26.068_PCS_KITCHEN GENERATOR_MEP_20260611.pdf
PDF 3 MB Posted
- Attached to
- Kitchen Generator
- Solicitation number
- RFP PCS 260000002267 1
- Issued by
- Allegan County, Michigan
About this file
This is a design and construction documentation file for a Kitchen Generator installation project at Plainwell Community Schools, located at 684 Starr Rd, Plainwell, Michigan 49080. The scope of work involves providing electrical power and natural gas infrastructure for a new generator installation that will serve a kitchen cooler and freezer system. The project documentation was prepared by IGNYTE DESIGN with MEP Engineer Lentz Becraft, PE, and is dated June 11, 2026. The design follows Michigan Building Code (2021), Michigan Mechanical Code (2021), Michigan Plumbing Code (2021), Michigan Electrical Code (NFPA 70, 2023), Michigan Energy Code (IECC/ASHRAE 90.1, 2021), Michigan Fire Sprinkler Code (NFPA 13, 2022), and ASHRAE Standard 55 (2023).
The project specifications detail comprehensive electrical and mechanical systems requirements. Electrical work includes installation of a new 40-50 kW/kVA diesel generator rated at 208/120V, 3-phase, 4-wire configuration, with a 150A automatic transfer switch (ATS-EMK) and associated standby panel (EMK). Natural gas piping work involves routing 1.5-inch and 4-inch gas lines from a building connection through the ceiling to the generator location below grade, with proper sizing for 500 CFH at 7-inch water gauge. The electrical system requires installation of new circuit breakers, recircuiting of existing cooler and freezer equipment loads from an existing panel (K2) to the new standby panel, conduit routing above existing ceilings with painted finish matching, and complete grounding and bonding per National Electrical Code standards. Installation specifications mandate use of licensed gas piping installers, qualified welders per ASME Section IX standards, full system pressure testing at 1.5 times operating pressure minimum, and demonstration and training upon completion. All work must comply with applicable codes and standards with materials and workmanship requirements governed by detailed schedules and specifications provided in the design documentation.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
THE FOLLOWING DIMENSION EQUALS
ONE INCH WHEN PRINTED TO SCALE.
1"
Project No:
Drawing Title:
© 2026 IGNYTE DESIGN
SCALE
STAMP
Issued For: Date
PROJECT DIRECTORY APPLICABLE CODES PROJECT SCOPE OF WORK SHEET INDEX
MEP ENGINEER:
DESIGN PROFESSIONAL CONTACT:
PROJECT LOCATION
G000
COVER SHEET
KITCHEN
GENERATOR
26.068
JUNE 11, 2026CONSTRUCTION
KITCHEN GENERATOR
PLAINWELL COMMUNITY SCHOOLS
684 Starr Rd, Plainwell, MI 49080
THE SCOPE OF WORK IS TO PROVIDE POWER AND NATURAL GAS FOR A NEW
GENERATOR INSTALLATION FOR A KITCHEN COOLER/FREEZER.
IGNYTE DESIGN
LENTZ BECRAFT, PE
(269) 203-5058
LBECRAFT@IGNYTE.DESIGN
• MICHIGAN BUILDING CODE (MBC) – 2021
• MICHIGAN MECHANICAL CODE (IMC) – 2021
• MICHIGAN PLUMBING CODE (IPC) – 2021
• MICHIGAN ELECTRICAL CODE (NFPA 70) – 2023
• MICHIGAN ENERGY CODE (IECC/ASHRAE 90.1) – 2021
• MICHIGAN FIRE SPRINKLER CODE (NFPA 13) – 2022
• ASHRAE STANDARD 55 – 2023
123 DEVISSER PLACE
KALAMAZOO, MI 49007
G000 COVER SHEET
P110 FIRST FLOOR PLUMBING PLAN
E000 ELECTRICAL SYMBOLS AND GENERAL NOTES
E001 ELECTRICAL SPECIFICATIONS
E110 FIRST FLOOR POWER PLAN
U
IT
'E
U
N
IT
'F ' U
N
IT
'K
UNIT 'J'
UNIT 'E'
UNIT 'K'
UNIT 'J'
UNIT 'K'
MENS
FREEZERCOOLER CART WASH
TRASH
DRY STORAGE
OFFICE
KITCHEN
PREP.
902 903 904 905
IDF / JANITOR
SERVING 'A'
SERVING 'B'
STOR.
TOILET
JANITOR
LOCKER
A LA CARTE
STORAGE
KILN
STORAGE
902 903 904 906
909 914
915A
915B
GRADE
DIRT LEG
GENERATOR
SHUT-OFF VALVE
PRESSURE REGULATOR PIPE VENT
OUTLET WITH DOWNTURN ELBOW
SIZED FOR 500 CFH @ 7" WG
UNION
1 1/2" G TO BUILDING
[E] 1 1/2" G
[E
G
[E] 4" G
[E
G
GENERATOR
1 1/2" G
1/
G
1 1/2" G
SLEEVE THRU WALL, THEN ROUTE
BELOW GRADE TO GENERATOR
ROUTE GAS PIPING ABOVE
EXISTING CEILING. PAINT PIPING
TO MATCH CEILING IN EXPOSED
AREAS. CONTRACTOR TO PROVIDE
BEST POSSIBLE ROUTE.
THE FOLLOWING DIMENSION EQUALS
ONE INCH WHEN PRINTED TO SCALE.
1"
Project No:
Drawing Title:
© 2026 IGNYTE DESIGN
SCALE
STAMP
Issued For: Date
P110
FIRST FLOOR PLUMBING
PLAN
KITCHEN
GENERATOR
26.068
JUNE 11, 2026CONSTRUCTION
NO SCALEP110
2 GENERATOR CONNECTION DETAIL
8' 16'4'0 1/8" = 1'-0"P110
1 FIRST FLOOR PLUMBING PLAN
PART 1 - GENERAL
1. SECTION INCLUDES:
• NATURAL-GAS PIPING SYSTEMS WITH VALVES, FITTINGS, AND APPURTENANCES.
• PIPING MATERIALS, JOINTS, AND CONNECTIONS TO EQUIPMENT.
• VALVE BOXES AND IDENTIFICATION.
2. REFERENCES:
• NFPA 54 – NATIONAL FUEL GAS CODE.
• ASTM A53/A53M – STEEL PIPE, BLACK AND HOT-DIPPED ZINC-COATED.
• ASME B31.9 – BUILDING SERVICES PIPING.
• ANSI Z223.1 – FUEL GAS CODE.
• IFGC – INTERNATIONAL FUEL GAS CODE.
3. QUALITY ASSURANCE:
• INSTALLER SHALL BE LICENSED FOR GAS PIPING WORK IN THE JURISDICTION OF INSTALLATION.
• MATERIALS AND WORKMANSHIP SHALL COMPLY WITH APPLICABLE CODES AND STANDARDS.
• WELDERS AND BRAZERS SHALL BE QUALIFIED IN ACCORDANCE WITH ASME SECTION IX.
4. REFERENCE DOCUMENTS:
A. REFER TO MECHANICAL PIPING & VALVE APPLICATION SCHEDULE, MECHANICAL PIPE & ACCESSORY INSULATION
APPLICATION SCHEDULE, DUCT SYSTEM APPLICATION SCHEDULE, MECHANICAL EQUIPMENT INSULATION
APPLICATION SCHEDULE, AND DUCT ACCESSORY INSULATION APPLICATION SCHEDULE ON SHEET M007 FOR
REQUIRED PIPE, DUCT, EQUIPMENT, AND ACCESSORY MATERIALS, CONNECTION TYPES, VALVES, AND INSULATION
APPLICATIONS.
B. THESE SCHEDULES GOVERN MATERIAL, INSTALLATION, AND INSULATION REQUIREMENTS FOR ALL HVAC SYSTEMS
UNLESS OTHERWISE NOTED IN THE CONTRACT DOCUMENTS.
C. COORDINATE ALL SUBMITTALS, INSTALLATION DETAILS, AND FIELD APPLICATIONS WITH THE MATERIALS AND
REQUIREMENTS INDICATED ON SHEET M007.
PART 2 - PRODUCTS
1. STEEL PIPE:
• ASTM A53/A53M, TYPE E OR S, GRADE B, SEAMLESS OR ELECTRIC-RESISTANCE WELDED, SCHEDULE 40.
• ENDS THREADED OR GROOVED AS REQUIRED.
2. PIPE FITTINGS:
• MALLEABLE-IRON THREADED FITTINGS CONFORMING TO ASME B16.3.
• WROUGHT-STEEL BUTT-WELDING FITTINGS ASME B16.9 WHERE INDICATED.
3. VALVES:
• BALL VALVES RATED FOR 125 PSIG MINIMUM, BRASS OR STEEL BODY, THREADED ENDS.
• PLUG VALVES NOT PERMITTED EXCEPT WHERE REQUIRED BY MANUFACTURER.
4. UNIONS AND JOINTS:
• THREADED UNIONS OF FORGED STEEL WITH GROUND JOINT SURFACES.
• DIELECTRIC UNIONS WHERE CONNECTING DISSIMILAR METALS.
5. VALVE BOXES AND COVERS:
• CAST-IRON BOXES WITH BOLTED COVERS LABELED “GAS.”
6. PIPE HANGERS AND SUPPORTS:
• GALVANIZED STEEL RING OR CLEVIS TYPE IN ACCORDANCE WITH SECTION 23 0529.
7. PIPE IDENTIFICATION:
• YELLOW LABEL TAPE WITH BLACK LETTERING “NATURAL GAS.”
PART 3 - EXECUTION
1. INSTALLATION:
• INSTALL PIPING AS INDICATED, TRUE TO LINE AND GRADE, WITH PROPER SUPPORT AND ALLOWANCE FOR MOVEMENT.
