24-0014 - Specifications REV.pdf
PDF 744 KB Posted
- Attached to
- B73 Parking Lot Repair Offutt AFB, NE
- Solicitation number
- FA460025B0004
About this file
This document is a comprehensive set of technical specifications for repairing the parking lot at Building 73 on Offutt Air Force Base in Nebraska. The project involves complete parking lot reconstruction, including demolition, earthwork, drainage improvements, concrete pavement installation, electrical lighting upgrades, and landscaping. Specific technical requirements cover detailed aspects such as concrete mix design, base course drainage layers, subdrainage piping, underground electrical distribution, pavement markings, and seeding.
The specifications are part of Solicitation Number FA460025B0004, with a planned site visit on September 12, 2025, at 11:00 AM CDT. The project is funded by the Department of the Air Force Air Combat Command, with a contingency that funds are subject to appropriation availability. The contract includes precise technical requirements for materials and installation, with specifications for everything from concrete strength and composition to electrical conduit installation and grounding systems. The total project involves repairing and replacing the entire parking lot infrastructure, ensuring comprehensive renovation of the site's transportation and utility systems.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| B73 Site Visit Attendee List.xlsx | XLSX spreadsheet | |
| Amendment 1- Bid Opening Information.pdf | ||
| WD 22 Aug 2025.txt | TXT text file | |
| SF FM 31 - EAL Request - Blank 1.docx | DOCX document | |
| 24-0014- Drawings REV.pdf | ||
| SAM Wage Determination.pdf | ||
| Solicitation - FA460025B0004.pdf | ||
| Bid Submission and Opening Information.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPECIFICATIONS
100% Submittal
REPAIR PARKING LOT, B73
Offutt A.F.B., Nebraska
OAFB Project No. SGBP 24-0014 Contract No. FA4600-22-D-0003
HGM Project No. 741224
July 23, 2025
COA NE CA-0065
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly licensed Professional Engineer under the laws of the State of Nebraska.
_ ____ ___ June 27, 2025 William J. Glismann, P.E.
My registration renewal date is December 31, 2025.
Pages or sheets covered by this seal:
DIVIDION 2-EXISTING CONDITIONS; DIVISION 31 – EARTHWORK; DIVISION 32 – EXTERIOR
IMPROVEMENTS; & SECTION 33 46 16
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly licensed Professional Engineer under the laws of the State of Nebraska.
______ June 27, 2025 Stephen M. Farrington, P.E.
My registration renewal date is December 31, 2025.
Pages or sheets covered by this seal:
DIVISION 26 – ELECTRICAL & SECTION 33 71 02
OAFB Repair Parking Lot B73 SGBP24-0014
HGM # 741224 Table of Contents Page 1 of 1
TABLE OF CONTENTS
SECTION DESCRIPTION
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
00 01 15 List of Drawings 00 10 00 General Conditions
DIVISION 01 - GENERAL REQUIREMENTS
01 11 00 Summary Of Work 01 33 00 Submittal Procedures 01 33 01 Schedule of Material Submittals (AF Form 66) 01 42 00 Sources for Reference Publications 01 57 19 Temporary Environmental Controls
DIVISION 02 - EXISTING CONDITIONS
02 41 00 Demolition
DIVISION 26 - ELECTRICAL
26 56 00 Exterior Lighting
DIVISION 31 - EARTHWORK
31 00 00 Earthwork 31 11 00 Clearing and Grubbing
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 01 19.61 Sealing of Joints in Rigid Pavement 32 11 23.23 Base Course Drainage Layers 32 13 13.06 Portland Cement Concrete Pavement for Roads and Site Facilities 32 16 19 Concrete Curbs, Gutters and Sidewalks 32 17 23.16 Road and Parking Lot Pavement Markings 32 92 19 Seeding
DIVISION 33 - UTILITIES
33 46 16 Subdrainage Piping 33 71 02 Underground Electrical Distribution
-- End of Table of Contents --
HGM #741224 DOCUMENT 00 01 15 Page 1
DOCUMENT 00 01 15
LIST OF DRAWINGS
02/24
PART 1 GENERAL
1.1 SUMMARY
This section lists the drawings for the project pursuant to contract clause "DFARS 252.236-7001, Contract Drawings and Specifications."
1.2 CONTRACT DRAWINGS
Contract drawings are as follows:
DRAWING NO. REVISION NO. NAVFAC DWG NO. TITLE
Cover Cover Sheet & Location Plan
C0.1 Contractor Access & Staging Plan
C0.2 Topographic Survey
C1.1 Removal Plan
C1.2 Site Plan
C1.3 Grading Plan
C1.4 Drainage Plan
C1.5 Joint Layout Plan
C1.6 Erosion Control Plan
C1.7 Permanent Stabilization Plan
C2.1 Pavement Details
C2.2 Pavement Details
C2.3 Miscellaneous Details
C2.4 Miscellaneous Details
E1.1 Site Lighting Plan - Demolition
E1.2 Site Lighting Plan
-- End of Document –
HGM #741224 SECTION 02 41 00 Page 1
SECTION 02 41 00
DEMOLITION
08/22
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF SAFETY PROFESSIONALS (ASSP)
ASSP A10.6 (2006) Safety & Health Program Requirements for Demolition Operations - American National Standard for Construction and Demolition Operations
U.S. ARMY CORPS OF ENGINEERS (USACE)
EM 385-1-1 (2024) Safety -- Safety and Occupational Health (SOH) Requirements
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
40 CFR 61 National Emission Standards for Hazardous Air Pollutants
1.2 PROJECT DESCRIPTION
1.2.1 Definitions
1.2.1.1 Demolition
Demolition is the process of tearing apart and removing any feature of a facility together with any related handling and disposal operations.
1.2.1.2 Demolition Plan
Demolition Plan is the planned steps and processes for managing demolition activities and identifying the required sequencing activities and disposal mechanisms.
