26.068_PCS_KITCHEN GENERATOR_MEP_20260611.pdf

PDF 3 MB Posted

Attached to
Kitchen Generator
Solicitation number
RFP PCS 260000002267 1
Issued by
Allegan County, Michigan

About this file

This is a design and construction documentation file for a Kitchen Generator installation project at Plainwell Community Schools, located at 684 Starr Rd, Plainwell, Michigan 49080. The scope of work involves providing electrical power and natural gas infrastructure for a new generator installation that will serve a kitchen cooler and freezer system. The project documentation was prepared by IGNYTE DESIGN with MEP Engineer Lentz Becraft, PE, and is dated June 11, 2026. The design follows Michigan Building Code (2021), Michigan Mechanical Code (2021), Michigan Plumbing Code (2021), Michigan Electrical Code (NFPA 70, 2023), Michigan Energy Code (IECC/ASHRAE 90.1, 2021), Michigan Fire Sprinkler Code (NFPA 13, 2022), and ASHRAE Standard 55 (2023).

The project specifications detail comprehensive electrical and mechanical systems requirements. Electrical work includes installation of a new 40-50 kW/kVA diesel generator rated at 208/120V, 3-phase, 4-wire configuration, with a 150A automatic transfer switch (ATS-EMK) and associated standby panel (EMK). Natural gas piping work involves routing 1.5-inch and 4-inch gas lines from a building connection through the ceiling to the generator location below grade, with proper sizing for 500 CFH at 7-inch water gauge. The electrical system requires installation of new circuit breakers, recircuiting of existing cooler and freezer equipment loads from an existing panel (K2) to the new standby panel, conduit routing above existing ceilings with painted finish matching, and complete grounding and bonding per National Electrical Code standards. Installation specifications mandate use of licensed gas piping installers, qualified welders per ASME Section IX standards, full system pressure testing at 1.5 times operating pressure minimum, and demonstration and training upon completion. All work must comply with applicable codes and standards with materials and workmanship requirements governed by detailed schedules and specifications provided in the design documentation.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N

THE FOLLOWING DIMENSION EQUALS

ONE INCH WHEN PRINTED TO SCALE.

1"

Project No:

Drawing Title:

© 2026 IGNYTE DESIGN

SCALE

STAMP

Issued For: Date

PROJECT DIRECTORY APPLICABLE CODES PROJECT SCOPE OF WORK SHEET INDEX

MEP ENGINEER:

DESIGN PROFESSIONAL CONTACT:

PROJECT LOCATION

G000

COVER SHEET

KITCHEN

GENERATOR

26.068

JUNE 11, 2026CONSTRUCTION

KITCHEN GENERATOR

PLAINWELL COMMUNITY SCHOOLS

684 Starr Rd, Plainwell, MI 49080

THE SCOPE OF WORK IS TO PROVIDE POWER AND NATURAL GAS FOR A NEW

GENERATOR INSTALLATION FOR A KITCHEN COOLER/FREEZER.

IGNYTE DESIGN

LENTZ BECRAFT, PE

(269) 203-5058

LBECRAFT@IGNYTE.DESIGN

• MICHIGAN BUILDING CODE (MBC) – 2021

• MICHIGAN MECHANICAL CODE (IMC) – 2021

• MICHIGAN PLUMBING CODE (IPC) – 2021

• MICHIGAN ELECTRICAL CODE (NFPA 70) – 2023

• MICHIGAN ENERGY CODE (IECC/ASHRAE 90.1) – 2021

• MICHIGAN FIRE SPRINKLER CODE (NFPA 13) – 2022

• ASHRAE STANDARD 55 – 2023

123 DEVISSER PLACE

KALAMAZOO, MI 49007

G000 COVER SHEET

P110 FIRST FLOOR PLUMBING PLAN

E000 ELECTRICAL SYMBOLS AND GENERAL NOTES

E001 ELECTRICAL SPECIFICATIONS

E110 FIRST FLOOR POWER PLAN

U

IT

'E

U

N

IT

'F ' U

N

IT

'K

UNIT 'J'

UNIT 'E'

UNIT 'K'

UNIT 'J'

UNIT 'K'

MENS

FREEZERCOOLER CART WASH

TRASH

DRY STORAGE

OFFICE

KITCHEN

PREP.

902 903 904 905

IDF / JANITOR

SERVING 'A'

SERVING 'B'

STOR.

TOILET

JANITOR

LOCKER

A LA CARTE

STORAGE

KILN

STORAGE

902 903 904 906

909 914

915A

915B

GRADE

DIRT LEG

GENERATOR

SHUT-OFF VALVE

PRESSURE REGULATOR PIPE VENT

OUTLET WITH DOWNTURN ELBOW

SIZED FOR 500 CFH @ 7" WG

UNION

1 1/2" G TO BUILDING

[E] 1 1/2" G

[E

G

[E] 4" G

[E

G

GENERATOR

1 1/2" G

1/

G

1 1/2" G

SLEEVE THRU WALL, THEN ROUTE

BELOW GRADE TO GENERATOR

ROUTE GAS PIPING ABOVE

EXISTING CEILING. PAINT PIPING

TO MATCH CEILING IN EXPOSED

AREAS. CONTRACTOR TO PROVIDE

BEST POSSIBLE ROUTE.

THE FOLLOWING DIMENSION EQUALS

ONE INCH WHEN PRINTED TO SCALE.

1"

Project No:

Drawing Title:

© 2026 IGNYTE DESIGN

SCALE

STAMP

Issued For: Date

P110

FIRST FLOOR PLUMBING

PLAN

KITCHEN

GENERATOR

26.068

JUNE 11, 2026CONSTRUCTION

NO SCALEP110

2 GENERATOR CONNECTION DETAIL

8' 16'4'0 1/8" = 1'-0"P110

1 FIRST FLOOR PLUMBING PLAN

PART 1 - GENERAL

1. SECTION INCLUDES:

• NATURAL-GAS PIPING SYSTEMS WITH VALVES, FITTINGS, AND APPURTENANCES.

• PIPING MATERIALS, JOINTS, AND CONNECTIONS TO EQUIPMENT.

• VALVE BOXES AND IDENTIFICATION.

2. REFERENCES:

• NFPA 54 – NATIONAL FUEL GAS CODE.

• ASTM A53/A53M – STEEL PIPE, BLACK AND HOT-DIPPED ZINC-COATED.

• ASME B31.9 – BUILDING SERVICES PIPING.

• ANSI Z223.1 – FUEL GAS CODE.

• IFGC – INTERNATIONAL FUEL GAS CODE.

3. QUALITY ASSURANCE:

• INSTALLER SHALL BE LICENSED FOR GAS PIPING WORK IN THE JURISDICTION OF INSTALLATION.

• MATERIALS AND WORKMANSHIP SHALL COMPLY WITH APPLICABLE CODES AND STANDARDS.

• WELDERS AND BRAZERS SHALL BE QUALIFIED IN ACCORDANCE WITH ASME SECTION IX.

4. REFERENCE DOCUMENTS:

A. REFER TO MECHANICAL PIPING & VALVE APPLICATION SCHEDULE, MECHANICAL PIPE & ACCESSORY INSULATION

APPLICATION SCHEDULE, DUCT SYSTEM APPLICATION SCHEDULE, MECHANICAL EQUIPMENT INSULATION

APPLICATION SCHEDULE, AND DUCT ACCESSORY INSULATION APPLICATION SCHEDULE ON SHEET M007 FOR

REQUIRED PIPE, DUCT, EQUIPMENT, AND ACCESSORY MATERIALS, CONNECTION TYPES, VALVES, AND INSULATION

APPLICATIONS.

B. THESE SCHEDULES GOVERN MATERIAL, INSTALLATION, AND INSULATION REQUIREMENTS FOR ALL HVAC SYSTEMS

UNLESS OTHERWISE NOTED IN THE CONTRACT DOCUMENTS.

C. COORDINATE ALL SUBMITTALS, INSTALLATION DETAILS, AND FIELD APPLICATIONS WITH THE MATERIALS AND

REQUIREMENTS INDICATED ON SHEET M007.

PART 2 - PRODUCTS

1. STEEL PIPE:

• ASTM A53/A53M, TYPE E OR S, GRADE B, SEAMLESS OR ELECTRIC-RESISTANCE WELDED, SCHEDULE 40.

• ENDS THREADED OR GROOVED AS REQUIRED.

2. PIPE FITTINGS:

• MALLEABLE-IRON THREADED FITTINGS CONFORMING TO ASME B16.3.

• WROUGHT-STEEL BUTT-WELDING FITTINGS ASME B16.9 WHERE INDICATED.

3. VALVES:

• BALL VALVES RATED FOR 125 PSIG MINIMUM, BRASS OR STEEL BODY, THREADED ENDS.

• PLUG VALVES NOT PERMITTED EXCEPT WHERE REQUIRED BY MANUFACTURER.

4. UNIONS AND JOINTS:

• THREADED UNIONS OF FORGED STEEL WITH GROUND JOINT SURFACES.

• DIELECTRIC UNIONS WHERE CONNECTING DISSIMILAR METALS.

5. VALVE BOXES AND COVERS:

• CAST-IRON BOXES WITH BOLTED COVERS LABELED “GAS.”

6. PIPE HANGERS AND SUPPORTS:

• GALVANIZED STEEL RING OR CLEVIS TYPE IN ACCORDANCE WITH SECTION 23 0529.

7. PIPE IDENTIFICATION:

• YELLOW LABEL TAPE WITH BLACK LETTERING “NATURAL GAS.”

PART 3 - EXECUTION

1. INSTALLATION:

• INSTALL PIPING AS INDICATED, TRUE TO LINE AND GRADE, WITH PROPER SUPPORT AND ALLOWANCE FOR MOVEMENT.

