This addendum document contains fire sprinkler inspection reports and related testing documentation for Fayette County, Georgia facilities, submitted in support of Request for Quotes #2068-A for Fire Sprinkler Inspection Services. The file includes comprehensive inspection reports for multiple county buildings, including fire stations, the 911 center, justice center, library, senior center, administrative complex, historic courthouse, and public works facility. These reports, conducted between March 9 and March 26, 2021, document system data, pressure readings, mechanical specifications, wet and dry system conditions, water supplies, fire pump performance, and deficiency assessments for each facility's sprinkler systems. The inspections were performed by certified inspectors from Fire-X, Inc., and include detailed documentation of sprinkler head types, piping materials, valve configurations, and alarm systems across the county's properties. The reports demonstrate compliance with NFPA 25 standards and include both passing inspections marked as "Green Tag" and those with noted deficiencies requiring attention.
The deficiency reports identify specific maintenance and repair needs at several facilities, most notably at the Fayette County 911 Center where corrosion was documented in multiple locations including lobbies, hallways, conference rooms, and bathrooms, along with six loaded sprinkler heads in the dispatch floor area. The Fayette County Historic Courthouse reported deficiencies including corroded piping, missing control valve signs, painted pendant heads, missing drain signs, and missing fire department connection caps. The Fayette County Senior Services Center identified pressure insufficiency in the dry system. The Fayette County Justice Center pump test report, dated March 26, 2021, documents a 1000 GPM turbine pump passing performance testing at rated and 150 percent capacity. Most facilities received passing inspections with no deficiencies noted. All inspection documentation indicates monitoring company coordination and adherence to NFPA 72 and NFPA 25 standards.
Text of this file
FIRE SPRINKLER INSPECTION REPORT
Disclaimer : 1.) All questions are to be answered YES, NO or NOT APPLICABLE (All NO answers are to be explained in Deficiency Report Section of this form.
2.) Inspection, testing and maintenance are to be performed with water supplies (including fire pumps) in service, unless the impairment procedures of Chapter 11 of NFPA 25 are followed.
3.) By signing this document, Signer agrees that :
*All (Part 1 - Owner’s Section) questions were asked and answered correctly by on-site representative.
* All deficiencies have been explained to them 4.) All visible inspections performed from ground level 5.) This is not an engineering review
Building: Fayette County 911 Center
Address: Volunteer way
Fayetteville GA
Contact: Robin
Phone:
Email:
Time: 0730-0830
Date: 3-18-21
Inspector: Randall Tenney IL# 000947
1. OWNER’S SECTION YES NO N/A
a.) Is the building occupied?
b.) Has the occupancy classification and hazard of contents remained the same since the last inspection?
c.) Are all fire protection systems in service?
d.) Has the system remained in service without modification since the last inspection?
e.) Was the system free of actuation devices or alarms since the last inspection?
f.) Has the internal inspection and/or fifth year obstruction investigation been performed within the last five years?
Signature of Owner/Representative :
System Data
Pressure Readings
Mechanical Data
System Type System Number Type of Pipe Location Wet 1 Steel Breakroom
System Number
Static Residual Air Pressure
Trip & Time Alarm Type
1 80 40 — — Flow Switch
Control Valve Size
Valve Type Valve Make Security Method
Signs Y/N
4” PIV Kennedy Monitor Yes
4” Butterfly Kennedy Monitor Yes
Drain Data
Sprinkler Heads
Drain Location Drain Size Valve Type Main/Test/Aux Signs Y/N @Riser 2” Ball Main Yes
Outside bathroom 1.25” Gate Test No
Head Type Head Model Head Size Quick/Standard Chrome Pendant RA1414 .5” Quick155
3. TANKS, PUMPS, FIRE DEPT. CONNECTIONS YES NO N/A
a.) Are fire pumps, gravity tanks, reservoirs and pressure tanks in good condition and properly maintained?
X b.) Are Fire Dept. connections in satisfactory condition, couplings free, caps in place, and check valves tight?
X c.) Are Fire Dept. Connections accessible and visible? X
d. ) Is the fire pump logbook up to date? X
4. WET SYSTEMS YES NO N/A
a.) Are cold weather valves (OS&Y) in the appropriate open or closed position? X b.) Have all disallowed antifreeze systems been removed? X c.) All sprinkler heads connected to wet systems free from paint, corrosion, and loading?
X d.) Are heads less than 50 years old? X e.) Piping appear to be in good condition, free of rust, corrosion, leaks? X f.) Are the sprinkler heads at proper temperature rating for their location? X g.) Exterior of sprinkler system appear to be satisfactory? X h.) Stock of spare heads with spare head wrench? X i.) Supervisory alarm test satisfactory? Or Locked? X j.) Waterflow alarm test satisfactory? Electric bell? X k.) Water motor gong test satisfactory? X l.) Are gauges less than 5 years old? X 18 m.) Has system had internal inspection conducted within last 5 years? X 18
5. DRY SYSTEMS YES NO N/A
a.) Are the dry valves in service? X b.) Is the air pressure and priming water level in accordance with the manufacturers instructions?
X c.) Has the operation of the air nitrogen supply been tested? X d.) Is it in service? X e.) Were low point drained during inspection? X f.) Did quick opening devices operate satisfactory? X g.) Did heating equipment in the dry valve room operate at the time of inspection? X h.) All sprinkler heads connected to dry systems free from paint, corrosion, and loading?
X i.) Are heads less than 50 years old? X j.)Piping appear to be in good condition, free of rust, corrosion, leaks? X k.) Exterior of dry system appear to be satisfactory? X l.) Stock of spare heads with spare head wrench? X m.) Supervisory alarm test satisfactory? Or Locked? X n.) Alarm devices test satisfactory? X o.) Water motor gong test satisfactory? X p.) Are gauges less than 5 years old? X q.) Has system had internal inspection conducted within last 5 years? X
6. WATER SUPPLIES YES NO N/A
a.) Was a water flow test of main drain made at sprinkler riser? X b.) Static Pressure 175 PSI or less? X
DEFICIENCY REPORT :
NOTES : Non Critcal
Signature of Inspector : Randa! Tenney Date : 3-18-21
IL #000947
Fire-X, INC.
2834 SULLIVAN RD.
ATLANTA, GA. 30337
(404)209-0919
LOCATION : DEFICIENCY :
Lobby Showing signs of corrosion
Hall after lobby Showing signs of corrosion
Conference room Showing signs of corrosion
Hall at clock in Showing signs of corrosion
Locker room Showing signs of corrosion
Riser room Showing signs of corrosion
Dispatch bathroom Showing signs of corrosion
Dispatch bathroom Showing signs of corrosion
Office bathroom Showing signs of corrosion
Dispatch floor x6 loaded heads
Disclaimer : 1.) All questions are to be answered YES, NO or NOT APPLICABLE (All NO answers are to be explained in Deficiency Report Section of this form.
2.) Inspection, testing and maintenance are to be performed with water supplies (including fire pumps) in service, unless the impairment procedures of Chapter 11 of NFPA 25 are followed.
