26150_B Drawings.pdf
PDF 27 MB Posted
- Solicitation number
- PE-65600-NONST-2027-000000237
- Issued by
- Douglas County, Georgia
About this file
This is a set of construction drawings for the Crosstown Water Treatment Plant (WTP) Chemical System Upgrades project in Fayette County, Georgia. The project encompasses comprehensive upgrades to the existing chemical feed and storage systems, including the replacement of sodium hypochlorite and fluoride (hydrofluorosilicic acid) chemical systems, water softening equipment, hot water heating systems, and associated piping infrastructure. The work involves demolition of existing equipment in multiple rooms (sodium hypochlorite feed room, fluoride dosing room, and post-treatment chemical building), installation of new bulk storage tanks for sodium hypochlorite and fluoride with capacities of 10,150 gallons and 3,156 gallons respectively, new day tanks, metering pump skids, and distribution piping throughout the facility and to injection points in the treatment process. The project includes site work such as concrete pads, sidewalks, curbing, yard piping, erosion and sediment control measures, and modifications to the roof drain system. All work must conform to Fayette County and State of Georgia standards and specifications, with contractors required to verify existing utility locations and coordinate operations with plant staff to minimize disruption to active treatment operations.
The drawings indicate the project is in the "For Bid" phase as of July 2026, prepared by ARCADIS U.S., Inc. as the engineer of record. Key contractual requirements include contractor responsibility for utility location verification and damage claims, compliance with OSHA trench safety requirements, installation of erosion and sediment control measures prior to land disturbance, and provision of an as-built survey upon project completion prepared by a registered Georgia land surveyor. The contractor must obtain road permits from Fayette County, provide 72 hours notice to Georgia 811 before digging, and coordinate temporary disconnection and restoration of utilities with county approval. Water pipes must be flushed, pressure tested, chlorinated, and bacteriologically tested per specification. All disturbed areas must be restored with seeding and stabilization, and no standing water or debris is permitted on site.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 26150_B ITB.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Know what's below.
before you dig.Call
R
CONSULTANTS
SEALS
SHEET TITLE
ARCADIS U.S., INC.COPYRIGHT:
DATE:
PROJECT NO.:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SCALE:
SHEET NO.: OF
REVISIONS
E
2 3 4 5 6
D
C
B
A
DRAWING NO.:
PROJECT STATUS:
BAR IS ONE INCH ON
UNREDUCED DRAWING
0 1
ARCADIS U.S., INC.
2839 PACES FERRY RD SUITE 1000
ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
LEGAL ENTITY:
10-06-2026 14:59:29 Autodesk Docs://AUS-30171943-FCWS WTP Chemical Upgrades/M-3D-CT-HFSA_R22.rvt
E. VAN DEVENTER
M. BHANUMATHI
T. THOMAS
JULY 2026
30240979
G-01
WTP CHEMICAL UPGRADES
FAYETTE COUNTY, GEORGIA
GENERAL
COVER SHEET AND SITE
LOCATION (S)
FAYETTE COUNTY,GEORGIA
FOR BID
CROSSTOWN
CROSSTOWN
PROJECT LOCATION
NOT TO SCALE
ARCADIS ASSUMES NO RESPONSIBILITY FOR EXISTING UTILITY
LOCATIONS (HORIZONTAL AND VERTICAL). THE EXISTING
UTILITIES SHOWN ON THESE DRAWINGS HAVE BEEN PLOTTED
FROM THE BEST AVAILABLE INFORMATION. IT IS, HOWEVER,
THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VERIFY
THE LOCATION OF ALL UTILITIES PRIOR TO THE
COMMENCEMENT OF ANY CONSTRUCTION ACTIVITIES.
FAYETTE COUNTY WATER SYSTEM
CROSSTOWN WTP CHEMICAL
UPGRADES
FOR BID
JULY 2026
VICINITY MAP
PROJECT LOCATION 2839 PACES FERRY ROAD, SUITE 1000, ATLANTA, GA 30339-3769
TEL: 770.431.8666 FAX: 770.435.2666
www.ARCADIS.com
ENGINEER OF RECORD:
LEGAL ENTITY: ARCADIS-U.S., INC.
NOT TO SCALE
OWNER:
LOCATION MAP
ADDRESS 3500 TDK BLVD PEACHTREE CITY, GA 30269
NO. DATE ISSUED FOR BY
6/19/2026 before you dig.Call
R
CONSULTANTS
SEALS
SHEET TITLE
ARCADIS U.S., INC.COPYRIGHT:
DATE:
PROJECT NO.:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SCALE:
SHEET NO.: OF
REVISIONS
E
2 3 4 5 6
D
C
B
A
DRAWING NO.:
PROJECT STATUS:
BAR IS ONE INCH ON
UNREDUCED DRAWING
0 1
ARCADIS U.S., INC.
2839 PACES FERRY RD SUITE 1000
ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
LEGAL ENTITY:
10-06-2026 14:59:29 Autodesk Docs://AUS-30171943-FCWS WTP Chemical Upgrades/M-3D-CT-HFSA_R22.rvt
E. VAN DEVENTER
M. BHANUMATHI
T. THOMAS
JULY 2026
30240979
G-02
WTP CHEMICAL UPGRADES
FAYETTE COUNTY, GEORGIA
GENERAL
SHEET INDEX
FAYETTE COUNTY,GEORGIA
FOR BID
CROSSTOWN
DRAWING INDEX
DRAWING
NUMBER
DRAWING NAME
GENERAL
G-01 COVER SHEET AND SITE LOCATION (S)
G-02 SHEET INDEX
CIVIL
C-01 CIVIL LEGEND, SYMBOLS, AND ABBREVIATIONS
C-02 EXISTING CONDITIONS AND DEMOLITION PLAN
C-03
PROCESS MECH
M-01 MECHANICAL LEGENDS, SYMBOLS, AND ABBREVIATIONS
POST - TREATMENT CHEMICAL BUILDING OVERALL PLAN
CIVIL DETAILS
M-02
M-04
M-05
M-06
M-07
SODIUM HYPOCHLORITE FEED ROOM DEMOLITION PLAN
FLUORIDE FEED ROOM DEMOLITION PLAN
FLUORIDE BULK STORAGE AREA PLAN AND SECTIONS
FLUORIDE DOSING ROOM PLAN AND SECTIONS
SODIUM HYPOCHLORITE STORAGE AREA PLAN
SODIUM HYPOCHLORITE STORAGE AREA SECTIONS (1 OF 2)
TYPICAL DETAILS (1 OF 4)
TYPICAL DETAILS (2 OF 4)
STRUCTURAL
S-01 GENERAL NOTES
S-02
S-03
STRUCTURAL SPECIAL INSPECTIONS
FLUORIDE DOSING ROOM PLAN AND SECTIONSS-04
FLUORIDE DOSING ROOM DEMOLITION PLAN AND SECTION
M-11
M-10
SHEET
NUMBER
M-0918
SODIUM HYPOCHLORITE FEED ROOM PLAN
ELECTRICAL
E-01 LEGEND, SYMBOLS, AND ABBREVIATIONS - SHEET 1 OF 2
E-02
E-03
LEGEND, SYMBOLS, AND ABBREVIATIONS - SHEET 2 OF 2
E-04
ELECTRICAL SITE PLAN
E-05 EXISTING ONE LINE DIAGRAM
E-06 ONE LINE DIAGRAM MODIFICATIONS AND PANELBOARD SCHEDULES
FLUORIDE STORAGE AREA PLAN
SODIUM HYPOCHLORITE STORAGE AREA POWER PLAN
SODIUM HYPOCHLORITE STORAGE AREA LIGHTING PLAN
E-12
E-07
E-08
E-09
E-10
E-11
SODIUM HYPOCHLORITE ROOM PLAN
POST-TREATMENT CHEMICAL BUILDING POWER PLAN
INTERCONNECT WIRING DIAGRAM AND PUMP WIRING SCHEMATIC
S-05
S-06
S-07
S-09
HFSA BULK TANK PAD DEMOLITION PLAN
SODIUM HYPOCHLORITE STORAGE AREA ROOF PLAN
SODIUM HYPOCHLORITE STORAGE AREA SECTIONS AND DETAIL - 1
TYPICAL DETAILS - 1
M-12
BASEMENT FILTER PIPE GALLERY PLAN AND SECTIONS
E-13
M-13
M-14
M-15
SODIUM HYPOCHLORITE FEED ROOM SECTIONS
FLUORIDE TANK DETAILS
SODIUM HYPOCHLORITE TANK DETAILS
S-08
SODIUM HYPOCHLORITE STORAGE AREA SECTIONS AND DETAIL - 2
POST - TREATMENT CHEMICAL BUILDING OVERALL TEPID WATER SUPPLY PLAN
M-03
M-08
FLOOR DRAIN MODIFICATIONS PLAN
TYPICAL DETAILS (3 OF 4)
M-18
M-16
M-1726
DRAWING INDEX
DRAWING
NUMBER
DRAWING NAME
SHEET
NUMBER
S-10
S-11
S-12
S-13
HFSA BULK TANK PAD SECTIONS - 1
SODIUM HYPOCHLORITE FEED ROOM DEMOLITION PLAN AND SECTION
SODIUM HYPOCHLORITE FEED ROOM SECTIONS
SODIUM HYPOCHLORITE STORAGE AREA FOUNDATION PLAN
POST - TREATMENT CHEMICAL BUILDING OVERALL EXISTING/DEMOLITION PLAN
M-19
OVERALL KEY PLAN
E-14
E-15
FLUORIDE ROOM PLAN
HFSA BULK TANK PAD PLAN
SODIUM HYPOCHLORITE FEED ROOM PLAN
S-14
S-15
C-04
C-05
C-06
C-07
OVERALL SITE LAYOUT AND YARD PIPING PLAN
GRADING AND STAKING PLAN
ES&C PLAN
EROSION AND SEDIMENT CONTROL NOTES & DETAILS
SODIUM HYPOCHLORITE STORAGE AREA SECTIONS (2 OF 2)
TYPICAL DETAILS (4 OF 4)
M-20
M-21
HFSA BULK TANK PAD SECTIONS - 2
S-16
E-16
PANELBOARD SCHEDULES
M-22
ROOF PLAN & DETAILS
HVAC
ABBREVIATIONS,SYMBOLS AND NOTES
POST-TREATMENT CHEMICAL BUILDING DEMOLITION PLAN
POST-TREATMENT CHEMICAL BUILDING NEW WORK PLAN
SCHEDULES AND AIRFLOW/CONTROL SCHEMATICS
H-01
H-02
H-03
H-04
H-05 DETAILS
TYPICAL DETAILS - 2
S-17
TYPICAL ELECTRICAL DETAILS - SHEET 1 OF 3
TYPICAL ELECTRICAL DETAILS - SHEET 2 OF 3
CONTROL SCHEMATICS
TYPICAL ELECTRICAL DETAILS - SHEET 3 OF 3
E-17
E-18
INSTRUMENTATION & CONTROLS
I-01 INSTRUMENTATION SYMBOLS AND LEGEND - SHEET 1 OF 3
I-02
I-03
I-04
I-05
I-07 SODIUM HYPOCHLORITE FEED SYSTEM P&ID
INSTRUMENTATION SYMBOLS AND LEGEND - SHEET 2 OF 3
INSTRUMENTATION SYMBOLS AND LEGEND - SHEET 3 OF 3
PARTIAL NETWORK ARCHITECTURE
HYDROFLUOROSILICIC ACID (FLUORIDE) SYSTEM P&ID
I-06 SODIUM HYPOCHLORITE STORAGE P&ID
I-08 FILL STATION PANEL DETAILS - SHEET 1 OF 2
I-09 FILL STATION PANEL DETAILS - SHEET 2 OF 2
I-10 INSTRUMENTATION INSTALLATION DETAILS
VALVE SCHEDULE (1 OF 2)M-23
VALVE SCHEDULE (2 OF 2)M-24
User:JRI00725 Spec:AUS-NCSMOD File:C:\USERS\JRI00725\DC\ACCDOCS\ARCADIS ACC US\AUS-30171943-FCWS WTP CHEMICAL UPGRADES\PROJECT FILES\10_WIP\10T_ARC_CIVIL\CROSSTOWN\XREF\C-01_CT.DWG Scale:1:1 SavedDate:6/5/2026 Time:14:24 Plot Date: Raj, Joel; 6/5/2026; 20:11 ; Layout:C-01 CT before you dig.Call
R
B
C
D
E
1 2 3 4 5 6
SEALS
CONSULTANTS
SEALS
Owner
WTP CHEMICAL UPGRADES
FAYETTE COUNTY, GEORGIA
REVISIONS
LEGAL ENTITY:
ARCADIS U.S., INC.
