2025_02_27 McIntosh Campsite Civil.pdf
PDF 12 MB Posted
- Attached to
- Ft. Barrington Campsite
- Solicitation number
- PE-77896-NONST-2025-000000005
- Issued by
- Miller County, Georgia
About this file
This is a comprehensive site construction plan for the Barrington Campsite project prepared by Roberts Civil Engineering for McIntosh County, Georgia, located in Townsend, GA. The project involves developing a campground with multiple pull-through sites, including a 25-foot boat ramp extension, a 30'x40' pavilion, a 30'x50' playground, proposed restroom/shower facilities, and associated infrastructure. The site plan details 11 camping sites ranging from 25' x 80' to 25' x 120' pull-through sites, with specific provisions for electrical, water, and sewer connections. The project includes relocating power poles, installing landscape timbers, and developing traffic patterns with signage.
The site plan incorporates extensive utility infrastructure, including a septic system designed to handle approximately 3,150 gallons per day, with separate septic tanks for a dump station and bath house. The system utilizes 179 Eljen modules across two drainage fields, with water supplied through multiple 2" PVC water lines totaling approximately 2,500 linear feet. The project includes two water wells (primary and secondary), underground power distribution, and electrical connections for individual campsites. The site is located in a flood zone (Zone A and Zone X) and was surveyed in November 2023, with the construction documents dated February 27, 2025. The project appears to be funded by McIntosh County and is designed to enhance recreational infrastructure in the Townsend area.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Entry Portal Kiosk Specs.pdf | ||
| RV Pumpout Specs.pdf | ||
| RFP 2502_ Proposal Documents_2025_03_06.pdf | ||
| Advertisement for RFP.pdf | ||
| McIntosh Bathhouse REV1 Plan.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SITE
CONSTRUCTION
PLANS
BARRINGTON CAMPSITE
TOWNSEND, GA
CONTENTS
02/27/25: ORIGINAL ISSUE DATE
VICINITY MAP NTS
02/21/25
Know what's below.
before you dig.Call
R
REVISIONS
COVER
RCE PROJECT NUMBER: 19110
WWW.ROBERTSCIVILENGINEERING.COM
301 SEA ISLAND ROAD, SUITE 10
ST. SIMONS ISLAND, GA 31522
912-638-9681
6001 CHATHAM CENTER DRIVE, SUITE 255
SAVANNAH, GA 31405
912-298-7006
14600 WHIRLWIND AVENUE, SUITE 119A
JACKSONVILLE, FL 32218
904-741-0099
4000 FABER PLACE DRIVE, SUITE 300
NORTH CHARLESTON, SC 29405
843-323-4224
PREPARED FOR:
MCINTOSH COUNTY, GEORGIA
OWNER
MCINTOSH COUNTY
CONTACT
STEVE MELLINGER
STEVE.MELLINGER@MCINTOSHCOUNTY-GA.GOV
ENGINEER
ROBERTS CIVIL ENGINEERING
CONTACT
JEFF BORS
JBORS@ROBERTSCIVILENGINEERING.COM
TOWNSEND, GA
BARRINGTON CAMPSITE
COVER
STAKING PLAN
EXISTING CONDITIONS
GRADING PLAN
No. 034205
PROFESSIONAL
SITE
LAT: 31.472401
LONG:-81.606434
UTILITY PLAN
GENERAL NOTES
SEPTIC SYSTEM DETAILS7-9
DRY UTILITY PLAN10
WELL DETAILS11-12
N
02/27/25
02/27/25
02/27/25
02/27/25
02/27/25
02/27/25
02/27/25
02/27/25
02/27/25
SC
AL
E:
N
A
SHEET:
G
EN
ER
AL
N O
TE
S
RE
VI
SI
O
N S
ST
. S
IM
O
N S
IS
LA
N D
SA
VA
N
N
AH
JA
CK
SO
N
VI
LL
E
CH
AR
LE
ST
O
N W
W W
.R O
BE
RT
SC
IV
IL
EN
GI
N
EE
RI
N G.
CO
M
No. 034205
PROFESSIONAL
CH
EC
KE
D
BY
BE
DR
AW
N B
Y:
C
S
DA
TE
2/
/2
PR
O
JE
CT
N U
M
BE
R:
PR
EP
AR
ED
F O
R
MC
IN
TO
SH
C
OU
NT
Y
BA
R
R
IN
G
TO
N C
AM
PS
IT
E
TO
W
N
SE
N D
, G A
ADA NOTES:
1. THE CONTRACTOR IS RESPONSIBLE FOR ADHERING TO ALL CURRENT ADA REQUIREMENTS.
2. THE EXTERIOR ACCESSIBLE ROUTE SHALL HAVE A MINIMUM WIDTH OF 3 FEET. IF THE ACCESSIBLE ROUTE CLEAR WIDTH IS LESS THAN 5 FEET, THEN 5'X5' PASSING SPACES SHALL BE PROVIDED EVERY 200' OR LESS.
INTERSECTING SIDEWALKS MEET THIS REQUIREMENT.
3. THE FINISHED SURFACE HEIGHT DIFFERENCE REQUIREMENTS SHALL MEET THE FOLLOWING:
0 - 14" NO REQUIREMENTS
4"- 12"BEVEL WITH 1:2 SLOPE
GREATER THAN 12" CONFORM TO RAMP REQUIREMENTS
4. RAMPS SHALL MEET THE FOLLOWING CONSTRAINTS:
MAX SLOPE 1:12
MAX RAMP RISE IS 30"
MAX RAMP LENGTH IS 30'
MAX CROSS SLOPE IS 2.00%
5. RAMP LANDINGS SHALL MEET THE FOLLOWING CONSTRAINTS:
A MINIMUM 5' LONG LEVEL LANDING AT LEAST AS WIDE AS THE RAMP SHALL BE PLACED AT THE TOP AND BOTTOM
OF THE RAMP.
LANDING SHALL BE MINIMUM 5'X5' WHERE RAMP CHANGES DIRECTION.
LANDINGS SHALL NOT EXCEED A 2.00% SLOPE
6. HANDRAILS SHALL MEET THE FOLLOWING CONSTRAINTS:
IF RAMP RISE IS GREATER THAN 6", THEN HANDRAILS ARE REQUIRED ON BOTH SIDES OF RAMP.MINIMUM OF 12"
LONG HANDRAIL EXTENSIONS SHALL BE PROVIDED AT THE TOP AND BOTTOM OF LANDINGS.