• MAINTAIN CLEARANCE FROM ELECTRICAL CONDUITS AND HEAT SOURCES PER CODE.

• PROVIDE UNIONS AT EQUIPMENT CONNECTIONS AND VALVES.

• PROVIDE SHUT-OFF VALVES AT EACH BRANCH AND EACH EQUIPMENT CONNECTION.

• INSTALL PIPING SLOPED NOT LESS THAN 1/4 INCH PER 15 FEET TO DRAIN POINTS.

2. JOINTING:

• THREAD PIPE WITH NPT THREADS; USE APPROVED PIPE DOPE SUITABLE FOR NATURAL GAS.

• TIGHTEN JOINTS TO ENSURE GAS-TIGHT SEAL WITHOUT OVERSTRESSING.

• WELD JOINTS WHERE INDICATED BY QUALIFIED WELDERS.

3. VALVE INSTALLATION:

• INSTALL VALVES IN ACCESSIBLE LOCATIONS WITH STEMS UPRIGHT OR HORIZONTAL.

• INSTALL SHUTOFF VALVE UPSTREAM OF EACH PIECE OF GAS-FIRED EQUIPMENT.

4. FIELD QUALITY CONTROL:

• TEST ENTIRE SYSTEM AT 1.5 TIMES OPERATING PRESSURE BUT NOT LESS THAN 10 PSIG FOR 10 MINUTES MINIMUM.

• USE DRY NITROGEN OR AIR FOR TESTING; DO NOT USE NATURAL GAS.

• INSPECT FOR LEAKS USING SOAP SOLUTION OR ELECTRONIC DETECTOR.

• REPAIR LEAKS AND RETEST UNTIL SYSTEM IS LEAK-FREE.

5. PAINTING AND IDENTIFICATION:

• CLEAN EXPOSED PIPING AND APPLY PRIMER AND SAFETY YELLOW FINISH COAT WHERE NOT FACTORY-COATED.

• LABEL ALL EXPOSED PIPING WITH FLOW DIRECTION ARROWS AND SERVICE NAME.

6. DEMONSTRATION AND TRAINING:

• PROVIDE OPERATION AND MAINTENANCE INSTRUCTION TO OWNER’S REPRESENTATIVE UPON COMPLETION OF TESTS.

SECTION 23 1123 - FACILITY NATURAL-GAS PIPING

ELECTRICAL ABBREVIATION LIST

ABBREVIATION DESCRIPTION

A

AF

AFCI

A.F.F.

AIC

AL

AR

AT

ATS

AUX

BKR

BPS

C

CB

CKT

CT

DEMO

DIM

DISC

DP

DS

DWG

EBU

EC

ELEC

EM/ EMERG

EMT

EO

EPO

EWC

EXIST

EXT

FA

FLA

FLR

FOH

FSEC

FU

G/GRD/EG

GFCI

GFP

HOA

HP

HV

HZ

IG

JB

KV

KVA

KW

KWH

LA

LP

LDP

AMPERES

AMPERES FRAME (BREAKER RATING)

ARC FAULT CIRCUIT INTERRUPTER

ABOVE FINISH FLOOR

AMPS INTERRUPTING CAPACITY

AUDIENCE LEFT

AUDIENCE RIGHT

AMPERS TRIP (BREAKER SETTING)

AUTOMATIC TRANSFER SWITCH

AUXILIARY

BREAKER

BOLTED PRESSURE SWITCH

CONDUIT

CIRCUIT BREAKER

CIRCUIT

CURRENT TRANSFORMER

DEMOLITION

DIMENSION

DISCONNECT

DISTRIBUTION PANEL

DOWNSTAGE

DRAWING

EMERGENCY BATTERY UNIT

ELECTRICAL CONTRACTOR

ELECTRICAL

EMERGENCY

ELECTRICAL METALLIC TUBING

ELECTRICALY OPERATED

EMERGENCY POWER OFF

ELECTRIC WATER COOLER

EXISTING

EXTERIOR

FIRE ALARM

FULL LOAD AMPS

FLOOR

FRONT OF HOUSE

FOOD SERVICE EQUIPMENT

FUSE

GROUND

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT PROTECTION

HAND-OFF-AUTO

HORSEPOWER

HIGH VOLTAGE

HERTZ

ISOLATED GROUND

JUNCTION BOX

KILOVOLT

KILOVOLT - AMPERES

KILOWATT

KILOWATT - HOURS

LIGHTING ARRESTOR

LIGHTING PANEL

LIGHTING DISTRIBUTION PANEL

MAX

MCB

MCC

MDP

MECH

MIN

MISC.

MLO

MTD

MTG

MTR

N

NC

NEC

NF

NIC

NL

NO

NTS

OC

OFCI

OFOI

P

PB

PH

PT

PDP

RECEPT.

RCP

RDP

RP

RSC

SCHED

SW

SWBD

SWGR

TB

TELECOM

TR

TTP

TYP

UNO

US

V

W

WG

WP

XFMR

XP

(E)

(R)

MAXIMUM

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN DISTRIBUTION PANEL

MECHANICAL

MINIMUM

MISCELLANEOUS

MAIN LUGS ONLY

MOUNTED

MOUNTING

MOTOR

NEUTRAL

NORMALLY CLOSED

NATIONAL ELECTRICAL CODE

NON-FUSIBLE

NOT IN CONTRACT

NIGHT LIGHT

NORMALLY OPEN

NOT TO SCALE

ON CENTER

OWNER FURNISHED,

CONTRACTOR INSTALLED

OWNER FURNISHED,

OWNER INSTALLED

POLE

PUSHBUTTON STATION

PHASE

POTENTIAL TRANSFORMER

POWER DISTRIBUTION PANEL

RECEPTACLE

RECEPTACLE

RECEPTACLE DISTRIBUTION PANEL

RECEPTACLE PANEL

RIGID STEEL CONDUIT

SCHEDULE

SWITCH

SWITCHBOARD

SWITCHGEAR

TERMINAL BOX

TELECOMMUNICATIONS

TAMPER RESISTANT

TELEPHONE TERMINAL BACKBOARD

TYPICAL

UNLESS OTHERWISE NOTED

UPSTAGE

VOLTS

WIRE OR WATTS

WIRE GUARD

WEATHERPROOF

TRANSFORMER

EXPLOSION PROOF

EXISTING

RELOCATED

ELECTRICAL SYMBOL LIST

SYMBOL DESCRIPTION

LIGHTING FIXTURE - ARCHITECTURAL TROFFER

EMERGENCY LIGHTING FIXTURE

LIGHTING FIXTURE - PENDANT

WALL MOUNTED LIGHTING FIXTURE

LIGHTING FIXTURE

LIGHTING TRACK OR ROPE LIGHT

TRACK LIGHTING FIXTURE

EMERGENCY LIGHTING UNIT

POLE MOUNTED LIGHTING FIXTURE

POLE MOUNTED LIGHTING FIXTURE - POST TOP

BOLLARD LIGHTING FIXTURE

EXIT LIGHTING FIXTURE WITH DIRECTIONAL

ARROWS (SHADED AREA INDICATES FACE)

EXIT LIGHTING FIXTURE WITH DIRECTIONAL

ARROWS (SHADED AREA INDICATES FACE)

EXIT LIGHTING FIXTURE - WALL MOUNTED

SINGLE POLE TOGGLE SWITCH

TWO POLE TOGGLE SWITCH

3 WAY TOGGLE SWITCH

4 WAY TOGGLE SWITCH

KEY OPERATED SWITCH

DIMMER SWITCH

PILOT SWITCH

OCCUPANCY SENSOR DEVICE - CEILING

SIMPLEX / DUPLEX RECEPTACLE

SIMPLEX / DUPLEX RECEPTACLE CONTROLLED BY

AUTOMATIC CONTROL DEVICE / SYSTEM

QUAD RECEPTACLE

ABOVE COUNTER DUPLEX RECEPTACLE (SIMILAR FOR

TAMPER RESISTANT, QUADS, EMERGENCY AND GFI

RECEPTACLES)

DUPLEX RECEPTACLE-GROUND FAULT CIRCUIT

INTERRUPTER

DUPLEX EMERGENCY RECEPTACLE

CEILING MOUNTED

DUPLEX RECEPTACLE

SPECIAL RECEPTACLE - REFER TO ELECTRICAL

STANDARD SCHEDULES

MULTI-OUTLET RACEWAY - LEGRAND AL3300 OR EQUAL

POKE-THROUGH ASSEMBLY - LEGRAND

EVOLUTION SERIES OR EQUAL

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

CONTROL PANEL

VARIABLE FREQUENCY DRIVE

MOTOR

MANUAL CONTROLLER

MAGNETIC CONTROLLER

COMBINATION MAGNETIC CONTROLLER

NON-FUSIBLE DISCONNECT SWITCH

FUSIBLE DISCONNECT SWITCH

ENCLOSED CIRCUIT BREAKER

PUSH BUTTON STATION

AUTOMATIC DOOR CONTROLLER

AUTOMATIC DOOR PUSH PAD OPERATOR

GROUND ROD

GROUND CONNECTION

CONDUIT SLEEVE WITH BUSHINGS; LENGTH AS REQUIRED

"X" INDICATES CONDUIT SIZE, 2" UNLESS NOTED OTHERWISE

CONDUIT STUB - UP/DOWN, 2" CONDUIT UNLESS

NOTED OTHERWISE.

