This document is a detailed modular building specification from Phoenix Modular for a 36'x60' office building project for Mobile Modular Management Group, located in California. The project involves a three-module building with 2,130 square feet of office space, designed as a commercial B occupancy type with a 14-person occupancy load. The building includes multiple office rooms, a corridor, lactation room, printer room, and restrooms, constructed with specific construction standards including 2x4 and 2x6 lumber framing, R-19 insulation, LP Smart-panel vertical siding, and an EPDM roof system.
The modular building is engineered to meet 2022 California Building Codes, including accessibility requirements, energy standards, and seismic design criteria. The structure features a perimeter I-beam chassis, 3-ton heat pump with 5kw heat strip, electrical panels with 125-amp main breakers, and comprehensive electrical, HVAC, and plumbing systems. The building is designed for pad/pier above-grade installation, with wind load specifications of 115 MPH, and includes provisions for future solar equipment. The project serial number is PMI-6563-3660, and the modules are manufactured by Phoenix Modular in Phoenix, Arizona, with detailed specifications for every aspect of construction from framing to finishes.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INTERIOR WALL CONSTRUCTION:
Framing: Stud: 2x4 #2 HF equal or better @ 16" O.C.
Top plate: Single 2x4 #2 HF equal or better (Double as needed) Bottom plate: Single 2x4 #2 HF or better bottom plate Stud length: Full Height to rafters (See hatching on floor plan) Stud length: 92-5/8" (Ceiling Ht.) (Remainder)
Insulation: R-11 unfaced battens (restroom walls only) (Ceiling Ht.)
Additional Interior Wall Items Included in Quoted Price:
Item 1: None
FRAME / CHASSIS:
Frame Type: Perimeter Quantity: (3) EA Frame Size: 11'-10" X 60'-0" Type: Perimeter I-Beam with Joists: Z1" x 2" x 8" x 2" x 1" x 14 ga. (minimum).
Joist spacing to be 16" o.c.
Beam Size: 12" Jr. I-beam Axles (UNDERSLUNG):
Modules #1&3: Qty: Five 6000# rated with (All) brake Offset: None
Modules #2: Qty: Quad 6000# rated with (All) brake Offset: None
Hitch: Detachable with Standard Hitch Tires: 8x14.5 14 ply rated
Additional Frame / Chassis Items Included in Quoted Price:
Item 1: None
FLOOR CONSTRUCTION:
Floor Joist: See Chassis Floor: Single layer 3/4" T&G Plywood. (Mechanically fastened) Insulation: R-19 unfaced fiberglass batt (No insulation in wheel wells (shipped loose and installed by others on site)) Bottom: Reinforced Plastic (No reinforced plastic in wheel wells (shipped loose and installed by others on site))
Additional Floor Items Included in Quoted Price:
Item 1: None
EXTERIOR WALL CONSTRUCTION:
Framing: Stud: 2x6 #2 HF equal or better @ 16" O.C.
Top Plate: Double 2x6 #2 HF equal or better Bottom Plate: Single 2x6 #2 HF or better Header: (3) 2x4 header with (2) 1/2" shim at all exterior openings (UNO)
Wall Sheathing: None Insulation: R-19 Kraft back fiberglass batt Siding Type: 7/16" LP Smart-panel vertical siding (8" grooves) with barricade wrap underlayment.
Sidewall Height: See cross section for heights
Additional Exterior Wall Items Included in Quoted Price:
Item 1: Post Height: 104-7/8"
ROOF CONSTRUCTION:
Roof Type: Complex or Mono or Shed (Sloped away from exterior doors) Roof Slope: 1/4 in 12 Rafter size: 2x8 #2 HF equal or better
(Roof diaphragm chord strap 'ST2215' at rafters installed on-site, see 5/6.0) Rafter Length: Mods 1&3: 137 1/8"
Mod 2: 135 1/4" Spacing: 16" O.C.
Mate Beam: Multi-layer plywood
Height: 18" to 25 1/2" to 18" Length: 60' No. of Layers: 4 No. of Beams: 4
Insulation: R-30 unfaced fiberglass batt (2-layer of R-15) with support netting Sheathing: 1/2" 24/0 Sheathing Roofing: 45 mil single ply EPDM over Densdeck or equal
Color: White (S.R. after 3 years: 0.64 / T.E. after 3 years: 0.87) (Fire / Wind Resistance, ESR-1463: table 2, system #9 (insul. board excluded), and table 4, system #1)
Additional Roof Items Included in Quoted Price:
Item 1: None
EXTERIOR/INTERIOR DOORS: (SEE DOOR SCHEDULE)
WINDOWS: (SEE WINDOW SCHEDULE)
CLOSEUP:
Type: Medium Notes: Module WILL NOT exceed 12'-0" (Except door hardware)
SKIRTING:
Skirting: 7/16"x4'x8' Sheets (Same material as siding)
Color: Same as body Qty: 16 Sheets
Trim: 7/16"x4"x16' (Same size / color as trim) Qty: 2 Pieces
FINISHES:
FLOOR COVERING:
Type 1: 1/8" V.C.T. Tile Hold back tile (5 1/2") at each side of the matelines.
Pattern: (1/4" turn) Location: (Throughout) Color to be: ( )
BASE:
Cove Base 1 : 6" Vinyl cove.
Location: (RR 116 & Jan. 113) Color to be: ( )
Cove Base 2 : 4" Vinyl cove.
Location: (Remainder) Color to be: ( )
WALLS:
Covering 1: 1/2" MR gyp Pre-laminated FRP panels (NUDO)(Class C)
Location: (RR 116 & Jan. 113 all walls) Covering height: 8' Color: (White)
Covering 2: 1/2" vinyl covered gypsum Location: (Remainder) Covering height: 8' Color to be: ( ).
Covering 3: 1/2" Raw gypsum (ONE Side) Location: (Full Height Walls - See Hatching) Covering height: Varies (Ceiling to Rafters)
TRIM:
Wall Trim 1: FRP Covered trim
Color to be: (White) Location: (RR 116 & Jan 113)
Wall Trim 2: Vinyl Covered trim Color to be: (To match VCG) Location: (Remainder)
CEILING:
Type 1: 2'x4' HEAVY DUTY T-Grid w/ Struts & wires
(Armstrong #2910A (Vinyl Washable) or Equal) Height: 7'-10" Location: (RR 116)
Type 1: 2'x4' HEAVY DUTY T-Grid w/ Struts & wires (Armstrong Tile #755B or Equal) Height: 7'-10" Location: (Remainder)
Installed at factory, held back at module lines.