GRADING & DRAINAGE NOTES:
1. STORM PIPES SHALL BE JOINED PER DOT SPECIFICATIONS.
2 ALL PIPE SHALL BE INSTALLED IN NEW CONDITION.
3. A RIGHT OF WAY WORK PERMIT MAY BE REQUIRED BEFORE ANY WORK CAN BE DONE IN THE RIGHT OF WAY.
4. ALL STORM DRAINAGE PIPING SHALL BE CONSTRUCTED PER DOT SPECS.
5. ALL STORM DRAINAGE PIPING JOINTS SHALL BE WRAPPED IN FILTER FABRIC.
6. CONTRACTOR TO REQUEST CONFIRMATION OF LATEST PLAN REVISION DATE FROM ENGINEER IN WRITING
PRIOR TO ORDERING MATERIALS,
7. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO REVIEW AND APPROVE SHOP DRAWINGS PRIOR TO
ORDERING MATERIALS.
EARTHWORK AND PAVING
1. CONTRACTOR TO REMOVE ALL UNSUITABLE MATERIAL BENEATH PROPOSED PAVEMENT AND BUILDINGS TO A DEPTH OF 3 FEET AND REPLACE WITH SUITABLE FILL. THIS ONLY APPLIES TO AREAS WHERE UNSUITABLE
MATERIAL IS PRESENT.
2. THE UPPER 12 INCHES OF SUBGRADE BELOW THE PAVEMENT AND BUILDINGS SHALL BE SCARIFIED AND RECOMPACTED TO 100% STANDARD PROCTOR MAX DRY WEIGHT DENSITY WITH A MOISTURE CONTENT WITHIN
2% OF THE OPTIMUM MOISTURE CONTENT.
3. IN AREAS WHERE STRUCTURAL FILL IS REQUIRED, THE FILL SHALL BE PLACED IN LIFTS OF 6 INCHES AND COMPACTED TO 100% STANDARD PROCTOR MAX DRY WEIGHT DENSITY. STRUCTURAL FILL SHALL CONSIST OF
GRANULAR SOIL CONTAINING LESS THAN 10% MATERIAL PASSING THE NO 200 SIEVE.
4. ALL FILLING AND EXCAVATION SHALL BE COMPLETED PRIOR TO THE INSTALLATION OF ANY UTILITIES.
5. CONTRACTOR TO PROVIDE TEST RESULTS OF SUBGRADE AND BASE COURSE COMPACTION TO ENGINEER.
GENERAL WATER NOTES:
1. PVC PIPE SHALL BE BLUE IN COLOR. PIPE 4" TO 12" SHALL CONFORM TO REQUIREMENTS OF AWWA C-900, DR
18 PRESSURE CLASS 235 PSI AND SHALL HAVE FOLLOWING MINIMUM WALL THICKNESS:
4" DIA - 0.267"
6" DIA - 0.383"
8" DIA - 0.503"
10" DIA - 0.617"
12" DIA - 0.733"
PIPE LESS THAN 4" IN DIAMETER SHALL CONFORM TO ASTM D-1784 AND D-2241 (SDR 21). PIPE SHALL HAVE A MINIMUM PRESSURE RATING OF 200 PSI. PVC PIPE SHALL BEAR NATIONAL SANITATION FOUNDATION SEAL
OF APPROVAL.
2. FITTINGS FOR PVC SHALL BE DUCTILE IRON IN ACCORDANCE WITH ANSI A-21.53 (AWWA C-153). FITTINGS SHALL BE CEMENT LINED IN ACCORDANCE WITH ANSI A-21,4 (AWWA C-104). FITTINGS LESS THAN 4" SHALL BE
PVC WITH RING TITE RUBBER JOINTS CONFORMING TO ASTM D-3139.
3. VALVES SHALL BE INSTALLED IN APPROVED UNDERGROUND VALVE BOXES OF DUCTILE IRON WITH A
SUITABLE CRUSHING STRENGTH FOR LOCATION INSTALLED.
4. MAINTAIN A 10' HORIZONTAL SEPARATION BETWEEN ANY EXISTING OR PROPOSED WATER MAIN AND
SANITARY SEWER, STORM SEWER, OR SEWER MANHOLE.
5. WHEN A 10' HORIZONTAL SEPARATION CANNOT BE MAINTAINED, WATER MAIN MAY BE LAID CLOSER TO SEWER PROVIDED THAT WATER MAIN IS LAID IN A SEPARATE TRENCH AT LEAST 18" ABOVE TOP OF SEWER.
6. WATER CROSSING A SEWER SHALL BE AT LEAST 18" ABOVE TOP OF SEWER. A FULL LENGTH (SECTION) OF WATER PIPE SHALL BE USED AT THESE CROSSINGS WITH ENDS OF WATER PIPE SECTION AS FAR AWAY
FROM SEWER AS POSSIBLE.
7. VERIFY SIZE AND LOCATION OF WATER SERVICES PRIOR TO CONSTRUCTION. NOTIFY ENGINEER OF ANY
DISCREPANCIES PRIOR TO ORDERING MATERIALS.
8. IF UTILITY CONFLICT IS ENCOUNTERED IN FIELD, SEE UTILITY CONFLICT DETAIL.
GENERAL SEWER NOTES:
1. PVC PIPE SHALL BE POLYVINYL CHLORIDE PLASTIC (PVC) AND SHALL MEET REQUIREMENTS OF ASTM D 3034 SDR 26. DEPTHS LESS THAN 3' SHALL BE DUCTILE IRON PIPE. ASTM D 2321 MUST BE FOLLOWED FOR INSTALLATION OF PVC PIPE. RUBBER RINGS SHALL BE USED FOR CONTRACTION AND EXPANSION AT EACH JOINT. FITTINGS SHALL MEET SAME SPECIFICATION REQUIREMENTS AS PIPE. TESTS ON PVC PIPE SHALL BE DESIGNED TO PASS TESTS AT 73° F. PIPE STANDARD LENGTHS SHALL BE 12.5' (PLUS OR MINUS 1"). PIPE
SIZES AND DIMENSIONS SHALL BE AS SHOWN IN THE TABLE BELOW:
NOM SIZE: OUTSIDE DIA: MIN WALL THICKNESS:
4" 4.215" 0.162" 6" 6.275" 0.241" 8" 8.400" 0.323" 10" 10.500" 0.404" 12" 12.500" 0.481"
2. JOINTS FOR PVC PIPE - SHALL BE INTEGRAL WALL BELL AND SPIGOT WITH A RUBBER RING GASKET. THE
JOINTS SHALL CONFORM TO ASTM D 3212 AND GASKETS SHALL CONFORM TO ASTM F 477.
3. PRECAST CONCRETE MANHOLES - SHALL BE REINFORCED CONCRETE CONSTRUCTED IN ACCORDANCE WITH ASTM C 478 AND DETAILS SHOWN ON PLANS. JOINTS SHALL BE TONGUE AND GROOVE SEALED WITH FLEXIBLE GASKETS OR MASTIC SEALANT. GASKETS SHALL BE O-RING OR EQUIVALENT TO TYPE A OR B "TYLOX" CONFORMING TO ASTM C 443. MASTIC SHALL BE EQUIVALENT TO "RAM-NEK" WITH PRIMER.
CONTACT SURFACES OF MANHOLE JOINT SHALL HAVE PRIMER IN ACCORDANCE WITH MANUFACTURER'S
INSTRUCTIONS.
4. FRAMES AND COVERS - SHALL BE EQUIVALENT OF NEENAH FOUNDRY CO. R-1668 TYPE "C" LID
5. MANHOLE STEPS - SHALL BE EQUIVALENT TO M.A. INDUSTRIES, TYPE PS-1 OF PS-2 OR IMCO REINFORCED PLASTICS, INC. MODEL FRP. STEPS SHALL BE INSTALLED AT MANHOLE FACTORY AND IN ACCORDANCE WITH
RECOMMENDATIONS OF STEP MANUFACTURER.
6. PIPE CONNECTIONS - SHALL HAVE FLEXIBLE WATERTIGHT JOINTS AT POINT OF ENTRY OF ANY SEWER MAIN INTO MANHOLE. JOINT SHALL BE WEDGED RUBBER SHAPE EQUIVALENT TO "PRESS WEDGE II," OR A RUBBER
SLEEVE EQUIVALENT TO "KOR-N-SEAL" OR 'LOCK JOINT."
7. #12 GAUGE SINGLE STRAND COPPER TRACING WIRE SHALL BE USED OVER ALL FORCE MAIN, SANITARY
SEWER, AND SERVICE LATERAL LINES.
8. SEWER EXCAVATIONS SHALL BE TO DESIRED DEPTHS SHOWN ON PLANS WITH ADHERENCE TO
OCCUPATIONAL AND SAFETY HEALTH ADMINISTRATION'S (OSHA) REGULATIONS. IN AREAS OF UNSUITABLE SOIL CONDITIONS, TRENCH MAY REQUIRE ADDITIONAL EXCAVATION AND BACKFILL WITH SAND, GRAVEL, OR
CONCRETE.
9. SEWER PIPES SHALL BE LAID UPGRADE WITH SPIGOTS POINTING DOWNGRADE. ASSEMBLY OF JOINTS SHALL COMPLY WITH MANUFACTURER'S RECOMMENDATIONS. SEAL OPEN ENDS OF PIPES IF INSTALLATION IS INTERRUPTED. MANHOLE CONNECTIONS SHALL BE WATER TIGHT WITH USE OF FLEXIBLE WATER STOPS AND
RESILIENT CONNECTORS.
10. MANHOLES SHALL HAVE A NON-SHRINK GROUT CHANNEL IN BOTTOM THAT IS SMOOTH, ROUNDED, AND SHAPED TO FACILITATE GRAVITY SEWER FLOW TOWARDS OUTGOING PIPE. CHANNEL WIDTH SHALL MATCH PIPING SIZE. INVERT OF CHANNEL SHALL BE UNIFORMLY SLOPED BETWEEN INCOMING AND OUTGOING PIPES. TOP OF BENCH SHALL MATCH TOP OF LARGEST PIPE. SLOPE TOP OF BENCH 1" PER FOOT TOWARDS
CHANNEL
11. MANHOLE TOP ELEVATIONS SHALL BE GREATER THAN OR EQUAL TO FIFTY (50) YEAR FLOOD ELEVATION, UNLESS WATERTIGHT COVERS ARE PROVIDED. OUTSIDE OF PAVED AREAS, MANHOLE TOP ELEVATION SHALL BE 1" ABOVE GROUND SURFACE IN DEVELOPED AREAS AND 6" ABOVE GROUND SURFACE IN UNDEVELOPED AREAS UNLESS SHOWN OTHERWISE ON PLANS. MANHOLES IN PAVED AREAS SHALL BE BUILT
AS DESIGNATED BY ENGINEER. NO LEAKS IN MANHOLES ARE ACCEPTABLE.
GENERAL NOTES:
1. CONSTRUCTION METHODS AND MATERIALS SHALL CONFORM TO APPLICABLE FEDERAL, STATE, AND LOCAL
LAWS.
2. PERMITS NECESSARY FOR CONSTRUCTION SHALL BE OBTAINED BY CONTRACTOR.
3. DEVIATIONS FROM PLANS ARE PROHIBITED WITHOUT WRITTEN CONSENT OF THE ENGINEER.
4. CONTRACTOR IS TO IMMEDIATELY CONTACT ENGINEER IF ANY UNFORESEEN CONDITIONS OR
DISCREPANCIES OCCUR.
5. CONTRACTOR SHALL COORDINATE CONSTRUCTION OF UTILITIES ON SITE WITH APPROPRIATE PROVIDER
(I.E., POWER, PHONE, CABLE, ETC.).
6. ENGINEER IS NOT RESPONSIBLE FOR PHYSICAL CONSTRUCTION OF SITE.
7. CONTRACTOR SHALL MAINTAIN A SAFE SITE AND MEET APPROPRIATE REGULATIONS CONCERNING SAFETY.
8. SURVEY DATA PROVIDED BY SHUPE SURVEYING COMPANY, PC.
A. DATE OF SURVEY 2023-11-29
B. SURVEYOR PROJECT OR FILE NO. 23542
9. EXISTING SURVEY INFORMATION TO BE VERIFIED BY CONTRACTOR PRIOR TO CONSTRUCTION.
CONTRACTOR TO NOTIFY ENGINEER OF DISCREPANCIES IN FIELD OBSERVATIONS VERSUS SURVEY DATA.
10. CONTRACTOR TO LOCATE UTILITIES PRIOR TO CONSTRUCTION BY CALLING "CALL BEFORE YOU DIG"
HOTLINE: 811.
