2026_11_02_VSU_EdCenter_Chiller_BidSet_NBP.pdf
PDF 3 MB Posted
- Attached to
- MRR-27-1101 Education Center Chiller Replacement
- Solicitation number
- PE-55100-RFQ-2027-000000070
- Issued by
- Lanier County, Georgia
About this file
This bid set document contains engineering drawings and specifications for Valdosta State University's Education Center Chiller Replacement project (Project No. MRR-27-1101), prepared by NBP Engineers, Inc., Consultants, located at 316 Corporate Parkway, Macon, Georgia. The project involves the replacement of existing water-cooled chiller equipment with two new air-cooled chillers, including demolition of existing components, installation of new HVAC piping, and related mechanical and electrical work. The scope encompasses chilled water system modifications, new circulation pumps with variable frequency drives (VFDs), expansion tanks, chemical feeder systems, and associated pipe supports and insulation. The bid set includes comprehensive HVAC and electrical plans with details for the mechanical room, roof installations, and site improvements such as new chain-link fencing and underground chilled water piping with 4 inches of pea gravel cover. The document is dated November 2, 2026, and carries NBP Engineers' Professional Engineers and Surveyors license (COA#PEF000774) expiring June 30, 2028.
The electrical work includes provision of a new pad-mounted transformer, new load center (LCHR) with associated breakers and controls, power distribution to both chillers with dedicated circuits for heat tracing on exposed piping, and integration of variable frequency drive controls through a BACnet interface to the building automation system. The chiller specifications indicate dual 405-GPM capacity units operating at 56°F entering water temperature with 44°F leaving water temperature, rated for 100-degree Fahrenheit ambient conditions. Piping includes 8-inch chilled water supply and return lines, 6-inch connections to building systems, and provisions for automatic air vents, manual drains, and pressure/temperature monitoring throughout the distribution network. The document provides detailed schedules for equipment including pump data, electrical panel configurations, and system control parameters, with notes requiring coordination between mechanical and electrical contractors and adherence to specified materials, insulation standards, and installation details for all components.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2026_11_02_VSU Ed Center Chiller Project Manu.pdf | ||
| 2026_11_02_VSU Ed Center Invitation to Bid.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INDEX OF
DRAWINGS
TITLESHEET NO.
316 CORPORATE PARKWAY MACON, GEORGIA
NBP ENGINEERS, INC.
CONSULTANTS
Valdosta, Georgia
VALDOSTA STATE UNIVERSITY
E3.1
M0.1
M3.1
EDUCATION CENTER CHILLER REPLACEMENT
M0.2 SITE PLAN - HVAC
ABBREVIATIONS, LEGENDS, & SCHEDULES - HVAC
LARGE SCALE - MECHANICAL ROOM - DEMOLITION & NEW WORK - HVAC
LARGE SCALE - MECHANICAL ROOM - EXISTING & NEW WORK - POWER & RISER DIAGRAM
E0.1 LEGEND, RISER, & DETAILS - ELECTRICAL
M3.2
LARGE SCALE - PARTIAL SECOND FLOOR - TOWER WELL DEMOLITION & NEW WORK - ELECE3.2
LARGE SCALE - PARTIAL SECOND FLOOR - TOWER WELL DEMOLITION & NEW WORK - HVAC
M2.1
M4.1
M5.1
M5.2
FLOW DIAGRAM - HVAC
DETAILS - HVAC
DETAILS - HVAC
PARTIAL FIRST FLOOR PLAN & ROOF PLAN - DEMOLITION & NEW WORK - HVAC
PROJECT No. MRR-27-1101
1 1.02.2026 BID SET
E0.2 SITE PLAN - ELECTRICAL
M0.1
A COMPRESSED AIR
AAV AUTOMATIC AIR VENT
AF AIR FOIL
-AFF ABOVE FINISHED FLOOR
AV ACID VENT
AVD AUTOMATIC VOLUME DAMPER
AW ACID WASTE
-AC ABOVE CEILING
AH- AIR HANDLING UNIT
BBD BOILER BLOW DOWN
BE BOTTOM ELEVATION
BOL BOTTOM OF LINE (UNINSULATED)
BOD BOTTOM OF DUCT
BP- BOOSTER PUMP
BTUH BRITISH THERMAL UNIT PER HOUR
-BF BELOW FLOOR
BFP BACK FLOW PREVENTOR
C CONDUIT
CC COOLING COIL
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CR CONDENSER WATER RETURN
CS CONDENSER WATER SUPPLY
CW DOMESTIC COLD WATER
CAB CABINET FAN
CF CENTRIFICAL FAN
CFM CUBIC FEET PER MINUTE
CFP CHEMICAL FEED PUMP
CFT CHEMICAL FEED TANK
CH CABINET HEATER
CHR CHILLER
CL CENTER LINE
CO CLEANOUT
CP CHILLER PUMP
CPHB CHROME PLATED HOSE BIBB
CT COOLING TOWER
CU COPPER
CV- CONVECTOR
Cv VALVE COEFFICIENT
D DRAIN
DDC DIRECT DIGITAL CONTROL
DHW DOMESTIC HOT WATER
DN DOWN
DP DIFFERENTIAL PRESSURE
DS DOWN SPOUT
DSO DOWN SPOUT OVER FLOW
DX DIRECT EXCHANGE
EAD EXHAUST AIR DAMPER
EAT ENTERING AIR TEMPERATURE
EDB ENTERING DRY BULB
EWB ENTERING WET BULB
ESP END SUCTION PUMP
ESP EXTERNAL STATIC PRESSURE
ELL ELBOW
ET EXPANSION TANK
EQT EQUIPMENT TRAP SET
EWT ENTERING WATER TEMPERATURE
EX EXPANSION TANK LINE
EXT EXTERNAL
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
F&BP FACE & BYPASS
FC FAN COIL UNIT
BPD BYPASS DAMPER
EAL EXHAUST AIR LOUVER
ECH ELECTRIC CABINET HEATER
ABBREVIATIONS
FD FLOOR DRAIN
FF FOULING FACTOR
FF- FLY FAN
FF FINISHED FLOOR
FF FINAL FILTER
FFM FIRE FLOW METER
FLEX FLEXIBLE
FM FIRE MAIN
FMS FLOW METER STATION
FOF FUEL OIL FLOW
FOR FUEL OIL RETURN
FOV FUEL OIL VENT
FOP FUEL OIL PUMP
FP FIRE PUMP
FP- FAN POWERED
FPM FEET PER MINUTE
FPS FEET PER SECOND
FRT FLOW RATE TRANSMITTER
