2419 Addendum 1.pdf
PDF 251 KB Posted
- Attached to
- Kenosha County Courthouse Ramp Renovation
- Solicitation number
- 2419
- Issued by
- Kenosha County, Kellnersville Village, Wisconsin
About this file
This document is an Addendum to the Kenosha Courthouse Ramp Remodel project being solicited by the County of Kenosha, Wisconsin. The addendum provides clarification on various aspects of the project, including the finish required on the stainless-steel ramp and landing rails, the scope of work on the existing railing system, the trench drain discharge pipe termination, and the ramp profile replacement. The addendum also addresses questions raised during the pre-bid walkthrough, such as the removal of existing steps, the chamfer on the new concrete cap, and the transition of the railing system. The project involves the demolition of the existing ramp and construction of a new ADA-accessible ramp, railing system, and trench drain at the Kenosha County Courthouse. Bids are due on September 18, 2024, at 3:00 pm local time.
The document does not provide any information on pricing terms, set-asides, incumbents, funding requirements or sources, or other salient financial details. It focuses solely on the technical aspects of the project and the clarifications provided in the addendum.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2419 Bid Documents.pdf | ||
| Vendor Responsibility Form Construction.pdf | ||
| 2419 Drawings.pdf.crdownload | CRDOWNLOAD file | |
| 2419 Specifications.pdf | ||
| RFQ 5335-0-2024-BG Thermal Imager.pdf | ||
| RSRT2025 QA.docx | DOCX document | |
| 2419 Drawings.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Kenosha Courthouse Ramp Remodel
ADDENDUM # 1
September 11, 2024
BIDS DUE: September 18, 2024 at 3:00pm Local Time by The County of Kenosha Purchasing Division 1010 56th Street, Second Floor Kenosha, WI 53140 at that time Bids will be opened publicly for consideration by the Owner.
To all Contract Bidders of record.
This Addendum is issued to modify, explain or correct the original Drawings and Specifications as noted below, and is hereby made a part of the Contract documents.
Please attach this Addendum to the Specifications in your possession. Acknowledge receipt of this Addendum in the space provided on the Bid Form. Failure to do so may subject Bidder to disqualification.
This Addendum consists of (2) written pages (1) Sign in sheet.
QUESTIONS AND ANSWERS
1. What type of finish is required on the stainless-steel ramp & landing rails? I did see something about removing paint before welding in the field but I’m not sure if they were talking about the rails or something else.
a. The complete railing system is stainless steel – no painted rails.
2. Is the L-shaped landing rail on the east end of the upper platform, getting replaced as well?
a. No, the east section of railing is not getting replaced.
3. I also saw something about the window wells being removed and replaced and noticed they have rails around them, do you need rail or grating for those new window wells?
a. There is no work on any window wells.
4. There’s a section of railing on the east side of the platform. Does that need to be replaced too?
a. No, that piece will remain as is.
5. The existing ramp has two sections of handrail that extend about 4 1/2 feet east of the ramp, are those required to be reinstalled?
a. The only section that needs to go back in is the southern extension. The northern one can be eliminated.
6. How should the trench drain discharge pipe be terminated on the east side?
a. The pipe should extend through the east wall 8 inches and 90 down to 6 inches off grade.
MFleming Typewritten Text Bid 2419
-2-
7. The project narrative talks about the trench strain work being done on a Saturday, is it possible to do it in sections during weekdays?
a. The trench drain can be done in sections but at all times either the east doors need to be accessible or the west pair of doors. Contractor will be required to remove the small section of glass wall at the interior vestibule during construction and reinstall it at completion. See the following photos.
8. Are we to replace the ramp profile as is, with the two flat landings?
a. Yes, the replacement of the ramp is matching the existing profile with the two flat landings.
9. At the pre-bid walk-through it was talked about at the location of the trench drain. The original old steps will be encountered during excavation. Scope of work should be planned as part of the bid.
a. The contractor should factor in having to remove enough depth of existing steps to get the new trench drain installed. The GC should assume the first step starts right under the trench drain location.
10. There is a chamfer where the existing concrete cap meets the foundation wall should the new concrete cap also have the camper where it meets the foundation wall chamfer?
a. Yes, the new ramp surface where it meets the foundation wall should be chamfered to match existing profile.
11. It was pointed out at the walk-through that the guard rail section of the ramp railing system stops at the first flat landing area and then transitions into just a handrail height section
a. Yes, as pointed out, the guard rail height section only needs to go as far as the current railing system, and then it turns into the handrail height, guard rail system for the remainder of the ramp.
12. We’re looking to get clarification on the railing material types: can we use a
3/4” x 1/4 inch flat bar right underneath the railing and 1/2“ twisted pickets and 3/4” main post; all those products would match the existing profiles.
a. Yes, the goal is to match the existing railing profiles as close as possible, including the profiles of the twisted pickets.