11. ACCORDING TO FEMA FLOOD INSURANCE RATEMAPS 13299C0234D DATED 09/25/2009. SITE IS LOCATED IN 100
YEAR FLOODPLAIN IN ZONE X.
12. HORIZONTAL DATUM BASED ON GEORGIA STATE PLANE COORDINATE SYSTEM, EAST ZONE NAD83.
PROJECT NOTES:
1. OWNER / DEVELOPER:
A. NAME: MCINTOSH COUNTY
B. CONTACT: STEVE MELLINGER
2. COUNTY NAME AND PARCEL / TAX MAP NUMBER(S): MCINTOSH / 0007 0002
3. ZONING CLASSIFICATION: (R-75MH) RESIDENTIAL MANUFACTURED HOMES
02/21/25
N:535,644.57 E:830,230.92
ZONE A
ZONE X
APPROXIMATE LOCATION OF
FLOOD HAZARD LINE
EDGE OF WATER
TOP OF BANK
N:535,950.24 E:830,867.29
.8
6'
S 79°32'19" E
773.05'
N 74°47'24" W 504.72'
S 48°3 7'56" W
94.60'
N 88°25'34" W
204.80'
N 09°03'54" W
107.01'
N 4 3°
'19
" E
.5
6'
4.
345.61'
52.71'
374.73'
S
3°
'0 6"
W
3.
S 70°56'05" W
166.05'130.97'
35.08'
PROPERTY BOUNDARY
PROPERTY BOUNDARY
EXISTING RESTROOM TO BE REMOVED
SC
AL
E:
' (F O
R
"X
" P
LO
T)
CH
EC
KE
D
BY
BE
SHEET:
Know what's below.
before you dig.Call
R
DR
AW
N B
Y:
C
S
LEGEND
EXISTING CONCRETE
EXISTING SPOT ELEVATION
EXISTING OVERHEAD UTILITY
EXISTING CONTOUR
PR
O
JE
CT
N U
M
BE
R:
PR
EP
AR
ED
F O
R
MC
IN
TO
SH
C
OU
NT
Y
EX
IS
TI
N
G C
O N
D
IT
IO
N
S
PL
AN
RE
VI
SI
O
N S
ST
. S
IM
O
N S
IS
LA
N D
SA
VA
N
N
AH
JA
CK
SO
N
VI
LL
E
CH
AR
LE
ST
O
N W
W W
.R O
BE
RT
SC
IV
IL
EN
GI
N
EE
RI
N G.
CO
M
GRAPHIC SCALE
1" = 40'
80'0' 40'
N
No. 034205
PROFESSIONAL
BA
R
R
IN
G
TO
N C
AM
PS
IT
E
TO
W
N
SE
N D
, G A
FLOOD LINE
PROPERTY BOUNDARY
DA
TE
2/
/2
ZONE A
ZONE X
APPROXIMATE LOCATION OF
FLOOD HAZARD LINE
EDGE OF WATER
TOP OF BANK
N:535,950.24 E:830,867.29
.8
6'
S 79°32'19" E
773.05'
N 74°47'24" W 504.72'
S 48°3 7'56" W
94.60'
N 88°25'34" W
204.80'
N 09°03'54" W
107.01'
N 4 3°
'19
" E
.5
6'
4.
345.61'
52.71'
374.73'
S
3°
'0 6"
W
3.
S 70°56'05" W
166.05'130.97'
35.08'
S 70°56'05" W
S 48°37'56" W
94.60'
R 5'
R15'
R 5'
R15'
R5
R75'
R10'
R10'
R10'
R10'
R15'
R5
R2'
R10'
R10'
R15'
R15'
R15'
R35'
R20'
R5'
R10'
R10'
R41' R23'
R34'
R55'
R102'
R58'
R43' R63'
R10'
R10
R 43'
R 63'
R
R10
R10
R1 0'
R50'
R1
R 10'
R6 5'
R89'
R17'
R70'
R 1'
R
1'
R10'R 156'
R 171'
R131'
R116'
R1
R5'
PROPOSED 30'X40' PAVILLION
PROPOSED 30'X50' PLAYGROUND
ARROW USED FOR TRAFFIC PATTERN.
NO STRIPING REQUIRED. (TYP)
POWER POLE
TO BE RELOCATED
POWER POLE
TO BE RELOCATED
POWER POLE
TO BE RELOCATED
BOAT AND TRAILER
PARKING
VEHICLE PARKING ONLY
TRAFFIC SIGN (TYP.)
PROPOSED RESTROOM/SHOWER
LANDSCAPE TIMBER (TYP.)
PROPOSED 15'X15' PAVILLION
TO BE INSTALLED BY OTHERS
TO BE INSTALLED BY OTHERS
25' x 100' Pull - Thru Site
(HO
ST SITE)
25' x 100' Pull - Thru Site
25' x 80' Pull - Thru Site
25' x 120' Pull - Thru Site
25' x 100' Pull - Thru Site
25' x 100' Pull - Thru Site
25' x 100' Pull - Thru Site
25' x 80' Pull - Thru Site
25' x 120' Pull - Thru Site 25' x 120' Pull - Thru Site
25' BOAT RAMP EXTENSION
PROPERTY BOUNDARY
PROPERTY BOUNDARY
SC
AL
E:
' (F O
R
"X
" P
LO
T)
SHEET:
Know what's below.
before you dig.Call
R
ST
AK
IN
G
P
LA
N
RE
VI
SI
O
N S
ST
. S
IM
O
N S
IS
LA
N D
SA
VA
N
N
AH
JA
CK
SO
N
VI
LL
E
CH
AR
LE
ST
O
N W
W W
.R O
BE
RT
SC
IV
IL
EN
GI
N
EE
RI
N G.
CO
M
GRAPHIC SCALE
1" = 40'
80'0' 40'
N
LEGEND
PROPOSED GRAVEL DRIVEWAY
EXISTING CONCRETE
No. 034205
PROFESSIONAL
CH
EC
KE
D
BY
BE
DR
AW
N B
Y:
C
S
PR
O
JE
CT
N U
M
BE
R:
PR
EP
AR
ED
F O
R
MC
IN
TO
SH
C
OU
NT
Y
BA
R
R
IN
G
TO
N C
AM
PS
IT
E
TO
W
N
SE
N D
, G A
EXISTING SPOT ELEVATION
EXISTING OVERHEAD UTILITY
EXISTING CONTOUR
FLOOD LINE
PROPERTY BOUNDARY
DA
TE
2/
/2
ZONE A
ZONE X
APPROXIMATE LOCATION OF
FLOOD HAZARD LINE
EDGE OF WATER
TOP OF BANK
N:535,950.24 E:830,867.29
.8
6'
S 79°32'19" E
773.05'
N 74°47'24" W 504.72'
S 48°3 7'56" W
94.60'
N 88°25'34" W
204.80'
N 09°03'54" W
107.01'
N 4 3°
'19
" E
.5
6'
4.
