- PROVIDE INSTALL AND TEST OF (3) EA. REMOTE PENDANTS FOR TEMPORARY FIREFIGHTING BOOSTER PUMPS
- Solicitation number
- SPMYM325Q6010
About this file
This Statement of Work (SOW) details requirements for providing, installing, and testing Remote Pendants for three existing Temporary Firefighting Booster Pumps at Naval Base Point Loma in San Diego, CA.
The work involves retrofitting three Mitchell-Lewis Stavers design booster pumps with remote monitoring and operator pendants, including Danfoss MCB105 relay expansion cards, 200-foot SOOW cords, stainless steel pendants with magnetic mounts, push-to-test indicator lights, push buttons, alarm buzzers, and protective cages. The equipment must comply with NAVSEA S0570-AC-CCM-010/8010 (Rev 1) requirements for remote monitoring and control capabilities. The target start date is January 7, 2025, with electronic documentation required for all installed equipment. The work area is outside the Enclave security boundary and no government furnished materials are provided. This is part of solicitation SPMYM325Q6010, which is a 100% small business set-aside with BALCO LLC specified as the mandatory source provider.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 25Q6010 Attachment 2 OPSEC.pdf | ||
| 25Q6010 RFQ REQUIRED.docx | DOCX document | |
| Clauses - Full Text Provisions and Clauses 241128.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK
Ship: N/A
JSN: 38FMV99502 S05
PLANNER:
1. SCOPE:
1.1. Title: Provide, install, and test Remote Pendants for Temporary Firefighting Booster Pumps
1.1.1. NAVSEA S0570-AC-CCM-010/8010 (Rev 1) requires remote monitoring, indications, and control capability for installed Temporary Firefighting System booster pumps.
1.2. Location of Work:
1.2.1. Naval Base Point Loma, San Diego, CA.
1.3. Equipment Identification:
1.3.1. (Existing Assets) QTY 3 Temporary Firefighting Booster Pumps, Mitchell-Lewis Stavers design
1.3.2. (Required Retrofit Equipment) QTY 3 of each of the following:
Remote monitoring & operator pendant for retrofitting existing fire boosters, including:
- Danfoss MCB105 relay expansion card
- 200 ft. 12 conductor, 16 ga. SOOW cord
- 3/4" SS strain relief and 12 conductor plug connected to the VFD
- 12 conductor receptacle and SS strain relief connected to pendant
- 6" x 6" x 12" 304 SS pendant with magnetic mounting provisions
- Push-to-test indicator lights for: Ready, Running, High & Low Pressure, & General Alarm
- Push buttons for: Start, Stop & Push to Silence Alarm
- Audible Alarm Buzzer
- All lights & operators installed w/metal protective cages to prevent damage
- Relays & terminals as required
-Installation and performance testing of all installed equipment
1.4. Period of Performance:
1.4.1. TBD: equipment installation and performance testing shall be performed at the earliest opportunity;
target start date of 07JAN2025 based on contracting office and contractor specified lead times. Actual start date TBD.
JSN: 38FMV99502 S05
2. REFERENCES:
2.1. NAVSEA S0570-AC-CCM-010/8010 Industrial Ship Safety Manual for Fire Prevention and Response (Rev 1)
3. REQUIREMENTS:
3.1. Provide, install, and performance test the equipment identified in 1.3.2 to ensure compliance with Ref
2.1 requirements.
3.1.1. Provide electronic copies of schematics, diagrams, manuals, and operating procedures for provided equipment.