24024 - EC EOC - Bid Plans.pdf
PDF 10 MB Posted
- Attached to
- Interior Renovations for Edgecombe County Emergency Operations Center - 400 E Walnut Street, Tarboro, NC
- Solicitation number
- 322-24024
- Issued by
- Edgecombe County, North Carolina
About this file
This document is a set of bid plans related to a contract opportunity for interior renovations to the Edgecombe County Emergency Operations Center located at 400 E Walnut Street in Tarboro, North Carolina. The contract is being solicited by Edgecombe County, with a pre-bid meeting scheduled for August 13, 2024 at 10:00am at the EOC, and the bid opening taking place on August 27, 2024 at 3:00pm at the Edgecombe County Administration Building.
The contract involves providing interior renovation services for the Edgecombe County EOC facility. No additional details are provided regarding the specific scope of work, quantities, or contract term. The document does not contain information on pricing, funding sources, incumbent contractors, or any set-aside requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 24024 - EC EOC - Bid Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELEVATION VALUE
REFERENCE
DESCRIPTION
15' - 4"
AFF
A2-03
SHEET NO.
DETAIL NO.
A2-03
A2-03
CALLOUT DETAIL
SHEET NO.
DETAIL NO.
EXTERIOR ELEVATION MARK
INTERIOR ELEVATION MARK
SHEET NO.
DETAIL NO.
CONTROL / ELEVATION MARK
A2-03
DETAIL NO.
DRAWING NO.
SHEET NO.
1 View Name 1/8" = 1'-0"A101
SCALE
DRAWING NAME
SHEET NO.
BUILDING SECTION MARK
DEMO MARK#
XXX
XXXX
B1
EHD
Room name
101A
ROOM MARK
DOOR MARK
WINDOW MARK
CASEWORK MARK
REVISION AREA / NUMBER
WALL MARK
ACCESSORIES MARK
ROOM NO.
ROOM NAME
A2-03
DETAIL NO.
SHEET NO.
WALL SECTION MARK
CR CARD READER
@ AT
ACC ACCENT COLOR
ACOUS ACOUSTIC
ACT ACOUSTICAL CEILING TILE
ACW ACOUSTICAL WALL PANELS
AD AREA DRAIN
ADJ ADJUSTABLE
AE APPROVED EQUAL
AFF ABOVE FINISH FLOOR
AFL ATHLETIC FLOORING
AHU AIR HANDLING UNIT
ALUM ALUMINUM
ANOD ANODIZED
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
ATTEN ATTENUATION
AWP ACRYLIC WALL PANELS
BBT BIOBASED TILE
BF BLOCK FILL
BFC BROOMED FINISHED
CONCRETE
BL BLINDS
BLDG BUILDING
BLKG BLOCKING
BOT BOTTOM
BPG BULLET PROOF GLASS
CB CATCH BASIN
CEM CEMENTITIOUS SIDING
CF CORK FLOORING
CFT CERAMIC FLOOR TILE
CG CURVED CEILING GRID
CI CAST IRON
CI# CURB INLET
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
CONC CONCRETE
CONSTR CONSTRUCTION
CONTR CONTRACTOR
CORR CORRUGATED
CPT CARPET
CPTT CARPET TILE
CRC COLD ROLLED CHANNEL
CRF CORK RUBBER FLOORING
CS COUNTERSUNK
CSCI CONTRACTOR SUPPLIED,
CONTRACTOR INSTALLED
CTB CERAMIC TILE BASE
CW CURTAINWALL
CWT CERAMIC WALL TILE
DFP DRY FOG PAINT
DIA DIAMETER
DISP DISPENSER
DN DOWN
DP DEEP
DR DOOR
DS DOWNSPOUT
DTL DETAIL
EDG EDGE BANDING
EES EMERGENCY EYE WASH AND
SHOWER
EFC EPOXY FLOOR COATING
EIFS EXTERIOR INSULATION FINISH
SYSTEM
EIP EXISTING IRON PIPE
EJ EXPANSION JOINT
ELEV ELEVATION
EN ENAMEL
EPT HIGH PERFORMANCE
EPOXY PAINT
EQ EQUAL
ES EXPOSED STRUCTURE
EST EXISTING
EXP EXPOSED CEILING
EXT EXTERIOR
E/W EACH WAY
EWC ELECTRIC WATER COOLER
FC FIRECODE
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
SURFACE MOUNTED
FEC FIRE EXTINGUISHER
SEMI-RECESSED
FF FINISH FLOOR
FH FIRE HYDRANT
FLU FLUORESCENT
FOF FACE OF FRAME
FOM FACE OF MASONRY
FT FLOOR TILE
FTG FOOTING
FV FLOOD VENT
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GCT GRANITE COUNTERTOP
GEN GENERATOR
GFT GRANITE FLOOR TILE
GL GLASS
GMT GLASS MOSAIC TILE
GT GROUT
GWB GYPSUM WALL BOARD
GYP GYPSUM BOARD
HB HOSE BIB
HC HOLLOW CORE
HDC HANDICAP
HDWD HARDWOOD
HM HOLLOW METAL
HORZ HORIZONTAL
HR HOUR
ID INSIDE DIAMETER
IMP INSULATED METAL PANEL
INSTAL INSTALLATION
INSUL INSULATION
INT INTERIOR
INV INVERT
JB JOIST BEARING
JB# JUNCTION BOX
JT JOINT
L LONG
LFT LINOLEUM FLOOR TILE
LP LIGHT POLE
LST LINOLEUM SHEET
FLOORING
LVS LEAVES (DOOR)
LVT LUXURY VINYL TILE
MATL MATERIAL
MAX MAXIMUM
MB MASONRY - BRICK
MBL MARBLE
MC METAL CANOPY
MCT METAL CEILING TILE
MECH MECHANICAL
MFR MANUFACTURER
MFT MARBLE FLOOR TILE
MIN MINIMUM
MO MASONRY OPENING
MTB MARBLE TILE BASE
MTD MOUNTED
MTL METAL
MWM METAL WALK-OFF MAT
MWT MARBLE WALL TILE
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NOM NORMAL
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED,
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED,
OWNER INSTALLED
OPP OPPOSITE
OSC OVERFLOW SCUPPER
OZ OUNCE
P PAINT
PC POLISHED CONCRETE
PERF PERFORATED
PFT PORCELAIN FLOOR TILE
PIV POST INDICATOR VALVE
PL PLATE
P-LAM PLASTIC LAMINATE
P-LAM WD PLASTIC LAMINATE
WOOD DOORS
PLYWD PLYWOOD
PNT PAINT
POLYETH POLYETHYLENE
PP POWER POLE
PR PAIR
PTB PORCELAIN TILE BASE
PTD PAINTED
PTP PLASTIC TOILET
PARTITIONS
PWT PORCELAIN WALL TILE
PVC POLYVINYL CHLORIDE
QS QUARTZ SURFACE
QT QUARRY TILE
QZT QUARTZ TILE
R RADIUS
R&S ROD AND SHELF
RB RESILIENT BASE
RBT RUBBER TILE
RCP REINFORCED CONCRETE
RD ROOF DRAIN
RDL ROOF DRAIN LEADER
RECEPT RECEPTACLE
RECYF RECYCLED FLOORING
REQD REQUIRED
RES RESILIENT
RM RUBBER MAT
RO ROUGH OPENING
ROW RIGHT OF WAY
RSF RESINOUS FLOORING
RTF RESILIENT TILE FLOORING
SAT SPRAYED ACOUSTICAL
TREATMENT
SC SEALED CONCRETE
SCH SCHEDULE
SCW SOLID CORE WOOD
SDT STATIC DISSIPATIVE TILE
SF STOREFRONT
SHEATH SHEATHING
SIM SIMILAR
SP SPACES
SQ SQUARE
SQFT SQUARE FEET
SRT SLIP RESISTANT TILE
SS STAINLESS STEEL
SSC STAINED SEALED
CONCRETE
SSG STRUCTURAL SILICON GLAZING
SSM SOLID SURFACE
ST STEEL
ST&R STAIR TREADS AND RISERS
STD STANDARD
SUSP SUSPENDED
T&G TONGUE AND GROOVE
TB TILE BASE
TC TERRA COTTA
TCA TILE COUNCIL OF AMERICA
TELE TELEPHONE
TEMP TEMPERED
TEXD TEXTURED
TFT TERRAZZO FLOOR
TILE
TOC TOP OF CURB
TOS TOP OF STEEL
TP TELEPHONE POLE
TS TRANSITION STRIP
TV TELEVISION
TVB TELEVISION MOUNTING
BRACKET
TYP TYPICAL
UL UNDERWRITERS
LABORATORY
U/L UTILITY/LIGHTS
UNO UNLESS NOTED OTHERWISE
VACT VINYL ACOUSTICAL TILE
VB VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VWC VINYL WALL COVERING
W/ WITH
WC WATER CLOSET
WD WOOD
WF WOOD FLOORING
WT WALL TILE
WT* WALL TILE - SEE ELEVATION
WWF WELDED WIRE
FABRIC
WWM WELDED WIRE MESH
DISCIPLINE
G COVER
G CODE SUMMARY
G LIFE SAFETY
CE CIVIL
L LANDSCAPE
S STRUCTURAL
D DEMOLITION
A ARCHITECTURAL
Q EQUIPMENT
FP FIRE PROTECTION
P PLUMBING
M MECHANICAL
E ELECTRICAL
FA FIRE ALARM
X MISCELLANEOUS
PAGE NUMBERSECTION
0 GENERAL
1 PLANS
2 EXTERIOR ELEVATIONS
3 BUILDING / WALL SECTIONS
4 VERTICAL CIRCULATION
5 DETAILS
6 WINDOW & DOOR SCHEDULES
7 INTERIOR ELEV / CASEWORK
A1.01
APPLICABLE TO ARCHITECTURAL SHEETS ONLY
3221 BLUE RIDGE ROAD, SUITE 113
RALEIGH, NC 27612 PHONE: 919-571-1111
PLUMBING, MECHANICAL, & ELECTRICAL ENGINEER:
R O
CKY MOUN
T, N C
O A K L E Y
C O
LL
IER ARCHITE
C
T S P .A
CERT NO.
