2024-07-29_PFRWTA MCC-6 Feeder Project_RFB2024-01_Drawings_Final.pdf
PDF 5 MB Posted
- Attached to
- Request for Bids
- Solicitation number
- 73196
- Issued by
- Roanoke County, Richmond City, Virginia
About this file
This document is a set of design drawings and specifications for the MCC-6 Feeder Project at the Pepper's Ferry Regional Wastewater Treatment Facility in Radford, Virginia. The project involves furnishing and installing a new below-grade electrical ductbank to connect an existing electrical manhole to the Solids Handling Building, as well as installing new conduit and wiring from the main electrical switchgear (SWGR-MAIN) to the MCC-6 panel inside the Solids Handling Building. The project is being solicited through Request for Bids (RFB) 2024-01 by the Pepper's Ferry Regional Wastewater Treatment Authority.
The bid documents provide detailed drawings, specifications, and general requirements for the electrical work, including specifications for concrete encasement, conduit routing, and cabling. No bid quantities or pricing information is included in the provided file. The project is located in Radford, Virginia and the solicitation is open to qualified contractors. The documents do not specify a bid due date, award date, or contract term.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2024-07-29_PFRWTA MCC-6 Feeder Project_RFB2024-01_Technical Specifications_Final.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VICINITY MAP (NTS) LOCATION MAP (NTS)
PEPPER'S FERRY REGIONAL WASTEWATER TREATMENT FACILITY
MCC-6 FEEDER PROJECT
JULY 2024
RADFORD, VIRGINIA
RFB 2024-01
703-218-2034
4035 RIDGE TOP ROAD, SUITE 500, FAIRFAX, VA 22030
HAZEN AND SAWYER
FINAL SUBMISSION
GENERAL
GENERAL
COVER SHEET
G-1 ABBREVIATIONS AND LEGEND
CIVIL
C-001 SITE PLAN
C-002 PARTIAL SITE PLAN AND PROFILE
C-003 DETAILS
INDEX OF DRAWINGS
ARCHITECTURAL
SOLIDS HANDLING BUILDING
A-700 PLANS AND SECTIONS
ELECTRICAL
E-001 SITE PLAN
SOLIDS HANDLING BUILDING
E-700 POWER PLAN UPPER AND LOWER
FLOORS SOUTH
E-701 SINGLE LINE DIAGRAMS
E-702 STANDARD DETAILS
GENERAL NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND BECOME FAMILIAR WITH
THE EXTENT OF THE WORK REQUIRED. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND
ELEVATIONS.
2. WORK SHALL BE COORDINATED WITH PEPPER'S FERRY REGIONAL WASTEWATER TREATMENT
AUTHORITY (PFRWTA).
3. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR ANY SEWAGE SPILLS. IN THE EVENT OF A
SPILL, THE CONTRACTOR SHALL CONTACT DEQ AND PEPPER'S FERRY REGIONAL WASTEWATER
TREATMENT AUTHORITY WITHIN 2 HOURS AND FOLLOW ALL DEQ AND PEPPER'S FERRY
REGIONAL WASTEWATER TREATMENT AUTHORITY REQUIREMENTS.
4. REFER TO ELECTRICAL DRAWINGS FOR AREA CLASSIFICATIONS. CONTRACTOR IS
RESPONSIBLE TO PERFORM WORK IN ACCORDANCE WITH REQUIRED PRACTICES.
5. YARD PIPING REPRESENTATIONS ARE BASED ON INFORMATION FROM "PEPPER'S FERRY
REGIONAL WASTEWATER TREATMENT AUTHORITY PLANT EXPANSION" BY OLVER
INCORPORATED, REVISED OCTOBER 1994, AND MAY UTILIZE IMAGES OF SCANNED ASBUILTS
FROM THIS PACKAGE OF INFORMATION. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS AND BECOME FAMILIAR WITH THE EXTENT OF WORK REQUIRED. CONTRACTOR
SHALL VERIFY ALL DIMENSIONS AND ELEVATIONS. CONTRACTOR TO TEST PIT AS NEEDED TO
CONFIRM UTILITY LOCATIONS.
6. EROSION AND SEDIMENT CONTROL PLAN IS NOT REQUIRED BECAUSE THE TOTAL LAND
DISTURBANCE FOR THIS PROJECT IS LESS THAN THE 10,000 SQ FT DISTURBANCE
REQUIREMENT IN THE VIRGINIA EROSION AND SEDIMENT CONTROL HANDBOOK
7. WORK SHALL BE COORDINATED WITH PEPPER'S FERRY REGIONAL WASTEWATER TREATMENT
AUTHORITY (PFRWTA) AND SEQUENCED IN ACCORDANCE WITH SPECIFICATION SECTION 01
14 00.
SITE INFORMATION
SURVEY DATUM:
1. THE MERIDAN SOURCE REFER TO THE VIRGINIA STATE PLANE,
SOUTH ZONE, (NAD 83) AND ARE BASED UPON EXISTING
ON-SITE CONTROL.
2. ELEVATIONS REFER TO NAVD88 AND ARE BASED UPON AN
EXISTING ON-SITE CONTROL.
PL
O
T D
AT
E:
/1
6/
:2
PM
B Y:
A
VE
C C
H
IO
Fi le
: O :\3
-0
\3
-0
\C
AD
_B
IM
\G
EN
L\
G -1
S av ed b y
AV
EC
C
H
IO
S av e da te : 7
/1 2/
:1
PM
31618-002
JULY 2024N. MCDERMOTT
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT NO.:
HAZEN NO.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
4035 RIDGE TOP ROAD, SUITE 400
FAIRFAX, VA 22030IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
TREATMENT AUTHORITY
RADFORD, VIRGINIA
WASTEWATER TREATMENT FACILITY
PEPPER'S FERRY REGIONAL WASTEWATER
MCC-6 FEEDER PROJECT
PFRWTA ID NO.: RFB 2024-01
M. VAN HORNE
GENERAL
ABBREVIATIONS AND LEGENDS
G-001
A. VECCHIO
A. VECCHIO
ABBREVIATIONS
LINETYPES
LEGEND
SYMBOLS
SECTION AND DETAIL KEYING
MATERIALS
PROCESS PIPE DESIGNATIONS
A
B
I
J
TPE
C
Q
G
L
W
V
U
M
F
S
H Y
O
N
D
R
1+
0+
0+
1+
NOTES:
1. CONTRACTOR SHALL USE THE DRY SLUDGE
STORAGE AREA 2, DEPICTED ON E-001, AS THE
PROJECT LAYDOWN AREA.