345.61'
52.71'
374.73'
S
3°
'0 6"
W
3.
S 70°56'05" W
166.05'130.97'
35.08'
W
W
W W
W
W
W
W W
WW
W
W
W
W
W W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W W
W
W W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W W
W
W
.2
4'
19.00
19.00
19.00
19.00 19.00
19.00
19.00
19.00
16.50
16.00
15.50
15.50
15.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
25' x 100' Pull - Thru Site
(HO
ST SITE)
25' x 100' Pull - Thru Site
25' x 80' Pull - Thru Site
25' x 120' Pull - Thru Site
25' x 100' Pull - Thru Site
25' x 100' Pull - Thru Site
25' x 100' Pull - Thru Site
25' x 80' Pull - Thru Site
25' x 120' Pull - Thru Site 25' x 120' Pull - Thru Site
25' BOAT RAMP EXTENSION
PROPERTY BOUNDARY
PROPERTY BOUNDARY
SHEET:
Know what's below.
before you dig.Call
R
G R
AD
IN
G
D R
AI
N
AG
E
PL
AN
RE
VI
SI
O
N S
ST
. S
IM
O
N S
IS
LA
N D
SA
VA
N
N
AH
JA
CK
SO
N
VI
LL
E
CH
AR
LE
ST
O
N W
W W
.R O
BE
RT
SC
IV
IL
EN
GI
N
EE
RI
N G.
CO
M
GRAPHIC SCALE
1" = 40'
80'0' 40'
N
No. 034205
PROFESSIONAL
SC
AL
E:
' (F O
R
"X
" P
LO
T)
CH
EC
KE
D
BY
BE
DR
AW
N B
Y:
C
S
PR
O
JE
CT
N U
M
BE
R:
PR
EP
AR
ED
F O
R
MC
IN
TO
SH
C
OU
NT
Y
BA
R
R
IN
G
TO
N C
AM
PS
IT
E
TO
W
N
SE
N D
, G A
LEGEND
PROPOSED GRAVEL DRIVEWAY
EXISTING CONCRETE
X.XX PROPOSED SPOT ELEVATION
EXISTING SPOT ELEVATION8.1
EXISTING OVERHEAD UTILITY
EXISTING CONTOUR7
OHU OHU OHU
X
PROPERTY BOUNDARY
DA
TE
2/
/2
ZONE A
ZONE X
APPROXIMATE LOCATION OF
FLOOD HAZARD LINE
EDGE OF WATER
TOP OF BANK
N:535,950.24 E:830,867.29
.8
6'
S 79°32'19" E
773.05'
N 74°47'24" W 504.72'
S 48°3 7'56" W
94.60'
N 88°25'34" W
204.80'
N 09°03'54" W
107.01'
N 4 3°
'19
" E
.5
6'
4.
345.61'
52.71'
374.73'
S
3°
'0 6"
W
3.
S 70°56'05" W
166.05'130.97'
35.08'
W
W
W W
W
W
W
W W
WW
W
W
W
W
W W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W W
W
W W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UG
P
UG
P
UG
P
UG
P
UG
P
U G
P U
G P U
G P
U G
P U
G P
U G
P
UGP UGP UGP UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
W
W
W
W
W W
W
W
.2
4'
1,000 GALLON (750 MINIMUM) DOSING TANK
SET FLOATS TO DELIVER NO MORE
THAN 175 GALLONS PER DOSE
127 LF 1.5" SCH 40
PVC FORCEMAIN
CLEAN OUT TYPICAL FOR
EACH LATERAL RUN
4" SCH 40 PVC (TYP)
1.25" PRESSURE LATERAL
REFER TO DETAILS AND ELJEN
INSTALLATION MANUAL
ELJEN DRAIN FIELD
(180)-A42 UNITS
60 UNITS FOR DUMP STATION
(MIN 59)
120 UNITS FOR BATH HOUSE
(MIN 117)
IM 1530 PRE AERATION TANK
W/ (2) PURAACE PA-68 POD
163 LF 1.5" SCH40 PVC FORCE MAIN
177 LF 4" SDR26 @
2.3% (MIN.)
10 LF 4" SDR26 @
1.0% (MIN.)
(1)1,000 GALLON
SEPTIC TANK
TOP: (±) 26.00
INV IN: (±) 24.00
INV OUT: (±) 23.84
CONTRACTOR TO VERIFY
FIELD ELEVATIONS
IM 1060 PRE AERATION TANK
W/ (1) PURAACE PA-68 POD
IM 1060 CLARIFIER
W/ SIM-TECH PLEATED FILTER
S 70°56'05" W
S 48°37'56" W
94.60'
1,000 GALLON (750 MINIMUM) DOSING TANK
SET FLOATS TO DELIVER NO MORE
THAN 175 GALLONS PER DOSE
WL SIM-TECH "NOVA" NO VAULT FILTER
(2) 1,000 GALLON
SEPTIC TANKS (2,100 MIN.)
TOP: (±) 32.00
INV IN: (±) 29.00
INV OUT: (±) 28.84
CONTRACTOR TO VERIFY
FIELD ELEVATIONS
DUMP STATION
TOP: 30.00
INV 28.00
25 LF 4" SDR26 @
1.0% (MIN.)
90 LF 1.5" SCH40 PVC FORCE MAIN
1,000 GALLON (750 MINIMUM) DOSING TANK
SET FLOATS TO DELIVER NO MORE
THAN 175 GALLONS PER DOSE
1,000 GALLON
SEPTIC TANK (1,000 MIN.)
TOP: (±) 25.50
INV IN: (±) 22.50
INV OUT: (±) 22.34
CONTRACTOR TO VERIFY
FIELD ELEVATIONS
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP UGP
UG
P
U G
P U
G P
U G
P U
G P
U G
P U
G P
25' x 100' Pull - Thru Site
(HO
ST SITE)
25' x 100' Pull - Thru Site
25' x 80' Pull - Thru Site
25' x 120' Pull - Thru Site
25' x 100' Pull - Thru Site
25' x 100' Pull - Thru Site
25' x 100' Pull - Thru Site
25' x 80' Pull - Thru Site
25' x 120' Pull - Thru Site 25' x 120' Pull - Thru Site
1" GV IN BOX WITH RV WATER
CONNECTION ASSEMBLY, TYP.