3.) By signing this document, Signer agrees that :
*All (Part 1 - Owner’s Section) questions were asked and answered correctly by on-site representative.
* All deficiencies have been explained to them 4.) All visible inspections performed from ground level 5.) This is not an engineering review
Building: Fire Station 3
Address: 420 Jenkins Rd
Tyrone GA
Contact: Robin
Phone: 770-320-6003
Email:
Time: 3:30-4:00
Date: 3-16-21
Inspector: Kurt Holden IL# 001063
1. OWNER’S SECTION YES NO N/A
a.) Is the building occupied?
b.) Has the occupancy classification and hazard of contents remained the same since the last inspection?
c.) Are all fire protection systems in service?
d.) Has the system remained in service without modification since the last inspection?
e.) Was the system free of actuation devices or alarms since the last inspection?
f.) Has the internal inspection and/or fifth year obstruction investigation been performed within
Pressure Readings
Mechanical Data
System Type System Number Type of Pipe Location Wet 1 CPVC Laundry
System Number
Static Residual Air Pressure
Trip & Time Alarm Type
1 80 55 — — Flow Switch
Control Valve Size
Valve Type Valve Make Security Method
Signs Y/N
1.5” Butterfly Milwaukee Monitor Yes
Sprinkler Heads
Drain Location Drain Size Drain Type Main/Test/Aux Signs Y/N @Riser 1” Ball Main No
White Pendant VK430 .5” Quick155 a.) Are fire pumps, gravity tanks, reservoirs and pressure tanks in good condition and properly maintained?
X b.) Are Fire Dept. connections in satisfactory condition, couplings free, caps in place, and check valves tight?
X c.) Are Fire Dept. Connections accessible and visible? X
d. ) Is the fire pump logbook up to date? X
4. WET SYSTEMS YES NO N/A
a.) Are cold weather valves (OS&Y) in the appropriate open or closed position? X b.) Have all disallowed antifreeze systems been removed? X c.) All sprinkler heads connected to wet systems free from paint, corrosion, and loading?
X d.) Are heads less than 50 years old? X e.) Piping appear to be in good condition, free of rust, corrosion, leaks? X f.) Are the sprinkler heads at proper temperature rating for their location? X g.) Exterior of sprinkler system appear to be satisfactory? X h.) Stock of spare heads with spare head wrench? X i.) Supervisory alarm test satisfactory? Or Locked? X j.) Waterflow alarm test satisfactory? Electric bell? X k.) Water motor gong test satisfactory? X l.) Are gauges less than 5 years old? X 20 m.) Has system had internal inspection conducted within last 5 years? X 20 a.) Are the dry valves in service? X b.) Is the air pressure and priming water level in accordance with the manufacturers instructions?
X c.) Has the operation of the air nitrogen supply been tested? X d.) Is it in service? X e.) Were low point drained during inspection? X f.) Did quick opening devices operate satisfactory? X g.) Did heating equipment in the dry valve room operate at the time of inspection? X h.) All sprinkler heads connected to dry systems free from paint, corrosion, and loading?
X i.) Are heads less than 50 years old? X j.)Piping appear to be in good condition, free of rust, corrosion, leaks? X k.) Exterior of dry system appear to be satisfactory? X l.) Stock of spare heads with spare head wrench? X m.) Supervisory alarm test satisfactory? Or Locked? X n.) Alarm devices test satisfactory? X o.) Water motor gong test satisfactory? X p.) Are gauges less than 5 years old? X q.) Has system had internal inspection conducted within last 5 years? X
6. WATER SUPPLIES YES NO N/A
NOTES :Green Tag
Signature of Inspector : KHolden Date : 3-16-21
IL #001063
Fire-X, INC.
2834 SULLIVAN RD.
ATLANTA, GA. 30337
(404)209-0919
LOCATION : DEFICIENCY :
Disclaimer : 1.) All questions are to be answered YES, NO or NOT APPLICABLE (All NO answers are to be explained in Deficiency Report Section of this form.
2.) Inspection, testing and maintenance are to be performed with water supplies (including fire pumps) in service, unless the impairment procedures of Chapter 11 of NFPA 25 are followed.
3.) By signing this document, Signer agrees that :
*All (Part 1 - Owner’s Section) questions were asked and answered correctly by on-site representative.
* All deficiencies have been explained to them 4.) All visible inspections performed from ground level 5.) This is not an engineering review
Building: Fayette Fire Station 10
Address: 195 Seay Rd
Fayetteville GA
Contact: Robin
Phone:
Email:
Time: 2:30-3:00
Date: 3-16-21
Inspector: Kurt Holden IL# 001063
1. OWNER’S SECTION YES NO N/A
a.) Is the building occupied?
b.) Has the occupancy classification and hazard of contents remained the same since the last inspection?
c.) Are all fire protection systems in service?
d.) Has the system remained in service without modification since the last inspection?
e.) Was the system free of actuation devices or alarms since the last inspection?
f.) Has the internal inspection and/or fifth year obstruction investigation been performed within
Pressure Readings
Mechanical Data
System Type System Number Type of Pipe Location Wet 1 Steel to CPVC Back laundry room
System Number
Static Residual Air Pressure
Trip & Time Alarm Type
1 110 45 — — Flow Switch
Control Valve Size
Valve Type Valve Make Security Method
1.5” Butterfly Milwaukee Monitor No
Sprinkler Heads
Drain Location Drain Size Valve Type Main/Test/Aux Signs Y/N @Riser 1’ Ball Main No
Head Type Head Model Head Size Quick/Standard White pendant Vk302 .5” Quick155
Brass pendant .5” Standard 200
Brass upright VK300 .5” Quick 200
Chrome concealed VK404 250 .5” Quick 165 a.) Are fire pumps, gravity tanks, reservoirs and pressure tanks in good condition and properly maintained?
X b.) Are Fire Dept. connections in satisfactory condition, couplings free, caps in place, and check valves tight?
X c.) Are Fire Dept. Connections accessible and visible? X
d. ) Is the fire pump logbook up to date? X
4. WET SYSTEMS YES NO N/A
a.) Are cold weather valves (OS&Y) in the appropriate open or closed position? X b.) Have all disallowed antifreeze systems been removed? X c.) All sprinkler heads connected to wet systems free from paint, corrosion, and loading?
X d.) Are heads less than 50 years old? X e.) Piping appear to be in good condition, free of rust, corrosion, leaks? X f.) Are the sprinkler heads at proper temperature rating for their location? X g.) Exterior of sprinkler system appear to be satisfactory? X h.) Stock of spare heads with spare head wrench? X i.) Supervisory alarm test satisfactory? Or Locked? X j.) Waterflow alarm test satisfactory? Electric bell? X k.) Water motor gong test satisfactory? X a.) Are the dry valves in service? X b.) Is the air pressure and priming water level in accordance with the manufacturers instructions?
X c.) Has the operation of the air nitrogen supply been tested? X d.) Is it in service? X e.) Were low point drained during inspection? X f.) Did quick opening devices operate satisfactory? X g.) Did heating equipment in the dry valve room operate at the time of inspection? X h.) All sprinkler heads connected to dry systems free from paint, corrosion, and loading?
