURAL,

STRUCTURAL, MECHANICAL AND EQUIPMENT DRAWINGS.

ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ALL

POWER, CONDUITS, CABLETRAY, AND OTHER COMPONENTS AS

SHOWN ON THE EQUIPMENT PROVIDER DRAWINGS FOR

INSTALLATION OF SYSTEM.

"BACK TO BACK" OR THROUGH THE WALL BOXES SHALL NOT BE

USED.

INSTALL HANDLE LOCK-ON, ON ALL CIRCUIT BREAKERS

CONTROLLING NIGHT LIGHT, EMERGENCY LIGHT AND EXIT

LIGHT CIRCUITS.

ALL RECEPTACLES SHALL BE HARD USE, SPECIFICATION

GRADE.

PROVIDE TAMPER RESISTANT RECEPTACLES WHERE

REQUIRED BY APPLICABLE CODES.

RECEPTACLES INDICATED AS GROUND FAULT CIRCUIT

INTERRUPTER TYPE SHALL BE MOUNTED IN AN ACCESIBLE

LOCATION, PER CODE OR PROVIDED WITH A GFCI BREAKER.

ALL CONDUCTORS SHALL BE COPPER. ALUMINUM WIRES SHALL

NOT BE USED.

MINIMUM CONDUIT SIZE SHALL BE 1/2" FOR POWER FEEDS AND

1" FOR DATA FEEDS.

FINAL CONNECTION TO ITEMS SUBJECT TO VIBRATION SHALL

BE MADE WITH LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT.

120/208VAC CIRCUIT WIRING FOR ANY ROOM OR AREA MAY BE

GROUPED INTO RACEWAYS UNLESS SEPARATE RACEWAYS ARE

REQUIRED BY THE NEC. COMPLY WITH NEC REQUIREMENTS

FOR CONDUCTOR DERATING.

PROVIDE EQUIPMENT GROUNDING CONDUCTORS FOR ALL

POWER AND LIGHTING CIRCUITS.

ALL LIGHTING AND POWER CONDUCTORS SHALL BE 12 AWG

MINIMUM. ALL CONTROL CONDUCTORS SHALL BE

14 AWG MINIMUM OR AS SPECIFIED BY MANUFACTURER.

DEDICATED NEUTRAL SHALL BE PROVIDED FOR ALL CIRCUITS.

SHARED NEUTRALS ARE NOT ALLOWED.

BASIS OF DESIGN IS FOR A COMPLETE ELECTRICAL SYSTEM,

INSTALLED PER CODE REQUIREMENTS.

17. PROVIDE AN UNSWITCHED HOT TO ALL EMERGENCY BATTERY

PACKS, LIGHTING INVERTERS AND EMERGENCY LIGHTING UNITS

AHEAD OF ANY LIGHTING CONTROLS FROM THE BRANCH CIRCUIT

SERVING LIGHTING IN THE SURROUNDING AREA.

GENERAL DEMO NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

DEMOLITION NOTES ARE BASED UPON FIELD OBSERVATION AND

EXISTING RECORD DOCUMENTS. THE ELECTRICAL CONTRACTOR

SHALL VERIFY EXACT CONDITIONS AT SITE AND REPORT

DISCREPANCIES TO THE ARCHITECT/ENGINEER BEFORE DISTURBING

THE INSTALLATION.

THE SCOPE OF REQUIRED DEMOLITION IS NOT LIMITED TO ITEMS OR

WORK INDICATED ON THE CONTRACT DOCUMENTS. THE ELECTRICAL

CONTRACTOR SHALL DETERMINE THE NATURE AND EXTENT OF WORK

REQUIRED. THE CONTRACTOR ACCEPTS EXISTING SITE CONDITIONS

AT THE START OF DEMOLITION.

WHERE ELECTRICAL COMPONENT ARE SHOWN TO BE REMOVED, THE

ELECTRICAL CONTRACTOR SHALL RECONNECT REMAINING

COMPONENTS TO EXISTING CIRCUIT(S).

WHERE THE DRAWINGS SHOW DEVICES OR EQUIPMENT TO BE

PERMANENTLY REMOVED, THE ELECTRICAL CONTRACTOR SHALL

REMOVE CONDUCTORS BACK TO SOURCE. TURN BREAKER 'OFF' AND

LABEL THE BREAKER AS 'SPARE' ON NEWLY PRINTED PANEL

DIRECTORY.

THE ELECTRICAL CONTRACTOR SHALL REMOVE ALL ABANDONED

CONDUIT. THE ELECTRICAL CONTRACTOR SHALL CUT CONDUIT FLUSH

WITH WALLS AND FLOORS, UON. PATCH ALL SURFACES AND PROVIDE

FIRESTOP WHERE REQUIRED.

THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE

REPAIR OF DAMAGE TO ALL ADJACENT CONSTRUCTION AND FINISHES.

REPAIRS SHALL BE MADE TO RETURN SPACE TO ORIGINAL CONDITION

PRIOR TO COMPLETION OF PROJECT.

EQUIPMENT AND DEVICES SHOWN AS DASHED ON THE DRAWING ARE

TO BE REMOVED.

THE ELECTRICAL CONTRACTOR SHALL DISCONNECT ALL ELECTRICAL

SYSTEMS IN WALLS, FLOORS AND CEILINGS SCHEDULED FOR

REMOVAL, INCLUDING SPECIAL SYSTEMS.

THE ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY WIRING

AND CONNECTIONS TO MAINTAIN OPERATION OF EXISTING SYSTEMS

DURING CONSTRUCTION. CONDITIONS SHALL BE RETURNED TO

NORMAL AT THE CLOSE OF THE PROJECT.

CONTRACTOR SHALL MAINTAIN ALL POWER AND DATA CONDUIT AND

WIRING SERVING AREAS NOT INCLUDED IN THE SCOPE OF WORK,

UON. NOTIFY ARCHITECT/ ENGINEER IF THESE DEVICES WILL IMPEDE

UPON SCOPE OF WORK DURING RENOVATION TO RECEIVED

DIRECTION ON RESOLUTION.

THE ELECTRICAL CONTRACTOR SHALL PROVIDE BLANK COVERS ON

ALL JUNCTION BOXES WHERE DEVICE HAS BEEN REMOVED AND THE

JUNCTION BOX IS TO REMAIN FOR FUTURE USE.

THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE DISPOSAL

OF ALL LAMPS AS REQUIRED AND DIRECTED IN THE LATEST STATE

LAWS.

THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE DISPOSAL

OF ALL EQUIPMENT AND DEVICES REMOVED.

ALL DISRUPTIONS OF SERVICE SHALL BE COORDINATED AND

APPROVED BY OWNER.

CONSULTANT

SHEET TITLE

PROJECT NUMBER

SHEET NUMBER

PROJECT

Copyright 2021, Hobbs + Black Associates, Inc.C

ALL RIGHTS RESERVED

H G F E D C B A

H G F E D C B A

Sheet Size - 24x36

DATE ISSUED

DRAWN BY

CHECKED BY

Au to de sk

D oc s:

//2

6-

M

SP

T ra in in g

Ac ad em y

AD

A

Li ft

PH

0-

0/

M

SP

T ra in in g Ac ad em y Au di to riu m

L ift

Ph as e

0-

- M

EP

R

.rv t

E-100

26-325

ELECTRICAL

COVER SHEET

AU

D

IT

O

R

IU

M A

D A

LI

FT

N . C

AN

AL

R D

LA

N

SI

N G

, M I 4

BTT

DDA

M

SP

T R

AI

N

IN

G

AC

AD

EM

Y

FAX: 517.487.2544

PHONE: 517.487.2511

LANSING, MI 48917

544 CHERBOURG DRIVE

MATRIX PROJECT: 260462.00

WEB: www.matrixceinc.com

MatrixMatrix

CONSULTING ENGINEERS, INC

RCH

SECTION 26 0000SECTION 26 0000

1. GENERAL ELECTRIC REQUIREMENTS

PART 1 - GENERAL

1.01 DESCRIPTION OF WORK

A. WORK INCLUDES ALL ELECTRICAL ITEMS AND SYSTEMS SHOWN ON THE CONTRACT

DRAWINGS AND SPECIFIED HEREIN.

B. UNLESS SPECIFICALLY DIMENSIONED, THE WORK SHOWN ON THE DRAWINGS IS

DIAGRAMMATIC AND IS INTENDED ONLY TO SHOW GENERAL ARRANGEMENT.

CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF LOCATION, INCLUDING

ELEVATIONS, BY COORDINATION WITH THE CONSTRUCTION MANAGER AND OTHER

TRADES AS WELL AS ALL THE DRAWINGS, PARTICULARLY ARCHITECTURAL.

C. INCLUDE IN THE WORK ALL ACCESSORIES AND DEVICES NECESSARY FOR THE

INTENDED OPERATION OF ANY SYSTEM, WHETHER OR NOT SPECIFICALLY SHOWN OR

SPECIFIED.

1.02 STANDARDS OF QUALITY

A. THE SPECIFICATIONS ESTABLISH THE STANDARD OF QUALITY REQUIRED, EITHER

BY DESCRIPTION OR BY REFERENCE TO BRAND NAME, NAME OF MANUFACTURERS OR

MANUFACTURER'S MODEL NUMBER.

B. WHERE ONE PRODUCT ONLY IS SPECIFICALLY IDENTIFIED BY NAME OF

MANUFACTURER'S MODEL NUMBER, THE CONTRACTOR SHALL BASE HIS BID ON THE USE

OF THE NAME PRODUCT. WHERE MULTIPLE NAMES ARE USED THE CONTRACTOR SHALL

BASE HIS BID ON THE USE OF ANY OF THOSE PRODUCTS NAMED.

C. WHEN EQUIPMENT AND/OR MATERIALS ARE PROPOSED TO BE PURCHASED FROM A

MANUFACTURER OTHER THAN THOSE SPECIFIED, THE CONTRACTOR SHALL PROVIDE

COMPLETE DATA ADEQUATE FOR THE ENGINEER'S EVALUATION OF THE PROPOSED

SUBSTITUTION.

D. WHEN THE EQUIPMENT OTHER THAN THAT SPECIFIED IS USED, THE CONTRACTOR

SHALL BE RESPONSIBLE FOR ANY EXTRA COST OF REQUIRED REVISIONS SUCH AS

STRUCTURAL STEEL, CONCRETE, ELECTRICAL, PIPING, ETC. SUCH ADDITIONAL COSTS

SHALL BE IDENTIFIED AT THE TIME SUCH SUBSTITUTIONS ARE PROPOSED.

1.03 SUMMARY

A. THIS SECTION INCLUDES GENERAL ADMINISTRATIVE AND PROCEDURAL

REQUIREMENTS FOR ELECTRICAL INSTALLATIONS.

1. SUBMITTALS.

2. MAINTENANCE MANUALS.

3. ROUGH-INS.

4. ELECTRICAL INSTALLATIONS.

1.04 SUBMITTALS

A. THE CONTRACTOR SHALL REVIEW, APPROVE AND SUBMIT SHOP DRAWINGS WITH

PROMPTNESS SO AS TO CAUSE NO DELAY IN HIS WORK OR IN THAT OF OTHERS. NO

SUBMISSIONS WILL BE ACCEPTED BY THE ENGINEER WITHOUT THE SIGNED REVIEW AND

APPROVAL OF THE CONTRACTOR.

B. THE CONTRACTOR SHALL CHECK AND VERIFY PERTINENT FIELD MEASUREMENTS,

QUANTITIES OF EQUIPMENT AND MATERIALS REQUIRED.

C. SUBMITTALS SHALL BE IDENTIFIED BY REFERENCE TO THE DRAWINGS, SECTIONS

OF SPECIFICATIONS OR EQUIPMENT SYMBOLS TO WHICH THEY RELATE.

D. SHOP DRAWINGS, WHEN REQUIRED, SHALL INCLUDE:

1. VERIFICATION OF INFORMATION GIVEN IN CONTRACT DOCUMENTS SUCH AS

PERFORMANCE, DIMENSIONS, WEIGHT, MATERIALS, CONSTRUCTION, TYPES, MODELS,

MANUFACTURER, ETC.