EMPTY BOX FOR FUTURE

TELECOMMUNICATION OUTLET

EMPTY BOX FOR FUTURE TELECOMMUNICATION

OUTLET MOUNTED 4" ABOVE COUNTERTOP

EMPTY BOX FOR FUTURE CEILING MOUNTED

TELECOMMUNICATION OUTLET

TELECOMMUNICATION OUTLET

"X" INDICATES TYPE

SPEAKER

SPEAKER - WALL MOUNTED

MICROPHONE

VOLUME CONTROL

SIGNALING BELL

SINGLE FACE CLOCK - CEILING MOUNTED

SINGLE FACE CLOCK - WALL MOUNTED

DOUBLE FACE CLOCK - CEILING MOUNTED

DOUBLE FACE CLOCK - WALL MOUNTED

P

PT

FB

CP

VFD

CB

DP

PP

X

X

S

S

MIC

VC

B

USB RECEPTACLE

GENERATOR TRANSFER DEVICEGTD

REMOTE GENERATOR ANNUNCIATOR PANELRGP

AUTOMATIC TRANSFER SWITCHATS

SWITCHBOARD

BRANCH CIRCUIT PANEL BOARD - 208/120V

TRANSFORMER

DISTRIBUTION PANEL - 208/120V

SECURITY CAMERA

MOTION DETECTOR

SECURITY KEY SWITCH

DOOR CONTACT

KEY PAD

CARD READER

CIRCUIT BREAKER

DRAWOUT CIRCUIT BREAKER

MANUALLY/ OPERATED

SWITCH

AUTOMATIC OR MANUAL TRANSFER

SWITCH

FUSE

TRANSFORMER

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

LIGHTNING ARRESTOR

PANELBOARD

"X" INDICATES PANELBOARD NAME

GROUND

SECURITY KEY INTERLOCK

ENGINE GENERATOR

UTILITY METER

AMMETER

VOLTMETER

AMMETER SWITCH

VOLTMETER SWITCH

SURGE PROTECTIVE DEVICE

TIME DELAY RELAY

THERMAL OVERLOAD RELAY

NORMALLY OPEN CONTACTS

NORMALLY CLOSED CONTACTS

N.O. PUSH BUTTON SINGLE CIRCUIT

N.C. PUSH BUTTON SINGLE CIRCUIT

GROUND BUS

MD

K

DC

KP

CR

X

K

G

M

A

V

AS

VS

SPD

TDR

GB

DURESS PUSH BUTTON STATION

DELAYED EGRESS

DB

DE

REQUEST TO EXIT STATIONREX

MANUAL FIRE ALARM PULL STATION

SMOKE DETECTOR

REMOTE TEST STATION (FOR DUCT DETECTOR)

FIRE ALARM BELL

NOTIFICATION APPLIANCE - WALL MOUNT SPEAKER/STROBE

TAMPER SWITCH

FLOW SWITCH

FIRE ALARM CONTROL PANEL

FIRE ALARM ANNUNCIATOR PANEL

F

SD

RT

F

F

TS

FS

FACP

FAA

NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANELNAC

R

E F

E R

T O

E L

E C

T R

IC

A

L

S T

A N

D A

R D

S C

H E

D U

L E

S

DIMMER OCCUPANCY SENSOR SWITCH

LOW VOLTAGE DIMMER SWITCH

POWER POLE - WIREMOLD TYPE

F NOTIFICATION APPLIANCE - CEILING MOUNT SPEAKER/STROBE

LIGHTING CONTROL DEVICE - REFER TO LIGHTING

CONTROL SCHEDULE

LC

K

D

OS

LV

GFI

USB

CLG

FLOOR BOX ASSEMBLY - LEGRAND

EVOLUTION SERIES OR EQUAL

TOUCH SCREEN SWITCHTS

OS

OCCUPANCY SENSOR DEVICE - WALLOS

PC PHOTOCELL DEVICE - REFER TO ZONES SHOWN ON

PLANS

EQ

EQUIPMENT CONNECTION - REFER TO ELECTRICAL

FEEDER AND PANEL SCHEDULE FOR BREAKER AND

CONDUCTOR SIZE/QUANTITY

J JUNCTION BOX

EMERGENCY POWER OFF BUTTON

V NOTIFICATION APPLIANCE - CEILING MOUNT STROBE

NOTIFICATION APPLIANCE - WALL MOUNT STROBEV

BRANCH CIRCUIT PANEL BOARD - 480/277V

DISTRIBUTION PANEL - 480/277V

CARBON MONOXIDE DETECTORCO

HEAT DETECTORHD

BEAM DETECTORBD

DUCT DETECTORDD

SMOKE DETECTOR - ELEVATOR TYPE; CONNECT TO FIRE ALARM

SYSTEM AND ELEVATOR CONTROL PANEL

SD

E

SPRINKLER VALVE MONITOR SWITCHOSY

SMOKE DAMPERSD

MAGNETIC DOOR HOLDERDH

S NOTIFICATION APPLIANCE - CEILING MOUNT SPEAKER

NOTIFICATION APPLIANCE - WALL MOUNT SPEAKERS

FIRE ALARM BATTERY CABINETBATT

EXIT FIXTURE-BACK

MOUNTED BOTTOM OF EXIT

SIGN TO BE 4" ABOVE TOP OF

DOOR FRAME

EXIT

EXIT

1' -6

EXIT

A/C SUPPLY

DIFFUSER

90" MAX (IBC)

4' -0

5"

8' -6

EXIT-CEILING MOUNTED

EXIT-FIXTURE END

MOUNTED

NFPA 72 AUDIBLE APPLIANCE 6" MIN

BELOW FINISHED CEILING

EMERGENCY

BATTERY

FIXTURE

ABOVE FINISHED FLOOR

AUDIBLE 80" MIN (IBC)

CEILING HEIGHTS LESS THEN 86" VISUAL

LENS MOUNTING HEIGHT WILL BE WITHIN 6"

OF THE CEILING

FINISHED CEILING

AUDIO/VISUAL &

VISUAL ONLY

DEVICES

SYNCHRONIZE MORE THAN

TWO APPLIANCES IN ANY

FIELD OF VIEW

MANUAL PULL STATION

AUDIBLE

ONLY

'-8

DOOR WIDTH LESS THEN 3'-0"

(MODIFY FOR DIFFERENT

DOOR WIDTHS)

FINISHED FLOOR

O R

A P

P R

O V

E D

F R

O M

A H

J

M

IN

A B

O V

E F

IN

IS

H E

D F

L O

O R

CEILING MOUNTED SMOKE/HEAT

DETECTOR

3'-0" MIN 4"

NOTES:

1. INSTALL ELECTRICAL DEVICES AT MOUNTING HEIGHTS NOTED ABOVE UNLESS OTHERWISE NOTED ON PLANS. COORDINATE WITH ALL OTHER DISCIPLINES PRIOR TO INSTALL.

2. VISUAL MOUNTING APPLIANCE MOUNTING HEIGHT IN SLEEPING ROOMS:

A. MINIMUM DISTANCE IN SLEEPING ROOMS IS 24" FROM CEILING TO THE TOP OF LENS FOR 110cd STROBES WITHIN 16' OF PILLOW

B. 177cd STROBES, USED IN SLEEPING ROOMS, CAN BE WITHIN THE 24" MINIMUM DISTANCE FROM THE CEILING, THE HIGHER INTENSITY IS TO COMPENSATE FOR A POSSIBLE SMOKE LAYER

7' -6

(M

IN

(M

A X

1' -0

"4"

M A

X

DO NOT INSTALL HEAT DETECTOR IN

SHADED AREA

WALL MOUNTED

SMOKE/HEAT

DETECTOR

MAGNETIC

DOOR

HOLDER

FINISHED WALL

SWITCHBANK

AUTOMATIC DOOR OPERATOR PUSH

BUTTON

RECEPTACLE, DATA JACK OR

TELEPHONE JACK

3'-0"

5' MAX TO EXIT DOOR

4' -0

4"

7' -6

ELECTRICAL DEVICE TYPICAL MOUNTING HEIGHTS

6' -6

BRANCH CIRCUIT PANELBOARDS

DISCONNECT SWITCH

5' -0

THE FOLLOWING DIMENSION EQUALS

ONE INCH WHEN PRINTED TO SCALE.

1"

Project No:

Drawing Title:

© 2026 IGNYTE DESIGN

SCALE

STAMP

Issued For: Date

E000

ELECTRICAL SYMBOLS

AND GENERAL NOTES

KITCHEN

GENERATOR

26.068

JUNE 11, 2026CONSTRUCTION

NOTE: SOME SYMBOLS AND ABBREVIATIONS SHOWN

MAY NOT APPLY TO THIS PROJECT.

GENERAL ELECTRICAL NOTES

1. CONTRACTOR TO PROCURE ALL REQUIRED BUILDING PERMITS AND INSPECTIONS TO COMPLETE PROJECT.

2. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE MICHIGAN ELECTRICAL CODE.

3. PROVIDE NEW ELECTRICAL SERVICES FROM CONSUMERS ENERGY AS INDICATED. COORDINATE SCOPE OF WORK AND PROVIDE ALL WORK TO PROVIDE A FULLY FUNCTIONAL ELECTRICAL SERVICE.

4. CONTRACTOR SHALL MEASURE AND VERIFY ALL LINE-LINE AND LINE-GROUND VOLTAGES PRIOR TO COMMENCING ANY WORK ON EXISTING ELECTRICAL DISTRIBUTION SYSTEMS. CONTRACTOR SHALL

REPORT BACK TO ENGINEER ANY SYSTEM VOLTAGES THAT ARE IN CONFLICT WITH INFORMATION AS SHOWN ON PLANS, ELECTRICAL ONE LINE DIAGRAM, AND SCHEDULES.

5. REMOVE ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, ETC ASSOCIATED WITH DEMOLISHED EQUIPMENT.

6. REMOVE ALL ABANDONDED ELECTRICAL CONDUIT AND WIRE BACK TO SOURCE.

7. PROVIDE SHOP DRAWINGS FOR THE FOLLOWING:

A. CONDUIT.

B. CONDUCTORS.

C. WIRING DEVICES INCLUDING COVERPLATES.

D. DISCONNECT SWITCHES, ENCLOSED CIRCUIT BREAKERS AND FUSED SWITCHES.

E. PANELBOARDS. AND SWITCHBOARDS

F. TRANSFORMERS.

G. SURGE PROTECTION DEVICES

H. POWER METERS.

I. INTERIOR LIGHT FIXTURES.

J. EXTERIOR LIGHT FIXTURES INCLUDING SITE POLES.

K. LIGHTING CONTROL SYSTEM AND DEVICES.

L. FIRE ALARM SYSTEM.

8. PATCH, REPAIR, AND PAINT ANY OPENINGS THROUGH ROOF, CEILINGS, WALLS, OR FLOORS TO MATCH EXISTING CONDITION.

9. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL OF ALL DEMOLISHED EQUIPMENT.

10. PROVIDE LAMACOID LABELS FOR:

A. PANELBOARDS AND SWITCHBOARDS.

B. TRANSFORMERS.

C. DISCONNECT SWITCHES.

D. VARIABLE FREQUENCY DRIVES.

E. LIGHTING CONTROL PANELS. LABEL SHALL INDICATE ROOMS CONTROLLED.

11. MINIMUM CONDUIT SIZE SHALL BE 1/2" TRADE SIZE.

12. USE THE CONDUIT TYPE SUITABLE FOR THE ENVIRONMENT IN WHICH IS IS LOCATED:

A. INDOORS: EMT WITH SET SCREW FITTINGS. MC CABLE IS ACCEPTABLE FOR BRANCH CIRCUITS WHERE CONCEALED.

B. OUTDOORS: RIGID GALVANIZED STEEL.

C. UNDERGROUND: RIGID NON METALLIC SCHEDULE 80 PVC.

D. CONDUIT EXITING FROM UNDERGROUND SHALL TRANSITION TO EMT/RGS PRIOR TO BEING EXPOSED.

13. PROVIDE CONDUIT SLEEVES FOR LOW VOLTAGE DATA CABLING.

14. ALL CABLING SHALL BE IN CONDUIT UNLESS ABOVE AN ACCESSIBLE CEILING WHERE "J" HOOKS ARE ACCEPTABLE.

15. USE CONDUIT SWEEPS FOR ALL DATA CABLING CONDUITS.

16. DATA BOXES SHALL BE DOUBLE GANG, 3 1/2" DEEP WITH SINGLE GANG MUD RING WITH 1" CONDUIT TO ABOVE ACCESSIBLE CEILING.

17. ALL BOXES SHALL BE RECESSED IN WALLS AND CONDUIT CONCEALED WHERE POSSIBLE.

18. EMERGENCY CIRCUITS SHALL NOT BE IN CONDUIT WITH OTHER NON-EMERGNECY CIRCUITS.

19. MINIMUM CONDUCTOR SIZE FOR POWER SHALL BE #12 AWG. ANY BRANCH CIRCUITS OVER 100' IN LENGTH SHALL BE #10 AWG MINIMUM FOR VOLTAGE DROP.

20. PROVIDE THHN-2 COPPER INDOORS AND THWN-2 COPPER OUTDOORS, UNLESS NOTED OTHERWISE OR DICTATED OTHERWISE BY THE NEC.

21. PROVIDE GROUNDING ELECTRODE SYSTEM AND EQUIPMENT GROUNDING PER THE NATIONAL ELECTRIC CODE.

22. PANELBOARDS SHALL BE FULLY RATED, SERIES RATED PANELS ARE NOT ACCEPTABLE. HAVE HINGED SWING DOOR-IN-DOOR. LOAD CENTERS ARE NOT ACCEPTABLE. SQUARE D NQOD OR EQUAL FOR

208/120V BRANCH PANELBOARDS. SQUARE D NF OR EQUAL FOR 480/277V PANELBOARDS. PROVIDE TYPED PANELBOARD CIRCUIT LABEL CARDS. UPDATE ALL EXISTING LABEL CARDS AS REQUIRED.

23. SURGE PROTECTION DEVICES SHALL BE MOUNTED AS CLOSE TO MAIN BUS AS POSSIBLE TO LIMIT FEEDER LENGTH.

24. ALL FLOOR MOUNTED EQUIPMENT SHALL BE ON 4" HOUSEKEEPING PAD.

25. RECEPTACLES SHALL BE TAMPER-RESISTANT EXTRA HEAVY DUTY GRADE, 20AMP MINIMUM. WHITE IN COLOR UNLESS NOTED OTHERWISE.

26. ALL DEVICE COVERS SHALL MATCH DEVICE COLOR UNLESS STAINLESS STEEL COVERS ARE SPECIFIED.

27. WEATHERPROOF RECEPTACLE COVERS SHALL BE METAL, WHILE-IN-USE TYPE.

28. SWITCHES SHALL BE HEAVY DUTY GRADE, 20 AMP, QUIET TYPE, WHITE UNLESS NOTED OTHERWISE.

29. LIGHTING CONTROL DEVICES SHALL BE MANUFACTURED BY N-LIGHT, UNLESS NOTED OTHERWISE.

30. ALL LIGHTING CONTROLS SHALL MEET ASHRAE 90.1 - 2013 WITH MICHIGAN AMENDMENTS.

31. IT IS UNDERSTOOD AND AGREED BY THE INSTALLER THAT WORK HEREIN DESCRIBED SHALL BE COMPLETE IN EVERY DETAIL, EVEN THOUGH EVERY ITEM INVOLVED IS NOT PARTICULARLY MENTIONED.

INSTALLER SHALL BE HELD TO PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR THE WORK INTENDED AND DESCRIBED FOR A COMPLETE AND OPERATIONAL SYSTEM. SUCH MATERIALS SHALL

INCLUDE, BUT ARE NOT LIMITED TO, CONDUIT, FITTINGS, COVERPLATES, WIRING, BREAKERS, CONTROL DEVICES, LIGHTING ACCESSORIES, ETC. THIS ALSO INCLUDES EQUIPMENT REQUIRED BY STATE AND

LOCAL CODES.

PART 1 - GENERAL

1. IT IS UNDERSTOOD AND AGREED BY THE INSTALLER THAT WORK HEREIN DESCRIBED SHALL BE COMPLETE IN EVERY DETAIL, EVEN THOUGH EVERY ITEM

INVOLVED IS NOT PARTICULARLY MENTIONED. INSTALLER SHALL BE HELD TO PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR THE WORK

INTENDED AND DESCRIBED FOR A COMPLETE AND OPERATIONAL SYSTEM. SUCH MATERIALS SHALL INCLUDE, BUT ARE NOT LIMITED TO, CONDUIT, FITTINGS, COVERPLATES, WIRING, BREAKERS, CONTROL DEVICES, LIGHTING ACCESSORIES, ETC. THIS ALSO INCLUDES EQUIPMENT REQUIRED BY STATE

AND LOCAL CODES.

2. CONTRACTOR TO PROCURE ALL REQUIRED BUILDING PERMITS AND INSPECTIONS TO COMPLETE PROJECT.

3. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE MICHIGAN ELECTRICAL CODE.

4. DO NOT INTERRUPT EXISTING ELECTRICAL SERVICE TO FACILITIES WITHOUT WRITTEN PERMISSION BY OWNER. COORDINATE WORK WITH EXISTING

ELECTRICAL SERVICES WITH OWNER AND UTILITY COMPANY.

5. ARRANGE TO PROVIDE TEMPORARY ELECTRICAL SERVICE AS REQUIRED FOR SCOPE OF WORK.

6. PROVIDE NEW ELECTRICAL SERVICES FROM UTILITY COMPANY AS DIRECTED. COORDINATE SCOPE OF WORK AND PROVIDE ALL WORK TO PROVIDE A

FULLY FUNCTIONAL ELECTRICAL SERVICE.

7. PROVIDE SHOP DRAWINGS FOR THE FOLLOWING:

A. CONDUIT

B. CONDUCTORS

C. WIRING DEVICES, INCLUDING COVER PLATES

D. DISCONNECT SWITCHES, ENCLOSED CIRCUIT BREAKERS AND FUSED SWITCHES

E. PANELBOARDS AND SWITCHBOARDS

F. SURGE PROTECTION DEVICES

G. INTERIOR AND EXTERIOR LIGHTING FIXTURES, INCLUDING SITE POLES

H. LIGHTING CONTROL SYSTEM AND DEVICES

I. FIRE ALARM SYSTEM

PART 2 - EXECUTION

1. PROVIDE SCHEDULE FOR ELECTRICAL INSTALLATION WORK TO OWNER AND ARCHITECT FOR MAJOR MILESTONE DATES.

2. COORDINATION DRAWINGS; PROVIDE COORDINATION DRAWINGS FOR FOLLOWING INSTALLATIONS:

A. LARGE INDOOR EQUIPMENT INSTALLATIONS.

B. LARGE OUTDOOR EQUIPMENT INSTALLATIONS.

3. DEMOLITION WORK

A. REMOVE ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, ETC., ASSOCIATED WITH DEMOLISHED EQUIPMENT.

B. REMOVE ALL ABANDONED ELECTRICAL CONDUIT AND WIRE BACK TO SOURCE.

C. PATCH, REPAIR AND PAINT ANY OPENINGS THROUGH ROOF, CEILINGS, WALLS OR FLOORS TO MATCH EXISTING CONDITION. MAINTAIN ALL FIRE

RATINGS OF WALLS AND DOORS.

D. OWNER SHALL HAVE FIRST RIGHT OF REFUSAL OF ALL DEMOLISHED EQUIPMENT.

4. CLOSEOUT ACTIVITIES

A. PROVIDE NORMAL OPERATION, EMERGENCY OPERATION AND PREVENTIVE MAINTENANCE MANUALS FOR EACH SYSTEM, EQUIPMENT AND DEVICE.

