2500185_Drawings (Issued For Bids 2025_0514).pdf
PDF 3 MB Posted
- Attached to
- Westfield Community Building Structural Repairs
- Solicitation number
- 2500185
- Issued by
- Wayne County, Warren City, Michigan
About this file
These are structural engineering drawings for the Westfield Community Building Structural Repairs project in Trenton, Michigan, issued for bidding on May 14, 2025, by the City of Trenton. The project documents detail comprehensive structural repair work for the community building, including removing and replacing the existing floor slab on grade, implementing chemical grout for slab leveling and void filling, repairing CMU wall cracks, installing Invisibeam reinforcing strips along interior walls, and adding lateral X-bracing to existing roof trusses. The project number is 2500185, and the drawings were prepared by Fishbeck engineering firm, located in Novi, Michigan.
The drawings provide detailed technical specifications for the repairs, including concrete reinforcement requirements, design loads, building code information, and specific installation methodologies. The project appears to be funded through municipal sources, with a focus on preserving and strengthening the existing community building's structural integrity. The technical documents specify precise repair techniques, such as using #6 rebar at 12" spacing for the new slab, installing 10 mil vapor barriers, using 2" high-load styrofoam insulation, and applying specific masonry repair techniques like tuckpointing and crack repair. The engineering drawings follow the 2021 Michigan Building Code and include comprehensive details on material specifications, connection methods, and structural reinforcement strategies.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2500185_Project Manual (Issued For Bids 2025_0514).pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Reviewer
Designer
Drawn By
Hard copy is intended to be 24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.
Manager
PROJECT NO.
SHEET NO.
© C o p y r i g h t 2025 A l l R i g h t s R e s e r v e d
PL
O
T
IN
FO
: Z
:\2
5\
5\ C
AD
\C
D \G
_G
1.
D W
G
L
AY
O U
T:
L
AY
O
U T1
D
AT
E:
/1
4/
T
IM
E:
0:
:2
AM
U
SE
R : B
BE
LL
ES
TR
I
R E V I S I O N S
NOT FOR
CONSTRUCTION
C ity o f T re nt on Tr en to n, M ic hi ga n
W es tfi el d C om m un ity
B ui ld in g St ru ct ur al
R ep ai rs
2500185
EHANSEN
G001
SMOORE
GELSAYED
CJOTTE
BUILDING CODE INFORMATION
VESTIBULE
ELEVATION, SECTION AND
DETAIL DESIGNATION
GRAPHIC SYMBOLS
SECTION CUT LINE ENLARGED DETAIL FRAME
INTERIOR ELEVATION TAG
A001
EXTERIOR ELEVATION TAG
ELEVATION TARGET
ELEVATION TAG
A201
ROOM NAME
AND NUMBER
DOOR NUMBER
DEMOLITION NOTE TAG
FINISH TAG
SIGNAGE TAG
KEY NOTE TAGWALL TYPE TAG
BARRIER FREE LOCATION
BULLETIN IDENTIFICATION
ADDENDUM IDENTIFICATION
SKETCH IDENTIFICATION
A501 1 SECTION
PLAN DESIGNATION
FLOOR PLAN
NORTH
NORTH ARROW
DESIGNATION
SHEET INDEX
G001 TITLE SHEET
City of Trenton Westfield Community Buidling
Trenton, Michigan Issued for Bids - May 14, 2025
Project Number 2500185 fishbeck.com 248.324.2090
39500 MacKenzie Drive, Suite 100 Novi, Michigan 48377
S102 LATERAL BRACING DETAILS
LOCATION PLAN
S002 NOTES AND DETAILS
S101 SLAB REPLACEMENT DETAILS
Structural Repairs
5/14/2025 BIDS
5/14/2025
S001
SCHEDULES / DIAGRAMS
CONCRETE REINFORCEMENT COVER
REQUIREMENTS
CONCRETE CAST AGAINST PERMANENTLY EXPOSED TO EARTH:
ALL
CONCRETE EXPOSED TO EARTH OR WEATHER:
NO. 5 BAR AND SMALLER:
NO. 6 BAR AND LARGER:
1 1/2" 2"
3"
3/4" 1 1/2"
1 1/2"
BEAMS, COLUMNS:
PRIMARY REINFORCEMENT,
TIES, STIRRUPS, SPIRALS:
CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH EARTH:
SLABS, WALLS, JOISTS:
NO. 11 BAR AND SMALLER:
NO. 14 BAR AND LARGER:
STRUCTURAL NOTES
LEGENDS
GENERAL NOTES: CAST-IN-PLACE CONCRETE NOTES:
CONCRETE BLOCK MASONRY NOTES:
CONCRETE LEGEND:
SOIL AND FOUNDATION NOTES:
BPX
PX
FX
BASEPLATE DESIGNATION, REFER TO BASEPLATE SCHEDULE.