50681
R E
G
IS
T
E R
E
D
AR
CH I
TECTURA L
C
O
R
P
O
R A T I O
N
N O R TH C A RO
L I N A
TI
M
OT
HY
D. OAKLE
Y
R O
C
KY
MOUN
T, N .C
N
OR TH CAR
OL
IN
A
R
EG
IS
TE
RED ARCHITE
C T
Revisions
Date Project No.
Sheet No.Drawn By
Checked By
Sheet Title
C a n d le w o o d R o a d R o c ky M o u n t, N C
P
.9
.2
W e st M a rt in S tr e e t, R a le ig h N
C
P
.9
.7
C o p y ri g h t
O a k le y C o lli e r
A rc h it e c ts
T h e s e d ra w in g s a re o f th e p ro p e rt y o f th e A rc h it e c t fo r u s e u n d e r h is s u p e rv is io n N o r e p ro d u c ti o n o r o th e r u s e i s a llo w e d w it h o u t p e rm is s io n
O A
K
LE
Y C
O
LL
IE
R
A R
C H
IT
E C
TS
24024
G0.1
TDO
JHH
COVER SHEET
8/2/24
R E
N O
V A
T
IO
N S
F O
R
E D
G E
C O
M B
E C
O U
N T
Y E
M E
R G
E N
C Y
O P
E R
A T
IO
N
S C
E N
T E
R
T A
R B
O R
O N
O R
T H
C A
R O
L
IN
A
E
W A
L N
U T
S T
R E
E T
8/2/24
EDGECOMBE COUNTY EMERGENCY OPERATIONS CENTER
RENOVATIONS FOR
400 E WALNUT STREET
TARBORO, NORTH CAROLINA
INDEX OF DRAWINGSSYMBOL LEGEND SHEET NAMING LEGENDABBREVIATIONS
CONSULTANTS
G0.1 COVER SHEET
G0.2 BUILDING CODE SUMMARY - EXISTING EOC BUILDING
G0.3 BUILDING CODE SUMMARY - EXISTING (ARMORY) BUILDING
G1.1 LIFE SAFETY PLAN
D1.1 DEMOLITION PLAN
A1.1 FLOOR PLAN
A1.2 REFLECTED CEILING PLAN
A1.3 DOOR SCHEDULE
P0.1 PLUMBING NOTES, LEGEND, FIXTURE SCHEDULE
P1.1 PLUMBING PLAN
M0.1 MECHANICAL NOTES, LEGEND, SCHEDULES, DETAILS
MD1.1 MECHANICAL DEMOLITION PLAN
M1.1 MECHANICAL RENOVATION PLAN
E0.1 ELECTRICAL SYMBOL LEGEND, GENERAL NOTES, DETAILS
ED1.1 LIGHTING DEMOLITION PLAN
ED1.2 POWER DEMOLITION PLAN
E1.1 LIGHTING PLAN
E1.2 POWER PLAN
E2.1 POWER RISER, PANEL SCHEDULE
FA0.1 FIRE ALARM SYMBOL LEGEND, RISER, NOTES, DETAILS
FAD1.1 FIRE ALARM DEMOLITION PLAN
FA1.1 FIRE ALARM PLAN
R O
CKY MOUN
T, N C
O A K L E Y
C O
LL
IER ARCHITE
C
T S P .A
CERT NO.
50681
R E
G
IS
T
E R
E
D
AR
CH I
TECTURA L
C
O
R
P
O
R A T I O
N
N O R TH C A RO
L I N A
TI
M
OT
HY
D. OAKLE
Y
R O
C
KY
MOUN
T, N .C
N
OR TH CAR
OL
IN
A
R
EG
IS
TE
RED ARCHITE
C T
Revisions
Date Project No.
Sheet No.Drawn By
Checked By
Sheet Title
C a n d le w o o d R o a d R o c ky M o u n t, N C
P
.9
.2
W e st M a rt in S tr e e t, R a le ig h N
C
P
.9
.7
C o p y ri g h t
O a k le y C o lli e r
A rc h it e c ts
T h e s e d ra w in g s a re o f th e p ro p e rt y o f th e A rc h it e c t fo r u s e u n d e r h is s u p e rv is io n N o r e p ro d u c ti o n o r o th e r u s e i s a llo w e d w it h o u t p e rm is s io n
O A
K
LE
Y C
O
LL
IE
R
A R
C H
IT
E C
TS
24024
G0.2
TDO
JHH
BUILDING CODE
SUMMARY - EXISTING
EOC BUILDING
8/2/24
R E
N O
V A
T
IO
N S
F O
R
E D
G E
C O
M B
E C
O U
N T
Y E
M E
R G
E N
C Y
O P
E R
A T
IO
N
S C
E N
T E
R
T A
R B
O R
O N
O R
T H
C A
R O
L
IN
A
E
W A
L N
U T
S T
R E
E T
8/2/24
FIRE PROTECTION REQUIREMENTS
Structural Frame, including columns, girders, trusses
Bearing Walls
Exterior
North
East
West
South
Interior
Nonbearing Walls and
Partitions
Exterior walls
North
East
West
South
Interior walls and partitions
Floor Construction
Including supporting beams and joists
Floor Ceiling Assembly
Columns Supporting Floors
Roof Construction, including supporting beams and joists
Roof Ceiling Assembly
Columns Supporting Roof
Shaft Enclosures - Exit
Shaft Enclosures - Other
Incidental Use Separation
* Indicate section number permitting reduction
Corridor Separation
Occupancy/Fire Barrier Separation
Party/Fire Wall Separation
Smoke Barrier Separation
Smoke Partition
Tenant/Dwelling Unit/Sleeping Unit
Separation
BUILDING ELEMENT FIRE
SEPARATION
DISTANCE
(FEET)
RATING
DETAIL#
AND
SHEET#
DESIGN#
FOR
RATED
ASSEMBLY
SHEET# FOR
RATED
PENETRATION
SHEET#
FOR
RATED
JOINTS
REQ'D PROVIDED
(W/________*
REDUCTION)
Fire and/or smoke rated wall locations (Chapter 7)
Assumed and real property line locations (if not on the site plan)
Exterior wall opening area with respect to distance to assumed property lines (705.8)
Occupancy Use for each area as it relates to occupant load calculation (Table 1004.1.2)
Occupant loads for each area
Exit access travel distances (1017)
Common path of travel distances (Tables 1006.2.1 & 1006.3.2(1))
Dead end lengths (1020.4)
Clear exit widths for each exit door
Maximum calculated occupant load capacity each exit door can accommodate based on egress width (1005.3)
Actual occupant load for each exit door
A separate schematic plan indicating where fire rated floor/ceiling and/or roof structure is provided for purposes of occupancy separation
Location of doors with panic hardware (1010.1.10)
Location of doors with delayed egress locks and the amount of delay (1010.1.9.7)
Location of doors with electromagnetic egress locks (1010.1.9.9)
Location of doors equipped with hold-open devices
Location of emergency escape windows (1030)
The square footage of each fire area (202)
The square footage of each smoke compartment for Occupancy Classification I-2 (407.5)
Note any code exceptions or table notes that may have been utilized regarding the items above
LIFE SAFETY PLAN REQUIREMENTS
Life Safety Plan Sheet #:
Emergency Lighting:
Exit Signs:
Fire Alarm:
Smoke Detection Systems:
Carbon Monoxide Detection:
LIFE SAFETY SYSTEM REQUIREMENTS
No Yes No Yes No Yes No Yes Partial No Yes
PERCENTAGE OF WALL OPENING CALCULATIONS
FIRE SEPARATION DISTANCE
(FEET) FROM PROPERTY LINES
DEGREE OF OPENINGS
PROTECTION
(TABLE 705.8)
ALLOWABLE AREA
ACTUAL SHOWN ON PLANS
ACCESSIBLE DWELLING UNITS
ACCESSIBLE PARKING
PLUMBING FIXTURE REQUIREMENTS
(TABLE 2902.1)
SPECIAL APPROVALS
(SECTION 1107)
(SECTION 1106)
TOTAL
UNITS
ACCESSIBLE
UNITS
REQUIRED
ACCESSIBLE
UNITS
PROVIDED
TYPE A
UNITS
REQUIRED
TYPE A
UNITS
PROVIDED
TYPE B
UNITS
REQUIRED
TYPE B
UNITS
PROVIDED
TOTAL
ACCESSIBLE UNITS
PROVIDED
LOT OR PARKING
AREA
TOTAL # OF PARKING SPACES # OF ACCESSIBLE SPACES PROVIDED TOTAL #
ACCESSIBLE
PROVIDEDREQUIRED PROVIDED REGULAR WITH
5' ACCESS AISLE
VAN SPACES WITH
TOTAL
USE WATERCLOSETS URINALS LAVATORIES SHOWERS
/TUBS
DRINKING FOUNTAINS
MALE FEMALE UNISEX MALE FEMALE UNISEX REGULAR ACCESSIBLE
SPACE EXIST'G
NEW
REQ'D
132” ACCESS
AISLE
8' ACCESS
AISLE
Special approval: (Local Jurisdiction, Department of Insurance, OSC, DPI, DHHS, etc., describe below)
2018 APPENDIX B BUILDING CODE SUMMARY - EXISTING EOC BUILDING
Building Height in Feet (Table 504.3) 2
Building Height in Stories (Table 504.4) 3
1. Provide code reference if the “Shown on Plans” quantity is not based on Table 504.3 or 504.4.
2. The maximum height of air traffic towers must comply with Table 412.3.1.
3. The maximum height of open parking garages must comply with Table 406.5.4.
ALLOWABLE SHOWN ON PLANS CODE REFERENCE 1
ALLOWABLE HEIGHT
ENERGY SUMMARY
ENERGY REQUIREMENTS:
Existing building envelope complies with code:
Exempt Building:
Climate Zone:
Method of Compliance:
THERMAL ENVELOPE (Prescriptive method only)
Roof/ceiling Assembly (each assembly)
Exterior Walls (each assembly)
Walls below grade (each assembly)
Floors over unconditioned space (each assembly)
Floors slab on grade
The following data shall be considered minimum and any special attribute required to meet the energy code shall also be provided. Each Designer shall furnish the required portions of the project information for the plan data sheet. If performance method, state the annual energy cost for the standard reference design vs annual energy cost for the proposed design.