SCALE: 1" = 10'
PLAN
PL
O
T D
AT
E:
/1
5/
:3
A
VE
C C
H
IO
Fi le
: O :\3
-0
\3
-0
\C
AD
_B
IM
\C
IV
IL
\C
Sa ve d by
A
VE
C C
H
IO
S av e da te : 7
/1 5/
:3
PM
31618-002
JULY 2024N. MCDERMOTT
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT NO.:
HAZEN NO.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
4035 RIDGE TOP ROAD, SUITE 400
FAIRFAX, VA 22030IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
TREATMENT AUTHORITY
RADFORD, VIRGINIA
WASTEWATER TREATMENT FACILITY
PEPPER'S FERRY REGIONAL WASTEWATER
MCC-6 FEEDER PROJECT
PFRWTA ID NO.: RFB 2024-01
PL
O
T D
AT
E:
/1
5/
:3
A
VE
C C
H
IO
Fi le
: O :\3
-0
\3
-0
\C
AD
_B
IM
\C
IV
IL
\C
Sa ve d by
A
VE
C C
H
IO
S av e da te : 7
/1 5/
:3
PM
31618-002
JULY 2024N. MCDERMOTT
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT NO.:
HAZEN NO.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
4035 RIDGE TOP ROAD, SUITE 400
FAIRFAX, VA 22030IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
TREATMENT AUTHORITY
RADFORD, VIRGINIA
WASTEWATER TREATMENT FACILITY
PEPPER'S FERRY REGIONAL WASTEWATER
MCC-6 FEEDER PROJECT
PFRWTA ID NO.: RFB 2024-01
CIVIL
SITE PLAN
A. VECCHIO
A. VECCHIO
B. SLAUGHTER
SOLIDS HANDLING
BUILDING
CONCRETE ENCASED
ELECTRICAL DUCTBANK,
30"W X 18" D, SEE DETAIL E-33-101
EXISTING CONCRETE
8'X6' EMH-1604,
DEPTH APPROX. 8'
DUCTBANK TO ENTER
BUILDING BELOW GRADE
AT INV EL.1769
DEMOLISH AND REPLACE
EXISTING ASPHALT PAVEMENT,
SEE DETAIL C-32-0550 AND
C-32-0556
CHLORINE CONTACT
TANK
NPW BUILDING
(OLD)
EXISTING ASPHALT PAVEMENT,
SEE SHEET C-003
MCC-5
FIBER
PATCH
PANEL
6" WS
6" PSL
10" SS
4" NPW
8" NPW
30" EFF,
ABANDONED
C-001
0+00 0+50 1+00 1+25
1+
0+
0+
1+
NOTES:
1. LOCATIONS OF EXISTING UTILITIES ARE
APPROXIMATED BASED ON BEST AVAILABLE DATA.
CONTRACTOR SHALL FIELD LOCATE ALL UTILITIES
PRIOR TO ORDERING MATERIALS.
2. PIPES WITH LESS THAN 12" OF COVER FROM
PROPOSED CONCRETE ENCASED DUCTBANK SHALL
BE CONCRETE ENCASED AT CROSSING, SEE DETAIL
C-01-0120R
3. EXISTING FIBER OPTICAL CABLES ARE UNENCASED
AND ARE LAID AT SHALLOW DEPTHS.
4. SITE FEATURES, TOPOGRAPHY, AND UTILITY
LOCATIONS ARE BASED ON THE 2017 SURVEY FOR
"PEPPER'S FERRY REGIONAL WASTEWATER
TREATMENT FACILITY SOLIDS HANDLING
UPGRADES" AND THE FEBRUARY 2011 CONTRACT
DRAWINGS PREPARED BY HAZEN AND SAWYER.
ELEVATIONS ARE BASED UPON AN EXISTING SITE
CONTROL.
HORIZONTAL SCALE: 1" = 10'
PROFILE
PL
O
T D
AT
E:
/1
6/
:5
A
VE
C C
H
IO
Fi le
: O :\3
-0
\3
-0
\C
AD
_B
IM
\C
IV
IL
\C
Sa ve d by
A
VE
C C
H
IO
S av e da te : 7
/1 6/
:5
PM
31618-002
JULY 2024N. MCDERMOTT
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT NO.:
HAZEN NO.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
4035 RIDGE TOP ROAD, SUITE 400
FAIRFAX, VA 22030IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
TREATMENT AUTHORITY
RADFORD, VIRGINIA
WASTEWATER TREATMENT FACILITY
PEPPER'S FERRY REGIONAL WASTEWATER
MCC-6 FEEDER PROJECT
PFRWTA ID NO.: RFB 2024-01
PL
O
T D
AT
E:
/1
6/
:5
A
VE
C C
H
IO
Fi le
: O :\3
-0
\3
-0
\C
AD
_B
IM
\C
IV
IL
\C
Sa ve d by
A
VE
C C
H
IO
S av e da te : 7
/1 6/
:5
PM
31618-002
JULY 2024N. MCDERMOTT
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT NO.:
HAZEN NO.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
4035 RIDGE TOP ROAD, SUITE 400
FAIRFAX, VA 22030IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
TREATMENT AUTHORITY
RADFORD, VIRGINIA
WASTEWATER TREATMENT FACILITY
PEPPER'S FERRY REGIONAL WASTEWATER
MCC-6 FEEDER PROJECT
PFRWTA ID NO.: RFB 2024-01
CIVIL
PARTIAL SITE PLAN AND PROFILE
A. VECCHIO
A. VECCHIO
B. SLAUGHTER
EXISTING GRADE
4" NPW
6" PSL
SCALE: 1" = 15'
PLAN
SOLIDS HANDLING
BUILDING
6" WS
6" PSL
10" SS
4" NPW
8" NPW
FO
FO, SEE NOTE 3
VERTICAL SCALE: 1" = 2'
EXISTING EMH-1604
ELECTRICAL DUCTBANK
30"W X 18" D
SEE DETAIL E-33-101
SOLIDS HANDLING
BUILDING
2.
' M
IN
FFL EL 1775.00
ELECTRICAL DUCTBANK PENETRATION
THROUGH EXISTING CONC WALL AT INV EL.
1769, SEE ARCH SHEETS
10" SS 8" NPW
6" WS
ST
AT
IO
N
+6
9.
ED
G
E O
F
PA
VE
M
EN
T
ELEVATIONS UNKNOWN,
FIELD VERIFY UGE LINES
EQUIPMENT ROOM
30" EFF,
ABANDONED
SEE NOTE 2
CHLORINE CONTACT
TANK
NPW BUILDING
(OLD)
MCC-5
FIBER PATCH PANEL
SEE NOTE 3
C-002
PL
O
T D
AT
E:
/1
6/
:5
A
VE
C C
H
IO
Fi le
: O :\3
-0
\3
-0
\C
AD
_B
IM
\C
IV
IL
\C
Sa ve d by
A
VE
C C
H
IO
S av e da te : 7
/1 6/
:3
PM
31618-002
JULY 2024N. MCDERMOTT
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT NO.:
HAZEN NO.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
4035 RIDGE TOP ROAD, SUITE 400
FAIRFAX, VA 22030IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
TREATMENT AUTHORITY
RADFORD, VIRGINIA
WASTEWATER TREATMENT FACILITY
PEPPER'S FERRY REGIONAL WASTEWATER
MCC-6 FEEDER PROJECT
PFRWTA ID NO.: RFB 2024-01
PL
O
T D
AT
E:
/1
6/
:5
A
VE
C C
H
IO
Fi le
: O :\3
-0
\3
-0
\C
AD
_B
IM
\C
IV
IL
\C
Sa ve d by
A
VE
C C
H
IO
S av e da te : 7
/1 6/
:3
PM
31618-002
JULY 2024N. MCDERMOTT
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT NO.:
HAZEN NO.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
4035 RIDGE TOP ROAD, SUITE 400
FAIRFAX, VA 22030IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
TREATMENT AUTHORITY
RADFORD, VIRGINIA
WASTEWATER TREATMENT FACILITY
PEPPER'S FERRY REGIONAL WASTEWATER
MCC-6 FEEDER PROJECT
PFRWTA ID NO.: RFB 2024-01
CIVIL
DETAILS
A. VECCHIO
A. VECCHIO
B. SLAUGHTER
4'-0"EQUALEQUAL4'-0"VARIES
12:1 3:1
3:1 SLOPE
12:1
3:1 SLOPE, MAX
VARIES - SEE SITE PLAN
C-32-0550
SLOPE AT 1/4:12 SLOPE AT 1/4:1212"
MIN
TYP
TACK COAT
1.5" ASPHALT
SURFACE COURSE
3.0" ASPHALT
BASE COURSE
NOTE:
THE 1.5" ASPHALT CONCRETE SURFACE COURSE AND THE
TACK COAT SHALL NOT BE PLACED UNTIL COMPLETION OF
ALL OTHER WORK IN CONTRACT.
TYPICAL ROADWAY SECTION
CUT SECTION FILL SECTION
CL
6" AGGREGATE BASE COURSE
COMPACTED SUB-GRADE
TYPE I SEPARATOR GEOTEXTILE
NEW ASPHALT PAVEMENT
AGGREGATE BASE COURSE
TACK COAT
CUT BACK EXIST BASE
COURSE 12" MIN
CUT BACK EXIST
TYPICAL PAVEMENT JUNCTION
EXIST BASE COURSE
C-32-0556
C-32-0550SEE
TACK COAT
ASPHALT SURFACE
COURSE, 2" MIN
ASPHALT BASE
COURSE, 3.5" MIN
SURFACE COURSE
6" MIN FROM BASE
SLOPE
EXIST SURFACE
COURSE
PROPOSED DUCTBANK OVER EXIST PIPE
12"
MIN
PROPOSED
DUCTBANK
6" MIN
12" MAX
PIPE
EXIST
DUCTBANK
PROPOSED
PROPOSED DUCTBANK UNDER EXIST PIPE
6" 6"PIPE
OD
EXIST
PIPE
12" MAX
6" MIN
JOINT FILLER MATERIAL
1" THICK COMPRESSIBLE
C-01-0120R
FLOWABLE FILL FULL TRENCH
WIDTH (NO ENCASEMENT
REQUIRED FOR SPACE GREATER
THAN 12")
CL
CL
SEE E-33-101
SEE E-33-101
EXISTING ROADWAY SECTION
C-003
FROM "PEPPER'S FERRY REGIONAL WASTEWATER TREATMENT AUTHORITY
PLANT EXPANSION" BY OLVER INCORPORATED, REVISED OCTOBER 1994
A
B.2
B.5
A.6
B.8
C
D
E
0.8 2.9 3.6 3.7
A-700
A_______
SLUDGE
BLENDING
TANK
T-11
VESTIBULE
EQUIPMENT
ROOM
A-700
B_______
CONDUITS SHALL
NOT BE INSTALLED
UNDER HVAC DUCT
AT THIS LOCATION
ELECTRICAL PULL BOX,
SEE ELECTRICAL FOR
OVERALL CONDUIT RUN
LOCATIONS, AND SEE
THIS SHEET FOR CABLE
RUN IN RELATION TO
STAIR AND HVAC DUCT.
CLEAN WALL, NOTE 2
22' - 4"
A-700
C_______
NOTE 5, OUTLINE OF
EGRESS PATH
NOTES
1. INSTALL DUCTBANK WITH PENETRATION
THROUGH EXISTING CONCRETE WALL IN
ACCORDANCE WITH STANDARD DETAILS
E-33-0101, TYPICAL DUCTBANK SECTION,
AND S-03-0402R, ENCASED ELECTRICAL
CONDUITS AT EXISTING STRUCTURES.
2. WASH/CLEAN WALL FROM SOUTHWEST
CORNER TO CONCRETE COLUMN, FLOOR TO
CEILING, AFTER SAW CUTTING OF DUCTBAK
PENETRATION .
3. CONDUIT ROUTE SHOWN IS AN EXAMPLE
ROUTE. DIMENSIONS SHOWN ARE FOR
ROUTE ABOVE LOWER STAIR RUN AND
BELOW UPPER STAIR RUN, TO WEST OF
EXISTING HVAC DUCT. PROVIDE 7 FT
CLEARANCE BETWEEN LOWER STAIR NOSING
AND BOTTOM OF CONDUITS, INCLUDING
FIRE BARRIER WRAP, AND RUN CONDUITS
UNDER UPPER STAIR FLIGHT. IF A DIFFERENT
PATH FOR CONDUIT IS USED, THE
FOLLOWING CONSTRAINTS SHALL APPLY:
A. 7 FT CLEARANCE BETWEEN BOTTOM
OF CONDUIT WRAP AND WALKING
SURFACE BELOW (FLOOR OR STAIR
NOSING), MIN.
4. WRAP CONDUITS IN FIRE BARRIER WRAP.
FOR EXAMPLE ROUTE SHOWN, WRAP
CONDUITS WHERE THEY CROSS STAIR AND 4'
ON EACH SIDE OF STAIR. 3M FIRE BARRIER
PLENUM WRAP 5A+ OR APPROVED EQUAL,
INSTALLED PER MFR INSTRUCTIONS. SEE
SECTION B THIS SHEET.
5. IF AN ALTERNATE PATH FOR THE CONDUIT IS
USED, WRAP CONDUIT OVER ALL SECTIONS
OF EGRESS PATH CROSSED, AND EXTEND TO
4' ON EACH SIDE OF EGRESS PATH CROSSED.
OUTLINE OF EGRESS PATHS IS SHOWN ON
PLAN.
6. COORDINATE ALL WORK SHOWN ON THIS
SHEET WITH ELECTRICAL DRAWINGS.
BUILDING CODE SUMMARY
2021 VIRGINIA EXISTING BUILDING CODE
EXISTING OCCUPANCY: F2-FACTORY INDUSTRIAL
LOW HAZARD
OCCUPANCY UNCHANGED
EXISTING CONSTRUCTION: IIB
CONSTRUCTION TYPE UNCHANGED
EXISTING BUILDING AREA: 9,400 SF
EXISTING BUILDING HEIGHT: 15 FT
EXISTING BUILDING STORIES : 1
+ WALKOUT
BASEMENT
EXISTING CALCULATED
OCCUPANT LOAD: 32
OCCUPANT LOAD DETERMINED BY DIVIDING FLOOR
SQUARE FOOTAGE BY 300. BUILDING IS OCCASIONALLY
OCCUPIED BY STAFF TO MONITOR, REPAIR, OR MAINTAIN
EQUIPMENT.
SCOPE OF WORK INCLUDES ELECTRICAL CONDUIT
REPLACEMENT.
EGRESS TRAVEL DISTANCE IS UNCHANGED.
0.82.93.63.7
A-700
B_______
EQUIPMENT
ROOM
RDT
ROOM
SEPTAGE
RECEIVING
FFL EL 1760.00
ELECTRICAL
PULL BOX
CLEAN WALL, NOTE 2
22' - 4"
C L E A N
W A L L
N O
T E
A B B.2 B.5A.6 B.8 C D
A-700
A_______
SLUDGE
BLENDING
TANK
T-11
EQUIPMENT
ROOM
STAIR
SEPTAGE
RECEIVING
ELECTRICAL
ROOM
SLUDGE
BLENDING
ROOM
PIPE
CHASE
SLUDGE
PUMP
ROOM
A-700
D
EXAMPLE ROUTE, CONDUIT RUNS
UNDER EXISTING UPPER STAIR RUN AND
ABOVE LOWER STAIR RUN, IN FRONT OF
EXISTING HVAC DUCT. SEE NOTES 3-6
AND SECTION C, THIS SHEET
A-700
C_______
4' - 0"
4' - 0"
14' - 2"
A
B
B.2
B.5
A.6
B.8
C
D
E
0.8 2.9 3.6 3.7
A-700
A_______
A-700
B_______
SLUDGE
BLENDING
ROOM
ELECTRICAL
ROOM
SEPTAGE
RECEIVING
STAIR
RDT
ROOM
ELECTRICAL
ROOM
A-700
C_______
A
M
IN
N
O T E
N O
T T
O S
C A
L E
EQUIPMENT
ROOM
SEPTAGE
RECEIVING
ELECTRICAL DUCTBANK,
SEE NOTE 1
ELECTRICAL DUCTBANK
PENETRATION THROUGH
EXISTING CONC WALL,
SEE NOTE 1
FFL EL 1760.00
ELECTRICAL PULL BOX,
SEE ELECTRICAL
PROTECT EXISTING BRICK SHELF
AND BRICK ABOVE. CONTRACTOR
IS EXCLUSIVELY RESPONSIBLE
FOR SUPPORT OF WALLS DURING
DEMOLITION AND CONSTRUCTION.
C L E
N
W
L L
N O
T E
GRADE EL 1774.50 (VERIFY)6
1769.00 BOTTOM OF DUCT BANK
0.8 2.9
CONDUIT RUNS
ALONGSIDE EXISTING
HVAC DUCT, UNDER
STAIR, SEE NOTES 3-6
EXISTING HVAC DUCT
RDT
ROOM
STAIR
EQUIPMENT
ROOM
N O
T E
M
IN
NOTE 3
10'-7" +/-
DESIGNED BY:
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
PROJECT
ENGINEER:
DRAWN BY:
CHECKED BY:
REV ISSUED FOR DATE BY
HAZEN AND SAWYER
4035 RIDGE TOP ROAD, SUITE 400
FAIRFAX, VA 22030
N. MCDERMOTT
0 1/2" 1"
DATE:
HAZEN NO.:
CONTRACT NO.:
DRAWING
NUMBER:
PEPPER'S FERRY REGIONAL WASTEWATER
TREATMENT AUTHORITY
RADFORD, VIRGINIA
WASTEWATER TREATMENT FACILITY
MCC-6 FEEDER PROJECT
JULY 2024
31618-002
PFRWTA ID NO.: RFB 2024-01
SOLIDS HANDLING
BUILDING KEYPLAN
C
U s e rs
\m m c in to s h \D o c u m e n ts
\3 -0
-7
-S
H -A
R C H m m c in to s h -r a l.
rv t
/1
/2
:3 :4
P
M
M. MCINTOSH
W. RUSSELL
M. MCINTOSH
A-700
SOLIDS HANDLING BUILDING
ARCHITECTURAL
PLANS AND SECTIONS
1/8" = 1'-0"
LOWER LEVEL PLAN
N P L A N
T N
O R T H
SECTION
1/8" = 1'-0" A-700
A
SOUTH WALL
SECTION
1/8" = 1'-0" A-700
B
WEST WALL
1/8" = 1'-0"
UPPER LEVEL PLAN
SECTION
1/2" = 1'-0" A-700
D
SECTION
1/8" = 1'-0" A-700
C
CONDUIT AT
STAIR
SCALE: 1" = 50'
PLAN
PL
O
T D
AT
E:
/1
2/
:2
A
VE
C C
H
IO
Fi le
: O :\3
-0
\3
-0
\C
AD
_B
IM
\E
LE
C
\E -0
S av ed b y
AV
EC
C H
IO
S av e da te
: 7 /1
2/
:2
PM
31618-002
JULY 2024N. MCDERMOTT
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT NO.:
HAZEN NO.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
4035 RIDGE TOP ROAD, SUITE 400
FAIRFAX, VA 22030IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
TREATMENT AUTHORITY
RADFORD, VIRGINIA
WASTEWATER TREATMENT FACILITY
PEPPER'S FERRY REGIONAL WASTEWATER
MCC-6 FEEDER PROJECT
PFRWTA ID NO.: RFB 2024-01
PL
O
T D
AT
E:
/1
2/
:2
A
VE
C C
H
IO
Fi le
: O :\3
-0
\3
-0
\C
AD
_B
IM
\E
LE
C
\E -0
S av ed b y
AV
EC
C H
IO
S av e da te
: 7 /1
2/
:2
PM
31618-002
JULY 2024N. MCDERMOTT
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECT
ENGINEER:
REV ISSUED FOR DATE BY
0 1"1/2"
CONTRACT NO.:
HAZEN NO.:
DATE:
DRAWING
NUMBER:HAZEN AND SAWYER
4035 RIDGE TOP ROAD, SUITE 400
FAIRFAX, VA 22030IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
TREATMENT AUTHORITY
RADFORD, VIRGINIA
WASTEWATER TREATMENT FACILITY
PEPPER'S FERRY REGIONAL WASTEWATER
MCC-6 FEEDER PROJECT
PFRWTA ID NO.: RFB 2024-01
ELECTRICAL
SITE PLAN
B. FARIS
B. FARIS
D. ATKINSON
NOTES:
1. LOCATIONS OF EXISTING UTILITIES ARE
APPROXIMATED BASED ON BEST AVAILABLE DATA.
CONTRACTOR SHOULD FIELD LOCATE ALL UTILITIES
PRIOR TO ORDERING MATERIALS.
E-001
NEW ELECTRICAL DUCTBANK,
SEE CIVIL DRAWINGS FOR
ADDITIONAL DETAILS.
EXISTING EMH-1604
SOLIDS HANDLING
BUILDING
(E700 SERIES)
BLOWER
BUILDING
EXISTING EMH-1602
(APPROX. LOCATION)
SWGR-MAIN
(APPROXIMATE LOCATION)
DB
DB
DB
EXISTING DUCTBANK,
SEE NOTE 2.
DUCTBANK NO. DUCTBANK STATUS PERTINENT CONDUITS PERTINENT WIRES NOTES
1 EXISTING 4" 6#400KCMIL, 2#250KCMIL, #1/0GND NEW WIRE IN EXISTING CONDUIT
2 EXISTING 4" 6#400KCMIL, 2#250KCMIL, #1/0GND NEW WIRE IN EXISTING CONDUIT
3 NEW 4" 6#400KCMIL, 2#250KCMIL, #1/0GND NEW WIRE IN NEW CONDUIT
4" EMPTY W/PULLSTRING EMPTY W/PULLSTRING
4" EMPTY W/PULLSTRING EMPTY W/PULLSTRING
4" EMPTY W/PULLSTRING EMPTY W/PULLSTRING
2" EMPTY W/PULLSTRING EMPTY W/PULLSTRING
2" EMPTY W/PULLSTRING EMPTY W/PULLSTRING
N
1. 1. LOCATIONS OF EXISTING UTILITIES ARE
APPROXIMATED BASED ON BEST AVAILABLE SITE DATA.
CONTRACTOR SHALL FIELD VERIFY ALL UTILITIES PRIOR
TO CONSTRUCTION.
2. EXISTING CONDUITS TO BE USED IN DUCTBANKS
SHALL HAVE A DOUBLE-ENDED MANDREL PULLED
THROUGH PRIOR TO CABLE INSTALLATION TO ENSURE
CONDUITS ARE FREE OF DEBRIS AND SUITABLE FOR
CABLE INSTALLATION.
3. CONTRACTOR SHALL INSTALL SERVICE LOOPS FOR THE
NEWLY INSTALLED CABLES WITHIN EACH MANHOLE.
CONTRACTOR SHALL INSTALL NON-METALLIC CABLE
RACKS AS REQUIRED TO SUPPORT SERVICE LOOPS. SEE
SPECIFICATION 33 71 19 - UNDERGROUND ELECTRICAL
FOR FURTHER DETAILS.
EXISTING DUCTBANK,
SEE NOTE 2.
SEE NOTE 3, TYP OF
ALL MANHOLES.
CONTRACTOR LAYDOWN
AREA, SEE CIVIL DRAWINGS
FOR ADDITIONAL DETAILS.
DRY SLUDGE
STORAGE
AREA 2
DRY SLUDGE
STORAGE
AREA 1
1 2 3 4 5 6 7 8 9 10
SLUDGE BLENDING
ROOM
SEPTAGE RECEIVING
ELECTRICAL ROOM
RDT ROOMSTAIR
PIPE CHASE
HOT WATER PUMP ROOM CORRIDOR
UP
NOTES:
1. CONTRACTOR SHALL FURNISH AND INSTALL 60"H X 36"W
X 12"D PULLBOX, MINIMUM. CONTRACTOR SHALL SIZE
BOX PER THE MOST RECENT EDITION OF THE NEC.
BOTTOM OF PULLBOX SHALL BE 10'-6" AFF, MINIMUM.
ONLY TWO NEW CONDUITS ARE TO BE INSTALLED
BEYOND THIS BOX. THE REMAINING CONDUITS FROM THE
DUCTBANK TERMINATE AT THE PULLBOX.
2. APPROXIMATE CONDUIT ROUTE OF NEW CONDUITS
SHOWN FOR REFERENCE ONLY. CONTRACTOR SHALL
ROUTE CONDUITS FROM NEW PULLBOX TO EXISTING
WIRE TROUGH, ENSURING CONDUIT ROUTE ACROSS
EXISTING STAIR ADJACENT TO EXISTING HVAC
DUCTWORK DOES NOT IMPEDE EGRESS FROM EQUIPMENT
ROOM. COORDINATE EXACT CONDUIT ROUTE WITH
OWNER/ENGINEER AND SUBMIT ROUTING PLAN FOR
APPROVAL PRIOR TO INSTALLATION.
3. SEE ARCHITECTURAL DRAWINGS FOR FIRE PROTECTION
MEASURES AND ADDITIONAL INFORMATION.
4. EQUIPMENT ROOM, STAIR, AND RDT ROOM ARE ALL
CONSIDERED INDOOR WET PROCESS AREAS. ELECTRICAL
ROOM IS CONSIDERED AN INDOOR DRY NON-PROCESS
AREA.
5. DUCTBANK SHOWN FOR REFERENCE ONLY. SEE CIVIL
DRAWINGS FOR ADDITIONAL REQUIREMENTS AND
DETAILS.
SLUDGE BLENDING TANK
EQUIPMENT ROOM
E-700
A_______
UP
UP
SLUDGE BLENDING TANK:
SPACE CLASSIFIED PER NFPA-820-2024 EDITION, TABLE 6.2.2(a), ROW 10a:
CLASS I, DIVISION 1 AREAS:
• ENTIRE TANK
SLUDGE BLENDING ROOM:
SPACE CLASSIFIED PER NFPA-820-2024 EDITION, TABLE 6.2.2(a), ROWS 10a:
CLASS I, DIVISION 1 AREAS:
• ENTIRE ROOM
SEPTAGE RECEIVING ROOM:
SPACE CLASSIFIED PER NFPA-820-2016 EDITION, TABLE 5.2.2,
ROW 2a:
CLASS I, DIVISION 1 AREAS:
• ENTIRE ROOM
CLASS I, DIVISION 1
CLASS I, DIVISION 2
LEGEND:
DESIGNED BY:
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
PROJECT
ENGINEER:
DRAWN BY:
CHECKED BY:
REV ISSUED FOR DATE BY
HAZEN AND SAWYER
4035 RIDGE TOP ROAD, SUITE 400
FAIRFAX, VA 22030
N. MCDERMOTT
0 1/2" 1"
DATE:
HAZEN NO.:
CONTRACT NO.:
DRAWING
NUMBER:
PEPPER'S FERRY REGIONAL WASTEWATER
TREATMENT AUTHORITY
RADFORD, VIRGINIA
WASTEWATER TREATMENT FACILITY
MCC-6 FEEDER PROJECT
JULY 2024
31618-002
PFRWTA ID NO.: RFB 2024-01
C
U s e rs
\B F a ri s \D o c u m e n ts
\3 -0
-7
-S
H -E
L E C b fa ri s F Y N
E Q
.r v t
/1
/2
:4 :1
P
M
B. FARIS
D. ATKINSON
B. FARIS
E-700
SOLIDS HANDLING BUILDING
ELECTRICAL
POWER PLAN - UPPER AND LOWER
FLOORS - SOUTH
1/4" = 1'-0"
POWER PLAN - UPPER FLOOR - SOUTH
N
P L A N
T N
O R T H
1/4" = 1'-0"
POWER PLAN - LOWER FLOOR - SOUTH
SECTION
1/4" = 1'-0" E-700
A
NEW DUCTBANK,
SEE SITE PLAN
AND NOTE 5.
NEW PULLBOX, SEE NOTE 1.
EXISTING WIRE TROUGHTERMINATE NEW WIRES
IN SECTION 10 OF MCC-6
MCC-6
6#400KCMIL, 2#250KCMIL, #1/0GND, IN 4"C,
(1) 4"C, EMPTY W/PULLSTRING,
SEE NOTE 2.
DB
DB
DUCTBANK PENETRATION THROUGH
WALL, SEE DETAIL S-03-0402R
NEW PULLBOX, SEE NOTE 1.
NEW DUCTBANK,
SEE SITE PLAN
AND NOTE 5.
MCC-6 (ABOVE)
MCC-6 (ABOVE)
EXISTING WIRE TROUGH
6#400KCMIL, 2#250KCMIL,
#1/0GND, IN 4"C,
(1) 4"C, EMPTY W/PULLSTRING,
SEE NOTE 2.
SEE NOTE 3.
DESIGNED BY:
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
PROJECT
ENGINEER:
DRAWN BY:
CHECKED BY:
REV ISSUED FOR DATE BY
HAZEN AND SAWYER
4035 RIDGE TOP ROAD, SUITE 400
FAIRFAX, VA 22030
N. MCDERMOTT
0 1/2" 1"
DATE:
HAZEN NO.:
CONTRACT NO.:
DRAWING
NUMBER:
PEPPER'S FERRY REGIONAL WASTEWATER
TREATMENT AUTHORITY
RADFORD, VIRGINIA
WASTEWATER TREATMENT FACILITY
MCC-6 FEEDER PROJECT
APRIL 2024
31618-002
PFRWTA ID NO.: 2024-02
C
U s e rs
\B F a ri s \D o c u m e n ts
\3 -0
-7
-S
H -E
L E C b fa ri s F Y N
E Q
.r v t
/6
/2
:0 :3
P
M
B. FARIS
D. ATKINSON
B. FARIS
E-701
SOLIDS HANDLING BUILDING
ELECTRICAL
SINGLE LINE DIAGRAMS
MCC-6
BELT FILTER PRESS LCP
(LCP ME-25)
208V
NS
9F
SLUDGE
PUMP P-17E
7.5
30A
3P
EXISTING RELOCATED PUMP
AF
AT
A
MCP
K
FROM
SWGR-MAIN B
AF
AT
SPD-700
100kA
600:5
(3)
10A
10C
PMU
9A
TSH
C-800-044
10A
PREPARED
SPACE
10B
SECTION 7
PROPOSED ELEVATION
MCC-6
7C
7C
7A
7E
7D
SECTION 8
8C
8B
8A
8D
8F
8F
8E
SECTION 9
9A
9D
9F
9F
SECTION 10
10B
10C
9E
9E
9B
9B
10A
10A
9C
9C
7B
7B
MAIN
SIDE
B
TO
MCC-6
FROM
SWGR-MAIN
NEW CABLES IN NEW AND EXISTING
CONDUIT, SEE NOTE 1.
TERMINATE OUTGOING
WIRES HERE
TERMINATE INCOMING
WIRES HERE
SWGR-MAIN
PARTIAL SINGLE LINE DIAGRAM
MCC-6
PARTIAL SINGLE LINE DIAGRAM
NOTES:
1. NEW MCC-6 B-SIDE SUPPLY CONDUCTORS ARE
ROUTED FROM SWGR-MAIN (LOCATED WITHIN BLOWER
BUILDING) USING BOTH NEW AND EXISTING CONDUITS
THAT ARE BOTH EXPOSED AND WITHIN NEW AND
EXISTING DUCTBANKS. SEE SITE PLAN AND SOLIDS
HANDLING BUILDING POWER PLAN FOR FURTHER
INFORMATION.
2. CONTRACTOR NOTE: EXISTING CABLE THAT SUPPLIED
POWER TO THE B-SIDE OF MCC-6 FAULTED AND WAS
REMOVED IN ITS ENTIRETY BY THE OWNER.
NEW CABLES IN NEW AND EXISTING CONDUIT,
SEE NOTE 1.
SWGR-MAIN
ELEVATION (NOT TO SCALE)
MCC-6
PARTIAL ELEVATION (NOT TO SCALE)
MAY 2024JULY 2024
7B
MCC-6 B-SIDE MAIN
CIRCUIT BREAKER
MCC-6 BUS B
: RFB 2024-01
DESIGNED BY:
IF THIS BAR DOES NOT
MEASURE 1" THEN DRAWING
IS NOT TO FULL SCALE
PROJECT
ENGINEER:
DRAWN BY:
CHECKED BY:
REV ISSUED FOR DATE BY
HAZEN AND SAWYER
4035 RIDGE TOP ROAD, SUITE 400
FAIRFAX, VA 22030
N. MCDERMOTT
0 1/2" 1"
DATE:
HAZEN NO.:
CONTRACT NO.:
DRAWING
NUMBER:
PEPPER'S FERRY REGIONAL WASTEWATER
TREATMENT AUTHORITY
RADFORD, VIRGINIA
WASTEWATER TREATMENT FACILITY
MCC-6 FEEDER PROJECT
APRIL 2024
31618-002
PFRWTA ID NO.: 2024-02
C
U s e rs
\B F a ri s \D o c u m e n ts
\3 -0
-7
-S
H -E
L E C b fa ri s F Y N
E Q
.r v t
/6
/2
:0 :3
P
M
B. FARIS
D. ATKINSON
B. FARIS
E-702
ELECTRICAL
STANDARD DETAILS
TYPICAL DUCTBANK SECTION
E-33-0101
NOTES:
1. CONCRETE SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH SPECIFICATION
SECTION 03 30 00.
2. REINFORCING STEEL AND TIES SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH
SPECIFICATION SECTION 03 21 00. OVERLAP FOR REINFORCING STEEL SPLICES ALONG THE
DUCTBANK LENGTH SHALL BE 15", MINIMUM.
3. CONDUIT SPACERS ARE REQUIRED IN ACCORDANCE WITH SPECIFICATION SECTION 33 71 19.
HORIZONTAL SPACING OF CONDUIT SPACER ASSEMBLIES ALONG LENGTH OF DUCTBANK
SHALL BE AS SHOWN IN THE TABLE.
4. FOR DUCTBANKS LESS THAN 15" IN HEIGHT, THE LAP SHALL BE THE HEIGHT OF THE DUCTBANK.
5. IN POOR SOIL CONDITIONS, DUCTBANKS SHALL BE FORMED WITH FORMING MATERIALS TO
MAINTAIN 4” MINIMUM ENCASEMENT. WHERE SOIL CONDITIONS PERMIT AND THE EXCAVATION
IS MAINTAINED FOR A 4” MINIMUM TO 10” MAXIMUM ENCASEMENT, THE FORMWORK CAN BE
OMITTED.