• MAINTAIN CLEARANCE FROM ELECTRICAL CONDUITS AND HEAT SOURCES PER CODE.
• PROVIDE UNIONS AT EQUIPMENT CONNECTIONS AND VALVES.
• PROVIDE SHUT-OFF VALVES AT EACH BRANCH AND EACH EQUIPMENT CONNECTION.
• INSTALL PIPING SLOPED NOT LESS THAN 1/4 INCH PER 15 FEET TO DRAIN POINTS.
2. JOINTING:
• THREAD PIPE WITH NPT THREADS; USE APPROVED PIPE DOPE SUITABLE FOR NATURAL GAS.
• TIGHTEN JOINTS TO ENSURE GAS-TIGHT SEAL WITHOUT OVERSTRESSING.
• WELD JOINTS WHERE INDICATED BY QUALIFIED WELDERS.
3. VALVE INSTALLATION:
• INSTALL VALVES IN ACCESSIBLE LOCATIONS WITH STEMS UPRIGHT OR HORIZONTAL.
• INSTALL SHUTOFF VALVE UPSTREAM OF EACH PIECE OF GAS-FIRED EQUIPMENT.
4. FIELD QUALITY CONTROL:
• TEST ENTIRE SYSTEM AT 1.5 TIMES OPERATING PRESSURE BUT NOT LESS THAN 10 PSIG FOR 10 MINUTES MINIMUM.
• USE DRY NITROGEN OR AIR FOR TESTING; DO NOT USE NATURAL GAS.
• INSPECT FOR LEAKS USING SOAP SOLUTION OR ELECTRONIC DETECTOR.
• REPAIR LEAKS AND RETEST UNTIL SYSTEM IS LEAK-FREE.
5. PAINTING AND IDENTIFICATION:
• CLEAN EXPOSED PIPING AND APPLY PRIMER AND SAFETY YELLOW FINISH COAT WHERE NOT FACTORY-COATED.
• LABEL ALL EXPOSED PIPING WITH FLOW DIRECTION ARROWS AND SERVICE NAME.
6. DEMONSTRATION AND TRAINING:
• PROVIDE OPERATION AND MAINTENANCE INSTRUCTION TO OWNER’S REPRESENTATIVE UPON COMPLETION OF TESTS.
SECTION 23 1123 - FACILITY NATURAL-GAS PIPING
ELECTRICAL ABBREVIATION LIST
ABBREVIATION DESCRIPTION
A
AF
AFCI
A.F.F.
AIC
AL
AR
AT
ATS
AUX
BKR
BPS
C
CB
CKT
CT
DEMO
DIM
DISC
DP
DS
DWG
EBU
EC
ELEC
EM/ EMERG
EMT
EO
EPO
EWC
EXIST
EXT
FA
FLA
FLR
FOH
FSEC
FU
G/GRD/EG
GFCI
GFP
HOA
HP
HV
HZ
IG
JB
KV
KVA
KW
KWH
LA
LP
LDP
AMPERES
AMPERES FRAME (BREAKER RATING)
ARC FAULT CIRCUIT INTERRUPTER
ABOVE FINISH FLOOR
AMPS INTERRUPTING CAPACITY
AUDIENCE LEFT
AUDIENCE RIGHT
AMPERS TRIP (BREAKER SETTING)
AUTOMATIC TRANSFER SWITCH
AUXILIARY
BREAKER
BOLTED PRESSURE SWITCH
CONDUIT
CIRCUIT BREAKER
CIRCUIT
CURRENT TRANSFORMER
DEMOLITION
DIMENSION
DISCONNECT
DISTRIBUTION PANEL
DOWNSTAGE
DRAWING
EMERGENCY BATTERY UNIT
ELECTRICAL CONTRACTOR
ELECTRICAL
EMERGENCY
ELECTRICAL METALLIC TUBING
ELECTRICALY OPERATED
EMERGENCY POWER OFF
ELECTRIC WATER COOLER
EXISTING
EXTERIOR
FIRE ALARM
FULL LOAD AMPS
FLOOR
FRONT OF HOUSE
FOOD SERVICE EQUIPMENT
FUSE
GROUND
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT PROTECTION
HAND-OFF-AUTO
HORSEPOWER
HIGH VOLTAGE
HERTZ
ISOLATED GROUND
JUNCTION BOX
KILOVOLT
KILOVOLT - AMPERES
KILOWATT
KILOWATT - HOURS
LIGHTING ARRESTOR
LIGHTING PANEL
LIGHTING DISTRIBUTION PANEL
MAX
MCB
MCC
MDP
MECH
MIN
MISC.
MLO
MTD
MTG
MTR
N
NC
NEC
NF
NIC
NL
NO
NTS
OC
OFCI
OFOI
P
PB
PH
PT
PDP
RECEPT.
RCP
RDP
RP
RSC
SCHED
SW
SWBD
SWGR
TB
TELECOM
TR
TTP
TYP
UNO
US
V
W
WG
WP
XFMR
XP
(E)
(R)
MAXIMUM
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION PANEL
MECHANICAL
MINIMUM
MISCELLANEOUS
MAIN LUGS ONLY
MOUNTED
MOUNTING
MOTOR
NEUTRAL
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NON-FUSIBLE
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
ON CENTER
OWNER FURNISHED,
CONTRACTOR INSTALLED
OWNER FURNISHED,
OWNER INSTALLED
POLE
PUSHBUTTON STATION
PHASE
POTENTIAL TRANSFORMER
POWER DISTRIBUTION PANEL
RECEPTACLE
RECEPTACLE
RECEPTACLE DISTRIBUTION PANEL
RECEPTACLE PANEL
RIGID STEEL CONDUIT
SCHEDULE
SWITCH
SWITCHBOARD
SWITCHGEAR
TERMINAL BOX
TELECOMMUNICATIONS
TAMPER RESISTANT
TELEPHONE TERMINAL BACKBOARD
TYPICAL
UNLESS OTHERWISE NOTED
UPSTAGE
VOLTS
WIRE OR WATTS
WIRE GUARD
WEATHERPROOF
TRANSFORMER
EXPLOSION PROOF
EXISTING
RELOCATED
ELECTRICAL SYMBOL LIST
SYMBOL DESCRIPTION
LIGHTING FIXTURE - ARCHITECTURAL TROFFER
EMERGENCY LIGHTING FIXTURE
LIGHTING FIXTURE - PENDANT
WALL MOUNTED LIGHTING FIXTURE
LIGHTING FIXTURE
LIGHTING TRACK OR ROPE LIGHT
TRACK LIGHTING FIXTURE
EMERGENCY LIGHTING UNIT
POLE MOUNTED LIGHTING FIXTURE
POLE MOUNTED LIGHTING FIXTURE - POST TOP
BOLLARD LIGHTING FIXTURE
EXIT LIGHTING FIXTURE WITH DIRECTIONAL
ARROWS (SHADED AREA INDICATES FACE)
EXIT LIGHTING FIXTURE WITH DIRECTIONAL
ARROWS (SHADED AREA INDICATES FACE)
EXIT LIGHTING FIXTURE - WALL MOUNTED
SINGLE POLE TOGGLE SWITCH
TWO POLE TOGGLE SWITCH
3 WAY TOGGLE SWITCH
4 WAY TOGGLE SWITCH
KEY OPERATED SWITCH
DIMMER SWITCH
PILOT SWITCH
OCCUPANCY SENSOR DEVICE - CEILING
SIMPLEX / DUPLEX RECEPTACLE
SIMPLEX / DUPLEX RECEPTACLE CONTROLLED BY
AUTOMATIC CONTROL DEVICE / SYSTEM
QUAD RECEPTACLE
ABOVE COUNTER DUPLEX RECEPTACLE (SIMILAR FOR
TAMPER RESISTANT, QUADS, EMERGENCY AND GFI
RECEPTACLES)
DUPLEX RECEPTACLE-GROUND FAULT CIRCUIT
INTERRUPTER
DUPLEX EMERGENCY RECEPTACLE
CEILING MOUNTED
DUPLEX RECEPTACLE
SPECIAL RECEPTACLE - REFER TO ELECTRICAL
STANDARD SCHEDULES
MULTI-OUTLET RACEWAY - LEGRAND AL3300 OR EQUAL
POKE-THROUGH ASSEMBLY - LEGRAND
EVOLUTION SERIES OR EQUAL
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
CONTROL PANEL
VARIABLE FREQUENCY DRIVE
MOTOR
MANUAL CONTROLLER
MAGNETIC CONTROLLER
COMBINATION MAGNETIC CONTROLLER
NON-FUSIBLE DISCONNECT SWITCH
FUSIBLE DISCONNECT SWITCH
ENCLOSED CIRCUIT BREAKER
PUSH BUTTON STATION
AUTOMATIC DOOR CONTROLLER
AUTOMATIC DOOR PUSH PAD OPERATOR
GROUND ROD
GROUND CONNECTION
CONDUIT SLEEVE WITH BUSHINGS; LENGTH AS REQUIRED
"X" INDICATES CONDUIT SIZE, 2" UNLESS NOTED OTHERWISE
CONDUIT STUB - UP/DOWN, 2" CONDUIT UNLESS
NOTED OTHERWISE.
