2571_B Drawings.pdf
PDF 22 MB Posted
- Attached to
- 2571-B: FCWS ¿ Trilith Tank Booster Pump Station
- Solicitation number
- PE-65600-NONST-2025-000000155
- Issued by
- Fayette County, Georgia
About this file
The provided document is a comprehensive set of engineering drawings for the FCWS-Trilith Tank Booster Pump Station project, prepared by ARCADIS for Fayette County Water System located in Fayetteville, Georgia. The project involves the construction of a new booster pump station with associated water infrastructure, including two 40 horsepower booster pumps, electrical systems, instrumentation, and site improvements. The drawings, issued for bid in April 2025, cover civil, structural, mechanical, electrical, and instrumentation aspects of the project, with detailed plans for the pre-fabricated pump station building, piping, grading, erosion control, and utility connections.
The project is funded by Fayette County Water System and will be located at the Trilith Studios campus, with a total disturbed area of approximately 0.63 acres. The drawings indicate a comprehensive approach to site development, including detailed specifications for electrical service from Coweta-Fayette EMC, a 480V power system, control infrastructure, and remote telemetry capabilities. The design incorporates provisions for future expansion, with spare capacity in electrical panels and considerations for potential equipment modifications. The project appears to be part of a broader water infrastructure improvement initiative, with careful attention to environmental controls, grounding systems, and compliance with local and state regulations.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2571_B ITB.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LEGAL ENTITY:
CONSULTANTS
SEALS
SHEET TITLE
ARCADIS U.S., INC.COPYRIGHT:
DATE:
PROJECT NO.:
FILE NAME:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SCALE:
SHEET OF
NO. DATE ISSUED FOR BY
E
2 3 4 5 6
D
C
B
A
ARCADIS U.S., INC.
2839 PACES FERRY ROAD
SUITE 900 ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
400 VETERANS PARKWAY,
FAYETTEVILLE, GA 30214,
UNITED STATES
PROJECT STATUS:
REVISIONS
NTS
/1
/2
:0 :5
P
M A u to d e s k D o c s /A
U S
-3 -T ri lit h S tu d io s E le va te d S to ra g e T a n k/
M -3
D -B
P S
R
.r v t
E. VAN DEVENTER
B. TARIT
T. THOMAS
APRIL 2025
30135792
G-01
G-01
FAYETTE COUNTY WATER
SYSTEM
FCWS-TRILITH TANK
BOOSTER PUMP
STATION
GENERAL
COVER SHEET AND SITE
LOCATION
FAYETTE COUNTY, GEORGIA
BID
2839 PACES FERRY ROAD, SUITE 400, ATLANTA,
GA 30339-3769 TEL: 770-431-8666 FAX: 770-435-2666
www.ARCADIS.com
LEGAL ENTITY: ARCADIS-U.S., INC.
ENGINEER OF RECORD
OWNER:
FCWS - TRILITH TANK
BOOSTER PUMP STATION
ARCADIS ASSUMES NO RESPONSIBILITY FOR EXISTING UTILITY
LOCATIONS (HORIZONTAL AND VERTICAL). THE EXISTING
UTILITIES SHOWN ON THESE DRAWINGS HAVE BEEN PLOTTED
FROM THE BEST AVAILABLE INFORMATION. IT IS, HOWEVER,
THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VERIFY
THE LOCATION OF ALL UTILITIES PRIOR TO THE
COMMENCEMENT OF ANY CONSTRUCTION ACTIVITIES.
LOCATION MAP
NOT TO SCALE
PROJECT LOCATION
ISSUED FOR BID
APRIL 2025
VICINITY MAP
NOT TO SCALE
PROJECT LOCATION
0 4/18/2025 ISSUED FOR BID TT
4/18/2025
LEGAL ENTITY:
CONSULTANTS
SEALS
SHEET TITLE
ARCADIS U.S., INC.COPYRIGHT:
DATE:
PROJECT NO.:
FILE NAME:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SCALE:
SHEET OF
NO. DATE ISSUED FOR BY
E
2 3 4 5 6
D
C
B
A
ARCADIS U.S., INC.
2839 PACES FERRY ROAD
SUITE 900 ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
400 VETERANS PARKWAY,
FAYETTEVILLE, GA 30214,
UNITED STATES
PROJECT STATUS:
REVISIONS
NTS
/1
/2
:0 :5
P
M A u to d e s k D o c s /A
U S
-3 -T ri lit h S tu d io s E le va te d S to ra g e T a n k/
M -3
D -B
P S
R
.r v t
E. VAN DEVENTER
B. TARIT
T. THOMAS
APRIL 2025
30135792
G-02
G-02
FAYETTE COUNTY WATER
SYSTEM
FCWS-TRILITH TANK
BOOSTER PUMP
STATION
GENERAL
DRAWING INDEX
FAYETTE COUNTY, GEORGIA
BID
DRAWING INDEX
DRAWING
NUMBER
DRAWING NAME
GENERAL
G - 01
G - 02
COVER SHEET AND SITE LOCATION
DRAWING INDEX
CIVIL
C - 02 EXISTING CONDITIONS PLAN
C - 03 BOOSTER PUMP STATION SITE AND YARD PIPING PLAN
C - 04
DRAWING INDEX
DRAWING
NUMBER
DRAWING NAME
C - 01 CIVIL NOTES, SYMBOLS AND ABBREVIATIONS
C - 05
C - 06 CIVIL DETAILS
ESC-01 EROSION & SEDIMENT CONTROL LEGEND & NOTES
ESC-02
ESC-03
ESC-04
ESC-05
ELECTRICAL
I&C
I - 01 INSTRUMENTATION SYMBOLS AND LEGEND 1 OF 3
I - 02
I - 03
I - 04
E - 01 LEGEND, SYMBOLS, AND ABBREVIATIONS -SHEET 1 OF 2
LEGEND, SYMBOLS, AND ABBREVIATIONS -SHEET 2 OF 2
ELECTRICAL SITE PLAN
ONE LINE DIAGRAM
BOOSTER PUMP STATION POWER AND GROUNDING PLAN
BOOSTER PUMP STATION LIGHTING AND RECEPTACLE PLAN
INTERCONNECT WIRING DIAGRAM
VFD CONTROL SCHEMATIC
TYPICAL ELECTRICAL DETAILS- SHEET 1 OF 2
I - 05 RTU CONTROL PANEL
E - 11 TYPICAL ELECTRICAL DETAILS- SHEET 2 OF 2
PANELBOARD SCHEDULE
I - 06 INSTRUMENTATION DETAILS
ELEVATED WATER STORAGE TANK P&ID
INSTRUMENTATION SYMBOLS AND LEGEND 2 OF 3
INSTRUMENTATION SYMBOLS AND LEGEND 3 OF 3
E - 02
E - 04
E - 05
E - 06
E - 07
E - 09
E - 03
E - 08
E - 10
PRESSURE PIPE PROFILES
SITE FINISH GRADING PLAN
SOIL MAP
EROSION AND SEDIMENT CONTROL PLAN
EROSION & SEDIMENT CONTROL DETAILS (SHEET 1 OF 2)
EROSION & SEDIMENT CONTROL DETAILS (SHEET 2 OF 2)
PROCESS MECHANICAL
M - 01 MECHANICAL LEGENDS, SYMBOLS, AND ABBREVIATIONS
M - 02
M - 03
BOOSTER PUMP STATION PLAN AND SECTIONS
BOOSTER PUMP STATION SECTIONS AND DETAILS
STRUCTURAL
S - 01 GENERAL NOTES
STRUCTURAL SPECIAL INSPECTION NOTES
BOOSTER PUMP STATION BASE SLAB PLAN, SECTIONS AND DETAILS
S - 02
S - 03
BOOSTER PUMP STATION STRUCTURAL DETAILSS - 04
T. THOMAS
C-02
4 37
T. THOMAS
PRESSURE PIPE
PROFILES
FILE NAME:
DESIGNED BY:
PROJECT NO.:
DATE:
U se r:N N
IA
S pe c:
AU
S-
N C
SM
O
D F ile :C
:\U
SE
R S\
N N
IA
\D
C \A
C C
D O
C S\
AR
C
AD
IS
\A U
S-
-T
R
IL
IT
H
S
TU
D
IO
S
EL
EV
AT
ED
S
TO
R
AG
E
TA
N
K\
PR
O
JE
C T
FI
LE
S\
W
IP
\C
IV
IL
\S H
EE
TS
\2 5-
T
R
IL
IT
H
B O
O
ST
ER
P
U M
P
ST
AT
IO
N \C
-0 4.
D W
G S ca le
:1 :1
S av ed D at e:
4/
/2
Ti m e:
:1
P lo t D at e:
E br ah im i N ia
, N og ol ; 4
/1 8/
; 0 8:
La yo ut :1
CONSULTANTS
SEALS
NO. ISSUED FORDATE BY
DRAWN BY:
CHECKED BY:
COPYRIGHT:
SHEET TITLE
SCALE:
FAYETTE COUNTY WATER
SYSTEM
FCWS-TRILITH TANK
BOOSTER PUMP STATION
REVISIONS
APRIL 2025
ISSUED FOR BID
COPYRIGHT:
LEGAL ENTITY:
ARCADIS U.S., INC.
ARCADIS U.S., INC.
AS SHOWN
OFSHEET
PROJECT STATUS:
2839 PACES FERRY ROAD
SUITE 900, ATLANTA, GA 30339
TE: 770-431-8666
WWW.ARCADIS.COM
400 VETERANS PARKWAY
FAYETTEVILLE, GA 30214
0 4/18/2025 ISSUED FOR BID TT
30239751
100% SUBMITTAL
N. NIA
N. NIA
T. THOMAS
C-05
CIVIL
NOTES:
1. ALL UNDERGROUND UTILITY LOCATIONS SHOULD BE CONSIDERED APPROXIMATE. THERE IS NO GUARANTEE
THAT ALL UTILITIES, WHETHER FUNCTIONAL OR ABANDONED WITHIN IN THE PROJECT AREA, ARE SHOWN ON THIS DRAWING. CONTRACTOR SHALL VERIFY EXACT LOCATION OF ALL UNDERGROUND UTILITIES BEFORE
STARTING WORK, AND SHALL BE RESPONSIBLE FOR ALL DAMAGE RESULTING FROM THIS WORK.
2. POST-GRADING TOPOGRAPHIC SURVEY IS NOT AVAILABLE, AND THEREFORE, TOPOGRAPHY CONTOUR LINES
PROVIDED ARE ESTIMATES OF EXISTING TOPOGRAPHY,
Know what'sbelow.
before you dig.Call
REXISTING GROUND
PROPOSED WATER PIPE
LEGEND
12" DIP PRESSURE PIPE
FROM EXISTING DISTRIBUTION SYSTEM TO PUMP HOUSE
SCALE: HORIZ.
VERT.
12" DIP PRESSURE PIPE
FROM PUMP HOUSE TO 12"X12" TEE
12" DIP SUCTION/DISCHARGE PRESSURE PIPE
FROM PUMP HOUSE TO STORAGE TANK
FROM STORAGE TANK TO PUMP HOUSE
ASSUMED
EXISTING GRADE
ASSUMED
EXISTING GRADE
C-05
RESTRAINT NOTES:
1. ALL PROPOSED PIPING SHALL BE RESTRAINT BY MECHANICAL JOINT OR OTHER MANUFACTURE
APPROVED RESTRAINTS.