Yes (The remainder of this section is not applicable)
Yes (Provide code or statutory reference)___________________
3A 4A 5A
Energy Code Performance Prescriptive
ASHRAE 90.1 Performance
Description of assembly:
U-Value of total assembly:
R-Value of insulation:
Skylights in each assembly:
U-Value of skylight:
Total square footage of skylights in each assembly:
Description of assembly:
U-Value of total assembly:
R-Value of insulation:
Openings (windows or doors with glazing)
U-Value of assembly:
Solar heat gain coefficient:
Projection factor:
Door R-Values:
Description of assembly:
U-Value of total assembly:
R-Value of total assembly:
Description of assembly:
U-Value of total assembly:
R-Value of total assembly:
Description of assembly:
U-Value of total assembly:
R-Value of insulation:
Horizontal/vertical requirement:
Slab heated:
(If "Other" specify here)
Prescriptive
STRUCTURAL DESIGN
DESIGN LOADS:
Importance Factors:
Live Loads:
Ground Snow Load:
Wind Load:
SEISMIC DESIGN CATEGORY:
Risk Category (Table 1604.5)
Spectral Response Acceleration
Site Classification (ASCE 7)
Basic structural system
Analysis Procedure:
Architectural, Mechanical, Components anchored?
LATERAL DESIGN CONTROL:
SOIL BEARING CAPACITIES:
Snow (I ) Seismic (I )
Roof Mezzanine psf
Floor
Ultimate Wind Speed
Exposure Category
A B C D
Provide the following Seismic Design Parameters:
I II III IV
S S
A B C D E F
Data Source: Field Test Presumptive Historical Data
Bearing Wall Dual w/Special Moment Frame Building Frame Dual w/Intermediate R/C or Special Steel Moment Frame Inverted Pendulum
Simplified Equivalent Lateral Force Dynamic
Yes No
Earthquake Wind
Field Test (provide copy of test report) psf
Presumptive Bearing capacity psf
Pile size, type, and capacity
S
E
S 1 psf psf mph (ASCE-7)
%g%g
MECHANICAL DESIGN
MECHANICAL SYSTEMS, SERVICE SYSTEMS AND EQUIPMENT
Thermal Zone
Interior design conditions
Building heating load:
Building cooling load:
Mechanical Spacing Conditioning System
List equipment efficiencies:
winter dry bulb:
summer dry bulb:
winter dry bulb:
summer dry bulb:
relative humidity:
Unitary description of unit:
heating efficiency:
cooling efficiency:
size category of unit:
Boiler Size category, if oversized, state reason:
Chiller Size category, if oversized, state reason:
ELECTRICAL DESIGN
ELECTRICAL SYSTEM AND EQUIPMENT
Method of Compliance:
Lighting schedule (each fixture type)
Additional Efficiency Package Options
(When using the 2018 NCECC; not required for ASHRAE 90.1)
Energy Code: Prescriptive Performance ASHRAE 90.1: Prescriptive Performance lamp type required in fixture number of lamps in fixture ballast type used in the fixture number of ballasts in fixture total wattage per fixture total interior wattage specified vs. allowed (whole building or space by space) total exterior wattage specified vs. allowed
C406.2 More Efficient HVAC Equipment Performance
C406.3 Reduced Lighting Power Density
C406.4 Enhanced Digital Lighting Controls
C406.5 On-Site Renewable Energy
C406.6 Dedicated Outdoor Air System
C406.7 Reduced Energy Use in Service Water Heating psf
YesNoSpecial Inspections Required:
YesNoFlood Hazard Area:YesNoFire District:
DryWetIIIIIIClassNoStandpipes:
NFPA 13DNFPA 13RNFPA 13PartialNoSprinklers:
V-BIII-BII-BI-B
V-AIVIII-AII-AI-AConstruction Type:
BASIC BUILDING DATA
Risk Category (Table 1604.5):
PROPOSED OCCUPANCY(S) (Ch.3):RENOVATED: (date)
CURRENT OCCUPANCY(S) (Ch.3):CONSTRUCTED: (date)
Change of UseHistoric Property
Level IIILevel IILevel I
Chapter 14RepairPrescriptive2018 NC EXISTING BUILDING CODE:
1st Time Interior Completion
AdditionNew Building2018 NC BUILDING CODE:
CONTACT:
StateCountyCityCode Enforcement Jurisdiction:
StatePrivateCity/CountyOwned By:
E-MailPhone #
Owner/Authorized Agent:
Zip CodeAddress:
Name of Project:
GROSS BUILDING AREA TABLE
FLOOR EXISTING (SQ FT) SUB-TOTAL
4th Floor
3rd Floor
2nd Floor
1st Floor
Basement
TOTAL
ALLOWABLE AREA
Primary Occupancy Classification(s):
Assembly A-1 A-2 A-3 A-4 A-5 Business
Educational Factory
Hazardous
Institutional
Mercantile
Residential
Storage
Parking Garage
Utility and Miscellaneous
F-1 Moderate F-2 Low
H-1 Detonate H-2 Deflagrate H-3 Combust H-4 Health H-5 HPM
I-1
I-2
R-1 R-2 R-3 R-4
S-1 Moderate S-2 Low High-piled
Open Enclosed Repair Garage
Non-Separated Use (508.3) - The required type of construction for the building shall be determined by applying the height and area limitations for each of the applicable occupancies to the entire buildign. The most restrictive type of construction, so determined, shall apply to the entire building.
1. Frontage area increases from Section 506.3 are computed thus:
a. Perimeter which fronts a public way or open space having 20 feet minimum width = _______ (F)
b. Total Building Perimeter = _____________(P).
c. Ratio (F/P) = _________(F/P)
d. W = Minimum width of public way = ________ (W)
2. Unlimited area applicable under conditions of Section 507.
3. Maximum Building Area = total number of stories in the building x D (maximum 3 stories) (506.2).
4. The maximum area of open parking garages must comply with Table 406.5.4 .
5. Frontage increase is based on the unsprinklered area value in Table 506.2.
Actual Area of Occupancy A + Actual Area of Occupancy B Allowable Area of Occupancy A Allowable Area of Occupancy B
<1
1.00<
1,5 2,3
STORY
NO.
DESCRIPTION AND
USE
(A)
BLDG AREA PER
STORY (ACTUAL)
(B)
TABLE 506.2
AREA
(C)
AREA FOR FRONTAGE
INCREASE
(D)
ALLOWABLE AREA PER
STORY OR UNLIMITED
Mixed Occupancy: No Yes Separation: Hr. Exception:
Accessory Occupancy Classification(s):
Special Provisions: (Chapter 5 - List Code Sections):
Special Uses (Chapter 4 - List Code Sections):
Incidental Uses (Table 509):
(“Other” should include firms and individuals such as truss, precast, pre-engineered, interior designers, etc.)
Other
Retaining Walls >5' High
Structural
Sprinkler-Standpipe
Mechanical
Plumbing Fire Alarm
Electrical
Civil
Architectural
E-MAILTELEPHONE#LICENSE#NAMEFIRMDESIGNER
Renovation
Shell/Core - Contact the local inspection jurisdiction for possible additional procedures and requirements
Phased Construction - Shell/Core - Contact the local inspection jurisdiction for possible additional procedures and requirements
Alteration
Existing
I
I
Proposed:
Current:
II
II
III
III
IV
IV
Yes
Yes
(Contact the local inspection jurisdiction for additional procedures and requirements. )
I-3
I-4
Condition 1 2
Condition 1 2
Condition 1 2 3 4 5
Separated Use (508.4) - See below for area calculations for each story, the area of the occupancy shall be such that the sum of the ratios of the actual floor area of each use divided by the allowable floor area for each use shall not exceed 1.
e. Percent of frontage increase If = 100[F/P-0.25] x W/30 = _____________ (%).
No
No
N/A N/A N/A N/A N/A N/A N/A N/A
EDGECOMBE COUNTY EOC RENOVATION
400 E WALNUT STREET, TARBORO, NORTH CAROLINA 27886
N/A B
B
TIMOTHY D. OAKLEY, ARCHITECT
4,346 788 4,346 N/A N/A N/A
4,346 788 4,346
N/A
N/A
N/A
N/A
N/A N/A
OAKLEY COLLIER ARCHITECTS TIM OAKLEY 5967 252-937-2500 TOAKLEY@OAKLEYCOLLIER.COM
MICHAEL MATTHEWS
MICHAELMATTHEWS@EDGECOMBECO.COM(252) 641-7833
TARBORO
G1.1
RENOVATION (SQ FT)
EXISTING TO REMAIN
EXISTING TO REMAIN
EXISTING TO REMAIN
6th Floor
5th Floor
NOT APPLICABLE
EXISTING TO REMAIN
EXISTING TO REMAIN
EXISTING TO REMAIN
EXISTING TO REMAIN
EXISTING TO REMAIN
ATLANTEC
ATLANTEC
ATLANTEC
ATLANTEC
N/A
N/A
N/A
N/A
N/A
EXISTING TO REMAIN
DAVID WHITNEY 17382 919-571-1111 DAVID@ATLANTECENGINEERS.COM
17382
BRADLEY FELTS 025036
PATRICK MCCABE 051195
919-571-1111 DAVID@ATLANTECENGINEERS.COM
919-571-1111 BRAD@ATLANTECENGINEERS.COM
919-571-1111 PATRICK@ATLANTECENGINEERS.COM
DAVID WHITNEY
EXISTING TO REMAIN
R O
CKY MOUN
T, N C
O A K L E Y
C O
LL
IER ARCHITE
C
T S P .A
CERT NO.
50681
R E
G
IS
T
E R
E
D
AR
CH I
TECTURA L
C
O
R
P
O
R A T I O
N
N O R TH C A RO
L I N A
TI
M
OT
HY
D. OAKLE
Y
R O
C
KY
MOUN
T, N .C
N
OR TH CAR
OL
IN
A
R
EG
IS
TE
RED ARCHITE
C T
Revisions
Date Project No.
Sheet No.Drawn By
Checked By
Sheet Title
C a n d le w o o d R o a d R o c ky M o u n t, N C
P
.9
.2
W e st M a rt in S tr e e t, R a le ig h N
C
P
.9
.7
C o p y ri g h t
O a k le y C o lli e r
A rc h it e c ts
T h e s e d ra w in g s a re o f th e p ro p e rt y o f th e A rc h it e c t fo r u s e u n d e r h is s u p e rv is io n N o r e p ro d u c ti o n o r o th e r u s e i s a llo w e d w it h o u t p e rm is s io n
O A
K
LE
Y C
O
LL
IE
R
A R
C H
IT
E C
TS
24024
G0.3
TDO
JHH
BUILDING CODE
SUMMARY - EXISTING
(ARMORY) BUILDING
8/2/24
R E
N O
V A
T
IO
N S
F O
R
E D
G E
C O
M B
E C
O U
N T
Y E
M E
R G
E N
C Y
O P
E R
A T
IO
N
S C
E N
T E
R
T A
R B
O R
O N
O R
T H
C A
R O
L
IN
A
E
W A
L N
U T
S T
R E
E T
8/2/24
FIRE PROTECTION REQUIREMENTS
Structural Frame, including columns, girders, trusses
Bearing Walls
Exterior
North
East
West
South
Interior
Nonbearing Walls and
Partitions
Exterior walls
North
East
West
South
Interior walls and partitions
Floor Construction
Including supporting beams and joists
Floor Ceiling Assembly
Columns Supporting Floors
Roof Construction, including supporting beams and joists
Roof Ceiling Assembly
Columns Supporting Roof
Shaft Enclosures - Exit
Shaft Enclosures - Other
Incidental Use Separation
* Indicate section number permitting reduction
Corridor Separation
Occupancy/Fire Barrier Separation
Party/Fire Wall Separation
Smoke Barrier Separation
Smoke Partition
Tenant/Dwelling Unit/Sleeping Unit
Separation
BUILDING ELEMENT FIRE
SEPARATION
DISTANCE
(FEET)
RATING
DETAIL#
AND
SHEET#
DESIGN#
FOR
RATED
ASSEMBLY
SHEET# FOR
RATED
PENETRATION
SHEET#
FOR
RATED
JOINTS
REQ'D PROVIDED
(W/________*
REDUCTION)
Fire and/or smoke rated wall locations (Chapter 7)
Assumed and real property line locations (if not on the site plan)
Exterior wall opening area with respect to distance to assumed property lines (705.8)
Occupancy Use for each area as it relates to occupant load calculation (Table 1004.1.2)
Occupant loads for each area
Exit access travel distances (1017)
Common path of travel distances (Tables 1006.2.1 & 1006.3.2(1))
Dead end lengths (1020.4)
Clear exit widths for each exit door
Maximum calculated occupant load capacity each exit door can accommodate based on egress width (1005.3)
Actual occupant load for each exit door
A separate schematic plan indicating where fire rated floor/ceiling and/or roof structure is provided for purposes of occupancy separation
Location of doors with panic hardware (1010.1.10)
Location of doors with delayed egress locks and the amount of delay (1010.1.9.7)
Location of doors with electromagnetic egress locks (1010.1.9.9)
Location of doors equipped with hold-open devices
Location of emergency escape windows (1030)
The square footage of each fire area (202)
The square footage of each smoke compartment for Occupancy Classification I-2 (407.5)
Note any code exceptions or table notes that may have been utilized regarding the items above
LIFE SAFETY PLAN REQUIREMENTS
Life Safety Plan Sheet #:
Emergency Lighting:
Exit Signs:
Fire Alarm:
Smoke Detection Systems:
Carbon Monoxide Detection:
LIFE SAFETY SYSTEM REQUIREMENTS
No Yes No Yes No Yes No Yes Partial No Yes
PERCENTAGE OF WALL OPENING CALCULATIONS
FIRE SEPARATION DISTANCE
(FEET) FROM PROPERTY LINES
DEGREE OF OPENINGS
PROTECTION
(TABLE 705.8)
ALLOWABLE AREA
ACTUAL SHOWN ON PLANS
ACCESSIBLE DWELLING UNITS
ACCESSIBLE PARKING
PLUMBING FIXTURE REQUIREMENTS
(TABLE 2902.1)
SPECIAL APPROVALS
(SECTION 1107)
(SECTION 1106)
TOTAL
UNITS
ACCESSIBLE
UNITS
REQUIRED
ACCESSIBLE
UNITS
PROVIDED
TYPE A
UNITS
REQUIRED
TYPE A
UNITS
PROVIDED
TYPE B
UNITS
REQUIRED
TYPE B
UNITS
PROVIDED
TOTAL
ACCESSIBLE UNITS
PROVIDED
LOT OR PARKING
AREA
TOTAL # OF PARKING SPACES # OF ACCESSIBLE SPACES PROVIDED TOTAL #
ACCESSIBLE
PROVIDEDREQUIRED PROVIDED REGULAR WITH
5' ACCESS AISLE
VAN SPACES WITH
TOTAL
USE WATERCLOSETS URINALS LAVATORIES SHOWERS
/TUBS
DRINKING FOUNTAINS
MALE FEMALE UNISEX MALE FEMALE UNISEX REGULAR ACCESSIBLE
SPACE EXIST'G
NEW
REQ'D
132” ACCESS
AISLE
8' ACCESS
AISLE
Special approval: (Local Jurisdiction, Department of Insurance, OSC, DPI, DHHS, etc., describe below)
2018 APPENDIX B BUILDING CODE SUMMARY - EXISTING (ARMORY) BUILDING
Building Height in Feet (Table 504.3) 2
Building Height in Stories (Table 504.4) 3
1. Provide code reference if the “Shown on Plans” quantity is not based on Table 504.3 or 504.4.
2. The maximum height of air traffic towers must comply with Table 412.3.1.
3. The maximum height of open parking garages must comply with Table 406.5.4.
ALLOWABLE SHOWN ON PLANS CODE REFERENCE 1
ALLOWABLE HEIGHT
ENERGY SUMMARY
ENERGY REQUIREMENTS:
Existing building envelope complies with code:
Exempt Building:
Climate Zone:
Method of Compliance:
THERMAL ENVELOPE (Prescriptive method only)
Roof/ceiling Assembly (each assembly)
Exterior Walls (each assembly)
Walls below grade (each assembly)
Floors over unconditioned space (each assembly)
Floors slab on grade
The following data shall be considered minimum and any special attribute required to meet the energy code shall also be provided. Each Designer shall furnish the required portions of the project information for the plan data sheet. If performance method, state the annual energy cost for the standard reference design vs annual energy cost for the proposed design.
Yes (The remainder of this section is not applicable)
Yes (Provide code or statutory reference)___________________
3A 4A 5A
Energy Code Performance Prescriptive
ASHRAE 90.1 Performance
Description of assembly:
U-Value of total assembly:
R-Value of insulation:
Skylights in each assembly:
U-Value of skylight:
Total square footage of skylights in each assembly:
Description of assembly:
U-Value of total assembly:
R-Value of insulation:
Openings (windows or doors with glazing)
U-Value of assembly:
Solar heat gain coefficient:
Projection factor:
Door R-Values:
Description of assembly:
U-Value of total assembly:
R-Value of total assembly:
Description of assembly:
U-Value of total assembly:
R-Value of total assembly:
Description of assembly:
U-Value of total assembly:
R-Value of insulation:
Horizontal/vertical requirement:
Slab heated:
(If "Other" specify here)
Prescriptive
STRUCTURAL DESIGN
DESIGN LOADS:
Importance Factors:
Live Loads:
Ground Snow Load:
Wind Load:
SEISMIC DESIGN CATEGORY:
Risk Category (Table 1604.5)
Spectral Response Acceleration
Site Classification (ASCE 7)
Basic structural system
Analysis Procedure:
Architectural, Mechanical, Components anchored?
LATERAL DESIGN CONTROL:
SOIL BEARING CAPACITIES:
Snow (I ) Seismic (I )
Roof Mezzanine psf
Floor
Ultimate Wind Speed
Exposure Category
A B C D
Provide the following Seismic Design Parameters:
I II III IV
S S
A B C D E F
Data Source: Field Test Presumptive Historical Data
Bearing Wall Dual w/Special Moment Frame Building Frame Dual w/Intermediate R/C or Special Steel Moment Frame Inverted Pendulum
Simplified Equivalent Lateral Force Dynamic
Yes No
Earthquake Wind
Field Test (provide copy of test report) psf
Presumptive Bearing capacity psf
Pile size, type, and capacity
S
E
S 1 psf psf mph (ASCE-7)
%g%g
MECHANICAL DESIGN
MECHANICAL SYSTEMS, SERVICE SYSTEMS AND EQUIPMENT
Thermal Zone
Interior design conditions
Building heating load:
Building cooling load:
Mechanical Spacing Conditioning System
List equipment efficiencies:
winter dry bulb:
summer dry bulb:
winter dry bulb:
summer dry bulb:
relative humidity:
Unitary description of unit:
heating efficiency:
cooling efficiency:
size category of unit:
Boiler Size category, if oversized, state reason:
Chiller Size category, if oversized, state reason:
ELECTRICAL DESIGN
ELECTRICAL SYSTEM AND EQUIPMENT
Method of Compliance:
Lighting schedule (each fixture type)
Additional Efficiency Package Options
(When using the 2018 NCECC; not required for ASHRAE 90.1)
Energy Code: Prescriptive Performance ASHRAE 90.1: Prescriptive Performance lamp type required in fixture number of lamps in fixture ballast type used in the fixture number of ballasts in fixture total wattage per fixture total interior wattage specified vs. allowed (whole building or space by space) total exterior wattage specified vs. allowed
C406.2 More Efficient HVAC Equipment Performance
C406.3 Reduced Lighting Power Density
C406.4 Enhanced Digital Lighting Controls
C406.5 On-Site Renewable Energy
C406.6 Dedicated Outdoor Air System
C406.7 Reduced Energy Use in Service Water Heating psf
YesNoSpecial Inspections Required:
YesNoFlood Hazard Area:YesNoFire District:
DryWetIIIIIIClassNoStandpipes:
NFPA 13DNFPA 13RNFPA 13PartialNoSprinklers:
V-BIII-BII-BI-B
V-AIVIII-AII-AI-AConstruction Type:
BASIC BUILDING DATA
Risk Category (Table 1604.5):
PROPOSED OCCUPANCY(S) (Ch.3):RENOVATED: (date)
CURRENT OCCUPANCY(S) (Ch.3):CONSTRUCTED: (date)
Change of UseHistoric Property
Level IIILevel IILevel I
Chapter 14RepairPrescriptive2018 NC EXISTING BUILDING CODE:
1st Time Interior Completion
AdditionNew Building2018 NC BUILDING CODE:
CONTACT:
StateCountyCityCode Enforcement Jurisdiction:
StatePrivateCity/CountyOwned By:
E-MailPhone #
Owner/Authorized Agent:
Zip CodeAddress:
Name of Project:
GROSS BUILDING AREA TABLE
FLOOR EXISTING (SQ FT) SUB-TOTAL
4th Floor
3rd Floor
2nd Floor
1st Floor
Basement
TOTAL
ALLOWABLE AREA
Primary Occupancy Classification(s):
Assembly A-1 A-2 A-3 A-4 A-5 Business
Educational Factory
Hazardous
Institutional
Mercantile
Residential
Storage
Parking Garage
Utility and Miscellaneous
F-1 Moderate F-2 Low
H-1 Detonate H-2 Deflagrate H-3 Combust H-4 Health H-5 HPM
I-1
I-2
R-1 R-2 R-3 R-4
S-1 Moderate S-2 Low High-piled
Open Enclosed Repair Garage
Non-Separated Use (508.3) - The required type of construction for the building shall be determined by applying the height and area limitations for each of the applicable occupancies to the entire buildign. The most restrictive type of construction, so determined, shall apply to the entire building.
1. Frontage area increases from Section 506.3 are computed thus:
a. Perimeter which fronts a public way or open space having 20 feet minimum width = _______ (F)
b. Total Building Perimeter = _____________(P).
c. Ratio (F/P) = _________(F/P)
d. W = Minimum width of public way = ________ (W)
2. Unlimited area applicable under conditions of Section 507.
3. Maximum Building Area = total number of stories in the building x D (maximum 3 stories) (506.2).
4. The maximum area of open parking garages must comply with Table 406.5.4 .
5. Frontage increase is based on the unsprinklered area value in Table 506.2.
Actual Area of Occupancy A + Actual Area of Occupancy B Allowable Area of Occupancy A Allowable Area of Occupancy B
<1
1.00<
1,5 2,3
STORY
NO.
DESCRIPTION AND
USE
(A)
BLDG AREA PER
STORY (ACTUAL)
(B)
TABLE 506.2
AREA
(C)
AREA FOR FRONTAGE
INCREASE
(D)
ALLOWABLE AREA PER
STORY OR UNLIMITED
Mixed Occupancy: No Yes Separation: Hr. Exception:
Accessory Occupancy Classification(s):
Special Provisions: (Chapter 5 - List Code Sections):
Special Uses (Chapter 4 - List Code Sections):
Incidental Uses (Table 509):
(“Other” should include firms and individuals such as truss, precast, pre-engineered, interior designers, etc.)
Other
Retaining Walls >5' High
Structural
Sprinkler-Standpipe
Mechanical
Plumbing Fire Alarm
Electrical
Civil
Architectural
E-MAILTELEPHONE#LICENSE#NAMEFIRMDESIGNER
Renovation
Shell/Core - Contact the local inspection jurisdiction for possible additional procedures and requirements
Phased Construction - Shell/Core - Contact the local inspection jurisdiction for possible additional procedures and requirements
Alteration
Existing
I
I
Proposed:
Current:
II
II
III
III
IV
IV
Yes
Yes
(Contact the local inspection jurisdiction for additional procedures and requirements. )
I-3
I-4
Condition 1 2
Condition 1 2
Condition 1 2 3 4 5
Separated Use (508.4) - See below for area calculations for each story, the area of the occupancy shall be such that the sum of the ratios of the actual floor area of each use divided by the allowable floor area for each use shall not exceed 1.
e. Percent of frontage increase If = 100[F/P-0.25] x W/30 = _____________ (%).
No
No
N/A N/A N/A N/A N/A N/A N/A N/A
EDGECOMBE COUNTY EOC RENOVATION
400 E WALNUT STREET, TARBORO, NORTH CAROLINA 27886
UNKNOWN
N/A B
B
TIMOTHY D. OAKLEY, ARCHITECT
12,952 597 12,952 N/A N/A N/A
12,952 597 12,952
N/A
N/A
N/A
N/A
N/A N/A
OAKLEY COLLIER ARCHITECTS TIM OAKLEY 5967 252-937-2500 TOAKLEY@OAKLEYCOLLIER.COM
MICHAEL MATTHEWS
MICHAELMATTHEWS@EDGECOMBECO.COM(252) 641-7833
TARBORO
G1.1
RENOVATION (SQ FT)
EXISTING TO REMAIN
EXISTING TO REMAIN
EXISTING TO REMAIN
6th Floor
5th Floor
NOT APPLICABLE
EXISTING TO REMAIN
EXISTING TO REMAIN
EXISTING TO REMAIN
EXISTING TO REMAIN
EXISTING TO REMAIN
N/A
N/A
N/A
N/A
N/A
EXISTING TO REMAIN
ATLANTEC
ATLANTEC
ATLANTEC
ATLANTEC DAVID WHITNEY 17382 919-571-1111 DAVID@ATLANTECENGINEERS.COM
17382
BRADLEY FELTS 025036
PATRICK MCCABE 051195
919-571-1111 DAVID@ATLANTECENGINEERS.COM
919-571-1111 BRAD@ATLANTECENGINEERS.COM
919-571-1111 PATRICK@ATLANTECENGINEERS.COM
DAVID WHITNEY
LIFE SAFETY LEGEND
MAXIMUM TRAVEL DISTANCE
NOTES:
1. SEE ELECTRICAL PLANS FOR COMPLETE DESCRIPTION OF DEVICES
AND ADDITIONAL DETAILS INCLUDING MOUNTING AND PLACEMENT.
X XXX
XX XX
OCCUPANCY
SQUARE FEET OF ROOM
OCCUPANT LOAD
OCCUPANT LOAD FACTOR
XX" DOOR / 0.2"
XXX OCC. ALLOWED
XXX ACTUAL
EGRESS WIDTH
EGRESS CAPACITY FACTOR
EGRESS CAPACITY ALLOWED
ANTICIPATED EGRESS LOAD
109 SF
OFFICE
B
EXISTING EGRESS
DOOR TO REMAIN
EXISTING EGRESS
DOOR TO REMAIN
N
LIMITS OF WORK
109 SF
OFFICE
B
376 SF
MEETING
B
EXISTING EGRESS
DOOR TO REMAIN
428 SF
BREAK ROOM
B
159 SF
OFFICE
B
129 SF
OFFICE
B
LIMITS OF WORK
EXISTING EGRESS
DOOR TO REMAIN
LIMITS OF WORK
EXISTING SHOWER EXISTING TLT
EXISTING SHOWER
EXISTING SHOWER
EXISTING TLT
EXISTING MECH
EXISTING CLASSROOM
EXISTING FITNESS
EXISTING OFFICE
EXISTING MECHANICAL EXISTING MECHANICAL
EXISTING MULTIPURPOSE SPACE
EXISTING VESTIBULE
EXISTING STORAGE
EX
IS
TI
N
G S
TO
R
AG
E
EX
IS
TI
N
G S
TO
R
AG
E
EXISTING BATHROOM
EXISTING OFFICE EXISTING OFFICE
EXISTING CORRIDOR EXISTING OFFICE EXISTING OFFICE EXISTING OFFICE
EXISTING OFFICE
EXISTING ROOM
EXISTING STORAGE
EXISTING VAULT
EXISTING SUPPLY STORAGE
EX
IS
TI
N
G S
TO
R
AG
E
ARMORY BUILDING
EOC BUILDING
R O
CKY MOUN
T, N C
O A K L E Y
C O
LL
IER ARCHITE
C
T S P .A
CERT NO.
50681
R E
G
IS
T
E R
E
D
AR
CH I
TECTURA L
C
O
R
P
O
R A T I O
N
N O R TH C A RO
L I N A
TI
M
OT
HY
D. OAKLE
Y
R O
C
KY
MOUN
T, N .C
N
OR TH CAR
OL
IN
A
R
EG
IS
TE
RED ARCHITE
C T
Revisions
Date Project No.
Sheet No.Drawn By
Checked By
Sheet Title
C a n d le w o o d R o a d R o c ky M o u n t, N C
P
.9
.2
W e st M a rt in S tr e e t, R a le ig h N
C
P
.9
.7
C o p y ri g h t
O a k le y C o lli e r
A rc h it e c ts
T h e s e d ra w in g s a re o f th e p ro p e rt y o f th e A rc h it e c t fo r u s e u n d e r h is s u p e rv is io n N o r e p ro d u c ti o n o r o th e r u s e i s a llo w e d w it h o u t p e rm is s io n
O A
K
LE
Y C
O
LL
IE
R
A R
C H
IT
E C
TS
24024
G1.1
TDO
JHH
LIFE SAFETY
8/2/24
R E
N O
V A
T
IO
N S
F O
R
E D
G E
C O
M B
E C
O U
N T
Y E
M E
R G
E N
C Y
O P
E R
A T
IO
N
S C
E N
T E
R
T A
R B
O R
O N
O R
T H
C A
R O
L
IN
A
E
W A
L N
U T
S T
R E
E T
8/2/24
1/8" = 1'-0"
LIFE SAFETY PLAN
MAXIMUM TRAVEL DISTANCE
70'
M
AX
IM
U
M T
R
AV
EL
D
IS
TA
N C
E
DEMOLITION NOTES
1. FIELD VERIFY ALL EXISTING CONSTRUCTION CONDITIONS AND FINISHES PRIOR TO SUBMITTING A
BID AND START OF ANY WORK. DISCREPANCIES IN ACTUAL CONDITIONS AND PLANS SHALL BE
BROUGHT TO THE ATTENTION OF THE ARCHITECT AND/OR ENGINEER FOR EVALUATION BEFORE
SUBMITTING BID AND/OR CONTINUING WITH WORK.
2. FIELD VERIFY THE LOCATION OF ALL UTILITIES, INCLUDING BURIAL DEPTH, PRIOR TO START OF
ANY WORK. CONDITIONS THAT PROHIBIT THE WORK FROM BEING PERFORMED AS SHOWN SHALL
BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND/OR ENGINEER FOR EVALUATION
BEFORE CONTINUING WITH WORK.
3. VERIFY WITH THE OWNER PRIOR TO THE START OF WORK THE EXTENT OF DEMOLITION ITEMS
TO BE SALVAGED.
4. ITEMS NOT BEING SALVAGED SHALL BE TRANSPORTED AND DISPOSED OF IN A LEGAL MANNER
IN ACCORDANCE WITH ALL APPLICABLE CODES.
5. ADDITIONAL DEMOLITION WORK ASSOCIATED WITH PLUMBING, MECHANICAL, AND ELECTRICAL
WORK IS REQUIRED. COORDINATE WORK REQUIRED WITH ALL TRADES.
6. ALL DEMOLITION PLUMBING, MECHANICAL, AND ELECTRICAL WORK SHALL BE PERFORMED IN
COMPLIANCE WITH ALL APPLICABLE CODES.
7. ALL DEMOLITION WORK SHALL BE COORDINATED AND BE PERFORMED IN ACCORDANCE WITH
OWNER.
8. CLEAN AND PREPARE EXISTING SUBSTRATES IN ALL AREAS RECEIVING NEW FLOOR FINISHES AS
REQUIRED BY RENOVATION WORK AND FOR PROPER INSTALLATION OF NEW FINISHES PER
MANUFACTURER'S RECOMMENDATIONS.
9. PERFORM DEMOLITION WORK IN A MANNER SO AS TO MINIMIZE DAMAGE TO EXISTING
SURROUNDING ITEMS TO REMAIN.
10. CUT AND PATCH EXISTING WALLS AS NECESSARY FOR RENOVATION AND DEMOLITION WORK.
WALLS SHALL BE PATCHED TO MATCH ADJACENT EXISTING SURFACES AND PROVIDE A SMOOTH
AND SEAMLESS TRANSITION FROM NEW TO EXISTING.
11. IT IS THE INTENT OF THESE DOCUMENTS THAT "PATCH" IMPLIES THAT THE EXISTING
CONSTRUCTION SHALL BE REPAIRED IN A MANNER, WITH SAME OR SIMILAR MATERIALS,
PROVIDING A SMOOTH AND SEAMLESS TRANSITION FROM NEW TO EXISTING MATERIALS AND
THE PATCH SHALL BE PREPARED TO RECEIVE NEW FINISHES PER FINISH MANUFACTURERS
RECOMMENDATIONS.
12. IT IS THE INTENT OF THESE DOCUMENTS THAT "PREPARED" IMPLIES THAT THE EXISTING
CONSTRUCTION SHALL BE MADE READY TO RECEIVE NEW FINISHES IN ACCORDANCE WITH
FINISH MANUFACTURER'S RECOMMENDATIONS.
7 7
6 6
6'-0" 3'-4" 1'-4" 3'-4"
4 4
EXISTING SHOWER EXISTING TLT EXISTING TLT
EXISTING SHOWER
EX
IS
TI
N
G S
H O
W
ER
EXISTING FITNESS EXISTING CLASSROOM
EXISTING MECH
EXISTING VESTIBULE
EXISTING STORAGE
EX
IS
TI
N
G S
TO
R
AG
E
EX
IS
TI
N
G S
TO
R
AG
E
EXISTING ROOM EXISTING BATHROOM
EXISTING OFFICE
EXISTING MECHANICAL
EX
IS
TI
N
G M
U
LT
IP
U
R
PO
SE
S
PA
C
E
EXISTING OFFICE
EXISTING LOCKER
EXISTING LOCKER
EXISTING CORRIDOR
D1.1
SLAB REPAIR NOTES
1. CONCRETE TO COMPLY WITH AMERICAN CONCRETE INSTITUTE (ACI 318-02 AND ACI 318R-02.
2. CONCRETE TO BE 4 INCH THICK 3000 PSI REINFORCED WITH 6 X 6 - W1.4 X W1.4 WWF AT MID DEPTH.
3. PROVIDE A MINIMUM OF 4" #57 STONE FILL AT ALL LOCATIONS; COORDINATE DEPTH WITH EXISTING
CONDITIONS.
4. PROVIDE REINFORCED 15 MIL VAPOR BARRIER AT ALL LOCATIONS.
5. SEE PLUMBING PLANS FOR LOCATIONS OF PIPING RUNS REQUIRING SLAB CUTS. COORDINATE SLAB
CUTS AND REPAIR WITH PLUMBING.
6. COORDINATE DEPTH OF PIPING WITH PLUMBING AND EXISTING CONDITIONS. NOTIFY ARCHITECT IF
EXISTING CONDITIONS PROHIBIT WORK AS SHOWN ON PLANS.
7. TREAT SOIL UNDER SLAB WITH PROPER TERMITE PROTECTION.
8. REINFORCING STEEL SHALL BE INTERMEDIATE GRADE DEFORMED BARS PER ASTM A615 GRADE 60
(FOR #5 AND LARGER) GRADE 40 (FOR #4 AND SMALLER).
9. WELDED WIRE FABRIC SHALL BE ASTM A 185, WELDED STEEL WIRE FABRIC, PROVIDE SHEET TYPE -
ROLL TYPE NOT ACCEPTABLE.
10. SLAB CUTS FOR PIPING INSTALLATION SHALL BE NO WIDER THAN NECESSARY TO PERFORM WORK
AS SHOWN ON PLANS AND AS REQUIRED BY FIELD CONDITIONS.
11. SLAB CUTS SHALL NOT BE MADE THAT REQUIRE THE REMOVAL OF EXISTING WALL UNLESS
APPROVED IN WRITING BY ARCHITECT PRIOR TO WORK.
12. LOCATION OF EXISTING UNDERSLAB PIPING SHALL BE VERIFIED IN THE FIELD PRIOR TO CUTTING OF
SLAB. LOCATION INCLUDES ESTABLISHING DEPTH OF EXISTING PIPING.
6" VARIES - COORDINATE WITH PME 6"
NEW 4" THICK 3000 PSI CONCRETE SLAB
WITH 6X6-W1.4XW1.4 WWF AT MID DEPTH,
SET FLUSH WITH EXISTING ADJACENT
SLAB.
SAW CUT EXISTING
CONCRETE SLAB.
#4 DOWELS X 1'-0" LONG X 6" EMBED
AT 24" O.C. CORE DRILL AND EPOXY
ANCHOR INTO EXISTING SLAB
TRENCH AS REQUIRED FOR PLUMBING,
FILL AND COMPACT PER PLUMBING
EXISTING SLAB
TO REMAIN
15MIL REINFORCED VAPOR BARRIER,
SEAL TO EXISTING, TYPICAL
4" (MINIMUM) #57 STONE,
TYPICAL
SEE PLUMBING FOR PIPING LOCATIONS AND
SIZES
EQ
R O
CKY MOUN
T, N C
O A K L E Y
C O
LL
IER ARCHITE
C
T S P .A
CERT NO.
50681
R E
G
IS
T
E R
E
D
AR
CH I
TECTURA L
C
O
R
P
O
R A T I O
N
N O R TH C A RO
L I N A
TI
M
OT
HY
D. OAKLE
Y
R O
C
KY
MOUN
T, N .C
N
OR TH CAR
OL
IN
A
R
EG
IS
TE
RED ARCHITE
C T
Revisions
Date Project No.
Sheet No.Drawn By
Checked By
Sheet Title
C a n d le w o o d R o a d R o c ky M o u n t, N C
P
.9
.2
W e st M a rt in S tr e e t, R a le ig h N
C
P
.9
.7
C o p y ri g h t
O a k le y C o lli e r
A rc h it e c ts
T h e s e d ra w in g s a re o f th e p ro p e rt y o f th e A rc h it e c t fo r u s e u n d e r h is s u p e rv is io n N o r e p ro d u c ti o n o r o th e r u s e i s a llo w e d w it h o u t p e rm is s io n
O A
K
LE
Y C
O
LL
IE
R
A R
C H
IT
E C
TS
24024
D1.1
TDO
JHH
DEMOLITION PLAN
8/2/24
R E
N O
V A
T
IO
N S
F O
R
E D
G E
C O
M B
E C
O U
N T
Y E
M E
R G
E N
C Y
O P
E R
A T
IO
N
S C
E N
T E
R
T A
R B
O R
O N
O R
T H
C A
R O
L
IN
A
E
W A
L N
U T
S T
R E
E T
8/2/24
DEMOLITION KEY NOTES
NUMBER DESCRIPTION
1 REMOVE EXISTING RAISED PLATFORM, FINISHES, FRAMING AND ALL RELATED
COMPNENTS COMPLETELY. PATCH EXISTING WALL AND FLOOR AS REQUIRED.
2 REMOVE EXISTING CEILING MOUNTED DEVICES, PATCH CEILING AS REQUIRED.
CORRDINATE WORK WITH PME.
3 REMOVE EXISTING CARPET FLOORING COMPLETELY INCLUDING ALL BONDING AGENTS.
CLEAN AND PREPARE EXISTING SUBFLOOR AS NECESSARY TO RECEIVE NEW FINISHES.
4 REMOVE EXISTING RUBBER/VINYL WALL BASE COMPLETELY INCLUDING ALL BONDING
AGENTS. CLEAN AND PREPARE EXISTING WALLS TO REMAIN AS NECESSARY TO RECEIVE
NEW FINISHES.
5 REMOVE EXISTING CHAIN -LINK FENCINGAND POSTS COMPLETELY, VERIFY ACTUAL
CONDITIONS IN FIELD.
6 REMOVE EXISTING STUD FRAMED WALL AND ALL RELATED COMPONENTS COMPLETELY,
INCLUDING PME, BACK TO EXISTING MASONRY WALL TO REMAIN. PATCH AND REPAIR
EXISTING WALL AS NECESSARY.
7 REMOVE EXISTING WOOD PANNELING AND FURRING COMPLETELY BACK TO EXISTING
MASONRY WALL TO REMAIN. PATCH AND REPAIR WALL AS NECESSARY.
8 SAW CUT AND REMOVE PORTION OF EXISTING MASONRY WALL AND ALL RELATED
COMPONENTS COMPLETELY FOR INSTALLATION OF NEW DOOR. REMOVE EXISTING
MASONRY AS REQUIRED FOR INSTALLATION OF NEW BOND BEAM OVER DOOR.
9 REMOVE EXISTING WINDOW AC, REWORK EXISTING STOREFRONT AND ADD NEW FRAMING
AND GLAZING TO MATCH EXISTING
10 REMOVE EXISTING DOOR AND HARDWARE, EXISTING FRAME TO REMAIN
11 EMOVE EXISTING CEILING TRIM FROM THE ENTIRE LENGTH OF THIS WALL AND REPLACE
WITH NEW TO MATCH EXISTING PAINTED.
12 REMOVE EXISTING TILE FROM JAMBS AT EXISTING OPENING
13 REMOVE AND RELOCATE EXISTING ATTIC ACCESS PANEL
14 CUT NEW OPENING AND ADD FRAMING AS REQUIRED FOR RELOCATED ATTIC ACCESS
PANEL
15 SAW CUT AND REMOVE PORTION OF EXISTING REINFORCED CONCRETE SLAB AS
REQUIRED FOR RENOVATION WORK. SEE PME FOR ADDITIONAL WORK.
1/8" = 1'-0"
DEMOLITION PLAN
N
1 1/2" = 1'-0"D1.1
1 TYPICAL SLAB REPAIR DETAIL
OFFICE
OFFICE
MEETING
'-0
9'-6 3/4" +/- 9'-6 3/4" +/-
OFFICE
OFFICE
BREAK ROOM
'-6
CORRIDOR
5'-8 3/8"
A1.1
EXISTING TO REMAIN
NO WORK REQUIRED
EX
IS
TI
N
G T
O R
EM
AI
N N
O W
O R
K R
EQ
U
IR
ED4'-0"
PAINT
6'-0" 3'-4"
1'-4" 3'-4"
PAINT
EX
IS
TI
N
G S
TO
R
AG
E
EX
IS
TI
N
G S
TO
R
AG
E
EXISTING SHOWER EXISTING TLT EXISTING TLT
EXISTING SHOWER
EXISTING SHOWER
EXISTING FITNESS
EXISTING CLASSROOM
EXISTING MECH
EXISTING OFFICE
EXISTING VESTIBULE
EXISTING STORAGE
EXISTING BATHROOM
EXISTING MULTIPURPOSE SPACE
EXISTING MECHANICAL EXISTING MECHANICAL
AC
AC
0"
EXISTING CORRIDOR
WALL LEGEND
PLAN VIEWMARK REMARKS
INTERIOR STUD WALL | 3 5/8"
2 TOP OF WALL = FULL HEIGHT TO ETR
5/8" TYPE "X" GYPSUM BOARD
3 5/8" 20 GA METAL STUDS AT 16" O.C,
WITH HORIZONTAL BRIDGING AT 48" O.C.
3 1/2" SOUND ATTENUATION BATT
INSULATION FULL HEIGHT
3 5/8"
PLAN VIEWMARK REMARKS
INFIL - EXISTING CMU - 8"
1 TOP OF WALL = ETR
NEW WOOD TRIM TO MATCH EXISTING
8" CMU - MATCH EXISTING - V.I.F. WITH
NEW TO EXISTING ANCHORS AT 16" O.C.
EACH SIDE
TILE TO MATCH EXISTING ON SHOWER
SIDE OF WALL
CEILING TO REMAIN
PLAN VIEWMARK REMARKS
INTERIOR STUD WALL | 3 5/8"
3 TOP OF WALL = FULL HEIGHT TO ETR
5/8" TYPE "X" GYPSUM BOARD
6" 20 GA METAL STUDS AT 16" O.C, WITH
HORIZONTAL BRIDGING AT 48" O.C.
5 1/2" SOUND ATTENUATION BATT
INSULATION FULL HEIGHT
6"
GENERAL NOTES
1. DIMENSIONS THIS PLAN ARE FROM: FACE OF EXISTING TO
CENTERLINE OF NEW STUD WALLS
2. INSTALL SOUND ATTENUATION BATT INSULATION FULL
HEIGHT IN ALL INTERIOR STUD WALLS.
3. VERIFY ALL DIMENSIONS AND SIZES PRIOR TO
CONSTRUCTION.
4. SCHEDULE AND COORDINATE ALL INSPECTIONS REQUIRED.
5. OBTAIN ALL PERMITS REQUIRED.
6. COORDINATE SCHEDULES WITH THE OWNER PRIOR TO
CONSTRUCTION.
7. SEE DOOR SCHEDULE FOR ALL DOOR SIZES.
CONDITIONS VARY - SEE PLAN/LEGEND FOR DESCRIPTION OF MATERIALS, TYPICAL
RECESSED DEVICE BOX, SEE ELECTRICAL FOR DESCRIPTION, TYPICAL
DO NOT PLACE ANY RECESSED DEVICE BOXES BACK TO BACK OR IN SAME
BAY UNLESS PHYSICALLY OR DIMENSIONALLY IMPOSSIBLE
NOTE:
RECESSED DEVICE BOXES IN ADJACENT SPACES TO BE INSTALLED OPPOSITE AND IN
ADJACENT BAY TYPICAL ALL LOCATIONS.
CONTINUOUS TREATED WOOD GROUND, TYPICAL.
DO NOT USE GROUND THICKER THAN WALL BOARD
BASE - SEE FINISH SCHEDULE FOR DESCRIPTION
CONDITIONS VARY, SEE PLAN/LEGEND FOR
DESCRIPTION OF MATERIALS, TYPICAL
CONDITIONS VARY - SEE ROOM FINISH SCHEDULE
FOR DESCRIPTION OF FINISHES
1/
2"
5/8"
WOOD GROUND - NON-RATED WALL
CONTINUOUS BACKER ROD AND ACOUSTICAL
SEALANT, TYPICAL
1. ALL EXISTING COVER PLATES IN WORK AREAS FOR DEVICES TO BE REPLACED WITH ALL NEW SS COVER PLATES.
2. VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO INSTALLATION OF FINISHES.
3. FURNISH AND INSTALL TRANSITION STRIP AT ALL FLOOR MATERIAL CHANGES AS SHOWN OR AS REQUIRED.
4. HEIGHT AND PROFILE OF ALL TRANSITIONS STRIPS SHALL COMPLY WITH HANDICAP CODE.
5. COLOR FOR ALL TRANSITION STRIPS SHALL BE AS SELECTED BY OWNER FROM MANUFACTURER'S FULL RANGE.
6. INSTALL NEW WOOD TRIM AT CEILING IN OFFICES, CORRIDOR, AND BREAK ROOM. PAINT TO MATCH EXISTING.
7. INSTALL NEW WOOD TRIM THE WIDTH OF THE EXISTING OPENING INFILL AT SHOWER SIDE . TRIM TO MATCH
EXISTING AND BE PAINTED.
8. COORDINATE LOCATION OF ALL TRANSITION STRIPS WITH EXISTING AND NEW CONDITIONS. WHERE POSSIBLE, LOCATE TRANSITION STRIPS UNDER DOOR SLABS. NO EXPOSED SLAB PERMITTED IN FINISHED AREAS.
9. COORDINATE SIZE OF ALL TRANSITION STRIPS WITH FINISH MATERIALS.
FINISH NOTES
18" 36" 33" 39" +/- V.I.F.
38" 126" +/- V.I.F.
PLASTIC LAMINATE
ADJUSTABLE SHELVING
SOLID SURFACE
PLASTIC LAMINATE
ADJUSTABLE SHELVING
BASE
SINK
FINISHED END
FINISHED END
FILLER PANEL
FILLER PANEL
MINIMUM
30" CLEAR
6" 2'
-6
A1.1
SINK - SEE PLUMBING FOR DESCRIPTION
SOLID SURFACE COUNTERTOP
FAUCET - SEE PLUMBING FOR
DESCRIPTION
COORDINATE DRAIN AND WATER
SUPPLY STUB-OUTS WITH SINK
" M
IN
C
LE
AR
1/
2"
1/ 2"
3/4" MARINE GRADE PLYWOOD
SUBSTRATE
PLASTIC LAMINATE
VALANCE
3/4" PLYWOOD, PROVIDE STIFFENERS ,
TYPICAL
3/4" REMOVABLE PLYWOOD
PANEL, COORDINATE WITH
SINK. PLASTIC LAMINATE
FINISH, PROVIDE COVER
CAPS FOR SCREW HEADS
2"X2" FRAMING EACH END
SECURELY ATTACHED TO WALL /
CABINET BASE
CONTINUOUS 2"X4" FRAME,
ANCHOR TO WALL
C
LE
AR
9"CLEAR
6"
DASHED LINE INDICATES EXTENTS
OF MINIMUM ADA CLEAR SPACE
4" HIGH SOLID SURFACE BACK
SPLASH, SURFACE MOUNTED,
CAULK
25"
R O
CKY MOUN
T, N C
O A K L E Y
C O
LL
IER ARCHITE
C
T S P .A
CERT NO.
50681
R E
G
IS
T
E R
E
D
AR
CH I
TECTURA L
C
O
R
P
O
R A T I O
N
N O R TH C A RO
L I N A
TI
M
OT
HY
D. OAKLE
Y
R O
C
KY
MOUN
T, N .C
N
OR TH CAR
OL
IN
A
R
EG
IS
TE
RED ARCHITE
C T
Revisions
Date Project No.
Sheet No.Drawn By
Checked By
Sheet Title
C a n d le w o o d R o a d R o c ky M o u n t, N C
P
.9
.2
W e st M a rt in S tr e e t, R a le ig h N
C
P
.9
.7
C o p y ri g h t
O a k le y C o lli e r
A rc h it e c ts
T h e s e d ra w in g s a re o f th e p ro p e rt y o f th e A rc h it e c t fo r u s e u n d e r h is s u p e rv is io n N o r e p ro d u c ti o n o r o th e r u s e i s a llo w e d w it h o u t p e rm is s io n
O A
K
LE
Y C
O
LL
IE
R
A R
C H
IT
E C
TS
24024
A1.1
TDO
JHH
FLOOR PLAN
8/2/24
R E
N O
V A
T
IO
N S
F O
R
E D
G E
C O
M B
E C
O U
N T
Y E
M E
R G
E N
C Y
O P
E R
A T
IO
N
S C
E N
T E
R
T A
R B
O R
O N
O R
T H
C A
R O
L
IN
A
E
W A
L N
U T
S T
R E
E T
8/2/24
1/8" = 1'-0"
FLOOR PLAN
1 1/2" = 1'-0"A1.1
1 DETAIL
3" = 1'-0"A1.1
2 DETAIL
FINISH SCHEDULE
ROOM
NUMBER ROOM NAME FLOOR BASE
WALLS
CEILING
ROOM
NUMBERNORTH SOUTH EAST WEST
100 MEETING CPT RB PT-1 PT-1 PT-1 PT-1 ETR - PATCH/PAINT 100
101 OFFICE CPT RB PT-1 PT-1 PT-1 PT-1 ETR - PATCH/PAINT 101
102 OFFICE CPT RB PT-1 PT-1 PT-1 PT-1 ETR - PATCH/PAINT 102
200 CORRIDOR CPT RB PT-1 PT-1 PT-1 PT-1 ETR - PATCH/PAINT 200
201 OFFICE CPT RB PT-1 PT-1 PT-1 PT-1 ETR - PATCH/PAINT 201
202 OFFICE CPT RB PT-1 PT-1 PT-1 PT-1 ETR - PATCH/PAINT 202
203 BREAK ROOM CPT RB PT-1 PT-1 PT-1 PT-1 ETR - PATCH/PAINT 203
N
3/8" = 1'-0"A1.1
3 ELEVATION 130
1" = 1'-0"A1.1
4 DETAIL
OFFICE
N
OFFICE
MEETING
OFFICE
OFFICE
CORRIDOR
BREAK ROOM
EXISTING TO REMAIN
NO WORK REQUIRED
EX
IS
TI
N
G T
O R
EM
AI
N N
O W
O R
K R
EQ
U
IR
ED
PATCH AND REPAIR FOR RELOCATION OF
LIGHT FIXTURES AND PAINTED.
EXISTING ATTIC ACCESS HATCH
RELOCATED INTO THE OFFICE
PATCH AND REPAIR FOR RELOCATION OF
LIGHT FIXTURES AND PAINTED.
EXISTING SHOWER EXISTING TLT EXISTING TLT
EXISTING SHOWER
EXISTING SHOWER
EXISTING CLASSROOM
EXISTING MECH
EXISTING FITNESS
EXISTING MECHANICAL EXISTING MECHANICAL
EXISTING MULTIPURPOSE SPACE
EXISTING OFFICE
EXISTING VESTIBULE
EXISTING STORAGE
EXISTING BATHROOM
EX
IS
TI
N
G S
TO
R
AG
E
EX
IS
TI
N
G S
TO
R
AG
E
PATCH AND REPAIR
FOR RELOCATION OF
LIGHT FIXTURES AND
PAINTED.
PATCH AND REPAIR
FOR RELOCATION OF
LIGHT FIXTURES AND
PAINTED.
PATCH AND REPAIR FOR RELOCATION OF
LIGHT FIXTURES AND PAINTED.
PATCH AND REPAIR FOR RELOCATION OF
LIGHT FIXTURES AND PAINTED.
EXISTING CORRIDOR
ETR
ETR
ETR ETR
ETR ETR
ETR
PATCH AND REPAIR FOR RELOCATION
OF ATTIC ACCESS AND PAINTED.
R O
CKY MOUN
T, N C
O A K L E Y
C O
LL
IER ARCHITE
C
T S P .A
CERT NO.
50681
R E
G
IS
T
E R
E
D
AR
CH I
TECTURA L
C
O
R
P
O
R A T I O
N
N O R TH C A RO
L I N A
TI
M
OT
HY
D. OAKLE
Y
R O
C
KY
MOUN
T, N .C
N
OR TH CAR
OL
IN
A
R
EG
IS
TE
RED ARCHITE
C T
Revisions
Date Project No.
Sheet No.Drawn By
Checked By
Sheet Title
C a n d le w o o d R o a d R o c ky M o u n t, N C
P
.9
.2
W e st M a rt in S tr e e t, R a le ig h N
C
P
.9
.7
C o p y ri g h t
O a k le y C o lli e r
A rc h it e c ts
T h e s e d ra w in g s a re o f th e p ro p e rt y o f th e A rc h it e c t fo r u s e u n d e r h is s u p e rv is io n N o r e p ro d u c ti o n o r o th e r u s e i s a llo w e d w it h o u t p e rm is s io n
O A
K
LE
Y C
O
LL
IE
R
A R
C H
IT
E C
TS
24024
A1.2
TDO
JHH
REFLECTED CEILING
PLAN
8/2/24
R E
N O
V A
T
IO
N S
F O
R
E D
G E
C O
M B
E C
O U
N T
Y E
M E
R G
E N
C Y
O P
E R
A T
IO
N
S C
E N
T E
R
T A
R B
O R
O N
O R
T H
C A
R O
L
IN
A
E
W A
L N
U T
S T
R E
E T
8/2/24
1/8" = 1'-0"
REFLECTED CEILING PLAN
D1
SE
E
SC
H
ED
SEE SCHED
SE
E
SC
H
ED
6'-0"
D2 F1
2"
2"
2"
SEE SCHED.
SE
E
SC
H
ED
. 2"
4"
2"
SEE SCHED.
SE
E
SC
H
ED
F2
GENERAL DOOR NOTES
1. ALL HARDWARE SHALL MEET ALL APPLICABLE
HANDICAP CODES.
2. TEMPERED GLAZING SHALL BE USED AS NOTED AND
AS REQUIRED BY CODE.
3. ALL HOLLOW METAL DOOR FRAMES SHALL BE
INSTALLED PER MANUFACTURER FOR PROPER
INSTALLATION AND OPERATION FOR SPECIFIC
APPLICATIONS.
4. DOOR THRESHOLDS SHALL BE 1/2" MAXIMUM HEIGHT.
TYPICAL FOR ALL INTERIOR DOORS
UNLESS DIMENSIONED OTHERWISE
ON PLANS
DOOR, SEE PLAN AND
DOOR SCHEDULE
4"
HINGE SIDE OF DOOR,
TYPICAL
SEE FLOOR PLAN AND WALL LEGEND
FOR DESCRITION OF MATERIALS,
TYPICAL
DOOR - SEE DOOR SCHEDULE
HOLLOW METAL FRAME WITH 3
STUD ANCHORS, TYPICAL
JACK/JAMB STUDS - SEE INTERIOR
HEADER SCHEDULE, TYPICAL
SEE WALL LEGEND/SECTIONS FOR
DESCRIPTION OF MATERIALS, TYPICAL
SEE FLOOR PLAN FOR THROAT DEPTH
CAULK JOINT ALL AROUND EACH
SIDE, TYPICAL
SEE WALL LEGEND/SECTIONS FOR
DESCRIPTION OF MATERIALS, TYPICAL
HOLLOW METAL FRAME, TYPICAL
HEADER - SEE INTERIOR HEADER
SCHEDULE, TYPICAL
DOOR - SEE DOOR SCHEDULE
SEE FLOOR PLAN FOR THROAT DEPTH
CAULK ALL AROUND EACH SIDE, TYPICAL
ATTACH TOP AND BOTTOM TRACKS ALONG
TOP AND FLANGE OF TRACK WITH (2) #10-18
SCREWS AT 8" O.C.
UNPUNCHED STUDS, SIZE AND GAGE
PER SCHEDULE
TOP AND BOTTOM TRACK GAGE
SHALL MATCH HEADER GAGE
FULL HEIGHT JACK STUDS, SEE HEADER
SCHEDULE FOR QUANTITY
2"X2"X16 GAGE CLIP ANGLES X1/2" LESS THAN STUD WIDTH,
ATTACH WITH (3) #10 SCREWS ON EACH LEG TO HEADER AND
JAMB STUDS
JAMB STUDS, SEE HEADER SCHEDULE FOR QUANTITY
NON-LOAD BEARING
OPENING SIZE JACK JAMB
INTERIOR HEADER SCHEDULE
ALL BOXED HEADERS SHALL BE SIZED TO FIT WALL SIZES SHOWN ARE
MINIMUMS.
6" X 20 GA.
3 5/8" X 20 GA.
PROVIDE…