2026_09_29_FVSU_Bond_Hunt_BidSet_NBP.pdf

PDF 2 MB Posted

Attached to
FVSU- Bond and Hunt
Solicitation number
PE-53300-RFP-2027-000000073
Issued by
Paulding County, Georgia

About this file

This is a bid set of engineering drawings prepared by NBP Engineers, Inc. for Fort Valley State University (FVSU) in Fort Valley, Georgia, detailing Air Handling Unit (AHU) upgrades for the Bond and Hunt buildings. The project, identified as Project Number 26011, involves comprehensive HVAC and electrical modifications to both buildings' mechanical systems. The scope of work includes demolition of existing equipment and installation of new air handling units, with specific work divided between the Bond Building penthouse and Hunt Library basement mechanical spaces. The Bond Building upgrade features a new VAV (Variable Air Volume) system with AH-B-1 air handler rated at 38,000 CFM maximum, incorporating a six-fan array with 7.5 HP motors each and wall-mounted variable frequency drives (VFDs). The Hunt Library scope includes new supply and return fan arrays with eight fans each (10 HP and 3 HP respectively), operating at 65,000 CFM and 55,000 CFM. The bid set includes detailed floor plans, sections, equipment schedules, piping diagrams, control system schematics, and electrical single-line diagrams for both demolition and new work phases. The drawings are dated September 29, 2026, indicating the bid set release date.

The project documentation includes comprehensive specifications for equipment removal, new equipment installation, piping connections, ductwork modifications, and control system integration using Direct Digital Control (DDC) technology. Electrical work encompasses new VFD installations, motor circuit protector panels, dedicated lighting circuits with LED fixtures including emergency egress capability, fire alarm system integration with duct-mounted smoke detectors, and control panel connections. The design incorporates chilled water cooling coils, heating water circuits, outdoor air dampers with automatic volume control, and relief air systems. Equipment to be removed includes existing inertia bases, cooling coils, roll filters, relief dampers, and associated piping and insulation. The new systems feature automatic air vents, balance valves, flow measurement stations, and isolation dampers throughout. Professional engineering services are provided by NBP Engineers, Inc., located in Macon, Georgia, with a Certificate of Authorization expiration date of June 30, 2028. The bid set establishes the technical baseline for contractor proposals and represents a significant mechanical and electrical infrastructure upgrade for both campus facilities.

View the file

Other files

File Type Posted
2026_09_29_FVSU Bond_Hunt AHU Upgrades_Projec.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT CONSULTANTS

INDEX OF

DRAWINGS

TITLESHEET NO.

316 CORPORATE PARKWAY MACON, GEORGIA

NBP ENGINEERS, INC.

CONSULTANTS

Fort Valley, Georgia

M00 ABBREVIATIONS, LEGENDS, & SCHEDULES - HVAC

MH10

MH20

E00

EH10

EH20

HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - DEMOLITION - HVAC

HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - NEW WORK- HVAC

HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - DEMOLITION - ELEC

HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - NEW WORK - ELEC

LEGEND - ELECTRICAL

EB20 BOND BUILDING - LARGE SCALE - PENTHOUSE PLANS - DEMOLITION & NEW WORK - ELEC

M40 FLOW DIAGRAM - VAV SYSTEM

M50 DETAILS - HVAC

MB10

MB20

BOND BUILDING - LARGE SCALE - PENTHOUSE PLAN - DEMOLITION - HVAC

BOND BUILDING - LARGE SCALE - PENTHOUSE PLAN - NEW WORK - HVAC

09.29.2026 BID SET

FVSU - Bond & Hunt AHU Upgrades

SEAL

SCALE:

FILE PATH:

P:\26011\26011m00.dgn

DATE PLOTTED

DGN FILE

30-SEP-2026

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26011\26011m00.dgn

AS SHOWN

26011

WSH

LTF

WSH

09.29.2026

B

ID

S E

T

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

F o rt V a ll e y

G e o rg ia

F V S

U B o n d H u n t

A H

U U p g ra d e s

M00

HVAC

SCHEDULES -

LEGENDS, &

ABBREVIATIONS,

A COMPRESSED AIR

AAV AUTOMATIC AIR VENT

AF AIR FOIL

-AFF ABOVE FINISHED FLOOR

AV ACID VENT

AVD AUTOMATIC VOLUME DAMPER

AW ACID WASTE

-AC ABOVE CEILING

AH- AIR HANDLING UNIT

BBD BOILER BLOW DOWN

BE BOTTOM ELEVATION

BOL BOTTOM OF LINE (UNINSULATED)

BOD BOTTOM OF DUCT

BP- BOOSTER PUMP

BTUH BRITISH THERMAL UNIT PER HOUR

-BF BELOW FLOOR

BFP BACK FLOW PREVENTOR

C CONDUIT

CC COOLING COIL

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CR CONDENSER WATER RETURN

CS CONDENSER WATER SUPPLY

CW DOMESTIC COLD WATER

CAB CABINET FAN

CF CENTRIFICAL FAN

CFM CUBIC FEET PER MINUTE

CFP CHEMICAL FEED PUMP

CFT CHEMICAL FEED TANK

CH CABINET HEATER

CHR CHILLER

CL CENTER LINE

CO CLEANOUT

CP CHILLER PUMP

CPHB CHROME PLATED HOSE BIBB

CT COOLING TOWER

CU COPPER

CV- CONVECTOR

Cv VALVE COEFFICIENT

D DRAIN

DDC DIRECT DIGITAL CONTROL

DHW DOMESTIC HOT WATER

DN DOWN

DP DIFFERENTIAL PRESSURE

DS DOWN SPOUT

DSO DOWN SPOUT OVER FLOW

DX DIRECT EXCHANGE

EAD EXHAUST AIR DAMPER

EAT ENTERING AIR TEMPERATURE

EDB ENTERING DRY BULB

EWB ENTERING WET BULB

ESP END SUCTION PUMP

ESP EXTERNAL STATIC PRESSURE

ELL ELBOW

ET EXPANSION TANK

EQT EQUIPMENT TRAP SET

EWT ENTERING WATER TEMPERATURE

EX EXPANSION TANK LINE

EXT EXTERNAL

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

F&BP FACE & BYPASS

FC FAN COIL UNIT

BPD BYPASS DAMPER

EAL EXHAUST AIR LOUVER

ECH ELECTRIC CABINET HEATER

ABBREVIATIONS

FD FLOOR DRAIN

FF FOULING FACTOR

FF- FLY FAN

FF FINISHED FLOOR

FF FINAL FILTER

FFM FIRE FLOW METER

FLEX FLEXIBLE

FM FIRE MAIN

FMS FLOW METER STATION

FOF FUEL OIL FLOW

FOR FUEL OIL RETURN

FOV FUEL OIL VENT

FOP FUEL OIL PUMP

FP FIRE PUMP

FP- FAN POWERED

FPM FEET PER MINUTE

FPS FEET PER SECOND

FRT FLOW RATE TRANSMITTER

FT FEET

G LOW PRESSURE GAS

GA GAUGE

GPM GALLONS PER MINUTE

GT GREASE TRAP

GTH GRAND TOTAL HEAT

H HEIGHT

HC HEATING COIL

HB HOSE BIBB

HBT HORIZONTAL BLOW THROUGH

HD HUB DRAIN

HDT HORIZONTAL DRAW THROUGH

HP HORSEPOWER/HIGH PRESSURE

HPA HIGH PRESSURE AIR

HPG HIGH PRESSURE GAS

HPS HIGH PRESSURE STEAM

HPWS HEAT PUMP WATER SUPPLY

HPWR HEAT PUMP WATER RETURN

HSC HORIZONTAL SPLIT CASE

HWG HOT WATER GENERATOR

HWR HEATING WATER RETURN

HWS HEATING WATER SUPPLY

ILC IN-LINE CENTRIFICAL

IT INTERVAL TIMER

IN INCHES

INV INVERT

JB JUNCTION BOX

L LENGTH

LR LONG RADIUS

LAT LEAVING AIR TEMPERATURE

LCP LOCAL CONTROL PANEL

LDB LEAVING DRY BULB

LN LIQUID NITROGEN

LWB LEAVING WET BULB

LWT LEAVING WATER TEMPERATURE

LPS LOW PRESSURE STEAM

MAV MANUAL AIR VENT

MVD MANUAL VOLUME DAMPER

MAX MAXIMUM

MBH ONE THOUSAND BTUH PER HOUR

MCC MOTOR CONTROL CENTER

MIN MINIMUM

MH MAN HOLE

MP SUMP (MUD) PUMP

MPS MEDIUM PRESSURE STEAM

MPR MEDIUM PRESSURE RETURN

MTS MEDIUM TEMPERATURE SUPPLY

MTR MEDIUM TEMPERATURE RETURN

MUA MAKE-UP AIR

MUW MAKE-UP WATER

MZ MULTIZONE

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OA OUTSIDE AIR

OAD OUTSIDE AIR DAMPER

ODT OUTDOOR TEMPERATURE

PC PUMP CONDENSATE

PD PRESSURE DROP

PRV PRESSURE REDUCING VALVE

PWF PROPELLER WALL FAN

R REFRIGERANT

RA RETURN AIR

RAD RETURN AIR DAMPER

RAS RELIEF AIR SUPPLY

RP RECIRCULATING PUMP

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID

RS REFRIGERANT SUCTION

RD ROOF DRAIN

RV RELIEF VALVE

SR SHORT RADIUS

OAL OUTSIDE AIR LOUVER

SAN SANITARY SEWER

SC SILL COCK

SCD SMOKE DAMPER

SD STORM DRAIN

SD SMOKE DETECTOR

SF SQUARE FEET

SDO STORM DRAIN OVERFLOW

SHC SENSIBLE HEAT CAPACITY

SP STAND PIPE

SP SUMP PUMP

SPS STATIC PRESSURE SENSOR

STA STATION

TR TEMPERED WATER RETURN

UG UNDERGROUND

VAC VACUUM PIPING

VDT VERTICAL DRAW THROUGH

VTR VENT THROUGH ROOF

WB WET BULB

O2 OXYGEN

F DEGREES FAHRE C DEGREES CENTI

WM WATER METER

WL WATER LINE

WH WATER HEATER

WG WATER GAUGE

W WIDTH

W WASTE

VT VERTICAL TURBINE

VFD VARIABLE FREQUENCY DRIVE

VB VACUUM BREAKER

VAV VARIABLE AIR VOLUME

V VENT

UC UNDERCUT (DOOR - 3/4")

V- VALVE

TOS TOP OF STRUCTURE

TB THRUST BLOCK

T TEMPERED WATER

STR STRAINER

SP STATIC PRESSURE

SP SPRINKLER PIPE

SG SPECIALTY GAS

EUH ELECTRIC UNIT HEATER

RECIRCULATING

DHR DOMESTIC HOT WATER

TRANSMITTER

DPT DIFFERENTIAL PRESSURE

PER MINUTE

SCIM STANDARD CUBIC INCHES

TEMPERATURE

SST SATURATED SUCTION

(UNINSULATED)

TE TOP ELEVATION

(TOWER) PUMP

TP CONDENSER WATER

FSD FIRE/SMOKE DAMPER

EA EXHAUST AIR

MA MIXED AIR

AE ADJUSTABLE AIR EXTRACTOR

RAO RETURN AIR OPENING

AD AREA DRAIN/ACCESS DOOR

SPS

SD

COMBINATION STARTER

STARTER

PIPE SLEEVE

CONCENTRIC REDUCER

PIPE ANCHOR

HVAC LEGEND

BALL VALVE WITH

3/4" HOSE END

BALANCE VALVE

THREADED & FLANGED

GLOBE VALVE

CHECK VALVE

GATE VALVE

BUTTERFLY VALVE

CONTROL VALVE

PLAN VIEW

RELIEF VALVE

FLANGED UNION

BRANCH OUT TOP

STRAINER

BRANCH OUT BOTTOM

ELBOW DOWN

ELBOW UP

TEE OUT TOP

BLIND FLANGE

PIPE CAP

AUTOMATIC AIR VENTAAV

FLEX. PIPE CONN.

BACKFLOW PREVENTER

TEE OUT BOTTOM

MANUAL AIR VENT

PIPE TEST PLUG

COLD WATER DOMESTIC

NATURAL GAS

DRAIN

CHILLED WATER RETURN

HEATING WATER RETURN

HOT WATER DOMESTIC

G

D

DUCT SIZE FIRST DIMENSION

IS SIDE SHOWN

24\12

DOOR GRILLE

C.F.M.

REFERS TO DETAIL OR

PLAN ON SHEET M-1.THERMOSTAT

INTERVAL TIMER

T

I.T.

1\M-4

DUCT/PLENUM w/LINER

FIRE DAMPER

ELBOW WITH

TURNING VANES

FLEX. DUCT CONN.

TURNING VANES

ELBOW WITHOUT

INSULATED FLEX. DUCT

INSULATED FLEX. DUCT

c

ECCENTRIC REDUCER

HWS

HWR

CHS

CHR

CONDENSER WATER RETURN

CS

CR

STATIC PRESSURE SENSOR

SMOKE DETECTOR

POINT OF CONNECTION

DUCT SPLIT

THREADED & FLANGED

THREADED & FLANGED

UNION

GAUGE TAPPING

GAUGE WITH TAPPING

THREADED & FLANGED

THREADED & FLANGED

PIPE SOCKET WELL

T G

ANNULAR ELEMENT FLOW STATION

DAMPER - BLADE VIEW DAMPER - END VIEW

xx{K OR xx/xx}K ROUND OR FLAT OVAL DUCT (K)

DOUBLE WALL INSULATED

ROUND OR FLAT OVAL DUCTxx{ OR xx/xx}

FLANGED

CIRCUIT SETTER TREADED &

FLOW INDICATOR BALANCER/

CONDENSER WATER SUPPY

CHILLED WATER SUPPLY

THERMOMETER IN WALL

2-WAY CONTROL VALVE

CO2 CO2 MONITER

THERMOSTAT w/GAURD

3-WAY CONTROL VALVE

& FLANGED

BALL VALVE THREADED

HEATING WATER SUPPLY

SINGLE LINE DUCT LEGEND

DUCT (SUPPLY, RETURN & EXHAUST)

SUPPLY DUCT UP

SUPPLY DUCT DOWN

RETURN OR EXHAUST DUCT UP

RETURN OR EXHAUST DUCT DOWN

DUCT RISE

DUCT DOWN

VOLUME DAMPER (MANUAL UNLESS INDICATED A.V.D.)

TRANSITION

DUCT TAKE-OFF (SEE SPEC. PERTAINING TO DEFLECTROLS)

TRANSITION (FLAT ON TOP)

TRANSITION (FLAT ON BOTTOM)

TRANSITION (TOP OR BOTTOM ONLY)

SUPPLY CEILING DIFFUSER

RETURN OR EXHAUST CEILING GRILLE

SIDEWALL SUPPLY

SIDEWALL RETURN

FLEXIBLE CONNECTION (DUCT)

RELIEF AIR SUPPLY TO TOILET

DUCT SPLIT WITH SPLITTER DAMPER

FLEX. DUCT WITH SCREW ON COLLAR, TAKE-OFF

DUCT WITH DUCT LINER

SQUARE ELBOW WITH TURNING VANES

RADIUS ELBOW (SEE SPECS. PERTAINING TO TURNING VANES)

AUTOMATIC VOLUME DAMPER

DN

R

12\10 SPLIT

OR

OR

SCD

FOB

T OR B

RAS

AVD

FD/SCD

FD

SMOKE CONTROL DAMPER

COMBINATION FIRE/SMOKE CONTROL DAMPER

FIRE DAMPER (FD)

FIRE DAMPER

FILE PATH:

P:\26011\26011mb10.dgn

DATE PLOTTED

DGN FILE

30-SEP-2026

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26011\26011mb10.dgn

AS SHOWN

26011

WSH

LTF

WSH

09.29.2026

T

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

F o rt V a ll e y

G e o rg ia

F V S

U B o n d H u n t

A H

U U p g ra d e s

ELEVATOR

MB10

SCALE:

= 1'-0

4 0 2 4 8

EXISTING TO REMAIN

DEMOLITION

LINE LEGEND

DEMOLITION - HVAC

FLOOR PLAN -

PARTIAL BASEMENT

LARGE SCALE -

BOND BUILDING -

BOND BUILDING - LARGE SCALE - PENTHOUSE PLAN - DEMOLITION - HVAC

S-1

R-132/16

E-1

AP

AP

4"

5"

GRATES IN FLOOR (4)

EXISTING 24"x60" RA

SD

SD

ACP-LCP-2

66"x84" RELIEF DAMPER

REMOVE EXISTING

RA DAMPER

66"x84"

EXISTING

REMOVE

8"W CONCRETE CURB

REMOVE EXISTING

TO REMAIN

EA LOUVER

EXISTING 36/32

TO REMAIN

EA LOUVER

EXISTING 24/24

TO REMAIN

EA LOUVER

EXISTING 32/16

MOUNTED ON WALL TO REMAIN

EXISTING AFTER COOLER

TO REMAIN

AIR COMPRESSOR

EXISTING CONTROL

FLOOR

FROM GROUND

EXISTING 36/24

INSULATION (TYP)

APPARATUS CASING

REMOVE EXISTING

FLUE TO REMAIN

12" FABRICATED

COOLING COILS, 108"x33" (3)

REMOVE EXISTING

TO REMAIN

100"x44" DN

SCALE:

= 1'-0

4 0 2 4 8

A

A

EXISTING

REMOVE

INERTIA BASE

8'-0"x7'-0"x 8" THICK

REMOVE EXISTING

8'-0"x7'-0"x8" THICK INERTIA BASE

REMOVE EXISTING

EXISTING

REMOVE

S-1

EXISTING

REMOVE

R-1

84"x66" RELIEF DAMPER

REMOVE EXISTING

B B

S-1EXISTING

REMOVE

INERTIA BASE

8'-0"x7'-0"x 8" THICK

REMOVE EXISTING

72"x60" MAX. OA DAMPER

72"x12" MIN .OA DAMPER;

REMOVE EXISTING

120"x20" OA LOUVER

REMOVE EXISTING

R E

M O

V

X

IS

T

IN

G

R O

L L

F

IL

T E

R

8'-0"x7'-0"x8" THICK INERTIA BASE

REMOVE EXISTING

8" WIDE x 48" HIGH CONCRETE PIERS

REMOVE EXISTING

& CASING INSULATION (TYP)

APPARATUS CASING

REMOVE EXISTING RA DAMPER

84"x66"

EXISTING

REMOVE

CEILING INSULATION (TYP)

MECH. RM.

REMOVE EXISTING CONCRETE CURBS

8'-0"x7'-0"x8" THICK INERTIA BASE

REMOVE EXISTING

& CASING INSULATION (TYP)

APPARATUS CASING

REMOVE EXISTING

SD

108"x33" (3)

COOLING COILS,

REMOVE EXISTING

CEILING INSULATION (TYP)

MECH. RM.

72"x60" MAX. OA DAMPER

72"x12" MIN .OA DAMPER;

REMOVE EXISTING

INSULATION (TYP)

APPARATUS CASING

REMOVE EXISTING

44"x100"

ROLL FILTER

REMOVE EXISTING

EXISTING FLOOR DRAIN

BOND BUILDING - LARGE SCALE - SECTION A-A - DEMOLITION - HVAC

SCALE:

= 1'-0

4 0 2 4 8

BOND BUILDING - LARGE SCALE - SECTION B-B - DEMOLITION - HVAC

INSULATION (TYP)

APPARATUS CASING

REMOVE EXISTING

STARTER TO REMAIN

EXISTING E-1

EXISTING VFD'S

REMOVE

EXISTING AP

EXISTING FD

FOR FAN, S-1

SHUT-DOWN SWITCH

REMOVE EMERGENCY

REMOVE

3"W-BF

4"W-BF

FILE PATH:

P:\26011\26011mb20.dgn

DATE PLOTTED

DGN FILE

30-SEP-2026

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26011\26011mb20.dgn

AS SHOWN

26011

WSH

LTF

WSH

09.29.2026

T

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

F o rt V a ll e y

G e o rg ia

F V S

U B o n d H u n t

A H

U U p g ra d e s

ELEVATOR

32/16

E-1

AP

AP

GRATES IN FLOOR (4)

EXISTING 24"x60" RA

TO REMAIN

EA LOUVER

EXISTING 36/32

TO REMAIN

EA LOUVER

EXISTING 24/24

TO REMAIN

EA LOUVER

EXISTING 32/16

FLOOR

FROM GROUND

EXISTING 36/24

FLUE TO REMAIN

12" FABRICATED

TO REMAIN

100"x44" DN

CEILING INSULATION (TYP)

MECH. RM.

44"x100"

EXISTING FLOOR DRAINSTARTER TO REMAIN

EXISTING E-1

EXISTING AP

EXISTING FD

3"W-BF

4"W-BF

MB20

SCALE:

= 1'-0

4 0 2 4 8

SCALE:

= 1'-0

4 0 2 4 8

BOND BUILDING - LARGE SCALE - PENTHOUSE PLAN - NEW WORK - HVAC BOND BUILDING - LARGE SCALE - SECTION B-B - NEW WORK - HVAC

NEW WORK - HVAC

PENTHOUSE PLANS -

LARGE SCALE -

BOND BUILDING -

100/44

AH-B-1NEW

CONCRETE PAD

COIL PULL

IN EXISTING WALL OPENING

OA INTAKE LOUVER

NEW 120"x120"

PLENUM ON BACK OF NEW LOUVER

PROVIDE FULLSIZE 18" DEEP

MIXING BOX

F

IL

T E

R

C O

O L

C

IL

F A

N

R A

Y

D

IS

C H

A R

G E

P

L E

N U

M

C H S

CHR

CHS

SD

122"x42" RA AVD

MIN. OA AVD

84/48 MAX. OA AVD

B

B

84/48

OA DUCT

24/12

AH-B-1NEW

CONCRETE PAD

D

IS

C H

A R

G E

P

L E

N U

M

F

R A

Y

C O

O L

IL

F

IL

T E

R

M

IX

X

IN EXISTING WALL OPENING

OA INTAKE LOUVER

NEW 120"x120"

PLENUM ON BACK OF NEW LOUVER

PROVIDE FULLSIZE 18" DEEP

SD

44/100

12/24

AFMS

AFMS

48/84

84/48 MAX. OA AVD

CHRCHS

SENSIBLETOTALMARK

NOTES:

MBH MBHDB WB DB WB

( F) ( F) ( F) ( F)

REMARKS

AH-B-1

TYPE

VAV

COOLING COIL

TOTAL

CFM

MIN. OA

CFM

ASSUMED

(IN.)

ESP

TSP (IN.)

MAX.

MOTOR

HP

FAN

TYPE WHEEL

MIN.

SIZE

CFM

COIL

38,000 2.0 4.0 7.5 24.5

ENTERING AIR LEAVING AIR

MAX. APDMIN. FACE

AREA

(FT )

1.25

( F) ( F)

EWT LWT

46 58

GPM

WPD

MAX.

(FT)

AIR FLOW

2,200 PLENUM 2 38,000 84 67 55 53 1,476 1,196 76

(IN.)

AIR HANDLING UNIT SCHEDULE

2 FAN ARRAY WITH SIX (6) FANS.

SIX (6) MOTORS @ 7.5 HP EACH. PROVIDE WALL MOUNTED VFDS. EACH VFD TO SERVE THREE (3) FAN MOTORS.

NEW VFD'S

6"

6"

6"

ACP

LINE LEGEND

POINT OF CONNECTION

EXISTING TO REMAIN

NEW WORK

122"x42" RA AVD

AP

AP

OA AVD

MIN.

NEW 3"FD

NEW 3"W-BF

CDEF

A R

E A

W A

Y

B

C O

R R

ID

O R

B

R O

O M

M A

C H

IN

E

E L

E V

A T

O R

SEAL

SCALE:

FILE PATH:

P:\26011\26011mh10.dgn

DATE PLOTTED

DGN FILE

30-SEP-2026

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26011\26011mh10.dgn

AS SHOWN

26011

WSH

LTF

WSH

09.29.2026

T

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

F o rt V a ll e y

G e o rg ia

F V S

U B o n d H u n t

A H

U U p g ra d e s

MH10

SCALE:

= 1'-0

OA DAMPER; 9500|

EXISTING 24"x60"

38/12

EF-1 1

T

EF-10

12/12 500|

T

HW

6" CHR

6" CHS

C O

O L

IL

C H S

C H

R

C O

O L

IL

H W

R

H W

S

H W

S

3" HWR

3" HWS

HWR

HWS

ƒ"

4 0 2 4 8

EF-1 1

MVD

w/FD

14"x14"RAO

EXISTING

EXISTING

HP-1

EXISTING

UH-1

EXISTING

EXISTING

T

N

DRAIN

EXISTING

& SADDLE SUPPORT

CONCRETE PAD

EXISTING 12"x12"

SD

EXISTING

ACP

UH-1

EXISTING BOILER

EXISTING HOSE BIB

WATER TREATMENT

EXISTING CONTROL PANEL CHEMICAL

TREATMENT TANKS

EXISTING CHEMICAL WATER

EXISTING PRV DRAIN LINE

EXISTING MAKE-UP WATER STATION LINE

AIR LOUVER

40"X40" COMBUSTION

EXISTING

EXISTING TO REMAIN

DEMOLITION

LINE LEGEND

EXISTING STARTERS

CT-1 & EF-1 1

F A

C P

F

HG

SWITCHBOARD"SB"

WATER EXPANSION TANK

EXISTING CHILLED

SUPPORT BEAMS B.E. 10'-8"

EXISTING GRATING

C H S

C H

R

6"

SMOKE DAMPER

96"x96" ISOLATION

EXISTING

6"

SLEEVE SEALS

MECHANICAL

EXISTING

WALL SUPPORT

EXISTING

CP-HL-1

6"

INLINE AIR PURGER

EXISTING

CHEMICAL FEEDER

EXISTING BYPASS

EXISTING

T

EF-10

EXISTING

BP

SWITCH-EF-1 1

EXISTING WALL PURGE

INTAKE LOUVER

EXISTING OA

ISOLATION DAMPER

EXISTING SMOKE

SF-1

RF-1

VFD-1

VFD-2

CONCRETE PAD

EXISTING

AIR COMPRESSOR

EXISTING CONTROL

TO REMAIN

CONCRETE PAD

EXISTING

DEMOLITION - HVAC

FLOOR PLAN -

PARTIAL BASEMENT

LARGE SCALE -

HUNT LIBRARY -HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - DEMOLITION - HVAC

EXISTING

REMOVE

EXISTING

REMOVE

EXISTING

REMOVE

EXISTING

REMOVE

TO REMAIN

EXISTING ACP

CDEF

A R

E A

W A

Y

B

C O

R R

ID

O R

B

R O

O M

M A

C H

IN

E

E L

E V

A T

O R

SEAL

SCALE:

FILE PATH:

P:\26011\26011mh20.dgn

DATE PLOTTED

DGN FILE

30-SEP-2026

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26011\26011mh20.dgn

AS SHOWN

26011

WSH

LTF

WSH

09.29.2026

T

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

F o rt V a ll e y

G e o rg ia

F V S

U B o n d H u n t

A H

U U p g ra d e s

OA DAMPER; 9500|

EXISTING 24"x60"

38/12

EF-1 1

T

EF-10

12/12 500|

T

HW

6" CHR

6" CHS

C O

O L

IL

C H S

C H

R

C O

O L

IL

H W

R

H W

S

H W

S

3" HWR

3" HWS

HWR

HWS

ƒ"

EF-1 1

MVD

w/FD

14"x14"RAO

EXISTING

EXISTING

HP-1

EXISTING

UH-1

EXISTING

EXISTING

T

DRAIN

EXISTING

& SADDLE SUPPORT

CONCRETE PAD

EXISTING 12"x12"

SD

EXISTING

ACP

UH-1

EXISTING BOILER

EXISTING HOSE BIB

WATER TREATMENT

EXISTING CONTROL PANEL CHEMICAL

TREATMENT TANKS

EXISTING CHEMICAL WATER

EXISTING PRV DRAIN LINE

EXISTING MAKE-UP WATER STATION LINE

AIR LOUVER

40"X40" COMBUSTION

EXISTING

EXISTING STARTERS

CT-1 & EF-1 1

F A

C P

F

HG

SWITCHBOARD"SB"

WATER EXPANSION TANK

EXISTING CHILLED

SUPPORT BEAMS B.E. 10'-8"

EXISTING GRATING

C H S

C H

R

6"

SMOKE DAMPER

96"x96" ISOLATION

EXISTING

6"

SLEEVE SEALS

MECHANICAL

EXISTING

WALL SUPPORT

EXISTING

CP-HL-1

6"

INLINE AIR PURGER

EXISTING

CHEMICAL FEEDER

EXISTING BYPASS

EXISTING

T

EF-10

EXISTING

BP

SWITCH-EF-1 1

EXISTING WALL PURGE

INTAKE LOUVER

EXISTING OA

CONCRETE PAD

EXISTING

AIR COMPRESSOR

EXISTING CONTROL

TO REMAIN

CONCRETE PAD

EXISTING

TO REMAIN

EXISTING ACP

MH20

SCALE:

= 1'-0

4 0 2 4 8

N

LINE LEGEND

POINT OF CONNECTION

EXISTING TO REMAIN

NEW WORK

HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - NEW WORK - HVAC

NEW WORK - HVAC

FLOOR PLAN -

PARTIAL BASEMENT

LARGE SCALE -

HUNT LIBRARY -

VFD VFD

EXISTING CASING WALL

NEW ACCESS DOOR IN

NEW CONCRETE PAD

RF-1

VFDVFD

SF-1

NEW NEW

NEW NEW

NEW CONCRETE PAD

(TYPICAL)

CONCRETE CURB

CASING WALL

NEW APPARATUS

CASING WALL

NEW APPARATUS

TYPE CFM

S.P.

IN W.G.

MARK

MAX.

RPM

REMARKS

FAN SCHEDULE

MIN.

FAN DIA.

(IN)

MOTOR

HP

DRIVE

NOTES:

1SF-1

RF-1

FAN ARRAY: EIGHT (8) FANS; 10 HP EACH.

FAN ARRAY: EIGHT (8) FANS; 3 HP EACH.