1.2.2 DemolitionPlan
Prepare a Demolition Plan and submit proposed demolition, and removal procedures for approval before work is started. Include in the plan procedures coordination with other work in progress, and a disconnection schedule of utility services. Coordinate with Waste Management Plan in accordance with Section 01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL. Provide procedures for safe conduct of the work in accordance with EM 385-1-1. Plan must be approved by Contracting Officer prior to work beginning.
1.2.3 General Requirements
Do not begin demolition until authorization is received from the Contracting Officer. The work includes demolition and removal of resulting rubbish and debris. Remove rubbish and debris from Government property daily, unless otherwise directed. Store materials that cannot be removed daily in areas specified by the Contracting Officer. In the interest of occupational safety and health, perform the work in accordance with EM 385-1-1, Section 17, Demolition, and other applicable Sections.
HGM #741224 SECTION 02 41 00 Page 2
1.3 ITEMS TO REMAIN IN PLACE
Comply with FAR 52.236-9 to protect existing vegetation, structures, equipment, utilities, and improvements. Coordinate the work of this section with all other work indicated. Construct and maintain shoring, bracing, and supports as required. Ensure that structural elements are not overloaded. Increase structural supports or add new supports as may be required as a result of any cutting, removal, deconstruction, or demolition work performed under this contract. Do not overload pavements to remain. Provide new supports and reinforcement for existing construction weakened by demolition, deconstruction, or removal work.
Repairs, reinforcement, or structural replacement require approval by the Contracting Officer prior to performing such work.
1.3.1 Existing Construction Limits and Protection
Do not disturb existing construction beyond the extent indicated or necessary for installation of new construction. Provide temporary shoring and bracing for support of building components to prevent settlement or other movement. Provide protective measures to control accumulation and migration of dust and dirt in all work areas. Remove snow, dust, dirt, and debris from work areas daily.
1.3.2 Trees
Protect trees within the project site which might be damaged during demolition, and which are indicated to be left in place Replace any tree designated to remain that is damaged during the work under this contract with like-kind or as approved by the Contracting Officer.
1.3.3 Utility Service
Maintain existing utilities indicated to stay in service and protect against damage during demolition and deconstruction operations. the Government or utility provider will disconnect and seal utilities serving each area of alteration or removal upon written request from the Contractor.
1.3.4 Facilities
Protect electrical and mechanical services and utilities. Where removal of existing utilities and pavement is specified or indicated, provide approved barricades, temporary covering of exposed areas, and temporary services or connections for electrical and mechanical utilities. Floors, roofs, walls, columns, pilasters, and other structural components that are designed and constructed to stand without lateral support or shoring, and are determined to be in stable condition, must remain standing without additional bracing, shoring, or lateral support until demolished or deconstructed, unless directed otherwise by the Contracting Officer.
Ensure that no elements determined to be unstable are left unsupported and place and secure bracing, shoring, or lateral supports as may be required as a result of any cutting, removal, deconstruction, or demolition work performed under this contract.
1.4 BURNING
The use of burning at the project site for the disposal of refuse and debris will not be permitted.
1.5 SUBMITTALS
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
HGM #741224 SECTION 02 41 00 Page 3
SD-01 Preconstruction Submittals
Demolition Plan; G
Existing Conditions
SD-07 Certificates
Notification; G
1.6 QUALITY ASSURANCE
Submit timely notification of demolition projects to Federal, State, regional, and local authorities in accordance with 40 CFR 61, Subpart M.
Notify the State's environmental protection agency and the Contracting Officer in writing 10 working days prior to the commencement of work in accordance with 40 CFR 61, Subpart M. Comply with federal, state, and local hauling and disposal regulations. In addition to the requirements of the "Contract Clauses," conform to the safety requirements contained in ASSP A10.6. Comply with the Environmental Protection Agency requirements specified. Use of explosives will not be permitted.
1.6.1 Dust and Debris Control
Prevent the spread of dust and debris and avoid the creation of a nuisance or hazard in the surrounding area. Do not use water if it results in hazardous or objectionable conditions such as, but not limited to, ice, flooding, or pollution.
1.7 PROTECTION
1.7.1 Traffic Control Signs
a. Where pedestrian and driver safety is endangered in the area of removal work, use traffic barricades with flashing lights. Anchor barricades in a manner to prevent displacement by wind. Notify the Contracting Officer prior to beginning such work.
1.7.2 Protection of Personnel
Before, during and after the demolition work continuously evaluate the condition of the site-specific features being demolished and take immediate action to protect all personnel working in and around the project site.
1.8 EXISTING CONDITIONS
Before beginning any demolition or deconstruction work, survey the site and examine the drawings and specifications to determine the extent of the work. Record existing conditions in the presence of the Contracting Officer or the Contracting Officer's Representative showing the condition of structures and other facilities adjacent to areas of alteration or removal. Photographs or electronic images with a minimum resolution of 3072 x 2304 pixels, capable of a print resolution of 300 dpi, will be acceptable as a record of existing conditions. Include in the record possible conflicting electrical conduits, plumbing lines, the location and extent of existing cracks and other damage and description of surface conditions that exist prior to starting work. It is the Contractor's responsibility to verify and document all required outages which will be required during the course of work, and to note these outages on the record document. Submit survey results to the Contracting Officer or the Contracting Officer's Representative.
PART 2 PRODUCTS – NOT USED
HGM #741224 SECTION 02 41 00 Page 4
PART 3 EXECUTION
3.1 DISPOSITION OF MATERIAL
3.1.1 Title to Materials
All materials and equipment removed and not reused , become the property of the Contractor and must be removed from Government property.
Materials approved for storage by the Contracting Officer must be removed before completion of the contract. Title to materials resulting from demolition and deconstruction, and materials and equipment to be removed, is vested in the Contractor upon approval by the Contracting Officer.