EROSION & SEDIMENT
CONTROL
LEGEND & NOTES
FILE NAME:
DESIGNED BY:
PROJECT NO.:
DATE:
U se r:N N
IA
S pe c:
AU
S-
N C
SM
O
D F ile :C
:\U
SE
R S\
N N
IA
\D
C \A
C C
D O
C S\
AR
C
AD
IS
\A U
S-
-T
R
IL
IT
H
S
TU
D
IO
S
EL
EV
AT
ED
S
TO
R
AG
E
TA
N
K\
PR
O
JE
C T
FI
LE
S\
W
IP
\C
IV
IL
\S H
EE
TS
\2 5-
T
R
IL
IT
H
B O
O
ST
ER
P
U M
P
ST
AT
IO
N \E
SC
-0
1.
D
W G
S ca le :1
:1 S av ed
D at e:
3/
/2
Ti m e:
:5
P lo t D at e:
E br ah im i N ia , N og ol
; 4 /1
8/
; 0
9:
La yo ut
:1
CONSULTANTS
SEALS
NO. ISSUED FORDATE BY
DRAWN BY:
CHECKED BY:
COPYRIGHT:
SHEET TITLE
SCALE:
FAYETTE COUNTY WATER
SYSTEM
FCWS-TRILITH TANK
BOOSTER PUMP STATION
REVISIONS
APRIL 2025
ISSUED FOR BID
COPYRIGHT:
LEGAL ENTITY:
ARCADIS U.S., INC.
ARCADIS U.S., INC.
AS SHOWN
OFSHEET
PROJECT STATUS:
2839 PACES FERRY ROAD
SUITE 900, ATLANTA, GA 30339
TE: 770-431-8666
WWW.ARCADIS.COM
400 VETERANS PARKWAY
FAYETTEVILLE, GA 30214
0 4/18/2025 ISSUED FOR BID TT
30239751
ISSUED FOR BID
N. NIA
N. NIA
ESC-01
EROSION & SEDIMENT CONTROL
Know what'sbelow.
before you dig.Call
R
MANAGEMENT PLAN:
ALL EROSION CONTROL MEASURES SHALL BE INSPECTED DAILY AND AFTER EVERY RAINFALL.
ALL NEEDED REPAIRS SHALL BE MADE IMMEDIATELY TO PREVENT FURTHER DAMAGE AND
EROSION. STRUCTURES THAT SHALL BE INSPECTED INCLUDE:
1. SEDIMENT BARRIER - SEDIMENT SHALL BE REMOVED ONCE IT HAS ACCUMULATED TO ONE-HALF
THE ORIGINAL HEIGHT OF THE BARRIER. SEDIMENT BARRIERS SHALL BE REPLACED PER
MANUFACTURER'S RECOMMENDATIONS OR THE HEIGHT OF THE PRODUCT IS NOT MAINTAINING
80% OF ITS PROPERLY INSTALLED HEIGHT.
2. STORM DRAIN INLET PROTECTION - INSPECT STONE FILTER RING INLET STRUCTURE AFTER HEAVY RAINS TO SEE IF ANY EROSION AROUND OR BELOW THE FILTER RING HAS TAKEN PLACE
OR IF STONES HAVE BEEN DISLODGED. IMMEDIATELY MAKE ALL NEEDED REPAIRS TO PREVENT
FURTHER DAMAGE.
3. SLOPE STABILIZATION - ALL EROSION CONTROL BLANKETS AND MATTING SHOULD BE INSPECTED
PERIODICALLY FOLLOWING INSTALLATION, PARTICULARLY AFTER RAINSTORMS TO CHECK FOR
EROSION AND UNDERMINING. ANY DISLOCATION OR FAILURE SHOULD BE REPAIRED
IMMEDIATELY. IF WASHOUTS OR BREAKAGE OCCURS, REINSTALL THE MATERIAL AFTER
REPAIRING DAMAGE TO THE SLOPE OR DITCH. CONTINUE TO MONITOR THESE AREAS UNTIL
THEY BECOME PERMANENTLY STABILIZED.
4. INLET SEDIMENT TRAP - TRAP SHOULD BE CLEANED OUT AFTER HEAVY RAIN EVENTS. SEDIMENT
SHALL BE REMOVED WHEN THE SEDIMENT HAS ACCUMULATED TO ONE-HALF THE HEIGHT OF
THE TRAP.
5. SEEDING, FERTILIZING, AND MULCHING - SEEDED AREAS SHALL BE INSPECTED FOR FAILURE
AND NECESSARY REPAIRS SHALL BE MADE IMMEDIATELY.
6. CONSTRUCTION ENTRANCE/EXIT - INSPECT CONSTRUCTION ROAD SURFACE DAILY, MAINTAIN WHEN NEEDED IN A CONDITION TO PREVENT SEDIMENT AND TOPSOIL FROM LEAVING THE SITE.
EROSION CONTROL
1. EROSION CONTROL PRACTICES MUST COMPLY WITH THE MINIMUM BEST MANAGEMENT
PRACTICES FOR EROSION CONTROL AND SHALL COMPLY WITH THE STANDARDS /
SPECIFICATIONS IN THE "MANUAL FOR EROSION CONTROL AND SEDIMENT CONTROL IN
GEORGIA", LATEST EDITION.
2. EROSION AND SEDIMENT CONTROL DEVICES MUST BE INSTALLED AND INSPECTED PRIOR TO
ANY GRADING ON SITE.
3. PERMANENT VEGETATION SHALL BE PLACED AT ALL AREAS GRADED TO FINAL GRADE
IMMEDIATELY UPON COMPLETION. WHEN HAND PLANTING, MULCH (HAY OR STRAW) SHOULD BE
UNIFORMLY SPREAD OVER SEEDED AREA WITHIN 24 HOURS OF SEEDING. DURING UNSUITABLE
GROWING SEASONS, MULCH WILL BE USED AS A TEMPORARY COVER (DS1). ON SLOPES THAT
ARE 2:1 OR STEEPER, MULCH WILL BE ANCHORED.
4. IN CONCENTRATED FLOW AREAS, ALL SLOPES STEEPER THAN 2.5:1 AND WITH THE HEIGHT TEN FEET OR GREATER, AND CUTS AND FILLS WITHIN STREAM BUFFER, SHALL BE STABILIZED WITH
THE APPROPRIATE EROSION CONTROL MATTING OR BLANKET.
5. SEDIMENT / EROSION CONTROL DEVICES MUST BE CHECKED AFTER EACH STORM EVENT.
EACH DEVICE IS TO BE MAINTAINED OR REPLACED IF SEDIMENT ACCUMULATION HAS REACHED
ONE HALF THE CAPACITY OF THE DEVICE. THE CONTRACTOR SHALL FURNISH, INSTALL, AND
MAINTAIN ANY ADDITIONAL EROSION CONTROL MEASURES AS DIRECTED BY THE GOVERNING
JURISDICTION AND/OR THE ENGINEER.
6. THE CONTRACTOR SHALL INSTALL ALL EROSION CONTROL DEVICES AND ENSURE THAT THEY
ARE PROPERLY FUNCTIONING PRIOR TO ANY LAND DISTURBANCE ACTIVITIES.
7. AMENDMENTS/REVISIONS TO THE ES&PC PLAN WHICH HAVE A SIGNIFICANT EFFECT ON BMPS
WITH A HYDRAULIC COMPONENT MUST BE CERTIFIED BY THE DESIGN PROFESSIONAL.
8. THE ESCAPE OF SEDIMENT FROM THE SITE SHALL BE PREVENTED BY THE INSTALLATION OF
EROSION AND SEDIMENT CONTROL MEASURES AND PRACTICES PRIOR TO LAND DISTURBING
ACTIVITIES.
9. EROSION CONTROL MEASURES WILL BE MAINTAINED AT ALL TIMES. IF FULL IMPLEMENTATION
OF THE APPROVED PLAN DOES NOT PROVIDE FOR EFFECTIVE EROSION CONTROL, ADDITIONAL
EROSION AND SEDIMENT CONTROL MEASURES SHALL BE IMPLEMENTED TO CONTROL OR
TREAT THE SEDIMENT SOURCE.
10. ANY DISTURBED AREAS LEFT EXPOSED FOR A PERIOD GREATER THAN 14 DAYS SHALL BE
STABILIZED WITH MULCH OR TEMPORARY SEEDING.
11. BUILDING MATERIALS AND BUILDING PRODUCTS NOT IN USE SHALL BE COVERED BY HEAVY
PLASTIC.
POLLUTION CONTROLS
1. BMP'S SUCH AS CONSTRUCTION EXITS, WATERING STATIONS, AND SWEEPERS MAY BE
UTILIZED TO MINIMIZE OFF-SITE VEHICLE TRACKING OF SEDIMENTS AND THE GENERATION OF
DUST.
2. NON-EXEMPT ACTIVITIES SHALL NOT BE CONDUCTED WITHIN THE 25 OR 50-FOOT
UNDISTURBED STREAM BUFFERS AS MEASURED FROM THE POINT OF WRESTED VEGETATION
OR WITHIN 25-FEET OF THE COASTAL MARSHLAND BUFFER AS MEASURED FROM THE
JURISDICTIONAL DETERMINATION LINE WITHOUT FIRST ACQUIRING THE NECESSARY
VARIANCES AND PERMITS.
3. PETROLEUM BASED PRODUCTS- CONTAINERS FOR PRODUCTS SUCH AS FUELS, LUBRICANTS,
TARS WILL BE INSPECTED DAILY FOR LEAKS AND SPILLS. THIS INCLUDES ON-SITE VEHICLE AND
MACHINERY DAILY INSPECTIONS AND REGULAR PREVENTATIVE MAINTENANCE OF SUCH
EQUIPMENT. EQUIPMENT MAINTENANCE AREAS WILL BE LOCATED AWAY FROM STATE WATER,
NATURAL DRAINS AND STORM WATER DRAINAGE INLETS. IN ADDITION, TEMPORARY FUELING
TANKS SHALL HAVE A SECONDARY CONTAINMENT LINER TO PREVENT/MINIMIZE SITE
CONTAMINATION. DISCHARGE OF OILS, FUELS AND LUBRICANTS IS PROHIBITED. PROPER
DISPOSAL METHODS WILL INCLUDE COLLECTION IN A SUITABLE CONTAINER AND DISPOSAL AS
REQUIRED BY LOCAL AND STATE REGULATIONS.
3.1. SOLVENTS- ALL PRODUCTS WILL BE STORED IN TIGHTLY SEALED ORIGINAL CONTAINERS
WHEN NOT IN USE. EXCESS PRODUCT WILL NOT BE DISCHARGED TO THE STORM WATER
COLLECTION SYSTEM. EXCESS PRODUCT, MATERIALS USED WITH THESE PRODUCTS AND
PRODUCT CONTAINERS WILL BE DISPOSED OF ACCORDING TO MANUFACTURER'S
SPECIFICATIONS AND RECOMMENDATIONS.
3.2. CONCRETE TRUCK WASHING- WASHOUT OF CONCRETE DRUMS AT THE CONSTRUCTION
SITE IS PROHIBITED. CONTRACTOR IS TO SELECT LOCATIONS ON THE SITE FOR CONCRETE
WASH DOWN THAT MEET THE CONDITIONS OF THE NPDES STAND ALONE PERMIT.
CONCRETE WASH DOWN AREA SHOULD BE OUTSIDE OF THE AREA THAT IS MARKED FOR
EXCAVATION. CONTRACTOR SHALL SELECT AN EPA RECOMMENDED WASHOUT BMP TO BE
USED AND SUBMIT LOCATIONS AND WASH OUT BMP TYPE FOR ENGINEER'S APPROVAL.
WASHOUT OF THE DRUM AT THE CONSTRUCTION SITE IS PROHIBITED.
