2026_09_29_FVSU_Bond_Hunt_BidSet_NBP.pdf
PDF 2 MB Posted
- Attached to
- FVSU- Bond and Hunt
- Solicitation number
- PE-53300-RFP-2027-000000073
- Issued by
- Paulding County, Georgia
About this file
This is a bid set of engineering drawings prepared by NBP Engineers, Inc. for Fort Valley State University (FVSU) in Fort Valley, Georgia, detailing Air Handling Unit (AHU) upgrades for the Bond and Hunt buildings. The project, identified as Project Number 26011, involves comprehensive HVAC and electrical modifications to both buildings' mechanical systems. The scope of work includes demolition of existing equipment and installation of new air handling units, with specific work divided between the Bond Building penthouse and Hunt Library basement mechanical spaces. The Bond Building upgrade features a new VAV (Variable Air Volume) system with AH-B-1 air handler rated at 38,000 CFM maximum, incorporating a six-fan array with 7.5 HP motors each and wall-mounted variable frequency drives (VFDs). The Hunt Library scope includes new supply and return fan arrays with eight fans each (10 HP and 3 HP respectively), operating at 65,000 CFM and 55,000 CFM. The bid set includes detailed floor plans, sections, equipment schedules, piping diagrams, control system schematics, and electrical single-line diagrams for both demolition and new work phases. The drawings are dated September 29, 2026, indicating the bid set release date.
The project documentation includes comprehensive specifications for equipment removal, new equipment installation, piping connections, ductwork modifications, and control system integration using Direct Digital Control (DDC) technology. Electrical work encompasses new VFD installations, motor circuit protector panels, dedicated lighting circuits with LED fixtures including emergency egress capability, fire alarm system integration with duct-mounted smoke detectors, and control panel connections. The design incorporates chilled water cooling coils, heating water circuits, outdoor air dampers with automatic volume control, and relief air systems. Equipment to be removed includes existing inertia bases, cooling coils, roll filters, relief dampers, and associated piping and insulation. The new systems feature automatic air vents, balance valves, flow measurement stations, and isolation dampers throughout. Professional engineering services are provided by NBP Engineers, Inc., located in Macon, Georgia, with a Certificate of Authorization expiration date of June 30, 2028. The bid set establishes the technical baseline for contractor proposals and represents a significant mechanical and electrical infrastructure upgrade for both campus facilities.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2026_09_29_FVSU Bond_Hunt AHU Upgrades_Projec.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT CONSULTANTS
INDEX OF
DRAWINGS
TITLESHEET NO.
316 CORPORATE PARKWAY MACON, GEORGIA
NBP ENGINEERS, INC.
CONSULTANTS
Fort Valley, Georgia
M00 ABBREVIATIONS, LEGENDS, & SCHEDULES - HVAC
MH10
MH20
E00
EH10
EH20
HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - DEMOLITION - HVAC
HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - NEW WORK- HVAC
HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - DEMOLITION - ELEC
HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - NEW WORK - ELEC
LEGEND - ELECTRICAL
EB20 BOND BUILDING - LARGE SCALE - PENTHOUSE PLANS - DEMOLITION & NEW WORK - ELEC
M40 FLOW DIAGRAM - VAV SYSTEM
M50 DETAILS - HVAC
MB10
MB20
BOND BUILDING - LARGE SCALE - PENTHOUSE PLAN - DEMOLITION - HVAC
BOND BUILDING - LARGE SCALE - PENTHOUSE PLAN - NEW WORK - HVAC
09.29.2026 BID SET
FVSU - Bond & Hunt AHU Upgrades
SEAL
SCALE:
FILE PATH:
P:\26011\26011m00.dgn
DATE PLOTTED
DGN FILE
30-SEP-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26011\26011m00.dgn
AS SHOWN
26011
WSH
LTF
WSH
09.29.2026
B
ID
S E
T
COA Expiration: 6.30.2028
COA#PEF000774
NBP Engineers, Inc.
F o rt V a ll e y
G e o rg ia
F V S
U B o n d H u n t
A H
U U p g ra d e s
M00
HVAC
SCHEDULES -
LEGENDS, &
ABBREVIATIONS,
A COMPRESSED AIR
AAV AUTOMATIC AIR VENT
AF AIR FOIL
-AFF ABOVE FINISHED FLOOR
AV ACID VENT
AVD AUTOMATIC VOLUME DAMPER
AW ACID WASTE
-AC ABOVE CEILING
AH- AIR HANDLING UNIT
BBD BOILER BLOW DOWN
BE BOTTOM ELEVATION
BOL BOTTOM OF LINE (UNINSULATED)
BOD BOTTOM OF DUCT
BP- BOOSTER PUMP
BTUH BRITISH THERMAL UNIT PER HOUR
-BF BELOW FLOOR
BFP BACK FLOW PREVENTOR
C CONDUIT
CC COOLING COIL
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CR CONDENSER WATER RETURN
CS CONDENSER WATER SUPPLY
CW DOMESTIC COLD WATER
CAB CABINET FAN
CF CENTRIFICAL FAN
CFM CUBIC FEET PER MINUTE
CFP CHEMICAL FEED PUMP
CFT CHEMICAL FEED TANK
CH CABINET HEATER
CHR CHILLER
CL CENTER LINE
CO CLEANOUT
CP CHILLER PUMP
CPHB CHROME PLATED HOSE BIBB
CT COOLING TOWER
CU COPPER
CV- CONVECTOR
Cv VALVE COEFFICIENT
D DRAIN
DDC DIRECT DIGITAL CONTROL
DHW DOMESTIC HOT WATER
DN DOWN
DP DIFFERENTIAL PRESSURE
DS DOWN SPOUT
DSO DOWN SPOUT OVER FLOW
DX DIRECT EXCHANGE
EAD EXHAUST AIR DAMPER
EAT ENTERING AIR TEMPERATURE
EDB ENTERING DRY BULB
EWB ENTERING WET BULB
ESP END SUCTION PUMP
ESP EXTERNAL STATIC PRESSURE
ELL ELBOW
ET EXPANSION TANK
EQT EQUIPMENT TRAP SET
EWT ENTERING WATER TEMPERATURE
EX EXPANSION TANK LINE
EXT EXTERNAL
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
F&BP FACE & BYPASS
FC FAN COIL UNIT
BPD BYPASS DAMPER
EAL EXHAUST AIR LOUVER
ECH ELECTRIC CABINET HEATER
ABBREVIATIONS
FD FLOOR DRAIN
FF FOULING FACTOR
FF- FLY FAN
FF FINISHED FLOOR
FF FINAL FILTER
FFM FIRE FLOW METER
FLEX FLEXIBLE
FM FIRE MAIN
FMS FLOW METER STATION
FOF FUEL OIL FLOW
FOR FUEL OIL RETURN
FOV FUEL OIL VENT
FOP FUEL OIL PUMP
FP FIRE PUMP
FP- FAN POWERED
FPM FEET PER MINUTE
FPS FEET PER SECOND
FRT FLOW RATE TRANSMITTER
FT FEET
G LOW PRESSURE GAS
GA GAUGE
GPM GALLONS PER MINUTE
GT GREASE TRAP
GTH GRAND TOTAL HEAT
H HEIGHT
HC HEATING COIL
HB HOSE BIBB
HBT HORIZONTAL BLOW THROUGH
HD HUB DRAIN
HDT HORIZONTAL DRAW THROUGH
HP HORSEPOWER/HIGH PRESSURE
HPA HIGH PRESSURE AIR
HPG HIGH PRESSURE GAS
HPS HIGH PRESSURE STEAM
HPWS HEAT PUMP WATER SUPPLY
HPWR HEAT PUMP WATER RETURN
HSC HORIZONTAL SPLIT CASE
HWG HOT WATER GENERATOR
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
ILC IN-LINE CENTRIFICAL
IT INTERVAL TIMER
IN INCHES
INV INVERT
JB JUNCTION BOX
L LENGTH
LR LONG RADIUS
LAT LEAVING AIR TEMPERATURE
LCP LOCAL CONTROL PANEL
LDB LEAVING DRY BULB
LN LIQUID NITROGEN
LWB LEAVING WET BULB
LWT LEAVING WATER TEMPERATURE
LPS LOW PRESSURE STEAM
MAV MANUAL AIR VENT
MVD MANUAL VOLUME DAMPER
MAX MAXIMUM
MBH ONE THOUSAND BTUH PER HOUR
MCC MOTOR CONTROL CENTER
MIN MINIMUM
MH MAN HOLE
MP SUMP (MUD) PUMP
MPS MEDIUM PRESSURE STEAM
MPR MEDIUM PRESSURE RETURN
MTS MEDIUM TEMPERATURE SUPPLY
MTR MEDIUM TEMPERATURE RETURN
MUA MAKE-UP AIR
MUW MAKE-UP WATER
MZ MULTIZONE
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OAD OUTSIDE AIR DAMPER
ODT OUTDOOR TEMPERATURE
PC PUMP CONDENSATE
PD PRESSURE DROP
PRV PRESSURE REDUCING VALVE
PWF PROPELLER WALL FAN
R REFRIGERANT
RA RETURN AIR
RAD RETURN AIR DAMPER
RAS RELIEF AIR SUPPLY
RP RECIRCULATING PUMP
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
RD ROOF DRAIN
RV RELIEF VALVE
SR SHORT RADIUS
OAL OUTSIDE AIR LOUVER
SAN SANITARY SEWER
SC SILL COCK
SCD SMOKE DAMPER
SD STORM DRAIN
SD SMOKE DETECTOR
SF SQUARE FEET
SDO STORM DRAIN OVERFLOW
SHC SENSIBLE HEAT CAPACITY
SP STAND PIPE
SP SUMP PUMP
SPS STATIC PRESSURE SENSOR
STA STATION
TR TEMPERED WATER RETURN
UG UNDERGROUND
VAC VACUUM PIPING
VDT VERTICAL DRAW THROUGH
VTR VENT THROUGH ROOF
WB WET BULB
O2 OXYGEN
F DEGREES FAHRE C DEGREES CENTI
WM WATER METER
WL WATER LINE
WH WATER HEATER
WG WATER GAUGE
W WIDTH
W WASTE
VT VERTICAL TURBINE
VFD VARIABLE FREQUENCY DRIVE
VB VACUUM BREAKER
VAV VARIABLE AIR VOLUME
V VENT
UC UNDERCUT (DOOR - 3/4")
V- VALVE
TOS TOP OF STRUCTURE
TB THRUST BLOCK
T TEMPERED WATER
STR STRAINER
SP STATIC PRESSURE
SP SPRINKLER PIPE
SG SPECIALTY GAS
EUH ELECTRIC UNIT HEATER
RECIRCULATING
DHR DOMESTIC HOT WATER
TRANSMITTER
DPT DIFFERENTIAL PRESSURE
PER MINUTE
SCIM STANDARD CUBIC INCHES
TEMPERATURE
SST SATURATED SUCTION
(UNINSULATED)
TE TOP ELEVATION
(TOWER) PUMP
TP CONDENSER WATER
FSD FIRE/SMOKE DAMPER
EA EXHAUST AIR
MA MIXED AIR
AE ADJUSTABLE AIR EXTRACTOR
RAO RETURN AIR OPENING
AD AREA DRAIN/ACCESS DOOR
SPS
SD
COMBINATION STARTER
STARTER
PIPE SLEEVE
CONCENTRIC REDUCER
PIPE ANCHOR
HVAC LEGEND
BALL VALVE WITH
3/4" HOSE END
BALANCE VALVE
THREADED & FLANGED
GLOBE VALVE
CHECK VALVE
GATE VALVE
BUTTERFLY VALVE
CONTROL VALVE
PLAN VIEW
RELIEF VALVE
FLANGED UNION
BRANCH OUT TOP
STRAINER
BRANCH OUT BOTTOM
ELBOW DOWN
ELBOW UP
TEE OUT TOP
BLIND FLANGE
PIPE CAP
AUTOMATIC AIR VENTAAV
FLEX. PIPE CONN.
BACKFLOW PREVENTER
TEE OUT BOTTOM
MANUAL AIR VENT
PIPE TEST PLUG
COLD WATER DOMESTIC
NATURAL GAS
DRAIN
CHILLED WATER RETURN
HEATING WATER RETURN
HOT WATER DOMESTIC
G
D
DUCT SIZE FIRST DIMENSION
IS SIDE SHOWN
24\12
DOOR GRILLE
C.F.M.
REFERS TO DETAIL OR
PLAN ON SHEET M-1.THERMOSTAT
INTERVAL TIMER
T
I.T.
1\M-4
DUCT/PLENUM w/LINER
FIRE DAMPER
ELBOW WITH
TURNING VANES
FLEX. DUCT CONN.
TURNING VANES
ELBOW WITHOUT
INSULATED FLEX. DUCT
INSULATED FLEX. DUCT
c
ECCENTRIC REDUCER
HWS
HWR
CHS
CHR
CONDENSER WATER RETURN
CS
CR
STATIC PRESSURE SENSOR
SMOKE DETECTOR
POINT OF CONNECTION
DUCT SPLIT
THREADED & FLANGED
THREADED & FLANGED
UNION
GAUGE TAPPING
GAUGE WITH TAPPING
THREADED & FLANGED
THREADED & FLANGED
PIPE SOCKET WELL
T G
ANNULAR ELEMENT FLOW STATION
DAMPER - BLADE VIEW DAMPER - END VIEW
xx{K OR xx/xx}K ROUND OR FLAT OVAL DUCT (K)
DOUBLE WALL INSULATED
ROUND OR FLAT OVAL DUCTxx{ OR xx/xx}
FLANGED
CIRCUIT SETTER TREADED &
FLOW INDICATOR BALANCER/
CONDENSER WATER SUPPY
CHILLED WATER SUPPLY
THERMOMETER IN WALL
2-WAY CONTROL VALVE
CO2 CO2 MONITER
THERMOSTAT w/GAURD
3-WAY CONTROL VALVE
& FLANGED
BALL VALVE THREADED
HEATING WATER SUPPLY
SINGLE LINE DUCT LEGEND
DUCT (SUPPLY, RETURN & EXHAUST)
SUPPLY DUCT UP
SUPPLY DUCT DOWN
RETURN OR EXHAUST DUCT UP
RETURN OR EXHAUST DUCT DOWN
DUCT RISE
DUCT DOWN
VOLUME DAMPER (MANUAL UNLESS INDICATED A.V.D.)
TRANSITION
DUCT TAKE-OFF (SEE SPEC. PERTAINING TO DEFLECTROLS)
TRANSITION (FLAT ON TOP)
TRANSITION (FLAT ON BOTTOM)
TRANSITION (TOP OR BOTTOM ONLY)
SUPPLY CEILING DIFFUSER
RETURN OR EXHAUST CEILING GRILLE
SIDEWALL SUPPLY
SIDEWALL RETURN
FLEXIBLE CONNECTION (DUCT)
RELIEF AIR SUPPLY TO TOILET
DUCT SPLIT WITH SPLITTER DAMPER
FLEX. DUCT WITH SCREW ON COLLAR, TAKE-OFF
DUCT WITH DUCT LINER
SQUARE ELBOW WITH TURNING VANES
RADIUS ELBOW (SEE SPECS. PERTAINING TO TURNING VANES)
AUTOMATIC VOLUME DAMPER
DN
R
12\10 SPLIT
OR
OR
SCD
FOB
T OR B
RAS
AVD
FD/SCD
FD
SMOKE CONTROL DAMPER
COMBINATION FIRE/SMOKE CONTROL DAMPER
FIRE DAMPER (FD)
FIRE DAMPER
FILE PATH:
P:\26011\26011mb10.dgn
DATE PLOTTED
DGN FILE
30-SEP-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26011\26011mb10.dgn
AS SHOWN
26011
WSH
LTF
WSH
09.29.2026
T
COA Expiration: 6.30.2028
COA#PEF000774
NBP Engineers, Inc.
F o rt V a ll e y
G e o rg ia
F V S
U B o n d H u n t
A H
U U p g ra d e s
ELEVATOR
MB10
SCALE:
= 1'-0
4 0 2 4 8
EXISTING TO REMAIN
DEMOLITION
LINE LEGEND
DEMOLITION - HVAC
FLOOR PLAN -
PARTIAL BASEMENT
LARGE SCALE -
BOND BUILDING -
BOND BUILDING - LARGE SCALE - PENTHOUSE PLAN - DEMOLITION - HVAC
S-1
R-132/16
E-1
AP
AP
4"
5"
GRATES IN FLOOR (4)
EXISTING 24"x60" RA
SD
SD
ACP-LCP-2
66"x84" RELIEF DAMPER
REMOVE EXISTING
RA DAMPER
66"x84"
EXISTING
REMOVE
8"W CONCRETE CURB
REMOVE EXISTING
TO REMAIN
EA LOUVER
EXISTING 36/32
TO REMAIN
EA LOUVER
EXISTING 24/24
TO REMAIN
EA LOUVER
EXISTING 32/16
MOUNTED ON WALL TO REMAIN
EXISTING AFTER COOLER
TO REMAIN
AIR COMPRESSOR
EXISTING CONTROL
FLOOR
FROM GROUND
EXISTING 36/24
INSULATION (TYP)
APPARATUS CASING
REMOVE EXISTING
FLUE TO REMAIN
12" FABRICATED
COOLING COILS, 108"x33" (3)
REMOVE EXISTING
TO REMAIN
100"x44" DN
SCALE:
= 1'-0
4 0 2 4 8
A
A
EXISTING
REMOVE
INERTIA BASE
8'-0"x7'-0"x 8" THICK
REMOVE EXISTING
8'-0"x7'-0"x8" THICK INERTIA BASE
REMOVE EXISTING
EXISTING
REMOVE
S-1
EXISTING
REMOVE
R-1
84"x66" RELIEF DAMPER
REMOVE EXISTING
B B
S-1EXISTING
REMOVE
INERTIA BASE
8'-0"x7'-0"x 8" THICK
REMOVE EXISTING
72"x60" MAX. OA DAMPER
72"x12" MIN .OA DAMPER;
REMOVE EXISTING
120"x20" OA LOUVER
REMOVE EXISTING
R E
M O
V
X
IS
T
IN
G
R O
L L
F
IL
T E
R
8'-0"x7'-0"x8" THICK INERTIA BASE
REMOVE EXISTING
8" WIDE x 48" HIGH CONCRETE PIERS
REMOVE EXISTING
& CASING INSULATION (TYP)
APPARATUS CASING
REMOVE EXISTING RA DAMPER
84"x66"
EXISTING
REMOVE
CEILING INSULATION (TYP)
MECH. RM.
REMOVE EXISTING CONCRETE CURBS
8'-0"x7'-0"x8" THICK INERTIA BASE
REMOVE EXISTING
& CASING INSULATION (TYP)
APPARATUS CASING
REMOVE EXISTING
SD
108"x33" (3)
COOLING COILS,
REMOVE EXISTING
CEILING INSULATION (TYP)
MECH. RM.
72"x60" MAX. OA DAMPER
72"x12" MIN .OA DAMPER;
REMOVE EXISTING
INSULATION (TYP)
APPARATUS CASING
REMOVE EXISTING
44"x100"
ROLL FILTER
REMOVE EXISTING
EXISTING FLOOR DRAIN
BOND BUILDING - LARGE SCALE - SECTION A-A - DEMOLITION - HVAC
SCALE:
= 1'-0
4 0 2 4 8
BOND BUILDING - LARGE SCALE - SECTION B-B - DEMOLITION - HVAC
INSULATION (TYP)
APPARATUS CASING
REMOVE EXISTING
STARTER TO REMAIN
EXISTING E-1
EXISTING VFD'S
REMOVE
EXISTING AP
EXISTING FD
FOR FAN, S-1
SHUT-DOWN SWITCH
REMOVE EMERGENCY
REMOVE
3"W-BF
4"W-BF
FILE PATH:
P:\26011\26011mb20.dgn
DATE PLOTTED
DGN FILE
30-SEP-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26011\26011mb20.dgn
AS SHOWN
26011
WSH
LTF
WSH
09.29.2026
T
COA Expiration: 6.30.2028
COA#PEF000774
NBP Engineers, Inc.
F o rt V a ll e y
G e o rg ia
F V S
U B o n d H u n t
A H
U U p g ra d e s
ELEVATOR
32/16
E-1
AP
AP
GRATES IN FLOOR (4)
EXISTING 24"x60" RA
TO REMAIN
EA LOUVER
EXISTING 36/32
TO REMAIN
EA LOUVER
EXISTING 24/24
TO REMAIN
EA LOUVER
EXISTING 32/16
FLOOR
FROM GROUND
EXISTING 36/24
FLUE TO REMAIN
12" FABRICATED
TO REMAIN
100"x44" DN
CEILING INSULATION (TYP)
MECH. RM.
44"x100"
EXISTING FLOOR DRAINSTARTER TO REMAIN
EXISTING E-1
EXISTING AP
EXISTING FD
3"W-BF
4"W-BF
MB20
SCALE:
= 1'-0
4 0 2 4 8
SCALE:
= 1'-0
4 0 2 4 8
BOND BUILDING - LARGE SCALE - PENTHOUSE PLAN - NEW WORK - HVAC BOND BUILDING - LARGE SCALE - SECTION B-B - NEW WORK - HVAC
NEW WORK - HVAC
PENTHOUSE PLANS -
LARGE SCALE -
BOND BUILDING -
100/44
AH-B-1NEW
CONCRETE PAD
COIL PULL
IN EXISTING WALL OPENING
OA INTAKE LOUVER
NEW 120"x120"
PLENUM ON BACK OF NEW LOUVER
PROVIDE FULLSIZE 18" DEEP
MIXING BOX
F
IL
T E
R
C O
O L
C
IL
F A
N
R A
Y
D
IS
C H
A R
G E
P
L E
N U
M
C H S
CHR
CHS
SD
122"x42" RA AVD
MIN. OA AVD
84/48 MAX. OA AVD
B
B
84/48
OA DUCT
24/12
AH-B-1NEW
CONCRETE PAD
D
IS
C H
A R
G E
P
L E
N U
M
F
R A
Y
C O
O L
IL
F
IL
T E
R
M
IX
X
IN EXISTING WALL OPENING
OA INTAKE LOUVER
NEW 120"x120"
PLENUM ON BACK OF NEW LOUVER
PROVIDE FULLSIZE 18" DEEP
SD
44/100
12/24
AFMS
AFMS
48/84
84/48 MAX. OA AVD
CHRCHS
SENSIBLETOTALMARK
NOTES:
MBH MBHDB WB DB WB
( F) ( F) ( F) ( F)
REMARKS
AH-B-1
TYPE
VAV
COOLING COIL
TOTAL
CFM
MIN. OA
CFM
ASSUMED
(IN.)
ESP
TSP (IN.)
MAX.
MOTOR
HP
FAN
TYPE WHEEL
MIN.
SIZE
CFM
COIL
38,000 2.0 4.0 7.5 24.5
ENTERING AIR LEAVING AIR
MAX. APDMIN. FACE
AREA
(FT )
1.25
( F) ( F)
EWT LWT
46 58
GPM
WPD
MAX.
(FT)
AIR FLOW
2,200 PLENUM 2 38,000 84 67 55 53 1,476 1,196 76
(IN.)
AIR HANDLING UNIT SCHEDULE
2 FAN ARRAY WITH SIX (6) FANS.
SIX (6) MOTORS @ 7.5 HP EACH. PROVIDE WALL MOUNTED VFDS. EACH VFD TO SERVE THREE (3) FAN MOTORS.
NEW VFD'S
6"
6"
6"
ACP
LINE LEGEND
POINT OF CONNECTION
EXISTING TO REMAIN
NEW WORK
122"x42" RA AVD
AP
AP
OA AVD
MIN.
NEW 3"FD
NEW 3"W-BF
CDEF
A R
E A
W A
Y
B
C O
R R
ID
O R
B
R O
O M
M A
C H
IN
E
E L
E V
A T
O R
SEAL
SCALE:
FILE PATH:
P:\26011\26011mh10.dgn
DATE PLOTTED
DGN FILE
30-SEP-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26011\26011mh10.dgn
AS SHOWN
26011
WSH
LTF
WSH
09.29.2026
T
COA Expiration: 6.30.2028
COA#PEF000774
NBP Engineers, Inc.
F o rt V a ll e y
G e o rg ia
F V S
U B o n d H u n t
A H
U U p g ra d e s
MH10
SCALE:
= 1'-0
OA DAMPER; 9500|
EXISTING 24"x60"
38/12
EF-1 1
T
EF-10
12/12 500|
T
HW
6" CHR
6" CHS
C O
O L
IL
C H S
C H
R
C O
O L
IL
H W
R
H W
S
H W
S
3" HWR
3" HWS
HWR
HWS
ƒ"
4 0 2 4 8
EF-1 1
MVD
w/FD
14"x14"RAO
EXISTING
EXISTING
HP-1
EXISTING
UH-1
EXISTING
EXISTING
T
N
DRAIN
EXISTING
& SADDLE SUPPORT
CONCRETE PAD
EXISTING 12"x12"
SD
EXISTING
ACP
UH-1
EXISTING BOILER
EXISTING HOSE BIB
WATER TREATMENT
EXISTING CONTROL PANEL CHEMICAL
TREATMENT TANKS
EXISTING CHEMICAL WATER
EXISTING PRV DRAIN LINE
EXISTING MAKE-UP WATER STATION LINE
AIR LOUVER
40"X40" COMBUSTION
EXISTING
EXISTING TO REMAIN
DEMOLITION
LINE LEGEND
EXISTING STARTERS
CT-1 & EF-1 1
F A
C P
F
HG
SWITCHBOARD"SB"
WATER EXPANSION TANK
EXISTING CHILLED
SUPPORT BEAMS B.E. 10'-8"
EXISTING GRATING
C H S
C H
R
6"
SMOKE DAMPER
96"x96" ISOLATION
EXISTING
6"
SLEEVE SEALS
MECHANICAL
EXISTING
WALL SUPPORT
EXISTING
CP-HL-1
6"
INLINE AIR PURGER
EXISTING
CHEMICAL FEEDER
EXISTING BYPASS
EXISTING
T
EF-10
EXISTING
BP
SWITCH-EF-1 1
EXISTING WALL PURGE
INTAKE LOUVER
EXISTING OA
ISOLATION DAMPER
EXISTING SMOKE
SF-1
RF-1
VFD-1
VFD-2
CONCRETE PAD
EXISTING
AIR COMPRESSOR
EXISTING CONTROL
TO REMAIN
CONCRETE PAD
EXISTING
DEMOLITION - HVAC
FLOOR PLAN -
PARTIAL BASEMENT
LARGE SCALE -
HUNT LIBRARY -HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - DEMOLITION - HVAC
EXISTING
REMOVE
EXISTING
REMOVE
EXISTING
REMOVE
EXISTING
REMOVE
TO REMAIN
EXISTING ACP
CDEF
A R
E A
W A
Y
B
C O
R R
ID
O R
B
R O
O M
M A
C H
IN
E
E L
E V
A T
O R
SEAL
SCALE:
FILE PATH:
P:\26011\26011mh20.dgn
DATE PLOTTED
DGN FILE
30-SEP-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26011\26011mh20.dgn
AS SHOWN
26011
WSH
LTF
WSH
09.29.2026
T
COA Expiration: 6.30.2028
COA#PEF000774
NBP Engineers, Inc.
F o rt V a ll e y
G e o rg ia
F V S
U B o n d H u n t
A H
U U p g ra d e s
OA DAMPER; 9500|
EXISTING 24"x60"
38/12
EF-1 1
T
EF-10
12/12 500|
T
HW
6" CHR
6" CHS
C O
O L
IL
C H S
C H
R
C O
O L
IL
H W
R
H W
S
H W
S
3" HWR
3" HWS
HWR
HWS
ƒ"
EF-1 1
MVD
w/FD
14"x14"RAO
EXISTING
EXISTING
HP-1
EXISTING
UH-1
EXISTING
EXISTING
T
DRAIN
EXISTING
& SADDLE SUPPORT
CONCRETE PAD
EXISTING 12"x12"
SD
EXISTING
ACP
UH-1
EXISTING BOILER
EXISTING HOSE BIB
WATER TREATMENT
EXISTING CONTROL PANEL CHEMICAL
TREATMENT TANKS
EXISTING CHEMICAL WATER
EXISTING PRV DRAIN LINE
EXISTING MAKE-UP WATER STATION LINE
AIR LOUVER
40"X40" COMBUSTION
EXISTING
EXISTING STARTERS
CT-1 & EF-1 1
F A
C P
F
HG
SWITCHBOARD"SB"
WATER EXPANSION TANK
EXISTING CHILLED
SUPPORT BEAMS B.E. 10'-8"
EXISTING GRATING
C H S
C H
R
6"
SMOKE DAMPER
96"x96" ISOLATION
EXISTING
6"
SLEEVE SEALS
MECHANICAL
EXISTING
WALL SUPPORT
EXISTING
CP-HL-1
6"
INLINE AIR PURGER
EXISTING
CHEMICAL FEEDER
EXISTING BYPASS
EXISTING
T
EF-10
EXISTING
BP
SWITCH-EF-1 1
EXISTING WALL PURGE
INTAKE LOUVER
EXISTING OA
CONCRETE PAD
EXISTING
AIR COMPRESSOR
EXISTING CONTROL
TO REMAIN
CONCRETE PAD
EXISTING
TO REMAIN
EXISTING ACP
MH20
SCALE:
= 1'-0
4 0 2 4 8
N
LINE LEGEND
POINT OF CONNECTION
EXISTING TO REMAIN
NEW WORK
HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - NEW WORK - HVAC
NEW WORK - HVAC
FLOOR PLAN -
PARTIAL BASEMENT
LARGE SCALE -
HUNT LIBRARY -
VFD VFD
EXISTING CASING WALL
NEW ACCESS DOOR IN
NEW CONCRETE PAD
RF-1
VFDVFD
SF-1
NEW NEW
NEW NEW
NEW CONCRETE PAD
(TYPICAL)
CONCRETE CURB
CASING WALL
NEW APPARATUS
CASING WALL
NEW APPARATUS
TYPE CFM
S.P.
IN W.G.
MARK
MAX.
RPM
REMARKS
FAN SCHEDULE
MIN.
FAN DIA.
(IN)
MOTOR
HP
DRIVE
NOTES:
1SF-1
RF-1
FAN ARRAY: EIGHT (8) FANS; 10 HP EACH.
FAN ARRAY: EIGHT (8) FANS; 3 HP EACH.
FAN ARRAY
FAN ARRAY
65,000
55,000
5.0
0.75
DIRECT
DIRECT2
FILE PATH:
P:\26011\26011m40.dgn
DATE PLOTTED
DGN FILE
30-SEP-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26011\26011m40.dgn
AS SHOWN
26011
WSH
LTF
WSH
09.29.2026
T
COA Expiration: 6.30.2028
COA#PEF000774
NBP Engineers, Inc.
F o rt V a ll e y
G e o rg ia
F V S
U B o n d H u n t
A H
U U p g ra d e s
M40
NOT TO SCALE
OUTPUTS INPUTS SOFTWARE
DIGITAL ANALOG ANALOG ALARM DDCDIGITAL ENERGY MGMT. LOGS
DDC PANELS
INPUT/OUTPUT
SUMMARIES
ACP
PRIMARY AIR FLOW
PERCENTAGE DESIGN FLOW-HEATING
PERCENTAGE DESIGN FLOW-COOLING
TAG
OA 1
FAR
TT 1
TT 2
TT 4
SPS H
SPS 1
TUC-XX
TUC-XX
TUC-XX
ZONE-SPACE TEMP.
SAT
LL
HT
CC-L.A.T.
L.L.-TEMP.
RA 1
T-XX
CC CONTROL VALVE
TT 5
VLV 1
HIGH LIMIT SPS
VAV SYSTEM
AFMS
OA 2
ELECTRIC HEATER - SCR
DP1 BUILDING PRESSURE
1. FAILURE MODES:
O - OPEN OR ON
C - CLOSE OR OFF
L - LAST COMMAND
2. WHERE FAILURE MODE IS INDICATED, THE INDICATED POSITION SHALL OCCUR ON INTERRUPTION OF
NOTES:
ELECTRIC POWER TO THE DDC PANEL.
S Y
S T
M
A P
H
IC
D
IS
P L
A Y
S T
A R
T
S T
O P
E N
A B
L E
D
IS
A B
L E
O P
E N
C L
O S
E
S T
A R
T
S T
P
K E
U P
S E
T P
O
T
J
U S
T
D
N T
R O
L
D
IF
F E
R E
N T
IA
L
P
R E S
S U
R E
P R
E S
S U
R E
S
W
IT
C H
A U
X
IL
IA
Y
N T
A C
T
A L
A
N T
A C
T
T E
M P
E R
A T
U R
E
R E
L A
T
IV
U
M
ID
IT
Y
P R
E S
S U
R E
H
IG
H
L
W
L
IM
IT
R
T A
L
IZ
A T
IO
N
P R
O P
O R
T
IO
N A
L
P R
O P
IN
T E
G R
A L
T
IM
E
S
C H
E D
U L
E
S
S
O P
T
IM
A R
T
S T
O P
D A
Y
N
IG
T B
A C
K
D E
M A
IT
C Y
C L
E
R E S
T
IM
IZ
A T
IO
N
E C
O N
O M
IZ
E R
F A
IL
U
D E (S
T E S
A
N D
N O
T E S
C U
R R
E
L A
Y
D R
IV
E
S
T A
T U
S
S P
E E
D
IN
D
IC
A T
IO
N
S P
E
N T
R O
L
E
W
IT
C H
C O
IR
F
O W
C A
L C
U L
A T
IN
T
P O
S
IT
IO
N
IN
D
IC
A T
IO
N
O P
E N
C L
O S
S
IT
IO
N
T R
E
G
S T
A T
U S
O
C
C
C
L
C
R
TT
FAR
CC
VLV
TTLL
TT
SPS
FIL
SPS
H
TUC
T-X
SAT
TU-X
A1
A1
A1D1
A1A1 D1
A0 A1
A1
A0 A1
SAF
VFD
VFD
FAR
A1D0 A0 D1
MCP
TUC
T-X
SAT
TU-X
A1
OA
A0 A1
A0 A1
RA
AFMS
TT
A1
OA
T
T
CHR
CHS
COND.
ZONE
COND.
ZONE
OA
MAX. OAD
MIN. OAD
HT
TRANSFER
DUCT
A1
DP
A1
TO ERU-1
TU-X
FP-X
FLOW DIAGRAM - VAV SYSTEM
AH AH
OA
OA
SA
SD
MIN. OA DAMPER
MAX/ OA DAMPER
MIN/ OA AFMS
RA DAMPER
RA TEMP.
RA-RH
RA
SA-TEMP.
SA-SPS
SA DAMPER ACTUATOR
SA TEMP. TO ZONE
MA TEMP.
FA RELAY
SA FAN ARRAY-VFD
AH-B-1 VAV SYSTEM
BOND AIR HANDLER
VFD 1, 2
EXISTING AIR TERMINAL UNITS (TU) (FP) FOR REFERENCE ONLY
A1
A1A0
A0 A1
A1
H W
S
H W
R
H W
S
H W
R
AH-B-1
R
VFD
FAR
A1D0 A0 D1
MCP
SAF
VFD
FAN ARRAY
VAV SYSTEM
FLOW DIAGRAM -
FILE PATH:
P:\26011\26011m50.dgn
DATE PLOTTED
DGN FILE
30-SEP-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26011\26011m50.dgn
AS SHOWN
26011
WSH
LTF
WSH
09.29.2026
T
COA Expiration: 6.30.2028
COA#PEF000774
NBP Engineers, Inc.
F o rt V a ll e y
G e o rg ia
F V S
U B o n d H u n t
A H
U U p g ra d e s
M50
HVAC
DETAILS -
TYPICAL DRAIN VALVE CONNECTION
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
ƒ" BALL VALVE
ADAPTER TO ƒ" HOSE THREAD
PROVIDE HOSE CAP NUT
NOTES:
DRAIN ALL LOW POINTS AS INDICATED ABOVE.1.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS
AND/OR PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
NOT TO SCALE
WELDED PIPING
ELEVATION
THREADED PIPING
ELEVATION
A
B
DRAIN LINE SHALL BE
AT LEAST THE SAME
SIZE AS THE NIPPLE
ON THE DRAIN PAN
DRAIN
PAN
1"
UNIT TYPE
WHERE X = STATIC PRESSURE IN PAN IN INCHES - H2O
A B
ADAPTER
DRAW THRU 2" PLUS X X
AIR HANDLING UNIT DRAIN TRAP
CLEAN OUT
SEDIMENT BUCKET
LOOSE CAP
GRATE
REMOVABLE
FITTING
LOOSE
THIS SIDE
FLOOR DRAIN (REFER TO DIVISION 220000)
FLOOR
PER FOOT SLOPE
MINIMUM 1/8 INCH
SLOPE TO DRAIN AT
1" (MIN)
DRAIN PIPE AS SPECIFIED
2" MAX.
REQUIRED BY CONDITIONS
DRAIN TERMINATION AS
BLOW THRU 1" MIN. 1.5"X
COIL
AIR FLOW
UNION
W\HOSE ADAPTOR
•" GATE VALVE
CONTROL
VALVE
N.C.
N.O.
C.
SUP
PL
Y
RET
URN
VALVE COEFFICIENTS
SYSTEM Cv RUNOUT SIZE
CIRCUIT SETTER
BALANCE VALVE (TYP)
TEST PLUG
BUTTERFLY VALVE
BUTTERFLY VALVE
HANGER ROD - SEE SPECIFICATIONS
SECTION OF RIGID INSULATION
SPECIFIED INSULATION
PIPE
• ROUND BEARING PLATE
PLATE WASHER
CUT ROD ABOVE ANGLE LEG
1" MIN.
TRAPEZE HANGER
LONG LEG VERTICAL
SEE SPECIFICATIONS
DOUBLE HEX NUTS
TRAPEZE PIPE HANGER
NOT TO SCALE
BRANCH CIRCUIT FROM
PANELBOARD,SWITCHGEAR,OR MCC
(2600)
SYSTEM SHOWN IN NORMAL (VFD NOT BYPASSED)
NUMBERS IN PARENTHESES INDICATE DIVISION
UNDER WHICH WORK OR EQUIPMENT IS SPECIFIED.
NOT TO SCALE
MODE, MOTOR RUNNING.
OVERLOAD
CIRCUIT
BREAKER
VFD SINGLE LINE DIAGRAM
VFD PACKAGE
RECTIFIER AND
INVERTER
NOTES:(THIS DETAIL ONLY)
(2600)
(2300)
MOTOR (2300)
NOT TO SCALE
NOT TO SCALE
(PROVIDE M.A.V. IF COIL IS NOT SELF VENTING)
(PROVIDE CONNECTIONS FOR NUMBER OF STACKED COILS PROVIDED WITH UNIT)
LOUVER
WALL MOUNTED LOUVER WITH PLENUM
COUNTER
FLASHING
20 GAUGE SLEEVE
16"MIN.
REFER TO ARCHITECTURAL
FOR STRUCTURE MATERIALS
SUB FRAME
IN BLOCK WALLS,
USE LINTELBLOCK
ON HEAD AND SILL
PROVIDE MINIMUM 16 INCH PLENUM BEHIND LOUVER
NOT TO SCALE
COOLING COIL PIPING
FILE PATH:
P:\26011\26011e00.dgn
DATE PLOTTED
DGN FILE
30-SEP-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26011\26011e00.dgn
AS SHOWN
26011
09.29.2026
TWT
BCO
TWT
T
COA Expiration: 6.30.2028
COA#PEF000774
NBP Engineers, Inc.
F o rt V a ll e y
G e o rg ia
F V S
U B o n d H u n t
A H
U U p g ra d e s
E00
CT
TRACK LIGHTS: QUANTITY OF HEADS AS SHOWN EMERGENCY BATTERY PACK-CEILING
EMERGENCY BATTERY PACK-WALL
PANELBOARD-250 VAC OR LESS
SURFACE MOUNTED
PANELBOARD-250 VAC OR LESS
RECESSED
PANELBOARD-OVER 250 VAC
SURFACE MOUNTED
PANELBOARD-OVER 250 VAC
RECESSED
CABLE TRAY
BACKBOARD
CONNECTION TO EQUIPMENT
CAP
CONDUIT DOWN
CONDUIT UP
J
F
BT
C
C
BR
U
SP
DP
PE
M
ICM
S
V
S
IC
MM
MC
LIGHTING FIXTURES (SYMBOLS VARY BASED ON FIXTURES TYPE)
LIGHTING CONTROL
RECEPTACLES
CIRCUITS
GENERAL EQUIPMENT
FIRE PROTECTION EQUIPMENT
COMMUNICATIONS
T
JJ
I
UI
I
ELECTRICAL LEGEND
TV
B
K
LED ON "NORMAL" POWER
CEILING MOUNTED FIXTURE
WALL MOUNTED FIXTURE
EXIT LIGHT (ARROWS AS SHOWN)
LIFE SAFETY EGRESS FIXTURE
CEILING MOUNTED ULTRASONIC OCCUPANCY
SENSOR AND RELAY
CEILING/WALL MOUNTED INFRARED OCCUPANCY
SENSOR AND RELAY
CEILING MOUNTED COMBINATION INFRARED/
ULTRASONIC OCCUPANCY SENSOR AND RELAY -
SWITCHING PHOTOCELL (INTERIOR TYPE) F.C. NOTED
DIMMING PHOTOCELL (INTERIOR TYPE)
EXTERIOR TYPE PHOTO SWITCH
LOW VOLTAGE OVERRIDE SWITCH
INFRARED OCCUPANCY SENSOR
WALL MOUNTED SWITCH
"P" INDICATES PILOT LIGHT
KEYED SWITCH
DIMMER SWITCH
FOUR WAY SWITCH
THREE WAY SWITCH
SINGLE POLE SWITCH
DUPLEX RECEPTACLE - NORMAL
QUAD - NORMAL
GFCI DUPLEX RECEPTACLE - NORMAL
GFCI QUAD - NORMAL
FLOOR DUPLEX RECEPTACLE - NORMAL
FLOOR QUAD - NORMAL
CEILING DUPLEX RECEPTACLE - NORMAL CLOCK OUTLET
WALL/CEILING RACEWAY
CEILING SPECIAL - TYPE NOTED OR SHOWN
SPECIAL - TYPE NOTED OR SHOWN
HORIZONTALLY MOUNTED DUPLEX RECEPTACLE
WEATHER PROOF RECEPTACLE (GFCI)
ELECTRIC WATER COOLER RECEPTACLE(GFCI)
CONDUIT CONCEALED IN CEILING OR WALL
CONDUIT IN GROUND, SLAB, OR UNDER FLOOR
FLEXIBLE RACEWAY
RACEWAY EXPOSED
TRANSFORMER
FRAME AMPS/POLES/NEMA TYPE
FUSE PER MANUFACTURERS RECOMMENDATIONS
ENCLOSED BREAKER-RECESSED IN WALL
ENCLOSED CIRCUIT BREAKER
EMERGENCY PUSHBUTTON
COMBINATION STARTER AND DISCONNECT
EXHAUST FAN
MANUAL STARTER AND MOTOR RATED SWITCH
MOTOR
JUNCTION BOX - WALL/CEILING/FLOOR
SURGE SUPPRESSOR
VOICE OUTLET, QUANTITY OF JACKS AS NOTED
DATA OUTLET, QUANTITY OF JACKS AS NOTED
COMBINATION VOICE/DATA OUTLET, QUANTITY OF
VOICE/DATA JACKS AS NOTED
FLOOR VOICE OUTLET, QUANTITY OF JACKS
AS NOTED
FLOOR DATA OUTLET, QUANTITY OF JACKS
AS NOTED
FLOOR COMBINATION VOICE/DATA OUTLET,
QUANTITY OF JACKS AS NOTED
MASTER CLOCK
INTERCOM MASTER STATION
INTERCOM CALL-IN STATION
WALL MOUNTED VOLUME CONTROL
BOX, STUB-UP, AND MODULAR PLATE W/ BLANKS
TELEVISION OUTLET
SPEAKER: CEILING/WALL
MICROPHONE: FLOOR/WALL
FIBER OUTLET
FACP
FAA
WF
VS
DH
SMOKE DETECTOR/SENSOR - BEAM RECEIVER
SMOKE DETECTOR/SENSOR - BEAM TRANSMITTER
SPEAKER/VISUAL ALARM: CEILING/WALL
VISUAL ALARM: CEILING/WALL
AUDIO/VISUAL ALARM: CEILING/WALL
MANUAL PULL STATION
FIRE ALARM ANNUNCIATOR
FIRE ALARM PANEL
DUCT MOUNTED SMOKE DETECTOR
SMOKE DETECTOR: CEILING / WALL
HEAT DETECTOR: CEILING / WALL
WATER FLOW SWITCH
WATER TAMPER SWITCH
DOOR HOLDER
FIREMAN'S PHONE OUTLET
EWC
WP
H
D
P
I
L
TWO ZONE LOW VOLTAGE SWITCHL2
VACANCY AUTO SHUT OFF
FOUR ZONE LOW VOLTAGE SWITCHL4
DUPLEX RECEPTACLE WITH INTEGRAL USBUSB
TV DUPLEX RECEPTACLETV
AC
ABOVE COUNTER DUPLEX RECEPTACLE (COORDINATE
HEIGHT WITH ARCHITECT)
J-HOOK
CABLE TRAY
DUPLEX RECEPTACLE MOUNTED IN RACEWAYR
R DATA OUTLET MOUNTED IN RACEWAY
DUPLEX RECEPTACLE - TAMPER PROOFT
DUPLEX RECEPTACLE - GENERATOR CIRCUIT, RED IN COLOR
QUAD - GENERATOR CIRCUIT, RED IN COLOR
SINGLE ZONE LOW VOLTAGE SWITCHL1
HOMERUN - ONE ARROW PER CIRCUIT
DISCONNECT SWITCH: "F" IF FUSED
F
ELECTRICAL
LEGEND -
FILE PATH:
P:\26011\26011eb20.dgn
DATE PLOTTED
DGN FILE
30-SEP-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26011\26011eb20.dgn
AS SHOWN
26011
09.29.2026
TWT
BCO
TWT
T
COA Expiration: 6.30.2028
COA#PEF000774
NBP Engineers, Inc.
F o rt V a ll e y
G e o rg ia
F V S
U B o n d H u n t
A H
U U p g ra d e s
ELEVATOR ELEVATOR
E-1
EXISTING
GRATES IN FLOOR (4)
EXISTING 24"x60" RA
PHA
J
DOWN
PHA-1
PHA-2
1•" C FEEDER DOWN
AC COMPRESSOR
•/460/3 ƒ/460/3 (E-1)
AFTER COOLER
/120/1
J
DOWN
STARTER TO REMAIN
EXISTING E-1
AH-B-1NEW
NEW VFD'S
ACP
EB20
SCALE:
= 1'-0
4 0 2 4 8
SCALE:
= 1'-0
4 0 2 4 8
BOND BUILDING - LARGE SCALE - PENTHOUSE PLAN - NEW WORK - ELEC
E-1
ACP-LCP-2
EXISTING
S-1
EXISTING
GRATES IN FLOOR (4)
EXISTING 24"x60" RA
PHA
TO REMAIN
BOND BUILDING - LARGE SCALE - PENTHOUSE PLAN - DEMOLITION - ELEC
NEW WORK - ELEC
DEMOLITION &
PENTHOUSE PLANS -
LARGE SCALE -
BOND BUILDING -
J
DOWN
PHA-5
PHA-1
PHA-8
PHA-2
LB-23
1•" C
40/460/3 (S-1)
30/1
FEEDER DOWN
AC COMPRESSOR
•/460/3 ƒ/460/3 (E-1)
AFTER COOLER
/120/1
J
‚/120/1 ROLLER FILTER
100/3
3#6-1"C
DOWN
3#10-3/4"C
15/460/3 (R-1)
STARTER TO REMAIN
EXISTING E-1
EXISTING VFD'S
REMOVE
FOR FAN, S-1, TO BE REMOVED
SHUT-DOWN SWITCH
EXISTING EMERGENCY
TO BE REMOVED
NEW
NOTES:(THIS SHEET ONLY)
LOCATED IN THIS PENTHOUSE. REMOVE THE EXISTING 100A/3P CIRCUIT BREAKER.
REMOVE EXISTING VFD AND CONDUCTORS/CONDUIT BACK TO SERVING PANEL PHA
LOCATED IN THIS PENTHOUSE. REMOVE THE EXISTING 50A/3P CIRCUIT BREAKER.
REMOVE EXISTING VFD AND CONDUCTORS/CONDUIT BACK TO SERVING PANEL PHA
120 VOLT CIRCUIT TO NEW ACP SHOWN BY NOTE 4.
EXISTING AUTOMATED CONTROL PANEL (ACP) BEING REMOVED. EXTEND EXISTING
3#6 AWG, 1#10G, 1"C.
THE MOTOR CIRCUIT PROTECTOR PANEL. FOR EACH 50 AMP CIRCUIT PROVIDE
PANEL AIC RATING. MAKE ALL FINAL CONNECTIONS THROUGH THE VFDS AND
NEW 50A/3P CIRCUIT BREAKERS IN EXISTING PANEL PHA, MATCHING EXISTING
SPLIT INTO TWO VFD CIRCUITS, ONE FOR BOTH SETS OF 3 FANS. PROVIDE TWO
PROTECTOR PANEL WITH INDIVIDUAL MOTOR PROTECTORS. THE FANS WILL BE
RETURN FANS. THE AHU MANUFACTURER WILL PROVIDE A MOTOR CIRCUIT
THE NEW AIR HANDLER WILL HAVE A FAN ARRAY WITH 6 SUPPLY FANS, BUT NO
IN EXISTING PATCH PANEL. NEW DATA CABLE SHALL BE PLENUM RATED.
CAT 6 DATA DROP AND ROUTE BACK TO NEAREST IDF OR BUILDING MDF. TERMINATE
NEW ACP LOCATION. MAKE ALL FINAL POWER CONNECTIONS. PROVIDE ONE NEW
BUILDING FIRE ALARM SYSTEM. PROVIDE FIRE ALARM RELAY TO SHUT DOWN AHU.
PROVIDE NEW DUCT MOUNTED SMOKE DETECTOR AND CONNECT TO EXISTING
RATING. MAKE ALL FINAL CONNECTIONS.
SPARE CAPACITY, PROVIDE A NEW 20A/1P CIRCUIT BREAKER MATCHING PANEL AIC
AND ACCESSORIES. ROUTE 3#12 AWG,•"C TO NEAREST 120 VOLT PANELBOARD WITH
PROVIDE DEDICATED 20 AMP, 120 VOLT CIRCUIT FOR NEW AIR HANDLING UNIT LIGHTS
TO NEW LIGHTS SHOWN ON NEW WORK PLAN.
SHALL REMAIN AND BE REUSED. EXISTING CIRCUITS SHALL REMAIN AND BE EXTENDED
REMOVE ALL OF THE EXISTING LIGHT FIXTURES IN THESE SPACES. EXISTING SWITCHES
THE SPACE.
THESE LIGHTS SHOULD BE SHIFTED AROUND AS REQUIRED TO ADEQUATELY LIGHT
PROVIDE ACUITY LIGHTING LED STRIP LIGHT MODEL CSS-L48-5000LM-MVOLT-40K.
PROVIDE WITH INTEGRAL BATTERY FOR EMERGENCY EGRESS LIGHTING.
8 8
J
9 10
9 9
CDEF
A R
E A
W A
Y
B
C O
R R
ID
O R
B
R O
O M
M A
C H
IN
E
E L
E V
A T
O R
SEAL
SCALE:
FILE PATH:
P:\26011\26011eh10.dgn
DATE PLOTTED
DGN FILE
30-SEP-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26011\26011eh10.dgn
AS SHOWN
26011
09.29.2026
TWT
BCO
TWT
T
COA Expiration: 6.30.2028
COA#PEF000774
NBP Engineers, Inc.
F o rt V a ll e y
G e o rg ia
F V S
U B o n d H u n t
A H
U U p g ra d e s
EH10
SCALE:
= 1'-0
EF-1 1
EF-10
HW
4 0 2 4 8
EXISTING
HP-1
EXISTING
UH-1 EXISTING
EXISTING
N
& SADDLE SUPPORT
CONCRETE PAD
EXISTING 12"x12"
EXISTING
ACP
EXISTING BOILER
WATER TREATMENT
EXISTING CONTROL PANEL CHEMICAL
TREATMENT TANKS
EXISTING CHEMICAL WATER
AIR LOUVER
40"X40" COMBUSTION
EXISTING
F A
C P
F
HG
SWITCHBOARD"SB"
WATER EXPANSION TANK
EXISTING CHILLED
S
ELEVATOR MOTOR
EXISTING SERVICE
100A/3P
SUPPORT BEAMS B.E. 10'-8"
EXISTING GRATING
EXISTING STARTERS
CT-1 & EF-1 1
CHEMICAL FEEDER
EXISTING BYPASS
CP-HL-1
EXISTING
OA DAMPER; 9500|
EXISTING 24"x60"
INTAKE LOUVER
EXISTING OA
EXISTING
BP
AIR COMPRESSOR
EXISTING CONTROL
SWITCH-EF-1 1
EXISTING WALL PURGE
HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - DEMOLITION - ELEC
DEMOLITION - ELEC
FLOOR PLAN -
PARTIAL BASEMENT
LARGE SCALE -
HUNT LIBRARY -
SF-1
RF-1
VFD-1
VFD-2
EXISTING
REMOVE
EXISTING
REMOVE
EXISTING
REMOVE
EXISTING
REMOVE
NOTES:(THIS SHEET ONLY)
WORK PLAN FOR NEW SCOPE.
VFD AND ALL WIRING/CONDUIT FROM THE VFD TO THE EXISTING FAN. SEE NEW
SHALL BE REUSED TO SERVE THE NEW SUPPLY FAN ARRAY. REMOVE THE EXISTING
THE EXISTING 3#4/0, 1#4G, 2"C FEEDER CURRENTLY SERVING SUPPLY FAN SF-1
WORK PLAN FOR NEW SCOPE.
VFD AND ALL WIRING/CONDUIT FROM THE VFD TO THE EXISTING FAN. SEE NEW
SHALL BE REUSED TO SERVE THE NEW RETURN FAN ARRAY. REMOVE THE EXISTING
THE EXISTING 3#4, 1#8G, 1"C FEEDER CURRENTLY SERVING RETURN FAN RF-1
TO NEW LIGHTS SHOWN ON NEW WORK PLAN.
SHALL REMAIN AND BE REUSED. EXISTING CIRCUITS SHALL REMAIN AND BE EXTENDED
REMOVE ALL OF THE EXISTING LIGHT FIXTURES IN THESE SPACES. EXISTING SWITCHES 3
EXISTING ACP
CDEF
A R
E A
W A
Y
B
C O
R R
ID
O R
B
R O
O M
M A
C H
IN
E
E L
E V
A T
O R
SEAL
SCALE:
FILE PATH:
P:\26011\26011eh20.dgn
DATE PLOTTED
DGN FILE
30-SEP-2026
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\26011\26011eh20.dgn
AS SHOWN
26011
09.29.2026
TWT
BCO
TWT
T
COA Expiration: 6.30.2028
COA#PEF000774
NBP Engineers, Inc.
F o rt V a ll e y
G e o rg ia
F V S
U B o n d H u n t
A H
U U p g ra d e s
EF-1 1
EF-10
HW
EXISTING
HP-1
EXISTING
UH-1 EXISTING
EXISTING
& SADDLE SUPPORT
CONCRETE PAD
EXISTING 12"x12"
EXISTING
ACP
EXISTING BOILER
WATER TREATMENT
EXISTING CONTROL PANEL CHEMICAL
TREATMENT TANKS
EXISTING CHEMICAL WATER
AIR LOUVER
40"X40" COMBUSTION
EXISTING
F A
C P
F
HG
SWITCHBOARD"SB"
WATER EXPANSION TANK
EXISTING CHILLED
S
ELEVATOR MOTOR
EXISTING SERVICE
100A/3P
SUPPORT BEAMS B.E. 10'-8"
EXISTING GRATING
EXISTING STARTERS
CT-1 & EF-1 1
CHEMICAL FEEDER
EXISTING BYPASS
CP-HL-1
EXISTING
OA DAMPER; 9500|
EXISTING 24"x60"
INTAKE LOUVER
EXISTING OA
EXISTING
BP
AIR COMPRESSOR
EXISTING CONTROL
SWITCH-EF-1 1
EXISTING WALL PURGE
TO REMAIN
EXISTING ACP
VFD VFD
RF-1
VFDVFD
SF-1
NEW NEW
NEW NEW
EH20
SCALE:
= 1'-0
4 0 2 4 8
N
HUNT LIBRARY - LARGE SCALE - PARTIAL BASEMENT FLOOR PLAN - NEW WORK - ELEC
NEW WORK - ELEC
FLOOR PLAN -
PARTIAL BASEMENT
LARGE SCALE -
HUNT LIBRARY -
F
F
NOTES:(THIS SHEET ONLY)
BACK IN THE MAIN SWITCHBOARD SHALL BE REUSED.
THE MOTOR CIRCUIT PROTECTOR PANEL. THE EXISTING 225A/3P CIRCUIT BREAKER
THERE ARE 8 FANS TOTAL. MAKE ALL FINAL CONNECTIONS THROUGH THE VFDS AND
3#1 AWG, 1#6G, 1-1/2"C. EACH VFD SHALL SERVE 4 FANS IN THE SUPPLY FAN ARRAY.
110A/3P ENCLOSED CIRCUIT BREAKER (TWO TOTAL) AT EACH TAP. EACH TAP SHALL BE
CIRCUIT BREAKER ABOVE EACH VFD. TAP THE #4/0 COPPER FEEDER AND PROVIDE THE
PROVIDE A WIRING TROUGH ABOVE THE NEW VFDS. PROVIDE A 110A/3P ENCLOSED
SWITCHBOARD AND SET A NEW 400A/3P FUSED DISCONNECT FUSED AT 225 AMPS.
INTERCEPT THE EXISTING FEEDER CONDUCTORS (3#4/0, 1#4G, 2"C) FROM THE MAIN
BACK IN THE MAIN SWITCHBOARD SHALL BE REUSED.
THE MOTOR CIRCUIT PROTECTOR PANEL. THE EXISTING 70A/3P CIRCUIT BREAKER
THERE ARE 8 FANS TOTAL. MAKE ALL FINAL CONNECTIONS THROUGH THE VFDS AND
BE 3#8 AWG, 1#10G, 1"C. EACH VFD SHALL SERVE 4 FANS IN THE SUPPLY FAN ARRAY.
THE 35A/3P ENCLOSED CIRCUIT BREAKER (TWO TOTAL) AT EACH TAP. EACH TAP SHALL
CIRCUIT BREAKER ABOVE EACH VFD. TAP THE #4 AWG COPPER FEEDER AND PROVIDE
PROVIDE A WIRING TROUGH ABOVE THE NEW VFDS. PROVIDE A 35A/3P ENCLOSED
SWITCHBOARD AND SET A NEW 100A/3P FUSED DISCONNECT FUSED AT 70 AMPS.
INTERCEPT THE EXISTING FEEDER CONDUCTORS (3#4, 1#8G, 1"C) FROM THE MAIN
FIRE ALARM SYSTEM. PROVIDE FIRE ALARM RELAY TO SHUT DOWN AHU.
PROVIDE NEW DUCT MOUNTED SMOKE DETECTOR AND CONNECT TO EXISTING BUILDING
ALARM RELAY TO SHUT DOWN AHU.
PROVIDE SPACE TYPE SMOKE DETECTOR INSIDE RETURN AIR PLENUM. PROVIDE FIRE
LIGHTS AROUND AS NECESSARY TO LIGHT SERVICE AREAS.
THESE LIGHTS SHALL BE MOUNTED INSIDE THE AIR HANDLING UNIT APPARATUS CASING. MOVE
PROVIDE ACUITY LIGHTING VAPOR TIGHT LED STRIP LIGHT MODEL CSVT-L48-5000LM-MVOLT-40K.
SHOULD BE SHIFTED AROUND AS REQUIRED TO ADEQUATELY LIGHT THE SPACE.
PROVIDE ACUITY LIGHTING LED STRIP LIGHT MODEL CSS-L48-5000LM-MVOLT-40K. THESE LIGHTS
PROVIDE WITH INTEGRAL BATTERY FOR EMERGENCY EGRESS LIGHTING.
5 7
5 5
5 7
5 5 5 7
5 7
6 7
6 7
6 7 6
| 26011aCov |
| 26011m00 |
| 26011mb10 |
| 26011mb20 |
| 26011mh10 |
| 26011mh20 |
| 26011m40 |
| 26011m50 |
| 26011e00 |
| 26011eb20 |
| 26011eh10 |
| 26011eh20 |
File details come from the government source that posted it. Updated .