23b1 Attachment 2 Drawings.pdf
PDF 45 MB Posted
- Attached to
- Install HF Antennas, Test Sites Federal contract opportunity
- Solicitation number
- FA875123B00010001
About this file
This file is an attachment to a federal solicitation for the installation of high frequency antennas and testing at sites for the Department of the Air Force Materiel Command Research Laboratory. The solicitation number is FA875123B00010001 and seeks offers for installing HF antennas and conducting tests at unspecified sites on behalf of the Air Force Materiel Command Research Laboratory. The attachment contains drawings related to the required installation and testing work but does not provide any other salient details regarding response dates, pricing, place of performance, or incumbent.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 23B0001 Q and A.docx | DOCX document | |
| 23b1 Attachment 1 Specifications.pdf | ||
| Solicitation Amendment - FA875123B00010001.pdf | ||
| 23b1 Attachment 3 AFRL Supplemental Requirements.pdf | ||
| 23b1 Attachment 4 Wage Decision.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROPOSED HF
TOWER
DRAWING SUFFIX DESIGNATION FACILITY NAME
• AE000-S STOCKBRIDGE
• AE000-T TANNER HILL
• AE000-I IRISH HILL
EXISTING
BUILDING B1628
DEMO EXISTING
BUILDING S1640
EXISTING
BUILDING B1624
EXISTING
BUILDING B1612
PROPOSED
WALK-UP TOWER
EXISTING
BUILDING B1621
EXISTING
BUILDING B1607
BUILDING 1609
(UNDER CONSTRUCTION)
DEMO EXISTING
BUILDING B1605
(BID ALTERNATE)
OLD BUILDING 1609
(TO BE DEMOLISHED UNDER
SEPARATE CONTRACT)
PROPOSED HF
TOWER
PROJECT NO. RTVW180301AE A/E CONTRACT NO. GS-07-P-16-UC-D-7008
STOCKBRIDGE SITE MAP
NKB
N. .______________________________________________________
ARCHITECTURE & ENGINEERING, PC..
K BHANDARI
SHEET SIZE: 24" x 36"
DESIGN FIRM:
FO
R A
P
PR
O V A L
NYS Education Law, Section 7209 Prohibits any person to alter these drawings other than a licensed architect or the design engineer. Information on these drawings remainsthe property of the licensed professionals who prepared them and may only be used on the project identified below.
Copyright 2021 N.K. BHANDARI, Architecture & Engineering, P.C.
DRAWING NO: SHEET: FACILITY NAME:
OF
SHEET TITLE:
PROJECT TITLE:
Rev. Date Description Drawn Approved
DATE:
PROJECT MANAGER:
PROJECT NO:
DRAFTER:
Rome Research Site
Air Force Research Laboratory
Information Directorate Rome, New York
RIO:
RIOCC:
RIOS:
66abw/def:
RIOC:
RIOCO:
RIOF:
USER:
RIOCC:
RIOCV:
DET 4/SE:
USER:DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DESIGNER:
CONSULTANT:
10/28/2021 10:10:44 AM
1 -G-001 10/29/2021
COVER SHEET
INSTALL HF ANTENNAS,
TEST SITES
RTVW180301AE
KRS
KRS
DBH
ARCHITECT, SITE/ CIVIL ENGINEER, &
STRUCTURAL ENGINEER:
N.K. BHANDARI,
ARCHITECTURE & ENGINEERING, P.C.
1005 W. FAYETTE STREET, SUITE 500
SYRACUSE, NEW YORK 13204
315.428.1177
SENSITIVE BUT UNCLASSIFIED (SBU) PROPERTY OF THE UNITED STATES
GOVERNMENT COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS
DOCUMENT TO UNAUTHORIZED RECIPIENTS IS PROHIBITED Do not remove this notice. Properly destroy or return documents when no longer needed.
PROJECT CERTIFICATION:
TO THE BEST OF MY KNOWLEDGE, BELIEF AND PROFESSIONAL JUDGMENT,
THE DRAWINGS AND SPECIFICATIONS WHICH COMPRISE THE
CONSTRUCTION DOCUMENTS FOR THE PROJECT ARE IN COMPLIANCE WITH
APPLICABLE CODES, INCLUDING THE LATEST EDITIONS OF THE
INTERNATIONAL BUILDING CODE AND NFPA 101.
MECHANICAL, ELECTRICAL, PLUMBING, & FIRE
PROTECTION ENGINEER:
C&S COMPANIES
499 COL. EILEEN COLLINS BLVD.
SYRACUSE, NEW YORK 13212
315.445.2000
HAZARDOUS MATERIALS:
COLDEN CORPORATION
5842 HERITAGE LANDING DRIVE
EAST SYRACUSE, NEW YORK 13057
315.445.0847
FACILITY IDENTIFICATION KEY
AIR FORCE RESEARCH LABORATORY
INFORMATION DIRECTORATE
ROME, NEW YORK 13441
INSTALL HF ANTENNAS, TEST SITES
IRISH HILL SITE MAP TANNER HILL SITE MAP DRAWING LIST
(BID ALTERNATE)
THE CONTRACTOR MUST VERIFY THE BUILDING
NUMBERS WITH AFRL.
1272.13
1272.63
1272.44
1272.20
1272.33
1272.25
1272.76
1273.00
1273.16
1272.72
1273.56
1273.23
1273.04
1273.15
1272.87
1272.93
1273.79
1273.87
1274.39
1274.32
1273.98
1274.29
1274.32
1274.68
1275.23
1275.91
1275.58
1275.35
1275.11
1275.23
1275.09
1275.07
1275.13
1275.52
1274.88
1275.60
1276.77
1275.43
1274.90
1273.87
1275.31
1273.48
1272.92
1272.77
1272.79
1273.07
1272.86
1272.22
1271.86
1271.56
1273.55
1272.49
1272.30
1272.06
1272.20
1272.66
1272.01
1271.82
1271.40
1271.53
1272.10
1272.89
1272.61
1272.22
1272.24
1272.20
1272.67
1272.89
1273.08
1271.19
1272.02
1271.78
1271.33
1271.02
1271.29
1271.08
1271.60
1271.72
1271.76 1271.56
1271.86
1271.76
1271.84
1272.28
1273.02
1272.60
1272.04
1271.87
1272.12
1272.01
1272.15
1272.39
1271.48
1270.96
1271.31
1270.84
1270.78
1271.21
1270.64
1270.27
1270.99
1269.60
1269.45
1269.73
1270.78
1269.46
1270.15
1270.83
1271.24
1271.80
1271.75
1271.78
1272.23
1272.15
1271.51
1271.97
1271.31
1271.35
1271.59
1271.21
1270.53
1269.56
1269.27
1269.80
1268.93
1269.14
1268.43
1268.08
1267.33
1267.28
1268.51
1269.30
1268.40
1269.65
1270.52
1271.30
1271.08
1269.93
1270.49
1270.69
1270.91
1271.79
1271.52
1271.27
1270.45
1268.81
1269.68
1270.50
1268.87
1267.94
1269.51
1269.05
1268.16
1267.89
1268.59
1267.78
1266.69
1267.14
1267.22
1266.03
1266.89
1267.75
1267.81
1267.44
1267.70
1268.15
1268.21
1268.48
1268.71
1268.68
1268.27
1267.21
1266.55
1264.40
1264.75
1266.35
1266.71
1266.90
1266.54
1266.17
1266.17
1266.25
1265.84
1266.04
1265.67
1265.02
1264.66
1264.39
1264.74
1265.34
1265.50
1264.37
1263.52
1262.37
1259.39
1260.48
1260.37
1259.11
1260.15
1260.70
1262.00
1263.56
1263.70
1263.78
1263.60
1260.34
1260.22
1259.77
1260.14
1259.01
1258.95
1258.66
1258.86
1259.01
1260.85
1260.91
1260.86
1262.19
1262.72
1262.08
1262.16
1262.58
1263.29
1263.82
1262.57
1261.82
1259.40
1258.24
1259.35
1258.51
1258.51
1258.74
1258.68
1259.57
1257.31
1256.39
1259.68
1259.29
1255.90
1255.96
1256.19
1256.06
1256.75
1258.40
1257.62
1261.43
1259.66
1258.10
1257.71
1260.03
1264.88
1267.74
1271.87
1272.58
1271.69
1269.85
1275.95
1277.22
1274.71
1275.25
1275.71
WOODS
WOODS
WOODS
WOODS
WOODS
WOODS
WOODS
METAL VAULT
PAVEMENT
ED
G
E M O
W
ED
A R
EA
E
D
G
E
M
O
W
D
A
R
E
A
MOWED GRASS
MOWED GRASS
G
R
A
V
E
L
R
O
A
D
G R A V E L
R O
A D
4"x4" WOOD POST
BRUSH / ROCK PILE
BRUSH / ROCK PILE
4.5' HIGH IRON PIPE
GUYED
TOWER
CONC. GUY PAD
CONC. GUY PAD
CONC. GUY PAD
ABANDONED
UTILITY
POLE
CONC. PAD
CONTROL PONT 1
MAGNETIC NAIL
N: 1106191.43
E: 1069063.55
ELEV=1271.30
CP 1
CONTROL PONT 2
MAGNETIC NAIL
N: 105858.21
E: 1069352.61
ELEV=1273.53
CP 2
BAR SCALE
1 inch = ft.
30 0 15 30 60
N: 1106300.0000
E: 1069300.0000
N: 1106000.0000
E: 1069300.0000
N: 1106000.0000
E: 1068550.0000
N: 1106300.0000
E: 1068550.0000
LANDS OF THE UNITED STATES OF AMERICA
(REPUTED OWNER)
TAX MAP PARCEL 54.-2-1
c
PROJECT NUMBER:
DATE REVISIONS RECORD/DESCRIPTION
PROJ. NO
CHECKED
DRAFTED
C.T. MALE ASSOCIATES
SCALE :
CHECKDRAFTER APPR.
OFSHEET
DWG. NO:
UNAUTHORIZED ALTERATION OR
ADDITION TO THIS DOCUMENT IS A
VIOLATION OF THE NEW YORK STATE
EDUCATION LAW.
DATE :
C.T. MALE ASSOCIATES
Engineering, Surveying, Architecture, Landscape Architecture & Geology, D.P.C.
50 CENTURY HILL DRIVE, LATHAM, NY 518.786.7400
www.ctmale.com
COBLESKILL, NY · GLENS FALLS, NY · POUGHKEEPSIE, NY · JOHNSTOWN, NY
LITTLE FALLS, NY · RED HOOK, NY · SYRACUSE, NY
20.0640
TOWN OF STOCKBRIDGE
MADISON COUNTY, NEW YORK
20.0640
10/29/20
20-0549
XREFS:
C
W G
F I L E
N
A M
E
C
W G
F I L E
N
A M
E
APPROVED
"ONLY COPIES OF THIS MAP SIGNED IN RED INK AND EMBOSSED WITH
THE SEAL OF AN OFFICER OF C.T. MALE ASSOCIATES OR A
DESIGNATED REPRESENTATIVE SHALL BE CONSIDERED TO BE A VALID
TRUE COPY".
