2490-2-M-09SEP25.pdf
PDF 240 KB Posted
- Solicitation number
- 10474262-03-26
- Issued by
- Lee County, North Carolina
About this file
This mechanical engineering document is for Lee County Courthouse and Jail, detailing a chiller replacement project prepared by Eubanks Humphrey Engineering. The project scope involves removing and replacing one 125-ton chiller (Chiller #2) with a new packaged chiller (ACC-2), including replacement of associated isolating valves, flow regulating valves, flow measuring devices, pressure tapping, flow switches, and flanged connections. The replacement requires interfacing the new chillers with existing automated controls and verifying existing component quantities and characteristics in the field.
The mechanical specifications outline comprehensive requirements for the HVAC system installation, including using new and unused materials, conforming to North Carolina Building Codes, and providing a two-year warranty on materials, equipment, and workmanship (with a five-year extended guarantee on refrigeration compressors). The project involves two air-cooled chillers (ACC-1 and ACC-2) from York, each with specific performance data including refrigerant type (R-454B), electrical specifications, and operating parameters. The contractor is responsible for re-insulating exposed piping, providing documentation such as operation and maintenance manuals, and creating record drawings upon project completion.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Lee County Chill 2 Bid Package.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL SPECIFICATIONS
THE WORK INCLUDES PROVIDING MATERIALS, FITTINGS AND ACCESSORIES NECESSARY FOR A COMPLETE FUNCTIONING HVAC SYSTEM. ALL
MATERIALS FURNISHED BY THE CONTRACTOR SHALL BE NEW AND UNUSED AND FREE FROM DEFECTS. ANY ITEM NOT SPECIFICALLY SHOWN ON
THE DRAWINGS OR CALLED FOR IN THE SPECIFICATIONS, BUT THAT IS NORMALLY REQUIRED TO CONFORM TO THE INTENT, ARE TO BE
CONSIDERED A PART OF THE CONTRACT. THE WORK MAY ALSO INCLUDE ROUGH-IN AND FINAL CONNECTIONS TO EQUIPMENT PROVIDED BY
OTHERS. ALL WORK SHALL BE IN ACCORDANCE WITH LOCAL CODES AND/OR ORDINANCES AND IS SUBJECT TO INSPECTION.
PROVIDE EQUIPMENT INDICATED ON THE DRAWINGS, AND AS REQUIRED FOR A COMPLETE FUNCTIONING SYSTEM. INSTALL ALL HVAC EQUIPMENT
AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
ALL HVAC WORK SHALL CONFORM TO THE REQUIREMENTS OF THE LATEST ADOPTED EDITIONS OF THE NORTH CAROLINA BUILDING CODES.
INCLUDE PERMITS AND INSPECTION FEES IN CONTRACT.
THE INTENT OF THE DRAWINGS IS TO INDICATE THE GENERAL EXTENT OF WORK REQUIRED FOR THE PROJECT. THE DRAWINGS FOR MECHANICAL
WORK ARE DIAGRAMMATIC, SHOWING THE LOCATION, TYPE, DEVICES AND EQUIPMENT REQUIRED. THE DRAWINGS SHALL NOT BE SCALED FOR
EXACT MEASUREMENTS. PROVIDE ALL EQUIPMENT, DEVICES, ACCESSORIES, DUCTWORK, OFFSETS, TRANSITIONS, MATERIALS, ETC. NECESSARY TO
FACILITATE THE SYSTEM'S FUNCTIONING AS INDICATED BY THE DESIGN AND THE EQUIPMENT FURNISHED BY OTHERS.
DEFINITIONS: FURNISH MEANS TO SUPPLY AND DELIVER TO PROJECT SITE, READY FOR INSTALLATION. INSTALL MEANS TO PLACE IN POSITION
AND MAKE CONNECTIONS FOR SERVICE OR USE. PROVIDE MEANS TO FURNISH AND INSTALL, COMPLETE AND READY FOR INTENDED USE.
WARRANTY: GUARANTEE ALL MATERIALS, EQUIPMENT AND WORKMANSHIP FOR TWO YEARS FROM THE DATE OF FINAL ACCEPTANCE BY OWNER
AS STATED IN WRITING, EXCEPT REFRIGERATION COMPRESSORS WHICH SHALL HAVE A FIVE YEAR EXTENDED GUARANTEE. REPAIR AND/OR
REPLACE, WITHOUT ANY COST TO THE OWNER, ANY DEFECTIVE PART OR PARTS OF THE WORK WITHIN THE GUARANTEE PERIOD FROM THE TIME
THE SYSTEM IS PUT INTO OPERATION AS DETERMINED BY THE DATE OF FINAL CERTIFICATE OF PAYMENT WITH EXCEPTIONS AS NOTED.
