21-123_BMS-0_to18_Rev3.pdf

PDF 5 MB Posted

Attached to
Submersible Pumps and Control Panel for LS# 74
Solicitation number
PSUT-2026-QQ-02
Issued by
Broward County, Florida

About this file

This is a specification document for the City of Pembroke Pines, Florida, detailing replacement equipment requirements for Lift Station #74's pump system. The solicitation requests quotes for two submersible pumps and a control panel that must include a Hydralink PLC and Blue Ribbon transducer in accordance with City standards. The scope of work references standard 11310 for submersible pump requirements and specifies that all equipment must comply with Davis-Bacon wage requirements under the posted wage determination FL20250197. Quotes are due June 25, 2026. The place of performance is Lift Station #74 located in Pembroke Pines, Broward County, Florida. No specific contract term, renewal options, or award date is indicated in the available documentation.

The solicitation imposes prevailing wage obligations and HUD Section 3 community-hiring requirements on prospective bidders. Specimen construction and contractual services agreements, along with insurance and lien-release templates, are provided to establish contract terms and bonding expectations. No contract value, incumbent vendor information, or evaluation criteria weighting is specified. Prospective bidders are required to familiarize themselves with all labor standards and prevailing wage obligations prior to submission. Detailed specifications are contained in the primary solicitation document (Submersible_Pumps_and_Control_Panel_for_LS#_74.pdf), with supporting exhibits and contract templates available for review.

View the file

Other files

File Type Posted
Submersible_Pumps_and_Control_Panel_for_LS#_74.pdf PDF
Submersible_Pumps_and_Control_Panel_for_LS#_74.pdf PDF
Submersible_Pumps_and_Control_Panel_for_LS#_74.pdf PDF
Specimen_Contract_Contractual_Services_Agreement.pdf PDF
Standard_Release_of_Lien.pdf PDF
Specimen_Contract_Contractual_Services_Agreement.pdf PDF
Specimen_Contract_Contractual_Services_Agreement.pdf PDF
Standard_Release_of_Lien.pdf PDF
Standard_Release_of_Lien.pdf PDF
21-123_BMS-0_to18_Rev3.pdf PDF
Sample_Insurance_Certificate.pdf PDF
Sample_Insurance_Certificate.pdf PDF
11310_-_Submersible_Pumps.pdf PDF
21-123_BMS-0_to18_Rev3.pdf PDF
Sample_Insurance_Certificate.pdf PDF
11310_-_Submersible_Pumps.pdf PDF
11310_-_Submersible_Pumps.pdf PDF
HUD's_Davis-Bacon_and_Labor_Standards_Contractor_Guide_Addendum.pdf PDF
HUD's_Davis-Bacon_and_Labor_Standards_Contractor_Guide_Addendum.pdf PDF
HUD's_Davis-Bacon_and_Labor_Standards_Contractor_Guide_Addendum.pdf PDF
HUD_Section_3_Implementation_Plan_and_Forms_1-6.pdf PDF
Specimen_Contract_-_Contractual_Services_Agreement.pdf PDF
HUD_Section_3_Implementation_Plan_and_Forms_1-6.pdf PDF
INTERNAL_GUIDANCE_FOR_DAVIS-BACON_WAGE_DECISIONS.docx DOCX document
SAMPLE_-_Davis-Bacon_Wage_Determination_(FL20250197_-_2025-07-04).pdf PDF
Specimen_Contract_-_Contractual_Services_Agreement.pdf PDF
INTERNAL_GUIDANCE_FOR_DAVIS-BACON_WAGE_DECISIONS.docx DOCX document
SAMPLE_-_Davis-Bacon_Wage_Determination_(FL20250197_-_2025-07-04).pdf PDF
Specimen_Contract_-_Construction_Agreement.pdf PDF
Specimen_Contract_-_Contractual_Services_Agreement.pdf PDF
Specimen_Contract_-_Professional_Services_(CCNA_Non-Continuing_Services).pdf PDF
HUD_Section_3_Implementation_Plan_and_Forms_1-6.pdf PDF
INTERNAL_GUIDANCE_FOR_DAVIS-BACON_WAGE_DECISIONS.docx DOCX document
Specimen_Contract_-_Professional_Services_(CCNA_Non-Continuing_Services).pdf PDF
Specimen_Contract_-_Professional_Services_(CCNA_Non-Continuing_Services).pdf PDF
SAMPLE_-_Davis-Bacon_Wage_Determination_(FL20250197_-_2025-07-04).pdf PDF
Specimen_Contract_-_Construction_Agreement.pdf PDF
Specimen_Contract_-_Construction_Agreement.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. ALL PRE-WIRED CONTROL PANELS SHALL BE U.L. LISTED AND LABELED, PRIOR

TO INSTALLATION.

2. ENCLOSURE MUST BE NEMA 3RX 304 SS WITH SUBPANEL AND INNER DOOR.

3. PANEL MUST INCLUDE DRIP SHIELD.

4. PANEL MUST BE PROVIDED WITH TEMPERATURE CONTROL.

5. USE CONDUIT HUBS WITH THE SAME ENVIRONMENTAL RATING AS ENCLOSURE

6. PANEL MUST INCLUDE ALL ELEMENTS DESCRIBED IN WIRING DIAGRAM SIZED

FOR THE CORRESPONDING SERVICE AND PUMP SIZE.

7. AMPS INTERRUPTING CAPACITY NOTED ON SCHEDULE

8. GENERATOR RECEPTACLE MUST INCLUDE REVERSED CONTACTS. MUST BE

ASSEMBLED WITH PLUG INTERIOR (EXPOSED CONTACTS) PLUG ASSEMBLED

WITH RECEPTACLE INTERIOR (RECESSED CONTACTS) FOR APPLICATIONS

WHERE PLUG IS ENERGIZED TO FEED NORMALLY DE-ENERGIZED RECEPTACLE.

(S22 OPTION ADDED TO MODEL IN SCHEDULE).

9. SUPPORT RACK DETAIL AND MATERIALS OF CONSTRUCTION BY OTHERS

10. SERVICE AND METER ATTACHED TO BACK SIDE OF PUMP STATION CONTROL

CENTER (WHEN APPLICABLE.)

11. ALL ELECTRICAL EQUIPMENT AND APPURTENANCES ARE IN COMPLIANCE WITH

N.E.C. 110-16.

12. PUMP STATION MUST BE SUPPLIED WITH A REMOTE-TELEMETRY MONITORING

UNIT R.T.U. THAT ALLOWS REMOTE MONITORING OF PUMPS' STATUS, LAG

ALARM, HIGH ALARM, AND POWER FAILURE. R.T.U. EQUIPPED WITH A BATTERY

BACK UP AND must be INSTALLED ABOVE THE 100 YEAR FLOOD ELEVATION.

13. THE DESIGN, SUBMITTAL, SUPPLY, SIZING, AND INSTALLATION OF ALL INCOMING

POWER FEEDS, GROUNDING, AND GROUNDING CONDUCTORS ARE TO BE

PROVIDED BY OTHERS; AND ARE REQUIRED TO COMPLY WITH THE NATIONAL

ELECTRIC CODE AND ALL OTHER LOCAL BUILDING CODES.

GENERAL NOTES

LEGENDS

AH ALARM HORN

AL ALARM LIGHT

AS ALTERNATING SWITCH

CB CIRCUIT BREAKER

DS DOOR SWITCH

ETM ELAPSED TIME METER

FU FUSE

HTE HEATING ELEMENT

LF LIGHT FIXTURE

MC MODBUS CONVERTER

MI MECHANICAL INTERLOCK

MR MODBUS RELAY

MS MOTOR STARTER

PB PUSHBUTTON

PDB POWER DISTRIBUTION BLOCK

PL PILOT LIGHT

PS POWER SUPPLY

R RELAY

RC RECEPTACLE

SLPD SURGE LIGHTING PROTECTION DEVICE

SS SELECTOR SWITCHT

TS TEMPERATURE SWITCH

VM VOLTAGE MONITOR

XF TRANSFORMER

D-00 COVER PAGE

D-01 ENCLOSURE DETAIL (FOR SITES WITH PUMPS LESS THAN 15 HP)

D-02 ENCLOSURE DETAIL (FOR SITES WITH PUMPS 15 HP OR HIGHER)

D-03 SUB-PANEL LAYOUT (FOR SITES WITH PUMPS LESS THAN 15 HP)

D-04 SUB-PANEL LAYOUT (FOR SITES WITH PUMPS 15 HP OR HIGHER)

D-05 NAMEPLATE DETAIL

D-06 POWER CIRCUIT, DC CIRCUIT (FOR SITES WITH PUMPS LESS THAN 15 HP)

D-07 POWER CIRCUIT, DC CIRCUIT (FOR SITES WITH PUMPS 15 HP OR HIGHER)

D-08 ALARM AND CONTROL CIRCUITS (FOR SITES WITH PUMPS LESS THAN 15 HP)

D-09 ALARM AND CONTROL CIRCUITS (FOR SITES WITH PUMPS 15 HP OR HIGHER)

D-10 LEVEL TRANSDUCER & FLOAT BACKUP CIRCUIT

D-11 HYDRALINK PLC I/O (FOR SITES WITH PUMPS LESS THAN 15 HP)

D-12 HYDRALINK PLC I/ O (FOR SITES WITH PUMPS 5 HP OR HIGHER)

D-13 HYDRALINK PLC I/O& HYDRALINK MODEM CIRCUIT

D-14 BLANK SPACE FOR FUTURE SOFT STARTERS PUMPS LESS THAN 15 H.P.

D-15 SOFT STARTER CIRCUITS (FOR SITES WITH PUMPS 15 HP OR HIGHER)

D-16 HYDRALINK ANALOG INPUT /OUTPUT MODULE

D-17 BILL OF MATERIALS

D-18 PART NUMBERS AND WIRE SIZING

DRAWING INDEX

No. :

Pag No. :

D - 00 0 of 18Rev No. Fecha Descripcion

0 04-28-22 Preliminary DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S MAY 2025

M.C.M 21-123

21-123-BMS-1-R2.DWGCOVER PAGE

LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

CITY OF PEMBROKE PINES1 08-28-22 PLC Control

LIFT STATIONS (DUPLEX SUBMERSIBLE)

- CONTROL PANEL CITY STANDARD -

CITY OF PEMBROKE PINES

2 10-27-23 Owner's Review 3 05-15-25 Float Review

3'

VENTILATION

HOOD WITH FILTER

ENCLOSURE NEMA 3R

PAINTED WHITE

REC-101

GENERATOR RECEPTACLE

WITH COVER AND ANGLE

ADAPTER (SEE NOTE 8)C

O N

TR

O

L

PO

W

ER

R

EC

PT

A

C

LE

PUMP No.1 PUMP No. 2

PUMP No.1 PUMP No. 2

RESET FLOAT

CONTROL

OFF

HAND AUTO

OFF

HAND AUTO

PUMP 1

RUNNING

PUMP 2

RUNNING

PUMP 1

FAULT

CAUTION:

RUN ONLY ONE PUMP ON

GENERATOR SERVICE

1'-4" DRIP

SHIELD

4'

CELL MODEM ANTENNA

FIELD MOUNTED

MAIN

POWER

GENERATOR

POWER

CONTROL

POWER ON

PUMP 2

FAULT

RUNNING ON

FLOAT CONTROL

7" TOUCHSCREEN

DISPLAY

ALL SHOWN DEVICES

LOCATED ON ENCLOSURE

INNER DOOR

AL205 GENERAL ALARM

FIELD MOUNTED

ALARM HORN

SILENCE

PB207

AH208

No. :

Pag No. :

D - 01 1 of 18Rev No. Fecha Descripcion

0 04-28-22 Preliminary DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S OCT. 2023

M.C.M 21-123

21-123-BMS-1-R2.DWG

1 08-28-22 PLC Control 2 10-27-23 Owner's Review

ENCLOSURE DETAIL

(ONLY FOR PUMPS LESS THAN 15 H.P. )

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

CITY OF PEMBROKE PINES

05-15-25 Float Review

3'

VENTILATION

HOOD WITH FILTER

ENCLOSURE NEMA 3R

PAINTED WHITE

REC-101

GENERATOR RECEPTACLE

WITH COVER AND ANGLE

ADAPTER (SEE NOTE 8)C

O N

TR

O

L

PO

W

ER

R

EC

PT

AC

LE

PUMP No.1 PUMP No. 2

PUMP No.1 PUMP No. 2

RESET FLOAT

CONTROL

OFF

HAND AUTO

OFF

HAND AUTO

PUMP 1

RUNNING

PUMP 2

RUNNING

PUMP 1

FAULT

PUMP 1

FAULT RESET

CAUTION:

RUN ONLY ONE PUMP ON

GENERATOR SERVICE

1'-4"

DRIP

SHIELD

5'

CELL MODEM ANTENNA

FIELD MOUNTED

MAIN

POWER

GENERATOR

POWER

CONTROL

POWER ON

PUMP 2

FAULT

RUNNING ON

FLOAT CONTROL

PUMP 2

FAULT RESET

7" TOUCHSCREEN

DISPLAY

ALL SHOWN DEVICES

LOCATED ON ENCLOSURE

INNER DOOR

AL205 GENERAL ALARM

FIELD MOUNTED

ALARM HORN

SILENCE

PUMP No.1

MS

PUMP No. 2

MS

PB207

AH208

No. :

Pag No. :

D - 02 2 of 18Rev No. Fecha Descripcion

0 04-28-22 Preliminary DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123

ENCLOSURE DETAIL

(ONLY FOR PUMPS 15 H.P. OR HIGHER)

1 08-28-22 PLC Control

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

W

IR

E D

U C

T 1.

1" X4

AC AND DC

BUSSING

TERMINALS

SH

SH

24VDC

24VDC

24VDC

GND

GND

GND

24VDC

24VDC

24VDC

24VDC

24VDC

24VDC

24VCOM

24VCOM

24VCOM

24VCOM

24VCOM

24VCOM

24VCOM

123A

GND

GND

GND

FIELD WIRING

TERMINALS

24COM

24COM

24COM

24VDC

24COM

24VDC

SH

INTRINSECALLY SAFE

TERMINAL STRIP

MS222 MS226

WIRE DUCT 1.0"X4"

CTS115 CTS119

C B

WIRE DUCT 1"X4"

SP

SP

G N

DPS126

PLC

C R

C R

C R

C R

ES521

C B

C R

C R

C R

C R

C R

C R

C R

C R

W

IR

E D

U C

T 1"

X4

TS125

FU-121

CM533

GROUND

BAT129,129A

XFMR122

CB102 CB102A

GND

DB106

(N)

CS104

DB106FU110

LA101

VM110

CB114 CB116

C R

TR

C R

C R

TR

C R

C R

TR

C R

TR

C R

AC AND DC BUSSING TERMINALS

SA

SA

SA

LR501 LR502

WIRE DUCT 1"X4"

IS

B

IS

B

G N

D

DOUBLE BREAKER

MOUNTING BRACKET

FIELD WIRING TERMINALS

24VDC

24VCOM

WIRE DUCT 1"X4"

WIRE DUCT 1"X4"

SH

IS

B

123123

No. :

Pag No. :

D - 03 3 of 18Rev No. Fecha Descripcion

04-28-22 Preliminary ENCLOSURE INNER SUB PANEL LAYOUT

(ONLY FOR PUMPS LESS THAN 15 H.P. )

DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123PLC Control 1 08-28-22

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 04-11-25 After Providence Review LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

CITY OF PEMBROKE PINES

05-15-25 Float Review

AutoCAD SHX Text 3'-9"

AutoCAD SHX Text 2'-9"

WIRE DUCT 1"X4"

C R

C R

C R

C R

C R

C R

C R

C R

C R

C R

AC AND DC BUSSING TERMINALS

SA

SA

SA

LR501 LR502

C

R

WIRE DUCT 1"X4"

CB102 CB102A GND

LA101PDB108

FU110

MS601 MS621

HTR25

VM110

CB114 CB118

W

IR

E D

U C

T 1.

1" X4

CS104

HTR125

FU-121

BAT129,129A

RC540

CM533

GROUND

XFMR122

C B

SP

SP

G N

DPS126

PLC

ES521

C B

WIRE DUCT 1"X4"

WIRE DUCT 1"X4"

C R

C R

C R

C R

C R

C R

C R

C R

C R

C R

C R

C R

C R

C R

WIRE DUCT 1"X4"

WIRE DUCT 1"X4"

DOUBLE BREAKER

MOUNTING BRACKET

IS

B

IS

B

G N

D

IS

B

AC AND DC

BUSSING

TERMINALS

SH

SH

24VDC

24VDC

24VDC

GND

GND

GND

24VDC

24VDC

24VDC

24VDC

24VDC

24VDC

24VCOM

24VCOM

24VCOM

24VCOM

24VCOM

24VCOM

24VCOM

123A

GND

GND

GND

FIELD WIRING

TERMINALS

24COM

24COM

24COM

24VDC

24COM

24VDC

SH

INTRINSECALLY SAFE

TERMINAL STRIP

24VDC

24VCOM

SH

123123

No. :

Pag No. :

D - 04 4 of 18Rev No. Fecha Descripcion

04-28-22 Preliminary DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123PLC Control 1 08-28-22

ENCLOSURE INNER SUB PANEL LAYOUT

(ONLY FOR PUMPS 15 H.P. OR HIGHER)

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

CITY OF PEMBROKE PINES

05-15-25 Float Review

AutoCAD SHX Text 2'-9"

AutoCAD SHX Text 5"

AutoCAD SHX Text 1"

AutoCAD SHX Text 4"

AutoCAD SHX Text 1"

AutoCAD SHX Text 1"

AutoCAD SHX Text 4'-9"

C O

N

TR

O L

PO

W

ER

R

EC

PT

AC

LE

CAUTION:

RUN ONLY 1 PUMP ON

GENERATOR SERVICE.

3.50"

2.25" PUMP No.1 PUMP No. 2

RESET FLOAT

CONTROL

OFF

HAND AUTO

OFF

HAND AUTO

PUMP 1

RUNNING

PUMP 2

RUNNING

PUMP 1

FAULT

CONTROL

POWER ON

PUMP 2

FAULT

RUNNING ON

FLOAT CONTROL

PL202

SS222 SS226

PL230 PL233

PB332

PL231 PL235 PL332

TEXT 0.25" HIGH

CIRCUIT BREAKER

NAME PLATE

TYP. OF 2

0.50"

CB122 CB540

NOTE:

ALL NAMEPLATES ARE 2.25" W X 0.75" H

BLACK PLASTIC WITH WHITE 5

32" H FRONT

ENGRAVED LETTERING. ADHESIVE

BACKED, BEVELED EDGE UNLESS

OTHERWISE NOTED.

PUMP 1

FAULT RESET

PUMP 2

FAULT RESET

PB607 PB627

ONLY FOR PANELS

WITH SOFTSTARTERS

No. :

Pag No. :

D - 05 5 of 18Rev No. Fecha Descripcion

04-28-22 Preliminary DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123

NAMEPLATE DETAIL0

1 08-28-22 PLC Control

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

INCOMING POWER

REC101

100AMP GENERATOR

RECEPTACLE WITH COVER

AND ANGLE ADAPTER

CB102

MECHANICAL

INTERLOCK

CB102A

DB106

CB114

3 3

TO LINE 713

CTS115

MS222

PUMP No. 1

PUMP No. 2

CTS119

L102B

TO LINE 121

L102A

TO LINE 121

*NOTE:

SEE PAGE 17 FOR WIRE,

BREAKERS AND FUSE SIZES

TO LINE 539

VOLTAGE: INCOMING VOLTAGE

RESTART: 20 SEC

TRIP: 20 SEC

UNBALANCE: 5%

VOLTAGE MONITOR

CONTACT LINE 237

TO LINE 135

TO LINE 713

TO LINE 715

TO LINE 137

TO LINE 715

VM109 1

N

120VAC

CAT 6 TO ETHERNET SWITCH

PORT 1 LINE 522

L1 L2 L3

N GND

GND

L102A L102B L102C

L101A L101B L101C

N

G 3

N L102C L102B L102A

N

N L102C L102B L102A

L1

L2

L3

LA101

N

L102C

L102B

L102A

L102C

L102B

L102A

L102C

L102B

L102A

CB118

L1

L2

L3

O.L.'S T1

T2

T3

M

MS226

L1

L2

L3

O.L.'S T1

T2

T3

M

SQUARE D

SURGE ARRESTOR

HIGH

LEG

USE

ONLY

(For 240V

ONLY)

FU110

CS104

TO LINE 236

FU121

500 VA

TRANSFORMER

XFMR122

PS126

POWER SUPPLY/

UPS CHARGER

DRC-100B

24VDC 100W

AC TO PLC407

LINE 416

24 COM

TO LINES

SP128

SP131

TO LINE 211

TO LINES 210 & 211

N124

TO LINES

109,201

24 VDC

TO LINES

L N

G

BAT+ N.O

C

BAT-

N.O

C

V-

V-

V+

V+

*NOTE:

SEE PAGE 17 FOR WIRE,

BREAKERS AND FUSE SIZES

CR135

CR137

CTS115

CTS119

INSTALL LINKS AS PER

TRANSFORMER

MANUAL

2 3 4 5

5 4 2

120 VAC

122A122

L102A L102B

N124

N123

BATTERY CH2, 1.25A

AC OK

BAT.LOW

OUTPUT CH1, 2.25A

24VDC

123A

128A

0.5 A

129A129

12VDC 7.0 AH

BATTERY WITH

16" TAB (TYP)

128A 129A

24VDC

24VDC COM

1.0 A

B22

B22

123A

TO LINE

CB122

CR139CS104

B12

TO LINES

109, 201

N124

PUMP NO.1

RUNNING

PUMP NO.2

RUNNING

GEN

RUNNING

HTR125

TO LINE 212

No. :

Pag No. :

D - 06 6 of 18Rev No. Fecha Descripcion

04-28-22 Preliminary POWER & DC CIRCUITS

(ONLY FOR PUMPS LESS THAN 15 H.P. )

DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123

1 08-28-22 PLC Control

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

INCOMING POWER

REC101

100AMP GENERATOR

RECEPTACLE WITH COVER

AND ANGLE ADAPTER

CB102

MECHANICAL

INTERLOCK

CB102A

DB106

CB114

3 3

TO LINE 713

CTS115

MS601

PUMP No. 1

PUMP No. 2

CTS119

L102C

TO LINES 121, 530

L102A

TO LINE 121

*NOTE:

SEE PAGE 17 FOR WIRE,

BREAKERS AND FUSE SIZES

TO LINE 539

VOLTAGE: INCOMING VOLTAGE

RESTART: 20 SEC

TRIP: 20 SEC

UNBALANCE: 5%

VOLTAGE MONITOR

CONTACT LINE 237

TO LINE 135

TO LINE 713

TO LINE 715

TO LINE 137

TO LINE 715

VM109 1

N

120VAC ( LINE 134 )

TO ETHERNET SWITCH

PORT 1 LINE 522

L1 L1 L3

N GND

GND

L102A L102B L102C

L101A L101B L101C

N

G 3

N L102C L102B L102A

N

N L102C L102B L102A

L1

L2

L3

LA101

N

L102C

L102B

L102A

L102C

L102B

L102A

L102C

L102B

L102A

CB118

L1

L2

L3

T1

T2

T3

M

MS621

L1

L2

L3

T1

T2

T3

M

SQUARE D

SURGE ARRESTOR

HIGH

LEG

USE

ONLY

(For 240V

ONLY)

FU110

CS104

TO LINE 139

FU121

500 VA

TRANSFORMER

XFMR122

PS126

POWER SUPPLY/

UPS CHARGER

DRC-100B

24VDC 100W

AC TO PLC407

LINE 416

SP128

SP131

TO LINE 211

TO LINE 209

L N

G

BAT+ N.O

C

BAT-

N.O

C

V-

V-

V+

V+

*NOTE:

SEE PAGE 17 FOR WIRE,

BREAKERS AND FUSE SIZES

CR135

CR137

CTS115

CTS119

INSTALL LINKS AS PER

TRANSFORMER

MANUAL

2 3 4 5

5 4 2

120 VAC

122A122

L102A L102B

N124

N123

BATTERY CH2, 1.25A

AC OK

BAT.LOW

OUTPUT CH1, 2.25A

24VDC

123A

128A

0.5 A

129A129

12VDC 7.0 AH

BATTERY WITH

16" TAB (TYP)

128A 129A

24VDC

24VDC COM

1.0 A

B22

B22

CB122

CR139CS104

B12

HTR125

24 COM

TO LINES

N124

TO LINES

109,201

24 VDC

TO LINES

TO LINES

109, 201

TO LINE 212

123A

TO LINE

No. :

Pag No. :

D - 07 7 of 18Rev No. Fecha Descripcion

04-28-22 Preliminary DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123

1 08-28-22 PLC Control

POWER & DC CIRCUITS

(ONLY FOR PUMPS 15 H.P.OR HIGHER )

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

FROM LINE 140 FROM LINE 140

CONTROL POWER ON

PL202

FIELD MOUNTED ON

TOP OF ENCLOSURE

COMMON ALARM LIGHT

(EXTERNAL)

CR237

CR508

PANEL MTD. CONNECTOR

(BOTTOM OF ENCLOSURE)

FIELD CONNECTOR

(FROM BYPASS PUMP TRAILER) *FIELD NOTE: OVERTEMP

COMPATIBLE ONLY WITH

STANDARD OVERLOAD

THERMALS*

PUMP NO. 2

OVER TEMP

206,226,414

PUMP NO. 1

OVER TEMP

205,222,413

VOLTAGE MONITOR

204,222,417

CR237

CR238

CR239

THERMOSTAT

TH238

THERMOSTAT

TH239

CR238

CR239

PUMP 1 MOTOR

STARTER

114,411

MS222

PUMP 2 MOTOR

STARTER

119,412

PUMP 1

FAULT

PUMP 2

FAULT

PUMP 1

RUNNING

PUMP 2

RUNNING

CR207

ALARM HORN SILENCE

CR207

CR207

AH208

PB207

AL205

W

N124R

9 5

9 5

9 5

9 5

A24

9 5

9 1

9 5

CR507

128A

129A

TO LINE 132

24VDC

TO LINE 133

TO LINE 415

TO LINE 425

TO LINE 708

CR515

TO LINE 221

BYPASS BATTERY

POWER

24VDC

BYPASS PUMP RUN

9 5

BYPASS PUMP FAIL

BYPASS PUMP START

BYPASS PUMP

FUEL LEVEL

TO LINE 221

FROM LINE 220

SS222

OFF

HAND AUTO

X00

00X

222B

12 8

CR512 CR237

10 6

SS226

OFF

HAND AUTO

X00

00X

226B

9 5

CR515

9 5

CR514

9 5

9 1

CR238

222D

95 96A2A1

O.L.

MS

MS226

226D

95 96A2A1

O.L.

MS9 1

CR239

CR328

9 5

CR135

A34 1314

A34 1314

A34 1314

R

G

CR238

CR137

R

G

CR239

VM109

TO LINE 321

TO LINE 321

PL230

PL231

PL233

PL235

4 7

TR203

TR203

A14

BA

SILENCE HORN

OFF DELAY TIMER

(SET MODE E, 15 MIN)

9 1

CR330

CR322

9 5

9 5

CR324

9 5

CR512

9 5

No. :

Pag No. :

D - 08 8 of 18Rev No. Fecha Descripcion

04-28-22 Preliminary INDICATORS, ALARMS & CONTROL CIRCUITS

(ONLY FOR PUMPS LESS THAN 15 H.P. )

DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123

1 08-28-22 PLC ControlPLC Control

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

FROM LINE 140 FROM LINE 140

CONTROL POWER ON

PL202

FIELD MOUNTED ON

TOP OF ENCLOSURE

COMMON ALARM LIGHT

(EXTERNAL)

CR237

CR508

PANEL MTD. CONNECTOR

(BOTTOM OF ENCLOSURE)

FIELD CONNECTOR

(FROM BYPASS PUMP TRAILER)

VOLTAGE MONITOR

204,222,417

CR237

CR620

CR640

PUMP 1 MOTOR

STARTER

CR222

PUMP 2 MOTOR

STARTER

PUMP 1

FAULT

PUMP 2

FAULT

PUMP 1

RUNNING

PUMP 2

RUNNING

CR207

ALARM HORN SILENCE

CR207

CR207

AH208

PB207

AL205

W

N124R

9 5

9 5

9 5

9 5

A24

9 5

9 1

9 5

CR507

128A

129A

TO LINE 132

24VDC

TO LINE 133

TO LINE 415

TO LINE 425

TO LINE 730

CR515

TO LINE 221

BYPASS BATTERY

POWER

24VDC

BYPASS PUMP RUN

9 5

BYPASS PUMP FAIL

BYPASS PUMP START

BYPASS PUMP

FUEL LEVEL

TO LINE 221

FROM LINE 220

SS222

OFF

HAND AUTO

X00

00X

9 5

CR512 CR237

10 6

SS226

OFF

HAND AUTO

X00

00X

9 5

CR515

9 5

9 5

9 1

CR 620

1314 A14

CR226

9 1

CR640

CR328

9 5

CR135

A34 1314

R

G

CR620

CR137

R

G

CR640

VM109

TO LINE 321

TO LINE 321

A14

4 7

TR203

CR514

TR203

A14

BA

SILENCE HORN

OFF DELAY TIMER

(SET MODE E, 15 MIN)

B(INTERVAL)

9 5

CR330

CR324

CR322

9 5

CR512

9 5

PL230

PL231

PL233

PL235

No. :

Pag No. :

D - 09 9 of 18Rev No. Fecha Descripcion

04-28-22 Preliminary DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123

1 08-28-22 PLC ControlPLC Control

INDICATORS, ALARMS & CONTROL CIRCUITS

(ONLY FOR PUMPS 15 H.P.OR HIGHER )

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

ISB 303

SUBMERSIBLE BIRD

CAGE BLUE RIBBON

TRANSDUCER.

INSTALL WITH SURGE

PROTECTOR FOR

LIFETIME WARRANTY

LEVEL TRANSMITTER

TO LINE 426

FORCE MAIN PRESSURE

TRANSMITTER

TO LINE 429

SA315

BLUE RIBBON

SURGE PROTECTOR

BCP 3000

TO LINE 321

FROM LINE 320 FROM LINE 240

FROM LINE 240

12424VDC COM

FROM LINE 140

24VDC 24COM

1.1

1.2

2.1

2.2

3.1

3.2

5.1

5.2

5.1

5.2

CBL306

SH

24VDC 24COM

315+

316-

SH

CBL315

ISR 322

1.1

1.2

2.2

3.1

3.2

4.3

4.1

5.3

5.1

HIGH LEVEL ALARM

336 A24 1314

REDUNDANT CONTROL

ACTIVE

337,402

CR336

PB337

RESET

FLOAT

CTRL

CANCEL

FLOAT CTRL

FROM PLC

9 1

RUNNING ON FLOAT

CONTROL

CR510

A

PL337

TO LINE 601

123 N124

TO LINE 601

BLUE RIBBON BR311

SS PRESSURE

TRANSDUCER

LS321

2.1

ISR 326

1.1

1.2

2.2

3.1

3.2

4.3

4.1

5.3

5.1

2.1

CR322

A2414

1314 A24

CR324

LS323

LS327

LS329

CR328

A2414

14 A14

CR330

PUMP 2 RUN ON FLOAT

(LAG)

PUMP1 RUN ON FLOAT

(LEAD)

ALL PUMPS OFF13

CR328

CR336

CBL316

LS321,LS323,LS327,LS329

ROTO FLOAT

ANCHOR SCIENTIFIC

24VDC COM

TO LINE 401

No. :

Pag No. :

D - 10 10 of 18Rev No. Fecha Descripcion

04-28-22 Preliminary LEVEL TRANSDUCER &

FLOAT BACKUP CIRCUIT

DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123

1 08-28-22 PLC ControlPLC Control

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

FROM LINE 340

24VDC 24COM

TO LINE 421

24VDC HYDRALINK PLC407

CONTINUED ON LINE 421

PLC 407

HYDRALINK

TOP BLACK TERMINAL

CM0 1

6 I4

I3

I2

I1

I0

12 4

00XPUMP NO. 1

IN AUTO

00X

SS226

MS222

PUMP NO. 2

IN AUTO

SS222

MS226

I9

I8

I7

I6

I5

PUMP NO. 1

RUN

PUMP NO. 2

RUN

PUMP NO. 1

OVERTEMP

PUMP NO. 2

OVERTEMP

PUMP NO. 2

OVERTEMP

GEN. RUNNING

AC POWER

FAIL

POWER FAIL

HIGH LEVEL

FLOAT ALARM

AC OKAC OK

CR238

CR239

PS126

CR237

TO LINE 212

CR139

GEN/BYPASS

RUN

REDUNDANT

CONTROL

ACTIVE

FROM LINE 340 FROM LINE 420

24VDC 24COM

FROM LINE 420

TOP GRAY TERMINAL

PLC 407

HYDRALINK CONTINUED

FROM LINE 420

CM1 16

19 I12

I11

I10

20 I12

21 I0I

TO LINE 213

CR336

LEVEL SIGNAL FROM LINE 306

CBL306

CLR

30 RT3-

RT3+

R-

RT2-

RT2+

I1V

I1I

CBL316

CLRFORCE PRESSURE SIGNAL

FROM LINE 316

I0V22

CM2

+V

+V

0V

GGND

HYDRALINK PLC407

CONTINUED ON LINE 501

CR539

INTRUSION /

PANEL DOOR

OPEN

NOTE: HYDRALINK INSTALLED BY OTHERS. ALL

INPUTS TO BE WIRED TO TERMINALS AS REQUIRED

CR322

TO LINE 501

24VDC

TO LINE 501

24VDC

No. :

Pag No. :

D - 11 11 of 18Rev No. Fecha Descripcion

04-28-22 Preliminary HYDRALINK PLC I/O

(ONLY FOR PUMPS LESS THAN 15 H.P. )

DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123

1 08-28-22 PLC ControlPLC Control

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

FROM LINE 340

24VDC 24COM

TO LINE 421

24VDC HYDRALINK PLC407

CONTINUED ON LINE 421

PLC 407

HYDRALINK

TOP BLACK TERMINAL

CM0 1

6 I4

I3

I2

I1

I0

12 4

00XPUMP NO. 1

IN AUTO

00X

SS226

CR135

PUMP NO. 2

IN AUTO

SS222

CR137

I9

I8

I7

I6

I5

PUMP NO. 1

RUN

PUMP NO. 2

RUN

PUMP NO. 1

FAULT

PUMP NO. 2

FAULT

GEN. RUNNING

AC POWER

FAIL

POWER FAIL

HIGH LEVEL

FLOAT ALARM

AC OKAC OK

CR620

CR640

PS126

CR237

TO LINE 212

CR139

GEN/BYPASS

RUN

REDUNDANT

CONTROL

ACTIVE

FROM LINE 340 FROM LINE 420

24VDC 24COM

FROM LINE 420

TOP GRAY TERMINAL

PLC 407

HYDRALINK CONTINUED

FROM LINE 420

CM1 16

19 I12

I11

I10

20 I12

21 I0I

TO LINE 213

CR336

LEVEL SIGNAL FROM LINE 306

CBL306

CLR

30 RT3-

RT3+

R-

RT2-

RT2+

I1V

I1I

CBL316

CLRFORCE PRESSURE SIGNAL

FROM LINE 316

I0V22

CM2

+V

+V

0V

GGND

HYDRALINK PLC407

CONTINUED ON LINE 501

CR539

INTRUSION /

PANEL DOOR

OPEN

NOTE: HYDRALINK INSTALLED BY OTHERS. ALL

INPUTS TO BE WIRED TO TERMINALS AS REQUIRED

CR322

TO LINE 501

24VDC

TO LINE 501

24VDC

No. :

Pag No. :

D - 12 12 of 18Rev No. Fecha Descripcion

04-28-22 Preliminary HYDRALINK PLC I/O

(ONLY FOR PUMPS 15 H.P.OR HIGHER )

DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123

1 08-28-22 PLC ControlPLC Control

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

LT540

FROM LINE 140

TO VOLTAGE METER

TO SOFT- STARTER

PUMP 1 MS601

TO SOFT-STARTER

PUMP 2 MS602

TO HMI DISPLAY

ONLY FOR PUMPS

15HP OR HIGHER

FROM LINE 121

L123A

FROM LINE 440

24VDC 24COM

FROM LINE 440

BOTTOM

BLACK TERMINALS

(RIGHT TO LEFT)

PLC 407

HYDRALINK CONTINUED

FROM LINE 440

LR501

AO1 1

LR502

AO0

CM5

6D07

7D06

8D05

CANCEL FLOAT

CONTROL

326,332

CR507

B12 1314

CR508

B12 1314

PUMP NO. 1

FAULT RESET

PUMP NO. 2

FAULT RESET

CR509

B12

CR510

B22 1314

9D04

10 CM4

11D03

CR512

B12

12D02

13D01

14D00

CR514 B12

CM4

CR515

B12 1314

FROM LINE 140

RC540

DS540

ES521

CR539

1314 A14

PUMP NO. 1

REQUIRED

PUMP NO. 2

REQUIRED

CONTROL

POWER CUT

ROUTER RESET

ACTIVE ALARM

BUZZER RESET

CR509

NOTE: HYDRALINK INSTALLED BY OTHERS. ALL

INPUTS TO BE WIRED TO TERMINALS AS

REQUIRED

NOTE: OPERATOR INTERFACE INSTALLED BY

OTHERS. HOLE TO BE CUT BY PANEL

MANUFACTURER.

ROUTER AND ANTENNA INSTALLED BY OTHERS

EXPANSION MODULE

TO LINE 701

24VDC

TO LINE 701

24VDC

No. :

Pag No. :

D - 13 13 of 18Rev No. Fecha Descripcion

04-28-22 Preliminary

HYDRALINK I/O, MODEM & IP CIRCUITS

DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123

1 08-28-22 PLC ControlPLC Control

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

CONTINUED ON LINE 421

No. :

Pag No. :

D - 14

MS-601

120VAC

NEUTRAL

COM

START

COM

DI-B

RELAY B COM

RELAY B N.O.

A8

A7

TER-05

DI-A

AO-08

AO-07

RELAY A N.O.

RELAY A COM

RELAY A N.C.

CR222

N124

PB607

FAULT RESET

INNER DOOR

MOUNTED KEYPAD

PUMP NO.1

REQUIRED

PUMP NO.1

RESET

CR620

PUMP NO.1

FAULT 231

123 N124

SET PATAMETER 3-8

REMOTE RESET TO 2

"NORMALLY OPEN"

TER-06

RESET

TO LINE 621

FROM LINE 340

COM

A9

TO ETHERNET SWITCH

PORT 2 LINE 523

LR501

A12 1314

N124 MS-601

120VAC

NEUTRAL

COM

START

COM

DI-B

A8

A7

TER-05

DI-A

AO-08

AO-07

CR226

PB627

FAULT RESET

INNER DOOR

MOUNTED KEYPAD

PUMP NO 2

REQUIRED

PUMP NO.2

RESET

PUMP NO.2

FAULT 231

SET PATAMETER 3-8

REMOTE RESET TO 2

"NORMALLY OPEN"

TER-06

RESET

FROM LINE 340

COM

A9

TO ETHERNET SWITCH

PORT 3 LINE 523

LR502

N124

RELAY B COM

RELAY B N.O.

RELAY A N.O.

RELAY A COM

RELAY A N.C.

34N124

CR640

A12 1314

No. :

Pag No. :

D - 15 15 of 18Rev No. Fecha Descripcion

04-28-22 Preliminary DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123

1 08-28-22 PLC Control

SOFT STARTERS

(ONLY FOR PUMPS 15 H.P. OR HIGHER )

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

CTS119

PUMP No. 2

CURRENT TRANSDUCER &

SWITCH.SET SETPOINT TO

CORRECT CURRENT RATING

PUMP No. 1

CURRENT TRANSDUCER &

SWITCH.SET SETPOINT TO

CORRECT CURRENT RATING

CTS115

FROM LINE 520

24VDC 24COM

I/0 702

HYDRALINK

I/O TOP TERMINALS

BLUE RIBBON SURGE

PROTECTOR

BCP3000

SA703

SH SH

CBL704

CLR

CLR

BLK

CBL703

703+

704-

SH

WATER DISTRIBUTION

PRESSURE

TRANSMITTER

4-20mA

0-XXX PSI 2

1 CM0

I0I

I0V3

CM1

I1I

I1V

CM2

I2I

I2V

CM3

I3I

I3V

BLUE RIBBON SURGE

PROTECTOR

BCP3000

SA707

SH SH

CBL707

BYPASS FUEL LEVEL

4-20mA

0-XXX FT CLR

SPACE INTELTIONALLY LEFT BLANK

NOTES:

1. IF PANEL FOR A LOW FLOW STATION

CONSULT WITH CITY OF PEMNBROKE PINES

IF I/O MODULE IS REQUIRED.

2. I/O MODULE INSTALLED BY OTHERS.

707+

708-

No. :

Pag No. :

D - 16 16 of 18Rev No. Fecha Descripcion

04-28-22 Preliminary

HYDRALINK ANALOG I/O MODULE

DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123

1 08-28-22 PLC ControlPLC Control

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

* SEE DRAWING 18 FOR EXACT PART NUMBERS FOR THE CORRRESPONDING PUMP HORSE POWER AND SITE VOLTAGE * SEE DRAWING 18 FOR EXACT PART NUMBERS FOR THE CORRRESPONDING PUMP HORSE POWER AND SITE VOLTAGE

No. :

Pag No. :

D - 17 17 of 18Rev No. Fecha Descripcion

- 04-28-22 Preliminary

BILL OF MATERIALS

DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123

1 08-28-22 PLC Control

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

No. :

Pag No. :

D - 18 18 of 18Rev No. Fecha Descripcion

04-28-22 Preliminary DRAWING No. :

SCALE :

APROVADE :

DATE :

No. PROJECT :

N.T.S

M.C.M 21-123

1 08-28-22 PLC Control

PART NO. & WIRES

OCT. 2023

21-123-BMS-1-R2.DWG

2 10-27-23 Owner's Review

3 LIFT STATIONS DUPLEX SUBMERSIBLE

CONTROL PANEL STANDARD

21-123 BMS-0
Sheets and Views
Details
21-123 BMS-1
Sheets and Views
Details
21-123 BMS-2
Sheets and Views
Details
21-123 BMS-3
Sheets and Views
Details
21-123 BMS-4
Sheets and Views
Details
21-123 BMS-5
Sheets and Views
Details
21-123 BMS-6
Sheets and Views
Details
21-123 BMS-7
Sheets and Views
Details
21-123 BMS-8
Sheets and Views
Details
21-123 BMS-9
Sheets and Views
Details
21-123 BMS-10
Sheets and Views
Details
21-123 BMS-11
Sheets and Views
Details
21-123 BMS-12
Sheets and Views
Details
21-123 BMS-13
Sheets and Views
Details
21-123 BMS-14
Sheets and Views
Details
21-123 BMS-15
Sheets and Views
Details
21-123 BMS-16
Sheets and Views
Details
21-123 BMS-17
Sheets and Views
Details
21-123 BMS-18
Sheets and Views
Details

File details come from the government source that posted it. Updated .