B. PROVIDE SOFTWARE AND FIRMWARE OPERATION DOCUMENTATION FOR SYSTEM INSTALLED.

C. PROVIDE BACKUP, UPGRADES AND UNRESTRICTED LICENSES FOR INSTALLED SOFTWARE, INCLUDING OPERATING SYSTEMS AND PROGRAMMING

TOOLS REQUIRED FOR MAINTENANCE AND OPERATION.

SECTION 26 0010

SUPPLEMENTAL REQUIREMENTS FOR ELECTRICAL

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL CONDUCTORS AND CABLES INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. COPPER BUILDING WIRE

A. FLEXIBLE, INSULATED, DRAWN COPPER WITH AN INSULATION JACKET, RATED 600V OR LESS.

B. PROVIDE THHN-2 COPPER INDOORS AND THWN-2 COPPER OUTDOORS, UNLESS NOTED OTHERWISE OR DICTATED OTHERWISE BY THE NEC.

C. MINIMUM CONDUCTOR SIZE FOR POWER SHALL BE #12 AWG. ANY BRANCH CIRCUIT(S) OVER 100' IN LENGTH SHALL BE #10 AWG MINIMUM FOR

VOLTAGE DROP.

D. PROVIDE COLOR CODED WIRE WITH DIFFERENT COLOR FOR EACH PHASE, NEUTRAL AND GROUND, BASED ON ELECTRICAL SYSTEM TYPE.

2. CONNECTORS AND SPLICES

A. FACTORY-FABRICATED CONNECTORS, SPLICES, AND LUGS OF SIZE, AMPACITY RATING, MATERIAL, TYPE, AND CLASS FOR APPLICATION AND SERVICE

INDICATED.

B. SHALL BE MARKED FOR INTENDED LOCATION AND USE.

PART 3 - EXECUTION

1. INSTALLATION

A. CONCEAL CABLES IN FINISHED WALLS, CEILINGS AND FLOORS UNLESS OTHERWISE NOTED.

B. USE PULLING MEANS, INCLUDING FISH TAPE, CABLE, ROPE, AND BASKET-WEAVE WIRE/CABLE GRIPS, THAT WILL NOT DAMAGE CABLES OR RACEWAY.

USE MANUFACTURER APPROVED PULLING COMPOUND OR LUBRICANT WHEN NECESSARY.

C. INSTALL CONDUCTORS AT EACH OUTLET, WITH AT LEAST 12" OF SLACK.

D. ALL CABLING SHALL BE IN CONDUIT UNLESS ABOVE AN ACCESSIBLE CEILING WHERE "J" HOOKS ARE ACCEPTABLE.

2. CONNECTIONS

A. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS ACCORDING TO MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES.

B. SPLICES, TERMINATIONS, AND TAPS SHALL BE COMPATIBLE WITH CONDUCTOR MATERIAL.

C. CONDUCTORS SHALL BE CONTINUOUS FROM ORIGIN TO PANEL OR EQUIPMENT TERMINATION WHERE POSSIBLE. SPLICES AND TAPS, WHERE

REQUIRED, SHALL BE MADE IN JUNCTION BOXES WITH SUITABLE CONNECTORS.

3. ACCEPTANCE

A. ALL CONDUCTORS AND CONNECTIONS SHALL TEST FREE OF GROUNDS, SHORTS, AND OPENS PRIOR TO ENERGIZING CIRCUIT.

SECTION 26 0519

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL CONDUIT AND RACEWAY PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. ALL PRODUCTS SHALL BE UL LISTED AND LABELED.

2. EMT - RIGID, STEEL, ZINC-COATED (INTERIOR AND EXTERIOR).

3. RMC - RIGID, STEEL, ZINC-COATED (INTERIOR AND EXTERIOR).

4. FMC - FLEXIBLE, STEEL. PROVIDE AT TERMINATION POINT FOR EQUIPMENT SUBJECT TO MOTION AND VIBRATION.

5. MC CABLE - COLOR-CODED COPPER CONDUCTORS WITH INTERLOCKING GALVANIZED STEEL SHEATHING.

6. PVC - SCHEDULE 40, SCHEDULE 80, FOR USE WITH MAXIMUM 90 DEG C WIRE.

7. FITTINGS

A. SHALL BE LISTED FOR USE WITH RACEWAY SYSTEM TO BE INSTALLED.

PART 3 - EXECUTION

1. CONDUIT TYPE SHALL BE SUITABLE FOR THE ENVIRONMENT IN WHICH IT IS LOCATED:

A. INDOORS - EMT, AND/OR RMC, WITH SET-SCREW FITTINGS. MC CABLE IS ACCEPTABLE FOR BRANCH CIRCUITS WHERE CONCEALED.

B. OUTDOORS - RIGID GALVANIZED STEEL.

C. UNDERGROUND - RIGID, NON-METALLIC SCHEDULE 80 PVC.

a. CONDUIT EXITING FROM UNDERGROUND SHALL TRANSITION TO EMT/RGS PRIOR TO BEING EXPOSED ABOVE GROUND.

2. MINIMUM CONDUIT SIZE SHALL BE 1/2" TRADE SIZE.

3. PROVIDE CONDUIT SLEEVES FOR LOW VOLTAGE DATA CABLING.

4. USE LARGE RADIUS ELLS FOR ALL CONDUIT BENDS.

5. CONDUITS SHALL BE CONCEALED WITHIN FINISHED WALLS, CEILINGS AND FLOORS UNLESS OTHERWISE INDICATED. CONDUITS SHALL BE

SUPPORTED WITHIN 12" OF ENCLOSURES TO WHICH ATTACHED.

6. INSTALL RACEWAY SEALS AND FITTINGS AT ACCESSIBLE LOCATIONS.

7. DO NOT INSTALL CONDUITS WITHIN 2" OF THE BOTTOM SIDE OF METAL DECK ROOF.

8. KEEP CONDUITS AT LEAST 6" AWAY FROM PARALLEL RUNS OF FLUES AND STEAM OR HOT-WATER PIPES.

9. INSTALL PULL WIRES IN EMPTY RACEWAYS FOR FUTURE USE. PROVIDE POLYPROPYLENE OR MONOFILAMENT PLASTIC LINE WITH NOT LESS THAN

200lb TENSILE STRENGTH. LEAVE AT LEAST 12" OF SLACK AT BOTH ENDS OF CONDUIT.

10. CAP AND SEAL UNDERGROUND RACEWAYS DESIGNATED AS SPARE ABOVE GRADE ALONGSIDE DUCT RACEWAYS IN USE.

11. PROVIDE SEPARATE RACEWAY SYSTEM FOR EMERGENCY CIRCUIT(S). EMERGENCY CIRCUITS SHALL NOT BE IN CONDUIT WITH OTHER NON-

EMERGENCY CIRCUITS.

SECTION 26 0533.13

CONDUITS FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL GROUNDING AND BONDING PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. GROUNDING AND BONDING CONDUCTORS

A. PROVIDE THHN/THWN-2, TINNED-COPPER WIRE OR CABLE, GREEN COLOR. CABLE SHALL BE RATED 600V.

2. GROUNDING AND BONDING CLAMPS

A. CLAMPS SUITABLE FOR ATTACHMENT OF GROUNDING AND BONDING CONDUCTORS TO ELECTRODES, PIPES, TUBING, AND REBAR. SUITABLE TYPES

SHALL BE:

a. STRAP-TYPE PIPE AND ROD CLAMPS

b. BEAM GROUNDING CLAMPS

c. EXOTHERMICALLY WELDED CONNECTIONS

3. GROUNDING (EARTHING) ELECTRODES

A. COPPER CLAD STEEL

B. 3/4" DIAMETER BY 10' LENGTH

PART 3 - EXECUTION

1. PROVIDE GROUNDING ELECTRODE SYSTEM AND EQUIPMENT GROUNDING PER THE NATIONAL ELECTRIC CODE.

2. GROUNDING AND BONDING CONDUCTORS

A. PROVIDE SOLID CONDUCTOR FOR 8 AWG AND SMALLER, AND STRANDED CONDUCTORS FOR 6 AWG AND LARGER, UNLESS OTHERWISE NOTED.

B. ROUTE CONDUCTORS ALONG SHORTEST AND STRAIGHTEST PATHS POSSIBLE. AVOID OBSTRUCTING ACCESS TO OR PLACING CONDUCTORS WHERE

THEY MAY BE SUBJECTED TO STRAIN, IMPACT, OR DAMAGE.

C. PROVIDE GROUNDING AND BONDING BUSBARS IN ELECTRICAL EQUIPMENT ROOMS, ROOMS HOUSING SERVICE EQUIPMENT, AND ELSEWHERE

INDICATED ON DRAWINGS.

3. CONNECTIONS

A. MAKE CONNECTIONS SO POSSIBILITY OF GALVANIC ACTION OR ELECTROLYSIS IS MINIMIZED.

B. USE EXOTHERMIC WELDS FOR ALL BELOW GRADE CONNECTIONS.

4. GROUNDING ELECTRODES

A. DRIVE GROUND RODS UNTIL TOPS ARE 2" BELOW FINISHED FLOOR OR GRADE.

B. INSTALL AT LEAST (3) RODS SPACED AT LEAST ONE-ROD LENGTH FROM EACH OTHER AND CONNECT TO SERVICE GROUNDING ELECTRODE

CONDUCTOR.

C. FOR CONCRETE-ENCASED ELECTRODE (UFER GROUND), USE MINIMUM 20' OF BARE COPPER CONDUCTOR NOT SMALLER THAN 4 AWG.

a. IF FOUNDATION IS LESS THAN 20' LONG, COIL EXCESS CONDUCTOR WITHIN BASE OF FOUNDATION.

b. BOND GROUNDING CONDUCTOR TO REINFORCING STEEL IN AT LEAST (4) LOCATIONS AND TO ANCHOR BOLTS. EXTEND GROUNDING CONDUCTOR

BELOW GRADE AND CONNECT TO GROUNDING GRID OR GROUNDING ELECTRODE EXTERNAL TO CONCRETE.

5. EQUIPMENT GROUNDING AND BONDING

A. INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTORS WITH THE FOLLOWING ITEMS:

a. FEEDERS AND BRANCH CIRCUITS

b. LIGHTING CIRCUITS

c. RECEPTACLE CIRCUITS

d. SINGLE, AND THREE-PHASE MOTOR AND APPLIANCE BRANCH CIRCUITS

e. FLEXIBLE RACEWAY, ARMORED, AND METAL-CLAD CABLE RUNS

B. ALL CORRUGATED STAINLESS STEEL TUBING FOR GAS PIPING SYSTEM IN KITCHENS SHALL BE BONDING TO THE GROUNDING ELECTRODE SYSTEM.

BONDING JUMPER SHALL NOT BE SMALLER THAN 6 AWG.

SECTION 26 0526

GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL SUPPORT, ANCHORAGE, AND ATTACHMENT PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

A. STEEL HANGERS, CLAMPS, AND ASSOCIATED FITTINGS SHALL BE DESIGNED FOR TYPES AND SIZES OF RACEWAY OR CABLE TO BE SUPPORTED.

B. MOUNTING, ANCHORING, AND ATTACHMENT COMPONENTS FOR FASTENING ELECTRICAL ITEMS OR SUPPORTS TO BUILDING SURFACES:

a. POWDER-ACTUATED FASTENERS

b. MECHANICAL-EXPANSION ANCHORS

c. CONCRETE INSERTS

d. CLAMPS FOR ATTACHMENT TO STEEL STRUCTURAL ELEMENTS

e. THROUGH BOLTS AND TOGGLE BOLTS

f. HANGER RODS

PART 3 - EXECUTION

A. SUPPORT INSTALLATION

a. PROVIDE SIZES OF COMPONENTS SO STRENGTH WILL BE ADEQUATE TO CARRY PRESENT AND FUTURE STATIC LOADS WITHIN SPECIFIED LIMITS.

b. CUT, FIT, AND PLACE MISCELLANEOUS METAL SUPPORTS ACCURATELY IN LOCATION, ALIGNMENT, AND ELEVATION TO SUPPORT AND ANCHOR

ELECTRICAL MATERIALS AND EQUIPMENT.

B. CONCRETE BASES

a. ALL FLOOR MOUNT ELECTRICAL EQUIPMENT SHALL BE ON 4" HOUSEKEEPING PADS. PADS SHALL BE NOT LESS THAN 4" LARGER IN BOTH

DIRECTIONS OF ELECTRICAL EQUIPMENT TO BE SUPPORTED.

C. TOUCHUP

a. CLEAN WELDS AND ABRADED AREAS OF SHOP PAINT. PAINT EXPOSED AREAS IMMEDIATELY AFTER ERECTING HANGERS AND SUPPORTS.

SECTION 26 0529

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL SURGE PROTECTIVE DEVICE PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. MANUFACTURER

A. RAYCAP

a. TYPE 1, SERVICE ENTRANCE - RAYVOSS

b. TYPE 2, BRANCH PANEL - RSE2

2. GENERAL CHARACTERISTICS

A. MCOV: NOT LESS THAN 125% OF NOMINAL SYSTEM VOLTAGE FOR 208Y/120V AND 120/240V SYSTEMS. NOT LESS THAN 115% OF NOMINAL

SYSTEM VOLTAGE FOR 480Y/277V SYSTEMS.

B. PEAK SURGE CURRENT RATING: MINIMUM SINGLE-PULSE SURGE CURRENT WITHSTAND RATING PER PHASE SHALL BE NOT LESS THAN -

a. TYPE 1: 160, OR 240 kA.

b. TYPE 2: 50, 100, 150, OR 200 kA.

C. PROTECTION MODES: DEVICE SHALL HAVE PROTECTION MODES FOR LINE-TO-NEUTRAL, AND LINE-TO-LINE, FOR TYPE 1 DEVICES, AND LINE-TO-

NEUTRAL, LINE-TO-GROUND, NEUTRAL-TO-GROUND, AND LINE-TO-LINE, FOR TYPE 2 DEVICES.

3. OPTIONS

A. INTERNAL THERMAL PROTECTION TO DISCONNECT SPD BEFORE DAMAGING INTERNAL SUPPRESSOR COMPONENTS.

B. INDICATOR LIGHT DISPLAY FOR PROTECTION STATUS.

C. AUDIBLE ALARM.

D. NEMA ICS 5, DRY FORM-C CONTACTS RATED AT 1 A AND 120 VAC FOR REMOTE MONITORING OF PROTECTION STATUS.

E. TYPE 2 DEVICES: TOV AND SURGE COUNTER WITH TIME AND DATE STAMP.

PART 3 - EXECUTION

1. INSTALLATION

A. PROVIDE OCPD AND DISCONNECT FOR INSTALLATION OF SPD IN ACCORDANCE WITH UL 1449 AND MANUFACTURER INSTRUCTIONS.

B. INSTALL LEADS BETWEEN DISCONNECT(S) AND SPD(S) IN ACCORDANCE WITH MANUFACTURER INSTRUCTIONS.

a. DO NOT SPLICE AND EXTEND SPD LEADS UNLESS PERMITTED BY MANUFACTURER.

b. DO NOT EXCEED MANUFACTURER RECOMMENDED LEAD LENGTH.

c. DO NOT BOND NEUTRAL AND GROUND.

d. USE CRIMPED CONNECTORS AND SPLICES ONLY. WIRE NUTS ARE NOT ACCEPTABLE.

C. SURGE PROTECTION DEVICES SHALL BE MOUNTED AS CLOSE TO MAIN BUS AS POSSIBLE TO LIMIT FEEDER LENGTH.

SECTION 26 4313

SURGE PROTECTIVE DEVICES FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL BOX AND COVER PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. METALLIC OUTLET BOXES

A. LISTED AND LABELED FOR INTENDED LOCATION AND USE.

B. MATERIAL SHALL BE SHEET METAL GALVANIZED STEEL, WITH A MINIMUM DEPTH OF 2.5".

C. BOXES SHALL HAVE PRYOUT OPENINGS, KNOCKOUTS, THREADED ENTRIES, OR HUBS IN EITHER SIDES OR BACK FOR CONDUITS OR CONDUIT

FITTINGS. SHALL HAVE PROVISIONS FOR MOUNTING OUTLET BOX COVER.

D. EXTENSION RINGS SHALL BE PROVIDED WHERE REQUIRED OR INDICATED ON DRAWINGS, TO EXTEND DEVICE BOX TO INCREASE DEPTH.

EXTENSION RINGS SHALL BE SUITABLE FOR USE WITH ASSOCIATED DEVICE BOX.

2. NONMETALLIC OUTLET BOXES

A. LISTED AND LABELED FOR INTENDED LOCATION AND USE.

3. COVER PLATES

A. LISTED AND LABELED FOR INTENDED LOCATION AND USE WITH ASSOCIATED OUTLET BOX TYPE.

B. FOR USE IN FINISHED LOCATIONS: .032" THICK, TYPE 302/304 NON-MAGNETIC STAINLESS STEEL.

a. ALL DEVICE COVERS SHALL BE BRUSHED STAINLESS STEEL, UNLESS SPECIFIC DEVICE COLOR IS SPECIFIED.

C. PROVIDE GASKETS FOR WALLPLATES IN DAMP OR WET LOCATIONS.

D. WEATHERPROOF COVERS

a. SHALL BE METAL, "WHILE-IN-USE" TYPE. COVER SHALL BE GRAY COLOR.

PART 3 - EXECUTION

1. ALL BOXES SHALL BE RECESSED IN WALLS AND CONDUIT CONCEALED WHERE POSSIBLE.

A. CUT, PATCH, REPAIR AND PAINT GYPSUM AND/OR MASONRY WALLS TO RECESS NEW BOXES WHERE INDICATED.

B. HORIZONTALLY SEPARATE BOXES MOUNTED ON OPPOSITE SIDES OF WALLS SO THEY ARE NOT IN THE SAME VERTICAL CHANNEL.

2. PROVIDE NEMA 1 BOXES AND COVERS FOR INDOOR LOCATIONS, UNLESS OTHERWISE NOTED.

3. PROVIDE NEMA 3R BOXES AND COVERS FOR OUTDOOR LOCATIONS, UNLESS OTHERWISE NOTED.

4. SUPPORT

A. SUPPORT BOXES IN RECESSED CEILINGS INDEPENDENT OF CEILING TILES OR GRID.

B. SUPPORT JUNCTION OR PULL BOXES FROM BUILDING STRUCTURE. DO NOT SUPPORT BOXES BY CONDUIT(S).

5. ALL BOXES USED FOR LOW VOLTAGE DATA CABLING SHALL BE DOUBLE GANG, 3-1/2" DEEP WITH SINGLE GANG MUD RING. PROVIDE 1" CONDUIT TO

ABOVE ACCESSIBLE CEILING FOR DATA CABLING.

SECTION 26 0533.16

BOXES AND COVERS ELECTRICAL SYSTEMS

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL LABEL AND IDENTIFICATION PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. LABELS

A. LISTED AND LABELED FOR INTENDED LOCATION AND APPLICATION.

B. VINYL WRAPAROUND LABELS - PREPRINTED, FLEXIBLE LABELS LAMINATED WITH CLEAR, WEATHER AND CHEMICAL-RESISTANT COATING.

C. SELF-ADHESIVE WRAPAROUND LABELS - PREPRINTED, VINYL FLEXIBLE LABEL WITH ACRYLIC PRESSURE-SENSITIVE ADHESIVE.

D. SELF-ADHESIVE LABELS - POLYESTER VINYL, THERMAL, TRANSFER PRINTED, MULTI-COLOR, WEATHER AND UV-RESISTANT, PRESSURE-

SENSITIVE ADHESIVE.

E. SIZE

a. 1-1/2" BY 6" FOR RACEWAYS AND CONDUCTORS.

b. 3-1/2" BY 5" FOR EQUIPMENT.

2. SIGNS

A. LAMINATED ACRYLIC OR MELAMINE PLASTIC.

a. 1/16" THICK FOR SIGNS UP TO 20 SQ. IN.

b. 1/8" THICK FOR SIGNS GREATER THAN 20 SQ. IN.

c. ENGRAVED LEGEND WITH BLACK LETTERS ON WHITE FACE.

d. PUNCHED OR DRILLED FOR MECHANICAL FASTENERS WITH 1/4" GROMMETS IN CORNERS FOR MOUNTING.

3. UNDERGROUND-LINE WARNING TAPE

A. SUITABLE TO IDENTIFY AND LOCATE UNDERGROUND ELECTRICAL AND COMMUNICATIONS UTILITY LINES.

B. PRINTING ON TAPE MUST BE PERMANENT AND NOT DAMAGED BY BURIAL OPERATIONS.

C. INSCRIPTIONS SHALL READ "CAUTION BURIED ELECTRIC LINE BELOW" OR "CAUTION BURIED COMMUNICATION LINE BELOW".

D. DETECTABLE WARNING TAPE

a. REINFORCED, DETECTABLE THREE-LAYER LAMINATE, CONSISTING OF ALUMINUM-FOIL CORE AND CLEAR PROTECTIVE FILM.

PART 3 - EXECUTION

1. PROVIDE BAKED ENAMEL SIGNS FOR:

A. PANELBOARDS AND SWITCHBOARDS

B. TRANSFORMERS

C. DISCONNECT SWITCHES

D. VARIABLE FREQUENCY DRIVES

E. LIGHTING CONTROL PANELS. LABELS SHALL INDICATED ROOMS CONTROLLED

2. IDENTIFY CONDUCTORS, CABLES, AND TERMINALS IN ENCLOSURES AND AT JUNCTIONS, TERMINALS, PULL POINTS, AND LOCATIONS OF HIGH

VISIBILITY. IDENTIFY BY SYSTEM AND CIRCUIT DESIGNATION.

3. PROVIDE UNDERGROUND-LINE WARNING TAPE FOR POWER, LIGHTING, AND COMMUNICATIONS CABLING.

4. LABEL INDIVIDUAL COVER PLATES WITH SELF-ADHESIVE LABELS. LABEL TO INDICATE CIRCUIT WHICH DEVICE IS FED FROM WITH THE FOLLOWING

INFORMATION:

A. PANELBOARD DESIGNATION - BRANCH CIRCUIT NUMBER.

5. INSTALL IDENTIFICATION MATERIALS AT LOCATIONS FOR MOST CONVENIENT VIEWING WITHOUT INTERFERENCE WITH OPERATION AND

MAINTENANCE OF EQUIPMENT.

6. PROVIDE FLOOR MARKING TAPE TO INDICATE WORKING CLEARANCE OF ELECTRICAL EQUIPMENT. FLOOR MARKING TAPE SHALL NOT BE USED FOR

SURFACE OR FLUSH-MOUNTED PANELBOARDS AND SIMILAR EQUIPMENT IN FINISHED SPACES.

SECTION 26 0553

IDENTIFICATION FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL PANELBOARD PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. MANUFACTURER

A. SQUARE D - NQOD FOR 208/120V BRANCH PANELBOARDS, NF FOR 480/277V BRANCH PANELBOARDS.

B. OR EQUAL BY:

a. EATON CORP.

b. SIEMENS

2. ELECTRICAL COMPONENTS, DEVICES, AND EQUIPMENT SHALL BE UL LABELED.

3. ENCLOSURES

A. RATED FOR ENVIRONMENTAL CONDITIONS AT INSTALLED LOCATION

a. INDOOR, DRY AND CLEAN LOCATIONS - NEMA 1

b. OUTDOOR LOCATIONS - NEMA 3R

c. KITCHEN LOCATIONS - NEMA 4X, STAINLESS STEEL

d. OTHER WET AND DAMP INDOOR LOCATIONS - NEMA 4

B. FRONT - SECURE TO BOX WITH CONCEALED TRIM CLAMPS. FOR SURFACE-MOUNTED FRONTS, MATCH DIMENSIONS; FOR FLUSH-MOUNTED

FRONTS, OVERLAP BOX. TRIMS MUST COVER LIVE PARTS AND MAY HAVE NO EXPOSED HARDWARE.

4. BUSES

A. TIN-PLATED ALUMINUM FOR 400A OR LESS.

B. HARD DRAWN COPPER FOR ABOVE 400A.

5. CONDUCTOR CONNECTORS

A. TIN-PLATED ALUMINUM OR HARD DRAWN COPPER, 98% CONDUCTIVITY.

B. MAIN AND NEUTRAL LUGS - MECHANICAL TYPE, WITH LUG ON NEUTRAL BAR FOR EACH POLE IN PANELBOARD.

C. GROUND LUGS AND BUS-CONFIGURED TERMINATORS - MECHANICAL TYPE, WITH LUG ON BAR FOR EACH POLE IN PANELBOARD.

D. SUBFEED LUGS - MECHANICAL TYPE, SUITABLE FOR USE WITH CONDUCTOR MATERIAL. LOCATE AT SAME END OF BUS AS INCOMING LUGS OR

MAIN DEVICE.

6. SHORT-CIRCUIT CURRENT RATING

A. FULLY RATED TO INTERRUPT SYMMETRICAL SHORT-CIRCUIT CURRENT AVAILABLE AT TERMINALS. SERIES RATED PANELS ARE NOT

ACCEPTABLE.

7. OVERCURRENT PROTECTIVE DEVICES

A. THERMAL-MAGNETIC CIRCUIT BREAKERS

a. INVERSE TIME CURRENT ELEMENT FOR LOW-LEVEL OVERLOADS.

b. INSTANTANEOUS MAGNETIC TRIP ELEMENT FOR SHORT CIRCUITS.

c. ADJUSTABLE MAGNETIC TRIP SETTING FOR CIRCUIT-BREAKER FRAME SIZES 250A AND LARGER.

B. ELECTRONIC TRIP CIRCUIT BREAKERS

a. RMS SENSING.

b. FIELD-REPLACEABLE RATING PLUG OR ELECTRONIC TRIP.

c. FIELD ADJUSTABLE SETTINGS FOR: INSTANTANEOUS TRIP, LONG AND SHORT TIME PICKUP LEVELS, LONG AND SHORT TIME ADJUSTMENTS, AND GROUND FAULT PICKUP LEVEL, TIME DELAY AND I

T RESPONSE.

C. SUBFEED CIRCUIT BREAKERS SHALL BE VERTICALLY ARRANGED ON PHASE BUSBARS.

PART 3 - EXECUTION

1. INSTALLATION

A. MOUNT TOP OF PANELBOARD TRIP 7.5' ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED.

B. MOUNT PANELBOARD CABINET PLUMB AND RIGID WITHOUT DISTORTION OF BOX.

C. MOUNT RECESSED PANELBOARDS WITH FRONT UNIFORMLY FLUSH WITH WALL FINISH.

a. FOR RECESSED PANELBOARDS, STUB (4) 1" EMPTY CONDUITS FROM PANELBOARD INTO ACCESSIBLE CEILING SPACE OR SPACE DESIGNATED

TO BE CEILING SPACE IN FUTURE.

D. MAKE GROUNDING CONNECTIONS AND BOND NEUTRAL FOR SERVICES AND SEPARATELY DERIVED SYSTEMS TO GROUND. MAKE CONNECTIONS

TO GROUNDING ELECTRODES, SEPARATE GROUNDS FOR ISOLATED GROUND BARS, AND CONNECTIONS TO SEPARATE GROUND BARS.

2. IDENTIFICATION

A. PANELBOARD LABEL MUST LIST MANUFACTURER NAME, TRADEMARK, VOLTAGE, AMPERAGE, NUMBER OF PHASES, AND NUMBER OF POLES AND

MUST BE LOCATED ON INTERIOR OF PANELBOARD DOOR.

B. CIRCUIT BREAKER LABELS MUST LIST CURRENT RATING, UL AND IEC CERTIFICATION STANDARDS, AND AIC RATING.

C. CIRCUIT DIRECTORY

a. PROVIDE CIRCUIT DIRECTORY CARD INSIDE PANELBOARD DOOR, MOUNTED IN TRANSPARENT CARD HOLDER.

b. PANELBOARD DIRECTORY SHALL BE TYPE-WRITTEN, AND PROVIDE DETAILED INFORMATION SHOWN ON ASSOCIATED PANELBOARD LOAD

SCHEDULE.

c. UPDATE ALL EXISTING CIRCUIT DIRECTORY CARDS AS REQUIRED.

SECTION 26 2416

PANELBOARDS

PART 1 - GENERAL

1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL WIRING DEVICE PRODUCTS INSTALLED DURING COURSE OF WORK.

PART 2 - PRODUCTS

1. GENERAL USE SWITCHES

A. MANUFACTURER

a. ARROW HART, WIRING DEVICES

b. HUBBELL WIRING DEVICE-KELLEMS, HUBBELL, INC.

c. LEVITON MANUFACTURING CO., INC.

d. PASS & SEYMOUR, LEGRAND NORTH AMERICA, LLC

B. GENERAL CHARACTERISTICS

a. HEAVY DUTY GRADE, QUIET TYPE, 120/277 VAC, RATED 20A MINIMUM.

b. COLOR - WHITE, UNLESS OTHERWISE INDICATED.

c. PROVIDE BRUSHED STAINLESS STEEL COVER DESIGNED FOR USE WITH DEVICE, UNLESS OTHERWISE INDICATED.

2. STRAIGHT-BLADE RECEPTACLES

A. MANUFACTURER

a. HUBBELL WIRING DEVICE-KELLEMS, HUBBELL, INC.

B. GENERAL CHARACTERISTICS

a. EXTRA HEAVY DUTY GRADE, TAMPER-RESISTANT, RATED 20A MINIMUM.

b. COLOR - WHITE, UNLESS OTHERWISE INDICATED.

c. PROVIDE BRUSHED STAINLESS STEEL COVER DESIGNED FOR USE WITH DEVICE, UNLESS OTHERWISE INDICATED.

PART 3 - EXECUTION

1. INSTALLATION

A. UNLESS OTHERWISE INDICATED, INSTALL SWITCHES, RECEPTACLES, AND OTHER WIRING DEVICES, AT MOUNTING HEIGHTS RECOMMENDED IN

NECA NEIS 1.

B. ORIENT RECEPTACLES TO MATCH CONFIGURATION DIAGRAM IN NEMA WD 6.

a. RECEPTACLES ORIENTED HORIZONTALLY SHALL BE MOUNTED WITH NEUTRAL BLADE FACING UP.

2. IDENTIFICATION

A. MARK INSIDE OF COVER OR COVER PLATE OF WIRING DEVICE(S) WITH PANELBOARD AND CIRCUIT NUMBER FEEDING WIRING DEVICE(S).

SECTION 26 2726

WIRING DEVICES

THE FOLLOWING DIMENSION EQUALS

ONE INCH WHEN PRINTED TO SCALE.

1"

Project No:

Drawing Title:

© 2026 IGNYTE DESIGN

SCALE

STAMP

Issued For: Date

E001

ELECTRICAL

SPECIFICATIONS

KITCHEN

GENERATOR

26.068

JUNE 11, 2026CONSTRUCTION

U

IT

'E

U

N

IT

'F ' U

N

IT

'K

UNIT 'J'

UNIT 'E'

UNIT 'K'

UNIT 'J'

UNIT 'K'

MENS

FREEZERCOOLER CART WASH

TRASH

DRY STORAGE

OFFICE

KITCHEN

PREP.

902 903 904 905

IDF / JANITOR

SERVING 'A'

SERVING 'B'

STOR.

TOILET

JANITOR

LOCKER

A LA CARTE

STORAGE

KILN

STORAGE

902 903 904 906

909 914

915A

915B

EQ EQ

EQ

EQ

W P

J J

J

1 K2

K1

EMK

ATS-EMK

GENERATOR

GENERATOR

EMERGENCY SHUT OFF

COOLER FREEZER

EMK-1,3 EMK-2,4

EMK-6,8,10

EMK-5,7,9

GENERATOR REMOTE

ANNUCIATOR

PROVIDE NEW CONCRETE

PAD, CUT AND PATCH

EXISTING CONCRETE AS

REQUIRED.

MDP1

RUN CONDUIT ABOVE EXISTING CEILING. PAINT

CONDUIT TO MATCH CEILING IN EXPOSED AREAS.

CONTRACTOR TO PROVIDE BEST POSSIBLE ROUTE.

EXPOSED CONDUIT

SHALL BE RIGID

GALVANIZED.

2 2

K2-1

COOLER ACCU

FREEZER ACCU

EMK-11

EMK-11

EMK-12

COOLER LTS FREEZER LTS

FREEZER HEAT TAPE

2 2

CONCRETE EQUIPMENT PAD

SUB-BASE DAY TANK

CONNECT BLOCK HEATER, BATTERY CHARGER, BATTERY

HEATER ETC. TO EXISTING PANEL K2

GEN

CONTROL

GENERATOR

E-STOP

GENERATOR

ANNUNCIATOR

MANUFACTURER

RECOMMENDED CABLE

(2) #14's

ATS

EMK

SEE ONE LINE

DIAGRAM

(10) #14's

ATS

ANNUNCIATOR

SB

MANUFACTURER

RECOMMENDED CABLE

PROVIDE CABLING FOR THE FOLLOWING SIGNALS:

• GENERATOR START

• GENERATOR RUNNING

• GENERATOR STOP

• GENERATOR TROUBLE

• SPARE

SAND FILL

#4 CONT.

SIZE PAD IN ACCORDANCE

WITH UTILITY CO. STANDARDS

OR MANUFACURERS

RECOMMENDATION. PROVIDE

CONDUIT AS REQUIRED.

#4 REINF. BARS 12" O.C.

12"

2"

OUTDOOR GENERATOR PAD

MDP1

208/120V, 3PH, 4W, 800A

GENERATOR

G

40/50 kW/kVA

208/120V, 3PH, 4W

DIESEL

N E

ATS-EMK

STAND-BY

150A

208V, 3PH, 4W

PANEL

EMK

PANEL

GG

PANEL

H

PANEL

N

PANEL

M

PANEL

K1

PANEL

K2

PANEL

K3

PANEL

L

PANEL

P

PANEL

MSP1

SPD

AHU-3

PROVIDE NEW CIRCUIT BREAKER IN EXISTING SQUARE D

HCP STYLE PANEL. MATCH EXISTING AIC RATING.

4 #1/0, 1 #6 GND. 2" C. 4 #1/0, 1 #6 GND. 2" C.

4 #1/0, 1 #6 GND. 2" C.

NOTE:

THERE ARE NO NEW LOADS BEING ADDED TO THE SYSTEM. EXISTING LOADS

FROM PANEL K2 ARE BEING RE-CIRCUITED TO A NEW STAND-BY PANEL EMK.

MARK EXISTING BREAKERS AS SPARE

FOR EQUIPMENT BEING RE-CIRCUITED

THE FOLLOWING DIMENSION EQUALS

ONE INCH WHEN PRINTED TO SCALE.

1"

Project No:

Drawing Title:

© 2026 IGNYTE DESIGN

SCALE

STAMP

Issued For: Date

E110

FIRST FLOOR POWER

PLAN

KITCHEN

GENERATOR

26.068

JUNE 11, 2026CONSTRUCTION

8' 16'4'0 1/8" = 1'-0"E110

1 FIRST FLOOR POWER PLAN

ELECTRICAL POWER KEYED NOTES

1 RENAME EXISTING COOLER AND FREEZER CIRCUIT BREAKERS AS

SPARE. REMOVE WIRE FROM PANEL AND MAKE READY FOR

CONNECTION TO NEW PANEL.

2 REFEED EXISTING EQUIPMENT FROM NEW STANDBY PANEL. REUSED

CONDUIT AND WIRE WHERE POSSIBLE, EXTEND AS REQUIRED.

MATCH EXISTING WIRE AND CONDUIT SIZE.

NOT TO SCALEE110

2 BUILDING ELECTRICAL SYSTEM GROUND BUS

NOT TO SCALEE110

3 CONCRETE EQUIPMENT PAD DETAIL

NOT TO SCALEE110

4 PARTIAL ELECTRICAL ONE LINE DIAGRAM

Notes:

Demand Current: 58 A

Demand Load: 21 kVA

Connected Current: 58 A

POWER 900 VA 100.00... 900 VA Connected Load: 21 kVA

HVAC 19944 VA 100.00... 19944 VA

Load Classification Connected Factor Demand

Current: 62 A 62 A 53 A

Connecte... 7 kVA 7 kVA 6 kVA

41 SPARE 20 1 0 -- 1 -- SPACE 42

39 SPARE 20 1 0 -- 1 -- SPACE 40

37 SPARE 20 1 0 -- 1 -- SPACE 38

35 SPARE 20 1 0 -- 1 -- SPACE 36

33 SPARE 20 1 0 -- 1 -- SPACE 34

31 SPARE 20 1 0 -- 1 -- SPACE 32

29 SPARE 20 1 0 -- 1 -- SPACE 30

27 SPARE 20 1 0 -- 1 -- SPACE 28

25 SPARE 20 1 0 -- 1 -- SPACE 26

23 SPARE 20 1 0 -- 1 -- SPACE 24

21 SPARE 20 1 0 -- 1 -- SPACE 22

19 SPARE 20 1 0 -- 1 -- SPACE 20

17 SPARE 20 1 0 -- 1 -- SPACE 18

15 SPARE 20 1 0 -- 1 -- SPACE 16

13 SPARE 20 1 0 -- 1 -- SPACE 14

11 COOLER/FREEZER LIGHTS 20 1 400 500 1 20 FREEZER HEAT TAPE 12

9 1800 3600 10

7 1800 3600 8

COOLER ACCU 20 3

1800 3600

3 40 FREEZER ACCU

3 850 1022 4

COOLER FAN COIL 15 2

850 1022

2 15 FREEZER FAN COIL

Ckt Description Trip

(A) Poles

ARC

FAU...

GFC

I

Phase A Load (VA)

Phase B Load (VA)

Phase C Load (VA)

GFC

I

ARC

FAU... Poles Trip

(A) Description Ckt

FED FROM: ATS-EMK RATING: 150.0 A MOUNTING: SURFACE

LOCATION:

VOLTS: 208Y/120,3Ø,4W A.I.C. RATING: 22,000

Panelboard: EMK

Sheets
E000 - ELECTRICAL SYMBOLS AND GENERAL NOTES
E001 - ELECTRICAL SPECIFICATIONS
E110 - FIRST FLOOR POWER PLAN
G000 - COVER SHEET
P110 - FIRST FLOOR PLUMBING PLAN

File details come from the government source that posted it. Updated .