PROVIDE OPERATION MANUALS, MAINTENANCE MANUALS AND SCHEMATICS FOR ALL MECHANICAL EQUIPMENT INSTALLED.
MAINTAIN A SOLELY DEDICATED DRAWING SET FOR RECORD DRAWING PURPOSES. RECORD CHANGES AS THEY OCCUR ON THIS SET, CLEARLY
AND PROFESSIONALLY. PROVIDE AS BUILT DRAWINGS TO OWNER UPON COMPLETION OF WORK.
CONTRACTOR SHALL AQUIRE A FULL UNDERSTANDING OF PHASING REQUIREMENTS FOR THIS PROJECT PRIOR TO BID. COORDINATE ALL PHASING
REQUIREMENTS WITH G.C. AND OWNER.
OR DEVICE APPEARING ON THIS LEGEND.
HVAC PLAN SYMBOLS
NOTE: THIS PROJECT MAY NOT USE EVERY SYMBOL
HVAC ABBREVIATIONS
ABV ABOVE
AD DUCT ACCESS DOOR
BDD BACK-DRAFT-DAMPER
CD CEILING DIFFUSER
CFM CUBIC FEET/MINUTE
CWS CHILLED WATER SUPPLY
CWR CHILLED WATER RETURN
COMP COMPRESSOR
DMPR DAMPER
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EG EXHAUST GRILLE
ER EXHAUST REGISTER
EVAP EVAPORATOR
FRAG FILTERED RETURN AIR GRILLE
FD FIRE DAMPER, PER ASSEMBLY RATING
FOB FLAT ON BOTTOM DUCT TRANSITION
FOT FLAT ON TOP DUCT TRANSITION
GC GENERAL CONTRACTOR
PC PLUMBING CONTRACTOR
PDD PERFORATED FACE DIRECTIONAL DIFFUSER
RAD RETURN-AIR DUCT
RAG RETURN AIR GRILLE
RAR RETURN AIR REGISTER
RCD ROUND CEILING DIFFUSER
RDR ROUND DUCT REGISTER
RH RADIANT HEATER
RTS ROUND TO SQUARE DUCT TRANSITION
RTU ROOFTOP HVAC UNIT
T'STAT THERMOSTAT
2024 APPENDIX B
BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS
MECHANICAL design mechanical summary
MECHANICAL SYSTEMS, SERVICE SYSTEMS AND EQUIPMENT
Thermal Zone winter dry bulb: ___________ summer dry bulb: ___________
Interior design conditions winter dry bulb: ___________ summer dry bulb: ___________ relative humidity: ___________
Building heating load: ___________
Building cooling load: ___________
Mechanical Spacing Conditioning System Unitary description of unit: ___________ heating efficiency: ___________ cooling efficiency: ___________ size category of unit: ___________
Boiler Size category. If oversized, state reason.: ___________
Chiller Size category. If oversized, state reason.: ___________
List equipment efficiencies: ___________
EXISTING
EXISTING
SEE SCHEDULE(S)
18° F
91.5° F
68° F
75° F
50%
SEE SCHEDULE(S)
SEE SCHEDULE(S)
SEE SCHEDULE(S)
SEE SCHEDULE(S)
6" CONCRETE PAD
ELECTRICAL
ROOM
460V, 3PH, 600 AMP
PANEL
EXISTING
EXISTING
EVAPORATOR
PUMP PKG
CWS
22'-10i"
7'-9"
EXISTING
6" CWS
EXISTING
6" CWR
RLAQTY.
COMPRESSOR DATA
AMBIENT EAT(°FDB)
CONDENSER DATA
DESIGN
(FT.WG)
(°F)
FLOW
(TONS)
CAPACITY
NET
AIR-COOLED CHILLER SCHEDULE
LOW
EVAPORATOR DATA
MAX.WPDLWT
(°F)
EWT
(TONS)
CAPACITY
OPERATING
EER
PERFORMANCE DATA
NPLV.IP (GPM)
FACTOR
FOULING
FLUID LRA STARTER
QTY.
FAN
FLA
FAN
ELECTRICAL DATA
VOLTAGE MCA MOCP
UNIT (SINGLE POINT) CONTROL CIRCUIT HEATER CIRCUIT
VOLTAGE KW VOLTAGE KW
MODEL NO.
MANUFACTURER &
MARK
53.14
29.1
48125
58118.2 10.48 17.89 300.8
0.0001 WATER 316 ALS
6 4.0 460/60/3 263 300 120V 0.5 NA NA
YORK YLAA0120SJ46XFBACC-1
REF
R-454B
OPERATING
WEIGHT(LBS)
6" CONCRETE PAD
ELECTRICAL
ROOM
460V, 3PH, 600 AMP
PANEL
EXISTING
EXISTING
22'-10i"
7'-9"
EXISTING
6" CWS
EXISTING
6" CWR
10' MIN
6' MIN
6' MIN
SINGLE POINT POWER
CONNECTION.
EX ACC-1
NEW ACC-2
5"
5"
5"
6"
53.14
29.1
48125
58118.2 10.48 17.89 300.8
0.0001 WATER 316 ALS
6 4.0 460/60/3 263 300 120V 0.5 NA NA
YORK YLAA0120SJ46XFB
ACC-2
R-454B
INTERFACE NEW CHILLERS WITH EXISTING AUTOMATED CONTROLS.
ISOLATING VALVE - NORMALLY OPEN
ISOLATING VALVE - NORMALLY CLOSED
FLOW REGULATING VALVE
FLOW MEASUREMENT DEVICE
STRAINER
PRESSURE TAPPING
FLOW SWITCH
FLANGED CONNECTION
DEMOLITION PLAN
SCALE: 1/8" = 1'-0"
RENOVATION PLAN
SCALE: 1/8" = 1'-0"
AIR COOLED CHILLER
CHILLED WATER PIPING
TYPICAL EVAPORATOR PIPING CONNECTIONS
NO SCALE
E V A P O R A T O R
CHILLED LIQUID PIPING
HAND STOP VALVES ARE RECOMMENDED FOR USE IN ALL LINES TO
FACILITATE SERVICING.
DRAIN CONNECTIONS SHOULD BE PROVIDED AT ALL LOW POINTS
TO PERMIT COMPLETE DRAINAGE OF THE COOLER AND SYSTEM
PIPING.
THE COOLER MUST BE PROTECTED BY A STRAINER, PREFERABLY
OF 40 MESH, FITTED AS CLOSE AS POSSIBLE TO THE LIQUID INLET
CONNECTION, AND PROVIDED WITH A MEANS OF LOCAL ISOLATION.
THE COOLER MUST NOT BE EXPOSED TO FLUSHING VELOCITIES OR
DEBRIS RELEASED DURING FLUSHING. IT IS RECOMMENDED THAT A
SUITABLY SIZED BYPASS AND VALVE ARRANGEMENT IS INSTALLED
TO ALLOW FLUSHING OF THE PIPING SYSTEM. THE BYPASS CAN BE
USED DURING MAINTENANCE TO ISOLATE THE HEAT EXCHANGER OR
OTHER UNITS.
PRESSURE GAUGE CONNECTIONS ARE RECOMMENDED FOR
INSTALLATION IN THE INLET AND OUTLET WATER LINES. GAUGES
ARE NOT FURNISHED WITH THE UNIT AND ARE TO BE FURNISHED
BY OTHER SUPPLIERS.
THE CHILLED LIQUID LINES THAT ARE EXPOSED TO OUTDOOR
AMBIENTS SHOULD BE WRAPPED WITH A SUPPLEMENTAL HEATER
CABLE AND COVERED WITH INSULATION.
A FLOW SWITCH IS AVAILABLE AS AN ACCESSORY ON ALL UNITS.
THE FLOW SWITCH (OR ITS EQUIVALENT) MUST BE INSTALLED IN
THE LEAVING WATER PIPING OF THE COOLER.
PROVIDE SCHEDULED EQUIPMENT OR EQUAL BY:
1. TRANE
2. CARRIER
3. MCQUAY
NOTE: DISPOSITION OF EXISTING CHILLER SHALL BE COORDINATED WITH OWNER PRIOR
TO BEGINNING WORK. CONTRACTOR SHALL HAND OVER TO OWNER ANY EQUIPMENT
COMPONENTS, RE-CLAIMED R-410 REFRIGERANT OR ACCESSORIES REQUESTED.
VSD SINGLE
PUMP
(FT.WG)
REQ. ESP
20.0
20.0
(FT.WG)
AVAILABLE ESP
49.1
49.1
HP
7.5
7.5
HYDRO-KIT (NOT DEPICTED) – FACTORY INSTALLED HYDRO-KIT SUITABLE
FOR WATER GLYCOL SYSTEMS WITH UP TO 35% GLYCOL AT LEAVING
TEMPERATURES DOWN TO 20°F. THE HYDRO-KIT OPTION IS AVAILABLE IN
A SINGLE OR DUAL CONFIGURATION (DUAL AS STANDBY DUTY ONLY),
WITH TOTALLY ENCLOSED PERMANENTLY LUBRICATED PUMP MOTORS. THE
HYDRO-KIT OPTION COMES STANDARD WITH A BALANCING VALVE,
DISCHARGE CHECK VALVE, DISCHARGE SHUTOFF VALVE, THERMAL
DISPERSION FLOW SWITCH, PRESSURE PORTS, INLET WYE-STRAINER,
BLEED AND DRAIN VALVES AND FROST PROTECTION. SERVICE SHUT OFF
VALVES, ADDITIONAL PRESSURE PORTS AND EXPANSION TANKS ARE
OPTIONAL WITHIN THE HYDRO-KIT OPTION.
PUMP
KIT
PUMP
KIT
EXISTING
CHILLER #1
EXISTING
CHILLER #2
SCOPE OF WORK
REMOVAL AND REPLACEMENT OF (1) 125 TON CHILLER.
EXISTING CHILLER #2 TO BE REPLACED WITH NEW
PACKAGED CHILLER ACC-2.
CHILLER REPLACEMENT SHALL INCLUDE REPLACING ALL
ASSOCIATED ISOLATING VALVES (N.O. & N.C.), FLOW
REGULATING VALVE, FLOW MEASURING DEVICE, PRESSURE
TAPPING, FLOW SWITCH, AND FLANGED CONNECTIONS (IF
SHOWING PITTING OR WEAR). VERIFY EXISTING
COMPONENT QUANTITIES AND CHARACTERISTICS IN FIELD.
CONTRACTOR IS RESPONSIBLE FOR RE-INSULATING ALL
EXPOSED PIPING FROM VALVE REPLACEMENT OR ANY
OTHER DEVICE REPLACEMENT BACK TO ORIGINAL
CONDITION.
PROVIDE TEE AND ISOLATION VALVE FOR CONNECTION OF
BACK-UP CHILLER. PROVIDE ADDITIONAL CHILLER
ISOLATION VALVES IF NOT PROVIDED WITH PUMP
PACKAGE.
NOTE 1
NOTE 1
NOTE 1
ACC-1
5"
PUMP
KIT
6"
TO REMAIN
TO BE REPLACED
OF 1
M-1
SCALE: 1/8" = 1'-0"
REF. NORTH
MECHANICAL PLANS
SHEET NO.
ORIGINAL ISSUE DATE
JOB NO.
REVISIONS
2490-2
09SEP25
C 2025 EUBANKS HUMPHREY ENGINEERING, P.C.
WRITTEN CONSENT OF THE ENGINEER.
REPRODUCED IN PART OR IN WHOLE WITHOUT THE SPECIFIC
ARE PROTECTED UNDER COPYRIGHT LAWS AND MAY NOT BE
REMAIN THE PROPERTY OF THE ENGINEER. THESE DRAWINGS
THESE DRAWINGS ARE INSTRUMENTS OF SERVICE AND SHALL
BEH
DRAWN BY
H U
M
PH
R
EY
E U
B A
N K
S E
N G
IN
E
E R
IN
G
P.
C
Pa is le y
St
Su ite
Ph on e
.3
.0
G re en sb or o, N C
Fa x
.3
.0
R
E
E
N
I
G
N
E
S
L
A
N
O
I
S
E
F
O
R
P
ALSE
N
O
R
T
H
C
A
R
O
L
N
A
032588
B
R
Y
A
N
E
H
U
M
P
H
R
E
I
Y
FIRM LICENSE: C-2272
BEH
CHECKED BY
W I L S O N
L Y S I A K
I N C h t t p w w w w l e n g c o m
G R E E N S B O R O
N O R T H
C A R O L I N A
G R O O M E T O W N
R O A D
Z I P
C O D E
P H O N E
L E
E C
O U
N T
Y
C H
IL
L
E R
R E
PL
A
C M
E N
T F
O R
C O
U T
H O
U
SE
A N
D J
A
IL
File details come from the government source that posted it. Updated .