24_1004 DESIGN.pdf
PDF 5 MB Posted
- Attached to
- Construction of Pickleball Pavilion
- Solicitation number
- PE-76500-NONST-2025-000000008
- Issued by
- Barrow County, Georgia
About this file
This document contains technical specifications and drawings for the design and construction of a metal structure for the Calhoun Park project in Calhoun, Georgia. The structure will be a 30' x 44' standing seam roof building with a clear height of 7'6". The drawings provide details on the structural framing, anchor and footing layout, frame connection details, and roof layout and connections. The design criteria includes wind, snow, and seismic loading parameters per the 2018 International Building Code with 2020 Georgia amendments. The manufacturer, Porter Corp., has several approvals and certifications for the fabrication and installation of the structure. The drawings are sealed by a professional engineer, and the foundation design is provided by the manufacturer.
The document outlines the material specifications, including ASTM designations for the steel tubing, pipes, plates, and roof panels. It also provides details on the hardware, welding, and installation requirements. Specific guidance is given on anchor bolt placement, concrete properties, and pretensioning of high-strength bolts. The drawings illustrate the framing layout, connection details, and roofing system installation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFQ 24_1004 Pickleball Pavillion.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R
A Division of PORTERCORP 4240 N. 136th AVE HOLLAND, MI 49424 (616) 888-3500
GENERAL:
2018 INTERNATIONAL BUILDING CODE w/ 2020 GA. AMD.
RISK CATEGORY: II
DEAD LOAD:
ROOF DEAD LOAD: 2 PSF
FRAME DEAD LOAD: SELF WEIGHT
LIVE LOAD:
ROOF LIVE LOAD: 20 PSF
SNOW DESIGN DATA:
GROUND SNOW LOAD (Pg): 5 PSF FLAT ROOF SNOW LOAD (Pf): 4 PSF SNOW EXPOSURE FACTOR (Ce): 1.0 SNOW LOAD IMPORTANCE FACTOR (Is): 1.0 THERMAL FACTOR (Ct): 1.2 ROOF SLOPE FACTOR (Cs): 1.0 DRIFT SURCHARGE LOAD (Pd): 11.68 PSF WIDTH OF SNOW DRIFT (w): 4.78 FT MINIMUM HORIZONTAL SEPARATION DISTANCE (s): 0 FT
WIND DESIGN DATA:
BASIC WIND SPEED (V): 110 MPH
ALLOWABLE STRESS DESIGN WIND SPEED (Vasd): 85 MPH
GUST EFFECT FACTOR (G): 0.85
INTERNAL PRESSURE COEFFICIENT (GCpi): 0
WIND EXPOSURE: C
SEISMIC DESIGN DATA:
STEEL SYSTEMS NOT SPECIFICALLY DETAILED
FOR SEISMIC RESISTANCE
SEISMIC IMPORTANCE FACTOR (Ie): 1.0
SEISMIC DESIGN CATEGORY: C
SEISMIC SITE CLASS: D DEFAULT
SHORT SPECTRAL RESPONSE (Ss): 0.55
1-SEC SPECTRAL RESPONSE (S1): 0.13
DESIGN SHORT SPECTRAL RESPONSE (SDS): 0.50
DESIGN 1-SEC SPECTRAL RESPONSE (SD1): 0.20
SEISMIC RESPONSE COEFFICIENT (Cs): 0.17
RESPONSE MODIFICATION COEFFICIENT (R): 3.00
EQUIVALENT LATERAL FORCE PROCEDURE
SEE CALCULATIONS FOR ADDITIONAL DATA
ADDITIONAL CRITERIA:
NONE
R by P
O R
TE
R
C O
R P
W W
W .P
O
LI
G O
N .C
O M
M A
IN
6)
-3
FI
EL
D
S U
PP
O
R T:
(6
) 8
-3
GENERAL NOTES:
UNLESS NOTED OTHERWISE, THIS STRUCTURE WAS DESIGNED TO ONLY SUPPORT WHAT IS 1.
SHOWN ON THESE DRAWINGS. POLIGON MUST BE CONTACTED IF ANYTHING ELSE IS TO
BE ATTACHED TO THIS STRUCTURE (WALLS, COLUMN WRAPS, RAILINGS, ETC.) SO THE
DESIGN OF THIS STRUCTURE CAN BE REVIEWED AND POSSIBLY REVISED.
THE ENGINEERING SEAL FOR THE STRUCTURE DETAILED IN THESE DRAWINGS IS ONLY 2.
VALID IF PORTER CORP DESIGNS AND FABRICATES THE STEEL COMPONENTS.
FABRICATING THE STEEL COMPONENTS ELSEWHERE VOIDS THE ENGINEERING PROVIDED
BY PORTER CORP.
UNLESS NOTED OTHERWISE, THIS STRUCTURE WAS DESIGNED ASSUMING A 20' 3.
SEPARATION BETWEEN ANY ADJACENT STRUCTURE WITH AN EAVE HEIGHT EQUAL TO OR
GREATER THAN THE EAVE HEIGHT OF THIS STRUCTURE (SEE SNOW DESIGN DATA). IF THAT
SEPARATION DOES NOT EXIST AND THE GROUND SNOW LOAD (Pg) IS GREATER THAN 0
PSF, POLIGON MUST BE CONTACTED SO THE DESIGN OF THIS STRUCTURE CAN BE
REVIEWED AND POSSIBLY REVISED.
STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED, AND ERECTED IN ACCORDANCE 4.
WITH THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) SPECIFICATION
MANUAL REFERENCED IN THE GOVERNING BUILDING CODE.
ALL WELDING IS PERFORMED BY AMERICAN WELDING SOCIETY (AWS) CERTIFIED 5.
WELDERS AND CONFORMS TO AWS D1.1 OR D1.3 AS REQUIRED.
PARTS SHOWN MAY BE UPGRADED DUE TO STANDARDIZED FABRICATION. REFER TO THE 6.
SHIPPING BILL OF MATERIALS AND FINAL INSTALLATION INSTRUCTIONS INCLUDED WITH
THE STRUCTURE FOR POSSIBLE SUBSTITUTIONS AND IMPROVEMENTS.
FOR PROPER FIELD INSTALLATION OF THE BUILDING IT IS RECOMMENDED THAT THE 7.
PRIMARY FRAME INSTALLER AND THE ROOF INSTALLER HAVE A MINIMUM FIVE (5) YEARS
DOCUMENTED EXPERIENCE INSTALLING THIS TYPE OF PRODUCT.
THE DRAWINGS REPRESENT THE FINISHED STRUCTURE. THE CONTRACTOR SHALL 8.
SUPERVISE AND DIRECT THE WORK, AND SHALL BE SOLELY RESPONSIBLE FOR
CONSTRUCTION MEANS, TECHNIQUES, SEQUENCES AND PROCEDURES, INCLUDING
BRACING, SHORING, LAYDOWN AND PROTECTION OF CONSTRUCTION MATERIALS, ETC.
TEMPORARY SHORING AND BRACING SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR.
FOR PROPER FIELD INSTALLATION OF THE BUILDING IT IS RECOMMENDED THAT ELECTRIC 9.
WIRING, IF REQUIRED, BE RUN THROUGH THE STRUCTURAL MEMBERS BEFORE THE
BUILDING IS ERECTED.
MAKING HOLES, CUTS OR MODIFICATIONS TO THE STRUCTURAL STEEL MEMBERS IS NOT 10.
PERMITTED IN THE FIELD WITHOUT SPECIFIC APPROVAL OF POLIGON.