DAVID J. UHRINEC, PLS
P.L.S. NO. 050052
C U s e r s D
J U
D e s k t o p
N
K B
R o m e
A F R L
S u r v e y s R o m e
A F R L
S u r v e y
S t o c k b r i d g e d w g
R o m e
A F R L
S u r v e y
S t o c k b r i d g e d dju
1"=30'
NONE
TOPOGRAPHIC SURVEY
A PORTION OF
ROME AIR FORCE RESEARCH LAB
STOCKBRIDGE SITE
5251 BURLESON ROAD ONEIDA, NEW YORK
THE CONTRACTOR MUST VERIFY THE BUILDING
NUMBERS WITH AFRL.
1271.33
1271.29
1271.60
1271.76
WOODS
METAL VAULT
PAVEMENT
EDGE MOWED AREA
EDGE MOWED AREA
MOWED GRASS
MOWED GRASS
G R A V
EL R
O A D
G R A V
EL R
O A D
4"x4" WOOD POST
BRUSH / ROCK PILE
CP 1
LANDS OF THE UNITED STATES OF AMERICA
(REPUTED OWNER)
TAX MAP PARCEL 54.-2-1
50'24
125' MAX SILT
FENCE SPACING
SILT FENCE TO BE INSTALLED UPON
COMPLETION OF ROUGH GRADING AND
TO REMAIN IN PLACE UNTIL FINAL
STABILIZATION IS ACHIEVED
SILT FENCE TO BE INSTALLED PRIOR
TO ROUGH GRADING. INSTALL
PARALLEL TO EXISTING CONTOUR.
CONTROL POINT 1
MAGNETIC NAIL
N: 1106191.43 E: 1069063.55
ELEV=1271.30
CONTRACTOR TO PROTECT CONTROL POINT
FROM DISTURBANCE FOR USE DURING
LAYOUT OF TOWER ANCHOR POINTS.
00 30' 60'
(IN FEET)
1 inch = 30 ft
GRAPHIC SCALE
LEGEND
EXISTING MAJOR CONTOUR
EXISTING MINOR CONTOUR
PROPOSED CONTOUR GRADES
3C100-S
STOCKBRIDGE
SITE PREPARATION &
EROSION CONTROL PLAN RTVW180301AE
RCI
RCI
DEMOLITION/SITE PREPARATION PLAN
KEYED NOTES:
1 REMOVE PAVEMENT SECTION INCLUDING GRAVEL SUBBASE;
RESTORE WITH FILL TO PROPOSED GRADE, SEED, AND MULCH
2 GRADING LIMIT
LIMIT OF DISTURBANCE
3 STABILIZED CONSTRUCTION ENTRANCE
STABILIZED CONSTRUCTION ENTRANCE/EXIT
SILT FENCE
SHEET SIZE: 24" x 36"
DESIGN FIRM:
NYS Education Law, Section 7209 Prohibits any person to alter these drawings other than a licensed architect or the design engineer. Information on these drawings remains the property of the licensed professionals who prepared them and may only be used on the project identified below.
Copyright 2021 N.K. BHANDARI, Architecture & Engineering, P.C.
DRAWING NO: SHEET: FACILITY NAME:
OF
SHEET TITLE:
PROJECT TITLE:
Rev. Date Description Drawn Approved
DATE:
STOCKBRIDGE
PROJECT MANAGER:
PROJECT NO:
DRAFTER:
Rome Research Site
Air Force Research Laboratory Information Directorate
Rome, New York
RIO:
RIOCC:
RIOS:
66abw/def:
RIOC:
RIOCO:
RIOF:
USER:
RIOCC:
RIOCV:
DET 4/SE:
USER:DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DESIGNER:
CONSULTANT:
NKBN. .______________________________________________________
ARCHITECTURE & ENGINEERING, P C..
KBHANDARI
N A P I E R A L A C O N S U L T I N G
PROFESSIONAL ENGINEER, P.C.
SITE DESIGN ENGINEERING
5/7/2021 1:10:17 PM
17 10/29/2021
RTVW180301AE
DBH
INSTALL HF ANTENNAS,
TEST SITES
4 TREE CLEARING; REFER TO EY100-S FOR LOCATION OF NEW
CONDUIT ALIGNMENT
5 REMOVE BRUSH/ROCK PILE
METAL VAULT
4"x4" WOOD POST
CP 1
CP 2
LANDS OF THE UNITED STATES OF AMERICA
(REPUTED OWNER)
TAX MAP PARCEL 54.-2-1
30'
R80'
6'
TOWER PIER
N:1106102.69 E:1069010.88
ERECTION ANCHOR
N:1106093.33 E:1069030.23
ANCHOR A
N:1106182.84 E:1068983.01
ANCHOR B
N:1106170.37 E:1068987.34
ANCHOR B
N:1106126.23 E:1069078.56
ANCHOR A
N:1106130.56 E:1069091.02
ANCHOR B
N:1106022.55 E:1069038.75
ANCHOR A
N:1106035.01 E:1069034.41
ANCHOR B
N:1106074.82
E:1068930.73 ANCHOR A
N:1106079.15
E:1068943.20 WINCH PIER
N:1106050.42 E:1069118.89
R1
21'-6"
120'-0"
50'-8"
60'-0"
0'
-0
1'
-4
EXISTING COMMUNICATIONS HANDHOLE
EXISTING PRIMARY
FEEDER HANDHOLE
CONTROL POINT 1
MAGNETIC NAIL
N: 1106191.43 E: 1069063.55
ELEV=1271.30
CONTROL POINT 2
MAGNETIC NAIL
N: 105858.21 E: 1069352.61
ELEV=1273.53
' 247'
00 30' 60'
(IN FEET)
1 inch = 30 ft
GRAPHIC SCALE
LAYOUT PLAN KEYED NOTES:
1 80-FT RADIUS GRADED GROUND PLANE, SEE GRADING PLAN;
RESTORE WITH TOPSOIL, SEED, AND MULCH
2 8-FT HIGH CHAINLINK SECURITY FENCE;
SEE DETAIL 1, SHEET C500-S
3 8-FT HIGH CHAINLINK SECURITY GATE;
SEE DETAIL 2, SHEET C500-S
6 GRAVEL ACCESS ROAD; SEE DETAIL 3, SHEET C501-S
4 CONCRETE PAD FOR UTILITIES (SEE DETAIL 1, SHEET C501-S); SEE
ELECTRICAL SITE PLAN FOR LOCATIONS OF ELECTRICAL CONDUIT
5 GRAVEL PAD; SEE DETAIL 2, SHEET C501-S
COORDINATES ARE BASED ON THE CENTRAL ZONE OF
THE NEW YORK STATE PLANE COORDINATE SYSTEM
4C200-S
STOCKBRIDGE
SITE PLAN
RTVW180301AE
RCI
RCI
SHEET SIZE: 24" x 36"
DESIGN FIRM:
NYS Education Law, Section 7209 Prohibits any person to alter these drawings other than a licensed architect or the design engineer. Information on these drawings remains the property of the licensed professionals who prepared them and may only be used on the project identified below.
Copyright 2021 N.K. BHANDARI, Architecture & Engineering, P.C.
DRAWING NO: SHEET: FACILITY NAME:
OF
SHEET TITLE:
PROJECT TITLE:
Rev. Date Description Drawn Approved
DATE:
STOCKBRIDGE
PROJECT MANAGER:
PROJECT NO:
DRAFTER:
Rome Research Site
Air Force Research Laboratory Information Directorate
Rome, New York
RIO:
RIOCC:
RIOS:
66abw/def:
RIOC:
RIOCO:
RIOF:
USER:
RIOCC:
RIOCV:
DET 4/SE:
USER:DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DESIGNER:
CONSULTANT:
NKBN. .______________________________________________________
ARCHITECTURE & ENGINEERING, P C..
KBHANDARI
N A P I E R A L A C O N S U L T I N G
PROFESSIONAL ENGINEER, P.C.
SITE DESIGN ENGINEERING
17 10/29/2021
RTVW180301AE
DBH
INSTALL HF ANTENNAS,
TEST SITES
7 TRENCH EXCAVATION FOR ELECTRICAL CONDUIT. SEE E100-S.
8 TRENCH EXCAVATION FOR COMMUNICATIONS CONDUIT. SEE EY100-S.
NEW CHAINLINK SECURITY FENCE
NEW UNDERGROUND COMMUNICATIONS TRENCH
NEW UNDERGROUND ELECTRIC TRENCH
LEGEND
CP 1
LANDS OF THE UNITED STATES OF AMERICA
(REPUTED OWNER)
TAX MAP PARCEL 54.-2-1
1272.4
MEE
1269.8
1269.6
1272.7
1272.8
1269.4
1271.2
1269.8
1269.4
1269.2
1270.2
1270.4 1270.6
1270.8
1271.5
1271.4 1271.6 1271.8
1272.8
1271.8
1271.6
1271.4
1271.2
1272.8
1272.9
1272.2
MEE
1272.1
1273.2
1272.8
1272.6
1272.4
1272.2
MEE
MEE
MEEMEE
MEE
MEE
MEE
MEE
MEE
MEE
MEE
MEE
MEE
MEE
MEE
1271.6
MEE
1271.6
1271.4
MEE
1271.6
MEE
1271.61271.6
80' RADIUS GRADED GROUND PLANE
CENTER OF GROUND PLANE
ELEV=1271.20
CONTROL POINT 1
MAGNETIC NAIL
N: 1106191.43 E: 1069063.55
ELEV=1271.30
MEE
00 20' 40'
(IN FEET)
1 inch = 20 ft
GRAPHIC SCALE
GRADING PLAN LEGEND
EXISTING MAJOR CONTOUR
EXISTING MINOR CONTOUR
PROPOSED CONTOUR GRADES
PROPOSED FINISHED SPOT ELEVATION
MATCH/MEET EXISTING ELEVATION
MEE
459.8
5C300-S
STOCKBRIDGE
GRADING PLAN
RTVW180301AE
RCI
RCI
SHEET SIZE: 24" x 36"
DESIGN FIRM:
NYS Education Law, Section 7209 Prohibits any person to alter these drawings other than a licensed architect or the design engineer. Information on these drawings remains the property of the licensed professionals who prepared them and may only be used on the project identified below.
Copyright 2021 N.K. BHANDARI, Architecture & Engineering, P.C.
DRAWING NO: SHEET: FACILITY NAME:
OF
SHEET TITLE:
PROJECT TITLE:
Rev. Date Description Drawn Approved
DATE:
STOCKBRIDGE
PROJECT MANAGER:
PROJECT NO:
DRAFTER:
Rome Research Site
Air Force Research Laboratory Information Directorate
Rome, New York
RIO:
RIOCC:
RIOS:
66abw/def:
RIOC:
RIOCO:
RIOF:
USER:
RIOCC:
RIOCV:
DET 4/SE:
USER:DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DESIGNER:
CONSULTANT:
NKBN. .______________________________________________________
ARCHITECTURE & ENGINEERING, P C..
KBHANDARI
N A P I E R A L A C O N S U L T I N G
PROFESSIONAL ENGINEER, P.C.
SITE DESIGN ENGINEERING
17 10/29/2021
RTVW180301AE
DBH
INSTALL HF ANTENNAS,
TEST SITES
CP 1
LANDS OF THE UNITED STATES OF AMERICA
0+
1+
2+
3+
3+
0+
1+
2+
0+00 0+50 1+00 1+50 2+00 2+50 3+00 3+36
0+00 0+50 1+00 1+50 2+00 2+50 3+00 3+36
PROPOSED GRADE=1.75%
80'R GROUND PLANE
FENCE LINE
PROPOSED GRADE
EXISTING GRADECENTER OF GROUND PLANE
00 20' 40'
(IN FEET)
1 inch = 20 ft
GRAPHIC SCALE
SCALE:
PLAN VIEW: EAST-WEST CENTERLINE
1"=20'
C400-S
SCALE:
PROFILE VIEW: EAST-WEST CENTERLINE
VERT: 1"=4'; HORZ: 1"=20'
C400-S 6C400-S
STOCKBRIDGE
PLAN AND PROFILE
RTVW180301AE
RCI
RCI
SHEET SIZE: 24" x 36"
DESIGN FIRM:
NYS Education Law, Section 7209 Prohibits any person to alter these drawings other than a licensed architect or the design engineer. Information on these drawings remains the property of the licensed professionals who prepared them and may only be used on the project identified below.
Copyright 2021 N.K. BHANDARI, Architecture & Engineering, P.C.
DRAWING NO: SHEET: FACILITY NAME:
OF
SHEET TITLE:
PROJECT TITLE:
Rev. Date Description Drawn Approved
DATE:
STOCKBRIDGE
PROJECT MANAGER:
PROJECT NO:
DRAFTER:
Rome Research Site
Air Force Research Laboratory Information Directorate
Rome, New York
RIO:
RIOCC:
RIOS:
66abw/def:
RIOC:
RIOCO:
RIOF:
USER:
RIOCC:
RIOCV:
DET 4/SE:
USER:DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DESIGNER:
CONSULTANT:
NKBN. .______________________________________________________
ARCHITECTURE & ENGINEERING, P C..
KBHANDARI
N A P I E R A L A C O N S U L T I N G
PROFESSIONAL ENGINEER, P.C.
SITE DESIGN ENGINEERING
17 10/29/2021
RTVW180301AE
DBH
NOTE: NORTH ORIENTATION IS ROTATED TO ALIGN WITH PROFILE
1269.14
4"x4" W O
O D
PO
ST
4.5' H
IG
H
IRO
N
PIPE
CP 1
LAN
D
S O
F TH
E U N
ITED
STATES O
F AM
ERICA
(REPU
TED
O W
N
ER)
TAX M
AP PARCEL 54.-2-1
0+
1+
2+
2+
0+
1+
FENCE LINE
PROPOSED GRADE
EXISTING GRADE
0+00 0+50 1+00 1+50 2+00 2+25
0+00 0+50 1+00 1+50 2+00 2+25
80'R GROUND PLANE
00 20' 40'
(IN FEET)
1 inch = 20 ft
GRAPHIC SCALE
7C401-S
STOCKBRIDGE
PLAN AND PROFILE
RTVW180301AE
RCI
RCI
SHEET SIZE: 24" x 36"
DESIGN FIRM:
NYS Education Law, Section 7209 Prohibits any person to alter these drawings other than a licensed architect or the design engineer. Information on these drawings remains the property of the licensed professionals who prepared them and may only be used on the project identified below.
Copyright 2021 N.K. BHANDARI, Architecture & Engineering, P.C.
DRAWING NO: SHEET: FACILITY NAME:
OF
SHEET TITLE:
PROJECT TITLE:
Rev. Date Description Drawn Approved
DATE:
STOCKBRIDGE
PROJECT MANAGER:
PROJECT NO:
DRAFTER:
Rome Research Site
Air Force Research Laboratory Information Directorate
Rome, New York
RIO:
RIOCC:
RIOS:
66abw/def:
RIOC:
RIOCO:
RIOF:
USER:
RIOCC:
RIOCV:
DET 4/SE:
USER:DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DESIGNER:
CONSULTANT:
NKBN. .______________________________________________________
ARCHITECTURE & ENGINEERING, P C..
KBHANDARI
N A P I E R A L A C O N S U L T I N G
PROFESSIONAL ENGINEER, P.C.
SITE DESIGN ENGINEERING
17 10/29/2021
RTVW180301AE
DBH
SCALE:
PLAN VIEW: NORTH-SOUTH CENTERLINE
1"=20'
C400-S
SCALE:
PROFILE VIEW: NORTH-SOUTH CENTERLINE
VERT: 1"=4'; HORZ: 1"=20'
C400-S
NOTE: NORTH ORIENTATION IS ROTATED TO ALIGN WITH PROFILE
SCALE:
BRACE PANEL DETAIL
NTS
C500-S
BARBED-WIRE APRON ON
EXTENSION ARMSTOP RAIL
1'-0"
TIE WIRES OR
HOG RINGS (TYP.)
CORNER, END,
OR PULL POST
BRACE RAIL
TIE WIRES OR
CLIPS (TYP.)
LINE POST
CHAIN-LINK FABRIC
(9 GAGE, 2" MESH)
FABRIC WIDTH
(96")
LINE POST
2"
TRUSS ROD
(3/8" MIN. DIA.)
BOTTOM OF
FABRIC
1 1/2" MIN
2 1/2" MAX
TENSION
WIRE
GRADE HOG RINGS (TYP.)
16" MIN. DIA.
6" 3'
-4
M
IN
CONCRETE BASE
10'-0" MAXIMUM 10'-0" O.C. MAXIMUM
LINE POSTS TO BE EQUALLY SPACED
10" MIN. DIA.
3/8" PLAIN PIN
RIVETED FLUSH (TYP.)
1' -0
6"
(TY
P.)
1'- 6"
1'-0"
LINE POST CORNER POST
3/8" PLAIN PIN
RIVETED FLUSH (TYP.)
1' -0
BARBED WIRE (TYP.)
7.5
(TY
P.)
1'-1
0"LOCK PIN (TYP.)
CONCRETE BASE
TRUSS ROD
(3/8" MIN. DIA.)
1 1/2" (TYP.)
TENSION
BAND
TRUSS ROD
(3/8" MIN. DIA.)
ROUND POST
H-BEAM
TENSION BAND (15" O.C.
MAX. AND WITHIN 4" FROM
TOP AND BOTTOM OF FABRIC)
FABRIC
TENSION BAR TO ENGAGE
EACH FABRIC LINK
TENSION BAR
CARRIAGE BOLT
BARBED WIRE OR
TENSION WIRE
9-GAGE STEEL TIE WIRES
(2'-0" O.C. MAX.)
FABRIC
TOP RAIL
LINE POST
BRACE RAILS
TRUSS ROD TRUSS ROD
PULL POST
BRACE RAILS
LINE POST
TENSION WIRE
10'-0" MAX. 10'-0" MAX.
NOTE:
PROVIDE BRACE PANEL WHENEVER
STRAIGHT RUNS EXCEED 500 FEET.
FENCE POST
#8 AWG SOLID
COPPER WIRE
1'-0"
'-0
MOLDED EXOTHERMIC WELD
OR APPROVED CLAMP-TYPE
FITTING OF COPPER
3/4" DIA COPPER-CLAD
STEEL GROUND ROD
H-BEAM ROUND POST
9-GAGE STEEL TIE WIRE (15"O.C.
MAX. AND WITHIN 4" FROM TOP
AND BOTTOM OF FABRIC)
NOTES:
1. DETAILS SHOWN ARE TO CLARIFY REQUIREMENTS AND ARE NOT
INTENDED TO LIMIT OTHER TYPES OF FENCE SECTIONS AND METHODS OF
INSTALLATION THAT COMPLY WITH THE SPECIFICATIONS.
2. WIRE TIES, RAILS, POSTS, AND BRACES SHALL BE CONSTRUCTED ON THE
SECURE SIDE OF THE FENCE ALIGNMENT. CHAIN-LINK FABRIC SHALL BE
PLACED ON THE SIDE OPPOSITE THE SECURE AREA.
3. UNLESS SPECIFICALLY SHOWN OR SPECIFIED, ALL FE6 FENCE SHALL HAVE
AN APRON EXTENDED OUTWARD FROM THE AREA BEING PROTECTED.
4. C-SECTION POSTS SHALL BE INSTALLED SO THAT THE VOID INSIDE THE
POST IS COMPLETELY FILLED WITH CONCRETE UP TO THE TOP OF THE
FOUNDATION.
STEEL POST SCHEDULE
USE AND SECTION
MINIMUM OUTSIDE DIMENSIONS (NOMINAL)
FABRIC WIDTH 84" TO 96"
CORNER, END & PULL POSTS
TUBULAR - ROUND
TUBULAR - SQUARE
C-SECTION (ROLL-FORMED)
LINE POSTS
TUBULAR - ROUND
H-SECTION
C-SECTION (ROLL-FORMED)
TOP, BOTTOM & BRACE RAILS
TUBULAR - ROUND
TUBULAR - SQUARE
H-SECTION
C-SECTION (ROLL-FORMED)
2.875" O.D.
2.50" SQ.
3.50" X 3.50"
2.375" O.D.
2.25" X 1.70" 2.25" X 1.70"
1.66" O.D.
1.50" SQ.
1.625" X 1.50" 1.625" X 1.25"
CHAIN LINK FABRIC
3 HORIZONTAL STRANDS
OF BARBED WIRE
3 STRANDS OF BARBED WIRE (TYP.)
CHAIN LINK FABRICGATE FRAME
GATE OPENING
DIRECTION OF GATE
SWING (TYP.)
PLAN
1'-0"
FABRIC WIDTH
(96")
LINE POST
6"
3'-10" FOR POSTS 8 5/8" O.D.
3'-4" FOR POST 6 5/8" O.D.
3'-0" MIN. FOR POSTS 4" O.D. & LESS
LEAF
GATE FRAME
DROP ROD
LATCH ASSEMBLY
3 STRANDS OF BARBED WIRE (TYP.)
3 STRANDS OF BARBED WIRE (TYP.)
TOP RAIL
CHAIN-LINK FABRIC
BRACE RAIL (TYP.)
HINGES (TYP.)
LINE POST
TRUSS ROD (TYP.)
BRACE RAIL (TYP.)
GRADE LINE
BOTTOM TENSION
WIRE (TYP.)
2" MIN
5" MAX FOR UNSENSORED FENCES3/8" DIA. TRUSS
RODS (TYP)
16" DIA. MIN. FOR GATE
POSTS 4" O.D. & LESS
24" DIA. FOR GATE POSTS
OVER 4" O.D. ELEVATION
OFFSET HINGE STANDARD HINGE
1/2" DIA. DROP ROD
(INDUSTRY STANDARD)
1"
6"
SAND/GRAVEL
6" DIA CONCRETE
1" I.D. STEEL PIPE
10"
6"
2' -0
NOTES:
1. FOR NON-SENSORED FENCES, DETAILS SHOWN
ARE TO CLARIFY REQUIREMENTS AND ARE NOT
INTENDED TO LIMIT OTHER TYPE OF FENCE
SECTIONS AND METHODS OF INSTALLATION
WHICH COMPLY WITH THE SPECIFICATIONS.
2. SWING GATES SHALL BE CONSTRUCTED WITH
DROP RODS, PADLOCKS, LATCH ASSEMBLY AND
GATE KEEPERS EXCEPT AS NOTED.
3. ALL GATE FRAMES SHALL MEET THE MINIMUM
REQUIREMENTS OF ASTM F900 1.90" NOMINAL
(ROUND) OR 2.00" NOMINAL (SQUARE). GATE
FRAMES SHALL BE OF WELDED CONSTRUCTION
OR SHALL BE ASSEMBLED USING HEAVY FITTINGS.
AT CONTRACTOR'S OPTION A WELDED
HORIZONTAL BRACE MAY BE USED IN LIEU OF
TRUSS RODS TO BRACE ALL-WELDED GATE
FRAMES. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR THE PROPER RIGID
CONSTRUCTION OF ALL GATES SUPPLIED.
GATE POST SCHEDULE
GATE LEAF WIDTH
(NOMINAL)
OUTSIDE DIMENSION
(NOMINAL)
6' OR LESS
GREATER THAN 6' TO 12'
GREATER THAN 12' TO 18'
MORE THAN 18'
2.875" OD
2.5" SQ
4.0" OD
6.625" OD
8.625" OD
8C500-S
STOCKBRIDGE
SITE DETAILS
RTVW180301AE
RCI
RCI
SHEET SIZE: 24" x 36"
DESIGN FIRM:
NYS Education Law, Section 7209 Prohibits any person to alter these drawings other than a licensed architect or the design engineer. Information on these drawings remains the property of the licensed professionals who prepared them and may only be used on the project identified below.
Copyright 2021 N.K. BHANDARI, Architecture & Engineering, P.C.
DRAWING NO: SHEET: FACILITY NAME:
OF
SHEET TITLE:
PROJECT TITLE:
Rev. Date Description Drawn Approved
DATE:
STOCKBRIDGE
PROJECT MANAGER:
PROJECT NO:
DRAFTER:
Rome Research Site
Air Force Research Laboratory Information Directorate
Rome, New York
RIO:
RIOCC:
RIOS:
66abw/def:
RIOC:
RIOCO:
RIOF:
USER:
RIOCC:
RIOCV:
DET 4/SE:
USER:DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DESIGNER:
CONSULTANT:
NKBN. .______________________________________________________
ARCHITECTURE & ENGINEERING, P C..
KBHANDARI
N A P I E R A L A C O N S U L T I N G
PROFESSIONAL ENGINEER, P.C.
SITE DESIGN ENGINEERING
17 10/29/2021
RTVW180301AE
DBH
SCALE:
LINE POST ATTACHMENTS DETAIL
NTS
C500-S
9-GAGE STEEL TIE WIRE (15"O.C.
MAX. AND WITHIN 4" FROM TOP
AND BOTTOM OF FABRIC)
SCALE:
CHAIN-LINK SECURITY FENCE DETAIL
NTS
C500-S
35°
45°
SCALE:
EXTENSION ARM DETAILS
NTS
C500-S
SCALE:
TRUSS ROD AND BAND
NTS
C500-S
SCALE:
TENSION BAND DETAIL
NTS
C500-S
SCALE:
END OR GATE POST DETAIL
NTS
C500-S
SCALE:
TOP OR BRACE RAIL
ATTACHMENT
NTS
C500-SSCALE:
GROUNDING DETAIL
NTS
C500-S SCALE:
BRACE RAIL CLAMP DETAILS
NTS
C500-S
SCALE:
DOUBLE SWING GATE DETAIL
NTS
C500-S
SCALE:
DROP ROD FOUNDATION
NTS
C500-S SCALE:
GATE KEEPER
(TO KEEP GATE OPEN)
NTS
C500-S SCALE:
LATCH ASSEMBLY
NTS
C500-S
SCALE:
DROP ROD ASSEMBLY
NTS
C500-S
SCALE:
HINGE DETAIL
NTS
C500-S
1' -8
3"
6"
6 x 6 x 10/10 WWF CLASS C REINFORCED
CEMENT CONCRETE
6" M
ID
PO
IN
T 6"
GRANULAR SUBBASE
NYSDOT ITEM 304.03
COMPACTED SUBGRADE
6'
30'
6'
12" WIDE x 4" DEEP
ISOLATION JOINT
12'
1 34" DEEP TOOLED OR
SAWCUT CONTRACTION
JOINT @ 6'-0" O.C.
2 #4 REBAR
CONTINUOUS
SCALE:
CONCRETE UTILITY PAD
NTS
C501-S
SCALE:
GRAVEL ACCESS ROAD SECTION
NTS
C501-S
TOPSOIL3" GRAVEL LEVELING COURSE
GEOSYNTHETIC FABRIC
MIRAFI 500X (OR APPROVED EQUAL)
COMPACTED SUBGRADE
(SUITABLE SOIL MATERIAL)
SLOPE AS INDICATED ON
SITE PLAN
NOTES
1. GRAVEL LEVELING COURSE TO BE IN CONFORMANCE WITH
NYSDOT STANDARD SPECIFICATIONS ITEM No. 411.01.
GRAVEL SHALL CONFORM TO THE FOLLOWING GRADATION
REQUIREMENTS:
PERCENT PASSING
SIEVE SIZE BY WEIGHT
2 INCH 100
1/4 INCH 30-65
No. 200 10-20
2. GRANULAR BASE COURSE SHALL BE IN CONFORMANCE
WITH NYSDOT STANDARD SPECIFICATIONS ITEM No. 304.11
(TYPE 1 SUBBASE) WITH THE FOLLOWING GRADATION
REQUIREMENTS:
PERCENT PASSING
SIEVE SIZE BY WEIGHT
3 INCH 100
2 INCH 90-100
1/4 INCH 30-65
No. 40 5-40 No. 200 0-10
3. RECLAIMED ASPHALT PAVEMENT IS ACCEPTABLE FOR USE
IN THE BASE COURSE. REFER TO NYSDOT STANDARD
SPECIFICATION SECTION 733-06.
TOPSOIL3" GRAVEL LEVELING COURSE
GEOSYNTHETIC FABRIC
MIRAFI 500X (OR APPROVED EQUAL)
COMPACTED SUBGRADE
(SUITABLE SOIL MATERIAL)
SLOPE AS INDICATED ON
SITE PLAN
NOTES
1. GRAVEL LEVELING COURSE TO BE IN CONFORMANCE WITH
NYSDOT STANDARD SPECIFICATIONS ITEM No. 411.01.
GRAVEL SHALL CONFORM TO THE FOLLOWING GRADATION
REQUIREMENTS:
PERCENT PASSING
SIEVE SIZE BY WEIGHT
2 INCH 100
1/4 INCH 30-65
No. 200 10-20
2. GRANULAR BASE COURSE SHALL BE IN CONFORMANCE
WITH NYSDOT STANDARD SPECIFICATIONS ITEM No. 304.12
(TYPE 2 SUBBASE) INSTALLED IN TWO LIFTS WITH THE
FOLLOWING GRADATION REQUIREMENTS:
PERCENT PASSING
SIEVE SIZE BY WEIGHT
2 INCH 100
1/4 INCH 25-60
No. 40 5-40 No. 200 0-10
9" BASE COURSE,
NYSDOT TYPE 1
(ITEM No. 304.11)
12" BASE COURSE,
NYSDOT TYPE 2
(ITEM No. 304.12)
INSTALLED IN TWO LIFTS
SCALE:
GRAVEL BUILDING PAD SECTION
NTS
C501-S
9C501-S
STOCKBRIDGE
SITE DETAILS
RTVW180301AE
RCI
RCI
SHEET SIZE: 24" x 36"
DESIGN FIRM:
NYS Education Law, Section 7209 Prohibits any person to alter these drawings other than a licensed architect or the design engineer. Information on these drawings remains the property of the licensed professionals who prepared them and may only be used on the project identified below.
Copyright 2021 N.K. BHANDARI, Architecture & Engineering, P.C.
DRAWING NO: SHEET: FACILITY NAME:
OF
SHEET TITLE:
PROJECT TITLE:
Rev. Date Description Drawn Approved
DATE:
STOCKBRIDGE
PROJECT MANAGER:
PROJECT NO:
DRAFTER:
Rome Research Site
Air Force Research Laboratory Information Directorate
Rome, New York
RIO:
RIOCC:
RIOS:
66abw/def:
RIOC:
RIOCO:
RIOF:
USER:
RIOCC:
RIOCV:
DET 4/SE:
USER:DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DESIGNER:
CONSULTANT:
NKBN. .______________________________________________________
ARCHITECTURE & ENGINEERING, P C..
KBHANDARI
N A P I E R A L A C O N S U L T I N G
PROFESSIONAL ENGINEER, P.C.
SITE DESIGN ENGINEERING
17 10/29/2021
RTVW180301AE
DBH
INSTALL HF ANTENNAS,
TEST SITES
SCALE:
TRENCH RESTORATION
NTS
C501-S
SELECT GRANULAR FILL IN
CONFORMANCE WITH NYSDOT
SPECIFICATION ITEM No. 733-1101;
PLACE IN 8" LOOSE LIFTS MAX AND
COMPACT TO 90% MODIFIED PROCTOR
GRAVEL PAVED
SELECT GRANULAR FILL IN CONFORMANCE
WITH NYSDOT SPECIFICATION ITEM No.
733-1101; PLACE IN 8" LOOSE LIFTS MAX AND
COMPACT TO 90% MODIFIED PROCTOR
6"6"
2" NYSDOT TYPE F3 ASPHALT TOP
COURSE, ITEM 402.128303
3" NYSDOT TYPE F9 ASPHALT BINDER
COURSE, ITEM 402.258903
12" GRAVEL SUBBASE, NYSDOT
733-0402 - SUBBASE COURSE,
TYPE 2
APPLY TACK COAT MEETING NYSDOT
SPECIFICATION SECTION 407 BETWEEN
ASPHALT COURSES
SEAL JOINT BETWEEN EXISTING
PAVEMENT AND NEW PAVEMENT WITH
ASPHALT PAVEMENT JOINT ADHESIVERESTORE LAWN AREAS WITH 4"
SCREENED TOPSOIL, SEED AND
MULCH; MOUND FOR SETTLING
3" GRAVEL LEVELING COURSE
NOTES
1. GRAVEL LEVELING COURSE TO BE IN CONFORMANCE WITH
NYSDOT STANDARD SPECIFICATIONS ITEM No. 411.01. GRAVEL
SHALL CONFORM TO THE FOLLOWING GRADATION
REQUIREMENTS:
PERCENT PASSING
SIEVE SIZE BY WEIGHT
2 INCH 100
1/4 INCH 30-65
No. 200 10-20
2. GRANULAR BASE COURSE SHALL BE IN CONFORMANCE WITH
NYSDOT STANDARD SPECIFICATIONS ITEM No. 304.11 (TYPE 1
SUBBASE) WITH THE FOLLOWING GRADATION REQUIREMENTS:
PERCENT PASSING
SIEVE SIZE BY WEIGHT
3 INCH 100
2 INCH 90-100
1/4 INCH 30-65
No. 40 5-40 No. 200 0-10
9" BASE COURSE,
NYSDOT TYPE 1 (ITEM No. 304.11)
REFER TO ELECTRICAL DETAILS FOR
CONDUIT INSTALLATION
REFER TO ELECTRICAL
DETAILS FOR CONDUIT
INSTALLATION
LAWN/GRASS AREAS
NOTES:
1. CONCRETE WAHSOUT AREA SHALL BE INSTALLED PRIOR TO ANY CONCRETE
PLACEMENT ON SITE.
2. SIGNS SHALL BE PLACED AT THE CONSTRUCTION ENTRANCE, AT THE WASHOUT
AREA, AND ELSEWHERE AS NECESSARY TO CLEARLY INDICATE LOCATION OF
CONCRETE WASHOUT AREA TO OPERATORS OF CONCRETE TRUCKS AND PUMP RIGS.
3. THE CONCRETE WAHSOUT AREA SHALL BE REPAIRED AND ENLARGED OR CLEANED
OUT AS NECESSARY TO MAINTAIN CAPACITY FOR WASTED CONCRETE.
4. AT THE END OF CONSTRUCTION, ALL CONCRETE SHALL BE REMOVED FROM SITE AND
DISPOSED OF AT AN ACCEPTED WASTE SITE.
5. WHEN THE CONCRETE WASHOUT AREA IS REMOVED, THE DISTURBED AREA SHALL
BE SEEDED AND MULCHED OR OTHERWISE STABILIZED.
SIGN TO INDICATE
LOCATION OF WASHOUT AREA
8' X 8' MIN
OR AS REQUIRED TO
CONTAIN WASTE CONCRETE
12" MIN
M
IN
2' M
IN GROUND SURFACE
BERM TO SURROUND
PERIMETER
1. WOVEN WIRE FENCE TO BE FASTENED SECURELY TO
FENCE POSTS WITH WIRE TIES OR STAPLES.
2. FILTER CLOTH IS TO BE FASTENED SECURELY TO WOVEN
WIRE FENCE WITH TIES SPACED EVERY 24" AT TOP AND
MID SECTION.
3. WHEN TWO SECTIONS OF FILTER CLOTH ADJOIN EACH
OTHER, THEY SHALL BE OVERLAPPED BY SIX INCHES AND
FOLDED.
4. MAINTENANCE SHALL BE PERFORMED AS NEEDED AND
MATERIAL REMOVED WHEN "BULGES" DEVELOP IN THE
SILT FENCE.
POSTS: STEEL, EITHER "T" OR "U" TYPE OR 2"
HARDWOOD
FENCE: WOVEN WIRE, 14 1/2 GAUGE, 6" MAX. MESH
OPENING
FILTER CLOTH:FILTER X., MIRAFI 100X, STABILINKA T140N
OR APPROVED EQUAL
PREFABRICATED UNIT:GEOFAB, ENVIROFENCE, OR APPROVED
EQUAL
DRIVEN MINIMUM
16" INTO GROUND WOVEN WIRE FENCE
(MIN 1412 GAUGE, MAX
6" MESH SPACING)
10' MAX O.C.
UNDISTURBED GROUND FLO
W
WOVEN WIRE FENCE WITH
FILTER CLOTH OVER
M
IN
16" MIN
UNDISTURBED
GROUND
EMBED FILTER CLOTH
MIN. 6" INTO GROUND
FLOW
1. STONE SIZE - USE 2" STONE, OR RECLAIMED OR RECYCLED CONCRETE EQUIVALENT.
2. LENGTH - NOT LESS THAN 50 FEET.
3. THICKNESS - NOT LESS THAN SIX (6) INCHES.
4. WIDTH - 24 FEET MINIMUM.
5. FILTER CLOTH - WILL BE PLACED OVER THE ENTIRE AREA PRIOR TO PLACING OF STONE.
6. SURFACE WATER - ALL SURFACE WATER FLOWING OR DIVERTED TOWARD CONSTRUCTION
ENTRANCES SHALL BE PIPED ACROSS THE ENTRANCE. IF PIPING IS IMPRACTICAL, A
MOUNTABLE BERM WITH 5:1 SLOPES WILL BE PERMITTED.
7. MAINTENANCE - THE ENTRANCE SHALL BE MAINTAINED IN A CONDITION WHICH WILL
PREVENT TRACKING OR FLOWING OF SEDIMENT ONTO PUBLIC RIGHTS-OF-WAY. ALL
SEDIMENT SPILLED, DROPPED, WASHED, OR TRACKED ONTO PUBLIC RIGHTS-OF-WAY MUST
BE REMOVED IMMEDIATELY.
8. WHEN WASHING IS REQUIRED, IT SHALL BE DONE ON AN AREA STABILIZED WITH STONE
AND WHICH DRAINS INTO AN APPROVED SEDIMENT TRAPPING DEVICE.
9. PERIODIC INSPECTION AND NEEDED MAINTENANCE SHALL BE PROVIDED AFTER EACH RAIN.
12'
MIN
M
IN
M
IN
12' MIN ONE WAY
24' MIN TWO WAY
50' MIN
FILTER CLOTH
50'
6" M
IN
EROSION AND SEDIMENT CONTROLS
1. STABILIZATION PRACTICES (TEMPORARY)
a. TEMPORARY SEEDING AND PLANTING OF ALL UNPAVED AREAS WHEN CONSTRUCTION
ACTIVITY HAS CEASED, OR WILL CEASE, IN AN AREA FOR 14 DAYS. SEEDING MIXTURES
AND APPLICATION RATES ARE LISTED ON SHEET C-2.
b. MULCHING EXPOSED AREAS.
c. FREQUENT WATERING TO MINIMIZE WIND EROSION DURING CONSTRUCTION.
2. STABILIZATION PRACTICES (PERMANENT)
a. LAND CLEARING ACTIVITIES SHALL BE DONE ONLY IN AREAS WHERE EARTHWORK
WILL BE PERFORMED AND SHALL PROGRESS AS EARTHWORK IS NEEDED.
b. PERMANENT SEEDING AND PLANTING OF ALL UNPAVED AREAS.
3. STRUCTURAL MEASURES TEMPORARY
a. STABILIZED CONSTRUCTION ENTRANCE: A STABILIZED CONSTRUCTION ENTRANCE
SHALL BE PROVIDED AT THE ENTRANCE TO THE DISTURBED AREAS FROM AN EXISTING
ROADWAY. THE PURPOSE OF THE STABILIZED CONSTRUCTION ENTRANCE IS TO
REDUCE OR ELIMINATE THE TRACKING OF SEDIMENT ONTO THE PUBLIC
RIGHT-OF-WAY.
b. SILT FENCE: SILT FENCE SHALL BE INSTALLED AS SHOWN ON THE EROSION CONTROL
PLAN . THE FABRIC SHALL MEET THE SPECIFICATIONS NOTED ON THE DETAILS
UNLESS OTHERWISE APPROVED BY THE APPROPRIATE EROSION AND SEDIMENT
CONTROL PLAN APPROVAL AUTHORITY. SUCH APPROVAL SHALL NOT CONSTITUTE
STATEWIDE ACCEPTANCE.
c. DUST CONTROL: DUST CONTROL IS THE CONTROL OF DUST RESULTING FROM
LAND-DISTURBING ACTIVITIES. THE PURPOSE IS TO PREVENT SURFACE AND AIR
MOVEMENT OF DUST FROM DISTURBED SOIL SURFACES THAT MAY CAUSE OFF-SITE
DAMAGE, HEALTH HAZARDS, AND TRAFFIC SAFETY PROBLEMS.
4. STRUCTURAL PRACTICES (PERMANENT)
a. LAND GRADING: PERMANENT RESHAPING OF THE EXISTING LAND SURFACE BY
GRADING IN ACCORDANCE WITH AN ENGINEERING TOPOGRAPHIC PLAN AND
SPECIFICATION TO PROVIDE EROSION CONTROL AND VEGETATIVE ESTABLISHMENT ON
DISTURBED, RESHAPED AREAS.
5. SEQUENCE OF MAJOR ACTIVITIES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR IMPLEMENTING THE ABOVE LISTED
EROSION AND SEDIMENT CONTROL PRACTICES. THE CONTRACTOR MAY DESIGNATE THESE
TASKS TO CERTAIN SUBCONTRACTORS AS IS SEEN FIT, BUT THE ULTIMATE
RESPONSIBILITY FOR IMPLEMENTING THESE CONTROLS AND ENSURING THEIR PROPER
FUNCTION REMAINS WITH THE CONTRACTOR. THE ORDER OF ACTIVITIES WILL BE AS
FOLLOWS:
a) CONSTRUCT TEMPORARY CONSTRUCTION ENTRANCE/EXIT AT THE LOCATION SHOWN
ON THE PLAN.
b) INSTALL PERIMETER SILT FENCE AN IN THE LOCATIONS SHOWN ON THE PLAN.
c) REMOVAL OF EXISTING ASPHALT PAD AS SHOWN ON THE PLAN.
d) SITE GRADING.
e) CONSTRUCTION OF ANTENNA FOUNDATION AND ANCHOR POINTS.
f) CONSTRUCTION OF CONCRETE UTILITY PAD.
g) CONSTRUCT GRAVEL DRIVEWAY BASE COURSE.
j) DEEP RIPPING OF NON-PAVED AREAS AS REQUIRED (NON-PAVED AREAS THAT HAVE
BEEN COMPACTED DURING CONSTRUCTION VIA CONSTRUCTION TRAFFIC).
k) FINAL GRADING, SEEDING, AND MULCHING.
l) PLACE FINAL GRAVEL SURFACE COURSE ON DRIVEWAY.
m) REMOVE SILT FENCE ONLY AFTER ALL PAVING IS COMPLETE AND EXPOSED SURFACES
ARE STABILIZED.
MAINTENANCE/INSPECTION PROCEDURES
THE FOLLOWING INSPECTION AND MAINTENANCE PRACTICES WILL BE USED TO MAINTAIN
EROSION AND SEDIMENT CONTROLS AND STABILIZATION MEASURES.
1. ALL CONTROL MEASURES WILL BE INSPECTED AT LEAST ONCE EVERY SEVEN (7) CALENDAR
DAYS
2. ALL MEASURES WILL BE MAINTAINED IN GOOD WORKING ORDER; IF REPAIRS OR OTHER
EROSION CONTROL MEASURES ARE FOUND TO BE NECESSARY, THEY WILL BE INITIATED
WITHIN 24 HOURS OF REPORT.
3. BUILT UP SEDIMENT WILL BE REMOVED FROM SILT FENCE WHEN IT HAS REACHED
ONE-THIRD THE HEIGHT OF THE FENCE.
4. SILT FENCES WILL BE INSPECTED FOR DEPTH OF SEDIMENT, TEARS, ETC., TO SEE IF THE
FABRIC IS SECURELY ATTACHED TO THE FENCE POSTS, AND TO SEE THAT THE FENCE
POSTS ARE SECURELY IN THE GROUND.
5. TEMPORARY AND PERMANENT SEEDING AND ALL OTHER STABILIZATION MEASURES WILL BE
INSPECTED FOR BARE SPOTS, WASHOUTS, AND HEALTHY GROWTH.
6. A MAINTENANCE INSPECTION REPORT WILL BE MADE AFTER EACH INSPECTION. COPIES OF
THE REPORT FORMS TO BE COMPLETED BY THE INSPECTOR ARE INCLUDED IN THIS SWPPP.
7. THE OPERATOR SHALL HAVE A "QUALIFIED PROFESSIONAL" CONDUCT SITE INSPECTIONS
FOLLOWING THE COMMENCEMENT OF CONSTRUCTION. A "QUALIFIED PROFESSIONAL" IS A
PERSON KNOWLEDGEABLE IN THE PRINCIPLES AND PRACTICE OF EROSION AND SEDIMENT
CONTROLS, SUCH AS A LICENSED PROFESSIONAL ENGINEER, CERTIFIED PROFESSIONAL IN
EROSION AND SEDIMENT CONTROL (CPESC), OR SOIL SCIENTIST.
8. DISTURBED AREAS AND MATERIALS STORAGE AREAS WILL BE INSPECTED FOR EVIDENCE
OF OR POTENTIAL FOR POLLUTANTS ENTERING STORMWATER SYSTEMS.
9. REPORT TO NYS DEC WITHIN 24 HOURS ANY NONCOMPLIANCE WITH THE SWPPP THAT WILL
ENDANGER PUBLIC HEALTH OR THE ENVIRONMENT. FOLLOW UP WITH A WRITTEN REPORT
WITHIN 5 DAYS OF THE NONCOMPLIANCE EVENT. THE FOLLOWING EVENTS REQUIRE 24
HOUR REPORTING: A) ANY UNANTICIPATED BYPASS WHICH EXCEEDS ANY EFFLUENT
LIMITATION IN THE PERMIT, B) ANY UPSET WHICH EXCEEDS ANY EFFLUENT LIMITATION IN
THE PERMIT, AND C) A VIOLATION OF A MAXIMUM DAILY DISCHARGE LIMITATION FOR ANY
OF THE POLLUTANTS LISTED BY THE EPA IN THE PERMIT TO BE REPORTED WITHIN 24
HOURS. THE WRITTEN SUBMISSION MUST CONTAIN A DESCRIPTION OF THE
NON-COMPLIANCE AND ITS CAUSE; THE PERIOD OF NON-COMPLIANCE, INCLUDING EXACT
DATES AND TIMES, AND IF THE NON-COMPLIANCE HAS NOT BEEN CORRECTED, THE
ANTICIPATED TIME IT IS EXPECTED TO CONTINUE; AND STEPS TAKEN OR PLANNED TO
REDUCE, ELIMINATE, AND PREVENT RECURRENCE OF THE NON-COMPLIANCE.
10. RELEASES OF HAZARDOUS SUBSTANCES OR OIL IN EXCESS OF REPORTABLE QUANTITIES
(AS ESTABLISHED UNDER 40 CFR 110, 40 CFR 117 OR 40 CFR 302) MUST BE REPORTED.
FORM G-1 PROVIDES FURTHER DETAILS ON THE NOTIFICATION AND REPORTING PROCESS.
INSPECTION AND MAINTENANCE REPORT FORMS
ONCE INSTALLATION OF ANY REQUIRED OR OPTIONAL EROSION CONTROL DEVICE OR MEASURE
HAS BEEN IMPLEMENTED, AT LEAST ONCE EVERY SEVEN (7) CALENDAR DAYS AND SHALL BE
PERFORMED BY A QUALIFIED PROFESSIONAL. THE FORMS FOUND IN THIS SWPPP SHALL BE
USED BY THE INSPECTORS TO INVENTORY AND REPORT THE CONDITION OF EACH MEASURE TO
ASSIST IN MAINTAINING THE EROSION AND SEDIMENT CONTROL MEASURES IN GOOD WORKING
ORDER.
THESE REPORT FORMS SHALL BECOME AN INTEGRAL PART OF THE SWPPP AND SHALL BE MADE
READILY ACCESSIBLE TO GOVERNMENTAL INSPECTION OFFICIALS, THE OPERATOR'S ENGINEER, AND THE OPERATOR FOR REVIEW UPON REQUEST DURING VISITS TO THE PROJECT SITE. IN
ADDITION, COPIES OF THE REPORTS SHALL BE PROVIDED TO ANY OF THESE PERSONS, UPON
REQUEST, VIA MAIL OR FACSIMILE TRANSMISSION. INSPECTION AND MAINTENANCE REPORT
FORMS ARE TO BE MAINTAINED BY THE PERMITTEE FOR FIVE YEARS FOLLOWING THE FINAL
STABILIZATION OF THE SITE.
OTHER RECORD-KEEPING REQUIREMENTS
THE CONTRACTOR SHALL KEEP THE FOLLOWING RECORDS RELATED TO CONSTRUCTION
ACTIVITIES AT THE SITE:
- DATES WHEN MAJOR GRADING ACTIVITIES OCCUR AND THE AREAS WHICH WERE
GRADED
- DATES AND DETAILS CONCERNING THE INSTALLATION OF STRUCTURAL CONTROLS
- DATES WHEN CONSTRUCTION ACTIVITIES CEASE IN AN AREA
- DATES WHEN AN AREAS IS STABILIZED, EITHER TEMPORARILY OR PERMANENTLY
- DATES OF RAINFALL AND THE AMOUNT OF RAINFALL
- DATES AND DESCRIPTIONS OF THE CHARACTER AND AMOUNT OF ANY SPILLS OF
HAZARDOUS MATERIALS
- RECORDS OF REPORTS FILED WITH REGULATORY AGENCIES IF REPORTABLE
QUANTITIES OF HAZARDOUS MATERIALS SPILLED
EROSION CONTROL NOTES
1. LAND DISTURBING ACTIVITIES SHALL NOT COMMENCE UNTIL APPROVAL TO DO SO HAS
BEEN RECEIVED BY GOVERNING AUTHORITIES. THE GENERAL CONTRACTOR SHALL
STRICTLY ADHERE TO THE APPROVED SWPPP DRAWINGS DURING CONSTRUCTION
OPERATIONS.
2. NO LAND CLEARING OR GRADING SHALL BEGIN UNTIL THE APPROPRIATE EROSION
CONTROL MEASURES HAVE BEEN INSTALLED.
3. ALL EXPOSED AREAS SHALL BE SEEDED AS SPECIFIED WITHIN 7 DAYS OF FINAL GRADING.
4. SHOULD CONSTRUCTION STOP FOR LONGER THAN 14 DAYS, THE SITE SHALL BE SEEDED AS
SPECIFIED.
5. MAINTAIN EROSION CONTROL MEASURES AFTER EACH RAIN AND AT LEAST ONCE A WEEK.
6. THIS PLAN SHALL NOT BE CONSIDERED ALL INCLUSIVE AS THE GENERAL CONTRACTOR
SHALL TAKE ALL NECESSARY PRECAUTIONS TO PREVENT SEDIMENT FROM LEAVING THE
SITE.
7. GENERAL CONTRACTOR SHALL COMPLY WITH ALL STATE AND LOCAL ORDINANCES THAT
APPLY.
8. ADDITIONAL EROSION AND SEDIMENT CONTROL MEASURES WILL BE INSTALLED IF DEEMED
NECESSARY BY ON SITE INSPECTION.
9. GENERAL CONTRACTOR SHALL BE RESPONSIBLE TO TAKE WHATEVER MEANS NECESSARY
TO ESTABLISH PERMANENT SOIL STABILIZATION.
10. ALL WORK TO BE DONE IN STRICT ACCORDANCE WITH THE NEW YORK STANDARDS AND
SPECIFICATIONS FOR EROSION AND SEDIMENT CONTROL.
EROSION CONTROL NOTES
SCALE:
STABILIZED CONSTRUCTION ENTRANCE
NTS
C502-S SCALE:
SILT FENCE
NTS
C502-S SCALE:
CONCRETE WASHOUT AREA
NTS
C502-S
10C502-S
STOCKBRIDGE
EROSION CONTROL
NOTES AND DETAILS RTVW180301AE
RCI
RCI
SHEET SIZE: 24" x 36"
DESIGN FIRM:
NYS Education Law, Section 7209 Prohibits any person to alter these drawings other than a licensed architect or the design engineer. Information on these drawings remains the property of the licensed professionals who prepared them and may only be used on the project identified below.
Copyright 2021 N.K. BHANDARI, Architecture & Engineering, P.C.
DRAWING NO: SHEET: FACILITY NAME:
OF
SHEET TITLE:
PROJECT TITLE:
Rev. Date Description Drawn Approved
DATE:
STOCKBRIDGE
PROJECT MANAGER:
PROJECT NO:
DRAFTER:
Rome Research Site
Air Force Research Laboratory Information Directorate
Rome, New York
RIO:
RIOCC:
RIOS:
66abw/def:
RIOC:
RIOCO:
RIOF:
USER:
RIOCC:
RIOCV:
DET 4/SE:
USER:DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DESIGNER:
CONSULTANT:
NKBN. .______________________________________________________
ARCHITECTURE & ENGINEERING, P C..
KBHANDARI
N A P I E R A L A C O N S U L T I N G
PROFESSIONAL ENGINEER, P.C.
SITE DESIGN ENGINEERING
17 10/29/2021
RTVW180301AE
DBH
ED
G E M
O W
ED
A
R
EA
BRUSH / ROCK PILE
PAVEMENT
4"x4" WOOD POST
MOWED GRASS
MOWED GRASS
N: 1106191.43
E: 1069063.55
ELEV=1271.30
CP 1
1269.8
1269.6
1272.7
1272.8
1269.4
1271.2
1269.8
1269.4
1269.2
1270.2
1270.4
1270.6
1270.8
1271.5
1271.4 1271.6
1271.8
1272.8
1271.8
1271.6
1271.4
1271.2
1272.8
1272.9
1272.2
MEE
1272.1
1273.2
1272.8
1272.6
1272.4
1272.2
MEE
MEE
MEEMEE
MEE
MEE
MEE
MEE
MEE
MEE
MEE
MEE
MEE
MEE
MEE
MEE
1271.6
MEE
1271.6
1271.4
MEE
1271.6
MEE
1271.61271.6
21' - 6"
120' - 0"
120' - 0"
9' - 4"
101' - 4"
9' - 4"
50' - 8"
50' - 8"
' - 1
" -T
Y P7 ' - 8
" -T Y
P
A
B
A
B
A
B
A
B
C E
60' - 0"
60' - 0"
128' - 0"
D
THIS AREA MUST
BE CLEAR FOR
ERECTION OF
ANTENNA
GRAVEL PATH
REFER TO SITE DWGS FOR
LOCATION AND GEOMETRY
GRAVEL PAD
REFER TO SITE DWGS FOR
LOCATION AND GEOMETRY
CONC PAD
REFER TO SITE DWGS FOR
LOCATION AND GEOMETRY
NKB
N. .______________________________________________________
ARCHITECTURE & ENGINEERING, PC..
K BHANDARI
SHEET SIZE: 24" x 36"
DESIGN FIRM:
FO
R A
P
PR
O V A L
NYS Education Law, Section 7209 Prohibits any person to alter these drawings other than a licensed architect or the design engineer. Information on these drawings remains the property of the licensed professionals who prepared them and may only be used on the project identified below.
Copyright 2021 N.K. BHANDARI, Architecture & Engineering, P.C.
DRAWING NO: SHEET: FACILITY NAME:
OF
SHEET TITLE:
PROJECT TITLE:
Rev. Date Description Drawn Approved
DATE:
STOCKBRIDGE
PROJECT MANAGER:
PROJECT NO:
DRAFTER:
Rome Research Site
Air Force Research Laboratory
Information Directorate Rome, New York
RIO:
RIOCC:
RIOS:
66abw/def:
RIOC:
RIOCO:
RIOF:
USER:
RIOCC:
RIOCV:
DET 4/SE:
USER:DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DESIGNER:
CONSULTANT:
10/21/2021 10:17:14 AM
11 17S-101-S 10/29/2021
ANTENNA
FOUNDATION PLAN
INSTALL HF ANTENNAS,
TEST SITES
RTVW180301AE
CAN
CAN
DBH
1" = 20'-0"S-101-S
A ANTENNA FOUNDATION PLAN
0 10' 20'
ANTENNA FOUNDATION NOTES:
1. TOWER FOUNDATIONS SHALL BE COMPLETED AS A PART OF A DELEGATED DESIGN BY THE ANTENNA
MANUFACTURER. COORDINATE ALL DIMENSIONS TO FINAL DELEGATED DESIGN.
2. DETAILS PROVIDED ARE SCHEMATIC, AND ARE ONLY TO BE USED FOR BIDDING PURPOSES. COORDINATE
FINAL GEOMETRY AND REQUIREMENTS WITH THE ANTENNA MANUFACTURER’S APPROVED FINAL DESIGN
OF TOWER FOUNDATIONS.
3. COORDINATE TOP OF FOUNDATION ELEVATION WITH FINAL DELEGATED DESIGN.
4. MAINTAIN A BOTTOM OF FOUNDATION DEPTH OF 5’-0” MINIMUM FOR FROST DEPTH PROTECTION.
5. BEDROCK MAY BE ENCOUNTERED DURING EXCAVATION FOR THE ANTENNA FOUNDATIONS.
6' - 6"
PLAN VIEW
SECTION VIEW
#1 - (1) ANCHOR
#2 - (6) J-BOLT
C O
O R
D W
D
E L
E G
A T
E D
D E
S
IG
N
V A
R
IE
S
T
O
18"
CL/ ANCHOR BLOCK
REINFORCING BARS
#1
#2
11" 21"
11 1/2"
/8
/8
/8
/8
M
IN
F R
O S
T P
R O
T E
C T
IO
N
ENCASE ANCHOR
IN 6" DIA CONC
120'-0" TO CL/
OF TOWER PIER
0 1' 2' 3'
COORDINATE HEIGHT
ABOVE GRADE WITH
DELEGATED DESIGN
COORD W/
DELEGATED
DESIGN
SECTION VIEW
#1 - (2) SCREW ANCHOR ASSY
C O
O R
D W
D
E L
E G
A T
E D
D E
S
IG
N
V A
R
IE
S
T
O
REINFORCING BARS
#1
3"
12"
42" SQUARE MIN
0 1' 2' 4'
M
IN
F R
O S
T P
R O
T E
C T
IO
N
COORDINATE HEIGHT
ABOVE GRADE WITH
DELEGATED DESIGN
60"
TOWARD TOWER
84'-10" TO TOWER
PLAN VIEW
SECTION VIEW
C
O O
R D
W D
E L
E G
A T
E D
D E
S
IG
N
V A
R
IE
S
T
O
34"
/2
CL/ ANCHOR BLOCK
REINFORCING BARS
#1
#1 - ANCHOR
0 1' 2' 4'
M
IN
F R
O S
T P
R O
T E
C T
IO
N
/4
COORDINATE
HEIGHT ABOVE
GRADE WITH
DELEGATED DESIGN
60"
PLAN VIEW
SECTION VIEW
#1 - (4) ANCHOR
#2 - (4) BOLT, SWEDGE, 1/2 x 2 3/4
71'-8" TO TOWER
3"
/8
/4
/8
12"
TOWARD
TOWER
C O
O R
D W
D
E L
E G
A T
E D
D E
S
IG
N
V A
R
IE
S
T
O
34"
56 1/2"
CL/ ANCHOR BLOCK
REINFORCING BARS
#1
#2
0 1' 2' 4'
M
IN
F R
O S
T P
R O
T E
C T
IO
N
COORDINATE HEIGHT
ABOVE GRADE WITH
DELEGATED DESIGN
PLAN VIEW
89 1/2"
SECTION VIEW
C O
O R
D W
D
E L E
G A
T E
D D
E S
IG
N
V A
R
IE
S
T
O
#1 - (6) BOLT, HxHd, 3/4-10 x 18 GALV #2 - (4) BOLT, HxHd, 1/2-13 x 9 GALV
REINFORCING, TYP
#1
#2
TOWARD
WINCH PIER
0 1' 2' 4'
M
IN
F R
O S
T P
R O
T E
C T
IO
N
COORDINATE HEIGHT
ABOVE GRADE WITH
DELEGATED DESIGN
NKB
N. .______________________________________________________
ARCHITECTURE & ENGINEERING, PC..
K BHANDARI
SHEET SIZE: 24" x 36"
DESIGN FIRM:
FO
R A
P
PR
O V A L
NYS Education Law, Section 7209 Prohibits any person to alter these drawings other than a licensed architect or the design engineer. Information on these drawings remains the property of the licensed professionals who prepared them and may only be used on the project identified below.
Copyright 2021 N.K. BHANDARI, Architecture & Engineering, P.C.
DRAWING NO: SHEET: FACILITY NAME:
OF
SHEET TITLE:
PROJECT TITLE:
Rev. Date Description Drawn Approved
DATE:
STOCKBRIDGE
PROJECT MANAGER:
PROJECT NO:
DRAFTER:
Rome Research Site
Air Force Research Laboratory
Information Directorate Rome, New York
RIO:
RIOCC:
RIOS:
66abw/def:
RIOC:
RIOCO:
RIOF:
USER:
RIOCC:
RIOCV:
DET 4/SE:
USER:DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DESIGNER:
CONSULTANT:
10/21/2021 10:17:15 AM
12 17S-500-S 10/29/2021
DETAILS
INSTALL HF ANTENNAS,
TEST SITES
RTVW180301AE
CAN
CAN
DBH
1/2" = 1'-0"S-500-S
4 FOUNDATION D
1/2" = 1'-0"S-500-S
5 FOUNDATION E
1/2" = 1'-0"S-500-S
1 FOUNDATION A
1/2" = 1'-0"S-500-S
2 FOUNDATION B
1/2" = 1'-0"S-500-S
3 FOUNDATION C
NO SCALE
SYMBOLS
1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL
ELECTRICAL CODES.
2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.
3. ITEMS OF SPECIFIC MANUFACTURERS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH
MANUFACTURER'S PRINTED INSTRUCTIONS AND/OR MANUFACTURER'S
REPRESENTATIVE'S DIRECTIONS.
4. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON
DRAWINGS.
5. ALL CONDUIT AND WIRING SCHEDULES SHALL BE VERIFIED BEFORE INSTALLATION.
6. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL
EQUIPMENT WITH OTHER CONTRACTORS.
7. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR
BETTER THAN ORIGINAL AS DETERMINED BY THE ENGINEER.
8. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED
SHALL BE REMOVED.
9. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE STARTING WORK.
IF ONLY A PORTION OF AN EXISTING CIRCUIT IS BEING REMOVED FOR DEMOLITION,
CONTINUITY SHALL BE MAINTAINED TO THE REST OF THE REMAINING CIRCUIT.
10. ALL BRANCH CIRCUIT CONDUCTORS SHALL BE #12AWG UNLESS OTHERWISE SHOWN.
11. ALL BRANCH CIRCUITS SHALL CONSIST OF 2 CONDUCTORS PLUS GROUND, UNLESS
OTHERWISE SHOWN. NO SHARED NEUTRALS.
AC ABOVE COUNTER
ACCU AIR COOLED CONDENSING UNIT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AU AT UNIT
BFG BELOW FINISHED GRADE
CDP CLOCK DISTRIBUTION PANEL
CH CHILLER
CL CEILING MOUNTED
CT CURRENT TRANSFORMER
CTB CLOCK TERMINAL BOX
DP DISTRIBUTION PANEL
DPM DISTRIBUTION PANEL MAIN
EF EXHAUST FAN
EMT ELECTRIC METALLIC TUBING
EP EXPLOSION PROOF
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FC FAN COIL
FD/SD FIRE DAMPER/SMOKE DAMPER
GF GROUND FAULT INTERRUPTER TYPE
GND GROUND
JB JUNCTION BOX
KA KILO AMP
KV KILO VOLT
KVA KILO VOLT AMP
KWHD KILOW WATT-HOUR DEMAND METER
LP LIGHTING PANEL
NC NORMALLY CLOSED
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NO NORMALLY OPEN
PB PULL BOX
PF POWER FEEDER
PT POTENTIAL TRANSFORMER
PUV PANEL-UNIT VENTILATOR
REM REMARKS
RGS RIGID GALVANIZED STEEL CONDUIT
UV UNIT VENTILATOR
VFD VARIABLE FREQUENCY DRIVE
WP WATER PROOF
TYP TYPICAL
TGB TELECOMMUNICATIONS GROUND BAR
W WALL MOUNT 48" AFF, UNLESS OTHERWISE NOTED
NO SCALE
ABBREVIATIONS
NO SCALE
GENERAL NOTES
E EXISTING DEVICE TO REMAIN
ACL ABOVE CEILING
CO CARBON MONOXIDE BASE
SB SOUNDER BASE
GB GROUND BAR
CLL CONTRACT LIMIT LINE
SHEET SIZE: 24" x 36"
DRAWING NO: SHEET: FACILITY NO:
OF
SHEET TITLE:
PROJECT TITLE:
Rev. Date Description Drawn Approved
DATE:
PROJECT MANAGER:
PROJECT NO:
DRAFTER:
Rome Research Site
RIO:
RIOCC:
RIOS:
66abw/def:
RIOC:
RIOCO:
RIOF:
USER:
RIOCC:
RIOCV:
DET 4/SE:
USER:DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DESIGNER:
3/6/2017 2:10:28 PM
DESIGN FIRM
CONSULTANT:
NKBN. .
ARCHITECTURE&ENGINEERING,PC..
KBHANDARI
NYS Education Law, Section 7209 Prohibits any person to alter these drawings other than a licensed architect or the design engineer. Information on these drawings remains the property of the licensed professionals who prepared them and may only be used on the project identified below.
Copyright 2021
N.K. BHANDARI, Architecture & Engineering, P.C.
Air Force Research Laboratory Information Directorate
Rome, New York
RTVW180301AE
STOCKBRIDGE17 10/29/2021
INSTALL HF ANTENNAS,
TEST SITES
NOTES, SYMBOLS AND
ABBREVIATIONS
JB
DJO, PE
E001-S 13
E001-S
E001-S
E001-S
HH
MH
HANDHOLE
MANHOLE
FUSED DISCONNECT SWITCH
XXX
PROPOSED UNDERGROUND ELECTRICAL DUCTBANKE
WP
GFI
DUPLEX RECEPTACLE, GROUND FAULT INTERRUPTER TYPE, WITH WEATHERPROOF COVER,
MOUNT 42" AFF UNLESS OTHERWISE NOTED
S
GROUND FAULT CIRCUIT INTERRUPTER TYPE, MOUNT 48" AFF UNLESS OTHERWISE NOTED
SINGLE POLE TOGGLE SWITCH
JUNCTION BOX
DISCONNECT SWITCH
CIRCUIT BREAKER
GROUND (IN ONE-LINES)
CONNECTION POINT OR CABLE SPLICE
TRANSFORMER
ELECTRICAL MOTOR (SEE EQUIPMENT CONNECTION SCHEDULE)
DISCONNECT SWITCH
BRANCH CIRCUIT HOME RUN WITH SOURCE PANEL AND CIRCUIT NUMBER.
SEE PANEL SCHEDULES FOR DETAILS
SPECIAL RECEPTACLE
COPPER GROUND BUS, 1/4" X 2", MOUNT 42" AFF
J
PROPOSED UNDERGROUND TELECOMMUNICATIONS DUCTBANKT
SURFACE MOUNTED PANEL
TO BE REMOVED BY CONTRACTOR
EXISTING TO REMAIN
NEW WORK PROVIDED BY CONTRACTOR
NOT TO SCALE
ONE LINE DIAGRAM
HH
MH
HANDHOLE
MANHOLE
FUSED DISCONNECT SWITCH
XXX
PROPOSED UNDERGROUND ELECTRICAL DUCTBANKE
WP
GFI
DUPLEX RECEPTACLE, GROUND FAULT INTERRUPTER TYPE, WITH WEATHERPROOF COVER,
MOUNT 42" AFF UNLESS OTHERWISE NOTED
S
GROUND FAULT CIRCUIT INTERRUPTER TYPE, MOUNT 48" AFF UNLESS OTHERWISE NOTED
SINGLE POLE TOGGLE SWITCH
JUNCTION BOX
DISCONNECT SWITCH
CIRCUIT BREAKER
GROUND (IN ONE-LINES)
CONNECTION POINT OR CABLE SPLICE
TRANSFORMER
ELECTRICAL MOTOR (SEE EQUIPMENT CONNECTION SCHEDULE)
DISCONNECT SWITCH
BRANCH CIRCUIT HOME RUN WITH SOURCE PANEL AND CIRCUIT NUMBER.
SEE PANEL SCHEDULES FOR DETAILS
SPECIAL RECEPTACLE
COPPER GROUND BUS, 1/4" X 2", MOUNT 42" AFF
J
PROPOSED UNDERGROUND TELECOMMUNICATIONS DUCTBANKT
SURFACE MOUNTED PANEL
TO BE REMOVED BY CONTRACTOR
EXISTING TO REMAIN
NEW WORK PROVIDED BY CONTRACTOR
NOT TO SCALE
ONE LINE DIAGRAM
E001-S
20A
EXISTING
MANHOLE
MH-1480
EXISTING LOAD
EXISTING
LOAD
EXISTING LOAD
NODE A
FOUR-WAY PAD
MOUNTED SWITCH
PRIMARY SWITCH
PS-1
PRIMARY TRANSFORMER,
PT-1480
75KVA, 4160V X 120/208V
PANEL LP-1
BUILDING
3-#2 (15 KV SHIELDED CABLE) IN
EXISTING 4" C. (CONCRETE ENCASED)
GRADE
PROVIDE PRIMARY
TRANSFORMER,
PT-ANTENNA
75KVA, 4160V X 120/208V
ANTENNA
PANEL
PROVIDE 3#2, 1#6G (15 KV SHIELDED
CABLE) IN 4" C. (CONCRETE ENCASED)
INTERCEPT EXISTING
FEEDER AND
RECONFIGURE TO
PROVIDE SEPARABLE
SPLICE IN EXISTING
MANHOLE FOR ALL
FEEDERS.
EXISTING OVERHEAD
4.16KV, 3Ø
UTILITY SERVICE
PROVIDE NEMA 4X, 120/208V, 3Φ, 30 SPACE PANELBOARD
PROVIDE 4#4/0 AWG, 1#4G IN
2 1/2" CONDUIT
NOT TO SCALE
PANEL SCHEDULES
E001-S
NOT TO SCALE
H-FRAME BACKBOARD DETAIL
E001-S
B-LINE SS4 4 HOLE TEE
PLATE OR APPROVED
EQUAL (TYP)
B-LINE B22 STAINLESS STEEL
OR APPROVED EQUAL
(TYP)
B-LINE SS4 4 HOLE TEE
PLATE OR APPROVED
EQUAL (TYP)
NEMA 4X RATED
NETWORK ENCLOSURE
GRADE
12" DIAMETER, 4'-0" DEEP
CONCRETE BASE
(TYP)
EXTEND STRUT TO 3'-6"
BELOW GRADE
(TYP)
GRADE
12" DIAMETER, 4'-0" DEEP
CONCRETE BASE
(TYP)
EXTEND STRUT TO 3'-6"
BELOW GRADE
(TYP)
B-LINE B22 STAINLESS STEEL
OR APPROVED EQUAL
(TYP)
NEMA 4X RATED
NETWORK ENCLOSURE
FRONT VIEW SIDE VIEW
4" CONDUITS (TYP)
4" CONDUITS (TYP)
CONDUITS SHALL BE AT LEAST
30" BELOW FINISHED GRADE (TYP)
CONDUITS (TYP)
ANTENNA PANEL
GFCI RECEPTACLE IN A
WEATHERPROOF ENCLOSURE
PROVIDE ELETRODE GROUND GRID
SEE SHEET E501-S FOR DETAILS
SITE PLAN
JB
DJO, PE
E100-S 14
E100-S
GENERAL FLOOR PLAN NOTES
1. REFER TO ONE LINE DIAGRAM FOR MORE INFORMATION.
2. CONFIRM ALL BUILDING IDENTIFICATION NOMENCLATURE WITH GOVERNMENT.
1" = 30'-0"
SITE PLAN
SHEET SIZE: 24" x 36"
DRAWING NO: SHEET: FACILITY NO:
OF
SHEET TITLE:
PROJECT TITLE:
Rev. Date Description Drawn Approved
DATE:
PROJECT MANAGER:
PROJECT NO:
DRAFTER:
Rome Research Site
RIO:
RIOCC:
RIOS:
66abw/def:
RIOC:
RIOCO:
RIOF:
USER:
RIOCC:
RIOCV:
DET 4/SE:
USER:DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DATE
DESIGNER:
3/6/2017 2:10:28 PM
DESIGN FIRM
CONSULTANT:
NKBN. .
engineer. Information on these drawings remains the property of the licensed professionals who prepared them and may only be used on the project identified below.
Copyright 2021
N.K. BHANDARI, Architecture & Engineering, P.C.
Air Force Research Laboratory Information Directorate
Rome, New York
RTVW180301AE
STOCKBRIDGE17 10/29/2021
INSTALL HF ANTENNAS,
TEST SITES
30' 60'
PROVIDE TRANSFORMER AND PAD.
PROVIDE PANELBOARD.
PROVIDE BOLLARD (TYPICAL OF 8).
KEYED NOTES
ANTENNA
PANEL
MH-1480
TAP FEEDER AND PROVIDE
SEPARABLE SPLICE IN MANHOLE.
REFER TO ONE-LINE DIAGRAM
EXISTING
EXISTING FEEDER
TO REMAIN
GRAVEL ROAD
PAVED DRIVE
GRAVEL DRIVE
PRIMARY…