TAG IS PLACED AT LEVEL CORRESPONDING TO THE BOTTOM
OF THE COLUMN.
PIER DESIGNATION, REFER TO PIER SCHEDULE.
SPREAD FOOTING DESIGNATION, REFER TO SPREAD
FOOTING SCHEDULE.
CJ CONSTRUCTION OR CONTROL JOINT, REFER TO TYPICAL DETAILS.
WSJ WATERSTOP CONSTRUCTION JOINT, REFER TO TYPICAL DETAIL.
* FOOTINGS MARKED THUS " * " REQUIRE INDICATED
REINFORCEMENT IN TOP AND BOTTOM OF FOOTING.
STEP FOOTING, REFER TO TYPICAL DETAIL.SF
1. INFORMATION ON THIS SHEET APPLIES TO ALL STRUCTURAL
SHEETS.
2. INFORMATION ON THIS SHEET SUPPLEMENTS THE PROJECT
SPECIFICATIONS, REFER TO THE PROJECT SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS.
3. DRAWINGS HAVE NOT NECESSARILY BEEN ORGANIZED
ACCORDING TO TRADES. A FULL SET OF DESIGN DRAWINGS MAY
BE REQUIRED FOR AN INDIVIDUAL TRADE TO DETERMINE THE FULL
SCOPE OF WORK, REFER TO OTHER DISCIPLINES' DRAWINGS FOR
OTHER ELEMENTS OF STRUCTURAL CONSTRUCTION.
4. DRAWINGS HAVE BEEN SET UP TO PLOT AS INTENDED WHEN
PLOTTED AS FULL SIZE. USE REDUCED SIZE DRAWINGS AT YOUR
OWN RISK.
5. COORDINATE WORK OF TRADES. NOTIFY ENGINEER OF
VARIANCES BEFORE WORK BEGINS.
6. OBTAIN ENGINEER'S REVIEW PRIOR TO MAKING ALTERATIONS TO
A STRUCTURAL ITEM OR MEMBER NOT INDICATED ON THE
DRAWINGS.
7. DO NOT SCALE DRAWINGS TO OBTAIN DIMENSIONS NOT
INDICATED.
8. FIELD VERIFY EXISTING CONDITIONS.
9. ALL KEYNOTES ON A DRAWING MAY NOT APPLY TO THAT
DRAWING.
1. FOUNDATION DESIGN IS BASED ON THE RECOMMENDATIONS
MADE IN THE GEOTECHNICAL REPORT PREPARED BY FK
ENGINEERING AND DATED MARCH 2025.
2. BRACE FOUNDATION WALLS THAT RETAIN EARTH AGAINST
UNBALANCED BACKFILL PRESSURES UNTIL FLOORS AT TOP AND
BOTTOM ARE IN PLACE.
1. COORDINATE SIZE, LOCATION AND PLACEMENT OF EMBEDDED ITEMS
SUCH AS PLATES, HARDWARE AND PIPE SLEEVES WITH RESPECTIVE
TRADES.
2. SECURELY PLACE EMBEDDED ITEMS PRIOR TO PLACING CONCRETE.
3. DO NOT CORE OR CUT CONCRETE UNLESS REVIEWED BY ENGINEER.
4. WHERE DRILLING OR CUTTING INTO HARDENED CONCRETE IS
REQUIRED, FIELD LOCATE REINFORCEMENT WITH A REINFORCING
BAR DETECTOR TO AVOID DAMAGING THE REINFORCING BAR.
5. DO NOT SAW CUT ELEVATED FLOOR SLABS.
6. SUBMIT LOCATIONS OF CONSTRUCTION OR CONTROL JOINTS, OTHER
THAN INDICATED ON THE DRAWINGS TO THE ENGINEER FOR REVIEW
PRIOR TO PLACING CONCRETE.
7. PROVIDE CORNER BARS OF THE SAME SIZE AND SPACING AS
HORIZONTAL WALL REINFORCING FOR WALLS UNLESS NOTED
OTHERWISE.
8. PROVIDE CLEAR COVER TO REINFORCING BARS AS SCHEDULED,
UNLESS NOTED OTHERWISE. REFER TO SCHEDULE THIS SHEET.