118 LF 2" PVC SCH 40
WATER LINE
78 LF 2" PVC SCH 40
WATER LINE
FENCE W/ GATE
5,000 GAL TANK
4" PRIMARY WELL
6" SECONDARY WELL
EXISTING WATER WELL
61 LF 2" PVC SCH 40 WATER LINE
38 LF 2" PVC SCH 40 WATER LINE
27 LF 2" PVC SCH 40 WATER
LINE
83 LF 2" PVC SCH 40
WATER LINE
42 LF 2" PVC SCH 40
WATER LINE
60 LF 2" PVC SCH 40 WATER
LINE
75 LF 2" PVC SCH 40 WATER
LINE
51 LF 2" PVC SCH 40
WATER LINE
53 LF 2" PVC SCH 40
WATER LINE
112 LF 2" PVC SCH 40
WATER LINE
39 LF 2" PVC SCH 40 WATER LINE
107 LF 2" PVC SCH 40
WATER LINE
122 LF 2" PVC SCH 40
WATER LINE
49 LF 2" PVC SCH 40
WATER LINE
50 LF 2" PVC SCH 40
WATER LINE
02 LF 2" PVC SCH 40
WATER LINE
12 LF 2" PVC SCH 40
WATER LINE
42 LF 2" PVC SCH 40
WATER LINE
16 LF 2" PVC SCH 40
WATER LINE
383 LF 2" PVC SCH 40
WATER LINE
248 LF 2" PVC SCH 40
WATER LINE
40 LF 2" PVC SCH 40
WATER LINE
110 LF 2" PVC SCH 40
WATER LINE
11 LF 2" PVC SCH 40
WATER LINE
139 LF 2" PVC SCH 40
WATER LINE
90 LF 2" PVC SCH 40
WATER LINE
47 LF 2" PVC SCH 40
WATER LINE
52 LF 2" PVC SCH 40
WATER LINE
26 LF 2" PVC SCH 40
WATER LINE
19 LF 2" PVC SCH 40
WATER LINE
110 LF 2" PVC SCH 40
WATER LINE
106 LF 2" PVC SCH 40
WATER LINE
100 LF 2" PVC SCH 40
WATER LINE
100 LF 2" PVC SCH 40
WATER LINE
47 LF 2" PVC SCH 40
WATER LINE
8 LF 2" PVC SCH 40
WATER LINE
67 LF 2" PVC SCH 40
WATER LINE
63 LF 2" PVC SCH 40
WATER LINE
68 LF 2" PVC SCH 40
WATER LINE
60 LF 2" PVC SCH 40
WATER LINE
25' BOAT RAMP EXTENSION
PROPERTY BOUNDARY
PROPERTY BOUNDARY
SC
AL
E:
' (F O
R
"X
" P
LO
T)
SHEET:
Know what's below.
before you dig.Call
R
U
TI
LI
TY
P
LA
N
RE
VI
SI
O
N S
ST
. S
IM
O
N S
IS
LA
N D
SA
VA
N
N
AH
JA
CK
SO
N
VI
LL
E
CH
AR
LE
ST
O
N W
W W
.R O
BE
RT
SC
IV
IL
EN
GI
N
EE
RI
N G.
CO
M
GRAPHIC SCALE
1" = 40'
80'0' 40'
N
No. 034205
PROFESSIONAL
PROPOSED SEWER LINE
PROPOSED WATER LINEW W W
EXISTING SPOT ELEVATION8.1
EXISTING OVERHEAD UTILITY
EXISTING CONTOUR7
OHU OHU OHU
X
CH
EC
KE
D
BY
BE
DR
AW
N B
Y:
C
S
PR
O
JE
CT
N U
M
BE
R:
PR
EP
AR
ED
F O
R
MC
IN
TO
SH
C
OU
NT
Y
BA
R
R
IN
G
TO
N C
AM
PS
IT
E
TO
W
N
SE
N D
, G A
LEGEND
PROPOSED GRAVEL DRIVEWAY
EXISTING CONCRETE
NOTES:
1. SITES 1 THROUGH 8 WILL HAVE DIRECT WIRING TO EACH SITE ON AN INDIVIDUAL BREAKER.
2. SITES 9 THROUGH 11 WILL HAVE A SECONDARY PANEL FED FROM A MASTER POWER POINT AND FROM THE
2ND PANEL TO EACH SITE.
ELJEN CALCULATION NOTES:
APPLICATION RATE: 1.42 GPD/SQ FT
ELJEN SEPARATION FROM WATER TABLE: 2'
SEWAGE USE:
DUMP STATION FOR TRAVEL TRAILERS - 50 GPD/VEHICLE X 21 = 1,050 GPD
BATH HOUSE FOR CAMPGROUND WITHOUT INDEPENDENT SEWER CONNECTIONS: (100 GPD/SPACE X 21) = 2,100 GPD
1,050 GPD + 2,100 GPD = 3,150 GPD
MODULES REQUIRED: 1,050 GPD / 18 GPD PER MODULE = 58.3 = 59 MODULES
2,100 GPD / 18 GPD PER MODULE = 116.7 = 117 MODULES
SAND BED SIZE:
SAND BED AREA = 3,150 GPD / 1.42 GPD/SQ FT = 2,219 SQ FT
PROPOSED SAND BED AREA: 2,250 SQ FT
SEPTIC CALCULATION NOTES:
USE (1) 1,000 GAL SEPTIC TANK FOR DUMP STATION AND (2) 1,000 GAL SEPTIC TANKS FOR BATH HOUSE
USE 1,000 GAL DOSING TANK FOR BOTH DUMP STATION AND BATH HOUSE
USE 60 ELJEN MODULES FOR DUMP STATION
USE 120 ELJEN MODULES FOR BATH HOUSE
PROPERTY BOUNDARY
DA
TE
2/
/2
E:
N
TS
SHEET:
SE
PT
IC
S
YS
TE
M D
ET
AI
LS
RE
VI
SI
O
N S
ST
. S
IM
O
N S
IS
LA
N D
SA
VA
N
N
AH
JA
CK
SO
N
VI
LL
E
CH
AR
LE
ST
O
N W
W W
.R O
BE
RT
SC
IV
IL
EN
GI
N
EE
RI
N G.
CO
M
No. 034205
PROFESSIONAL
CH
EC
KE
D
BY
BE
DR
AW
N B
Y:
C
S
PR
O
JE
CT
N U
M
BE
R:
PR
EP
AR
ED
F O
R
MC
IN
TO
SH
C
OU
NT
Y
BA
R
R
IN
G
TO
N C
AM
PS
IT
E
TO
W
N
SE
N D
, G A
0.58'
0.5'
2'
SANDBED DETAIL A-A
NTS
EXISTING GRADE EXISTING GRADE
PROPOSED GRADE EL = 9.50 PROPOSED GRADE EL = 34.0
GEOTEXTILE FABRIC
4" EFFLUENT PIPE
(SCH 40)
ELJEN GSF MODULE
0.92'
1.08'
0.33'
0.58'
COMPONENT SPACING DETAIL
NTS
4' M
O D
U
LE
L
EN
G
TH
2' MODULE WIDTH
1' SPACING
DUMP STATION MODULESBATH HOUSE MODULES
PIPE BREAK
PIPE BREAK
DA
TE
2/
/2
E:
N
TS
SHEET:
SE
PT
IC
S
YS
TE
M D
ET
AI
LS
RE
VI
SI
O
N S
ST
. S
IM
O
N S
IS
LA
N D
SA
VA
N
N
AH
JA
CK
SO
N
VI
LL
E
CH
AR
LE
ST
O
N W
W W
.R O
BE
RT
SC
IV
IL
EN
GI
N
EE
RI
N G.
CO
M
No. 034205
PROFESSIONAL
CH
EC
KE
D
BY
BE
DR
AW
N B
Y:
C
S
PR
O
JE
CT
N U
M
BE
R:
PR
EP
AR
ED
F O
R
MC
IN
TO
SH
C
OU
NT
Y
BA
R
R
IN
G
TO
N C
AM
PS
IT
E
TO
W
N
SE
N D
, G A
PUMP OFF: 20% DEPTH
PUMP ON: 20% DEPTH + 175 GALLONS
ALARM ON: 50% DEPTH
ZOELLER 4/10 HP PUMP
MODEL 152 OR EQUIVALENT
LENGTH VARIES
APPRX.
5'
HEIGHT
NOTES:
1) CONTRACTOR IS RESPONSIBLE FOR
LOCATING AND IDENTIFYING ANY EXISTING
WELLS WITHIN 100FT OF THE PROPOSED DRAIN FIELD.
2) A DIG OUT INSPECTION WILL BE REQUIRED PRIOR TO PLACEMENT OF ELJEN UNITS
3) SEE SOIL REPORT FOR DIG OUT SPECS.
FINISHED GRADE
LATERAL ENDS AT LAST
ORIFICE WHERE VARIABLE
LENGTH CLEANOUT BEGINS
4" PERFORATED PIPE
4" END
CAP
CLEAN OUT
DISTRIBUTION LATERAL LATERAL CLEANOUT
4" DIAMETER
PERFORATED PIPE
PRESSURE CLEAN OUT
1.5" LOW PRESSURE PIPE
(LPP)
4" END CAP WITH
HOLE DRILLED
PRESSURE PIPE CROSS SECTION FOR ALL APPLICATIONS
4" DIAMETER PERFORATED PIPE
LOW PRESSURE PIPE
PRESSURE CLEAN OUT
NTS
PRESSURE PIPE PLACEMENT DETAIL
NTS
SEPTIC TANK DETAIL
NTS
ELJEN A-42 UNITS
1/4" HOLES SPACED 30" APART
PUMP OFF: 20% DEPTH
PUMP ON: 20% DEPTH + 175 GALLONS
ALARM ON: 50% DEPTH
ZOELLER 4/10 HP PUMP
MODEL 152 OR EQUIVALENT
LENGTH VARIES
APPRX.
5'
HEIGHT
NOTES:
1) CONTRACTOR IS RESPONSIBLE FOR
LOCATING AND IDENTIFYING ANY EXISTING
WELLS WITHIN 100FT OF THE PROPOSED DRAIN FIELD.
2) A DIG OUT INSPECTION WILL BE REQUIRED PRIOR TO PLACEMENT OF ELJEN UNITS
3) SEE SOIL REPORT FOR DIG OUT SPECS.
FINISHED GRADE
LATERAL ENDS AT LAST
ORIFICE WHERE VARIABLE
LENGTH CLEANOUT BEGINS
4" PERFORATED PIPE
4" END
CAP
CLEAN OUT
DISTRIBUTION LATERAL LATERAL CLEANOUT
4" DIAMETER
PERFORATED PIPE
PRESSURE CLEAN OUT
1.5" LOW PRESSURE PIPE
(LPP)
4" END CAP WITH
HOLE DRILLED
PRESSURE PIPE CROSS SECTION FOR ALL APPLICATIONS
4" DIAMETER PERFORATED PIPE
LOW PRESSURE PIPE
PRESSURE CLEAN OUT
NTS
PRESSURE PIPE PLACEMENT DETAIL
NTS
SEPTIC TANK DETAIL
NTS
ELJEN A-42 UNITS
1/4" HOLES SPACED 30" APART
DA
TE
2/
/2
E:
N
TS
SHEET:
RE
VI
SI
O
N S
ST
. S
IM
O
N S
IS
LA
N D
SA
VA
N
N
AH
JA
CK
SO
N
VI
LL
E
CH
AR
LE
ST
O
N W
W W
.R O
BE
RT
SC
IV
IL
EN
GI
N
EE
RI
N G.
CO
M
No. 034205
PROFESSIONAL
CH
EC
KE
D
BY
BE
DR
AW
N B
Y:
C
S
PR
O
JE
CT
N U
M
BE
R:
PR
EP
AR
ED
F O
R
MC
IN
TO
SH
C
OU
NT
Y
BA
R
R
IN
G
TO
N C
AM
PS
IT
E
TO
W
N
SE
N D
, G A
SE
PT
IC
S
YS
TE
M D
ET
AI
LS
DA
TE
2/
/2
ZONE A
ZONE X
APPROXIMATE LOCATION OF
FLOOD HAZARD LINE
EDGE OF WATER
TOP OF BANK
N:535,950.24 E:830,867.29
.8
6'
S 79°32'19" E
773.05'
N 74°47'24" W 504.72'
S 48°3 7'56" W
94.60'
N 88°25'34" W
204.80'
N 09°03'54" W
107.01'
N 4 3°
'19
" E
.5
6'
4.
