240068 WSFCS Admin Bldg AHU Replacement_100% CD Set (1).pdf

PDF 4 MB Posted

Attached to
HVAC 475 Admin Building
Solicitation number
260-260-02182025-91400
Issued by
Forsyth County, North Carolina

About this file

This is a complete construction drawing set from SKA Consulting Engineers for an AHU (Air Handling Unit) replacement project at the Winston-Salem/Forsyth County Schools Administrative Office building located at 475 Corporate Square Drive in Winston-Salem, NC. The drawings detail the replacement of two air handling units (AHU-1 and AHU-2) along with associated condensing units, ductwork modifications, electrical connections, and controls integration. The project includes both base bid work for AHU-1 and Alternate No. 1 for AHU-2. The drawing set is dated May 29, 2024 and includes mechanical and electrical plans, specifications, schedules, and control diagrams.

The drawings specify split DX air handling units with VFD-driven supply fans, electric duct heaters (EDH-1 and EDH-2), and new condensing units (CU-1 and CU-2). The electrical scope includes new power connections from the existing main switchboard MSB and panel LP2, along with control panel and VFD installations. The mechanical systems are designed for 92°F summer and 18°F winter outdoor conditions, maintaining 70°F indoor temperature and 50% relative humidity. The drawings include detailed demolition and new work plans for both floors, showing precise locations and specifications for all new equipment and modifications to existing systems.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONSULTING

ENGINEERS

7900 Triad Center Drive, Suite 200 Greensboro, NC 27409-9075 t: 336 855 0993

NC License No. F-0508

GREENSBORO, NC

CORPORATE OFFICE

ASHEVILLE, NC

CHARLESTON, SC

CHARLOTTE, NC

CHARLOTTESVILLE, VA

RALEIGH-DURHAM, NC

WILMINGTON, NC

Quality. Integrity. Innovation.www.skaeng.com

SKA Consulting Engineers, Inc.

DRAWING SHEET INDEX VICINITY MAP

Date:

Set No:

Issued For:

These drawings are instruments of service and shall remain the property of SKA Consulting Engineers, Inc. whether the project for which they are made is executed or not. These drawings are not to be used in part or in whole by the owner or any other person or agency on this or any other projects or extensions to this project except by agreement in writing and with appropriate compensation to SKA. © Copyright 2024 by SKA Consulting Engineers, Inc. all rights reserved except as permitted under the United States Copyright Act of 1976, no part of this document may be reproduced or distributed in any form or by any means without the written permission of SKA

Consulting Engineers, Inc.

Project Number: 230268-0000 File Name: 240068-G0000.dwg Plotted: 5/28/2024 1:00:25 PM

475 CORPORATE SQUARE DR. SKA PROJECT NUMBER: 240068 WINSTON-SALEM, NC 27105

GENERAL

G0.1 APPENDIX "B"

MECHANICAL

M1.1 MECHANICAL NOTES, SYMBOLS, SPECIFICATIONS, LEGENDS, CONTROL DIAGRAMS, DETAILS, SECTIONS AND SCHEDULES

M2.1 MECHANICAL FIRST FLOOR DEMOLITION AND NEW WORK PLANS

M2.2 MECHANICAL SECOND FLOOR DEMOLITION AND NEW WORK PLANS - ALTERNATE NO. 1

ELECTRICAL

E1.1 ELECTRICAL LEGEND, SPECIFICATIONS, AND SCHEDULES

E2.1 ELECTRICAL FIRST FLOOR PLANS

E2.2 ELECTRICAL SECOND FLOOR PLANS - ALTERNATE NO. 1

E3.1 ELECTRICAL ONE-LINE DIAGRAMS AND PANEL SCHEDULES

WSFCS ADMIN OFFICE

FOR

AHU REPLACEMENT

PROJECT LOCATION

FOR CONSTRUCTION

05-29-2024

AP

PE

N D

IX

B

M ar k D at e

R ev is io n

Designed By:

Drawn By:

Checked By:

Date:

JMM

JAM

JMM

05-29-2024

G0.1

Project Number:

File Name: 240068-G0001 Plotted: 5/28/2024 9:52 AM

CONSULTING

ENGINEERS

240068

7900 Triad Center Drive, Suite 200 Greensboro, NC 27409-9075 t: 336 855 0993

NC License No. F-0508

GREENSBORO, NC

CORPORATE OFFICE

ASHEVILLE, NC

CHARLESTON, SC

CHARLOTTE, NC

CHARLOTTESVILLE, VA

RALEIGH-DURHAM, NC

WILMINGTON, NC

QUALITY. INTEGRITY. INNOVATION.

www.skaeng.com

SKA Consulting Engineers, Inc.

These drawings are instruments of service and shall remain the property of SKA Consulting Engineers, Inc. whether the project for which they are made is executed or not. These drawings are not to be used in part or in whole by the owner or any other person or agency on this or any other projects or extensions to this project except by agreement in writing and with appropriate compensation to SKA. © Copyright 2024 by SKA Consulting Engineers, Inc. all rights reserved except as permitted under the United States Copyright Act of 1976, no part of this document may be reproduced or distributed in any form or by any means without the written permission of SKA Consulting Engineers, Inc.

FO

R

C O

N

ST

R U

C

TI

O N

AH

U

R

EP

LA

C

EM

EN

T

FO

R

W

SF

C S

AD

M

IN

O

FF

IC

E

C

O R

PO

R

AT

E

SQ

U

AR

E

D R

W

IN

ST

O N

-S

AL

EM

, N

C

Address:

Owner/ Authorized Agent:

DESIGNER

Architectural

Electrical Fire Alarm Plumbing Mechanical Sprinkler-Standpipe Structural

Other

Phone #

FIRM TELEPHONE #LICENSE #

Name of Project:

Code Enforcement Jurisdiction:

Owned By: City/County

County Private State

NAME

Civil

New Construction Addition Renovation

I-B

I-A II-A

II-B

III-A IV V-A

III-B

Yes NFPA 13 NFPA 13R NFPA 13DNo WetYesNo Class III III Dry

YesNo

FLOOR

3rd Floor

EXISTING (SQ FT) NEW (SQ FT) SUB-TOTAL

1st Floor Basement

Mezzanine 2nd Floor

TOTAL

A-1Assembly Business

A-3A-2 A-4 A-5

Retaining Walls >5' High

City

CONTACT:

2018 NC BUILDING CODE:

BASIC BUILDING DATA:

Construction Type:

Sprinklers:

Standpipes:

Fire District:

Gross Building Area Table:

STORY NO. DESCRIPTION

AND USE

(A)

BLDG AREA PER

STORY (ACTUAL)

(B)

TABLE 506.2

AREA

(C)

AREA FOR FRONTAGE

INCREASE

(D)

ALLOWABLE AREA

PER STORYOR

UNLIMITED

1,5 2,3

ALLOWABLE AREA

Primary Occupancy Classification(s):

1. Frontage area increases from section 506.3 are computed thus:

a. Perimeter which fronts a public way or open space having 20 feet minimum width = _________________(F)

b. Total Building Perimeter = _________________(P)

c. Ratio (F/P) = _________________(F/P)

d. W = Minimum width of public way = _________________(W)

e. Percent of frontage increase I = 100 [F/P - 0.25] x W/30 = _________________(%)

2. Unlimited area applicable under conditions of Sections 507.

3. Maximum Building Area = total number of stories in the building x D (maximum 3 stories) (506.2).

4. The maximum area of open parking garages must comply with Table 406.5.4.

5. Frontage increase is based on the unsprinklered area value in Table 506.2 f

* indicate section number permitting reduction

BUILDING ELEMENT FIRE

SEPARATION

DISTANCE

(FEET)

RATING DETAIL #

AND

SHEET #

DESIGN #

FOR

RATED

ASSEMBLY

DESIGN # FOR

RATED

PENETRATION

DESIGN #

FOR

RATED

JOINTS

REQ'D. PROVIDED

(W/________*

REDUCTION)

Structural Frame, including columns, girders, trusses

Bearing walls

Exterior

North

East

West

South

Interior

Nonbearing walls and partitions . Exterior walls

North

East

West

South

Interior walls and partitions

Floor construction Including supporting beams and joists

Floor Ceiling Assembly

Columns Supporting Floors

Roof construction Including supporting beams and joists

Roof Ceiling Assembly

Columns Supporting Floors

Shaft Enclosures - Exit

Shaft Enclosures - Other

Corridor Separation

Occupancy/Fire Barrier Separation

Party/Fire Wall Separation

Smoke Barrier Separation

Tenant/Dwelling Unit/Sleeping Unit Separation

Incidental Use Separation

LIFE SAFETY SYSTEM REQUIREMENTS

No No No

Yes Yes Yes

No Yes No Yes

Emergency Lighting:

Exit Signs:

Fire Alarm:

Smoke Detection Systems:

Panic Hardware:

FIRE PROTECTION REQUIREMENTS

SSSpectral Response Acceleration %g S1 %g Site Classification

Basic structural system Bearing wall Dual w/special moment frame Building frame Dual w/intermediate R/C or special steel Moment frame Inverted pendulum

V =Seismic base shear Analysis Procedure Simplified Equivalent Lateral Force Dynamic Architectural, Mechanical, Components anchored?

Earthquake Wind

Field Test (provide copy of test report) psf Presumptive Bearing capacity psf Pile size, type, and capacity

ENERGY REQUIREMENTS:

(Local Jurisdiction, Department of Insurance, OSC, DPI, DHHS, ICC, etc., describe

The following data shall be considered minimum and any special attribute required to meet the energy code shall also be provided. Each Designer shall furnish the required portions of the project information for the plan data sheet. If performance method, state the annual energy cost budget vs annual energy cost for the proposed design.