9. PROVIDE MINIMUM LAP SPLICE LENGTH, IN INCHES, SHALL BE AS
SCHEDULED, UNLESS NOTED OTHERWISE. REFER TO SCHEDULE THIS
SHEET.
10. PROVIDE ADDITIONAL REINFORCING AROUND THE PERIMETER OF
OPENINGS IN SLABS AND WALLS, REFER TO TYPICAL DETAILS.
11. MIXING, BATCHING, TRANSPORTING, AND PLACING OF ALL CONCRETE
AND SELECTION OF CONCRETE MATERIALS SHALL CONFORM TO ACI
301 SPECIFICATION FOR STRUCTURAL CONCRETE FOR BUILDINGS,
UNO.
12. EACH MIX DESIGN LISTED BELOW SHALL BE SUBMITTED, WITH
CURRENT SUPPORTING DATA, AND BE APPROVED BY
ARCHITECT/STRUCTURAL ENGINEER AND THE TESTING LABORATORY
PRIOR TO USE. CONCRETE MIX DESIGNS SHALL BE STAMPED AND
SIGNED BY A CIVIL OR STRUCTURAL ENGINEER LICENSED IN THE
STATE OF MICHIGAN. SUBMITTAL SHALL INCLUDE THE FOLLOWING:
A. CEMENT TYPE AND SOURCE.
B. CEMENT CUBE STRENGTH.
C. COURSE AND FINE AGGREGATE SOURCE AND GRADING.
D. ADMIXTURE DATA SHEETS.
13. USE OF CALCIUM CHLORIDE, CHLORIDE IONS OR OTHER SALTS IN
CONCRETE MIX IS PROHIBITED.
14. THE SCHEDULE BELOW INDICATES THE MINIMUM CONCRETE DESIGN
MIX REQUIREMENTS. SOME DESIGN MIX PROPERTIES MAY NEED TO
EXCEED MINIMUM REQUIREMENTS IN ORDER TO MAKE OTHER
PROPERTIES MEET MINIMUM REQUIREMENTS.
A. TYPE C - SLAB-ON-GRADE (INCLUDING CURBS AND PADS)
• NORMAL WEIGHT CONCRETE (150 PCF)
• STRENGTH - F’C = 4000 PSI (AT 28 DAYS)
• MAX W/C RATIO = 0.40
• FLYASH / CEMENT RATIO = 50 PERCENT
• SHRINKAGE LIMIT = 0.040%
15. CONCRETE EXPOSED TO FREEZE/THAW CYCLES INCLUDING
FOUNDATION WALLS SHALL BE AIR-ENTRAINED 6% +/- 1%.
16. MINIMUM CONCRETE COVER OVER REINFORCING STEEL SHALL BE AS
FOLLOWS (UNO):
A. SLAB ON GRADE – 3” FROM BOTTOM
ABBREVIATIONS
AFF ABOVE FINISHED FLOOR
ADJ. ADJUSTABLE
AHU AIR HANDLING UNIT
ALT. ALTERNATE
AL. ALUMINUM
AB ANCHOR BOLT
APPROX. APPROXIMATE
ARCH. ARCHITECT
BSMT. BASEMENT
BRG. BEARING
BIT. BITUMINOUS
BOT. BOTTOM
BOD BOTTOM OF DECK
BOF BOTTOM OF FOOTING
CLG. CEILING
CTR. CENTER
CL CENTERLINE
CO. CLEAN OUT
COL. COLUMN
CONC. CONCRETE
CONN. CONNECTION
CMU CONCRETE MASONRY UNIT
CONST. CONSTRUCTION
CJ CONSTRUCTION JOINT
CONT. CONTINUOUS
CJ CONTROL JOINT
COORD. COORDINATE
DEG. DEGREES
DEMO. DEMOLITION
DIA. DIAMETER
DIM. DIMENSION
DR. DOOR
DWL. DOWEL
DBL. DOUBLE
DN. DOWN
DWG. DRAWING
EA. EACH
EF EACH FACE
EW EACH WAY
EOS EDGE OF STEEL
EL. ELEVATION
EQ. EQUAL
EQUIP. EQUIPMENT
EF EXHAUST FAN
EXIST. EXISTING
EXP. EXPANSION
EJ EXPANSION JOINT
EXT. EXTERIOR
EIFS EXTERIOR INSULATION AND FINISH SYSTEM
FAB. FABRICATED
FF FAR FACE
FS FAR SIDE
FT. FEET
FRP FIBERGLASS REINFORCED PLASTIC
FIN. FINISH
FF FINISHED FLOOR
FLR. FLOOR
FD FLOOR DRAIN
FTG. FOOTING
FDN. FOUNDATION
FV FIELD VERIFY
GA. GAUGE
GALV. GALVANIZED
GC GENERAL CONTRACTOR