Completion of ceiling installation on-site by others; not in PMI's scope.
EXTERIOR:
Siding body: Color: ( ) 8' sheets Hood: Color: ( ) Corner trim: Color: ( ) Door & window trim: Color: ( ) Bottom horizontal trim: Color: ( ) Intermediate horizontal trim: Color: ( ) separates hood & body Top horizontal trim: Color: ( ) Module line trim: Color: (Match hood above intermediate horizontal trim & match body below) All paint to be: Satin Finish (Sherwin Williams)
DEALER:
MOBILE MODULAR MANAGEMENT GROUP
PROJECT:
BUILDING MB-ND
36'X60'
PMI-6563-3660
DRAWING INDEX
SHEET 1.0: SPECIFICATIONS AND CONDITIONS
SHEET 1.1: WINDOW AND DOOR SCHEDULE, PLUMBING
SCHEDULE, ELECTRICAL SCHEDULE, &
HVAC SCHEDULE
SHEET 2.0: FLOOR PLAN, PLUMBING LEGEND, STRUCTURAL
LEGEND, PLUMBING SCHEMATICS
SHEET 3.0: ELECTRICAL PLAN, ELECTRICAL CALCS AND
ELECTRICAL NOTES
SHEET 4.0: REFLECTED CEILING PLAN
SHEET 5.0: HVAC PLAN
SHEET 6.0: BUILDING CROSS-SECTION & MISC. DETAILS
SHEET 7.0: ELEVATIONS
"PLEASE REVIEW DRAWINGS AND SPECIFICATIONS
CAREFULLY. WHILE EVERY EFFORT IS MADE TO
ASSURE THE DRAWINGS REFLECT THE
EXPECTATIONS AND QUOTATION, THE FINAL
CONSTRUCTION WILL BE BASED SOLELY ON THE
SPECIFICATIONS AND DRAWINGS APPROVED."
APPROVED
APPROVED EXCEPT AS NOTED
REVISE AND RESUBMIT
BY: DATE:
DATA PLATE AND STATE DECAL TO BE LOCATED ON
LOWER RIGHT HAND CORNER OF THE ENDWALL
OPPOSITE THE HITCH END OF THE MODULE.
SPRINKLERS REQUIRED: NO
FIRE ALARM REQUIRED: NO
SPECIAL CONDITIONS AND OR
LIMITATIONS:
IDENTIFICATION:
NOTES:
1.0
1. SITE PLAN NOT AVAILABLE AT THIS TIME. BUILDING
DESIGNED TO HAVE FIRE SEPARATION DISTANCE
GREATER THAN 10 FT. TO PROPERTY LINES AS PER
LOCAL BUILDING DEPARTMENT REQUIREMENTS.
2. THIS PLAN MAY BE REVERSED AND/OR MIRRORED.
3. SEE STRUCTURAL PACKAGE FOR ALL STRUCTURAL
STANDARDS AND DETAILS.
4. BUILDING WILL NOT BE LOCATED IN A FLOOD HAZARD
AREA.
5. BUILDING SHALL NOT BE SITED WHERE LOCAL
CONDITIONS EXCEED THE DESIGN PARAMETERS.
6. INTERIOR WALL PARTITIONS COMPLY WITH SEC.
1607.14 OF THE 2015 IBC, SEC. 1607.15 OF THE 2018 IBC
AND SEC. 1607.16 OF THE 2021 AND 2024 IBC.
7. STRUCTURAL SKIRTING / FRAMING, BY OTHERS, IS
REQUIRED FOR SNOW LOADS EXCEEDING 20 psf.
8. COMPLIANCE WITH HCD IGNITION RESISTANT
CONSTRUCTION SYSTEM REQUIREMENTS?
(CBC CHAPTER 7A) NO .
9. TO BE INSTALLED ON A PERMANENT FOUNDATION? NO .
10.THIS BUILDING IS DESIGNED TO COMPLY WITH THE
COMMERCIAL MODULAR REQUIREMENTS OF
CALIFORNIA CODE OF REGULATIONS TITLE 25.
11.DUE TO UNKNOWN SITE CONDITIONS, A
PHOTOVOLTAIC AND BATTERY STORAGE SYSTEM IS
NOT INCLUDED. EACH SYSTEM SHALL BE DESIGNED,
SUPPLIED, AND INSTALLED AT SITE BY OTHERS AS
REQUIRED BY LOCAL AHJ. A MINIMUM SOLAR ROOF
ZONE OF 320 SQ. FT. IS PROVIDED AS REQUIRED BY
SECTION 110.10(b)1B OF THE CEC.
MANUFACTURER:
DESIGN CRITERIA / LOADS:
NOT INCLUDED IN SCOPE OF WORK:
1. PORCHES, STEPS, AND RAMPS TO BE SUPPLIED AND
INSTALLED BY OTHERS IN ACCORDANCE WITH THE
LOCAL BUILDING DEPARTMENT
2. PORTABLE FIRE EXTINGUISHERS TO BE SUPPLIED AND
INSTALLED ON SITE BY OWNER IN ACCORDANCE WITH
LOCAL BUILDING DEPARTMENT
3. ACCESSIBLE DRINKING FOUNTAIN TO BE PROVIDED
ON SITE BY OWNER (AS APPLICABLE)
4. ANY REQUIRED SPRINKLER / FIRE ALARM /
FIRE/SMOKE DETECTION AND/OR SUPPRESSION AS
REQUIRED BY THE IBC/IFC AND/OR LOCAL FIRE
AUTHORITY TO BE INSTALLED BY OTHERS ON SITE IN
ACCORDANCE WITH THE LOCAL BUILDING
DEPARTMENT.
5. THE BUILDING OWNER IS RESPONSIBLE FOR THE
DEVELOPMENT & DESIGN OF ALL SITE REQUIRED
ACCESSIBILITY ELEMENTS. THESE ELEMENTS ARE
NOT INCLUDED IN THE SCOPE OF THIS DESIGN.
SUBMITTALS ARE REQUIRED BY OWNER THROUGH
THEIR DESIGN PROFESSIONAL.
6. INTERCONNECTION OF SMOKE ALARMS AS
REQUIRED,SHALL BE INTERCONNECTED ON SITE BY
OTHERS.
7. INSTALLATION AND COMPLETE WATERTIGHT
WEATHER SEALING IS THE RESPONSIBILITY OF THE
PURCHASER. SPECIAL CONSIDERATION SHOULD BE
GIVEN TO COASTAL OR EXTREME WEATHER
LOCATIONS.
CA: 2022 CBC, 2022 CPC, 2022 CMC, 2022 CEC, 2022 CFC
2022 CA Energy, & 2022 CBC Chapter 11B Accessibility
NO OF MODULES. 3
BUILDING SQ.FT. 2130
TYPE OF CONSTRUCTION. VB
OCCUPANCY USE GROUP. B
OCCUPANCY LOAD. 14
FLOOR LIVE LOAD. 50 psf. (2000 lb concentrated)
(100 psf. @ corridor) ROOF LIVE LOAD. 20 psf.
ROOF DEAD LOAD. 12 psf.
ROOF SNOW LOAD. 20 psf.
GROUND SNOW LOAD: 28.6 psf.
WIND LOAD.
OCCUPANCY/RISK CATG. II
SEISMIC
PERMISSIBLE GAS TYPE. N/A
CLIMATE ZONE. 10
FIRE RATING OF EXT. WALLS: 0
NAME AND DATE OF CODES;
Ss=3.730, S1=1.389 Site Class 'D' Design Category 'E'
MANUFACTURER & ADDRESS PHOENIX MODULAR
5301 W. MADISON ST.
(SEE WEBSITE FOR PHOENIX, AZ. 85043
WARRANTY INFORMATION) PHOENIXMODULAR.COM
STATE REQUIRED INFORMATION ON USE AND
LOCATION OF FACTORY-BUILT BUILDING
1. PROPOSED ADDRESS
2. EXPLANATION OF
AND/OR LOCATION OF UNIT.
BUILDING USE.
3. SET TYPE
ASSUMED F.F. TO BE 36" A.F.G.
OFFICE
PATTON, CA, 92369
3102 E. HIGHLAND AVE
PAD/PIER ABOVE GRADE
V: 115 MPH, EXP. C
Vasd: 89 MPH, EXP. C
RED TAG:
W . M
A D
IS
O
N S
T.
PH
O
EN
IX
, A Z
PH
-4
-6
F A
X
-4
-6
SU
N
B
EL
T M
O D
U
LA
R
IN
C
THESE DRAWINGS REMAIN
THE PROPERTY OF PHOENIX
MODULAR AND ARE NOT TO BE
USED IN ANYWAY WITHOUT
WRITTEN PERMISSION.
SHEET:
OF
DEALER:
MOBILE MODULAR
MANAGEMENT GROUP
PROJECT:
BUILDING MB-ND
STATES:
CA
SERIAL NUMBERS:
PMI-6563-3660
DRAWN BY:
RQ/JK
PLOT DATE:
2/19/2025
REV # / DATE:
PH
O
EN
IX M
OD
UL
AR
MODEL NUMBER:
© 2025
V.T. ESKELSEN, P.E.
DESIGN ENGINEER
5301 W. MADISON ST.
PHOENIX, AZ 85043
(602) 447-6460
NONE
DOORS:
Qty NO. Type Jamb Wall Thickness Glazing Size Rough Opening U-Factor Color Closer Deadbolt Hardware Fire Rating Keying Notes
STEEL, INSULATED 18 GA.
PREFINISHED WOOD
SOLID CORE
PREFINISHED WOOD
SOLID CORE
PREFINISHED WOOD
SOLID CORE
KD 16 GA.
BRONZE
TIMELY METAL
FRAME
BROWNTONE
TIMELY METAL
FRAME
BROWNTONE
TIMELY METAL
FRAME
BROWNTONE
6 7/16"
4 1/2"
4 1/2"
4 1/2"
NONE
NONE
NONE
NONE
3/0X7/0
3/0X7/0
3/0X7/0
3/0X7/0
38" x 85"
37 1/2" x 84 3/4"
37 1/2" x 84 3/4"
37 1/2" x 84 3/4"
0.31
N/A
N/A
N/A
T.B.D. (SAME BOTH SIDES)
LEGACY OAK
LEGACY OAK
LEGACY OAK
HYDRAULIC
CLOSER NORTON
(8501 AL)
NONE
NONE
NONE
NONE
NONE
NONE
NONE
LIGATURE-RESISTANT
MORTISE CLASSROOM
LEVER, (CORBIN
RUSSWIN
ML2055-BHSS-630)
LIGATURE-RESISTANT
MORTISE CLASSROOM
LEVER, (CORBIN
RUSSWIN
ML2055-BHSS-630)
LIGATURE-RESISTANT
MORTISE PRIVACY
LEVER, (CORBIN
RUSSWIN
ML2068-BHSS-630)
LIGATURE-RESISTANT
MORTISE STOREROOM
LEVER, (CORBIN
RUSSWIN
ML2057-BHSS-630)
NONE
NONE
NONE
NONE
ALIKE
N/A
N/A
N/A
DRIP CAP, (2) STD & (1) NRP HINGES,
WEATHERSTRIPPING, THRESHOLD, DOOR
SWEEP, LATCH GUARD, & SIGN ("THIS
DOOR TO REMAIN UNLOCKED WHEN
BUILDINGS OCCUPIED")
ALUM. CONTINUOUS HINGE (172758
HOSPITAL TIP) & WALL MOUNT STOPS
ALUM. CONTINUOUS HINGE (172758
HOSPITAL TIP) & WALL MOUNT STOPS
ALUM. CONTINUOUS HINGE (172758
HOSPITAL TIP) & WALL MOUNT STOPS
WINDOWS:
Qty NO. Type Glazing Size Rough Opening U-Factor SHGC Mini-Blind Notes
11 A
WHITE VINYL
HORIZONTAL
SLIDER
CLEAR, DUAL
GLAZED, LOW-E 4/0X3/0 48" x 36" 0.31 0.23 NONE HEADER AT 85" AFF
PLUMBING:
Symbol Type Qty Note Description
H C
FD
B-3574
S30
W H
Water Closet
Grab Bars
Lavatory
Sink
Mirror
2" Floor Drain
Seat-Cover / Tissue
Dispenser / Napkin
Disposal
Water Heater
Water Heater
Water Hammer
In-line Strainer Supply
DWV
System
R.R. Sign
R.R. Sign
Low Flow
(1.28 GPF)
Low Flow Thermostatic mixing valve
Bobrick: B-3574 / R.O.: 16"W x
29-1/4"H
Chronomite:
S30LLMB120V or equal
6 gallon w/ seismic straps and expansion tank
3/4"
1 1/4"
Copper Inlet
Wall Mtd
Door Mtd
Floor mtd. ADA elongated bowl with flush valve, shut off valve, and open front seat (Factory standard) Set(s) with (1) each 48", 36" horizontal, and 18" vertical
19" X 17" White vitreous wall hung with ADA handles and shut off valves. (Factory standard)
24x24 Floor mounted mop sink with wall mounted faucet (Factory standard) 24"x36" w/ s.s. frame mtd. 38" to bottom edge (Factory standard)
Floor drain with drip primer (Factory standard)
Recessed toilet seat-cover, toilet tissue dispenser, and napkin disposal mtd. 43" to top of opening
Insta-Hot Chronomite S-30 (Electric - 120V)
120v Electric with relief valve (relief valve to drain into pan), water tight drain pan (aluminum,
0.6010 mm min. thickness, 1-1/2" depth) with 3/4" drained to exterior, and pipe insulated first 8' (non-simulataneous operation) (Factory standard)
Water hammer arrestor
Strainer at supply entrance
Type M copper or Pex
ABS Schedule 40 (Manifold is by others)
Unisex ADA restroom sign w/ braille mtd. 59" a.f.f. to center Unisex ADA restroom sign mtd. 59" a.f.f. to center
ELECTRICAL:
Symbol Type Qty Note Description
PC
EXIT
EXIT
O
D
DIM
3DIM
OCC
GFCI
GFCI
WR
XH
CA
M
SO
WAP
T
Elec Service Elec
Raceway
Elec Panel
Elec Panel
Lights
Lights
Lights
Lights
Emerg. Light
Emerg. Light
Exit Sign
Emerg. Light
Switch
Switch
Switch
Switch
Switch
Switch
Occupancy Sensor
Receptacle
Receptacle
Receptacle
Receptacle
Floor Box
J-Box
J-Box
J-Box
J-Box
Water Heater J-Box
J-Box
J-Box
J-Box
J-Box
Exhaust Fan
Exhaust Fan
T-Stat
Device Color
Min. 12 Space (Panel B & C)
Min. 12 Space 1" conduit with pull string to J-Box 'SO' for future solar equipment.
(PANEL A)
30W
50W
30W
Halo:
FE08A40FDB or equal
Red lens
Red lens
Wattstopper:
IOS-DOV or equal Lutron: MS-Z101 or equal Lutron: DVTV or equal Lutron: DVSTV or equal Sensor: CI-305 /
Power pack:
BZ-150 or equal
L5-30R
Walker: 880-W2 box, 827PCC-BLK flange, (1)
829PSTC-BLK
data plate, (1)
828PR-BLK recep plate
3/4" Conduit stubbed above ceiling w/ pull string
Future inlet
Pass & Seymour:
TV3LVKITWCC2
or equal
Broan: AE80B or equal
Broan: A70L
White Rogers:
1F951277
120/240V 60 HZ. single phase E.M.T. thin wall conduit with flex cable to lights and THHN wire 120/240v 1PH 125 amp panel w/ 125 amp main breaker. Exterior NEMA 3R mounted 36" a.f.f. to top (Factory standard)
120/240v 1PH 125 amp panel w/ 125 amp main breaker. Exterior NEMA 3R mounted 36" a.f.f. to top (Factory standard)
2'x4' Flat panel LED 3900 lumens recessed lay-in with dimmable electronic ballast (Factory standard) 2'x4' Flat panel LED 6500 lumens recessed lay-in with dimmable electronic ballast (Factory standard) 2'x2' Flat panel LED 3900 lumens recessed lay-in with electronic ballast (Factory standard)
8W LED porch light with photocell mtd. 87" a.f.f.
Combo dual emergency light/exit sign with battery backup mtd. 88" a.f.f. ceiling mounted (Factory standard) Exterior remote head mtd. 90" a.f.f. (Mounted in octagon box) (Factory Standard) 120v with battery backup ceiling mounted (Factory standard) Interior double head battery pack mtd. 88" a.f.f. (Factory standard) 15a/120v Standard single toggle w/ cover plate mtd. 46" a.f.f. (Factory standard) 15a/120v 3-Way wall mtd. single toggle w/ cover plate mtd. 46" a.f.f. (Factory standard) 20a/120v Wall mtd. occupancy / vacancy sensor w/ cover plate mtd. 46" a.f.f.
20a/120v Wall mtd. occupancy / dimming sensor switch w/ cover plate mtd. 46" a.f.f.
0-10v Wall mtd. dimming w/ cover plate mtd.
46" a.f.f.
0-10v Wall mtd. 3-way dimming w/ cover plate mtd. 46" a.f.f.
Ceiling mounted occupancy sensor w/ power pack
20a/120v Duplex w/ cover plate mtd. 18" a.f.f.
(Factory standard) 20a/120v GFCI protected w/ cover plate mtd.
42" a.f.f. (Factory standard) 20a/120v GFCI 'WR' rated exterior receptacle with weatherproof extra-duty in-use cover mtd. 18" a.f.f. (Factory standard) 30a/120v Sng. for water heater w/ cover plate mtd. 18" a.f.f. (Factory standard)
20A/120V 2-Gang wood floor mtd. box w/ (1) duplex recep and (1) phone/data and 3/4" conduit stubbed below floor w/ pull string
4x4 Empty box w/ sngl. gang mud ring, and blank cover plate mtd. 18" a.f.f. for future phone/data (Factory standard) 6x6x6 Empty semi-recessed/surface mount NEMA-3R box w/ metal cover and 1" conduit stubbed above ceiling mtd. 18" a.f.f. (Factory standard) 4-11/16" Empty exterior j-box w/ sng gang mud ring, and cover plate mtd. 102" a.f.f. for future speaker 4-11/16" Empty exterior j-box w/ sng gang mud ring, and cover plate mtd. 102" a.f.f. for future camera 20A/120V 3-gang recessed TV box w/ pull through brushes mtd. 60" a.f.f. w/ 3/4" conduit stubbed to attic w/ pull string 30a/120v 4x4 Wired box w/ sng gang mud ring and cover plate for water heater mtd. 18" a.f.f. (Factory standard) 4x4 J-Box w/1" conduit from Panel 'A' mtd. at rafters with cover plate (For future Solar Equipment) See Reflected ceiling plan for location.
4-11/16" Empty box w/ sng gang mud ring, and cover plate w/ face flush w/ ceiling (Factory standard) for future speaker 4-11/16" Empty box w/ sng gang mud ring, and cover plate w/ face flush w/ ceiling (Factory standard) for wireless access point 30a/120v 4x4 Wired box w/ sng gang mud ring and cover plate mtd. 18" a.f.f. (Factory standard)
80 cfm Ceiling mounted / vent thru roof
70 CFM Ceiling mounted fan / light combo with 9W LED bulb / vent thru wall (Factory standard)
Programmable T-Stat(s) mtd. 46" a.f.f.
Color to be: (WHITE) / Exterior device(s) and mansonry boxes with metal cover plate as applicable
NOTE:
1. ALL A.F.F. DIMENSIONS ARE TO THE CENTER OF THE DEVICE BOX UNLESS
NOTED OTHERWISE (REFER TO SCHEDULE AND PLANS FOR HEIGHTS).
2. ALL ELECTRICAL ITEMS ARE FACTORY STANDARD UNLESS NOTED
OTHERWISE.
3. BLANK COVERS WILL BE PROVIDED ON J-BOXES UNLESS NOTED OTHERWISE.
4. ALL EXTERIOR ELECTRICAL DEVICES TO BE WEATHERPROOF AND MARKED
FOR EXTRA-DUTY.
HVAC:
Symbol Type Qty Note Description
HVAC HVAC Unit
Duct Sleeve
Return Air Plenum
Fiberglass Duct
Fiberglass Duct
Fiberglass Duct
Fiberglass Duct
Fiberglass Duct
Supply Diffusers Supply
Diffusers Supply
Diffusers Supply
Diffusers Supply
Diffusers
R/A Grille
R/A Grille
R/A Grille
Duct type
Misc
Economizer
6"
8"
6"
8"
10"
8"
10"
6"
3 Ton heat pump with 5kw heat strip (11.1 EER / 3.3 COP) end mount unit / Model: W36HF-B05Y or equal
29"x9" To 22"x10" Galvanized sleeve, 16" long
32"x7" Return air plenum w/ 28"x14"x6" tap-in
22"x10"x10'-0" long Fiberglass
16"x10"x10'-0" long Fiberglass
16"x10"x5'-0" long Fiberglass
22"x10"x7'-6" long Fiberglass
16"x10"x7'-6" long Fiberglass
24" x 24" 4-way throw diffuser with start collar, collar w/ scoop and damper, and flex (Factory standard) 24" x 24" 4-way throw diffuser with start collar, collar w/ scoop and damper, and flex (Factory standard) 24" x 24" 4-way throw diffuser with start collar, collar w/ scoop and damper, and flex (Factory standard) 24" x 24" 4-way throw diffuser with start collar, collar w/ scoop and damper, and flex (Factory standard) 24" x 24" 4-way throw diffuser with start collar, collar w/ scoop and damper, and flex (Factory standard) 24" x 24" Perforated lay-in with start collar, collar, and flex (Factory standard) 24" x 24" Perforated lay-in with start collar, collar, and flex (Factory standard) 24" x 24" Perforated lay-in with start collar, collar, and flex (Factory standard) R-4.2 Fiberglass insulation. Flex duct not to exceed 5' HVAC ventilation system(s) shall be balanced at site by others.
1.1
W . M
A D
IS
O
N S
T.
PH
O
EN
IX
, A Z
PH
-4
-6
X
-4
-6
SU
N
B
EL
T M
O D
U
LA
R
IN
C
THESE DRAWINGS REMAIN
THE PROPERTY OF PHOENIX
MODULAR AND ARE NOT TO BE
USED IN ANYWAY WITHOUT
WRITTEN PERMISSION.
SHEET:
OF
DEALER:
MOBILE MODULAR
MANAGEMENT GROUP
PROJECT:
BUILDING MB-ND
STATES:
CA
SERIAL NUMBERS:
PMI-6563-3660
DRAWN BY:
RQ/JK
PLOT DATE:
2/19/2025
REV # / DATE:
PH
O
EN
IX M
OD
UL
AR
MODEL NUMBER:
© 2025
V.T. ESKELSEN, P.E.
DESIGN ENGINEER
5301 W. MADISON ST.
PHOENIX, AZ 85043
WALL HATCHING LEGEND:
FULL HEIGHT WALL. SEE WALL FINISH
SCHEDULE FOR WALL COVERING
STRUCTURAL LEGEND
Symbol Description Qty
**ALL INTERIOR DIMENSIONS ARE FROM FINISH TO FINISH
& ALL EXTRIOR DIMENSIONS ARE FROM STUD TO STUD**
SHEARWALL TAG: 2-1/4"x0.099" DIA. NAILS, 6" O.C. AT EDGES AND 12" O.C. IN FIELD
HOLD DOWN TAG: SINGLE 3"x18"x26GA
GALV. STRAP WITH (11) 7d OR (8) 10d BOX
NAILS EACH END OF STRAP
DIAPHRAGM CHORD TIE SIMPSON 'ST2215'
(SEE DETAIL 5/6.0.)
(3) 2X6 HF #2 POST ON EACH SIDE OF
MOD-LINE W/ BLOCKING UNDER POST (TYP.
#3 HOLDOWN STRAP @ TOP & BOTTOM)
(3) 2x4 HF #2 POST ON EACH SIDE OF
MOD-LINE W/ BLOCKING UNDER POST (TYP.
#3 HOLDOWN STRAP @ TOP & BOTTOM)
TYP @ 4
LOCATIONS
TYP @ 40
LOCATIONS
TYP @ 4
LOCATIONS
TYP @ 4
LOCATIONS
TYP @ 4
LOCATIONS
WASTE & VENT LEGEND
DESCRIPTIONSYM
WASTE DRAIN (FACTORY INSTALLED)
WASTE DRAIN (SUPPLIED & INSTALLED BY OTHERS)
WASTE VENT (FACTORY INSTALLED)
NOTE:
1. ALL PIPE TO BE ABS SCHEDULE 40 & WILL SLOPE 1/4
PER FOOT.
2. PLUMBING MANIFOLD TO BE SUPPLIED & INSTALLED
AT SITE BY OTHERS.
3. ALL PLUMBING VENTS ARE INSTALLED 6" ABOVE
ROOF. IF VENT IS REQUIRED TO BE TALLER BY
LOCAL AHJ, THEN EXTENSION SHALL BE SUPPLIED
AND INSTALLED AT SITE BY OTHERS.
COLD & HOT SCHEMATIC
1. MAX PRESSURE RANGE @ CONNECTION:
2. MAX DEVELOPED LENGTH:
NOTE:
A. PEX HOT / COLD WATER SUPPLY MAY BE INSTALLED
ABOVE CEILING.
B. SHUT-OFF VALVES TO BE INSTALLED ON ALL
FIXTURES.
30-45 (CPC)
100'
DESCRIPTIONSYM
COLD WATER LINE
HOT WATER LINE
3" TO MAIN>>>
SAN-T
W.C.
2" 3"
LTTY
LTTY
SAN-T LAV.
2" 2"
LTTY
CO
LTTY
SAN-T M.SINK
2" 2"
V.T.R 3"
3"
3"
3"
2"
V.T.R 2"
2"
CO
LTTY
LTTY CO
SAN-T
F.D.
2" 2"
2"
2"
2"
WC
1"
LAV
1/ 2"
1/ 2"
1 1/4" INLET
G.V.
INLINE
STRAINER
M.SINK
1/ 2"
1/ 2"
EXP. TANK
W.H.
TEMP PRESSURE
RELIEF DRAIN
INTO PAN
1 1/4"
3/4"
3/4"
1/2"
1/2"
DRIP
PRIMER
H
AM
M
ER
1 1
1 1
'-1
0"
'-1 0"
'-1
0"
'-6
60'-0"
PANEL A
PANEL B
H
VA
C H
VA
C
PANEL C
10'-2"
9' -3
10'-2"
9' -3
8' -1
1"
8'-0"
8' -1
1"
7'-11 1/2"
8'-0" 7'-11 1/2"
4'-0"
02 03
8'-0"
10'-2"
8' -1
1"
4'-0"
16'-6"
9' -3
3' -1
1"
3' -1
1"
3' -1
1"
9'-4 1/2"
8'-0"
'-6
/2
8' -1
1"
8' -1
1"
5'-11"
4' -6
8'-0" 8'-0" 8'-0" 8'-0" 8'-0" 8'-0" 7'-7 1/2"
'-8
/2
'-8
/2
'-8
/2
'-8
/2
'-8
/2
'-8
/2
'-8
/2
04 02
02 02 02 02 02 02 02
9' -3
'-1
/2
'-6
86 SF
OFFICE
TILE
86 SF
OFFICE
TILE
86 SF
OFFICE
TILE
86 SF
OFFICE
TILE
86 SF
OFFICE
TILE
86 SF
OFFICE
TILE
82 SF
OFFICE
TILE
382 SF
CORRIDOR
TILE
71 SF
OFFICE
TILE
109 71 SF
LACTATION
TILE
71 SF
OFFICE
TILE
71 SF
PRINTER
TILE
53 SF
JAN.
TILE
174 SF
OFFICE
TILE
141 SF
OFFICE
TILE
82 SF
RR
TILE
11682 SF
OFFICE
TILE
82 SF
OFFICE
TILE
H
VA
C
A 11
3'-8"
A 11 A 11 A 11 A 11 A 11 A 11
12'-0" 20'-5" 28'-9" 37'-2" 45'-7" 53'-11"
A 11 A 11 A 11 A 11
4'-9" 15'-3" 39'-6" 52'-10"
W H
S3
B-3574
7' -1
1"
7' -1
1"
MODULE ( )1
MODULE ( )2
MODULE ( )3
2 2
H C
FD
2'-3"
2' -9
6"
36" MIN.
M
IN
9"
48" MIN. 9"
7" - 9"
" M
IN
T
O T
O P
TO
6" M
AX
TO
T
O P
" M
IN
T
O T
O P
TO
6" M
AX
TO
T
O P
57" MIN.
16" TO 18"
HANDICAPPED WATER
CLOSET SIDE VIEW
HANDICAPPED WATER
CLOSET FRONT VIEW
17" MIN
FIXTURE
DEPTH
6" MAX
TOE CLEARANCE
9" M
IN
" M
IN
" M
AX
" M
IN
8"
KNEE CLEARANCE
" M
IN
17" MIN.
19"
MAX.48" MAX.
5"
CLEAR FLOOR SPACE
AT LAVATORIESLAV CLEARANCES
WRAP ALL
EXPOSED
PIPES
MIRROR
CLEAR
FLOOR
SPACE
1 FLOOR PLAN
1/4"=1'-0" SQUARE FOOTAGE - 2130 S.F.
OCCUPANCY LOAD = 14
2.0
W . M
A D
IS
O
N S
T.
PH
O
EN
IX
, A Z
PH
-4
-6
X
-4
-6
SU
N
B
EL
T M
O D
U
LA
R
IN
C
THESE DRAWINGS REMAIN
THE PROPERTY OF PHOENIX
MODULAR AND ARE NOT TO BE
USED IN ANYWAY WITHOUT
WRITTEN PERMISSION.
SHEET:
OF
DEALER:
MOBILE MODULAR
MANAGEMENT GROUP
PROJECT:
BUILDING MB-ND
STATES:
CA
SERIAL NUMBERS:
PMI-6563-3660
DRAWN BY:
RQ/JK
PLOT DATE:
2/19/2025
REV # / DATE:
PH
O
EN
IX M
OD
UL
AR
MODEL NUMBER:
© 2025
V.T. ESKELSEN, P.E.
DESIGN ENGINEER
5301 W. MADISON ST.
PHOENIX, AZ 85043
(602) 447-6460
3 HOT / COLD SUPPLY
N.T.S.
4 D.W.V.
N.T.S.
AutoCAD SHX Text
ESTCODE
PANEL A
PANEL B
H
VA
C 2,4A
H
VA
C
2,4B
PANEL C
H
VA
C
2,4C
3DIM 3
PC
1C PC
1C
EXIT
1B
EX
IT
1B 1B
1B 1B
GFCI
11A
GFCI
WR
3B
GFCI
7A
W H
6B
6A
S3
3A
3A 3A 3A
11A
11A
7A 11A
11A 7A
7A 7A
7A
3B 3B
11A3A
3B 3B
3C3C
3C
5C3C
3C
5C5C
5C
7C5C
5C
7C7C
7C
9C7C
9C
9C9C
9C
3A 11A
3C 7C
7A
B-3574
XH+102
MODULE ( )1
MODULE ( )2
MODULE ( )3
M
CA
+102
T
T
T
3B
3B
H C
5'-4"
5' -5
/2
DIM
D D D D D D D
D D D D
D D D D
M
FD
O
5B
7B
3B
3A
3.0
W . M
A D
IS
O
N S
T.
PH
O
EN
IX
, A Z
PH
-4
-6
X
-4
-6
SU
N
B
EL
T M
O D
U
LA
R
IN
C
THESE DRAWINGS REMAIN
THE PROPERTY OF PHOENIX
MODULAR AND ARE NOT TO BE
USED IN ANYWAY WITHOUT
WRITTEN PERMISSION.
SHEET:
OF
DEALER:
MOBILE MODULAR
MANAGEMENT GROUP
PROJECT:
BUILDING MB-ND
STATES:
CA
SERIAL NUMBERS:
PMI-6563-3660
DRAWN BY:
RQ/JK
PLOT DATE:
2/19/2025
REV # / DATE:
PH
O
EN
IX M
OD
UL
AR
MODEL NUMBER:
© 2025
V.T. ESKELSEN, P.E.
DESIGN ENGINEER
5301 W. MADISON ST.
PHOENIX, AZ 85043
(602) 447-6460
1 ELECTRIC PLAN
1/4"=1'-0"
INDICATES T-GRID
SUSPENDED CEILING
INSTALLED @ FACTORY
INDICATES SUSPENDED
CEILING HOLD-BACK @
MATELINES, TO BE
COMPLETED ON-SITE
BY OTHERS
CEILING LEGEND
PANEL A
PANEL B
H
VA
C H
VA
C
PANEL C
2'-4 1/2"
1' -4
1' -4
1' -4
1' -4
2'-7 1/2"2'-4" 1'-9"
3'-2 1/2"
5"
1' -5
1' -3
7"
30W 1B 30W 1B 30W 1B 30W 1B
50W 1B 50W 1B 50W 1B 50W 1B 1B 30W
50W 1A
50W 1A
50W 1A50W 1A50W 1A
50W 1C 50W 1C 50W 1C 50W 1C 50W 1C 50W 1C 50W 1C
3'-6"
1' -3
7" 1'
-3
6" 1' -4
6" 1' -4
6" 1' -4
6" 1' -4
6" 1' -4
2'-4 1/2"
1' -1
1/
4"
1' -1
1/
4"
1' -1
1/
4"
1' -1
1/
4"
1' -1
1/
4"
1' -1
1/
4"
1' -1
1/
4"
2'-0" 1'-7 1/2" 2'-7" 2'-2 1/2" 1'-10" 1'-5 1/2"
H
VA
C
OCC
3DIM 3
OCC OCC
OCC
PC
PC
EXITEX
IT
1B
EXIT
1B
EXIT
MODULE ( )1
MODULE ( )2
MODULE ( )3
80 CFM
1B
T
T
T
1B 30W
1B 30W
3"
DIM
D D D D D D D
D D D D
D D D D
2'-4 1/2" 2'-4" 2'-7 1/2" 2'-0"
2'-10" 3'-2 1/2"
WAP
O
1A
70 CFM
SO
1 REFLECTED CEILING PLAN
1/4"=1'-0"
4.0
W . M
A D
IS
O
N S
T.
PH
O
EN
IX
, A Z
PH
-4
-6
X
-4
-6
SU
N
B
EL
T M
O D
U
LA
R
IN
C
THESE DRAWINGS REMAIN
THE PROPERTY OF PHOENIX
MODULAR AND ARE NOT TO BE
USED IN ANYWAY WITHOUT
WRITTEN PERMISSION.
SHEET:
OF
DEALER:
MOBILE MODULAR
MANAGEMENT GROUP
PROJECT:
BUILDING MB-ND
STATES:
CA
SERIAL NUMBERS:
PMI-6563-3660
DRAWN BY:
RQ/JK
PLOT DATE:
2/19/2025
REV # / DATE:
PH
O
EN
IX M
OD
UL
AR
MODEL NUMBER:
© 2025
V.T. ESKELSEN, P.E.
DESIGN ENGINEER
5301 W. MADISON ST.
PANEL A
PANEL B
H
VA
C H
VA
C
PANEL C
30W 30W 30W 30W
50W 50W 50W 50W 30W
50W
50W
50W50W50W
50W 50W 50W 50W 50W 50W 50W
TS-3 22x10 22x10
TS-3 22x10
H
VA
C
22x10 16x10 16x10 16x10 16x10
22x10 22x10 22x10 22x10 22x10
16x10 16x10 16x10
22x10 22x10 22x10 22x10
TS-3 22x10 22x10 16x10 16x10 16x10
22x10 22x10 22x10 22x10 22x10
16x10
6"
8" 8" 8" 8"
6" 6" 6" 6"
8" 8" 8"
8" 8" 8" 8" 8" 8" 8"
8"
OCC
OCC OCC
OCC
EXIT
EXIT
8" 8" 8" 8" 8" 8"
6" 6" 6" 10"
10"
6" 6" 10" 10"
MODULE ( )1
MODULE ( )2
MODULE ( )3
80 CFM
T
T
T
6' -9
30W
10"
30W
2' -4
6'
-4
2' -4
/2
5'
-8
/4
2' -1
0"
16x10
WAP
70 CFM
SO
1 HVAC PLAN
1/4"=1'-0"
5.0
W . M
A D
IS
O
N S
T.
PH
O
EN
IX
, A Z
PH
-4
-6
X
-4
-6
SU
N
B
EL
T M
O D
U
LA
R
IN
C
THESE DRAWINGS REMAIN
THE PROPERTY OF PHOENIX
MODULAR AND ARE NOT TO BE
USED IN ANYWAY WITHOUT
WRITTEN PERMISSION.
SHEET:
OF
DEALER:
MOBILE MODULAR
MANAGEMENT GROUP
PROJECT:
BUILDING MB-ND
STATES:
CA
SERIAL NUMBERS:
PMI-6563-3660
DRAWN BY:
RQ/JK
PLOT DATE:
2/19/2025
REV # / DATE:
PH
O
EN
IX M
OD
UL
AR
MODEL NUMBER:
© 2025
V.T. ESKELSEN, P.E.
DESIGN ENGINEER
5301 W. MADISON ST.
7' -1
0" C
EI
LI
N G
H T.8"
1"
M
IN
. S
TU
D H
T.
5/
" M
AX
S
TU
D
H T.
'-6
/4
" S H
IP
PI
N G
H
EI
G H
T W
/ P
LU
M
BI
N G
V
EN
T
" 60'-0" FLOOR LENGTH
GRADE
R-30 UNFACED INSULATION
(USING 2 LAYERS OF R-15)
2x8 RAFTERS
EPDM ROOFING
ROOF SHEATHING FASTENED W/
2-3/8"x0.113" NAILS OR 16GA
STAPLES W/ MIN. 1" PEN. @ 6" O.C.
@ EDGES & 12" O.C. IN FIELD
3/4" T&G PLYWOOD
DECKING
1/2" VCG OVER 2x6
EXT. STUDS @ 16" O.C.
STEEL 'Z' MEMBER
@ 16" O.C.
SUSPENDED LAY-IN
CEILING @ 7'-10" A.F.F.
R-19 UNFACED BATT
FIRE BLOCKING AT
CEILING
1/2" VCG OVER 2x4 INT.
STUDS @ 16" O.C.