CERTIFICATES:
MIAMI-DADE COUNTY CERTIFICATE OF COMPETENCY NO. 23-0915.11
PCI (POWDER COATING INSTITUTE) 4000 CERTIFIED
FABRICATOR APPROVALS:
CITY OF PHOENIX, AZ APPROVED FABRICATOR #C08-2010
CITY OF LOS ANGELES, CA APPROVED FABRICATOR #FB01596
CITY OF RIVERSIDE, CA APPROVED FABRICATOR #SF_000042
CITY OF HOUSTON, TX APPROVED FABRICATOR #470
CLARK COUNTY, NV APPROVED FABRICATOR #264
STATE OF UTAH APPROVED FABRICATOR 02008-14
AISC APPROVED FABRICATOR C-00022589
AWS CERTIFIED WELDING FABRICATOR #221003F
MATERIALS:
DESCRIPTION
TUBE STEEL
SCHEDULE PIPE
RMT PIPE
LIGHT GAGE COLD FORMED
STRUCTURAL STEEL PLATE
ROOF PANELS (STEEL)
ANCHOR BOLTS
ASTM DESIGNATION
A500 (GRADE C)
A53 (GRADE B)
A519
A1003 (GRADE 50)
A36 A653
SEE SHEET 2.1
SHEET NUMBER DRAWING DESCRIPTION
CS COVER SHEET
1 ARCHITECTURAL ELEVATIONS
2-2.1 ANCHOR AND FOOTING LAYOUT / DETAILS
3-3.1 STRUCTURAL FRAMING PLAN
4-4.2 FRAME CONNECTION DETAILS
5 ELECTRICAL VIEWS-N/A
6-6.1 ROOF LAYOUT
7-7.3 ROOF CONNECTION DETAILS
SHEET
CS
PR
O
JE
C
T:
PR
O
JE
C
T L
O C
A
TIO
N
C O
V
ER
S
HE
ET
C
A D
M O
D
EL
D
RA
W
IN
G
:C A
LH
O
UN
P
A
RK
C A
LH
O
UN
, G
A
PROJECT NAME:
PROJECT LOCATION:
DRAWING LIST:
BUILDING TYPE:
ROOF TYPE:
CALHOUN PARK
STANDING SEAM (22 GA)
CHE 30X44
O
RD
ER
N O
A
C
RE
A
TIO
N D
A
TE
: 5/
/2
1:
4/ 4/
~P
PR
IN
T D
A
TE
RE
V
L
EV
EL
SC
A
LE
D
RA
W N
B Y:
IF THESE DRAWINGS ARE SEALED, THE SEAL APPLIES ONLY TO BUILDING
COMPONENTS DETAILED WITHIN THESE DRAWINGS AND SUPPLIED BY
PORTER CORP AS WELL AS THE FOUNDATION DESIGN, IF APPLICABLE.
CALHOUN, GA
MANUFACTURER NOTES:
DESIGN CRITERIA:
P18946BUILDING NUMBER:
2024B
78831ORDER NUMBER:
m ax
.m ac d er m ai d by P
O R
TE
R
C O
R P
W W
W .P
O
LI
G O
N .C
O M
M A
IN
6)
-3
FI
EL
D
S U
PP
O
R T:
(6
) 8
-3
FINISH GRADE
(ASSUMED AT CONSTANT
ELEVATION UNLESS
OTHERWISE NOTED)
15'-9 1/8"
REF
7'-6"
CLEAR
FINISH GRADE
(ASSUMED AT CONSTANT
ELEVATION UNLESS
OTHERWISE NOTED)
15'- 3/16"
REF
30'- 3/16"
REF
44'- 1/8"
REF
SHEET
PR
O
JE
C
T:
PR
O
JE
C
T L
O C
A
TIO
N
A
RC
HI
TE
C
TU
RA
L
EL
EV
A
TIO
N S
C A
D M
O D
EL
D
RA
W
IN
G :C
A
LH
O
UN
P A
RK
C al ho un
, G A
O
RD
ER
N O
A
C
RE
A
TIO
N D
A
TE
: 5/
/2
1:
4/ 4/
~P
PR
IN
T D
A
TE
RE
V
L
EV
EL
SC
A
LE
D
RA
W N
B Y:
IF THESE DRAWINGS ARE SEALED, THE SEAL APPLIES ONLY TO BUILDING
COMPONENTS DETAILED WITHIN THESE DRAWINGS AND SUPPLIED BY
PORTER CORP AS WELL AS THE FOUNDATION DESIGN, IF APPLICABLE.
m ax
.m ac d er m
P
O R
TE
R
C O
R P
W W
W .P
O
LI
G O
N .C
O M
M A
IN
6)
-3
FI
EL
D
S U
PP
O
R T:
(6
) 8
-3
ANCHOR BOLT PATTERN1
2 BASE PLATE THICKNESS: 1/2"
40'-0"
26'-0"
47'-8 1/2"
REF
20'-0"
TYP.
32'-9 5/8"
REF.
SHEET 2
1 1/2" TYP 3"
TYP
1 1/8" THRU
ELECTRICAL ACCESS HOLE
4X 3/4" THRU
ANCHOR BOLT HOLE
7"
11"
ARROW TIP ON TEMPLATE
POINTS TO TRUSS SIDE OF COLUMN.
SHEET
PR
O
JE
C
T:
PR
O
JE
C
T L
O C
A
TIO
N
A N
C
HO
R A
N D
F O
O
TIN
G L
A
YO
UT
C
A D
M O
D
EL
D
RA
W
IN
G
:C A
LH
O
UN
P
A
RK
C al ho un
, G A
O
RD
ER
N O
A
C
RE
A
TIO
N D
A
TE
: 5/
/2
1:
4/ 4/
~P
PR
IN
T D
A
TE
RE
V
L
EV
EL
SC
A
LE
D
RA
W N
B Y:
IF THESE DRAWINGS ARE SEALED, THE SEAL APPLIES ONLY TO BUILDING
COMPONENTS DETAILED WITHIN THESE DRAWINGS AND SUPPLIED BY
PORTER CORP AS WELL AS THE FOUNDATION DESIGN, IF APPLICABLE.
ANCHOR AND FOOTING LAYOUT NOTES:
ANCHORS MUST BE CENTERED IN 1.
FOOTINGS
FOOTINGS MUST BE TURNED TO ALIGN 2.
WITH COLUMN AND TRUSS
CENTERLINE.
m ax
.m ac d er m
ENSURE 3" CLEAR DISTANCE BETWEEN
EDGE OF REINFORCING AND EDGE OF
CONCRETE FOOTING (TOP, SIDE, AND BOTTOM)
MINIMUM
Ø
COLUMN
(LOCATED AT CENTER OF FOOTING)
FINISHED GRADE
(ASSUMED AT CONSTANT ELEVATION
UNLESS OTHERWISE NOTED)
TOP OF CONCRETE FOOTING
PIER FOOTING OPTION (INTERNAL ANCHOR BOLTS)
2 TIES IN THE TOP 5"
(4) PLACES
(ENSURE 1 1/2"
EXPOSED FROM TOP
OF FOOTING)
Ø
ANCHOR BOLT
(4) PLACES
FROM TOP OF FOOTING TO
TOP OF HEAD/THREADED NUT)
OPTIONAL SLAB &
EXPANSION MATERIAL
NOT BY MANUFACTURER
+1/2" -0"
FOOTING DESIGN BY MANUFACTURER, FOOTING MATERIALS BY OTHERS.
(TYPICAL WITH EACH COLUMN, QTY OF REINFORCING AND ANCHOR BOLTS
SPECIFIED IN NOTES REFLECT SITE SPECIFIC REQUIREMENTS)
5'-0"
3'-6"
(12) #7 VERTICAL BARS (EQ. SPACED)
#4 HORIZONTAL TIES AT 6" O.C. WITH
1/2" NUT
1/2" WASHER
1/2"X10" LONG
(8" EFFECTIVE EMBEDMENT
ENSURE 3" CLEAR DISTANCE BETWEEN
EDGE OF REINFORCING AND EDGE OF
CONCRETE FOOTING (TOP, SIDE, AND BOTTOM)
MINIMUM
Ø
MINIMUM
COLUMN
(LOCATED AT CENTER OF FOOTING)
FINISHED GRADE
(ASSUMED AT CONSTANT ELEVATION
UNLESS OTHERWISE NOTED)
TOP OF CONCRETE FOOTING
PIER FOOTING OPTION (INTERNAL ANCHOR BOLTS)
FOOTING DESIGN BY MANUFACTURER, FOOTING MATERIALS BY OTHERS.
