2220 Drawings.pdf
PDF 5 MB Posted
- Attached to
- Automatic Irrigation Improvement Project at the Brighton Dale Links Red Pine Golf Course
- Solicitation number
- 2220
- Issued by
- Kenosha County, Wisconsin
About this file
This is a technical specification document for an irrigation system upgrade project at Brighton Dale Links Golf Course in Kansasville, Wisconsin, prepared by Erik Christiansen Design Group, Ltd. for the County of Kenosha, Wisconsin. The project involves the installation of a comprehensive automatic irrigation system featuring 370 Toro turf sprinklers (various models including INF54-538-2, INF54-558-2, INF55-548-2, and INF55-578-2), 9 Toro G4 OSMAC Controllers with radio control capabilities, 1 wireless solar weather station, and central control software with support for two Apple iPads. The system requires approximately 25,466 linear feet of PVC Class 200 SDR21 irrigation lateral line and 13,329 linear feet of mainline pipe, along with 26 quick coupler valves, 58 isolation valves, 5 air/vacuum relief valves, and 3 drain/fill valves. The design specifies HDPE 4710 DR13.5 piping for main and lateral systems with connections to existing greens loops and mainlines at multiple field locations. The irrigation system is designed to achieve head-to-head coverage across all grassed and seeded areas on the golf course.
The specifications include detailed electrical requirements with 120 VAC primary power distribution via tray cable and 24 VAC secondary wiring to individual sprinkler heads, all requiring installation by licensed electricians in compliance with National Electrical Code requirements. Grounding and bonding requirements specify 6 AWG solid bare copper conductors, supplementary grounding electrodes, copper ground plates, and earth contact material to achieve maximum 10 ohms resistance. The contractor bears responsibility for proper equipment location as staked by the irrigation consultant, field adjustments to account for site conditions, thrust blocking or joint restraints at all pipe deflection points, and delivery of an operating schedule to the owner at no additional cost. All HDPE fittings must be fusion-compatible with no brand mixing allowed, and contractor equipment must be site-certified by the supplier. The plans note that all quantities are for reference only, with the contractor responsible for actual bid counts based on field conditions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Vendor Responsibility Form Construction.pdf | ||
| 2220 Addendum 1.pdf | ||
| 2220 Bid Documents.pdf | ||
| 2220 Specifications.pdf | ||
| 2220 Addendum 2.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LI-0
C O
V E
R
11/03/2022
B R
I G
H T
O N
D
A L
E
L
I N
K S
R
E
P
I N
E
K A
N S
A S
V I L
L E
W
I
IMPACT COVERAGE PLAN
DESCRIPTION
COVER
HYDRAULIC PIPING PLANLI-2
LI-1
LI-0
SHEET
BRIGHTON DALE LINKS - RED PINE
IRRIGATION CONSULTANT
ELECTRICAL SCHEMATIC PLANLI-3
SITE IRRIGATION PLANLI-4
IRRIGATION DETAILSLI-5
A S I C
PROFESSIONAL
IRRIGATION
CONSULTANT
AutoCAD SHX Text
ERIK CHRISTIANSEN DESIGN GROUP, LTD.
AutoCAD SHX Text
400 5TH STREET WEST DES MOINES, IOWA 50265-0036
AutoCAD SHX Text
PHONE (515) 225-6365
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REVISIONS:
AutoCAD SHX Text
SHEET #:
AutoCAD SHX Text
DRAWING TITLE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
FAX (515) 225-6366
AutoCAD SHX Text
NONE
AutoCAD SHX Text NOTE: 1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW OF THE ABOVE AND ANY OTHER PLANS THAT PERTAIN TO THE COORDINATION OF THE IRRIGATION CONSTRUCTION, WHETHER THEY BE NOTED OR NOT. 2. IRRIGATION PLANS AND SPECIFICATIONS ARE DIAGRAMMATIC IN NATURE AND ARE NOT A LIST OF INSTRUCTIONS FOR CONSTRUCTION, BUT RATHER TO ILLUSTRATE A DESIGN INTENT. THEREFORE ANY AND ALL CHANGES, CONFLICTS, DISCREPANCIES, OMISSIONS, AND QUESTIONS SHOULD BE BROUGHT TO THE ATTENTION OF THE SAID IRRIGATION CONSULTANT DURING THE BIDDING AND CONSTRUCTION PERIOD IN WRITING.
AutoCAD SHX Text
ERIK CHRISTIANSEN ASIC-PIC
PG
NG
SYMBOL MANUFACTURER/MODEL/DESCRIPTION QTY
Toro INF54-538-2 1-1/2" ACME inlet turf sprinkler, full circle, pressure regulation at 80psi, Spike Guard Solenoid
Toro INF54-558-2 1-1/2" ACME inlet turf sprinkler, full circle, pressure regulation at 80psi, Spike Guard Solenoid
Toro INF55-548-2 1-1/2" ACME inlet turf sprinkler, part-circle and full-circle in one, pressure regulation at 80psi, Spike Guard Solenoid
Toro INF55-578-2 1-1/2" ACME inlet turf sprinkler, part-circle and full-circle in one, pressure regulation at 80psi, Spike Guard Solenoid
SYMBOL MANUFACTURER/MODEL/DESCRIPTION QTY
Toro 474-00 One-Piece, 1" Single Lug Quick Coupler Valve with Standard Metal Cover.
RT/RW Isolation Valve (3" Laterals) 34
RT/RW Isolation Valve - Line Sized (Mains) 24
Bermad C30 Air/Vacuum Relief Valve
(5) To Be Field Located By Irrigation Consultant
Drain/Fill Valve 3
Toro G4-XXP6R4 Toro G4 OSMAC Controller w/ plastic green cabinet, radio control, large terminal block, switches, and premium surge - See plan for station counts.
Toro T107-SP-XXXX Wireless/Solar Weather Station - Actual Location By Owner
Toro LX-04-5-21 Toro Lynx Central Control Software w/ premium computer, (5) years NSN support, (2) Apple iPads w/ LifeProof Cases - Actual Location By Owner
Pump Station 1
Irrigation Lateral Line: PVC Class 200 SDR21 25,466 l.f.
Irrigation Mainline: PVC Class 200 SDR21 13,329 l.f.
120vac Power Wire Pair W/ Grn (Tray Cable) - As Per Local Codes
Irrigation Zone Limits
Note: All Quantities Are For Reference Only. Contractor Responsible For Actual Bid Counts.
A
D
X
XX
W
CC
P
LEGEND
SCALE: NOT TO SCALE
TYPICAL HOLE
XX
X
DESIGN NOTES
ELECTRICAL NOTES:
PLUMBING NOTES:
PROGRAMMING NOTES:
X
LI-1
I M
P A
T
V
E R
A G
E
P
L A
N
11/03/2022
B R
I G
H T
L
E
L
I N
N
E
K A
N S
A S
V I L
L E
W
I
NORTH
0 feet200
1" = 100'
100 300
AutoCAD SHX Text
AQUAFUSE 3" PE 360° BALLVALVE
AutoCAD SHX Text 3"
AutoCAD SHX Text 1" Q.C.V.
AutoCAD SHX Text
TEE SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
HDPE 4710 DR13.5 (UNLESS NOTED) LATERAL PIPING
AutoCAD SHX Text
FAIRWAY SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
GREENS SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
SURROUND SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
ALL PIPE HDPE 4710 DR13.5 (UNLESS NOTED)
AutoCAD SHX Text
AQUAFUSE 3" PE 360°BALL VALVE
AutoCAD SHX Text 3"
AutoCAD SHX Text
TORO OSMAC CONTROLLER - SEE PLAN FOR STATION COUNTS
AutoCAD SHX Text
120 V.A.C. TRAY CABLE POWER WIRE - SEE PLANS AND GROUNDING DETAIL
AutoCAD SHX Text
HDPE 4710 DR13.5 MAIN LINE PIPING
AutoCAD SHX Text 3"
AutoCAD SHX Text
AQUAFUSE 3" PE 360° BALLVALVE
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text 3"
AutoCAD SHX Text 2"
AutoCAD SHX Text
XX
AutoCAD SHX Text
1. ALL 120 V.A.C. POWER SPLICES AT FIELD SATELLITES. 2. ALL POWER WIRE TAPS AND CONNECTIONS SHALL CONFORM TO ALL LOCAL AND STATE CODES AND PERFORMED BY LICENSED ELECTRICIAN. 3. 24" LOOP OF WIRE LOCATED BELOW EACH HEAD. 4. ALL 24 V.A.C. SECONDARY WIRING SHALL BE (RED) #14 HOT AND (WHITE) #12 COMMON. (ONE HOT WIRE PER HEAD) 5. ALL WIRE SHALL HAVE ENOUGH SLACK AS TO ACCOMMODATE FOR EXPANSION AND/OR CONTRACTION. 6. ALL WIRE TO BE UL APPROVED FOR DIRECT BURIAL. 7. ALL 120 V.A.C. PRIMARY, AND 24 V.A.C. SECONDARY POWER TO BE INSTALLED AS PER STATE AND LOCAL CODES. SIZED AS PER PLAN WITH GROUND WIRE; MEETING N.E.C. REQUIREMENTS. 8. ONE SPARE HOT (#14) WIRE TO EACH GREEN AND TEE COMPLEX AND MARKED AS SPACE (BLUE IN COLOR).
AutoCAD SHX Text
1. FIELD SATELLITES SHALL CARRY APPROPRIATE STATION CARDS FOR INDIVIDUAL HEAD CONTROL OF ALL SPRINKLERS. 2. ALL SPRINKLERS SHALL HAVE ONE WIRE (HOT 24 V.A.C.) TO ONE WIRE (HOT 24 V.A.C.) TO (HOT 24 V.A.C.) TO RESPECTIVE FIELD SATELLITE. 3. ALL SATELLITE LOCATIONS SHALL BE IN ACCORDANCE WITH RAIN FALL SURVEYS AND OUT OF 100 YEAR FLOOD PLAIN.
AutoCAD SHX Text
1. ALL PRODUCT APPLICATIONS AND INSTALLATIONS MUST MEET MANUFACTURER'S REQUIREMENTS. 2. FLOW RATES THROUGH HDPE PIPING NOT TO EXCEED MANUFACTURER'S RECOMMENDATIONS. 3. PIPING AS SHOWN IS DIAGRAMMATIC IN NATURE. ALL PIPING TO BE LOCATED WITHIN OWNER'S PROPERTY LINES. 4. CONTRACTOR IS RESPONSIBLE FOR PROPER OPERATION OF IRRIGATION SYSTEM. SYSTEM SHALL NOT EXCEED MANUFACTURER'S RECOMMENDATIONS AND SHALL WATER ALL SEEDED AND SODDED AREAS NOTED. IRRIGATION PLAN IS INTENDED TO INCLUDE EVERYTHING NECESSARY TO THE PROPER OPERATION OF SAID IRRIGATION SYSTEM. IF ADJUSTMENTS ARE REQUIRED, CONTRACTOR SHALL MAKE ADJUSTMENTS FOR SAME. 5. IRRIGATION PLANS SHALL HAVE PRECEDENCE OVER IRRIGATION SPECIFICATIONS. ANY DISCREPANCIES BETWEEN THESE TWO DOCUMENTS MUST BE BROUGHT TO THE ATTENTION OF THE IRRIGATION CONSULTANT BEFORE INSTALLATION. 6. IT IS THE INTENT TO KEEP IRRIGATION WATER OFF OF ALL BUILDINGS, SIDEWALKS AND PARKING AREAS. IT WILL BE THE RESPONSIBILITY OF THE IRRIGATION CONTRACTOR TO FIELD TUNE EACH SPRINKLER AS TO KEEPING IRRIGATION ADJUSTED TO GRASSED AND SEEDED AREAS ONLY. IT WILL ALSO BE THE RESPONSIBILITY OF THE IRRIGATION CONTRACTOR TO SUPPLY THE OWNER WITH AN OPERATING SCHEDULE THAT WORKS WITH EXISTING PLANS AND ANY FIELD ADJUSTMENTS. 7. IT IS THE INTENT OF THE IRRIGATION DESIGN TO ACHIEVE HEAD TO HEAD COVERAGE IN ALL GRASSED AND SEEDED AREAS. IT WILL BE THE RESPONSIBILITY OF THE IRRIGATION CONTRACTOR TO ADJUST FOR SAME. 8. IRRIGATION PLANS ARE DIAGRAMMATIC IN NATURE CONTRACTOR WILL BE RESPONSIBLE FOR THE LOCATION OF ALL EQUIPMENT AS ALL EQUIPMENT AS EQUIPMENT AS STAKED BY IRRIGATION CONSULTANT. SAID EQUIPMENT, WHEN FIELD LOCATED, MAY VARY FROM PROPOSED PLAN DUE TO SITE CONDITIONS AND CONTRACTOR WILL MAKE ADJUSTMENTS ACCORDINGLY AT NO ADDITIONAL COST TO OWNER.NO ADDITIONAL COST TO OWNER. ADDITIONAL COST TO OWNER.
AutoCAD SHX Text
SATELLITE NUMBER
AutoCAD SHX Text
APPROXIMATE STATION COUNT
AutoCAD SHX Text
1. ALL HDPE FITTINGS SHALL BE FUSION COMPATIBLE AND HEAT FUSED WITH SPRINKLERS MOUNTED ON AQUAFUSE FUSIBLE SADDLES. NO BRAND MIXING ALLOWED AND CONTRACTOR/EQUIPMENT TO BE SITE CERTIFIED BY SUPPLIER AS SPECIFIED - NO EXCEPTIONS. 2. ALL PIPE SHALL BE CARRIED IN SEPARATE TRENCH.
AutoCAD SHX Text
ERIK CHRISTIANSEN DESIGN GROUP, LTD.
AutoCAD SHX Text
400 5TH STREET WEST DES MOINES, IOWA 50265-0036
AutoCAD SHX Text
PHONE (515) 225-6365
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REVISIONS:
AutoCAD SHX Text
SHEET #:
AutoCAD SHX Text
DRAWING TITLE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
FAX (515) 225-6366
1" = 100'-0"
PG
NG
TIE INTO EXISTING
GREENS LOOP -
CONFIRM ACTUAL
LOCATION IN FIELD
A
TIE INTO EXISTING
GREENS LOOP -
CONFIRM ACTUAL
LOCATION IN FIELD
D
D
D
4" STUB FOR
FUTURE DRIVING
RANGE IRRIGATION
3" STUB FOR
FUTURE DRIVING
RANGE IRRIGATION
P
TIE INTO WASH
PAD LINE
4" LINE FOR
MAINTENANCE
FACILITY W/ MIN. 36"
TOP COVER
4"
4"
8"
12" 10"
12"
4"
12"
12"
TIE INTO EXISTING
MAINLINE -
CONFIRM ACTUAL
LOCATION IN FIELD
TIE INTO EXISTING
GREENS LOOP -
CONFIRM ACTUAL
LOCATION IN FIELD
10" 8"
TIE INTO EXISTING
SPORTS COMPLEX
MAINLINE -
CONFIRM ACTUAL
LOCATION IN FIELD
4"
6" 8"
6"
6"
8"
4"
6"
4"
6"
6"
8"
TIE INTO EXISTING
MAINLINE -
CONFIRM ACTUAL
LOCATION IN FIELD
8"
8"
8"
8"
8"
8"
4" 8"
8"
4" LINE FOR
MAINTENANCE
FACILITY W/ MIN. 36"
TOP COVER
COORDINATE
MAINLINE ROUTING
WITH FUTURE
ARCHITECTURAL
CHANGES
4"
APPROXIMATE
FUTURE GREEN -
FOR REFERENCE
ONLY
SYMBOL MANUFACTURER/MODEL/DESCRIPTION QTY
Toro INF54-538-2 1-1/2" ACME inlet turf sprinkler, full circle, pressure regulation at 80psi, Spike Guard Solenoid
Toro INF54-558-2 1-1/2" ACME inlet turf sprinkler, full circle, pressure regulation at 80psi, Spike Guard Solenoid
Toro INF55-548-2 1-1/2" ACME inlet turf sprinkler, part-circle and full-circle in one, pressure regulation at 80psi, Spike Guard Solenoid
Toro INF55-578-2 1-1/2" ACME inlet turf sprinkler, part-circle and full-circle in one, pressure regulation at 80psi, Spike Guard Solenoid
SYMBOL MANUFACTURER/MODEL/DESCRIPTION QTY
Toro 474-00 One-Piece, 1" Single Lug Quick Coupler Valve with Standard Metal Cover.
RT/RW Isolation Valve (3" Laterals) 34
RT/RW Isolation Valve - Line Sized (Mains) 24
Bermad C30 Air/Vacuum Relief Valve
(5) To Be Field Located By Irrigation Consultant
Drain/Fill Valve 3
Toro G4-XXP6R4 Toro G4 OSMAC Controller w/ plastic green cabinet, radio control, large terminal block, switches, and premium surge - See plan for station counts.
Toro T107-SP-XXXX Wireless/Solar Weather Station - Actual Location By Owner
Toro LX-04-5-21 Toro Lynx Central Control Software w/ premium computer, (5) years NSN support, (2) Apple iPads w/ LifeProof Cases - Actual Location By Owner
Pump Station 1
Irrigation Lateral Line: PVC Class 200 SDR21 25,466 l.f.
Irrigation Mainline: PVC Class 200 SDR21 13,329 l.f.
120vac Power Wire Pair W/ Grn (Tray Cable) - As Per Local Codes
Irrigation Zone Limits
Note: All Quantities Are For Reference Only. Contractor Responsible For Actual Bid Counts.
A
D
X
XX
W
CC
P
LEGEND
SCALE: NOT TO SCALE
TYPICAL HOLE
XX
X
DESIGN NOTES
ELECTRICAL NOTES:
PLUMBING NOTES:
PROGRAMMING NOTES:
X
LI-2
H Y
D R
A U
L
P
I N
G
P
L A
N
11/03/2022
B R
I G
H T
L
E
L
I N
N
E
K A
N S
A S
V I L
L E
W
I
NORTH
0 feet200
1" = 100'
100 300
AutoCAD SHX Text
AQUAFUSE 3" PE 360° BALLVALVE
AutoCAD SHX Text 3"
AutoCAD SHX Text 1" Q.C.V.
AutoCAD SHX Text
TEE SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
HDPE 4710 DR13.5 (UNLESS NOTED) LATERAL PIPING
AutoCAD SHX Text
FAIRWAY SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
GREENS SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
SURROUND SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
ALL PIPE HDPE 4710 DR13.5 (UNLESS NOTED)
AutoCAD SHX Text
AQUAFUSE 3" PE 360°BALL VALVE
AutoCAD SHX Text 3"
AutoCAD SHX Text
TORO OSMAC CONTROLLER - SEE PLAN FOR STATION COUNTS
AutoCAD SHX Text
120 V.A.C. TRAY CABLE POWER WIRE - SEE PLANS AND GROUNDING DETAIL
AutoCAD SHX Text
HDPE 4710 DR13.5 MAIN LINE PIPING
AutoCAD SHX Text 3"
AutoCAD SHX Text
AQUAFUSE 3" PE 360° BALLVALVE
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text 3"
AutoCAD SHX Text 2"
AutoCAD SHX Text
XX
AutoCAD SHX Text
1. ALL 120 V.A.C. POWER SPLICES AT FIELD SATELLITES. 2. ALL POWER WIRE TAPS AND CONNECTIONS SHALL CONFORM TO ALL LOCAL AND STATE CODES AND PERFORMED BY LICENSED ELECTRICIAN. 3. 24" LOOP OF WIRE LOCATED BELOW EACH HEAD. 4. ALL 24 V.A.C. SECONDARY WIRING SHALL BE (RED) #14 HOT AND (WHITE) #12 COMMON. (ONE HOT WIRE PER HEAD) 5. ALL WIRE SHALL HAVE ENOUGH SLACK AS TO ACCOMMODATE FOR EXPANSION AND/OR CONTRACTION. 6. ALL WIRE TO BE UL APPROVED FOR DIRECT BURIAL. 7. ALL 120 V.A.C. PRIMARY, AND 24 V.A.C. SECONDARY POWER TO BE INSTALLED AS PER STATE AND LOCAL CODES. SIZED AS PER PLAN WITH GROUND WIRE; MEETING N.E.C. REQUIREMENTS. 8. ONE SPARE HOT (#14) WIRE TO EACH GREEN AND TEE COMPLEX AND MARKED AS SPACE (BLUE IN COLOR).
AutoCAD SHX Text
1. FIELD SATELLITES SHALL CARRY APPROPRIATE STATION CARDS FOR INDIVIDUAL HEAD CONTROL OF ALL SPRINKLERS. 2. ALL SPRINKLERS SHALL HAVE ONE WIRE (HOT 24 V.A.C.) TO ONE WIRE (HOT 24 V.A.C.) TO (HOT 24 V.A.C.) TO RESPECTIVE FIELD SATELLITE. 3. ALL SATELLITE LOCATIONS SHALL BE IN ACCORDANCE WITH RAIN FALL SURVEYS AND OUT OF 100 YEAR FLOOD PLAIN.
AutoCAD SHX Text
1. ALL PRODUCT APPLICATIONS AND INSTALLATIONS MUST MEET MANUFACTURER'S REQUIREMENTS. 2. FLOW RATES THROUGH HDPE PIPING NOT TO EXCEED MANUFACTURER'S RECOMMENDATIONS. 3. PIPING AS SHOWN IS DIAGRAMMATIC IN NATURE. ALL PIPING TO BE LOCATED WITHIN OWNER'S PROPERTY LINES. 4. CONTRACTOR IS RESPONSIBLE FOR PROPER OPERATION OF IRRIGATION SYSTEM. SYSTEM SHALL NOT EXCEED MANUFACTURER'S RECOMMENDATIONS AND SHALL WATER ALL SEEDED AND SODDED AREAS NOTED. IRRIGATION PLAN IS INTENDED TO INCLUDE EVERYTHING NECESSARY TO THE PROPER OPERATION OF SAID IRRIGATION SYSTEM. IF ADJUSTMENTS ARE REQUIRED, CONTRACTOR SHALL MAKE ADJUSTMENTS FOR SAME. 5. IRRIGATION PLANS SHALL HAVE PRECEDENCE OVER IRRIGATION SPECIFICATIONS. ANY DISCREPANCIES BETWEEN THESE TWO DOCUMENTS MUST BE BROUGHT TO THE ATTENTION OF THE IRRIGATION CONSULTANT BEFORE INSTALLATION. 6. IT IS THE INTENT TO KEEP IRRIGATION WATER OFF OF ALL BUILDINGS, SIDEWALKS AND PARKING AREAS. IT WILL BE THE RESPONSIBILITY OF THE IRRIGATION CONTRACTOR TO FIELD TUNE EACH SPRINKLER AS TO KEEPING IRRIGATION ADJUSTED TO GRASSED AND SEEDED AREAS ONLY. IT WILL ALSO BE THE RESPONSIBILITY OF THE IRRIGATION CONTRACTOR TO SUPPLY THE OWNER WITH AN OPERATING SCHEDULE THAT WORKS WITH EXISTING PLANS AND ANY FIELD ADJUSTMENTS. 7. IT IS THE INTENT OF THE IRRIGATION DESIGN TO ACHIEVE HEAD TO HEAD COVERAGE IN ALL GRASSED AND SEEDED AREAS. IT WILL BE THE RESPONSIBILITY OF THE IRRIGATION CONTRACTOR TO ADJUST FOR SAME. 8. IRRIGATION PLANS ARE DIAGRAMMATIC IN NATURE CONTRACTOR WILL BE RESPONSIBLE FOR THE LOCATION OF ALL EQUIPMENT AS ALL EQUIPMENT AS EQUIPMENT AS STAKED BY IRRIGATION CONSULTANT. SAID EQUIPMENT, WHEN FIELD LOCATED, MAY VARY FROM PROPOSED PLAN DUE TO SITE CONDITIONS AND CONTRACTOR WILL MAKE ADJUSTMENTS ACCORDINGLY AT NO ADDITIONAL COST TO OWNER.NO ADDITIONAL COST TO OWNER. ADDITIONAL COST TO OWNER.
AutoCAD SHX Text
SATELLITE NUMBER
AutoCAD SHX Text
APPROXIMATE STATION COUNT
AutoCAD SHX Text
1. ALL HDPE FITTINGS SHALL BE FUSION COMPATIBLE AND HEAT FUSED WITH SPRINKLERS MOUNTED ON AQUAFUSE FUSIBLE SADDLES. NO BRAND MIXING ALLOWED AND CONTRACTOR/EQUIPMENT TO BE SITE CERTIFIED BY SUPPLIER AS SPECIFIED - NO EXCEPTIONS. 2. ALL PIPE SHALL BE CARRIED IN SEPARATE TRENCH.
AutoCAD SHX Text
ERIK CHRISTIANSEN DESIGN GROUP, LTD.
AutoCAD SHX Text
400 5TH STREET WEST DES MOINES, IOWA 50265-0036
AutoCAD SHX Text
PHONE (515) 225-6365
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REVISIONS:
AutoCAD SHX Text
SHEET #:
AutoCAD SHX Text
DRAWING TITLE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
FAX (515) 225-6366
PG
NG
P
CC
W
CENTRAL, WEATHER
STATION, AND PUMP
STATION ANTENNAS -
ACTUAL LOCATION BY
OWNER
#6 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#6 PAIR
W/ GRN
#8 PAIR
W/ GRN
#6 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
SYMBOL MANUFACTURER/MODEL/DESCRIPTION QTY
Toro INF54-538-2 1-1/2" ACME inlet turf sprinkler, full circle, pressure regulation at 80psi, Spike Guard Solenoid
Toro INF54-558-2 1-1/2" ACME inlet turf sprinkler, full circle, pressure regulation at 80psi, Spike Guard Solenoid
Toro INF55-548-2 1-1/2" ACME inlet turf sprinkler, part-circle and full-circle in one, pressure regulation at 80psi, Spike Guard Solenoid
Toro INF55-578-2 1-1/2" ACME inlet turf sprinkler, part-circle and full-circle in one, pressure regulation at 80psi, Spike Guard Solenoid
SYMBOL MANUFACTURER/MODEL/DESCRIPTION QTY
Toro 474-00 One-Piece, 1" Single Lug Quick Coupler Valve with Standard Metal Cover.
RT/RW Isolation Valve (3" Laterals) 34
RT/RW Isolation Valve - Line Sized (Mains) 24
Bermad C30 Air/Vacuum Relief Valve
(5) To Be Field Located By Irrigation Consultant
Drain/Fill Valve 3
Toro G4-XXP6R4 Toro G4 OSMAC Controller w/ plastic green cabinet, radio control, large terminal block, switches, and premium surge - See plan for station counts.
Toro T107-SP-XXXX Wireless/Solar Weather Station - Actual Location By Owner
Toro LX-04-5-21 Toro Lynx Central Control Software w/ premium computer, (5) years NSN support, (2) Apple iPads w/ LifeProof Cases - Actual Location By Owner
Pump Station 1
Irrigation Lateral Line: PVC Class 200 SDR21 25,466 l.f.
Irrigation Mainline: PVC Class 200 SDR21 13,329 l.f.
120vac Power Wire Pair W/ Grn (Tray Cable) - As Per Local Codes
Irrigation Zone Limits
Note: All Quantities Are For Reference Only. Contractor Responsible For Actual Bid Counts.
A
D
X
XX
W
CC
P
LEGEND
SCALE: NOT TO SCALE
TYPICAL HOLE
XX
X
DESIGN NOTES
ELECTRICAL NOTES:
PLUMBING NOTES:
PROGRAMMING NOTES:
X
LI-3
E L
E C
T R
I C
L
H
E M
A T
I C
P L
A N
11/03/2022
B R
I G
H T
L
E
L
I N
N
E
K A
N S
A S
V I L
L E
W
I
NORTH
0 feet200
1" = 100'
100 300
AutoCAD SHX Text
AQUAFUSE 3" PE 360° BALLVALVE
AutoCAD SHX Text 3"
AutoCAD SHX Text 1" Q.C.V.
AutoCAD SHX Text
TEE SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
HDPE 4710 DR13.5 (UNLESS NOTED) LATERAL PIPING
AutoCAD SHX Text
FAIRWAY SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
GREENS SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
SURROUND SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
ALL PIPE HDPE 4710 DR13.5 (UNLESS NOTED)
AutoCAD SHX Text
AQUAFUSE 3" PE 360°BALL VALVE
AutoCAD SHX Text 3"
AutoCAD SHX Text
TORO OSMAC CONTROLLER - SEE PLAN FOR STATION COUNTS
AutoCAD SHX Text
120 V.A.C. TRAY CABLE POWER WIRE - SEE PLANS AND GROUNDING DETAIL
AutoCAD SHX Text
HDPE 4710 DR13.5 MAIN LINE PIPING
AutoCAD SHX Text 3"
AutoCAD SHX Text
AQUAFUSE 3" PE 360° BALLVALVE
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text 3"
AutoCAD SHX Text 2"
AutoCAD SHX Text
XX
AutoCAD SHX Text
1. ALL 120 V.A.C. POWER SPLICES AT FIELD SATELLITES. 2. ALL POWER WIRE TAPS AND CONNECTIONS SHALL CONFORM TO ALL LOCAL AND STATE CODES AND PERFORMED BY LICENSED ELECTRICIAN. 3. 24" LOOP OF WIRE LOCATED BELOW EACH HEAD. 4. ALL 24 V.A.C. SECONDARY WIRING SHALL BE (RED) #14 HOT AND (WHITE) #12 COMMON. (ONE HOT WIRE PER HEAD) 5. ALL WIRE SHALL HAVE ENOUGH SLACK AS TO ACCOMMODATE FOR EXPANSION AND/OR CONTRACTION. 6. ALL WIRE TO BE UL APPROVED FOR DIRECT BURIAL. 7. ALL 120 V.A.C. PRIMARY, AND 24 V.A.C. SECONDARY POWER TO BE INSTALLED AS PER STATE AND LOCAL CODES. SIZED AS PER PLAN WITH GROUND WIRE; MEETING N.E.C. REQUIREMENTS. 8. ONE SPARE HOT (#14) WIRE TO EACH GREEN AND TEE COMPLEX AND MARKED AS SPACE (BLUE IN COLOR).
AutoCAD SHX Text
1. FIELD SATELLITES SHALL CARRY APPROPRIATE STATION CARDS FOR INDIVIDUAL HEAD CONTROL OF ALL SPRINKLERS. 2. ALL SPRINKLERS SHALL HAVE ONE WIRE (HOT 24 V.A.C.) TO ONE WIRE (HOT 24 V.A.C.) TO (HOT 24 V.A.C.) TO RESPECTIVE FIELD SATELLITE. 3. ALL SATELLITE LOCATIONS SHALL BE IN ACCORDANCE WITH RAIN FALL SURVEYS AND OUT OF 100 YEAR FLOOD PLAIN.
AutoCAD SHX Text
1. ALL PRODUCT APPLICATIONS AND INSTALLATIONS MUST MEET MANUFACTURER'S REQUIREMENTS. 2. FLOW RATES THROUGH HDPE PIPING NOT TO EXCEED MANUFACTURER'S RECOMMENDATIONS. 3. PIPING AS SHOWN IS DIAGRAMMATIC IN NATURE. ALL PIPING TO BE LOCATED WITHIN OWNER'S PROPERTY LINES. 4. CONTRACTOR IS RESPONSIBLE FOR PROPER OPERATION OF IRRIGATION SYSTEM. SYSTEM SHALL NOT EXCEED MANUFACTURER'S RECOMMENDATIONS AND SHALL WATER ALL SEEDED AND SODDED AREAS NOTED. IRRIGATION PLAN IS INTENDED TO INCLUDE EVERYTHING NECESSARY TO THE PROPER OPERATION OF SAID IRRIGATION SYSTEM. IF ADJUSTMENTS ARE REQUIRED, CONTRACTOR SHALL MAKE ADJUSTMENTS FOR SAME. 5. IRRIGATION PLANS SHALL HAVE PRECEDENCE OVER IRRIGATION SPECIFICATIONS. ANY DISCREPANCIES BETWEEN THESE TWO DOCUMENTS MUST BE BROUGHT TO THE ATTENTION OF THE IRRIGATION CONSULTANT BEFORE INSTALLATION. 6. IT IS THE INTENT TO KEEP IRRIGATION WATER OFF OF ALL BUILDINGS, SIDEWALKS AND PARKING AREAS. IT WILL BE THE RESPONSIBILITY OF THE IRRIGATION CONTRACTOR TO FIELD TUNE EACH SPRINKLER AS TO KEEPING IRRIGATION ADJUSTED TO GRASSED AND SEEDED AREAS ONLY. IT WILL ALSO BE THE RESPONSIBILITY OF THE IRRIGATION CONTRACTOR TO SUPPLY THE OWNER WITH AN OPERATING SCHEDULE THAT WORKS WITH EXISTING PLANS AND ANY FIELD ADJUSTMENTS. 7. IT IS THE INTENT OF THE IRRIGATION DESIGN TO ACHIEVE HEAD TO HEAD COVERAGE IN ALL GRASSED AND SEEDED AREAS. IT WILL BE THE RESPONSIBILITY OF THE IRRIGATION CONTRACTOR TO ADJUST FOR SAME. 8. IRRIGATION PLANS ARE DIAGRAMMATIC IN NATURE CONTRACTOR WILL BE RESPONSIBLE FOR THE LOCATION OF ALL EQUIPMENT AS ALL EQUIPMENT AS EQUIPMENT AS STAKED BY IRRIGATION CONSULTANT. SAID EQUIPMENT, WHEN FIELD LOCATED, MAY VARY FROM PROPOSED PLAN DUE TO SITE CONDITIONS AND CONTRACTOR WILL MAKE ADJUSTMENTS ACCORDINGLY AT NO ADDITIONAL COST TO OWNER.NO ADDITIONAL COST TO OWNER. ADDITIONAL COST TO OWNER.
AutoCAD SHX Text
SATELLITE NUMBER
AutoCAD SHX Text
APPROXIMATE STATION COUNT
AutoCAD SHX Text
1. ALL HDPE FITTINGS SHALL BE FUSION COMPATIBLE AND HEAT FUSED WITH SPRINKLERS MOUNTED ON AQUAFUSE FUSIBLE SADDLES. NO BRAND MIXING ALLOWED AND CONTRACTOR/EQUIPMENT TO BE SITE CERTIFIED BY SUPPLIER AS SPECIFIED - NO EXCEPTIONS. 2. ALL PIPE SHALL BE CARRIED IN SEPARATE TRENCH.
AutoCAD SHX Text
ERIK CHRISTIANSEN DESIGN GROUP, LTD.
AutoCAD SHX Text
400 5TH STREET WEST DES MOINES, IOWA 50265-0036
AutoCAD SHX Text
PHONE (515) 225-6365
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REVISIONS:
AutoCAD SHX Text
SHEET #:
AutoCAD SHX Text
DRAWING TITLE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
FAX (515) 225-6366
PG
NG
TIE INTO EXISTING
GREENS LOOP -
CONFIRM ACTUAL
LOCATION IN FIELD
A
TIE INTO EXISTING
GREENS LOOP -
CONFIRM ACTUAL
LOCATION IN FIELD
D
D
D
4" STUB FOR
FUTURE DRIVING
RANGE IRRIGATION
3" STUB FOR
FUTURE DRIVING
RANGE IRRIGATION
P
CC
TIE INTO WASH
PAD LINE
W
CENTRAL, WEATHER
STATION, AND PUMP
STATION ANTENNAS -
ACTUAL LOCATION BY
OWNER
4" LINE FOR
MAINTENANCE
FACILITY W/ MIN. 36"
TOP COVER
4"
4"
8"
12" 10"
12"
4"
12"
12"
TIE INTO EXISTING
MAINLINE -
CONFIRM ACTUAL
LOCATION IN FIELD
TIE INTO EXISTING
GREENS LOOP -
CONFIRM ACTUAL
LOCATION IN FIELD
10" 8"
TIE INTO EXISTING
SPORTS COMPLEX
MAINLINE -
CONFIRM ACTUAL
LOCATION IN FIELD
4"
6" 8"
6"
6"
8"
4"
6"
4"
6"
6"
8"
TIE INTO EXISTING
MAINLINE -
CONFIRM ACTUAL
LOCATION IN FIELD
8"
8"
8"
8"
8"
8"
4" 8"
8"
#6 PAIR
W/ GRN
4" LINE FOR
MAINTENANCE
FACILITY W/ MIN. 36"
TOP COVER
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#6 PAIR
W/ GRN
#8 PAIR
W/ GRN
#6 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
#8 PAIR
W/ GRN
COORDINATE
MAINLINE ROUTING
WITH FUTURE
ARCHITECTURAL
CHANGES
4"
APPROXIMATE
FUTURE GREEN -
FOR REFERENCE
ONLY
SYMBOL MANUFACTURER/MODEL/DESCRIPTION QTY
Toro INF54-538-2 1-1/2" ACME inlet turf sprinkler, full circle, pressure regulation at 80psi, Spike Guard Solenoid
Toro INF54-558-2 1-1/2" ACME inlet turf sprinkler, full circle, pressure regulation at 80psi, Spike Guard Solenoid
Toro INF55-548-2 1-1/2" ACME inlet turf sprinkler, part-circle and full-circle in one, pressure regulation at 80psi, Spike Guard Solenoid
Toro INF55-578-2 1-1/2" ACME inlet turf sprinkler, part-circle and full-circle in one, pressure regulation at 80psi, Spike Guard Solenoid
SYMBOL MANUFACTURER/MODEL/DESCRIPTION QTY
Toro 474-00 One-Piece, 1" Single Lug Quick Coupler Valve with Standard Metal Cover.
RT/RW Isolation Valve (3" Laterals) 34
RT/RW Isolation Valve - Line Sized (Mains) 24
Bermad C30 Air/Vacuum Relief Valve
(5) To Be Field Located By Irrigation Consultant
Drain/Fill Valve 3
Toro G4-XXP6R4 Toro G4 OSMAC Controller w/ plastic green cabinet, radio control, large terminal block, switches, and premium surge - See plan for station counts.
Toro T107-SP-XXXX Wireless/Solar Weather Station - Actual Location By Owner
Toro LX-04-5-21 Toro Lynx Central Control Software w/ premium computer, (5) years NSN support, (2) Apple iPads w/ LifeProof Cases - Actual Location By Owner
Pump Station 1
Irrigation Lateral Line: PVC Class 200 SDR21 25,466 l.f.
Irrigation Mainline: PVC Class 200 SDR21 13,329 l.f.
120vac Power Wire Pair W/ Grn (Tray Cable) - As Per Local Codes
Irrigation Zone Limits
Note: All Quantities Are For Reference Only. Contractor Responsible For Actual Bid Counts.
A
D
X
XX
W
CC
P
LEGEND
SCALE: NOT TO SCALE
TYPICAL HOLE
XX
X
DESIGN NOTES
ELECTRICAL NOTES:
PLUMBING NOTES:
PROGRAMMING NOTES:
X
LI-4
S I T
E
I R
R I G
A T
I O
N
P
L A
N
11/03/2022
B R
I G
H T
L
E
L
I N
N
E
K A
N S
A S
V I L
L E
W
I
NORTH
0 feet200
1" = 100'
100 300
AutoCAD SHX Text
AQUAFUSE 3" PE 360° BALLVALVE
AutoCAD SHX Text 3"
AutoCAD SHX Text 1" Q.C.V.
AutoCAD SHX Text
TEE SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
HDPE 4710 DR13.5 (UNLESS NOTED) LATERAL PIPING
AutoCAD SHX Text
FAIRWAY SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
GREENS SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
SURROUND SPRINKLER NOZZLES AND SPACING SUBJECT TO CHANGE AS PER STAKING
AutoCAD SHX Text
ALL PIPE HDPE 4710 DR13.5 (UNLESS NOTED)
AutoCAD SHX Text
AQUAFUSE 3" PE 360°BALL VALVE
AutoCAD SHX Text 3"
AutoCAD SHX Text
TORO OSMAC CONTROLLER - SEE PLAN FOR STATION COUNTS
AutoCAD SHX Text
120 V.A.C. TRAY CABLE POWER WIRE - SEE PLANS AND GROUNDING DETAIL
AutoCAD SHX Text
HDPE 4710 DR13.5 MAIN LINE PIPING
AutoCAD SHX Text 3"
AutoCAD SHX Text
AQUAFUSE 3" PE 360° BALLVALVE
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text 3"
AutoCAD SHX Text 2"
AutoCAD SHX Text
XX
AutoCAD SHX Text
1. ALL 120 V.A.C. POWER SPLICES AT FIELD SATELLITES. 2. ALL POWER WIRE TAPS AND CONNECTIONS SHALL CONFORM TO ALL LOCAL AND STATE CODES AND PERFORMED BY LICENSED ELECTRICIAN. 3. 24" LOOP OF WIRE LOCATED BELOW EACH HEAD. 4. ALL 24 V.A.C. SECONDARY WIRING SHALL BE (RED) #14 HOT AND (WHITE) #12 COMMON. (ONE HOT WIRE PER HEAD) 5. ALL WIRE SHALL HAVE ENOUGH SLACK AS TO ACCOMMODATE FOR EXPANSION AND/OR CONTRACTION. 6. ALL WIRE TO BE UL APPROVED FOR DIRECT BURIAL. 7. ALL 120 V.A.C. PRIMARY, AND 24 V.A.C. SECONDARY POWER TO BE INSTALLED AS PER STATE AND LOCAL CODES. SIZED AS PER PLAN WITH GROUND WIRE; MEETING N.E.C. REQUIREMENTS. 8. ONE SPARE HOT (#14) WIRE TO EACH GREEN AND TEE COMPLEX AND MARKED AS SPACE (BLUE IN COLOR).
AutoCAD SHX Text
1. FIELD SATELLITES SHALL CARRY APPROPRIATE STATION CARDS FOR INDIVIDUAL HEAD CONTROL OF ALL SPRINKLERS. 2. ALL SPRINKLERS SHALL HAVE ONE WIRE (HOT 24 V.A.C.) TO ONE WIRE (HOT 24 V.A.C.) TO (HOT 24 V.A.C.) TO RESPECTIVE FIELD SATELLITE. 3. ALL SATELLITE LOCATIONS SHALL BE IN ACCORDANCE WITH RAIN FALL SURVEYS AND OUT OF 100 YEAR FLOOD PLAIN.
AutoCAD SHX Text
1. ALL PRODUCT APPLICATIONS AND INSTALLATIONS MUST MEET MANUFACTURER'S REQUIREMENTS. 2. FLOW RATES THROUGH HDPE PIPING NOT TO EXCEED MANUFACTURER'S RECOMMENDATIONS. 3. PIPING AS SHOWN IS DIAGRAMMATIC IN NATURE. ALL PIPING TO BE LOCATED WITHIN OWNER'S PROPERTY LINES. 4. CONTRACTOR IS RESPONSIBLE FOR PROPER OPERATION OF IRRIGATION SYSTEM. SYSTEM SHALL NOT EXCEED MANUFACTURER'S RECOMMENDATIONS AND SHALL WATER ALL SEEDED AND SODDED AREAS NOTED. IRRIGATION PLAN IS INTENDED TO INCLUDE EVERYTHING NECESSARY TO THE PROPER OPERATION OF SAID IRRIGATION SYSTEM. IF ADJUSTMENTS ARE REQUIRED, CONTRACTOR SHALL MAKE ADJUSTMENTS FOR SAME. 5. IRRIGATION PLANS SHALL HAVE PRECEDENCE OVER IRRIGATION SPECIFICATIONS. ANY DISCREPANCIES BETWEEN THESE TWO DOCUMENTS MUST BE BROUGHT TO THE ATTENTION OF THE IRRIGATION CONSULTANT BEFORE INSTALLATION. 6. IT IS THE INTENT TO KEEP IRRIGATION WATER OFF OF ALL BUILDINGS, SIDEWALKS AND PARKING AREAS. IT WILL BE THE RESPONSIBILITY OF THE IRRIGATION CONTRACTOR TO FIELD TUNE EACH SPRINKLER AS TO KEEPING IRRIGATION ADJUSTED TO GRASSED AND SEEDED AREAS ONLY. IT WILL ALSO BE THE RESPONSIBILITY OF THE IRRIGATION CONTRACTOR TO SUPPLY THE OWNER WITH AN OPERATING SCHEDULE THAT WORKS WITH EXISTING PLANS AND ANY FIELD ADJUSTMENTS. 7. IT IS THE INTENT OF THE IRRIGATION DESIGN TO ACHIEVE HEAD TO HEAD COVERAGE IN ALL GRASSED AND SEEDED AREAS. IT WILL BE THE RESPONSIBILITY OF THE IRRIGATION CONTRACTOR TO ADJUST FOR SAME. 8. IRRIGATION PLANS ARE DIAGRAMMATIC IN NATURE CONTRACTOR WILL BE RESPONSIBLE FOR THE LOCATION OF ALL EQUIPMENT AS ALL EQUIPMENT AS EQUIPMENT AS STAKED BY IRRIGATION CONSULTANT. SAID EQUIPMENT, WHEN FIELD LOCATED, MAY VARY FROM PROPOSED PLAN DUE TO SITE CONDITIONS AND CONTRACTOR WILL MAKE ADJUSTMENTS ACCORDINGLY AT NO ADDITIONAL COST TO OWNER.NO ADDITIONAL COST TO OWNER. ADDITIONAL COST TO OWNER.
AutoCAD SHX Text
SATELLITE NUMBER
AutoCAD SHX Text
APPROXIMATE STATION COUNT
AutoCAD SHX Text
1. ALL HDPE FITTINGS SHALL BE FUSION COMPATIBLE AND HEAT FUSED WITH SPRINKLERS MOUNTED ON AQUAFUSE FUSIBLE SADDLES. NO BRAND MIXING ALLOWED AND CONTRACTOR/EQUIPMENT TO BE SITE CERTIFIED BY SUPPLIER AS SPECIFIED - NO EXCEPTIONS. 2. ALL PIPE SHALL BE CARRIED IN SEPARATE TRENCH.
AutoCAD SHX Text
ERIK CHRISTIANSEN DESIGN GROUP, LTD.
AutoCAD SHX Text
400 5TH STREET WEST DES MOINES, IOWA 50265-0036
AutoCAD SHX Text
PHONE (515) 225-6365
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
REVISIONS:
AutoCAD SHX Text
SHEET #:
AutoCAD SHX Text
DRAWING TITLE:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
FAX (515) 225-6366
SCALE: NOT TO SCALE
CAST IRON VALVE DETAIL - MJ
SCALE: NOT TO SCALE
THRUST BLOCK
LARGE TURF GEARED ROTOR
SCALE: NOT TO SCALE
SCALE: NOT TO SCALE
QUICK-COUPLING VALVE
WITH STABILIZER - GREENS/TEES
SCALE: NOT TO SCALE
TRENCH CROSS SECTION
ROAD CROSSING DETAIL
SCALE: NOT TO SCALE
BRIDGE CROSSING DETAIL
SCALE: NOT TO SCALE
STREAM CROSSING DETAIL
SCALE: NOT TO SCALE
PEDESTAL-MOUNT CONTROLLER
R.F. SATELLITE
SCALE: NOT TO SCALE
R.F. WEATHER STATION
SCALE: NOT TO SCALE
LI-5
I R
R I G
A T
I O
N
D
E T
A I L
S
11/03/2022
B R
I G
H T
L
E
L
I N
N
E
K A
N S
A S
V I L
L E
W
I
AutoCAD SHX Text
VALVE BOX WITH COVER
AutoCAD SHX Text
PVC SLEEVE NOTCH PIPE TO FIT VALVE
AutoCAD SHX Text
GATE VALVE
AutoCAD SHX Text
PVC MAIN LINE PIPE
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text PIPE TO PIPE RESTRAINT, HARCO PT# 82xx15 OR EQUAL
AutoCAD SHX Text
PIPE SIZE
AutoCAD SHX Text 2"
AutoCAD SHX Text 2.5"
AutoCAD SHX Text 3"
AutoCAD SHX Text 4"
AutoCAD SHX Text 5"
AutoCAD SHX Text 8"
AutoCAD SHX Text 10"
AutoCAD SHX Text 12"
AutoCAD SHX Text 4.56
AutoCAD SHX Text 6.65
AutoCAD SHX Text 9.80
AutoCAD SHX Text 16.2
AutoCAD SHX Text 24.7
AutoCAD SHX Text 59.0
AutoCAD SHX Text 91.5
AutoCAD SHX Text 129.0
AutoCAD SHX Text
DEAD END OR TEE
AutoCAD SHX Text
90° ELBOW
AutoCAD SHX Text
45° ELBOW
AutoCAD SHX Text
22.5° ELBOW
AutoCAD SHX Text 1.5"
AutoCAD SHX Text 2.94
AutoCAD SHX Text 3.5"
AutoCAD SHX Text 12.8
AutoCAD SHX Text 6"
AutoCAD SHX Text 34.8
AutoCAD SHX Text 6.45
AutoCAD SHX Text 9.40
AutoCAD SHX Text 13.9
AutoCAD SHX Text 23.0
AutoCAD SHX Text 35.0
AutoCAD SHX Text 83.5
AutoCAD SHX Text 130.0
AutoCAD SHX Text 182.0
AutoCAD SHX Text 4.16
AutoCAD SHX Text 18.1
AutoCAD SHX Text 49.2
AutoCAD SHX Text 3.50
AutoCAD SHX Text 5.10
AutoCAD SHX Text 7.51
AutoCAD SHX Text 12.4
AutoCAD SHX Text 18.9
AutoCAD SHX Text 45.2
AutoCAD SHX Text 70.0
AutoCAD SHX Text 98.5
AutoCAD SHX Text 2.25
AutoCAD SHX Text 9.81
AutoCAD SHX Text 26.7
AutoCAD SHX Text 1.78
AutoCAD SHX Text 2.60
AutoCAD SHX Text 3.82
AutoCAD SHX Text 6.31
AutoCAD SHX Text 9.63
AutoCAD SHX Text 23.0
AutoCAD SHX Text 35.8
AutoCAD SHX Text 50.3
AutoCAD SHX Text 1.15
AutoCAD SHX Text 4.99
AutoCAD SHX Text 13.6
AutoCAD SHX Text
BASED ON POUNDS PER PSI WORKING PRESSURE.
AutoCAD SHX Text STEP 1. MULTIPLY THE PRESSURE LEVEL DESIRED FOR TESTING BY THE APPROPRIATE VALUE SHOWN IN THE FOLLOWING TABLE:
AutoCAD SHX Text
STEP 2. DETERMINE THE BEARING STRENGTH OF THE SOIL FROM THE TABLE BELOW:
AutoCAD SHX Text BEARING STRENGTH OF SOILS SOILS AND SAFE BEARING LOADS LBS. SQ. FT. SOUND SHALE CEMENTED GRAVEL AND SAND-DIFFICULT TO PICK COARSE AND FINE COMPACT SAND MEDIUM CLAY - CAN BE SPADED SOFT CLAY MUCK
AutoCAD SHX Text 10,000 4,000 3,000 2,000 1,000 0
AutoCAD SHX Text STEP 3. DIVIDE THE TOTAL THRUST OBTAINED IN STEP 1 BY THE BEARING STRENGTH OF THE SOIL: THIS GIVES THE SQUARE FEET OF AREA NEEDED.
AutoCAD SHX Text
THRUST BLOCKING
AutoCAD SHX Text AN OUTWARD PRESSURE EXISTS ON ALL DEFLECTIONS FROM A STRAIGHT LINE. GOOD SOIL, PROPERLY TAMPED, IS SUFFICIENT TO HOLD SIDE THRUST - UNLESS SOIL CONDITIONS ARE UNSTABLE. IN THAT CASE, TO ANCHOR AGAINST THIS SIDE THRUST, THE BLOCKING SHOULD BE PLACED AGAINST THE PIPE ON EACH SIDE OF THE COUPLING. DO NOT THRUST BLOCK THE COUPLING ITSELF.
AutoCAD SHX Text
SIDE THRUST ON CURVES
AutoCAD SHX Text
PIPE SIZE INCHES
AutoCAD SHX Text 2"
AutoCAD SHX Text 2.5"
AutoCAD SHX Text 3"
AutoCAD SHX Text 4"
AutoCAD SHX Text 5"
AutoCAD SHX Text 8"
AutoCAD SHX Text 10"
AutoCAD SHX Text 12"
AutoCAD SHX Text
SIDE THRUST POUNDS PER DEGREE
AutoCAD SHX Text 1.5"
AutoCAD SHX Text 3.5"
AutoCAD SHX Text 6"
AutoCAD SHX Text 7.9
AutoCAD SHX Text 11.6
AutoCAD SHX Text 17.1
AutoCAD SHX Text 28.3
AutoCAD SHX Text 43.1
AutoCAD SHX Text 103.0
AutoCAD SHX Text 160.0
AutoCAD SHX Text 225.0
AutoCAD SHX Text 5.1
AutoCAD SHX Text 22.4
AutoCAD SHX Text 60.8
AutoCAD SHX Text
BASED ON SIDE THRUST PER 100 LBS/SQUARE INCH PRESSURE PER DEGREE OF DEFLECTION
AutoCAD SHX Text NOTE: MULTIPLY SIDE THRUST POUNDS BY DEGREES OF DEFLECTION TIMES POUNDS OF PRESSURE DIVIDED BY 100 TO OBTAIN TOTAL SIDE THRUST IN POUNDS.
AutoCAD SHX Text NOTE: : ALL MAINLINE AND LATERAL CHANGE OF DIRECTION THAT ARE TRENCHED OR OPENED SHALL RECEIVE THRUST BLOCKING OR JOINT RESTRAINTS. - SEE THRUST BLOCKING TABLE FOR BEARING STRENGTH. FURTHERMORE ANY SOILS NOT STABLE FOR ADEQUATE THRUST BLOCKING, SAID FITTINGS MUST UTILIZE JOINT RESTRAINTS AT NO ADDITIONAL COST TO OWNER. IT IS ULTIMATELY THE CONTRACTORS RESPONSIBILITY TO INSTALL THE APPROPRIATE APPLICATION TO ENSURE THAT THE FITTING OR VALVE DOES NOT MOVE FROM A OUTWARD DEFLECTION.
AutoCAD SHX Text
ELL
AutoCAD SHX Text
CROSS
AutoCAD SHX Text
TEE
AutoCAD SHX Text
45° ELL
AutoCAD SHX Text
45° ELL
AutoCAD SHX Text
WYE
AutoCAD SHX Text
UNDISTURBED SOIL (TYPICAL)
AutoCAD SHX Text
CONCRETE THRUST BLOCK (TYPICAL)
AutoCAD SHX Text
FITTING (TYPICAL)
AutoCAD SHX Text
REBAR BENT AROUND FITTING (TYPICAL)
AutoCAD SHX Text
PIPE (TYPICAL)
AutoCAD SHX Text 30°-40°
AutoCAD SHX Text
LAY LENGTH AS PER LATERAL DEPTH AND MANUFACTURES INSTRUCTIONS
AutoCAD SHX Text
MANUFACTURED SWING JOINT (AS SPECIFIED)
AutoCAD SHX Text
APPROVED BACKFILL
AutoCAD SHX Text
NOTE: INSTALL SPRINKLER AT FINISHED GRADE
AutoCAD SHX Text
PRESSURIZED MAIN OR LATERAL PIPE
AutoCAD SHX Text
12" SWING (SIDE VIEW)
AutoCAD SHX Text
REGULATION
AutoCAD SHX Text
PRESSURE
AutoCAD SHX Text INSTALLATION NOTES: CUT PIPE END SQUARE AND BEVEL AT 15° TO 20° FOR PROPER INSERTING. MARK PIPE TO INDICATE PROPER INSERTION DEPTH. APPLY APPROVED PIPE LUBRICANT FROM END TO PIPE INSERTION DEPTH (REFERENCE MARK). INSERT PIPE INTO TAP'T COUPLING UNTIL MARK REACHES GASKET.
AutoCAD SHX Text
SWING JOINT
AutoCAD SHX Text
SWING JOINT IS REQUIRED TO HAVE THE "M" INLET CONNECTION (MALE ACME THREAD)
AutoCAD SHX Text SWING JOINT INSTALLATION NOTE: 1. ACME O-RING SEALED THREADS ARE TO BE FINGER TIGHTENED AND "BACKED OFF" ONE FULL ROTATION BEFORE INSTALLATION. 2. THE SWING JOINT LAY ARM IS TO BE INSTALLED AT AN ANGLE BETWEEN 30° AND 45°.
AutoCAD SHX Text NOTE: : FURNISH FITTINGS AND PIPING NOMINALLY SIZED IDENTICAL TO NOMINAL QUICK COUPLING VALVE INLET SIZE.
AutoCAD SHX Text
SCH. 80 NIPPLE (LENGTH AS REQUIRED)
AutoCAD SHX Text
QUICK COUPLER ANCHOR HARCO PT# 82202
AutoCAD SHX Text
MANUFACTURED SWING JOINT
AutoCAD SHX Text
PVC SCH. 40 TEE OR ELL
AutoCAD SHX Text
PVC MAINLINE PIPE
AutoCAD SHX Text
BRICK (1 OF 2)
AutoCAD SHX Text
3" MINIMUM DEPTH OF 3/4" WASHED GRAVEL
AutoCAD SHX Text
QUICK-COUPLING VALVE: INSTALLED AT HEIGHT TO ALLOW KEY HANDLE TO CLEAR BOX
AutoCAD SHX Text
FINISH GRADE
AutoCAD SHX Text
VALVE BOX WITH COVER
AutoCAD SHX Text
MIN.
AutoCAD SHX Text 2'-0"
AutoCAD SHX Text 2'-0"
AutoCAD SHX Text
MIN.
AutoCAD SHX Text
2'-0" MIN.
AutoCAD SHX Text SHIELDING THE BONDING CONDUCTORS ARE TO BE INSTALLED IN SUCH A WAY SO THAT THEY ALSO ACT AS SHIELDING CONDUCTORS. THIS BECOMES A NETWORK OF SOLID BARE COPPER WIRE OVER ALL THE MAIN BUNDLES OF OTHER WIRES AND CABLES AS SHOWN IN THE DETAIL.
AutoCAD SHX Text THE BARE WIRE IS TO BE INSTALLED AS CLOSE TO THE SURFACE AS POSSIBLE, YET BEING SUFFICIENTLY BELOW THE GROUND LEVEL AS TO PREVENT DAMAGE FROM MAINTENANCE EQUIPMENT SUCH AS AERATORS. AND IT MUST BE PLACED ABOVE ALL OTHER VALVE/ POWER/ COMMUNICATION WIRES AND CABLES, PER DETAIL, AND INSTALLED IN ALL TRENCHES AS SHOWN ON THE ELECTRICAL PLAN DRAWINGS. IT IS NOT NECESSARY TO INSTALL THIS CONDUCTOR OVER A SHORT WIRE RUNS (LESS THAN 150 FEET) AWAY FROM THE MAIN WIRE BUNDLES. THE CONDUCTOR IS LAID IN AS STRAIGHT A LINE AS POSSIBLE, AND WHEN NECESSARY TO MAKE BENDS, DO SO IN A SWEEPING MOTION USING THE FOLLOWING DETAIL AS A GUIDELINE.
AutoCAD SHX Text NOTE: WHEN CONNECTING BARE COPPER WIRES TO THE GROUND LUG OF ELECTRONIC EQUIPMENT, FEED IT THROUGH A DEDICATED 1 1/2" PLASTIC SWEEP DEDICATED 1 1/2" PLASTIC SWEEP SWEEP ELL TO AUTOMATICALLY MEET THE REQUIREMENTS OF THE "SWEEP BEND" SHOWN HERE.
AutoCAD SHX Text 90°
AutoCAD SHX Text
8" MINIMUM
AutoCAD SHX Text THE SHIELD NETWORK IS TO BE CONNECTED TO THE SERVICE ENTRANCE EARTH GROUND, TO ALL ELECTRONIC EQUIPMENT GROUND LUGS, AND ALL EQUIPMENT SUPPLEMENTARY GROUNDING ELECTRODES. ONE SUCH NETWORK IS NECESSARY FOR EACH POWER SOURCE. DO NOT INTERCONNECT THE EQUIPMENT GROUND WIRES FROM DIFFERENT POWER SOURCES.
AutoCAD SHX Text WHEN JOINING BARE COPPER WIRES, DO SO USING AN ERICO PG11L "ONE-SHOT" KIT AS SHOWN IN THE DETAILS. [PAIGE ELECTRIC PART NUMBER 1820074.]
AutoCAD SHX Text
WIRE STUB
AutoCAD SHX Text
STRAIGHT CONNECTION
AutoCAD SHX Text
90° ELL
AutoCAD SHX Text
TEE
AutoCAD SHX Text
CROSS
AutoCAD SHX Text
CADWELD PG11
AutoCAD SHX Text
SWEEP BEND
AutoCAD SHX Text DISCLAIMER: EC DESIGN GROUP, LTD. HAS MADE EVERY EFFORT TO ENSURE THAT THE INFORMATION EC DESIGN GROUP, LTD. HAS MADE EVERY EFFORT TO ENSURE THAT THE INFORMATION AND RECOMMENDATIONS CONTAINED WITHIN ARE CORRECT. HOWEVER, NEITHER EC DESIGN GROUP, LTD NOR ANY OF ITS EMPLOYEES WARRANTS NOR ACCEPTS ANY LIABILITY FOR THE USE OF THIS INFORMATION. NATIONAL AND LOCAL ELECTRICAL CODES SHOULD ALWAYS BE FOLLOWED. WIRING, GROUNDING, SHIELDING, AND BONDING IRRIGATION SYSTEMS COMPONENTS OFTEN REQUIRE COMPETENT ENGINEER JUDGMENT ON A CASE-BY-CASE BASIS. COMPETENT ENGINEERING ASSISTANCE SHOULD BE SOUGHT FROM FIRMS SPECIALIZING IN THIS FIELD.
AutoCAD SHX Text BONDING THE ABOVE GROUNDING CIRCUIT IS REFERRED-TO AS "SUPPLEMENTARY GROUNDING" IN THE NEC. AND FOR SAFETY REASONS, THE NEC REQUIRES THAT ALL SUPPLEMENTARY GROUNDS BE ALL SUPPLEMENTARY GROUNDS BE SUPPLEMENTARY GROUNDS BE "BONDED" TO EACH OTHER AND TO THE SERVICE ENTRANCE GROUND (POWER SOURCE) AS SHOWN IN THE DETAIL. THIS IS ALSO "RECOMMENDED PRACTICE " OF IEEE STANDARD 1100-1999. NOTE THAT THIS IS IN ADDITION TO THE EQUIPMENT GROUND, WHICH IS COMMONLY REFERRED-TO AS "THE GREEN WIRE." THE BLACK, WHITE AND GREEN WIRES MUST ALWAYS BE KEPT TOGETHER IN A TRENCH/CONDUIT/TRAY/ETC. SEE TRENCH DETAIL.
AutoCAD SHX Text THE BONDING CONDUCTORS ARE TO BE 6 AWG SOLID BARE COPPER UNLESS THE SYSTEM POWER CONDUCTORS ARE LARGER THAT 1/0 AWG, IN WHICH CASE THEY ARE TO BE 4 AWG SOLID BARE COPPER. ALL SPLICES TO THE BONDING CONDUCTORS SHALL BE MADE USING A CADWELD "ONE-SHOT" KIT AS SHOWN IN THE DETAILS. [PAIGE ELECTRIC PART NUMBER 1820074.]
AutoCAD SHX Text
FUSE OR CRKT. BRKR
AutoCAD SHX Text
GROUND BUS BAR
AutoCAD SHX Text
SERVICE ENTRANCE
AutoCAD SHX Text
POWER SOURCE FROM UTILITY COMPANY
AutoCAD SHX Text
IRRIGATION CONTROLLER
AutoCAD SHX Text
BLACK (LINE OR HOT)
AutoCAD SHX Text
WHITE (NEUTRAL)
AutoCAD SHX Text
GREEN OR BARE ( EQUIP. GRD)
AutoCAD SHX Text
BONDING CONDUCTOR
AutoCAD SHX Text
EARTH GROUND BY THE UTILITY COMPANY
AutoCAD SHX Text
SUPPLEMENTARY GROUND
AutoCAD SHX Text EARTH GROUNDING IT IS THE RESPONSIBILITY OF THE INSTALLER TO CONNECT ALL ELECTRONIC IRRIGATION EQUIPMENT FOR WHICH HE IS RESPONSIBLE TO EARTH IN ACCORDANCE WITH ARTICLE 250 OF THE NATIONAL ELECTRICAL CODE (NEC.) GROUNDING COMPONENTS WILL INCLUDE THE ITEMS DESCRIBED IN THE FOLLOWING PARAGRAPHS, AT A MINIMUM. USE GROUNDING ELECTRODES THAT ARE UL LISTED OR MANUFACTURED TO MEET THE MINIMUM REQUIREMENTS OF ARTICLE 250-52 OF THE 2002 EDITION OF THE NEC. AT THE VERY MINIMUM, THE GROUNDING CIRCUIT WILL INCLUDE A COPPER CLAD STEEL GROUND ROD, A SOLID COPPER GROUND PLATE AND 100 POUNDS OF POWERSET® EARTH CONTACT MATERIAL, AS DEFINED BELOW EARTH CONTACT MATERIAL, AS DEFINED BELOW AND PER THE FOLLOWING DETAIL.
AutoCAD SHX Text GROUND RODS ARE TO HAVE A MINIMUM DIAMETER OF 5/8" AND A MINIMUM LENGTH OF 10 FEET. THESE ARE TO BE DRIVEN INTO THE GROUND IN A VERTICAL POSITION OR AN OBLIQUE ANGLE NOT TO EXCEED 45 DEGREES AT A LOCATION 10 FEET FROM THE ELECTRONIC EQUIPMENT, THE GROUND PLATE, OR THE WIRES AND CABLES CONNECTED TO SAID EQUIPMENT, AS SHOWN IN THE DETAIL ABOVE. THE ROD IS TO BE STAMPED WITH THE UL LOGO [PAIGE ELECTRIC PART NUMBER 1820037.] A 6 AWG SOLID BARE COPPER WIRE (ABOUT 12 FEET LONG) SHALL BE CONNECTED TO THE ELECTRONIC EQUIPMENT GROUND LUG AS SHOWN IN THE DETAIL ABOVE.
AutoCAD SHX Text THE COPPER GROUNDING PLATE ASSEMBLIES [PAIGE ELECTRIC PART NUMBER 182199L] MUST MEET THE MINIMUM REQUIREMENTS OF ARTICLE 250-52(D) OF THE 1999 NEC. THEY ARE TO BE MADE OF A COPPER ALLOY INTENDED FOR GROUNDING APPLICATIONS AND WILL HAVE MINIMUM DIMENSIONS OF 4" X 96" X 0.0625". A 25-FOOT CONTINUOUS LENGTH (NO SPLICES ALLOWED UNLESS USING EXOTHERMIC WELDING PROCESS) OF 6 AWG SOLID BARE COPPER WIRE IS TO BE ATTACHED TO THE PLATE BY THE MANUFACTURER USING AN APPROVED WELDING PROCESS. THIS WIRE IS TO BE CONNECTED TO THE ELECTRONIC EQUIPMENT GROUND LUG AS SHOWN IN THE DETAIL. THE GROUND PLATE IS TO BE INSTALLED TO A MINIMUM DEPTH OF 30", AT A LOCATION 8 FEET FROM THE ELECTRONIC EQUIPMENT AND UNDERGROUND WIRES AND CABLES. TWO 50 - POUND BAGS OF POWERSET® [PAIGE ELECTRIC PART NUMBER 1820058] EARTH CONTACT MATERIAL [PAIGE ELECTRIC PART NUMBER 1820058] EARTH CONTACT MATERIAL MUST BE SPREAD SO THAT IT SURROUNDS THE COPPER PLATE EVENLY ALONG ITS LENGTH WITHIN A 6" WIDE TRENCH. SALTS, FERTILIZERS, BENTONITE CLAY, CEMENT, COKE, CARBON, AND OTHER CHEMICALS ARE NOT TO BE USED TO IMPROVE SOIL CONDUCTIVITY BECAUSE THESE MATERIALS ARE CORROSIVE AND WILL CAUSE THE COPPER ELECTRODES TO ERODE AND BECOME LESS EFFECTIVE WITH TIME. INSTALL ALL GROUNDING CIRCUIT COMMONEST IN STRAIGHT LINES. WHEN NECESSARY TO MAKE BENDS, DO NOT MAKE SHARP TURNS. TO PREVENT THE ELECTRODE-DISCHARGED ENERGY FROM REENTERING THE UNDERGROUND WIRES AND CABLES, ALL ELECTRODES SHALL BE INSTALLED AWAY FROM SAID WIRES AND CABLES. THE SPACING BETWEEN ANY TWO ELECTRODES SHALL BE AS SHOWN IN THE DETAIL OF PAGE 1, SO THAT THEY DON'T COMPETE FOR THE SAME SOIL. THE EARTH-TO-GROUND RESISTANCE OF THIS CIRCUIT TO BE MEASURED USING A MEGGER®, OR OR OTHER SIMILAR INSTRUMENTS, AND THE READING IS TO BE NO MORE THAT 10 OHMS. IF THE RESISTANCE IS MORE THAN 10 OHMS, ADDITIONAL GROUND PLATES AND THE SOIL SURROUNDING COPPER ELECTRODES BE KEPT AT A MINIMUM MOISTURE LEVEL OF 15% AT ALL TIMES BY DEDICATING AN IRRIGATION STATION AT EACH CONTROLLER LOCATION. THE IRRIGATED AREA SHOULD INCLUDE A CIRCLE WITH A 10-FOOT RADIUS AROUND THE GROUND ROD AND A RECTANGLE MEASURING 1-FOOT X 24-FEET AROUND THE PLATE. ALL UNDERGROUND CIRCUIT CONNECTIONS ARE TO BE MADE USING AN EXOTHERMIC WELDING PROCESS BY UTILIZING PRODUCTS SUCH AS THE CADWELD "ONE-SHOT" KITS. SOLDER SHALL NOT BE ALLOWED TO MAKE CONNECTIONS. IN ORDER TO ENSURE PROPER IGNITION OF THE "ONE-SHOT", THE CADWELD T-320 IGNITER MUST BE UTILIZED [PAIGE ELECTRIC PART NUMBER 1820040.] THE 6 AWG BARE COPPER WIRES ARE TO BE INSTALLED IN AS STRAIGHT A LINE AS POSSIBLE, AND IF IT IS NECESSARY TO MAKE A TURN OR A BEND IT SHALL BE DONE IN A SWEEPING CURVE WITH A MINIMUM RADIUS OF 8" AND A MINIMUM INCLUDED ANGLE OF 90°. MECHANICAL CLAMPS SHALL BE PERMITTED TEMPORARILY DURING THE RESISTANCE TEST PROCESS, BUT ARE TO BE REPLACED WITH CADWELD "ONE-SHOT" KITS IMMEDIATELY THEREAFTER.
AutoCAD SHX Text
CONTROLLER
AutoCAD SHX Text
CONCRETE PAD
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text 2'-6"
AutoCAD SHX Text
6 AWG SOLID BARE COPPER WIRES
AutoCAD SHX Text
COPPER GROUND PLATE
AutoCAD SHX Text
GROUND ROD
AutoCAD SHX Text
EARTH CONTACT MATERIAL
AutoCAD SHX Text
CADWELD CONNECTION
AutoCAD SHX Text
DEDICATED PLASTIC SWEEP ELL (1 1/2" OR LARGER)
AutoCAD SHX Text 11'-0"
AutoCAD SHX Text 10'-0"
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text C
AutoCAD SHX Text
6 AWG SOLID BARE COPPER WIRES
AutoCAD SHX Text
GROUND ROD 58" X 10'-0"
AutoCAD SHX Text
COPPER GROUND PLATE 4" X 8'-0"
AutoCAD SHX Text
TOP VIEW
AutoCAD SHX Text
SIDE VIEW
AutoCAD SHX Text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
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text
MIN.
AutoCAD SHX Text
SEE SPECS
AutoCAD SHX Text MIN. 6 AWG SHIELDING WIRE (SOLID BARE COPPER) SOLID BARE COPPER) BARE COPPER) - SEE SPEC
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text
MIN.
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
COMMUNICATION CABLE - AS REQUIRED AND AS PER MANUFACTURES RECOMMENDATIONS
AutoCAD SHX Text NOTE: MIN. VALVE WIRES SEPARATION FROM ALL COMMUNICATION CABLE - AS REQUIRED. COMM. CABLES AS PER MANUFACTURES RECOMMENDATIONS.
AutoCAD SHX Text
SEE SPECS
AutoCAD SHX Text
POWER WARNING TAPE
AutoCAD SHX Text POWER CABLE - MIN. WIRE SEPARATION FROM ALL COMMUNICATION AND SECONDARY WIRING (AS APPLICABLE).
AutoCAD SHX Text MIN. OF 1-0" IN DEPTH OR DEEP ENOUGH TO PREVENT DAMAGE FROM MAINTENANCE EQUIPMENT.
AutoCAD SHX Text
AS PER N.E.C. CODE
AutoCAD SHX Text
SPHERE OF INFLUENCE
AutoCAD SHX Text NOTES: 1. CONNECT ALL 6 AWG WIRES INSIDE THE CONTROLLER. CONNECT ONE WIRE TO THE CONTROLLER GROUND LUG AND USE A #4 SPLIT BOLT TO CONNECT ALL WIRES TOGETHER. 2. MAKE SURE THAT THE EARTH CONTACT MATERIAL COMPLETELY COVERS THE WELD JOINT OF THE GROUND PLATE. THE GREEN/YELLOW WIRE INSULATION SHOULD BE COVERED BY THE EARTH CONTACT MATERIAL.
AutoCAD SHX Text NOTE: : ALL 120 V.A.C AND 24 V.A.C. SHALL BE CARRIED IN SEPARATE PVC CLASS 315 SLEEVES. ALL SLEEVES SHALL BE INSTALLED AS PER LOCAL, STATE AND FEDERAL CODES.
AutoCAD SHX Text NOTE: : ALL STREAM CROSSINGS SHALL BE PERFORMED IN ACCORDANCE WITH ALL GOVERNING BODIES. CONTRACTOR WILL ALL GOVERNING BODIES. CONTRACTOR WILL GOVERNING BODIES. CONTRACTOR WILL BE RESPONSIBLE FOR ALL COSTS INCURRED AS THEY PERTAIN TO SAID CROSSINGS.
AutoCAD SHX Text
FLANGE SIZE AS PER PVC PIPING
AutoCAD SHX Text
FLANGE SIZE AS PER PVC PIPING
AutoCAD SHX Text
PREFABRICATED STEEL, OR YELLOW MINE PIPING
AutoCAD SHX Text
STAINLESS STEEL HANGERS AT 2'-0" O.C. OR AS REQUIRED FOR ENGINEERED WEIGHT LOAD
AutoCAD SHX Text
FLANGE SIZE AS PER PVC PIPING
AutoCAD SHX Text
FLANGE SIZE AS PER PVC PIPING
AutoCAD SHX Text
PREFABRICATED STEEL, HDPE DR11, OR YELLOW MINE PIPING.
AutoCAD SHX Text
PVC MAIN
AutoCAD SHX Text
PVC MAIN
AutoCAD SHX Text
CAST IRON TO PVC MECHANICAL JOINT
AutoCAD SHX Text
FLANGE/GASKET JOINT
AutoCAD SHX Text
STREET
AutoCAD SHX Text
CLASS 50 OR 51 DUCTILE IRON PIPE
AutoCAD SHX Text MIN. 6 AWG SHIELDING WIRE (SOLID BARE COPPER) SOLID BARE COPPER) BARE COPPER) - SEE SPEC
AutoCAD SHX Text
PIPE
AutoCAD SHX Text
COMMUNICATION CABLE - AS REQUIRED AND AS PER MANUFACTURES RECOMMENDATIONS
AutoCAD SHX Text NOTE: MIN. VALVE WIRES SEPARATION FROM ALL COMMUNICATION CABLE - AS REQUIRED. COMM. CABLES AS PER MANUFACTURES RECOMMENDATIONS.
AutoCAD SHX Text
POWER WARNING TAPE
AutoCAD SHX Text
POWER CABLE - MIN. WIRE SEPARATION FROM ALL COMMUNICATION AND SECONDARY WIRING.
AutoCAD SHX Text MIN. OF 1-0" IN DEPTH OR DEEP ENOUGH TO PREVENT DAMAGE FROM MAINTENANCE EQUIPMENT.
AutoCAD SHX Text
VALVE BOX WITH LID/GRATE
AutoCAD SHX Text
CONNECTION LOCATED IN VALVE BOX
AutoCAD SHX Text
CONNECTION LOCATED IN VALVE BOX
AutoCAD SHX Text
SECTION/ELEVATION
AutoCAD SHX Text
SEE SPECS.
AutoCAD SHX Text
SEE SPECS.
AutoCAD SHX Text
FRONT
AutoCAD SHX Text 6"
AutoCAD SHX Text
CONDUIT FOR GROUND
AutoCAD SHX Text
SECTION/ELEVATION
AutoCAD SHX Text
RIGHT-SIDE
AutoCAD SHX Text 6"
AutoCAD SHX Text
FINISHED SURFACE
AutoCAD SHX Text
6" MIN.
AutoCAD SHX Text
CONDUIT FOR VALVE
AutoCAD SHX Text
WIRES
AutoCAD SHX Text
CONCRETE FOOTING
AutoCAD SHX Text
SLOPE TO DRAIN (1/2" SLOPE MIN.)
AutoCAD SHX Text
IRRIGATION CONTROLLER
AutoCAD SHX Text
SEE PLAN FOR NUMBER
AutoCAD SHX Text
OF STATIONS.
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
MIN.
AutoCAD SHX Text
MIN.
AutoCAD SHX Text
MIN.
AutoCAD SHX Text
MIN.
AutoCAD SHX Text
CONDUIT FOR SUMP
AutoCAD SHX Text
GRAVEL SUMP
AutoCAD SHX Text 115V CONDUIT WITH CONDUCTORS PER LOCAL & NATIONAL ELECTRICAL CODES - BY LICENSED ELECTRICIAN
AutoCAD SHX Text
SOLAR POWERED
AutoCAD SHX Text
R.F. ANTENNA FROM WEATHER STATION TO CENTRAL LOCATION (MAINT. BLDG.)
AutoCAD SHX Text
GROUNDING DEVICE TO PROVIDE 10 OHMS RESISTANCE. SEE GROUNDING PLATE DETAIL.
AutoCAD SHX Text SHORTER THAN 20-FOOT DISTANCES... WHEN THE DISTANCE BETWEEN A RESTRAINED FITTING TO THE NEXT JOINT IS LESS THAN 20 FEET, THE ABOVE RECOMMENDATIONS ARE NO LONGER VALID. ONE MUST REFER TO THE FOLLOWING TABLE THAT LISTS THE LENGTH (IN FEET) FOR EACH SIZE/TYPE FITTING WITHIN WHICH ALL JOINTS MUST BE RESTRAINED.