FAN ARRAY

FAN ARRAY

65,000

55,000

5.0

0.75

DIRECT

DIRECT2

FILE PATH:

P:\26011\26011m40.dgn

DATE PLOTTED

DGN FILE

30-SEP-2026

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26011\26011m40.dgn

AS SHOWN

26011

WSH

LTF

WSH

09.29.2026

T

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

F o rt V a ll e y

G e o rg ia

F V S

U B o n d H u n t

A H

U U p g ra d e s

M40

NOT TO SCALE

OUTPUTS INPUTS SOFTWARE

DIGITAL ANALOG ANALOG ALARM DDCDIGITAL ENERGY MGMT. LOGS

DDC PANELS

INPUT/OUTPUT

SUMMARIES

ACP

PRIMARY AIR FLOW

PERCENTAGE DESIGN FLOW-HEATING

PERCENTAGE DESIGN FLOW-COOLING

TAG

OA 1

FAR

TT 1

TT 2

TT 4

SPS H

SPS 1

TUC-XX

TUC-XX

TUC-XX

ZONE-SPACE TEMP.

SAT

LL

HT

CC-L.A.T.

L.L.-TEMP.

RA 1

T-XX

CC CONTROL VALVE

TT 5

VLV 1

HIGH LIMIT SPS

VAV SYSTEM

AFMS

OA 2

ELECTRIC HEATER - SCR

DP1 BUILDING PRESSURE

1. FAILURE MODES:

O - OPEN OR ON

C - CLOSE OR OFF

L - LAST COMMAND

2. WHERE FAILURE MODE IS INDICATED, THE INDICATED POSITION SHALL OCCUR ON INTERRUPTION OF

NOTES:

ELECTRIC POWER TO THE DDC PANEL.

S Y

S T

M

A P

H

IC

D

IS

P L

A Y

S T

A R

T

S T

O P

E N

A B

L E

D

IS

A B

L E

O P

E N

C L

O S

E

S T

A R

T

S T

P

K E

U P

S E

T P

O

T

J

U S

T

D

N T

R O

L

D

IF

F E

R E

N T

IA

L

P

R E S

S U

R E

P R

E S

S U

R E

S

W

IT

C H

A U

X

IL

IA

Y

N T

A C

T

A L

A

N T

A C

T

T E

M P

E R

A T

U R

E

R E

L A

T

IV

U

M

ID

IT

Y

P R

E S

S U

R E

H

IG

H

L

W

L

IM

IT

R

T A

L

IZ

A T

IO

N

P R

O P

O R

T

IO

N A

L

P R

O P

IN

T E

G R

A L

T

IM

E

S

C H

E D

U L

E

S

S

O P

T

IM

A R

T

S T

O P

D A

Y

N

IG

T B

A C

K

D E

M A

IT

C Y

C L

E

R E S

T

IM

IZ

A T

IO

N

E C

O N

O M

IZ

E R

F A

IL

U

D E (S

T E S

A

N D

N O

T E S

C U

R R

E

L A

Y

D R

IV

E

S

T A

T U

S

S P

E E

D

IN

D

IC

A T

IO

N

S P

E

N T

R O

L

E

W

IT

C H

C O

IR

F

O W

C A

L C

U L

A T

IN

T

P O

S

IT

IO

N

IN

D

IC

A T

IO

N

O P

E N

C L

O S

S

IT

IO

N

T R

E

G

S T

A T

U S

O

C

C

C

L

C

R

TT

FAR

CC

VLV

TTLL

TT

SPS

FIL

SPS

H

TUC

T-X

SAT

TU-X

A1

A1

A1D1

A1A1 D1

A0 A1

A1

A0 A1

SAF

VFD

VFD

FAR

A1D0 A0 D1

MCP

TUC

T-X

SAT

TU-X

A1

OA

A0 A1

A0 A1

RA

AFMS

TT

A1

OA

T

T

CHR

CHS

COND.

ZONE

COND.

ZONE

OA

MAX. OAD

MIN. OAD

HT

TRANSFER

DUCT

A1

DP

A1

TO ERU-1

TU-X

FP-X

FLOW DIAGRAM - VAV SYSTEM

AH AH

OA

OA

SA

SD

MIN. OA DAMPER

MAX/ OA DAMPER

MIN/ OA AFMS

RA DAMPER

RA TEMP.

RA-RH

RA

SA-TEMP.

SA-SPS

SA DAMPER ACTUATOR

SA TEMP. TO ZONE

MA TEMP.

FA RELAY

SA FAN ARRAY-VFD

AH-B-1 VAV SYSTEM

BOND AIR HANDLER

VFD 1, 2

EXISTING AIR TERMINAL UNITS (TU) (FP) FOR REFERENCE ONLY

A1

A1A0

A0 A1

A1

H W

S

H W

R

H W

S

H W

R

AH-B-1

R

VFD

FAR

A1D0 A0 D1

MCP

SAF

VFD

FAN ARRAY

VAV SYSTEM

FLOW DIAGRAM -

FILE PATH:

P:\26011\26011m50.dgn

DATE PLOTTED

DGN FILE

30-SEP-2026

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26011\26011m50.dgn

AS SHOWN

26011

WSH

LTF

WSH

09.29.2026

T

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

F o rt V a ll e y

G e o rg ia

F V S

U B o n d H u n t

A H

U U p g ra d e s

M50

HVAC

DETAILS -

TYPICAL DRAIN VALVE CONNECTION

TYPICAL WATER PIPING

REDUCER, IF REQUIRED

ƒ" BALL VALVE

ADAPTER TO ƒ" HOSE THREAD

PROVIDE HOSE CAP NUT

NOTES:

DRAIN ALL LOW POINTS AS INDICATED ABOVE.1.

2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS

AND/OR PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.

NOT TO SCALE

WELDED PIPING

ELEVATION

THREADED PIPING

ELEVATION

A

B

DRAIN LINE SHALL BE

AT LEAST THE SAME

SIZE AS THE NIPPLE

ON THE DRAIN PAN

DRAIN

PAN

1"

UNIT TYPE

WHERE X = STATIC PRESSURE IN PAN IN INCHES - H2O

A B

ADAPTER

DRAW THRU 2" PLUS X X

AIR HANDLING UNIT DRAIN TRAP

CLEAN OUT

SEDIMENT BUCKET

LOOSE CAP

GRATE

REMOVABLE

FITTING

LOOSE

THIS SIDE

FLOOR DRAIN (REFER TO DIVISION 220000)

FLOOR

PER FOOT SLOPE

MINIMUM 1/8 INCH

SLOPE TO DRAIN AT

1" (MIN)

DRAIN PIPE AS SPECIFIED

2" MAX.

REQUIRED BY CONDITIONS

DRAIN TERMINATION AS

BLOW THRU 1" MIN. 1.5"X

COIL

AIR FLOW

UNION

W\HOSE ADAPTOR

•" GATE VALVE

CONTROL

VALVE

N.C.

N.O.

C.

SUP

PL

Y

RET

URN

VALVE COEFFICIENTS

SYSTEM Cv RUNOUT SIZE

CIRCUIT SETTER

BALANCE VALVE (TYP)

TEST PLUG

BUTTERFLY VALVE

BUTTERFLY VALVE

HANGER ROD - SEE SPECIFICATIONS

SECTION OF RIGID INSULATION

SPECIFIED INSULATION

PIPE

• ROUND BEARING PLATE

PLATE WASHER

CUT ROD ABOVE ANGLE LEG

1" MIN.

TRAPEZE HANGER

LONG LEG VERTICAL

SEE SPECIFICATIONS

DOUBLE HEX NUTS

TRAPEZE PIPE HANGER

NOT TO SCALE

BRANCH CIRCUIT FROM

PANELBOARD,SWITCHGEAR,OR MCC

(2600)

SYSTEM SHOWN IN NORMAL (VFD NOT BYPASSED)

NUMBERS IN PARENTHESES INDICATE DIVISION

UNDER WHICH WORK OR EQUIPMENT IS SPECIFIED.

NOT TO SCALE

MODE, MOTOR RUNNING.

OVERLOAD

CIRCUIT

BREAKER

VFD SINGLE LINE DIAGRAM

VFD PACKAGE

RECTIFIER AND

INVERTER

NOTES:(THIS DETAIL ONLY)

(2600)

(2300)

MOTOR (2300)

NOT TO SCALE

NOT TO SCALE

(PROVIDE M.A.V. IF COIL IS NOT SELF VENTING)

(PROVIDE CONNECTIONS FOR NUMBER OF STACKED COILS PROVIDED WITH UNIT)

LOUVER

WALL MOUNTED LOUVER WITH PLENUM

COUNTER

FLASHING

20 GAUGE SLEEVE

16"MIN.

REFER TO ARCHITECTURAL

FOR STRUCTURE MATERIALS

SUB FRAME

IN BLOCK WALLS,

USE LINTELBLOCK

ON HEAD AND SILL

PROVIDE MINIMUM 16 INCH PLENUM BEHIND LOUVER

NOT TO SCALE

COOLING COIL PIPING

FILE PATH:

P:\26011\26011e00.dgn

DATE PLOTTED

DGN FILE

30-SEP-2026

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26011\26011e00.dgn

AS SHOWN

26011

09.29.2026

TWT

BCO

TWT

T

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

F o rt V a ll e y

G e o rg ia

F V S

U B o n d H u n t

A H

U U p g ra d e s

E00

CT

TRACK LIGHTS: QUANTITY OF HEADS AS SHOWN EMERGENCY BATTERY PACK-CEILING

EMERGENCY BATTERY PACK-WALL

PANELBOARD-250 VAC OR LESS

SURFACE MOUNTED

PANELBOARD-250 VAC OR LESS

RECESSED

PANELBOARD-OVER 250 VAC

SURFACE MOUNTED

PANELBOARD-OVER 250 VAC

RECESSED

CABLE TRAY

BACKBOARD

CONNECTION TO EQUIPMENT

CAP

CONDUIT DOWN

CONDUIT UP

J

F

BT

C

C

BR

U

SP

DP

PE

M

ICM

S

V

S

IC

MM

MC

LIGHTING FIXTURES (SYMBOLS VARY BASED ON FIXTURES TYPE)

LIGHTING CONTROL

RECEPTACLES

CIRCUITS

GENERAL EQUIPMENT

FIRE PROTECTION EQUIPMENT

COMMUNICATIONS

T

JJ

I

UI

I

ELECTRICAL LEGEND

TV

B

K

LED ON "NORMAL" POWER

CEILING MOUNTED FIXTURE

WALL MOUNTED FIXTURE

EXIT LIGHT (ARROWS AS SHOWN)

LIFE SAFETY EGRESS FIXTURE

CEILING MOUNTED ULTRASONIC OCCUPANCY

SENSOR AND RELAY

CEILING/WALL MOUNTED INFRARED OCCUPANCY

SENSOR AND RELAY

CEILING MOUNTED COMBINATION INFRARED/

ULTRASONIC OCCUPANCY SENSOR AND RELAY -

SWITCHING PHOTOCELL (INTERIOR TYPE) F.C. NOTED

DIMMING PHOTOCELL (INTERIOR TYPE)

EXTERIOR TYPE PHOTO SWITCH

LOW VOLTAGE OVERRIDE SWITCH

INFRARED OCCUPANCY SENSOR

WALL MOUNTED SWITCH

"P" INDICATES PILOT LIGHT

KEYED SWITCH

DIMMER SWITCH

FOUR WAY SWITCH

THREE WAY SWITCH

SINGLE POLE SWITCH

DUPLEX RECEPTACLE - NORMAL

QUAD - NORMAL

GFCI DUPLEX RECEPTACLE - NORMAL

GFCI QUAD - NORMAL

FLOOR DUPLEX RECEPTACLE - NORMAL

FLOOR QUAD - NORMAL

CEILING DUPLEX RECEPTACLE - NORMAL CLOCK OUTLET

WALL/CEILING RACEWAY

CEILING SPECIAL - TYPE NOTED OR SHOWN

SPECIAL - TYPE NOTED OR SHOWN

HORIZONTALLY MOUNTED DUPLEX RECEPTACLE

WEATHER PROOF RECEPTACLE (GFCI)

ELECTRIC WATER COOLER RECEPTACLE(GFCI)

CONDUIT CONCEALED IN CEILING OR WALL

CONDUIT IN GROUND, SLAB, OR UNDER FLOOR

FLEXIBLE RACEWAY

RACEWAY EXPOSED

TRANSFORMER

FRAME AMPS/POLES/NEMA TYPE

FUSE PER MANUFACTURERS RECOMMENDATIONS

ENCLOSED BREAKER-RECESSED IN WALL

ENCLOSED CIRCUIT BREAKER

EMERGENCY PUSHBUTTON

COMBINATION STARTER AND DISCONNECT

EXHAUST FAN

MANUAL STARTER AND MOTOR RATED SWITCH

MOTOR

JUNCTION BOX - WALL/CEILING/FLOOR

SURGE SUPPRESSOR

VOICE OUTLET, QUANTITY OF JACKS AS NOTED

DATA OUTLET, QUANTITY OF JACKS AS NOTED

COMBINATION VOICE/DATA OUTLET, QUANTITY OF

VOICE/DATA JACKS AS NOTED

FLOOR VOICE OUTLET, QUANTITY OF JACKS

AS NOTED

FLOOR DATA OUTLET, QUANTITY OF JACKS

AS NOTED

FLOOR COMBINATION VOICE/DATA OUTLET,

QUANTITY OF JACKS AS NOTED

MASTER CLOCK

INTERCOM MASTER STATION

INTERCOM CALL-IN STATION

WALL MOUNTED VOLUME CONTROL

BOX, STUB-UP, AND MODULAR PLATE W/ BLANKS

TELEVISION OUTLET

SPEAKER: CEILING/WALL

MICROPHONE: FLOOR/WALL

FIBER OUTLET

FACP

FAA

WF

VS

DH

SMOKE DETECTOR/SENSOR - BEAM RECEIVER

SMOKE DETECTOR/SENSOR - BEAM TRANSMITTER

SPEAKER/VISUAL ALARM: CEILING/WALL

VISUAL ALARM: CEILING/WALL

AUDIO/VISUAL ALARM: CEILING/WALL

MANUAL PULL STATION

FIRE ALARM ANNUNCIATOR

FIRE ALARM PANEL

DUCT MOUNTED SMOKE DETECTOR

SMOKE DETECTOR: CEILING / WALL

HEAT DETECTOR: CEILING / WALL

WATER FLOW SWITCH

WATER TAMPER SWITCH

DOOR HOLDER

FIREMAN'S PHONE OUTLET

EWC

WP

H

D

P

I

L

TWO ZONE LOW VOLTAGE SWITCHL2

VACANCY AUTO SHUT OFF

FOUR ZONE LOW VOLTAGE SWITCHL4

DUPLEX RECEPTACLE WITH INTEGRAL USBUSB

TV DUPLEX RECEPTACLETV

AC

ABOVE COUNTER DUPLEX RECEPTACLE (COORDINATE

HEIGHT WITH ARCHITECT)

J-HOOK

CABLE TRAY

DUPLEX RECEPTACLE MOUNTED IN RACEWAYR

R DATA OUTLET MOUNTED IN RACEWAY

DUPLEX RECEPTACLE - TAMPER PROOFT

DUPLEX RECEPTACLE - GENERATOR CIRCUIT, RED IN COLOR

QUAD - GENERATOR CIRCUIT, RED IN COLOR

SINGLE ZONE LOW VOLTAGE SWITCHL1

HOMERUN - ONE ARROW PER CIRCUIT

DISCONNECT SWITCH: "F" IF FUSED

F

ELECTRICAL

LEGEND -

FILE PATH:

P:\26011\26011eb20.dgn

DATE PLOTTED

DGN FILE

30-SEP-2026

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26011\26011eb20.dgn

AS SHOWN

26011

09.29.2026

TWT

BCO

TWT

T

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

F o rt V a ll e y

G e o rg ia

F V S

U B o n d H u n t

A H

U U p g ra d e s

ELEVATOR ELEVATOR

E-1

EXISTING

GRATES IN FLOOR (4)

EXISTING 24"x60" RA

PHA

J

DOWN

PHA-1

PHA-2

1•" C FEEDER DOWN

AC COMPRESSOR

•/460/3 ƒ/460/3 (E-1)

AFTER COOLER

/120/1

J

DOWN

STARTER TO REMAIN

EXISTING E-1

AH-B-1NEW

NEW VFD'S

ACP

EB20

SCALE:

= 1'-0

4 0 2 4 8

SCALE:

= 1'-0

4 0 2 4 8

BOND BUILDING - LARGE SCALE - PENTHOUSE PLAN - NEW WORK - ELEC

E-1

ACP-LCP-2

EXISTING

S-1

EXISTING

GRATES IN FLOOR (4)

EXISTING 24"x60" RA

PHA

TO REMAIN

BOND BUILDING - LARGE SCALE - PENTHOUSE PLAN - DEMOLITION - ELEC

NEW WORK - ELEC

DEMOLITION &

PENTHOUSE PLANS -

LARGE SCALE -

BOND BUILDING -

J

DOWN

PHA-5

PHA-1

PHA-8

PHA-2

LB-23

1•" C

40/460/3 (S-1)

30/1

FEEDER DOWN

AC COMPRESSOR

•/460/3 ƒ/460/3 (E-1)

AFTER COOLER

/120/1

J

‚/120/1 ROLLER FILTER

100/3

3#6-1"C

DOWN

3#10-3/4"C

15/460/3 (R-1)

STARTER TO REMAIN

EXISTING E-1

EXISTING VFD'S

REMOVE

FOR FAN, S-1, TO BE REMOVED

SHUT-DOWN SWITCH

EXISTING EMERGENCY

TO BE REMOVED

NEW

NOTES:(THIS SHEET ONLY)

LOCATED IN THIS PENTHOUSE. REMOVE THE EXISTING 100A/3P CIRCUIT BREAKER.

REMOVE EXISTING VFD AND CONDUCTORS/CONDUIT BACK TO SERVING PANEL PHA

LOCATED IN THIS PENTHOUSE. REMOVE THE EXISTING 50A/3P CIRCUIT BREAKER.

REMOVE EXISTING VFD AND CONDUCTORS/CONDUIT BACK TO SERVING PANEL PHA

120 VOLT CIRCUIT TO NEW ACP SHOWN BY NOTE 4.

EXISTING AUTOMATED CONTROL PANEL (ACP) BEING REMOVED. EXTEND EXISTING

3#6 AWG, 1#10G, 1"C.

THE MOTOR CIRCUIT PROTECTOR PANEL. FOR EACH 50 AMP CIRCUIT PROVIDE

PANEL AIC RATING. MAKE ALL FINAL CONNECTIONS THROUGH THE VFDS AND

NEW 50A/3P CIRCUIT BREAKERS IN EXISTING PANEL PHA, MATCHING EXISTING

SPLIT INTO TWO VFD CIRCUITS, ONE FOR BOTH SETS OF 3 FANS. PROVIDE TWO

PROTECTOR PANEL WITH INDIVIDUAL MOTOR PROTECTORS. THE FANS WILL BE

RETURN FANS. THE AHU MANUFACTURER WILL PROVIDE A MOTOR CIRCUIT

THE NEW AIR HANDLER WILL HAVE A FAN ARRAY WITH 6 SUPPLY FANS, BUT NO

IN EXISTING PATCH PANEL. NEW DATA CABLE SHALL BE PLENUM RATED.

CAT 6 DATA DROP AND ROUTE BACK TO NEAREST IDF OR BUILDING MDF. TERMINATE

NEW ACP LOCATION. MAKE ALL FINAL POWER CONNECTIONS. PROVIDE ONE NEW

BUILDING FIRE ALARM SYSTEM. PROVIDE FIRE ALARM RELAY TO SHUT DOWN AHU.

PROVIDE NEW DUCT MOUNTED SMOKE DETECTOR AND CONNECT TO EXISTING

RATING. MAKE ALL FINAL CONNECTIONS.

SPARE CAPACITY, PROVIDE A NEW 20A/1P CIRCUIT BREAKER MATCHING PANEL AIC

AND ACCESSORIES. ROUTE 3#12 AWG,•"C TO NEAREST 120 VOLT PANELBOARD WITH

PROVIDE DEDICATED 20 AMP, 120 VOLT CIRCUIT FOR NEW AIR HANDLING UNIT LIGHTS

TO NEW LIGHTS SHOWN ON NEW WORK PLAN.

SHALL REMAIN AND BE REUSED. EXISTING CIRCUITS SHALL REMAIN AND BE EXTENDED

REMOVE ALL OF THE EXISTING LIGHT FIXTURES IN THESE SPACES. EXISTING SWITCHES

THE SPACE.

THESE LIGHTS SHOULD BE SHIFTED AROUND AS REQUIRED TO ADEQUATELY LIGHT

PROVIDE ACUITY LIGHTING LED STRIP LIGHT MODEL CSS-L48-5000LM-MVOLT-40K.

PROVIDE WITH INTEGRAL BATTERY FOR EMERGENCY EGRESS LIGHTING.

8 8

J

9 10

9 9

CDEF

A R

E A

W A

Y

B

C O

R R

ID

O R

B

R O

O M

M A

C H

IN

E

E L

E V

A T

O R

SEAL

SCALE:

FILE PATH:

P:\26011\26011eh10.dgn

DATE PLOTTED

DGN FILE

30-SEP-2026

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26011\26011eh10.dgn

AS SHOWN

26011

09.29.2026

TWT

BCO

TWT

T

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

F o rt V a ll e y

G e o rg ia

F V S

U B o n d H u n t

A H

U U p g ra d e s

EH10

SCALE:

= 1'-0

EF-1 1

EF-10

HW

4 0 2 4 8

EXISTING

HP-1

EXISTING

UH-1 EXISTING

EXISTING

N

& SADDLE SUPPORT

CONCRETE PAD

EXISTING 12"x12"

EXISTING

ACP

EXISTING BOILER

WATER TREATMENT

EXISTING CONTROL PANEL CHEMICAL

TREATMENT TANKS

EXISTING CHEMICAL WATER

AIR LOUVER

40"X40" COMBUSTION

EXISTING

F A

C P

F

HG

SWITCHBOARD"SB"

WATER EXPANSION TANK

EXISTING CHILLED

S

ELEVATOR MOTOR

EXISTING SERVICE

100A/3P

SUPPORT BEAMS B.E. 10'-8"

EXISTING GRATING

EXISTING STARTERS

CT-1 & EF-1 1

CHEMICAL FEEDER

EXISTING BYPASS

CP-HL-1

EXISTING

OA DAMPER; 9500|

EXISTING 24"x60"

INTAKE LOUVER

EXISTING OA

EXISTING

BP

AIR COMPRESSOR

EXISTING CONTROL

SWITCH-EF-1 1

EXISTING WALL PURGE

HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - DEMOLITION - ELEC

DEMOLITION - ELEC

FLOOR PLAN -

PARTIAL BASEMENT

LARGE SCALE -

HUNT LIBRARY -

SF-1

RF-1

VFD-1

VFD-2

EXISTING

REMOVE

EXISTING

REMOVE

EXISTING

REMOVE

EXISTING

REMOVE

NOTES:(THIS SHEET ONLY)

WORK PLAN FOR NEW SCOPE.

VFD AND ALL WIRING/CONDUIT FROM THE VFD TO THE EXISTING FAN. SEE NEW

SHALL BE REUSED TO SERVE THE NEW SUPPLY FAN ARRAY. REMOVE THE EXISTING

THE EXISTING 3#4/0, 1#4G, 2"C FEEDER CURRENTLY SERVING SUPPLY FAN SF-1

WORK PLAN FOR NEW SCOPE.

VFD AND ALL WIRING/CONDUIT FROM THE VFD TO THE EXISTING FAN. SEE NEW

SHALL BE REUSED TO SERVE THE NEW RETURN FAN ARRAY. REMOVE THE EXISTING

THE EXISTING 3#4, 1#8G, 1"C FEEDER CURRENTLY SERVING RETURN FAN RF-1

TO NEW LIGHTS SHOWN ON NEW WORK PLAN.

SHALL REMAIN AND BE REUSED. EXISTING CIRCUITS SHALL REMAIN AND BE EXTENDED

REMOVE ALL OF THE EXISTING LIGHT FIXTURES IN THESE SPACES. EXISTING SWITCHES 3

EXISTING ACP

CDEF

A R

E A

W A

Y

B

C O

R R

ID

O R

B

R O

O M

M A

C H

IN

E

E L

E V

A T

O R

SEAL

SCALE:

FILE PATH:

P:\26011\26011eh20.dgn

DATE PLOTTED

DGN FILE

30-SEP-2026

SHEET NUMBER:

316 CORPORATE PARKWAY

NBP Engineers, Inc.

MACON, GEORGIA 31210

NBP

ENGINEERS

478-745-1691 www.nbpengineers.com

No. REVISIONS/SUBMISSIONS DATE

DRAWN:

CHECKED:

DESIGNED:

DATE:

PROJECT NUMBER:

P R

O J E

C T

T

IT

L E

SHEET TITLE:

CONSULTANTS

THIS DRAWING IS THE PROPERTY OF THE

ENGINEER AND MAY NOT BE REPRODUCED

OR USED IN WHOLE OR IN PART

WITHOUT HIS WRITTEN PERMISSION. IT IS

TO BE USED FOR THE PROJECT

SPECIFICALLY IDENTIFIED HEREIN AND TO

BE RETURNED UPON REQUEST.

P:\26011\26011eh20.dgn

AS SHOWN

26011

09.29.2026

TWT

BCO

TWT

T

COA Expiration: 6.30.2028

COA#PEF000774

NBP Engineers, Inc.

F o rt V a ll e y

G e o rg ia

F V S

U B o n d H u n t

A H

U U p g ra d e s

EF-1 1

EF-10

HW

EXISTING

HP-1

EXISTING

UH-1 EXISTING

EXISTING

& SADDLE SUPPORT

CONCRETE PAD

EXISTING 12"x12"

EXISTING

ACP

EXISTING BOILER

WATER TREATMENT

EXISTING CONTROL PANEL CHEMICAL

TREATMENT TANKS

EXISTING CHEMICAL WATER

AIR LOUVER

40"X40" COMBUSTION

EXISTING

F A

C P

F

HG

SWITCHBOARD"SB"

WATER EXPANSION TANK

EXISTING CHILLED

S

ELEVATOR MOTOR

EXISTING SERVICE

100A/3P

SUPPORT BEAMS B.E. 10'-8"

EXISTING GRATING

EXISTING STARTERS

CT-1 & EF-1 1

CHEMICAL FEEDER

EXISTING BYPASS

CP-HL-1

EXISTING

OA DAMPER; 9500|

EXISTING 24"x60"

INTAKE LOUVER

EXISTING OA

EXISTING

BP

AIR COMPRESSOR

EXISTING CONTROL

SWITCH-EF-1 1

EXISTING WALL PURGE

TO REMAIN

EXISTING ACP

VFD VFD

RF-1

VFDVFD

SF-1

NEW NEW

NEW NEW

EH20

SCALE:

= 1'-0

4 0 2 4 8

N

HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - NEW WORK - ELEC

NEW WORK - ELEC

FLOOR PLAN -

PARTIAL BASEMENT

LARGE SCALE -

HUNT LIBRARY -

F

F

NOTES:(THIS SHEET ONLY)

BACK IN THE MAIN SWITCHBOARD SHALL BE REUSED.

THE MOTOR CIRCUIT PROTECTOR PANEL. THE EXISTING 225A/3P CIRCUIT BREAKER

THERE ARE 8 FANS TOTAL. MAKE ALL FINAL CONNECTIONS THROUGH THE VFDS AND

3#1 AWG, 1#6G, 1-1/2"C. EACH VFD SHALL SERVE 4 FANS IN THE SUPPLY FAN ARRAY.

110A/3P ENCLOSED CIRCUIT BREAKER (TWO TOTAL) AT EACH TAP. EACH TAP SHALL BE

CIRCUIT BREAKER ABOVE EACH VFD. TAP THE #4/0 COPPER FEEDER AND PROVIDE THE

PROVIDE A WIRING TROUGH ABOVE THE NEW VFDS. PROVIDE A 110A/3P ENCLOSED

SWITCHBOARD AND SET A NEW 400A/3P FUSED DISCONNECT FUSED AT 225 AMPS.

INTERCEPT THE EXISTING FEEDER CONDUCTORS (3#4/0, 1#4G, 2"C) FROM THE MAIN

BACK IN THE MAIN SWITCHBOARD SHALL BE REUSED.

THE MOTOR CIRCUIT PROTECTOR PANEL. THE EXISTING 70A/3P CIRCUIT BREAKER

THERE ARE 8 FANS TOTAL. MAKE ALL FINAL CONNECTIONS THROUGH THE VFDS AND

BE 3#8 AWG, 1#10G, 1"C. EACH VFD SHALL SERVE 4 FANS IN THE SUPPLY FAN ARRAY.

THE 35A/3P ENCLOSED CIRCUIT BREAKER (TWO TOTAL) AT EACH TAP. EACH TAP SHALL

CIRCUIT BREAKER ABOVE EACH VFD. TAP THE #4 AWG COPPER FEEDER AND PROVIDE

PROVIDE A WIRING TROUGH ABOVE THE NEW VFDS. PROVIDE A 35A/3P ENCLOSED

SWITCHBOARD AND SET A NEW 100A/3P FUSED DISCONNECT FUSED AT 70 AMPS.

INTERCEPT THE EXISTING FEEDER CONDUCTORS (3#4, 1#8G, 1"C) FROM THE MAIN

FIRE ALARM SYSTEM. PROVIDE FIRE ALARM RELAY TO SHUT DOWN AHU.

PROVIDE NEW DUCT MOUNTED SMOKE DETECTOR AND CONNECT TO EXISTING BUILDING

ALARM RELAY TO SHUT DOWN AHU.

PROVIDE SPACE TYPE SMOKE DETECTOR INSIDE RETURN AIR PLENUM. PROVIDE FIRE

LIGHTS AROUND AS NECESSARY TO LIGHT SERVICE AREAS.

THESE LIGHTS SHALL BE MOUNTED INSIDE THE AIR HANDLING UNIT APPARATUS CASING. MOVE

PROVIDE ACUITY LIGHTING VAPOR TIGHT LED STRIP LIGHT MODEL CSVT-L48-5000LM-MVOLT-40K.

SHOULD BE SHIFTED AROUND AS REQUIRED TO ADEQUATELY LIGHT THE SPACE.

PROVIDE ACUITY LIGHTING LED STRIP LIGHT MODEL CSS-L48-5000LM-MVOLT-40K. THESE LIGHTS

PROVIDE WITH INTEGRAL BATTERY FOR EMERGENCY EGRESS LIGHTING.

5 7

5 5

5 7

5 5 5 7

5 7

6 7

6 7

6 7 6

26011aCov
26011m00
26011mb10
26011mb20
26011mh10
26011mh20
26011m40
26011m50
26011e00
26011eb20
26011eh10
26011eh20