GEN. GENERATOR
GT. GROUT
HT. HEIGHT
HP HIGH POINT
HORIZ. HORIZONTAL
HEF HORIZONTAL EACH FACE
IN. INCHES
ID INSIDE DIAMETER
IF INSIDE FACE
INSUL. INSULATION
INV. INVERT
IE INVERT ELEVATION
LF LINEAL FEET
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LP LOW POINT
MH. MANHOLE
MFR. MANUFACTURER
MO MASONRY OPENING
MATRL. MATERIAL
MAX. MAXIMUM
MECH. MECHANICAL
MTL. METAL
MEZZ. MEZZANINE
MIN. MINIMUM
MISC. MISCELLANEOUS
NF NEAR FACE
NS NEAR SIDE
NOM. NOMINAL
NTS NOT TO SCALE
NO. NUMBER
OC ON CENTER
OPP. OPPOSITE
ORIG. ORIGINAL
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
PERF. PERFORATED
PERP. PERPENDICULAR
PL. PLATE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PREFAB. PREFABRICATED
PROP. PROPOSED
R. RADIUS
REF. REFERENCE
REINF. REINFORCING
REQD. REQUIRED
REV. REVISION
RD ROOF DRAIN
SCHED. SCHEDULE
SIM. SIMILAR
SQ. FT. SQUARE FOOT
SS STAINLESS STEEL
STD. STANDARD
STL. STEEL
SF STEP FOOTING
STRUC. STRUCTURAL
T & B TOP AND BOTTOM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOS TOP OF SLAB
TOS TOP OF STEEL
TOW TOP OF WALL
TYP. TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT. VERTICAL
VEF VERTICAL EACH FACE
VOL. VOLUME
WSJ WATER STOP JOINT
WT. WEIGHT
WWF WELDED WIRE FABRIC
WF WIDE FLANGE
W/ WITH
WD. WOOD
WP WORKPOINT
1. DESIGN AND CONSTRUCTION OF FORMWORK IS THE RESPONSIBILITY OF
THE CONTRACTOR AND SHALL BE IN CONFORMANCE WITH ACI 301.
2. THE CONTRACTOR SHALL DETERMINE THE NEED FOR SHORING AND RE-
SHORING. DESIGN AND CONSTRUCTION OF SHORING / RESHORING,
INCLUDING ANALYSIS OF THE STRUCTURE, IS THE RESPONSIBILITY OF
THE CONTRACTOR. SUBMIT PROPOSED SHORING AND RESHORING
PLANS, CONFORMING TO ACI 301, TO THE ENGINEER FOR RECORD ONLY.
3. ALL CONSTRUCTION JOINTS SHALL BE CONSTRUCTED IN ACCORDANCE
WITH THE TYPICAL CONSTRUCTION JOINT DETAILS SHOWN ON THE
STRUCTURAL DRAWINGS. ALL CONSTRUCTION JOINTS SHALL BE
COORDINATED AND CONSTRUCTED IN ACCORDANCE WITH
ARCHITECTURAL FINISHES AND TREATMENTS.
4. THE CONTRACTOR SHALL SUBMIT THE PROPOSED LOCATIONS OF
CONSTRUCTION JOINTS TO THE ARCHITECT/ENGINEER AND RECEIVE
APPROVAL PRIOR TO FABRICATION OF FORMWORK.
5. CLEAN AND ROUGHEN TO ¼” AMPLITUDE, ALL HORIZONTAL
CONSTRUCTION JOINT SURFACES AGAINST WHICH CONCRETE IS TO BE
PLACED. ALL CONSTRUCTION JOINTS SHALL BE WETTED AND STANDING
WATER REMOVED IMMEDIATELY BEFORE NEW CONCRETE IS PLACED.
6. FOR EXISTING CONCRETE, MECHANICALLY ROUGHEN TO ¼” AMPLITUDE,
CLEAN AND DE-GREASE EXISTING CONCRETE BEFORE PLACING
CONCRETE ADJACENT TO EXISTING CONCRETE. APPLY BONDING AGENT
PRIOR TO PLACING CONCRETE. BONDING AGENT SHALL BE
CEMENTITIOUS OR EPOXY-BASED BONDING AGENT APPROVED BY
STRUCTURAL ENGINEER.