2. EQUIPMENT LAYOUTS DRAWN TO SCALE AS MAY BE REQUIRED.

3. WIRING DIAGRAMS AND SCHEMATICS FOR EQUIPMENT.

4. ANY SPECIAL CONSTRUCTION CONDITIONS.

5. OTHER INFORMATION/DATA AS MAY BE REQUESTED.

E. ALL SUBMITTALS SHALL IDENTIFY THE SPECIFIC DETAILS OF THE PRODUCT OR

ASSEMBLY. ALL OPTIONAL FEATURES BEING PROPOSED SHALL BE SO NOTED OR THE

SUBMITTAL WILL BE REJECTED.

F. REVIEW IS ONLY FOR GENERAL CONFORMANCE WITH THE DESIGN CONCEPT OF THE

PROJECT AND GENERAL COMPLIANCE WITH THE INFORMATION GIVEN IN THE

CONTRACT DOCUMENTS. ANY ACTION SHOWN IS SUBJECT TO THE REQUIREMENTS OF

THE PLANS AND SPECIFICATION. CONTRACTOR IS RESPONSIBLE FOR DIMENSIONS

WHICH SHALL BE CONFIRMED AND CORRELATED AT THE JOB SITE; FABRICATION

PROCESSES AND TECHNIQUES OF CONSTRUCTION; COORDINATION OF HIS WORK WITH

THAT OF ALL OTHER TRADES; AND THE SATISFACTORY PERFORMANCE OF HIS WORK.

G. FOR ITEMS BEING RESUBMITTED, CLEARLY IDENTIFY CHANGES MADE FROM THE

INITIAL SUBMITTAL REQUESTED BY THE ENGINEER. THE ENGINEER WILL REVIEW ONLY

THOSE CHANGES REQUESTED AND IDENTIFIED BY THE CONTRACTOR.

1.05 MAINTENANCE MANUALS

A. PREPARE MAINTENANCE MANUALS INCLUDING THE FOLLOWING INFORMATION FOR

EQUIPMENT ITEMS:

1. DESCRIPTION OF FUNCTION, NORMAL OPERATING CHARACTERISTICS AND

LIMITATIONS, PERFORMANCE CURVES, ENGINEERING DATA AND TESTS AND COMPLETE

NOMENCLATURE AND COMMERCIAL NUMBERS OF REPLACEMENT PARTS.

1.06 DELIVERY, STORAGE AND HANDLING

A. DELIVER PRODUCTS TO THE PROJECT PROPERLY IDENTIFIED WITH NAMES, MODEL

NUMBERS, TYPES, GRADES, COMPLIANCE LABELS AND OTHER INFORMATION NEEDED

FOR IDENTIFICATION.

B. PERMITS, FEES AND CERTIFICATES OF APPROVAL

C. CONTRACTOR SHALL ACQUIRE ALL PERMITS AND CERTIFICATES.

1.07 COMPLIANCE WITH CODES, STANDARDS AND REGULATIONS

A. IN THE ABSENCE OF SPECIFIC INSTRUCTION IN THE TECHNICAL SPECIFICATIONS,

EQUIPMENT AND INSTALLATION SHALL CONFORM TO THE FOLLOWING APPLICABLE

CODES, STANDARDS AND REGULATIONS, LATEST EDITIONS:

1. AMERICAN SOCIETY FOR TESTING MATERIALS (ASTM).

2. AMERICAN NATIONAL STANDARD INSTITUTE (ANSI).

3. UNDERWRITER'S LABORATORIES, INC. (UL).

4. AMERICANS WITH DISABILITIES ACT (ADA).

5. LOCAL BUILDING, ELECTRICAL, AND FIRE CODES.

6. NATIONAL ELECTRICAL CODE (NEC).

7. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA).

8. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA).

PART 2 - EXECUTION

2.01 ROUGH-IN

A. VERIFY FINAL LOCATIONS FOR ROUGH-INS WITH FIELD MEASUREMENTS AND WITH

REQUIREMENTS OF THE ACTUAL EQUIPMENT TO BE CONNECTED.

2.02 ELECTRICAL INSTALLATIONS

A. GENERAL: SEQUENCE, COORDINATE, AND INTEGRATE THE VARIOUS ELEMENTS OF

ELECTRICAL SYSTEMS, MATERIALS, AND EQUIPMENT. COMPLY WITH THE FOLLOWING

REQUIREMENTS:

B. IN THE ABSENCE OF SPECIFIC INSTRUCTION IN THE TECHNICAL SPECIFICATIONS,

EQUIPMENT AND INSTALLATION SHALL CONFORM TO THE FOLLOWING APPLICABLE

CODES, STANDARDS AND REGULATIONS, LATEST EDITIONS:

1. COORDINATE ELECTRICAL SYSTEMS, EQUIPMENT, AND MATERIALS INSTALLATION

WITH OTHER BUILDING COMPONENTS.

2. VERIFY ALL DIMENSIONS BY FIELD MEASUREMENTS.

3. INSTALL SYSTEMS, MATERIALS, AND EQUIPMENT TO CONFORM WITH APPROVED

SUBMITTAL DATA, INCLUDING COORDINATION DRAWINGS, TO GREATEST EXTENT

POSSIBLE. CONFORM TO ARRANGEMENTS INDICATED BY THE CONTRACT DOCUMENTS,

RECOGNIZING THAT PORTIONS OF THE WORK ARE SHOWN ONLY IN DIAGRAMMATIC

FORM. WHERE COORDINATION REQUIREMENTS CONFLICT WITH INDIVIDUAL SYSTEM

REQUIREMENTS, REFER CONFLICT TO THE ENGINEER.

2.03 UTILITY COMPANY ELECTRICITY-METERING EQUIPMENT

A. INSTALL EQUIPMENT ACCORDING TO UTILITY COMPANY'S WRITTEN

REQUIREMENTS. PROVIDE GROUNDING AND EMPTY CONDUITS AS REQUIRED BY UTILITY

COMPANY. VERIFY PAD AND CLEARANCE REQUIREMENTS FOR ALL EQUIPMENT. LOCATE

ESSENTIALLY AS SHOWN ON THE PLANS. NOTIFY ENGINEER AND CONSTRUCTION

MANAGER IF LOCATIONS, SIZES AND OR QUANTITY OF EQUIPMENT ARE NOT AS SHOWN,

PRIOR TO INSTALLATION.