EMPTY BOX FOR FUTURE
TELECOMMUNICATION OUTLET
EMPTY BOX FOR FUTURE TELECOMMUNICATION
OUTLET MOUNTED 4" ABOVE COUNTERTOP
EMPTY BOX FOR FUTURE CEILING MOUNTED
TELECOMMUNICATION OUTLET
TELECOMMUNICATION OUTLET
"X" INDICATES TYPE
SPEAKER
SPEAKER - WALL MOUNTED
MICROPHONE
VOLUME CONTROL
SIGNALING BELL
SINGLE FACE CLOCK - CEILING MOUNTED
SINGLE FACE CLOCK - WALL MOUNTED
DOUBLE FACE CLOCK - CEILING MOUNTED
DOUBLE FACE CLOCK - WALL MOUNTED
P
PT
FB
CP
VFD
CB
DP
PP
X
X
S
S
MIC
VC
B
USB RECEPTACLE
GENERATOR TRANSFER DEVICEGTD
REMOTE GENERATOR ANNUNCIATOR PANELRGP
AUTOMATIC TRANSFER SWITCHATS
SWITCHBOARD
BRANCH CIRCUIT PANEL BOARD - 208/120V
TRANSFORMER
DISTRIBUTION PANEL - 208/120V
SECURITY CAMERA
MOTION DETECTOR
SECURITY KEY SWITCH
DOOR CONTACT
KEY PAD
CARD READER
CIRCUIT BREAKER
DRAWOUT CIRCUIT BREAKER
MANUALLY/ OPERATED
SWITCH
AUTOMATIC OR MANUAL TRANSFER
SWITCH
FUSE
TRANSFORMER
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
LIGHTNING ARRESTOR
PANELBOARD
"X" INDICATES PANELBOARD NAME
GROUND
SECURITY KEY INTERLOCK
ENGINE GENERATOR
UTILITY METER
AMMETER
VOLTMETER
AMMETER SWITCH
VOLTMETER SWITCH
SURGE PROTECTIVE DEVICE
TIME DELAY RELAY
THERMAL OVERLOAD RELAY
NORMALLY OPEN CONTACTS
NORMALLY CLOSED CONTACTS
N.O. PUSH BUTTON SINGLE CIRCUIT
N.C. PUSH BUTTON SINGLE CIRCUIT
GROUND BUS
MD
K
DC
KP
CR
X
K
G
M
A
V
AS
VS
SPD
TDR
GB
DURESS PUSH BUTTON STATION
DELAYED EGRESS
DB
DE
REQUEST TO EXIT STATIONREX
MANUAL FIRE ALARM PULL STATION
SMOKE DETECTOR
REMOTE TEST STATION (FOR DUCT DETECTOR)
FIRE ALARM BELL
NOTIFICATION APPLIANCE - WALL MOUNT SPEAKER/STROBE
TAMPER SWITCH
FLOW SWITCH
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
F
SD
RT
F
F
TS
FS
FACP
FAA
NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANELNAC
R
E F
E R
T O
E L
E C
T R
IC
A
L
S T
A N
D A
R D
S C
H E
D U
L E
S
DIMMER OCCUPANCY SENSOR SWITCH
LOW VOLTAGE DIMMER SWITCH
POWER POLE - WIREMOLD TYPE
F NOTIFICATION APPLIANCE - CEILING MOUNT SPEAKER/STROBE
LIGHTING CONTROL DEVICE - REFER TO LIGHTING
CONTROL SCHEDULE
LC
K
D
OS
LV
GFI
USB
CLG
FLOOR BOX ASSEMBLY - LEGRAND
EVOLUTION SERIES OR EQUAL
TOUCH SCREEN SWITCHTS
OS
OCCUPANCY SENSOR DEVICE - WALLOS
PC PHOTOCELL DEVICE - REFER TO ZONES SHOWN ON
PLANS
EQ
EQUIPMENT CONNECTION - REFER TO ELECTRICAL
FEEDER AND PANEL SCHEDULE FOR BREAKER AND
CONDUCTOR SIZE/QUANTITY
J JUNCTION BOX
EMERGENCY POWER OFF BUTTON
V NOTIFICATION APPLIANCE - CEILING MOUNT STROBE
NOTIFICATION APPLIANCE - WALL MOUNT STROBEV
BRANCH CIRCUIT PANEL BOARD - 480/277V
DISTRIBUTION PANEL - 480/277V
CARBON MONOXIDE DETECTORCO
HEAT DETECTORHD
BEAM DETECTORBD
DUCT DETECTORDD
SMOKE DETECTOR - ELEVATOR TYPE; CONNECT TO FIRE ALARM
SYSTEM AND ELEVATOR CONTROL PANEL
SD
E
SPRINKLER VALVE MONITOR SWITCHOSY
SMOKE DAMPERSD
MAGNETIC DOOR HOLDERDH
S NOTIFICATION APPLIANCE - CEILING MOUNT SPEAKER
NOTIFICATION APPLIANCE - WALL MOUNT SPEAKERS
FIRE ALARM BATTERY CABINETBATT
EXIT FIXTURE-BACK
MOUNTED BOTTOM OF EXIT
SIGN TO BE 4" ABOVE TOP OF
DOOR FRAME
EXIT
EXIT
1' -6
EXIT
A/C SUPPLY
DIFFUSER
90" MAX (IBC)
4' -0
5"
8' -6
EXIT-CEILING MOUNTED
EXIT-FIXTURE END
MOUNTED
NFPA 72 AUDIBLE APPLIANCE 6" MIN
BELOW FINISHED CEILING
EMERGENCY
BATTERY
FIXTURE
ABOVE FINISHED FLOOR
AUDIBLE 80" MIN (IBC)
CEILING HEIGHTS LESS THEN 86" VISUAL
LENS MOUNTING HEIGHT WILL BE WITHIN 6"
OF THE CEILING
FINISHED CEILING
AUDIO/VISUAL &
VISUAL ONLY
DEVICES
SYNCHRONIZE MORE THAN
TWO APPLIANCES IN ANY
FIELD OF VIEW
MANUAL PULL STATION
AUDIBLE
ONLY
'-8
DOOR WIDTH LESS THEN 3'-0"
(MODIFY FOR DIFFERENT
DOOR WIDTHS)
FINISHED FLOOR
O R
A P
P R
O V
E D
F R
O M
A H
J
M
IN
A B
O V
E F
IN
IS
H E
D F
L O
O R
CEILING MOUNTED SMOKE/HEAT
DETECTOR
3'-0" MIN 4"
NOTES:
1. INSTALL ELECTRICAL DEVICES AT MOUNTING HEIGHTS NOTED ABOVE UNLESS OTHERWISE NOTED ON PLANS. COORDINATE WITH ALL OTHER DISCIPLINES PRIOR TO INSTALL.
2. VISUAL MOUNTING APPLIANCE MOUNTING HEIGHT IN SLEEPING ROOMS:
A. MINIMUM DISTANCE IN SLEEPING ROOMS IS 24" FROM CEILING TO THE TOP OF LENS FOR 110cd STROBES WITHIN 16' OF PILLOW
B. 177cd STROBES, USED IN SLEEPING ROOMS, CAN BE WITHIN THE 24" MINIMUM DISTANCE FROM THE CEILING, THE HIGHER INTENSITY IS TO COMPENSATE FOR A POSSIBLE SMOKE LAYER
7' -6
(M
IN
(M
A X
1' -0
"4"
M A
X
DO NOT INSTALL HEAT DETECTOR IN
SHADED AREA
WALL MOUNTED
SMOKE/HEAT
DETECTOR
MAGNETIC
DOOR
HOLDER
FINISHED WALL
SWITCHBANK
AUTOMATIC DOOR OPERATOR PUSH
BUTTON
RECEPTACLE, DATA JACK OR
TELEPHONE JACK
3'-0"
5' MAX TO EXIT DOOR
4' -0
4"
7' -6
ELECTRICAL DEVICE TYPICAL MOUNTING HEIGHTS
6' -6
BRANCH CIRCUIT PANELBOARDS
DISCONNECT SWITCH
5' -0
THE FOLLOWING DIMENSION EQUALS
ONE INCH WHEN PRINTED TO SCALE.
1"
Project No:
Drawing Title:
© 2026 IGNYTE DESIGN
SCALE
STAMP
Issued For: Date
E000
ELECTRICAL SYMBOLS
AND GENERAL NOTES
KITCHEN
GENERATOR
26.068
JUNE 11, 2026CONSTRUCTION
NOTE: SOME SYMBOLS AND ABBREVIATIONS SHOWN
MAY NOT APPLY TO THIS PROJECT.
GENERAL ELECTRICAL NOTES
1. CONTRACTOR TO PROCURE ALL REQUIRED BUILDING PERMITS AND INSPECTIONS TO COMPLETE PROJECT.
2. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE MICHIGAN ELECTRICAL CODE.
3. PROVIDE NEW ELECTRICAL SERVICES FROM CONSUMERS ENERGY AS INDICATED. COORDINATE SCOPE OF WORK AND PROVIDE ALL WORK TO PROVIDE A FULLY FUNCTIONAL ELECTRICAL SERVICE.
4. CONTRACTOR SHALL MEASURE AND VERIFY ALL LINE-LINE AND LINE-GROUND VOLTAGES PRIOR TO COMMENCING ANY WORK ON EXISTING ELECTRICAL DISTRIBUTION SYSTEMS. CONTRACTOR SHALL
REPORT BACK TO ENGINEER ANY SYSTEM VOLTAGES THAT ARE IN CONFLICT WITH INFORMATION AS SHOWN ON PLANS, ELECTRICAL ONE LINE DIAGRAM, AND SCHEDULES.