FT FEET
G LOW PRESSURE GAS
GA GAUGE
GPM GALLONS PER MINUTE
GT GREASE TRAP
GTH GRAND TOTAL HEAT
H HEIGHT
HC HEATING COIL
HB HOSE BIBB
HBT HORIZONTAL BLOW THROUGH
HD HUB DRAIN
HDT HORIZONTAL DRAW THROUGH
HP HORSEPOWER/HIGH PRESSURE
HPA HIGH PRESSURE AIR
HPG HIGH PRESSURE GAS
HPS HIGH PRESSURE STEAM
HPWS HEAT PUMP WATER SUPPLY
HPWR HEAT PUMP WATER RETURN
HSC HORIZONTAL SPLIT CASE
HWG HOT WATER GENERATOR
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
ILC IN-LINE CENTRIFICAL
IT INTERVAL TIMER
IN INCHES
INV INVERT
JB JUNCTION BOX
L LENGTH
LR LONG RADIUS
LAT LEAVING AIR TEMPERATURE
LCP LOCAL CONTROL PANEL
LDB LEAVING DRY BULB
LN LIQUID NITROGEN
LWB LEAVING WET BULB
LWT LEAVING WATER TEMPERATURE
LPS LOW PRESSURE STEAM
MAV MANUAL AIR VENT
MVD MANUAL VOLUME DAMPER
MAX MAXIMUM
MBH ONE THOUSAND BTUH PER HOUR
MCC MOTOR CONTROL CENTER
MIN MINIMUM
MH MAN HOLE
MP SUMP (MUD) PUMP
MPS MEDIUM PRESSURE STEAM
MPR MEDIUM PRESSURE RETURN
MTS MEDIUM TEMPERATURE SUPPLY
MTR MEDIUM TEMPERATURE RETURN
MUA MAKE-UP AIR
MUW MAKE-UP WATER
MZ MULTIZONE
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OAD OUTSIDE AIR DAMPER
ODT OUTDOOR TEMPERATURE
PC PUMP CONDENSATE
PD PRESSURE DROP
PRV PRESSURE REDUCING VALVE
PWF PROPELLER WALL FAN
R REFRIGERANT
RA RETURN AIR
RAD RETURN AIR DAMPER
RAS RELIEF AIR SUPPLY
RP RECIRCULATING PUMP
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
RD ROOF DRAIN
RV RELIEF VALVE
SR SHORT RADIUS
OAL OUTSIDE AIR LOUVER
SAN SANITARY SEWER
SC SILL COCK
SCD SMOKE DAMPER
SD STORM DRAIN
SD SMOKE DETECTOR
SF SQUARE FEET
SDO STORM DRAIN OVERFLOW
SHC SENSIBLE HEAT CAPACITY
SP STAND PIPE
SP SUMP PUMP
SPS STATIC PRESSURE SENSOR
STA STATION
TR TEMPERED WATER RETURN
UG UNDERGROUND
VAC VACUUM PIPING
VDT VERTICAL DRAW THROUGH
VTR VENT THROUGH ROOF
WB WET BULB
O2 OXYGEN
F DEGREES FAHRE C DEGREES CENTI
WM WATER METER
WL WATER LINE
WH WATER HEATER
WG WATER GAUGE
W WIDTH
W WASTE
VT VERTICAL TURBINE
VFD VARIABLE FREQUENCY DRIVE
VB VACUUM BREAKER
VAV VARIABLE AIR VOLUME
V VENT
UC UNDERCUT (DOOR - 3/4")
V- VALVE
TOS TOP OF STRUCTURE
TB THRUST BLOCK
T TEMPERED WATER
STR STRAINER
SP STATIC PRESSURE
SP SPRINKLER PIPE
SG SPECIALTY GAS
EUH ELECTRIC UNIT HEATER
RECIRCULATING
DHR DOMESTIC HOT WATER
TRANSMITTER
DPT DIFFERENTIAL PRESSURE
PER MINUTE
SCIM STANDARD CUBIC INCHES
TEMPERATURE
SST SATURATED SUCTION
(UNINSULATED)
TE TOP ELEVATION
(TOWER) PUMP
TP CONDENSER WATER
FSD FIRE/SMOKE DAMPER
EA EXHAUST AIR
MA MIXED AIR
AE ADJUSTABLE AIR EXTRACTOR
RAO RETURN AIR OPENING
AD AREA DRAIN/ACCESS DOOR
SINGLE LINE DUCT LEGEND
DUCT (SUPPLY, RETURN & EXHAUST)
SUPPLY DUCT UP
SUPPLY DUCT DOWN
RETURN OR EXHAUST DUCT UP
RETURN OR EXHAUST DUCT DOWN
DUCT RISE
DUCT DOWN
VOLUME DAMPER (MANUAL UNLESS INDICATED A.V.D.)
TRANSITION
DUCT TAKE-OFF (SEE SPEC. PERTAINING TO DEFLECTROLS)
TRANSITION (FLAT ON TOP)
TRANSITION (FLAT ON BOTTOM)
TRANSITION (TOP OR BOTTOM ONLY)
SUPPLY CEILING DIFFUSER
RETURN OR EXHAUST CEILING GRILLE
SIDEWALL SUPPLY
SIDEWALL RETURN
FLEXIBLE CONNECTION (DUCT)
RELIEF AIR SUPPLY TO TOILET
DUCT SPLIT WITH SPLITTER DAMPER
FLEX. DUCT WITH SCREW ON COLLAR, TAKE-OFF
DUCT WITH DUCT LINER
SQUARE ELBOW WITH TURNING VANES
RADIUS ELBOW (SEE SPECS. PERTAINING TO TURNING VANES)
AUTOMATIC VOLUME DAMPER
DN
R
12\10 SPLIT
OR
OR
SCD
FOB
T OR B
RAS
AVD
FD/SCD
FD
SMOKE CONTROL DAMPER
COMBINATION FIRE/SMOKE CONTROL DAMPER
FIRE DAMPER (FD)
FIRE DAMPER
SPS
SD
COMBINATION STARTER
STARTER
PIPE SLEEVE
CONCENTRIC REDUCER
PIPE ANCHOR
HVAC LEGEND
BALL VALVE WITH
3/4" HOSE END
BALANCE VALVE
THREADED & FLANGED
GLOBE VALVE
CHECK VALVE
GATE VALVE
BUTTERFLY VALVE
CONTROL VALVE
PLAN VIEW
RELIEF VALVE
FLANGED UNION
BRANCH OUT TOP
STRAINER
BRANCH OUT BOTTOM
ELBOW DOWN
ELBOW UP
TEE OUT TOP
BLIND FLANGE
PIPE CAP
AUTOMATIC AIR VENTAAV
FLEX. PIPE CONN.
BACKFLOW PREVENTER
TEE OUT BOTTOM
MANUAL AIR VENT
PIPE TEST PLUG
COLD WATER DOMESTIC
NATURAL GAS
DRAIN
CHILLED WATER RETURN
HEATING WATER RETURN
HOT WATER DOMESTIC
G
D
DUCT SIZE FIRST DIMENSION
IS SIDE SHOWN
24\12
DOOR GRILLE
C.F.M.
REFERS TO DETAIL OR
PLAN ON SHEET M-1.THERMOSTAT
INTERVAL TIMER
T
I.T.
1\M-4
DUCT/PLENUM w/LINER
FIRE DAMPER
ELBOW WITH
TURNING VANES
FLEX. DUCT CONN.
TURNING VANES
ELBOW WITHOUT
INSULATED FLEX. DUCT
INSULATED FLEX. DUCT
c
ECCENTRIC REDUCER
HWS
HWR
CHS
CHR
CONDENSER WATER RETURN
CS
CR
STATIC PRESSURE SENSOR
SMOKE DETECTOR
POINT OF CONNECTION
DUCT SPLIT
THREADED & FLANGED
THREADED & FLANGED
UNION
GAUGE TAPPING
GAUGE WITH TAPPING
THREADED & FLANGED
THREADED & FLANGED
PIPE SOCKET WELL
T G
ANNULAR ELEMENT FLOW STATION
DAMPER - BLADE VIEW DAMPER - END VIEW
xx{K OR xx/xx}K ROUND OR FLAT OVAL DUCT (K)
DOUBLE WALL INSULATED
ROUND OR FLAT OVAL DUCTxx{ OR xx/xx}
FLANGED
CIRCUIT SETTER TREADED &
FLOW INDICATOR BALANCER/
CONDENSER WATER SUPPY
CHILLED WATER SUPPLY
THERMOMETER IN WALL
2-WAY CONTROL VALVE
CO2 CO2 MONITER
THERMOSTAT w/GAURD
3-WAY CONTROL VALVE
& FLANGED
BALL VALVE THREADED
HEATING WATER SUPPLY
CHILLER SCHEDULE
RATING
EWT LWT
WATER
FLOW-GPM
EVAPORATOR DATA
MAXIMUM PRESSURE
DROP-FT-H O2
FOULING
FACTOR
MARK
MIN.
MBH INPUT Kw
MAX
VOLT/PHASE
ELECTRICAL DATA
REMARKS
MIN IPLV
AT AHRI
F F
CHR-2
CHR-1
MARK SERVICE
TYPE
PUMP
GPM DYNAMIC
FT.H O
MAX. MIN.
EFF.%
REMARKS
2 B&G(EA.) HP
PUMP SCHEDULE
RPM
NOTES:
CP-2
CP-1 VFD
VFD
ESP
ESP 83
175090
PUMP SIZED FOR 100% REDUNDANCY.1
NOTES:
1 SELECT CHILLER FOR 100 F AMBIENT TEMPERATURE.
2430 56 44 405 12 0.00010 280 460/3 18.5 1
2430 56 44 405 12 0.00010 280 460/3 18.5 1
CHILLED WATER
CHILLED WATER 810
5EB
5EB
MANUFACTURERS
PATTERSON
6x4x1 1
6x4x1 1
TACO
6x5x1 1
6x5x1 1
HEAD
SHUTOFF
MIN.
HVAC
& SCHEDULES -
LEGENDS,
ABBREVIATIONS,
SEAL
SCALE:
FILE PATH:
P:\26080\26080m01.dgn
DATE PLOTTED
DGN FILE
02-NOV-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26080\26080m01.dgn
AS SHOWN
26080
WSH
LTF
WSH
11.02.2026
V a ld o s ta
G e o rg ia
V A
L D
O S
T A S
T A
T E U
N
IV
E R
S
IT
Y
E D
U C
A T
IO
N C
E N
T E
R C
H
IL
L E
R R
E P
L A
C E
M E
N T
EXPIRES: 06.30.2028
COA#PEF000774
NBP ENGINEERS, INC.
P R
O J E
C T N o
M R
R -2
-1
B
ID
S
T
M0.2
SITE PLAN - HVAC
SITE PLAN - HVAC
SCALE: 1 = 20'-0
20 0 10 20 40
N
CHR-1
CHR-2
8" U.G. CHW PIPING
4 INCHES OF PEA GRAVEL
COVER WITH 6 MIL POLY AND
STERILIZE CHILLER YARD SOIL;
EXISTING
WALKWAY; REPLACE TO MATCH
REMOVE EXISTING CONCRETE
PIPE SUPPORT (TYPICAL)
CHRCHS
6" CHW PIPING
NEW CHAIN LINK FENCE
NEW CHAIN LINK FENCE
BASE (TYPICAL)
EXTERIOR CONCRETE
SEAL
SCALE:
FILE PATH:
P:\26080\26080m02.dgn
DATE PLOTTED
DGN FILE
02-NOV-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26080\26080m02.dgn
AS SHOWN
26080
WSH
LTF
WSH
11.02.2026
V a ld o s ta
G e o rg ia
V A
L D
O S
T A S
T A
T E U
N
IV
E R
S
U C
A T
IO
N C
E N
T E
R C
H
IL
L E
R R
E P
L A
C E
M E
N T
EXPIRES: 06.30.2028
COA#PEF000774
NBP ENGINEERS, INC.
P R
O J E
C T N o
M R
R -2
-1
T
C
C
EM
E
S
S
S
S
S
T
T
12" PINE
10" MAGNOLIA TWIN
12" PINE
12" PINE
10" PINE
30" OAK
12" PINE
12" PINE
20" TREE
12" PINE
12" PINE
12" PINE
12" PINE
28" OAK
28" OAK
18" PINE
15" PINE
15" PINE
12" PINE
12" PINE
15" PINE
22" OAK
24" OAK
18" PINE
24" OAK
12" PALM
12" PALM
12" PALM
12" PINE
15" MAGNOLIA
10" PALM
10" PALM
10" PALM
8" PINE
" R
C P
INV: 173.24'
TOP: 177.29'
CATCH BASIN
" R
C P
164.97'
INV:
166.84'
INV:
166.65'
INV:
166.65'
INV:
167.78'
INV:
INV: N/A
TOP: 178.80'
EXISTING MANHOLE
INV C: 172.60'
INV B: 167.00'
INV A: 166.55'
TOP: 175.30'
EXISTING MANHOLE
12" R C P
" P
VC
A
B
A
B
C
P V C
INV C: 167.18'
INV B: 166.68'
INV A: 166.63'
TOP: 175.48'
EXISTING MANHOLE
SIDEWALK
S
ID
E W
A L K
S
ID
E W
A L
K
S
ID
E W
A L
K
(TYP)
PLANTER
R A
M P
7' x 10' B
OX
CULVERT
NOBLES & ASSOCIATES DATED 8/24/2007)
ASPHALT PAVEMENT (R/W PER SURVEY FOR THE BOARD OF REGENTS PREPARED BY ALLEN
BAYTREE ROAD (70' R/W)
N O
R
H
O A
K
S
T R
E
P
H A
L T P
A V E
M E
N T
FFE = 177.24'
STUCCO BUILDING
TWO STORY
TABLE
PICNIC
R/W R
W
EASE
MENT
' U
TI
LI
TY
WM
W
W
10" PINE
8" PINE
8" PALM
8" PALM
8" PALM
E
SIGN
VSU
(TYP)
BIKE RACK
T
T SIGNAL
CROSSWALK
BOX
SIGNAL
TRAFFIC
ST
EAMLI
NE
ST
EAMLI
NE
INV: N/A
TOP: 177.85'
CATCH BASIN
C H
A
IN
L
IN
K F
E N
C E
6" STEEL
45' M.B.L.
' M .B .L
8" PALM
10" PALM
10" PALM
10" PALM
15" OAK
24" OAK
AC
GATE
E
E
INV: 171.29'
TOP: 172.84'
DROP INLET
B
" C
M P
INV B: 170.65'
INV A: 170.70'
TOP: 173.25'
DROP INLET
" C
M P
" R
C P
" R
C P
R C P
INV B: 170.25'
INV A: 170.30'
TOP: 172.75'
DROP INLET
INV B: 169.91'
INV A: 170.01'
TOP: 172.51'
DROP INLET
INV C: 169.58'
INV B: 169.88'
INV A: 169.83'
TOP: 172.43'
DROP INLET
INV: 170.38'
TOP: 172.88'
DROP INLET
A
B
A
B
A
BA
C
BOTTOM: 171.23'
TOP: 173.03'
DROP INLET
(FULL OF SILT)
INV: INACCESSIBLE
TOP: 175.45'
CATCH BASIN
STEAMLINE
15" OAK TWIN
E
7' x 10' B
OX
CULVERT
ADDITION
LECTURE HALL
12" WATER MAIN
INV: 171.16'
TOP: 174.31'
DROP INLET
W
WM
W M pivfdc
WM
ball
C
M2.1
SCALE:
= 1'-0
4 0 2 4 8
N
EXISTING AH-2 TO REMAIN
FEEDER; CAP PIPING
BYPASS CHEMICAL
REMOVE EXISTING
CAP PIPING
CHW EXPANSION TANK;
REMOVE EXISTING
CAP PIPING
MUW STATION;
REMOVE EXISTING
BASE TO REMAIN
EXISTING CONCRETE
COOLED CHILLER CHR-1;
REMOVE EXISTING AIR
SUPPORT
PIPE
EXISTING TO REMAIN
DEMOLITION
NEW WORK
POINT OF CONNECTION
LINE LEGEND
& CHILLER YARD - DEMOLITION & NEW WORK - HVAC
PARTIAL FIRST FLOOR PLAN
ROOF PLAN - DEMOLITION & NEW WORK - HVAC
SCALE:
= 1'-0
16 0 8 16 32
N
CHR
CHS
ROOM
MECHANICAL
SEE 2/M2.1 FOR CONTINUATION
ALONG EXTERIOR WALL;
CHR/S LINES UP TO ROOF
HVAC
PLAN- DEMOLITION -
FLOOR PLAN & ROOF
PARTIAL FIRST -
CHS
CHR
CHS
CHR
6" CHR/S DN
6"
6" CHR/S DN
REPLACE WITH 6" PIPE SECTION
AIR SEPARATOR;
REMOVE EXISTING
SEAL
SCALE:
FILE PATH:
P:\26080\26080m21.dgn
DATE PLOTTED
DGN FILE
02-NOV-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26080\26080m21.dgn
AS SHOWN
26080
WSH
LTF
WSH
11.02.2026
V a ld o s ta
G e o rg ia
V A
L D
O S
T A S
T A
T E U
N
IV
E R
S
U C
A T
IO
N C
E N
T E
R C
H
IL
L E
R R
E P
L A
C E
M E
N T
EXPIRES: 06.30.2028
COA#PEF000774
NBP ENGINEERS, INC.
