24-015 CNU Forbes Air Valves - Drawings (04-08-26).pdf

PDF 12 MB Posted

Attached to
Christopher Newport University, Replace Forbes Hall Fume Hoods and Pressurization Valves & Control, IFB 242-18755-000, 1268/70586
Solicitation number
IV117705
Issued by
Newport News City, Nathalie CDP, Virginia

About this file

Summary

This file contains comprehensive construction drawings and technical specifications for the replacement of laboratory supply and exhaust air valves and associated controls throughout Forbes Hall at Christopher Newport University in Newport News, Virginia. The project, identified as State Project No. 242-18755-000 and MJT# 24-015, involves the replacement of integrated science center fume hoods and pressurization valves across three floors of the approximately 196,867 square foot building, originally constructed in 2011. The scope of work includes disconnection and removal of existing air valves, installation of new variable and general exhaust valves (designated as VSV, VEV, GXV, HXV, and WXV units), reconnection of hot water supply and return piping to reheat coils, fume hood sash replacement, and complete balancing and commissioning of all replaced valves. The mechanical engineer of record is Thompson Consulting Engineers, with laboratory airflow consultation provided by an external specialist. Work is phased to accommodate the academic calendar, with summer work (May 18 – August 7, 2026) permitted 24 hours daily and during-school-year work (August 10, 2026 – January 8, 2027) restricted to after-hours periods (5:00 PM – 5:00 AM weekdays, 24 hours weekends), subject to coordination with the owner. The project specifications reference Virginia Construction Code 2021 and ASHRAE 90.1-2019 compliance, with strict adherence to life safety requirements including egress maintenance and fire protection protocols throughout construction.

The drawings indicate that air valves and valve controls, fume hood controls, valve accessories, room controllers, temperature sensors, and programming/startup services will be furnished by the owner under a separate contract, while the contractor is responsible for installation of all mechanical equipment and associated controls. Multiple mechanical schedules detail specific valve configurations across all three floors, including ductwork and piping plans organized by floor and area, with enlarged plans provided for individual laboratory spaces. The contract requires temporary removal and reinstallation of existing acoustical ceiling systems in work areas, with contractors responsible for damage to ceiling components during removal and reinstallation. Fire protection requirements mandate coordination with the Virginia State Fire Marshal regarding ceiling removals and potential temporary upright sprinkler installation if fire protection coverage cannot be maintained. Building occupancy protocols require contractors to maintain all egress paths, restrict work in corridors to unoccupied hours, and provide bi-weekly construction schedules with annotated floor plans demonstrating compliance with egress requirements throughout the construction period.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DATE:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

COMM. NO:

C O

X

RO

A D

Co ns ul tin g En gi ne er s

TH

O

M

PS

O N

E

N

TE

RP

RI

SE

P

A

RK

W A

Y G

LE

N

A

LL

EN

, V

A

REVISIONS

H A

M

PT

O N

, V A

DESCRIPTIONMARK DATE

S . L

YN

N

H A

VE

N

R O

A D

VA

B

EA

CH

, V A

TE

LE

PH

O N

E:

(7

) 5

-4

PR

O

JE

CT

N U

M

BE

R:

4-

04.10.2026

N

EW

PO

R

T N

EW

S, V

IR

G

IN

IA

AI

R

V

AL

VE

R

EP

LA

C

EM

EN

T

M

AR

Y

BR

O C

K

FO

R

BE

S H

AL

L

- C H

R

IS

TO

PH

ER

N

EW

PO

R T

U N

IV

ER

SI

TY

ST

AT

E

PR

O

JE

C T

N O

2-

5-

24-015

04-10-2026

TITLE SHEET

DRAWING TITLESSHEET NO.

T001

DRAWING INDEX

M001

M101A

GENERAL NOTES, LEGEND, AND ABBREVIATIONS

FIRST FLOOR DUCTWORK PLAN - AREA A - DEMOLITION AND NEW WORK

VICINITY MAPAREA MAP

GENERAL CODE DATA:VECC COMPLIANCE STATEMENT

IN ACCORD WITH THE VIRGINIA ENERGY CONSERVATION CODE (VECC), THE BUILDING

SHALL COMPLY WITH ASHRAE 90.1-2019 SECTIONS 5, 6, 7, 8, 9, & 10. SECTION 5

BUILDING ENVELOPE WILL BE VIA SECTION 5.5 - PRESCRIPTIVE BUILDING ENVELOPE

OPTION. SECTION 6 COMPLIANCE WILL BE VIA SECTIONS 6.4 - MANDATORY

PROVISIONS AND 6.5 - PRESCRIPTIVE PATH.

LEAD MATERIALS DISCLOSURE STATEMENT

AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING COMPONENTS

HAS NOT BEEN CONDUCTED BECAUSE THE BUILDING WAS CONSTRUCTED AFTER

JANUARY 1, 1985 AND THE OWNER HAS NO KNOWLEDGE OF LEAD CONTAINING OR

COATED BUILDING COMPONENTS IN THE BUILDING. IT IS THE CONTRACTOR'S

RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA OCCUPATIONAL SAFETY AND

HEALTH (VOSH) REGULATIONS AS THEY PERTAIN TO EMPLOYEE EXPOSURES TO

LEAD. ALL LEAD AND LEAD-COATED BUILDING COMPONENTS SHALL BE RECYCLED

TO THE EXTENT POSSIBLE.

ASBESTOS DISCLOSURE STATEMENT

AN ASBESTOS INSPECTION WAS NOT PERFORMED BECAUSE ALL PORTIONS OF THE

EXISTING BUILDING THAT MAY BE AFFECTED BY THE WORK WERE ORIGINALLY

CONSTRUCTED AFTER JANUARY 1, 1985.

HPBA COMPLIANCE STATEMENT

IN ACCORD WITH THE HIGH PERFORMANCE BUILDINGS ACT, THE BUILDING IS

EXEMPT FROM COMPLIANCE BECAUSE THE COST OF THE RENOVATIONS DOES NOT

EXCEED 50% OF THE VALUE OF THE BUILDING.

APPLICABLE CODES: VIRGINIA UNIFORM STATEWIDE BUILDING CODE (VUSBC) 2021 EDITION,

EFFECTIVE JANUARY 18, 2024

VIRGINIA EXISTING BUILDING CODE (VEBC), 2021 EDITION: LEVEL 2 ALTERATION

VIRGINIA CONSTRUCTION CODE (VCC), 2021 - VUSBC PART 1

VIRGINIA ENERGY CONSERVATION CODE, 2021

VIRGINIA MECHANICAL CODE, 2021

VIRGINIA PLUMBING CODE, 2021

NATIONAL ELECTRICAL CODE - NFPA 70, 2020

VIRGINIA STATEWIDE FIRE PREVENTION CODE, 2021

INTERNATIONAL FIRE CODE, 2021

CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL (CPSM) 2025 REV 0, DATED MAR 17, 2025

USE GROUP: BUSINESS GROUP B

TYPE OF CONSTRUCTION: (NON-COMBUSTIBLE, UNPROTECTED) CONSTRUCTION UNDER 2021

VCC (TYPE II-B)

ORIGINAL CONSTRUCTION YEAR: 2011, UNDER THE VIRGINIA UNIFORM STATEWIDE BUILDING

CODE (VUSBC) 2006 EDITION.

FIRE ALARM SYSTEM: EXISTING

FIRE SUPPRESSION SYSTEM: SPRINKLERED THROUGHOUT

NO PROPOSED CHANGES IN OCCUPANCY LOADS OR MEANS OF EGRESS

BUILDING TOTAL AREA: APPROX. 196,867 SF

SEISMIC DESIGN DATA:

1. RISK CATEGORY: III

2. SEISMIC IMPORTANCE FACTOR : 1.25

3. WIND LOAD: 127 MPH

4. SS: 0.12g

5. S1: 0.041g

6. SDS: 0.11g

7. SD1: 0.059g

8. SEISMIC DESIGN CATEGORY: A

REPLACE INTEGRATED SCIENCE CENTER

FUME HOODS AND PRESSURIZATION

VALVES AND CONTROLS

CHRISTOPHER NEWPORT UNIVERSITY -

MARY BROCK FORBES HALL

NEWPORT NEWS, VIRGINIA

STATE PROJECT NO: 242-18755-000

MJT# 24-015

CHRISTOPHER NEWPORT UNIVERSITY

1 AVENUE OF THE ARTS

NEWPORT NEWS, VA 23606

PROJECT DIRECTORY

OWNER’S CONTACT: CHRISTOPHER NEWPORT UNIVERSITY

ATTN: DAVID GUGLIELMO

DIRECTOR OF FACILITIES PLANNING AND SUSTAINABILITY

PHONE: (757) 594-8964

MECHANICAL ENGINEER: THOMPSON CONSULTING ENGINEERS

ATTN: KEVIN ALLEN, P.E.

22 ENTERPRISE PARKWAY, SUITE 120

HAMPTON, VIRGINIA 23666

PHONE: (757) 599-4415

ELECTRICAL ENGINEER: THOMPSON CONSULTING ENGINEERS

ATTN: KENZIE CAMBAR, P.E.

22 ENTERPRISE PARKWAY, SUITE 120

HAMPTON, VIRGINIA 23666

PHONE: (757) 599-4415

LABORATORY AIRFLOW CONSULTANT

ATTN: ROBERT LUKENS

VP OF SERVICES AND PRODUCTS

PHONE: (919) 319-4290

IN COMPLIANCE WITH VIRGINIA CONSTRUCTION CODE SECTION 3302.3, VIRGINIA EXISTING BUILDING CODE SECTIONS 1201.5 AND 1210.7, THE REQUIREMENTS OF CHAPTER 33 OF THE INTERNATIONAL FIRE CODE SHALL BE

MET AND MAINTAINED THROUGHOUT CONSTRUCTION. SITE SAFETY PLANS WILL BE REVIEWED AT EACH

CONSTRUCTION ADMINISTRATION MEETING.

FOR ANY CONSTRUCTION ALTERATION OR DEMOLITION OUTSIDE THE SCOPE OF CHAPTER 33 OF THE

INTERNATIONAL FIRE CODE REFER TO NFPA

241-2019 FOR REQUIREMENTS.

REQUIREMENTS OF THE VIRGINIA EXISTING BUILDING CODE AND INTERNATIONAL FIRE CODE SHALL BE STRICTLY OBSERVED TO SAFEGUARD AGAINST ALL FIRE HAZARDS ATTENDANT UPON CONSTRUCTION OPERATIONS.

SPECIFICALLY SECTIONS 1204.2 OF THE VIRGINIA EXISTING BUILDING CODE AND 3309.2 OF THE VIRGINIA

CONSTRUCTION CODE BOTH OF WHICH ARE TITLED "FIRE EXTINGUISHERS".

FIRE SAFETY

DESCRIPTION OF WORK:

APRIL 10, 2026

FORBES HALL

T001

TI

TL

E

SH

EE

T

BDC

MAR

KDA

REPLACEMENT OF LABORATORY SUPPLY AND EXHAUST AIR VALVES AND ASSOCIATED CONTROLS

THROUGHOUT THE BUILDING.

M002 MECHANICAL SCHEDULES

M003 MECHANICAL SCHEDULES

M004 MECHANICAL SCHEDULES

M005 MECHANICAL SCHEDULES

M006 MECHANICAL SCHEDULES

M101B FIRST FLOOR DUCTWORK PLAN - AREA B - DEMOLITION AND NEW WORK

M101C FIRST FLOOR DUCTWORK PLAN - AREA C - DEMOLITION AND NEW WORK

M101D FIRST FLOOR DUCTWORK PLAN - AREA D - DEMOLITION AND NEW WORK

M102A SECOND FLOOR DUCTWORK PLAN - AREA A - DEMOLITION AND NEW WORK

M102B SECOND FLOOR DUCTWORK PLAN - AREA B - DEMOLITION AND NEW WORK

M102C SECOND FLOOR DUCTWORK PLAN - AREA C - DEMOLITION AND NEW WORK

M102D SECOND FLOOR DUCTWORK PLAN - AREA D - DEMOLITION AND NEW WORK

M103A THIRD FLOOR DUCTWORK PLAN - AREA A - DEMOLITION AND NEW WORK

M103B THIRD FLOOR DUCTWORK PLAN - AREA B - DEMOLITION AND NEW WORK

M201A FIRST FLOOR PIPING PLAN - AREA A - DEMOLITION AND NEW WORK

M201B FIRST FLOOR PIPING PLAN - AREA B - DEMOLITION AND NEW WORK

M201C FIRST FLOOR PIPING PLAN - AREA C - DEMOLITION AND NEW WORK

M201D FIRST FLOOR PIPING PLAN - AREA D - DEMOLITION AND NEW WORK

M202A SECOND FLOOR PIPING PLAN - AREA A - DEMOLITION AND NEW WORK

M202B SECOND FLOOR PIPING PLAN - AREA B - DEMOLITION AND NEW WORK

M202C SECOND FLOOR PIPING PLAN - AREA C - DEMOLITION AND NEW WORK

M202D SECOND FLOOR PIPING PLAN - AREA D - DEMOLITION AND NEW WORK

M203A THIRD FLOOR PIPING PLAN - AREA A - DEMOLITION AND NEW WORK

M203B THIRD FLOOR PIPING PLAN - AREA B - DEMOLITION AND NEW WORK

M301 ENLARGED PLANS - LAB 1002, 1007 & 1009 - DEMOLITION AND NEW WORK

M302 ENLARGED PLANS - LAB 1013, 1015, 1026 & 1028 - DEMOLITION AND NEW WORK

M303 ENLARGED PLANS - LAB 1014, 1025, 1027, 1034 & 1040 - DEMOLITION AND NEW WORK

M304 ENLARGED PLANS - LAB 1033, 1036, 1038 & 1039 - DEMOLITION AND NEW WORK

M305 ENLARGED PLANS - LAB 2002, 2007, 2009 & 2013 - DEMOLITION AND NEW WORK

M306 ENLARGED PLANS - LAB 2015, 2041-2045 & 2047 - DEMOLITION AND NEW WORK

M307 ENLARGED PLANS - LAB 2051-2053 & 2055-2057 - DEMOLITION AND NEW WORK

M308 ENLARGED PLANS - LAB 3002, 3007 & 3009 - DEMOLITION AND NEW WORK

M309 ENLARGED PLANS - LAB 3013, 3015 & 3041 - DEMOLITION AND NEW WORK

M310 ENLARGED PLANS - LAB 3038, 3040, 3042, 3045, 3049 & 3051 - DEMOLITION AND NEW WORK M311 ENLARGED PLANS - LAB 3044, 3048, 3050, 3052, 3053 & 3054 - DEMOLITION AND NEW WORK

M401 AIR VALVE INSTALLATION DETAILS

M501 AUTOMATIC TEMPERATURE CONTROLS

RP101-106 REFERENCE CEILING PLANS

DRAWN BY:

DESIGNED BY:

COMM. NO:

C O

X

RO

A D

Co ns ul tin g En gi ne er s

TH

O

M

PS

O N

E

N

TE

RP

RI

SE

P

A

RK

W A

Y G

LE

N

A

LL

EN

, V

A

REVISIONS

H A

M

PT

O N

, V A

DESCRIPTIONMARK DATE

S . L

YN

N

H A

VE

N

R O

A D

VA

B

EA

CH

, V A

TE

LE

PH

O N

E:

(7

) 5

-4

PR

O

JE

CT

N U

M

BE

R:

4-

04.10.2026

N

EW

PO

R

T N

EW

S, V

IR

G

IN

IA

AI

R

V

AL

VE

R

EP

LA

C

EM

EN

T

M

AR

Y

BR

O C

K

FO

R

BE

S H

AL

L

- C H

R

IS

TO

PH

ER

N

EW

PO

R T

U N

IV

ER

SI

TY

ST

AT

E

PR

O

JE

C T

N O

2-

5-

24-015

04-10-2026

M001

G

EN

ER

AL

N O

TE

S, L

EG

EN

D

, A N

D A

BB

R

EV

IA

TI

O

N S

BDC

MAR

KDA

1. WHERE EQUIPMENT IS INDICATED TO BE REMOVED, IT SHALL MEAN COMPLETE REMOVAL

OF EQUIPMENT, INCLUDING CONTROLS AND INCIDENTAL ITEMS CONNECTED OR

FASTENED TO EQUIPMENT. OWNER MAINTAINS THE OWNERSHIP OF ALL ITEMS TAGGED

OR IDENTIFIED.

2. WHERE DUCTWORK IS INDICATED TO BE REMOVED, IT SHALL MEAN COMPLETE REMOVAL

OF DUCTWORK, INCLUDING FITTINGS, INSULATION, CONTROLS, AND INCIDENTAL ITEMS

CONNECTED OR FASTENED TO THE DUCTWORK. DUCTWORK IS DIAGRAMMATIC AND

INDICATES THE GENERAL EXTENT OF WORK. NO ATTEMPT IS MADE TO SHOW EVERY ELL,

TEE, OFFSET AND FITTING. REMOVE DUCTWORK AS INDICATED AND SPECIFIED.

GENERAL DEMOLITION NOTES

1. CONTRACTOR SHALL VISIT JOB SITE TO DETERMINE EXTENT OF WORK INVOLVED PRIOR

TO BIDDING THE PROJECT.

2. COORDINATE LOCATION OF ALL NEW AIR VALVES WITH EXISTING LIGHT FIXTURES,

SPRINKLER SYSTEMS AND ACCESSORIES INSTALLED BY OTHER TRADES SO AS TO

PRESENT A NEAT AND ATTRACTIVE INSTALLATION THROUGHOUT THE BUILDING.

3. ALL AIR VALVES, DUCTWORK, ETC., SHALL BE CONCEALED UNLESS OTHERWISE NOTED.

4. ARRANGE DUCTWORK PARTICULARLY ABOVE CEILING AS REQUIRED TO CLEAR

STRUCTURE, CONDUIT, LIGHTS, ETC., ALLOWING SPACE FOR HANGERS, INSULATION,

ETC.

5. DUCT DIMENSIONS MAY BE MODIFIED AS APPROVED BY ENGINEER.

6. DUCT SIZES SHOWN ARE INSIDE FREE AREA DIMENSIONS.

7. MAINTAIN PROPER CLEARANCES PER ELECTRICAL CODE ON ALL EQUIPMENT.

COORDINATE WITH ALL TRADES TO ENSURE CLEARANCES ARE NOT OBSTRUCTED.

8. INSTALL ALL WALL MOUNTED NON-ADJUSTABLE SENSORS AT 5'-0" FROM FINISHED

FLOOR TO TOP OF SENSOR. ADJUSTABLE DEVICES SHALL BE INSTALLED AT 4'-0" FROM

FINISHED FLOOR TO TOP OF SENSOR.

GENERAL NOTES

ABBREVIATIONS

ø DIAMETER

APD AIR PRESSURE DROP

APPROX APPROXIMATE

CFM CUBIC FEET PER MINUTE

CONFIG CONFIGURATION

DIA DIAMETER

FLP FAIL LAST POSITION

FSP FAIL SAFE POSITION

GXV-x GENERAL EXHAUST VALVE DESIGNATION

HS HIGH-SPEED

HWR HOT WATER RETURN

HWS HOT WATER SUPPLY

HXV-x HAZARDOUS EXHAUST VALVE DESIGNATION

IN INCH/INCHES

L LENGTH

MAX MAXIMUM

MIN MINIMUM

OFCI OWNER-FURNISHED, CONTRACTOR-INSTALLED

TYP TYPICAL

V VOLTS

VA VOLT AMPS

VAC VOLTS ALTERNATING CURRENT

VAV-x (EXISTING) VAV TERMINAL UNIT DESIGNATION

VDC VOLTS DIRECT CURRENT

VEV-x VARIABLE EXHAUST VALVE DESIGNATION

VSV-x VARIABLE SUPPLY VALVE DESIGNATION

W WATTS

W WIDTH

WXV-x WET EXHAUST VALVE DESIGNATION

LEGEND

(X"/X") ø

SUPPLY AIR DEVICE WITH FLEXIBLE DUCT

LINEAR DIFFUSER WITH FLEXIBLE DUCT

90° DUCT ELBOW - TURNED DOWN

DUCT ELBOW WITH TURNING VANES

DUCTWORK TURNING DOWN

90° DUCT ELBOW - TURNED UP

RETURN OR EXHAUST AIR DEVICE

90° DUCT ELBOW - TURNED DOWN

TRANSFER DUCT ABOVE CEILING, SIZE AS INDICATED

TRANSFER GRILLE, SIZE AS INDICATED

DUCT TRANSITION

SQUARE TO ROUND DUCT TRANSITION

DUCT HEATING COIL

VARIABLE EXHAUST/SUPPLY AIR VALVE

ROUND DUCT

DIRECTION OF AIRFLOW

POINT OF CONNECTION FOR NEW WORK

REMOVE EXISTING TO THIS POINT

DEMOLITION NOTE

EXISTING SIZES AS INDICATED

NEW WORK NOTE

EXISTING TO REMAIN

NEW WORK

BALANCE EXISTING AIR TERMINAL TO CFM INDICATEDXXX

HWR

HWS HOT WATER SUPPLY PIPING

PIPE DOWN

PIPE TEE DOWN

PIPE TEE UP

PIPE UP

HOT WATER RETURN PIPING

90° DUCT ELBOW - TURNED UP ENLARGED PLAN: NUMBER "1A" ON DRAWING MXXX

SEE DRAWING MYYY AND MZZZ

D1

1A

MYYYMXXX

MZZZ

1. DURING THE SCHOOL YEAR (APPROX. AUGUST 10, 2026 THROUGH JANUARY 8, 2027), THE

CONTRACTOR SHALL ONLY BE PERMITTED TO WORK ONSITE DURING AFTER-HOURS

PERIODS. THESE PERIODS SHALL TYPICALLY BE BETWEEN 5:00PM AND 5:00 AM,

MONDAY-FRIDAY AND 24 HOURS A DAY ON SATURDAY AND SUNDAY. EXACT TIMES

SHALL BE COORDINATED WITH THE OWNER POST-BID DURING THE PRE-CONSTRUCTION

CONFERENCE. ADDITIONAL HOLIDAYS AND BREAKS THROUGHOUT THE ACADEMIC

YEAR MAY WARRANT THE OPPORTUNITY FOR THE CONTRACTOR TO WORK ONSITE

DURING NORMAL WORKING HOURS, BUT THESE MUST BE COORDINATED WITH THE

OWNER AT LEAST SEVEN (7) DAYS BEFORE WORK WOULD BE SCHEDULED TO BEGIN.

2. DURING THE SUMMER TIME PERIOD (APPROX. MAY 18, 2026 THROUGH AUGUST 7, 2026),

THE CONTRACTOR SHALL BE PERMITTED TO WORK ONSITE 24 HOURS A DAY.