THERMAL ENVELOPE

Roof/ceiling assembly

Description of assembly U-value of total assembly R-value of insulation Skylights in each assembly

U-value of skylight Total square footage of skylights in each assembly

Exterior walls

Openings (windows or doors with glazing) R-value of insulation U-value of total assembly

Projection factor Solar heat gain coefficient U-value of assembly

Door R-Values

Description of assembly

LATERAL DESIGN CONTROL:

SOIL BEARING CAPACITIES:

PLUMBING FIXTURE REQUIREMENTS

USE WATERCLOSETS URINALS LAVATORIES SHOWERS/

TUBS

DRINKING FOUNTAINS

MALE FEMALE MALE FEMALE REGULAR ACCESSIBLE

SPECIAL APPROVALS

ENERGY SUMMARY

Mechanical spacing conditioning system

Description of unit Heating efficiency Cooling efficiency Size category of unit

Unitary

Building cooling load

Interior design conditions winter dry bulb summer dry bulb relative humidity

Building heating load

Thermal zone: 4A winter dry bulb summer dry bulb

Performance Prescriptive

ELECTRICAL SYSTEM AND EQUIPMENT

MECHANICAL SUMMARY

Method of Compliance:

Lighting schedule lamp type required in fixture number of lamps in fixture ballast type used in fixture number of ballasts in fixture total wattage per fixture total interior wattage specified vs allowed (whole building or space by space) total exterior wattage specified vs allowed

MECHANICAL SYSTEMS, SERVICE SYSTEMS, AND EQUIPMENT:

List equipment efficiencies

State

E-MAIL

2018 APPENDIX B

BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS

(except 1 and 2-family dwellings and townhouses) (Reproduce the following data on the building plans sheet 1 or 2)

ALLOWABLE

(TABLE 503)

SHOWN ON

PLANS

CODE

REFERENCE

Building Height in Feet (Table 504.3) Feet _____________

Building Height in Stories (Table 504.4) Stories ___________ Stories

ALLOWABLE HEIGHT

V-B

Prescriptive Repair2018 NC EXISTING BUILDING CODE: EXISTING:

CONSTRUCTED: CURRENT OCCUPANCY(S) (Ch. 3):

RENOVATED:

Partial

YesNoFlood Hazard Area:

Field Test Presumptive Historical Data

V =

Size category. If oversized, state reason:

Boiler

Chiller

Special approval:

Zip Code

Partial x y

(each assembly)

(each assembly)

(check one)

Chapter 14

Life Safety Plan Sheet #: _____________________ Fire and/or smoke rated wall locations (Chapter 7) Assumed and real property line locations (if not on the site plan) Exterior wall opening area with respect to distance to assumed property lines (705.8) Occupancy Use for each area as it relates to occupant load calculation (Table 1004.1.2) Occupant loads for each area Exit access travel distances (1017) Common path of travel distances (Tables 1006.2.1 & 1006.3.2 (1) ) Dead end lengths (1020.4) Clear exit widths for each exit door

Actual occupant load for each exit door

Location of doors with panic hardware (1010.1.10) Location of doors with delayed egress locks and the amount of delay (1010.1.9.7) Location of doors with electromagnetic egress locks (1010.1.9.9) Location of doors equipped with hold-open devices Location of emergency escape windows (1030) The square footage of each fire area (202) The square footage of each smoke compartment for Occupancy Classification I-2 (407.5) Note any code exceptions or table notes that may have been utilized regarding the items above

C406.2 More Efficient HVAC Equipment Performance C406.3 Reduced Lighting Power Density C406.4 Enhanced Digital Lighting Controls C406.5 On-Site Renewable Energy C406.6 Dedicated Outdoor Air System C406.7 Reduced Energy Use in Service Water Heating

LIFE SAFETY PLAN REQUIREMENTS

A separate schematic plan indicating where fire rated floor/ceiling and/or roof structure is provided for purposes of occupancy separation

Maximum calculated occupant load capacity each exit door can accommodate based on egress width (1005.3)

ACCESSIBLE DWELLING UNITS

(SECTION 1107)

TOTAL

UNITS

ACCESSIBLE

UNITS

REQUIRED

ACCESSIBLE

UNITS

PROVIDED

TYPE A

UNITS

REQUIRED

TYPE A

UNITS

PROVIDED

TYPE B

UNITS

REQUIRED

TYPE B

UNITS

PROVIDED

TOTAL

ACCESSIBLE

UNITS PROVIDED

ACCESSIBLE PARKING

(SECTION 1106)

TOTAL UNITS TOTAL # OF PARKING SPACES # OF ACCESSIBLE SPACES PROVIDED TOTAL # ACCESSIBLE

PROVIDED

REQUIRED PROVIDED REGULAR 5'

ACCESS

AISLE

VAN SPACES WITH

132" ACCESS

AISLE

8' ACCESS

AISLE

TOTAL

Importance factors: Snow (I )Seismic (I )S

E Live loads:

Floor Mezzanine Roof psf psf psf

Ground snow load: psf Wind load:

Exposure category Ultimate wind speed mph (ASCE-7)

Provide the following seismic design parameters:

STRUCTURAL DESIGN

DESIGN LOADS:

SEISMIC DESIGN CATEGORY B DCA

Occupancy Category (Table 1604.5) II IVIIII

(ASCE 7)) B DCA E F

Data Source:

Yes No

(TABLE 2902.1)

3AClimate Zone: 4A 5A

Method of Compliance: Energy Code

Walls below grade

R-value of insulation U-value of total assembly Description of assembly

(each assembly)

Floors over unconditional space

R-value of insulation U-value of total assembly Description of assembly

(each assembly)

Floors slab on grade

R-value of insulation U-value of total assembly Description of assembly

Horizontal/vertical requirement slab heated

Size category. If oversized, state reason:

Energy Code:

Performance PrescriptiveASHRAE 90.1:

Additional Efficiency Package Options

AHU Replacement For WSFCS Admin Office 435 Corporate Square Dr. Winston-Salem, NORTH CAROLINA 27105

18 deg F

WSFCS 336-748-4000

N/A (OCCUPANT LOAD EGRESS

SYSTEM UNCHANGED)

N/A (BUILDING PROTECTION

REQUIREMENTS

UNCHANGED)

N/A - NO CHANGES

N/A - NO CHANGES

N/A N/A N/A N/A N/A

N/A (BUILDING UNCHANGED)

(336)855-0993SKA CONSULTING

ENGINEERS, INC. JAMES M. MALONEY 033109 jmmaloney@skaeng.com

JAMES M. MALONEY

N/A (BUILDING UNCHANGED)

1980 BUSINESS

BASEMENT

FIRST

N/A

1st Time Interior Completion Shell / Core - Contact the local inspection jurisdiction for possible additional procedures and requirements Phased Construction - Shell / Core - contact the local inspection jurisdiction for possible additional procedures and requirements

Level I Level II Historic Property

Alteration: Level III Change of Use

PROPOSED OCCUPANCY(S) (Ch. 3):

IRISK CATEGORY (Table 1604.5): Current: II III IV IProposed: II III IV

(Check all that apply)

Special Inspections Required: YesNo (Contact the local inspection jurisdiction for additional procedures and requirements.)

Educational Factory Hazardous Institutional

F-1 Moderate F-2 Low H-2 Detonate H-2 Deflagrate H-3 Combust H-4 Health H-5 HPM I-1 Condition 1 2 I-2 Condition 1 2 I-3 Condition 1 2 I-4

3 4 5

Mercantile Residential Storage S-1 Moderate

R-1 R-3R-2 R-4 S-2 Low High Piled

Parking Garage Open Enclosed Repair Garage Utility and Miscellaneous

Accessory Occupancy Classifications:

Incidental Uses (Table 509):

Special Uses (Chapter 4 - List Code Sections):

Special Provisions (Chapter 5 - List Code Sections):

Allowable Area Of Occupancy B

See below for area calculations for each story, the area of the occupancy shall be such that the sum of the ratios of the actual floor area of each use divided by the allowable floor area for each use shall not exceed 1.

The required type of construction for the building shall be determined by applying the height and area limitations for each of the applicable occupancies to the entire building. The most restrictive type of construction, so determined, shall apply to the entire building.

Separated Use (508.4) -

Exception:

Actual Area Of Occupancy A Allowable Area Of Occupancy A +

Actual Area Of Occupancy B

Non-Separated Use (508.3) -

Separation:No Yes Hr.

+ ...... = _ 1.00

_ 1

Mixed Occupancy:

1. Provide code reference if the "Shown on Plans" quantity is not based on Table 504.3 or 504.4.

2. The maximum height of air traffic control towers must comply with Table 412.3.1.

3. The maximum height of open parking garages must comply with table 406.5.4.

FIRE SEPARATION DISTANCE

(FEET) FROM PROPERTY LINES

DEGREE OF OPENINGS

PROTECTION (TABLE 705.8)

ALLOWABLE AREA (%) ``

PERCENTAGE OF WALL OPENING CALCULATIONS

N/A (BUILDING UNCHANGED)

NoExisting building envelope complies with code: Yes

NoExempt Building: Yes (provide code or statutory reference:)

Performance Prescriptive ASHRAE 90.1 Performance Prescriptive

(If "Other" specify source here)

(Prescriptive method only)

(PROVIDE ON THE STRUCTURAL SHEETS IF APPLICABLE)

(PROVIDE ON THE MECHANICAL SHEETS IF APPLICABLE)

ELECTRICAL SUMMARY

(PROVIDE ON THE ELECTRICAL SHEETS IF APPLICABLE)

(When using the 2018 NCECC; not required for ASHRAE 90.1)

E-mail:

N/A - NO CHANGES

CSanders@wsfcs.k12.nc.us

N/A (NO CHANGES TO EXISTING BUILDING FOOTPRINT)

92 deg F

70 deg F

50%

DX SPLIT AIR HANDLING UNITS

(SEE SCHEDULE)

N/A

N/A

(SEE SCHEDULE)

75 deg F

(SEE SCHEDULE)

(SEE SCHEDULE)

(336)855-0993SKA CONSULTING

ENGINEERS, INC. JOSH M. BOYER 055966 jmboyer@skaeng.com

35,760 0 35,760 0 0 0 35,040 0 35,040 35,040 0 35,040

105,840 0 105,840

N/A (LIFE SAFETY SYSTEMS UNCHANGED)

N/A

N/A

N/A - NO CHANGES

N/A (BUILDING UNCHANGED)

N O

TE

S, S

YM

BO

LS

, S

PE

C

IF

IC

AT

IO

N

S, L

EG

EN

D S, C O

N

TR

O L

D

IA

G R

AM

S, D

ET

AI

LS

, S

EC

TI

O

N S

AN

D

S C

H

ED

U

LE

S

M ar k D at e

R ev is io n

Designed By:

Drawn By:

Checked By:

Date:

JMM

JAM

JMM

05-29-2024

M1.1

Project Number:

File Name: 240068-M0101 Plotted: 5/28/2024 3:33 PM

CONSULTING

ENGINEERS

240068

7900 Triad Center Drive, Suite 200 Greensboro, NC 27409-9075 t: 336 855 0993

NC License No. F-0508

GREENSBORO, NC

CORPORATE OFFICE

ASHEVILLE, NC

CHARLESTON, SC

CHARLOTTE, NC

CHARLOTTESVILLE, VA

RALEIGH-DURHAM, NC

WILMINGTON, NC

QUALITY. INTEGRITY. INNOVATION.

www.skaeng.com

SKA Consulting Engineers, Inc.