P R
O J E
C T N o
M R
R -2
-1
T
HOOD
HOOD
L
E C
T R
IC
A L
UH
E-8
EXISTING MCC
SPRK. ENT.
VFD-CT
6"CHS
CHR
H W
S 4 "H
W R
CONCRETE PAD
LARGE SCALE - MECHANICAL ROOM - DEMOLITION - HVAC
SCALE:
= 1'-0
4 0 2 4 8
SCALE:
= 1'-0
4 0 2 4 8
LARGE SCALE - MECHANICAL ROOM - NEW WORK - HVAC
EXISTING TO REMAIN
DEMOLITION
NEW WORK
POINT OF CONNECTION
LINE LEGEND
N N
FM
CHILLER
EXISTING
X
L
D
L
EXISTING CONTROL PRV
EXISTING REFRIGERATED DRYER
M3.1
NEW WORK - HVAC
DEMOLITION &
MECHANICAL ROOM -
LARGE SCALE -
HP-ED-1
HP-ED-2
FM
FD
CR
CS
4"HWS
4"HWR
"H
W S
TO BUILDING
EXISTING BYPASS CHEMICAL FEEDER
EXISTING CONTROL AIR COMPRESSOR
CONTROL AIR TO BUILDING TO REMAIN
FLOOR DRAIN
EXISTING COMMUNICATIONS BACKBOARD
E L
E C
MCC
BLR
BOILER SERVICE CLEARANCE
CAP PIPE
EXISTING INSECT SCREEN
EXISTING LOUVER
AIR/DIRT SEPARATOREXISTING
CHEMICAL FEEDER
REMOVE EXISTING BYPASS
TO TOWER ABOVE
EXISTING CR UP
REMOVE
& CONCRETE PAD
EXISTING CHILLER
REMOVE
TP-E-1REMOVE EXISTING
TP-E-2REMOVE EXISTING
FROM TOWER ABOVE
EXISTING CS DOWN
REMOVE
REMOVE
EXISTING
TO REMAIN
EXISTING CONTROL PANEL
EXISTING
EXISTING
U P
REMOVE EXISTING AIR SEPARATOR
1CP-ED-REMOVE EXISTING PUMP
MONITOR
REMOVE EXISTING REFRIGERANT LEAK
REMOVE EXISTING EXPANSION TANK
CP-ED-2REMOVE EXISTING
CONDUCTIVITY CONTROLS
COOLING TOWER
REMOVE
CP-1
CP-2
CHW EXPANSION TANK
CHEMICAL FEEDER
CHW BYPASS
VFD
VFD
C H
R
C H S
C H
R
C H S
CHS
CHR
MECHANICAL SLEEVE SEALS
8" CHR/S TO NEW AIR COOLED CHILLERS
8" 8"
6"
MUW
8"
8"
6"
6"
6" CHR/S UP TO ROOF
SEAL
SCALE:
FILE PATH:
P:\26080\26080m31.dgn
DATE PLOTTED
DGN FILE
02-NOV-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26080\26080m31.dgn
AS SHOWN
26080
WSH
LTF
WSH
11.02.2026
V a ld o s ta
G e o rg ia
V A
L D
O S
T A S
T A
T E U
N
IV
E R
S
U C
A T
IO
N C
E N
T E
R C
H
IL
L E
R R
E P
L A
C E
M E
N T
EXPIRES: 06.30.2028
COA#PEF000774
NBP ENGINEERS, INC.
P R
O J E
C T N o
M R
R -2
-1
T
E L
E C
T R
IC
A L
UH
E-8
EXISTING MCC
SPRK. ENT.
H W
S 4 "H
W R
CONCRETE PAD
X
L
D
L
EXISTING CONTROL PRV
EXISTING REFRIGERATED DRYER
HP-ED-1
HP-ED-2
FM
FD
4"HWS
4"HWR
"H
W S
TO BUILDING
EXISTING BYPASS CHEMICAL FEEDER
EXISTING CONTROL AIR COMPRESSOR
CONTROL AIR TO BUILDING TO REMAIN
FLOOR DRAIN
EXISTING COMMUNICATIONS BACKBOARD
MCC
BLR
BOILER SERVICE CLEARANCE
EXISTING INSECT SCREEN
AIR/DIRT SEPARATOREXISTING
EXISTING
TO REMAIN
EXISTING CONTROL PANEL
EXISTING
EXISTING
U P
SCALE:
= 1'-0
4 0 2 4 8
EXISTING TO REMAIN
DEMOLITION
NEW WORK
POINT OF CONNECTION
LINE LEGEND
N
M3.2
NEW WORK - HVAC
DEMOLITION &
FLOOR - TOWER WELL
PARTIAL SECOND
LARGE SCALE -
PARTIAL SECOND FLOOR - TOWER WELL - DEMOLITION - HVAC
LARGE SCALE -
SCALE:
= 1'-0
4 0 2 4 8
N
PARTIAL SECOND FLOOR - TOWER WELL - NEW WORK - HVAC
LARGE SCALE -
EXISTING ROOF
ERD
ERD
SUPPORT RAILS TO REMAIN
EXISTING CONCRETE
OA INTAKE
OA INTAKE
6"CR
"C
S
O
20A/3P/4X
100A/3P/4X
W8x18
W8x18
IP
E
E
EXISTING ROOF
RAILS TO REMAIN
EXISTING STEEL SUPPORT
RAILS TO REMAIN
EXISTING STEEL SUPPORT
FREEZE PROTECTION
REMOVE EXISTING
2" PIPE STANCHION
REMOVE EXISTING
ELECTRIC HEATER CABLE
REMOVE EXISTING
INSULATED METAL CURB CAP
WATER PIPING; PROVIDE
REMOVE EXISTING CONDENSER
COOLING TOWERREMOVE EXISTING
INSULATED METAL CURB CAP
WATER PIPING; PROVIDE
REMOVE EXISTING CONDENSER
FULL SIZE OVERFLOW
REMOVE EXISTING
THRU PIPE CURB
6" CHR/S UP & DN
SEAL
SCALE:
FILE PATH:
P:\26080\26080m32.dgn
DATE PLOTTED
DGN FILE
02-NOV-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26080\26080m32.dgn
AS SHOWN
26080
WSH
LTF
WSH
11.02.2026
V a ld o s ta
G e o rg ia
V A
L D
O S
T A S
T A
T E U
N
IV
E R
S
U C
A T
IO
N C
E N
T E
R C
H
IL
L E
R R
E P
L A
C E
M E
N T
EXPIRES: 06.30.2028
COA#PEF000774
NBP ENGINEERS, INC.