X i.) Are heads less than 50 years old? X j.)Piping appear to be in good condition, free of rust, corrosion, leaks? X k.) Exterior of dry system appear to be satisfactory? X l.) Stock of spare heads with spare head wrench? X m.) Supervisory alarm test satisfactory? Or Locked? X n.) Alarm devices test satisfactory? X o.) Water motor gong test satisfactory? X p.) Are gauges less than 5 years old? X q.) Has system had internal inspection conducted within last 5 years? X
6. WATER SUPPLIES YES NO N/A
NOTES :Green Tag
Signature of Inspector : KHolden Date : 3-16-21
IL # 001063
Fire-X, INC.
2834 SULLIVAN RD.
ATLANTA, GA. 30337
Fire Alarm Semi Annual Inspection Report
Customer: Fayette Senior Center Date : 9-28-20 Address: 4 Center Dr Technician: R. Tenney Fayetteville GA Panel Type: NFS640 Contact: Robin / Jeff Serial #: N/A Phone #: Panel Location: Rm 138 Email: Batteries: 12v7Amp12Hr Voltage: 120VAC Comments:
-Monitoring company contacted before and after inspection -No troubles come in when NACs are taken out.
*Inspected/tested per NFPA 72.
Device Tested Location Zone Pass/Fail Tamper Switch Wet riser 34 Pass
Tamper Switch Dry riser 36 Pass
Flow Switch Wet riser 35 Pass
Pressure switch Dry riser 37 Pass
Smoke Detector @ FACP 10 Pass
Duct Detector @ FACP 12 Pass
Duct Detector @FACP 11 Pass
Manual Pull Station Center back exit 10 Pass
Smoke Detector Center bathroom area 60 Pass
Smoke Detector Center Men’s bathroom 24 Pass
Smoke Detector Center women’s bathroom
59 Pass
Smoke Detector Exercise storage 57 Pass
Smoke Detector Kitchen catering 51 Pass
Smoke Detector Catering kit pantry 58 Pass
Smoke Detector Outside hvac 13 Pass
Duct Detector Outside hvac 16 Pass
Duct Detector Outside hvac 15 Pass
Smoke Detector Outside storage 11 Pass
Smoke Detector Break room 32 Pass
Smoke Detector Hub closet 31 Pass
Manual Pull Station Break room 34 Pass
Smoke Detector Mail room hall 33 Pass
Smoke Detector Mail room 45 Pass
Smoke Detector Closed files 35 Pass
Smoke Detector Rm 131 41 Pass
Smoke Detector Rm 130 39 Pass
Smoke Detector Rm 129 97 Pass
Smoke Detector Rm 128 12 Pass
Smoke Detector Rm 127 40 Pass
Smoke Detector Hall at Rm129 36 Pass
Smoke Detector Rm 124 42 Pass
Smoke Detector Cubicle area 21 Pass
Smoke Detector Rm 121 38 Pass
Smoke Detector Rm 122 37 Pass
Smoke Detector Kitchenette at craft room 2 Pass
Manual Pull Station Kitchenette at craft room 2 Pass
Manual Pull Station Cave 1 Pass
Smoke Detector Cave 1 Pass
Manual Pull Station North rear exit 3 Pass
Smoke Detector Outside cardio room 17 Pass
Smoke Detector Cardio room 15 Pass
Smoke Detector Cardio room 14 Pass
Smoke Detector Cardio storage 6 Pass
Smoke Detector Cardio hvac 9 Pass
Duct Detector Cardio hvac 13 Pass
Duct Detector Cardio hvac 5 Pass
Duct Detector Cardio hvac 43 Pass
Smoke Detector Lobby to weight room 18 Pass
Smoke Detector Library 19 Pass
Smoke Detector Weight room 20 Pass
Smoke Detector Weight room 22 Pass
Smoke Detector North entrance 24 Pass
Manual Pull Station North entrance 4 Pass
Smoke Detector North entrance 25 Pass
Manual Pull Station North entrance 2 8 Pass
Smoke Detector Fire place 46 Pass
Smoke Detector Fire place 61 Pass
Manual Pull Station Mid entrance 14 Pass
Smoke Detector Mid entrance 62 Pass
Smoke Detector Cafe entrance 64 Pass
Smoke Detector Storage 163 65 Pass
Smoke Detector South entrance 66 Pass
Manual Pull Station South entrance 32 Pass
Smoke Detector South entrance 68 Pass
Smoke Detector South entrance 69 Pass
Smoke Detector Coat storage 79 Pass
Manual Pull Station South entrance 33 Pass
Smoke Detector Outside Rm177 82 Pass
Smoke Detector Rm 177 86 Pass
Smoke Detector Rm 178 87 Pass
Smoke Detector At 179 88 Pass
Smoke Detector Rm 179 90 Pass
Smoke Detector Rm 180 91 Pass
Smoke Detector Art room 92 Pass
Smoke Detector Art room 93 Pass
Smoke Detector Gathering room 94 Pass
Smoke Detector Gathering room 95 Pass
Smoke Detector Gathering closet 98 Pass
Smoke Detector Side hall exit 23 Pass
Smoke Detector Side Exit 43 Pass
Manual Pull Station Side Exit 29 Pass
Smoke Detector Side women’s bathroom 49 Pass
Smoke Detector Side men’s bathroom 5 Pass
Smoke Detector Hall side men’s bathroom 44 Pass
Smoke Detector Laundry room 79 Pass
Smoke Detector Laundry mop sink 70 Pass
Smoke Detector Mech 196a 69 Pass
Duct Detector Mech 196a 68 Pass
Duct Detector Mech 196a 67 Pass
Duct Detector Outside dock mech room 78 Pass
Duct Detector Outside dock mech room 77 Pass
Smoke Detector Outside dock mech room 76 Pass
Heat Detector Meals on wheels dock 75 Pass
Heat Detector Meals on wheels dock 80 Pass
Smoke Detector Meals on wheels dock 74 Pass
Manual Pull Station Meals on wheels dock 25 Pass
Heat Detector Kitchen pantry 72 Pass
Heat Detector Kitchen 73 Pass
Heat Detector Kitchen 71 Pass
Manual Pull Station Kitchen 21 Pass
Smoke Detector Cafe 89 Pass
Smoke Detector Cafe 43 Pass
Smoke Detector Cafe 44 Pass
Smoke Detector Cafe 45 Pass
Smoke Detector Cafe 65 Pass
Smoke Detector Cafe 66 Pass
Manual Pull Station Cafe 20 Pass
Manual Pull Station Cafe 19 Pass
Manual Pull Station Cafe 18 Pass
Manual Pull Station Cafe 17 Pass
Smoke Detector Cafe storage 48 Pass
Horn / Strobe 27 Throughout Pass
Disclaimer : 1.) All questions are to be answered YES, NO or NOT APPLICABLE (All NO answers are to be explained in Deficiency Report Section of this form.