345.61'
52.71'
374.73'
S
3°
'0 6"
W
3.
S 70°56'05" W
166.05'130.97'
35.08'
W
W
W W
W
W
W
W W
WW
W
W
W
W
W W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W W
W
W W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UG
P
UG
P
UG
P
UG
P
UG
P
U G
P U
G P U
G P
U G
P U
G P
U G
P
UGP UGP UGP UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
W
W
W
W
W W
W
W
.2
4'
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP
UGP UGP
UG
P
U G
P U
G P
U G
P U
G P
U G
P U
G P
25' x 100' Pull - Thru Site
(HO
ST SITE)
25' x 100' Pull - Thru Site
25' x 80' Pull - Thru Site
25' x 120' Pull - Thru Site
25' x 100' Pull - Thru Site
25' x 100' Pull - Thru Site
25' x 100' Pull - Thru Site
25' x 80' Pull - Thru Site
25' x 120' Pull - Thru Site 25' x 120' Pull - Thru Site
25' BOAT RAMP EXTENSION
PROPERTY BOUNDARY
PROPERTY BOUNDARY
214 LF 2"-2.5"
CONDUIT
PROPOSED
LIGHT
PROPOSED
LIGHT
PROPOSED
TRANSFORMER
PROPOSED CABINET
EXISTING
POLE
PROPOSED
LIGHT
PROPOSED
TRANSFORMER
PROPOSED
LIGHT
PROPOSED
LIGHT
PROPOSED
LIGHT
PROPOSED
LIGHT
153 LF 1"-1.5"
CONDUIT
18 LF 1"-1.5"
CONDUIT
76 LF 1"-1.5"
CONDUIT
130 LF 2"-2.5"
CONDUIT
138 LF 1"-1.5"
CONDUIT
183 LF 1"-1.5"
CONDUIT
214 LF 1"-1.5" CONDUIT
225 LF 1"-1.5" CONDUIT
305 LF 2"-2.5" CONDUIT
207 LF 1"-1.5" CONDUIT
SC
AL
E:
' (F O
R
"X
" P
LO
T)
SHEET:
Know what's below.
before you dig.Call
R
D R
Y U
TI
LI
TY
P
LA
N
RE
VI
SI
O
N S
ST
. S
IM
O
N S
IS
LA
N D
SA
VA
N
N
AH
JA
CK
SO
N
VI
LL
E
CH
AR
LE
ST
O
N W
W W
.R O
BE
RT
SC
IV
IL
EN
GI
N
EE
RI
N G.
CO
M
GRAPHIC SCALE
1" = 40'
80'0' 40'
N
No. 034205
PROFESSIONAL
PROPOSED SEWER LINE
PROPOSED WATER LINEW W W
EXISTING SPOT ELEVATION8.1
EXISTING OVERHEAD UTILITY
EXISTING CONTOUR7
OHU OHU OHU
X
CH
EC
KE
D
BY
BE
DR
AW
N B
Y:
C
S
PR
O
JE
CT
N U
M
BE
R:
PR
EP
AR
ED
F O
R
MC
IN
TO
SH
C
OU
NT
Y
BA
R
R
IN
G
TO
N C
AM
PS
IT
E
TO
W
N
SE
N D
, G A
LEGEND
PROPOSED GRAVEL DRIVEWAY
EXISTING CONCRETE
NOTES:
1. SITES 1 THROUGH 8 WILL HAVE DIRECT WIRING TO EACH SITE ON AN INDIVIDUAL BREAKER.
2. SITES 9 THROUGH 11 WILL HAVE A SECONDARY PANEL FED FROM A MASTER POWER POINT AND FROM THE
2ND PANEL TO EACH SITE.
PROPERTY BOUNDARY
PROPOSED LIGHT
PROPOSED UNDERGROUND POWERUGP UGP
PROPOSED CABINET
PROPOSED TRANSFORMER
DA
TE
2/
/2
E:
N
TS
SHEET:
W
EL
L D
ET
AI
LS
RE
VI
SI
O
N S
ST
. S
IM
O
N S
IS
LA
N D
SA
VA
N
N
AH
JA
CK
SO
N
VI
LL
E
CH
AR
LE
ST
O
N W
W W
.R O
BE
RT
SC
IV
IL
EN
GI
N
EE
RI
N G.
CO
M
No. 034205
PROFESSIONAL
CH
EC
KE
D
BY
BE
DR
AW
N B
Y:
C
S
PR
O
JE
CT
N U
M
BE
R:
PR
EP
AR
ED
F O
R
MC
IN
TO
SH
C
OU
NT
Y
BA
R
R
IN
G
TO
N C
AM
PS
IT
E
TO
W
N
SE
N D
, G A
DA
TE
2/
/2
E:
N
TS
SHEET:
W
EL
L D
ET
AI
L
RE
VI
SI
O
N S
ST
. S
IM
O
N S
IS
LA
N D
SA
VA
N
N
AH
JA
CK
SO
N
VI
LL
E
CH
AR
LE
ST
O
N W
W W
.R O
BE
RT
SC
IV
IL
EN
GI
N
EE
RI
N G.
CO
M
No. 034205
PROFESSIONAL
CH
EC
KE
D
BY
BE
DR
AW
N B
Y:
C
S
PR
O
JE
CT
N U
M
BE
R:
PR
EP
AR
ED
F O
R
MC
IN
TO
SH
C
OU
NT
Y
BA
R
R
IN
G
TO
N C
AM
PS
IT
E
TO
W
N
SE
N D
, G A
SECONDARY WELL DETAIL
FENCE DETAIL GATE DETAIL
PRIMARY WELL DETAIL
DA
TE
2/
/2
| Sheets and Views |
| COVER |
| Sheets and Views |
| GENERAL NOTES |
| Sheets and Views |
| EXISTING CONDITIONS |
| Sheets and Views |
| STAKING PLAN |
| Sheets and Views |
| GRADING & DRAINAGE PLAN |
| Sheets and Views |
| UTILITY PLAN |
| Sheets and Views |
| SEPTIC DETAIL1 |
| Sheets and Views |
| SEPTIC DETAIL2 |
| Sheets and Views |
| SEPTIC DETAIL3 |
| Sheets and Views |
| DRY UTILITY PLAN |
| Sheets and Views |
| WELL DETAILS |
| Sheets and Views |
| WELL DETAILS2 |
File details come from the government source that posted it. Updated .