2.04 FIRESTOPPING

A. APPLY FIRE STOPPING TO CABLE AND RACEWAY PENETRATIONS OF FIRE-

RATED FLOOR AND WALL ASSEMBLIES TO ACHIEVE FIRE-RESISTANCE RATING OF

THE ASSEMBLY.

2.06 DEMOLITION

A. PROTECT EXISTING ELECTRICAL EQUIPMENT AND INSTALLATIONS INDICATED

TO REMAIN. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK, REMOVE

DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY, QUALITY,

AND FUNCTIONALITY.

B. ACCESSIBLE WORK: REMOVE EXPOSED ELECTRICAL EQUIPMENT AND

INSTALLATIONS, INDICATED TO BE DEMOLISHED, IN THEIR ENTIRETY.

C. ABANDONED WORK: CUT AND REMOVE BURIED RACEWAY AND WIRING,

INDICATED TO BE ABANDONED IN PLACE, 2 INCHES BELOW THE SURFACE OF

ADJACENT CONSTRUCTION. CAP RACEWAYS AND PATCH SURFACE TO MATCH

EXISTING FINISH.

D. MAKE AVAILABLE TO OWNER ANY SALVAGEABLE ITEMS REMOVED, IF NOT

DESIRED BY OWNER, REMOVE DEMOLISHED MATERIAL FROM PROJECT SITE.

E. REMOVE, STORE, CLEAN, REINSTALL, RECONNECT, AND MAKE OPERATIONAL

COMPONENTS INDICATED FOR RELOCATION.

F. PROVIDE COVERS FOR ALL OUTLETS, BOXES, FITTINGS, ENCLOSURES OR

WIREWAYS. PROVIDE BLANK COVERS FOR RECEPTACLE AND SWITCH BOXES TO

MATCH COLOR AND MATERIAL SPECIFIED FOR DEVICE COVERS. PROVIDE MATERIAL

AND FINISH TO MATCH BOXES, FITTINGS, ENCLOSURES AND WIREWAYS.

2.07 CUTTING AND PATCHING

A. CUT, CHANNEL, CHASE, AND DRILL FLOORS, WALLS, PARTITIONS, CEILINGS,

AND OTHER SURFACES REQUIRED TO PERMIT ELECTRICAL INSTALLATIONS.

PERFORM CUTTING BY SKILLED MECHANICS OF TRADES INVOLVED.

B. REPAIR AND REFINISH DISTURBED FINISH MATERIALS AND OTHER SURFACES

TO MATCH ADJACENT UNDISTURBED SURFACES. INSTALL NEW FIREPROOFING

WHERE EXISTING FIRE-STOPPING HAS BEEN DISTURBED. REPAIR AND REFINISH

MATERIALS AND OTHER SURFACES BY SKILLED MECHANICS OF TRADES INVOLVED.

2.08 FIELD QUALITY CONTROL

A. TEST ALL SYSTEMS AND EQUIPMENT FOR PROPER OPERATION, ACCURACY AND

SUITABILITY. MAKE CORRECTIONS TO THE SATISFACTION OF THE OWNER AND

DESIGN TEAM.

2.09 REFINISHING AND TOUCHUP PAINTING

A. REFINISH AND TOUCH UP PAINT:

1. CLEAN DAMAGED AND DISTURBED AREAS AND APPLY PRIMER, INTERMEDIATE,

AND FINISH COATS TO SUIT THE DEGREE OF DAMAGE AT EACH LOCATION.

2. FOLLOW PAINT MANUFACTURER'S WRITTEN INSTRUCTIONS FOR SURFACE

PREPARATION AND FOR TIMING AND APPLICATION OF SUCCESSIVE COATS.

3. REPAIR DAMAGE TO GALVANIZED FINISHES WITH ZINC-RICH PAINT

RECOMMENDED BY MANUFACTURER.

4. REPAIR DAMAGE TO PVC OR PAINT FINISHES WITH MATCHING TOUCHUP

COATING RECOMMENDED BY MANUFACTURER.

2.10 CLEANING AND PROTECTION

A. ON COMPLETION OF INSTALLATION, INCLUDING OUTLETS, FITTINGS, AND

DEVICES, INSPECT EXPOSED FINISH. REMOVE BURRS, DIRT, PAINT SPOTS, AND

CONSTRUCTION DEBRIS.

B. PROTECT EQUIPMENT AND INSTALLATIONS AND MAINTAIN CONDITIONS TO

ENSURE THAT COATINGS, FINISHES, AND CABINETS ARE WITHOUT DAMAGE OR

DETERIORATION AT TIME OF SUBSTANTIAL COMPLETION.

2. LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 V AND LESS)

PART 1 - PRODUCTS

1.01 WIRING REQUIREMENTS

A. CONCEALED DRY INTERIOR LOCATIONS: USE ONLY BUILDING WIRE WITH TYPE

THHN-THWN INSULATION IN RACEWAY, ARMORED CABLE, OR METAL CLAD CABLE.

B. EXPOSED DRY INTERIOR LOCATIONS: USE ONLY BUILDING WIRE WITH TYPE

THHN-THWN INSULATION IN RACEWAY.

C. ABOVE ACCESSIBLE CEILINGS: USE ONLY BUILDING WIRE WITH TYPE THHN-

THWN INSULATION IN RACEWAY OR ARMORED CABLE FOR FIXTURE "WHIPS" ONLY,

NOT TO EXCEED 6 FOOT EACH.

D. EXTERIOR LOCATIONS: USE ONLY BUILDING WIRE WITH TYPE THHN-THWN

INSULATION IN RACEWAY.

E. UNDERGROUND INSTALLATIONS: USE ONLY BUILDING WIRE WITH TYPE THHN-

THWN INSULATION IN RACEWAY.

F. USE CONDUCTOR NOT SMALLER THAN 12 AWG FOR POWER AND LIGHTING

CIRCUITS.

G. USE 10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS

LONGER THAN 75 FEET.

H. CONDUCTOR SIZES ARE BASED ON COPPER.

1.02 BUILDING WIRE

A. DESCRIPTION: SINGLE CONDUCTOR INSULATED WIRE.

B. CONDUCTOR: COPPER.

C. INSULATION VOLTAGE RATING: 600 VOLTS.

1.03 ARMORED CABLE

A. INSULATION VOLTAGE RATING: 600 VOLTS.

B. CONDUCTOR: COPPER.

C. DESCRIPTION: NFPA 70, TYPE AC.

PART 2 - EXECUTION

2.01 EXAMINATION

A. VERIFY THAT RACEWAY INSTALLATION IS COMPLETE AND SUPPORTED.

B. VERIFY THAT MECHANICAL WORK LIKELY TO DAMAGE WIRE AND CABLE HAS

BEEN COMPLETED.

C. VERIFY THAT INTERIOR OF BUILDING HAS BEEN PROTECTED FROM WEATHER.

2.02 INSTALLATION

A. INSTALL WIRE AND CABLE SECURELY, IN A NEAT AND WORKMANLIKE MANNER,

AS SPECIFIED IN NECA 1.

B. IDENTIFY AND COLOR CODE WIRE AND CABLE AS SPECIFIED. IDENTIFY EACH

CONDUCTOR WITH ITS CIRCUIT NUMBER OR OTHER DESIGNATION INDICATED.

C. USE WIRING METHODS INDICATED.

D. PULL ALL CONDUCTORS INTO RACEWAY AT SAME TIME.

E. USE SUITABLE WIRE PULLING LUBRICANT FOR BUILDING WIRE 4 AWG AND

LARGER.

F. ROUTE WIRE AND CABLE AS REQUIRED TO MEET PROJECT CONDITIONS.

3. GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.01 SECTION INCLUDES

A. PROVIDE ALL COMPONENTS NECESSARY TO COMPLETE THE GROUNDING

SYSTEM(S) CONSISTING OF:

1. METAL UNDERGROUND WATER PIPE.

2. METAL FRAME OF THE BUILDING.

3. ROD ELECTRODES.

PART 2 - PRODUCTS

2.01 ELECTRODES

A. ROD ELECTRODES: COPPER-CLAD STEEL.

1. DIAMETER: 5/8 INCH.

2. LENGTH: 8 FEET.

2.02 CONNECTORS AND ACCESSORIES

A. GROUNDING CONDUCTORS.

1. EQUIPMENT GROUNDING CONDUCTORS: INSULATED WITH GREEN-

COLORED INSULATION.

2. GROUNDING ELECTRODE CONDUCTOR: STRANDED COPPER CABLE.

3. GROUNDING BUS: BARE, ANNEALED COPPER BARS OF RECTANGULAR

CROSS SECTION, MINIMUM 1/4", MOUNTED ON INSULATORS.

PART 3 - EXECUTION

3.01 INSTALLATION

A. PROVIDE GROUNDING ELECTRODE CONDUCTOR AND CONNECT TO

REINFORCING STEEL IN FOUNDATION FOOTING. BOND STEEL TOGETHER.

B. INSTALL GROUND ELECTRODES AT LOCATIONS INDICATED.

C. INSTALL GROUNDING TO COMPLY WITH UTILITY COMPANY REQUIREMENTS

AND THE NEC. PROVIDE A MINIMUM THREE DRIVEN GROUND RODS SPACED AT

LEAST 8' APART.

4. HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.01 REFERENCES

A. NECA 1 - STANDARD PRACTICES FOR GOOD WORKMANSHIP IN ELECTRICAL

CONTRACTING; NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION; 2006.

B. NFPA 70 - NATIONAL ELECTRICAL CODE; NATIONAL FIRE PROTECTION

ASSOCIATION; 2005.

PART 2 - EXECUTION

2.01 INSTALLATION

A. INSTALL HANGERS AND SUPPORTS AS REQUIRED TO ADEQUATELY AND

SECURELY SUPPORT ELECTRICAL SYSTEM COMPONENTS, IN A NEAT AND

WORKMANLIKE MANNER, AS SPECIFIED IN NECA 1.

1. DO NOT FASTEN SUPPORTS TO PIPES, DUCTS, MECHANICAL EQUIPMENT,

OR CONDUIT.

B. IN WET AND DAMP LOCATIONS USE STEEL CHANNEL SUPPORTS TO STAND

CABINETS AND PANELBOARDS 1 INCH OFF WALL.

C. INSTALL SURFACE-MOUNTED CABINETS AND PANELBOARDS WITH

MINIMUM OF FOUR ANCHORS.

D. RIGIDLY WELD SUPPORT MEMBERS OR USE HEXAGON-HEAD BOLTS TO

PRESENT NEAT APPEARANCE WITH ADEQUATE STRENGTH AND RIGIDITY. USE

SPRING LOCK WASHERS UNDER ALL NUTS.

5. CONDUIT

PART 1 - GENERAL

1.03 QUALITY ASSURANCE

A. CONFORM TO REQUIREMENTS OF NFPA 70.

PART 2 - PRODUCTS

2.01 CONDUIT REQUIREMENTS

A. CONDUIT SIZE: COMPLY WITH NFPA 70.

1. MINIMUM SIZE: 3/4 INCH UNLESS OTHERWISE SPECIFIED.

B. UNDERGROUND INSTALLATIONS: USE THICKWALL NON-METALLIC

CONDUIT.

C. WET AND DAMP LOCATIONS: USE RIGID STEEL CONDUIT OR

INTERMEDIATE METAL CONDUIT.

D. DRY LOCATIONS:

1. CONCEALED: USE ELECTRICAL METALLIC TUBING.

2. EXPOSED: USE ELECTRICAL METALLIC TUBING.

2.02 METAL CONDUIT

A. RIGID STEEL CONDUIT: ANSI C80.1.

B. INTERMEDIATE METAL CONDUIT (IMC): RIGID STEEL.

C. FITTINGS AND CONDUIT BODIES: NEMA FB 1; ALL STEEL FITTINGS.

2.02 FLEXIBLE METAL CONDUIT

A. DESCRIPTION: INTERLOCKED STEEL CONSTRUCTION.

B. FITTINGS: NEMA FB 1.

2.04 LIQUIDTIGHT FLEXIBLE METAL CONDUIT

A. DESCRIPTION: INTERLOCKED STEEL CONSTRUCTION WITH PVC JACKET.

B. FITTINGS: NEMA FB 1.

2.05 ELECTRICAL METALLIC TUBING (EMT)

A. DESCRIPTION: ANSI C80.3; GALVANIZED TUBING.

B. FITTINGS AND CONDUIT BODIES: NEMA FB 1; STEEL SET SCREW TYPE.

2.06 NONMETALLIC CONDUIT

A. DESCRIPTION: NEMA TC 2; SCHEDULE 40 PVC.

B. FITTINGS AND CONDUIT BODIES: NEMA TC 3.

PART 3 - EXECUTION

3.01 EXAMINATION

A. VERIFY ROUTING AND TERMINATION LOCATIONS OF CONDUIT PRIOR TO

ROUGH-IN.

3.02 INSTALLATION

A. INSTALL CONDUIT SECURELY, IN A NEAT AND WORKMANLIKE MANNER, AS

SPECIFIED IN NECA 1.

B. INSTALL STEEL CONDUIT AS SPECIFIED IN NECA 101.

C. INSTALL NONMETALLIC CONDUIT IN ACCORDANCE WITH MANUFACTURER'S

INSTRUCTIONS.

D. DO NOT ATTACH CONDUIT TO CEILING SUPPORT WIRES.

E. ROUTE EXPOSED CONDUIT PARALLEL AND PERPENDICULAR TO WALLS.

F. ROUTE CONDUIT INSTALLED ABOVE ACCESSIBLE CEILINGS PARALLEL AND

PERPENDICULAR TO WALLS.

G. INSTALL NO MORE THAN EQUIVALENT OF THREE 90 DEGREE BENDS

BETWEEN BOXES. USE CONDUIT BODIES TO MAKE SHARP CHANGES IN

DIRECTION, AS AROUND BEAMS. USE HYDRAULIC ONE SHOT BENDER TO

FABRICATE BENDS IN METAL CONDUIT LARGER THAN 2 INCH SIZE.

H. AVOID MOISTURE TRAPS; PROVIDE JUNCTION BOX WITH DRAIN FITTING AT

LOW POINTS IN CONDUIT SYSTEM.

I. PROVIDE SUITABLE PULL STRING IN EACH EMPTY CONDUIT EXCEPT

SLEEVES AND NIPPLES.

J. GROUND AND BOND CONDUIT PER THE NEC.

3.03 INTERFACE WITH OTHER PRODUCTS

A. ROUTE CONDUIT THROUGH ROOF OPENINGS FOR PIPING AND DUCTWORK

WHEREVER POSSIBLE. WHERE SEPARATE ROOFING PENETRATION IS REQUIRED,

COORDINATE LOCATION AND INSTALLATION METHOD WITH ROOFING

INSTALLATION SPECIFIED IN SECTION FOR ROOFING.

6. BOXES

PART 1 - GENERAL

1.01 QUALITY ASSURANCE

A. CONFORM TO REQUIREMENTS OF NFPA 70.

B. PRODUCTS: PROVIDE PRODUCTS LISTED AND CLASSIFIED BY

UNDERWRITERS LABORATORIES INC., AS SUITABLE FOR THE PURPOSE

SPECIFIED AND INDICATED.

PART 2 - PRODUCTS

2.01 OUTLET BOXES

A. SHEET METAL OUTLET BOXES: NEMA OS 1, GALVANIZED STEEL.

1. LUMINAIRE AND EQUIPMENT SUPPORTING BOXES: RATED FOR WEIGHT

OF EQUIPMENT SUPPORTED; INCLUDE 1/2 INCH MALE FIXTURE STUDS WHERE

REQUIRED.

2.02 PULL AND JUNCTION BOXES

A. SHEET METAL BOXES: NEMA OS 1, GALVANISED STEEL.

B. HINGED ENCLOSURES: AS SPECIFIED IN SECTION 26 2716.

PART 3 - EXECUTION

3.01 EXAMINATION

A. VERIFY LOCATIONS OF FLOOR BOXES AND OUTLETS IN OFFICES AND

WORK AREAS PRIOR TO ROUGH-IN.

3.02 INSTALLATION

A. INSTALL IN LOCATIONS AS SHOWN ON DRAWINGS, AND AS REQUIRED

FOR SPLICES, TAPS, WIRE PULLING, EQUIPMENT CONNECTIONS, AND AS

REQUIRED BY NFPA 70.

B. SET WALL MOUNTED BOXES AT ELEVATIONS TO ACCOMMODATE

MOUNTING HEIGHTS INDICATED.

C. INSTALL PULL BOXES AND JUNCTION BOXES ABOVE ACCESSIBLE

CEILINGS AND IN UNFINISHED AREAS ONLY.

D. COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF OUTLETS

MOUNTED ABOVE COUNTERS, BENCHES, AND BACKSPLASHES.

E. LOCATE OUTLET BOXES TO ALLOW LUMINAIRES POSITIONED AS SHOWN

ON REFLECTED CEILING PLAN.

F. ALIGN ADJACENT WALL MOUNTED OUTLET BOXES FOR SWITCHES,

THERMOSTATS, AND SIMILAR DEVICES.

G. USE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS.

H. USE GANG BOX WHERE MORE THAN ONE DEVICE IS MOUNTED

TOGETHER. DO NOT USE SECTIONAL BOX.

I. USE CAST OUTLET BOX IN EXTERIOR LOCATIONS EXPOSED TO THE

WEATHER AND WET LOCATIONS.

7. IDENTIFICATION FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.01 SECTION INCLUDES

A. NAMEPLATES AND LABELS.

B. WIRE AND CABLE MARKERS.

C. CONDUIT MARKERS.

D. FIELD-PAINTED IDENTIFICATION OF CONDUIT.

PART 2 - GENERAL

2.01 NAMEPLATES AND LABELS

A. NAMEPLATES: ENGRAVED THREE-LAYER LAMINATED PLASTIC, BLACK

LETTERS ON WHITE BACKGROUND.

B. LOCATIONS:

1. EACH ELECTRICAL DISTRIBUTION AND CONTROL EQUIPMENT

ENCLOSURE.

C. LETTER SIZE:

1. USE 1/8 INCH LETTERS FOR IDENTIFYING INDIVIDUAL EQUIPMENT AND

LOADS.

D. LABELS: EMBOSSED ADHESIVE TAPE, WITH 3/16 INCH WHITE LETTERS

ON BLACK BACKGROUND. USE ONLY FOR IDENTIFICATION OF INDIVIDUAL

WALL SWITCHES AND RECEPTACLES, CONTROL DEVICE STATIONS, AND

OTHER OUTLETS, WHERE INDICATED FOR SPECIFIC PURPOSES OR AS A

DEDICATED CIRCUIT.

2.02 WIRE MARKERS

A. DESCRIPTION: CLOTH OR TAPE TYPE WIRE MARKERS.

B. LOCATIONS: EACH CONDUCTOR AT PANELBOARD GUTTERS AND

OUTLET BOXES EACH LOAD CONNECTION.

C. LEGEND:

1. POWER AND LIGHTING CIRCUITS: BRANCH CIRCUIT OR FEEDER

NUMBER INDICATED ON DRAWINGS.

2.03 CONNECTORS AND ACCESSORIES

A. SPACING: 20 FEET ON CENTER.

B. COLOR:

1. FIRE ALARM SYSTEM: RED.

2. TELECOMMUNICATION SYSTEM: GREEN AND YELLOW.

3. MECHANICAL AND ELECTRICAL SUPERVISOR SYSTEM: GREEN AND

BLUE.

PART 3 - EXECUTION

3.01 INSTALLATION

A. INSTALL NAMEPLATES AND LABELS PARALLEL TO EQUIPMENT LINES.

B. SECURE NAMEPLATES TO EQUIPMENT FRONT USING SCREWS.

C. SECURE NAMEPLATES TO INSIDE SURFACE OF DOOR ON PANELBOARD

THAT IS RECESSED IN FINISHED LOCATIONS.

D. IDENTIFY UNDERGROUND CONDUITS USING UNDERGROUND WARNING

TAPE. INSTALL ONE TAPE PER TRENCH AT 3 INCHES BELOW FINISHED

GRADE.

10. WIRING DEVICES

PART 1 - GENERAL

1.01 SUBMITTALS

A. PRODUCT DATA: PROVIDE MANUFACTURER'S CATALOG INFORMATION

SHOWING DIMENSIONS, COLORS, AND CONFIGURATIONS.

PART 2 - PRODUCTS

2.01 MANUFACTURERS

A. COOPER WIRING DEVICES

B. LEVITON MANUFACTURING, INC

C. HUBBELL INC.

D. PASS & SEYMOUR/LEGRAND

2.04 WALL PLATES

A. DECORATIVE COVER PLATES: COLOR TO MATCH DEVICE, SMOOTH

PLASTIC.

B. WEATHERPROOF IN-USE COVER PLATES: GASKETED CAST METAL WITH

HINGED.

PART 3 - EXECUTION

3.01 PREPARATION

A. PROVIDE EXTENSION RINGS TO BRING OUTLET BOXES FLUSH WITH

FINISHED SURFACE.

3.02 INSTALLATION

A. INSTALL DEVICES PLUMB AND LEVEL.

B. INSTALL SWITCHES WITH OFF POSITION DOWN.

C. INSTALL RECEPTACLES WITH GROUNDING POLE ON BOTTOM.

D. CONNECT WIRING DEVICE GROUNDING TERMINAL TO OUTLET BOX WITH

BONDING JUMPER.

E. INSTALL DECORATIVE PLATES ON SWITCH, RECEPTACLE, AND BLANK

OUTLETS IN FINISHED AREAS.

11. ENCLOSED SWITCHES

PART 1 - GENERAL

1.01 SUBMITTALS

A. PRODUCT DATA: PROVIDE SWITCH RATINGS AND ENCLOSURE

DIMENSIONS.

PART 2 - PRODUCTS

2.01 COMPONENTS

A. FUSIBLE SWITCH ASSEMBLIES: NEMA KS 1, TYPE HD ENCLOSED LOAD

INTERRUPTER KNIFE SWITCH.

1. EXTERNALLY OPERABLE HANDLE INTERLOCKED TO PREVENT OPENING

FRONT COVER WITH SWITCH IN ON POSITION.

2. HANDLE LOCKABLE IN OFF POSITION.

3. FUSE CLIPS: DESIGNED TO ACCOMMODATE NEMA FU1, CLASS R

FUSES.

B. NONFUSIBLE SWITCH ASSEMBLIES: NEMA KS 1, TYPE HD ENCLOSED

LOAD INTERRUPTER KNIFE SWITCH.

1. EXTERNALLY OPERABLE HANDLE INTERLOCKED TO PREVENT OPENING

FRONT COVER WITH SWITCH IN ON POSITION.

2. HANDLE LOCKABLE IN OFF POSITION.

C. ENCLOSURES: NEMA KS 1.

1. INTERIOR DRY LOCATIONS: TYPE 1.

2. EXTERIOR LOCATIONS: TYPE 3R.

PART 3 - EXECUTION

3.01 INSTALLATION

A. INSTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.

B. INSTALL FUSES IN FUSIBLE DISCONNECT SWITCHES.

C. APPLY ADHESIVE TAG ON INSIDE DOOR OF EACH FUSED SWITCH

INDICATING NEMA FUSE CLASS AND SIZE INSTALLED.

12. INTERIOR LIGHTING

PART 1 - GENERAL

1.01 SUBMITTALS

A. SHOP DRAWINGS: INDICATE DIMENSIONS AND COMPONENTS FOR EACH

LUMINAIRE.

PART 2 - PRODUCTS

2.01 LUMINAIRES

A. FURNISH PRODUCTS AS INDICATED IN SCHEDULE INCLUDED ON THE

DRAWINGS.

PART 3 - EXECUTION

3.01 INSTALLATION

A. INSTALL FIXTURES SECURELY, IN A NEAT AND WORKMANLIKE

MANNER, AS SPECIFIED IN NECA

B. INSTALL SUSPENDED LUMINAIRES AND EXIT SIGNS USING PENDANTS

SUPPORTED FROM SWIVEL HANGERS. PROVIDE PENDANT LENGTH

REQUIRED TO SUSPEND LUMINAIRE AT INDICATED HEIGHT.

C. LOCATE RECESSED CEILING LUMINAIRES AS INDICATED ON

REFLECTED CEILING PLAN.

D. INSTALL SURFACE MOUNTED LUMINAIRES AND EXIT SIGNS PLUMB

AND ADJUST TO ALIGN WITH BUILDING LINES AND WITH EACH OTHER.