2839 PACES FERRY RD. SE# 1000
ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
COPYRIGHT: ARCADIS U.S., INC.
PROJECT STATUS:
PROJECT NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SHEET TITLE
SHEET NO.: OF
SCALE:
DRAWING NO.:
BAR IS ONE INCH ON
UNREDUCED DRAWING
0 1
NO. DATE ISSUED FOR BY
30240979
JULY 2026
J. SWAIM
FOR BID
N. NIA
N. NIA
C-01
CIVIL LEGEND,
SYMBOLS,
AND ABBREVIATIONS
APPROXIMATE
ASPHALT
BUILDING
BOTTOM OF CURB
CENTERLINE
CATCH BASIN
CLEANOUT
CONCRETE
CONTINUED
COUPLING
CUBIC YARD(S)
DIATOMACEOUS EARTH
DETAIL
DROP INLET
DUCTILE IRON PIPE
DIAMETER
DISCHARGE
DRAWING
EACH
EFFLUENT
EXPANSION JOINT
ELEVATION
ELECTRIC
EQUAL
EXISTING
FLOW CONTROL VALVE
FLOOR DRAIN
FOUNDATION
FINISHED
FLEXIBLE
FLANGE
FLOOR
FOOTING
FEET
GROUND
APPROX.
ASPH
BLDG.
BOC
CB
CO
CONC.
CONT.
CPLG.
CY
DE
DET.
DI
DIP
DIA.
DISCH.
DWG
EA.
EFF.
EJ
ELEV.
ELEC.
EQ.
EXIST.
FCV
FD
FDN
FIN.
FLEX.
FLG
FLR.
FTG.
FT.
GRD.
GRATING
GATE VALVE
HORIZONTAL
INSIDE DIAMETER
INCHES
INFLUENT
INVERT
JOINT
LINEAR FOOT/FEET
MASONRY
MAXIMUM
MANUFACTURER
MILLION GALLONS PER DAY
MANHOLE
MINIMUM
NORMALLY CLOSED
NORMALLY OPEN
NUMBER
OUTSIDE DIAMETER
PROCESS DRAIN TO WASTE
POLYETHYLENE
PROPOSED GROUND
PROPOSED
POUNDS PER SQUARE INCH
REDUCER
REINFORCEMENT OR REINFORCE
REQUIRED
RIGHT OF WAY
SHEET
STAINLESS STEEL
STANDARD
STRUCTURAL
TOP OF CURB
THICK
TYPICAL
VERTICAL
WITH
GRAT.
GV
HORIZ.
ID
IN., "
INF.
INV.
JT.
LF
MAS
MAX.
MFR.
MGD
MH
MIN.
NC
NO
NO.
OD
PDW
PE
PG.
PROP.
PSI
R
REINF.
REQ'D.
ROW
SHT.
SS
STD.
STRUC.
TOC
THK.
TYP.
VERT.
W/
CIVIL ABBREVIATIONS
C-01
DRAWING
NUMBER
COMPONENT
DESIGNATOR
DRAWING NUMBER EXPLANATION
TITLE MARKERS
SECTION
SHEET SECTION IS SHOWN ON
SECTION MARKERS
REFERENCE BACK TO THE
PLAN SHEET SECTION IS
CUT FROM
SECTION NUMBER
DETAIL MARKERS
G00-01 A
DETAIL LETTER
SHEET DETAIL
IS SHOWN ON
GOO-01
SECTION
PLAN
TYPICAL DETAILS
DETAIL LETTER
REFERENCE BACK TO THE
DETAIL MARKER
A
GOO-01
DETAIL
GENERAL SITE AND YARD PIPING NOTES
1. EXISTING BASE MAPPING SHOWN CONSISTS OF COMPILATION OF THE FOLLOWING:
-TOPOGRAPHY AND SITE SURVEY RECEIVED FROM GPI, DATED APRIL 3, 2025.
COORDINATE SYSTEM: NSRS 2011 GEORGIA STATE PLANES, WEST ZONE, US FOOT.
COORDINATE SYSTEM CODE: NSRS11.GA-WF
HORIZONTAL DATUM: NSRS11
DIMENSIONS SHOWN ARE IN U.S. SURVEY FEET.
-PLANT RECORD DRAWINGS.
*EXISTING CONDITIONS MAY VARY TO THOSE SHOWN ON THESE PLANS. THE CONTRACTOR
SHALL VERIFY EXISTING CONDITIONS AND ADJUST WORK PLAN ACCORDINGLY PRIOR TO
BEGINNING OF CONSTRUCTION.
2. THE CONTRACTOR SHALL FURNISH ALL MATERIALS FOR, AND PROPERLY RESTORE ALL
PAVEMENT, DRIVES, SIDEWALK, AND CURBS, WHICH MAY HAVE BEEN DAMAGED, REMOVED
OR DISTURBED AS A RESULT OF ACCOMPLISHING THE WORK.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING GRADES AND DIMENSIONS AND
NOTIFYING THE ENGINEER IN ADVANCE AND IN WRITING OF ANY DISCREPANCIES PRIOR TO
PERFORMING ANY WORK.
4. EXISTING UTILITY LOCATIONS SHOWN ARE BASED ON RECORD DRAWINGS AND SURVEY
DRAWING OBTAINED FROM GPI, AND DATED APRIL 3, 2025. NOT ALL EXISTING UTILITIES ARE
SHOWN ON THE DRAWING. CONTRACTOR IS RESPONSIBLE FOR DETERMINING BOTH THE
EXACT LOCATION AND INSTALLED ELEVATION OF ALL EXISTING UTILITIES AND FOR
DETERMINING THEIR PROTECTION DURING CONSTRUCTION. IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO COORDINATE ALL OPERATIONS WITH ALL UTILITIES
WHICH MAY BE IN CONFLICT WITH HIS WORK. NOTIFY THE ENGINEER IN ADVANCE AND IN
WRITING OF ANY DISCREPANCIES PRIOR TO PERFORMING ANY WORK.
5. UNLESS OTHERWISE SHOWN, ALL PIPING SHALL HAVE A MINIMUM OF 3 FEET COVER.
6. ALL PIPES SHALL HAVE A CONSTANT SLOPE BETWEEN INVERT ELEVATIONS UNLESS A
FITTING SHOWN.
7. ALL NEW WATER PIPES MUST BE PROPERLY FLUSHED, PRESSURE TESTED, CHLORINATED
AND BACTERIOLOGICALLY TESTED, AS SPECIFIED.
8. A COPY OF THE APPROVED SET OF CONSTRUCTION PLANS MUST BE ON THE JOBSITE AT ALL
TIMES DURING CONSTRUCTION.
9. ALL EROSION AND SEDIMENTATION CONTROLS AND TREE PROTECTION SHALL BE INSTALLED
PRIOR TO ANY LAND DISTURBANCE ACTIVITY.
10. UNLESS NOTED OTHERWISE ALL CONSTRUCTION SHALL CONFORM TO THE FAYETTE
COUNTY AND STATE OF GEORGIA STANDARDS AND SPECIFICATIONS.
11. WHERE SHOWN ON DRAWINGS ALL SUBSURFACE TOPOGRAPHICAL FEATURES SHOWN ARE
APPROXIMATE. THE CONTRACTOR AT HIS EXPENSE SHALL CONDUCT ADDITIONAL
SUBSURFACE SOIL EXPLORATION IF DEEMED NECESSARY.
12. THE CONTRACTOR SHALL COORDINATE, OBTAIN APPROVAL AND PROVIDE TEMPORARY
TRAFFIC ROUTING PLANS PRIOR TO ANY LANE CLOSURES WITH THE FAYETTE COUNTY.
13. CONTRACTOR SHALL PROVIDE AND MAINTAIN PLANT ROADS ACCESSIBLE AT ALL TIMES.
TEMPORARY CLOSURE OF PLANT ROAD SHALL BE COORDINATED WITH PLANT OPERATOR.
14. ALL WORK AROUND THE EXISTING UTILITIES AND UTILITY STRUCTURES WHETHER ABOVE OR
BELOW GROUND SHALL BE PERFORMED IN A MANNER THAT WILL AVOID DAMAGE TO THE
UTILITIES AND STRUCTURES. PRIOR TO COMMENCING WORK, THE CONTRACTOR SHALL
ACCURATELY LOCATE ABOVE AND BELOW GROUND UTILITIES WHICH MAY BE AFFECTED BY
THE WORK AND PROTECT ALL UTILITIES NOT DESIGNATED FOR REMOVAL, RESTORATION,
OR REPLACEMENT IN THE COURSE OF CONSTRUCTION. PROVIDE 72 HOURS OF ADVANCE
NOTICE TO THE UTILITY OWNER AND FAYETTE COUNTY PRIOR TO BEGINNING
CONSTRUCTION IN THE VICINITY OF THE EXISTING UTILITIES. FOR EXISTING UTILITY
LOCATION ASSISTANCE CALL THE UNDERGROUND UTILITIES PROTECTION CENTER (GA 811).
15. ANY DAMAGE TO EXISTING UTILITIES CAUSED BY THE CONTRACTOR, CONTRACTOR'S CREW
AND/OR EQUIPMENT SHALL BE THE CONTRACTOR'S COST AND RESPONSIBILITY TO REPLACE
PER OWNER'S STANDARDS AND SPECIFICATIONS.
16. THE REFUSE RESULTING FROM THE CLEARING AND GRUBBING OPERATION SHALL BE
HAULED TO A DISPOSAL SITE SECURED BY THE CONTRACTOR AND SHALL BE DISPOSED OF
IN ACCORDANCE WITH ALL REQUIREMENTS OF FEDERAL, STATE, COUNTY AND MUNICIPAL
REGULATIONS. NO DEBRIS OF ANY KIND SHALL BE DEPOSITED IN ANY STREAM OR BODY OF
WATER, OR IN ANY STREET OR ALLEY. NO DEBRIS SHALL BE DEPOSITED UPON ANY PRIVATE
PROPERTY EXCEPT BY WRITTEN CONSENT OF THE PROPERTY OWNER. IN NO CASE SHALL
ANY MATERIAL BE LEFT ON THE PROJECT, SHOVED ONTO ABUTTING PRIVATE PROPERTIES,
OR BE BURIED IN THE EMBANKMENTS OR TRENCHES ON THE PROJECT.
17. FINISHED GRADING OF THE DISTURBED AREA SHALL BE ACCORDING TO CIVIL DRAWINGS. NO
STANDING WATER OR PONDING OF ANY KIND IS ALLOWED. ALL DISTURBED AREA SHALL BE
IMMEDIATELY GRASSED.
18. THE CONTRACTOR SHALL COMPLY WITH THE STATE OF GEORGIA MANUAL FOR EROSION
AND SEDIMENT CONTROL STANDARDS, LATEST EDITION.
19. THE ESCAPE OF SEDIMENT FROM THE SITE SHALL BE PREVENTED BY THE INSTALLATION OF
EROSION AND SEDIMENT CONTROL MEASURES AND PRACTICES PRIOR TO, AND
CONCURRENT WITH ANY LAND-DISTURBING ACTIVITIES. SEE EROSION CONTROL DRAWINGS
FOR FURTHER NOTES AND DETAILS.
20. ALL DISTURBED AREAS NOT RECEIVING A HARD SURFACE SHALL BE COVERED WITH
COMMON BERMUDA GRASS UNLESS OTHERWISE SHOWN IN THE PLANS.
21. CONTRACTOR SHALL BE RESPONSIBLE FOR IMPLEMENTING AND MAINTAINING EROSION
CONTROL DEVICES DURING CONSTRUCTION.
22. CONTRACTOR SHALL TAKE ALL OTHER MEASURES TO POSITIVELY PRECLUDE EROSION
MATERIALS FROM LEAVING THE SITE.
23. IN THE EVENT ACTIVE UTILITY SERVICES REQUIRE INTERRUPTION, THE CONTRACTORS
SHALL COORDINATE AND CONSULT WITH THE OWNER OR/OWNERS AND OBTAIN APPROVAL
FROM THEM PRIOR TO SERVICES BEING DISRUPTED.
24. THE CONTRACTOR SHALL AT ALL TIMES CONTROL DUST AND DEBRIS FROM THE
OPERATIONS TO A LEVEL ACCEPTABLE TO FAYETTE COUNTY AND LOCAL BUSINESSES AT
ALL TIMES.
25. TEMPORARY DISCONNECTION, REMOVAL AND/OR REPLACEMENT OF THE FOLLOWING ITEMS
BUT NOT LIMITED TO, FIRE HYDRANTS, WATER METERS, BACK FLOW PREVENTION DEVICES,
VAULTS, MANHOLE AND OTHER POTABLE WATER SYSTEM APPURTENANCES. ASSOCIATED
APPURTENANCES SHALL BE IN STRICT ACCORDANCE WITH THE LATEST FAYETTE COUNTY
STANDARDS AND SPECIFICATIONS. BEFORE CONNECTION, REMOVAL AND/OR REPLACEMENT
OF ANY UTILITIES. THE CONTRACTOR SHALL CONTACT AND OBTAIN APPROVAL FROM
FAYETTE COUNTY PUBLIC WORKS REPRESENTATIVES PRIOR TO CONSTRUCTION.
PROJECT COMPLETION
1. PRIOR TO ACCEPTANCE AND FINAL PAYMENT, CONTRACTOR IS TO PROVIDE AN AS-BUILT SURVEY, WHICH IS A DRAWING PREPARED AND SIGNED BY A REGISTERED LAND SURVEYOR REGISTERED IN
THE STATE OF GEORGIA ILLUSTRATING THE LOCATIONS, DIMENSIONS AND ELEVATIONS OF A
DEVELOPMENT AS IT HAS BEEN CONSTRUCTED FOLLOWING COMPLETION OF CONSTRUCTION ON
DIRECT FIELD MEASUREMENTS AND SHOWN TO SCALE.
LEGEND & SYMBOLS
26. ALL EXCAVATION SHALL BE ADEQUATELY SHORED TO ENSURE WORKER SAFETY. ALL PIPE
LAYING OPERATIONS SHALL COMPLY WITH OSHA REQUIREMENTS FOR TRENCH SAFETY.
27. MAINTENANCE AND TRAFFIC: THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL
ROAD PERMITS FROM FAYETTE COUNTY INCLUDING PROVIDING ANY RESTORATION BONDS.
THE CONTRACTOR SHALL PROVIDE A DETAILED PHASED TRAFFIC CONTROL PLAN BASED
ON THE PROPOSED WORK PHASING AS DETERMINED BY THE CONTRACTOR.
28. 72 HOURS NOTICE IS REQUIRED TO GEORGIA 811 UTILITY PROTECTION CENTER BEFORE
ANY PLANNED DIGGING. HTTP://WWW.GEORGIA811.COM
PROPOSED WATER PIPE
EXISTING WATER LINE
EXISTING MAJOR CONTOUR
EXISTING MINOR CONTOUR
PROPOSED ASPHALT PAVEMENT
PROPOSED CONCRETE
PROPOSED GRAVEL
X X PROPOSED SILT FENCE
W W
20" DIP FW
30" DIP SETTLED WATER
8" SLUDGE DRAIN
6" DIP PLANT UTILITY LINE
24" DIP
W
SD SD
W
W
EXISTING BUILDING
EXISTING CONCRETE
EXISTING GRAVEL DRIVE
E
FH
WV
WM
LP EXISTING LIGHT POLE
EXISTING ELECTRICAL MANHOLE
EXISTING WATER METER
EXISTING WATER VALVE
EXISTING FIRE HYDRANT
EXISTING FLAG POLE
EXISTING MANHOLE
EXISTING ASPHALT DRIVE
CIVIL
CROSSTOWN
AC
ELBOX
ELBOX
ELBOX
ELBOX
ELBOX
EMH
844.47
LP
LP
LP
LP
LP
LP
PM PM
VLTVLT
VLT
VLT
VLT
VLT
VLT
VLT
VLT
VLT
VLT
LOADING
DOCK
BLD
G
FIN
ISH
ED
W
ATER
PU
M P
STATIO
N
BLD
G
SLUDGE
THICKNER
FILTER
BLDG.
FILTER
BLDG.
FLAG POLE
SEDIMENTATION
BASIN
SEDIMENTATION
BASIN
LIME STORAGE TANK
BURIED FUEL
TANK
CLEARWELL
GPC
BACKWASH
METER PIT
CHEMICAL
VAULT
6" CP W/ 6
LIME TUBES
ELEC
CONDUIT
C H
EM
IC
AL TR
EN
C H
W W W W W W W
W W
W W
W W
W W
W W
W W
W W
W W
W W W
W W
W W
W W
W W
W W
W
W W W W
W W
W W
W W W W
W W
W
W W W W W
W W
W W
W W
W W
W W
W W
W W
WWWWWWWWWWWWWW
W
SD
SD
SD
SD SD
30" DIP SETTLED WATER
8" SLUDGE DRAIN
" D
IP
F
W
6" DIP PLANT UTILITY LINE
6" D
IP TH
IC
KEN
ER
D
EC
AN
T R
EC
YC
LE
ABAN
D
O N
ED
6" D
IP
SD
SD
SD
SD
SD
SD
8" SLU
D
G E W
ITH
D
R
AW
L LIN
E
8" SLU
D
G E D
R
AIN
1%
SLO
PE
INV EL: 841.96
INV EL: 840.65
24" DIP FILTER EFFLUENT
20" DIP FW
6" DIP
POST FLASH MIX
FILTER FILTER FILTER FILTER
8" SLUDGE WITHDRAWAL LINE
6" CHEM FEED LINE
SIDEWALK
FILTER FILTER FILTER FILTER
EXISTIN
G
ASPH
ALT
AC
C
ESS D
R
IVE
30" D
IP SETTLED
W
ATER
W W
W W
W
User:JRI00725 Spec:AUS-NCSMOD File:C:\USERS\JRI00725\DC\ACCDOCS\ARCADIS ACC US\AUS-30171943-FCWS WTP CHEMICAL UPGRADES\PROJECT FILES\10_WIP\10T_ARC_CIVIL\CROSSTOWN\XREF\CROSSTOWN_CHM-UPG_BASE.DWG Scale:1:1 SavedDate:6/5/2026 Time:14:24 Plot Date: Raj, Joel; 6/5/2026; 20:12 ; Layout:C-02 CT
Know what's below.
before you dig.Call
R
B
C
D
E
1 2 3 4 5 6
SEALS
CONSULTANTS
SEALS
Owner
WTP CHEMICAL UPGRADES
FAYETTE COUNTY, GEORGIA
REVISIONS
LEGAL ENTITY:
ARCADIS U.S., INC.
2839 PACES FERRY RD. SE# 1000
ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
COPYRIGHT: ARCADIS U.S., INC.
PROJECT STATUS:
PROJECT NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SHEET TITLE
SHEET NO.: OF
SCALE:
DRAWING NO.:
BAR IS ONE INCH ON
UNREDUCED DRAWING
0 1
NO. DATE ISSUED FOR BY
30240979
JULY 2026
J. SWAIM
FOR BID
N. NIA
N. NIA
C-02
EXISTING CONDITIONS
AND DEMOLITION
PLAN
DEMO EXISTING
CONCRETE PAD
REMOVE & RELOCATE
EXISTING LIME TANK STAIR
NOTES:
1. ALL UNDERGROUND UTILITY LOCATIONS SHOULD BE CONSIDERED APPROXIMATE. THERE IS NO
GUARANTEE THAT ALL UTILITIES, WHETHER FUNCTIONAL OR ABANDONED WITHIN THE PROJECT
AREA, ARE SHOWN ON THIS DRAWING. CONTRACTOR SHALL VERIFY EXACT LOCATION OF ALL
UNDERGROUND UTILITIES BEFORE STARTING WORK, AND SHALL BE RESPONSIBLE FOR ALL
DAMAGE RESULTING FROM THIS WORK.
SAW CUT AND
DEMOLISH ASPHALT
ROADWAY AND CURB
DEMOLISH HVAC
CONCRETE PAD
CIVIL
DI-
RIM:844.09
ELBOX
ELBOX
ELBOX
ELBOX
ELBOX
EMH
844.47
FH
LP
LP
LP
LP
LP
LP
PM PM
WM
WM
WM
WM
WM
WV
WV
WV
WV
WV
VLTVLT
VLT
VLT
VLT
VLT
VLT
VLT
VLT
VLT
VLT
LOADING
DOCK
BLD
G
FIN
ISH
ED
W
ATER
PU
M P
STATIO
N
BLD
G
SLUDGE
THICKNER
FILTER
BLDG.
FILTER
BLDG.
FLAG POLE
SEDIMENTATION
BASIN
SEDIMENTATION
BASIN
LIME STORAGE TANK
BURIED FUEL
TANK
CLEARWELL
GPC
BACKWASH
METER PIT
CHEMICAL
VAULT
6" CP W/ 6
LIME TUBES
ELEC
CONDUIT
C H
EM
IC
AL TR
EN
C H
W W W W W W W
W W
W W
W W
W W
W W
W W
W W
W W
W W W
W W
W W
W W
W W
W W
W
W W W W
W W
W W
W W W W
W W
W
W W W W W
W W
W W
W W
W W
W W
W W
W W
WWWWWWWWWWWWWW
W
SD
SD
SD
SD SD
30" DIP SETTLED WATER
8" SLUDGE DRAIN
" D
IP
F
W
6" DIP PLANT UTILITY LINE
6" D
IP TH
IC
KEN
ER
D
EC
AN
T R
EC
YC
LE
ABAN
D
O N
ED
6" D
IP
SD
SD
SD
SD
SD
SD
W
8" SLU
D
G E W
ITH
D
R
AW
L LIN
E
8" SLU
D
G E D
R
AIN
1%
SLO
PE
INV EL: 841.96
INV EL: 840.65
24" DIP FILTER EFFLUENT
843.90
842.47
842.98
20" DIP FW
6" DIP
POST FLASH MIX
FILTER FILTER FILTER FILTER
8" SLUDGE WITHDRAWAL LINE
6" CHEM FEED LINE
SIDEWALK
FILTER FILTER FILTER FILTER
EXISTIN
G
ASPH
ALT
AC
C
ESS D
R
IVE
30" D
IP SETTLED
W
ATER
W W
W W
W
User:JRI00725 Spec:AUS-NCSMOD File:C:\USERS\JRI00725\DC\ACCDOCS\ARCADIS ACC US\AUS-30171943-FCWS WTP CHEMICAL UPGRADES\PROJECT FILES\10_WIP\10T_ARC_CIVIL\CROSSTOWN\XREF\CROSSTOWN_CHM-UPG_BASE.DWG Scale:1:1 SavedDate:6/5/2026 Time:14:24 Plot Date: Raj, Joel; 6/5/2026; 20:17 ; Layout:C-03 CT
Know what's below.
before you dig.Call
R
B
C
D
E
1 2 3 4 5 6
SEALS
CONSULTANTS
SEALS
Owner
WTP CHEMICAL UPGRADES
FAYETTE COUNTY, GEORGIA
REVISIONS
LEGAL ENTITY:
ARCADIS U.S., INC.
2839 PACES FERRY RD. SE# 1000
ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
COPYRIGHT: ARCADIS U.S., INC.
PROJECT STATUS:
PROJECT NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SHEET TITLE
SHEET NO.: OF
SCALE:
DRAWING NO.:
BAR IS ONE INCH ON
UNREDUCED DRAWING
0 1
NO. DATE ISSUED FOR BY
30240979
JULY 2026
J. SWAIM
FOR BID
N. NIA
N. NIA
C-03
OVERALL SITE LAYOUT
AND YARD PIPING
PLAN
3"-DR-PVC
DAYLIGHT THROUGH CURB
IE: 842.0
SEE NOTE 2
NEW
SIDEWALK
SODIUM HYPOCHLORITE (SHC)
BULK CHEMICAL SYSTEM
SEE SHEET M-07
CHEMICAL PULL BOX
SEE NOTE 1
2"-SWE-PVC
(IN 6" PVC CASING)
2"-SHC-PVC
(IN 6" PVC CASING)
CORE INTO EXISTING CHEMICAL TRENCH
FOR THE FOLLOWING CONNECTIONS
2"-SWE-PVC
2"-SHC-PVC
2"-PLW-PVC
3"-SHC-PVC
FILL LINE
CHEMICAL FILL STATION
SEE DETAIL SHEET M-15
FLUORIDE BULK
CHEMICAL SYSTEM
SEE SHEET M-06
SEE NOTE 3
2"-PLW-PVC
3" BALL VALVE
AND VALVE BOX
NOTES:
1. SEE CHEMICAL PULL BOX DETAIL ON SHEET M-10. TOP SHALL BE 3" ABOVE FINISHED GRADE.
2. FLUSH IE OF 3"-DR-PVC WITH THE ELEVATION OF BOTTOM OF EXISTING CURB.
3. CONTRACTOR TO REPURPOSE EXISTING 6" CASING FOR PROPOSED HYPO FEED SEE SHEET M-9 &
M-12 FOR DETAIL. CONTRACTOR TO VERIFY ROUTE, LINE SIZE, CASING SIZE AND
LOCATION OF EXISTING CASING PRIOR TO ORDERING MATERIAL AND NOTIFY ENGINEER OF ANY
DISCREPANCIES.
4. CONTRACTOR TO POT HOLE AND VERIFY LOCATION OF EXISTING 20" SETTLED WATER LINE PRIOR
TO ORDERING EQUIPMENT. CONTACT ENGINEER OVER DISCREPANCIES.
5. CONTRACTOR TO POT HOLE AND VERIFY LOCATION OF EXISTING 8" PROCESS DRAIN PRIOR TO
ORDERING EQUIPMENT. CONTACT ENGINEER OVER DISCREPANCIES.
6. CONTRACTOR TO POT HOLE AND VERIFY LOCATION OF EXISTING 6" DUCTILE IRON PLANT WATER
PRIOR TO ORDERING EQUIPMENT. CONTACT ENGINEER OVER DISCREPANCIES IN LINE SIZE
LOCATION OR MATERIAL. WATER LINE TO BE ENCASED IN CONCRETE BELOW PROPOSED FLUORIDE
BULK STORAGE STRUCTURE.
3"-DR-PVC
DAYLIGHT THROUGH
LOADING DOCK WALL
IE:841.8
CHEMICAL FILL STATION
SEE DETAIL SHEET M-15
2"-PLW-PVC
CORE TO EXISTING
CHEMICAL TRENCH
2"-HFSA-PVC
FILL LINE
SEE NOTE 4
SEE NOTE 5
CONNECT TO EXISTING 6" PLANT WATER
LINE W/ 6"X2" TEE & 2" GATE VALVE W/
VALVE BOX AND CONCRETE BLOCKING
SEE SHEET M-07 FOR SMALL DIAMETER
PIPE CONTINUATION SEE NOTE 6.
CORE EXISTING MANHOLE
AND PROVIDE MANHOLE
BOOT CONNECTION
4"-DR-PVC MIN GRADE 1%
CONTRACTOR TO COORDINATE GRADE
PIPING TO BE BEDDED IN MINIMUM 6"
#57 STONE BELOW THE PIPE AND
FILLED TO THE SPRING LINE
WYE & CLEANOUT
45° BEND
CIVIL
5.0%
1.0%
843.35
845.81
846.61
845.02 845.06844.09 843.96
1.0% 1.0%
842.90
842.90
844.68844.60
844.67
844.42 844.60
842.86
842.86
843.21
843.32
844.10
843.67
843.62843.84
843.79
843.11
844.67
844.07
844.09843.90
842.47
843.58843.62
842.81
843.76
843.67
843.92
9.7%
.0
8 2
2.8%
842.98
843.92
843.96
844.00 843.45
1.0%
844.65
844.67
846.80
846.65
845.88
845.78
HP=846.58
1.
5%
1.5%
.8
3.6%
1.5% 1.1%
1.
5%
5.
2%
3.2%
4.
9%
PAD
844.67
843.47
843.16
-1.0%
845.10
844.14 844.09
845.10
STAKING POINTS
POINT #
DESCRIPTION
WALL NW CORNER
WALL NE CORNER
WALL SW CORNER
WALL SE CORNER
SIDEWALK NW CORNER
SIDEWALK SW CORNER
CURB NW CORNER
WALL NE CORNER
WALL SW CORNER
WALL SE CORNER
LANDING NE CORNER
LANDING SE CORNER
NORTHING
1224473.67
1224488.66
1224442.93
1224457.92
1224454.04
1224439.77
1224454.97
1224460.08
1224448.72
1224451.10
1224459.75
1224457.55
EASTING
2171895.08
2171911.18
2171923.69
2171939.80
2171875.02
2171888.20
2171874.16
2171879.65
2171885.44
2171888.01
2171904.39
2171906.44
STAKING POINTS
POINT #
DESCRIPTION
SIDEWALK SE CORNER
PAD NW CORNER
PAD SW CORNER
PAD W CORNER
PAD N CORNER
PAD S CORNER
PAD E CORNER
NORTHING
1224414.70
1224425.96
1224420.07
1224407.40
1224423.91
1224393.00
1224409.08
EASTING
2171873.28
2171851.93
2171857.32
2171829.24
2171846.42
2171842.39
2171859.99
User:JRI00725 Spec:AUS-NCSMOD File:C:\USERS\JRI00725\DC\ACCDOCS\ARCADIS ACC US\AUS-30171943-FCWS WTP CHEMICAL UPGRADES\PROJECT FILES\10_WIP\10T_ARC_CIVIL\CROSSTOWN\XREF\CROSSTOWN_CHM-UPG_BASE.DWG Scale:1:1 SavedDate:6/5/2026 Time:14:24 Plot Date: Raj, Joel; 6/5/2026; 20:18 ; Layout:C-04 CT
Know what's below.
before you dig.Call
R
B
C
D
E
1 2 3 4 5 6
SEALS
CONSULTANTS
SEALS
Owner
WTP CHEMICAL UPGRADES
FAYETTE COUNTY, GEORGIA
REVISIONS
LEGAL ENTITY:
ARCADIS U.S., INC.
2839 PACES FERRY RD. SE# 1000
ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
COPYRIGHT: ARCADIS U.S., INC.
PROJECT STATUS:
PROJECT NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SHEET TITLE
SHEET NO.: OF
SCALE:
DRAWING NO.:
BAR IS ONE INCH ON
UNREDUCED DRAWING
0 1
NO. DATE ISSUED FOR BY
30240979
JULY 2026
J. SWAIM
FOR BID
N. NIA
N. NIA
C-04
GRADING AND STAKING
PLAN
CHEMICAL FILL STATION
CONCRETE PAD
TANK CONTAINMENT STRUCTURE
(REFER TO STRUCTURAL
DRAWINGS FOR ELEVATIONS)
3'X3' CONCRETE
LANDING PAD
4-FT WIDE CONCRETE
SIDEWALK, MATCHES EXISTING
BACK OF CURB ELEVATION
3-FT WIDE CONCRETE
SIDEWALK
PROPOSED
CONCRETE PAD
PROPOSED 8-IN WIDE
CONCRETE WALL
(SEE STRUCTURAL DRAWINGS)
EXISTING GRADE
SECTION1
4-FT WIDE CONCRETE
SIDEWALK, MATCHES EXISTING
BACK OF CURB ELEVATION
3' -0
4'-0"
4'-0"
8-IN CONCRETE CURB, TOP MATCHES
EXISTING CHEMICAL TRENCH ELEVATION
SEE NOTE 1
LIMITS OF
GRADING
SIDEWALK MATCHES EXISTING
CHEMICAL TRENCH ELEVATION
8-IN WIDE
CONCRETE WALL
TOP EL.= 845.10
PROPOSED
SIDEWALK
NOTES:
1. PROVIDE 8-IN WIDE CONCRETE CURB TRANSITION AT END OF SIDEWALK.
TOP ELEVATION TO MATCH EXISTING CHEMICAL TRENCH ELEVATION.
SEE NOTE 1
PROPOSED ELEVATION
EXISTING ELEVATION
GRASS LINED
SWALE CENTERLINE
GRASS LINED
SWALE CENTERLINE
TANK CONTAINMENT STRUCTURE
(REFER TO STRUCTURAL
DRAWINGS FOR ELEVATIONS)
2'-0"
CONSTRUCTION JOINT FOR
CONCRETE STAIR LANDING PAD
TO CONCRETE SIDEWALK
'-1
7/
8"
CIVIL
DI-
RIM:844.09
ELBOX
ELBOX
ELBOX
ELBOX
ELBOX
EMH
844.47
FH
LP
LP
LP
LP
LP
LP
PM PM
WM
WM
WM
WM
WM
WV
WV
WV
WV
WV
VLTVLT
VLT
VLT
VLT
VLT
VLT
VLT
VLT
VLT
VLT
LOADING
DOCK
BLD
G
FIN
ISH
ED
W
ATER
PU
M P
STATIO
N
BLD
G
SLUDGE
THICKNER
FILTER
BLDG.
FILTER
BLDG.
FLAG POLE
SEDIMENTATION
BASIN
SEDIMENTATION
BASIN
LIME STORAGE TANK
BURIED FUEL
TANK
CLEARWELL
GPC
BACKWASH
METER PIT
CHEMICAL
VAULT
6" CP W/ 6
LIME TUBES
ELEC
CONDUIT
W W W W W W W
W W
W W
W W
W W
W W
W W
W W
W W
W W W
W W
W W
W W
W W
W W
W
W W W W
W W
W W
W W W W W W
W W
W
W W W W W
W W
W W
W W
W W
W W
W W
W W
WWWWWWWWWWWWWW
W
SD
SD
SD
SD SD
30" DIP SETTLED WATER
8" SLUDGE DRAIN
" D
IP
F
W
6" DIP PLANT UTILITY LINE
6" D
IP TH
IC
KEN
ER
D
EC
AN
T R
EC
YC
LE
ABAN
D
O N
ED
6" D
IP
SD
SD
SD
SD
SD
SD
SD
SD SD SD SD SD SD
W
INV EL: 841.96
INV EL: 840.65
24" DIP FILTER EFFLUENT
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
842.86
842.86
20" DIP FW
6" DIP
POST FLASH MIX
FILTER FILTER FILTER FILTER
6" CHEM FEED LINE
SIDEWALK
FILTER FILTER FILTER FILTER
EXISTIN
G
ASPH
ALT
AC
C
ESS D
R
IVE
W W
W W
W
User:JRI00725 Spec:AUS-NCSMOD File:C:\USERS\JRI00725\DC\ACCDOCS\ARCADIS ACC US\AUS-30171943-FCWS WTP CHEMICAL UPGRADES\PROJECT FILES\10_WIP\10T_ARC_CIVIL\CROSSTOWN\XREF\CROSSTOWN_CHM-UPG_BASE.DWG Scale:1:1 SavedDate:6/5/2026 Time:14:24 Plot Date: Raj, Joel; 6/5/2026; 20:20 ; Layout:C-05 CT
Know what's below.
before you dig.Call
R
B
C
D
E
1 2 3 4 5 6
SEALS
CONSULTANTS
SEALS
Owner
WTP CHEMICAL UPGRADES
FAYETTE COUNTY, GEORGIA
REVISIONS
LEGAL ENTITY:
ARCADIS U.S., INC.
2839 PACES FERRY RD. SE# 1000
ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
COPYRIGHT: ARCADIS U.S., INC.
PROJECT STATUS:
PROJECT NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SHEET TITLE
SHEET NO.: OF
SCALE:
DRAWING NO.:
BAR IS ONE INCH ON
UNREDUCED DRAWING
0 1
NO. DATE ISSUED FOR BY
30240979
JULY 2026
J. SWAIM
FOR BID
N. NIA
N. NIA
C-05
ES&C PLAN
Sd1- NS TYPE-B
COMPOST FILTER SOCK
CAN BE REMOVED AND
RE-INSTALLED AS NEEDED
Sd1- NS TYPE-B
COMPOST FILTER SOCK
CAN BE REMOVED AND
RE-INSTALLED AS NEEDED
CIVIL
User:JRI00725 Spec:AUS-NCSMOD File:C:\USERS\JRI00725\DC\ACCDOCS\ARCADIS ACC US\AUS-30171943-FCWS WTP CHEMICAL UPGRADES\PROJECT FILES\10_WIP\10T_ARC_CIVIL\CROSSTOWN\XREF\DETAILS_CT.DWG Scale:1:1 SavedDate:6/5/2026 Time:14:24 Plot Date: Raj, Joel; 6/5/2026; 20:23 ; Layout:C-06 CT before you dig.Call
R
B
C
D
E
1 2 3 4 5 6
SEALS
CONSULTANTS
SEALS
Owner
WTP CHEMICAL UPGRADES
FAYETTE COUNTY, GEORGIA
REVISIONS
LEGAL ENTITY:
ARCADIS U.S., INC.
2839 PACES FERRY RD. SE# 1000
ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
COPYRIGHT: ARCADIS U.S., INC.
PROJECT STATUS:
PROJECT NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SHEET TITLE
SHEET NO.: OF
SCALE:
DRAWING NO.:
BAR IS ONE INCH ON
UNREDUCED DRAWING
0 1
NO. DATE ISSUED FOR BY
30240979
JULY 2026
J. SWAIM
FOR BID
N. NIA
N. NIA
C-06
EROSION AND
SEDIMENT CONTROL
NOTES & DETAILS
SIDE VIEW
FRONT VIEW
NOTES:
1. USE STEEL OR WOOD POSTS OR AS SPECIFIED BY THE EROSION, SEDIMENTATION, AND
POLLUTION CONTROL PLAN.
2. SILT FENCE - TYPE SENSITIVE (Sd1-S) SHALL MEET THE SPECIFICATIONS OF SILT FENCE, TYPE C
AS DESCRIBED IN SECTION 171 OF THE "GDOT STANDARD SPECIFICATIONS CONSTRUCTION OF
TRANSPORTATION SYSTEMS", 2013 EDITION.
3. Sd1-S = TYPE C SILT FENCE.
SILT FENCE - TYPE SENSITIVE
N.T.S.
DEFINITION
CONTROLLING SURFACE AND AIR MOVEMENT OF DUST ON CONSTRUCTION SITES, ROADS, AND DEMOLITION SITES.
CONDITIONS
THIS PRACTICE IS APPLICABLE TO AREAS SUBJECT TO SURFACE AND AIR MOVEMENT OF DUST WHERE ON AND OFF-SITE DAMAGE
MAY OCCUR WITHOUT TREATMENT.
METHOD AND MATERIALS
A. TEMPORARY METHODS
MULCHES. SEE STANDARD DS1 - DISTURBED AREA STABILIZATION (WITH MULCHING ONLY). SYNTHETIC RESINS MAY BE USED INSTEAD OF ASPHALT TO BIND MULCH MATERIAL. REFER TO STANDARD TB-TACKIFIERS AND BINDERS. RESINS SUCH AS
CURASOL OR TERRATACK SHOULD BE USED ACCORDING TO MANUFACTURER'S RECOMMENDATIONS.
VEGETATIVE COVER. SEE STANDARD DS2 - DISTURBED AREA STABILIZATION (WITH TEMPORARY SEEDING).
SPRAY-ON ADHESIVES. THESE ARE USED ON MINERAL SOILS (NOT EFFECTIVE ON MUCK SOILS). KEEP TRAFFIC OFF THESE
AREAS. REFER TO STANDARD TB-TACKIFIERS AND BINDERS.
TILLAGE. THIS PRACTICE IS DESIGNED TO ROUGHEN AND BRING CLODS TO THE SURFACE. IT IS AN EMERGENCY MEASURE WHICH SHOULD BE USED BEFORE WIND EROSION STARTS. BEGIN PLOWING ON WINDWARD SIDE OF SITE. CHISEL-TYPE PLOWS SPACED ABOUT 12 INCHES APART, SPRING-TOOTHED HARROWS, AND SIMILAR PLOWS ARE EXAMPLES OF EQUIPMENT WHICH
MAY PRODUCE THE DESIRED EFFECT.
IRRIGATION. THIS IS GENERALLY DONE AS AN EMERGENCY TREATMENT. SITE IS SPRINKLED WITH WATER UNTIL THE SURFACE
IS WET. REPEAT AS NEEDED.
BARRIERS. SOLID BOARD FENCES, SNOW FENCES, BURLAP FENCES, CRATE WALLS, BALES OF HAY AND SIMILAR MATERIAL CAN BE USED TO CONTROL AIR CURRENTS AND SOIL BLOWING. BARRIERS PLACED AT RIGHT ANGLES TO PREVAILING CURRENTS AT INTERVALS OF ABOUT 15 TIMES THEIR HEIGHT ARE EFFECTIVE IN CONTROLLING WIND EROSION.
CALCIUM CHLORIDE. APPLY AT RATE THAT WILL KEEP SURFACE MOIST. MAY NEED RETREATMENT.
B. PERMANENT METHODS
PERMANENT VEGETATION. SEE STANDARD DS3 -DISTURBED AREA STABILIZATION (WITH PERMANENT VEGETATION). EXISTING
TREES AND LARGE SHRUBS MAY AFFORD VALUABLE PROTECTION IF LEFT IN PLACE.
TOPSOILING. THIS ENTAILS COVERING THE SURFACE WITH LESS EROSIVE SOIL MATERIAL. SEE STANDARD TP - TOPSOILING.
STONE. COVER SURFACE WITH CRUSHED STONE OR COARSE GRAVEL. SEE STANDARD CR-CONSTRUCTION ROAD
STABILIZATION.
Du
DUST CONTROL ON DISTURBED AREAS
2/1-6/15
3/15-6/1
1/1-12/31
4 LBS.
40 LBS.
75 LBS.1.7 POUNDS
0.1 POUND
0.9 POUNDSWITCH GRASS
LESPEDEZA
LOVE GRASS
WEEPING
4/1-7/1
1/1-12/31
2/15-7/1
BLOCK SOD
ONLY
60 LBS.
10 LBS.
ONLY
1.4 POUNDS
BLOCK SOD
0.2 POUND
BAHIA
BERMUDA
CENTIPEDE
SEEDING RATES FOR
PERMANENT SEEDING
* UNUSUAL SITE CONDITIONS MAY REQUIRE HEAVIER SEEDING RATES
** SEEDING DATES MAY NEED TO BE ALTERED TO FIT TEMPERATURE
VARIATIONS AND CONDITIONS.
SPECIES RATE PerRATE Per 1,000 sq.ft. Acre *
PLANTING
DATES **
MULCHING
MULCH IS REQUIRED FOR ALL PERMANENT VEGETATION APPLICATIONS.
MULCH APPLIED TO SEEDED AREAS SHALL ACHIEVE 75% SOIL COVER. SELECT
THE MULCHING MATERIAL FROM THE FOLLOWING AND APPLY AS INDICATED:
1. DRY STRAW OR DRY HAY OF GOOD QUALITY AND FREE OF WEED SEEDS CAN
BE USED. DRY STRAW SHALL BE APPLIED AT THE RATE OF 2 TONS PER ACRE.
DRY HAY SHALL BE APPLIED AT A RATE OF 2 1/2 TONS PER ACRE.
2. WOOD CELLULOSE MULCH OR WOOD PULP FIBER SHALL BE USED WITH
HYDRAULIC SEEDING. IT SHALL BE APPLIED AT THE RATE OF 500 POUNDS PER
ACRE. DRYSTRAW OR DRY HAY SHALL BE APPLIED (AT THE RATE INDICATED
ABOVE) AFTER HYDRAULIC SEEDING.
3. ONE THOUSAND POUNDS OF WOOD CELLULOSE OR WOOD PULP FIBER,
WHICH INCLUDES A TACKIFIER, SHALL BE USED WITH HYDRAULIC SEEDING ON
SLOPES 3/4:1 OR STEEPER.
4. SERICEA LESPEDEZA HAY CONTAINING MATURE SEED SHALL BE APPLIED AT
A RATE OF THREE TONS PER ACRE.
5. PINE STRAW OR PINE BARK SHALL BE APPLIED AT A THICKNESS OF 3 INCHES
FOR BEDDING PURPOSES. OTHER SUITABLE MATERIALS IN SUFFICIENT
QUANTITY MAY BE USED WHERE ORNAMENTALS OR OTHER GROUND COVERS
ARE PLANTED. THIS IS NOT APPROPRIATE
FOR SEEDED AREAS.
6. WHEN USING TEMPORARY EROSION CONTROL BLANKETS OR BLOCK SOD,
MULCH IS NOT REQUIRED.
7. BITUMINOUS TREATED ROVING MAY BE APPLIED ON PLANTED AREAS ON
SLOPES, IN DITCHES OR DRY WATERWAYS TO PREVENT EROSION. BITUMINOUS
TREATED ROVING SHALL BE APPLIED WITHIN 24 HOURS AFTER AN AREA HAS
BEEN PLANTED. APPLICATION RATES AND MATERIALS MUST MEET GEORGIA
DEPARTMENT OF TRANSPORTATION SPECIFICATIONS.
WOOD CELLULOSE AND WOOD PULP FIBERS SHALL NOT CONTAIN
GERMINATION OR GROWTH INHIBITING FACTORS. THEY SHALL BE EVENLY
DISPERSED WHEN AGITATED IN WATER. THE FIBERS SHALL CONTAIN A DYE TO
ALLOW VISUAL METERING AND AID IN UNIFORM APPLICATION DURING SEEDING.
APPLYING MULCH
STRAW OR HAY MULCH WILL BE SPREAD UNIFORMLY WITHIN 24 HOURS AFTER
SEEDING AND/OR PLANTING. THE MULCH MAY BE SPREAD BY BLOWER-TYPE
SPREADING EQUIPMENT, OTHER SPREADING EQUIPMENT OR BY HAND. MULCH
SHALL BE APPLIED TO COVER 75% OF THE SOIL SURFACE.
WOOD CELLULOSE OR WOOD FIBER MULCH SHALL BE APPLIED UNIFORMLY
WITH HYDRAULIC SEEDING EQUIPMENT.
ANCHORING MULCH
ANCHOR STRAW OR HAY MULCH IMMEDIATELY AFTER APPLICATION BY ONE OF
THE FOLLOWING METHODS:
1. EMULSIFIED ASPHALT CAN BE (A) SPRAYED UNIFORMLY ONTO THE MULCH
AS IT IS EJECTED FROM THE BLOWER MACHINE OR (B) SPRAYED ON THE
MULCH IMMEDIATELY FOLLOWING MULCH APPLICATION WHEN STRAW OR HAY
IS SPREAD BY METHODS OTHER THAN SPECIAL BLOWER EQUIPMENT.
THE COMBINATION OF ASPHALT EMULSION AND WATER SHALL CONSIST OF A
HOMOGENEOUS MIXTURE SATISFACTORY FOR SPRAYING. THE MIXTURE SHALL
CONSIST OF 100 GALLONS OF GRADE SS-1H OR CSS-1H EMULSIFIED ASPHALT
AND 100 GALLONS OF WATER PER TON OF MULCH.
CARE SHALL BE TAKEN AT ALL TIMES TO PROTECT STATE WATERS, THE
PUBLIC, ADJACENT PROPERTY, PAVEMENTS, CURBS, SIDEWALKS, AND ALL
OTHER STRUCTURES FROM ASPHALT DISCOLORATION.
2. HAY AND STRAW MULCH SHALL BE PRESSED INTO THE SOIL IMMEDIATELY
AFTER THE MULCH IS SPREAD. A SPECIAL “PACKER DISK”' OR DISK HARROW
WITH THE DISKS SET STRAIGHT MAY BE USED. THE DISKS MAY BE SMOOTH OR
SERRATED AND SHOULD BE 20 INCHES OR MORE IN DIAMETER AND 8 TO 12
INCHES APART. THE EDGES OF THE DISKS SHALL BE DULL ENOUGH TO PRESS
THE MULCH INTO THE GROUND WITHOUT CUTTING IT, LEAVING MUCH OF IT IN
AN ERECT POSITION. MULCH SHALL NOT BE PLOWED INTO THE SOIL.
3. SYNTHETIC TACKIFIERS OR BINDERS APPROVED BY GDOT SHALL BE
APPLIED IN CONJUNCTION WITH OR IMMEDIATELY AFTER THE MULCH IS
SPREAD. SYNTHETIC TACKIFIERS SHALL BE MIXED AND APPLIED ACCORDING
TO MANUFACTURER'S SPECIFICATIONS. REFER TO TB - TACKIFIERS AND
BINDERS.
4. RYE OR WHEAT CAN BE INCLUDED WITH FALL AND WINTER PLANTINGS TO
STABILIZE THE MULCH. THEY SHALL BE APPLIED AT A RATE OF ONE-QUARTER
TO ONE HALF BUSHEL PER ACRE.
5. PLASTIC MESH OR NETTING WITH MESH NO LARGER THAN ONE INCH BY ONE
INCH MAY BE NEEDED TO ANCHOR STRAW OR HAY MULCH ON UNSTABLE SOILS
AND CONCENTRATED FLOW AREAS. THESE MATERIALS SHALL BE INSTALLED
AND ANCHORED ACCORDING TO MANUFACTURER'S SPECIFICATIONS.
IRRIGATION
IRRIGATION SHALL BE APPLIED AT A RATE THAT WILL NOT CAUSE RUNOFF.
DEFINITION
THE PLANTING OF PERENNIAL VEGETATION SUCH AS TREES, SHRUBS, VINES,
GRASSES, OR LEGUMES ON EXPOSED AREAS FOR FINAL PERMANENT
STABILIZATION. PERMANENT PERENNIAL VEGETATION SHALL BE USED TO
ACHIEVE FINAL STABILIZATION.
CONDITIONS
PERMANENT PERENNIAL VEGETATION IS USED TO PROVIDE A PROTECTIVE
COVER FOR EXPOSED AREAS INCLUDING CUTS, FILLS, DAMS, AND OTHER
DENUDED AREAS.
SPECIFICATIONS
GRADING AND SHAPING
GRADING AND SHAPING MAY NOT BE REQUIRED WHERE HYDRAULIC SEEDING
AND FERTILIZING EQUIPMENT IS TO BE USED. VERTICAL BANKS SHALL BE
SLOPED TO ENABLE PLANT ESTABLISHMENT.
WHEN CONVENTIONAL SEEDING AND FERTILIZING ARE TO BE DONE, GRADE
AND SHAPE WHERE FEASIBLE AND PRACTICAL, SO THAT EQUIPMENT CAN BE
USED SAFELY AND EFFICIENTLY DURING SEEDBED PREPARATION, SEEDING,
MULCHING AND MAINTENANCE OF THE VEGETATION.
CONCENTRATIONS OF WATER THAT WILL CAUSE EXCESSIVE SOIL EROSION
SHALL BE DIVERTED TO A SAFE OUTLET. DIVERSIONS AND OTHER TREATMENT
PRACTICES SHALL CONFORM WITH THE APPROPRIATE STANDARDS AND
SPECIFICATIONS.
SEEDBED PREPARATION
SEEDBED PREPARATION MAY NOT BE REQUIRED WHERE HYDRAULIC SEEDING
AND FERTILIZING EQUIPMENT IS TO BE USED. WHEN CONVENTIONAL SEEDING
IS TO BE USED, SEEDBED PREPARATION WILL BE DONE AS FOLLOWS:
BROADCAST PLANTINGS
1. TILLAGE AT A MINIMUM, SHALL ADEQUATELY LOOSEN THE SOIL TO A
DEPTH OF 4 TO 6 INCHES; ALLEVIATE COMPACTION; INCORPORATE LIME AND
FERTILIZER; SMOOTH AND FIRM THE SOIL; ALLOW FOR THE PROPER
PLACEMENT OF SEED, SPRIGS, OR PLANTS; AND ALLOW FOR THE ANCHORING
OF STRAW OR HAY MULCH IF A DISK IS TO BE USED.
2. TILLAGE MAY BE DONE WITH ANY SUITABLE EQUIPMENT.
3. TILLAGE SHOULD BE DONE ON THE CONTOUR WHERE FEASIBLE.
4. ON SLOPES TOO STEEP FOR THE SAFE OPERATION OF TILLAGE
EQUIPMENT, THE SOIL SURFACE SHALL BE PITTED OR TRENCHED ACROSS THE
SLOPE WITH APPROPRIATE HAND TOOLS TO PROVIDE TWO PLACES 6 TO 8
INCHES APART IN WHICH SEED MAY LODGE AND GERMINATE. HYDRAULIC
SEEDING MAY ALSO BE USED.
INDIVIDUAL PLANTS
1. WHERE INDIVIDUAL PLANTS ARE TO BE SET, THE SOIL SHALL BE PREPARED
BY EXCAVATING HOLES, OPENING FURROWS, OR DIBBLE PLANTING.
2. FOR NURSERY STOCK PLANTS, HOLES SHALL BE LARGE ENOUGH TO
ACCOMMODATE ROOTS WITHOUT CROWDING.
3. WHERE PINE SEEDLINGS ARE TO BE PLANTED, SUBSOIL UNDER THE ROW 36
INCHES DEEP ON THE CONTOUR FOUR TO SIX MONTHS PRIOR TO PLANTING.
SUBSOILING SHOULD BE DONE WHEN THE SOIL IS DRY, PREFERABLY IN
AUGUST OR SEPTEMBER.
PLANTING
HYDRAULIC SEEDING
MIX THE SEED (INNOCULATED IF NEEDED), FERTILIZER, AND WOOD CELLULOSE
OR WOOD PULP FIBER MULCH WITH WATER AND APPLY IN A SLURRY
UNIFORMLY OVER THE AREA TO BE TREATED. APPLY WITHIN ONE HOUR AFTER
THE MIXTURE IS MADE.
CONVENTIONAL SEEDING
SEEDING WILL BE DONE ON A FRESHLY PREPARED AND FIRMED SEEDBED. FOR
BROADCAST PLANTING, USE A CULTIPACKER SEEDER, DRILL, ROTARY SEEDER,
OTHER MECHANICAL SEEDER,
OR HAND SEEDING TO DISTRIBUTE THE SEED UNIFORMLY OVER THE AREA TO
BE TREATED. COVER THE SEED LIGHTLY WITH 1/8 TO 1/4 INCH OF SOIL FOR
SMALL SEED AND 1/2 TO 1 INCH FOR LARGE SEED WHEN USING A
CULTIPACKER OR OTHER SUITABLE EQUIPMENT.
NO-TILL SEEDING
NO-TILL SEEDING IS PERMISSIBLE INTO ANNUAL COVER CROPS WHEN
PLANTING IS DONE FOLLOWING MATURITY OF THE COVER CROP OR IF THE
TEMPORARY COVER STAND IS SPARSE ENOUGH TO ALLOW ADEQUATE
GROWTH OF THE PERMANENT (PERENNIAL) SPECIES. NO-TILL SEEDING SHALL
BE DONE WITH APPROPRIATE NO-TILL SEEDING EQUIPMENT. THE SEED MUST
BE UNIFORMLY DISTRIBUTED AND PLANTED AT THE PROPER DEPTH.
INDIVIDUAL PLANTS
SHRUBS, VINES AND SPRIGS MAY BE PLANTED WITH APPROPRIATE PLANTERS
OR HAND TOOLS. PINE TREES SHALL BE PLANTED MANUALLY IN THE SUBSOIL
FURROW. EACH PLANT SHALL BE SET IN A MANNER THAT WILL AVOID
CROWDING THE ROOTS. NURSERY STOCK PLANTS SHALL BE PLANTED AT THE
SAME DEPTH OR SLIGHTLY DEEPER THAN THEY GREW AT THE NURSERY. THE
TIPS OF VINES AND SPRIGS MUST BE AT OR SLIGHTLY ABOVE THE GROUND
SURFACE. WHERE INDIVIDUAL HOLES ARE DUG, FERTILIZER SHALL BE PLACED
IN THE BOTTOM OF THE HOLE, TWO INCHES OF SOIL SHALL BE ADDED AND THE
PLANT SHALL BE SET IN THE HOLE.
Ds3
DISTURBED AREA STABILIZATION
(WITH PERMANENT VEGETATION)
1/ APPLY IN SPRING FOLLOWING SEEDING.
2/ APPLY IN SPLIT APPLICATIONS WHEN HIGH RATES ARE USED.
3/ APPLY IN 3 SPLIT APPLICATIONS.
4/ APPLY WHEN PLANTS ARE PRUNED.
5/ APPLY TO GRASS SPECIES ONLY.
6/ APPLY WHEN PLANTS GROW TO A HEIGHT OF 2 TO 4 INCHES.
LIME: APPLY AT A RATE OF ONE TON PER ACRE
SEEDING SCHEDULE PERMANENT COVER
FERTILIZER REQUIREMENTS PERMANENT COVER
CIVIL
User:JRI00725 Spec:AUS-NCSMOD File:C:\USERS\JRI00725\DC\ACCDOCS\ARCADIS ACC US\AUS-30171943-FCWS WTP CHEMICAL UPGRADES\PROJECT FILES\10_WIP\10T_ARC_CIVIL\CROSSTOWN\XREF\DETAILS_CT.DWG Scale:1:1 SavedDate:6/5/2026 Time:14:24 Plot Date: Raj, Joel; 6/5/2026; 20:24 ; Layout:C-07 CT before you dig.Call
R
B
C
D
E
1 2 3 4 5 6
SEALS
CONSULTANTS
SEALS
Owner
WTP CHEMICAL UPGRADES
FAYETTE COUNTY, GEORGIA
REVISIONS
LEGAL ENTITY:
ARCADIS U.S., INC.
2839 PACES FERRY RD. SE# 1000
ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
COPYRIGHT: ARCADIS U.S., INC.
PROJECT STATUS:
PROJECT NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SHEET TITLE
SHEET NO.: OF
SCALE:
DRAWING NO.:
BAR IS ONE INCH ON
UNREDUCED DRAWING
0 1
NO. DATE ISSUED FOR BY
30240979
JULY 2026
J. SWAIM
FOR BID
N. NIA
N. NIA
C-07
CIVIL DETAILS
X X X X X
PITCH TO DRAIN
CONCRETE SIDEWALK SECTION3
C-07
6"X6"-10/10 WELDED
WIRE FABRIC
4" CONCRETE DEPTH
5'-0"
UNLESS OTHERWISE NOTED
3" TYP.
CONCRETE CURB
WHERE SHOWN ON PLAN
NOT TO SCALE
COMPACTED SUBGRADE
2" MIN. GRANULAR BASE
1/2" JOINT FILLER
GRAVEL SURFACE DETAIL2
C-07
3" OF #57 STONE
COMPACTED SUBGRADE
NON-WOVEN GEOTEXTILE
FABRIC OR APPROVED EQUAL
NOT TO SCALE
3" OF COMPACTED GRADED AGGREGATE BASE
CONC.
FLOW
PLUG (TYP.)
CONC.
AS PIPE IS LAID
PLACED AND COMPACTED
GRAVEL BACKFILL
OR EARTH
CRUSHED STONE
CONC. PAVEMENT,
PAVEMENT
ABUTTING CONC.
ALL AROUND WHEN
EXPANSION JT.
1/2" PREMOLDED
SQ. LAMPHOLE COVER
TAPPED FOR STUDS(TYP.)
M.J. PLUG AND M.J. FLG.
12"12"
MIN.
6"
MIN.
6"
VA
R
IE
S
45°
6"
TYPICAL DRAIN CLEANOUT DETAIL6
C-07 NOT TO SCALE
D-2T
Bd
OR
(SUITABLE)
SUITABLE BEDDING MATERIAL TO
BE APPROVED BY ENGINEER
SUITABLE BACKFILL MATERIAL TO
BE APPROVED BY ENGINEER
SUITABLE BACKFILL MATERIAL
(IN SHADED AREA) TO BE
COMPACTED BY HAND IN 6" LAYERS
NOTE:
REMOVE LARGE ROCKS FROM
WITHIN 6" BOTTOM OF PIPE
4" 2.00 6" 2.00 8" 2.33 10" 2.50 12" 2.67 15" 3.00 18" 3.25 20" 3.54 24" 3.83
Bd - MAXIMUM TRENCH WIDTH AT
12" ABOVE TOP OF PIPE IF
DITCH IS CUT WIDER THAN Bd
SHOWN THE CONTRACTOR WILL BE
REQUIRED TO INCREASE BEDDING
TO COMPENSATE FOR ADDITIONAL
LOAD ON PIPE AT HIS OWN
EXPENSE.
OPEN AREAS
WATER LINE DETAILS FOR PVC & D.I. PIPE
Bd
TRENCH WIDTH
TOP OF PIPE FEET
PIPE OR CASING
DIA INCHES
USE No. 12 OR 14 INSULATED CAP
WIRE TAPED TO PIPE (PVC PIPE ONLY)
SURFACE
12"
6"
D
EARTH
TRENCH
3" 2.00 2" 2.00
C-07 NOT TO SCALE
ROCK
TRENCH
6" 6"
6"18"
1"
EARTH OR
CONCRETE SLAB
COMPACTED SUBGRADE
2" MIN. MINERAL
AGGREGATE BASE
4000 PSI CONC. TYP.
ASPHALT OR CONCRETE
PAVEMENT - SEE SITE PLAN
1" R
FLOW LINE
NOTE:
PROVIDE TOOLED JOINTS AT 10'-0" O.C. IN ALL CURBS & GUTTERS
1IN / FT
CONCRETE CURB AND GUTTER1
C-07 NOT TO SCALE
1"
1 1/2" SURFACE COURSE,
MODIFIED TYPE "F"
8" GRADED AGGREGATE BASE (GAB)
12" MIN. (COMPACTED
TO 100% STD. MAX. DRY
DENSITY)
PRIME COAT 0.35 GAL/YD (MAX.)
5" ASPHALTIC CONCRETE
INTERMEDIATE COURSE,
MODIFIED TYPE "B"
TACK COAT
STANDARD ASPHALT PAVEMENT4
C-07 NOT TO SCALE
6" (MIN) GRADED AGGREGATE BASE (GAB)
12" MIN. (COMPACTED
TO 100% STD. MAX. DRY
DENSITY)
PRIME COAT 0.35 GAL/YD (MAX.)
TACK COAT
HEAVY DUTY ASPHALT PAVEMENT7
C-07 NOT TO SCALE
1 1/2" (MIN.) ASPHALTIC CONCRETE SURFACE COURSE,
PER GDOT SPECIFICATION SECTION 400
1 1/2" (MIN) ASPHALTIC CONCRETE BINDER
COURSE, PER GDOT SPECIFICATION SECTION 400
NOTE:
ASPHALTIC PAVEMENT SHALL BE INSTALLED IN ACCORDANCE WITH GEORGIA
DOT (GDOT) SPECIFICATIONS. ASPHALTIC TYPE AND MIXES SHALL BE GDOT
APPROVED MIX TYPES.
NOTE:
ASPHALTIC PAVEMENT SHALL BE INSTALLED IN ACCORDANCE WITH GEORGIA
DOT (GDOT) SPECIFICATIONS. ASPHALTIC TYPE AND MIXES SHALL BE GDOT
APPROVED MIX TYPES.
6"
MIN
C
4" MIN
(TYP)
B
3" MIN
(TYP)
A
MIN
6"
BE
AR
IN
G
S U
R
FA
C E
BE
AR
IN
G
SU
R
FA
C
E
PLAN SECTION
CONC THRUST
BLOCK
C -0
MINIMUM 6 MIL.
POLYETHYLENE
PROTECTION BARRIER
UNDISTURBED
EARTH OR FIRM
SUBGRADE
CONCRETE BLOCKING DETAIL FOR TEES8
C-07 NOT TO SCALE
NOTES:
1. MAXIMUM TEST PRESSURE = 1.50 x 150 PSI
2. MINIMUM ALLOWABLE SOIL BEARING
PRESSURE = 2000 PSF
3. BEARING AREA = A x B
4. C SHALL BE GREATER THAN A/2 AND B/2.
5. WHEN POSSIBLE JOINTS TO BE TIED WITH
THREE (3) - 3/4" RODS TO RESTRAINER ON
STRAIGHT PIPE IN LIEU OF THRUST
BLOCKING.
NOMINAL
PIPE SIZE
(IN)
MAXIMUM
PIPE OD
(IN)
REQUIRED
BEARING AREA
(SQ FT)
4 4.80 2
6 6.90 4
8 9.05 7
10 11.10 11
12 13.20 15
14 15.30 21
16 17.40 27
18 19.50 34
CONCRETE BLOCKS FOR
TEES, CAPS AND PLUGS
CIVIL
S
PIPING SYMBOLS VALVE LEGEND
DIAPHRAGM VALVE (DV)
RELIEF VALVE (RV)
PINCH VALVE (PI)
BALL VALVE (BV)
NEEDLE VALVE (NV)
ECCENTRIC PLUG VALVE (PV)
AIR RELEASE VALVE (AR)
FOUR-WAY VALVE (FW)
SUCTION FOOT VALVE (FV)
SLUICE GATE (SL)
GLOBE VALVE (GL)
BALL CHECK VALVE (BC)
MUD VALVE (MD)
THREE-WAY PLUG VALVE (TW)
BUTTERFLY VALVE (BFV)
AIR/VACUUM VALVE (AV)
COMBINATION AIR VALVE (CA)
CHECK VALVE (CV)
GATE VALVE (GV)
CURB STOP (CS)
AUTOMATIC PRESSURE
REDUCING VALVES (PR)
AUTOMATIC PRESSURE
SUSTAINING VALVES (PS)
SLIDE GATE (SG)
SLIDE PLATE (SP)
FC=FAIL CLOSED
FO=FAIL OPEN
SOLENOID VALVE (SV)
TELESCOPING VALVE (TV)
KNIFE GATE VALVE (KV)
BUTTERFLY DAMPER (BD)
SYM PLAN ELEV
NOTES:
1. PIPELINES, VALVES AND EQUIPMENT SHALL BE FURNISHED, FABRICATED, ERECTED AND OTHERWISE INSTALLED TO LINES, ELEVATIONS, LOCATIONS, AND DIMENSIONS AS SHOWN, SPECIFIED OR REQUIRED FOR A COMPLETE INSTALLATION. THE CONTRACTOR SHALL MEASURE ALL DIMENSIONS SHOWN PROPERLY AND SHALL TAKE SUCH FIELD DIMENSIONS AS MAY BE NECESSARY TO PROPERLY INSTALL ALL PIPELINES, VALVES AND EQUIPMENT.
2. ALL PIPELINES, VALVES AND EQUIPMENT SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH CONTRACT DOCUMENTS AND MANUFACTURER'S SPECIFICATIONS, IN A NEAT WORKMANLIKE MANNER, AND IN
ACCORDANCE WITH APPROVED SHOP AND WORKING DRAWINGS.
3. ALL CONSTRUCTION MATERIALS REQUIRING STORAGE SHALL BE STORED IN STRICT CONFORMANCE WITH CONTRACT DOCUMENTS, MANUFACTURER'S SPECIFICATIONS, RECOMMENDATIONS AND INSTRUCTIONS.
4. ALL PIPING 4” IN DIAMETER AND SMALLER IS SHOWN SCHEMATICALLY; CONTRACTOR SHALL PROVIDE ALL PIPE, FITTINGS AND ACCESSORIES NECESSARY FOR A COMPLETE INSTALLATION.
5. SEE INSTRUMENTATION DRAWINGS FOR ALL EQUIPMENT TAG NUMBERS.
6. NOT ALL EXISTING OBSTRUCTIONS/EQUIPMENT MAY BE SHOWN ON PLANS. FIELD VERIFICATION OF EXISTING CONDITIONS IS REQUIRED.
7. REFER TO SECTION 01 14 16 - COORDINATION WITH OWNER'S OPERATIONS FOR TIE IN SCHEDULE.
REDUCER
UNION
CAP OR PLUG
FLANGE
BELL & SPIGOT
BLIND FLANGE
FLEXIBLE CONNECTION
NEW PIPING, EQUIPMENT & STRUCTURES
EXISTING PIPING, EQUIPMENT & STRUCTURES
MECHANICAL JOINT
ABBREVIATIONS
PIPE SERVICE
PIPE MATERIALS
DR DRAIN
CU COPPER
CPVC CHLORINATED POLYVINYL CHLORIDE
PVC POLYVINYL CHLORIDE
RPVC REINFORCED PVC FLEXIBLE HOSE
SS STAINLESS STEEL
ST STEEL
VALVE TYPES
AECV AUTOMATIC ELECTRONIC CONTROL VALVES
ARV AIR RELEASE VALVE
CV CHECK VALVE
PRV PRESSURE REDUCING VALVE
DEMOLITION SYMBOLS
TO BE DEMOLISHED
PHOTO DETAIL, SHEET NUMBER, AND PHOTO ORIENTATION
PHOTO DETAIL SYMBOLS
BV BALL VALVE
PRESSURE GAUGE
DRAIN
EXAMPLE: NEW PIPE LABEL
DIAMETER
(INCHES)
PIPE
SERVICE
PIPE
MATERIAL
EXAMPLE: VALVE LABEL
DIAMETER
(INCHES)
VALVE
TYPE
36" - RW - DI
16" - BFV
INSULATED
- INS
EXAMPLE: FLOW DIRECTION IN PIPE
LS LEVEL SENSOR
OF OVERFLOW
RW RAW WATER
SAM SAMPLE
PER PERMANGANATE (POTASSIUM OR SODIUM)
PW POTABLE WATER
TW TEPID WATER
PLW PLANT WATER
4 M-04
HFSA HYDROFLUOROSILICIC ACID
SD STORM DRAIN
SHC SODIUM HYPOCHLORITE
SW SOFTENED WATER
CW COLD WATER
HW HOT WATER
VT VENT
PHOS PHOSPHATE
Know what's below.
before you dig.Call
R
CONSULTANTS
SEALS
SHEET TITLE
ARCADIS U.S., INC.COPYRIGHT:
DATE:
PROJECT NO.:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SCALE:
SHEET NO.: OF
REVISIONS
E
2 3 4 5 6
D
C
B
A
DRAWING NO.:
PROJECT STATUS:
BAR IS ONE INCH ON
UNREDUCED DRAWING
0 1
ARCADIS U.S., INC.
2839 PACES FERRY RD SUITE 1000
ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
LEGAL ENTITY:
12" = 1'-0"
10-06-2026 14:59:29 Autodesk Docs://AUS-30171943-FCWS WTP Chemical Upgrades/M-3D-CT-HFSA_R22.rvt
E. VAN DEVENTER
M. BHANUMATHI
T. THOMAS
JULY 2026
30240979
M-01
WTP CHEMICAL UPGRADES
FAYETTE COUNTY, GEORGIA
MECHANICAL
MECHANICAL LEGENDS,
SYMBOLS, AND
ABBREVIATIONS
FAYETTE COUNTY,GEORGIA
FOR BID
CROSSTOWN
PHOSPHATE
FEED ROOM FLUORIDE
FEED
ROOM
LIME / ALUM
ROOM
STORAGE
ELECTRIC ROOM
SHOP
LOBBY
MENS LOCKER ROOM
MAINTENANCE
AREA
HALL
LOADING
DOCK
H A
L L
LIME
CONTAINMENT
AREA
C H
E M
IC
A
L T
R E
N C
H
M-05 M-06
DEMO EXISTING
CONCRETE PAD
RELOCATE EXISTING
ALUMINUM STAIRS
BULK
CHLORINE
FEED ROOM
CHLORINATOR
ROOM
RELOCATE
EXISTING
HVAC
DEMOLISH EXISTING EYEWASH
COORDINATE WITH OWNER AND ENGINEER
ON DEMOLITION OF EYE WASH FEED WATER
KMNO4
FEED
ROOM
DEMO ALL
EXISTING
CHLORINATOR
EQUIPMENT
DEMO ALL EXISTING BULK
CHLORINE EQUIPMENT
DEMO EXISTING HOT WATER HEATER.
EXISTING HOT WATER PIPING TO REMAIN. CAP HOT
WATER AT HOT WATER HEATER
EXISTING HOT
WATER
EXISTING EQUALIZATION TANK TO
REMAIN
EXISTING POTABLE
WATER FROM PIPE
GALLERY
EXISTING PLANT
WATER FROM PIPE
GALLERY
DEMOLISH EXISTING
EYEWASH COORDINATE WITH
OWNER AND ENGINEER ON
DEMOLITION OF EYE WASH
FEED WATER
EXISTING
PLANT WATER
EXISTING HOT WATER
EXISTING POTABLE WATER
CONTRACTOR TO VERIFY
LINE SIZE AND LOCATION
REMOVE EXISTING 90 AND REPLACE w/ TEE
FOR FLUORIDE CARRIER WATER
EXISTING PLANT WATER CONTRACTOR TO
VERIFY SIZE AND LOCATION
Know what's below.
before you dig.Call
R
CONSULTANTS
SEALS
SHEET TITLE
ARCADIS U.S., INC.COPYRIGHT:
DATE:
PROJECT NO.:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SCALE:
SHEET NO.: OF
REVISIONS
E
2 3 4 5 6
D
C
B
A
DRAWING NO.:
PROJECT STATUS:
BAR IS ONE INCH ON
UNREDUCED DRAWING
0 1
ARCADIS U.S., INC.
2839 PACES FERRY RD SUITE 1000
ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
LEGAL ENTITY:
1/8" = 1'-0"
10-06-2026 14:59:32 Autodesk Docs://AUS-30171943-FCWS WTP Chemical Upgrades/M-3D-CT-HFSA_R22.rvt
E. VAN DEVENTER
M. BHANUMATHI
T. THOMAS
JULY 2026
30240979
M-02
WTP CHEMICAL UPGRADES
FAYETTE COUNTY, GEORGIA
MECHANICAL
POST - TREATMENT
CHEMICAL BUILDING
OVERALL
EXISTING/DEMOLITION
PLAN
FAYETTE COUNTY,GEORGIA
FOR BID
CROSSTOWN
SCALE: 1/8" = 1'-0"
POST - TREATMENT CHEMICAL BUILDING OVERALL EXISTING/DEMOLITION PLAN
0' 8' 16'4'
NOTES:
1. REFER TO SPECIFICATION 01 11 13 SUMMARY OF WORK AND 01 14 16
COORDINATION WITH OWNER'S OPERATIONS FOR SYSTEM
REPLACEMENT SEQUENCING AND TIE-IN SCHEDULES. COORDINATE
WITH CONSTRUCTION SCHEDULE WITH ENGINEER AND OPERATIONS
TO NOT DISRUPT EXISTING CHEMICAL FEED AND PLANT OPERATIONS
STORAGE
ELECTRIC ROOM
SHOP
LOBBY
MENS LOCKER
ROOM
MAINTENANCE
AREA
FLUORIDE
DOSING
ROOM
HALL
SODIUM HYPO
FEED ROOM
DOCK
HALL
LOADING
DOCK
H A
L L
M-07
LIME
CONTAINMENT
AREA
M-08
M-10
C H
E M
IC
A
L T
R E
N C
H
NEW PLC
M-09
SODIUM HYPO
STORAGE AREA
FLUORIDE BULK
STORAGE AREA
SODIUM HYPO
FILL STATION
FLUORIDE FILL
STATION
30" SETTLED
WATER
24" FILTER TO
WASTE
PRE FILTER HYPO
INJECTION & SPARE
(ON 30", BELOW FEED
ROOM IN PIPE GALLERY)
FLUORIDE
CONNECTION POINT
PHOSPHATE
FEED ROOM
WATER
SOFTENING
ROOM
MECHANICAL
ROOM
EXISTING POTABLE
WATER TO REMAIN
M-13
M-09
M-17
TO POST
TREATMENT
INJECTION VAULT
M-17
POST FILTER HYPO INJECTION
& SPARE (ON 24" IN EXISTING
INJECTION VAULT)
EXISTING, ABANDONED 2" PVC FLUORIDE FEED
LINE. TO BE PLACED BACK IN SERVICE (SEE
CONNECTION SHEET M-11)CONTRACTOR TO
VERIFY LOCATION OF EXISTING FEED LINE AND
FLUSH LINE PRIOR TO CONNECTING NEW
FLUORIDE SERVICE. CONTRACTOR TO SUBMIT
FLUSHING PLAN TO ENGINEER FOR APPROVAL
Know what's below.
before you dig.Call
R
CONSULTANTS
SEALS
SHEET TITLE
ARCADIS U.S., INC.COPYRIGHT:
DATE:
PROJECT NO.:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SCALE:
SHEET NO.: OF
REVISIONS
E
2 3 4 5 6
D
C
B
A
DRAWING NO.:
PROJECT STATUS:
BAR IS ONE INCH ON
UNREDUCED DRAWING
0 1
ARCADIS U.S., INC.
2839 PACES FERRY RD SUITE 1000
ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
LEGAL ENTITY:
3/32" = 1'-0"
10-06-2026 14:59:41 Autodesk Docs://AUS-30171943-FCWS WTP Chemical Upgrades/M-3D-CT-HFSA_R22.rvt
E. VAN DEVENTER
M. BHANUMATHI
T. THOMAS
JULY 2026
30240979
M-03
WTP CHEMICAL UPGRADES
FAYETTE COUNTY, GEORGIA
MECHANICAL
POST - TREATMENT
CHEMICAL BUILDING
OVERALL PLAN
FAYETTE COUNTY,GEORGIA
FOR BID
CROSSTOWN
SCALE: 3/32" = 1'-0"
POST-TREATMENT CHEMICAL BUILDING OVERALL PLAN
0' 16' 24'8'
STORAGEELECTRIC ROOM
SHOP
LOBBY
MENS LOCKER ROOM
MAINTENANCE AREA
FLUORIDE
DOSING
ROOM
HALL
SODIUM HYPO
FEED ROOM
DOCK
HALL
LOADING
DOCK
H A
L L
M-07
LIME
CONTAINMENT
AREA
M-08
M-10
C H
E M
IC
A
L T
R E
N C
H
TO POST TREATMENT
INJECTION VAULT
THROUGH EXISTING
CASING & PULL BOXES
NEW PLC
GENERAL PLUMBING NOTES:
1. EXISTING PLUMBING NOT SHOWN FOR CLARITY. CONTRACTOR TO FIELD VERIFY
AND SUBMIT A ROUTING PLAN FOR PROPOSED PLUMBING
2. ALL TEPID WATER TO BE HEAT TRACE AND INSULATED W/ TEMPERATURE
MAINTENANCE CABLE
EXISTING
NEUTRALIZATION TANK
2"-TW-CU
1 1/4"-TW-CU
2"-TW-CU
2"-TW-CU
BURIED
RELOCATE EXISTING EYEWASH
TO PHOSPHATE ROOM
EXISTING 2 1/2"
FROM BASEMENT
2"-TW-CU
INSTALLED
IN CHEMICAL
TRENCH
M-09
SODIUM HYPO
STORAGE AREA
FLUORIDE BULK
STORAGE AREA
MECHANICAL
ROOM
2"-PLW-PVC
2"-SWE-PVC
2"-PLW-PVC
NON-FREEZE
EYEWASH &
SHOWER
FROST RESISTANT
HYDRANT
WATER
HOSE RACK
M-21
M-20
M-22
NON-FREEZE
EYEWASH &
SHOWER
FROST
RESISTANT
HYDRANT
WATER
HOSE RACK
M-21
M-20
M-22
EXISTING 6" PLANT WATER
CONTRACTOR TO POTHOLE
AND VERIFY LINE SIZE,
DEPTH AND LOCATION.
COORDINATE WITH
ENGINEER OVER
DISCREPANCI…