24002038.01_Ypsilanti HS Corridor Access Control - Reviewed - BCC Approved w Conditions_20240812.pdf
PDF 5 MB Posted
- Solicitation number
- RFP-YCS-240000002995-3
- Issued by
- Washtenaw County, Michigan
About this file
This document is a review and approval from the Department of Licensing and Regulatory Affairs for a construction project at Ypsilanti High School in Ypsilanti, Michigan. The project consists of installing new interior doors in the existing southwest vestibule, southwest stairwell, and lunch room area to control access into specific areas of the building during scheduled times without interfering with emergency egress pathways. The review includes comments regarding requirements for fire protection system shop drawings, fire and smoke-resistant penetrations, and maintenance of means of egress during construction. The project will take place at the Ypsilanti High School located at 2095 Packard St, Ypsilanti, MI 48197.
The document outlines construction specifications for the new doors, including requirements for aluminum framing, FRP doors with half-lite, and tempered glass. It also includes details on the door hardware, glazing, gypsum board assemblies, and interior painting. No specific pricing terms, funding sources, or incumbent contractors are mentioned.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Reviewer Name Reviewer Email Reviewer Phone
Kevin Oglesbee OglesbeeK@michigan.gov 517-582-8582
Department of Licensing and Regulatory Affairs
Report Date: 08/09/2024 Description : THIS PROJECT CONSISTS OF PLACING NEW INTERIOR DOORS IN THE EXISTING SOUTH WEST VESTIBULE OF THE MAIN FLOOR, NEW INTERIOR DOORS AT THE SOUTH WEST STAIRWELL ON TWO LEVELS, AND NEW INTERIOR DOORS AT TWO LOCATIONS OF THE EXISTING LUNCH ROOM AREA OF THE LOWER LEVEL. NEW DOORS WILL BE TO CONTROL ACCESS INTO SPECIFIC AREAS OF THE BUILDING DURING SCHEDULED TIMES AND WILL NOT INTERFERE WITH EMERGENCY EGRESS PATHWAYS.
Address : 2095 PACKARD ST, YPSILANTI, MI, 48197 Record Type : Bureau of Construction Codes Plan Review Application Document Filename : 24002038.01_Ypsilanti HS Corridor Access Control.pdf
Reviewer Contact Information:
Markups for this Approved Document or Plan
Final Report - Approved
Comment ID Page Ref Reviewer : Department Review Comments
1 A000 Kevin Oglesbee : Building Please ensure to submit all required plans before beginning construction.
[A] 107.2.2 Fire protection system shop drawings. Shop drawings for the fire protection system(s) shall be submit-ted to indicate conformance to this code and the construc-tion documents and shall be approved prior to the start of system installation. Shop drawings shall contain all infor-mation as required by the referenced installation standards in Chapter 9.
2 A000 Kevin Oglesbee : Building MRHB2015 - 109.3.6 Fire and smoke-resistant penetrations. Protection of joints and penetrations in fire-resistance-rated assemblies, smoke barriers and smoke partitions shall not be concealed from view until inspected and approved.
3 A000 Kevin Oglesbee : Building MRHB2015 - 1505.2 Maintenance of means of egress. Required means of egress shall be maintained at all times during construction, demolition, remodeling or alterations and additions to any building.
General Comments
1st Floor Ottawa Building 611 W. Ottawa Street Lansing, MI 48933
Application Number: PR2024BCC-002279
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2023 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
201 S. ANN ARBOR STREET
SALINE, MI 48176
P: 734.429.8900
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #24002038.00
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
AERIAL IMAGE
NO SCALE
VICINITY MAP
APPLICABLE CODES & SUMMARY
PROJECT DESCRIPTION
PROJECT DIRECTORY
CLIENT:
1885 PACKARD
YPSILANTI, MI 48195
PHONE: (734) 646-8120
CONTACT: AARON ROSE
EMAIL: facilitiesdirector@ycschools.us
ARCHITECTURAL
DESIGNER:
IMEG
201 S. ANN ARBOR ST.
SALINE, MI 48176
PHONE: (734) 418-9223
CONTACT: BILL KWASNIAK
EMAIL: bill.j.kwasniak@imegcorp.com
DRAWING INDEX
PROJECT #2402038.00
SPECIFICATIONS
/1
/2
:3 :3
A
M
PERMIT AND CONSTRUCTION
07/01/2024
A000
ARCHITECTURE COVERSHEET
Dale Niethammer
Bill Kwasniak
Zach Goeglein
24002038.01
07/01/2024
PERMIT AND CONSTRUCTION
Y P
S
IL
A N
T I
H S
C O
R R
ID
O
R A
C C
E S
S C
O N
T R
O L
.0
YPSILANTI HS CORRIDOR ACCESS
CONTROL
2095 PACKARD ST.
YPSILANTI, MI 48197
YPSILANTI COMMUNITY SCHOOLS
YPSILANTI COMMUNITY SCHOOLS
2095 PACKARD ST.
YPSILANTI, MI 48197
YPSILANTI HS CORRIDOR
ACCESS CONTROL
SHEET
NUMBER SHEET TITLE 0
/1
/2
O
W N
E R
R E
V
IE
W
/0
/2
P
E R
M
IT
A N
D C
O N
S T
R U
C T
IO
N
A000 ARCHITECTURE COVERSHEET ● ●
A001 GENERAL NOTES ● ●
A100 LEVEL 01 & 02 PARTIAL FLOOR & LIFE SAFETY PLAN ● ●
A101 LEVEL 01 ENLARGED FLOOR PLANS ● ●
A102 LEVEL 01 ENLARGED REFLECTED CEILING PLAN ● ●
A103 LEVEL 01 ELEVATIONS AND DETAILS ● ●
A104 LEVEL 02 PLANS AND ELEVATIONS ● ●
GRAND TOTAL: 7 BUILDING CODE: 2015 MICHIGAN BUILDING CODE (MBC 2015)
2015 MICHIGAN REHABILITATION CODE (MRC 2015)
FIRE CODE: NFPA: 101-2018 EDITION
LARA: STATE FIRE SAFETY BOARD, NEW AND EXISTING
SCHOOL, COLLEGE AND UNIVERSITY FIRE SAFETY
PLUMBING CODE: 2021 MICHIGAN PLUMBING CODE (MPC 2021)
MECHANICAL CODE: 2021 MICHIGAN MECHANICAL CODE (MMC 2021)
ELECTRICAL CODE: NFPA 70 (NEC) 2023 EDITION
LIFE SAFETY CODE: NFPA 101 2018 EDITION
USE GROUP: EXISTING E (EDUCATION)
GROSS BUILDING AREA: LEVEL 1: 173,126 SF
LEVEL 2: 184,818 SF
LEVEL 3: 13,130 SF
TOTAL: 371,074 SF (APPROXIMATE EXISTING)
BUILDING HEIGHT: 3 STORY
CONSTRUCTION TYPE: ASSUMED: IIA (111)
WORK AREA: LEVEL 1: 1,600 SF
LEVEL 2: 200 SF
LEVEL 3: NO WORK
TOTAL: 1,800 SF
FIRE SUPPRESSION: YES
FIRE ALARM: YES
YPSILANTI HIGH SCHOOL
THIS PROJECT CONSISTS OF PLACING NEW INTERIOR DOORS IN THE EXISTING SOUTH
WEST VESTIBULE OF THE MAIN FLOOR, NEW INTERIOR DOORS AT THE SOUTH WEST
STAIRWELL ON TWO LEVELS, AND NEW INTERIOR DOORS AT TWO LOCATIONS OF THE
EXISTING LUNCH ROOM AREA OF THE LOWER LEVEL. NEW DOORS WILL BE TO
CONTROL ACCESS INTO SPECIFIC AREAS OF THE BUILDING DURING SCHEDULED
TIMES AND WILL NOT INTERFERE WITH EMERGENCY EGRESS PATHWAYS.
SITE LOCATION
2095 PACKARD ST.
YPSILANTI, MI
PROJECT SITE
2095 PACKARD ST.
YPSILANTI, MI
PACKARD ST.
DIVISION 04 - MASONRY
SECTION 04 20 00 - UNIT MASONRY
MORTAR AND GROUT MATERIALS
• Masonry Cement: ASTM C91/C91M, Type N.
• Portland Cement: ASTM C150/C150M, Type I.
• Mortar Aggregate: ASTM C144.
• Grout Aggregate: ASTM C404.
• Pigments for Colored Mortar: Pure, concentrated mineral pigments specifically intended for mixing into mortar and complying with ASTM C979/C979M.
• Color(s): Match existing.
• Water: Clean and potable.
ACCESSORIES
• Cleaning Solution: Non-acidic, not harmful to masonry work or adjacent materials.