3.3. FERTILIZER/HERBICIDES- THESE PRODUCTS WILL BE APPLIED AT RATES THAT DO NOT
EXCEED THE MANUFACTURER'S SPECIFICATIONS OR ABOVE THE GUIDELINES SET FORTH
IN THE CROP ESTABLISHMENT OR IN THE GSWCC MANUAL FOR EROSION AND SEDIMENT
CONTROL IN GEORGIA. ANY STORAGE OF THESE MATERIALS WILL BE UNDER ROOF IN
SEALED CONTAINERS.
3.4. CONSTRUCTION MATERIALS- NO CONSTRUCTION MATERIALS WILL BE BURIED OR
DISPOSED OF ONSITE. ALL SUCH MATERIAL WILL BE DISPOSED OF ACCORDING TO
APPLICABLE STATE AND LOCAL REGULATIONS.
3.5. WASTE MATERIALS SHALL NOT BE DISCHARGED TO WATERS OF THE STATE, EXCEPT AS
AUTHORIZED BY A SECTION 404 PERMIT.
4. SOIL CLEANUP AND CONTROL PRACTICES
4.1. LOCAL, STATE AND MANUFACTURER'S RECOMMENDED METHODS FOR SPILL CLEANUP
WILL BE CLEARLY POSTED AND PROCEDURES MADE AVAILABLE TO SITE PERSONNEL.
4.2. MATERIAL AND EQUIPMENT NECESSARY FOR SPILL CLEANUP WILL BE KEPT IN THE
MATERIAL STORAGE AREAS. TYPICAL MATERIALS AND EQUIPMENT INCLUDES, BUT IS NOT
LIMITED TO: BROOMS, DUSTPANS, MOPS, RAGS, GLOVES, GOGGLES, CAT LITTER, SAND,
SAWDUST AND PROPERTY LABELED PLASTIC AND METAL WASTE CONTAINERS.
4.3. SPILL PREVENTION PRACTICES AND PROCEDURES WILL BE REVIEWED AFTER A SPILL AND
ADJUSTED AS NECESSARY TO PREVENT FUTURE SPILLS.
4.4. ALL SPILLS WILL BE CLEANED UP IMMEDIATELY UPON DISCOVERY. ALL SPILLS WILL BE
REPORTED AS REQUIRED BY LOCAL, STATE AND FEDERAL REGULATIONS.
4.5. FOR SPILLS THAT IMPACT SURFACE WATER (LEAVE A SHEEN ON SURFACE WATER), THE
NATIONAL RESPONSE CENTER (NRC) WILL BE CONTACTED WITHIN 24 HOURS AT
1-800-424-8802.
4.6. FOR SPILLS OF AN UNKNOWN AMOUNT, THE NATIONAL RESPONSE CENTER (NRC) WILL BE
CONTACTED WITHIN 24 HOURS A 1-800-424-8802.
4.7. FOR SPILLS GREATER THAN 25 GALLONS AND NO SURFACE WATER IMPACTS, THE
GEORGIA EPD WILL BE CONTACTED WITHIN 24 HOURS.
4.8. FOR SPILLS LESS THAN 25 GALLONS AND NO SURFACE WATER IMPACTS, THE SPILL WILL
BE CLEANED UP AND LOCAL AGENCIES WILL BE CONTACTED AS REQUIRED.
4.9. THE CONTRACTOR SHALL NOTIFY THE ENGINEER OF RECORD WHO PREPARED THIS PLAN
IF MORE THAN 1320 GALLONS OF PETROLEUM IS STORED ONSITE (THIS INCLUDES
CAPACITIES OF EQUIPMENT) OR IF ANY ONE PIECE OF EQUIPMENT HAS A CAPACITY
GREATER THAN 660 GALLONS. THE CONTRACTOR WILL NEED A SPILL PREVENTION
CONTAINMENT AND COUNTERMEASURES PLAN PREPARED BY A LICENSED
PROFESSIONAL.
5. A PORTABLE SANITARY WASTE UNIT WILL BE ONSITE TO COLLECT SANITARY WASTE DURING
CONSTRUCTION.
SITE NOTES:
1. PROJECT IS LOCATED IN FAYETTE COUNTY WITHIN THE CITY OF FAYETTEVILLE, GEORGIA.
2. PROJECT LATITUDE/LONGITUDE: (33.469492, -84.510849)
3. APPROXIMATE TOTAL DISTURBED ACREAGE OF THE TRILITH STUDIOS ELEVATED WATER TANK
SITE IS 0.63 ACRES.
4. THE STORMWATER RUNOFF FOR THIS PROJECT FLOWS INTO TRILITH STUDIO'S POND #5 WHICH
DISCHARGES TO SANDY CREEK. SEE STORMWATER MANAGEMENT REPORT ISSUED BY
ROCHESTER & ASSOCIATES FOR DETAILS.
5. IT IS ANTICIPATED THAT THE PROJECT WILL NOT HAVE ANY BUFFER ENCROACHMENTS AND
BUFFER VARIANCE WILL NOT BE REQUIRED.
6. WETLAND CERTIFICATION: THE DESIGN PROFESSIONAL, WHOSE SEAL APPEARS HEREON,
CERTIFIES THE FOLLOWING: THE NATIONAL WETLAND INVENTORY MAPS HAVE BEEN CONSULTED;
AND, WETLANDS ARE INDICATED ON THE PROPERTY; HOWEVER, NO PORTION OF PROPOSED
PROJECT AND DISTURBED AREA IS WITHIN THE WETLAND AREA. THE LAND DISTURBANCE OF
PROTECTED WETLAND SHALL NOT OCCUR.
7. NO PORTION OF THIS SITE LIES WITHIN A SPECIAL FLOOD HAZARD ZONE "AE" OR "A". THE SITE LIES WITHIN THE FIRM MAPS OF THE CITY OF FAYETTEVILLE FLOOD INSURANCE STUDY. FIRM MAP
NUMBERS: 13113C0082E AND 13113COO84E, EFFECTIVE DATE: SEPTEMBER 26, 2008.
8. MAINTENANCE AND TRAFFIC: THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL ROAD
PERMITS FROM CITY OF FAYETTEVILLE AS NECESSARY.
9. PRIMARY PERMITTEE & 24-HOUR CONTACT:
VANESSA TIGERT
FAYETTE COUNTY WATER SYSTEM
ADDRESS: 245 MCDONOUGH RD.
FAYETTEVILLE, GA 30214
PHONE: 770-320-6016
EMAIL: VTIGERT@FAYETTECOUNTYGA.GOV
CONSTRUCTION SEQUENCE:
1. FOR EACH STAGE OF CONSTRUCTION THE FOLLOWING SEQUENCE WILL
APPLY:
1.1. CONFIRM LOCATIONS OF AND CONSTRUCT/INSTALL INITIAL
EROSION AND SEDIMENT CONTROL BMPS WITHIN THE LIMITS OF
THE STAGE PRIOR TO ANY OTHER CONSTRUCTION ACTIVITIES ON
SITE. INITIAL EROSION AND SEDIMENT CONTROL BMPS SHALL
INCLUDE THE FOLLOWING: CONSTRUCTION FENCING, TREE
PROTECTION FENCING, SILT FENCING, INLET SEDIMENT TRAPS,
SAND BAG SEDIMENT BARRIER, AND CONSTRUCTION ENTRANCES.
ALL EROSION AND SEDIMENT CONTROL BMPS TO BE CONSTRUCTED
IN ACCORDANCE WITH THE PLANS.
1.2. CLEAR AND GRUB TO THE LIMITS REQUIRED FOR CONSTRUCTION
AND REMOVE EXISTING TREES AS SHOWN ON THE PLANS.
1.3. EXCAVATE TRENCHES FOR INSTALLATION OF THE WATER
INFRASTRUCTURE PIPING, AS NECESSARY, CONSTRUCT PIPE
DIVERSIONS TO DIVERT AND BYPASS RUNOFF FROM EXISTING
SYSTEM.
1.4. BEGIN INTERMEDIATE PHASE EXCAVATION AND GRADING
ACTIVITIES AFTER ALL REQUIRED INITIAL EROSION CONTROL
MEASURES HAVE BEEN INSTALLED AND CONSTRUCTED.
1.5. BEGIN CONSTRUCTION OF WATER TANK AND WATER
INFRASTRUCTURE PIPING, UTILITY RELOCATIONS, CURB AND
GUTTER, DRIVEWAYS, ROADWAYS, AND REMAINING STRUCTURES
AS SHOWN ON PLANS. INSTALL INLET PROTECTION AS SHOWN ON
PLANS.
1.6. ESTABLISH FINISHED GRADES AT EARLIEST POSSIBLE DATE.
DISTURBED AREAS SHALL BE STABILIZED WITH TEMPORARY
VEGETATION AND MULCH IF LAND-DISTURBING ACTIVITIES CEASE
FOR MORE THAN 14 CALENDAR DAYS IN ACCORDANCE WITH NPDES
REQUIREMENTS. ONCE FINAL GRADES ARE ESTABLISHED, APPLY
PERMANENT SOIL STABILIZATION IN ACCORDANCE WITH PLANS.
ANY DISTURBED AREA REMAINING IDLE FOR 30 DAYS SHALL BE
STABILIZED WITH PERMANENT VEGETATION.
2. THE FOLLOWING SHALL APPLY AFTER ALL CONSTRUCTION STAGES ARE
COMPLETE:
2.1. AFTER FINAL STABILIZATION FOR THE PROJECT AS DEFINED BY
NPDES GAR100001 IS ACHIEVED, RETURN TO THE SITE AND REMOVE
ALL TEMPORARY MEASURES INCLUDING SILT FENCES, SEDIMENT
TRAPS, AND DIVERSIONS. INSTALL PERMANENT VEGETATION TO ALL
AREAS (EXCEPT IMPERVIOUS SURFACES) DISTURBED BY THE
TEMPORARY MEASURES.
2.2. REMOVE ALL TEMPORARY EROSION CONTROL MEASURES
INCLUDING CONSTRUCTION FENCING, TREE PROTECTION FENCING,
AND CONSTRUCTION ENTRANCES WITHIN 30 DAYS AFTER FINAL
SITE STABILIZATION.
PROJECT DESCRIPTION
THE TRILITH TANK BOOSTER PUMP STATION PROJECT INCLUDES THE CONSTRUCTION OF,
PRE-FABRICATED BOOSTER PUMP STATION AND ASSOCIATED WATER INFRASTRUCTURE.
THE EXISTING TRILITH STUDIOS SITE IS A MOVIE PRODUCTION CAMPUS THAT HAS MULTIPLE STAGE
BUILDINGS FOR PRODUCTION. THE PROJECT AREA FOR THE WATER TANK IS ON AN EXISTING
GRASSED HILL ADJACENT TO THE CEMETERY NEAR AN ENTRANCE OF THE TRILITH CAMPUS.
DESCRIPTION OF BMP'S:
· INITIAL PHASE:
DURING INITIAL PHASE OF CONSTRUCTION SILT FENCE, INLET PROTECTION, STONE CHECK
DAMS AND FILTER RINGS WILL BE INCORPORATED TO PREVENT SEDIMENTS ESCAPING THE
SITE.
· INTEMEDIATE PHASE:
DURING INTERMEDIATE PHASE, USE OF SILT FENCE, INLET PROTECTION, TEMPORARY
STABILIZATION PRACTICES, DUST CONTROL, CHECK DAMS, AND FILTER RING WILL BE
INCORPORATED.
· FINAL PHASE:
DURING FINAL PHASE ALL NON IMPERVIOUS DISTURBED AREAS WILL BE STABILIZED USING
PERMANENT STABILIZATION PRACTICES.