7/16" LP SMART
PANEL SIDING OVER
BARRICADE WRAP
R-19 KRAFT FACED
INSULATION
PLYWOOD BEAM 18
H
EE
L
/4
'-1
3/
4" B
U
IL
D
IN
G H
EI
G
H T
/2
PE
AK
12" 1/4"
12" 1/4"
FILLER
LP SIDING
NAILER
FLOOR SHEATHING
WALL STUDS
@ 16" O.C.
2x BOTTOM
PLATE
CHASSIS MAIN RAIL
OR ENDMEMBER 3/
4"
LP TRIM
PLUMBING
VENT
PREMOLDED
EPDM PIPE BOOT
CLAMPING RING
LAP SEALANT
6" M
IN
LAP
SEALANT
BUTYL TAPE
TAPE PRIMER
ROOF UNDERLAYMENT EPDM
MEMBRANEROOF SHEATHING FLEX FROM
EXHAUST FAN
ROOF DECK
ROOF SHEATHING
LAP SEALANT
TAPE PRIMER
EPDM MEMBRANE
FACTORY INSTALLED
EXHAUST FAN VENT CAP
(FASTEN TO ROOF DECK)
CURED COVER TAPE
LAP SEALANT
3" MIN (TYP)
TOP TRIM (SHIP LOOSE
& SITE INSTALLED
OVER TENSION TIE)
TENSION TIE (SHIP LOOSE
& SITE INSTALL)
4" L.P. TRIM (SHIP LOOSE
& SITE INSTALLED)
J-RAIL
(FACTORY
INSTALLED)
M O
D U
LE
LI
N E
6" L.P. TRIM
(FACTORY
INSTALLED)
1'-6" 1'-6"
J-RAIL (SHIP LOOSE
& SITE INSTALLED
OVER TRIM)
WALL FINISH
VALUE
(LBS)STRAP TYPE FASTENERS
SIMPSON 'ST2215'
(20) 10d NAILS
(0.148"Ø x 1-1/2") 1791#
1 BUILDING CROSS SECTION
1/4"=1'-0"
6.0
W . M
A D
IS
O
N S
T.
PH
O
EN
IX
, A Z
PH
-4
-6
X
-4
-6
SU
N
B
EL
T M
O D
U
LA
R
IN
C
THESE DRAWINGS REMAIN
THE PROPERTY OF PHOENIX
MODULAR AND ARE NOT TO BE
USED IN ANYWAY WITHOUT
WRITTEN PERMISSION.
SHEET:
OF
DEALER:
MOBILE MODULAR
MANAGEMENT GROUP
PROJECT:
BUILDING MB-ND
STATES:
CA
SERIAL NUMBERS:
PMI-6563-3660
DRAWN BY:
RQ/JK
PLOT DATE:
2/19/2025
REV # / DATE:
PH
O
EN
IX M
OD
UL
AR
MODEL NUMBER:
© 2025
V.T. ESKELSEN, P.E.
DESIGN ENGINEER
5301 W. MADISON ST.
PHOENIX, AZ 85043
(602) 447-6460
2 WALL FINISH
1 1/2"=1'-0" @ FLOOR 3 PLUMBING VENT
1 1/2"=1'-0" FACTORY INSTALLED 4 EXHAUST VENT
1 1/2"=1'-0" FACTORY INSTALLED 5 ROOF DIAPHRAGM CHORD TIE
1" = 1'-0" @ MODLINE
6 NOT USED
1 1/2"=1'-0" @ FLOOR
HATCHING DENOTES
SHIPLOOSE TRIM
A
B
D C
12" (7/16") LP TRIM
(BOTTOM HORIZONTAL)
HOOD
4" (7/16") LP TRIM
(INTERMEDIATE HORIZONTAL)
4" (7/16") LP TRIM
(CORNER)
BODY
6" (7/16") LP TRIM
(TOP HORIZONTAL)
EXHAUST FAN
VENT (TYP 2)
'-1
3/
4" B
U
IL
D
IN
G H
T.
13'-6 3/4" SHIPPING HEIGHT
12"
1/4" 12"
1/4"
4" (7/16") LP
WINDOW TRIM
12" 1/4"
12" 1/4"
6.0
HW J-BOX FOR
FUTURE SPEAKERS
ELEC. PANEL
6x6 INLET BOX WP GFCI RECEP
PORCH LIGHT
(TYP 2)
4" (7/16") LP
MOD-LINE TRIM
(SHIPPED LOOSE)
4" (7/16") LP MOD-LINE
TRIM (SHIPPED LOOSE) 4" (7/16") LP
DOOR TRIM
6.0
HW J-BOX FOR
FUTURE CAMERA
REMOTE HEAD
(TYP 2)
4" (7/16") LP MOD-LINE
TRIM (SHIPPED LOOSE)
4" (7/16") LP MOD-LINE
TRIM (SHIPPED LOOSE)
A ELEVATIONS
1/4"=1'-0"
7.0
W . M
A D
IS
O
N S
T.
PH
O
EN
IX
, A Z
PH
-4
-6
X
-4
-6
SU
N
B
EL
T M
O D
U
LA
R
IN
C
THESE DRAWINGS REMAIN
THE PROPERTY OF PHOENIX
MODULAR AND ARE NOT TO BE
USED IN ANYWAY WITHOUT
WRITTEN PERMISSION.
SHEET:
OF
DEALER:
MOBILE MODULAR
MANAGEMENT GROUP
PROJECT:
BUILDING MB-ND
STATES:
CA
SERIAL NUMBERS:
PMI-6563-3660
DRAWN BY:
RQ/JK
PLOT DATE:
2/19/2025
REV # / DATE:
PH
O
EN
IX M
OD
UL
AR
MODEL NUMBER:
© 2025
V.T. ESKELSEN, P.E.
DESIGN ENGINEER
5301 W. MADISON ST.
PHOENIX, AZ 85043
(602) 447-6460
B ELEVATIONS
1/4"=1'-0"
D ELEVATIONS
1/4"=1'-0" C ELEVATIONS
1/4"=1'-0"
| Sheets and Views |
| PMI-6563-3660 (CA) mu-Plot-SPEC-C (1.0) |
| PMI-6563-3660 (CA) mu-Plot-SCHED-C (1.1) |
| PMI-6563-3660 (CA) mu-Plot-FLR-C (2.0) |
| PMI-6563-3660 (CA) mu-Plot-ELEC-C (3.0) |
| PMI-6563-3660 (CA) mu-Plot-RCP-C (4.0) |
| PMI-6563-3660 (CA) mu-Plot-HVAC-C (5.0) |
| PMI-6563-3660 (CA) mu-Plot-X-SECT-C (6.0) |
| PMI-6563-3660 (CA) mu-Plot-ELEVS-C (7.0) |