2.) Inspection, testing and maintenance are to be performed with water supplies (including fire pumps) in service, unless the impairment procedures of Chapter 11 of NFPA 25 are followed.
3.) By signing this document, Signer agrees that :
*All (Part 1 - Owner’s Section) questions were asked and answered correctly by on-site representative.
* All deficiencies have been explained to them 4.) All visible inspections performed from ground level 5.) This is not an engineering review
Building: Fire Station 1
Address: 450 Hwy 279
Fayetteville GA
Contact: Robin
Phone: 770-320-6003
Email:
Time: 1:00-1:30
Date: 3-17-21
Inspector: Kurt Holden IL# 001063
1. OWNER’S SECTION YES NO N/A
a.) Is the building occupied?
b.) Has the occupancy classification and hazard of contents remained the same since the last inspection?
c.) Are all fire protection systems in service?
d.) Has the system remained in service without modification since the last inspection?
e.) Was the system free of actuation devices or alarms since the last inspection?
f.) Has the internal inspection and/or fifth year obstruction investigation been performed within
Pressure Readings
Mechanical Data
System Type System Number Type of Pipe Location Wet 1 CPVC Laundry
System Number
Static Residual Air Pressure
Trip & Time Alarm Type
1 120 50 — — Flow Switch
Control Valve Size
Valve Type Valve Make Security Method
1.5” Ball Milwaukee Monitor Yes
Sprinkler Heads
Drain Location Drain Size Drain Type Main/Test/Aux Signs Y/N @Riser 1” Ball Main No
Head Type Head Model Head Size Quick/Standard White Pendant AS5651 .5” Quick155
Brass upright AS5652 .5” Quick200
White concealed AS5603 .5” Standard155 a.) Are fire pumps, gravity tanks, reservoirs and pressure tanks in good condition and properly maintained?
X b.) Are Fire Dept. connections in satisfactory condition, couplings free, caps in place, and check valves tight?
X c.) Are Fire Dept. Connections accessible and visible? X
d. ) Is the fire pump logbook up to date? X
4. WET SYSTEMS YES NO N/A
a.) Are cold weather valves (OS&Y) in the appropriate open or closed position? X b.) Have all disallowed antifreeze systems been removed? X c.) All sprinkler heads connected to wet systems free from paint, corrosion, and loading?
X d.) Are heads less than 50 years old? X e.) Piping appear to be in good condition, free of rust, corrosion, leaks? X f.) Are the sprinkler heads at proper temperature rating for their location? X g.) Exterior of sprinkler system appear to be satisfactory? X h.) Stock of spare heads with spare head wrench? X i.) Supervisory alarm test satisfactory? Or Locked? X j.) Waterflow alarm test satisfactory? Electric bell? X k.) Water motor gong test satisfactory? X a.) Are the dry valves in service? X b.) Is the air pressure and priming water level in accordance with the manufacturers instructions?
X c.) Has the operation of the air nitrogen supply been tested? X d.) Is it in service? X e.) Were low point drained during inspection? X f.) Did quick opening devices operate satisfactory? X g.) Did heating equipment in the dry valve room operate at the time of inspection? X h.) All sprinkler heads connected to dry systems free from paint, corrosion, and loading?
X i.) Are heads less than 50 years old? X j.)Piping appear to be in good condition, free of rust, corrosion, leaks? X k.) Exterior of dry system appear to be satisfactory? X l.) Stock of spare heads with spare head wrench? X m.) Supervisory alarm test satisfactory? Or Locked? X n.) Alarm devices test satisfactory? X o.) Water motor gong test satisfactory? X p.) Are gauges less than 5 years old? X q.) Has system had internal inspection conducted within last 5 years? X
6. WATER SUPPLIES YES NO N/A
NOTES :Green Tag
Signature of Inspector : KHolden Date : 3-17-21
IL #001063
Fire-X, INC.
2834 SULLIVAN RD.
ATLANTA, GA. 30337
Disclaimer : 1.) All questions are to be answered YES, NO or NOT APPLICABLE (All NO answers are to be explained in Deficiency Report Section of this form.
2.) Inspection, testing and maintenance are to be performed with water supplies (including fire pumps) in service, unless the impairment procedures of Chapter 11 of NFPA 25 are followed.
3.) By signing this document, Signer agrees that :
*All (Part 1 - Owner’s Section) questions were asked and answered correctly by on-site representative.
* All deficiencies have been explained to them 4.) All visible inspections performed from ground level 5.) This is not an engineering review
Building: Fire Station 7
Address: 220 Hampton Rd
Fayetteville Ga
Contact: Robin
Phone:
Email:
Time: 4:30-5:00
Date: 3-16-21
Inspector: Kurt Holden IL# 001063
1. OWNER’S SECTION YES NO N/A
a.) Is the building occupied?
b.) Has the occupancy classification and hazard of contents remained the same since the last inspection?
c.) Are all fire protection systems in service?
d.) Has the system remained in service without modification since the last inspection?
e.) Was the system free of actuation devices or alarms since the last inspection?
f.) Has the internal inspection and/or fifth year obstruction investigation been performed within
Pressure Readings
Mechanical Data
System Type System Number Type of Pipe Location Wet 1 Steel Back storage
System Number
Static Residual Air Pressure
Trip & Time Alarm Type
1 115 95 — — Flow Switch
Control Valve Size
Valve Type Valve Make Security Method
1.5” Butterfly Victaulic Monitor No
Sprinkler Heads
Drain Location Drain Size Drain Type Main/Test/Aux Signs Y/N @Riser 1” Ball Main No
White pendant GL4210 .5” Quick155 a.) Are fire pumps, gravity tanks, reservoirs and pressure tanks in good condition and properly maintained?
X b.) Are Fire Dept. connections in satisfactory condition, couplings free, caps in place, and check valves tight?
X c.) Are Fire Dept. Connections accessible and visible? X
d. ) Is the fire pump logbook up to date? X
4. WET SYSTEMS YES NO N/A
a.) Are cold weather valves (OS&Y) in the appropriate open or closed position? X b.) Have all disallowed antifreeze systems been removed? X c.) All sprinkler heads connected to wet systems free from paint, corrosion, and loading?
X d.) Are heads less than 50 years old? X e.) Piping appear to be in good condition, free of rust, corrosion, leaks? X f.) Are the sprinkler heads at proper temperature rating for their location? X g.) Exterior of sprinkler system appear to be satisfactory? X h.) Stock of spare heads with spare head wrench? X i.) Supervisory alarm test satisfactory? Or Locked? X j.) Waterflow alarm test satisfactory? Electric bell? X k.) Water motor gong test satisfactory? X a.) Are the dry valves in service? X b.) Is the air pressure and priming water level in accordance with the manufacturers instructions?
X c.) Has the operation of the air nitrogen supply been tested? X d.) Is it in service? X e.) Were low point drained during inspection? X f.) Did quick opening devices operate satisfactory? X g.) Did heating equipment in the dry valve room operate at the time of inspection? X h.) All sprinkler heads connected to dry systems free from paint, corrosion, and loading?
X i.) Are heads less than 50 years old? X j.)Piping appear to be in good condition, free of rust, corrosion, leaks? X k.) Exterior of dry system appear to be satisfactory? X l.) Stock of spare heads with spare head wrench? X m.) Supervisory alarm test satisfactory? Or Locked? X n.) Alarm devices test satisfactory? X o.) Water motor gong test satisfactory? X p.) Are gauges less than 5 years old? X q.) Has system had internal inspection conducted within last 5 years? X
6. WATER SUPPLIES YES NO N/A
NOTES :Green Tag
Signature of Inspector : KHolden Date : 3-16-21
IL #001063
Fire-X, INC.
2834 SULLIVAN RD.
ATLANTA, GA. 30337
Disclaimer : 1.) All questions are to be answered YES, NO or NOT APPLICABLE (All NO answers are to be explained in Deficiency Report Section of this form.
2.) Inspection, testing and maintenance are to be performed with water supplies (including fire pumps) in service, unless the impairment procedures of Chapter 11 of NFPA 25 are followed.
3.) By signing this document, Signer agrees that :
*All (Part 1 - Owner’s Section) questions were asked and answered correctly by on-site representative.
* All deficiencies have been explained to them 4.) All visible inspections performed from ground level 5.) This is not an engineering review
Building: Fayette County Historic Courthouse
Address: 200 Courthouse Sq.
Fayetteville Ga
Contact: Robin
Phone: 770-320-6003
Email:
Time: 11:30-12:30
Date: 3-19-21
Inspector: Kurt Holden IL# 001063
1. OWNER’S SECTION YES NO N/A
a.) Is the building occupied?
b.) Has the occupancy classification and hazard of contents remained the same since the last inspection?
c.) Are all fire protection systems in service?
d.) Has the system remained in service without modification since the last inspection?
e.) Was the system free of actuation devices or alarms since the last inspection?
f.) Has the internal inspection and/or fifth year obstruction investigation been performed within
Pressure Readings
Mechanical Data
System Type System Number Type of Pipe Location Wet 1 Steel Basement
System Number
Static Residual Air Pressure
Trip & Time Alarm Type
1 65 40 — — Flow Switch
Control Valve Size
Valve Type Valve Make Security Method
Signs Y/N
3” Ball Kennedy Lock Yes
2.5” Ball Kennedy Lock No
2.5” Ball Kennedy Lock Yes
2.5” Ball Kennedy Lock No
Sprinkler Heads
Drain Location Drain Size Drain Type Main/Test/Aux Signs Y/N 1st Floor Sectional .5” Gate Main No
3 floor back closet 1” Gate Test No
3rd Floor Sectional .5” Gate Main No
2nd Floor Sectional .5” Gate Main No
Head Type Head Model Head Size Quick/Standard Chrome Pendant SSP453A .5” Standard155
Brass upright CSC1980 .5” Standard155 a.) Are fire pumps, gravity tanks, reservoirs and pressure tanks in good condition and properly maintained?
X b.) Are Fire Dept. connections in satisfactory condition, couplings free, caps in place, and check valves tight?
X c.) Are Fire Dept. Connections accessible and visible? X
d. ) Is the fire pump logbook up to date? X
4. WET SYSTEMS YES NO N/A
a.) Are cold weather valves (OS&Y) in the appropriate open or closed position? X b.) Have all disallowed antifreeze systems been removed? X c.) All sprinkler heads connected to wet systems free from paint, corrosion, and loading?
X d.) Are heads less than 50 years old? X e.) Piping appear to be in good condition, free of rust, corrosion, leaks? X f.) Are the sprinkler heads at proper temperature rating for their location? X g.) Exterior of sprinkler system appear to be satisfactory? X h.) Stock of spare heads with spare head wrench? X i.) Supervisory alarm test satisfactory? Or Locked? X j.) Waterflow alarm test satisfactory? Electric bell? X k.) Water motor gong test satisfactory? X l.) Are gauges less than 5 years old? X 17 m.) Has system had internal inspection conducted within last 5 years? X 17 a.) Are the dry valves in service? X b.) Is the air pressure and priming water level in accordance with the manufacturers instructions?
X c.) Has the operation of the air nitrogen supply been tested? X d.) Is it in service? X e.) Were low point drained during inspection? X f.) Did quick opening devices operate satisfactory? X g.) Did heating equipment in the dry valve room operate at the time of inspection? X h.) All sprinkler heads connected to dry systems free from paint, corrosion, and loading?
X i.) Are heads less than 50 years old? X j.)Piping appear to be in good condition, free of rust, corrosion, leaks? X k.) Exterior of dry system appear to be satisfactory? X l.) Stock of spare heads with spare head wrench? X m.) Supervisory alarm test satisfactory? Or Locked? X n.) Alarm devices test satisfactory? X o.) Water motor gong test satisfactory? X p.) Are gauges less than 5 years old? X q.) Has system had internal inspection conducted within last 5 years? X
6. WATER SUPPLIES YES NO N/A
@ Riser Missing control valve sign
1st Floor Sectional Corroded leaking 3” pipe
Missing drain sign and needs to be piped out.
3rd Floor Sectional Missing control sign
2nd floor hall Painted pendant
All Floor Sectionals Main drain isn’t piped out. Recommended to pipe out all drains for future maintenance needed.
FDC Both caps are missing
NOTES :Green Tag
Signature of Inspector : KHolden Date : 3-19-21
IL #001063
Fire-X, INC.
2834 SULLIVAN RD.
ATLANTA, GA. 30337
Disclaimer : 1.) All questions are to be answered YES, NO or NOT APPLICABLE (All NO answers are to be explained in Deficiency Report Section of this form.
2.) Inspection, testing and maintenance are to be performed with water supplies (including fire pumps) in service, unless the impairment procedures of Chapter 11 of NFPA 25 are followed.
3.) By signing this document, Signer agrees that :
*All (Part 1 - Owner’s Section) questions were asked and answered correctly by on-site representative.
* All deficiencies have been explained to them 4.) All visible inspections performed from ground level 5.) This is not an engineering review
Building: Fire Station 5
Address: 1850 Hwy 85
Fayetteville GA
Contact: Robin
Phone: 770-320-6003
Email:
Time: 4:00-4:30
Date: 3-16-21
Inspector: Kurt HoldenIL# 001063
1. OWNER’S SECTION YES NO N/A
a.) Is the building occupied?
b.) Has the occupancy classification and hazard of contents remained the same since the last inspection?
c.) Are all fire protection systems in service?
d.) Has the system remained in service without modification since the last inspection?
e.) Was the system free of actuation devices or alarms since the last inspection?
f.) Has the internal inspection and/or fifth year obstruction investigation been performed within
Pressure Readings
Mechanical Data
System Type System Number Type of Pipe Location Wet 1 CPVC Laundry
System Number
Static Residual Air Pressure
Trip & Time Alarm Type
1 110 85 — — Flow Switch
Control Valve Size
Valve Type Valve Make Security Method
1.5” Butterfly Milwaukee Monitor Yes
Sprinkler Heads
Drain Location Drain Size Drain Type Main/Test/Aux Signs Y/N @Riser 1” Ball Main No
White Pendant VK430 .5” Quick155 a.) Are fire pumps, gravity tanks, reservoirs and pressure tanks in good condition and properly maintained?
X b.) Are Fire Dept. connections in satisfactory condition, couplings free, caps in place, and check valves tight?
X c.) Are Fire Dept. Connections accessible and visible? X
d. ) Is the fire pump logbook up to date? X
4. WET SYSTEMS YES NO N/A
a.) Are cold weather valves (OS&Y) in the appropriate open or closed position? X b.) Have all disallowed antifreeze systems been removed? X c.) All sprinkler heads connected to wet systems free from paint, corrosion, and loading?
X d.) Are heads less than 50 years old? X e.) Piping appear to be in good condition, free of rust, corrosion, leaks? X f.) Are the sprinkler heads at proper temperature rating for their location? X g.) Exterior of sprinkler system appear to be satisfactory? X h.) Stock of spare heads with spare head wrench? X i.) Supervisory alarm test satisfactory? Or Locked? X j.) Waterflow alarm test satisfactory? Electric bell? X k.) Water motor gong test satisfactory? X l.) Are gauges less than 5 years old? X20 m.) Has system had internal inspection conducted within last 5 years? X20 a.) Are the dry valves in service? X b.) Is the air pressure and priming water level in accordance with the manufacturers instructions?
X c.) Has the operation of the air nitrogen supply been tested? X d.) Is it in service? X e.) Were low point drained during inspection? X f.) Did quick opening devices operate satisfactory? X g.) Did heating equipment in the dry valve room operate at the time of inspection? X h.) All sprinkler heads connected to dry systems free from paint, corrosion, and loading?
X i.) Are heads less than 50 years old? X j.)Piping appear to be in good condition, free of rust, corrosion, leaks? X k.) Exterior of dry system appear to be satisfactory? X l.) Stock of spare heads with spare head wrench? X m.) Supervisory alarm test satisfactory? Or Locked? X n.) Alarm devices test satisfactory? X o.) Water motor gong test satisfactory? X p.) Are gauges less than 5 years old? X q.) Has system had internal inspection conducted within last 5 years? X
6. WATER SUPPLIES YES NO N/A
NOTES : Green Tag
Signature of Inspector : Ku! Holden Date : 3-16-21
IL #001063
Fire-X, INC.
2834 SULLIVAN RD.
ATLANTA, GA. 30337
Disclaimer : 1.) All questions are to be answered PASS, FAIL or NOT APPLICABLE (All FAIL answers are to be explained in Deficiency Report Section of this form.
2.) All Inspections Testing and Maintenance are conducted to NFPA 25 Standards.
3.) By signing this document, Signer agrees that :
*All (Part 1 - Owner’s Section) questions were asked and answered correctly by on-site representative.
* All deficiencies have been explained to them 4.) All visible inspections performed from ground level 5.) This is not an engineering review
Building: Fayette County Justice Center
Address: 6 Center Dr
Fayetteville Ga
Contact: Jeff Mayo
Phone:
Email:
Time: 7:00 am
Date: 3/26/2021
Test Frequency: Annual
Inspector: E.Eubanks #001118
Results: Green
Owners Section
Mechanical Data
To Be Answered By Owner/Owner Representative Only Yes No N/A a.) Is the building occupied?
b.) Has the occupancy classification and hazard of contents remained the same since the last inspection?
c.) Are all fire protection systems in service?
d.) Has the system remained in service without modification since the last inspection?
e.) Was the system free of actuation devices or alarms since the last inspection?
f.) Has the internal inspection and/or fifth year obstruction investigation been performed within the last five years?
Signature of Owner/Representative :
System Type
System Number
Type of Pipe
Monitored Y/N Location
Wet 1 (@pump) Galvanized Y Pump room
Wet 2 Steel Y Riser room
Location System Number
Valve Type
Valve Make
Security Method
Valve Size Sign Y/N
Test ed
Y/N Pump room 1 PIV Kennedy Monitor 6” Pump Y
Pump room 1 OS&Y Kennedy Monitor 8” BF Y
Pump room 1 OS&Y Kennedy Monitor 8” BF Y
Pump room 1 Butterfly Nibco Monitor 8” Tank Supply Y
Dry Mechanical Data
Pressure Readings
Pump room 1 Butterfly Nibco Monitor 8” Supply Y
Pump room 1 Butterfly Nibco Monitor 8” Supply Y
Pump room 1 Butterfly Nibco Monitor 6” Flow meter Y
Pump room 1 Butterfly Nibco Monitor 6” Flow meter Y
Riser room 2 Butterfly Victaulic Monitor 4” Y Y
1st floor north N2-1 Butterfly Victaulic Monitor 1.5” N Y
2nd floor north N2-2 Butterfly Victaulic Monitor 1.5” N Y
3rd floor north N2-3 Butterfly Victaulic Monitor 1.5” N Y
3rd floor south S2-3 Butterfly Victaulic Monitor 1.5” N Y
2nd floor south S2-2 Butterfly Victaulic Monitor 1.5” N Y
1st floor south S2-1 Butterfly Victaulic Monitor 1.5” N Y
Location System Number
Valve Type
Valve Make
Security Method
Valve Size Sign Y/N
Test ed
Y/N
Dry Valve Make/ Model Compressor Make Model/ SSN HP / Size Pass /Fail
N/A N/A N/A N/A N/A
System Number Static Residual Air
Pressure Trip & Time Static After Flow Alarm Type
1 190 100 Flow Switch
2 160 150 Flow Switch
1st floor north
200 160 Flow Switch
Sprinkler Heads
2nd floor north
190 160 Flow Switch
3rd floor north
180 150 Flow Switch
3rd floor south
200 175 Flow Switch
2nd floor south
185 170 Flow Switch
1st floor south
195 180 Flow Switch
System Number Static Residual Air
Pressure Trip & Time Static After Flow Alarm Type
Drain Location System Number Drain Size Valve Type Main/Test/
Aux Signs Y/N
2nd Janitor closet N2-1 1” Gate Aux Aux
2nd Janitor closet N2-2 1” Gate Aux Aux
2nd Janitor closet N2-3 1” Gate Aux Aux
1st Janitor closet S2-3 1” Gate Aux Aux
1st Janitor closet S2-2 1” Gate Aux Aux
1st Janitor closet S2-1 1” Gate Aux Aux
@Riser 2 1.5” Gate Main Y
Head Type Head Model Head Size Quick/Standard
Brass Pendant R1015 .5” Standard155
Chrome Pendant R3615 .5” Quick155
Brass pendant 701A .5” Quick155
White concealed G4A 701A .5” Standard155
Institutional ZX-SR-Inst .5” Standard165
Wet Systems Pass Fail N/A
Are valves in the appropriate open or closed position? X
Are sprinkler heads connected to system free of paint, corrosion & loading? X
Are heads less than 50 years old? X
Piping appear to be in good condition, free of rust, corrosion, leaks? X
Are the sprinkler heads at proper temperature rating for their location? X
Exterior of sprinkler system appear to be satisfactory? X
Stock of spare heads with spare head wrench? X
Supervisory alarm test satisfactory? Or Locked? X
Waterflow alarm test satisfactory? X
Electric bell test satisfactory? X
Water motor gong test satisfactory? X
Are gauges less than 5 years old? X
Has system had internal inspection conducted within last 5 years? X
Are visible pipe, hangers and seismic braces appear not be damaged or loose? X
Adequate heat in areas of wet piping? X