P R
O J E
C T N o
M R
R -2
-1
T
EXISTING ROOF
ERD
ERD
SUPPORT RAILS TO REMAIN
EXISTING CONCRETE
OA INTAKE
OA INTAKE
W8x18
W8x18
E
E
EXISTING ROOF
RAILS TO REMAIN
EXISTING STEEL SUPPORT
RAILS TO REMAIN
EXISTING STEEL SUPPORT
M4.1
HVAC
FLOW DIAGRAM -
CHILLED WATER SYSTEM
SUMMARIES
INPUT/OUTPUT
DDC PANELS
ACP
OUTPUTS INPUTS SOFTWARE
DIGITAL ANALOG DIGITAL ANALOG ALARM DDC ENERGY MGMT. LOGS
F A
IL
U R
M
D E (S
N
T E S
A
N D
N O
T E S
T R
E
G
S Y
S T
G
A P
IC
IS
P L
A Y
S T
A R
T
S T
O P
E N
A B
L E
D
IS
A B
L E
O P
E N
C L
O S
E
S T
A R
T
S T
K E
U P
S E
T P
O
IN
J
U S
T
D
N T
R O
L
D
IF
F E
R E
N T
IA
L
P
R E S
S U
R E
P R
E S
S U
R E
S
W
IT
C H
A U
X
IL
IA
N T
A C
T
A L
A
N T
A C
T
T E
M P
E R
A T
U R
E
H
IG
H
L
W
IM
IT
R
T A
L
IZ
A T
IO
N
P R
O P
O R
T
IO
N A
L
P R
O P
IN
T E
G R
A L
T
IM
E
S
C H
E D
U L
E
S
S
O P
T
IM
A R
T
S T
O P
D A
Y
N
IG
T B
A C
K
D E
M A
IT
C Y
C L
E
R E S
T
IM
IZ
A T
IO
N
E C
O N
O M
IZ
E R
C U
R R
E
L A
Y
D
IF
F
P
R E S
S U
R E
S P
E
N T
R O
L
S T
E A
M
W A
T
F
O W
O P
E R
A T
IN
A T
U S
D R
IV
E
S
T A
T U
S
P O
S
IT
IO
N
IN
D
IC
A T
IO
N
S P
E E
D
IN
D
IC
A T
IO
N
G
F
O W
U S
A
F
B T
U
K W
H
S T
A T
U S
TAG
TT 1
TT 2
TT 3
TT 5
1. FAILURE MODES:
O - OPEN OR ON
C - CLOSE OR OFF
L - LAST COMMAND
2. WHERE FAILURE MODE IS INDICATED, THE INDICATED POSITION SHALL OCCUR ON INTERRUPTION OF
NOTES:
ELECTRIC POWER TO THE DDC PANEL.
3. PROVIDE FULL INTEGRATION THROUGH THE VFD BACNET INTERFACE CARD FOR INPUT OF ALL VFD
OPERATING PARAMETERS TO THE BAS.
TT 7
TT 6
TT 4
CHILLED WATER RETURN - CAMPUS LOOP
CHILLED WATER SUPPLY - CAMPUS LOOP
CHILLED WATER PUMP - CAMPUS LOOP
CHILLED WATER PUMP - CAMPUS LOOP
FRT-1
DP-1
CHILLER
CHILLER
CHILLER WATER FLOW RATE
DIFFERENTIAL PRESSURE
CHILLED WATER RETURN - CHR-1
CHILLED WATER SUPPLY - CHR-1
CHILLED WATER RETURN - CHR-2
CHILLED WATER SUPPLY - CHR-2
CHILLED WATER BYPASS
VLV-3
CHR ISOLATION VALVE (SLOW ACTING)
BYPASS VALVE C
C
SUCTION DIFFUSER
RELIEF VALVE
SET 80#
TO AND FROM
AIR HANDLING
EQUIPMENT
CHR
CHS
CHR
AAV
BLADDER TYPE EXPANSION
TANK. MINIMUM TANK VOLUME
ACCEPTANCE 130 GALLONS.
TT
AI
TT
AI
AI
FRT
CHEMICAL FEEDER
VSD
DIAIDO AO
CP
VSD
DIAIDO AO
CP
MUW
AI
TT
AI
TT
AI
TT
AI
TT
"C
H S
"C
H R
"C
H S
"C
H R
CHS
1"1"
TANGENTIAL AIR SEPARATOR
250 GALLONS, MINIMUM
1•" TO DOMESTIC WATER
45 PSI FILL PRESSURE
ROUTE TO DRAIN
1"
AIAO
VLV
VLV
AIAO
VLV
AIAO
CONCRETE
HOUSKEEPING PAD
CHILLED WATER FLOW DIAGRAM - HVAC
NOT TO SCALE
VLV-1, 2
TT
AI
8" 8"
8"
8"
8"
CHR-2 CHR-1
CP-1
CP-2
CHR-1
CHR-2
CP-1
CP-2
OUTSIDE INSIDE
TEMPORARY CHILLER
w/BLIND FLANGE FOR
6" BUTTERFLY VALVE
SEAL
SCALE:
FILE PATH:
P:\26080\26080m41.dgn
DATE PLOTTED
DGN FILE
02-NOV-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26080\26080m41.dgn
AS SHOWN
26080
WSH
LTF
WSH
11.02.2026
V a ld o s ta
G e o rg ia
V A
L D
O S
T A S
T A
T E U
N
IV
E R
S
U C
A T
IO
N C
E N
T E
R C
H
IL
L E
R R
E P
L A
C E
M E
N T
EXPIRES: 06.30.2028
COA#PEF000774
NBP ENGINEERS, INC.
P R
O J E
C T N o
M R
R -2
-1
M5.1
AIR COOLED CHILLER ISOMETRIC
DRAIN VALVE WITH HOSE
CONNECTION AT LOW POINT
M.A.V. AT
HIGH POINTS
(FOR ESTIMATING PURPOSES ONLY. PROVIDE PIPING ARRANGEMENT FOR UNIT FURNISHED.)
C H S
C H
R
CABLE ON PIPING
OUTDOORS ABOVE
GRADE
FLANGE ON GROUND
CONDUCTOR TO EVAPORATOR
ELECTRIC HEATING
GRADE
NOT TO SCALE
REDUCER
‚" COPPER TUBING
•" GATE VALVE
•" 4" NIPPLE
CIRCULATING WATER PIPING
NOTES:
1.
2.
VENT ALL HIGH POINTS AS INDICATED ABOVE.
IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.
ELEVATION TYPICAL AIR VENT
A
BC
E
TO SYSTEM
B -ƒ" TO DISCHARGE OF PUMP.
C -ƒ" TO SUCTION OF PUMP.
F - RISER CLAMP. WELD TO 2X3/4 " FLAT
OFFSET BRACKET TO WALL.
A - CHEMICAL FEEDER TANK.
D -ƒ" TO FLOOR DRAIN.
D
4"MIN.
WELD
F
BALL VALVES
E -‚" BALL VALVE FOR VENT.
BY-PASS CHEMICAL FEEDER
WALL
AS SYSTEM PIPE.
MANUAL AIR VENT
TERMINATE DRAIN WITH HOSE END
CONNECTION 18" ABOVE FLOOR.
WHERE AIR VENTS OCCUR ABOVE ACCESSIBLE
CEILING. LOCATE VALVE AND TERMINATE DRAIN
HERE, UNLESS NOTED OTHERWISE AND POSITION
VALVE FOR VERTICAL DOWN DISCHARGE.
•" PIPE SAME MATERIAL
2•"
VERTICAL
PIPE
SUPPORT
WELDED PIPETHREADED / BRAISED
PIPING
BALL VALVE (EXPOSED) OR
GATE VALVE (CONCEALED)
ARRANGEMENT FOR LOCATIONS
WITH LIMITED CLEARANCE
6"MAX.
SERVICE TEE
ECCENTRIC REDUCER
•" STREET ELL.
AUTOMATIC AIR VENT
MAINS
•"x2" NIPPLE
„"MPT x ‚" FLARE ELL.
‚" COPPER TO FLOOR
AUTOMATIC AIR VENT
NOT TO SCALE
3 4
NOT TO SCALE
NOT TO SCALE
DRAIN OR OUTSIDE AS SHOWN.
NOT TO SCALE
INSULATED PIPE
STEEL
4" C4 STEEL CHANNEL
ROUND CONCRETE PIER
3" STEEL PIPE
2'
6"
12"
18"
END VIEW
4" C4 STEEL CHANNEL
ROUND CONCRETE PIER
NOT TO SCALE
OUTDOOR HVAC PIPE SUPPORT DETAIL
BACKFLOW PREVENTER
1"1"
MAKE - UP WATER STATION
GAUGE COCK
ƒ"
PRESSURE REDUCING
VALVE. SET AT
1"
AIR GAP DRAIN
FITTING
1" ROUTE TO WALL, DOWN TO FLOOR, AND ALONG FLOOR
TO FLOOR DRAIN. SECURE TO FLOOR WITH STRAP TYPE
CLAMPS SAME MATERIAL AS PIPE.
PSI.
GAUGE
GATE VALVE
GATE VALVE
TO FILL POINT
OF SYSTEM
BALL VALVE
QUICK FILL
CONNECTION
TO DOMESTIC COLD
WATER SUPPLY
TYPICAL DRAIN VALVE CONNECTION
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
ƒ" GATE VALVE
ADAPTER TO ƒ" HOSE THREAD
PROVIDE HOSE CAP NUT
NOTES:
DRAIN ALL LOW POINTS AS INDICATED ABOVE.1.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS
AND/OR PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
HANGER ROD - SEE SPECIFICATIONS
SECTION OF RIGID INSULATION
SPECIFIED INSULATION
PIPE
• ROUND BEARING PLATE
PLATE WASHER
CUT ROD ABOVE ANGLE LEG
1" MIN.
TRAPEZE HANGER
LONG LEG VERTICAL
SEE SPECIFICATIONS
DOUBLE HEX NUTS
TRAPEZE PIPE HANGER
NOT TO SCALE
WELDED PIPING
ELEVATION
THREADED PIPING
ELEVATION
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
SECTION THROUGH TRENCH
18" MIN.
FINISHED GRADE
6"
COMPACTED SAND
18"
MIN.
CL CL
COMPACTED
BACKFILL
18" MINIMUM
ELASTOMERIC SEAL ELEMENT
BOLT
PRESSURE PLATE
WALL
PIPE WITH INSULATION
CL
1 1
MECHANICAL SLEEVE SEAL
NOT TO SCALE
DRILLED HOLE
CAST/CORE
HVAC
DETAILS -
SEAL
SCALE:
FILE PATH:
P:\26080\26080m51.dgn
DATE PLOTTED
DGN FILE
02-NOV-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26080\26080m51.dgn
AS SHOWN
26080
WSH
LTF
WSH
11.02.2026
V a ld o s ta
G e o rg ia
V A
L D
O S
T A S
T A
T E U
N
IV
E R
S
U C
A T
IO
N C
E N
T E
R C
H
IL
L E
R R
E P
L A
C E
M E
N T
EXPIRES: 06.30.2028
COA#PEF000774
NBP ENGINEERS, INC.
P R
O J E
C T N o
M R
R -2
-1
M5.2
HVAC
DETAILS -
CONCRETE BASE
4"
4" 4"
LIQUID TIGHT,NEOPRENE COATED
FLEXIBLE CONDUIT
BEVEL
WATER PUMP(S) ONLY
18 GA. S.S. DRIP PAN
(CHILLED WATER PUMP(S)
ONLY)
GAUGE COCK
RIGID CONDUIT STUB
TO 3" ABOVE BASE
AS SPECIFIED
•" SCH. 40 TO DRAIN (CHILLED
PLAN
END SUCTION PUMP
NOT TO SCALE
NOT TO SCALE
ELEVATION
TYPICAL END SUCTION PUMP-
FLEXIBLE CONNECTION
FLEXIBLE COUPLING AND
COUPLING GUARD
PRESSURE GAUGE
TEST PLUG
‚" BALL VALVE, TYPICAL
ADJUSTABLE FOOT FULL SIZE BLOWDOWN
‚" DRAIN
1"
SUCTION DIFFUSER
WITH STRAINER
2"
EXISTING CONCRETE BASE
18 GA. S.S. DRIP
PAN (CHILLED WATER
PUMP(S) ONLY)
1/2" DRAIN TAPPING
PIPE TO FLOOR DRAIN
TO FLOOR DRAIN
PIPE INSULATION
BALL OR BUTTERFLY
CIRCUIT SETTER
SEAL
SCALE:
FILE PATH:
P:\26080\26080m52.dgn
DATE PLOTTED
DGN FILE
02-NOV-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26080\26080m52.dgn
AS SHOWN
26080
WSH
LTF
WSH
11.02.2026
V a ld o s ta
G e o rg ia
V A
L D
O S
T A S
T A
T E U
N
IV
E R
S
U C
A T
IO
N C
E N
T E
R C
H
IL
L E
R R
E P
L A
C E
M E
N T
EXPIRES: 06.30.2028
COA#PEF000774
NBP ENGINEERS, INC.
P R
O J E
C T N o
M R
R -2
-1
E0.1
ELECTRICAL
RISER & DETAILS -
LEGEND, SCHEDULES,
RECEPTACLES
CIRCUITS
DUPLEX - NORMAL
GFI DUPLEX - NORMAL
QUADRAPLEX - NORMAL
GFI QUADRAPLEX - NORMAL
ELECTRICAL LEGEND
WP WEATHER PROOF OUTLET
RACEWAY EXPOSED
FLEXIBLE RACEWAY
CONDUIT UP
CONDUIT DOWN
HOMERUN- ONE ARROW PER CIRCUIT
ONE CROSSMARK PER WIRE
(3 WIRE UNLESS SHOWN)
RACEWAY CONCEALED IN CEILING OR WALL
RACEWAY IN GROUND, SLAB, OR UNDER FLOOR
CAP
CONNECTION TO EQUIPMENT
GENERAL EQUIPMENT
BACKBOARD
CT
TRANSFORMER
F
PANELBOARD-250 VAC OR LESS
SURFACE MOUNTED
PANELBOARD-250 VAC OR LESS
RECESSED
PANELBOARD-OVER 250 VAC
RECESSED
PANELBOARD-OVER 250 VAC
SURFACE MOUNTED
T
M MANUAL STARTER AND MOTOR RATED SWITCH
EMERGENCY PUSHBUTTON
EXHAUST FAN
MOTOR
JJ J
G
ENCLOSED CIRCUIT BREAKER
ENCLOSED BREAKER-RECESSED IN WALL
JUNCTION BOX - WALL/CEILING/FLOOR
DISCONNECT SWITCH: "F" IF FUSED
FRAME AMPS/POLES/NEMA TYPE
FUSE PER MANUFACTURERS RECOMMENDATIONS
SURGE SUPPRESSOR
COMBINATION STARTER AND DISCONNECT
CABLE TRAY
GROUNDING PLATE
GROUND CONNECTION (SCHEMATIC)
NOT TO SCALE
T
GROUND TRIAD
#3/0
750KVA
MOUNT
PAD
1200A
MSB-CHR
LCHR CHR-1
WP
CHR-2
WP
POWER RISER
NOTES:(THIS SHEET ONLY)
PRIMARY SERVICE. SEE DETAIL 2 THIS SHEET.
BASIS OF DESIGN: EATON #P48G11S1526.
60A MAIN SECONDARY BREAKER. SEE SCHEDULE THIS SHEET.
SINGLE POLE BREAKERS MIN. 30A MAIN PRIMARY BREAKER,
15KVA, 3-PHASE, 480V TO 208/120V, 30A LOAD CENTER, 6 20A,
LOW VOLTAGE DRY TRANSFORMER TYPE MINI-POWER SYSTEM.
SEE MECHANICAL WIRING SCHEDULE FOR FEEDER.
ƒ"C, 4#10.
CIRCUIT NUMBER.
LCHR SCHEDULE AND MECHANICAL WIRING SCHEDULE FOR
WITH MECHANICAL FOR JUNCTION BOX LOCATION. SEE PANEL
PROVIDE POWER TO CHILLER PIPING HEAT TRACE. COORDINATE
FOR CIRCUIT NUMBER.
PANEL LCHR SCHEDULE AND MECHANICAL WIRING SCHEDULE
PROVIDE A CONVENIENCE RECEPTACLE AT EACH CHILLER. SEE
4 SETS: 2•" C WITH 4#350KCMIL.
277/480V
1000 KVA
T-8
C2C1C2C1
277/480V
1000 KVA
T-8A
C2C1120/208V
300 KVA
T-9
BLDG.
P.E.
9B
9A
1 PH
25 KVA
T-10
LOT
PARKING
C2C1
C2C1
277/480V
300 KVA
T-7
COURT
TENNIS
C2 C2
EDUCATION BLDG.
277/480V
750 KVA
ST-6
C2C2
V-6
4-WAY
E.L.L.AE.L.L.A
C2C1
C1
PARKING LOT
1 PH
25 KVA
T-11
1#4/0 AL
1#4/0 AL
PARKING LOT
C1
C1
2-WAY
480/277V
750 KVA
ST-26
C2C1
NOT TO SCALE
PRIMARY ONE LINE DIAGRAM
C2
EDUCATION BLDG.
C2
277/480V
750 KVA
ST-6A
THROUGH NEW ST-6A.
IN MANHOLE 9. REROUTE
INTERRUPT THE C2 CIRCUIT
SEAL
SCALE:
FILE PATH:
P:\26080\26080e01.dgn
DATE PLOTTED
DGN FILE
02-NOV-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26080\26080e01.dgn
AS SHOWN
SHD
BCO
SHD
26080
11.02.2026
V a ld o s ta
G e o rg ia
V A
L D
O S
T A S
T A
T E U
N
IV
E R
S
U C
A T
IO
N C
E N
T E
R C
H
IL
L E
R R
E P
L A
C E
M E
N T
EXPIRES: 06.30.2028
COA#PEF000774
NBP ENGINEERS, INC.
P R
O J E
C T N o
M R
R -2
-1
T
P O
L E
P O
L E
P O
L E
P O
L E
CKT
MSB-CHR
NOTES
Minimum KAIC:
CKT
TRIP
4#10
WIRE
3/4"
CD.
MULTISECTION CONN AMPS
MULTISECTION CONN V A
PANEL SECTION CONN AMPS
PANEL SECTION CONN V A
PREPARED SPACE
PREPARED SPACE
POWER UNIT
PANEL LCHR
PROTECTIVE DEVICE
SURGE
INTEGRAL
SERVES
WIRE
PH,
AMPS
VOLT-
250500
250500
125850
124650
A
PHASE LOAD V.A.
250500
250500
125850
124650
B
FED BY
249700
249700
125050
124650
C
NEW PAD MOUNT TRANS.
LOCATION:
124650
124650
124650
124650
124650
124650
AMPS
VOLT-
CHILLER YARD
FOR CHILLERS
WIRING SCHEDULE
SEE MECHANICAL
CHR-2
CHILLER NO.
CHR-1
CHILLER NO.
SERVES
MAIN BREAKER
CD. WIRE
PAD
OR
OR
TRIP
MOUNTED
AMPS
P O
L E
P O
L E
P O
L E
P O
L E
NOTES
Minimum KAIC:
CKT
TRIP
#10
#10
#10
WIRE
3/4"
3/4"
3/4"
CD.
MULTISECTION CONN AMPS
MULTISECTION CONN V A
PANEL SECTION CONN AMPS
PANEL SECTION CONN V A
CONV. RECEPTACLES
CHR-2 HEAT TRACE
CHR-1 HEAT TRACE
SERVES
WIRE
PH,
AMPS
VOLT-
A
PHASE LOAD V.A.
B
FED BY
C
MSB-CHR VIA INTEGRAL XFORMER
LOCATION:
AMPS
VOLT-
CHILLER PLANT MER
SPARE
SPARE
SPARE
SERVES
MAIN BREAKER
CD. WIRE
SURFACE
TRIP
MOUNTED
AMPS
CKT
LCHR
E0.2
SCALE: 1 = 20'-0
20 0 10 20 40
N
CHR-1
CHR-2
NEW CHAIN LINK FENCE
NEW CHAIN LINK FENCE
ELECTRICAL
SITE PLAN -
T LCHR
MSB-CHR
EXISTING PANEL MDP IN MECH/ELEC ROOM.
CONDUIT AND CONDUCTORS TO
REMOVE EXISTING FEEDER
REMOVE EXISTING DISCONNECT.
SITE PLAN - ELECTRICAL
WITH PIPING/HVAC FOR LOCATION OF HEAT TRACE J-BOX.
BE A DEDICATED CIRCUIT USINGƒ"C, 3#8. COORDINATE
CIRCUIT PER PIPE, TWO CIRCUITS TOTAL. EACH SHALL
MECHANICAL/ELECTRICAL ROOM. ALLOW FOR ONE
BREAKERS IN EXISTNG PANEL LM IN GROUND FLOOR
PROVIDE POWER TO HEAT TRACE FROM SPARE 20A/1P
NEW CHILL WATER PIPING LOCATED ON THE ROOF.
SEAL
SCALE:
FILE PATH:
P:\26080\26080e02.dgn
DATE PLOTTED
DGN FILE
02-NOV-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26080\26080e02.dgn
AS SHOWN
SHD
BCO
SHD
26080
11.02.2026
V a ld o s ta
G e o rg ia
V A
L D
O S
T A S
T A
T E U
N
IV
E R
S
U C
A T
IO
N C
E N
T E
R C
H
IL
L E
R R
E P
L A
C E
M E
N T
EXPIRES: 06.30.2028
COA#PEF000774
NBP ENGINEERS, INC.
P R
O J E
C T N o
M R
R -2
-1
T
C
C
E
EM
E
S
S
S
S
S
T
T
" R
C P
INV: 173.24'
TOP: 177.29'
CATCH BASIN
" R
C P
INV B: 165.80'
INV A: 165.55'
TOP: 172.30'
DROP INLETA
B
" R
C P
" R
C P
INV: 166.11'
TOP: 174.06'
DROP INLET
164.97'
INV:
166.84'
INV:
166.65'
INV:
166.65'
INV:
167.78'
INV:
INV: N/A
TOP: 178.80'
EXISTING MANHOLE
INV C: 172.60'
INV B: 167.00'
INV A: 166.55'
TOP: 175.30'
EXISTING MANHOLE
12" R C P
" P
VC
A
B
A
B
C
P V C
INV C: 167.18'
INV B: 166.68'
INV A: 166.63'
TOP: 175.48'
EXISTING MANHOLE
" P
VC
SIDEWALK
S
ID
E W
A L K
S
ID
E W
A L
K
S
ID
E W
A L
K
(TYP)
PLANTER
R A
M P
7' x 10' B
OX
CULVERT
NOBLES & ASSOCIATES DATED 8/24/2007)
ASPHALT PAVEMENT (R/W PER SURVEY FOR THE BOARD OF REGENTS PREPARED BY ALLEN
BAYTREE ROAD (70' R/W)
N O
R
K
S
T R
E
P
H A
L T P
A V E
M E
N T
FFE = 177.24'
STUCCO BUILDING
TWO STORY
TABLE
PICNIC
TABLE
PICNIC
R/W R
W
EASE
MENT
' U
TI
LI
TY
WM
W
W
E
SIGN
VSU
(TYP)
BIKE RACK
T
T SIGNAL
CROSSWALK
BOX
SIGNAL
TRAFFIC
ST
EAMLI
NE
ST
EAMLI
NE
INV: N/A
TOP: 177.85'
CATCH BASIN
C H
A
IN
L
IN
K F
E N
C E
ONE
M
IL
E
BRANCH
6" STEEL
45' M.B.L.
' M .B .L
AC
GATE
SHED
METAL
E
E
INV: 171.29'
TOP: 172.84'
DROP INLET
B
" C
M P
INV B: 170.65'
INV A: 170.70'
TOP: 173.25'
DROP INLET
" C
M P
" R
C P
" R
C P
R C P
" R
C P
INV B: 170.25'
INV A: 170.30'
TOP: 172.75'
DROP INLET
INV B: 169.91'
INV A: 170.01'
TOP: 172.51'
DROP INLET
INV C: 169.58'
INV B: 169.88'
INV A: 169.83'
TOP: 172.43'
DROP INLET
INV: 170.38'
TOP: 172.88'
DROP INLET
A
B
A
B
A
BA
C
BOTTOM: 171.23'
TOP: 173.03'
DROP INLET
(FULL OF SILT)
INV: INACCESSIBLE
TOP: 175.45'
CATCH BASIN
STEAMLINE
TV
E
7' x 10' B
OX
CULVERT
ADDITION
LECTURE HALL
12" WATER MAIN
INV: 171.16'
TOP: 174.31'
DROP INLET
W
WM
W M pivfdc
WM
ball
UH
E-8
SPRK. ENT.