SECURE TO PREVENT MOVEMENT.

E. INSTALL RECESSED LUMINAIRES TO PERMIT REMOVAL FROM BELOW.

F. INSTALL CLIPS TO SECURE RECESSED GRID-SUPPORTED LUMINAIRES

IN PLACE.

G. INSTALL WALL MOUNTED LUMINAIRES AND EXIT SIGNS AT HEIGHT AS

INDICATED ON DRAWINGS.

H. BOND PRODUCTS AND METAL ACCESSORIES TO BRANCH CIRCUIT

EQUIPMENT GROUNDING CONDUCTOR.

3.02 SCHEDULES - SEE DRAWINGS

CONSULTANT

SHEET TITLE

PROJECT NUMBER

SHEET NUMBER

PROJECT

Copyright 2021, Hobbs + Black Associates, Inc.C

ALL RIGHTS RESERVED

H G F E D C B A

H G F E D C B A

Sheet Size - 24x36

DATE ISSUED

DRAWN BY

CHECKED BY

Au to de sk

D oc s:

//2

6-

M

SP

T ra in in g

Ac ad em y

AD

A

Li ft

PH

0-

0/

M

SP

T ra in in g Ac ad em y Au di to riu m

L ift

Ph as e

0-

- M

EP

R

.rv t

E-101

26-325

ELECTRICAL

SPECIFICATIONS

AU

D

IT

O

R

IU

M A

D A

LI

FT

N . C

AN

AL

R D

LA

N

SI

N G

, M I 4

BTT

DDA

M

SP

T R

AI

N

IN

G

AC

AD

EM

Y

FAX: 517.487.2544

PHONE: 517.487.2511

LANSING, MI 48917

544 CHERBOURG DRIVE

MATRIX PROJECT: 260462.00

WEB: www.matrixceinc.com

MatrixMatrix

CONSULTING ENGINEERS, INC

V

CR

EPD1

CONSULTANT

SHEET TITLE

PROJECT NUMBER

SHEET NUMBER

PROJECT

Copyright 2021, Hobbs + Black Associates, Inc.C

ALL RIGHTS RESERVED

H G F E D C B A

H G F E D C B A

Sheet Size - 24x36

DATE ISSUED

DRAWN BY

CHECKED BY

Au to de sk

D oc s:

//2

6-

M

SP

T ra in in g

Ac ad em y

AD

A

Li ft

PH

0-

0/

M

SP

T ra in in g Ac ad em y Au di to riu m

L ift

Ph as e

0-

- M

EP

R

.rv t

E-300

26-325

LOWER LEVEL

AND LEVEL ONE

- DEMOLITION

AU

D

IT

O

R

IU

M A

D A

LI

FT

N . C

AN

AL

R D

LA

N

SI

N G

, M I 4

BTT

DDA

M

SP

T R

AI

N

IN

G

AC

AD

EM

Y

SCALE: 1/4" = 1'-0"

LOWER LEVEL - DEMOLITION

SCALE: 1/4" = 1'-0"

LEVEL ONE - DEMOLITION

SCALE: 1" = 100'-0"

Keyplan

FAX: 517.487.2544

PHONE: 517.487.2511

LANSING, MI 48917

544 CHERBOURG DRIVE

MATRIX PROJECT: 260462.00

WEB: www.matrixceinc.com

MatrixMatrix

CONSULTING ENGINEERS, INC

KEYNOTES:

1 EXISTING DEVICE TO REMAIN.

2 EXISTING LIGHT FIXTURE TO REMAIN.

3 CONTRACTOR SHALL DISCONNECT AND RELOCATE EXISTING LIGHT FIXTURE. EXTEND ASSOCIATED

CONDUIT AND WIRE TO NEW LOCATION.

4 EXISTING FIRE ALARM DEVICE TO REMAIN.

CR

J

V

J

CR

J

EPD1

EPD2

EX

EXEX

EX

EX EX

EX

EX

EPD1

EPD2

CONTROL

STATION

EPD1-16

EX

EX

EPD1-14

CONTROL

STATION

EPD1- 16

EPD1

CONSULTANT

SHEET TITLE

PROJECT NUMBER

SHEET NUMBER

PROJECT

Copyright 2021, Hobbs + Black Associates, Inc.C

ALL RIGHTS RESERVED

H G F E D C B A

H G F E D C B A

Sheet Size - 24x36

DATE ISSUED

DRAWN BY

CHECKED BY

Au to de sk

D oc s:

//2

6-

M

SP

T ra in in g

Ac ad em y

AD

A

Li ft

PH

0-

0/

M

SP

T ra in in g Ac ad em y Au di to riu m

L ift

Ph as e

0-

- M

EP

R

.rv t

E-400

26-325

LOWER LEVEL

AND LEVEL ONE

- NEW POWER

AND LIGHTING

AU

D

IT

O

R

IU

M A

D A

LI

FT

N . C

AN

AL

R D

LA

N

SI

N G

, M I 4

BTT

DDA

M

SP

T R

AI

N

IN

G

AC

AD

EM

Y

SCALE: 1/8" = 1'-0"

LEVEL ONE - LIGHTING SCALE: 1/8" = 1'-0"

LEVEL ONE - POWER

SCALE: 1/4" = 1'-0"

LOWER LEVEL - LIGHTING SCALE: 1/4" = 1'-0"

LOWER LEVEL - POWER

SCALE: 1" = 100'-0"

New Keyplan

KEYNOTES:

1 RELOCATED LIGHT FIXTURE. SPLICE AND EXTEND ASSOCIATED CONDUIT AND WIRE AS REQUIRED.

2 ROUTE SURFACE RACEWAY BELOW SOFFIT TO CONTROL LOCATION. SEE ARCHITECTURAL

ELEVATIONS H4/A-300.

FAX: 517.487.2544

PHONE: 517.487.2511

LANSING, MI 48917

544 CHERBOURG DRIVE

MATRIX PROJECT: 260462.00

WEB: www.matrixceinc.com

MatrixMatrix

CONSULTING ENGINEERS, INC

CONSULTANT

SHEET TITLE

PROJECT NUMBER

This is the start of the file's text. The full file is on GovTribe.