ESC-01
D.Wilson
VETER
AN
S PAR
KW
AY
VETER
AN
S PAR
KW
AY
W
EL
C O
M E
C
EN
TE
R
±2 ,3
S
F
FF
E:
.5
0'
G U
AR
D
H O
U
SE
±1 ,9
S
F
FF
E:
.5
0'
R300'
R150'
W
AT
ER
FE
AT
U
R E
W W
W
W W
W W
W W
W W
W W
W
O
FF
IC
E
BU
IL
D
IN
G
D
ES
IG
N
F
FE
: 8
.0 0'
±8 3, SF
X
X
X
X X
X
X
OE
OE
OE
OE
OE
OE
OE
OE
T
W W
W W
W W
W
W
W W
W W
W
W
W
WW
W
W
W
W
W W W
W
W
SS
W W
W
SOIL INFORMATION
MAP UNIT
SYMBOL MAP UNIT NAME SLOPE (%) SYMBOL
AkA ALTAVISTA
SANDY LOAM 0 - 3
AmB APPLING SANDY
LOAM 2 - 6
CeB CECIL SANDY
LOAM 2 - 6
CeC CECIL SANDY
LOAM 6 - 10
SOIL MAP
FILE NAME:
DESIGNED BY:
PROJECT NO.:
DATE:
U se r:N N
IA
S pe c:
AU
S-
N C
SM
O
D F ile :C
:\U
SE
R S\
N N
IA
\D
C \A
C C
D O
C S\
AR
C
AD
IS
\A U
S-
-T
R
IL
IT
H
S
TU
D
IO
S
EL
EV
AT
ED
S
TO
R
AG
E
TA
N
K\
PR
O
JE
C T
FI
LE
S\
W
IP
\C
IV
IL
\S H
EE
TS
\2 5-
T
R
IL
IT
H
B O
O
ST
ER
P
U M
P
ST
AT
IO
N \E
SC
-0
3.
D
W G
S ca le :1
:1 S av ed
D at e:
4/
/2
Ti m e:
:2
P lo t D at e:
E br ah im i N ia , N og ol
; 4 /1
8/
; 0
9:
La yo ut
:1
CONSULTANTS
SEALS
NO. ISSUED FORDATE BY
DRAWN BY:
CHECKED BY:
COPYRIGHT:
SHEET TITLE
SCALE:
FAYETTE COUNTY WATER
SYSTEM
FCWS-TRILITH TANK
BOOSTER PUMP STATION
REVISIONS
APRIL 2025
ISSUED FOR BID
COPYRIGHT:
LEGAL ENTITY:
ARCADIS U.S., INC.
ARCADIS U.S., INC.
AS SHOWN
OFSHEET
PROJECT STATUS:
2839 PACES FERRY ROAD
SUITE 900, ATLANTA, GA 30339
TE: 770-431-8666
WWW.ARCADIS.COM
400 VETERANS PARKWAY
FAYETTEVILLE, GA 30214
0 4/18/2025 ISSUED FOR BID TT
30239751
ISSUED FOR BID
N. NIA
N. NIA
ESC-02
CIVIL
Know what'sbelow.
before you dig.Call
R
O
FF
IC
E
BU
IL
D
IN
G
D
ES
IG
N
F
FE
: 87 8.
±8 3, SF
X
X
X X
X
X
W
W
W
W
X X
X
X X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
LOD
LOD
LOD
LO
D
LO
D
LOD
LOD
LO
D
LO
D
LO
D
LO
DLOD
LOD
LODLOD
LOD
LO
D
LO
DLO
D
LO
DLOD
LO
D
LO
D
LO
D
LO
D
LOD LOD
LOD LOD LOD
LO
D
LO
D
LOD
LOD
LOD
X X
X X
LO
D
LOD
LO
D
LOD
X
X
EROSION & SEDIMENT
CONTROL PLAN
FILE NAME:
DESIGNED BY:
PROJECT NO.:
DATE:
U se r:N N
IA
S pe c:
AU
S-
N C
SM
O
D F ile :C
:\U
SE
R S\
N N
IA
\D
C \A
C C
D O
C S\
AR
C
AD
IS
\A U
S-
-T
R
IL
IT
H
S
TU
D
IO
S
EL
EV
AT
ED
S
TO
R
AG
E
TA
N
K\
PR
O
JE
C T
FI
LE
S\
W
IP
\C
IV
IL
\S H
EE
TS
\2 5-
T
R
IL
IT
H
B O
O
ST
ER
P
U M
P
ST
AT
IO
N \E
SC
-0
5.
D
W G
S ca le :1
:1 S av ed
D at e:
4/
/2
Ti m e:
:3
P lo t D at e:
E br ah im i N ia , N og ol
; 4 /1
8/
; 0
9:
La yo ut
:1
CONSULTANTS
SEALS
NO. ISSUED FORDATE BY
DRAWN BY:
CHECKED BY:
COPYRIGHT:
SHEET TITLE
SCALE:
FAYETTE COUNTY WATER
SYSTEM
FCWS-TRILITH TANK
BOOSTER PUMP STATION
REVISIONS
APRIL 2025
ISSUED FOR BID
COPYRIGHT:
LEGAL ENTITY:
ARCADIS U.S., INC.
ARCADIS U.S., INC.
AS SHOWN
OFSHEET
PROJECT STATUS:
2839 PACES FERRY ROAD
SUITE 900, ATLANTA, GA 30339
TE: 770-431-8666
WWW.ARCADIS.COM
400 VETERANS PARKWAY
FAYETTEVILLE, GA 30214
0 4/18/2025 ISSUED FOR BID TT
30239751
ISSUED FOR BID
N. NIA
N. NIA
ESC-03
CIVIL
Know what'sbelow.
before you dig.Call
R
SILT FENCEX
PROPOSED GRAVEL
NOTES:
1. THE CONTRACTOR SHALL PREVENT SEDIMENT FROM ESCAPING THE SITE AND PROVIDE STREET
SWEEPING DAILY TO KEEP ROADS CLEAN. THE CONTRACTOR CAN ONLY ACCESS THE SITE VIA THE
CONSTRUCTION ENTRANCE.
2. TOTAL DISTURBED AREA FOR THIS PROJECT IS 0.63 ACRES.
3. WASHOUT OF THE DRUM AT THE CONSTRUCTION SITE IS PROHIBITED.
LEGEND
LOD LIMITS OF DISTURBANCE (1.30 AC)
CONSTRUCTION
STAGING AREA
LIMITS OF DISTURBANCE
CONSTRUCTION
ROAD
FINAL LOCATION OF
CONSTRUCTION STAGING
AREA TO BE FIELD
LOCATED BY
CONTRACTOR
FIELD LOCATE THE PIZOMETER.
CAP AND PROVIDE TRAFFIC
RATED LID/COVER TO PROTECT
Lat: 33.469492 Long: -84.510849
CONCRETE
WASHOUT
DOUBLE ROW
SILT FENCE
FENCE TYPE B
ESC-05
DOUBLE ROW
SILT FENCE
FENCE TYPE B
TYPE-B
COMPOST FILTER
SOCK (DOUBLE ROW)
CAN BE REMOVED
AND RE-INSTALLED
ON A DAILY BASIS
DURING
CONSTRUCTION OF
PIPE
LIMIT OF
DISTURBANCE
EXTEND EXISTING CHECK DAMS
TO THE EDGE OF PAVEMENT
LIMITS OF DISTURBANCE
Ds3
Ds3
Ds3
Ds3
DOUBLE ROW
SILT FENCE
FENCE TYPE B
Ds3
Ds3
Ds3
Ds3
Ds3
FILL/STABALIZE AND RE-SEED
THE EXPOSED AREAS ON
SLOPE
RE-ESTABLISH GRASS
AFTER CONSTRUCTION
ACTIVITIES ARE
COMPLETEDDs3
Ds3
Ds3
EROSION CONTROL NOTES:
THE CONTRACTOR SHALL STRICTLY ADHERE TO
DUST CONTROL GUIDELINES AS SET FORTH IN
THE MANUAL FOR EROSION AND SEDIMENT
CONTROL IN GEORGIA, LATEST EDITION.
ALL NON IMPERVIOUS DISTURBED AREAS TO BE
STABILIZED USING TEMPORARY/PERMANENT
STABILIZATION PRACTICES (TYPICAL). ALL
TEMPORARY/PERMANENT STABILIZATION
PRACTICES ARE TO BE IN ACCORDANCE WITH
THE MANUAL FOR EROSION AND SEDIMENT
CONTROL IN GEORGIA, LATEST EDITION.
Du
Ds3
REMOVE DEBRIS AND
CLEAN UP EXISTING INLET
Ds3
LIMITS OF DISTURBANCE
CONSTRUCTION
ENTRANCE
ESC-0
EROSION & SEDIMENT
CONTROL DETAILS
(SHEET 1 OF 2)
EROSION & SEDIMENT CONTROL
Know what'sbelow.
before you dig.Call
R
ENTRANCE ELEVATION
EXIT DIAGRAM
SCALE: NONE
SIDE VIEW
FRONT VIEW
SILT FENCE -
N.T.S.
HARD SURFACE PUBLIC ROAD
SEDIMENT TRAP
(SEE NOTE 8)
CULVERT UNDER
ENTRANCE (IF NEEDED)
DIVERSION RIDGE (SEE NOTE 6)
N.S.A. R-2 (1.5"-3.5")
COARSE AGGREGATE
GEOTEXTILE UNDERLINER
SUPPLY WATER TO WASH
WHEELS IF NECESSARY
TIRE WASHRACK AREA/
TIRE WASHERS
GEOTEXTILE UNDERLINER
N.S.A. R-2 (1.5"-3.5")
COARSE AGGREGATE
ORIGINAL GRADE
FILE NAME:
DESIGNED BY:
PROJECT NO.:
DATE:
U se r:N N
IA
S pe c:
AU
S-
N C
SM
O
D F ile :C
:\U
SE
R S\
N N
IA
\D
C \A
C C
D O
C S\
AR
C
AD
IS
\A U
S-
-T
R
IL
IT
H
S
TU
D
IO
S
EL
EV
AT
ED
S
TO
R
AG
E
TA
N
K\
PR
O
JE
C T
FI
LE
S\
W
IP
\C
IV
IL
\S H
EE
TS
\2 5-
T
R
IL
IT
H
B O
O
ST
ER
P
U M
P
ST
AT
IO
N \E
SC
-0
8.
D
W G
S ca le :1
:1 S av ed
D at e:
4/
/2
Ti m e:
:4
P lo t D at e:
E br ah im i N ia , N og ol
; 4 /1
8/
; 0
9:
La yo ut
:1
CONSULTANTS
SEALS
NO. ISSUED FORDATE BY
DRAWN BY:
CHECKED BY:
COPYRIGHT:
SHEET TITLE
SCALE:
FAYETTE COUNTY WATER
SYSTEM
FCWS-TRILITH TANK
BOOSTER PUMP STATION
REVISIONS
APRIL 2025
ISSUED FOR BID
COPYRIGHT:
LEGAL ENTITY:
ARCADIS U.S., INC.
ARCADIS U.S., INC.
AS SHOWN
OFSHEET
PROJECT STATUS:
2839 PACES FERRY ROAD
SUITE 900, ATLANTA, GA 30339
TE: 770-431-8666
WWW.ARCADIS.COM
400 VETERANS PARKWAY
FAYETTEVILLE, GA 30214
0 4/18/2025 ISSUED FOR BID TT
30239751
ISSUED FOR BID
N. NIA
N. NIA
Ss
Du
SCALE: NONE
Sd2-F
FILTER FABRIC INLET SEDIMENT TRAP
ESC-03
D.Wilson
S
PIPING
SYMBOLS
SCHEMATIC
VALVE LEGEND
ABBREVIATIONS
WELD NECK FLANGE
FLANGED
MECHANICAL JOINT
GROOVED END
WELDED
CONCRETE
BELL &
SPIGOT
CPVC/PVC/COPPER
FASTITE
(RESTRAINED JOINT)
FORGED STEEL
SOCKET/THREADED
HDPE IPS (FLANGED)
HDPE IPS
CAST IRON HUBLESS
FLANGED FLARE
BLIND FLANGE
EXPANSION JOINT
FLEXIBLE COUPLING
FLANGED
COUPLING ADAPTER
DISMANTLING JOINT
HARNESSED
DISMANTLING JOINT
FLANGED
COUPLING ADAPTER
DIAPHRAGM VALVE (DV)
RELIEF VALVE (RV)
PINCH VALVE (PI)
BALL VALVE (BV)
NEEDLE VALVE (NV)
ECCENTRIC PLUG VALVE (PV)
AIR RELEASE VALVE (AR)
FOUR-WAY VALVE (FW)
SUCTION FOOT VALVE (FV)
SLUICE GATE (SL)
GLOBE VALVE (GL)
BALL CHECK VALVE (BC)
MUD VALVE (MD)
THREE-WAY PLUG VALVE (TW)
BUTTERFLY VALVE (BFV)
AIR/VACUUM VALVE (AV)
COMBINATION AIR VALVE (CA)
CHECK VALVE (CH)
GATE VALVE (GV)
CURB STOP (CS)
AUTOMATIC PRESSURE
REDUCING VALVES (PR)
AUTOMATIC PRESSURE
SUSTAINING VALVES (PS)
SLIDE GATE (SG)
SLIDE PLATE (SP)
FC=FAIL CLOSED
FO=FAIL OPEN
SOLENOID VALVE (SV)
TELESCOPING VALVE (TV)
KNIFE GATE VALVE (KV)
BUTTERFLY DAMPER (BD)
SYM PLAN ELEV
NOTES:
1. PIPELINES, VALVES AND EQUIPMENT SHALL BE FURNISHED, FABRICATED, ERECTED AND OTHERWISE INSTALLED TO LINES, ELEVATIONS LOCATIONS, AND DIMENSIONS AS SHOWN, SPECIFIED OR REQUIRED FOR A COMPLETE INSTALLATION. THE CONTRACTOR SHALL MEASURE ALL DIMENSIONS SHOWN PROPERLY AND SHALL TAKE SUCH FIELD DIMENSIONS AS MAY BE NECESSARY TO PROPERLY INSTALL ALL PIPELINES, VALVES AND EQUIPMENT.
DIMENSIONS AND LOCATIONS OF EXISTING EQUIPMENT, PIPING, AND STRUCTURES SHALL BE FIELD VERIFIED BY CONTRACTOR PRIOR TO NEW EQUIPMENT FABRICATION.
2. ALL PIPELINES, VALVES AND EQUIPMENT SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH CONTRACT DOCUMENTS AND MANUFACTURER'S SPECIFICATIONS, IN A NEAT WORKMANLIKE MANNER, AND IN
ACCORDANCE WITH APPROVED SHOP AND WORKING DRAWINGS.
3. ALL CONSTRUCTION MATERIALS REQUIRING STORAGE SHALL BE STORED IN STRICT CONFORMANCE WITH CONTRACT DOCUMENTS, MANUFACTURER'S SPECIFICATIONS, RECOMMENDATIONS AND INSTRUCTIONS.
PIPE SERVICE
VALVE TYPES
EXAMPLE: VALVE LABEL
16" - BFV
DIAMETER VALVE
(INCHES) TYPE
EXAMPLE: NEW PIPE LABEL
36" - RW - DIP -
DIAMETER PIPE PIPE
(INCHES) SERVICE MATERIAL
PIPE MATERIALS
ALP AIR (LOW PRESSURE PROCESS)
CA COMPRESSED AIR
DR DRAIN
HO HYDRAULIC OIL
LS LEVEL SENSOR
OF OVERFLOW
SAM SAMPLE
SAN SANITARY
POT POTABLE WATER
AECV AUTOMATIC ELECTRONIC CONTROL VALVES
ARV AIR RELEASE VALVE
AVV AIR VACUUM VALVE
BFV BUTTERFLY VALVE
ECV ELECTRIC CHECK VALVE
GV GATE VALVE
GBV GLOVE VALVE
KGV KNIFE GATE VALVE
SG SLUICE GATE
SV SOLENOID VALVE
PRV PRESSURE REDUCING VALVE
PSV PRESSURE SUSTAINING VALVE
BS BLACK STEEL
CU COPPER
CPVC CHLORINATED POLYVINYL CHLORIDE
CS CARBON STEEL
DIP DUCTILE IRON
PVC POLYVINYL CHLORIDE
RPVC REINFORCED PVC FLEXIBLE HOSE
SSTL STAINLESS STEEL
ST STEEL
BLV BALL VALVE
DG DIVERTER GATE
HPW3 HIGH PRESSURE PLANT WATER
HT/I
HEAT TRACED/
INSULATED
LEGAL ENTITY:
CONSULTANTS
SEALS
SHEET TITLE
ARCADIS U.S., INC.COPYRIGHT:
DATE:
PROJECT NO.:
FILE NAME:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SCALE:
SHEET OF
NO. DATE ISSUED FOR BY
E
2 3 4 5 6
D
C
B
A
ARCADIS U.S., INC.
2839 PACES FERRY ROAD
SUITE 900 ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
400 VETERANS PARKWAY,
FAYETTEVILLE, GA 30214,
UNITED STATES
PROJECT STATUS:
REVISIONS
NTS
/1
/2
:0 :0
P
M A u to d e s k D o c s /A
U S
-3 -T ri lit h S tu d io s E le va te d S to ra g e T a n k/
M -3
D -B
P S
R
.r v t
E. VAN DEVENTER
B. TARIT
T. THOMAS
APRIL 2025
30135792
M-01
M-01
FAYETTE COUNTY WATER
SYSTEM
FCWS-TRILITH TANK
BOOSTER PUMP
STATION
MECHANICAL
MECHANICAL LEGENDS,
SYMBOLS AND
ABBREVATIONS
FAYETTE COUNTY, GEORGIA
BID
A
M-02
B
M-02
C
M-03
M-03 D
4" FLOOR DRAIN
SEE NOTE 4
HEATER 30"
FROM FLOOR
36" X 80"
SINGLE DOOR
10'W X 7'H DOUBLE
HINGED HOLLOW
METAL DOOR
PUMP 1 PUMP 2
C/L
SUCTION
C/L
PUMP 1
C/L
PUMP 2
C/L
DISCHARGE
C/L 12"
DISCHARGE
C/L 12"
SUCTION
C/L 12"
SUCTION
0' - 9"
2' - 1"
13' - 4"
22' - 1"
27' - 7"
34' - 7"
2' - 0"
6' - 8"
8" FM
LOUVERED BLOWER
90" FROM FLOOR
8" PSV
AIR INTAKE
24" FROM FLOOR
ARV
4" THICK INSULATED
SANDWICH PANEL WALL
REFER TO ELECTRICAL GROUNDING
AND POWER PLAN FOR ELECTRICAL
EQUIPMENT LAYOUT
6" BFV
(TYP)
8" BFV
SEE CIVIL SHEET
FOR
CONTINUATION
SEE NOTE 3
SEE CIVIL SHEET
FOR
CONTINUATION
SEE NOTE 3
1" ARV DRAIN
SEE NOTE 5
SEE CIVIL SHEET
FOR
CONTINUATION
CONCRETE ENCASED,
SEE STRUCTURAL SHEET
FOR DETAIL
SEE NOTE 2
PRESSURE
TRANSMITTER
PRESSURE GAUGE
FCA RESTRAINED TYPE
8" FCA
W/RESTRAINTS
8" FM
12"-POT-DIP
(DISCHARGE)
PIPE SUPPORT
(TYP.)
HEATER 30"
FROM FLOOR
LOUVERED
BLOWER
90" FROM
FLOOR
12"-POT-CS
12"-POT-DIP
(SUCTION)
5" DISMANTLING
JOINT (TYP)
1" COMBINATION
AIR VALVE
PI (TYP)
1" BV (TYP)
0.5" ARV
(TYP)
PI AND PSL
(TYP)
1" BV (TYP)
10"-POT-CS
0.5"-DR-PVC
SAMPLE
POINT
12" BFV
REFER TO STRUCTURAL
FOR CONCRETE PAD
LAYOUT
SILENT CV
(TYP)
0.5" ARV (TYP)
CL. EL.= 871.50 CL. EL.= 871.51
PROVIDED BY THE
BPS
MANUFACTURER
(FROM
DISTRIBUTION
SYSTEM TO PS)
PROVIDED BY BPS
MANUFACTURER
SEE NOTE 6
(FROM PS TO
DISTRIBUTION
SYSTEM)
EL.= 875.75
8"X12" 90 REDUCING
ELBOW
PIT
METAL RAFTER PEAKED
STANDING SEAM METAL ROOM
10" CHANNEL
12"-POT-DIP
(SUCTION) 12"-POT-DIP
(DISCHARGE)
OVERLAPPING
STEEL PANELS
OVERHANG TYP.
FOR PERIMETER
REMOVABLE
LIFT EYES
/2
ALUM GUTTERS AND DOWNSPOUT,
TYP.
PROVIDE PRECAST CONCRETE
SPLASH BLOCK AT THE BOTTOMS
OF THE DOWNSPOUTS.
SLOPE
2:12
AIR INTAKE 24"
FROM FLOOR
ARV
PROVIDED BY THE
BPS MANUFACTURER
PROVIDED BY THE
BPS
MANUFACTURER
(FROM PS TO
DISTRIBUTION
SYSTEM)
(FROM
DISTRIBUTION
SYSTEM TO PS)
CL. EL.= 871.51
/8
PIT AND PI
8" PSV
ARV
8" BFV
HANDWHEEL
OPERATED
LEGAL ENTITY:
CONSULTANTS
SEALS
SHEET TITLE
ARCADIS U.S., INC.COPYRIGHT:
DATE:
PROJECT NO.:
FILE NAME:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SCALE:
SHEET OF
NO. DATE ISSUED FOR BY
E
2 3 4 5 6
D
C
B
A
ARCADIS U.S., INC.
2839 PACES FERRY ROAD
SUITE 900 ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
400 VETERANS PARKWAY,
FAYETTEVILLE, GA 30214,
UNITED STATES
PROJECT STATUS:
REVISIONS
3/8" = 1'-0"
/1
/2
:0 :1
P
M A u to d e s k D o c s /A
U S
-3 -T ri lit h S tu d io s E le va te d S to ra g e T a n k/
M -3
D -B
P S
R
.r v t
E. VAN DEVENTER
B. TARIT
T. THOMAS
APRIL 2025
30135792
M-02
M-02
FAYETTE COUNTY WATER
SYSTEM
FCWS-TRILITH TANK
BOOSTER PUMP
STATION
MECHANICAL
PLAN AND SECTIONS
(FROM PS TO
DISTRIBUTION SYSTEM)
FAYETTE COUNTY, GEORGIA
BID
BOOSTER PUMP
STATION
SCALE: 3/8" = 1'-0"
FLOOR PLAN VIEW
SCALE: 3/8" = 1'-0"M-02
A SECTION VIEW
SCALE: 3/8" = 1'-0"M-02
B SECTION VIEW
0' 4' 6'2'
0' 4' 6'2' 0' 4' 6'2'
NOTES:
1. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL EQUIPMENT COORDINATION
AND INSTALLATION CONSIDERATIONS, AND FURNISH AND INSTALL ALL
EQUIPMENT, APPURTENANCES, AND SERVICES NOT PROVIDED BY THE PS
MANUFACTURER TO ALLOW FOR A COMPLETE AND OPERABLE BOOSTER PUMP
STATION SYSTEM.
2. CONTRACTOR TO INSTALL AND ENCASE IN CONCRETE PIPING FROM PS TO
DISTRIBUTION SYSTEM PRIOR TO SETTING THE PS ON THE FOUNDATION SLAB.
3. CONTRACTOR TO SET PS ON FOUNDATION SLAB THEN CONNECT AND INSTALL
DISTRIBUTION SYSTEM AND TANK CONNECTING PIPING UNDER THE PS.
4. CONTRACTOR TO ROUTE DRAIN TO TRENCH DRAIN OUTSIDE THE PS.
5. CONTRACTOR TO COMBINE AND ROUTE ALL AIR VALVE DRAINS TO DRAIN IN PS
CORNER.
6. CONTRACTOR TO GROUT FILL AROUND PIPING ONCE CONNECTED TO PS.
E
M-03
6" BUTTERFLY
VALVE (TYP.)
1" COMBINATION
AIR VALVE
PI
0.5" ARVPI AND PSL
(TYP)
PIT
PUMP 2
12" SUCTION12" SUCTION
8" BFV
(TYP.)
8" PSV
8" FCA W/RESTRAINTS
12" X 8" TEE
ARV (TYP)
PI AND PIT
8' - 3"
6" X 5" ECCENTRIC
REDUCER
6" L.R.
ELBOW
5" FCA
W/RESTRAINTS
6" ELBOW
6" X 4" ECCENTRIC
REDUCER
6" L.R. ELBOW
6" SILENT CV
PI AND PSL
(TYP)
PI
0.5" ARV
6" BFV (TYP)
LEGAL ENTITY:
CONSULTANTS
SEALS
SHEET TITLE
ARCADIS U.S., INC.COPYRIGHT:
DATE:
PROJECT NO.:
FILE NAME:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SCALE:
SHEET OF
NO. DATE ISSUED FOR BY
E
2 3 4 5 6
D
C
B
A
ARCADIS U.S., INC.
2839 PACES FERRY ROAD
SUITE 900 ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
400 VETERANS PARKWAY,
FAYETTEVILLE, GA 30214,
UNITED STATES
PROJECT STATUS:
REVISIONS
3/4" = 1'-0"
/1
/2
:0 :2
P
M A u to d e s k D o c s /A
U S
-3 -T ri lit h S tu d io s E le va te d S to ra g e T a n k/
M -3
D -B
P S
R
.r v t
E. VAN DEVENTER
B. TARIT
T. THOMAS
APRIL 2025
30135792
M-03
M-03
FAYETTE COUNTY WATER
SYSTEM
FCWS-TRILITH TANK
BOOSTER PUMP
STATION
MECHANICAL
SECTIONS AND DETAILS
FAYETTE COUNTY, GEORGIA
BID
BOOSTER PUMP
STATION
0' 2' 3'1'
NOTE:
1. PIPE EXTERNAL TO STATION MUST BE
INDEPENDENTLY SUPPORTED.
SCALE: 3/4" = 1'-0"M-02
D PUMPS ENLARGED PLAN VIEW
SCALE: 3/4" = 1'-0"M-02
C SECTION VIEW
SCALE: 3/4" = 1'-0"M-03
E SECTION VIEW
0' 2' 3'1'
0' 2' 3'1'
REINFORCEMENT LAP SPLICE, EMBEDMENT LENGTH AND STANDARD HOOKS TABLE IS
BASED ON A MINIMUM CONCRETE COMPRESSIVE STRENGTH OF 4000 PSI MINIMUM OR GREATER
AND 60000 PSI REINFORCEMENT (WITH NO EPOXY COATING).
ALL LAP SPLICES SHALL BE CLASS B SPLICES.
* THE MINIMUM LAP LENGTHS FOR BEAMS, COLUMNS AND STRAIGHT EMBEDMENTS ARE
BASED ON A 3 BAR DIAMETER MINIMUM CENTER TO CENTER BAR SPACING AND
A 2" BAR COVER. IF THE SPLICE AND/OR EMBEDMENT DOES NOT CONFORM
TO THESE REQUIREMENTS, THEN CONTRACTOR SHALL APPLY APPROPRIATE FACTORS
IN COMPLIANCE WITH ACI 318 WITH APPROVAL BY ENGINEER.
** THE MINIMUM LAP LENGTHS FOR SLABS, WALLS AND STRAIGHT EMBEDMENTS ARE
BASED ON A 6" BAR SPACING AND A 2" BAR COVER. IF THE LAP CONDITION
DOES NOT CONFORM TO THESE REQUIREMENTS, THEN USE BEAM LAP LENGTHS OR
COMPLY WITH LAP REQUIREMENTS OF ACI 318 WITH APPROVAL BY ENGINEER.
*** TOP BARS ARE DEFINED AS ALL HORIZONTAL BARS WITH 12" OR MORE FRESH
CONCRETE BENEATH.
WHERE SPLICES ARE REQUIRED BETWEEN BARS OF DIFFERENT SIZES,
THE LAP LENGTH SHALL BE NO LESS THAN THE EMBEDMENT LENGTH OF
THE LARGER BAR OR THE LAP LENGTH OF THE SMALLER BAR, WHICHEVER IS GREATER.
STRAIGHT
STRAIGHT BAR
EMBEDMENT
LENGTH
90° HOOK
EMBEDMENT
LENGTH WITH
STD HOOK
A OR G
HOOK
135° HOOK
H
A O
R G
H O
O K
REINFORCEMENT LAP SPLICE, EMBEDMENT LENGTH AND STANDARD HOOKS (INCHES)
BAR
SIZE
MIN LAP LENGTHS FOR MIN EMBEDMENT LENGTHS
CLASS B CLASS B
TOP*** OTHERS OTHERS
WITH
STANDARD
HOOK
25#3 #4 #5 #6 #7 #8 #9
#10 #11
TOP***
BEAMS AND COLUMNS* SLABS AND WALLS ** FOR BEAMS
AND COLUMNS *
FOR SLABS
AND WALLS **
TOP*** OTHERS TOP*** OTHERS
MIN STD HOOKS
90°
A OR G
135°
A OR G H
4.5 5.5
10.5
2.5
3.75
5.25
4.5
LAP SPLICE AND EMBEDMENT LENGTH TABLEGENERAL
G-1 THESE NOTES ARE GENERAL AND SUPPLEMENTAL TO THE SPECIFICATIONS
AND APPLY TO THE ENTIRE PROJECT UNLESS MODIFIED OR NOTED
OTHERWISE IN THE CONTRACT DOCUMENTS.
G-2 STANDARD DETAILS SHOWN ON STRUCTURAL TYPICAL DRAWINGS SHALL BE
USED WHEN REFERRED TO, UNLESS DIFFERENT DETAILS ARE SHOWN
ON THE DRAWINGS.
G-3 DESIGN IS IN ACCORDANCE WITH AND CONSTRUCTION SHALL COMPLY WITH
THE PROVISIONS OF THE 2018 INTERNATIONAL BUILDING CODE WITH
GEORGIA STATE AMENDMENTS (2022-2025), EXCEPT WHERE OTHER
APPLICABLE CODES AND THE CONTRACT DOCUMENTS ARE MORE
RESTRICTIVE.
DESIGN LOADS:
LIVE LOADS:
-FLOOR LIVE LOAD 300 PSF
SNOW LOAD:
-GROUND SNOW LOAD, P g 5 PSF
-SNOW IMPORTANCE FACTOR 1.1
WIND LOAD:
-ULTIMATE DESIGN WIND SPEED 114 MPH
-WIND EXPOSURE C
-RISK CATEGORY III
SEISMIC LOAD:
-RISK CATEGORY III
-SPECTRAL RESPONSE ACCELERATIONS, S s 0.163
-SPECTRAL RESPONSE ACCELERATIONS, S 1 0.082
-SITE CLASS D
-SPECTRAL RESPONSE COEFFICIENT, S DS 0.173
-RESPONSE COEFFICIENT, S D1 0.130
-SEISMIC DESIGN CATEGORY B
-ANALYSIS PROCEDURE ASCE 7-16,11.7
-SEISMIC IMPORTANCE FACTOR, I e 1.25
G-4 WHERE THE ASTERISK SYMBOL (*) IS SHOWN IN THE DRAWINGS, DIMENSIONS
AND ELEVATIONS ARE TO BE VERIFIED EITHER BY FIELD MEASUREMENTS FOR
EXISTING STRUCTURES OR BY SHOP DRAWINGS FOR EQUIPMENT FURNISHED.
STRUCTURAL DIMENSIONS NOT SHOWN BUT CONTROLLED BY OR RELATED
TO EQUIPMENT SHALL BE VERIFIED BY THE CONTRACTOR WITH THE
MANUFACTURER PRIOR TO CONSTRUCTION.
G-5 EQUIPMENT ANCHOR BOLT SIZES, TYPES, LOCATIONS AND PATTERNS SHALL
BE AS REQUIRED BY THE APPROVED EQUIPMENT MANUFACTURER. ALL BOLT
PATTERNS SHALL BE TEMPLATED TO ENSURE ACCURACY OF PLACEMENT.
G-6 STRUCTURAL DRAWINGS SHALL BE USED IN COORDINATION WITH DRAWINGS
OF ALL OTHER DISCIPLINES AND MANUFACTURER'S SHOP DRAWINGS.
G-7 IF A CONFLICT IS FOUND BETWEEN DIFFERENT PORTIONS OF THE
CONTRACT DOCUMENTS, THE CONTRACTOR SHALL NOTIFY THE OWNER
IMMEDIATELY. CONTINUED CONSTRUCTION OF THE AREA IN CONFLICT
SHALL BE AT THE CONTRACTOR'S OWN RISK UNTIL THE CONFLICT IS
RESOLVED BY THE OWNER.
G-8 STRUCTURES HAVE BEEN DESIGNED FOR OPERATIONAL LOADS ON THE
COMPLETED STRUCTURE. DURING CONSTRUCTION, THE STRUCTURES
SHALL BE PROTECTED BY BRACING AND TEMPORARY SUPPORTS
WHEREVER EXCESSIVE CONSTRUCTION LOADS MAY OCCUR.
OVERSTRESSING OF ANY STRUCTURAL ELEMENT IS PROHIBITED.
G-9 NO BACKFILL SHALL BE PLACED AGAINST ANY WALL UNLESS ALL SUPPORTING
ELEMENTS OF THE STRUCTURE HAVE BEEN CONSTRUCTED AND HAVE
REACHED THE SPECIFIED MINIMUM CONCRETE STRENGTH.
G-10 ALL THE DIMENSIONS AND LEVELS ARE IN FEET UON.
DO NOT SCALE THESE DRAWINGS, USE DIMENSIONS.
G-11 CONTRACTOR'S CONSTRUCTION AND/OR ERECTION SEQUENCES SHALL
RECOGNIZE AND CONSIDER THE EFFECTS OF THERMAL MOVEMENTS OF
STRUCTURAL ELEMENTS DURING THE CONSTRUCTION PERIOD.
G-12 WHERE CONNECTIONS TO OR MODIFICATIONS OF EXISTING STRUCTURES
ARE SHOWN, EXISTING FOUNDATIONS, WALLS, COLUMNS, SLABS, BEAMS,
FLOORS, DECKS (CONCRETE, STEEL, TIMBER, ETC.) ARE ASSUMED TO BE
IN GOOD CONDITION. THIS MUST BE VERIFIED IN THE FIELD BY THE
CONTRACTOR. UNSOUND CONDITIONS SHALL BE REPORTED TO THE
ENGINEER. ALL UNSOUND STRUCTURAL ELEMENTS SHALL BE REPAIRED TO
SOUND CONDITION AS APPROVED BY THE ENGINEER. EXISTING
CONSTRUCTION DIMENSIONS SHALL BE VERIFIED BY THE CONTRACTOR
BEFORE WORK COMMENCES. VARIATIONS FROM DIMENSIONS
SHOWN ON THESE DRAWINGS SHALL BE REPORTED TO THE ENGINEER.
G-13 OPENINGS AND PENETRATIONS:
THE CONTRACTOR SHALL SUBMIT COMPOSITE DRAWINGS INDICATING ALL
FLOOR OPENINGS AND PENETRATIONS THROUGH STRUCTURAL
MEMBERS REQUIRED TO ACCOMMODATE THE HVAC, PLUMBING AND
ELECTRICAL WORK. THE CONTRACTOR SHALL FOLLOW THE TYPICAL
FRAMING DETAILS AT OPENINGS AND REINFORCEMENT DETAILS AT
PENETRATIONS THROUGH STRUCTURAL MEMBERS. ACCORDINGLY, THE
CONTRACTOR SHALL SUBMIT SHOP DETAILS TO THE ENGINEER FOR REVIEW.
CONCRETE
C-1 CONCRETE 28-DAY COMPRESSIVE STRENGTH:
CLASS A - 4500 PSI
CLASS B - 3000 PSI
C-2 PORTLAND CEMENT: ASTM C150, TYPE I/II OR ASTM C595 TYPE IL.
C-3 REINFORCEMENT: ASTM A615, GRADE 60.
C-4 FLY ASH: ASTM C618, CLASS F OR SLAG ASTM C989 GRADE 120, MAX CONTENT 25% BY
WEIGHT.
C-5 CONCRETE COVER FOR REINFORCING:
A) SURFACES CAST AGAINST EARTH 3"
B) SURFACE WITH EMBEDDED PVC WATERSTOP 3"
C) ALL OTHER SURFACES 2"
C-6 CONSTRUCTION JOINTS SHALL BE LOCATED AS SHOWN ON THE
DRAWINGS. WHERE NOT SHOWN, CONSTRUCTION JOINTS SHALL
BE LOCATED AS REQUIRED BY THE SPECIFICATIONS. CONSTRUCTION
JOINT, TYPES AND LOCATIONS SHALL BE AS APPROVED BY THE ENGINEER.
C-7 WHERE HORIZONTAL CONSTRUCTION JOINTS, LOCATED ABOVE
THE FOUNDATION SLAB, EXTEND BEYOND WHERE NEEDED,
TERMINATE AT A VERTICAL CONSTRUCTION JOINT AS APPROVED BY
THE ENGINEER.
C-8 EQUIPMENT SUPPORTS, ANCHORAGES, OPENINGS, RECESSES
AND REVEALS NOT SHOWN ON THE STRUCTURAL DRAWINGS BUT
REQUIRED BY OTHER CONTRACT DOCUMENTS, SHALL BE PROVIDED FOR
PRIOR TO PLACING CONCRETE.
C-9 AT ALL TYPICAL CURBS, EQUIPMENT PADS, AND PIPE SUPPORT
PIERS, REINFORCING DOWELS SHOWN MAY BE REPLACED WITH
MATCHING DOWELS SET IN EPOXY IN DRILLED HOLES AS
SPECIFIED. DOWELS LOCATED CLOSER THAN 3 INCHES FROM ANY EDGE
OF CONCRETE SHALL NOT BE REPLACED WITH DRILLED DOWELS.
C-10 WHERE DRILLED EPOXY DOWELS ARE PLACED INTO HARDENED
CONCRETE, ADJUST THE DOWEL LOCATIONS AS NEEDED TO AVOID
DRILLING THROUGH ANY REINFORCING BARS. IF THE DOWEL LOCATION
NEEDS TO BE MODIFIED, CONTACT THE ENGINEER BEFORE PROCEEDING.
C-11 DOWELS, ANCHOR BOLTS, PIPES, AND OTHER EMBEDDED ITEMS
SHALL BE HELD SECURELY IN POSITION WHILE CONCRETE IS
BEING PLACED.
C-12 CONDUITS AND PIPES EMBEDDED IN OR PENETRATING THROUGH CONCRETE SHALL
BE SPACED ON CENTER NOT LESS THAN 3 TIMES THEIR OUTSIDE DIMENSION, BUT
NOT LESS THAN 2 1/2 INCHES CLEAR. OUTSIDE DIMENSION OF EMBEDDED ITEMS
SHALL NOT EXCEED 1/3 OF THE CONCRETE MEMBER THICKNESS. CLEAR SPACING
REQUIREMENTS SHALL APPLY FOR EMBEDDED CONDUITS OR PIPES CROSSING AT AN
ANGLE LESS THAN 60 DEGREES.
C-13 THE EFFECTIVE DIMENSION USED TO MEET MEMBER THICKNESS LIMITATIONS SHALL
BE THE SUM OF THE OUTER DIMENSIONS OF CROSSING ELEMENTS.
C-14 EMBEDDED CONDUITS AND PIPES SHALL BE LOCATED BETWEEN THE LAYERS OF
REINFORCEMENT AND A MINIMUM OF 2 1/2 INCHES CLEAR FROM APPROXIMATELY
PARALLEL REINFORCING BARS. REQUIREMENTS FOR EMBEDDED ELEMENTS
CROSSING REINFORCING BARS SHALL BE AS REQUIRED FOR CROSSING EMBEDDED
ELEMENTS.
C-15 CONDUITS AND PIPES SHALL NOT BE EMBEDDED IN OR PASS THROUGH COLUMNS
AND BEAMS.
C-16 REINFORCING BARS AND ACCESSORIES SHALL NOT BE IN CONTACT WITH ANY METAL
PIPE, PIPE FLANGE, METAL CONDUIT OR OTHER METAL PARTS EMBEDDED IN
CONCRETE. A MINIMUM CLEARANCE OF 2 INCHES SHALL BE PROVIDED.
C-17 CONTRACTOR SHALL PROVIDE 3/4 INCH CHAMFER USING WOOD CHAMFER STRIPS ON
ALL EXPOSED CORNERS OF COLUMNS, BEAMS AND WALLS OR AS REQUIRED TO
MATCH EXISTING.
C-18 LAP SPLICES SHALL BE IN ACCORDANCE WITH THE TABLE SHOWN ON SHEET S-01.
C-19 PROVIDE ADDITIONAL REINFORCEMENT AT OPENINGS AND WALL INTERSECTIONS
AS SHOWN ON TYPICAL DETAILS (UON).
C-20 PROVIDE WATERSTOPS IN ALL FOUNDATIONS, TANKS AND OTHER SUBSTRUCTURES.
STRUCTURAL METALS
S-1 DETAIL, FABRICATE, AND ERECT STRUCTURAL STEEL IN ACCORDANCE
WITH AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS,
LATEST EDITION.
S-2 STEEL MATERIAL:
A) STRUCTURAL TUBING: ASTM A500, GRADE C
B) STRUCTURAL PIPE: ASTM A53, GRADE B
C) W SHAPES: ASTM A992
D) ALL OTHER SHAPES: ASTM A572, GRADE 50
E) PLATES AND ANGLES: ASTM A36, UON
S-3 DO NOT PAINT STEEL SURFACES WHICH ARE TO BE WELDED OR
ENCASED IN CONCRETE.
S-4 ALL GROOVE AND BUTT WELDS SHALL BE FULL PENETRATION.
S-5 FILLET WELD SIZES SHALL BE THE MINIMUM SIZE REQUIRED BY AISC
CODE FOR PLATE SIZES TO BE CONNECTED BUT NOT LESS THAN 3/16"
AND SHALL BE APPLIED TO THE ENTIRE JOINT CONTACT LENGTH.
S-6 ALL BOLTS, ANCHOR BOLTS, AND CONCRETE ANCHORS CONNECTING
GALVANIZED STEEL SHALL BE SS 316.
S-7 WHENEVER ONE MEMBER IS FASTENED TO ANOTHER WITH
FASTENINGS (BOLTS, WELDS, ETC.) SET AT A UNIFORM SPACING,
THERE SHALL BE A MINIMUM OF TWO FASTENINGS PER PIECE
CONNECTED AND THE FIRST AND LAST FASTENINGS SHALL BE
LOCATED NOT TO EXCEED 1/4 SPACE FROM EACH END.
S-8 A) ALUMINUM SHAPES
1. ASTM B308/B308M, ALLOY 6061-T6, ASTM B221, ALLOY 6061-T6
2. ALUMINUM TUBES AND PIPES: ASTM B429, ALLOY 6061-T6
3. ALUMINUM BARS AND RODS: ASTM B211, ALLOY 6061-T6
4. ALUMINUM PLATES: ASTM B209, ALLOY 6061-T6
B) ELECTRODES FOR WELDING: ER 5356 COMPLYING WITH AWS
D1.2/D1.2M
S-9 STAINLESS STEEL:
1. ANSI, TYPE 316/316L
2. SECTION, SHAPES AND BARS ASTM A 276
3. BOLTED CONNECTIONS - BOLTS AND ANCHOR BOLTS:
A. MATCH ALLOY OF THE STRUCTURAL MEMBER CONNECTED
B., TYPE 316/316L : ASTM F 593, GRADE B8M, CLASS 1, HEAVY HEX
C., TYPE 304/304L : ASTM F593, GRADE B8, CLASS 1, HEAVY HEX
4. WELDED CONNECTIONS:, TYPE 316L : E316L- 15 ELECTRODE
F-1 FOR FOUNDATION DESIGN CRITERIA REFER TO DESIGN PHASE
GEOTECHNICAL ENGINEERING REPORT PREPARED BY OASIS
CONSULTING SERVICES, PROJECT NO. 224927, DATED OCTOBER 4, 2022,
AND REPORT ADDENDUM, DATED NOVEMBER 22, 2022.
FOUNDATION NOTES
ADHESIVE ANCHORS FOR ANCHORAGE INTO CONCRETE:
MANUFACTURERS:
1.HILTI HIT-RE 500 V3 EPOXY ADHESIVE ANCHORS
2.OR AS APPROVED.
A. INJECTABLE TWO-COMPONENT ADHESIVE.
B. HILTI ANCHOR ROD HAS-R 316 STAINLESS STEEL THREADED ROD COMPLYING WITH
ASTM F593 CONDITION CW.
C. ADHESIVE ANCHORAGE SYSTEM SHALL BE SEISMIC QUALIFIED WITH CURRENT
ICC-ES ESR REPORT (ICC-ES-ESR 3814).
D. INSTALLERS TO BE TRAINED BY ANCHOR MANUFACTURER.
E. 10% OF ALL ADHESIVE ANCHORS TO BE LOAD TESTED, AS INSTALLED IN FIELD, TO
ENSURE ALLOWABLE MANUFACTURER LOADS ARE ACHIEVED.