DIVISION 05 – METALS
SECTION 05 40 00 - COLD-FORMED METAL FRAMING
FRAMING SYSTEM
• Provide primary and secondary framing members, bridging, bracing, plates, gussets, clips, fittings, reinforcement, and fastenings as required to provide a complete framing system.
FRAMING MATERIALS
• Studs and Track: ASTM C955; studs formed to channel, "C", or "Sigma" shape with punched web; U-shaped track in matching nominal width and compatible height.
• Framing Connectors: Factory-made, formed steel sheet.
• Material: ASTM A653/A653M SS Grade 33 and 40 (minimum), with G90/Z275 hot dipped galvanized coating for base metal thickness less than 10 gage, 0.1345 inch, and factory punched holes and slots.
FASTENERS
• Self-Drilling, Self-Tapping Screws, Bolts, Nuts and Washers: Hot dip galvanized per ASTM A153/A153M.
• Anchorage Devices: Powder actuated.
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
SECTION 07 92 00 - JOINT SEALANTS
JOINT SEALANT APPLICATIONS
• Confirm compatibility with sealants and all adjacent materials prior to application.
• Interior Joints: Do not seal interior joints unless specifically indicated to be sealed. Interior joints to be sealed include, but are not limited to, the following items.
a. Joints between door, window, and other frames and adjacent construction.
b. Joints between dissimilar materials.
c. Other joints indicated below.
• Do not seal the following types of joints.
a. Joints indicated to be treated with manufactured expansion joint cover or some other type of sealing device.
b. Joints where sealant is specified to be provided by manufacturer of product to be sealed.
c. Joints where installation of sealant is specified in another section.
d. Joints between suspended panel ceilings/grid and walls.
e. Exception: If wall deflects away from grid by 1/8"+, infill void with sealant matching grid
• Interior Joints: Use nonsag polyurethane sealant unless otherwise indicated.
• Wall and Ceiling Joints in Non-Wet Areas: Acrylic emulsion latex sealant.
• Sealant Color: To match adjacent material or grout colors.
DIVISION 08 - OPENINGS
SECTION 08 41 13 - ALUMINUM FRAMED ENTRANCES AND STOREFRONTS
FRAMING SYSTEM
• Brackets and Reinforcements: Manufacturer's standard high-strength aluminum with non-staining, nonferrous shims for aligning system components.
• Fasteners and Accessories: Manufacturer's standard corrosion-resistant, non-staining, nonbleeding fasteners and accessories compatible with adjacent materials. Where exposed shall be stainless steel.
• Perimeter Anchors: When steel anchors are used, provide insulation between steel material and aluminum material to prevent galvanic action.
• Install aluminum-framed storefront system level, plumb, square, true to line, without distortion, anchored securely in place to structural support, and in proper relation to.
• Set sill members in bed of sealant or with gaskets.
• Separate aluminum and other corrodible surfaces from sources of corrosion or electrolytic action at points of contact with other materials.
• Tubular aluminum sections, factory fabricated, factory finished, thermally broken, vision glass, related flashings, anchorage and attachment devices.
a. 2” profile x 4 1/2” depth.
• Finish: Dark bronze anodized aluminum finish (to match existing).
a. Class 2 (0.4 mils min.) anodized finish acceptable where components are used for interior applications only.
SECTION 08 71 00 - DOOR HARDWARE
GENERAL REQUIREMENTS
• Provide hardware as specified and/or as required to make doors fully functional, compliant with applicable codes, and secure to the extent indicated.
• Provide products that comply with the following:
a. Applicable provisions of federal, state, and local codes and ordinances.
• Manufacturer, style, and finish of all door hardware elements shall match existing building standard, UNO.
WARRANTY
• Closers shall carry manufacturer's 30-year warranty against manufacturing defects and workmanship.
• Locksets shall carry manufacturer's 3-year warranty against manufacturing defects and workmanship.
• Exit Devices shall carry manufacturer's 3-year warranty against manufacturing defects and workmanship.
• Continuous gear hinges shall carry manufacturer's lifetime warranty to be free from defects in material and workmanship.
• Balance of items shall carry a manufacturer's 1-year warranty against manufacturing defects and workmanship.
• During the warranty period, replace defective work, including labor, materials and other costs incidental to the work.
INSTALLATION
• Install hardware according to manufacturer’s installations and template dimensions. Attach all items of finish hardware to doors, frames, walls, etc. with fasteners furnished and required by the manufacture of the item.
• Provide blocking/reinforcement for all wall mounted Hardware.
• Reinforced aluminum door and frames will be drilled and tapped for machine screws.
• Inspect material furnished, its installation and adjustment, and instruct the Owner's personnel in adjustment, care and maintenance of hardware.
• Locksets and exit devices shall be inspected after installation and after the HVAC system is in operation and balanced, to insure correct installation and proper operation.
• Closers shall be inspected and adjusted after the HVAC system is in operation and balanced, to insure correct installation and proper operation.
SECTION 08 80 00 - GLAZING
STANDARDS/ PERFORMANCE REQUIREMENTS
• CPSC 16 CFR 1201 Cat I and Cat II for safety glass
• ANSI Z97.1 for safety glass
GLAZING
• Interior: 1/4” (minimum) glazing (thicker as recommended by manufacturer given opening sizes.) Perform Work in accordance with GANA Glazing Manual glazing installation methods.
• General: provide fully laminated safety glazing in conditions required by the Michigan Building Code.
GLASS MATERIALS
• Heat-Strengthened and Fully Tempered Types: ASTM C1048, Kind HS and FT.
WARRANTY
• 10 years from date of Substantial Completion.
DIVISION 09 - FINISHES
WOOD FRAMING MATERIALS
• Where wood framing is allowed for non-load bearing gypsum board assemblies, framing to comply with Rough
Carpentry specifications indicated elsewhere in the Construction Documents.
• Wood Framing Allowed: NO
SECTION 09 21 16 - GYPSUM BOARD ASSEMBLIES
METAL FRAMING MATERIALS
• Non-Loadbearing Framing System Components: ASTM C645; galvanized sheet steel, of size and properties necessary to comply with ASTM C754 for the spacing indicated, with maximum deflection of wall framing of L/240 at 5 psf.
• Partition Head to Structure Connections: Provide track fastened to structure with legs of sufficient length to accommodate deflection, for friction fit of studs cut short and fastened as indicated on drawings.
BOARD MATERIALS
• Install per most current version of ASTM C840 (Standard Specification for Application and Finishing of Gypsum
Board)
• Gypsum Wallboard: Paper-faced gypsum panels as defined in ASTM C1396/C1396M; sizes to minimize joints in place; ends square cut.
a. Type: 5/8 inch Type X Abuse Resistance
b. Application: Use for vertical surfaces, unless otherwise indicated.
ACCESSORIES
• Beads, Joint Accessories, and Other Trim: ASTM C1047, galvanized steel, rolled zinc, or extruded aluminum, unless noted otherwise. Provide pre-finished aluminum accessories where indicated on drawings, or where trim is otherwise to be left exposed.
• Control Joints: Install per most current version of ASTM C840. In addition to C840:
• Install (1) control joint on each side of cross corridor bulkheads.
• Materials: ASTM C475 and as recommended by gypsum board manufacturer for project conditions.
• Acoustic insulation: ASTM C665; Fiberglass, friction fit type, unfaced. Acoustic insulation to be applied in thickness as required to meet STC requirement shown on drawings, or to fill wall cavity depth if acoustic insulation is required by wall type and no STC is identified.
• Acoustic sealant: Acrylic emulsion latex or water-based elastomeric sealant; do not use solvent-based non-curing butyl sealant.
SECTION 09 91 23 - INTERIOR PAINTING
GENERAL REQUIREMENTS
• Products, surface preparation and application shall comply with manufacturers written instructions and with MPI
Standards.
• Products used shall be compatible with one another and with substrates.
• Paints and primers to be manufacturer's highest grade zero-VOC product.
• Remove hardware, cover plates, and similar items in place that are removable. If removal is impractical or impossible because of size or weight of item, provide surface-applied protection before surface preparation and finishing.
• Do not apply finishes over labels of independent testing agencies or equipment name, identification, performance rating or nomenclature plates.
• Provide painting continuous over entire surface from corner/edge to corner/edge.
• Provide (1) coat primer, (2) coats finish minimum.
• Patch and paint throughout area of work.
• Sheen: eggshell finish for walls, semi-gloss for door frames and other metal surfaces U.N.O
PAINT SYSTEMS - INTERIOR
• Interior Surfaces to be Painted, Unless Otherwise Indicated: gypsum board.