The Government will not be responsible for the condition or loss of, or damage to, such property after contract award. Showing for sale or selling materials and equipment on site is prohibited.
3.2 CLEANUP
Remove debris and rubbish from project site and similar excavations.
Remove and transport the debris in a manner that prevents spillage on streets or adjacent areas. Apply local regulations regarding hauling and disposal.
3.3 DISPOSAL OF REMOVED MATERIALS
3.3.1 Regulation of Removed Materials
Dispose of debris, rubbish, scrap, and other nonsalvageable materials resulting from removal operations with all applicable federal, state and local regulations as contractually specified off of Base property. Storage of removed materials on the project site is prohibited.
3.3.2 Burning on Government Property
Burning of materials removed from demolished and deconstructed structures will not be permitted on Government property
3.3.3 Removal from Government Property
Transport waste materials removed from demolition from Government property for legal disposal. Dispose of waste soil as directed.
-- End of Section --
HGM #741224 SECTION 26 56 00 Page 1
SECTION 26 56 00
EXTERIOR LIGHTING
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ALLIANCE FOR TELECOMMUNICATIONS INDUSTRY SOLUTIONS (ATIS)
ATIS ANSI O5.1 (2017) Wood Poles -- Specifications &
Dimensions
AMERICAN ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION OFFICIALS
(AASHTO)
AASHTO LTS (2013; Errata 2013) Standard
Specifications for Structural Supports for Highway Signs, Luminaires and Traffic Signals
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7-16 (2017; Errata 2018; Supp 1 2018) Minimum
Design Loads and Associated Criteria for Buildings and Other Structures
AMERICAN WOOD PROTECTION ASSOCIATION (AWPA)
AWPA U1 (2024) Use Category System: User
Specification for Treated Wood
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2024) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A153/A153M (2023) Standard Specification for Zinc
Coating (Hot-Dip) on Iron and Steel Hardware
ASTM B108/B108M (2019) Standard Specification for
Aluminum-Alloy Permanent Mold Castings
ASTM B117 (2019) Standard Practice for Operating Salt Spray (Fog) Apparatus
ASTM C1089 (2013) Standard Specification for Spun
Cast Prestressed Concrete Poles
HGM #741224 SECTION 26 56 00 Page 2
ASTM G154 (2023) Standard Practice for Operating Fluorescent Ultraviolet (UV) Lamp Apparatus for Exposure of Materials
CALIFORNIA ENERGY COMMISSION (CEC)
CEC Title 24 (2016) Building Energy Efficiency
Standards For Residential and Nonresidential Buildings
EUROPEAN UNION (EU)
Directive 2011/65/EU (2011) Restriction of the Use of Certain
Hazardous Substances in Electrical and Electronic Equipment
ILLUMINATING ENGINEERING SOCIETY (IES)
ANSI/IES LM-79 (2019) Approved Method: Electrical and
Photometric Measurements of Solid State Lighting Products
ANSI/IES LM-80 (2020) Approved Method: Measuring Luminous
Flux and Color Maintenance of LED Packages, Arrays and Modules
ANSI/IES LP-11 (2020) Lighting Practice: Environmental
Considerations for Outdoor Lighting
ANSI/IES LS-1 (2020) Lighting Science: Nomenclature and Definitions for Illuminating Engineering
ANSI/IES RP-8 (2018; Addenda 1 2020; Errata 1-2 2021)
Recommended Practice for Design and Maintenance of Roadway and Parking Facility Lighting
ANSI/IES TM-15 (2020) Technical Memorandum: Luminaire
Classification System for Outdoor Luminaires
ANSI/IES TM-21 (2021) Technical Memorandum: Projecting
Long-TermLuminous, Photon, and Radiant Flux Maintenance of LED Light Sources
IES Lighting Library IES Lighting Library
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 100 (2000; Archived) The Authoritative
Dictionary of IEEE Standards Terms
IEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
HGM #741224 SECTION 26 56 00 Page 3
ANSI C136.3 (2020) Roadway and Area Lighting Equipment
- Luminaire Attachments
ANSI C136.13 (2020) Roadway and Area Lighting Equipment
- Metal Brackets for Wood Poles
ANSI C136.21 (2014) American National Standard for Roadway and Area Lighting Equipment - Vertical Tenons Used with Post-Top-Mounted Luminaires
ANSI C136.41 (2013) Roadway and Area Lighting
Equipment-Dimming Control Between an External Locking Type Photocontrol and Ballast or Driver
NEMA 250 (2020) Enclosures for Electrical Equipment
(1000 Volts Maximum)
NEMA ANSLG C78.377 (2024) Electric Lamps— Specifications for the Chromaticity of Solid State Lighting Products
NEMA C82.77-10 (2020) Harmonic Emission Limits - Related
Power Quality Requirements
NEMA C136.10 (2023) American National Standard for Roadway and Area Lighting Equipment-Locking-Type Photocontrol Devices and Mating Receptacles--Physical and Electrical Interchangeability and Testing
NEMA C136.20 (2012; R 2021) Roadway and Area Lighting
Equipment - Fiber Reinforced Composite (FRC) Lighting Poles
NEMA C136.31 (2023) Roadway and Area Lighting Equipment
- Luminaire Vibration
NEMA ICS 2 (2000; R 2020) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 6 (1993; R 2016) Industrial Control and
Systems: Enclosures
NEMA IEC 60529 (2004) Degrees of Protection Provided by Enclosures (IP Code)
NEMA SSL 1 (2016) Electronic Drivers for LED Devices, Arrays, or Systems
NEMA SSL 3 (2011) High-Power White LED Binning for General Illumination
NEMA WD 7 (2011; R 2016; R 2021) Occupancy Motion
HGM #741224 SECTION 26 56 00 Page 4
Sensors Standard
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023; ERTA 1 2024; TIA 24-1) National Electrical Code
U.S. DEPARTMENT OF AGRICULTURE (USDA)
RUS Bull 1728F-700 (2011) Specification for Wood Poles, Stubs, and Anchor Logs
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
47 CFR 15 Radio Frequency Devices
UL SOLUTIONS (UL)
UL 773 (2016; Reprint Jul 2020) UL Standard for Safety Plug-In, Locking Type Photocontrols for Use with Area Lighting
UL 773A (2016; Reprint Jan 2024) UL Standard for
Safety Nonindustrial Photoelectric Switches for Lighting Control
UL 916 (2015; Reprint Oct 2021) UL Standard for
Safety Energy Management Equipment
UL 924 (2016; Reprint Dec 2022) UL Standard for Safety Emergency Lighting and Power Equipment
UL 1310 (2018; Reprint Jun 2022) UL Standard for
Safety Class 2 Power Units
UL 1598 (2021; Reprint Jan 2024) UL Standard for Safety Luminaires
UL 8750 (2020; Reprint Aug 2024) UL Standard for
Safety Light Emitting Diode (LED) Equipment for Use in Lighting Products
1.2 DEFINITIONS
a. Unless otherwise specified or indicated, electrical and electronics terms used in these specifications and on the drawings must be as defined in IEEE 100 and ANSI/IES LS-1.
b. For LED luminaire light sources, "Useful Life" is the operating hours before reaching 70 percent of the initial rated lumen output (L70) with no catastrophic failures under normal operating conditions. This is also known as 70 percent "Rated Lumen Maintenance Life" as defined in
ANSI/IES LM-80.
c. For LED luminaires, "Luminaire Efficacy" (LE) is the appropriate measure of energy efficiency, measured in lumens/watt. This is
HGM #741224 SECTION 26 56 00 Page 5 gathered from LM-79 data for the luminaire, in which absolute photometry is used to measure the lumen output of the luminaire as one entity, not the source separately and then the source and housing together.
d. Total Harmonic Distortion (THD) is the Root Mean Square (RMS) of all the harmonic components divided by the total fundamental current.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Luminaire Drawings; G, Pole Drawings; G, SD-03 Product Data
Luminaires; G
Light Sources; G
LED Drivers; G
Luminaire Warranty; G
Pole Warranty; G
Poles; G
SD-05 Design Data
Luminaire Design Data; G
Photometric Plan; G
SD-06 Test Reports
ANSI/IES LM-79 Test Report; G
ANSI/IES LM-80 Test Report; G
ANSI/IES TM-21 Test Report; G
SD-08 Manufacturer's Instructions
Poles
HGM #741224 SECTION 26 56 00 Page 6
1.4 QUALITY ASSURANCE
Data, drawings, and reports must employ the terminology, classifications and methods prescribed by the IES Lighting Library as applicable, for the lighting system specified.
1.4.1 Drawing Requirements
1.4.1.1 Luminaire Drawings
Include dimensions, effective projected area (EPA), weight, accessories, and installation and construction details. Photometric data, including CRI, CCT, TM-15-11 BUG rating, LED driver type,[ aiming diagram,] zonal lumen data, and candlepower distribution data per LM-79 must accompany shop drawings.
1.4.1.2 Pole Drawings
Include dimensions, wind load determined in accordance with ASCE 7-16, pole deflection, pole class, and other applicable information.
1.4.2 Luminaire Design Data
a. Provide distribution data according to IES classification type as defined in IES Lighting Library and ANSI/IES RP-8.
b. B.U.G. rating for the installed position as defined by ANSI/IES TM-15 and shielding as defined by ANSI/IES RP-8.
c. Provide safety certification and file number for the luminaire family.
Include listing, labeling and identification in accordance with NFPA 70 (NEC). Applicable testing bodies are determined by the US Occupational Safety Health Administration (OSHA) as Nationally Recognized Testing Laboratories (NRTL) and include: CSA (Canadian Standards Association), ETL (Edison Testing Laboratory), and UL (Underwriters Laboratories).
d. Provide long term lumen maintenance projections for each LED luminaire in accordance with ANSI/IES TM-21. Data used for projections must be obtained from testing in accordance with ANSI/IES LM-80.
e. Provide wind loading calculations for luminaires mounted on poles.
Weight and effective projected area (EPA) of luminaires and mounting brackets must not exceed maximum rating of pole as installed in particular wind zone area.
1.4.3 ANSI/IES LM-79 Test Report
Submit test report on manufacturer's standard production model of specified luminaire. Testing must be performed at the same operating drive current as specified luminaire. Include all applicable and required data as outlined under "14.0 Test Report" in ANSI/IES LM-79.
1.4.4 ANSI/IES LM-80 Test Report
Submit report on manufacturer's standard production LED light source (package, array, or module) of specified luminaire. Testing must be performed at the same operating drive current as specified luminaire.
HGM #741224 SECTION 26 56 00 Page 7
Include all applicable and required data as outlined under "8.0 Test Report" in ANSI/IES LM-80.
1.4.5 ANSI/IES TM-21 Test Report
Submit test report on manufacturer's standard production LED light source (package, array or module) of specified luminaire. Testing must be performed at the same operating drive current as specified luminaire.
Include all applicable and required data, as well as required interpolation information as outlined under "7.0 Report" in ANSI/IES TM-21.
1.4.6 Photometric Plan
For parking lots include computer-generated photometric analysis of the "designed to" values in accordance with ANSI/IES RP-8 andANSI/IES LP-11 for the "end of useful life" of the luminaire installation using a light loss factor of 0.81. Provide photometric plans that meet criteria in the Basis of Design in the project plans. Include the following in the submittal:
a. Horizontal illuminance measurements at finished grade, taken at a maximum grid size of 10 feet by 10 feet.
b. Vertical illuminance measurements at 5 feet above finished grade at all sidewalks and crosswalks, taken at a maximum of 10 feet.
c. Minimum and maximum footcandle levels.
d. Average maintained footcandle level.
e. Maximum to minimum ratio for horizontal illuminance only.
1.4.7 Test Laboratories
Test laboratories for the ANSI/IES LM-79 and ANSI/IES LM-80 test reports must be one of the following:
a. National Voluntary Laboratory Accreditation Program (NVLAP) accredited for solid-state lighting testing as part of the Energy-Efficient Lighting Products laboratory accreditation program.
b. One of the qualified labs listed on the Department of Energy - Energy
Efficiency & Renewable Energy, Solid-State Lighting web site.
c. One of the EPA-Recognized Laboratories listed at for LM-80 testing.
1.4.8 Regulatory Requirements
Equipment, materials, installation, and workmanship must be in accordance with the mandatory provisions of NFPA 70 unless more stringent requirements are specified or indicated. Provide luminaires and assembled components that are approved by and bear the label of UL for the applicable location and conditions unless otherwise specified.
1.4.9 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal
HGM #741224 SECTION 26 56 00 Page 8 material, design and workmanship. Products must have been in satisfactory commercial or industrial use for six months prior to bid opening. The six-month period must include applications of equipment and materials under similar circumstances and of similar size. The product must have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the six-month period. Where two or more items of the same class of equipment are required, these items must be products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
1.4.9.1 Alternative Qualifications
Products having less than a six-month field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.4.9.2 Material and Equipment Manufacturing Date
Do not use products manufactured more than six months prior to date of delivery to site, unless specified otherwise.
1.5 DELIVERY, STORAGE, AND HANDLING OF POLES
1.5.1 Steel Poles
Do not store poles on ground. Support poles so they are at least one foot above ground level and growing vegetation. Do not remove factory-applied pole wrappings until just before installing pole.
1.6 WARRANTY
Support all equipment items by service organizations which are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
1.6.1 Luminaire Warranty
Provide and transfer to the government the original LED luminaire manufacturers standard commercial warranty for each different luminaire manufacturer used in the project.
a. Provide a written five year minimum replacement warranty for material, luminaire finish, and workmanship. Provide written warranty document that contains all warranty processing information needed, including customer service point of contact, whether or not a return authorization number is required, return shipping information, and closest return location to the luminaire location.
(1) Finish warranty must include failure and substantial deterioration such as blistering, cracking, peeling, chalking, or fading.
(2) Material warranty must include:
(a) All LED drivers and integral control equipment.
HGM #741224 SECTION 26 56 00 Page 9
(b) Replacement when more than 15 percent of LED sources in any lightbar or subassembly(s) are defective, non-starting, or operating below 70 percent of specified lumen output.
b. Warranty period must begin in accordance with the manufacturer's standard warranty starting date.
c. Provide replacements that are promptly shipped, without charge, to the using Government facility point of contact and that are identical to or an improvement upon the original equipment. All replacements must include testing of new components and installation.
1.6.2 Pole Warranty
Provide and transfer to the government the original pole manufacturers standard commercial warranty for each different pole manufacturer used in the project. Warranty coverage must begin from date of final system commissioning or three months from date of delivery, whichever is the earliest. Provide a written one year minimum replacement warranty for material, luminaire finish, and workmanship. Warranty service must be performed by a factory-trained engineer or technician.
PART 2 PRODUCTS
2.1 PRODUCT COORDINATION
2.2 LUMINAIRES
UL 1598, NEMA C82.77-10. Provide luminaires as indicated in the luminaire schedule and XL plates or details on project plans, complete with light source, wattage, and lumen output indicated. All luminaires of the same type must be provided by the same manufacturer. Luminaires must be specifically designed for use with the LED driver and light source provided.
2.2.1 Luminaires
UL 8750, ANSI/IES LM-79, ANSI/IES LM-80. For all luminaires, provide:
a. Complete system with LED drivers and light sources.
b. Housing constructed of non-corrosive materials. All new aluminum housings must be anodized or powder-coated. All new steel housings must be treated to be corrosion resistant.
c. ANSI/IES TM-21, ANSI/IES LM-80. Minimum L70 lumen maintenance value of
50,000 hours unless otherwise indicated in the luminaire schedule.
Luminaire drive current value must be identical to that provided by test data for luminaire in question.
d. Product rated for operation within an ambient temperature range of minus 22 degrees F to 104 degrees F.
e. UL listed for wet locations.
f. IES Lighting Library. Light distribution and NEMA field angle classifications as indicated in luminaire schedule on project plans.
HGM #741224 SECTION 26 56 00 Page 10
g. Housing finish that is baked-on enamel, anodized, or baked-on powder coat paint. Finish must be capable of surviving ASTM B117 salt fog environment testing for 2500 hours minimum without blistering or peeling.
h. LED driver and light source package, array, or module are accessible for service or replacement without removal or destruction of luminaire.
i. ANSI/IES TM-15. Does not exceed the BUG ratings as listed in the luminaire schedule. If BUG ratings are not listed in the luminaire schedule, provide luminaires that meet the following minimum values for each application and mounting conditions:
Lighting Application Mounting Conditions BUG Rating
Area and Roadway All B3-U0-G3
Pedestrian Post-Top All B2-U1-G1
Exterior Wall Sconce Above 4 feet AFF B1-U0-G2
Exterior Wall Sconce Below or at 4 feet AFF B4-U0-G4
Steplight Above 4 feet AFF B1-U1-G2
Steplight Below or at 4 feet AFF B4-U1-G4
Parking Garage Luminaire Ceiling mounted B4-U4-G3
j. Fully assembled and electrically tested prior to shipment from factory.
k. Finish color is as indicated in the luminaire schedule or detail on the project plans.
l. Lenses constructed of clear tempered glass or UV-resistant acrylic.
m. All factory electrical connections are made using crimp, locking, or latching style connectors. Twist-style wire nuts are not acceptable.
n. NEMA C136.31. Comply with 3G vibration testing.
o. Luminaire arm bolts constructed from 304 stainless steel or zinc-plated steel.
p. Wiring compartment on pole-mounted, street and area luminaires is accessible without the use of hand tools to manipulate small screws, bolts, or hardware.
q. Incorporate modular electrical connections, and construct luminaires to allow replacement of all or any part of the optics, heat sinks, LED drivers, surge suppressors and other electrical components using only a simple tool, such as a manual or cordless electric screwdriver.
HGM #741224 SECTION 26 56 00 Page 11
r. ANSI C136.3. For all roadway and area luminaires, provide products with an integral tilt adjustment of plus or minus 5 degrees to allow the unit to be leveled.
2.3 LIGHT SOURCES
NEMA ANSLG C78.377, NEMA SSL 3. Provide type, lumen rating, and wattage as indicated in luminaire schedule on project plans.
2.3.1 LED Light Sources
Provide LED light sources that meet the following requirements:
a. NEMA ANSLG C78.377. Emit white light and have a nominal Correlated
Color Temperature (CCT) of 4000 Kelvin.
b. Minimum Color Rendering Index (CRI) of 70.
c. Directive 2011/65/EU. Restriction of Hazardous Substances (RoHS) compliant.
d. Light source color consistency by utilizing a binning tolerance within a 4-step McAdam ellipse.
2.4 LED DRIVERS
NEMA SSL 1, UL 1310. Provide LED Drivers that are electronic, UL Class 1 or Class 2, constant-current type and meet the following requirements:
a. The combined LED driver and LED light source system is greater than or equal to the minimum luminaire efficacy values as listed in the luminaire schedule provided.
b. Operate at a voltage of 120-277 volts at 50/60 hertz, with input voltage fluctuations of plus or minus 10 percent.
c. Power Factor (PF) greater than or equal to 0.90 at full input power and across specified dimming range.
d. Maximum Total Harmonic Distortion (THD) less than or equal to 20 percent at full input power and across specified dimming range.
e. Operates for at least 50,000 hours at maximum case temperature and 90 percent non-condensing relative humidity.
f. Meets the "Elevated" (10kV/10kA) requirements per IEEE C62.41.2 -2002.
Manufacturer must indicate whether failure of the electrical immunity system can possibly result in disconnect of power to luminaire.
Provide surge protection that is integral to the LED driver.
g. Contains integral thermal protection that reduces the output power to protect the driver and light source from damage if the case temperature approaches or exceeds the driver's maximum operating temperature.
h. Complies with the requirements of the Federal Communications Commission
(FCC) rules and regulations, Title 47 CFR part 15, Non-Consumer (Class A) for EMI/RFI (conducted and radiated).
HGM #741224 SECTION 26 56 00 Page 12
i. Directive 2011/65/EU. Restriction of Hazardous Substances (RoHS) compliant.
j. UL listed for wet locations typical of exterior installations.
k. Rated to operate between ambient temperatures of minus 22 degrees F and
104 degrees F.
2.5 POLES
Provide round straight poles designed for wind loading of 110 miles per hour while supporting luminaires and all other appurtenances indicated. The effective projected areas (EPA) of luminaires and appurtenances used in calculations must be specific for the actual products provided on each pole. Provide poles that are anchor-base type designed for use with underground supply conductors. Poles must have oval-shaped hand hole having a minimum clear opening of 3 by 5 inches. Secure hand hole covers by stainless steel captive screws. Provide metal poles with an internal grounding connection accessible from the hand hole near the bottom of each pole. Install a means of wire disconnection accessible from the hand hole. Do not install square poles. Provide poles from a Manufacturer with a standard provision for protecting the finish during shipment and installation. Do not install scratched, stained, chipped, or dented poles.
2.5.1 Steel Poles
Provide steel poles with hot-dipped galvanized in accordance with ASTM A123/A123M factory finish. Provide poles that meet the following requirements:
a. Minimum 11-gage steel with minimum yield/strength of 48,000 psi.
b. Pole is mounted by anchor bolts.
c. Consists of tapered tubular members, either round in cross section or polygonal.
d. Pole shaft is one piece and is of welded construction with no bolts, rivets, or other means of fastening except as specifically approved.
e. Base covers are of structural quality hot-rolled carbon steel plate, with a minimum yield of 36,000 psi.
f. Markings are approximately 3 to 4 feet above grade and includes manufacturer, year of manufacture, top and bottom diameters, and length.
g. Grounding connection is designed to prevent electrolysis when used with copper ground wire.
2.5.2 Brackets and Supports
ANSI C136.3, ANSI C136.13, and ANSI C136.21. Provide pole brackets that are not less than 1 1/4 inch galvanized steel pipe secured to pole.
Slip-fitter or pipe-threaded brackets may be used, but brackets must be coordinated to luminaires provided, and brackets for use with one type of luminaire must be identical. Brackets for pole-mounted street lights must correctly position luminaire no lower than mounting height indicated.
HGM #741224 SECTION 26 56 00 Page 13
Mount brackets not less than 24 feet above street. Provide special mountings or brackets as indicated and of metal which will not promote galvanic reaction with luminaire head.
2.5.3 Pole Foundations
Provide anchor bolts consisting of a steel rod with a minimum yield strength of 50,000 psi; the top 12 inches of the rod must be galvanized in accordance with ASTM A153/A153M. Concrete must be as specified in Section 03 30 00 CAST-IN-PLACE CONCRETE and Section 33 71 02 UNDERGROUND ELECTRICAL
DISTRIBUTION.
2.6 EQUIPMENT IDENTIFICATION
2.6.1 Manufacturer's Nameplate
Each item of equipment must have a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.
2.6.2 Labels
UL 1598. Luminaires must be clearly marked for operation of specific light sources and drivers according to proper light source type. Note the following luminaire characteristics in the format "Use Only ":
a. Correlated color temperature (CCT) and color rendering index (CRI) for all luminaires.
2.7 FACTORY APPLIED FINISH
NEMA 250. Provide all luminaires and lighting equipment with factory-applied painting system that as a minimum meets requirements of corrosion-resistance testing.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Luminaires
Install all luminaires in accordance with the luminaire manufacturer's written instructions. Install all luminaires at locations and heights as indicated on the project plans. Level all luminaires in accordance to manufacturer's written instructions.
3.1.2 LED Drivers
Provide LED drivers integral to luminaire as constructed by the manufacturer.
3.1.3 Aluminum and Steel Poles
Provide pole foundations with galvanized steel anchor bolts, threaded at the top end and bent 90 degrees at the bottom end. Provide ornamental covers to match pole and galvanized nuts and washers for anchor bolts.
HGM #741224 SECTION 26 56 00 Page 14
Concrete for anchor bases, polyvinyl chloride (PVC) conduit bells, and ground rods must be as specified in Section 03 30 00 CAST-IN-PLACE CONCRETE and Section 33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION. Thoroughly compact backfill with compacting arranged to prevent pressure between conductor, jacket, or sheath and the end of conduit ell. Adjust poles as necessary to provide a permanent vertical position with the bracket arm in proper position for luminaire location. Install according to pole manufacturer's instructions. Alterations to poles after fabrication will void manufacturer's warranty and is not allowed.
3.1.4 Pole Setting
Set pole to depth as indicated. Poles in straight runs must be in a straight line. Dig holes large enough to permit the proper use of tampers to the full depth of the hole. Place backfill in the hole in 6 inch maximum layers and thoroughly tamp. Place surplus earth around the pole in a conical shape and pack tightly to drain water away.
3.1.5 Grounding
Ground noncurrent-carrying parts of equipment including metal poles, luminaires, mounting arms, brackets, and metallic enclosures as specified in Section 33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION. Where copper grounding conductor is connected to a metal other than copper, provide specially treated or lined connectors suitable for this purpose.
3.2 FIELD QUALITY CONTROL
3.2.1 Tests
Upon completion of installation, verify that equipment is properly installed, connected, and adjusted. Perform initial operational test, consisting of the entire system energized for 72 consecutive hours without any failures of any kind occurring in the system. All circuits must test clear of faults, grounds, and open circuits.
3.2.1.1 Lighting Control Verification Test
Verify lighting control system and devices operate according to approved sequence of operations. Verification tests are to be completed after commissioning.
3.3 CLOSEOUT ACTIVITIES
3.3.1 Training
Provide on-site training to the Owner's personnel in the operation and maintenance of lighting and lighting control system. Provide training that includes calibration, adjustment, troubleshooting, maintenance, repair, and replacement.
3.3.1.1 Maintenance Staff Training
Submit a Maintenance Staff Training Plan at least 30 calendar days prior to training session that describes training procedures for Owner's personnel in the operation and maintenance of lighting and lighting control system. Provide on-site training which demonstrate full system
HGM #741224 SECTION 26 56 00 Page 15 functionality, assigning schedules, calibration adjustments for light levels and sensor sensitivity, integration procedures for connecting to third-party devices, and manual override including information on appropriate use. Provide protocols for troubleshooting, maintenance, repair, and replacement, and literature on available system updates and process for implementing updates.
3.3.1.2 End-User Training
Submit a End-User Training Plan at least 30 calendar days prior to training session that describes training procedures for end-users on the lighting control system. Provide demonstration for each type of user interface.
Provide users with the curfew schedule as currently commissioned, including conditional programming based on astronomic time clock functionality.
Provide users with the correct contact information for maintenance personnel who will be available to address any lighting control issues.
HGM #741224 SECTION 31 00 00 Page 1
SECTION 31 00 00
EARTHWORK
08/23
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM C117 (2023) Standard Test Method for Materials Finer than 75-um (No. 200) Sieve in Mineral Aggregates by Washing
ASTM C136/C136M (2019) Standard Test Method for Sieve Analysis of Fine and Coarse Aggregates
ASTM D1140 (2017) Standard Test Methods for Determining the Amount of Material Finer than 75-µm (No. 200) Sieve in Soils by Washing
ASTM D1557 (2012; E 2015) Standard Test Methods for Laboratory Compaction Characteristics of Soil Using Modified Effort (56,000 ft-lbf/ft3) (2700 kN-m/m3)
ASTM D2216 (2019) Standard Test Methods for Laboratory Determination of Water (Moisture) Content of Soil and Rock by Mass
ASTM D2487 (2017; E 2020) Standard Practice for Classification of Soils for Engineering Purposes (Unified Soil Classification System)
ASTM D4253 (2016; E 2019) Standard Test Methods for Maximum Index Density and Unit Weight of Soils Using a Vibratory Table
ASTM D4254 (2016) Standard Test Methods for Minimum Index Density and Unit Weight of Soils and Calculation of Relative Density
ASTM D4318 (2017; E 2018) Standard Test Methods for Liquid Limit, Plastic Limit, and Plasticity Index of Soils
ASTM D4829 (2021) Standard Test Method for Expansion Index of Soils
ASTM D5268 (2019) Topsoil Used for Landscaping Purposes
U.S. ARMY CORPS OF ENGINEERS (USACE)
EM 385-1-1 (2024) Safety -- Safety and Occupational Health (SOH) Requirements
HGM #741224 SECTION 31 00 00 Page 2
1.2 DEFINITIONS
1.2.1 Structural Fill
Soil material placed to support buildings, walls, pads, and other similar facilities.
1.2.2 Embankment Fill
Soil material placed to construct embankment.
1.2.3 Porous Fill
Free-draining material placed for subsurface drainage, as a capillary break, or another specific purpose.
1.2.4 Topsoil
Surface layer of primarily organic soil capable of supporting vegetation growth.
1.2.5 Utility Bedding Material
Fill placed to directly support pipes, conduits, cables, and appurtenant structures. Bedding may also be used to provide a cushion between utilities and bedrock, obstacles, obstructions and other unyielding materials.
1.2.6 Satisfactory Materials
Satisfactory materials for fill, backfill, and/or any in-situ soils to remain in place comprise any materials classified by ASTM D2487 as CL.
Maximum particle size to be no greater than 3 inches in any dimension.
On-site materials are suitable for use as fill if free of debris and particles greater than 3 inches.
1.2.7 Unsatisfactory Materials
Materials which do not comply with the requirements for satisfactory materials are unsatisfactory. Unsatisfactory materials also include man-made fills; trash; refuse; backfills from previous construction; roots and other organic matter or frozen material. Notify the Contracting Officer when encountering any contaminated materials.
1.2.8 Cohesionless Materials
Cohesionless materials include materials classified in ASTM D2487 as GW, GP, SW, and SP. Materials classified as GM and SM will be identified as cohesionless only when the fines are non-plastic. Perform testing, required for classifying materials, in accordance with ASTM D4318, ASTM C117, ASTM C136/C136M and ASTM D1140.
1.2.9 Cohesive Materials
Cohesive materials include materials classified as GC, SC, ML, CL, MH, and CH. Materials classified as GM and SM will be identified as cohesive only when the fines are plastic. Perform testing, required for classifying materials, in accordance with ASTM D4318, ASTM C117, ASTM C136/C136M and
ASTM D1140.
1.2.10 Hard/Unyielding Materials
Hard/Unyielding materials comprise weathered rock, dense consolidated deposits, or conglomerate materials which are not included in the definition of "rock" with stones greater than 3 inches in any dimension or as defined by the pipe manufacturer, whichever is smaller. These
HGM #741224 SECTION 31 00 00 Page 3 materials usually require the use of heavy excavation equipment, ripper teeth, or jack hammers for removal.
1.2.11 Unstable Material
Unstable materials are too weak to adequately support the utility pipe, conduit, equipment, or appurtenant structure. Satisfactory material may become unstable due to ineffective drainage, dewatering, becoming frozen, excessive loading.
1.2.12 Expansive Soils
Expansive soils are defined as soils that have an expansion index greater than 20 when tested in accordance with ASTM D4829.
1.2.13 Rock
Solid homogeneous interlocking crystalline material with firmly cemented, laminated, or foliated masses or conglomerate deposits, neither of which can be removed without systematic drilling and blasting, drilling and the use of expansion jacks or feather wedges, or the use of backhoe-mounted pneumatic hole punchers or rock breakers; also, large boulders, buried masonry, or concrete other than pavement exceeding 1/2 cubic yard in volume. Removal of hard material will not be considered rock excavation because of intermittent drilling and blasting that is performed merely to increase production.
1.2.14 Capillary Water Barrier
A layer of clean, poorly graded crushed rock, stone, or natural sand or gravel having a high porosity which is placed beneath a building slab with or without a vapor barrier to cut off the capillary flow of pore water to the area immediately below a slab.
1.2.15 Degree of Compaction (Proctor)
Degree of compaction required, except as noted in the second sentence, is expressed as a percentage of the maximum density obtained by the test procedure presented in ASTM D1557 abbreviated as a percent of laboratory maximum density. Since ASTM D1557 applies only to soils that have 30 percent or less by weight of their particles retained on the 3/4-inch sieve, express the degree of compaction for material having more than 30 percent by weight of their particles retained on the 3/4-inch sieve as a percentage of the maximum density in accordance with ASTM D1557, Method C.
1.2.16 Degree of Compaction (Relative Density)
Degree of compaction required for soils with less than 5 percent passing the No. 200 sieve, is expressed as a relative percentage of the maximum index density/dry unit weight and minimum index density/dry unit weight, obtained by the test procedures in accordance with ASTM D4253 and ASTM D4254, respectively, abbreviated as a percent of laboratory relative density.
1.2.17 Borrow
Soil brought to the project site from an external location for the purposes of project construction.
1.2.18 Subgrade
Earth materials directly below foundations and directly below granular base materials in building slab and pavement areas including shoulders.
HGM #741224 SECTION 31 00 00 Page 4
1.3 SUBSURFACE DATA
Subsurface soil boring logs are shown in an Attachment to these specifications. This data represent available subsurface information;
however, variations may exist between boring locations.
1.4 CRITERIA FOR BIDDING
Base bids on the following criteria:
a. Surface elevations are as indicated.
e. Material character is indicated by the boring logs.
1.5 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-01 Preconstruction Submittals
Disposition of Surplus Materials; G
Preconstruction Meeting; G
SD-06 Test Reports
Material Test Report; G
1.6 QUALITY CONTROL
1.6.1 Qualified Technician
Provide a Qualified Technician to inspect, monitor, sample, and performing field testing. The technician qualifications need to be one of the following: a current National Institute for Certification in Engineering Technologies (NICET) Level II minimum certification in Construction Materials Testing Soils; a Geologist-in-Training with minimum one-year experience; an Engineer-in-Training with minimum one-year experience; a Registered Geologist; or a Professional Engineer.
1.6.2 Lab Validation
Perform testing by a Corps validated commercial testing laboratory or
Contractor established testing laboratory meeting the requirements of Section 01 45 00 (or similar number) entitled QUALITY CONTROL and approved by the Contracting Officer. Submit testing laboratory validation for the testing to be performed. Do not permit work requiring testing until testing facilities have been inspected, Corps validated and approved by the Contracting Officer.
1.6.3 Preconstruction Meeting
Conduct a preconstruction meeting at the jobsite at least five business days prior to the start of earthwork operations on the project. The preconstruction meeting is to be arranged by the Contractor and is to follow the written agenda submitted prior to the meeting. The purpose of this meeting is to review the requirements of this specification and the associated plans.