Hydraulic placard securely attached to riser and legible? X
Is FDC visible and free from damage? X
Do FDC couplings swivel and rotate smoothly? X
FDC capsid place and free of damage? X
Main drain test performed? X
Static pressure less than 175PSI? X
Dry Systems Pass Fail N/A
Are the dry valves in service? X
Is the air pressure and priming water level in accordance with the manufacturers instructions? X
Were low point drained during inspection? X
Did quick opening devices operate satisfactory? X
Did heating equipment in the dry valve room operate at the time of inspection? X
All sprinkler heads connected to dry systems free from paint, corrosion, and loading? X
Are heads less than 50 years old? X
Piping appear to be in good condition, free of rust, corrosion, leaks? X
Exterior of dry system appear to be satisfactory? X
Stock of spare heads with spare head wrench? X
Alarm devices test satisfactory? X
Water motor gong test satisfactory? X
Electric bell test satisfactory? X
Are gauges less than 5 years old? X
Has system had internal inspection conducted within last 5 years? X
Main drain test performed? X
Static pressure leads than 175PSI? X
X
Fire Pumps Pass Fail N/A
Is it service? X
Are valves in the appropriate open or closed position? X
Is the fire pump log book up to date? X
Is drain line free of debris? X
Does the PRV operate properly during churn? X
Are gauges less than 5 years old? X
Has system had internal inspection conducted within last 5 years? X
Piping appear to be in good condition, free of rust, corrosion, leaks? X
Supervisory alarm test satisfactory? Or Locked? X
Does the pump reach 100% capacity? X
Does the reach 150% capacity? X
Is fuel level above 3/4 for diesel pumps only? X
Test header free from damage and corrosion? Caps in place? X
Are the batteries levels at proper rating for diesel pumps only? X
Does jockey pump operate with pressure drop correctly? X
Are gauges less than 5 years old? X
Has system had internal inspection conducted within last 5 years? X
Deficiency Page
NOTES :3rd floor north stairwell riser has 2 control valves only one is monitored the other is not nor is it secured.
Signature of Inspector :Ed!e Eubanks Date :3/26/2021
IL #001118
FIRE-X, INC.
2834 SULLIVAN RD.
ATLANTA, GA. 30337
Disclaimer : 1.) All questions are to be answered YES, NO or NOT APPLICABLE (All NO answers are to be explained in Deficiency Report Section of this form.
2.) Inspection, testing and maintenance are to be performed with water supplies (including fire pumps) in service, unless the impairment procedures of Chapter 11 of NFPA 25 are followed.
3.) By signing this document, Signer agrees that :
*All (Part 1 - Owner’s Section) questions were asked and answered correctly by on-site representative.
* All deficiencies have been explained to them 4.) All visible inspections performed from ground level 5.) This is not an engineering review
Building: Fayette County Library
Address: 1821 Heritage Park Way
Fayetteville GA
Contact: Robin
Phone: 770-320-6003
Email:
Time: 0830-0930
Date: 3-9-21
Inspector: Kurt Holden IL# 001063
1. OWNER’S SECTION YES NO N/A
a.) Is the building occupied?
b.) Has the occupancy classification and hazard of contents remained the same since the last inspection?
c.) Are all fire protection systems in service?
d.) Has the system remained in service without modification since the last inspection?
e.) Was the system free of actuation devices or alarms since the last inspection?
f.) Has the internal inspection and/or fifth year obstruction investigation been performed within
Pressure Readings
Mechanical Data
System Type System Number Type of Pipe Location Wet 1 Steel Boiler/electrical room
System Number
Static Residual Air Pressure
Trip & Time Alarm Type
1 65 45 — — Flow Switch
Water gong
Control Valve Size
Valve Type Valve Make Security Method
Signs Y/N
4” Butterfly Nibco Monitor Yes
4” Alarm Star — —
Sprinkler Heads
Drain Location Drain Size Drain Type Main/Test/Aux Signs Y/N @riser 2” Gate Main Yes
Head Type Head Model Head Size Quick/Standard White concealed SSP7224 .5” Quick155
Brass upright SSU722A .5” Standard155
DD Sidewalls Standard155
Chrome Pendant SSP722A .5” Standard155 a.) Are fire pumps, gravity tanks, reservoirs and pressure tanks in good condition and properly maintained?
X b.) Are Fire Dept. connections in satisfactory condition, couplings free, caps in place, and check valves tight?
X c.) Are Fire Dept. Connections accessible and visible? X
d. ) Is the fire pump logbook up to date? X
4. WET SYSTEMS YES NO N/A
a.) Are cold weather valves (OS&Y) in the appropriate open or closed position? X b.) Have all disallowed antifreeze systems been removed? X c.) All sprinkler heads connected to wet systems free from paint, corrosion, and loading?
X d.) Are heads less than 50 years old? X e.) Piping appear to be in good condition, free of rust, corrosion, leaks? X f.) Are the sprinkler heads at proper temperature rating for their location? X g.) Exterior of sprinkler system appear to be satisfactory? X h.) Stock of spare heads with spare head wrench? X i.) Supervisory alarm test satisfactory? Or Locked? X j.) Waterflow alarm test satisfactory? Electric bell? X k.) Water motor gong test satisfactory? X l.) Are gauges less than 5 years old? X 18 m.) Has system had internal inspection conducted within last 5 years? X 18 a.) Are the dry valves in service? X b.) Is the air pressure and priming water level in accordance with the manufacturers instructions?
X c.) Has the operation of the air nitrogen supply been tested? X d.) Is it in service? X e.) Were low point drained during inspection? X f.) Did quick opening devices operate satisfactory? X g.) Did heating equipment in the dry valve room operate at the time of inspection? X h.) All sprinkler heads connected to dry systems free from paint, corrosion, and loading?
X i.) Are heads less than 50 years old? X j.)Piping appear to be in good condition, free of rust, corrosion, leaks? X k.) Exterior of dry system appear to be satisfactory? X l.) Stock of spare heads with spare head wrench? X m.) Supervisory alarm test satisfactory? Or Locked? X n.) Alarm devices test satisfactory? X o.) Water motor gong test satisfactory? X p.) Are gauges less than 5 years old? X q.) Has system had internal inspection conducted within last 5 years? X
6. WATER SUPPLIES YES NO N/A
NOTES : Green Tag
Signature of Inspector : KHolden Date : 3-9-21
IL #001063
Fire-X, INC.
2834 SULLIVAN RD.
ATLANTA, GA. 30337
Disclaimer : 1.) All questions are to be answered YES, NO or NOT APPLICABLE (All NO answers are to be explained in Deficiency Report Section of this form.
2.) Inspection, testing and maintenance are to be performed with water supplies (including fire pumps) in service, unless the impairment procedures of Chapter 11 of NFPA 25 are followed.
3.) By signing this document, Signer agrees that :
*All (Part 1 - Owner’s Section) questions were asked and answered correctly by on-site representative.
* All deficiencies have been explained to them 4.) All visible inspections performed from ground level 5.) This is not an engineering review
Building: Fayette County Admin Complex
Address: 140 Stonewall Ave W
Fayetteville GA
Contact: Robin
Phone: 770-320-6003
Email:
Time: 930-1100
Date: 3-9-21
Inspector: Kurt Holden IL# 001063
1. OWNER’S SECTION YES NO N/A
a.) Is the building occupied?
b.) Has the occupancy classification and hazard of contents remained the same since the last inspection?
c.) Are all fire protection systems in service?
d.) Has the system remained in service without modification since the last inspection?
e.) Was the system free of actuation devices or alarms since the last inspection?
f.) Has the internal inspection and/or fifth year obstruction investigation been performed within
Pressure Readings
Mechanical Data
System Type System Number Type of Pipe Location Wet 1 Steel Center of building in lobby
System Number
Static Residual Air Pressure
Trip & Time Alarm Type
1 60 50 — — Flow Switch
Water gong
Control Valve Size
Valve Type Valve Make Security Method
Signs Y/N
6” Butterfly Grinnell Lock Yes
6” Alarm Viking — —
4” Butterfly Grinnell Lock Yes
6 Butterfly Grinnell Lock Yes
Sprinkler Heads
Drain Location Drain Size Drain Type Main/Test/Aux Signs Y/N @Riser 2” Gate Main No
Fire&EMS Admin 1.25” Gate
Ball
Test Yes
Head Type Head Model Head Size Quick/Standard Chrome sidewall TY3331 .5” Quick155
Chrome Pendant VK589A .5” Standard155
Brass upright VK589A .5” Standard155
White concealed SSP701A G4 .5” Standard155 a.) Are fire pumps, gravity tanks, reservoirs and pressure tanks in good condition and properly maintained?
X b.) Are Fire Dept. connections in satisfactory condition, couplings free, caps in place, and check valves tight?
X c.) Are Fire Dept. Connections accessible and visible? X
d. ) Is the fire pump logbook up to date? X
4. WET SYSTEMS YES NO N/A
a.) Are cold weather valves (OS&Y) in the appropriate open or closed position? X b.) Have all disallowed antifreeze systems been removed? X c.) All sprinkler heads connected to wet systems free from paint, corrosion, and loading?
X d.) Are heads less than 50 years old? X e.) Piping appear to be in good condition, free of rust, corrosion, leaks? X f.) Are the sprinkler heads at proper temperature rating for their location? X g.) Exterior of sprinkler system appear to be satisfactory? X h.) Stock of spare heads with spare head wrench? X i.) Supervisory alarm test satisfactory? Or Locked? X j.) Waterflow alarm test satisfactory? Electric bell? X k.) Water motor gong test satisfactory? X l.) Are gauges less than 5 years old? X 21 m.) Has system had internal inspection conducted within last 5 years? X 21 a.) Are the dry valves in service? X b.) Is the air pressure and priming water level in accordance with the manufacturers instructions?
X c.) Has the operation of the air nitrogen supply been tested? X d.) Is it in service? X e.) Were low point drained during inspection? X f.) Did quick opening devices operate satisfactory? X g.) Did heating equipment in the dry valve room operate at the time of inspection? X h.) All sprinkler heads connected to dry systems free from paint, corrosion, and loading?
X i.) Are heads less than 50 years old? X j.)Piping appear to be in good condition, free of rust, corrosion, leaks? X k.) Exterior of dry system appear to be satisfactory? X l.) Stock of spare heads with spare head wrench? X m.) Supervisory alarm test satisfactory? Or Locked? X n.) Alarm devices test satisfactory? X o.) Water motor gong test satisfactory? X p.) Are gauges less than 5 years old? X q.) Has system had internal inspection conducted within last 5 years? X
6. WATER SUPPLIES YES NO N/A
NOTES : Green Tag
Signature of Inspector : KHolden Date : 3-9-21
IL #001063
Fire-X, INC.
2834 SULLIVAN RD.
ATLANTA, GA. 30337
PUMP TEST REPORT
DATE: 3/26/21
NAME OF PROPERTY: Fayette County Justice Center TIME: 700
ADDRESS: 6 Center Drive INS.FILE#:
Fayetteville GA City State Zip
IDENTIFY ALL SYSTEM(S) INVOLVED: Justice Center systems/ Sheriffs Office and Jail systems/ Hydrants/ Watere Storage tank
PUMP INFO: MAKE: POWER TYPE: Electric TYPE: Turbine SUPERVISION: Yes
RATED CAPACITY: 1000
RATED PRESSURE: 80 CONTROLLER: MAKE: Eaton
RATED R.P.M.: 1700
Pressure at 150% 75 LISTED: Yes
Maximum Pressure 90 WATER SUPPLY: City & Tank
SPRINKLER SYSTEM DEMAND: 1000 G.P.M. AT LBS. PRESSURE
SUCTION DISCHARGE NET R.P.M. Oriface Size uses to capture PSI: FLOW METER TOTAL DISCHARGE PRESSURE PRESSURE PRESSURE Coefficients: N/A PERCENTAGE
90 190 83 PITOT CHURN CHURN CHURN CHURN CHURN CHURN CHURN CHURN CHURN 0%G.P.M. X X X X X X X X
0 183 79 PITOT F.M.100% 100.00G.P.M. 1000 0 0 0 0 0 0 0
0 160 70 PITOT F.M.150% 150.00G.P.M. 1500 0 0 0 0 0 0 0
0 PITOT 0.00G.P.M. 0 0 0 0 0 0 0 0
0 PITOT 0.00G.P.M. 0 0 0 0 0 0 0 0
0 PITOT 0.00G.P.M. 0 0 0 0 0 0 0 0
REMARKS ON TEST:
Pass *with in 5% of rating
Randall Tenney CUSTOMER:
SIGNATURE OF PERSON PERFORMING TEST ADDRESS:
Jeff Mayo
PHONE:
WITNESS (OWNER OR LESEE OF PROPERTY)
PS
I
22.5
67.5
GPM
0 400 800 1200 1600
Rated Actual
Disclaimer : 1.) All questions are to be answered YES, NO or NOT APPLICABLE (All NO answers are to be explained in Deficiency Report Section of this form.
2.) Inspection, testing and maintenance are to be performed with water supplies (including fire pumps) in service, unless the impairment procedures of Chapter 11 of NFPA 25 are followed.
3.) By signing this…
This is the start of the file's text. The full file is on GovTribe.
Other files
| File | Type | Posted |
|---|---|---|
| Award Information | — | |
| #2068-A Addendum 2 | — | |
| #2068-A RFQ | — |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .