2026-026B Drawings.pdf

PDF 8 MB Posted

Attached to
Valentine Early Learning Facility Improvements
Solicitation number
2026-026B
Issued by
Calhoun County, Michigan

About this file

This document is a comprehensive architectural design and renovation set of plans for the Valentine Center, located at 75 Irving Park Dr, Battle Creek, MI 49037. The project involves renovating an existing brick educational building, with the scope of work covering approximately 7,107 square feet, which represents 93% of the total building area. The renovation is classified as a Level 3 Alteration, which requires compliance with specific Michigan Rehabilitation Code standards. The project includes significant upgrades to interior spaces, including classrooms, restrooms, kitchen, office areas, and mechanical systems, with a focus on creating a functional child care and educational environment.

The design includes multiple alternate options for consideration, such as replacing existing glazing, tuckpointing masonry, and adding an extended canopy. The renovation will maintain the building's historic character while modernizing its functionality, with careful attention to accessibility requirements, fire safety, and energy efficiency. The plans detail specific improvements to finishes, lighting, electrical and plumbing systems, and spatial configurations. The project appears to be funded through institutional or governmental sources, with provisions for maintaining the building's existing infrastructure while making significant improvements to create a more modern and efficient educational space.

View the file

Other files

File Type Posted
2026-026B Valentine Center Early Learning Facility Improvements.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

© 2024 Driven Design Studio, All Rights Reserved.

Driven Design Studio PLLC

117 West Michigan Avenue

Battle Creek, MI 49017

(269) 753-8040 cody@drivendesignstudio.com

PROJECT NUMBER

STAMP

SCALE

DATE

DRAWN BY

PROJECT ADDRESS

PROJECT NAME

ARCHITECTURE/INTERIOR DESIGN

THIS DOCUMENT IS THE EXCLUSIVE

PROPERTY OF DRIVEN DESIGN. THE

DOCUMENT & THE INFORMATION IT

CONTAINS MAY NOT BE REPRODUCED

OR USED FOR OTHER THAN THE

SPECIFIC PROJECT FOR WHICH IT WAS

PREPARED WITHOUT THE EXPLICIT

CONSENT OF DRIVEN DESIGN.

OWNER

ISSUE

10/17/2025 9:32:36 AM

T000

TITLE SHEET

VALENTINE CENTER

75 IRVING PARK DR, BATTLE CREEK, MI

49037

CMN

VALENTINE CENTER

75 IRVING PARK DR, BATTLE CREEK, MI 49037

2025.024

City of Battle Creek

10 N Division St

Battle Creek, MI

(269) 966-3355

CONSTRUCTION DOCUMENTS

X

PROJECT NOTES

1. CONSTRUCTION MUST COMPLY WITH ALL NATIONAL, STATE, AND LOCAL BUILDING CODES,

AS WELL AS ALL LOCAL ORDINANCES.

2. DO NOT SCALE DRAWINGS. NOMINAL DIMENSIONS ARE SHOWN. REFER TO DETAILS, NOTES,

SPECIFICATIONS AND PARTITION KEY FOR INFORMATION. CONTACT ARCHITECT IF

ADDITIONAL INFORMATION IS REQUIRED.

3. EXISTING BUILDING AND SITE INFORMATION WAS OBTAINED FROM THE OWNER AND

ADDITIONAL FIELD MEASUREMENTS BY THE ARCHITECT. THE CONTRACTOR SHALL VERIFY ALL

EXISTING FIELD CONDITIONS PRIOR TO COMMENCEMENT OF WORK. DRAWINGS MAY

CONTAIN DISCREPANCIES DUE TO CONCEALED CONDITIONS, INACCURACIES IN THE

ORIGINAL DRAWINGS, INACCESSIBLE LOCATIONS, UNRECORDED BUILDING ALTERATIONS

AND OTHER CONFLICTING INFORMATION. INFORMATION OUTSIDE OF CONTRACT AREA IS

RELATIVE AND FOR REFERENCE ONLY. ALWAYS VERIFY FIELD CONDITIONS BEFORE

COMMENCING WORK. NOTIFY ARCHITECT IF FIELD CONDITIONS CONFLICT SUBSTANTIALLY

WITH PROPOSED WORK.

4. INSTRUCTIONS FOR BUILDING CONSTRUCTION MAY BE LOCATED IN ANY PART OF THE

CONSTRUCTION DRAWINGS. FAILURE OF THE GENERAL CONTRACTOR OR HIS SUB

CONTRACTORS AND SUPPLIERS TO SEE INFORMATION IN ANY PART OF THE CONTRACT

DOCUMENTS WILL NOT BE A VALID REASON FOR ISSUING A CHANGE ORDER.

5. ALL HOLES CREATED FROM ABANDONED DUCT, CONDUIT, ELEC. DEVICES, ETC., WHICH ARE

IN VIEW AND ARE NOT SCHEDULED TO BE BOARDED OVER, OR ON A WALL TO BE

DEMOLISHED, ARE TO BE FILLED AND PATCHED TO MATCH EXISTING.

6. PATCH AND REPAIR ALL EXISTING WALL SURFACES ADJACENT TO NEW WORK AS REQUIRED

TO ACHIEVE AN UNINTERRUPTED SURFACE APPEARANCE. PATCH AND REPAIR ALL FLOORING

FOR EXISTING BUILDINGS TO ACHIEVE A CONTINUOUS, SMOOTH, AND FLUSH FLOOR

SURFACE.

7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SHORING REQUIRED TO EXECUTE WORK.

THE CONTRACTOR SHALL COORDINATE ALL TEMPORARY CONSTRUCTION WITH THE

ARCHITECT AND OWNER TO ASSURE A MINIMUM AMOUNT OF INTERRUPTION WITH THE

OWNER'S ACTIVITIES.

8. IF THE PROJECT IS A REMODEL, THE CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL

SURFACES NOT BEING REMODELED IN THE PROJECT AND IN THE PATH OF THE CONTRACTORS

TRAVEL, SETUP AND/ OR PROJECT MATERIAL STORAGE. THE CONTRACTOR MUST RETURN THE

AREAS DISTURBED AS REQUIRED FOR ACCESS TO ITS PRE-EXISTING CONDITION.

9. THE CONTRACTOR AND ALL SUB-CONTRACTORS SHALL BE RESPONSIBLE TO OBTAIN AND PAY

FOR ALL LOCAL/REQUIRED PERMITS AND INSPECTIONS.

10. ALL SAFETY ISSUES RELATED TO CONSTRUCTION ARE THE RESPONSIBILITY OF THE

CONTRACTOR AND MUST COMPLY WITH ALL STATE, LOCAL, ENVIRONMENTAL AND LABOR

LAWS DURING THE CONSTRUCTION OF THIS PROJECT.

11. ALL WORK TO BE GUARANTEED A MINIMUM OF ONE YEAR FROM THE DATE OF OWNER

ACCEPTANCE OF WORK, EXCEPT WHERE MANUFACTURER'S GUARANTEE IS LONGER.

12. IF DISCREPANCIES OCCUR BETWEEN DRAWINGS AND FIELD CONDITIONS CONTACT THE

ARCHITECT TO VERIFY HOW TO PROCEED BEFORE DOING SO.

13. SEE T001 FOR ADDITIONAL PROJECT NOTES, MOUNTING HEIGHTS, AND SYMBOLS

14. 3D VIEWS AND RENDERINGS ON THIS PAGE AND THROUGHOUT THE SET ARE FOR REFERENCE

ONLY, VERIFY ALL CONSTRUCTION DETAILS THROUGHOUT THE ENTIRE SET OF DOCUMENTS

15. THE PROJECT SHALL CONFORM TO UNDERWRITERS LABORATORY FIRE RESISTANCE DIRECTORY

AND BUILDING MATERIALS DIRECTORY.

16. ANY MATERIAL SUBSTITUTIONS TO A LISTED UL DESIGN NUMBER SHALL BE COORDINATED BY

THE CONSTRUCTION MANAGER, CONTRACTOR, SUBCONTRACTOR AND/OR MATERIAL

SUPPLIER FOR COMPLIANCE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL

APPROVALS - FOR ANY MATERIALS SUBSTITUTION IN THE REQUIRED UL DESIGN ASSEMBLY - BY

THE FIRE MARSHAL AND BUILDING INSPECTOR HAVING JURISDICTION PRIOR TO

ACCEPTANCE.

17. FOR ANY CHANGE OF UL DESIGN NUMBER, OR ANY CHANGE IN MATERIAL(S) IN A UL DESIGN

ASSEMBLY, IT WILL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE ALL OTHER

RELATED MATERIALS OR ASSEMBLIES AFFECTED BY THE CHANGE OF MATERIAL OR UL DESIGN

NUMBER ASSEMBLY.

18. PROVIDE COMPLETE UL APPROVED THROUGH-PENETRATION FIRESTOP SYSTEMS AT ALL RATED

WALL PENETRATIONS.

19. PROVIDE FIRESTOPPING AS REQUIRED AT ALL OPENINGS FOR PLUMBING, CONDUIT,

DUCTWORK, ETC AT FIRE RATED ASSEMBLIES.

20. REFER TO THE FLOOR PLANS FOR IDENTIFICATION OF ALL FIRE AND SMOKE-RATED PARTITIONS.

SHEET

NUMBER DRAWING TITLE 3

/1

/2

D

E S

IG

N D

E V

E

LO

P M

E N

T

/1

/2

P

E R

M

IT

S E T

GENERAL

T000 TITLE SHEET X X

T001 RENDERINGS X X

T002 GENERAL MOUNTING HEIGHTS + ABBREVIATIONS X X

T003 PLUMBING MOUNTING HEIGHTS X X

T004 CODE COMPLIANCE - REHAB CODE X X

T005 CODE COMPLIANCE X X

T006 AREA PLANS X X

T007 SECURITY PLAN X X

CIVIL

C100 ARCHITECTURAL SITE PLAN AND DETAILS X X

ARCHITECTURAL

A000 EXISTING FLOOR PLANS X X

A110 DEMOLITION PLANS X X

A120 NEW FLOOR PLANS X X

A130 ENLARGED PLANS X X

A140 FINISH PLAN & SCHEDULE X X

A200 REFLECTED CEILING PLAN AND DETAIL X X

A210 ROOF PLAN X X

A300 INTERIOR ELEVATIONS X X

A310 INTERIOR DETAILS X X

A400 DOOR SCHEDULE X X

A410 GLAZING ELEVATIONS AND SECTIONS X X

A500 EXTERIOR ELEVATIONS X X

A600 BUILDING SECTIONS X X

MECHANICAL

MEP101 MECH, ELEC, PLUMB SPECS/NOTES X X

Grand total: 23

EXISTING PHOTOS - FOR REFERENCE ONLY

ZONING - GRN - GREEN DISTRICT

CONTEXT MAP

DRAWING LIST

PROJECT DESCRIPTION

AN EXISTING BRICK EDUCATIONAL BUILDING IS BEING RENOVATED INTO A DAYCARE

ZONING MAP

RENDERING - FOR REFERENCE ONLY

PROJECT LOCATION

PROJECT LOCATION

WALTER AVE

M

IL

E R

D

ALTERNATES

THE FOLLOWING ITEMS ARE TO BE BID OUT AS ALTERNATES;

1. BASIS OF DESIGN: THE EXISTING ENTRYWAY IS TO BE PAINTED, ALTERNATE: PROVIDE THE PRICE

FOR THE NEW STEEL CANOPY

2. BASIS OF DESIGN: PAINT OR REPAIR EXISTING CEILINGS IN ROOMS 106, 107, 109, 115,116, &

117, ALTERNATE: REPLACE EXISTING CEILINGS WITH NEW CEILINGS

3. BASIS OF DESIGN: EXISTING EXTERIOR GLAZING TO REMAIN, ALTERNATE: REPLACE ALL

EXISTING EXTERIOR GLAZING

4. BASIS OF DESIGN: EXISTING MASONRY TO REMAIN, ALTERNATE: TUCKPOINT EXISTING

MASONRY

5. BASIS OF DESIGN: RELOCATE OFFICE DOOR 103, ALTERNATE, LEAVE IN EXISTING LOCATION

Headquarters Driven Design

117 West Michigan Avenue

Battle Creek, MI 49017

(269) 753-8040 cody@drivendesignstudio.com

PROJECT NUMBER

STAMP

SCALE

DATE

DRAWN BY

PROJECT ADDRESS

PROJECT NAME

ARCHITECTURE/INTERIOR DESIGN

THIS DOCUMENT IS THE EXCLUSIVE

PROPERTY OF DRIVEN DESIGN. THE

DOCUMENT & THE INFORMATION IT

CONTAINS MAY NOT BE REPRODUCED

OR USED FOR OTHER THAN THE

SPECIFIC PROJECT FOR WHICH IT WAS

PREPARED WITHOUT THE EXPLICIT

CONSENT OF DRIVEN DESIGN.

OWNER

ISSUE

10/17/2025 9:32:36 AM

T001

RENDERINGS

VALENTINE CENTER

75 IRVING PARK DR, BATTLE CREEK, MI

49037

CMN

2025.024

City of Battle Creek

10 N Division St

Battle Creek, MI

(269) 966-3355

CONSTRUCTION DOCUMENTS

X

RENDERINGS OPTION 1- FOR REFERENCE ONLY

RENDERINGS - FOR REFERENCE ONLY

1i

1t

ROOM NUMBER

FINISH TYPE

DOOR NUMBER

WALL TYPES

WINDOW NUMBER

EXISTING WALL TO REMAIN

CONCRETE

WOOD BLOCKING

STEEL (LARGE SCALE)

GYPSUM BOARD/PLASTER

RIGID INSULATION

PLYWOOD

ELEMENTS TO BE REMOVED

MATERIAL DESIGNATIONS & SYMBOLS DETAIL / PLAN / ELEVATION

BLDG SECTION CUT

NEW ELEVATION

EXISTING ELEVATION

DRAWING REFERENCE

SHEET REFERENCE

DRAWING REFERENCE

SHEET REFERENCE

CMU

A101

SIM

A101

SIM

WALL SECTION

DRAWING REFERENCE

SHEET REFERENCE

A101

SIM

Room name

BATT INSULATION

EXTENT OF WORK

NEW WALL

MILLWORK

1i

CR

COLUMN CENTER LINE / IDENTIFIER1

REVISION INDICATION

3 HOUR PARTITION

2 HOUR PARTITION

1 HOUR PARTITION

TYPICAL MOUNTING HEIGHTS

1. MOUNTING HEIGHTS SHOWN ARE BASED UPON RECOGNIZED DESIGN

STANDARDS AND/OR BARRIER FREE CODE REQUIREMENTS. IT IS INTENDED

THAT LIKE DEVISES ALL BE MOUNTED AT THE SAME HEIGHT THROUGHOUT THE

ENTIRE PROJECT. RECESSED DEVICES IN MASONRY WALLS MAY DICTATE A

DEVIATION (+/- 2") FROM THESE HEIGHTS (WHEN PERMITTED BY CODE) SO

AS TO ALLOW THE BOTTOM OR THE TOP OF THE DEVICE RECESS TO ALIGN

WITH MASONRY COURSING. COORDINATE THESE DEVIATIONS WITH THE

ARCHITECT'S/OWNER'S REPRESENTATIVE. MOUNTING HEIGHTS ARE TYPICAL

UNLESS NOTED OTHERWISE ON DRAWINGS.

DIMENSIONING

1. DIMENSIONS ARE FROM FINISHED FACE TO FINISHED FACE, UNLESS NOTED

OTHERWISE, SEE DIMENSIONING KEY ON THIS PAGE FOR REFERENCE

GENERAL NOTES

1. THE MOUNTING HEIGHTS, MATERIALS, AND SYMBOLS SHOWN ON THIS PAGE

ARE FOR REFERENCE THROUGHOUT THE PROJECT. NOT ALL ELEMENTS

SHOWN WILL APPLY TO THIS SPECIFIC PROJECT. REVIEW THE PROJECT

PLANS, SECTIONS, AND ELEVATIONS FOR ADDITIONAL DETAILS AND TO

VERIFY WHAT RELATES TO THIS PROJECT.

M

IN

30" MIN

M

IN

52" MIN

FORWARD APPROACH PARALLEL APPROACH

52" MIN

CLEAR FLOOR SPACE

M

IN

ALCOVE, FORWARD APPROACH

X

36" MIN

ALCOVE, SIDE APPROACH

X

60" MIN

REQUIRED CLEARANCES

67" TURNING DIAMETER

60" IN EXISTING

67" MIN. IN NEW CONST

T - SHAPED TURNING SPACE

ALL DIMENSIONS ARE MIN.

1' - 6" 3' - 0" 1' - 6"

8"

M

IN

18" MIN

FRONT APPROACH - PULL SIDE

REQUIRED PUSH/PULL CLEARANCES

M

IN

12" MIN

FRONT APPROACH - PUSH SIDE

M

IN

FRONT APPROACH - PUSH SIDE

M

IN

HINGE APPROACH - PULL SIDE

42" MIN

HINGE APPROACH - PUSH SIDE

M

IN

22" MIN 12" MIN

DIMENSIONING SYSTEM (UNLESS NOTED OTHERWISE)

4"

PARTITION AT

RIGHT ANGLE

2' - 6"FINISH FACE OF

NEW

CONSTRUCTION

COLUMN

LINE

2' - 0"FINISH FACE OF

NEW

CONSTRUCTION

FINISH FACE OF

EXISTING

CONSTRUCTION

ALIGNFINISH FACE OF

NEW

CONSTRUCTION

FINISH FACE OF

EXISTING

CONSTRUCTION

DIMENSIONING KEY

*IF THE DOOR IS

NOT AGAINST A

RIGHT ANGLE

PARTITION OR

EXISTING, IT IS TO BE

CENTERED IN THE

ROOM, U.N.O.

UNOBSTRUCTED

APPROACH

FIRE

EXTINGUISHER

FIRE

EXTINGUISHER

CABINET

HI-LOW ADA

DRINKING

FOUNTAIN

OPTIONAL BOTTLE FILLER,

VERIFY W/OWNER

SHOWER HEAD, VALVES

AND CURTAIN ROD

CURTAIN ROD

SHOWER HEAD

SHOWER

CONTROLS

SANITARY NAPKIN

DISPENSER

M A

X

PAPER TOWEL

DISPENSER

LIQUID SOAP

DISPENSER

COAT HOOK AUTOMATIC

DOOR BUTTON

CLOSET ROD

AND SHELF

HAND LOTION

DISPENSER

UNOBSTRUCTED

APPROACH

OPERATING

PARTS MUST BE

BELOW MAXIMUM

HEIGHT

UNOBSTRUCTED

APPROACH

UNOBSTRUCTED

APPROACH

UNOBSTRUCTED

APPROACH

CLOSET ROD

W/OUT SHELF

UNOBSTRUCTED

APPROACH

FIRE VALVE

CABINET

FIRE HOSE RACK

OR VALVE

MOUNTING HEIGHTS

MAX SLOPE

1' - 0"

1.5" MIN.

2" OD

1.25" TO

HANDRAIL AT TOP OR

BOTTOM OF RAMP

HANDRAIL / GRAB

BAR SIZE AND

WALL SPACING

LINE OF END OR

RAMP AT BOTTOM

(OR TOP)

M

A X

M

IN

RAILING DETAILS

M A

X

BABY

CHANGING

STATION

ADA RESTROOM

SIGN

POST-MOUNTED

PARKING SIGNS

WALL-MOUNTED

PARKING SIGN

M

IN

1' - 0"

M

IN

1' - 0"

RESTROOM M EN'S W OM EN'S

VAN

ACCESSIBLE

M

IN

TO

W O

R K

S U

R

FA

C E

M A

X

MOUNTING HEIGHTS

© 2024 Driven Design Studio, All Rights Reserved.

Driven Design Studio PLLC

117 West Michigan Avenue

Battle Creek, MI 49017

(269) 753-8040 cody@drivendesignstudio.com

PROJECT NUMBER

STAMP

SCALE

DATE

DRAWN BY

PROJECT ADDRESS

PROJECT NAME

ARCHITECTURE/INTERIOR DESIGN

THIS DOCUMENT IS THE EXCLUSIVE

PROPERTY OF DRIVEN DESIGN. THE

DOCUMENT & THE INFORMATION IT

CONTAINS MAY NOT BE REPRODUCED

OR USED FOR OTHER THAN THE

SPECIFIC PROJECT FOR WHICH IT WAS

PREPARED WITHOUT THE EXPLICIT

CONSENT OF DRIVEN DESIGN.

OWNER

ISSUE

10/17/2025 9:32:37 AM

As indicated

T002

GENERAL MOUNTING HEIGHTS +

ABBREVIATIONS

VALENTINE CENTER

75 IRVING PARK DR, BATTLE CREEK, MI

49037

CMN

2025.024

City of Battle Creek

10 N Division St

Battle Creek, MI

(269) 966-3355

CONSTRUCTION DOCUMENTS

X

ABBREVIATION LIST

A/C AIR CONDITIONING

A/V AUDIO/VISUAL

ACP ACOUSTICAL CEILING PANEL

AD AREA DRAIN

ADA AMERICANS WITH DISABILITIES ACT

ADJ ADJUSTABLE

AFF ABOVE FINISHED FLOOR

ALT ALTERNATE

ALUM ALUMINIUM

APPROX APPROXIMATELY

ARCH ARCHITECT(URAL, URE)

ASSOC ASSOCIATED

AUTO AUTOMATIC

AWP ACOUSTICAL WALL PANEL

BD BOARD

BF BARRIER FREE

BIT BITUMINOUS, BITUMEN

BLDG BUILDING

BLKG BLOCKING

BM BEAM

BOT BOTTOM

CAB CABINET

CJ CONTROL JOINT

CLG CEILING

CLR CLEAR(ANCE)

CMU CONCRETE MASONRY UNIT

COL COLUMN

COM COMMUNICATIONS

CONC CONCRETE

CONFIG CONFIGURATION

CONST CONSTRUCTION

CONT CONTINUOUS

COORD COORDINATE

CORR CORRIDOR

CPT CARPET

CT CERAMIC TILE

CTR CENTER

DEG DEGREE

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL

DIM DIMENSION

DIV DIVISION

DN DOWN

DR DOOR

DS DOWNSPOUT

DTL DETAIL

DWG(S) DRAWING(S)

E EAST

EA EACH

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATION

EMER EMERGENCY

ENCL ENCLOS(E,URE)

EQ EQUAL

EQUIP EQUIPMENT

EST ESTIMATE(D)

EXIST EXISTING

EXP EXPANSION

EXT EXTERIOR

FA FIRE ALARM

FD FLOOR DRAIN

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FINISHED FACE

FGL FIBERGLASS

FHC FIRE HOSE CABINET

FIXT FIXTURE

FL FLOOR(ING)

FLUOR FLUORESCENT

FOC FACE OF CONCRETE

FOS FACE OF STUDS

FP FIREPROOF(ING)

FT FEET

FTG FOOTING

FUR FURR(ED,ING)

GA GAUGE

GALV GALVANIZED

GB GRAB BAR

GC GENERAL CONTRACT(OR)

GL GLASS, GLAZING

GOVT GOVERNMENT

GT GROUT

GYP BD GYPSUM WALLBOARD

HC HOLLOW CORE

HDR HEADER

HDWD HARDWOOD

HDWR HARDWARE

HGT HEIGHT

HM HOLLOW METAL

HORIZ HORIZONTAL

HP HIGH POINT

HR HOUR

HT HEIGHT

HVAC HEATING, VENTILATION & AIR

CONDITIONING

ABBREVIATION LIST

ID INSIDE DIAMETER

IN INCH(ES)

INCAN INCANDESCENT

INCL INCLUDE(D,ING)

INSUL INSULATION, INSULATED

INT INTERIOR

JAN JANITOR

JT(S) JOINT(S)

KIT KITCHEN

LAM LAMINATE(D)

LAV LAVATORY

LBL LABEL

LH LEFT HAND

LL LIVE LOAD

LP LOW POINT

LTG LIGHTING

LTL LINTEL

MANF MANUFACTURE(R)

MAS MASONRY

MATL MATERIAL(S)

MAX MAXIMUM

MECH MECHANICAL

MEMB MEMBRANE

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MTD MOUNTED

MTG MOUNTING

MTL METAL

N NORTH

N/A NOT APPLICABLE

NAT NATURAL

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OPNG OPENING

OPP OPPOSITE

OPP HD OPPOSITE HAND

PART PARTITION

PC PRECAST

PERF PERFORATE(D)

PL PLATE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLWD PLYWOOD

PNL PANEL(ED)

PR PAIR

PREP PREPARE (SURFACE)

PROV PROVIDE

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PAINT

PVMT PAVEMENT

QTY QUANTITY

R RISER

RAD RADIUS

RB RUBBER BASE

REF REFRIDGERATOR

REINF REINFORCED

REQD /

REQ'D

REQUIRED

RES RESILIENT

RET RETAINING

REV REVISION(S) / REVISE(D)

RFG ROOFING

RH RIGHT HAND

RM ROOM

RO ROUGH OPENING

S SOUTH

SC SOLID CORE

SCHED SCHEDULE

SECT SECTION

SF SQUARE FEET

SHT SHEET

SIM SIMILAR

SPEC(S) SPECIFICATION(S)

SQ SQUARE

SS STAINLESS STEEL

STD STANDARD

STL STEEL

STN STAIN

STO STORAGE

STRUC STRUCTURAL

SUSP SUSPENDED

SYM SYMMETRICAL

SYS SYSTEM

T TREAD

T&G TONGUE AND GROOVE

T.O. TOP OF

TECH TECHNOLOGY

TEL TELEPHONE

TEMP TEMPERED

THK THICK(NESS)

ABBREVIATION LIST

THRESH THRESHOLD

TOC TOP OF CURB

TOM TOP OF MASONRY

TOS TOP OF STEEL

TOW TOP OF WALL

TRANS TRANSPARENT

TV TELEVISION

TYP TYPICAL

UL UNDERWRITER'S LABORATORY

UNFIN UNFINISHED

UNO UNLESS OTHERWISE NOTED

VAR VARIES

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

VU VENTILATION UNIT

VWC VINYL WALLCOVERING

W WATER RESISTANT

W/ WITH

W/O WITHOUT

WC WATER CLOSET

WD WOOD

WDW WINDOW

WH WALL HUNG

WP WORK POINT

WR PAINT(ED)

WT WEIGHT

WWF WELDED WIRE FABRIC

# NUMBER

& AND

+/- EXIST (OR APPROX) DIM - VIF

CL CENTER LINE

L ANGLE

M

IN

C

LE

A

R

7' 4" - MIN. CLEAR

32" CLEAR MIN.

ADA RESTROOM PLAN - NTS

30" X 52" LAVATORY

CLEAR FLOOR SPACE

IN NEW CONST. (30" X

48" IN EXISTING BLDGS.)

30" X 52" MANEUVERING

CLEAR FLOOR SPACE PAST

DOOR SWING

67" DIAMETER TURNING

SPACE FOR NEW

CONST. (60" DIA. FOR

EXISTING BLDGS)

54" x 60" CLEAR FLOOR

SPACE AT DOOR

60" X 59" WATER

CLOSET CLEAR FLOOR

SPACE (SHADED)

1' - 6"1' - 6" TYP

M

IN

11" MIN.

8" MIN.

LAVATORY

LAVATORY

WIDTH

MIN. ROOM

WIDTH

20" 6'-11"

21" 7'-0"

22" 7'-1"

LAVATORY NOT

CENTERED ON

30 X 48 CLEAR AREA

M

IN

M

A X

M

IN

MAX.

3"

1' - 6"

6" 3' - 0"

REQUIRED CLEAR SPACE

1'-0" ABOVE AND 1 1/2"

BELOW GRAB BAR

9"

42" MIN.

MAX.

1' - 0"

M

IN

EDGE OF REFLECTIVE

SURFACE

INSTALL TRUEBRO LAV

GUARD 2 UNDERSINK

PIPING COVER OR EQ. AT

ALL UNDERSINK PIPING

TOILET PAPER DISPENSER

SANITARY NAPKIN DISPOSAL

MIN. CLEAR

3' - 0" *

* CAN BE 2'-6" IF PARTITION SCREEN

DOES NOT EXTEND PAST URINAL

WALL MTD. SCREEN REQUIRED ON

EACH SIDE OF URINAL

URINALADA RESTROOM SIDE VIEWADA RESTROOM FRONT VIEW

ELEC OUTLETS NEAR SINKS IN

BF TOILET ROOMS TO BE

MOUNTED 33" TO 36" AFF TO

CENTERLINE AND BE GFI

MIN.

1' - 3"

MIN

2' - 6"

RESTROOM DETAILS - NTS

*NOTE: PROVIDE BLOCKING AS

REQUIRED FOR ALL GRAB BARS AND

FIXTURE MOUNTING PER

MANUFACTURER'S RECOMMENDATION

39"-41"

S

TA

N D

A R

D

B .F

M

A X

M A

X

5' - 0" MIN. 2' - 0"

M

A X

B .F

M

A X1

M

A X

67" DIA. FOR NEW CONST.

60" DIA. FOR EXISTING BLDGS.

7'-4 " M

IN

.7' 4" MIN.

18" O .C

30" M

IN

M

A X

M A

X

36" G

RAB BAR

30"X36"

MIRROR

PAPER

DISPENSER

" M A

X

42" GRAB

BAR

18" GRAB BAR

TOILET

COVER

DISPENSER

TOILET PAPER

DISPENSER

CLEAR FLOOR SPACE

30" X 52" (NEW

30" X 48" (EXIST.)

REST

ROOM

ENTR

Y

TILE ON WET WALL GYP. BD. OR TILE, SEE

FINISH SCHEDULE

ADA RESTROOM AXON - NTS

1.5" MIN.

2" OD

1.25" TO

HANDRAIL / GRAB

BAR SIZE AND

WALL SPACING

MEDICINE

CABINET

MEDICINE

CABINET

(BF)

M A

X

TO

U

S A

B

LE

S H

E

LF

TOWEL

BAR AND

SHELF

TOWEL

BAR

M

A X

MIRROR /

VANITY

COUNTER

M

IN

M A

X

M

IN

1' - 6" MIN.

DRESSING

MIRROR

(BF)

SEAT

COVER

DISP

(B F)

TOWEL DISP

OR MULTI-

PURPOSE

UNIT

TOWEL DISP

AND WASTE

RECEPTACLE

HEIGHT OF DISPENSER

OR OPERATING

CONTROLS

M

IN

WASTE

RECEPT

B

F

FACIAL

TISSUE

DISP

SANITARY

NAPKIN DISP

SOAP

DISH

HAND

DRYER

SOAP

DISP

TOILET PAPER

HOLDER

BASE CABINET WITH

SINK & KNEE SPACE

(BF)

LINE OF WALL

2' - 0"

4"

TO

R

IM

M

A X

(2

B F)

(3

B F)

BACKSPLASH

M

IN

M A

X

TO

6" MAX.

MIN.

8"

17" TO 19"

3" MAX.

WALL AND BASE

CABINETS

HIGH-LOW EWC OR

DRINKING FOUNTAIN

M A

X

M

A X

M

A X

ADDITIONAL RESTROOM MOUNTING HEIGHTS

© 2024 Driven Design Studio, All Rights Reserved.

Driven Design Studio PLLC

117 West Michigan Avenue

Battle Creek, MI 49017

(269) 753-8040 cody@drivendesignstudio.com

PROJECT NUMBER

STAMP

SCALE

DATE

DRAWN BY

PROJECT ADDRESS

PROJECT NAME

ARCHITECTURE/INTERIOR DESIGN

THIS DOCUMENT IS THE EXCLUSIVE

PROPERTY OF DRIVEN DESIGN. THE

DOCUMENT & THE INFORMATION IT

CONTAINS MAY NOT BE REPRODUCED

OR USED FOR OTHER THAN THE

SPECIFIC PROJECT FOR WHICH IT WAS

PREPARED WITHOUT THE EXPLICIT

CONSENT OF DRIVEN DESIGN.

OWNER

ISSUE

10/17/2025 9:32:38 AM

As indicated

T003

PLUMBING MOUNTING HEIGHTS

VALENTINE CENTER

75 IRVING PARK DR, BATTLE CREEK, MI

49037

CMN

2025.024

City of Battle Creek

10 N Division St

Battle Creek, MI

(269) 966-3355

CONSTRUCTION DOCUMENTS

X

117 West Michigan Avenue

Battle Creek, MI 49017

(269) 753-8040 cody@drivendesignstudio.com

PROJECT NUMBER

STAMP

SCALE

DATE

DRAWN BY

PROJECT ADDRESS

PROJECT NAME

ARCHITECTURE/INTERIOR DESIGN

THIS DOCUMENT IS THE EXCLUSIVE

PROPERTY OF DRIVEN DESIGN. THE

DOCUMENT & THE INFORMATION IT

CONTAINS MAY NOT BE REPRODUCED

OR USED FOR OTHER THAN THE

SPECIFIC PROJECT FOR WHICH IT WAS

PREPARED WITHOUT THE EXPLICIT

CONSENT OF DRIVEN DESIGN.

OWNER

ISSUE

10/17/2025 9:32:38 AM

T004

CODE COMPLIANCE - REHAB CODE

VALENTINE CENTER

75 IRVING PARK DR, BATTLE CREEK, MI

49037

CMN

2025.024

City of Battle Creek

10 N Division St

Battle Creek, MI

(269) 966-3355

CONSTRUCTION DOCUMENTS

X

2021 MICHIGAN REHABILITATION CODE

CHAPTER 6: CLASSIFICATION OF WORK

SECTION 604

AREA OF RENOVATION = 7,107 SQUARE FEET, WHICH IS 93% OF THE TOTAL BUILDING AREA.

THE WORK IS GREATER THAN 50% AND THEREFORE IS CONSIDERED A LEVEL 3 ALTERATION.

SECTION 508.2 EXCEPT AS SPECIFICALLY PROVIDED FOR IN CHAPTER 12, HISTORIC BUILDINGS SHALL COMPLY WITH APPLICABLE PROVISIONS OF THIS CODE FOR THE TYPE OF WORK BEING PERFORMED. THE BUILDING IS CURRENTLY LISTED ON THE STATE REGISTRY OF HISTORIC PROPERTIES.

CHAPTER 7: ALTERATIONS - LEVEL 1

SECTION 702.5 EMERGENCY ESCAPE AND RESCUE OPENINGS. WHERE WINDOWS ARE REQUIRED TO PROVIDE EMERGENCY ESCAPE AND RESCUE OPENINGS IN GROUP R-2 AND R-23 OCCUPANCIES AND ONE AND TWO FAMILY DWELLINGS AND TOWNHOUSES REGULATED BY THE INTERNATIONAL RESIDENTIAL CODE, REPLACEMENT WINDOWS SHALL BE EXEMPT FROM THE REQUIREMENTS OF SECTIONS 1030.2, 1030.3 AND 1030.5 OF THE INTERNATIONAL BUILDING CODE AND SECTIONS R310.21

AND R310.2.3 OF THE INTERNATIONAL RESIDENTIAL CODE ACCORDINGLY. PROVIDED THE REPLACEMENT WINDOW IS THE MANUFACTURER'S LARGEST STANDARD SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR EXISTING ROUGH OPENING. THE REPLACEMENT WINDOW SHALL BE PERMITTED TO BE OF THE SAME OPERATING STYLE AS THE EXISTING WINDOW OR A STYLE THAT PROVIDES FOR AN EQUAL OR GREATER WINDOW OPENING AREA THAN THE EXISTING WINDOWS.

SECTION 702.6 MATERIALS AND METHODS. ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND METHOD REQUIREMENTS IN THE INTERNATIONAL BUILDING CODE, INTERNATIONAL ENERGY CONSERVATION CODE, INTERNATIONAL MECHANICAL CODE, AND INTERNATIONAL PLUMBING CODE, AS APPLICABLE, THAT SPECIFY MATERIAL STANDARDS, DETAIL OF INSTALLATION AND CONNECTION, JOINTS, PENETRATIONS, AND CONTINUITY OF ANY ELEMENT, COMPONENT, OR SYSTEM IN THE

BUILDING.

SECTION 704.1 GENERAL. ALTERATIONS SHOWS BE DONE IN A MANNER THAT MAINTAINS THE LEVEL OF PROTECTION PROVIDED FOR THE MEANS OF EGRESS.

SECTION 708.1 MINIMUM REQUIREMENTS. LEVEL 1 ALTERATIONS TO EXISTING BUILDINGS OR STRUCTURES ARE PERMITTED WITHOUT REQUIRING THE ENTIRE BUILDING OR STRUCTURE TO COMPLY WITH THE ENERGY REQUIREMENTS OF THE INTERNATIONAL ENERGY CONSERVATION CODE OR INTERNATIONAL RESIDENTIAL CODE. THE ALTERATIONS SHALL CONFIRM TO THE ENERGY REQUIREMENTS OF THE INTERNATIONAL ENERGY CONSERVATION CODE OR INTERNATIONAL RESIDENTIAL CODE AS

THEY RELATE TO NEW CONSTRUCTION ONLY.

CHAPTER 8: ALTERATIONS - LEVEL 2

SECTION 801.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE. EXCEPTIONS: 1. WINDOWS MAY BE ADDED WITHOUT REQUIRING COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE. 2. NEWLY INSTALLED ELECTRICAL EQUIPMENT SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 808. 3. THE

LENGTH OF DEAD-END CORRIDORS IN NEWLY CONSTRUCTED SPACES SHALL ONLY BE REQUIRED TO COMPLY WITH THE PROVISIONS OF SECTION 805.6. 4. THE MINIMUM CEILING HEIGHT OF THE NEWLY CREATED HABITABLE AND OCCUPIABLE SPACES AND CORRIDORS SHALL BE 7 FEET.

SECTION 803.2 VERTICAL OPENINGS. EXISTING VERTICAL OPENINGS SHALL COMPLY WITH THE PROVISIONS OF SECTION 803.1, 803.2.2, AND 803.2.3.

SECTION 803.2.1 EXISTING VERTICAL OPENINGS. ALL EXISTING INTERIOR VERTICAL OPENINGS CONNECTING TWO OR MORE FLOORS SHALL BE ENCLOSED WITH APPROVED ASSEMBLIES HAVING A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR WITH APPROVED OPENING PROTECTIVE. EXCEPTIONS: 1.WHERE VERTICAL OPENING ENCLOSURE IS NOT REQUIRED BY THE INTERNATIONAL BUILDING OR INTERNATIONAL FIRE CODE. 2. INTERIOR VERTICAL OPENINGS OTHER THAN STAIRWELLS MAY

BE BLOCKED AT THE FLOOR AND CEILING OF THE WORK AREA BY INSTALLATION OF NEW LESS THAN 2" OF SOLID WOOD OR EQUIVALENT CONSTRUCTION. 3. THE ENCLOSURE SHALL NOT BE REQUIRED WHERE: 3.1 CONNECTING THE MAIN FLOOR AND MEZZANINES, OR 3.2 ALL OF THE FOLLOWING REQUIREMENTS ARE MET: THE COMMUNICATING AREA HAS A LOW HAZARD OCCUPANCY OR HAS A MODERATE HAZARD OCCUPANCY THAT IS PROTECTED THROUGHOUT WITH AN AUTOMATIC

SPRINKLER SYSTEM. 3.2.2 THE LOWEST OR NEXT TO THE LOWEST LEVEL IS THE STREET LEVEL. 3.2.3 THE ENTIRE AREA IS OPEN AND UNOBSTRUCTED IN A MANNER SUCH THAT IT MAY NE ASSUMED THAT A FIRE IN ANY PART OF THE INTERCONNECTED SPACES WILL BE READILY OBVIOUS TO ALL OF THE OCCUPANTS. 3.2.4 EXIT CAPACITY IS SUFFICIENT TO PROVIDE EGRESS SIMULTANEOUSLY FOR ALL OCCUPANTS OF ALL LEVELS BY CONSIDERING ALL AREAS TO BE A SINGLE FLOOR AREA FOR THE

DETERMINATE OF REQUIRED EXIT CAPACITY. 3.2.5 EACH FLOOR LEVEL, CONSIDERED SEPARATELY HAS AT LEAST ONE-HALF OF ITS INDIVIDUAL REQUIRED EXIT CAPACITY PROVIDE BY AN EXIT OR EXITS LEADING DIRECTLY OUT OF THAT LEVEL WITHOUT HAVING TO TRAVERSE ANOTHER COMMUNICATING FLOOR LEVEL OR BE EXPOSED TO THE SMOKE OR FIRE SPREADING FROM ANOTHER COMMUNICATING FLOOR LEVEL.

SECTION 803.2.1 #11. IN GROUP R-2 OCCUPANCIES, A MINIMUM 30-MINUTE ENCLOSURE SHALL BE PROVIDED TO PROTECT ALL VERTICAL OPENINGS NOT EXCEEDING THREE STORIES. THIS ENCLOSURE OF THE ENCLOSURE SPECIFIED IN SECTION 803.2.1, SHALL NOT BE REQUIRED IN THE FOLLOWING LOCATIONS: 11.1 VERTICAL OPENINGS NOT EXCEEDING TWO STORIES WITH NOT MORE THAN FOUR DWELLING UNITS PER FLOOR. 11.2 BUILDINGS PROTECT THROUGHOUT BY AN APPROVED

AUTOMATIC SPRINKLER SYSTEM. 11.3 BUILDING WITH NOT MORE THAN FOUR DWELLING UNITS PER FLOOR WHERE EVERY SLEEPING ROOM ABOVE THE SECOND FLOOR IS PROVIDED WITH DIRECT ACCESS TO A FIRE ESCAPE OR OTHER APPROVED EXTERIOR DOOR OR WINDOW S HAVING A SILL HEIGHT OR NOT GREAT THAN 44 INCHES AND THE BUILDING IS PROTECTED THROUGHOUT BY AN AUTOMATIC FIRE ALARM SYSTEM COMPLYING WITH SECTION 804.4.

SECTION 804.2.2.1 MIXED USES. IN WORK AREAS CONTAINING MIXED USES, ONE OR MORE OF WHICH REQUIRES AUTOMATIC SPRINKLER PROTECTION IN ACCORDANCE WITH SECTION 804.2.2, WHICH PROTECTION SHALL NOT BE REQUIRED THROUGHOUT THE WORK AREA PROVIDED THAT THE USES REQUIRING SUCH PROTECTION ARE SEPARATED FROM THOSE NOT REQUIRING PROTECTION BY FIRE RESISTANCE RATED CONSTRUCTION HAVING A MINIMUM 2-HOUR RATING FOR GROUP H AND A

MINIMUM 1-HOUR RATING FOR ALL OTHER OCCUPANCY GROUPS.

SECTION 804.4.1.6 A FIRE ALARM SYSTEM SHALL BE INSTALLED IN WORK AREAS OF GROUP R-2 APARTMENT BUILDINGS AS REQUIRED BY THE INTERNATIONAL FIRE CODE FOR EXISTING GROUP R-2 OCCUPANCIES.

SECTION 804.4.3 INDIVIDUAL SLEEPING UNITS AND INDIVIDUAL DWELLING UNITS IN ANY WORK AREA IN GROUP R OCCUPANCIES SHALL BE PROVIDED WITH SMOKE ALARMS IN ACCORDANCE WITH THE MICHIGAN BUILDING CODE.

SECTION 805.3.1 EVERY STORY UTILIZED FOR HUMAN OCCUPANCY ON WHICH THERE IS A WORK AREA THAT INCLUDES EXIT OR CORRIDORS SHARED BY MORE THAN ONE TENANT WITHIN THE WORK AREA SHALL BE PROVIDED WITH THE MINIMUM NUMBER OF EXITS BASED ON THE OCCUPANCY AND THE OCCUPANT LOAD IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE.

SECTION 805.3.1.1 SINGLE-EXIT BUILDINGS. ONLY ONE EXIT IS REQUIRED FROM BUILDINGS AND SPACES OF THE FOLLOWING OCCUPANCIES. 5. GROUPS R-1 AND R-2 NOT MORE THAN TWO STORIES IN HEIGHT, WHEN THERE ARE NOT MORE THAN FOUR DWELLING UNITS PER FLOOR AND THE EXIT ACCESS TRAVEL DISTANCE DOES NOT EXCEED 50 FEET. THE MINIMUM FIRE-RESISTANCE RATING OF THE EXIT ENCLOSURE AND OF THE OPENING PROTECTION SHALL BE 1 HOUR. 6. IN MULTILEVEL DWELLING

UNITS IN BUILDINGS OF

SECTION 805.4.3 IN ANY WORK AREA, ALL DOORS OPENING ONTO AN EXIT PASSAGEWAY AT GRADE OR AN EXIT STAIRWAY SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING BY LISTED CLOSING DEVICES.

SECTION 805.5.1 ALL DWELLING UNIT OR SLEEPING UNIT CORRIDOR DOORS IN WORK AREAS IN BUILDINGS OF GROUPS R-2 SHALL BE AT LEAST 1 3/8" SOLID CORE WOOD OR APPROVED EQUIVALENT AND SHALL BE EQUIPPED WITH APPROVED DOOR CLOSERS. EXCEPTION 5: DOOR ASSEMBLIES HAVING A FIRE PROTECTION RATING OF AT LEAST 20 MINUTES.

SECTION 805.5.2 TRANSOMS. IN ALL BUILDINGS OF GROUP I-1, I-2, R-1, AND R-2 OCCUPANCIES, ALL TRANSOMS IN CORRIDOR WALLS IN WORK AREAS SHALL BE EITHER GLAZED WITH 1/4" WIRED GLASS SET IN METAL FRAMES OR OTHER GLAZING ASSEMBLIES HAVING A FIRE PROTECTION RATING AS REQUIRED FOR THE DOOR AND PERMANENTLY SECURED IN THE CLOSED POSITION OR SEALED WITH MATERIAL CONSISTENT WITH THE CORRIDOR CONSTRUCTION.

SECTION 805.6 DEAD-END CORRIDORS IN ANY WORK AREA SHALL NOT EXCEED 35 FEET.

SECTION 805.8.1 MEANS OF EGRESS IN ALL WORK AREAS SHALL BE PROVIDED WITH EXIT SIGNS IN ACCORDANCE WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE.

SECTION 807.2 NEW STRUCTURAL ELEMENTS IN ALTERATIONS SHALL COMPLY WITH THE INTERNATIONAL BUILDING CODE.

SECTION 807.4 ALTERATIONS SHALL NOT REDUCE THE CAPACITY OF EXISTING GRAVITY LOAD-CARRYING STRUCTURAL ELEMENTS UNLESS IT IS DEMONSTRATED THAT THE ELEMENTS HAVE THE CAPACITY TO CARRY THE APPLICABLE DESIGN GRAVITY LOADS REQUIRED BY THE INTERNATIONAL BUILDING CODE.

SECTION 808.1 ALL NEWLY INSTALLED ELECTRICAL EQUIPMENT AND WIRING RELATING TO WORK DONE IN ANY WORK AREA SHALL COMPLY WITH ALL APPLICABLE REQUIREMENTS OF NFPA 70.

SECTION 809.1 ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY AND ALL SPACES CONVERTED TO HABITABLE SPACE IN ANY WORK AREA SHALL BE PROVIDED WITH NATURAL OR MECHANICAL VENTILATION IN ACCORDANCE WITH THE INTERNATIONAL MECHANICAL CODE.

SECTION 811.1 LEVEL 2 ALTERATIONS TO EXISTING BUILDINGS SHALL CONFORM TO THE ENERGY REQUIREMENTS OF THE INTERNATIONAL ENERGY CONSERVATION CODE AS THEY RELATE TO NEW CONSTRUCTION ONLY.

CHAPTER 9: ALTERATIONS - LEVEL 3

SECTION 901.1 SCOPE. LEVEL 3 ALTERATIONS AS DESCRIBED IN SECTION 505 SHALL COMPLY WITH THE REQUIREMENTS OF THIS CHAPTER.

SECTION 903.1 EXISTING SHAFTS AND VERTICAL OPENINGS. EXISTING STAIRWAYS THAT ARE PART OF THE MEANS OF EGRESS SHALL BE ENCLOSED IN ACCORDANCE WITH SECTION 803.2.1 FROM THE HIGHEST WORK AREA FLOOR TO, AND INCLUDING, THE LEVEL OF EXIT DISCHARGE AND ALL FLOORS BELOW.

SECTION 903.3 INTERIOR FINISH. INTERIOR FINISH IN EXITS SERVING THE WORK AREA SHALL COMPLY WITH SECTION 803.4 BETWEEN THE HIGHEST FLOOR ON WHICH THERE IS A WORK AREA TO THE FLOOR OF EXIT DISCHARGE.

SECTION 904.1 AUTOMATIC SPRINKLER SYSTEMS. AN AUTOMATIC SPRINKLER SYSTEM SHALL BE REQUIRED BY SECTION 804.2 OR THIS SECTION.

SECTION 904.2 FIRE ALARM AND DETECTION SYSTEMS. FIRE ALARM AND DETECTION SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 907 OF THE INTERNATIONAL BUILDING CODE AS REQUIRED FOR NEW CONSTRUCTION.

SECTION 906.2 TYPE B DWELLING OR SLEEPING UNITS. WHERE FOUR OR MORE GROUP I-1, I-2, R-1, R-2, R-3, OR R-4 DWELLING OR SLEEPING UNITS ARE BEING ALTERED, THE REQUIREMENTS OF SECTION 1107 OF THE INTERNATIONAL BUILDING CODE FOR TYPE B UNITS AND CHAPTER 9 OF THE INTERNATIONAL BUILDING CODE FOR VISIBLE ALARMS APPLY ONLY TO THE QUANTITY OF THE SPACES BEING ALTERED. EXCEPTION: GROUP I-1, I-2, R-2, R-3, AND R-4 DWELLING OR SLEEPING UNITS WHERE THE

FIRST CERTIFICATE OF OCCUPANCY WAS ISSUED BEFORE MARCH 15TH, 1991 ARE NOT REQUIRED TO PROVIDE TYPE B DWELLING OR SLEEPING UNITS.

SECTION 908.1 MINIMUM REQUIREMENTS. LEVEL 3 ALTERATIONS TO EXISTING BUILDINGS OR STRUCTURES ARE PERMITTED WITHOUT REQUIRING THE ENTIRE BUILDING OR STRUCTURE TO COMPLY WITH THE ENERGY REQUIREMENTS OF THE INTERNATIONAL ENERGY CONSERVATION CODE OR INTERNATIONAL RESIDENTIAL CODE. THE ALTERATIONS SHALL CONFIRM TO THE ENERGY REQUIREMENTS OF THE INTERNATIONAL ENERGY CONSERVATION CODE OR INTERNATIONAL RESIDENTIAL CODE AS

THEY RELATE TO NEW CONSTRUCTION ONLY.

FE

SYMBOL ITEM

FIRE EXTINGUISHER

EXIT SIGN W/ EGRESS LIGHTS

EGRESS LIGHTING

TRAVEL DISTANCE

1 HOUR WALL

2 HOUR WALL

COMPLIANCE LEGEND

EDUCATION

INSTITUTIONAL

NOT IN SCOPE

EGRESS TRAVEL

DISTANCE = 25'

EGRESS TRAVEL

DISTANCE = 21'

EGRESS TRAVEL

DISTANCE = 36'

EGRESS TRAVEL

DISTANCE = 25'

EGRESS TRAVEL

DISTANCE = 33'

EGRESS TRAVEL

DISTANCE = 39'

EGRESS TRAVEL

DISTANCE = 36'

3235 SF

EDUCATIONAL

658 SF

EDUCATIONAL

770 SF

EDUCATIONAL

Not

Enclosed

INSTITUTIONAL I-4

99 SF

INSTITUTIONAL I-4

212 SF

INSTITUTIONAL I-4

88 SF

STORAGE

253 SF

NOT IN SCOPE

217 SF

NOT IN SCOPE

CHILDREN AGES 2-4

PLANNED OCCUPANCY = 93

CHILDREN AGES 2-4

PLANNED OCCUPANCY = 22

INFANTS ROOM

PLANNED OCCUPANCY = 19

1. ENSURE EXIT SIGNS ARE MOUNTED ABOVE THE DOORS AND VISIBLE FROM 75 FEET AWAY. ALL EGRESS LIGHTING IS TO POINT

DOWN TO ILLUMINATE THE EGRESS PATH OF TRAVEL.

2. ALL FIRE EXTINGUISHERS ARE TO BE ABC EXTINGUISHERS, UNLESS NOTED OTHERWISE. ALL EXTINGUISHERS ARE TO BE TAGGED

WITH THE CURRENT YEAR'S INSPECTION ON IT. ANNUAL INSPECTIONS ARE TO OCCUR FOR ALL FIRE EXTINGUISHERS.

3. PROVIDE ADA RESTROOM SIGNS AT ALL RESTROOMS, CORRESPONDING TO THE CORRECT SEX.

4. SEE T002 FOR MOUNTING HEIGHTS AND LOCATIONS

5. SEE T003 FOR ADDITIONAL CODE COMPLIANCE INFORMATION

6. FURNITURE AND EQUIPMENT SHOWN ON COMPLIANCE DRAWINGS ARE FOR REFERENCE ONLY

CHAPTER 7: FIRE AND SMOKE PROTECTION

SECTION 708.3 EXCEPTION 1: CORRIDOR WALLS PERMITTED TO HAVE A 1/2 HOUR FIRE RESISTANCE RATING BY TABLE 1020.1.

TABLE 716.5 OPENINGS IN ONE HOUR FIRE BARRIERS FOR SHAFTS, EXIT ACCESS STAIRWAYS, AND INTERIOR EXIT STAIRWAYS ARE

TO HAVE ONE HOUR FIRE DOORS

CHAPTER 12: INTERIOR ENVIRONMENT

SECTION 1208.2 OCCUPIABLE SPACES, HABITABLE SPACES, AND CORRIDORS SHALL HAVE A CEILING HEIGHT OF NOT LESS THAN

7'-6". BATHROOMS, TOILET ROOMS, KITCHENS, STORAGE ROOMS, AND LAUNDRY ROOMS SHALL HAVE A CEILING HEIGHT OF

NOT LESS THAN 7'-0".

EXCEPTION 4: CORRIDORS CONTAINED WITHIN A DWELLING UNIT OR SLEEPING UNIT IN A GROUP R OCCUPANCY SHALL HAVE

A CEILING HEIGHT OF NOT LESS THAN 7'-0".

CODE COMPLIANCE GENERAL NOTES

© 2024 Driven Design Studio, All Rights Reserved.

Driven Design Studio PLLC

117 West Michigan Avenue

Battle Creek, MI 49017

(269) 753-8040 cody@drivendesignstudio.com

PROJECT NUMBER

STAMP

SCALE

DATE

DRAWN BY

PROJECT ADDRESS

PROJECT NAME

ARCHITECTURE/INTERIOR DESIGN

THIS DOCUMENT IS THE EXCLUSIVE

PROPERTY OF DRIVEN DESIGN. THE

DOCUMENT & THE INFORMATION IT

CONTAINS MAY NOT BE REPRODUCED

OR USED FOR OTHER THAN THE

SPECIFIC PROJECT FOR WHICH IT WAS

PREPARED WITHOUT THE EXPLICIT

CONSENT OF DRIVEN DESIGN.

OWNER

ISSUE

10/17/2025 9:32:40 AM

As indicated

T005

CODE COMPLIANCE

VALENTINE CENTER

75 IRVING PARK DR, BATTLE CREEK, MI

49037

CMN

2025.024

City of Battle Creek

10 N Division St

Battle Creek, MI

(269) 966-3355

CONSTRUCTION DOCUMENTS

X

CODE COMPLIANCE

TOPIC SECTION ALLOWED/REQUIRED ACTUAL

APPLICABLE CODES

2021 MICHIGAN BUILDING CODE

2021 MICHIGAN MECHANICAL

CODE

2021 MICHIGAN PLUMBING CODE

2021 MICHIGAN REHABILITATION

CODE

604 LEVEL III ALTERATION WORK AREA EXCEEDS 50% OF TOTAL BUILDING AREA

2021INTERNATIONAL FIRE CODE

2023 MICHIGAN ELECTRICAL CODE

ANSI/ASHRAE 90.1-2019

ICC/ANSI 117.1-2017

NFPA 101 (2021) / NFPA 13 (2019)

ZONING

ZONING CITY OF

BATTLE

CREEK

GRN - GREEN

1 - SCOPE AND ADMIN

DEFERRED SUBMITTALS 107.3.4.1 THERE ARE NO DEFERRED SUBMITTALS FOR THIS

PROJECT

DESIGN PROFESSIONAL IN CHARGE 107.3.4 CODY NEWMAN IS TO BE THE DESIGN PROFESSIONAL

IN CHARGE

SPECIAL INSPECTIONS 110 THERE ARE NO SPECIAL INSPECTIONS FOR THIS

PROJECT

5 - GENERAL BUILDING HEIGHTS AND AREAS

ALLOWABLE BUILDING HEIGHT TABLE

504.3

65 FEET 20 FEET AT MAX.

BASE STORIES ALLOWED TABLE

504.4

3 STORIES 1 STORY

TABULAR AREA TABLE

506.2

23,500 SF 7,576 SF

6 - TYPE OF CONSTRUCTION

TYPE OF CONSTRUCTION TABLE

III-A

7 - FIRE AND SMOKE PROTECTION

SMOKE AND CARBON MONOXIDE DETECTORS

REQUIRED THROUGHOUT

9 - FIRE PROTECTION SYSTEMS

AUTOMATIC SPRINKLER SYSTEM 903.2.1.3 LESS THAN 12,000 SF, NOT REQUIRED 7,149 SF, NOT REQUIRED

FIRE ALARM AND DETECTION

SYSTEMS

907 MANUAL FIRE ALARM REQUIRED AT MIN. PROVIDED

27 - ELECTRICAL

EMERGENCY LIGHTING 1008.1 WILL COMPLY ON COMPLIANCE DRAWINGS

EMERGENCY POWER 1008.3.2,

1008.3.3

WILL COMPLY ON COMPLIANCE DRAWINGS

EXIT SIGNS 1011.1 WILL COMPLY ON COMPLIANCE DRAWINGS

28 - PLUMBING

TABLE 403.1

PLUMBING

CLASS OCCUPANCY

WATER CLOSETS LAVATORIES DRINKING FOUNTAINS

REQUIRED PROVIDED REQUIRED PROVIDED REQUIRED PROVIDED

I-4 190 7 MALE / 7 FEMALE SEE BELOW 7 MALE / 7 FEMALE SEE ELOW 2 REQUIRED SEE BELOW

10 - OCCUPANCY

OCCUPANCY TYPE AREA OCCUPANCY

INSTITUTIONAL

DAY CARE 5062 SF 147

NOT IN SCOPE

DAY CARE 469 SF 15

5531 SF 162

10 - MEANS OF EGRESS

TOTAL

OCCUPANCY

DOOR EGRESS WIDTH 1005.3.2

EXIT ACCESS TRAVEL DISTANCE

TABLE 1017.2

NUMBER OF EXITS TABLE

1006.3.1 STAIR EGRESS WIDTH 1005.3.1

REQUIRED PROVIDED ALLOWED PROVIDED REQUIRED PROVIDED REQUIRED PROVIDED

190 38" 38" 200 FEET 50 2 EXITS 6 EXITS 57" N/A

1/8" = 1'-0"T005

1 FIRST FLOOR COMPLIANCE PLAN

3 - BUILDING AREA BY USE

OCCUPANCY TYPE PERCENTAGE OF PROJECT AREA

FLOOR

INSTITUTIONAL 92% 5062 SF

NOT IN SCOPE 8% 469 SF

100% 5531 SF

Grand total 100% 5531 SF

LICENSING RULES FOR CHILD CARE CENTERS

LICENSING AND REGULATORY AFFAIRS (LARA)

BUREAU OF COMMUNITY AND HEALTH SYSTEMS

CHILD CARE LICENSING DIVISION

R 400.8350 TOILETS; HAND WASHING SINKS.

RULE 350

(1) A CENTER SHALL PROVIDE TOILET AND HAND WASHING SINKS AS FOLLOW

(A) A CENTER OPERATING WITH CHILDREN IN ATTENDANCE LESS THAN 5

CONTINUOUS HOURS A DAY SHALL PROVIDE AT LEAST 1 TOILET AND

WASHING SINK FOR EVERY 20 CHILDREN OR FRACTION THEREOF.

(B) A CENTER OPERATING WITH CHILDREN IN ATTENDANCE 5 OR MORE

CONTINUOUS HOURS A DAY SHALL PROVIDE AT LEAST 1 TOILET AND

WASHING SINK FOR EVERY 15 CHILDREN OR FRACTION THEREOF.

CHILD OCCUPANT LOAD: 134 OCCUPANTS

9 CHILDREN'S WATER CLOSETS REQUIRED

9 CHILDREN'S SINKS REQUIRED

9 CHILDREN SINKS PROVIDED + 2 ADULT SINKS W/STOOLS = 11 TOTAL

10 CHILDREN TOILETS PROVIDED + 1 ADULT TOILETS = 11 TOTAL

CORRIDOR

WOMENS

RESTROOM

STORAGE

INFANT AREA

STORAGE

MENS RESTROOM

STAFF RESTROOM

MECH ROOM

OFFICE

VESTIBULE

LOBBY

OFFICE

KITCHEN

3-4 YR OLDS AREA

STORAGE

RESTROOM

= COMMON AREAS/ ANCILLARY SPACES

NO LAYOUT CHANGES - 1,421 SQ.FT.

= STAFF/ OFFICE - NO LAYOUT CHANGES

199 SQ.FT.

= NEW RESTROOM LAYOUTS

525 SQ.FT.

= CHILD CARE AREA - SOME LAYOUT CHANGES

4,664 SQ. FT.

= NEW KITCHEN / LAUNDRY LAYOUT

390 SQ.FT.

© 2024 Driven Design Studio, All Rights Reserved.

Driven Design Studio PLLC

117 West Michigan Avenue

Battle Creek, MI 49017

(269) 753-8040 cody@drivendesignstudio.com

PROJECT NUMBER

STAMP

SCALE

DATE

DRAWN BY

PROJECT ADDRESS

PROJECT NAME

ARCHITECTURE/INTERIOR DESIGN

THIS DOCUMENT IS THE EXCLUSIVE

PROPERTY OF DRIVEN DESIGN. THE

DOCUMENT & THE INFORMATION IT

CONTAINS MAY NOT BE REPRODUCED

OR USED FOR OTHER THAN THE

SPECIFIC PROJECT FOR WHICH IT WAS

PREPARED WITHOUT THE EXPLICIT

CONSENT OF DRIVEN DESIGN.

OWNER

ISSUE

10/17/2025 9:32:44 AM

1/8" = 1'-0"

T006

AREA PLANS

VALENTINE CENTER

75 IRVING PARK DR, BATTLE CREEK, MI

49037

CMN

2025.024

City of Battle Creek

10 N Division St

Battle Creek, MI

(269) 966-3355

CONSTRUCTION DOCUMENTS

X

1/8" = 1'-0"T006

1 FIRST FLOOR AREA PLAN

AXIS 4-MEGAPIXEL OUTDOOR CAMERA OR EQUIVALENT

AXIS 2-MEGAPIXEL INDOOR CAMERA OR EQUIVALENT

SECURITY LEGEND

OUTDOOR LED LIGHT FIXTURE

*SECURITY PLANS ARE SHOWN SCHEMATICALLY, A

SECURITY CONSULTANT TO ENSURE ALL AREAS OUTSIDE

OF THE BATHROOMS ARE VISIBLE ON THE INTERIOR AND

EXTERIOR BY CAMERAS

MONITOR AND PRINTER

DVR LOCKBOX

LIMITED ACCESS AREA

RESTRICTED ACCESS AREA

PUBLIC ACCESS AREA

STORAGE

INFANT AREA

STORAGE

WOMENS

RESTROOM

MENS RESTROOM

STAFF RESTROOM

MECH ROOM

OFFICE

CORRIDOR

VESTIBULE

LOBBY

OFFICE

KITCHEN

STORAGE

RESTROOM

3-4 YR OLDS AREA

EXIT/ STORAGE

CLASSROOM 2

CLASSROOM 3

EXIT / STORAGE

CLASSROOM 4

CLASSROOM 1

CORRIDOR

© 2024 Driven Design Studio, All Rights Reserved.

Driven Design Studio PLLC

117 West Michigan Avenue

Battle Creek, MI 49017

(269) 753-8040 cody@drivendesignstudio.com

PROJECT NUMBER

STAMP

SCALE

DATE

DRAWN BY

GENERAL NOTES

PROJECT ADDRESS

PROJECT NAME

ARCHITECTURE/INTERIOR DESIGN

THIS DOCUMENT IS THE EXCLUSIVE

PROPERTY OF DRIVEN DESIGN. THE

DOCUMENT & THE INFORMATION IT

CONTAINS MAY NOT BE REPRODUCED

OR USED FOR OTHER THAN THE

SPECIFIC PROJECT FOR WHICH IT WAS

PREPARED WITHOUT THE EXPLICIT

CONSENT OF DRIVEN DESIGN.

OWNER

ISSUE

10/17/2025 9:32:46 AM

As indicated

T007

SECURITY PLAN

VALENTINE CENTER

75 IRVING PARK DR, BATTLE CREEK, MI

49037

CMN

2025.024

City of Battle Creek

10 N Division St

Battle Creek, MI

(269) 966-3355

CONSTRUCTION DOCUMENTS

X

1/8" = 1'-0"T007

1 FIRST FLOOR SECURITY PLAN

EXISTING SECURITY SHOWN FOR REFERENCE, THE SECURITY IS TO BE MONITORED BY THE CITY OF BATTLE CREEK.

EXISTING POND TO REMAIN

EXISTING BUILDING TO REMAIN

EXISTING PARKING TO REMAIN

EXISTING SIDEWALK TO REMAIN

EXISTING GREENSPACE TO REMAIN

EXISTING GREENSPACE TO REMAIN

EXISTING FENCE TO REMAIN TYP.

IR

V

IN

G

P A

R K

D R

EXISTING KNOX BOX

REMOVE AND DISPOSE OF ALL

EXISTING PLAYGROUND EQUIPMENT

M

IN

10' - 0" MAX. 10' - 0" MAX.

TENSION BANDS

TENSION BAR

3 - 1/2" DIA. TERMINAL

POST (GALVANIZED

STEEL PIPE)

CORNER POST CAP (TYP.)

RAIL END ASSEMBLY LINE POST CAP (TYP.) 1-3/4" DIA. TOP RAIL

(GALVANIZED STEEL PIPE)

4' - 0" - 9 GA. 2"

MESH GALV. CHAIN

LINK FENCE

# 6 GA. TENSION WIRE

6" DIA. 6,000 P.S.I. (28

DAYS) CONCRETE PIER

ATEACH POST (TYP.)

GRANULAR MATERIAL

EXISTING GRADE

8" DI. 6,000 P.S.I. (28

DAYS) CONCRETE PIERS

AT CORNER POSTS (TYP.)

M A

X

1' - 0"

REPLACE DAMAGED FENCING AS REQUIRED

© 2024 Driven Design Studio, All Rights Reserved.

Driven Design Studio PLLC

117 West Michigan Avenue

Battle Creek, MI 49017

(269) 753-8040 cody@drivendesignstudio.com

PROJECT NUMBER

STAMP

SCALE

DATE

DRAWN BY

PROJECT ADDRESS

PROJECT NAME

ARCHITECTURE/INTERIOR DESIGN

THIS DOCUMENT IS THE EXCLUSIVE

PROPERTY OF DRIVEN DESIGN. THE

DOCUMENT & THE INFORMATION IT

CONTAINS MAY NOT BE REPRODUCED

OR USED FOR OTHER THAN THE

SPECIFIC PROJECT FOR WHICH IT WAS

PREPARED WITHOUT THE EXPLICIT

CONSENT OF DRIVEN DESIGN.

OWNER

ISSUE

10/17/2025 9:32:47 AM

As indicated

C100

ARCHITECTURAL SITE PLAN AND DETAILS

VALENTINE CENTER

75 IRVING PARK DR, BATTLE CREEK, MI

49037

CMN

2025.024

City of Battle Creek

10 N Division St

Battle Creek, MI

(269) 966-3355

CONSTRUCTION DOCUMENTS

X

1. EXISTING BUILDING TO REMAIN ON THE EXISTING SITE

2. THE UTILITIES THAT ARE CURRENTLY CONNECTED TO THE BUILDING ARE TO REMAIN

3. CONTACT MISS DIG TO LOCATE ALL EXISTING UTILITIES BEFORE DOING ANY SITE WORK

4. EXISTING VEGETATION TO REMAIN ON THE SITE, TRIM AS REQUIRED

5. REUSE THE EXISTING KNOX BOX AT THE BUILDING ENTRY. REPLACE THE KEYS AS REQUIRED.

6. WORK WITHIN THE STREET TO BE DONE IN ACCORDANCE WITH THE REQUIREMENTS OF THE AGENCIES HAVING

JURISDICTION.

7. PERMITS, TESTING, BONDS & INSURANCES ETC., SHALL BE PAID FOR BY THE CONTRACTOR. CITY INSPECTION

FEES SHALL BE PAID FOR BY THE OWNER.

PARKING REQUIREMENTS

ADULT AND CHILD DAYCARE FACILITIES: 2 SPACES, PLUS 1 SPACE PER 8 ADULTS OR CHILDREN OF LICENSED

AUTHORIZED CAPACITY; PLUS, 1 DROP-OFF SPACES PER 8 ADULTS OR CHILDREN OF LICENSED AUTHORIZED

CAPACITY.

THE EXISTING PARKING LOT IS TO REMAIN, IT IS OWNED BY THE CITY OF BATTLE CREEK AND THERE ARE NO

PROPOSED CHANGES TO THE LOT.

1" = 20'-0"C100

1 SITE PLAN

3/4" = 1'-0"C100

2 CHAIN LINK FENCE

LANDSCAPE REQUIREMENTS

"WHENEVER ANY YARD (FRONT, SIDE, OR REAR) OF A USE OTHER THAN SINGLE OR TWO-FAMILY RESIDENTIAL, IS NOT DESIGNATED FOR A BUILDING, OFF-STREET PARKING, LOADING OR UNLOADING, OR OTHER PURPOSE

REQUIRED BY THE ZONING DISTRICT REQUIREMENTS, SUCH YARD SHALL BE IMPROVED WITH EITHER NATURAL OR

LIVING GROUNDCOVER INCLUDING GRASS, PLANT MATERIAL, ROCKS, STONES, MULCH, ETC."

LEGAL DESCRIPTION

WILLIS ADD POB 66 FT N OF NE COR LOT 15-N 578 FT-NELY 648 FT-W 1101.5 FT-S 714FT-W 96.5FT-S 1 32FT-W 66FT-S

66FT-W 66 FT-S 280 FT-E 1176 FT TO POB 30 AC +/- ACRES M/L

GENERAL NOTES

VESTIBULE

CRAFTS AND

WARMING CENTER

STORAGE

MENS RESTROOM

WOMENS

RESTROOM

KITCHEN

OFFICE

STORAGE

WOMENS

RESTROOM

READING ROOM

STORAGE

MENS RESTROOM

CORRIDOR

MECH ROOM

COAT CLOSET

LOBBY

RECREATION

ROOM

CORRIDOR

45' - 0 5/8"

/2

29' - 2 1/4"12' - 0 1/2"

/4

/4

/8

/8

/4

10' - 6 1/4" 18' - 5 1/4"

19' - 0 1/4"8' - 11"16' - 7 3/8"9' - 10 3/8"

73' - 3 1/2"

45' - 2"13' - 4 1/2"

/2

/8

© 2024 Driven Design Studio, All Rights Reserved.

Driven Design Studio PLLC

117 West Michigan Avenue

Battle Creek, MI 49017

(269) 753-8040 cody@drivendesignstudio.com

PROJECT NUMBER

STAMP

SCALE

DATE

DRAWN BY

GENERAL NOTES

PROJECT ADDRESS

PROJECT NAME

ARCHITECTURE/INTERIOR DESIGN

THIS DOCUMENT IS THE EXCLUSIVE

PROPERTY OF DRIVEN DESIGN. THE

DOCUMENT & THE INFORMATION IT

CONTAINS MAY NOT BE REPRODUCED

OR USED FOR OTHER THAN THE

SPECIFIC PROJECT FOR WHICH IT WAS

PREPARED WITHOUT THE EXPLICIT

CONSENT OF DRIVEN DESIGN.

OWNER

ISSUE

10/17/2025 9:32:47 AM

1/8" = 1'-0"

A000

EXISTING FLOOR PLANS

VALENTINE CENTER

75 IRVING PARK DR, BATTLE CREEK, MI

49037

CMN

2025.024

City of Battle Creek

10 N Division St

Battle Creek, MI

(269) 966-3355

CONSTRUCTION DOCUMENTS

X

EXISTING PLANS AND DIMENSIONS ARE SHOWN FOR REFERENCE ONLY

1/8" = 1'-0"A000

1 FIRST FLOOR EXISTING PLAN

REMOVE ALL FIXTURES

AND FINISHES IN THE

BATHROOMS

COMPLETELY

REMOVE ALL FIXTURES

AND FINISHES IN THE

BATHROOMS

COMPLETELY

REMOVE ALL

EXISTING CASEWORK,

FINISHES, AND

FIXTURES IN KITCHEN

REMOVE RAISED

PLATFORM AND

SUPPORTING

FEATURES

COMPLETELY

REMOVE ALL FIXTURES

AND FINISHES IN THE

BATHROOMS

COMPLETELY

GENERAL DEMOLITION NOTES

• REMOVE ALL EXISTING FLOORING BACK TO A LEVEL BASE

• REMOVE ALL WALL FINISHES BACK TO A LEVEL BASE OR PRIME

EXISTING WALLS AT THIS PHASE

• REMOVE AND DISPOSE OF ALL EXISTING CEILING GRIDS AND TILES

• REMOVE ALL PERMANENTLY MOUNTED EXTERIOR PLAYGROUND

EQUIPMENT AND DISPOSE OF AS REQUIRED

REMOVE ALL

EXISTING

CASEWORK,

FINISHES,

AND

CAMERA

SYSTEM

BASIS OF DESIGN, REMOVE

EXISTING ENTRY

STOREFRONT DOORS AND

REPLACE, ALTERNATE:

REPLACE GLAZING AS WELL

BASE BID IS TO RELOCATE DOOR

(103) TO NEW LOCATION AND

INFILL CURRENT LOCATION.

ALTERNATE IS TO LEAVE EXISTING

DOOR (103) IN CURRENT

LOCATION.

1. REMOVE ALL DASHED WALLS, WINDOWS, AND DOORS COMPLETELY.

2. OWNER TO REMOVE ALL FURNISHINGS/ EQUIPMENT THAT THEY WISH TO RETAIN FROM THE AREAS OF

DEMOLITION/ CONSTRUCTION PRIOR TO THE START OF CONSTRUCTION WORK IN EACH AREA. OWNER TO

COORDINATE WITH CONTRACTOR REGARDING THE TIME SCHEDULE FOR THIS TO BE COMPLETED.

3. PATCH AND FILL ANY HOLES IN THE WALL CAUSED BY THE REMOVAL OF DOORS, WINDOWS, OR WALLS TO

MATCH SURROUNDINGS.

4. CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL SURFACES NOT BEING REMODELED IN THE PROJECT AND

IN THE PATH OF THE CONTRACTORS TRAVEL, SETUP AND/ OR PROJECT MATERIAL STORAGE. THE CONTRACTOR

MUST RETURN THE AREAS DISTURBED AS REQUIRED FOR ACCESS TO ITS PRE-EXISTING CONDITION.

5. ANY HAZARDOUS MATERIALS ARE TO BE REMOVED BY A LICENSED PROFESSIONAL IN THE STATE OF

MICHIGAN.

6. ALL SAFETY ISSUES RELATED TO DEMOLITION ARE THE RESPONSIBILITY OF THE CONTRACTOR AND MUST

COMPLY WITH ALL STATE, LOCAL, ENVIRONMENTAL AND LABOR LAWS DURING THE CONSTRUCTION OF THIS

PROJECT.

7. SEQUENCE DEMOLITION WITH STRUCTURAL WORK TO ASSURE SAFETY, PROVIDE SHORING AS REQ'D TO

ENSURE SAFE CONDITIONS EXIST. SHORING IS NOT SHOWN ON PLANS. STRUCTURAL ELEMENTS ARE TO

REMAIN, UNLESS NOTED OTHERWISE, COORDINATE WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS.

8. ALL TRADES TO COORDINATE BETWEEN ONE ANOTHER TO AVOID CONFLICTS.

9. NOTATIONS ARE MADE IN VARIOUS PLACES ON THE DRAWINGS TO CALL ATTENTION TO DEMOLITION WHICH

IS REQUIRED. THESE DRAWINGS ARE NOT INTENDED TO SHOW EACH AND EVERY ITEM TO BE REMOVED.

CONTRACTOR SHALL REMOVE ALL MATERIALS RELATED TO THEIR RESPECTIVE TRADES AS REQUIRED TO PERMIT

THE CONSTRUCTION OF THE NEW WORK AS SHOWN.

10. THE CONTRACTOR SHOULD TAKE CARE DURING THE PROJECT TO NOT INTERRUPT THE USE IN AREAS NOT IN

SCOPE.

11. PRIOR TO ANY DIGGING ON OR AROUND THE SITE UTILITIES ARE TO BE LOCATED USING MISS DIG.

12. ALL RUBBISH AND DEBRIS FROM DEMOLITION IS TO BE REMOVED IMMEDIATELY FROM THE SITE AFTER

DEMOLITION. COORDINATE ALL DEMOLITION, DUMPSTER LOCATIONS, BARRICADING, PEDESTRIAN

PROTECTION MEASURES, ETC. WITH THE OWNER AND LOCAL MUNICIPALITY PRIOR TO COMMENCEMENT.

13. REMOVE ALL LIGHTING, WIRING, FIRE ALARM DEVICES, RECEPTACLES, AND SPEAKERS FROM WALLS AND

CEILINGS BEING REMOVED. COORDINATE WITH ARCHITECT AS REQUIRED. REMOVE ALL ABANDONED

EXPOSED CONDUIT AND WIRING BACK TO SOURCE. REMOVE WIRING BACK TO PANEL OR NEAREST

JUNCTION BOX. RE-LABEL CIRCUIT BREAKER AS SPARE, IN SCOPE OF WORK.

14. PROVIDE BLANK COVERPLATE OVER EMPTY OUTLET BOXES IF DEVICE IS REMOVED AND NOT REPLACED.

15. REMOVE ALL EXISTING HVAC, FIRE PROTECTION AND PLUMBING EQUIPMENT, PIPING BACK TO MAIN AND

ALL ASSOCIATED ACCESSORIES. SANITARY, STORM, AND VENT STACKS TO REMAIN, CAP ANY UNUSED AREAS.

16. SALVAGE MATERIALS AS REQUIRED IF PART OF THE SCOPE IS MATCHING MATERIALS OR INFILL MATERIALS AS

PART OF A RENOVATION PROJECT.

17. REMOVE ALL CEILINGS AND FLOOR FINISHES IN AREAS OF DEMOLITION U.N.O.

18. ALL EXISTING COLUMNS AND STRUCTURAL ELEMENTS TO REMAIN. ANY DISCREPANCIES THAT OCCUR IN THE

FIELD DURING DEMOLITION SHOULD BE BROUGHT TO THE ARCHITECT'S ATTENTION.

19. THE CONTRACTOR SHALL MAINTAIN THE JOB SITE TO BROOM CLEAN AT ALL TIMES.

20. THE OWNER WILL MAINTAIN OCCUPANCY OF SPACES ADJACENT TO AREAS OF DEMOLITION. THE

CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL POTENTIALLY DISRUPTIVE ACTIVITIES WITH THE

OWNER.

21. WHERE NEW ACT AND GYP. CEILING ARE SPECIFIED, EXISTING CEILINGS ARE TO BE REMOVED WHILE

SALVAGING AL EXISTING LIGHT FIXTURES. EXISTING LIGHT FIXTURES TO REMAIN IN OR NEAR EXACT

LOCATIONS THEY ARE SALVAGED FROM. CONTRACTOR TO COORDINATE AND GET APPROVAL OF

RECOMMENDED PLACEMENT OF EXISTING LIGHT FIXTURES FROM OWNER PRIOR TO INSTALLATION OF NEW

CEILINGS AND RE-INSTALLATION OF EXISTING LIGHT FIXTURES.

EXISTING WALL TO REMAIN

CONCRETE

WOOD BLOCKING

STEEL (LARGE SCALE)

PLASTER

RIGID INSULATION

PLYWOOD

ELEMENTS TO BE REMOVED

WALL LEGEND

CMU

EXTENT OF WORK

MILLWORK

2 HOUR PARTITION

1 HOUR PARTITION

MATERIAL LEGEND

© 2024 Driven Design Studio, All Rights Reserved.

Driven Design Studio PLLC

117 West Michigan Avenue

Battle Creek, MI 49017

(269) 753-8040 cody@drivendesignstudio.com

PROJECT NUMBER

STAMP

SCALE

DATE

DRAWN BY

PROJECT ADDRESS

PROJECT NAME

ARCHITECTURE/INTERIOR DESIGN

DEMOLITION NOTES

THIS DOCUMENT IS THE EXCLUSIVE

PROPERTY OF DRIVEN DESIGN. THE

DOCUMENT & THE INFORMATION IT

CONTAINS MAY NOT BE REPRODUCED

OR USED FOR OTHER THAN THE

SPECIFIC PROJECT FOR WHICH IT WAS

PREPARED WITHOUT THE EXPLICIT

CONSENT OF DRIVEN DESIGN.

OWNER

ISSUE

10/17/2025 9:32:47 AM

As indicated

A110

DEMOLITION PLANS

VALENTINE CENTER

75 IRVING PARK DR, BATTLE CREEK, MI

49037

CMN

2025.024

City of Battle Creek

10 N Division St

Battle Creek, MI

(269) 966-3355

CONSTRUCTION DOCUMENTS

X

1/8" = 1'-0"A110

1 FIRST FLOOR DEMOLITION PLAN

ALIGN

ALIGN

STORAGE

INFANT AREA

STORAGE

WOMENS

RESTROOM

MENS RESTROOM

STAFF RESTROOM

MECH ROOM

OFFICE

CORRIDOR

VESTIBULE

LOBBY

OFFICE

KITCHEN

RESTROOM

3-4 YR OLDS AREA

A130

A130

A130

EXIT/ STORAGE

118B

CR

108B

113C

112C

108A

118A

NOT IN SCOPE

NOT IN SCOPE

STORAGE

121 124

123122

113A 113B

112B

CLASSROOM 3

32' - 1 7/8" 10' - 0" 30' - 4"

23' - 11 7/8"

/4

/8

30' - 4"10' - 0"32' - 1 7/8"

CLASSROOM 2

EXIT / STORAGE

CLASSROOM 4

CLASSROOM 1

CORRIDOR

LAUNDRY ROOM

5' - 6"

NEW FENCE TO

SCREEN

MECHANICAL UNIT,

GC TO VERIFY

LENGTH NEEDED

/4

/2

/2

112A 3

PROVIDE

ACCESS

GATE

PROVIDE

ACCESS

GATE

B.O.D. NEW DOORS

IN EXISTING FRAMES,

ALTERNATE: PROVIDE

NEW GLAZING AND

DOORS

CR

100 101

4"2' - 9"4"2' - 9"

4"2' - 9"4"2' - 9"

HSS4X4X3/8 STEEL

COLUMNS SET ON

18"X18"X42" FTG.

HSS4X4X3/8 STEEL

COLUMNS SET ON

18"X18"X42" FTG.

REBUILD PLANTER AS

REQUIRED AFTER

INSTALLATION OF NEW

COLUMNS, EA. SIDE

BASE BID IS TO RELOCATE

DOOR (103) TO NEW

LOCATION AND INFILL

CURRENT LOCATION.

ALTERNATE IS TO LEAVE

EXISTING DOOR (103) IN

CURRENT LOCATION.

1. ALL GYPSUM BOARD THROUGHOUT IS TO BE 5/8" TYPE-X AS A MINIMUM.

2. ALL EXISTING INTERIOR WALLS THAT ARE TO REMAIN ARE TO BE PATCHED AS REQUIRED FROM NEW UTILITIES

OR GENERAL CONSTRUCTION.

3. INFILL OF EXISTING WALL OPENINGS IS TO RESULT IN FLUSH FINISHES ON BOTH SIDES OF THE WALL. UNLESS

OTHERWISE NOTED, USE APPROPRIATE STUD FRAMING TO ACHIEVE DESIRED FINISH.

4. INSTALL WOOD BLOCKING IN WALLS AS NECESSARY FOR INSTALLATION OF ALL CASEWORK, MIRRORS, TOWEL

BARS, SHOWER CURTAIN RODS, TOILET PAPER DISPENSERS, PAPER TOWEL HOLDERS, TOILET PARTITIONS, RAILINGS, AND ANY OTHER ACCESSORIES.

5. DRAWINGS ESTABLISH THE DESIGN INTENT OF WORK TO BE PERFORMED. ALL PRODUCTS SHALL BE INSTALLED IN

ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ALL TRADES SHALL CAREFULLY

COORDINATE WORK OF ALL OTHER TRADES. CONTRACTORS SHALL BE RESPONSIBLE FOR FIELD VERIFYING

EXISTING CONDITIONS AND FOR VERIFYING THEM WITH THE CONTRACT DOCUMENTS. ANY DISCREPANCIES

OR CONFLICTS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT AND THE OWNER PRIOR

TO FABRICATION OR INSTALLATION.

6. VERIFY QUANTITY, SIZE, AND LOCATION OF ALL FLOOR, ROOF, AND WALL OPENINGS FOR ALL DISCIPLINES

INCLUDING BUT NOT RESTRICTED TO MECHANICAL AND ELECTRICAL WORK WITH THE APPROPRIATE TRADE.

PROVIDE ALL OPENINGS SHOWN OR REQUIRED FOR THE COMPLETION OF THE WORK. PROVIDE ALL LINTELS

REQUIRED FOR THESE OPENINGS PER SPECIFICATIONS.

7. DIMENSIONS PRECEDED BY +/- SHOULD BE REVIEWED AND ALL NECESSARY ADJUSTMENTS MADE PRIOR TO

FABRICATION AND/OR INSTALLATION OF AFFECTED WORK. NOTIFY ARCHITECT'S REPRESENTATIVE IF

DISCREPANCIES ARISE BEFORE PROCEEDING WITH THE WORK.

8. BATHROOM MIRRORS AND LIGHT FIXTURES ABOVE VANITIES SHALL BE CENTERED ON THE SINKS.

FRAMING DETAILS

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .