2026 CU WPCD Smithdale Heights Water Booster .pdf

PDF 148 KB Posted

Attached to
2026 CU WPCD Smithdale Heights Water Booster Station
Solicitation number
PE-66895-NONST-2026-000000055
Issued by
Fayette County, Georgia

About this file

This is a Scope of Work specification document for the City of Cumming Department of Utilities in Georgia for the Smithdale Heights Water Booster Station project. The project requires the procurement and installation of one factory-assembled, diesel-powered emergency standby generator set rated at 40 kW with a standby voltage of 277/480 VAC, three-phase, 4-wire configuration, and 60 Hz frequency. The generator must be new, factory-tested, and listed for emergency standby service, complete with a weatherproof aluminum enclosure, sub-base fuel tank with 24-hour fuel capacity, automatic transfer switch rated at 125 amps at 480 VAC, and associated controls. The equipment must comply with U.S. EPA Stationary Emergency requirements, UL 2200 listing, NFPA 110 Type 10 Level 1, EPA Tier 3 emissions standards, and ASCE 7-10 wind loading requirements with a 180 MPH wind load rating. Bids are to be submitted to the City of Cumming Department of Utilities, 4th Floor Front Desk, 100 Main Street, Cumming, Georgia 30040.

The generator specification includes an electronic isochronous governor, brushless alternator with Class 105C insulation and Increased Motor Starting capability, sound-attenuated enclosure meeting Sound Level 2 attenuation standards, dual-wall regional steel fuel tank with high and low fuel level switches, digital controller with programmable inputs and outputs, 250 Amp 3-pole circuit breaker, 12-volt starting battery system with 6 amp regulated charger, and MODBUS TCP communications module. The manufacturer shall provide a two-year comprehensive warranty commencing upon successful startup and commissioning, factory startup, operational testing, maintenance training, and factory load bank testing. Additional items to be furnished and installed by others include generator unloading, concrete pad placement, fuel piping, exhaust piping, electrical conduit and wiring, NETA testing, and a maintenance agreement. Equipment pricing excludes sales tax and must include shipping; current lead times are to be confirmed by the manufacturer.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project: Smithdale Heights Generator

1.0 General

Provide one (1) factory-assembled, diesel-powered emergency standby generator set complete with weatherproof enclosure, sub-base fuel tank, automatic transfer switch, and associated controls as specified herein. Equipment shall be new, factory tested, and listed for emergency standby service.

The generator shall have the following minimum ratings:

Description Requirement

Standby Rating 40 kW

Frequency 60 Hz

Voltage 277/480 VAC

Phase Three Phase

Configuration 4-Wire Wye

Duty Rating Emergency Standby Power (ESP)

Application Stationary Emergency

Fuel Type Diesel

The generator shall comply with U.S. EPA Stationary Emergency requirements.

The generator shall comply with the latest editions of:

UL 2200 Listed NFPA 110 Type 10, Level 1 capable EPA Tier 3 Emissions EPA NSPS Stationary Emergency Certification ASCE 7-10 Wind Loading Requirements

The engine shall include:

Four-cycle diesel engine Electronic isochronous governor 12-volt DC electric starter Engine-mounted battery charging alternator Normal-duty air cleaner Radiator cooling system suitable for high ambient temperatures Low coolant shutdown protection Coolant drain extension Oil drain extension Factory-filled 50/50 antifreeze mixture

Provide a brushless alternator with:

480/277 Volt output 60 Hz operation Class 105°C insulation 40°C ambient rating Increased Motor Starting (IMS) capability Aluminum winding construction Torque matched excitation and voltage regulation

Provide a factory-installed sound attenuated enclosure meeting the following requirements:

Aluminum construction Sound Level 2 attenuation Integrated exhaust system Green factory finish Wind load rating of 180 MPH Intake baffle

Housing-ready skid base Larger battery rack

Provide a factory-mounted sub-base fuel system including:

Regional dual-wall steel fuel tank Minimum 24-hour fuel capacity at rated load High fuel level alarm 90% high fuel level switch 40% low fuel level switch Mechanical fuel gauge Five-gallon lockable spill containment fill box Fuel tank rupture basin monitoring

Digital controller English language display Emergency stop switch Oil pressure gauge Auxiliary relays (2) Eight (8) programmable digital inputs Eight (8) programmable digital outputs Single-point load connection capability

Provide:

70 250 Amp, 3-pole circuit breaker 600 VAC rating 100% rated breaker UL listed

12-volt starting battery system Six (6) amp regulated battery charger

Description Requirement

Rating 125 Amps

Voltage 480 VAC

Frequency 60 Hz

Phase Three Phase

Neutral Solid Neutral

Cabinet NEMA Type 1

Listing UL 1008 / CSA

The transfer switch shall include:

Electronic controller Security key cover MODBUS TCP communications module Auxiliary contact module (8 contacts) Emergency position relay Normal position relay Generator starting interface Two-year comprehensive warranty

Generator shall be factory tested prior to shipment.

Provide load bank testing.

Generator: Two (2) year manufacturer's warranty Transfer Switch: Two (2) year comprehensive warranty

Warranty shall commence upon successful startup and commissioning.

The following shall be furnished and installed by others unless specifically noted otherwise:

Generator unloading Placement and rigging Concrete pad Fuel Fuel piping Exhaust piping Electrical conduit and wiring Load-side power connections Ship-loose component installation Final installation Startup coordination NETA testing Maintenance agreement

Manufacturer shall provide:

Standard factory startup Operational testing Maintenance training concurrent with startup Load bank testing as specified

Equipment pricing excludes sales tax.

Pricing must include shipping Current lead times are to be confirmed by manufacturer.

Generator maintenance agreement is not included.

Item Description

Generator Diesel Generator

Rating 40 kW Standby

Voltage 277/480V, 3Ø, 4W

Frequency 60 Hz

Fuel Diesel

Enclosure Sound Level 2 Aluminum

Fuel Tank Dual-wall 24-hour sub-base tank

ATS 125A, 480V

Warranty 2 Years

Included Service Factory load bank testing

File details come from the government source that posted it. Updated .