260424 - Forest Hills Nature Center - Bid set - Civil.pdf
PDF 1 MB Posted
- Attached to
- Forest Hill Nature Center - New Building
- Solicitation number
- RFP GIR 260000001926 2
- Issued by
- Ingham County, Michigan
About this file
This is a civil engineering bid set document for the Forest Hills Nature Center New Building project located at 1297 N Rich Road, Alma, Michigan 48801, in Seville Township, Gratiot County. The document contains detailed technical drawings and specifications for wastewater and drainage infrastructure systems required for the new nature center facility. Key components specified include a duplex sump pump station with dual pumps featuring redundant high water and low water alarms, a lift station with specific operational sequencing, a septic tank system designed for H-25 loading with 0.0 to 3.0 feet of earth cover per AASHTO 17th edition and ASTM specifications, and a drain field system measuring 40 feet in width. The document details all piping specifications including Schedule 80 PVC pipe with tracer wire and warning tape for force mains, perforated HDPE N12 pipe for cooling tower drains, and Schedule 40 PVC piping for various lateral connections. Concrete specifications require 5000 PSI at 28 days with reinforcement per ASTM A-615 and A-496 standards.
The bid set provides comprehensive technical specifications and design criteria based on Mid-Michigan Health Department guidelines for septic and drainage systems. All drawings are presented at various scales with detailed elevation references, dimensions, and materials callouts necessary for contractor bidding and construction. The contractor is responsible for providing and installing all controls on the building to meet the specified sequence of operations for the pump station. No pricing information, bid deadlines, award dates, or contract terms are included in this civil engineering document.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C-4
GENERAL NOTES
1. PIPE/ FORCE MAIN - SCHEDULE 80 PVC WITH
TRACER WIRE AND WARNING TAPE.
2. COOLING TOWER DRAIN - PERFORATED HDPE
N12 PIPE.
EXISTING LEGEND
-4
F o re st
H il ls N a tu re C en te r N ew N a tu re C en te r N
R ic h R d A lm a
M I
S ev il le
T o w n sh ip , G ra ti o t
C o u n ty
A lm a , M ic h ig a n 4
M A
T R
I X
C-400
BASIN COVER
BASIN
NON-SLAM
(TYPICAL)
CHECK VALVE
2"
GATE VALVE
LEVEL 4: PUMP 2 (LAG)
'ON' HIGH WATER ALARM
2"-OUTLET AS
NOTED ON PLANS
LEVEL 5: REDUNDANT
HIGH WATER ALARM
GAS TIGHT COVER
EXISTING GRADE
BASIN (60"Øx112" DEEP)
DISCHARGE PIPE
PUMP CASE
VOLUTE
LEVEL 1: LOW WATER ALARM
NOTE:
WATER LEVEL MINIMUM 1'-6" ABOVE PUMP
CASE
PROVIDE TIE DOWNS PER THE
MANUFACTURER'S WRITTEN SPECIFICATIONS.
4' 6"
6" 1'-
6"
SUPPORT POLE
6'x6' CONCRETE PAD
#4 REBAR 8" O.C.
EACH DIRECTION
GATE VALVE
2"
3'- 9"
LEVEL 3: PUMP 1 'ON'
LEVEL 2: PUMPS 'OFF'
FF ELEV. = 815.27
2"
2' 6"
4" SAN
812.00
PUMP STATION SEQUENCE OF OPERATION:
- LEVEL 1 - LOW WATER ALARM
- LEVEL 2 - BOTH PUMPS 'OFF'
- LEVEL 3 - START LEAD PUMP; PUMPS SHALL
ALTERNATE ON EACH CALL
- LEVEL 4 - START LAG PUMP; BOTH PUMPS
RUNNING SIMULTANEOUSLY; HIGH WATER
ALARM
- LEVEL 5 - REDUNDANT HIGH WATER LEVEL
ALARM
*CONTRACTOR IS RESPONSIBLE FOR PROVIDING
AND INSTALLING ALL CONTROLS ON THE BUILDING
AS NEEDED TO MEET THE SEQUENCE OF
OPERATIONS.
LIFT STATION
4D
2.5D
1D
D FLOW
1D
8"
24"
PVC FEMALE CLEANOUT ADAPTER WITH
INVERTED NUT SCREW CAP OR FLAT SLOTTED
SCREW CAP
PVC PIPE
45° BEND
SEWER LATERAL
E.J.I.W. 1040 M3 MANHOLE FRAME LID
INSTALLED FLUSH WITH FINISHED SURFACE
EXISTING GRADE
CONCRETE COLLAR POURED AROUND
CLEANOUT COVER (3,500 PSI)
KOR-N-SEAL NO. S406-10 AWS*
6"x6" TWO-WAY TEE
SEWER LATERAL
45° BEND
SEWER
TOP ELEVATION
4"
6"6" 10'-8-1/2" 11'-8-1/2"
6'- 0-
1/4
PVC SCHEDULE
40 BY OTHERS
5'- 6-
1/2
11'-8-1/2"
4"
4"x24" OPENING
7K KOR-N-SEAL
FOR 4" PVC
TYP-(2) PLACES
24" ACCESS (ABOVE)
TYP-(2) PLACES
7'-2-1/2" 3'-6"
5"x1" KEYWAY
TYP-(3) SIDES
CAULK ALL AROUND
TYP- BOTH SIDES
4'- 0-
1/4
2'- 0"
6"
4'-
-1 /4"
7"
5'-6-1/2" 4'-6-1/2"6" 6"
56"
CASTING & ADJUSTMENT TO
FINISH GRADE NOT INCLUDED
NOTES:
SEPTIC TANK SECTIONS TO BE MANUFACTURED PER AASHTO 17TH ED. AND
ASTM SPECIFICATIONS W/H-25 LOADING AND 0.0' TO 3.0' OF EARTH COVER.
CONCRETE: 5000 PSI @ 28 DAYS
REINFORCEMENT PER ASTM A-615 & A-496
COVER TO BE SEALED W/1-1/2" EZ-STIK OR EQUAL
PIPE AND FITTINGS FOR INLETS & OUTLETS ARE NOT INCLUDED
4" I.E.=814.80
I.E.=814.90
RIM ELEV. = 818.40 RIM ELEV. = 818.20
6'x6' CONCRETE PAD
12" 12"6"
6" OVERFILL
4" PERF.
PVC, TYP. 5 MDOT 6A
DRAIN FIELD WIDTH - 40'
NOTE: SEPTIC TANK AND DRAINFIELD DETAILS AND DESIGN
CRITERIA BASED ON THE MID-MICHIGAN HEALTH DEPARTMENT
4' 3'
18"
C-800
-4
F o re st
H il ls N a tu re C en te r N ew N a tu re C en te r
N
R ic h R d
A lm a M
I
S ev il le
T o w n sh ip
, G ra ti o t C o u n ty
A lm a , M ic h ig a n 4
M A
T R
I X
2 ROCK RIPRAP DISSIPATOR
SCALE: NTS
3 DOUBLE SANITARY CLEANOUT DETAIL
SCALE: NTS1 SUMP PUMP DUPLEX DETAIL
SCALE: NTS
4 SEPTIC TANK DETAIL
SCALE: NTS
1 DRAIN FIELD SECTION VIEW
SCALE: NTS
| 24-0569 TOPO_PRELIMINARY-new-Layout1-Ttlb 30x42 |
| C800-25034900-Layout1 |