5. REMOVE ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, ETC ASSOCIATED WITH DEMOLISHED EQUIPMENT.
6. REMOVE ALL ABANDONDED ELECTRICAL CONDUIT AND WIRE BACK TO SOURCE.
7. PROVIDE SHOP DRAWINGS FOR THE FOLLOWING:
A. CONDUIT.
B. CONDUCTORS.
C. WIRING DEVICES INCLUDING COVERPLATES.
D. DISCONNECT SWITCHES, ENCLOSED CIRCUIT BREAKERS AND FUSED SWITCHES.
E. PANELBOARDS. AND SWITCHBOARDS
F. TRANSFORMERS.
G. SURGE PROTECTION DEVICES
H. POWER METERS.
I. INTERIOR LIGHT FIXTURES.
J. EXTERIOR LIGHT FIXTURES INCLUDING SITE POLES.
K. LIGHTING CONTROL SYSTEM AND DEVICES.
L. FIRE ALARM SYSTEM.
8. PATCH, REPAIR, AND PAINT ANY OPENINGS THROUGH ROOF, CEILINGS, WALLS, OR FLOORS TO MATCH EXISTING CONDITION.
9. THE OWNER SHALL HAVE FIRST RIGHT OF REFUSAL OF ALL DEMOLISHED EQUIPMENT.
10. PROVIDE LAMACOID LABELS FOR:
A. PANELBOARDS AND SWITCHBOARDS.
B. TRANSFORMERS.
C. DISCONNECT SWITCHES.
D. VARIABLE FREQUENCY DRIVES.
E. LIGHTING CONTROL PANELS. LABEL SHALL INDICATE ROOMS CONTROLLED.
11. MINIMUM CONDUIT SIZE SHALL BE 1/2" TRADE SIZE.
12. USE THE CONDUIT TYPE SUITABLE FOR THE ENVIRONMENT IN WHICH IS IS LOCATED:
A. INDOORS: EMT WITH SET SCREW FITTINGS. MC CABLE IS ACCEPTABLE FOR BRANCH CIRCUITS WHERE CONCEALED.
B. OUTDOORS: RIGID GALVANIZED STEEL.
C. UNDERGROUND: RIGID NON METALLIC SCHEDULE 80 PVC.
D. CONDUIT EXITING FROM UNDERGROUND SHALL TRANSITION TO EMT/RGS PRIOR TO BEING EXPOSED.
13. PROVIDE CONDUIT SLEEVES FOR LOW VOLTAGE DATA CABLING.
14. ALL CABLING SHALL BE IN CONDUIT UNLESS ABOVE AN ACCESSIBLE CEILING WHERE "J" HOOKS ARE ACCEPTABLE.
15. USE CONDUIT SWEEPS FOR ALL DATA CABLING CONDUITS.
16. DATA BOXES SHALL BE DOUBLE GANG, 3 1/2" DEEP WITH SINGLE GANG MUD RING WITH 1" CONDUIT TO ABOVE ACCESSIBLE CEILING.
17. ALL BOXES SHALL BE RECESSED IN WALLS AND CONDUIT CONCEALED WHERE POSSIBLE.
18. EMERGENCY CIRCUITS SHALL NOT BE IN CONDUIT WITH OTHER NON-EMERGNECY CIRCUITS.
19. MINIMUM CONDUCTOR SIZE FOR POWER SHALL BE #12 AWG. ANY BRANCH CIRCUITS OVER 100' IN LENGTH SHALL BE #10 AWG MINIMUM FOR VOLTAGE DROP.
20. PROVIDE THHN-2 COPPER INDOORS AND THWN-2 COPPER OUTDOORS, UNLESS NOTED OTHERWISE OR DICTATED OTHERWISE BY THE NEC.
21. PROVIDE GROUNDING ELECTRODE SYSTEM AND EQUIPMENT GROUNDING PER THE NATIONAL ELECTRIC CODE.
22. PANELBOARDS SHALL BE FULLY RATED, SERIES RATED PANELS ARE NOT ACCEPTABLE. HAVE HINGED SWING DOOR-IN-DOOR. LOAD CENTERS ARE NOT ACCEPTABLE. SQUARE D NQOD OR EQUAL FOR
208/120V BRANCH PANELBOARDS. SQUARE D NF OR EQUAL FOR 480/277V PANELBOARDS. PROVIDE TYPED PANELBOARD CIRCUIT LABEL CARDS. UPDATE ALL EXISTING LABEL CARDS AS REQUIRED.
23. SURGE PROTECTION DEVICES SHALL BE MOUNTED AS CLOSE TO MAIN BUS AS POSSIBLE TO LIMIT FEEDER LENGTH.
24. ALL FLOOR MOUNTED EQUIPMENT SHALL BE ON 4" HOUSEKEEPING PAD.
25. RECEPTACLES SHALL BE TAMPER-RESISTANT EXTRA HEAVY DUTY GRADE, 20AMP MINIMUM. WHITE IN COLOR UNLESS NOTED OTHERWISE.
26. ALL DEVICE COVERS SHALL MATCH DEVICE COLOR UNLESS STAINLESS STEEL COVERS ARE SPECIFIED.
27. WEATHERPROOF RECEPTACLE COVERS SHALL BE METAL, WHILE-IN-USE TYPE.
28. SWITCHES SHALL BE HEAVY DUTY GRADE, 20 AMP, QUIET TYPE, WHITE UNLESS NOTED OTHERWISE.
29. LIGHTING CONTROL DEVICES SHALL BE MANUFACTURED BY N-LIGHT, UNLESS NOTED OTHERWISE.
30. ALL LIGHTING CONTROLS SHALL MEET ASHRAE 90.1 - 2013 WITH MICHIGAN AMENDMENTS.
31. IT IS UNDERSTOOD AND AGREED BY THE INSTALLER THAT WORK HEREIN DESCRIBED SHALL BE COMPLETE IN EVERY DETAIL, EVEN THOUGH EVERY ITEM INVOLVED IS NOT PARTICULARLY MENTIONED.
INSTALLER SHALL BE HELD TO PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR THE WORK INTENDED AND DESCRIBED FOR A COMPLETE AND OPERATIONAL SYSTEM. SUCH MATERIALS SHALL
INCLUDE, BUT ARE NOT LIMITED TO, CONDUIT, FITTINGS, COVERPLATES, WIRING, BREAKERS, CONTROL DEVICES, LIGHTING ACCESSORIES, ETC. THIS ALSO INCLUDES EQUIPMENT REQUIRED BY STATE AND
LOCAL CODES.
PART 1 - GENERAL
1. IT IS UNDERSTOOD AND AGREED BY THE INSTALLER THAT WORK HEREIN DESCRIBED SHALL BE COMPLETE IN EVERY DETAIL, EVEN THOUGH EVERY ITEM
INVOLVED IS NOT PARTICULARLY MENTIONED. INSTALLER SHALL BE HELD TO PROVIDE ALL LABOR AND MATERIALS NECESSARY FOR THE WORK
INTENDED AND DESCRIBED FOR A COMPLETE AND OPERATIONAL SYSTEM. SUCH MATERIALS SHALL INCLUDE, BUT ARE NOT LIMITED TO, CONDUIT, FITTINGS, COVERPLATES, WIRING, BREAKERS, CONTROL DEVICES, LIGHTING ACCESSORIES, ETC. THIS ALSO INCLUDES EQUIPMENT REQUIRED BY STATE
AND LOCAL CODES.
2. CONTRACTOR TO PROCURE ALL REQUIRED BUILDING PERMITS AND INSPECTIONS TO COMPLETE PROJECT.
3. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE MICHIGAN ELECTRICAL CODE.
4. DO NOT INTERRUPT EXISTING ELECTRICAL SERVICE TO FACILITIES WITHOUT WRITTEN PERMISSION BY OWNER. COORDINATE WORK WITH EXISTING
ELECTRICAL SERVICES WITH OWNER AND UTILITY COMPANY.
5. ARRANGE TO PROVIDE TEMPORARY ELECTRICAL SERVICE AS REQUIRED FOR SCOPE OF WORK.
6. PROVIDE NEW ELECTRICAL SERVICES FROM UTILITY COMPANY AS DIRECTED. COORDINATE SCOPE OF WORK AND PROVIDE ALL WORK TO PROVIDE A
FULLY FUNCTIONAL ELECTRICAL SERVICE.
7. PROVIDE SHOP DRAWINGS FOR THE FOLLOWING:
A. CONDUIT
B. CONDUCTORS
C. WIRING DEVICES, INCLUDING COVER PLATES
D. DISCONNECT SWITCHES, ENCLOSED CIRCUIT BREAKERS AND FUSED SWITCHES
E. PANELBOARDS AND SWITCHBOARDS
F. SURGE PROTECTION DEVICES
G. INTERIOR AND EXTERIOR LIGHTING FIXTURES, INCLUDING SITE POLES
H. LIGHTING CONTROL SYSTEM AND DEVICES
I. FIRE ALARM SYSTEM
PART 2 - EXECUTION
1. PROVIDE SCHEDULE FOR ELECTRICAL INSTALLATION WORK TO OWNER AND ARCHITECT FOR MAJOR MILESTONE DATES.
2. COORDINATION DRAWINGS; PROVIDE COORDINATION DRAWINGS FOR FOLLOWING INSTALLATIONS:
A. LARGE INDOOR EQUIPMENT INSTALLATIONS.
B. LARGE OUTDOOR EQUIPMENT INSTALLATIONS.
3. DEMOLITION WORK
A. REMOVE ALL ELECTRICAL EQUIPMENT, WIRE, CONDUIT, ETC., ASSOCIATED WITH DEMOLISHED EQUIPMENT.
B. REMOVE ALL ABANDONED ELECTRICAL CONDUIT AND WIRE BACK TO SOURCE.
C. PATCH, REPAIR AND PAINT ANY OPENINGS THROUGH ROOF, CEILINGS, WALLS OR FLOORS TO MATCH EXISTING CONDITION. MAINTAIN ALL FIRE
RATINGS OF WALLS AND DOORS.
D. OWNER SHALL HAVE FIRST RIGHT OF REFUSAL OF ALL DEMOLISHED EQUIPMENT.
4. CLOSEOUT ACTIVITIES
A. PROVIDE NORMAL OPERATION, EMERGENCY OPERATION AND PREVENTIVE MAINTENANCE MANUALS FOR EACH SYSTEM, EQUIPMENT AND DEVICE.
B. PROVIDE SOFTWARE AND FIRMWARE OPERATION DOCUMENTATION FOR SYSTEM INSTALLED.
C. PROVIDE BACKUP, UPGRADES AND UNRESTRICTED LICENSES FOR INSTALLED SOFTWARE, INCLUDING OPERATING SYSTEMS AND PROGRAMMING
TOOLS REQUIRED FOR MAINTENANCE AND OPERATION.
SECTION 26 0010
SUPPLEMENTAL REQUIREMENTS FOR ELECTRICAL
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL CONDUCTORS AND CABLES INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. COPPER BUILDING WIRE
A. FLEXIBLE, INSULATED, DRAWN COPPER WITH AN INSULATION JACKET, RATED 600V OR LESS.
B. PROVIDE THHN-2 COPPER INDOORS AND THWN-2 COPPER OUTDOORS, UNLESS NOTED OTHERWISE OR DICTATED OTHERWISE BY THE NEC.
C. MINIMUM CONDUCTOR SIZE FOR POWER SHALL BE #12 AWG. ANY BRANCH CIRCUIT(S) OVER 100' IN LENGTH SHALL BE #10 AWG MINIMUM FOR
VOLTAGE DROP.
D. PROVIDE COLOR CODED WIRE WITH DIFFERENT COLOR FOR EACH PHASE, NEUTRAL AND GROUND, BASED ON ELECTRICAL SYSTEM TYPE.
2. CONNECTORS AND SPLICES
A. FACTORY-FABRICATED CONNECTORS, SPLICES, AND LUGS OF SIZE, AMPACITY RATING, MATERIAL, TYPE, AND CLASS FOR APPLICATION AND SERVICE
INDICATED.
B. SHALL BE MARKED FOR INTENDED LOCATION AND USE.
PART 3 - EXECUTION
1. INSTALLATION
A. CONCEAL CABLES IN FINISHED WALLS, CEILINGS AND FLOORS UNLESS OTHERWISE NOTED.
B. USE PULLING MEANS, INCLUDING FISH TAPE, CABLE, ROPE, AND BASKET-WEAVE WIRE/CABLE GRIPS, THAT WILL NOT DAMAGE CABLES OR RACEWAY.
USE MANUFACTURER APPROVED PULLING COMPOUND OR LUBRICANT WHEN NECESSARY.
C. INSTALL CONDUCTORS AT EACH OUTLET, WITH AT LEAST 12" OF SLACK.
D. ALL CABLING SHALL BE IN CONDUIT UNLESS ABOVE AN ACCESSIBLE CEILING WHERE "J" HOOKS ARE ACCEPTABLE.
2. CONNECTIONS
A. TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS ACCORDING TO MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES.
B. SPLICES, TERMINATIONS, AND TAPS SHALL BE COMPATIBLE WITH CONDUCTOR MATERIAL.
C. CONDUCTORS SHALL BE CONTINUOUS FROM ORIGIN TO PANEL OR EQUIPMENT TERMINATION WHERE POSSIBLE. SPLICES AND TAPS, WHERE
REQUIRED, SHALL BE MADE IN JUNCTION BOXES WITH SUITABLE CONNECTORS.
3. ACCEPTANCE
A. ALL CONDUCTORS AND CONNECTIONS SHALL TEST FREE OF GROUNDS, SHORTS, AND OPENS PRIOR TO ENERGIZING CIRCUIT.
SECTION 26 0519
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL CONDUIT AND RACEWAY PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. ALL PRODUCTS SHALL BE UL LISTED AND LABELED.
2. EMT - RIGID, STEEL, ZINC-COATED (INTERIOR AND EXTERIOR).
3. RMC - RIGID, STEEL, ZINC-COATED (INTERIOR AND EXTERIOR).
4. FMC - FLEXIBLE, STEEL. PROVIDE AT TERMINATION POINT FOR EQUIPMENT SUBJECT TO MOTION AND VIBRATION.
5. MC CABLE - COLOR-CODED COPPER CONDUCTORS WITH INTERLOCKING GALVANIZED STEEL SHEATHING.
6. PVC - SCHEDULE 40, SCHEDULE 80, FOR USE WITH MAXIMUM 90 DEG C WIRE.
7. FITTINGS
A. SHALL BE LISTED FOR USE WITH RACEWAY SYSTEM TO BE INSTALLED.
PART 3 - EXECUTION
1. CONDUIT TYPE SHALL BE SUITABLE FOR THE ENVIRONMENT IN WHICH IT IS LOCATED:
A. INDOORS - EMT, AND/OR RMC, WITH SET-SCREW FITTINGS. MC CABLE IS ACCEPTABLE FOR BRANCH CIRCUITS WHERE CONCEALED.
B. OUTDOORS - RIGID GALVANIZED STEEL.
C. UNDERGROUND - RIGID, NON-METALLIC SCHEDULE 80 PVC.
a. CONDUIT EXITING FROM UNDERGROUND SHALL TRANSITION TO EMT/RGS PRIOR TO BEING EXPOSED ABOVE GROUND.
2. MINIMUM CONDUIT SIZE SHALL BE 1/2" TRADE SIZE.
3. PROVIDE CONDUIT SLEEVES FOR LOW VOLTAGE DATA CABLING.
4. USE LARGE RADIUS ELLS FOR ALL CONDUIT BENDS.
5. CONDUITS SHALL BE CONCEALED WITHIN FINISHED WALLS, CEILINGS AND FLOORS UNLESS OTHERWISE INDICATED. CONDUITS SHALL BE
SUPPORTED WITHIN 12" OF ENCLOSURES TO WHICH ATTACHED.
6. INSTALL RACEWAY SEALS AND FITTINGS AT ACCESSIBLE LOCATIONS.
7. DO NOT INSTALL CONDUITS WITHIN 2" OF THE BOTTOM SIDE OF METAL DECK ROOF.
8. KEEP CONDUITS AT LEAST 6" AWAY FROM PARALLEL RUNS OF FLUES AND STEAM OR HOT-WATER PIPES.
9. INSTALL PULL WIRES IN EMPTY RACEWAYS FOR FUTURE USE. PROVIDE POLYPROPYLENE OR MONOFILAMENT PLASTIC LINE WITH NOT LESS THAN
200lb TENSILE STRENGTH. LEAVE AT LEAST 12" OF SLACK AT BOTH ENDS OF CONDUIT.
10. CAP AND SEAL UNDERGROUND RACEWAYS DESIGNATED AS SPARE ABOVE GRADE ALONGSIDE DUCT RACEWAYS IN USE.
11. PROVIDE SEPARATE RACEWAY SYSTEM FOR EMERGENCY CIRCUIT(S). EMERGENCY CIRCUITS SHALL NOT BE IN CONDUIT WITH OTHER NON-
EMERGENCY CIRCUITS.
SECTION 26 0533.13
CONDUITS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL GROUNDING AND BONDING PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. GROUNDING AND BONDING CONDUCTORS
A. PROVIDE THHN/THWN-2, TINNED-COPPER WIRE OR CABLE, GREEN COLOR. CABLE SHALL BE RATED 600V.
2. GROUNDING AND BONDING CLAMPS
A. CLAMPS SUITABLE FOR ATTACHMENT OF GROUNDING AND BONDING CONDUCTORS TO ELECTRODES, PIPES, TUBING, AND REBAR. SUITABLE TYPES
SHALL BE:
a. STRAP-TYPE PIPE AND ROD CLAMPS
b. BEAM GROUNDING CLAMPS
c. EXOTHERMICALLY WELDED CONNECTIONS
3. GROUNDING (EARTHING) ELECTRODES
A. COPPER CLAD STEEL
B. 3/4" DIAMETER BY 10' LENGTH
PART 3 - EXECUTION
1. PROVIDE GROUNDING ELECTRODE SYSTEM AND EQUIPMENT GROUNDING PER THE NATIONAL ELECTRIC CODE.
2. GROUNDING AND BONDING CONDUCTORS
A. PROVIDE SOLID CONDUCTOR FOR 8 AWG AND SMALLER, AND STRANDED CONDUCTORS FOR 6 AWG AND LARGER, UNLESS OTHERWISE NOTED.
B. ROUTE CONDUCTORS ALONG SHORTEST AND STRAIGHTEST PATHS POSSIBLE. AVOID OBSTRUCTING ACCESS TO OR PLACING CONDUCTORS WHERE
THEY MAY BE SUBJECTED TO STRAIN, IMPACT, OR DAMAGE.
C. PROVIDE GROUNDING AND BONDING BUSBARS IN ELECTRICAL EQUIPMENT ROOMS, ROOMS HOUSING SERVICE EQUIPMENT, AND ELSEWHERE
INDICATED ON DRAWINGS.
3. CONNECTIONS
A. MAKE CONNECTIONS SO POSSIBILITY OF GALVANIC ACTION OR ELECTROLYSIS IS MINIMIZED.
B. USE EXOTHERMIC WELDS FOR ALL BELOW GRADE CONNECTIONS.
4. GROUNDING ELECTRODES
A. DRIVE GROUND RODS UNTIL TOPS ARE 2" BELOW FINISHED FLOOR OR GRADE.
B. INSTALL AT LEAST (3) RODS SPACED AT LEAST ONE-ROD LENGTH FROM EACH OTHER AND CONNECT TO SERVICE GROUNDING ELECTRODE
CONDUCTOR.
C. FOR CONCRETE-ENCASED ELECTRODE (UFER GROUND), USE MINIMUM 20' OF BARE COPPER CONDUCTOR NOT SMALLER THAN 4 AWG.
a. IF FOUNDATION IS LESS THAN 20' LONG, COIL EXCESS CONDUCTOR WITHIN BASE OF FOUNDATION.
b. BOND GROUNDING CONDUCTOR TO REINFORCING STEEL IN AT LEAST (4) LOCATIONS AND TO ANCHOR BOLTS. EXTEND GROUNDING CONDUCTOR
BELOW GRADE AND CONNECT TO GROUNDING GRID OR GROUNDING ELECTRODE EXTERNAL TO CONCRETE.