• Top Coat(s): Institutional Low Odor/VOC Interior Latex; MPI # 143, 144, 145, 146, 147, or 148.
• Primer: As recommended by top coat manufacturer for specific substrate.
• Dry Fall: Metals; exposed structure, including metal fabrications.
• Top Coat: Water Based Dry Fall for Galvanized Steel; MPI #133.
• Primer: As recommended by top coat manufacturer for specific substrate.
PRIMERS
• Primers: Provide the following unless other primer is required or recommended by manufacturer of top coats.
• Interior Institutional Low Odor/VOC Primer Sealer; MPI #149.
• Interior/Exterior Quick Dry Alkyd Primer for Metal; MPI #76.
1 06/10/2024 OWNER REVIEW
2 07/01/2024 PERMIT AND CONSTRUCTION
Kevin Oglesbee Note MRHB2015 - 1505.2 Maintenance of means of egress. Required means of egress shall be maintained at all times during construction, demolition, remodeling or alterations and additions to any building.
Kevin Oglesbee Note MRHB2015 - 109.3.6 Fire and smoke-resistant penetrations. Protection of joints and penetrations in fire-resistance-rated assemblies, smoke barriers and smoke partitions shall not be concealed from view until inspected and approved.
Kevin Oglesbee Note Please ensure to submit all required plans before beginning construction.
[A] 107.2.2 Fire protection system shop drawings. Shop drawings for the fire protection system(s) shall be submit-ted to indicate conformance to this code and the construc-tion documents and shall be approved prior to the start of system installation. Shop drawings shall contain all infor-mation as required by the referenced installation standards in Chapter 9.
ALIGN
ALIGN
GENERAL NOTES
1. THIS PROJECT SHALL COMPLY WITH ALL LOCAL, STATE AND FEDERAL LAWS, CODES, ORDINANCES, RULES, AND REGULATIONS OF PUBLIC AUTHORITIES GOVERNING THE WORK.
2. ALL PARTS OF THE WORK - INCLUDING MATERIALS, METHODS, ASSEMBLIES, ETC, MUST COMPLY WITH THE MINIMUM REQUIREMENTS OF THE GOVERNING REGULATIONS OF ALL FEDERAL, STATE, DISTRICT AND LOCAL AUTHORITIES HAVING JURISDICTION OVER THE PROJECT AS WELL AS THOSE GREATER REQUIREMENTS INDICATED BY THE CONTRACT DOCUMENTS. NO PART OF THE CONTRACT
DOCUMENTS MAY BE CONSTRUED TO REQUIRE OR PERMIT WORK CONTRARY TO A GOVERNING
REGULATION. WHERE THERE IS A DISCREPANCY BETWEEN THE GOVERNING CODE AND THE
DRAWINGS, THE MOST RESTRICTIVE CASE SHALL GOVERN. IN SUCH CASE, CONFER WITH
ARCHITECT PRIOR TO PROCEEDING.
3. FURNISH AND INSTALL ALL LABOR, MATERIALS, TOOLS, DUMPSTERS, PERMITS, ETC. TO PROVIDE A
COMPLETE AND FINISHED INSTALLATION PER THESE CONTRACT DOCUMENTS AND WHERE
SOMETHING IS NOT SPECIFIED, PER THE MOST STRINGENT INDUSTRY STANDARDS AND CODE
REQUIREMENTS.
4. ALL WORK SHALL BE PERFORMED BY QUALIFIED AND SKILLED WORKERS, IN A NEAT AND
WORKMANLIKE MANNER, AND IN ACCORDANCE WITH INDUSTRY STANDARDS AND PRACTICES.
5. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PERMITS AND INSPECTIONS RELATING TO THE
WORK, AND SHALL OBTAIN ALL FIELD APPROVALS ON THE WORK FROM REGULATING AGENCIES
WHERE REQUIRED.
6. CONTRACTOR OR CONSTRUCTION MANAGER SHALL COORDINATE BETWEEN VARIOUS TRADES FOR
ROUGH-IN REQUIREMENTS.
7. CONTRACTOR SHALL PROVIDE A SCHEDULE TO OWNER, ARCHITECT, ENGINEER AND SUB-
CONTRACTORS PRIOR TO THE START OF CONSTRUCTION OPERATIONS.
8. PROVIDE SHORING, BRACING, UNDERPINNING AND ANY OTHER MEANS REQUIRED TO PROTECT THE
SAFETY, INTEGRITY AND STABILITY OF ALL NEW AND EXISTING CONSTRUCTION.
9. THESE DRAWINGS ARE BASED ON DESIGN DRAWINGS. AS SUCH, ACTUAL CONDITIONS MAY VARY
FROM WHAT IS SHOWN. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL FIELD
CONDITIONS AND COORDINATING ANY CHANGES WITH ARCHITECT. ALL CHANGES REQUIRED TO
MEET THE INTENT OF THESE DRAWINGS SHALL BE AT THE CONTRACTOR'S COST.
10. TEMPORARY REMOVAL OF ANY AND ALL EXISTING MISCELLANEOUS ITEMS (I.E. CONDUIT, PIPING, LIGHTING, ETC.) FOR THE PURPOSE OF PERFORMING THIS WORK SHALL BE REINSTALLED BACK TO PRE-CONSTRUCTION LEVEL AS PART OF THIS PROJECT. NO ADDITIONAL FEES WILL BE AWARDED.
11. COORDINATE ALL CONSTRUCTION OPERATIONS WITH OCCUPANTS OF SPACE. SPACE SHALL REMAIN OCCUPIED DURING CONSTRUCTION AND CONTRACTOR SHALL ENSURE THAT ALL PATHS OF EGRESS ARE FREE OF CONSTRUCTION MATERIALS, DEBRIS, TOOLS, ETC THROUGHOUT THE DURATION OF
THE PROJECT.
12. MAINTAIN EXITS, EXIT LIGHTING, FIRE PROTECTIVE DEVICES, AND ALARMS IN CONFORMANCE WITH
CODES AND ORDINANCES.
13. VERIFY THE SIZES, LOCATIONS, ELEVATIONS AND DETAILS OF EXISTING CONDITIONS THAT AFFECT THE WORK. NOTIFY THE ARCHITECT OF ANY DISCREPANCIES IN DIMENSIONS, SIZES, LOCATIONS AND
CONDITIONS BEFORE PROCEEDING WITH THE WORK.
14. PROVIDE THOROUGH CLEANUP OF ENTIRE SCOPE OF WORK AND ANY SURROUNDING AREAS
AFFECTED BY THE CONSTRUCTION OPERATIONS.
15. PROTECT AREA OF WORK AND ADJACENT AREAS FROM DAMAGE.
16. LEAVE JOB SITE BROOM CLEAN AT THE END OF EACH WORKING DAY'S OPERATIONS.
17. PROVIDE ALL TEMPORARY PROTECTION MEASURES REQUIRED TO ENSURE CONTROL OF DUST
TRANSMISSION THROUGHOUT THE PROJECT.
18. DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS GOVERN. IN CASE OF CONFLICT, CONSULT THE
ARCHITECT.
19. MAINTAIN WORK AREAS SECURE AND LOCKABLE DURING CONSTRUCTION. COORDINATE WITH
OWNER TO ENSURE SECURITY.
20. REVIEW DOCUMENTS, VERIFY DIMENSIONS AND FIELD CONDITIONS AND CONFIRM THAT WORK IS
BUILDABLE AS SHOWN. REPORT ANY CONFLICTS OR OMISSIONS TO THE ARCHITECT FOR
CLARIFICATION PRIOR TO PERFORMING ANY WORK IN QUESTION.
21. COORDINATE WORK WITH THE OWNER, INCLUDING SCHEDULING TIME AND LOCATIONS FOR
DELIVERIES,BUILDING ACCESS, USE OF BUILDING SERVICES AND FACILITIES, AND USE OF
ELEVATORS. MINIMIZE DISTURBANCE OF BUILDING FUNCTIONS AND OCCUPANTS.
22. OWNER WILL PROVIDE WORK NOTED "BY OTHERS" OR "NIC" UNDER SEPARATE CONTRACT. INCLUDE
SCHEDULE REQUIREMENTS IN CONSTRUCTION PROGRESS SCHEDULE AND COORDINATE TO
ASSURE ORDERLY SEQUENCE OF INSTALLATION.
23. AS-BUILT DRAWINGS (RECORD DRAWINGS): CONTRACTOR SHALL RECORD ON AS-BUILT DRAWINGS ANY DEVIATIONS FROM THE DESIGN DRAWINGS. DRAWINGS SHALL BE SUBMITTED TO OWNER AND
ARCHITECT AFTER COMPLETION OF PROJECT.