VFD-CT
CONCRETE PAD
LARGE SCALE - MECHANICAL ROOM - DEMOLITION - ELEC
SCALE:
= 1'-0
4 0 2 4 8
SCALE:
= 1'-0
4 0 2 4 8
LARGE SCALE - MECHANICAL ROOM - NEW WORK - ELEC
EXISTING TO REMAIN
DEMOLITION
NEW WORK
POINT OF CONNECTION
LINE LEGEND
N N
X
L
D
L
EXISTING CONTROL PRV
EXISTING REFRIGERATED DRYER
E3.1
NEW WORK - ELEC
DEMOLITION &
MECHANICAL ROOM -
LARGE SCALE -
HP-ED-1
HP-ED-2
FD
EXISTING BYPASS CHEMICAL FEEDER
EXISTING CONTROL AIR COMPRESSOR
CONTROL AIR TO BUILDING TO REMAIN
FLOOR DRAIN
EXISTING COMMUNICATIONS BACKBOARD
E L
E C
MCC
BLR
BOILER SERVICE CLEARANCE
EXISTING INSECT SCREEN
EXISTING LOUVER
EXISTING
& CONCRETE PAD
EXISTING CHILLER
REMOVE
TP-E-1REMOVE EXISTING
TP-E-2REMOVE EXISTING
REMOVE
EXISTING
TO REMAIN
EXISTING CONTROL PANEL
EXISTING
EXISTING
U P
1CP-ED-REMOVE EXISTING PUMP
CP-ED-2REMOVE EXISTING
CONDUCTIVITY CONTROLS
COOLING TOWER
REMOVE
SERVING MAIN ED CENTER.
EXISTING ELECTRICAL GEAR
SEE MCC ELEVATION DETAIL 3 THIS SHEET.
WITH MECHANICAL.
REMOVE CONTROLS CONDUIT AND CONDUCTORS IN COORDINATION
REMOVE FEEDER CONDUIT AND CONDUCTORS FROM MCC1.
AND 1#8G.
PROVIDE NEW FEEDER TO PUMP FROM MCC1, 1‚"C WITH 3#4
ON BUILDING EXTERIOR TO CHILLER.
REMOVE FEEDER CONDUIT AND CONDUCTORS FROM SWITCHGEAR
NOTES:(DETAIL 1 AND 2 ONLY)
MCC ELEVATION - NEW WORK - ELEC
NOT TO SCALE
BREAKER
MAIN
CAC
CPP
DRIVE
FAN
TOWER
CP-1/2
TP-1/2
HP-1
HP-2
IP RP
CP-1
NEW
CP-2
NEW
SPACE
MCC1
EXISTING MCC IS EATON FREEDOM SERIES 2100
NOTES:(DETAIL 3 ONLY)
SEPARATELY MOUNTED VFD.
PUMP CP-1 (CP-2). PUMP SHALL BE CONTROLLED BY
PROVIDE NEW 60A/3P BREAKER-ONLY BUCKET FOR NEW
LEAVE DISCONNECT AND HOA IN OFF POSITION.
POWER AND CONTROL CONDUCTORS. REMOVE LABEL.
ABANDON EXISTING STARTER IN PLACE. REMOVE ALL
SEAL
SCALE:
FILE PATH:
P:\26080\26080e31.dgn
DATE PLOTTED
DGN FILE
02-NOV-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26080\26080e31.dgn
AS SHOWN
SHD
BCO
SHD
26080
11.02.2026
V a ld o s ta
G e o rg ia
V A
L D
O S
T A S
T A
T E U
N
IV
E R
S
U C
A T
IO
N C
E N
T E
R C
H
IL
L E
R R
E P
L A
C E
M E
N T
EXPIRES: 06.30.2028
COA#PEF000774
NBP ENGINEERS, INC.
P R
O J E
C T N o
M R
R -2
-1
T
UH
E-8
SPRK. ENT.
CONCRETE PAD
X
L
D
L
EXISTING CONTROL PRV
EXISTING REFRIGERATED DRYER
HP-ED-1
HP-ED-2
FD
EXISTING BYPASS CHEMICAL FEEDER
EXISTING CONTROL AIR COMPRESSOR
CONTROL AIR TO BUILDING TO REMAIN
FLOOR DRAIN
EXISTING COMMUNICATIONS BACKBOARD
MCC
BLR
BOILER SERVICE CLEARANCE
EXISTING INSECT SCREEN
EXISTING
EXISTING
TO REMAIN
EXISTING CONTROL PANEL
EXISTING
EXISTING
U P
SERVING MAIN ED CENTER.
EXISTING ELECTRICAL GEAR
CP-1
CP-2
VFD
VFD
SCALE:
= 1'-0
4 0 2 4 8
EXISTING TO REMAIN
DEMOLITION
NEW WORK
POINT OF CONNECTION
LINE LEGEND
N
E3.2
NEW WORK - ELEC
DEMOLITION &
FLOOR - TOWER WELL
PARTIAL SECOND
LARGE SCALE -
PARTIAL SECOND FLOOR - TOWER WELL - DEMOLITION - ELEC
LARGE SCALE -
SCALE:
= 1'-0
4 0 2 4 8
N
PARTIAL SECOND FLOOR - TOWER WELL - NEW WORK - ELEC
LARGE SCALE -
EXISTING ROOF
ERD
ERD
SUPPORT RAILS TO REMAIN
EXISTING CONCRETE
OA INTAKE
OA INTAKE
6"CR
"C
S
20A/3P/4X
100A/3P/4X
W8x18
W8x18
E
E
EXISTING ROOF
RAILS TO REMAIN
EXISTING STEEL SUPPORT
RAILS TO REMAIN
EXISTING STEEL SUPPORT
NO NEW WORK
FREEZE PROTECTION
REMOVE EXISTING
ELECTRIC HEATER CABLE
REMOVE EXISTING
COOLING TOWERREMOVE EXISTING
ELECTRIC HEATER CABLE
REMOVE EXISTING
NOTES:(THIS SHEET ONLY)
REMOVE CONDUIT AND CONDUCTORS COMPLETELY BACK TO SOURCE.1
1 SEAL
SCALE:
FILE PATH:
P:\26080\26080e32.dgn
DATE PLOTTED
DGN FILE
02-NOV-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26080\26080e32.dgn
AS SHOWN
SHD
BCO
SHD
26080
11.02.2026
V a ld o s ta
G e o rg ia
V A
L D
O S
T A S
T A
T E U
N
IV
E R
S
U C
A T
IO
N C
E N
T E
R C
H
IL
L E
R R
E P
L A
C E
M E
N T
EXPIRES: 06.30.2028
COA#PEF000774
NBP ENGINEERS, INC.
P R
O J E
C T N o
M R
R -2
-1
T
EXISTING ROOF
ERD
ERD
SUPPORT RAILS TO REMAIN
EXISTING CONCRETE
OA INTAKE
OA INTAKE
W8x18
W8x18
E
E
EXISTING ROOF
RAILS TO REMAIN
EXISTING STEEL SUPPORT
RAILS TO REMAIN
EXISTING STEEL SUPPORT
| 26080aCov |
| 26080m01 |
| 26080m02 |
| 26080m21 |
| 26080m31 |
| 26080m32 |
| 26080m41 |
| 26080m51 |
| 26080m52 |
| 26080e01 |
| 26080e02 |
| 26080e31 |
| 26080e32 |
File details come from the government source that posted it. Updated .