CONTRACTOR'S WORK SCHEDULE MUST BE COORDINATED WITH THE OWNER ON A

WEEKLY BASIS, PROVIDING AT LEAST FOURTEEN (14) DAYS' ADVANCE NOTICE OF EACH

VALVE REPLACEMENT.

3. DURING EACH VALVE REPLACEMENT WHILE THE BUILDING IS OCCUPIED DURING THE

ACADEMIC YEAR (APPROX. AUGUST 10, 2026 THROUGH JANUARY 8, 2027), PRIOR TO THE

CONTRACTOR LEAVING THE SITE FOR THE DAY (OR WEEKEND), ALL VALVES MUST BE

PROPERLY BALANCED AND COMMISSIONED TO ENSURE PROPER AIRFLOW DURING ALL

MODES OF OPERATION. REFER TO SPECIFICATIONS 230593 AND 230800 FOR

ADDITIONAL REQUIREMENTS.

PHASING NOTES

THERMOSTAT OR TEMPERATURE SENSORT

EQUIPMENT TO BE REMOVED

1. CONTRACTOR SHALL ENSURE THAT ALL PATHS OF EGRESS ARE MAINTAINED

THROUGHOUT THE CONSTRUCTION PROCESS WHEN WORK IS BEING PERFORMED

ONSITE. ALL DEMOLITION AND NEW WORK LOCATED WITHIN THE MEANS OF EGRESS,

INCLUDING ALL AIR VALVE WORK LOCATED IN CORRIDORS, SHALL BE PERFORMED

DURING UNOCCUPIED HOURS (TYPICALLY SATURDAYS AND SUNDAYS). CONTRACTOR

SHALL CLOSELY COORDINATE OCCUPANCY SCHEDULE WITH OWNER DURING

CONSTRUCTION.

A. FOR THE DURATION OF THE CONSTRUCTION PERIOD, CONTRACTOR SHALL BE

RESPONSIBLE FOR PROVIDING A BI-WEEKLY CONSTRUCTION SCHEDULE AND

ANNOTATED FLOOR PLAN INDICATING THE VALVES ANTICIPATED FOR

REPLACEMENT. FLOOR PLAN SHALL DEMONSTRATE THAT ALL EGRESS PATHS

CAN BE MAINTAINED WHEN WORK IS PERFORMED OUTSIDE OF CORRIDORS, OR

HAVE SPECIFIC DIRECTIONS FOR RESTRICTING CORRIDOR ACCESS WHEN WORK

IS PERFORMED IN CORRIDORS.

B. NO DEAD-END EGRESS CONDITIONS LONGER THAN 50 FEET SHALL BE CREATED

AS A RESULT OF THE CONTRACTOR'S WORK THROUGHOUT THE BUILDING.

WHERE ANY EXIT SIGNS OR OTHER LABELED EGRESS PATHS ARE TEMPORARILY

OBSTRUCTED BY CONTRACTOR'S WORK, TEMPORARY EGRESS SIGNS SHALL BE

CLEARLY DISPLAYED IN THE AREA OF WORK.

C. CONTRACTOR SHALL MAKE SPECIAL CONSIDERATIONS WHERE WORK IS IN THE

PROXIMITY OF AN EXIT STAIR, AS ALL UPSTREAM AREAS WILL BE AFFECTED AND

WILL STILL REQUIRE CODE-MANDATED EGRESS PATHWAYS.

D. EXIT WIDTH SHALL BE NO LESS THAN 44" IN CORRIDORS AND 36" IN SPACES WITH

OCCUPANCY OF LESS THAN 50 PERSONS.

2. WHILE PERFORMING ANY WORK DURING HOURS IN WHICH THE BUILDING MAY BE

PARTIALLY OCCUPIED (APPROXIMATELY 5:00 PM THROUGH 11:00 PM, MONDAY-FRIDAY),

CONTRACTOR SHALL ENSURE THAT ALL PATHS OF EGRESS ARE MAINTAINED AND ALL

CODE-REQUIRED EGRESS WIDTHS ARE AVAILABLE. WHEREVER POSSIBLE WHEN

PERFORMING VALVE REPLACEMENTS LOCATED IN THE PATH OF EGRESS, CONTRACTOR

SHALL LOCATE ALL NON-CRITICAL COMPONENTS (TOOL BOXES, MISCELLANEOUS

MATERIALS, VALVE COMPONENTS, ETC.) IN THE NEAREST ADJACENT UNOCCUPIED

CLASSROOM SPACE SO AS TO NOT FURTHER IMPEDE THE PATH OF EGRESS.

3. WHERE AN EXIT ACCESS CORRIDOR MUST BE BLOCKED OUT OF NECESSITY,

CONTRACTOR SHALL MAKE PRIOR ARRANGEMENTS WITH CHRISTOPHER NEWPORT

UNIVERSITY AND THE SATE FIRE MARSHAL TO ENSURE THAT NO OCCUPANTS ARE

TEMPORARILY PRESENT IN A SPACE SERVED BY A BLOCKED CORRIDOR.

PATH OF EGRESS AND LIFE SAFETY NOTES

1. CONTRACTOR SHALL CAREFULLY REMOVE EXISTING CEILING TILES, GRID, LIGHT

FIXUTRES, SPRINKLER HEAD COVERS, AND OTHER CEILING MOUNTED EQUIPMENT (ALL

AS NECESSARY) TO FACILITATE THE AIR VALVE REPLACEMENTS. APPROXIAMTE AREA

OF REMOVAL IS A 6'X6' SQUARE CENTERED UNDER EACH AIR VALVE. UPON

COMPLETION OF THE VALVE REPLACEMENT, RE-INSTALL CEILING TILES, GRID, LIGHT

FIXTURES, SPRINKLER HEAD COVERS, AND ANY OTHER CEILING-MOUNTED EQUIPMENT.

2. IT IS UNDERSTOOD THAT ALL WORK ASSOCIATED WITH THE AIR VALVE REPLACEMENT,

SPECIFICALLY ANY WORK TAKING PLACE IN THE MEANS OF EGRESS, WILL OCCUR WHEN

THE BUILDING IS NOT REGULARLY OCCUPIED OR FULLY UNOCCUPIED. CONTRACTOR

SHALL COORDINATE OCCUPANCY SCHEDULE WITH OWNER DURING CONSTRUCTION.

3. CONTRACTOR SHALL FIELD VERIFY ALL REFLECTED CEILING GRID ELEVATIONS,

ORIENTATIONS, AND POSITIONS AS INDICATED IN THE CEILING REFERENCE PLANS

RP101-RP106. REFLECTED CEILING GRID MAY VARY FROM THAT SHOWN ON THE

REFERENCE PLANS.

4. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO TEMPORARILY REMOVE AND

SALVAGE THE EXISTING ACOUSTICAL PANEL CEILING SYSTEM. AFTER COMPLETION OF

MECHANICAL AND ELECTRICAL WORK, THE CONTRACTOR SHALL REINSTALL THE

SALVAGED ACOUSTICAL PANEL CEILING AND RESTORE TO PRE-CONSTRUCTION

CONDITIONS. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY CEILING COMPONENTS

DAMAGED DURING THE REMOVAL AND REINSTALLATION PROCESS. ANY ACOUSTICAL

PANEL CEILING SYSTEM COMPONENTS DAMAGED PRIOR TO REMOVAL SHALL BE

DOCUMENTED AND SHARED WITH THE OWNER. UPON OWNER AUTHORIZATION,

CONTRACTOR SHALL PROVIDE NEW COMPONENTS TO REPLACE SAID DAMAGED

EXISTING COMPONENTS. REFER TO THE BID FORM FOR ADDITIONAL INFORMATION.

5. THE CONTRACTOR SHALL STORE AND PROTECT ALL REMOVED CEILING TILES AND GRID

FOR REINSTALLATION. IMPROPERLY STORED AND HANDLED MATERIALS SHALL BE

REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.

6. DURING DEMOLITION, SORT TILES REMOVED BY APPEARANCE AND CONDITION. UPON

REINSTALLATION, PROVIDE TILES OF LIKE APPEARANCE TO PRESENT A UNIFORM

CEILING FINISH.

7. CONTRACTOR SHALL COORDINATE EXACT QUANTITY AND LOCATION OF CEILING TILES,

GRID, AND ELECTRICAL FIXTURES TO BE REMOVED WITH THE REQUIREMENTS OF

MECHANICAL DEMOLITION AND NEW WORK.

CEILING REMOVAL AND REPLACEMENT NOTES

1. LIFE SAFETY SHALL BE MAINTAINED DURING THE ENTIRE CONSTRUCTION PERIOD,

SPECIFICALLY WHEN WORK IS BEING PERFORMED THROUGHOUT THE BUILDING.

OWNER AND CONTRACTOR SHALL COORDINATE WITH THE STATE FIRE MARSHAL PRIOR

TO ANY CEILING REMOVAL. IF COVERAGE CANNOT BE MAINTAINED, A FIRE WATCH THAT

IS APPROVED BY THE STATE FIRE MARSHAL AND COMPLIANT WITH IFC 901.7 WILL BE

NECESSARY.

2. THE PROVISIONS OF THE 2021 INTERNATIONAL FIRE CODE (CHAPTER 33) SHALL BE

STRICTLY OBSERVED AT ALL TIMES. ALL CONSTRUCTION SHALL BE IN COMPLIANCE

WITH NFPA 241-2019 FOR CONDITIONS NOT COVERED BY THE IFC.

3. IN THE EVENT OF ANY PLANNED OR UNPLANNED OUTAGE OF THE FIRE PROTECTION

SYSTEM, THE CONTRACTOR SHALL NOTIFY THE OWNER, STATE FIRE MARSHAL, AND

LOCAL FIRE MARSHAL.

4. IN THE EVENT THAT COVERAGE CANNOT BE MAINTAINED AND AN IFC 901.7 COMPLIANT

FIRE WATCH CANNOT BE PROVIDED BY THE CONTRACTOR, THE CONTRACTOR SHALL

REPLACE PENDANT SPRINKLERS WITH UPRIGHT SPRINKLERS WHEN THE CEILING TILES

ARE REMOVED DURING DEMOLITION. UPRIGHT SPRINKLERS SHALL BE LOCATED NO

MORE THAN 12" FROM THE DECK ABOVE. AFTER UPRIGHT SPRINKLERS ARE INSTALLED,

ANY OBSTRUCTIONS CREATED BY DUCTWORK AND OTHER MEP ELEMENTS SHALL BE

COORDINATED WITH THE STATE FIRE MARSHAL FOR CORRECTION. ALL WORK SHALL

COMPLY WITH NFPA 13-2019 AND BE COORDINATED WITH THE STATE FIRE MARSHAL.

TEMPORARY UPRIGHT SPRINKLERS SHALL HAVE THE SAME TEMPERATURE RATINGS,

RESPONSE RATINGS, AND K FACTORS AS THE EXISTING SPRINKLERS. FLEXIBLE

SPRINKLER CONNECTORS ARE NOT ALLOWED.

SPRINKLER AND FIRE PROTECTION NOTES

1. THE FOLLOWING ITEMS WILL BE FURNISHED BY THE OWNER UNDER A SEPARATE

CONTRACT:

A. AIR VALVES AND VALVE CONTROLS

B. FUME HOOD CONTROLS

C. VALVE ACCESSORIES (DRAWBAND CLAMPS)

D. ROOM CONTROLLERS AND ACCESSORIES

E. ROOM TEMPERATURE SENSORS

F. PROGRAMMING AND STARTUP OF VALVE AND ROOM CONTROLLERS

2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE INSTALLATION OF THE AIR VALVES,

VALVE CONTROLS, VALVE ACCESSORIES FUME HOOD CONTROLLERS, ROOM

CONTROLLERS, ROOM TEMPERATURE SENSORS, AND ALL OTHER BAS CONTROLS OR

CONTROLS NOT EXPLICITLY LISTED ABOVE.

3. CONTRACTOR IS NOT RESPONSIBLE FOR INCLUDING THE WORK IN ITEM 1 AS PART OF

THEIR TOTAL BASE BID AMOUNT ON THE PROJECT BID FORM. A SEPARATE CONTRACT

HAS ALREADY BEEN EXECUTED.

OWNER-FURNISHED, CONTRACTOR-INSTALLED EQUIPMENT NOTES

DRAWN BY:

DESIGNED BY:

COMM. NO:

C O

X

RO

A D

Co ns ul tin g En gi ne er s

TH

O

M

PS

O N

E

N

TE

RP

RI

SE

P

A

RK

W A

Y G

LE

N

A

LL

EN

, V

A

REVISIONS

H A

M

PT

O N

, V A

DESCRIPTIONMARK DATE

S . L

YN

N

H A

VE

N

R O

A D

VA

B

EA

CH

, V A

TE

LE

PH

O N

E:

(7

) 5

-4

PR

O

JE

CT

N U

M

BE

R:

4-

04.10.2026

N

EW

PO

R

T N

EW

S, V

IR

G

IN

IA

AI

R

V

AL

VE

R

EP

LA

C

EM

EN

T

M

AR

Y

BR

O C

K

FO

R

BE

S H

AL

L

- C H

R

IS

TO

PH

ER

N

EW

PO

R T

U N

IV

ER

SI

TY

ST

AT

E

PR

O

JE

C T

N O

2-

5-

24-015

04-10-2026

M002

M

EC

H

AN

IC

AL

S C

H

ED

U

LE

S

BDC

MAR

KDA

8GENERAL EXHAUST

SERVICE SIZE

(IN.)

UNIT

TAG

VSV-1007-1

ROUND

SHAPE

AIR VALVE SCHEDULE (OFCI)

MIN

FLOWRATE

(CFM)

MAX

FLOWRATE

(CFM)

REMARKS

6SUPPLY 0 190

VEV-1007-1 8FUME HOOD EXHAUST 270 640

VEV-1007-2 6GENERAL EXHAUST 0 190

VSV-1009-1 8SUPPLY 0 450

VEV-1009-1 8FUME HOOD EXHAUST 240 400

VEV-1009-2 8GENERAL EXHAUST 450 450

VSV-1013-1 10SUPPLY 0 0

VEV-1013-1 8FUME HOOD EXHAUST 240 400

VEV-1013-2 12GENERAL EXHAUST 0 0

VSV-1014-1 14SUPPLY 1200 2700

VEV-1014-1 12 X 18AUTOCLAVE EXHAUST 1500 3000

VSV-1015-1 10SUPPLY 600 600

VEV-1015-1 8FUME HOOD EXHAUST 270 640

VEV-1015-2 8GENERAL EXHAUST 415 600

VSV-1025-1 6SUPPLY 100 120

VEV-1025-1 8FUME HOOD EXHAUST 240 400

VEV-1025-2 6GENERAL EXHAUST 95 250

VSV-1026-1 8SUPPLY 340 340

VEV-1026-1 8FUME HOOD EXHAUST 240 400

VEV-1026-2 6GENERAL EXHAUST 90 250

VSV-1027-1 8SUPPLY 260 260

VEV-1027-1 8GENERAL EXHAUST 260 260

VSV-1028-1 8 380 380

VEV-1028-1 8 240 400

VEV-1028-2 6 135 295

VSV-1033-1 8 250 250

VEV-1033-1 8 270 640

VEV-1033-2 6 65 250

VSV-1034-1 370 370

VEV-1034-1 240 400

VEV-1034-2 125 285

VSV-1036-1 12SUPPLY 0 0

VEV-1036-1 8GENERAL EXHAUST 450 450

VSV-1038-1 12X24SUPPLY 0 0

VEV-1038-1 6GENERAL EXHAUST 150 150

VSV-1039-1 SUPPLY 80 600

VEV-1039-1 GENERAL EXHAUST 520 600

VSV-1040-1 SUPPLY 120 390

VEV-1040-1 FUME HOOD EXHAUST 240 400

VEV-1040-2 GENERAL EXHAUST 140 300

VSV-L1C01-1 10SUPPLY 700 770

VSV-L1C01-2

VEV-L1C03-1 6GENERAL EXHAUST 40 40

VSV-L1C05-1 14SUPPLY 1525 1525

VSV-L1C06-1 6 90 90

6 90 90

10SUPPLY 600 660

VEV-L1C08-1 0 0

REMARKS: 1

ROOM

SERVED

VEV-1002-1

8SUPPLY ROUND 400 400VSV-1002-1

INTEGRAL

CONTROLLER MATERIAL ACTUATOR

TYPE

ALUMINUM

YES

YES

YES

YES

YES

YES

YES

YES

YES

YES

INSULATION

TYPE

2" BLANKET

2" BLANKET

2" BLANKET

2" BLANKET

2" BLANKET

2" BLANKET

2" BLANKET

2" BLANKET

2" BLANKET

2" BLANKET

2" BLANKET

2" BLANKET

2" BLANKET

APD @ MAX

DESIGN

CFM

MIN CFM MAX CFM CONFIG

RANGE

(CFM)

DESIGN AIRFLOW RANGE OF VALVE RANGE OF VALVE

ANALOG OUTPUT #1 MODEL NUMBER

BASED ON

"ACCUTROL"

ESTIMATED POWER

REQUIREMENTS

24 VDC

(W)

24 VAC

(VA)

EXISTING

DUCT SIZE

(IN. DIA OR

IN. L X W)

0.09

0.00

0.06

0.00

0.00

0.05

0.14

0.00

0.05

0.00

0.08

0.11

0.10

0.06

0.12

0.05

0.05

0.04

0.09

0.05

0.04

0.05

0.05

0.11

0.05

0.09

0.05

0.06

0.02

0.10

0.05

0.07

0.00

0.15

0.11

0.01

0.19

0.01

0.05

0.10

0.13

0.00

0.13

0.04

0.04

0.10

0.00

0.12

80 800

30 315

80 800

30 315

80 800

80 800

80 800

120 1300

80 800

180 1790

250 2750

260 3200

120 1300

80 800

80 800

30 315

80 800

30 315

80 800

80 800

30 315

30 315

180 1790

80 800

350 4000

30 315

120 1300

30 315

250 2750

30 315

120 1300

250 2750

80 800 0-10V

0-800

0-315

0-800

0-315

0-1300

0-800

0-1790

0-2750

0-3200

0-1300

0-800

0-800

0-315

0-800

0-315

0-800

0-800

0-315

0-1790

0-800

0-4000

0-315

0-1300

0-315

0-2750

0-1300

0-2750

0-800 AVT6408-02-I

AVT6408-02

AVT6406-02-I

AVC6208-05

AVT6406-02

AVT6408-02-IS

AVC6208-05

AVT6408-02

AVT6410-02-IS

AVC6208-05

AVT6412-02-S

AVT6414-02-I

AVC6218-03

AVT6410-02-I

AVC6208-05

AVT6408-02

AVT6406-02-I

AVC6208-05

AVT6406-02

AVT6408-02-I

AVC6208-05

AVT6406-02

AVT6408-02-I

AVT6408-02

AVT6412-02-IS

AVT6408-02

AVT6424-02-IS

AVT6406-02

AVT6408-02-I

AVT6410-02-I

AVT6406-02

AVT6414-02-I

AVT6406-02-I

AVT6410-02-I

AVT6414-02-S

16 31 12 X 24

12 X 24

12 X 24

12 X 24

12 X 24

12 X 24

12 X 24

12 X 24

12 X 24

12 X 24

12 X 24

12 x 24

12 X 24

12 X 24

12 X 24

12 X 24

12 X 24

12 X 24

L1C-01

L1-C-03

L1-C-05

L1-C-06

L1-C-07

L1-C-08

VALVE COMPONENTS

VEV-L1C04-1 8GENERAL EXHAUST 300 300

VSV-1049-1 12 X 18SUPPLY 575 1470

VSV-1049-2 575 1470

HXV-1049-1 10FUME HOOD EXHAUST 120 640

HXV-1049-2 270 640

HXV-1049-3 270 640

HXV-1049-4 120 640

HXV-1049-5 8SNORKEL EXHAUST 430 430

HXV-1049-6

GXV-1049-1 12 X 18GENERAL EXHAUST 260 1790

VSV-1055-1 10SUPPLY 350 640

GXV-1055-1 10OTHER EXHAUST 390 790

VSV-1056-1 6SUPPLY 30 100

HXV-1056-1 8FUME HOOD EXHAUST 240 400

GXV-1056-1 6GENERAL EXHAUST

YES

YES

YES

2" BLANKET

2" BLANKET

0.07

0.10

0.10

0.11

0.11

0.11

0.11

0.13

0.15

0.11

0.17

0.05

0.12

80 800

260 3200

260 3200

120 1300

120 1300

80 800

260 3200

120 1300

120 1300

30 315

80 800

0-800

0-3200

0-3200

0-1300

0-1300

0-800

0-3200

0-1300

0-1300

0-315

0-800

AVT6408-02

AVT6418-02-I

AVC6210-05

AVT6418-02-S

AVT6410-02-I

AVT6210-05

AVT6406-02-I

AVC6208-05

12 X 36

12 X 18

12 X 18

12 X 18

12 X 18

12 X 18

12 X 18

L1-C-04

ALUMINUM

304SS

ALUMINUM

ALUMINUM

304SS

ALUMINUM

ALUMINUM

304SS

ALUMINUM

304SS

ALUMINUM

ALUMINUM

304SS

ALUMINUM

ALUMINUM

ALUMINUM

ROUND

ROUND

ROUND

ROUND

ROUND

ROUND

ROUND

RECTANGULAR

ROUND

ROUND

ROUND

ROUND

ROUND

ROUND

RECTANGULAR

ROUND

ROUND

ROUND

ALUMINUM

304SS

ALUMINUM

RECTANGULAR

ROUND

ROUND

RECTANGULAR

HS FLP 0-10V

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

ALUMINUM 2" BLANKET

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

HS FSP 2-10V

ROUND

ROUND

ROUND

304SS

ALUMINUM

ALUMINUM

HS FLP 0-10V

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

HS FLP 0-10V

HS FLP 0-10V

0-800

0-800

0-800

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

HS FLP 0-10V

HS FLP 2-10V

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

ALUMINUM

304SS

ALUMINUM

ROUND

ROUND

ROUND

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

ROUND

ROUND

ALUMINUM

ALUMINUM

HS FLP 0-10V

HS FLP 0-10V

80 800

80 800

0-800

0-800

SUPPLY

FUME HOOD EXHAUST

GENERAL EXHAUST

ALUMINUM

304SS

ALUMINUM

ROUND

ROUND

ROUND

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

80 800

80 800

0-800

0-800

0-315

AVT6408-02-I

AVC6208-05

AVT6406-02

SUPPLY

FUME HOOD EXHAUST

GENERAL EXHAUST

ALUMINUM

304SS

ALUMINUM

ROUND

ROUND

ROUND

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

30 315

80 800

80 800

0-800

0-800

0-315

AVT6408-02-I

AVC6208-05

AVT6406-02

YES

SUPPLY

FUME HOOD EXHAUST

GENERAL EXHAUST

ALUMINUM

304SS

ALUMINUM

ROUND

ROUND

ROUND

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

30 315

80 800

80 800

0-800

0-800

0-315

AVT6408-02-I

AVC6208-05

AVT6406-02

ALUMINUMROUND

ALUMINUMROUND

HS FLP 0-10V

HS FLP 0-10V

2" BLANKETALUMINUM

ALUMINUM

HS FLP 0-10V

HS FLP 0-10V

ALUMINUMROUND

ALUMINUMROUND

HS FLP 0-10V

HS FLP 0-10V

2" BLANKET 80 800

80 800

0-800

0-800

AVT6408-02-I

AVT6408-02

6 30 315

80 800

80 800

0-800

0-800

0-315

AVC6208-05

AVT6406-02

ALUMINUMROUND HS FLP 0-10V

10SUPPLY 700 770- 2" BLANKET 0.13 120 1300 0-1300 AVT6410-02-I 1016 310-10VALUMINUMROUND HS FLP 0-10V

VSV-L1C01-3 10SUPPLY 700 770- 2" BLANKET 0.13 120 1300 0-1300 AVT6410-02-I 816 310-10VALUMINUMROUND HS FLP 0-10V

HS FLP 0-10V

HS FLP 0-10V 2" BLANKET

VSV-L1C06-2

SUPPLY

SUPPLY

ALUMINUM

ALUMINUM

ROUND

ROUND

HS FLP 0-10V

HS FLP 0-10V

2" BLANKET

2" BLANKET

0-315

30 315 0-315 AVT6406-02-I

VSV-L1C07-1 ALUMINUMROUND HS FLP 0-10V 2" BLANKET

14GENERAL EXHAUST - -ALUMINUMROUND HS FLP 0-10V

ALUMINUMROUND HS FLP 0-10V

HS FLP 0-10V

12 X 18SUPPLY - 2" BLANKETALUMINUMRECTANGULAR HS FLP 0-10V AVT6418-02-I

HS FSP 2-10V

10FUME HOOD EXHAUST YES -ROUND HS FSP 2-10V

10FUME HOOD EXHAUST YES -ROUND HS FSP 2-10V

10FUME HOOD EXHAUST YES -ROUND HS FSP 2-10V

120 1300

120 1300

0-1300

0-1300

0-10V

0-10V

AVC6210-05

AVC6210-05

AVC6210-05

AVC6208-05

AVC6208-05

10304SS

304SS

304SS

304SS

HS FSP 2-10V

8SNORKEL EXHAUST 430 430YES - 0.13 80 800 0-800304SSROUND 0-10VHS FSP 2-10V

HS FLP 0-10V

ALUMINUMROUND HS FLP 0-10V

304SSROUND HS FSP2-10V

2" BLANKET

ALUMINUM

304SS

ALUMINUM

ROUND

ROUND

ROUND

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

30 100 0.05 30 315 0-315 AVT6406-020-10V

"HS FLP" INDICATES A HIGH-SPEED ACTUATOR WHICH WILL FAIL TO ITS LAST

POSITION. "HS FSP" INDICATES A HIGH-SPEED ACTUATOR WHICH WILL FAIL

OPEN/CLOSED. ALL "FSP" ACTUATORS SHALL BE SET TO FAIL OPEN.

2 ALL ROUND VALVES SHALL BE PROVIDED WITH BAND CLAMPS

FROM THE FACTORY FOR SIMPLIFIED CONNECTION TO

UPSTREAM/DOWNSTREAM ROUND DUCTWORK.

3 REFER TO SPECIFICATION SECTION 230500

FOR ADDITIONAL REQUIREMENTS.

4 VALVES WITH INLET/OUTLET SIZES DIFFERING FROM EXISTING DUCT SIZES SHALL

BE PROVIDED WITH DUCTWORK TRANSITIONS BY THE MECHANICAL CONTRACTOR.

DUCTWORK SHALL BE SAME MATERIAL AS VALVE CONSTRUCTION.

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3

1 2 3

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3

1 2 3 4

1 2 3 4

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3 4

1 2 3 4

1 2 3

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

NOTE: THE DESIGN SHOWN IS BASED ON ACCUTROL

"AVT6400" AND "AVC6200" EQUIPMENT AND IS INTEDED

ONLY TO SHOW THE GENERAL SIZE, CONFIGURATION,

LOCATION, CONNECTIONS, AND SUPPORT FOR

EQUIPMENT OR SYSTEMS SPECIFIED WITH RELATION

TO THE OTHER BUILDING SYSTEMS. SEE

SPECIFICATION 230500 FOR TECHNICAL

REQUIREMENTS PERTAINING TO THE EQUIPMENT.

2" BLANKET

ALUMINUM

304SS

ALUMINUM

ROUND

ROUND

ROUND

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

HXV-1055-1 CADAVER TABLE EXHAUST YES 8 ROUND 304SS HS FSP 2-10V - 220 340 0.12 80 800 0-800 AVC6208-05 -16 310-10V 1 2 3

DRAWN BY:

DESIGNED BY:

COMM. NO:

C O

X

RO

A D

Co ns ul tin g En gi ne er s

TH

O

M

PS

O N

E

N

TE

RP

RI

SE

P

A

RK

W A

Y G

LE

N

A

LL

EN

, V

A

REVISIONS

H A

M

PT

O N

, V A

DESCRIPTIONMARK DATE

S . L

YN

N

H A

VE

N

R O

A D

VA

B

EA

CH

, V A

TE

LE

PH

O N

E:

(7

) 5

-4

PR

O

JE

CT

N U

M

BE

R:

4-

04.10.2026

N

EW

PO

R

T N

EW

S, V

IR

G

IN

IA

AI

R

V

AL

VE

R

EP

LA

C

EM

EN

T

M

AR

Y

BR

O C

K

FO

R

BE

S H

AL

L

- C H

R

IS

TO

PH

ER

N

EW

PO

R T

U N

IV

ER

SI

TY

ST

AT

E

PR

O

JE

C T

N O

2-

5-

24-015

04-10-2026

M003

M

EC

H

AN

IC

AL

S C

H

ED

U

LE

S

BDC

MAR

KDA

10UTILITY OVEN EXHAUST

SERVICE SIZE

(IN.)

UNIT

TAG

GXV-1057-2

SHAPE

AIR VALVE SCHEDULE (OFCI)

MIN

FLOWRATE

(CFM)

MAX

FLOWRATE

(CFM)

REMARKS

10GENERAL EXHAUST 120 590

VSV-1058-1 6SUPPLY 30 90

GXV-1058-1 8GENERAL EXHAUST 300 390

VSV-1059-1 6SUPPLY

GXV-1059-1 8GENERAL EXHAUST

VSV-1060-1 12 X 18SUPPLY 0 0

GXV-1060-1 8GENERAL EXHAUST 300 300

VSV-1062-1 6SUPPLY 30 70

VSV-1062A-1 12SUPPLY 180 1000

WXV-1062A-1 10CAGE EXHAUST 250 700

WXV-1062A-2 10SPRAYDOWN AREA EXHAUST 160 550

GXV-1062A-1 10GENERAL EXHAUST 120 840

VSV-1062B-1 SUPPLY 0 0

GXV-1062B-1 250 250

845 1425

160 400

120 580

VSV-1062D-1 8 80 570

GXV-1062D-1 12 510 1020

VSV-1062E-1 8 330 460

GXV-1062E-1 6 180 180

GXV-1062E-2 6 130 130

VSV-1062F-1 330 500

GXV-1062F-1 180 350

VSV-1062G-1

GXV-1062G-1

GXV-1062G-2

VSV-1062H-1 110/410 110/410

GXV-1062H-1 180 180

GXV-1062H-2 75 80

100/400 100/400

180 180

75 80

VSV-1062K-1 8 80 305

GXV-1062K-1 180 180

GXV-1062K-2 260 305

HXV-1062L-1 50 50

VSV-1063-1 8 170 360

GXV-1063-2 170 350

170 340

170 340

345 455

REMARKS:

ROOM

SERVED

GXV-1057-1

10SUPPLY ROUND 120 600VSV-1057-1

INTEGRAL

CONTROLLER MATERIAL ACTUATOR

TYPE

ALUMINUM

YES

YES

YES

YES

INSULATION

TYPE

2" BLANKET

APD @ MAX

DESIGN

CFM

MIN CFM MAX CFM CONFIG

RANGE

(CFM)

DESIGN AIRFLOW RANGE OF VALVE RANGE OF VALVE

ANALOG OUTPUT #1 MODEL NUMBER

BASED ON

"ACCUTROL"

ESTIMATED POWER

REQUIREMENTS

24 VDC

(W)

24 VAC

(VA)

EXISTING

DUCT SIZE

(IN. DIA OR

IN. L X W)

0.15

0.09

0.04

0.11

0.00

0.07

0.03

0.14

0.13

0.08

0.19

0.00

0.05

0.10

0.12

0.09

0.23

0.14

0.15

0.16

0.08

0.18

0.09

0.12

0.16

0.03

0.12

0.16

0.03

0.07

0.16

0.01

0.01

0.10

0.09

0.09

0.09

0.15

0.10

30 315

80 800

260 3200

80 800

30 315

180 1790

120 1300

120 1300

120 1300

30 315

80 800

260 3200

80 800

120 1300

80 800

180 1790

80 800

80 800

120 1300 0-10V

0-315

0-800

0-800

0-315

0-1790

0-1300

0-1300

0-1300

0-315

0-800

0-3200

0-800

0-1300

0-800

0-1790

0-800

0-800

0-1300 AVT6410-02-I

AVC6210-05

AVT6410-02-S

AVT6406-02-I

AVT6408-02

AVT6418-02-IS

AVT6408-02

AVT6406-02-I

AVT6412-02-I

AVC6210-05

AVT6410-02-S

AVT6406-02-I

AVT6408-02

AVT6418-02-I

AVC6208-05

AVT6410-02-S

AVT6408-02-I

AVT6412-02

AVT6408-02-I

AVC6206-05

AVT6408-02-I

AVC6206-05

AVT6408-02-I

AVT6408-02-I

16 31 8

12 X 18

VALVE COMPONENTS

60 60

110 165

VSV-L1C12-1 230 450

GXV-L1C12-1 8-

0.02

0.13

0.06

30 315

30 315

80 800

0-315

0-315

0-800

AVC6206-05

AVT6406-02

304SS

ALUMINUMROUND

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

YES

RECTANGULAR ALUMINUM 0-3200

80 800

30 315

0-800

0-315

30 315

80 800

0-315 AVT6406-02

AVT6408-02-I

AVT6408-02

YES

6 30 315

80 800

30 315

0-800

0-315

0-315

AVT6408-02-I

AVC6206-05

AVT6406-02

YES

30 315

80 800

0-315

0-800

AVC6206-05

AVT6408-02

6 30 315 0-315

0-800

0-800

AVT6408-02-IS

AVT6408-02

10- AVT6408-02-I

HS FLP 0-10V

-HS FSP 2-10V

2" BLANKET

2" BLANKET

2" BLANKET

2" BLANKET

-HS FSP 2-10V

1062A

1062E

1062H

1062K

1062L

1067A

ROUND 304SS

ROUND

ROUND ALUMINUM HS FLP 0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-1300

0-1300

ROUND ALUMINUM HS FLP 0-10V

ROUND ALUMINUM HS FLP 0-10V

2" BLANKET

ROUND ALUMINUM HS FLP 0-10V

ROUND ALUMINUM HS FLP 0-10V

30 90

300 390

0.04

0.11

30 315

80 800

0-315

0-800

AVT6406-02-I

AVT6408-02

HS FLP 0-10V

HS FLP 0-10V

ALUMINUMROUND HS FLP 0-10V

GENERAL EXHAUST

SUPPLY

GENERAL EXHAUST

SUPPLY

IVC RACK EXHAUST

GENERAL EXHAUST

SUPPLY

IVC RACK EXHAUST

GENERAL EXHAUST

SUPPLY

IVC RACK EXHAUST

GENERAL EXHAUST

SUPPLY

ISO CUBICLES EXHAUST

GENERAL EXHAUST

GAS CABINET EXHAUST

SUPPLY

GENERAL EXHAUST

SUPPLY

GENERAL EXHAUST

ALUMINUMROUND HS FLP 0-10V

ALUMINUMROUND HS FLP 0-10V

304SS HS FSP 2-10VROUND

304SS HS FSP 2-10VROUND

2" BLANKET

AVC6210-05

1062B

2" BLANKET

ROUND ALUMINUM HS FLP 0-10V

ROUND ALUMINUM HS FLP 0-10V

1062C

VSV-1062C-1 12 X 18SUPPLY

WXV-1062C-1 8CAGE EXHAUST

GXV-1062C-1 10GENERAL EXHAUST

YES

ALUMINUMROUND HS FLP 0-10V

ALUMINUMROUND HS FLP 0-10V

304SS HS FSP 2-10VROUND

2" BLANKET

1062D

ALUMINUMROUND HS FLP 0-10V

ALUMINUMROUND HS FLP 0-10V

ALUMINUMROUND

ALUMINUMROUND

304SSROUND

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

2" BLANKET

1062F

2" BLANKET

SUPPLY

GENERAL EXHAUST

ALUMINUMROUND HS FLP 0-10V

ALUMINUMROUND HS FLP 0-10V 80 800 0-800

0-800

1062G

YES

ALUMINUMROUND

ALUMINUMROUND

304SSROUND

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

2" BLANKET 330 500

180 180

130 130

0.18

0.16

0.08

80 800

30 315

30 315

AVT6408-02-I

AVC6206-05

0-800

0-315

0-315 AVT6406-02

ALUMINUMROUND

ALUMINUMROUND

304SSROUND

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

2" BLANKET

1062J

VSV-1062J-1

GXV-1062J-1

GXV-1062J-2

YES

SUPPLY

IVC RACK EXHAUST

GENERAL EXHAUST

ALUMINUMROUND

ALUMINUMROUND

304SSROUND

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

2" BLANKET

30 315

80 800

30 315

0-800

0-315

0-315

AVT6408-02-I

AVC6206-05

AVT6406-02

0-10V

0-10V

0-10V

ALUMINUMROUND

ALUMINUMROUND

304SSROUND

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

2" BLANKET

1062M

VSV-1062M-1 0 0

GXV-1062M-1 300 300

0.00

0.07

80 8008

2" BLANKET

SUPPLY

GENERAL EXHAUST

ALUMINUMROUND HS FLP 0-10V

ALUMINUMROUND HS FLP 0-10V 80 800

16 31

16 31

0-800

0-800

AVT6408-02-IS

AVT6408-02

0-10V

0-10V 1062X

VSV-1062X-1 0 0

GXV-1062X-1 300 300

0.00

0.07

80 8008

2" BLANKET

SUPPLY

GENERAL EXHAUST

ALUMINUMROUND HS FLP 0-10V

ALUMINUMROUND HS FLP 0-10V 80 800

16 31

16 31

0-1790

0-800

AVT6412-02-I

AVT6412-02

0-10V

0-10V 1062Y

VSV-1062Y-1 0/1020 0/1140

GXV-1062Y-1 180/900 240/900

0.18

0.11

180 179012

2" BLANKET

SUPPLY

GENERAL EXHAUST

ALUMINUMROUND HS FLP 0-10V

ALUMINUMROUND HS FLP 0-10V 80 800

ALUMINUMROUND

8 ALUMINUMROUND

HS FLP 0-10V

HS FLP 0-10V

2" BLANKET 0-8000-10V80 800

0-8000-10V80 800 AVT6408-02

VSV-1067-1 8

GXV-1067-1

SUPPLY

GENERAL EXHAUST

ALUMINUMROUND

8 ALUMINUMROUND

HS FLP 0-10V

HS FLP 0-10V

2" BLANKET 0-8000-10V80 800 AVT6408-02-I

0-8000-10V80 800 AVT6408-02

VSV-1067A-1 8

GXV-1067A-1

GXV-1067A-2

YES

SUPPLY

ISO CUBICLE EXHAUST

GENERAL EXHAUST

ALUMINUMROUND

ALUMINUMROUND

304SSROUND

HS FLP 0-10V

HS FLP 0-10V

HS FSP 2-10V

2" BLANKET

L1-C-12

ALUMINUMROUND HS FLP 0-10V

ALUMINUMROUND HS FLP 0-10V

2" BLANKET

80 350 0.09 80 800 0-800 AVT6408-020-10V

1 "HS FLP" INDICATES A HIGH-SPEED ACTUATOR WHICH WILL FAIL TO ITS LAST

POSITION. "HS FSP" INDICATES A HIGH-SPEED ACTUATOR WHICH WILL FAIL

OPEN/CLOSED. ALL "FSP" ACTUATORS SHALL BE SET TO FAIL OPEN.

2 ALL ROUND VALVES SHALL BE PROVIDED WITH BAND CLAMPS

FROM THE FACTORY FOR SIMPLIFIED CONNECTION TO

UPSTREAM/DOWNSTREAM ROUND DUCTWORK.

3 REFER TO SPECIFICATION SECTION 230500

FOR ADDITIONAL REQUIREMENTS.

4 VALVES WITH INLET/OUTLET SIZES DIFFERING FROM EXISTING DUCT SIZES SHALL

BE PROVIDED WITH DUCTWORK TRANSITIONS BY THE MECHANICAL CONTRACTOR.

DUCTWORK SHALL BE SAME MATERIAL AS VALVE CONSTRUCTION.

1 2 3 4

1 2 3

1 2 3

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3

1 2 3

1 2 3

1 2 3 4

1 2 3 4

1 2 3

1 2 3 4

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3

1 2 3 4

1 2 3

1 2 3

1 2 3 4

1 2 3

1 2 3

1 2 3 4

1 2 3 4

1 2 3

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3

1 2 3 4

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3 4

1 2 3 4

NOTE: THE DESIGN SHOWN IS BASED ON ACCUTROL

"AVT6400" AND "AVC6200" EQUIPMENT AND IS INTEDED

ONLY TO SHOW THE GENERAL SIZE, CONFIGURATION,

LOCATION, CONNECTIONS, AND SUPPORT FOR

EQUIPMENT OR SYSTEMS SPECIFIED WITH RELATION

TO THE OTHER BUILDING SYSTEMS. SEE

SPECIFICATION 230500 FOR TECHNICAL

REQUIREMENTS PERTAINING TO THE EQUIPMENT.

GXV-1061-1 8GENERAL EXHAUST 80 250- 0.05 80 800 0-800 AVT6408-02-S 816 31-1061 0-10VALUMINUMROUND HS FLP 0-10V 1 2 3

GXV-1064-1 8GENERAL EXHAUST 125 300- 0.07 80 800 0-800 AVT6408-02-S 1016 31-1064 0-10VALUMINUMROUND HS FLP 0-10V 1 2 3 4

GXV-1068-1 6GENERAL EXHAUST 70 190- 0.17 30 315 0-315 AVT6406-02 816 31-1068 0-10VALUMINUMROUND HS FLP 0-10V 1 2 3 4

GXV-1069-1 6GENERAL EXHAUST 140 180- 0.16 30 315 0-315 AVT6406-02 1016 31-1069 0-10VALUMINUMROUND HS FLP 0-10V 1 2 3 4

VSV-L1C11-1 10SUPPLY 120 600- 0.10 120 1300 0-1300 AVT6410-02-I 1016 31L1-C-11 0-10VALUMINUMROUND HS FLP 0-10V 1 2 32" BLANKET

80 320 0.08 80 800 0-800 AVT6408-02-I 8

120 640

180 1000

0.11

0.14

120 1300

180 1790

0-1300

0-1790 AVT6412-02-S

16 31

16 31

16 31

L1-C-13

0-10V

0-10V

0-10V

VSV-L1C13-1 8

VSV-L1C13-2

GXV-L1C13-1

SUPPLY

SUPPLY

GENERAL EXHAUST -

ALUMINUMROUND

ALUMINUMROUND

ROUND

HS FLP 0-10V

HS FLP 0-10V 2" BLANKET 1 2 3

1 2 3

1 2 3

ALUMINUM HS FLP 0-10V 2" BLANKET AVT6410-02-I 4

GXV-1070F-1 6GENERAL EXHAUST 100 100- 0.05 30 315 0-315 AVT6406-02 616 31-1070F 0-10VALUMINUMROUND HS FLP 0-10V 1 2 3

GXV-1076-1 8GENERAL EXHAUST 300 300- 0.07 80 800 0-800 AVT6406-02-S 12 X 616 31-1076 0-10VALUMINUMROUND HS FLP 0-10V 1 2 3 4

DRAWN BY:

DESIGNED BY:

COMM. NO:

C O

X

RO

A D

Co ns ul tin g En gi ne er s

TH

O

M

PS

O N

E

N

TE

RP

RI

SE

P

A

RK

W A

Y G

LE

N

A

LL

EN

, V

A

REVISIONS

H A

M

PT

O N

, V A

DESCRIPTIONMARK DATE

S . L

YN

N

H A

VE

N

R O

A D

VA

B

EA

CH

, V A

TE

LE

PH

O N

E:

(7

) 5

-4

PR

O

JE

CT

N U

M

BE

R:

4-

04.10.2026

N

EW

PO

R

T N

EW

S, V

IR

G

IN

IA

AI

R

V

AL

VE

R

EP

LA

C

EM

EN

T

M

AR

Y

BR

O C

K

FO

R

BE

S H

AL

L

- C H

R

IS

TO

PH

ER

N

EW

PO

R T

U N

IV

ER

SI

TY

ST

AT

E

PR

O

JE

C T

N O

2-

5-

24-015

04-10-2026

M004

M

EC

H

AN

IC

AL

S C

H

ED

U

LE

S

BDC

MAR

KDA

SERVICE SIZE

(IN.)

UNIT

TAG

VSV-2041-1

SHAPE

AIR VALVE SCHEDULE (OFCI)

MIN

FLOWRATE

(CFM)

MAX

FLOWRATE

(CFM)

REMARKS

6 0 150

VEV-2041-1 10 270 640

VEV-2041-2 8 0 640

VSV-2042-1 90 180

VEV-2042-1 240 400

VEV-2042-2 0 160

VSV-2043-1 10 120 610

VEV-2043-1 10 530 610

VSV-2044-1 14 850 1470

VEV-2044-1 10 270 640

VEV-2044-2 12 750 990

VEV-2044-3 10 0 620

0 0

300 300

165 695

530 685

110 370

240 400

120 280

110 370

240 400

0 160

70 130

60 125

0 120

110 120

155 675

80 320

0 870

120 390

240 400

145 305

VSV-L2C03-1 0 0

VEV-L2C03-1 50 50

VSV-L2C04-1

VEV-L2C07-1 0 0

VSV-L2C09-1 12

VSV-L2C09-2

REMARKS:

ROOM

SERVED

VEV-2015-1

8SUPPLY ROUND 0 250VSV-2015-1

INTEGRAL

CONTROLLER MATERIAL ACTUATOR

TYPE

ALUMINUM

YES

YES

YES

INSULATION

TYPE

2" BLANKET

APD @ MAX

DESIGN

CFM

MIN CFM MAX CFM CONFIG

RANGE

(CFM)

DESIGN AIRFLOW RANGE OF VALVE RANGE OF VALVE

ANALOG OUTPUT #1 MODEL NUMBER

BASED ON

"ACCUTROL"

ESTIMATED POWER

REQUIREMENTS

24 VDC

(W)

24 VAC

(VA)

EXISTING

DUCT SIZE

(IN. DIA OR

IN. L X W)

0.05

0.11

0.11

0.09

0.16

0.04

0.12

0.10

0.10

0.12

0.11

0.13

0.10

0.00

0.07

0.13

0.13

0.10

0.04

0.06

0.10

0.12

0.12

0.08

0.08

0.07

0.07

0.12

0.08

0.10

0.11

0.12

0.07

0.00

0.01

0.00

0.05

80 800

30 315

120 1300

80 800

30 315

120 1300

30 315

120 1300

120 1300

250 2750

120 1300

180 1790

120 1300

120 1300

80 800

120 1300

120 1300

180 1790

180 1790

80 800 0-10V

0-315

0-1300

0-800

0-1300

0-1300

0-2750

0-1300

0-1790

0-1300

0-1300

0-800

0-1300

0-1300

0-1790

0-1790

0-800 AVT6408-02-IS

AVT6408-02

AVT6406-02-I

AVC6210-05

AVT6408-02-S

AVT6406-02-I

AVC6210-05

AVT6406-02

AVT6410-02-I

AVT6410-02

AVT6414-02-I

AVC6210-05

AVC6212-05

AVT6410-02-S

AVT6410-02-IS

AVT6408-02

AVT6410-02-I

AVT6410-02

AVT6408-02-I

AVC6210-05

AVT6408-02

AVT6408-02-I

AVC6208-05

AVT6406-02

AVT6412-02-S

AVT6408-02-I

AVC6208-05

AVT6406-02

AVT6412-02-I

16 31 12 X 24

12 X 24

12 X 24

12 X 24

12 X 24

12 X 24

12 X 24

12 X 24

12 X 36

VALVE COMPONENTS

304SS

ALUMINUM

ROUND

ROUND

ROUND

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

ALUMINUM

0-315

0-1300

0-315

80 800

120 1300 0-1300

0-800

AVT6410-02-I

AVC6208-05

30 315 0-315

AVT6408-02

AVT6406-02-I

6 30 315

30 315 0-315

0-315 AVT6406-02

12- 180 1790 0-1790 AVT6412-02-I 1216 31

VEV-L2C10-1 8 300 350- 0.09 80 800 0-800 AVT6408-02 12 X 2416 31

HS FLP 0-10V

2" BLANKETHS FLP 0-10V

-HS FSP 2-10V

-HS FLP 0-10V

L2-C-04

L2-C-07

L2-C-10

GENERAL EXHAUST

SUPPLY

FUME HOOD EXHAUST

GENERAL EXHAUST

SUPPLY

FUME HOOD EXHAUST

GENERAL EXHAUST

SUPPLY

GENERAL EXHAUST

SUPPLY

FUME HOOD EXHAUST

FUME HOOD EXHAUST

GENERAL EXHAUST

GENERAL EXHAUST

GENERAL EXHAUST

ROUND ALUMINUM HS FLP 0-10V 0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-800

YES 304SS

ALUMINUM

ROUND

ROUND

ROUND

ALUMINUM

- 2" BLANKETHS FLP 0-10V

-HS FSP 2-10V

-HS FLP 0-10V

ALUMINUMROUND HS FLP 0-10V

ROUND ALUMINUM 2" BLANKETHS FLP 0-10V

ROUND ALUMINUM 2" BLANKETHS FLP 0-10V

304SSROUND HS FSP 2-10V

304SSROUND HS FSP 2-10V

ROUND ALUMINUM HS FLP 0-10V

VSV-2047-1 10

VEV-2047-1 8

SUPPLY

GENERAL EXHAUST ALUMINUMROUND HS FLP 0-10V

ROUND ALUMINUM 2" BLANKETHS FLP 0-10V

VSV-2051-1 10

VEV-2051-1 10

SUPPLY

GENERAL EXHAUST ALUMINUMROUND HS FLP 0-10V

ROUND ALUMINUM 2" BLANKETHS FLP 0-10V

VSV-2052-1

VEV-2052-1

VEV-2052-2

SUPPLY

FUME HOOD EXHAUST

GENERAL EXHAUST

YES 304SS

ALUMINUM

ROUND

ROUND

ROUND

ALUMINUM

- 2" BLANKETHS FLP 0-10V

-HS FSP 2-10V

-HS FLP 0-10V

80 800

80 800

120 1300

0-800

0-800

0-1300

VSV-2053-1

VEV-2053-1

VEV-2053-2

SUPPLY

FUME HOOD EXHAUST

GENERAL EXHAUST

YES 304SS

ALUMINUM

ROUND

ROUND

ROUND

ALUMINUM

- 2" BLANKETHS FLP 0-10V

-HS FSP 2-10V

-HS FLP 0-10V

80 800 0-800

80 800 0-800

30 315 0-315

VSV-2055-1 6

VEV-2055-1 6

SUPPLY

GENERAL EXHAUST ALUMINUMROUND HS FLP 0-10V

ROUND ALUMINUM 2" BLANKETHS FLP 0-10V AVT6406-02-I0-10V30 315 0-315

AVT6406-020-10V30 315 0-315

2055B

VSV-2055B-1 6

VEV-2055B-1 6

SUPPLY

GENERAL EXHAUST ALUMINUMROUND HS FLP 0-10V

ROUND ALUMINUM 2" BLANKETHS FLP 0-10V AVT6406-02-I0-10V30 315 0-315

AVT6406-020-10V30 315 0-315

VSV-2056-1 10-SUPPLY ROUND ALUMINUM 2" BLANKETHS FLP 0-10V

VEV-2056-1 SNORKEL EXHAUST 8YES 304SSROUND -HS FSP 2-10V

VEV-2056-2 SNORKEL EXHAUST 8YES 304SSROUND -HS FSP 2-10V

VEV-2056-3 SNORKEL EXHAUST 8YES 304SSROUND -HS FSP 2-10V

VEV-2056-4 SNORKEL EXHAUST 8YES 304SSROUND -HS FSP 2-10V

VEV-2056-6 12- -GENERAL EXHAUST ALUMINUMROUND HS FLP 0-10V

VEV-2056-5 VENTILATED TABLE 8YES 304SSROUND -HS FSP 2-10V

80 320

80 320

80 320

80 320

0.08 80 800 0-800 AVC6208-050-10V

0.08 80 800 0-800 AVC6208-050-10V

0.08 80 800 0-800 AVC6208-050-10V

0.08 80 800 0-800 AVC6208-050-10V

VSV-2057-1

VEV-2057-1

VEV-2057-2

SUPPLY

FUME HOOD EXHAUST

GENERAL EXHAUST

YES 304SS

ALUMINUM

ROUND

ROUND

ROUND

ALUMINUM

- 2" BLANKETHS FLP 0-10V

-HS FSP 2-10V

-HS FLP 0-10V

80 800 0-8000-10V

80 800 0-8000-10V

80 800 0-8000-10V

L2-C-03

SUPPLY 6 ROUND ALUMINUM- 2" BLANKETHS FLP 0-10V

GENERAL EXHAUST 6 ROUND ALUMINUM- -HS FLP 0-10V

0 0 0.00 AVT6410-02-IS -16 31120 1300 0-13000-10VSUPPLY 10 ROUND ALUMINUM- 2" BLANKETHS FLP 0-10V

ROUND ALUMINUM HS FLP 0-10V

L2-C-09

SUPPLY

SUPPLY

2" BLANKET

ROUND ALUMINUM 2" BLANKETHS FLP 0-10V

ROUND ALUMINUM HS FLP 0-10V

975 1005 0.14

975 1005 0.14

ROUND ALUMINUM HS FLP 0-10V

1 "HS FLP" INDICATES A HIGH-SPEED ACTUATOR WHICH WILL FAIL TO ITS LAST

POSITION. "HS FSP" INDICATES A HIGH-SPEED ACTUATOR WHICH WILL FAIL

OPEN/CLOSED. ALL "FSP" ACTUATORS SHALL BE SET TO FAIL OPEN.

2 ALL ROUND VALVES SHALL BE PROVIDED WITH BAND CLAMPS

FROM THE FACTORY FOR SIMPLIFIED CONNECTION TO

UPSTREAM/DOWNSTREAM ROUND DUCTWORK.

3 REFER TO SPECIFICATION SECTION 230500

FOR ADDITIONAL REQUIREMENTS.

4 VALVES WITH INLET/OUTLET SIZES DIFFERING FROM EXISTING DUCT SIZES SHALL

BE PROVIDED WITH DUCTWORK TRANSITIONS BY THE MECHANICAL CONTRACTOR.

DUCTWORK SHALL BE SAME MATERIAL AS VALVE CONSTRUCTION.

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3

1 2 3 4

1 2 3 4

1 2 3

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3

1 2 3

1 2 3 4

NOTE: THE DESIGN SHOWN IS BASED ON ACCUTROL

"AVT6400" AND "AVC6200" EQUIPMENT AND IS INTEDED

ONLY TO SHOW THE GENERAL SIZE, CONFIGURATION,

LOCATION, CONNECTIONS, AND SUPPORT FOR

EQUIPMENT OR SYSTEMS SPECIFIED WITH RELATION

TO THE OTHER BUILDING SYSTEMS. SEE

SPECIFICATION 230500 FOR TECHNICAL

REQUIREMENTS PERTAINING TO THE EQUIPMENT.VSV-2002-1 80 570

VEV-2002-1 390 530

VEV-2002-2 490 570

VSV-2007-1 10 0 0

VEV-2007-1

0 250

250 250

VSV-2013-1 8 0 340

VEV-2013-1 10 270 640

VEV-2013-2 8 0 340

YES

0.23

0.08

0.23

0.00

0.05

0.05

0.09

0.11

0.09

80 800

80 800

80 800

80 800

120 1300

80 800

0-800

0-800

0-800

AVT6408-02-IS

AVT6408-02

AVT6408-02-IS

AVC6210-05

AVT6408-02-S

12 X 24

12 X 24

ALUMINUMROUND

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

8- ROUND

10YES

8-

80 800

AVT6408-02-I

AVC6208-05

AVT6408-02

AVT6408-02-I

AVT6408-02

12 X 24

12 X 24

ALUMINUM

8 450 450- 0.15 80 800 0-800

ALUMINUMROUND

304SS

ALUMINUM

ROUND

ROUND

2" BLANKETHS FLP 0-10V

-HS FSP 2-10V

-HS FLP 0-10V

2" BLANKETHS FLP 0-10V

-HS FSP 2-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

SUPPLY

FUME HOOD EXHAUST

GENERAL EXHAUST

SUPPLY

GENERAL EXHAUST

SUPPLY

FUME HOOD EXHAUST

GENERAL EXHAUST

304SSROUND

ROUND ALUMINUM

80 800

80 800

0-800

0-800

0-800

ALUMINUMROUND HS FLP 0-10V

VSV-2009-1 8

VEV-2009-1

- ALUMINUMROUND

8-

2" BLANKETHS FLP 0-10V

SUPPLY

GENERAL EXHAUST ALUMINUMROUND HS FLP 0-10V

HS FLP 0-10V

HS FLP 0-10V

2" BLANKET 0-800

0-1300

0-800

1 2 3 4

1 2 3

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 4

2055A 80 415

200 565

0.13

0.09

16 31

16 31

VSV-2055A-1 8

VEV-2055A-1 10

SUPPLY

GENERAL EXHAUST ALUMINUMROUND HS FLP 0-10V

ROUND ALUMINUM 2" BLANKETHS FLP 0-10V AVT6408-02-I0-10V80 800 0-800

AVT6410-020-10V120 1300 0-1300

1 2 3

1 2 3

DRAWN BY:

DESIGNED BY:

COMM. NO:

C O

X

RO

A D

Co ns ul tin g En gi ne er s

TH

O

M

PS

O N

E

N

TE

RP

RI

SE

P

A

RK

W A

Y G

LE

N

A

LL

EN

, V

A

REVISIONS

H A

M

PT

O N

, V A

DESCRIPTIONMARK DATE

S . L

YN

N

H A

VE

N

R O

A D

VA

B

EA

CH

, V A

TE

LE

PH

O N

E:

(7

) 5

-4

PR

O

JE

CT

N U

M

BE

R:

4-

04.10.2026

N

EW

PO

R

T N

EW

S, V

IR

G

IN

IA

AI

R

V

AL

VE

R

EP

LA

C

EM

EN

T

M

AR

Y

BR

O C

K

FO

R

BE

S H

AL

L

- C H

R

IS

TO

PH

ER

N

EW

PO

R T

U N

IV

ER

SI

TY

ST

AT

E

PR

O

JE

C T

N O

2-

5-

24-015

04-10-2026

M005

M

EC

H

AN

IC

AL

S C

H

ED

U

LE

S

BDC

MAR

KDA

SERVICE SIZE

(IN.)

UNIT

TAG

VEV-3015-2

SHAPE

AIR VALVE SCHEDULE (OFCI)

MIN

FLOWRATE

(CFM)

MAX

FLOWRATE

(CFM)

REMARKS

8 240 400

VEV-3015-3 6 80 110

VEV-3015-4 8 0 380

170 320

470 620

0 150

895 1480

750 990

680 1350

0 585

175 745

110 240

0 325

VSV-3042-1 12 305 1045

VEV-3042-1 10 270 640

VEV-3042-2 10

VEV-3042-3 10 0 740

950 2360

270 640

680 1350

0 1300

VSV-3048-1 12 345 1165

VSV-3048-2 12

VEV-3048-1

0 160

12 0 820

REMARKS:

ROOM

SERVED

VEV-3015-1

14 ROUND 865 1245VSV-3015-1

INTEGRAL

CONTROLLER MATERIAL ACTUATOR

TYPE

ALUMINUM

YES

YES

YES

INSULATION

TYPE

2" BLANKET

APD @ MAX

DESIGN

CFM

MIN CFM MAX CFM CONFIG

RANGE

(CFM)

DESIGN AIRFLOW RANGE OF VALVE RANGE OF VALVE

ANALOG OUTPUT #1 MODEL NUMBER

BASED ON

"ACCUTROL"

ESTIMATED POWER

REQUIREMENTS

24 VDC

(W)

24 VAC

(VA)

EXISTING

DUCT SIZE

(IN. DIA OR

IN. L X W)

0.13

0.12

0.06

0.11

0.03

0.10

0.11

0.12

0.13

0.10

0.24

0.15

0.05

0.08

0.15

0.11

0.15

0.16

0.11

0.10

0.23

0.19

0.12

0.09

0.08

180 1790

80 800

30 315

80 800

120 1300

120 1300

30 315

250 2750

180 1790

250 2750

80 800

120 1300

80 800

80 800

250 2750

180 1790

180 1790

180 1790

250 2750

0-1790

0-800

0-315

0-800

0-2750

0-1790

0-2750

0-800

0-1300

0-800

0-800

0-2750

0-1790

0-1790

0-2750 AVT6414-02-I

AVC6212-03

AVC6208-05

AVC6206-05

AVT6408-02-S

AVT6410-02-I

AVC6210-05

AVT6406-02

AVT6414-02-I

AVC6212-05

AVC6214-05

AVT6408-02-S

AVT6410-02-I

AVC6208-05

AVT6408-02-S

AVT6412-02-I

AVC6210-05

AVC6214-05

AVT6412-02-S

AVC6212-02-S

16 31 14

12 X 24

12 X 24

12 X 24

12 X 36

VALVE COMPONENTS

304SS 16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

16 31

YES

YES

0-1300

0-1300

0-315

180 1790

120 1300

0-1790

0-1300

120 1300 0-1300 AVT6410-02-S

350 4000

120 1300

0-4000

0-1300

AVT6424-02-I

AVC6210-05

6 30 315 0-315 AVC6206-05

12- 1216 31

HS FLP 0-10V

-HS FSP 2-10V

SUPPLY

FUME HOOD EXHAUST

FUME HOOD EXHAUST

SNORKEL EXHAUST

GENERAL EXHAUST

SUPPLY

GENERAL EXHAUST

SUPPLY

ROUND

ROUND

ROUND

ROUND

304SS

304SS

ALUMINUM HS FLP 0-10V

HS FSP 2-10V

HS FSP 2-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

0-10V

SUPPLY

FUME HOOD EXHAUST

GENERAL EXHAUST

YES 304SS

ALUMINUM

ROUND

ROUND

ROUND

ALUMINUM

- 2" BLANKETHS FLP 0-10V

-HS FSP 2-10V

-HS FLP 0-10V

VSV-3038-1

VEV-3038-1

VEV-3038-2

VSV-3040-1

VSV-3040-2

VEV-3040-1

VEV-3040-2

VEV-3040-3

VEV-3040-4

12YES

SUPPLY

FUME HOOD EXHAUST

ROUND ALUMINUM HS FLP 0-10V

14-SUPPLY ROUND ALUMINUM HS FLP 0-10V

304SSROUND HS FSP 2-10V

12YESFUME HOOD EXHAUST 304SSROUND HS FSP 2-10V

14YESCANOPY HOOD EXHAUST 304SSROUND HS FSP 2-10V

8-GENERAL EXHAUST ROUND ALUMINUM HS FLP 0-10V

2" BLANKET

2" BLANKET

VEV-3040-5 8-GENERAL EXHAUST ROUND ALUMINUM HS FLP 0-10V

895 1480 0.12 250 2750 0-2750 AVT6414-02-I 12 X 2416 310-10V

750 990 0.13 180 1790 0-1790 AVC6212-05 1016 310-10V

0 585 0.24 80 800 0-800 AVT6408-02-S 12 X 2416 310-10V

VSV-3041-1

VEV-3041-1

VEV-3041-2

VEV-3041-3

VEV-3041-4

VEV-3041-5

8YES

SUPPLY ROUND ALUMINUM HS FLP 0-10V

8YESSNORKEL EXHAUST ROUND

304SSROUND HS FSP 2-10V

8YES 304SSROUND HS FSP 2-10V

8YES 304SSROUND HS FSP 2-10V

8-GENERAL EXHAUST ROUND ALUMINUM HS FLP 0-10V

2" BLANKET

VEV-3041-6 8-GENERAL EXHAUST ROUND ALUMINUM HS FLP 0-10V

SNORKEL EXHAUST

SNORKEL EXHAUST

SNORKEL EXHAUST

304SS HS FSP 2-10V -

110 240 0.05 80 800 0-800 AVC6208-05 1016 310-10V

110 240 0.05 80 800 0-800 AVC6208-05 1016 310-10V

110 240 0.05 80 800 0-800 AVC6208-05 1016 310-10V

0 325 0.08 80 800 0-800 AVT6408-02-S 1216 310-10V

FUME HOOD EXHAUST

FUME HOOD EXHAUST

ROUND ALUMINUM HS FLP 0-10V 2" BLANKET

ROUND

304SSROUND HS FSP 2-10V

304SS HS FSP 2-10V -

ROUND ALUMINUM HS FLP 0-10V

270 640 0.11 AVC6210-05120 1300 0-13000-10V

VSV-3044-1 12 305 1045

VEV-3044-1 10 270 640

VEV-3044-2 10

VEV-3044-3 10 0 740

YES

YES

0.15

0.11

0.15

AVT6412-02-I

AVC6210-05

180 1790

120 1300

0-1790

0-1300

120 1300 0-1300 AVT6410-02-S

SUPPLY

GENERAL EXHAUST

0-10V

0-10V

0-10V

0-10V

FUME HOOD EXHAUST

FUME HOOD EXHAUST

ROUND ALUMINUM HS FLP 0-10V 2" BLANKET

ROUND

304SSROUND HS FSP 2-10V

304SS HS FSP 2-10V -

ROUND ALUMINUM HS FLP 0-10V

270 640 0.11 AVC6210-05120 1300 0-13000-10V

VSV-3045-1 12-SUPPLY ROUND ALUMINUM HS FLP 0-10V 2" BLANKET

VEV-3045-1 10

VEV-3045-2 10

YES

YES

FUME HOOD EXHAUST

FUME HOOD EXHAUST -

ROUND

304SSROUND HS FSP 2-10V

304SS HS FSP 2-10V -

VEV-3045-3 14YESCANOPY HOOD EXHAUST -304SSROUND HS FSP 2-10V

VEV-3045-4 10-GENERAL EXHAUST ROUND ALUMINUM HS FLP 0-10V -

270 640 0.11 120 1300 0-1300 AVC6210-050-10V

VEV-3048-2

VEV-3048-3

VEV-3048-4

VEV-3048-5

VEV-3048-6

VEV-3048-7

SUPPLY

FUME HOOD EXHAUST

FUME HOOD EXHAUST

FUME HOOD EXHAUST

FUME HOOD EXHAUST

SNORKEL EXHAUST

GENERAL EXHAUST

GENERAL EXHAUST

YES

YES

YES

YES

YES

ROUND ALUMINUM

ROUND ALUMINUM

ROUND ALUMINUM

HS FLP 0-10V

HS FLP 0-10V

HS FLP 0-10V

2" BLANKET

2" BLANKET

ROUND 304SS HS FSP 2-10V

ROUND 304SS HS FSP 2-10V

ROUND 304SS HS FSP 2-10V

ROUND 304SS HS FSP 2-10V

ROUND 304SS HS FSP 2-10V

ROUND ALUMINUM HS FLP 0-10V

0-1790 AVT6412-02-I

345 1165 0.19 180 1790 0-10V 0-1790 AVT6412-02-I

270 640 0.11 120 1300 0-1300 AVC6210-050-10V

270 640 0.11 120 1300 0-1300 AVC6210-050-10V

270 640 0.11 120 1300 0-1300 AVC6210-050-10V

270 640 0.11 120 1300 0-1300 AVC6210-05

0 820 0.09 180 1790 0-1790 AVC6212-02-S0-10V

1 "HS FLP" INDICATES A HIGH-SPEED ACTUATOR WHICH WILL FAIL TO ITS LAST

POSITION. "HS FSP" INDICATES A HIGH-SPEED ACTUATOR WHICH WILL FAIL

OPEN/CLOSED. ALL "FSP" ACTUATORS SHALL BE SET TO FAIL OPEN.

2 ALL ROUND VALVES SHALL BE PROVIDED WITH BAND CLAMPS

FROM THE FACTORY FOR SIMPLIFIED CONNECTION TO

UPSTREAM/DOWNSTREAM ROUND DUCTWORK.

3 REFER TO SPECIFICATION SECTION 230500

FOR ADDITIONAL REQUIREMENTS.

4 VALVES WITH INLET/OUTLET SIZES DIFFERING FROM EXISTING DUCT SIZES…