(TYPICAL WITH EACH COLUMN, QTY OF REINFORCING SHOWN IN
DRAWINGS MAY NOT REFLECT REQUIREMENTS)
2 TIES IN THE TOP 5"
1/2" NUT
1/2" WASHER
(4) PLCS
(ENSURE 1 1/2"
EXPOSED FROM TOP
OF FOOTING
Ø1/2"X10" LONG
ANCHOR BOLT
(4) PLCS
(8" MINIMUM
EMBEDMENT INTO
CONCRETE FOOTING)
OPTIONAL SLAB &
EXPANSION MATERIAL
NOT BY MANUFACTURER
+1/2" -0"
5'-0"
3'-6"
(12) #7 VERTICAL BARS (EQ. SPACED)
#4 HORIZONTAL TIES AT 6" O.C. WITH
ENSURE 3" CLEAR DISTANCE BETWEEN
EDGE OF REINFORCING AND EDGE OF
CONCRETE FOOTING (TOP, SIDE, AND BOTTOM)
MINIMUM
MINIMUM
SQUARE
COLUMN
(LOCATED AT CENTER OF FOOTING)
FINISHED GRADE
(ASSUMED AT CONSTANT ELEVATION
UNLESS OTHERWISE NOTED)
TOP OF CONCRETE FOOTING
PAD FOOTING OPTION (INTERNAL ANCHOR BOLTS)
FOOTING DESIGN BY MANUFACTURER, FOOTING MATERIALS BY OTHERS.
(TYPICAL WITH EACH COLUMN, QTY OF REINFORCING SHOWN IN
DRAWINGS MAY NOT REFLECT REQUIREMENTS)
Ø1/2"X10" LONG
ANCHOR BOLT
(4) PLCS
(8" MINIMUM
EMBEDMENT INTO
CONCRETE FOOTING)
OPTIONAL SLAB &
EXPANSION MATERIAL
NOT BY MANUFACTURER
1/2" NUT
1/2" WASHER
(4) PLCS
(ENSURE 1 1/2
EXPOSED FROM TOP
OF FOOTING)
+1/2" -0"
EACH WAY, TOP & BOTTOM
1'-6"
5'-6"
(7) #5 VERTICAL BARS (EQ. SPACED)
R by P
O R
TE
R
C O
R P
W W
W .P
O
LI
G O
N .C
O M
M A
IN
6)
-3
FI
EL
D
S U
PP
O
R T:
(6
) 8
-3
THE FOUNDATION DESIGN SHOWN ON THESE DRAWINGS IS NOT SITE
SPECIFIC, BUT BASED ON THE PRESUMPTIVE ALLOWABLE FOUNDATION
PRESSURES IN CHAPTER 18 OF THE BUILDING CODE (CLASS 5 SOIL). THE
BUILDING OFFICIAL IN THE JURISDICTION IN WHICH THIS STRUCTURE IS
LOCATED MAY REQUIRE A SITE SPECIFIC GEOTECHNICAL REPORT OR
LETTER FROM A QUALIFIED LOCAL PROFESSIONAL ENGINEER ATTESTING
TO WHETHER THE ACTUAL SITE CONDITIONS MEET THE ASSUMPTIONS
IDENTIFIED ABOVE.
FOUNDATION NOTES:
FOUNDATIONS SHALL BEAR ON COMPETENT, UNDISTRUBED SOIL OR 95% COMPACTED FILL. 1.
IF SIGNS OF ORGANIC MATERIAL, UNCONTROLLED FILL, CLAY OR SILT, HIGH WATER TABLE
OR OTHER POSSIBLE DETRIMENTAL CONDITIONS ARE FOUND, CONSTRUCTION OF THE
FOUNDATIONS MUST BE STOPPED AND A GEOTECHNICAL ENGINEER BE CONTACTED.
NO FOUNDATIONS SHALL BE PLACED INTO OR ADJACENT TO SUBGRADE CONTAINING 2.
WATER, ICE, FROST, ORGANIC OR LOOSE MATERIAL.
WATER SHALL NOT BE PERMITTED TO ACCUMULATE IN FOUNDATION EXCAVATIONS.3.
IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE LOCAL FROST DEPTH REQUIREMENT 4.
PRIOR TO CONSTRUCTION.
IF FOUNDATIONS SHOWN DO NOT MEET LOCAL FROST DEPTH REQUIREMENTS, EXTEND THE 5.
DRILLED PIER FOUNDATION AS REQUIRED, EXTENDING THE VERTICAL BARS AND PROVIDING
ADDITIONAL TIES TO MEET SPACING REQUIREMENTS AS SHOWN. IF FROST DEPTH
REQUIREMENTS ARE NOT MET, AND NO DRILLED PIER DESIGN IS PROVIDED, CONTACT
POLIGON.
ALLOWABLE SOIL PRESSURES (AS APPLICABLE):6.
ENSURE 3" CLEAR DISTANCE BETWEEN
EDGE OF REINFORCING AND EDGE OF
CONCRETE FOOTING (TOP, SIDE,
SQUARE
COLUMN
(LOCATED AT CENTER OF FOOTING)
FINISHED GRADE
(ASSUMED AT CONSTANT ELEVATION
UNLESS OTHERWISE NOTED)
TOP OF CONCRETE FOOTING
PAD FOOTING OPTION (INTERNAL ANCHOR BOLTS)
Ø
ANCHOR BOLT
(4) PLACES
FROM TOP OF FOOTING TO
TOP OF HEAD/THREADED NUT)
OPTIONAL SLAB &
EXPANSION MATERIAL
NOT BY MANUFACTURER
(4) PLACES
(ENSURE 1 1/2
EXPOSED FROM TOP
OF FOOTING)
+1/2" -0"
EACH WAY, TOP & BOTTOM
FOOTING DESIGN BY MANUFACTURER, FOOTING MATERIALS BY OTHERS.
(TYPICAL WITH EACH COLUMN, QTY OF REINFORCING AND ANCHOR BOLTS
SPECIFIED IN NOTES REFLECT SITE SPECIFIC REQUIREMENTS)
AND BOTTOM)
1'-6"
5'-6"
1/2"X10" LONG
(8" EFFECTIVE EMBEDMENT
1/2" NUT
1/2" WASHER
(7) #5 HORIZONTAL BARS (EQ. SPACED)
SPREAD PAD
VERTICAL BEARING 1500 PSF
LATERAL COHESION 130 PSF
DRILLED PIER
VERTICAL BEARING 1500 PSF
LATERAL BEARING 100 PSF/FT
SHEET
2.1
PR
O
JE
C
T:
PR
O
JE
C
T L
O C
A
TIO
N
A N
C
HO
R A
N D
F O
O
TIN
G D
ET
A
IL
S
C A
D M
O D
EL
D
RA
W
IN
G :C
A
LH
O
UN
P A
RK
C al ho un
, G A
O
RD
ER
N O
A
C
RE
A
TIO
N D
A
TE
: 5/
/2
1:
4/ 4/
~P
PR
IN
T D
A
TE
RE
V
L
EV
EL
SC
A
LE
D
RA
W N
B Y:
IF THESE DRAWINGS ARE SEALED, THE SEAL APPLIES ONLY TO BUILDING
COMPONENTS DETAILED WITHIN THESE DRAWINGS AND SUPPLIED BY
PORTER CORP AS WELL AS THE FOUNDATION DESIGN, IF APPLICABLE.
m ax
.m ac d er m ai d
ANCHOR BOLT NOTES - INTERNAL (ANCHOR BOLTS LOCATED WITHIN COLUMN):
ANCHOR BOLTS SHALL BE ASTM A307 (GRADE A) MATERIAL UNLESS OTHERWISE NOTED.1.
ANCHOR BOLTS SHALL BE EITHER "HEADED" OR "THREADED WITH NUT" AS DEFINED IN THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION MANUAL.2.
HOOKED ANCHOR BOLTS ARE NOT ACCEPTABLE.3.
ACCURATE ANCHOR BOLT PLACEMENT IS CRITICAL. TO ENSURE THE ANCHOR BOLT LAYOUT MEETS THE DIMENSIONS REQUIRED ON THE DRAWINGS, 4.
SURVEY (OR MEASURE) THE LOCATION OF ALL ANCHOR BOLTS PRIOR TO POURING THE FOOTINGS. AN ADDITIONAL SURVEY (OR MEASUREMENT) SHOULD BE MADE AFTER THE FOOTINGS ARE POURED TO CONFIRM THE ANCHOR BOLTS DID NOT SHIFT DURING THE CONCRETE POUR.
THE MANUFACTURER STRONGLY RECOMMENDS USING ANCHOR BOLT TEMPLATES BECAUSE THEY SIGNIFICANTLY IMPROVE THE ACCURACY OF 5.
ANCHOR BOLT PLACEMENT. AN ANCHOR BOLT TEMPLATE IS PROVIDED WITH ANY ANCHOR BOLT KIT PURCHASED.
IF OUTSIDE CONSULTING ENGINEERS ARE DESIGNING THE FOUNDATIONS FOR THIS STRUCTURE, THEY MUST REFER TO THE MANUFACTURER'S 6.
CALCULATIONS FOR MINIMUM CONCRETE PROPERTIES (COMPRESSIVE STRENGTH, EDGE DISTANCE, ETC.) REQUIRED FOR THE ANCHOR BOLT DESIGN.
ELECTRICAL ACCESS HOLE IS ALWAYS LOCATED IN THE COLUMN BASE PLATE AS SHOWN. BE SURE TO KEEP THE ANCHOR BOLT TEMPLATE PROPERLY 7.
ORIENTED WHEN ELECTRICAL ACCESS TO THE COLUMN IS REQUIRED. TEMPLATE MUST BE REMOVED BEFORE INSTALLING COLUMNS.
THE CALCULATIONS FOR THIS STRUCTURE ASSUME A PINNED COLUMN BASE.8.
THE FOLLOWING ADHESIVE ANCHORS MAY BE SUBSTITUTED FOR THE CAST-IN-PLACE ANCHOR BOLTS:
-HILTI HIT-HY 200 (A OR R) V3 ADHESIVE WITH Ø 1/2" HAS-E ROD WITH 6" EFFECTIVE EMBEDMENT.
CONTRACTOR SHALL FOLLOW ALL INSTALLATION SPECIFICATIONS AND REQUIREMENTS OF ANCHOR MANUFACTURER.
9.
ANCHOR BOLT NOTES - EXTERNAL (ANCHOR BOLTS LOCATED OUTSIDE COLUMN):
ANCHOR RODS TO BE ASTM F1554 GRADE 55 TYPE S1 WITH "UNC" CLASS 2A THREADS, HEAVY HEX NUTS AND STANDARD CUT WASHERS, UNLESS 1.
OTHERWISE NOTED.
ANCHOR BOLTS SHALL BE EITHER "HEADED" OR "THREADED WITH NUT" AS DEFINED IN THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION MANUAL.2.
HOOKED ANCHOR BOLTS ARE NOT ACCEPTABLE.3.
ACCURATE ANCHOR BOLT PLACEMENT IS CRITICAL. TO ENSURE THE ANCHOR BOLT LAYOUT MEETS THE DIMENSIONS REQUIRED ON THE DRAWINGS, 4.
SURVEY (OR MEASURE) THE LOCATION OF ALL ANCHOR BOLTS PRIOR TO POURING THE FOOTINGS. AN ADDITIONAL SURVEY (OR MEASUREMENT) SHOULD BE MADE AFTER THE FOOTINGS ARE POURED TO CONFIRM THE ANCHOR BOLTS DID NOT SHIFT DURING THE CONCRETE POUR.
THE MANUFACTURER STRONGLY RECOMMENDS USING ANCHOR BOLT TEMPLATES BECAUSE THEY SIGNIFICANTLY IMPROVE THE ACCURACY OF 5.
ANCHOR BOLT PLACEMENT. AN ANCHOR BOLT TEMPLATE IS PROVIDED WITH ANY ANCHOR BOLT KIT PURCHASED.
IF OUTSIDE CONSULTING ENGINEERS ARE DESIGNING THE FOUNDATIONS FOR THIS STRUCTURE, THEY MUST REFER TO THE MANUFACTURER'S 6.
CALCULATIONS FOR MINIMUM CONCRETE PROPERTIES (COMPRESSIVE STRENGTH, EDGE DISTANCE, ETC.) REQUIRED FOR THE ANCHOR BOLT DESIGN.
ELECTRICAL ACCESS HOLE IS ALWAYS LOCATED IN THE COLUMN BASE PLATE AS SHOWN. TEMPLATE MUST BE REMOVED BEFORE INSTALLING COLUMNS.7.
GROUT UNDER BASEPLATES SHALL BE NON-METALLIC, NON-SHRINK GROUT WITH MINIMUM f'c=6500 PSI.8.
THE CALCULATIONS FOR THIS STRUCTURE ASSUME A FIXED COLUMN BASE.9.
THE FOLLOWING ADHESIVE ANCHORS MAY BE SUBSTITUTED FOR THE CAST-IN-PLACE ANCHOR BOLTS:
-HILTI HIT-HY 200 (A OR R) V3 ADHESIVE WITH Ø 1/2" HAS-E ROD WITH 6" EFFECTIVE EMBEDMENT.
CONTRACTOR SHALL FOLLOW ALL INSTALLATION SPECIFICATIONS AND REQUIREMENTS OF ANCHOR MANUFACTURER.
10.
CONCRETE NOTES:
ALL CONCRETE CONSTRUCTION SHALL CONFORM TO THE CURRENT “ACI MANUAL OF CONCRETE PRACTICE”.1.
PORTLAND CEMENT SHALL CONFORM TO ASTM C-150 TYPE II OR TYPE V.2.
IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE CONCRETE MIX DESIGN MEETS THE "ACI MANUAL OF CONCRETE PRACTICE" REQUIREMENTS 3.
FOR CONCRETE BY EXPOSURE CLASS.
THE USE OF CHLORIDE ACCELERATORS IS NOT PERMITTED.4.
COARSE AGGREGATE SHALL BE #57 OR LARGER.5.
CONCRETE AT PLACEMENT SHALL HAVE A SLUMP OF 4" +/- 1".6.
MINIMUM CONCRETE COMPRESSIVE STRENTGH AT 28 DAYS: 4500 PSI.7.
REINFORCING STEEL SHALL BE DEFORMED STEEL CONFORMING TO THE REQUIREMENTS OF ASTM A615 (DEFORMATIONS SHALL BE IN 8.
ACCORDANCE WITH ASTM A305) AS FOLLOWS:
GRADE 60: #4 BARS AND LARGER
GRADE 40: #3 BARS
PRIOR TO PLACING OF CONCRETE, REINFORCING STEEL AND EMBEDDED ITEMS SHALL BE WELL SECURED IN POSITION.9.
MAINTAIN 3" CONCRETE COVERAGE TO FACE OF BARS UNLESS OTHERWISE NOTED.10.
BARS SHALL BE CLEAN OF RUST, GREASE OR OTHER MATERIAL LIKELY TO IMPAIR BOND. BENDS SHALL BE MADE COLD.11.
WELDING OF REINFORCEMENT IS NOT ALLOWED.12.
ALL EXPOSED EXTERNAL CORNER OF FOUNDATIONS TO BE CHAMFERED BY 3/4" BY 45 DEGREES UNLESS NOTED OTHERWISE.13.
ALL NEW CONCRETE SHALL BE CURED IMMEDIATELY AFTER FINISHING OF REMOVING FORMWORK. CURING SHALL BE EITHER A MOIST CURE 14.
METHOD OR THE USE OF A CURING COMPOUND.
P
O R
TE
R
C O
R P
W W
W .P
O
LI
G O
N .C
O M
M A
IN
6)
-3
FI
EL
D
S U
PP
O
R T:
(6
) 8
-3
SHEET 4.2
A-100
SHEET 4.2
P-100
ITEM QTY. PART NO. DESCRIPTION MATERIAL WEIGHT
28 2 - UP TRUSS_MID ASM HSS10"X6"X3/16" 128.65
27 2 - UP TRUSS_RH ASM HSS10"X6"X3/16" 143.60
26 2 - UP TRUSS_LH ASM HSS10"X6"X3/16" 143.60
25 8 - PURLIN ASM HSS6"X4"X1/8" 236.28
24 4 - UP E-TAIL ASM HSS6"X4"X1/8" 23.51
23 4 - LO E-TAIL ASM HSS6"X4"X1/8" 17.04
22 8 - EAVE BEAM ASM HSS6"X4"X1/8" 162.23
21 2 - UP T-TAIL ASM_MID HSS10"X6"X3/16" 24.20
20 2 - UP T-TAIL ASM_RH HSS10"X6"X3/16" 24.20
19 2 - UP T-TAIL ASM_LH HSS10"X6"X3/16" 24.20
18 4 - RH CMEM TAIL ASM HSS6"X4"X1/8" 16.49
17 4 - LH CMEM TAIL ASM HSS6"X4"X1/8" 16.49
16 2 - RIDGE BEAM ASM HSS6"X4"X1/8" 162.25
15 1 - MID C-TUBE ASM HSS8"X8"X5/8" 57.92
14 2 - C-TUBE ASM HSS8"X8"X5/8" 72.47
13 8 - C-MEMBER ASM HSS6"X4"X1/8" 162.25
12 2 - RH J-COLUMN ASM HSS8"X8"X5/8" 203.04
11 2 - LH J-COLUMN ASM HSS8"X8"X5/8" 203.14
10 2 - MID J-COLUMN ASM HSS8"X8"X5/8" 202.87
9 2 - LO TRUSS 1 ASM HSS12"X6"X3/16" 188.77
8 2 - LO TRUSS 2 ASM HSS12"X6"X3/16" 188.77
7 2 - LO TRUSS 3 ASM HSS12"X6"X3/16" 173.81
6 2 - RH T-MEM TAIL ASM HSS6"X4"X1/8" 17.15
5 2 - LH T-MEM TAIL ASM HSS6"X4"X1/8" 17.15
4 4 - TMEM ASM HSS6"X4"X1/8" 162.93
3 2 - MID COLUMN 1 ASM HSS10"X6"X3/16" 253.62
2 2 - RH COLUMN ASM HSS10"X6"X3/16" 245.41
1 2 - LH COLUMN ASM HSS10"X6"X3/16" 245.41
SHEET
PR
O
JE
C
T:
PR
O
JE
C
T L
O C
A
TIO
N
ST
RU
C
TU
RA
L
FR
A
M
IN
G P
LA
N
C A
D M
O D
EL
D
RA
W
IN
G :C
A
LH
O
UN
P A
RK
C al ho un
, G A
O
RD
ER
N O
A
C
RE
A
TIO
N D
A
TE
: 5/
/2
1:
4/ 4/
~P
PR
IN
T D
A
TE
RE
V
L
EV
EL
SC
A
LE
D
RA
W N
B Y:
IF THESE DRAWINGS ARE SEALED, THE SEAL APPLIES ONLY TO BUILDING
COMPONENTS DETAILED WITHIN THESE DRAWINGS AND SUPPLIED BY
PORTER CORP AS WELL AS THE FOUNDATION DESIGN, IF APPLICABLE.
m ax
.m ac d er m
P
O R
TE
R
C O
R P
W W
W .P
O
LI
G O
N .C
O M
M A
IN
6)
-3
FI
EL
D
S U
PP
O
R T:
(6
) 8
-3
FINISH GRADE
(ASSUMED AT CONSTANT
ELEVATION UNLESS
OTHERWISE NOTED)
15'-6 13/16"
7'-6"
CLEAR
FINISH GRADE
(ASSUMED AT CONSTANT
ELEVATION UNLESS
OTHERWISE NOTED)
SHEET 4
K-100
SHEET 4
T-100
SHEET 4.1
J-100
SHEET 4.1
J-200
SHEET 4.1
E-100
SHEET 4.1
E-200
SHEET
3.1
PR
O
JE
C
T:
PR
O
JE
C
T L
O C
A
TIO
N
ST
RU
C
TU
RA
L
FR
A
M
IN
G P
LA
N
C A
D M
O D
EL
D
RA
W
IN
G :C
A
LH
O
UN
P A
RK
C al ho un
, G A
O
RD
ER
N O
A
C
RE
A
TIO
N D
A
TE
: 5/
/2
1:
4/ 4/
~P
PR
IN
T D
A
TE
RE
V
L
EV
EL
SC
A
LE
D
RA
W N
B Y:
IF THESE DRAWINGS ARE SEALED, THE SEAL APPLIES ONLY TO BUILDING
COMPONENTS DETAILED WITHIN THESE DRAWINGS AND SUPPLIED BY
PORTER CORP AS WELL AS THE FOUNDATION DESIGN, IF APPLICABLE.
m ax
.m ac d er m
120.00°+- 30° 30°
AFTER SNUG TIGHT,
MATCH MARK PLATE
TURN-OF-NUT PRETENSIONING METHOD:
THESE STEPS ILLUSTRATE THE
REQUIREMENTS OUTLINED IN THE AISC
SPECIFICATION. THE ROTATION
INDICATED IS ACCURATE FOR MOST
BOLT DIAMETERS AND LENGTHS BUT IT IS
THE RESPONSIBILITY OF THE INSTALLER
TO MEET AISC REQUIREMENTS.
THEN TURN BOLT/NUT PAST
SNUG TIGHT 1/3 TURN
STEP ONE:
STEP TWO:
COLUMN CONNECTIONS K-100 COMPRESSION MEMBER CONNECTION T-100
R by P
O R
TE
R
C O
R P
W W
W .P
O
LI
G O
N .C
O M
M A
IN
6)
-3
FI
EL
D
S U
PP
O
R T:
(6
) 8
-3
LOWER TRUSS
TENSION MEMBER
T-MEM TAIL
COLUMN
NUT, HEX, 5/8-11
(2) PLCS EACH CONNECTION
1" PLATE
1/2" PLATE
3/4" FLG. PLT.
LOWER TRUSS TAIL
(HSS12"X6"X3/16")
WELDED TO COLUMN
NUT, HEX, 1-8
(4) PLCS EACH CONNECTION
BOLT, HEX, 5/8-11x2 A325
(2) PLCS EACH CONNECTION
3/8" PLATE
1/2" FLG. PLT.
3/8" PLATE
COMPRESSION TUBE
RIDGE BEAM RIDGE TAIL
(HSS6"X4"X1/8")
WELDED TO C-TUBE
UPPER TRUSS
UPPER TRUSS
5/8" PLATE
5/8" PLATE
1/2" PLATE
BOLT, HEX, 5/8-11x2 A325
(2) PLCS EACH CONNECTION
BOLT, HEX, 5/8-11x2-1/4 A325
(4) PLCS EACH CONNECTION
1/2" PLATE
RIDGE BEAM
SHEET
PR
O
JE
C
T:
PR
O
JE
C
T L
O C
A
TIO
N
FR
A
M E
C O
N N
EC
TIO
N D
ET
A
IL
S
C A
D M
O D
EL
D
RA
W
IN
G :C
A
LH
O
UN
P A
RK
C al ho un
, G A
O
RD
ER
N O
A
C
RE
A
TIO
N D
A
TE
: 5/
/2
1:
4/ 4/
~P
PR
IN
T D
A
TE
RE
V
L
EV
EL
SC
A
LE
D
RA
W N
B Y:
IF THESE DRAWINGS ARE SEALED, THE SEAL APPLIES ONLY TO BUILDING
COMPONENTS DETAILED WITHIN THESE DRAWINGS AND SUPPLIED BY
PORTER CORP AS WELL AS THE FOUNDATION DESIGN, IF APPLICABLE.
m ax
.m ac d er m ai d
CONNECTION NOTES:
HIGH STRENGTH BOLTS SHALL BE ASTM F3125 (A325, TYPE 1) MATERIAL.1.
HIGH STRENGTH NUTS SHALL BE ASTM A563 (GRADE DH) MATERIAL.2.
HIGH STRENGTH WASHERS SHALL CONFORM TO ASTM F436.3.
UNLESS A SNUG-TIGHT JOINT IS PERMITTED IN THE CONNECTION DETAIL, ALL BOLTS ARE TO 4.
BE INSTALLED BY ONE OF THE FOLLOWING PRETENSIONING METHODS AS SPECIFIED IN THE
AISC "SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS", SECTION 8:
A. TURN-OF-NUT PRETENSIONING
B. CALIBRATED WRENCH PRETENSIONING
THE SNUG-TIGHT CONDITION IS THE TIGHTNESS THAT IS ATTAINED WITH A FEW IMPACTS OF 5.
AN IMPACT WRENCH OR THE FULL EFFORT OF AN IRONWORKER USING AN ORDINARY
SPUD WRENCH TO BRING THE CONNECTED PLIES INTO FIRM CONTACT.
ANCHOR BOLTS NEED NOT BE TIGHTENED PAST SNUG-TIGHT.6.
WHEN INSTALLING BOLTS REFER TO SECTIONS 8.4.1, 8.4.2, AND 8.4.3 OF THE 7.
"SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS" FOR GUIDANCE.
LOCAL JURISDICTIONS MAY REQUIRE AN INSPECTOR TO BE PRESENT TO WITNESS 8.
HARDWARE INSTALLATION AND INDEPENDENT TESTING. INSPECTION REQUIREMENTS
SHOULD BE VERIFIED BY INSTALLER PRIOR TO STEEL ERECTION.
ERECTION OF THE FRAMING MEMBERS WILL REQUIRE THE MAIN COLUMNS TO BE PLUMB 9.
SQUARE AND TIGHTENED TO THE TRUSSES AND/OR TENSION MEMBERS BEFORE INSTALLING
THE PURLINS. PURLINS, IF REQUIRED, MUST BE AS SHOWN IN FRAMING PLAN.
TEMPORARY SHORING OR BRACING SHALL BE USED TO COMPACT THE JOINTS UNTIL THE 10.
CONNECTED PLIES ARE IN FIRM CONTACT PRIOR TO PRETENSIONING.
PRIOR TO THE ERECTION OF SHELTER COMPONENTS, IT IS RECOMMENDED TO CHASE AND 11.
TAP STRUCTURAL HARDWARE.
ALL BOLTS MUST BE LUBRICATED WITH WAX TO ASSIST IN PROPER TIGHTENING. TO 12.
LUBRICATE A BOLT IN THE FIELD, APPLY THE WAX STICK DOWN THE LENGTH OF THE BOLT’S
THREADS.
TO PREVENT RUST STAINING OF FINISH, ALL METAL SHAVINGS MUST BE REMOVED AFTER 13.
INSTALLATION. ENSURE NO SHAVING ARE TRAPPED BETWEEN MATING SURFACES.
TOUCH-UP PAINT MUST BE APPLIED TO ALL EXPOSED FASTENERS. PERIODIC TOUCH-UP AT 14.
THESE CONNECTIONS IS REQUIRED.
NOTE:
SEE UC-100 FOR U-CLIP INSTALLATION
NOTE:
COVER PLATE
ATTACHED WITH POP RIVETS
(1P2903) (1) PER CLEAT
AT BOTTOM OF CONNECTION
P
O R
TE
R
C O
R P
W W
W .P
O
LI
G O
N .C
O M
M A
IN
6)
-3
FI
EL
D
S U
PP
O
R T:
(6
) 8
-3
LOWER EAVE BEAM CONNECTION E-100LOWER J-COLUMN CONNECTION
NOTE:
CTUBE COVER PLATE
ATTACHED WITH POP RIVETS
(1P2903) (1) PER CLEAT
AT BOTTOM OF CONNECTION
J-100
UPPER EAVE BEAM CONNECTION E-200UPPER J-COLUMN CONNECTION J-200
J-COLUMN
CLERESTORY MEMBER C-MEM TAIL
LOWER TRUSS
NUT, HEX, 5/8-11
(2) PLCS EACH CONNECTION
BOLT, HEX, 5/8-11x2 A325
(4) PLCS EACH CONNECTION
5/8" PLATE
BOLT, HEX, 5/8-11x2 A325
(2) PLCS EACH CONNECTION
J-COLUMN
CLERESTORY MEMBER
C-MEM TAIL
UPPER TRUSS
NUT, HEX, 5/8-11
(2) PLCS EACH CONNECTION
3/8" PLATE
3/8" PLATE
5/8" PLATE
UPPER TRUSS TAIL
NUT, HEX, 5/8-11
(4) PLCS EACH CONNECTION
BOLT, HEX, 5/8-11x2 A325
(2) PLCS EACH CONNECTION
3/8" PLATE1/2" PLATE
1/2" PLATE
NUT, HEX, 5/8-11
(2) PLCS EACH CONNECTION
UPPER EAVE TAIL UPPER EAVE BEAM
COVER ACCESS HOLES WITH
GRACE ICE AND WATER
SHIELD BEFORE ATTACHING
ROOF DECKING.
UPPER TRUSS TAIL
3/8" PLATE3/8" PLATE
NUT, HEX, 5/8-11
(2) PLCS EACH CONNECTION
BOLT, HEX, 5/8-11x1-1/2
(2) PLCS EACH CONNECTION
UPPER EAVE BEAM
3/8" PLATE
LOWER TRUSS TAIL
LOWER EAVE BEAM
LOWER EAVE TAIL
COVER ACCESS HOLES WITH
GRACE ICE AND WATER
SHIELD BEFORE ATTACHING
ROOF DECKING.
3/8" PLATE3/8" PLATE
BOLT, HEX, 5/8-11x1-1/2
(2) PLCS EACH CONNECTION
NUT, HEX, 5/8-11
(2) PLCS EACH CONNECTION
3/8" PLATE
LOWER EAVE BEAM
SHEET
4.1
PR
O
JE
C
T:
PR
O
JE
C
T L
O C
A
TIO
N
FR
A
M E
C O
N N
EC
TIO
N D
ET
A
IL
S
C A
D M
O D
EL
D
RA
W
IN
G :C
A
LH
O
UN
P A
RK
C al ho un
, G A
O
RD
ER
N O
A
C
RE
A
TIO
N D
A
TE
: 5/
/2
1:
4/ 4/
~P
PR
IN
T D
A
TE
RE
V
L
EV
EL
SC
A
LE
D
RA
W N
B Y:
IF THESE DRAWINGS ARE SEALED, THE SEAL APPLIES ONLY TO BUILDING
COMPONENTS DETAILED WITHIN THESE DRAWINGS AND SUPPLIED BY
PORTER CORP AS WELL AS THE FOUNDATION DESIGN, IF APPLICABLE.
m ax
.m ac d er m
P
O R
TE
R
C O
R P
W W
W .P
O
LI
G O
N .C
O M
M A
IN
6)
-3
FI
EL
D
S U
PP
O
R T:
(6
) 8
-3
ANCHOR ACCESS COVER PLATE A-100
U-CLIP
INSIDE FACE
OF TENSION MEMBER
OUTSIDE FACE
OF TENSION MEMBER
12-24 X 1 1/2" ONE STEP SCREW
(1P2905)
12" O.C. BOTH SIDES
REMOVE METAL SHAVINGS
UC-100
NOTE:
U-CLIP MUST BE ATTACHED TO
TENSION MEMBER AS SHOWN
PRIOR TO BUILDING ASSEMBLY.
U-CLIP CONNECTION
U-CLIP SHOULD NOT
REST ON WELD SEAM
IF TUBE HAS DRAIN HOLES
NEAR TUBE END, ATTACH U-CLIP
SO HOLES FACE UP.
12" O.C. BOTH SIDES
(1P2905)
1 1/2" ONE STEP SCREW
RIDGE BEAM
HAT CHANNEL
HAT CHANNEL CONNECTION HC-100PURLIN CONNECTION
NOTE: ENSURE PURLIN CONNECTIONS ARE
EVENLY SPACED BETWEEN TRUSS MEMBERS
BEFORE INSTALLING SIDE SCREWS
P-100
COLUMN
(1) COVER PLATE (1M1002950)
(1) COVER STRAP (1K1002)
(1) ONE WAY SCREW (1P3089)
PURLIN TAIL
(HSS6"X4"X1/8")
WELDED TO TRUSS
PURLIN
TRUSS
(7) #12-24 x 1 1/2
ONE STEP SCREW
(1P2905FNULL)
(3) ALONG TOP
(2) ALONG EACH SIDE
EACH CONNECTION
SHEET
4.2
PR
O
JE
C
T:
PR
O
JE
C
T L
O C
A
TIO
N
FR
A
M E
C O
N N
EC
TIO
N D
ET
A
IL
S
C A
D M
O D
EL
D
RA
W
IN
G :C
A
LH
O
UN
P A
RK
C al ho un
, G A
O
RD
ER
N O
A
C
RE
A
TIO
N D
A
TE
: 5/
/2
1:
4/ 4/
~P
PR
IN
T D
A
TE
RE
V
L
EV
EL
SC
A
LE
D
RA
W N
B Y:
IF THESE DRAWINGS ARE SEALED, THE SEAL APPLIES ONLY TO BUILDING
COMPONENTS DETAILED WITHIN THESE DRAWINGS AND SUPPLIED BY
PORTER CORP AS WELL AS THE FOUNDATION DESIGN, IF APPLICABLE.
m ax
.m ac d er m
P
O R
TE
R
C O
R P
W W
W .P
O
LI
G O
N .C
O M
M A
IN
6)
-3
FI
EL
D
S U
PP
O
R T:
(6
) 8
-3
SHEET 7
SS-101
SHEET 7
SS-200
SHEET 7.1
SS-400
SHEET 7.1
SS-501
SHEET 7.2
SS-600
SHEET 7.2
SS-902
SHEET
PR
O
JE
C
T:
PR
O
JE
C
T L
O C
A
TIO
N
EL
EC
TR
IC
A L
V
IE
W S
C A
D M
O D
EL
D
RA
W
IN
G :C
A
LH
O
UN
P A
RK
C al ho un
, G A
O
RD
ER
N O
A
C
RE
A
TIO
N D
A
TE
: 5/
/2
1:
4/ 4/
~P
PR
IN
T D
A
TE
RE
V
L
EV
EL
SC
A
LE
D
RA
W N
B Y:
IF THESE DRAWINGS ARE SEALED, THE SEAL APPLIES ONLY TO BUILDING
COMPONENTS DETAILED WITHIN THESE DRAWINGS AND SUPPLIED BY
PORTER CORP AS WELL AS THE FOUNDATION DESIGN, IF APPLICABLE.
m ax
.m ac d er m
P
O R
TE
R
C O
R P
W W
W .P
O
LI
G O
N .C
O M
M A
IN
6)
-3
FI
EL
D
S U
PP
O
R T:
(6
) 8
-3
7'-10 5/16"
9'-7 3/8"
2"
2"
1'-7 13/16"
1'-6 13/16"
3'-7 5/8"
1'-4 5/16"
2'-11 15/16"
RIDGE BEAM
CLERESTORY MEMBER
EAVE BEAM
EAVE BEAM
STANDING SEAM ROOF (22 GA)
STANDING SEAM ROOF (22 GA)
TENSION MEMBER
PURLIN
PURLIN
44'-0"
7'-10 5/16"
1'-4 3/16"
STANDING SEAM PANELS
NEED TO BE FIELD CUT TO LENGTH.
STANDING SEAM PANELS
MUST BE INSTALLED LEFT TO RIGHT
9'-7 3/8"
44'-0"
1'-4 3/16"
STANDING SEAM PANELS
NEED TO BE FIELD CUT TO LENGTH.
STANDING SEAM PANELS
MUST BE INSTALLED LEFT TO RIGHT
SHEET
6.1
PR
O
JE
C
T:
PR
O
JE
C
T L
O C
A
TIO
N
RO
O
F
LA
YO
UT
C A
D M
O D
EL
D
RA
W
IN
G :C
A
LH
O
UN
P A
RK
C al ho un
, G A
O
RD
ER
N O
A
C
RE
A
TIO
N D
A
TE
: 5/
/2
1:
4/ 4/
~P
PR
IN
T D
A
TE
RE
V
L
EV
EL
SC
A
LE
D
RA
W N
B Y:
IF THESE DRAWINGS ARE SEALED, THE SEAL APPLIES ONLY TO BUILDING
COMPONENTS DETAILED WITHIN THESE DRAWINGS AND SUPPLIED BY
PORTER CORP AS WELL AS THE FOUNDATION DESIGN, IF APPLICABLE.
m ax
.m ac d er m ai d
STANDING SEAM INSTALLATION NOTES:
THE DETAILS SHOWN ARE SUGGESTIONS OR GUIDELINES ON HOW TO 1.
ERECT THE SYSTEMS. THE INFORMATION SHOWN IS ACCURATE, BUT IT
IS NOT INTENDED TO COVER ALL INSTANCES, BUILDING
REQUIREMENTS, DESIGNS OR CODES. THE DETAILS MAY REQUIRE
CHANGES OR REVISIONS DUE TO FIELD CONDITIONS.
IT SHALL BE THE RESPONSIBILITY OF THE ERECTOR TO ENSURE THAT THE 2.
DETAILS MEET PARTICULAR BUILDING REQUIREMENTS AND TO
ASSURE ADEQUATE WATER TIGHTNESS.
THE ERECTOR SHOULD THOROUGHLY FAMILIARIZE HIMSELF/HERSELF 3.
WITH ALL ERECTION INSTRUCTIONS BEFORE STARTING WORK.
THE PANELS SHOULD BE INSTALLED PLUMB, STRAIGHT, AND 4.
ACCURATELY TO THE ADJACENT WORK.
FLASHING AND TRIM SHALL BE INSTALLED TRUE, AND IN PROPER 5.
ALIGNMENT, WITH ANY EXPOSED FASTENERS EQUALLY SPACED FOR
THE BEST APPEARANCE.
SEALANT SHALL BE FIELD APPLIED ON DRY, CLEAN SURFACES. SOME 6.
FIELD CUTTING AND FITTING OF PANELS AND FLASHING IS TO BE
EXPECTED BY THE ERECTOR AND MINOR FIELD CORRECTIONS ARE A
PART OF NORMAL ERECTION WORK.
WORKMANSHIP SHALL BE OF THE BEST INDUSTRY STANDARDS AND 7.
INSTALLATION SHALL BE PERFORMED BY EXPERIENCED METAL
CRAFTSMEN.
METAL SHAVINGS FROM DRILLING OR INSTALLATION OF ROOF 8.
FASTENERS MUST BE CAREFULLY REMOVED FROM THE ROOF BY
BRUSHING OR SWEEPING AT THE END OF EACH DAY DURING
INSTALLATION. SHAVINGS LEFT ON THE ROOF WILL QUICKLY RUST
AND STAIN THE ROOF FINISH.
P
O R
TE
R
C O
R P
W W
W .P
O
LI
G O
N .C
O M
M A
IN
6)
-3
FI
EL
D
S U
PP
O
R T:
(6
) 8
-3
#12-14x1 1/4" SELF DRILLING
SCREW.
#12-14x3/4" SELF DRILLING SCREW
#10x1" PANCAKE HEAD
SELF TAPPING SCREW
1/8" POP RIVET
PART DESCRIPTIONS:
SS-101
2022B
EAVE DETAIL
EAVE BEAM
TENSION MEMBER
ROOF CLIP
SELF-DRILLING SCREWS
STANDING SEAM PANEL (22 GA.)
OFFSET CLEAT
(OVERHANG 1")
FIELD BEND PANEL
SLIDE AROUND PANEL
(2) #10x1" PANCAKE HEAD
AND SIDES)
(ALONG TOP, BOTTOM,
BUTYL TAPE
(EACH SIDE OF RIB)
DRILLING SCREW
#12-24 X 1-1/4" SELF
12" O.C.
DRILLING SCREW
#12-14 X 3/4" SELF
U-CLIP
24" O.C.
POP RIVET
CLERESTORY MEMBER
C-CLOSURE
HIGH SIDE TRIM
STANDING SEAM PANEL (22 GA.)
2022B
HIGH SIDE DETAIL (VIEWING FROM ABOVE) SS-200
SHEET
PR
O
JE
C
T:
PR
O
JE
C
T L
O C
A
TIO
N
RO
O
F C
O N
N
EC
TIO
N
D
ET
A
IL
S C
A D
M O
D
EL
D
RA
W
IN
G
:C A
LH
O
UN
P
A
RK
C al ho un
, G A
O
RD
ER
N O
A
C
RE
A
TIO
N D
A
TE
: 5/
/2
N
TS
4/ 4/
~P
PR
IN
T D
A
TE
RE
V
L
EV
EL
SC
A
LE
D
RA
W N
B Y:
IF THESE DRAWINGS ARE SEALED, THE SEAL APPLIES ONLY TO BUILDING
COMPONENTS DETAILED WITHIN THESE DRAWINGS AND SUPPLIED BY
PORTER CORP AS WELL AS THE FOUNDATION DESIGN, IF APPLICABLE.
m ax
.m ac d er m
P
O R
TE
R
C O
R P
W W
W .P
O
LI
G O
N .C
O M
M A
IN
6)
-3
FI
EL
D
S U
PP
O
R T:
(6
) 8
-3
AND ENDS)
(ALONG TOP, BOTTOM,
BUTYL TAPE
12" O.C.
POP RIVET
RAKE CLOSURE
TOP AND SIDE
12" O.C.
DRILLING SCREW
#12-14 X 3/4" SELF
RAKE TRIM
STANDING SEAM PANEL (22 GA.)
TRUSS
SS-400RAKE DETAIL
2022A
RIDGE DETAIL
(6" OVERLAP)
2022A
SS-501
STANDING SEAM PANEL (22 GA.)
RIDGE CAP
C-CLOSURE
(TRIM TO FIT)
RIDGE BEAM
AND/OR TAIL
#12-14 X 3/4" SELF
DRILLING SCREW
12" O.C.
#12-24 X 1-1/4" SELF
DRILLING SCREW
(1) @ EACH SIDE OF RIB
BUTYL TAPE
(ALONG TOP, BOTTOM,
AND ENDS)
RIDGE CAP
HAT CHANNEL
SHEET
7.1
PR
O
JE
C
T:
PR
O
JE
C
T L
O C
A
TIO
N
RO
O
F C
O N
N
EC
TIO
N
D
ET
A
IL
S C
A D
M O
D
EL
D
RA
W
IN
G
:C A
LH
O
UN
P
A
RK
C al ho un
, G A
O
RD
ER
N O
A
C
RE
A
TIO
N D
A
TE
: 5/
/2
N
TS
4/ 4/
~P
PR
IN
T D
A
TE
RE
V
L
EV
EL
SC
A
LE
D
RA
W N
B Y:
IF THESE DRAWINGS ARE SEALED, THE SEAL APPLIES ONLY TO BUILDING
COMPONENTS DETAILED WITHIN THESE DRAWINGS AND SUPPLIED BY
PORTER CORP AS WELL AS THE FOUNDATION DESIGN, IF APPLICABLE.
m ax
.m ac d er m
P
O R
TE
R
C O
R P
W W
W .P
O
LI
G O
N .C
O M
M A
IN
6)
-3
FI
EL
D
S U
PP
O
R T:
(6
) 8
-3
(2) #10x1" PANCAKE HEAD
ROOF CLIP
SELF-DRILLING SCREWS
TAIL
AND/ OR
PURLIN
STANDING SEAM PANEL (22 GA.)
SS-600PURLIN DETAIL
2022B
(THROUGH TRIM AND TAB)
#12-14 X 3/4" SELF DRILLING SCREW
FORMED IN FIELD
TAB CUT AND
RAKE TRIM
STANDING SEAM PANEL
SS-902RAKE DETAIL
2023A
SHEET
7.2
PR
O
JE
C
T:
PR
O
JE
C
T L
O C
A
TIO
N
RO
O
F C
O N
N
EC
TIO
N
D
ET
A
IL
S C
A D
M O
D
EL
D
RA
W
IN
G
:C A
LH
O
UN
P
A
RK
C al ho un
, G A
O
RD
ER
N O
A
C
RE
A
TIO
N D
A
TE
: 5/
/2
N
TS
4/ 4/
~P
PR
IN
T D
A
TE
RE
V
L
EV
EL
SC
A
LE
D
RA
W N
B Y:
IF THESE DRAWINGS ARE SEALED, THE SEAL APPLIES ONLY TO BUILDING
COMPONENTS DETAILED WITHIN THESE DRAWINGS AND SUPPLIED BY
PORTER CORP AS WELL AS THE FOUNDATION DESIGN, IF APPLICABLE.
m ax
.m ac d er m
P
O R
TE
R
C O
R P
W W
W .P
O
LI
G O
N .C
O M
M A
IN
6)
-3
FI
EL
D
S U
PP
O
R T:
(6
) 8
-3
-STANDING SEAM PANELS COME PRE-NOTCHED FROM THE FACTORY
-PANELS MUST BE INSTALLED FROM LEFT TO RIGHT (FEMALE LEG ON LEFT, MALE LEG ON THE RIGHT
-HEM TOOL NOT PROVIDED AS PART OF THE ROOF KIT
2022A
HEM DETAIL SS HEM
HEM TOOL
SLIDE OVER PANEL
STANDING SEAM PANEL (22 GA.)
FINISHED HEM
HEM STANDING SEAM
PANEL OVER OFFSET CLEAT
SHEET
7.3
PR
O
JE
C
T:
PR
O
JE
C
T L
O C
A
TIO
N
RO
O
F C
O N
N
EC
TIO
N
D
ET
A
IL
S C
A D
M O
D
EL
D
RA
W
IN
G
:C A
LH
O
UN
P
A
RK
C al ho un
, G A
O
RD
ER
N O
A
C
RE
A
TIO
N D
A
TE
: 5/
/2
N
TS
4/ 4/
~P
PR
IN
T D
A
TE
RE
V
L
EV
EL
SC
A
LE
D
RA
W N
B Y:
IF THESE DRAWINGS ARE SEALED, THE SEAL APPLIES ONLY TO BUILDING
COMPONENTS DETAILED WITHIN THESE DRAWINGS AND SUPPLIED BY
PORTER CORP AS WELL AS THE FOUNDATION DESIGN, IF APPLICABLE.
m ax
.m ac d er m
| CS |
| Drawing View18 |
| 1 |
| Drawing View6 |
| Drawing View28 |
| Drawing View29 |
| Drawing View34 |
| 2 |
| Drawing View19 |
| Detail View (1 : 6) |
| 2.1 |
| 3 |
| Drawing View33 |
| 3.1 |
| Drawing View37 |
| Drawing View38 |
| Drawing View39 |
| 4 |
| Detail View (1 : 8) |
| Detail View (1 : 6) |
| 4.1 |
| Detail View (1 : 6) |
| Detail View (1 : 6) |
| Detail View (1 : 6) |
| Detail View (1 : 6) |
| 4.2 |
| Detail View (1 : 6) |
| Detail View (1 : 6) |
| 6 |
| Drawing View32 |
| 6.1 |
| Drawing View57 |
| Drawing View63 |
| Drawing View64 |
| 7 |
| 7.1 |
| 7.2 |
| 7.3 |
| 2024-04-12T09:38:28-0400 | |
| Tyler Bowden |
| 2024-04-12T09:38:35-0400 | |
| Tyler Bowden |
| 2024-04-12T09:38:42-0400 | |
| Tyler Bowden |
| 2024-04-12T09:38:44-0400 | |
| Tyler Bowden |
| 2024-04-12T09:38:46-0400 | |
| Tyler Bowden |
| 2024-04-12T09:38:48-0400 | |
| Tyler Bowden |
| 2024-04-12T09:38:51-0400 | |
| Tyler Bowden |
| 2024-04-12T09:38:53-0400 | |
| Tyler Bowden |
| 2024-04-12T09:38:55-0400 | |
| Tyler Bowden |
| 2024-04-12T09:38:57-0400 | |
| Tyler Bowden |
| 2024-04-12T09:39:00-0400 | |
| Tyler Bowden |
| 2024-04-12T09:39:03-0400 | |
| Tyler Bowden |
| 2024-04-12T09:39:04-0400 | |
| Tyler Bowden |
| 2024-04-12T09:39:07-0400 | |
| Tyler Bowden |
| 2024-04-12T09:39:10-0400 | |
| Tyler Bowden |
File details come from the government source that posted it. Updated .