This document contains the technical specifications for two Computer Room Air Handler (CRAH) units required for Project 22S004. The CRAH units must have a downflow blower configuration, a cooling capacity of 174,000 BTU/HR, and a minimum airflow of 9,000 CFM. Key requirements include a 2-way chilled water control valve, infrared humidification, MERV 8 filters, and electronically commutated (EC) direct drive variable speed fans. The units must be equipped with humidity and temperature sensors, as well as a display for setting parameters. Physical dimensions and weights are also specified.

The related federal contract opportunity is Solicitation FA8126-24-Q-0051 for Computer Room Air Handlers, issued by the Department of the Air Force Materiel Command Air Force Sustainment Center. This is a 100% small business set-aside solicitation, with a description that references the attached item specifications. The solicitation replaces/updates the previous solicitation FA8126-24-Q-0045.

View the file

Other files for this federal contract opportunity

Other files attached to Computer Room Air Handlers, newest first.
File Type Posted
CSS_FA812624Q0051.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project 22S004

558 LAB COMPUTER ROOM HANDLER UNIT SPECIFICATIONS (CRAH-1 & CRAH-2)

• COMPUTER ROOM AIR HANDLER UNIT (CRAH)

• BLOWER CONFIGURATION: DOWNFLOW.

• CAPACITY BASED ON 45°F ENTERING WATER, 10°F WATER RISE

o ENTERING TEMPERATURE: 75°F DB, 61°F WB, 45%RH o COOLING CAPACITY: 174,000 BTU/HR (NOMINAL 51kW) MINIMUM

• AIR FLOW: 9,000 CFM MINIMUM

• CHILLED WATER CONTROL VALVE: 2-WAY, 1-1/2"∅ STANDARD PRESSURE.

• INFRARED HUMIDIFICATION

• CHILLED WATER COIL FACE VELOCITY: 500 FPM MAXIMUM

• MERV 8 FILTER MINIMUM

• UNIT FLOOR STAND FOR INSTALLATION IN 18" RAISED FLOOR

• CONDENSATE PUMP, FACTORY INSTALLED

• FACTORY INSTALLED DISCONNECT SWITCH

• ELECTRICAL DATA: UNIT VOLTAGE: 460/3/60

• AIR RETURN TOP OPENING

• CHILLED WATER SUPPLY/RETURN CONNECTION SIZE: 1-5/8" O.D. (COPPER)

• INFRARED HUMIDIFIER CONNECTION SIZE: 1/4“ O.D. (COPPER)

• CONDENSATE DRAIN: 3/4" (NPTF)

• ELECTRIC REHEAT SECTION FOR DEHUMIDIFICATION

• SMOKE DETECTION SENSOR

• UNDERFLOOW WATER DETECTION SENSOR CABLE

• ELECTRONICALLY COMMUTATED (EC) DIRECT DRIVE VARIABLE SPEED FAN(S)

• EQUIPPED WITH:

o HUMIDITY SENSOR o TEMPERATURE SENSOR o DISPLAY WITH MENU DRIVEN VIEWING AND EDITING OF SET POINTS, OPERATIONAL STATUS, ALARM CONDITIONS.

• Unit Cabinet Dimensional Data o Length: 74” Maximum o Width: 35” Maximum o Height: 76” Maximum o Weight: 1,500 Lbs. Dry Weight Maximum