7. PROVIDE WATER-STOPS IN ALL CONSTRUCTION JOINTS IN ELEMENTS
EXPOSED TO WEATHER, SOIL OR LIQUID ON ONE SIDE. REFER TO
ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
WATERPROOFING AND DAMP-PROOFING REQUIREMENTS.
8. JOINTS SHALL BE PREPARED AND SEALED WITH JOINT SEALANT.
1. MASONRY CONSTRUCTION SHALL BE IN ACCORDANCE WITH TMS 402.
2. COMPRESSIVE STRENGTH OF THE GROUT SHALL BE 2000 PSI. MAXIMUM
SIZE OF AGGREGATE IN GROUT SHALL BE PER CODE.
3. MORTAR SHALL CONFORM TO CODE WITH STRENGTH OF 2500 PSI.
4. F’M SHALL BE JUSTIFIED BY PRECONSTRUCTION PRISM TESTS AND PRISM
TESTS DURING CONSTRUCTION AS SPECIFIED IN CODE.
5. LAY ALL UNITS IN RUNNING BOND WITH FULLY MORTARED HEAD JOINTS
6. HORIZONTAL JOINT REINFORCING SHALL BE “LADDER TYPE” WITH W1.7
DIAMETER LONGITUDINAL BARS. PROVIDE 3/16 DIAMETER LONGITUDINAL
BARS AT WALLS BE BRICK VENEER.
7. PROVIDE MINIMUM #5 VERTICAL BARS AT 48” O.C. AND HORIZONTAL JOINT
REINFORCING AT 16” O.C. UNLESS INDICATED OTHERWISE ON DRAWINGS.
8. PROVIDED MINIMUM (2) #5 VERTICAL BARS ADDITIONAL AT EACH SIDE OF
OPENINGS OR CONTROL JOINT UNLESS NOTED OTHERWISE.
9. PIPES AND CONDUITS SHALL NOT BE EMBEDDED IN ANY MASONRY
UNLESS APPROVED BY ARCHITECT & STRUCTURAL ENGINEER.
CONCRETE FORMWORK AND JOINTS NOTES:
WOOD GENERAL NOTES:
1. PRE-DRILL LAG SCREWS TO 70% LAG SCREW SHANK
DIAMETER.
2. FASTEN ALL MEMBERS ACCORDING TO THE FASTENING
SCHEDULE ON THIS SHEET OR UNLESS NOTED OTHERWISE.
3. ALL PREFABRICATED METAL CONNECTORS AND HARDWARE
SPECIFIED ARE SIMPSON STRONG-TIE.
REFER TO DRAWINGS AND
SPECIFICATIONS AS TO WHETHER
OR NOT SAND CUSHION AND VAPOR
BARRIER ARE REQUIRED
CONCRETE SLAB ELEVATION,
THICKNESS AND REINFORCING NOTED
ON PLAN; 6x6-W1.4xW1.4 WWF, MINIMUM
REFER TO DRAWINGS AND
SPECIFICATIONS AS TO WHETHER
OR NOT SAND CUSHION AND VAPOR
BARRIER ARE REQUIRED
CONCRETE SLAB ELEVATION,
THICKNESS AND REINFORCING NOTED
ON PLAN; 6x6-W1.4xW1.4 WWF, MINIMUM
T
SAWCUT
T /4
FASTENING SCHEDULE
CONNECTION FASTENING LOCATION
TOP PLATE TO STUD (2) 16d END NAIL
STUD TO SOLE PLATE
(4) 8d
(2) 16d
TOENAIL
END NAIL
DOUBLE STUDS 16d @ 12" FACE NAIL
DOUBLE TOP PLATES
16d @ 12"
(8) 16d
FACE NAIL
LAP SPLICE
TOP PLATE LAPS AND INTERSECTIONS (2) 16d FACE NAIL
CONTINUOUS HEADER, TWO PIECES 16d @ 16" ALONG EA EDGE
RAFTER OR TRUSS TO PLATE (3) 8d TOENAIL
BUILT-UP CORNER STUDS 16d @ 24"
BUILT-UP GIRDER AND BEAMS 20d @ 32"
BLOCKING BETWEEN RAFTERS TO TOP
PLATE
(3) 8d TOENAIL
CONTINUOUS HEADER TO STUD (4) 8d TOENAIL
FACE NAIL TOP & BOT
STAGGERED ON OPP SIDES
ROOF RAFTER TO 2x RIDGE BEAM (2) 16d TOENAIL
FACE NAIL
Hard copy is intended to be 24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.
PROJECT NO.
Drawn By
Designer
Reviewer
Manager
P L O
T I N
F O
© C o p y r i g h t 2 0 2 5 A l l R i g h t s R e s e r v e d
R E V I S I O N S
C it y o f T re n to n
T re n to n M ic h ig a n
W e s tf ie ld
C o m m u n it y B u ild in g
S tr u c tu ra l R e p a ir s
03/31/2025 60% DESIGN TO CITY
SHEET NO.
NOT FOR
CONSTRUCTION
EHANSEN
2500185
05/02/2025 90% DESIGN TO CITY
05/14/2025 BIDS
C W o rk
\R e v it \2
S s m o o re V
M
.r v t
-M a y -2
:5
:1
S001
GELSAYED
TIMSMITH
SMOORE
WIND LOADS
BASIC WIND SPEED (3-SECOND GUST) 108 MPH
EXPOSURE (ALL DIRECTIONS) B
INTERNAL PRESSURE COEFFICIENT ±0.18
COMPONENTS AND CLADDING WALL PRESSURE 30 PSF
DESIGN LOADS
ROOF DEAD LOADS
ROOF TRUSSES AND SHEATHING AS CALCULATED
FLOOR DEAD LOAD
CONCRETE AS CALCULATED
LIVE LOADS
ROOF 20 PSF
REDUCTION PER CODE
SLAB ON GRADE 150 PSF
DESIGN DATA
BUILDING CODE 2021 MICHIGAN BUILDING CODE
RISK CATEGORY II
ALLOWABLE SOIL PRESSURE 3,000 PSF
DESIGN STRESSES
CONCRETE REINFORCING Fy = 60,000 PSI WELDED WIRE FABRIC Fy = 65,000 PSI
CONCRETE
FOUNDATION WALLS AND FOOTINGS f'c = 4,000 PSI INTERIOR SLABS f'c = 4,000 PSI
MASONRY f'm = 2,000 PSI
8 96 74 40 30
7 74 54 36 30
6 42 36 24 20
5 30 24 20 16
4 20 16 16 12
3 12 12 12 12
TOP BARS OTHERS TOP BARS OTHERS
BAR
SIZE
BEAMS & COLUMNS WALLS & SLABS
CONCRETE REINFORCEMENT
LAP SPLICE SCHEDULE (INCHES)
NO SCALE
SLAB ON GRADE FORMED CONSTRUCTION JOINT
NO SCALE
SLAB ON GRADE SAW CUT CONTROL JOINT
S101
S101
S101
S101
L6X3-1/2X1/2
L X
-1
/2 X
/2
L X
X
/2
L X
-1
/2 X
/2
L6X3-1/2X1/2
L X
-1
/2 X
/2
REMOVE EXISTING SLAB ON GRADE IN
AREA INDICATED.
REPLACE WITH 6" SLAB ON GRADE
REINFORCED WITH #6 @12" EACH WAY,
MID DEPTH, ON VAPOR BARRIER ON
STYROFOAM INSULATION ON 6"
ENGINEERED FILL COMPACTED TO 95%
DRY DENSITY.
SUGGESTED SAWCUT
PATTERN (TYP.)
S101
73'-4 3/8"
61'-2 3/8"
1'-8 3/8" (FV)
10'-5 5/8"
L X
-1
/2 X
/2
S101
S101
L X
-1
/2 X
/2
SAWCUT AT EXISTING
FOUNDATION (FV)
CHEMICAL GROUT FOR
SLAB LEVELING AND VOID
FILLING IN AREA
INDICATED. SEE DETAIL
ON THIS SHEET.
INSTALL INVISIBEAM
REINFORCING STRIPS BY
FORTRESS, AT 4'-0" OC
ALONG FULL LENGTH OF
INSIDE FACE OF THIS
WALL. APPLY PER MFG'S
RECOMMENDATIONS.
FIRST FLOOR
100' - 0"
1/2" THICK PREMOLDED EXPANSION
STRIP WITH BACKER ROD AND
CHEMICAL RESISTANT SEALANT
CONT. L6X3 1/2 - SEE PLAN
1 1/4"⌀ HAS V36 ANCHOR, HOT
DIPPED GALVANIZED, EMBED 10"
@ 3'-0"
NEW SLAB ON GRADE
SEE PLAN
10 MIL VAPOR BARRIER OVER
2" STYROFOAM
2" HIGH LOAD STYROFOAM
(TYP. @ SUPPORTS)
FIRST FLOOR
100' - 0"
1/2" THICK PREMOLDED EXPANSION
STRIP WITH BACKER ROD AND
CHEMICAL RESISTANT SEALANT
CONT. L6X3 1/2 - SEE PLAN
1 1/4"⌀ HAS V36 ANCHOR, HOT
DIPPED GALVANIZED, EMBED 10"
@ 3'-0"
NEW SLAB ON GRADE
SEE PLAN
10 MIL VAPOR BARRIER OVER
2" STYROFOAM
2" HIGH LOAD STYROFOAM
(TYP. @ SUPPORTS)
CRACKS THROUGH EXIST. MORTAR
JOINTS TO BE GROUND OUT AND
TUCKPOINTED (SEE TUCKPOINTING
DETAILS)
EXIST. CRACK IN CMU.