INSIDE FACE
INSIDE DIAMETER
JOINT
KNOCK OUT
INVERT
IF
ID
JT
KO
INV
LIVE LOAD
ANGLE (STRUCTURAL SHAPE)
LONG LEG HORIZ
LOCATION
LOW POINT
LONG WAY
LONG LEG VERT
L
LL
LLH
LP
LW
LOC
LLV
ADD'L
AB
A
ALT
APPROX
AL
ADDITIONAL
ALUMINUM
ALTERNATE
APPROXIMATE
ARCHITECTURAL
ANCHOR BOLTS
BLDG
BET
BAL
BL
BRG
BOT
BM
BLK
BALANCE
BETWEEN
BUILDING LINE
BUILDING
BLOCK
BEAM
BOTTOM
BEARING
MEZZANINE
MAXIMUM
MECHANICAL
MIDDLE
MANHOLE
MANUFACTURE,MANUFACTURER
MECH
MEZZ
MAX
MID
MH
MFR
NUMBER
NORTH
NEAR FACE
OUTSIDE DIAMETER
ON CENTER
NOT TO SCALE
NF
N
OD
NTS
OC
MIN MINIMUM
OF OUTSIDE FACE
CANT'L
C
CANTILEVER
CHANNEL (STRUCTURAL SHAPE)
LONGLG
ANCH ANCHOR
MATCH/MATCHINGMTCH
ABBREVIATIONS
CJ
COL
CMU
CL
CONSTRUCTION JOINT
CLEAR
COLUMN
CONCRETE MASONRY UNIT
CONT
CONN
CONC
CONST
CONCRETE
CONNECTION
CONTINUOUS
CONSTRUCTION
COMPRESSIBLECOMP
DIM
DIAG
DIA
DL
DWG
DP
DN
DO
DIAMETER
DIAGONAL
DIMENSION
DOWN
DITTO
DRAWING
DEAD LOAD
DEEP
EA
E
EMB
ELEC
EL
EJ
EF
EMBEDMENT
EAST
EACH
EXPANSION JOINT
ELEVATION
ELECTRICAL
EACH FACE
DOWELDWL
DETAILDET
EQUIP
EQ
ENCL
ES
EXIST
EXP
EW T&B
EW
EQUAL
EQUIPMENT
EACH SIDE
EACH WAY
EXISTING
EXPANSION
EACH WAY TOP & BOTTOM
ENCLOSURE
EXT EXTERIOR
CTR
C/C CENTER TO CENTER
CENTER
CF COMBINED FOOTING
FD
FB
FL
FIN
FF
FDN
FLOOR BEAM
FLOOR DRAIN
FOUNDATION
FAR FACE
FINISH
FLOOR
GA
GB
GALV
H
GRTG
GR GRADE
GRADE BEAM
GALVANIZE
GAUGE
GRATING
HIGH
HP
HORIZ
HIGH POINT
HORIZONTAL
HEIGHTHT
FOOTINGFTG
HVAC
AIR CONDITIONING
HEATING, VENTILATING &
OPENING
OPPOSITE
OPNG
OPP
RADIUS
ROOF DRAIN
REINFORCEMENT
ROOM
ROUGH OPENING
REQUIRED
RAD
RD
REINF
RM
RO
REQD
RISERR
STANDARD
SQUARE
STAINLESS STEEL
SPECIFICATION
SST
STD
SQ
SPEC
STIRRUP
STEEL
STRUCTURAL
SHORT WAYSW
STL
STIR
STRUCT
SPACINGSPA
WP WORKING POINT
THICK
TOP OF
TOP AND BOTTOM
TOP OF CONCRETE
THK
TOC
T&B
TYPICAL
TREAD
VERTICAL
T
TYP
UON
WF
VERT
WITH
WATERSTOPWS
W/
UNLESS OTHERWISE NOTED
WIDE FLANGE STRUCTURAL SHAPE
T/
W WIDTH, WEST
TO BE DECIDEDTBD
SOUTHS
SECTION
SLAB
SHEET
SIMILAR
SL
SIM
SHT
SECT
PC PRECAST CONCRETE
PLATE
POUNDS PER SQUARE FOOT
PL
PSF
POLYVINYL CHLORIDEPVC
PB PLINTH BEAM
OH OVER HEAD
LEGAL ENTITY:
CONSULTANTS
SEALS
SHEET TITLE
ARCADIS U.S., INC.COPYRIGHT:
DATE:
PROJECT NO.:
FILE NAME:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
SCALE:
SHEET OF
NO. DATE ISSUED FOR BY
E
2 3 4 5 6
D
C
B
A
ARCADIS U.S., INC.
2839 PACES FERRY ROAD
SUITE 900 ATLANTA, GA 30339
TEL: 770-431-8666
WWW.ARCADIS.COM
400 VETERANS PARKWAY,
FAYETTEVILLE, GA 30214,
UNITED STATES
PROJECT STATUS:
REVISIONS
BID SET
As indicated
-0
4-
8:
:3
Au to de sk
D oc s:
//A
U S-
-T ril ith S tu di os E le va te d
St or ag e
Ta nk
/S -3
D -B
PS
_R
.rv t
N. SADASHIVA
A. RAJESH
D. DUNCAN
APRIL 2025
30135792
S-01
S-01
FAYETTE COUNTY WATER
SYSTEM
FCWS - TRILITH
TANK BOOSTER
PUMP STATION
STRUCTURAL
GENERAL NOTES
FAYETTE COUNTY, GEORGIA
NO SCALE
0 4/18/2025 ISSUED FOR BID TT
04.18.25 vandevee0123 Ellipse Sketch to Scale
0.03 sf
GENERAL:
STRUCTURAL QUALITY ASSURANCE PLAN
SOILS:
THIS STRUCTURAL QUALITY ASSURANCE PLAN IDENTIFIES THE RESPONSIBILITIES OF THE
CONTRACTOR AND THE SPECIAL INSPECTOR IN PERFORMING THE TESTING AND INSPECTION OF
THE WORK REQUIRED BY CHAPTER 17 OF THE BUILDING CODE THAT IS WITHIN THE SCOPE OF THE
STRUCTURAL ENGINEERING SERVICES FOR THIS PROJECT. REFER TO OTHER PORTIONS OF THE
CONSTRUCTION DOCUMENTS FOR TESTING AND INSPECTIONS REQUIRED OF MECHANICAL,
ELECTRICAL, CIVIL, OR OTHER BUILDING COMPONENTS.
CONTRACTOR'S RESPONSIBILITIES:
CONTRACTOR IS RESPONSIBLE FOR THE CONSTRUCTION OF A WIND OR SEISMIC FORCE
RESISTING SYSTEM/COMPONENT LISTED IN THE "STATEMENT OF SPECIAL INSPECTION" AND SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE BUILDING OFFICIAL AND THE OWNER
PRIOR TO THE COMMENCEMENT OF WORK ON SUCH SYSTEM OR COMPONENT PER SECTION 1704.4
OF THE IBC 2018 EDITION. CONTRACTOR SHALL GIVE 48 HOURS ADVANCED NOTICE FOR ALL
REQUIRED INSPECTIONS.
SPECIAL INSPECTOR'S RESPONSIBILITIES:
THE SPECIAL INSPECTOR SHALL BE A LICENSED ENGINEER IN THE STATE OF GEORGIA OR
PERFORMING APPROPRIATE DUTIES DIRECTLY UNDER THE SUPERVISION OF A LICENSED
PROFESSIONAL ENGINEER IN THE STATE OF GEORGIA AND HAVE A THOROUGH UNDERSTANDING OF THE SPECIAL INSPECTION REQUIREMENTS OF THE 2018 IBC. THE SPECIAL INSPECTOR SHALL BE AN INDIVIDUAL OR INDIVIDUALS CERTIFIED OR EXPERIENCED TO PERFORM SUCH INSPECTIONS IN
A PARTICULAR FIELD.
THE SPECIAL INSPECTOR SHALL KEEP RECORDS OF ALL INSPECTIONS AND FURNISH REPORTS TO
THE BUILDING OFFICIAL AND TO THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE
CHARGE. PERIODIC REPORTS SHALL BE PROVIDED AND SHALL INDICATE THAT WORK INSPECTED
WAS DONE IN CONFORMANCE WITH APPROVED CONSTRUCTION DOCUMENTS. DISCREPANCIES
SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF
THE DISCREPANCIES ARE NOT CORRECTED TO THE SATISFACTION OF THE SPECIAL INSPECTOR, THE DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE BUILDING
OFFICIAL AND TO THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE PRIOR TO
THE COMPLETION OF THAT PHASE WORK.
A WEEKLY REPORT OF INSPECTIONS DOCUMENTING REQUIRED SPECIAL INSPECTIONS AND
CORRECTION OF ANY DISCREPANCIES NOTED IN THE INSPECTIONS SHALL BE SUBMITTED. AT THE COMPLETION OF THE SPECIAL INSPECTIONS, THE LICENSED PROFESSIONAL ENGINEER IN CHARGE
OF PERFORMING THE SPECIAL INSPECTION SHALL CERTIFY THE FINAL SPECIAL INSPECTION
REPORT AND AFFIX HIS/HER SEAL TO THE SPECIAL INSPECTOR'S FINAL REPORT. PROVIDE THREE
(3) COPIES OF THIS REPORT TO THE PROJECT ENGINEER.
CONTRACTOR SHALL PERFORM THE FOLLOWING:
1. SUBMIT TEST REPORTS FOR ENGINEERED FILL. CONTRACTOR TO COORDINATE BUILDING
DEPARTMENT INSPECTIONS AND SPECIAL INSPECTIONS.
INSPECTOR SHALL PERFORM THE FOLLOWING:
REQUIRED SPECIAL INSPECTION AND TESTS OF SOILS
TYPE C P
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS
ARE ADEQUATE TO ACHIEVE THE DESIGN BEARING
CAPACITY.
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER
DEPTH AND HAVE REACHED PROPER MATERIAL.
3. PERFORM CLASSIFICATION AND TESTING OF
COMPACTED FILL MATERIALS.
4. VERIFY USE OF PROPER MATERIALS, DENSITIES,
AND LIFT THICKNESS DURING PLACEMENT AND
COMPACTION OF COMPACTED FILL.
5. PRIOR TO PLACEMENT OF COMPACTED FILL,
INSPECT SUBGRADE AND VERIFY THAT SITE HAS
BEEN PREPARED PROPERLY.
X
X
X
X
X
C = CONTINUOUS SPECIAL INSPECTION
P = PERIODIC SPECIAL INSPECTION
CAST-IN-PLACE CONCRETE:
CONTRACTOR SHALL PERFORM THE FOLLOWING:
1. ESTABLISH CONCRETE MIX DESIGN PROPORTIONS PER ACI 318. SUBMIT THREE
COPIES OF THE CONCRETE MIX DESIGNS. INCLUDE THE FOLLOWING:
A. TYPE AND QUANTITIES OF MATERIALS
B. SLUMP
C. AIR CONTENT
D. FRESH UNIT WEIGHT
E. AGGREGATES SIEVE ANALYSIS
F. DESIGN COMPRESSIVE STRENGTH
G. LOCATION OF PLACEMENT IN STRUCTURE
H. METHOD OF PLACEMENT
I. METHOD OF CURING
J. SEVEN-DAY AND 28-DAY COMPRESSIVE STRENGTHS
2. SUBMIT CERTIFICATION FROM EACH MANUFACTURER OR SUPPLIER STATING THAT MATERIALS
MEET THE REQUIREMENTS OF THE SPECIFIED ASTM AND ACI STANDARDS.
3. SUBMIT CERTIFICATION THAT THE READY-MIXED CONCRETE PLANT COMPLIES WITH THE
REQUIREMENTS OF THE NATIONAL READY MIX CONCRETE ASSOCIATION.
TABLE 1705.6
C = CONTINUOUS SPECIAL INSPECTION P = PERIODIC SPECIAL INSPECTION
TABLE 1705.3
REQUIRED SPECIAL INSPECTIONS AND TESTS OF CONCRETE CONSTRUCTION
TYPE C P
REFERENCE
STANDARD IBC REFERENCE
1. INSPECT REINFORCEMENT, INCLUDING PRESTRESSING
TENDONS, AND VERIFY PLACEMENT.
ACI 318 Ch: 20, 25.2, 25.3, 26.6.1-26.6.3
1908.4-
2. REINFORCING…