DEMOLITION
1. COMPLY WITH APPLICABLE CODES AND REGULATIONS FOR DEMOLITION OPERATIONS AND SAFETY OF ADJACENT STRUCTURES AND THE PUBLIC. COMPLY WITH APPLICABLE REQUIREMENTS OF NFPA
241 (STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION
OPERATIONS; 2009)
2. DRAWINGS SHOWING EXISTING CONSTRUCTION AND UTILITIES ARE BASED ON FIELD OBSERVATION
AND EXISTING RECORD DOCUMENTS ONLY. VERIFY THAT CONSTRUCTION AND UTILITY
ARRANGEMENTS ARE AS SHOWN AND REPORT DISCREPANCIES BEFORE DISTURBING EXISTING
INSTALLATION. BEGINNING OF DEMOLITION WORK CONSTITUTES ACCEPTANCE OF EXISTING
CONDITIONS THAT WOULD BE APPARENT UPON EXAMINATION PRIOR TO STARTING DEMOLITION.
3. PROTECT EXISTING PROPERTY, SITE ELEMENTS, FINISHES, EQUIPMENT, REMAINING SURFACES, UTILITIES AND SERVICES WITHIN AND ADJACENT TO WORK FROM DAMAGE DUE TO OPERATIONS.
SHORE AND BRACE EXISTING CONSTRUCTION DURING CUTTING OPERATIONS AS REQUIRED TO
PREVENT CRACKING, MOVEMENT, OR COLLAPSE OF EXISTING ASSEMBLIES, SURFACES AND
MATERIALS. REPLACE OR REPAIR ANY ITEM OR ELEMENT DAMAGED AS A RESULT OF
CONSTRUCTION OPERATIONS OR A LACK OF ADEQUATE PROTECTION BY CONTRACTOR.
4. IT IS THE CONTRACTOR’S RESPONSIBILITY TO PROVIDE ADEQUATE SHORING AND BRACING DURING CONSTRUCTION TO ACCOUNT FOR ALL FORCES, INCLUDING BUT NOT LIMITED TO; FORCES FROM
GRAVITY, EARTH, WIND, AND UNBALANCED FORCES DUE TO CONSTRUCTION SEQUENCE.
5. SAW CUTTING OF NEW OPENINGS IN EXISTING CONCRETE AND/OR MASONRY WALLS SHALL BE
DONE WITHOUT OVERCUTTING BEYOND THE BOUNDARIES OF THE INTENDED OPENING. ANY
STRUCTURAL REPAIRS REQUIRED BY THE STRUCTURAL ENGINEER AS A RESULT OF OVERCUTTING
BEYOND THE BOUNDARIES OF AN OPENING SHALL BE PAID FOR BY THE SAW CUTTING
CONTRACTOR.
6. PROTECT EXISTING WORK TO REMAIN AND PROTECT THE WORKERS AND THE PUBLIC FROM
CONSTRUCTION OPERATIONS. TO THAT END, CONSTRUCT TEMPORARY DUST PROOF ENCLOSURES
TO PREVENT DUST MIGRATION INTO OCCUPIED SPACES AND PROVIDE, ERECT, AND MAINTAIN
TEMPORARY BARRIERS AND SECURITY DEVICES TO PREVENT ACCESS TO AREAS THAT COULD BE
HAZARDOUS TO WORKERS OR THE PUBLIC.
7. DO NOT CLOSE OR OBSTRUCT ROADWAYS OR SIDEWALKS WITHOUT PERMIT AND CONDUCT
OPERATIONS TO MINIMIZE OBSTRUCTION OF PUBLIC AND PRIVATE ENTRANCES AND EXITS; DO NOT
OBSTRUCT REQUIRED EXITS AT ANY TIME; PROTECT PERSONS USING ENTRANCES AND EXITS
FROM REMOVAL OPERATIONS.
8. DO NOT BEGIN REMOVAL UNTIL BUILT ELEMENTS TO BE SALVAGED OR RELOCATED HAVE BEEN
REMOVED.
9. MAINTAIN SEPARATE DUMPSTER FACILITIES FOR CONSTRUCTION OPERATIONS. COORDINATE
DUMPSTER LOCATION WITH OWNER. PROVIDE ASPHALT PROTECTION FOR DUMPSTER.
IMMEDIATELY REMOVE DEBRIS, JUNK, AND TRASH FROM SITE AND AT THE END OF EACH WORK
DAY, LEAVE SITE IN CLEAN AND SAFE CONDITION, READY FOR SUBSEQUENT WORK AND AS
INDICATED IN SPECIAL CONDITIONS (WHERE APPLICABLE).
10. COORDINATE ANY REQUIRED UTILITY SHUT-DOWNS PRIOR TO BEGINNING CONSTRUCTION
OPERATIONS. PROVIDE OWNER A MINIMUM OF 24 HOUR NOTICE PRIOR TO PERFORMING ACTUAL
SHUT-DOWN WORK.
11. IF UTILITIES OR SERVICES ARE UNCOVERED THAT ARE NOT INDICATED ON DRAWINGS, ADVISE
OWNER AND DO NOT WORK IN IMMEDIATE AREA UNTIL INSTRUCTED BY OWNER.
12. REMOVE DESIGNATED PARTITIONS, CEILINGS COMPONENTS, BUILDING EQUIPMENT, AND FIXTURES.
13. REMOVE EXISTING WORK AS REQUIRED TO ACCOMMODATE NEW WORK, EVEN WHERE NOT
EXPRESSLY INDICATED ON DEMOLITION PLANS.
14. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COORDINATION WORK REQUIRED FOR A FINISHED
AND COMPLETE INSTALLATION OF ALL WORK BY ALL SUB-TRADES INCLUDED IN THE SCOPE OF
WORK INCLUDING ALL CUTTING AND PATCHING; THE EXTENT OF WHICH IS GENERALLY NOT
SPECIFICALLY SHOWN ON THE DRAWINGS.
15. CUT HOLES AND OPENINGS IN, OR REMOVE PORTIONS OF, EXISTING CONSTRUCTION NECESSARY FOR CONNECTION OF NEW ARCHITECTURAL ELEMENTS, MECHANICAL AND ELECTRICAL UTILITIES
AND SERVICES, EQUIPMENT AND SUPPORTS. PATCH AROUND MECHANICAL AND ELECTRICAL
PENETRATIONS. PATCH FLOORS, WALLS, AND CEILINGS DAMAGED BY DEMOLITION OPERATIONS, INCLUDING REMOVAL OF INDICATED MECHANICAL AND ELECTRICAL ITEMS, AND INDICATED WALL-, FLOOR-, AND CEILING-MOUNTED ITEMS. PATCH AND PAINT OPENINGS IN WALLS, FLOORS AND
CEILINGS CREATED BY DEMOLITION AND REMOVAL OPERATIONS. PATCH AND REPAIR BLEMISHES
AND HOLES IN EXISTING CONSTRUCTION SURFACES LEFT IN PLACE, AND SCHEDULED TO BE
EXPOSED, THAT HAVE BEEN DAMAGED DUE TO CONSTRUCTION OPERATIONS.
16. UNLESS OTHERWISE INDICATED, USE MATERIALS FOR PATCHING IDENTICAL TO EXISTING
MATERIALS. IF IDENTICAL MATERIALS ARE NOT AVAILABLE, OR CANNOT BE USED, USE MATERIALS MATCHING EXISTING ADJACENT SURFACES TO THE FULLEST EXTENT POSSIBLE WITH REGARD TO
VISUAL EFFECT. USE MATERIALS FOR PATCHING THAT RESULT IN EQUAL-OR-BETTER
PERFORMANCE CHARACTERISTICS. ALL CUTTING AND PATCHING SHALL BE THE RESPONSIBILITY
OF THE APPROPRIATE ARCHITECTURAL TRADE. FINAL APPROVAL OF REPAIR OR REPLACEMENT
SHALL BE AT DISCRETION OF ARCHITECT.
1. REFER TO GENERAL NOTES FOR ADDITIONAL REQUIREMENTS.
2. PARTITIONS ARE DIMENSIONED FROM FINISH FACE TO FINISH FACE OR COLUMN CENTERLINES, UNLESS OTHERWISE NOTED. MAINTAIN DIMENSIONS MARKED "CLEAR". ALLOW FOR THICKNESS OF
FINISHES.
3. COORDINATE AND PROVIDE BACKING FOR ITEMS ATTACHED OR MOUNTED TO WALLS OR CEILINGS.
4. UNDERCUT DOORS TO CLEAR TOP OF FLOOR FINISHES BY 1/4 INCH, UNLESS OTHERWISE NOTED.
5. ALL PARTITION TYPES ARE INDICATED ON PLAN.
6. DIMENSIONS LOCATING DOORS IN GYPSUM BOARD PARTITIONS ARE TO BE FROM FINISHED FACE OF
PARTITION TO THE INSIDE FACE OF FRAME.
7. PATCH AND REPAIR ANY FIREPROOFING DAMAGED OR REMOVED BY CONSTRUCTION.
8. ALL DIMENSIONS ARE FROM FINISHED FACE, DIMENSIONS SHALL GOVERN, DO NOT SCALE DRAWINGS.
9. WHERE NEW WORK ADJOINS EXISTING, SUCH NEW WORK SHALL BE PROPERLY INTEGRATED WITH THE
EXISTING TO ENSURE A UNIFORM APPEARANCE AND LEAVE NO EVIDENCE OF REMODELING.
10. "ALIGNED", AS USED IN THESE DOCUMENTS, SHALL MEAN TO ACCURATELY LOCATE FINISH FACES IN
THE SAME PLANE.
11. "TYPICAL" (OR "TYP"), AS USED IN THESE DOCUMENTS, SHALL MEAN THAT THE CONDITION IS THE SAME
REPRESENTATIVE FOR ALL SIMILAR CONDITIONS, U.N.O.
12. DESIGN BUILD CONTRACTOR SHALL DESIGN AND PROVIDE ALL FRAMING AND SUPPORT FOR NEW
PARTITIONS AND DOORS.
CONSTRUCTION NOTES
1. ENSURE SURFACES TO RECEIVE FINISHES ARE CLEAN, TRUE, AND FREE OF IRREGULARITIES. DO NOT
PROCEED WITH WORK UNTIL UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED.
2. PROTECT AREA OF WORK AND ADJACENT AREAS FROM DAMAGE.
3. CONTRACTOR TO PREPARE WALL, FLOOR AND CEILING SURFACES AS REQUIRED AND RECOMMENDED
BY MANUFACTURER TO RECEIVE NEW FINISHES AS INDICATED ON PLAN, INCLUDING FLOOR PREP.
4. PARTITIONS ARE DIMENSIONED FROM FINISH FACE TO FINISH FACE OR COLUMN CENTERLINES, UNLESS
OTHERWISE NOTED. MAINTAIN DIMENSIONS MARKED "CLEAR". ALLOW FOR THICKNESS OF FINISHES.
5. ALL FLOORING TRANSITIONS SHALL BE CENTERED UNDER THE DOOR IN THE CLOSED POSITION. COLOR
TO BE SELECTED FROM MANUFACTURER'S STANDARD COLORS.
6. REFER TO DOOR SCHEDULE FOR INDICATED DOOR AND FRAME FINISHES.
7. CONTRACTOR TO PROVIDE FINAL CLEAN OF SPACE BEFORE MOVE-IN.
FINISH NOTES
1. CONTRACTORS ARE ALSO ADVISED THAT OWNER WILL REMAIN OPERATIONAL DURING
CONSTRUCTION HOURS.
2. COORDINATE AND SCHEDULE ANY SHUTDOWNS AND HEAVY NOISE GENERATING ACTIVITIES WITH
OWNER PERSONNEL AT LEAST 24 HOURS PRIOR TO IMPLEMENTING TO ALLOW TIME FOR
COORDINATION.
3. LIFE SAFETY SYSTEM SHUTDOWNS (AND STARTUPS) SHALL BE COORDINATED WITH OWNER
PERSONNEL, AND LOCAL FIRE AUTHORITIES AND CENTRAL STATION MONITORING SERVICES (IF
APPLICABLE).
4. LIFE SAFETY SYSTEMS SHALL BE IN OPERATION DURING OCCUPIED AND UNOCCUPIED (I.E. NIGHT, WEEKEND, AND HOLIDAY) TIMES. PROVIDE FIRE WATCH DURING ALL TIMES THAT THE FIRE
SUPPRESSION SYSTEM AND/OR FIRE ALARM CONTROL PANEL (FACP) IS DEACTIVATED.
SHUT DOWNS
1. THIS PROJECT AREA MAY CONTAIN HAZARDOUS MATERIALS. IF THE CONTRACTOR SHOULD
ENCOUNTER ANY ITEMS SUSPECTED TO CONTAIN ASBESTOS, LEAD, OR MERCURY, CONTACT THE
PROJECT CONSTRUCTION MANAGER IMMEDIATELY FOR DIRECTION. DO NOT DISTURB THE
MATERIAL IN ITS LOCATION. PROJECT CONSTRUCTION MANAGER SHALL COORDINATE REMOVAL OF
ANY ITEMS SUSPECTED OF CONTAINING HAZARDOUS MATERIALS. REMOVAL OF HAZARDOUS
MATERIALS SHALL BE IN ACCORDANCE WITH EPA REQUIREMENTS AS WELL AS REQUIREMENTS OF
ANY OTHER AGENCIES WITH JURISDICTION OVER SUCH WORK.
HAZARDOUS MATERIALS NOTE
A101
SIM
A101
SIM
A101
SIM
A101
SIM
A101
A101
1 1
A
A
NAME
ELEVATION
T/WALL
1i
TAG-E
TAG
PATH #1i
REFERENCE OF
SIMILAR OR OPPOSITE
DETAIL NUMBER
(LOCATION ON SHEET)
SHEET NUMBER
AREA TO BE DETAILED
TAIL INDICATES DIRECTION
OF DETAIL SECTION
TAIL INDICATES DIRECTION
OF WALL SECTION
DIRECTION OF ELEVATION
SHEET NUMBER
DETAIL NUMBER
(LOCATION ON SHEET)
DIRECTION OF ELEVATION
SHEET NUMBER
DETAIL NUMBER
(LOCATION ON SHEET)
EXTERIOR ELEVATION MARKER
INTERIOR ELEVATION MARKER
ELEVATION DATUM REFERENCE
SHEET NOTE SYMBOL
EXISTING CONSTRUCTION
TO REMAIN
EXISTING CONSTRUCTION
TO BE DEMOLISHED
NEW CONSTRUCTION
EXISTING DOORS SHOWN
OPEN AT 45° IN EXISTING
CONSTRUCTION
NEW DOORS SHOWN OPEN
AT 90° IN NEW & EXISTING
CONSTRUCTION
SPOT ELEVATION REFERENCE
FACE OF CONSTRUCTION
TO BE ALIGNED WITH
EXISTING CONSTRUCTION
PARTITION TYPE REFERENCE
TAGS WITH DASH 'E' INDICATES THE
REFERENCED OBJECT IS EXISTING
UNDERLINED TAG INDICATES OBJECT IS IN-
SCOPE. IF NEW, ADDITIONAL INFORMATION
IS AVAILABLE IN A SCHEDULE, MATERIAL
LIST, OR SYMBOL LIST
EXIT ACCESS TRAVEL DISTANCE
TAG, REFER TO SCHEDULE
EGRESS PATH
DIRECTION OF EGRESS TRAVEL
PATH OF EXIT ACCESS
START OF PATH
COMMON PATH OF EGRESS
TRAVEL DISTANCE END POINT
GENERAL SYMBOL LIST
SPRINKLER
NORMAL BRANCH LUMINAIRE
SINGLE FACE EXIT SIGN
DOUBLE FACE EXIT SIGN
EMERGENCY UNIT
WALL/CEILING EMERGENCY
EXIT SIGN
SUPPLY/OUTSIDE AIR DUCT
SECTION
RETURN AIR DUCT SECTION
1i FIRE ALARM MANUAL PULL STATIONM
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2023 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
201 S. ANN ARBOR STREET
SALINE, MI 48176
P: 734.429.8900
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #24002038.01
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #2402038.01
12" = 1'-0"
/1
/2
:3 :3
A
M
2095 PACKARD ST.
YPSILANTI, MI 48197
YPSILANTI HS CORRIDOR
ACCESS CONTROL
A001
GENERAL NOTES
Dale Niethammer
Bill Kwasniak
Zach Goeglein
24002038.01
07/01/2024
PERMIT AND CONSTRUCTION
Y P
S
IL
A N
T I
H S
C O
R R
ID
O
R A
C C
E S
S C
O N
T R
O L
.0
1 06/10/2024 OWNER REVIEW
2 07/01/2024 PERMIT AND CONSTRUCTION
K-5264M ILLBROO KC_FO UNTAINSVITREO US CHINA
D D
K-5264M ILLBROO KC_FO UNTAINSVITREO US CHINA
K-5264M
ILLBROO
K
C_FO
UNTAINS
VITREO
US CHINA
K-5264M
ILLBROO
K
C_FO
UNTAINS
VITREO
US CHINA
K-5264M
ILLBROOK
C_F
OUNTAINS
VITREOU
S CHINA
K-5264M
ILLBROOK
C_F
OUNTAINS
VITREOU
S CHINA
K-5264MILLBROOK C_FOUNTAINS VITREOUS CHINAK-5264MILLBROOK C_FOUNTAINS VITREOUS CHINA
A101
A101
A101
A101
A
B
A
B
STAIR
B1
B102A
B102B
B102C
TRAINING
B114
WRESTLING
B115
GYMNASIUM
B111
CORRIDOR
B102
WEIGHT ROOM
E112
CONF. ROOM
D111
ATHLETIC OFFICE
D110
CORRIDOR
B101
COMMONS
D101
CAFETERIA
D102
WOMEN
B103
MEN
B104
DN
RAMP DOWN RAMP DOWN
DN
UP
EXIS
TIN
G E
G R E
SS
P
ATH
T O E
XIT
EXIS
TIN
G
EG
R E
SS
P
ATH
E X
IS
T
IN
G
E G
R E
S S
P A
T H
T O
E X
IT
B O
T H
D
IR
E C
T
IO
N S
EXIS
EG
R E
SS
P
ATH
EXISTING
EGRESS PATH
EXISTING
EGRESS PATH
EXISTING
EGRESS PATH
E X
IS
T
IN
E
R
E S
S P
A T
H
EXISTING
EGRESS PATH
E
XIS
R E
SS
P
ATH
EXISTING
EGRESS PATH
EXISTING
EGRESS PATH
A101
EXIT TO PARKING LOT
SCOPE OF WORK
LEVEL 01 KEY PLAN
B201C-E
CORRIDOR
B201
B201B-E
B201A-E
B203A-E
B203B-E
STAIR
B1
CORRIDOR
B202
STORAGE
B204
B202B
B202A
SPORTS DECK
B203
MUSIC
E233
CORRIDOR
E205
STAGE
E224
AUDITORIUM
D220
N.I.S.
DN
E
XIS
TIN
G E
G R
ES
S
P
ATH
T O
E
XIT
EXISTING
EGRESS PATH
EXISTING
EGRESS PATH
E X
IS
T
IN
G
E G
R E
S S
P A
T H
EXISTING EGRESS PATH
EXISTIN
G E
G R
SS
PA
TH
TO
E
XIT
A104
CORRIDOR
B202
D220A-E
D220B-E
E204-E
EXIT TO PARKING LOT
SCOPE OF WORK
LEVEL 02 KEY PLAN
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2023 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
201 S. ANN ARBOR STREET
SALINE, MI 48176
P: 734.429.8900
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #24002038.01
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #2402038.01
As indicated
/1
/2
:3 :3
A
M
2095 PACKARD ST.
YPSILANTI, MI 48197
YPSILANTI HS CORRIDOR
ACCESS CONTROL
A100
LEVEL 01 & 02 PARTIAL FLOOR & LIFE
SAFETY PLAN
Dale Niethammer
Bill Kwasniak
Zach Goeglein
24002038.01
07/01/2024
PERMIT AND CONSTRUCTION
Y P
S
IL
A N
T I
H S
C O
R R
ID
O
R A
C C
E S
S C
O N
T R
O L
.0
N O R
HT
1/8" = 1'-0"
LEVEL 01 - PARTIAL OVERALL / LIFE SAFETY PLAN
N O R
HT
1/8" = 1'-0"
LEVEL 02 - PARTIAL OVERALL / LIFE SAFETY PLAN
CORR.
D
K-5264M ILLBROO KC_FO UNTAINSVITREO US CHINA
K-5264M
ILLBROO
K
C_FO
UNTAINS
VITREO
US CHINA
K-5264M
ILLBROO
K
C_FO
UNTAINS
VITREO
US CHINA
K-5264M
ILLBROOK
C_F
OUNTAINS
VITREOU
S CHINA
K-5264M
ILLBROOK
C_F
OUNTAINS
VITREOU
S CHINA
A103
8" 2" 3'-3 1/2" 3'-3 1/2" 2"11"2" 3'-1" 3'-1" 2" 8"
CAFETERIA
D102
CORRIDOR
B101
CORRIDOR
B101
ATHLETIC OFFICE
D110
D102BD102A
A
NEW GYP BD
PARTITION
NEW INTERIOR ALUMINUM
STOREFRONT SYSTEM WITH
1/4" TEMPERED GLASS
NEW FRP DOORS
WITH HALF LITE
15'-8" +/-
A1033
8'-0 1/4"
4 1/2"
/2
4"
CAFETERIA
D102
COMMONS
D101
D102C
D102D
DN
RAMP DOWN
NEW GYP BD JAMB
TO UNDERSIDE OF
COLUMN SOFFIT
NEW INTERIOR ALUMINUM
STOREFRONT SYSTEM WITH
1/4" TEMPERED GLASS.
CENTER ON SOFFIT ABOVE
NEW FRP DOORS
WITH HALF LITE
STORAGE
C156
/2
/2
/4
A103
STAIR
B1
CORRIDOR
B102
B1
5'-4"
A
UP
NEW GYP BD
PARTITION
NEW INTERIOR ALUMINUM
STOREFRONT SYSTEM WITH
1/4" TEMPERED GLASS
NEW FRP DOORS
WITH HALF LITE
5' -3
EQ
2"
3' -0
2"
3' -0
2"
EQ
2"
A103 4
NEW 4'-0" SCREEN WALL CENTERED
ON TOP OF EXISTING HALF WALL
CAFETERIA
D102
COMMONS
D101
NEW GYP BD JAMB
TO UNDERSIDE OF
COLUMN SOFFIT
A103
E Q
E
Q
A103
NEW 4'-0" SCREEN WALL CENTERED ON
TOP OF EXISTING HALF WALL
CAFETERIA
D102
CORRIDOR
B101
COMMONS
D101
E Q
E Q
'-6
3' -3
3' -3
3' -3
3' -3
3' -3
3' -3
3' -3
3' -3
3' -3
3' -3
5'-5"
EQ EQ
/2
E Q
E Q
SCOPE OF WORK
LEVEL 01 KEY PLAN
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2023 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
201 S. ANN ARBOR STREET
SALINE, MI 48176
P: 734.429.8900
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #24002038.01
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #2402038.01
As indicated
/1
/2
:3 :3
A
M
2095 PACKARD ST.
YPSILANTI, MI 48197
YPSILANTI HS CORRIDOR
ACCESS CONTROL
A101
LEVEL 01 ENLARGED FLOOR PLANS
Dale Niethammer
Bill Kwasniak
Zach Goeglein
24002038.01
07/01/2024
PERMIT AND CONSTRUCTION
Y P
S
IL
A N
T I
H S
C O
R R
ID
O
R A
C C
E S
S C
O N
T R
O L
.0
N O R
HT
1/4" = 1'-0"
LEVEL 01 - CAFETERIA ACCESS 'A'
N O R
HT
1/4" = 1'-0"
LEVEL 01 - CAFETERIA ACCESS 'B'
N O R
HT
1/4" = 1'-0"
LEVEL 01 - STAIR ACCESS
N O R
HT
1/4" = 1'-0"
LEVEL 01 - SCREEN WALL
N O R
HT
1/4" = 1'-0"
LEVEL 01 - SCREEN WALL CONTINUATION
A A
B B
A A
B B
LEVEL 01 DOOR SCHEDULE, FINISH AND HARDWARE
DOORS D102A AND D102B:
• FRP STOREFRONT DOUBLE DOOR WITH 1/4" TEMPERED GLASS
- REMOVABLE, LOCKABLE MULLION (DOOR D102A ONLY)
- MEDIUM STILE
- DARK BRONZE ANODIZED FINISH (MATCH EXISTING)
- 10" BOTTOM RAIL
• DOOR HARDWARE
- CONTINUOUS HINGE
- PANIC HARDWARE "VON DUPRIN 99" W/ EXT. CYLINDER
- LCN 4000 SERIES CLOSERS
- DOOR SWEEPS
- STANDARD PULL HARDWARE TO MATCH EXISTING INTERIOR DOORS
DOORS D102C AND D102D:
• FRP STOREFRONT DOUBLE DOOR WITH 1/4" TEMPERED GLASS
- REMOVABLE, LOCKABLE MULLION (DOOR D102D ONLY)
- MEDIUM STILE
- DARK BRONZE ANODIZED FINISH (MATCH EXISTING)
- 10" BOTTOM RAIL
• DOOR HARDWARE
- CONTIUOUS HINGE
- PANIC HARDWARE "VON DUPRIN 99" W/ EXT. CYLINDER
- LCN 4000 SERIES CLOSERS
- DOOR SWEEPS
- STANDARD PULL HARDWARE TO MATCH EXISTING INTERIOR DOORS
DOOR B1:
• FRP STOREFRONT DOUBLE DOOR WITH 1/4" TEMPERED GLASS
- MEDIUM STILE
- DARK BRONZE ANODIZED FINISH (MATCH EXISTING)
- 10" BOTTOM RAIL
• DOOR HARDWARE
- CONTIUOUS HINGE
- PANIC HARDWARE "VON DUPRIN 99" W/ EXT. CYLINDER
- LCN 4000 SERIES CLOSERS
- DOOR SWEEPS
- STANDARD PULL HARDWARE TO MATCH EXISTING INTERIOR DOORS
K-5264M ILLBROO KC_FO UNTAINSVITREO US CHINA
K-5264M
ILLBROO
K
C_FO
UNTAINS
VITREO
US CHINA
K-5264M
ILLBROO
K
C_FO
UNTAINS
VITREO
US CHINA
K-5264M
ILLBROOK
C_F
OUNTAINS
VITREOU
S CHINA
K-5264M
ILLBROOK
C_F
OUNTAINS
VITREOU
S CHINA
C156
SCOPE OF WORK
LEVEL 01 KEY PLAN
NOTE: EXISTING 2X4 AND RECESSED CAN LIGHTS TO REMAIN
IN THIS AREA. SPRINKLERS TO REMAIN IN THIS AREA.
NEW LITHONIA
EXIT SIGN
CORRIDOR
B101
CAFETERIA
D102
(E1)
NEW LITHONIA
EXIT SIGN
EXIST. CAMERA TO
BE RELOCATED
RELOCATED
CAMERA
NOTE: ALL SPRINKLERS AND
LIGHTS IN THIS AREA TO REMAIN
COMMONS
D101
CAFETERIA
D102
(E1)
EXISTING 2x4 LIGHTS TO
BE RELOCATED
RELOCATED 2x4 LIGHT
NEW LITHONIA
EMERGENCY EXIT
SIGN/LIGHT COMBO @
7'-6" AFF.
EXISTING SPRINKLER
HEADS TO REMAIN
CORRIDOR
B102
STAIR
B1
NEW SPRINKLER HEAD
BY FIRE SUPPRESSION
CONTRACTOR
NOTE: FIRE SUPPRESSION CONTRACTOR TO REVIEW ARCHITECTURAL DRAWINGS AND SUBMIT PLANS WITH HYDRAULIC CALCULATIONS AND SYSTEM DESIGN TO LOCAL AUTHORITY HAVING JURISDICTION (AHJ). FIRE
SUPPRESSION SYSTEM SHALL COMPLY WITH CURRENT CODES.
RELOCATED 2x4 LIGHT
(E3)
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2023 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
201 S. ANN ARBOR STREET
SALINE, MI 48176
P: 734.429.8900
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #24002038.01
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #2402038.01
As indicated
/1
/2
:3 :3
A
M
2095 PACKARD ST.
YPSILANTI, MI 48197
YPSILANTI HS CORRIDOR
ACCESS CONTROL
A102
LEVEL 01 ENLARGED REFLECTED
CEILING PLAN
Dale Niethammer
Bill Kwasniak
Zach Goeglein
24002038.01
07/01/2024
PERMIT AND CONSTRUCTION
Y P
S
IL
A N
T I
H S
C O
R R
ID
O
R A
C C
E S
S C
O N
T R
O L
.0
N O R
HT
1/4" = 1'-0"
LEVEL 01 - CAFETERIA ACCESS 'A' RCP
N O R
HT
1/4" = 1'-0"
LEVEL 01 - CAFETERIA ACCESS 'B' RCP
N O R
HT
1/4" = 1'-0"
LEVEL 01 - STAIR ACCESS RCP
LEVEL 01 EMERGENCY LIGHTING AND SIGNAGE
EMERGENCY EXIT SIGN (E1)
- LITHONIA: DIE-CAST ALUMINUM LE-BLANK-DOUBLE FACE-RED-EL N WITH
BATTERY BACKUP, CEILING MOUNTED. (OR APPROVED EQUIVALENT)
EMERGENCY LIGHT (E2)
- LITHONIA: ELM6L EMERGENCY LIGHT (OR APPROVED EQUIVALENT)
- 1100 LUMEN, 5000K, WHITE, WALL MOUNTED
EMERGENCY SIGN/LIGHT COMBO (E3)
- LITHONIA: LHQM LED R, WHITE, CEILING OR WALL MOUNT, BATTERY BACKUP.
(OR APPROVED EQUIVALENT)
K-5264M ILLBROO KC_FO UNTAINSVITREO US CHINA
K-5264M
ILLBROO
K
C_FO
UNTAINS
VITREO
US CHINA
K-5264M
ILLBROO
K
C_FO
UNTAINS
VITREO
US CHINA
K-5264M
ILLBROOK
C_F
OUNTAINS
VITREOU
S CHINA
K-5264M
ILLBROOK
C_F
OUNTAINS
VITREOU
S CHINA
LEVEL 01
0"
4"
/2
8" 8"
EXIST. BULK HEAD
EXIST. GYP.BD. WALL
TO REMAIN
EXIST. BRICK WALL
TO REMAIN
NEW GYP.BD. WALL NEW GYP.BD. WALL
NEW INTERIOR
ALUMINUM STOREFRONT
SYSTEM WITH 1/4"
TEMPERED GLASS
NEW FRP DOORS WITH
1/4" TEMPERED GLASS
HALF LITE. TYP. OF ALL
D102AD102B
EXISTING COLUMN
2"3'-3 1/2"3'-3 1/2"2" 11"
2"3'-0"2"3'-0"
15'-8"
LEVEL 01
0"
STAIRS UP TO CAFETERIA
ACCESS 'B'
/2
/2
4 1/2" EQ EQ. 2"
NEW INTERIOR ALUMINUM
STOREFRONT SYSTEM WITH
1/4" TEMPERED GLASS
LEVEL 01
0"
EXISTING BULKHEAD
TO REMAIN
NEW BULK HEAD TO
MATCH EXISTING
NEW INTERIOR ALUMINUM
STOREFRONT SYSTEM WITH
1/4" TEMPERED GLASS
NEW FRP DOORS WITH
1/4" TEMPERED GLASS
HALF LITE TYP. OF ALL
D102D D102C
2" 3'-3 1/2" 3'-3 1/2" 2"
5 1/4"
2" 3'-2" 2" 3'-2" 2" 5"
LEVEL 01
0"
SEE PLAN ON SHEET A101.
STOREFRONT SYSTEM RETURN BEYOND.
2"EQ2"3'-0"2"3'-0"2"EQ2"
NEW GYP BD
PARTITION
NEW INTERIOR
ALUMINUM STOREFRONT
SYSTEM WITH 1/4"
TEMPERED GLASS
NEW FRP DOORS
WITH 1/4" TEMPERED
GLASS HALF LITE
B1
/2
/2
DARK BRONZE
ANODIZED ALUMINUM
LOUVERS IN TRANSOM
ABOVE DOORS
5'-3"
LEVEL 01
0"
EXISTING BRICK HALF WALL
NEW 4'-0" TALL SCREEN WALL. 1"x1"
TOP AND BOTTOM FRAME WITH
1"x1" INTERMEDIATE POSTS
3'-3"3'-3"3'-3"3'-3"3'-3"3'-3"3'-3"3'-3"3'-3"3'-3"
EVERY SECOND POST TO EXTEND
ABOVE CEILING AND BE SECURED
TO STRUCTURE ABOVE
EVERY POST TO BE EMBEDDED INTO BRICK HALF WALL MINIMUM 12" -
REMOVE TOP SOLDIER COURSE AT POST PRIOR TO CORING, MODIFY
AND REPLACE TOP SOLDIER COURSE, GROUT AROUND POST
LEVEL 01
0"
NEW 4'-0" TALL SCREEN WALL. 1"x1"
TOP AND BOTTOM FRAME WITH
1"x1" INTERMEDIATE POSTS
EXISTING BRICK
HALF WALL
A103
A103
TYP
TYP
2'-9" 3'-3" 3'-3" 3'-3" 3'-3" 3'-3" 3'-3" 3'-3" 3'-3" 3'-3" 3'-3" 2'-9"
EVERY SECOND POST TO EXTEND
ABOVE CEILING AND BE SECURED
TO STRUCTURE ABOVE
EVERY POST TO BE EMBEDDED INTO BRICK HALF WALL MINIMUM 12" -
REMOVE TOP SOLDIER COURSE AT POST PRIOR TO CORING, MODIFY
AND REPLACE TOP SOLDIER COURSE, GROUT AROUND POST
SCOPE OF WORK
LEVEL 01 KEY PLAN
ACOUSTICAL BATT INSULATION
NON-STRUCTURAL
METAL STUD AT 16" O.C.