SAW CUT EXISTING CRACK IN CMU
TO MINIMUM 2.5 TIMES THE DEPTH OF BLADE.
DO NOT EXCEED 1/2" WIDE. DO NOT
OVER CUT CMU. TUCKPOINT SAW
CUT JOINTS AT CRACK PER
APPROVED TUCKPOINTING
SPECIFICATIONS AND MOCKUPS.
STEP 1 STEP 2
STEP 4STEP 3
TOOL JOINT IN CONCAVE PROFILE
AFTER LAST LAYER OF MORTAR IS
"THUMBPRINT" HARD.
SECOND LAYER
CUT OUT MORTAR IN HEAD AND BED
JOINTS TO A MINIMUM UNIFORM DEPTH OF
3/4". REMOVE ADDITIONAL UNSOUND
MORTAR. REMOVE DUST AND DEBRIS
FROM THE JOINT BY BLOWING WITH AIR.
BRICK SURFACES MUST BE FREE OF
MORTAR OR OTHER RESIDUE BEFORE
POINTING.
DAMPEN JOINTS TO BE TUCKPOINTED. PACK MORTAR TIGHTLY INTO
THE JOINTS IN THREE LAYERS (1/4" MAXIMUM). EACH LAYER SHOULD
BECOME "THUMBPRINT" HARD BEFORE APPLYING NEXT LAYER.
WHERE STEEL IS PRESENT, PACK MORTAR AROUND STEEL.
O F
J O
IN
T
F U
L L W
ID
T
H
D
W D
1/4 IN
1/4 IN
SEALANT CHART
1/4 TO 1/2 IN
1/4 IN
W/21/2 TO 1 N
D
W
NEW BACKER ROD
AND SEALANT
1 1/4" MAX THICKNESS
1/2" MIN THICKNESS
M A
X
/2
M
IN
FIRST FLOOR
100' - 0"
L6X3 1/2 - SEE PLAN
1 1/4"⌀ HAS V36 ANCHOR, HOT
DIPPED GALVANIZED, EMBED 10"
@ 3'-0"
10 MIL VAPOR BARRIER OVER
2" STYROFOAM
℄ JOINT AND
SUPPORT ANGLE
L6X6 - SEE PLAN
ATTACH EACH END TO WALL
FOUNDATION W/ L4X4 CLIP
2" HIGH LOAD STYROFOAM
(TYP. @ SUPPORTS)
6" 6"
EXISTING SLAB ON GRADE
SAWCUT EXISTING SLAB#4 @12"
(2) #4 CONT.
DRILL HOLES THROUGH EXISTING SLAB TO INJECT
PRODUCT 'A' AND PROVIDE PRESSURE RELIEF
NO. AND SPACING OF GROUT PORTS BY
CONTRACTOR
PRODUCT LIST
'A' UNDERSLAB CHEMICAL PRIME RESINS PRIME FLEX 985 LX10
GROUT FILLER
Hard copy is intended to be 24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.
PROJECT NO.
Drawn By
Designer
Reviewer
Manager
P L O
T I N
F O
© C o p y r i g h t 2 0 2 5 A l l R i g h t s R e s e r v e d
R E V I S I O N S
C it y o f T re n to n
T re n to n M ic h ig a n
W e s tf ie ld
C o m m u n it y B u ild in g
S tr u c tu ra l R e p a ir s
03/31/2025 60% DESIGN TO CITY
SHEET NO.
NOT FOR
CONSTRUCTION
EHANSEN
2500185
05/02/2025 90% DESIGN TO CITY
05/14/2025 BIDS
C W o rk
\R e v it \2
S s m o o re V
M
.r v t
-M a y -2
:5
:1
S101
GELSAYED
TIMSMITH
SMOORE
NORTH
SCALE: 3/16" = 1'-0"
PARTIAL FIRST FLOOR PLAN
SCALE: 3/4" = 1'-0"
DETAIL
SCALE: 3/4" = 1'-0"
DETAIL
SCALE: 3/4" = 1'-0"
SEALANT JOINT GUIDELINES
SCALE: 1 1/2" = 1'-0"
CMU CRACK REPAIR
SCALE: 3/4" = 1'-0"
TYPICAL BUTT SEALANT JOINT
SCALE: 3/4" = 1'-0"
MASONRY TUCK POINTING DETAIL
SCALE: 3/4" = 1'-0"
DETAIL
SCALE: 3/4" = 1'-0"
DETAIL
SCALE: 1 1/2" = 1'-0"
SLAB VOIDS REPAIR
KEY NOTES
1 STEPPED MASONRY CRACKS OBSERVED ON WEST FACE OF
PARTITION WALL. FIELD VERIFY EXISTING CRACKS AND
QUANTIFY REPAIRS BASED ON REPAIR DETAILS 4, 7, 8, AND 9.
2 FIELD VERIFY CRACKING OF EAST FACE OF EXTERIOR WALL
FOR REPAIRS 4, 7,8, AND 9. REPAIR PER OWNER'S
DISCRETION.
S102
EXISTING 8" CMU +
BRICK WALL
EXISTING 8" CMU WALL
EXISTING SCISSOR
TRUSSES @ 24"
S102
S102
TRUSS BEARING
110' - 4 1/4"
EXISTING ROOF
TRUSSES @ 24"
EXISTING 8" CMU + BRICK WALL
2 PLY 2X4
F V
F V
SIMPSON A34
CONNECTOR (TYP)
2X6
2X6
X
X
2X6
TRUSS BEARING
110' - 4 1/4"
EXISTING 8" CMU + BRICK WALL
EXISTING 8" CMU WALL
2X6
2X6
EXISTING ROOF
TRUSSES @ 24"
SIMPSON A34
CONNECTOR (TYP)
2 PLY 2X4 (TYP)
NEW 2X4 SILL PLATE
FASTEN TO CMU WEBS OR FACESHELLS WITH
TAPCON HD 5/16" AT 24" OC
X
X
F V
F V
2X4 SILL PLATE
W/ TAPCON 5/16"⌀ ANCHORS
@ 24"
FIRST FLOOR
100' - 0"
TRUSS BEARING
110' - 4 1/4"
INSTALL INVISIBEAM
REINFORCING STRIPS BY
FORTRESS, AT 4'-0" OC
ALONG FULL LENGTH OF
INSIDE FACE OF THIS
WALL. APPLY PER MFG'S
RECOMMENDATIONS.
EXTEND STRIPS OVER
TOP OF CMU AND
ANCHOR TO TRUSS PER
MANUFACTURER'S
RECOMMENDATIONS
(TYP).
EXISTING CMU WALL
TYP.
4'-0"
Hard copy is intended to be 24"x36" when plotted. Scale(s) indicated and graphic quality may not be accurate for any other size.
PROJECT NO.
Drawn By
Designer
Reviewer
Manager
P L O
T I N
F O
© C o p y r i g h t 2 0 2 5 A l l R i g h t s R e s e r v e d
R E V I S I O N S
C it y o f T re n to n
T re n to n M ic h ig a n
W e s tf ie ld
C o m m u n it y B u ild in g
S tr u c tu ra l R e p a ir s
03/31/2025 60% DESIGN TO CITY
SHEET NO.
NOT FOR
CONSTRUCTION
EHANSEN
2500185
05/02/2025 90% DESIGN TO CITY
05/14/2025 BIDS
C W o rk
\R e v it \2
S s m o o re V
M
.r v t
-M a y -2
:5
:1
S102
GELSAYED
TIMSMITH
SMOORE
NORTH
SCALE: 3/16" = 1'-0"
PARTIAL ROOF PLAN AT TRUSS BEARING
SCALE: 3/4" = 1'-0"
SECTION
SCALE: 3/4" = 1'-0"
SECTION
NO SCALE
TOP OF INTERIOR WALL
NO SCALE
TOP OF EXTERIOR WALL
SCALE: 1/4" = 1'-0"
ELEVATION
| G0012500185_G001 |
| 2024_S_2500185_smooreV86M9 - Sheet - S001 - GENERAL NOTES SCHEDULES & LEGENDS |
| 2024_S_2500185_smooreV86M9 - Sheet - S101 - PLAN AND DETAILS |
| 2024_S_2500185_smooreV86M9 - Sheet - S102 - PLAN AND DETAILS |