5. EQUIPMENT GROUNDING AND BONDING
A. INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTORS WITH THE FOLLOWING ITEMS:
a. FEEDERS AND BRANCH CIRCUITS
b. LIGHTING CIRCUITS
c. RECEPTACLE CIRCUITS
d. SINGLE, AND THREE-PHASE MOTOR AND APPLIANCE BRANCH CIRCUITS
e. FLEXIBLE RACEWAY, ARMORED, AND METAL-CLAD CABLE RUNS
B. ALL CORRUGATED STAINLESS STEEL TUBING FOR GAS PIPING SYSTEM IN KITCHENS SHALL BE BONDING TO THE GROUNDING ELECTRODE SYSTEM.
BONDING JUMPER SHALL NOT BE SMALLER THAN 6 AWG.
SECTION 26 0526
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL SUPPORT, ANCHORAGE, AND ATTACHMENT PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
A. STEEL HANGERS, CLAMPS, AND ASSOCIATED FITTINGS SHALL BE DESIGNED FOR TYPES AND SIZES OF RACEWAY OR CABLE TO BE SUPPORTED.
B. MOUNTING, ANCHORING, AND ATTACHMENT COMPONENTS FOR FASTENING ELECTRICAL ITEMS OR SUPPORTS TO BUILDING SURFACES:
a. POWDER-ACTUATED FASTENERS
b. MECHANICAL-EXPANSION ANCHORS
c. CONCRETE INSERTS
d. CLAMPS FOR ATTACHMENT TO STEEL STRUCTURAL ELEMENTS
e. THROUGH BOLTS AND TOGGLE BOLTS
f. HANGER RODS
PART 3 - EXECUTION
A. SUPPORT INSTALLATION
a. PROVIDE SIZES OF COMPONENTS SO STRENGTH WILL BE ADEQUATE TO CARRY PRESENT AND FUTURE STATIC LOADS WITHIN SPECIFIED LIMITS.
b. CUT, FIT, AND PLACE MISCELLANEOUS METAL SUPPORTS ACCURATELY IN LOCATION, ALIGNMENT, AND ELEVATION TO SUPPORT AND ANCHOR
ELECTRICAL MATERIALS AND EQUIPMENT.
B. CONCRETE BASES
a. ALL FLOOR MOUNT ELECTRICAL EQUIPMENT SHALL BE ON 4" HOUSEKEEPING PADS. PADS SHALL BE NOT LESS THAN 4" LARGER IN BOTH
DIRECTIONS OF ELECTRICAL EQUIPMENT TO BE SUPPORTED.
C. TOUCHUP
a. CLEAN WELDS AND ABRADED AREAS OF SHOP PAINT. PAINT EXPOSED AREAS IMMEDIATELY AFTER ERECTING HANGERS AND SUPPORTS.
SECTION 26 0529
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL SURGE PROTECTIVE DEVICE PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. MANUFACTURER
A. RAYCAP
a. TYPE 1, SERVICE ENTRANCE - RAYVOSS
b. TYPE 2, BRANCH PANEL - RSE2
2. GENERAL CHARACTERISTICS
A. MCOV: NOT LESS THAN 125% OF NOMINAL SYSTEM VOLTAGE FOR 208Y/120V AND 120/240V SYSTEMS. NOT LESS THAN 115% OF NOMINAL
SYSTEM VOLTAGE FOR 480Y/277V SYSTEMS.
B. PEAK SURGE CURRENT RATING: MINIMUM SINGLE-PULSE SURGE CURRENT WITHSTAND RATING PER PHASE SHALL BE NOT LESS THAN -
a. TYPE 1: 160, OR 240 kA.
b. TYPE 2: 50, 100, 150, OR 200 kA.
C. PROTECTION MODES: DEVICE SHALL HAVE PROTECTION MODES FOR LINE-TO-NEUTRAL, AND LINE-TO-LINE, FOR TYPE 1 DEVICES, AND LINE-TO-
NEUTRAL, LINE-TO-GROUND, NEUTRAL-TO-GROUND, AND LINE-TO-LINE, FOR TYPE 2 DEVICES.
3. OPTIONS
A. INTERNAL THERMAL PROTECTION TO DISCONNECT SPD BEFORE DAMAGING INTERNAL SUPPRESSOR COMPONENTS.
B. INDICATOR LIGHT DISPLAY FOR PROTECTION STATUS.
C. AUDIBLE ALARM.
D. NEMA ICS 5, DRY FORM-C CONTACTS RATED AT 1 A AND 120 VAC FOR REMOTE MONITORING OF PROTECTION STATUS.
E. TYPE 2 DEVICES: TOV AND SURGE COUNTER WITH TIME AND DATE STAMP.
PART 3 - EXECUTION
1. INSTALLATION
A. PROVIDE OCPD AND DISCONNECT FOR INSTALLATION OF SPD IN ACCORDANCE WITH UL 1449 AND MANUFACTURER INSTRUCTIONS.
B. INSTALL LEADS BETWEEN DISCONNECT(S) AND SPD(S) IN ACCORDANCE WITH MANUFACTURER INSTRUCTIONS.
a. DO NOT SPLICE AND EXTEND SPD LEADS UNLESS PERMITTED BY MANUFACTURER.
b. DO NOT EXCEED MANUFACTURER RECOMMENDED LEAD LENGTH.
c. DO NOT BOND NEUTRAL AND GROUND.
d. USE CRIMPED CONNECTORS AND SPLICES ONLY. WIRE NUTS ARE NOT ACCEPTABLE.
C. SURGE PROTECTION DEVICES SHALL BE MOUNTED AS CLOSE TO MAIN BUS AS POSSIBLE TO LIMIT FEEDER LENGTH.
SECTION 26 4313
SURGE PROTECTIVE DEVICES FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL BOX AND COVER PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. METALLIC OUTLET BOXES
A. LISTED AND LABELED FOR INTENDED LOCATION AND USE.
B. MATERIAL SHALL BE SHEET METAL GALVANIZED STEEL, WITH A MINIMUM DEPTH OF 2.5".
C. BOXES SHALL HAVE PRYOUT OPENINGS, KNOCKOUTS, THREADED ENTRIES, OR HUBS IN EITHER SIDES OR BACK FOR CONDUITS OR CONDUIT
FITTINGS. SHALL HAVE PROVISIONS FOR MOUNTING OUTLET BOX COVER.
D. EXTENSION RINGS SHALL BE PROVIDED WHERE REQUIRED OR INDICATED ON DRAWINGS, TO EXTEND DEVICE BOX TO INCREASE DEPTH.
EXTENSION RINGS SHALL BE SUITABLE FOR USE WITH ASSOCIATED DEVICE BOX.
2. NONMETALLIC OUTLET BOXES
A. LISTED AND LABELED FOR INTENDED LOCATION AND USE.
3. COVER PLATES
A. LISTED AND LABELED FOR INTENDED LOCATION AND USE WITH ASSOCIATED OUTLET BOX TYPE.
B. FOR USE IN FINISHED LOCATIONS: .032" THICK, TYPE 302/304 NON-MAGNETIC STAINLESS STEEL.
a. ALL DEVICE COVERS SHALL BE BRUSHED STAINLESS STEEL, UNLESS SPECIFIC DEVICE COLOR IS SPECIFIED.
C. PROVIDE GASKETS FOR WALLPLATES IN DAMP OR WET LOCATIONS.
D. WEATHERPROOF COVERS
a. SHALL BE METAL, "WHILE-IN-USE" TYPE. COVER SHALL BE GRAY COLOR.
PART 3 - EXECUTION
1. ALL BOXES SHALL BE RECESSED IN WALLS AND CONDUIT CONCEALED WHERE POSSIBLE.
A. CUT, PATCH, REPAIR AND PAINT GYPSUM AND/OR MASONRY WALLS TO RECESS NEW BOXES WHERE INDICATED.
B. HORIZONTALLY SEPARATE BOXES MOUNTED ON OPPOSITE SIDES OF WALLS SO THEY ARE NOT IN THE SAME VERTICAL CHANNEL.
2. PROVIDE NEMA 1 BOXES AND COVERS FOR INDOOR LOCATIONS, UNLESS OTHERWISE NOTED.
3. PROVIDE NEMA 3R BOXES AND COVERS FOR OUTDOOR LOCATIONS, UNLESS OTHERWISE NOTED.
4. SUPPORT
A. SUPPORT BOXES IN RECESSED CEILINGS INDEPENDENT OF CEILING TILES OR GRID.
B. SUPPORT JUNCTION OR PULL BOXES FROM BUILDING STRUCTURE. DO NOT SUPPORT BOXES BY CONDUIT(S).
5. ALL BOXES USED FOR LOW VOLTAGE DATA CABLING SHALL BE DOUBLE GANG, 3-1/2" DEEP WITH SINGLE GANG MUD RING. PROVIDE 1" CONDUIT TO
ABOVE ACCESSIBLE CEILING FOR DATA CABLING.
SECTION 26 0533.16
BOXES AND COVERS ELECTRICAL SYSTEMS
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL LABEL AND IDENTIFICATION PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. LABELS
A. LISTED AND LABELED FOR INTENDED LOCATION AND APPLICATION.
B. VINYL WRAPAROUND LABELS - PREPRINTED, FLEXIBLE LABELS LAMINATED WITH CLEAR, WEATHER AND CHEMICAL-RESISTANT COATING.
C. SELF-ADHESIVE WRAPAROUND LABELS - PREPRINTED, VINYL FLEXIBLE LABEL WITH ACRYLIC PRESSURE-SENSITIVE ADHESIVE.
D. SELF-ADHESIVE LABELS - POLYESTER VINYL, THERMAL, TRANSFER PRINTED, MULTI-COLOR, WEATHER AND UV-RESISTANT, PRESSURE-
SENSITIVE ADHESIVE.
E. SIZE
a. 1-1/2" BY 6" FOR RACEWAYS AND CONDUCTORS.
b. 3-1/2" BY 5" FOR EQUIPMENT.
2. SIGNS
A. LAMINATED ACRYLIC OR MELAMINE PLASTIC.
a. 1/16" THICK FOR SIGNS UP TO 20 SQ. IN.
b. 1/8" THICK FOR SIGNS GREATER THAN 20 SQ. IN.
c. ENGRAVED LEGEND WITH BLACK LETTERS ON WHITE FACE.
d. PUNCHED OR DRILLED FOR MECHANICAL FASTENERS WITH 1/4" GROMMETS IN CORNERS FOR MOUNTING.
3. UNDERGROUND-LINE WARNING TAPE
A. SUITABLE TO IDENTIFY AND LOCATE UNDERGROUND ELECTRICAL AND COMMUNICATIONS UTILITY LINES.
B. PRINTING ON TAPE MUST BE PERMANENT AND NOT DAMAGED BY BURIAL OPERATIONS.
C. INSCRIPTIONS SHALL READ "CAUTION BURIED ELECTRIC LINE BELOW" OR "CAUTION BURIED COMMUNICATION LINE BELOW".
D. DETECTABLE WARNING TAPE
a. REINFORCED, DETECTABLE THREE-LAYER LAMINATE, CONSISTING OF ALUMINUM-FOIL CORE AND CLEAR PROTECTIVE FILM.
PART 3 - EXECUTION
1. PROVIDE BAKED ENAMEL SIGNS FOR:
A. PANELBOARDS AND SWITCHBOARDS
B. TRANSFORMERS
C. DISCONNECT SWITCHES
D. VARIABLE FREQUENCY DRIVES
E. LIGHTING CONTROL PANELS. LABELS SHALL INDICATED ROOMS CONTROLLED
2. IDENTIFY CONDUCTORS, CABLES, AND TERMINALS IN ENCLOSURES AND AT JUNCTIONS, TERMINALS, PULL POINTS, AND LOCATIONS OF HIGH
VISIBILITY. IDENTIFY BY SYSTEM AND CIRCUIT DESIGNATION.
3. PROVIDE UNDERGROUND-LINE WARNING TAPE FOR POWER, LIGHTING, AND COMMUNICATIONS CABLING.
4. LABEL INDIVIDUAL COVER PLATES WITH SELF-ADHESIVE LABELS. LABEL TO INDICATE CIRCUIT WHICH DEVICE IS FED FROM WITH THE FOLLOWING
INFORMATION:
A. PANELBOARD DESIGNATION - BRANCH CIRCUIT NUMBER.
5. INSTALL IDENTIFICATION MATERIALS AT LOCATIONS FOR MOST CONVENIENT VIEWING WITHOUT INTERFERENCE WITH OPERATION AND
MAINTENANCE OF EQUIPMENT.
6. PROVIDE FLOOR MARKING TAPE TO INDICATE WORKING CLEARANCE OF ELECTRICAL EQUIPMENT. FLOOR MARKING TAPE SHALL NOT BE USED FOR
SURFACE OR FLUSH-MOUNTED PANELBOARDS AND SIMILAR EQUIPMENT IN FINISHED SPACES.
SECTION 26 0553
IDENTIFICATION FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL PANELBOARD PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. MANUFACTURER
A. SQUARE D - NQOD FOR 208/120V BRANCH PANELBOARDS, NF FOR 480/277V BRANCH PANELBOARDS.
B. OR EQUAL BY:
a. EATON CORP.
b. SIEMENS
2. ELECTRICAL COMPONENTS, DEVICES, AND EQUIPMENT SHALL BE UL LABELED.
3. ENCLOSURES
A. RATED FOR ENVIRONMENTAL CONDITIONS AT INSTALLED LOCATION
a. INDOOR, DRY AND CLEAN LOCATIONS - NEMA 1
b. OUTDOOR LOCATIONS - NEMA 3R
c. KITCHEN LOCATIONS - NEMA 4X, STAINLESS STEEL
d. OTHER WET AND DAMP INDOOR LOCATIONS - NEMA 4
B. FRONT - SECURE TO BOX WITH CONCEALED TRIM CLAMPS. FOR SURFACE-MOUNTED FRONTS, MATCH DIMENSIONS; FOR FLUSH-MOUNTED
FRONTS, OVERLAP BOX. TRIMS MUST COVER LIVE PARTS AND MAY HAVE NO EXPOSED HARDWARE.
4. BUSES
A. TIN-PLATED ALUMINUM FOR 400A OR LESS.
B. HARD DRAWN COPPER FOR ABOVE 400A.
5. CONDUCTOR CONNECTORS
A. TIN-PLATED ALUMINUM OR HARD DRAWN COPPER, 98% CONDUCTIVITY.
B. MAIN AND NEUTRAL LUGS - MECHANICAL TYPE, WITH LUG ON NEUTRAL BAR FOR EACH POLE IN PANELBOARD.
C. GROUND LUGS AND BUS-CONFIGURED TERMINATORS - MECHANICAL TYPE, WITH LUG ON BAR FOR EACH POLE IN PANELBOARD.
D. SUBFEED LUGS - MECHANICAL TYPE, SUITABLE FOR USE WITH CONDUCTOR MATERIAL. LOCATE AT SAME END OF BUS AS INCOMING LUGS OR
MAIN DEVICE.
6. SHORT-CIRCUIT CURRENT RATING
A. FULLY RATED TO INTERRUPT SYMMETRICAL SHORT-CIRCUIT CURRENT AVAILABLE AT TERMINALS. SERIES RATED PANELS ARE NOT
ACCEPTABLE.
7. OVERCURRENT PROTECTIVE DEVICES
A. THERMAL-MAGNETIC CIRCUIT BREAKERS
a. INVERSE TIME CURRENT ELEMENT FOR LOW-LEVEL OVERLOADS.
b. INSTANTANEOUS MAGNETIC TRIP ELEMENT FOR SHORT CIRCUITS.
c. ADJUSTABLE MAGNETIC TRIP SETTING FOR CIRCUIT-BREAKER FRAME SIZES 250A AND LARGER.
B. ELECTRONIC TRIP CIRCUIT BREAKERS
a. RMS SENSING.
b. FIELD-REPLACEABLE RATING PLUG OR ELECTRONIC TRIP.
c. FIELD ADJUSTABLE SETTINGS FOR: INSTANTANEOUS TRIP, LONG AND SHORT TIME PICKUP LEVELS, LONG AND SHORT TIME ADJUSTMENTS, AND GROUND FAULT PICKUP LEVEL, TIME DELAY AND I
T RESPONSE.
C. SUBFEED CIRCUIT BREAKERS SHALL BE VERTICALLY ARRANGED ON PHASE BUSBARS.
PART 3 - EXECUTION
1. INSTALLATION
A. MOUNT TOP OF PANELBOARD TRIP 7.5' ABOVE FINISHED FLOOR UNLESS OTHERWISE INDICATED.
B. MOUNT PANELBOARD CABINET PLUMB AND RIGID WITHOUT DISTORTION OF BOX.
C. MOUNT RECESSED PANELBOARDS WITH FRONT UNIFORMLY FLUSH WITH WALL FINISH.
a. FOR RECESSED PANELBOARDS, STUB (4) 1" EMPTY CONDUITS FROM PANELBOARD INTO ACCESSIBLE CEILING SPACE OR SPACE DESIGNATED
TO BE CEILING SPACE IN FUTURE.
D. MAKE GROUNDING CONNECTIONS AND BOND NEUTRAL FOR SERVICES AND SEPARATELY DERIVED SYSTEMS TO GROUND. MAKE CONNECTIONS
TO GROUNDING ELECTRODES, SEPARATE GROUNDS FOR ISOLATED GROUND BARS, AND CONNECTIONS TO SEPARATE GROUND BARS.
2. IDENTIFICATION
A. PANELBOARD LABEL MUST LIST MANUFACTURER NAME, TRADEMARK, VOLTAGE, AMPERAGE, NUMBER OF PHASES, AND NUMBER OF POLES AND
MUST BE LOCATED ON INTERIOR OF PANELBOARD DOOR.
B. CIRCUIT BREAKER LABELS MUST LIST CURRENT RATING, UL AND IEC CERTIFICATION STANDARDS, AND AIC RATING.
C. CIRCUIT DIRECTORY
a. PROVIDE CIRCUIT DIRECTORY CARD INSIDE PANELBOARD DOOR, MOUNTED IN TRANSPARENT CARD HOLDER.
b. PANELBOARD DIRECTORY SHALL BE TYPE-WRITTEN, AND PROVIDE DETAILED INFORMATION SHOWN ON ASSOCIATED PANELBOARD LOAD
SCHEDULE.
c. UPDATE ALL EXISTING CIRCUIT DIRECTORY CARDS AS REQUIRED.
SECTION 26 2416
PANELBOARDS
PART 1 - GENERAL
1. PROVIDE SHOP DRAWING SUBMITTALS FOR ALL WIRING DEVICE PRODUCTS INSTALLED DURING COURSE OF WORK.
PART 2 - PRODUCTS
1. GENERAL USE SWITCHES
A. MANUFACTURER
a. ARROW HART, WIRING DEVICES
b. HUBBELL WIRING DEVICE-KELLEMS, HUBBELL, INC.
c. LEVITON MANUFACTURING CO., INC.
d. PASS & SEYMOUR, LEGRAND NORTH AMERICA, LLC
B. GENERAL CHARACTERISTICS
a. HEAVY DUTY GRADE, QUIET TYPE, 120/277 VAC, RATED 20A MINIMUM.
b. COLOR - WHITE, UNLESS OTHERWISE INDICATED.
c. PROVIDE BRUSHED STAINLESS STEEL COVER DESIGNED FOR USE WITH DEVICE, UNLESS OTHERWISE INDICATED.
2. STRAIGHT-BLADE RECEPTACLES
A. MANUFACTURER
a. HUBBELL WIRING DEVICE-KELLEMS, HUBBELL, INC.
B. GENERAL CHARACTERISTICS
a. EXTRA HEAVY DUTY GRADE, TAMPER-RESISTANT, RATED 20A MINIMUM.
b. COLOR - WHITE, UNLESS OTHERWISE INDICATED.
c. PROVIDE BRUSHED STAINLESS STEEL COVER DESIGNED FOR USE WITH DEVICE, UNLESS OTHERWISE INDICATED.
PART 3 - EXECUTION
1. INSTALLATION
A. UNLESS OTHERWISE INDICATED, INSTALL SWITCHES, RECEPTACLES, AND OTHER WIRING DEVICES, AT MOUNTING HEIGHTS RECOMMENDED IN
NECA NEIS 1.
B. ORIENT RECEPTACLES TO MATCH CONFIGURATION DIAGRAM IN NEMA WD 6.
a. RECEPTACLES ORIENTED HORIZONTALLY SHALL BE MOUNTED WITH NEUTRAL BLADE FACING UP.
2. IDENTIFICATION
A. MARK INSIDE OF COVER OR COVER PLATE OF WIRING DEVICE(S) WITH PANELBOARD AND CIRCUIT NUMBER FEEDING WIRING DEVICE(S).
SECTION 26 2726
WIRING DEVICES
THE FOLLOWING DIMENSION EQUALS
ONE INCH WHEN PRINTED TO SCALE.
1"
Project No:
Drawing Title:
© 2026 IGNYTE DESIGN
SCALE
STAMP
Issued For: Date
E001
ELECTRICAL
SPECIFICATIONS
KITCHEN
GENERATOR
26.068
JUNE 11, 2026CONSTRUCTION
U
IT
'E
U
N
IT
'F ' U
N
IT
'K
UNIT 'J'
UNIT 'E'
UNIT 'K'
UNIT 'J'
UNIT 'K'
MENS
FREEZERCOOLER CART WASH
TRASH
DRY STORAGE
OFFICE
KITCHEN
PREP.
902 903 904 905
IDF / JANITOR
SERVING 'A'
SERVING 'B'
STOR.
TOILET
JANITOR
LOCKER
A LA CARTE
STORAGE
KILN
STORAGE
902 903 904 906
909 914
915A
915B
EQ EQ
EQ
EQ
W P
J J
J
1 K2
K1
EMK
ATS-EMK
GENERATOR
GENERATOR
EMERGENCY SHUT OFF
COOLER FREEZER
EMK-1,3 EMK-2,4
EMK-6,8,10
EMK-5,7,9
GENERATOR REMOTE
ANNUCIATOR
PROVIDE NEW CONCRETE
PAD, CUT AND PATCH
EXISTING CONCRETE AS
REQUIRED.
MDP1
RUN CONDUIT ABOVE EXISTING CEILING. PAINT
CONDUIT TO MATCH CEILING IN EXPOSED AREAS.
CONTRACTOR TO PROVIDE BEST POSSIBLE ROUTE.
EXPOSED CONDUIT
SHALL BE RIGID
GALVANIZED.
2 2
K2-1
COOLER ACCU
FREEZER ACCU
EMK-11
EMK-11
EMK-12
COOLER LTS FREEZER LTS
FREEZER HEAT TAPE
2 2
CONCRETE EQUIPMENT PAD
SUB-BASE DAY TANK
CONNECT BLOCK HEATER, BATTERY CHARGER, BATTERY
HEATER ETC. TO EXISTING PANEL K2
GEN
CONTROL
GENERATOR
E-STOP
GENERATOR
ANNUNCIATOR
MANUFACTURER
RECOMMENDED CABLE
(2) #14's
ATS
EMK
SEE ONE LINE
DIAGRAM
(10) #14's
ATS
ANNUNCIATOR
SB
MANUFACTURER
RECOMMENDED CABLE
PROVIDE CABLING FOR THE FOLLOWING SIGNALS:
• GENERATOR START
• GENERATOR RUNNING
• GENERATOR STOP
• GENERATOR TROUBLE
• SPARE
SAND FILL
#4 CONT.
SIZE PAD IN ACCORDANCE
WITH UTILITY CO. STANDARDS
OR MANUFACURERS
RECOMMENDATION. PROVIDE
CONDUIT AS REQUIRED.
#4 REINF. BARS 12" O.C.
12"
2"
OUTDOOR GENERATOR PAD
MDP1
208/120V, 3PH, 4W, 800A
GENERATOR
G
40/50 kW/kVA
208/120V, 3PH, 4W
DIESEL
N E
ATS-EMK
STAND-BY
150A
208V, 3PH, 4W
PANEL
EMK
PANEL
GG
PANEL
H
PANEL
N
PANEL
M
PANEL
K1
PANEL
K2
PANEL
K3
PANEL
L
PANEL
P
PANEL
MSP1
SPD
AHU-3
PROVIDE NEW CIRCUIT BREAKER IN EXISTING SQUARE D
HCP STYLE PANEL. MATCH EXISTING AIC RATING.
4 #1/0, 1 #6 GND. 2" C. 4 #1/0, 1 #6 GND. 2" C.
4 #1/0, 1 #6 GND. 2" C.
NOTE:
THERE ARE NO NEW LOADS BEING ADDED TO THE SYSTEM. EXISTING LOADS
FROM PANEL K2 ARE BEING RE-CIRCUITED TO A NEW STAND-BY PANEL EMK.
MARK EXISTING BREAKERS AS SPARE
FOR EQUIPMENT BEING RE-CIRCUITED
THE FOLLOWING DIMENSION EQUALS
ONE INCH WHEN PRINTED TO SCALE.
1"
Project No:
Drawing Title:
© 2026 IGNYTE DESIGN
SCALE
STAMP
Issued For: Date
E110
FIRST FLOOR POWER
PLAN
KITCHEN
GENERATOR
26.068
JUNE 11, 2026CONSTRUCTION
8' 16'4'0 1/8" = 1'-0"E110
1 FIRST FLOOR POWER PLAN
ELECTRICAL POWER KEYED NOTES
1 RENAME EXISTING COOLER AND FREEZER CIRCUIT BREAKERS AS
SPARE. REMOVE WIRE FROM PANEL AND MAKE READY FOR
CONNECTION TO NEW PANEL.
2 REFEED EXISTING EQUIPMENT FROM NEW STANDBY PANEL. REUSED
CONDUIT AND WIRE WHERE POSSIBLE, EXTEND AS REQUIRED.
MATCH EXISTING WIRE AND CONDUIT SIZE.
NOT TO SCALEE110
2 BUILDING ELECTRICAL SYSTEM GROUND BUS
NOT TO SCALEE110
3 CONCRETE EQUIPMENT PAD DETAIL
NOT TO SCALEE110
4 PARTIAL ELECTRICAL ONE LINE DIAGRAM
Notes:
Demand Current: 58 A
Demand Load: 21 kVA
Connected Current: 58 A
POWER 900 VA 100.00... 900 VA Connected Load: 21 kVA
HVAC 19944 VA 100.00... 19944 VA
Load Classification Connected Factor Demand
Current: 62 A 62 A 53 A
Connecte... 7 kVA 7 kVA 6 kVA
41 SPARE 20 1 0 -- 1 -- SPACE 42
39 SPARE 20 1 0 -- 1 -- SPACE 40
37 SPARE 20 1 0 -- 1 -- SPACE 38
35 SPARE 20 1 0 -- 1 -- SPACE 36
33 SPARE 20 1 0 -- 1 -- SPACE 34
31 SPARE 20 1 0 -- 1 -- SPACE 32
29 SPARE 20 1 0 -- 1 -- SPACE 30
27 SPARE 20 1 0 -- 1 -- SPACE 28
25 SPARE 20 1 0 -- 1 -- SPACE 26
23 SPARE 20 1 0 -- 1 -- SPACE 24
21 SPARE 20 1 0 -- 1 -- SPACE 22
19 SPARE 20 1 0 -- 1 -- SPACE 20
17 SPARE 20 1 0 -- 1 -- SPACE 18
15 SPARE 20 1 0 -- 1 -- SPACE 16
13 SPARE 20 1 0 -- 1 -- SPACE 14
11 COOLER/FREEZER LIGHTS 20 1 400 500 1 20 FREEZER HEAT TAPE 12
9 1800 3600 10
7 1800 3600 8
COOLER ACCU 20 3
1800 3600
3 40 FREEZER ACCU
3 850 1022 4
COOLER FAN COIL 15 2
850 1022
2 15 FREEZER FAN COIL
Ckt Description Trip
(A) Poles
ARC
FAU...
GFC
I
Phase A Load (VA)
Phase B Load (VA)
Phase C Load (VA)
GFC
I
ARC
FAU... Poles Trip
(A) Description Ckt
FED FROM: ATS-EMK RATING: 150.0 A MOUNTING: SURFACE
LOCATION:
VOLTS: 208Y/120,3Ø,4W A.I.C. RATING: 22,000
Panelboard: EMK
| Sheets |
| E000 - ELECTRICAL SYMBOLS AND GENERAL NOTES |
| E001 - ELECTRICAL SPECIFICATIONS |
| E110 - FIRST FLOOR POWER PLAN |
| G000 - COVER SHEET |
| P110 - FIRST FLOOR PLUMBING PLAN |
File details come from the government source that posted it. Updated .