METAL TRACK RUNNER
FASTENED TO FLOOR
FLOOR LINE
CONTINUOUS ACOUSTICAL
SEALANT, BOTH SIDES, FINISH
FLUSH WITH PARTITION
COMPRESSIBLE NEOPRENE
FOAM GASKET ABOVE TRACK
AT CEILING
5/8" TYPE 'X' ABUSE
RESISTANCE GYPSUM
BOARD, BOTH SIDES
CONTINUOUS TOP TRACK
CONTINUOUS TEAR-AWAY
BEAD EACH SIDE OF WALL,
TYP
SECTION VIEW
PLAN VIEW
SECTION VIEW
EXISTING CEILING / SOFFIT
NEW BASE TO MATCH EXISTING 4"
BLACK RESILIENT BASE
/2
/2
1/4" PERFORATED PANEL
BASIS OF DESIGN: MCNICHOLS
PERFORATED METAL - SLOTTED,
CARBON STEEL, COLD ROLLED, 16
GAUGE, 1/8" X 1" ROUND-END SLOT,
SIDE STAGGERED, 44% STAGGERED
/8
/2
/2
/2
1"x1"x1/4" STEEL TUBE
TOP RAIL AND POSTS
PANEL CLIP WELDED
TO RAILS AND POSTS
SECURE PANEL TO CLIP WITH
STAINLESS STEEL SHOLDER
SCREW AND BARREL NUT (WITH
SECURITY PINS)
1"X1"X1/4" BOTTOM RAIL
WELDED TO STEEL POSTS
1" U-EDGING - MITER, WELD AND GRIND
CORNERS OF PERIMETER FRAME
BASIS OF DESIGN: MCNICHOLS
MATCHING CARBON STEEL U-EDGING
REFER TO PLANS AND ELEVATIONS
3'-4" MAX
1" 1" 5" 2" 2" 5" 1" 1"
EXISTING CEILING
EXTEND POST THROUGH
CEILING AND SECURE TO
STRUCTURE ABOVE
REMOVE SOLDIER COURSE
BRICK AT POST LOCATIONS
EMBED POST INTO BRICK
MINIMUM (3) THREE COURSES
BELOW SOLDIER COURSE,
GROUT AROUND POST
REINSTALL AND MODIFY
SOLDIER COURSE AROUND
POST - GROUT AROUND POST
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2023 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
201 S. ANN ARBOR STREET
SALINE, MI 48176
P: 734.429.8900
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #24002038.01
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #2402038.01
As indicated
/1
/2
:3 :3
A
M
2095 PACKARD ST.
YPSILANTI, MI 48197
YPSILANTI HS CORRIDOR
ACCESS CONTROL
A103
LEVEL 01 ELEVATIONS AND DETAILS
Dale Niethammer
Bill Kwasniak
Zach Goeglein
24002038.01
07/01/2024
PERMIT AND CONSTRUCTION
Y P
S
IL
A N
T I
H S
C O
R R
ID
O
R A
C C
E S
S C
O N
T R
O L
.0
1/4" = 1'-0"
CAFETERIA ACCESS 'A' DOORS
11/4" = 1'-0"
CAFETERIA ACCESS 'B'
21/4" = 1'-0"
CAFETERIA ACCESS 'B' DOOR
1/4" = 1'-0"
LEVEL 01 - STAIR ACCESS
1/4" = 1'-0"
SCREEN WALL - 'NORTH' EXTENT
5 1/4" = 1'-0"
SCREEN WALL - 'SOUTH' EXTENT
AB
AB
AB
AB
1 1/2" = 1'-0"
METAL STUD W GYP BOARD (BOTH SIDES)
A3" = 1'-0"
MESH SCREEN DETAIL
71 1/2" = 1'-0"
MESH INFILL ELEVATION
K-5264MILLBROOK C_FOUNTAINS VITREOUS CHINAK-5264MILLBROOK C_FOUNTAINS VITREOUS CHINA
SCOPE OF WORK
LEVEL 02 KEY PLAN
A104
2"
3'-3 1/2"
3'-3 1/2" 2"
2"
3'-2"
2"
3'-2"
2" 1'-7"
B202A
B202B
CORRIDOR
B201
STAIR
B1
STORAGE
B204
CORRIDOR
B202
15'-4"
LEVEL 02
14'-0"
NEW INTERIOR ALUMINUM
STOREFRONT SYSTEM WITH
1/4" TEMPERED GLASS
NEW FRP DOORS WITH
1/4" TEMPERED GLASS
HALF LITE TYP. OF ALL
B202BB202A
DARK BRONZE ANODIZED
ALUMINUM LOUVERS IN
TRANSOM ABOVE DOORS
15'-4"
2"3'-2 1/2"2"3'-2 1/2"2" 1'-7"
2"3'-2"2"3'-2"2"
NEW LITHONIA EXIT
SIGN
EXISTING CAMERA.
MOVE OR REPOSITION
AS NECESSARY
EXISTING DIGITAL
CLOCK TO REMAIN
EXISTING SPRINKLERS
TO REMAIN. TYP. @
LEVEL 2
EXISTING 2x4 LIGHTS
TO REMAIN. TYP @
LEVEL 2
ALTERNATE: ADD
EXIST. LIGHT TO
EMERGENCY CIRCUIT
NEW WALL MOUNTED
EMERGENCY LIGHT @
10' ABOVE LANDING
CORRIDOR
B201
STAIR
B1
STORAGE
B204
SPORTS DECK
B203
EXISTING SPRINKLER
HEADS TO REMAIN,
TYP
EXISTING
WIRELESS ACCESS
POINT TO REMAIN
OC
EXIST. OCCUPANCY
SENSOR TO REMAIN
(E1)
(E2)
EXISTING EMERGENCY
EXIT SIGN
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2023 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
201 S. ANN ARBOR STREET
SALINE, MI 48176
P: 734.429.8900
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #24002038.01
KEY PLAN
AGENCY APPROVAL
REVISIONS
PROFESSIONAL SEAL
CONSULTANT
No. Date Revision / Issue
DISCLAIMER
SHEET INFORMATION
Date
Project #
Drawn
Checked
Approved
SHEET TITLE
SCALE
Scale:
SHEET NUMBER
Issue
PROJECT #2402038.01
As indicated
/1
/2
:3 :3
A
M
2095 PACKARD ST.
YPSILANTI, MI 48197
YPSILANTI HS CORRIDOR
ACCESS CONTROL
A104
LEVEL 02 PLANS AND ELEVATIONS
Dale Niethammer
Bill Kwasniak
Zach Goeglein
24002038.01
07/01/2024
PERMIT AND CONSTRUCTION
Y P
S
IL
A N
T I
H S
C O
R R
ID
O
R A
C C
E S
S C
O N
T R
O L
.0
LEVEL 02 DOOR SCHEDULE, FINISH AND HARDWARE
DOORS B202A AND B202B:
• FRP STOREFRONT DOUBLE DOOR WITH 1/4" TEMPERED GLASS
- REMOVABLE, LOCKABLE MULLION (DOOR 202B ONLY)
- MEDIUM STILE
- DARK BRONZE ANODIZED FINISH (MATCH EXISTING)
- 10" BOTTOM RAIL
• DOOR HARDWARE
- CONTIUOUS HINGE
- PANIC HARDWARE "VON DUPRIN 99" W/ EXT. CYLINDER
- LCN 4000 SERIES CLOSERS
- DOOR SWEEPS
- STANDARD PULL HARDWARE TO MATCH EXISTING INTERIOR DOORS
N O R
HT
1/4" = 1'-0"
LEVEL 02 - VESTIBULE ACCESS
1/4" = 1'-0"
LEVEL 02 - VESTIBULE ACCESS
N O R
HT
1/4" = 1'-0"
LEVEL 02 - REFLECTED CEILING PLAN
LEVEL 02 EMERGENCY LIGHTING AND SIGNAGE
EMERGENCY EXIT SIGN (E1)
- LITHONIA: DIE-CAST ALUMINUM LE-BLANK-DOUBLE FACE-RED-EL N WITH
BATTERY BACKUP, CEILING MOUNTED. (OR APPROVED EQUIVALENT)
EMERGENCY LIGHT (E2)
- LITHONIA: ELM6L EMERGENCY LIGHT (OR APPROVED EQUIVALENT)
- 1100 LUMEN, 5000K, WHITE, WALL MOUNTED
| A000 |
| A001 |
| A100 |
| A101 |
| A102 |
| A103 |
| A104 |
File details come from the government source that posted it. Updated .