These drawings are instruments of service and shall remain the property of SKA Consulting Engineers, Inc. whether the project for which they are made is executed or not. These drawings are not to be used in part or in whole by the owner or any other person or agency on this or any other projects or extensions to this project except by agreement in writing and with appropriate compensation to SKA. © Copyright 2024 by SKA Consulting Engineers, Inc. all rights reserved except as permitted under the United States Copyright Act of 1976, no part of this document may be reproduced or distributed in any form or by any means without the written permission of SKA Consulting Engineers, Inc.

FO

R

C O

N

ST

R U

C

TI

O N

AH

U

R

EP

LA

C

EM

EN

T

FO

R

W

SF

C S

AD

M

IN

O

FF

IC

E

C

O R

PO

R

AT

E

SQ

U

AR

E

D R

W

IN

ST

O N

-S

AL

EM

, N

C

THE CONTRACTOR MUST HAVE WRITTEN APPROVAL FROM THE ENGINEER PRIOR

TO INSTALLING ANY ALTERNATE PRODUCT.

PROVIDE SLEEVES FOR ALL PIPE AND DUCT THRU WALLS, FLOORS AND CEILINGS.

ROUTE CONDENSATE LINES FROM AIR CONDITIONING EQUIPMENT FULL SIZE AT

EQUIPMENT CONNECTION TO TERMINATION POINT BUT IN NO CASE LESS THAN 1" PIPE

SIZE OR 7/8" TUBING SIZE FOR GRAVITY DRAINS. PROVIDE P TRAPS ON EACH

CONDENSATE DRAIN.

UNLESS SPECIFICALLY NOTED OTHERWISE, ELECTRICAL CONTRACTOR SHALL

BE RESPONSIBLE FOR WIRING THE EQUIPMENT COMPLETE.

MANUAL BALANCING DAMPERS, ACCESS DOORS AND OTHER DUCTWORK

ACCESSORIES SHALL BE CONSTRUCTED OF THE SAME MATERIAL AS THE ADJACENT

DUCTWORK IN WHICH THEY ARE INSTALLED.

MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING IN THE FIELD

THAT THE MECHANICAL EQUIPMENT AND DUCTWORK FOR THIS PROJECT HAS BEEN

INSTALLED IN SUCH MANNER THAT VIBRATIONS SHALL NOT BE TRANSMITTED TO THE

BUILDING STRUCTURE. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO, AVOIDING

CONTACT BETWEEN DUCTWORK, DUCTWORK SUPPORTS AND CEILING HANGERS,

CONDUIT, WALL STUDS OR BRACES, PIPING AND PIPING HANGERS, AND THE LIKE.

EQUIPMENT CONNECTION SIZES, ELEVATION, AND CONFIGURATIONS ARE SUBJECT TO

CHANGE WHEN CERTIFIED VENDOR SHOP DRAWINGS ARE RECEIVED. CONTRACTOR

SHALL CHECK CERTIFIED SHOP DRAWINGS PRIOR TO INSTALLATION OF DUCTWORK

AND PIPING, AND SHALL MAKE REQUIRED ADJUSTMENTS AT NO ADDITIONAL COST TO

THE OWNER.

COORDINATE DUCTWORK ROUTING AND SIZES WITH NEW PIPING, CONDUIT,

STRUCTURES AND OTHER INTERFERENCES TO AVOID CONFLICTS. ADJUST DUCT SHAPE

TO FIT OPENING. IF SIZE MUST BE CHANGED, USE EQUIVALENT FRICTION METHOD TO

SELECT REVISED SIZE.

CONTRACTOR SHALL COORDINATE LOCATIONS OF ALL DUCT AND PIPING TO INTERFACE

WITH PLUMBING, FIRE PROTECTION, ELECTRICAL, CONTROLS, STRUCTURAL, AND ALL

OTHER WORK, EXISTING OR NEW.

ALL PIPE LAYOUTS ARE GENERALLY DIAGRAMMATIC. CONTRACTOR SHALL FIELD

VERIFY AND RE-CONFIGURE FOR AVAILABLE SPACE FOR INDICATED PIPES BASED ON

MEASUREMENTS AND SURVEYS TAKEN OF THE FIELD CONDITIONS.

ALL DUCT LAYOUTS ARE GENERALLY DIAGRAMMATIC. CONTRACTOR SHALL FIELD

VERIFY AND RE-CONFIGURE FOR AVAILABLE SPACE FOR INDICATED DUCTS BASED ON

MEASUREMENTS AND SURVEYS TAKEN OF THE AS-BUILT CONDITIONS.

EQUIPMENT SELECTIONS SCHEDULED ON THE DRAWINGS AND IN THE

SPECIFICATIONS INDICATE A MINIMUM LEVEL OF ACCEPTABLE PERFORMANCE.

MATERIALS, EQUIPMENT AND INSTALLATION SHALL COMPLY WITH ALL

REQUIREMENTS OF THE SPECIFICATIONS.

12.

11.

10.

8.

7.

6.

5.

4.

3.

1.

2.

9.

15.

13.

14.

Dwg #

GENERAL NOTES:

240068-M1001.DWG

CONTRACTOR SHALL PREPARE, SUBMIT AND OBTAIN APPROVAL ON

SHOP DRAWINGS.

LOCATE ALL CONTROL DEVICES, AND THE LIKE, IN ACCESSIBLE POSITIONS WITH

ADEQUATE MAINTENANCE CLEARANCE. COORDINATE AND LOCATE DEVICES SO

ACCESS IS NOT BLOCKED BY LIGHTS, GRILLES, DUCTWORK, PIPING, STRUCTURE,

CONDUIT AND THE LIKE.

1.

3.

4.

5.

6.

7.

8.

9.

10.

11.

2.

EXISTING PIPING SYSTEMS THAT ARE SHOWN TO BE

COMPLETELY OR PARTIALLY REMOVED SHALL BE THOROUGHLY

DRAINED. LABEL OR TAG ALL ABANDONED OR OUT-OF-SERVICE

PIPING.ALL PIPING SYSTEMS THAT ARE TO BE ABANDONED IN PLACE SHALL BE

PROPERLY CAPPED OR TERMINATED WITH ISOLATION VALVE AND CAP

ASSEMBLIES ON THE ENDS. IN GENERAL, PIPING WILL NOT BE ABANDONED

ANYWHERE IN THIS FACILITY UNLESS IT EXTENDS INTO AN EXISTING FINISHED

SPACE IN THE PLANT THAT IS NOT INCLUDED IN THE RENOVATION WORK OF

THIS CONTRACT.

WHERE EXISTING PIPING IS NOTED OR OTHERWISE REQUIRED TO BE REMOVED,

DEMOLITION SHALL INCLUDE ALL PIPE HANGERS, THREADED ROD, INSULATION

ASSEMBLIES, AND THE LIKE, COMPLETE. SUPPORT ATTACHMENTS TO

PERMANENT BUILDING STRUCTURAL MEMBERS MAY BE ABANDONED IN PLACE

EXCEPT WHERE NOTED OTHERWISE.

WHERE EXISTING DUCTWORK IS NOTED OR OTHERWISE REQUIRED TO BE

REMOVED, DEMOLITION SHALL INCLUDE ALL DUCT HANGERS, THREADED ROD,

INSULATION ASSEMBLIES, AIR DISTRIBUTION, DUCTWORK ACCESSORIES, DUCT

HEATERS, AND THE LIKE, COMPLETE. SUPPORT ATTACHMENTS TO PERMANENT

BUILDING STRUCTURAL MEMBERS MAY BE ABANDONED IN PLACE EXCEPT WHERE

NOTED OTHERWISE.

UNDER NO CIRCUMSTANCES SHALL EXISTING EQUIPMENT OR FINISHES BE

REMOVED SUCH THAT THE EXISTING BUILDING FINISHES WILL BE EXPOSED TO THE

WEATHER OR ACCESSIBLE FOR UNAUTHORIZED ENTRY INTO THE PLANT. THIS

SHALL INCLUDE, BUT NOT BE LIMITED TO THE REMOVAL OF EXHAUST FANS, ROOF

MOUNTED EQUIPMENT, LOUVERS, AND THE LIKE. WHEN ROOFTOP EQUIPMENT IS

REMOVED, ROOF OPENINGS SHALL BE PROPERLY FLAGGED AND CLOSED TO

PREVENT INJURY TO PERSONNEL WORKING ABOVE OR BELOW THE ROOF.

WHERE CONCRETE HOUSEKEEPING PADS ARE INDICATED FOR REMOVAL,

DEMOLITION SHALL INCLUDE REMOVING THE CONCRETE PAD FLUSH WITH THE

EXISTING FLOOR SLAB. ALL DOWELS OR ANCHOR BOLTS SHALL BE GROUND

OFF FLUSH WITH THE FLOOR SLAB.

WHERE CONCRETE PADS ARE INDICATED TO REMAIN AFTER EQUIPMENT IS

REMOVED, DEMOLITION SHALL INCLUDE CUTTING AND GRINDING ANCHOR BOLTS

FLUSH WITH THE CONCRETE PAD SURFACE. DO NOT LEAVE BOLT STUDS

PROJECTING ABOVE THE PAD.

WHERE STEEL SUPPORT FRAMES ARE INDICATED FOR REMOVAL, DEMOLITION

SHALL INCLUDE REMOVING THE FRAME TO THE EXISTING CONCRETE SUPPORT

PIER OR PAD. ALL ANCHOR BOLTS SHALL BE GROUND OFF FLUSH WITH THE

CONCRETE SUPPORT PIER OR PAD. UNLESS NOTED OTHERWISE, STEEL SUPPORT

FRAMES WILL BE REMOVED BY THE MECHANICAL CONTRACTOR.

WHERE EXISTING CONTROLS ARE TO BE DECOMMISSIONED IN EXISTING CONTROL

CABINETS (EG.: EXISTING AHU AND PUMP STARTERS, LEAD/LAG SWITCHES, AND

THE LIKE), COMPONENTS SHALL BE SAFELY TERMINATED AND/OR REMOVED FROM

THE CONTROL CABINET. REMOVE EXISTING LABELS AND RELABEL DEVICE AS OUT

OF SERVICE. DO NOT ABANDON "HOT" SWITCHES IN CABINETS.

ALL ITEMS REMOVED PER THE DEMOLITION DRAWINGS SHALL, UNLESS

SPECIFICALLY NOTED OTHERWISE, BECOME THE CONTRACTOR'S PROPERTY AND

BE REMOVED PROMPTLY FROM THE SITE.

EXISTING MECHANICAL EQUIPMENT AND PIPING SYSTEMS WITH REFRIGERANT

CHARGE SHALL BE PROPERLY DECOMMISSIONED IN STRICT ACCORDANCE WITH

EPA REGULATIONS CONCERNING CONTAINMENT OF HCFC AND CFC

REFRIGERANTS. REFRIGERANT RECLAIM FROM THESE SYSTEMS PRIOR TO

DEMOLITION SHALL BE ACCOMPLISHED BY PROPERLY TRAINED, LICENSED

CONTRACTORS. UNDER NO CIRCUMSTANCES SHALL REFRIGERANTS BE RELEASED

INTO THE ATMOSPHERE AS A MEANS OF PURGING THE EXISTING SYSTEM CHARGE.

Dwg #

GENERAL DEMOLITION NOTES

240068-M1002.DWG

NET FREE FLOW AREA)

FOR NET FREE FLOW AREA)

FANS

CENTRIFUGAL

DUCTWORK

DUCT SIZE (FIRST FIGURE SIDE SHOWN)(DIMENSIONS

DUCT SECTION, SUPPLY (DIMENSIONS FOR NET FREE FLOW AREA)

DUCT SECTION, RETURN OR EXHAUST (DIMENSIONS FOR

20x12

30x12

30x12

FILTER

DETECTORS, FIRE AND/OR SMOKES

DAMPERS

ELECTRIC OPERATED

SUPPLY

EXHAUST OR RETURN

GRILLE OR REGISTER

OPPOSED BLADE

PARALLEL BLADE

M

Dwg #

SYMBOLS - AIR MOVING DEVICES AND COMPONENTS

240068-M1003.DWG

D.I.

D.O.

A.O.

A.I.

DIGITAL INPUT

DIGITAL OUTPUT

ANALOG INPUT

ANALOG OUTPUT

D.W. DIRECT WIRED

T ROOM THERMOSTAT

TS TEMPERATURE SENSOR

FT FLOW TRANSMITTER

TE TEMPERATURE ELEMENT

S SMOKE DETECTOR

TT TEMPERATURE TRANSMITTER

HUMIDITY TRANSMITTERHT

Dwg #

INSTRUMENT IDENTIFICATION

240068-M1005.DWG

FACP FIRE ALARM CONTROL PANEL

M

VALVE ACTUATORS (ELECTRIC)

PIPING LEGEND

MOTOR

RS/RL REFRIGERANT SUCTION/LIQUID PIPING

POINT OF CONNECTION

NEW TO OLD

CD CONDENSATE DRAIN

LIMITS OF DEMOLITION

Dwg #

SYMBOLS, VALVES PIPING SPECIALTIES AND LEGEND

240068-M1006.DWG

1 CONSTRUCTION NOTE (REF. #)

HOA HAND-OFF-AUTO SELECTOR SWITCH (STARTER)

DS DISCONNECT SWITCH

EC

MC

BY ELECTRICAL CONTRACTOR

BY MECHANICAL CONTRACTOR

BY GENERAL CONTRACTORGC

BY CONTROLS CONTRACTORCC

Dwg #

SPECIALTY SYMBOLS

240068-M1007.DWG

MOTOR HORSEPOWER:

NUMBER OF PHASES:

MINIMUM EFFICIENCY

MOTOR TYPE:

# OF POLES:

LIST EQUIPMENT EFFICIENCIES -

EQUIPMENT SCHEDULES WITH MOTORS (MECHANICAL SYSTEMS)

BOILER -

TOTAL BOILER OUTPUT. IF OVERSIZED, STATE REASON:

CHILLER TOTAL CHILLER CAPACITY. IF OVERSIZED, STATE

REASON:

MECHANICAL SPACING CONDITIONING SYSTEM

UNITARY

DESCRIPTION OF UNIT: -

HEATING EFFICIENCY: -

COOLING EFFICIENCY: -

HEAT OUTPUT OF UNIT: -

COOLING OUTPUT OF UNIT: -

BUILDING HEATING LOAD -

BUILDING COOLING LOAD -

INTERIOR DESIGN CONDITIONS

WINTER DRY BULB: -

SUMMER DRY BULB: -

RELATIVE HUMIDITY: -

THERMAL ZONE

WINTER DRY BULB: -

SUMMER DRY BULB: -

SUMMER WET BULB: -

PRESCRIPTIVE ENERGY COST BUDGET

METHOD OF COMPLIANCE

70°F

18°F 92°F 74°F

N/A

N/A

N/A

N/A N/A N/A N/A

SEE SCHEDULE

SEE SCHEDULE

SEE SCHEDULE

SEE SCHEDULE

SEE SCHEDULE

N/A

SEE SCHEDULE

Dwg #

MECHANICAL SYSTEMS, SERVICE SYSTEMS AND EQUIPMENT

240068-M1008.DWG

THERMAL ZONE4A

N/A

75°F 50%

AHU DIRECT REPLACEMENT

Dwg #

MECHANICAL SPECIFICATIONS

240068-M1009.DWG

GENERAL:

THE WORK SHOWN ON THE DRAWINGS CONSISTS OF PROVIDING A COMPLETE SYSTEM

INCLUDING LABOR, MATERIALS, ETC.

THE TERM "PROVIDE" USED THROUGHOUT SPECIFICATIONS AND ON DRAWINGS SHALL

MEAN TO "FURNISH, INSTALL AND CONNECT WITH ALL RELATED ACCESSORIES AS

REQUIRED FOR COMPLETE INSTALLATION READY FOR USE."

COMPLY WITH ALL APPLICABLE LOCAL AND STATE CODES, LAWS AND REGULATIONS

APPLICABLE TO MECHANICAL, HEATING, VENTILATING AND AIR CONDITIONING

INSTALLATION.

THE CONTRACTOR SHALL PAY ALL INSPECTION FEES AND SHALL INCLUDE THE COST

OF SUCH FEES IN HIS PROPOSAL.

ALL MATERIAL AND EQUIPMENT SHALL BE STRICTLY INSTALLED ACCORDING TO THE

MANUFACTURER'S INSTALLATION INSTRUCTIONS.

ELECTRONIC SHOP DRAWINGS SHALL BE SUBMITTED TO THE ENGINEER FOR THE

FOLLOWING: AIR HANDLING UNIT, ELECTRIC DUCT HEATER, INSULATION SYSTEMS.

CHECK AND VERIFY WITH THE OWNER, EQUIPMENT SUPPLIERS, AND ALL OTHER

DOCUMENTS FOR THE PROJECT THE EXACT REQUIREMENTS FOR PROVIDING

REQUIRED AND COMPLETE SERVICES FOR EQUIPMENT, SYSTEMS, ETC. AS SHOWN OR

INDICATED. MINOR CHANGES IN PIPE, DUCT, OR EQUIPMENT LOCATIONS MAY BE

MADE AT ANY TIME PRIOR TO ROUGHING-IN OF THE MECHANICAL WORK AT NO

ADDITIONAL COSTS TO THE OWNER.

FURNISH TO ENGINEER ONE SET OF MARKED UP MECHANICAL, PRINTS WITH ALL

DEVIATIONS AND CORRECTIONS SHOWING THE AS-BUILT CONDITIONS AND

DIMENSIONED, IF NECESSARY, LOCATIONS, ELEVATIONS, ETC. OF ALL PIPING,

EQUIPMENT, DUCTS, VALVES, ETC.

SEAL AIR- AND WATER-TIGHT AROUND ALL DUCTWORK, RUN THRU NEW WALLS,

PARTITIONS, FLOORS, CEILINGS, ETC. USE FIRE BARRIER CAULK AND PUTTY EQUAL

TO 3M TYPE 303 PUTTY OR TYPE CP-25 CAULK AS APPLICABLE AROUND

PENETRATIONS THRU FIRE-RATED WALLS, PARTITIONS, FLOOR, CEILING, ETC.

ARRANGE WORK TO AVOID CUTTING WORK OF OTHER TRADES. WHERE CUTTING IS

UNAVOIDABLE, CUT AND PATCH IN A MANNER NOT TO WEAKEN THE STRUCTURE OR

ADVERSELY AFFECT THE FINISHED APPEARANCE. REPAIR CUT AREAS TO MATCH

ADJACENT WORK.

CONTRACTOR SHALL VERIFY EXISTING CONDITIONS & DUCT SIZES. NEW DUCT SIZES

ON DRAWINGS ARE FREE AREA DIMENSIONS.

ALL EQUIPMENT SHALL HAVE UL LABEL AS APPLICABLE.

MATERIALS:

DUCTWORK:

GALVANIZED STEEL FABRICATED IN ACCORDANCE WITH LATEST SMACNA AND

ASHRAE GUIDE AND STANDARDS. TURNS SHALL BE SQUARE WITH TURNING VANES OR

WITH PROPER SIZE RADIUS. USE FOLLOWING GAUGES FOR LOW PRESSURE

DUCTWORK: WHERE THE LONGEST SECTION DIMENSION IS 0-12 INCHES - 26 GAUGE;

13-30 INCHES - 24 GAUGE. NEW DUCTWORK NOT UTILIZING FLANGED & GASKETED

JOINTS SHALL BE SEALED WITH NON-VOC SEALANT. DUCTWORK UPSTREAM OF VAV

BOXES SHALL COMPLY TO SMACNA SEAL CLASS B.

PROVIDE MANUAL BALANCING DAMPERS IN ALL BRANCH DUCTS. MANUAL DAMPERS

SHALL BE RUSKIN MODEL CD35, MD25 OR MDRS25, AS APPLICABLE OR EQUAL. ALL

MANUAL DAMPERS SHALL BE FURNISHED WITH A MATCHING HEAVY DUTY HAND

QUADRANT WITH MINIMUM 1-1/2" CLEARANCE FOR DUCT INSULATION SYSTEMS.

DUCT LINER:

ASTM C-518 GLASS FIBER DUCT LINER FOR THERMAL AND ACOUSTICAL INSULATION.

PRODUCT SHALL BE TYPE 1, RESILIENT, EASY-TO-HANDLE IN ROLL FORM WITH A

MINIMUM DENSITY OF 3.0 LB/CU.FT., 250°F INSULATION SERVICE TEMPERATURE,

MINIMUM "K" VALUE OF 0.28 AT 75°F MEAN TEMPERATURE, AND SUITABLE FOR USE IN

DUCTWORK WITH MAXIMUM AIR STREAM VELOCITIES OF 4000 FT/MIN. AIR STREAM

SIDE OF THE DUCT LINER SHALL BE FACTORY COATED WITH A SMOOTH,

BLACK-COATED MAT PLASTIC COATING OR NEOPRENE SPRAY COATING. DUCT LINER

SHALL COMPLY WITH NFPA 90A AND 255, ASTM E84, AND UL 723 REQUIREMENTS FOR

MAXIMUM FLAME SPREAD OF 25 OR LESS AND SMOKE DEVELOPED RATING NOT

EXCEEDING 50. THE DUCT LINER SHALL MEET THE REQUIREMENTS OF ASTM C-1071

FOR NOISE REDUCTION CRITERIA (NRC). AS A MINIMUM, THE CALCULATED NRC FOR

TYPE 1 DUCT LINER ONE INCH THICK (1") SHALL BE 0.45 AND AS A MINIMUM FOR TWO

INCH THICK (2") SHALL BE 0.95.

EXISTING DUCTWORK:

WHERE EXISTING DUCTWORK HAS BEEN CUT OR OPENED, IT SHALL BE CLOSED,

SEALED, & INSULATED WITH SAME MATERIALS TO MATCH EXISTING. CONTRACTOR

SHALL EXAMINE EXISTING DUCT FOR OBVIOUS SIGNS OF LEAKAGE. JOINTS FOUND TO

BE LEAKING SHALL BE SEALED WITH NON-VOC DUCT SEALANT MASTIC OR

EQUIVALENT.

CLEANING, PAINTING:

CLEAN ALL HANGERS, DUCTWORK, GRILLES, DIFFUSERS, EQUIPMENT, ETC. AND ALL

MARKINGS ON DUCTWORK, AND LEAVE READY FOR USE OR PAINTING.

ANY DUCTWORK, PIPING, EQUIPMENT, CONDUITS, ETC. INSTALLED OR MODIFIED IN

THE BUILDING SHALL BE PAINTED BY THE HEATING AND AIR CONDITIONING

CONTRACTOR AT HIS EXPENSE TO MATCH ADJACENT AREAS.

PIPE INSULATION:

ASTM C-534 CLOSED CELL ELASTOMERIC THERMAL INSULATION. TYPE I, WATER

VAPOR PERMEABILITY OF MAXIMUM 0.20 PERM-IN PER ASTM E-96, "K" VALUE OF 0.28

AT 75°F MEAN TEMPERATURE, SERVICE TEMPERATURE RANGE OF -40 TO +220°F.

INSULATION TO 3/4" THICKNESS SHALL HAVE A FLAME SPREAD RATING OF 25, SMOKE

DEVELOPED 50 PER ASTM E-84.

PIPE INSULATION JACKETING:

METAL JACKETING SHALL BE 0.016" THICK ALUMINUM OR ALUMINUM ALLOYS

CONFORMING TO ASTM B-209. METAL JACKETING INSTALLED OUTDOORS SHALL BE

FURNISHED WITH A STUCCO EMBOSSED PATTERN AND 3/16" DEEP CORRUGATED

EXTERIOR SURFACE. METAL JACKETING INSTALLED INDOORS SHALL BE SMOOTH,

NON-CORRUGATED TYPE. ALL JACKETING SHALL HAVE AN INTEGRALLY BONDED

MOISTURE BARRIER COATING OVER THE ENTIRE SURFACE IN CONTACT WITH THE

INSULATION. THE MOISTURE BARRIER COATING SHALL BE COMPOSED OF ONE LAYER

OF ONE MIL THICK POLYETHYLENE FILM WITH A PROTECTIVE LAYER OF 40 POUND

KRAFT PAPER, OR THE EQUIVALENT, TO PREVENT MOISTURE AND CORROSIVES

WITHIN THE INSULATION FROM CONTACTING THE METAL JACKET AND CAUSING A

GALVANIC OR CHEMICAL CORROSION.

JACKETING FOR STRAIGHT PIPE SHALL HAVE A WEATHERTIGHT (OR WATERTIGHT)

SIDE CRIMP CLOSURE. FASTENING DEVICES SHALL BE TYPE T-304 STAINLESS STEEL

BANDS, 0.020" THICK, 3/4" WIDE, EQUAL TO FABSTRAPS BY CHILDERS PRODUCTS

COMPANY. SEAL ALL LAPS, SEAMS, JOINTS AND RAW EDGES OF ALUMINUM JACKETS

INSTALLED ON OUTDOOR PIPING OR WHERE REQUIRED FOR INDOOR PIPING JACKETS

WITH CAULKING OR SEALANT; CHILDERS CHIL-BYL CP-76, FOSTER 95-44, OR CLEAR

SILICONE CAULKING (G.E. 1200, OR EQUAL).

HVAC CONTROLS:

HVAC CONTROLS SHALL BE CAPABLE OF "STAND ALONE" OPERATION WITH ELECTRONIC

PROGRAMMABLE MICROPROCESSOR BASED CONTROLLERS FOR THE HVAC EQUIPMENT.

CONTROLLERS SHALL BE CONNECTED INTO THE EXISTING BAS.

CONTRACTOR SHALL PROVIDE ALL SENSORS, CONTROLLERS, CONTROL WIRING, RELAYS,

INTERLOCK WIRING, PROGRAMMING, GRAPHICS, ETC. REQUIRED TO INTERFACE WITH

THE EXISTING CONTROL SYSTEM AND TO PROVIDE FOR A COMPLETE AND OPERABLE

SYSTEM.

CONTRACTOR SHALL PROVIDE A MINIMUM OF 2 HOURS OF ON-SITE TRAINING FOR THE

OWNERS AND OPERATING PERSONEL.

EQUIPMENT IDENTIFICATION:

PROVIDE IDENTIFICATION AND LABELING ON ALL EQUIPMENT AND VALVES. LABELS

SHALL BE BLACK BACKGROUND WITH WHITE LETTERING. VALVE TAGS SHALL BE

MINIMUM 1 1/2" DIAMETER IN POLISHED BRASS. PROVIDE VALVE TAG LIST TO INDICATE

TAG NUMBER, LOCATION AND SERVICE. FOR EQUIPMENT LOCATED ABOVE CEILING,

PROVIDE IDENTIFICATION ON THE DEVICE IN ADDITION TO A PERMANENTLY ATTACHED

LABEL AFFIXED TO THE CEILING GRID NEAR THE EQUIPMENT. PROVIDE PIPING

IDENTIFICATION IN ACCORDANCE WITH ANSI A13.1 (INCLUDE LABELING AND FLOW

DIRECTION ARROWS AT ENDS OF RUNS, ON EACH SIDE OF PENETRATIONS AND AT 30

FOOT INTERVALS).

EXECUTION:

EXAMINE THE BUILDING TO VERIFY THAT SUFFICIENT SPACE IS AVAILABLE FOR

INSTALLATION.

DURING CONSTRUCTION, PROVIDE TEMPORARY CLOSURES OF METAL OR TAPED

POLYETHYLENE ON OPEN DUCTWORK TO PREVENT CONSTRUCTION DUST FROM

ENTERING THE DUCTWORK SYSTEM. CLEAN AND CAP DUCTWORK AS IT IS INSTALLED.

MAINTAIN REQUIRED VERTICAL AND LATERAL CLEARANCES FOR PROPER

PERFORMANCE, SERVICE ACCESS, MAINTENANCE AND SAFETY.

ALL PENETRATIONS SHALL BE SEALED VERMIN PROOF AND MOISTURE TIGHT.

GUARANTEE:

GUARANTEE ALL MATERIALS, EQUIPMENT AND WORKMANSHIP FOR ONE YEAR FROM THE

DATE OF FINAL ACCEPTANCE BY OWNER AS STATED IN WRITING. REPAIR AND/OR

REPLACE, WITHOUT ANY COST TO THE OWNER, ANY DEFECTIVE PART OR PARTS OF THE

WORK WITHIN THE GUARANTEE PERIOD FROM THE TIME THE SYSTEM IS PUT INTO

OPERATION AS DETERMINED BY THE DATE OF FINAL CERTIFICATE OF PAYMENT WITH

EXCEPTIONS AS NOTED.

PROVIDE PERIODICAL INSPECTION AND ADJUSTMENT SERVICE THROUGHOUT THE

GUARANTEE PERIOD.

TEST AND BALANCE:

TEST AND BALANCE NEW AIR HANDLING UNIT. TEST AND BALANCE SHALL BE PERFORMED

BY NEBB OR AABC CERTIFIED TEST AND BALANCE COMPANY. CERTIFIED TEST AND

BALANCE REPORT IN PDF FORM SHALL BE PROVIDED TO OWNER & DESIGN ENGINEER

UPON COMPLETION OF CONSTRUCTION. TEST AND BALANCE PROCEDURES SHALL

FOLLOW THOSE AS PRESCRIBED BY NEBB OR AABC.

TEST & BALANCE AIR DISTRIBUTION TO WITHIN 10% OF DESIGN CFM.

Dwg.#

MECHANICAL ROOM SECTION

N.T.S.

240068-M6001.DWG

M1.1

ALTERNATE NO. 1

ALTERNATE NO. 1

EXISTING

OUTSIDE AIR

DUCT TO LOUVER

AHU-1,2

OUTSIDE AIR

MODULATING

DAMPER

RETURN AIR

MODULATING

DAMPER

VFD

EXISTING

SUPPLY AIR

EDH-1,2

EXISTING RELIEF AIR

DAMPER & LOUVER;

NEW DAMPER

ACTUATOR

EXTERIOR WALL

NEW DUCT

AHU FLOW AND CONTROL DIAGRAM

NO SCALE

240068-M7001.DWG

M1.1

M

OUTDOOR

CONDENSING

UNIT

RETURN

AIR

PRE FILTER DX COOLING

COIL

ECEC DS460 / 3

EC

EC

SHUTDOWN

EC R EC

EC

HOA

VFD

FWE

CC

D.I. ALARM

CC

460 / 3

CC

START/ STOPD.O.

CC

CC CS

CC

D.I.

FAN STATUS

A.I. TEMP

TT

FACP

EC

EC

S

SUPPLY AIR

EC

EC

A.I.

TT

ROOM

TEMP.

FACP

EC

EC

S

MER

WALL

RETURN AIR

DUCT MOUNTED

REHEAT COIL

DS (BY DIV 26)

EC

460 / 3

M

A.O.

OUTSIDE AIR

M A.O.

DUCT

STATIC

PRESSURE

A.I.

SP

D.I.

PT

FILTER

ALARM

CC

PT

A.I.

DUCT MOUNTED

STATIC PRESSURE

TRANSMITTER

D.I.

PHL

A.I. A.I.

TT HT

A.I.AFMS

MER

WALL

RELIEF AIR

M

A.O.

(2-FANS)

ELECTRIC HEATING

COIL CONTROL

PANEL (FWE)

SCR

EC

A.O.

Dwg.#

AHU CONDENSATE TRAP

INSTALLATION DETAIL

NO SCALE

240068-M8001.DWG

M1.1

SCH. 40 PVC PIPE

SCREW PLUGS FOR

LINE CLEANOUTS

FLEX CONN.

(NOTE 5)

DISTANCE TO

DRAIN VARIES

4" MINIMUM OR 2P*

(WHICHEVER IS

GREATER)

8" MINIMUM OR 2P*

(WHICHEVER IS GREATER)

WHERE P = NEGATIVE PRESSURE

SLOPE 1/4" / LF

LOW PRESSURE SYSTEM, P < 2"WG NEGATIVE PRESSURE

1. DETAIL IS SHOWN FOR SINGLE DRAIN CONNECTION. ON UNITS WITH TWO DRAIN

CONNECTIONS, TRAP EACH INDIVIDUAL DRAIN AND RUN SEPARATELY TO THE NEAREST

OR DESIGNATED DRAIN.

2. DETAIL AS SHOWN IS FOR CONDENSATE DRAIN IN THE NEGATIVE STATIC PORTION OF

THE CABINET.

3. THE AHU AND DRAIN PAN MUST BE LEVEL TO WITHIN 0.25 INCH SIDE TO SIDE.

4. CONDENSATE DRAIN LINES SHALL HAVE PROVISIONS FOR REGULAR CLEANING TO

PREVENT SEDIMENT FROM PLUGGING THE DRAIN AND CAUSING THE DRAIN PAN TO

OVERFLOW.

5. FLEX CONNECTION REQUIRED WHERE AHU IS MOUNTED WITH EXTERNAL SPRING

VIBRATION CONTROL.

AHU

Dwg.#

NOTES:

240068-M8001.DWG

FLOOR

1. SET PIPE SUPPORTS AT MAXIMUM 6'-0" O.C. OR AT SPACING

TO PREVBENT SAG.

NOTES

REFRIGERANT PIPE

COPPER TUBE STRAP

POLYETHYLENE PIPE PIER

EQUAL TO DURABLOK.

TYPICAL PIPE SUPPORT DETAIL

NO SCALE

240068-M8002.DWG

M1.1

OA

TEMPERATURE

GLOBAL POINTS ONLY ONE

REQUIRED FOR ALL

BUILDING SYSTEMS

OUTSIDE TEMP.

FULL SCALE

240068-M7002.DWG

(NOTE: THESE POINTS MAY BE

EXISTING AND CAN BE USED AS PART

OF ECONOMIZER CYCLE CONTROL)

TE A.I.

OA

HUMIDITY

HT A.I.

YORK

TO 0 F°

M

EC

H

AN

IC

AL

F

IR

ST

F

LO

O

R D

EM

O

LI

TI

O N

A N

D N

EW

W

O R

K

PL

AN

S

M ar k D at e

R ev is io n

Designed By:

Drawn By:

Checked By:

Date:

JMM

JAM

JMM

05-29-2024

M2.1

Project Number:

File Name: 240068-M0201 Plotted: 5/28/2024 3:49 PM

CONSULTING

ENGINEERS

240068

7900 Triad Center Drive, Suite 200 Greensboro, NC 27409-9075 t: 336 855 0993

NC License No. F-0508

GREENSBORO, NC

CORPORATE OFFICE

ASHEVILLE, NC

CHARLESTON, SC

CHARLOTTE, NC

CHARLOTTESVILLE, VA

RALEIGH-DURHAM, NC

WILMINGTON, NC

QUALITY. INTEGRITY. INNOVATION.

www.skaeng.com

SKA Consulting Engineers, Inc.

These drawings are instruments of service and shall remain the property of SKA Consulting Engineers, Inc. whether the project for which they are made is executed or not. These drawings are not to be used in part or in whole by the owner or any other person or agency on this or any other projects or extensions to this project except by agreement in writing and with appropriate compensation to SKA. © Copyright 2024 by SKA Consulting Engineers, Inc. all rights reserved except as permitted under the United States Copyright Act of 1976, no part of this document may be reproduced or distributed in any form or by any means without the written permission of SKA Consulting Engineers, Inc.

FO

R

C O

N

ST

R U

C

TI

O N

AH

U

R

EP

LA

C

EM

EN

T

FO

R

W

SF

C S

AD

M

IN

O

FF

IC

E

C

O R

PO

R

AT

E

SQ

U

AR

E

D R

W

IN

ST

O N

-S

AL

EM

, N

C

AREA OF WORK

KEY PLAN

240068-G2002.DWG

PLAN NORTH

EXISTING

AHU-1

OA

PNEUMATIC

CONTROL

PANEL

EXISTING

FLOOR

DRAIN

S

S

RETURN AIR

DAMPER

OUTSIDE AIR DAMPER

LOCATED AT TOP OF

UNIT OPENING

RELIEF AIR

DAMPER

72" WIDE

INTAKE

LOUVER

72" WIDE

INTAKE

LOUVER

50X38

54X34

54X34

EX. CU-3

EX. 1ST FLOOR, 1ST STAGE

CONDENSING UNIT

EX. CONDENSING UNIT

FOR DATA ROOM

TR-R

90X26

PLENUM

RETURN

AIR DUCT

12X8

12X8

EX. 1ST FLOOR, 2ND STAGE

CONDENSING UNIT

EX. 2ND FLOOR, 1ST STAGE

CONDENSING UNIT

EX. 2ND FLOOR, 2ND STAGE

CONDENSING UNIT

Dwg.#

DEMOLITION NOTES

240068-MD3001.DWG

DEMOLISH EXISTING AIR HANDLING UNIT.

DEMOLISH SUPPLY AIR DUCT TO POINT SHOWN. KEEP EXISTING DISTRIBUTION INTACT. REFER TO SECTION 1 / M1.1.

DEMOLISH OUTSIDE AIR DUCT TO POINT SHOWN. REFER TO SECTION 1 / M1.1.

DEMOLISH REFRIGERANT PIPING.

DEMOLISH PNEUMATIC CONTROL PANEL AND AIR LINES ASSOCIATED WITH THE AHU.

EXISTING PLASMA AIR BIPOLAR IONIZATION SYSTEM TO REMAIN.

DEMOLISH EXISTING CONDENSING UNIT, COMPLETE. INCLUDING UNIT, PIPING, ELECTRICAL CONNECTIONS, ETC.

EXISTING RELIEF LOUVER TO REMAIN.

EXISTING RELIEF AIR DAMPER TO REMAIN. DEMOLISH PNEUMATIC DAMPER ACTUATOR.

EXISTING AIR COMPRESSORS AND DRYER TO REMAIN.

MEASURE SUPPLY AIR FLOW PRIOR TO DEMOLITION. RE-ESTABLISH CFM FOLLOWING NEW WORK.

7 7

RS/RL

RS/RL

R S/

R L

R S/

R L

RA

EX. CU-3

EX. CONDENSING UNIT

FOR DATA ROOM

TR-R

CU-2

CU-1

AHU-1OA

RELIEF AIR

EXISTING

FLOOR

DRAIN

S

S

RETURN AIR

DAMPER

RELIEF AIR

DAMPER

REFRIGERANT PIPING

TO EQUIPMENT YARD

72" WIDE

INTAKE

LOUVER

72" WIDE

INTAKE

LOUVER

50X38

54X34

54X34

90X26

PLENUM

RETURN

AIR DUCT

12X8

NEW ELECTRIC

DUCT HEATER,

EDH-1

ALTERNATE NO. 1

SET AHU ON STRUCTURAL

STEEL TO ALLOW FOR

REQUIRED TRAP DEPTH AND

CONDENSATE DRAINAGE

12X12

X8

VFD

EXISTING DUCT

DETECTOR

EXISTING

PLASMA AIR

SYSTEM

Dwg.#

NEW WORK NOTES

240068-M3001.DWG

NEW AIR HANDLING UNIT. REFER TO EQUIPMENT SCHEDULE ON SHEET M1.1.

RECONNECT SUPPLY AIR DUCT TO POINT SHOWN. PROVIDE TRANSITION DUCT.

RECONNECT OUTSIDE AIR DUCT TO POINT SHOWN. PROVIDE TRANSITION DUCT.

NOT USED.

PROVIDE NEW CONDENSING UNIT, COMPLETE. INCLUDING UNIT, PIPING, ELECTRICAL CONNECTIONS, ETC. REFER TO EQUIPMENT SCHEDULE ON SHEET M3.1. SET CONDENSING UNIT ON NEW 4" CONCRETE PAD. EXTEND PAD 6" BEYOND UNIT FOOTPRINT AND CHAMFER

ALL EDGES.

ROUTE NEW REFRIGERANT PIPING FROM NEW AHU TO NEW CONDENSING UNIT. SIZE PIPING IN ACCORDANCE WITH MANUFACTURER'S

INSTRUCTIONS.

ROUTE FULL SIZE CONDENSATE TO EXISTING FLOOR DRAIN.

NEW MODULATING DAMPER SHALL BE PROVIDED BY AHU MANUFACTURER. PROVIDE NEW 24 VAC DAMPER MOTOR.

NEW DDC CONTROL PANEL, 120V.

EXISTING AIR COMPRESSORS AND DRYER.

MAINTAIN A MINIMUM OF 3' SERVICE CLEARANCE FOR FILTER MAINTENANCE.

PROVIDE NEW 24 VAC DAMPER MOTOR.

RS/RL

RS/RL

RS/RL

R S/

R L

R S/

R L

R S/

R L

OUTSIDE AIR

DAMPER

RA

FIRST FLOOR AND EQUIPMENT YARD DEMOLITION PLAN

1/4" = 1'-0"

240068-MD3001.DWG

M2.1

FIRST FLOOR AND EQUIPMENT YARD NEW WORK PLAN

240068-M3001.DWG

M2.1

ALTERNATE NO. 1

ALTERNATE NO. 1

M

H

AN

IC

AL

S

EC

O N

D F

LO

O

R D

EM

O

LI

TI

O N

A N

D N

EW

W

O R

K

PL

AN

S

- A

LT

ER

N

AT

E

N O

. 1

M ar k D at e

R ev is io n

Designed By:

Drawn By:

Checked By:

Date:

JMM

JAM

JMM

05-29-2024

M2.2

Project Number:

File Name: 240068-M0202 Plotted: 5/28/2024 3:58 PM

CONSULTING

ENGINEERS

240068

7900 Triad Center Drive, Suite 200 Greensboro, NC 27409-9075 t: 336 855 0993

NC License No. F-0508

GREENSBORO, NC

CORPORATE OFFICE

ASHEVILLE, NC

CHARLESTON, SC

CHARLOTTE, NC

CHARLOTTESVILLE, VA

RALEIGH-DURHAM, NC

WILMINGTON, NC

QUALITY. INTEGRITY. INNOVATION.

www.skaeng.com

SKA Consulting Engineers, Inc.

These drawings are instruments of service and shall remain the property of SKA Consulting Engineers, Inc. whether the project for which they are made is executed or not. These drawings are not to be used in part or in whole by the owner or any other person or agency on this or any other projects or extensions to this project except by agreement in writing and with appropriate compensation to SKA. © Copyright 2024 by SKA Consulting Engineers, Inc. all rights reserved except as permitted under the United States Copyright Act of 1976, no part of this document may be reproduced or distributed in any form or by any means without the written permission of SKA Consulting Engineers, Inc.

FO

R

C O

N

ST

R U

C

TI

O N

AH

U

R

EP

LA

C

EM

EN

T

FO

R

W

SF

C S

AD

M

IN

O

FF

IC

E

C

O R

PO

R

AT

E

SQ

U

AR

E

D R

W

IN

ST

O N

-S

AL

EM

, N

C

240068-G2002.DWG

PLAN NORTH

EXISTING

AHU-2

OA

RELIEF AIR

PNEUMATIC

CONTROL

PANEL

EXISTING

FLOOR

DRAIN

S

S

RETURN AIR

DAMPER

RELIEF AIR

DAMPER

DEMOLISH

REFRIGERANT PIPING

DOWN TO 1ST FLOOR

72" WIDE

INTAKE

LOUVER

72" WIDE

INTAKE

LOUVER

50X38

54X34

54X34

90X26

OUTSIDE AIR

DAMPER LOCATED

AT TOP OF OPENING

EXISTING PLENUM

RETURN AIR DUCT

TO REMAIN

Dwg.#

DEMOLITION NOTES

240068-MD3002.DWG

4 3

DEMOLISH EXISTING AIR HANDLING UNIT.

DEMOLISH SUPPLY AIR DUCT TO POINT SHOWN. KEEP EXISTING DISTRIBUTION INTACT. REFER TO SECTION 1 / M1.1.

DEMOLISH OUTSIDE AIR DUCT TO POINT SHOWN. REFER TO SECTION 1 / M1.1.

REMOVE OUTSIDE AIR LOUVER SECTION AND OA PLENUM TO ALLOW REMOVAL OF AHU FROM EQUIPMENT ROOM. ITEMS TO BE

REINSTALLED UNDER NEW WORK.

DEMOLISH PNEUMATIC CONTROL PANEL AND AIR LINES ASSOCIATED WITH THE AHU.

EXISTING PLASMA AIR BIOPOLAR IONIZATION SYSTEM TO REMAIN.

DEMOLISH EXISTING CONDENSING UNIT, COMPLETE. INCLUDING UNIT, PIPING, ELECTRICAL CONNECTIONS, ETC. SEE WORK ON M2.1.

EXISTING RELIEF LOUVER TO REMAIN.

EXISTING RELIEF AIR DAMPER TO REMAIN. DEMOLISH PNEUMATIC DAMPER ACTUATOR.

REMOVE SUPPLY AIR DUCT SMOKE DETECTOR. RELOCATE UNDER NEW WORK.

DEMOLISH REFRIGERANT PIPING (TYP. 2 SETS)

RS/RL

RS/RL

AHU-2OA

RELIEF AIR

EXISTING

FLOOR

DRAIN

S

S

RETURN AIR

DAMPER

RELIEF AIR

DAMPER

REFRIGERANT

PIPING DOWN

TO 1ST FLOOR

72" WIDE

INTAKE

LOUVER

72" WIDE

INTAKE

LOUVER

50X38

54X34

54X34

90X26

OUTSIDE AIR

DAMPER

EXIST. PLENUM

RETURN AIR DUCT

NEW ELECTRIC

DUCT HEATER,

EDH-2

SET AHU ON STRUCTURAL

STEEL TO ALLOW FOR

REQUIRED TRAP DEPTH AND

CONDENSATE DRAINAGE

VFD

REINSTALL DUCT

DETECTOR AS SHOWNEXISTING PLASMA

AIR SYSTEM

Dwg.#

NEW WORK NOTES

240068-M3002.DWG

NEW AIR HANDLING UNIT. REFER TO EQUIPMENT SCHEDULE ON SHEET M1.1.

RECONNECT SUPPLY AIR DUCT TO POINT SHOWN. PROVIDE TRANSITION DUCT.

RECONNECT OUTSIDE AIR DUCT TO POINT SHOWN. PROVIDE TRANSITION DUCT.

REINSTALL OUTSIDE AIR LOUVER SECTION AND OA PLENUM AFTER NEW UNIT IS BROUGHT INTO EQUIPMENT ROOM. REINSTALL OUTSIDE

TRANSITION DUCT.

PROVIDE NEW CONDENSING UNIT COMPLETE INCLUDING UNIT, PIPING, ELECTRICAL CONNECTIONS, ETC. REFER TO EQUIPMENT

SCHEDULE ON SHEET M3.1.

ROUTE NEW REFRIGERANT PIPING FROM NEW AHU TO NEW CONDENSING UNIT. SIZE PIPING IN ACCORDANCE WITH MANUFACTURER'S

INSTRUCTIONS. SEE WORK ON M2.1.

ROUTE FULL SIZE CONDENSATE TO EXISTING FLOOR DRAIN.

PROVIDE NEW MODULATING DAMPER AND 24 VAC DAMPER MOTOR.

PROVIDE NEW DDC CONTROL PANEL, 120V.

MAINTAIN A MIN. OF 3' CLEARANCE FOR FILTER MAINTENANCE.

PROVIDE NEW 24 VAC DAMPER MOTOR.

RS/RL

RS/RL

SECOND FLOOR DEMOLITION PLAN

240068-MD3002.DWG

M2.2

SECOND FLOOR NEW WORK PLAN

240068-M3002.DWG

M2.2

ALL WORK SHOWN ON THIS DRAWING SHALL BE BID ALTERNATE NO. 1

EL

TR

IC

AL

L

EG

EN

D , S

PE

C

IF

IC

AT

IO

N S, A N

D S

C H

ED

U

LE

S

M ar k D at e

R ev is io n

Designed By:

Drawn By:

Checked By:

Date:

JMB

MRS

JMB

05-29-2024

E1.1

Project Number:

File Name: 240068-E0101 Plotted: 5/28/2024 4:48 PM

CONSULTING

ENGINEERS

240068

7900 Triad Center Drive, Suite 200 Greensboro, NC 27409-9075 t: 336 855 0993

NC License No. F-0508NJ License No. 24GA28097200AL License No. CA-3746-EFL License No. 9261GA License No. PEF002658MS License No. E-1463SC License No. 699VA License No. 0407001534WV License No. C01628-00WI License No. 2146-011

GREENSBORO, NC

CORPORATE OFFICE

ASHEVILLE, NC

CHARLESTON, SC

CHARLOTTE, NC

CHARLOTTESVILLE, VA

RALEIGH-DURHAM, NC

WILMINGTON, NC

QUALITY. INTEGRITY. INNOVATION.

www.skaeng.com

SKA Consulting Engineers, Inc.

These drawings are instruments of service and shall remain the property of SKA Consulting Engineers, Inc. whether the project for which they are made is executed or not. These drawings are not to be used in part or in whole by the owner or any other person or agency on this or any other projects or extensions to this project except by agreement in writing and with appropriate compensation to SKA. © Copyright 2024 by SKA Consulting Engineers, Inc. all rights reserved except as permitted under the United States Copyright Act of 1976, no part of this document may be reproduced or distributed in any form or by any means without the written permission of SKA Consulting Engineers, Inc.

FO

R

C O

N

ST

R U

C

TI

O N

AH

U

R

EP

LA

C

EM

EN

T

FO

R

W

SF

C S

AD

M

IN

O

FF

IC

E

C

O R

PO

R

AT

E

SQ

U

AR

E

D R

W

IN

ST

O N

-S

AL

EM

, N

C

E1.1 ELECTRICAL LEGEND, SPECIFICATIONS, AND SCHEDULES

E2.1 FIRST FLOOR ELECTRICAL PLANS

E2.2 SECOND FLOOR ELECTRICAL PLANS - ALTERNATE NO. 1

Dwg.#

DRAWING INDEX:

240068-E1001.DWG

GENERAL:

REFER TO GENERAL AND SPECIAL CONDITIONS, ETC. OF

THE CONTRACT REGARDING THE INSURANCE, TEMPORARY

UTILITIES, AND OTHER ITEMS AFFECTING THIS CONTRACT.

THE WORK COVERED IN THE SPECIFICATIONS AND SHOWN

ON THE DRAWINGS CONSISTS OF PROVIDING A COMPLETE

SYSTEM INCLUDING LABOR, MATERIALS, ETC.

THE TERM "PROVIDE" USED THROUGHOUT

SPECIFICATIONS AND ON DRAWINGS SHALL MEAN TO

"FURNISH, INSTALL AND CONNECT WITH ALL RELATED

ACCESSORIES AS REQUIRED FOR COMPLETE

INSTALLATION READY FOR USE."

COMPLY WITH ALL CODES, LAWS AND REGULATIONS

APPLICABLE TO ELECTRICAL INSTALLATION, INCLUDING

LATEST NATIONAL ELECTRICAL AND OTHER APPLICABLE

CODES.

THE ENTIRE INSTALLATION SHALL COMPLY WITH THE

REQUIREMENTS OF THE NORTH CAROLINA STATE

BUILDING CODE WHICH INCLUDES THE LATEST EDITION OF

THE NATIONAL ELECTRICAL AND ALL OTHER APPLICABLE

CODES, WITH LATEST REVISIONS.

THIS CONTRACTOR SHALL PAY ALL INSPECTION FEES AND

SHALL INCLUDE THE COST OF SUCH FEES IN HIS

PROPOSAL.

CHECK AND VERIFY WITH THE OWNER ALL OTHER

CONTRACT DOCUMENTS FOR THE PROJECT, THE EXACT

REQUIREMENTS FOR PROVIDING REQUIRED AND

COMPLETE SERVICES FOR EQUIPMENT, SYSTEMS, ETC., AS

SHOWN OR INDICATED. MINOR CHANGES IN OUTLET,

LIGHT AND EQUIPMENT LOCATION MAY BE MADE AT ANY

TIME PRIOR TO ROUGHING-IN OF THE ELECTRICAL WORK

WITHOUT ANY ADDITIONAL COSTS.

SUBMIT ELECTRONIC SUBMITTAL DATA FOR APPROVAL

FOR ALL MATERIALS AND EQUIPMENT. PRIOR TO

SUBMITTAL, THE CONTRACTOR SHALL STAMP ALL SHOP

DRAWINGS AND SUBMITTAL DATA AS "APPROVED",

INDICATING FULL COMPLIANCE WITH THE DRAWINGS AND

SPECIFICATIONS. SHOP DRAWINGS AND SUBMITTAL DATA

WILL NOT BE REVIEWED WITHOUT THE "APPROVED"

STAMP.

SHOP DRAWINGS AND SUBMITTAL DATA SHALL BE

CLEARLY MARKED AND EQUIPMENT SIZES, CAPACITIES,

ETC. INDICATED FOR THE PROJECT. INDICATE CLEARLY

THE EXACT REQUIREMENTS FOR ACCESS FOR SERVICE

AND MAINTENANCE AND MINIMUM CLEARANCES AS

REQUIRED BY THE MANUFACTURERS AND FOR

COMPLIANCE WITH ALL APPLICABLE CODES. ALL SHOP

DRAWINGS SHALL BE SUBMITTED AT SAME TIME AS SOON

AS POSSIBLE AFTER AWARD OF CONTRACT.

NO MATERIALS OR EQUIPMENT SHALL BE PLACED ON THE

JOB SITE, OR INSTALLED, WITHOUT PRIOR APPROVAL BY

THE ENGINEER.

FURNISH TO THE ENGINEER TWO (2) SETS OF MARKED UP

ELECTRICAL PRINTS WITH ALL DEVIATIONS AND

CORRECTIONS SHOWING THE AS-BUILT AND DIMENSIONED,

IF NECESSARY, LOCATIONS, ELEVATIONS, ETC. OF ALL

CONDUITS, EQUIPMENT, BOXES, ETC., UNDERGROUND, IN

WALLS, ABOVE CEILINGS AND OTHERWISE CONCEALED,

WHICH WILL REQUIRE SERVICE AND MAINTENANCE.

WATERPROOF ALL CONDUITS, ETC. THRU WALLS, FLOORS,

ROOF, ETC. AND ALL CUT AND PATCHED AREAS WHICH

ARE SUBJECT TO MOISTURE PENETRATION.

CODES AND STANDARDS:

MATERIALS INSTALLED IN THIS CONTRACT SHALL

CONFORM TO THE STANDARDS LISTED BELOW WHERE

SUCH STANDARDS ARE APPLICABLE AND SHALL BE NEW

AND FIRST CLASS IN ALL RESPECTS.

UNDERWRITER'S LABORATORIES, INC. STANDARDS AND

APPROVED LISTINGS (UL)

ELECTRICAL TESTING LABORATORIES STANDARDS (ETL)

CERTIFIED BALLAST MANUFACTURER'S STANDARDS (CBM)

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

STANDARDS (NEMA)

NORTH CAROLINA STATE BUILDING CODE, LATEST EDITION

WHICH INCLUDES THE NATIONAL ELECTRICAL CODE (NEC)

WITH LATEST REVISIONS.

INSULATED POWER CABLE ENGINEERS ASSOCIATION

STANDARD (IPCEA)

EDISON ELECTRICAL INSTITUTE (EEI)

AMERICAN NATIONAL STANDARDS INSTITUTE STANDARDS

(ANSI)

AMERICAN SOCIETY FOR TESTING MATERIALS STANDARDS

(ASTM)

ELECTRICAL AND OTHER EQUIPMENT AND/OR MATERIALS

THAT ARE DEFECTIVE, OR ARE DAMAGED IN THE COURSE

OF CONSTRUCTION, SHALL BE REMOVED AND REPLACED

BY THIS CONTRACTOR AT HIS EXPENSE.

DEPARTURES AND/OR DEVIATIONS FROM THE

SPECIFICATIONS SHALL BE REQUESTED IN WRITING BY

THE CONTRACTOR FROM THE ENGINEER AND NO SUCH

DEPARTURES AND/OR DEVIATIONS SHALL BE MADE

WITHOUT WRITTEN APPROVAL FROM THE ENGINEER.

WORKMANSHIP SHALL BE OF THE HIGHEST GRADE,

PERFORMED BY MECHANICS SKILLED IN THE INSTALLATION

OF THIS TYPE OF WORK, AND LICENSED BY THE PROPER

AUTHORITIES TO PERFORM THE WORK.

ELECTRICAL DEMOLITION:

UNLESS NOTED OTHERWISE DISCONNECT AND REMOVE

EXISTING EQUIPMENT AND/OR DEVICES AS INDICATED ON THE

DRAWINGS OR AS REQUIRED TO ACCOMMODATE

CONSTRUCTION. REMOVE CONDUCTORS IN CONDUIT

COMPLETELY BACK TO THE SOURCE WITHOUT CREATING

ADDITIONAL DEMOLITION OR REPAIR WORK FOR OTHER

TRADES. FOR BRANCH CIRCUITS THAT ARE REMOVED

ENTIRELY, TURN ASSOCIATED CIRCUIT BREAKERS TO THE 'OFF'

POSITION AND LABEL AS 'SPARE'. EXISTING CONDUITS AND

CONDUCTORS ARE PERMITTED TO BE REUSED TO THE EXTENT

PRACTICABLE.

WHEN EXISTING CIRCUITS THAT ARE TO REMAIN IN SERVICE

ARE INTERRUPTED BY DEMOLITION, REWORK AND REINSTALL

CIRCUITS AS REQUIRED.

TURN ANY DESIRED MATERIAL OVER TO THE OWNER AS

DIRECTED. REMOVE AND DISPOSE OF MATERIAL ACCORDING

TO APPLICABLE LAW THAT IS NOT TO BE TURNED OVER TO THE

OWNER.

PATCH SURFACES TO MATCH AND PROVIDE COVER PLATES

WHERE BOXES REMAIN AND ARE MADE SPARE.

WIRING METHODS:

FOR CONNECTIONS TO MOTORS USE LIQUID TIGHT FLEXIBLE

CONDUIT.

SUPPORT AND ATTACH ALL CONDUITS, BOXES, ETC. WITH

APPROVED HANGERS, CLAMPS, ETC. AS REQUIRED BY CODES.

DO NOT SUPPORT CONDUITS OR CABLES FROM DUCTWORK,

PIPING, ANY PART OF CEILING TILES OR CEILING SUPPORT

SYSTEM, ETC. PROVIDE SUPPLEMENTARY STEEL SUPPORTS

BETWEEN JOISTS, BEAMS, OR PURLINS, TRUSSES, ETC. WIRE

TYPE OR PERFORATED HANGERS WILL NOT BE PERMITTED.

PROVIDE TYPED CIRCUIT INDEX FOR ALL REVISED PANELS AND

EQUIPMENT, SHOWING ALL CIRCUIT DESIGNATIONS, INCLUDING

ROOM NAMES, EQUIPMENT AND AREAS…

This is the start of the file's text. The full file is on GovTribe.