MAX SPACING BETWEEN CONDUIT
SPACER ASSEMBLIES
CONDUIT SIZE SPACING
1" 3 FT
1 1/4-2" 5 FT
2 1/2-3" 6 FT
3 1/2-5" 7 FT
6" 8 FT
" M
IN
DUCTBANK WIDTH AND
HEIGHT AS REQUIRED
2", TYP
#4 REINFORCING STEEL (U-BAR)
SPACED EVERY 36" HORIZONTALLY
ALONG LENGTH OF DUCTBANK
#4 REINFORCING STEEL SPACED
EVERY 12" AND AT EVERY
CORNER, TYP 4 SIDES
CONDUIT SIZE(S), QUANTITY
AND TYPE AS REQUIRED
TIE, TYP
2"
(TYP)
4" MIN, 6" MAX CONCRETE
ENCASEMENT AROUND ALL DUCTS 24" MIN COVER
FINISHED GRADE
#4 REINFORCING STEEL BARS
DRIVEN INTO SOIL OR SET IN
CONCRETE PAD, SPACED EVERY
72" HORIZONTALLY ALONG LENGTH
OF DUCTBANK, TYP EACH SIDE
" M
IN
L
AP
CONDUIT SPACER ASSEMBLY,
SIZE AND CONFIGURATION AS
REQUIRED
#4/0 BARE COPPER GROUNDING
CONDUCTOR, INSTALLED INSIDE
REINFORCING STEEL CAGE
CONCRETE ENCASEMENT
AROUND DUCTS, TYP
SPACING DEPENDS UPON NUMBER OF
DUCTS AND TYPE OF SPACERS
SE
E
N O
TE
FORMWORK, SEE NOTE 5
CONDUIT, TYP
1" SPONGE RUBBER
EXPANSION JOINT
MATERIAL (TYP ALL
AROUND)
CONNECT GROUNDING
ELECTRODE CONDUCTOR
TO BLDG GROUNDING
ELECTRODE SYSTEM
CONDUIT BELL END FITTINGS
FINISHED FLUSH WITH INSIDE
WALL, SEE NOTE 2
OUTSIDE INSIDE
1"x4" ELASTOMERIC BEARING PAD (50
DUROMETER) UNDERSIDE OF ENCASEMENT
ONLY, FULL WIDTH. ADHERE TO BASE WITH
APPROVED ADHESIVE
NOTES:
1. BLOCK-OUT IN WALL SHALL BE SMOOTH AND PLUM BUILT TO
ACCOMMODATE THE REQUIRED CONCRETE DUCT BANK ENCASEMENT
PLUS 1" ALL AROUND.
2. INSTALL EXPANDING FOAM SEALANT IN CONDUIT AROUND
CONDUCTORS PER MANUFACTURER'S RECOMMENDATIONS.
CAULK WITH 1" SYNTHETIC
RUBBER ALL AROUND, EACH
FACE
CONCRETE DUCT BANK
ENCASEMENT, SEE DUCT
BANK SCHEDULE FOR SIZE,
PER STANDARD DETAIL
E-33-0101
WALL
BELOW-GRADE DUCT BANK TERMINATION TO EXISTING MANHOLE
WATERPROOF MEMBRANE PATCH
PER SPECIFICATION SECTION 03 15 00
(TYP ALL AROUND)
CL
COMPACTED
SUBGRADE
E-33-0106
MAY 2024JULY 2024
BELL END BUSHING, TYP
GROUND CONDUCTOR
CONDUIT(S)
#4 ADH DWLS @8"OC, EF (ALT
FACES) EMBED 8", SEE NOTE 3
SECTION A-A
#4 ADHESIVE DWLS, TYP
EXP RUBBER WS, CENTERED
IN WALL, CONT ALL AROUND
OPNG W/ 6" MIN LAP AT ENDS
S-03-0402R
CONCRETE ENCASEMENT, SEE
TYPICAL DUCT BANK DETAIL
ENCASED ELECTRICAL CONDUITS
AT EXISTING STRUCTURES
CJ
18" MIN,
SEE NOTE 1
NOTES:
1. CLASS A CONCRETE SHALL BE USED FOR THE CONCRETE
ENCASEMENT WHERE ENTERING EXISTING BUILDING WALL.
CLASS B CONCRETE MAY USED BEYOND THESE EXTENTS.
2. FOR DUCT BANKS LESS THAN 15" IN HEIGHT, THE LAP SPLICE
SHALL BE THE HEIGHT OF THE DUCTBANK OR TO THE
GREATEST LENGTH POSSIBLE.
3. REINFORCING DOWELS SHALL BE POSITIONED TO PASS
BETWEEN DUCT BANK CONDUIT, ADJUST SPACING TO 10" ON
CENTER MAXIMUM WHERE REQUIRED.
INSIDE FACE OF EXIST
CONC WALL, TYP
OUTSIDE FACE OF EXIST
CONC WALL, TYP
EXP RUBBER WS, CENTERED IN
WALL, CONT ALL AROUND OPNG
W/ 6" MIN LAP AT ENDS
SAW CUT LINE, TYP
A A
M
IN
L
A P
S
E E
N O
T E
: RFB 2024-01
| GENERAL |
| COVER |
| G-001 ABBREVIATIONS AND LEGEND |
| CIVIL |
| C-001 SITE PLAN |
| C-002 PARTIAL SITE PLAN AND PROFILE |
| C-003 DETAILS |
| ARCHITECTURAL |
| A-700 SOLIDS HANDLING BUILDING |
| ELECTRICAL |
| E-001 SITE PLAN |
| E-700 SOLIDS HANDLING BUILDING POWER PLAN |
| E-701 SOLIDS HANDLING BUILDING SINGLE LINE DIAGRAMS |
| E-702 DETAILS |
| 2024-07-24T14:06:50-0400 | |
| Matthew Van Horne |
| 2024-07-24T14:06:58-0400 | |
| Matthew Van Horne |
| 2024-07-24T17:46:01-0400 | |
| Benjamin Slaughter |
| 2024-07-24T17:46:11-0400 | |
| Benjamin Slaughter |
| 2024-07-24T17:46:19-0400 | |
| Benjamin Slaughter |
| 2024-07-25T14:37:24-0400 | |
| Raleigh | |
| William H. Russell | |
| I have reviewed this document |
| 2024-07-29T10:23:14-0400 | |
| David A. Atkinson Jr. |
| 2024-07-29T10:23:19-0400 | |
| David A. Atkinson Jr. |
| 2024-07-29T10:23:24-0400 | |
| David A. Atkinson Jr. |
| 2024-07-29T10:23:33-0400 | |
| David A. Atkinson Jr. |
File details come from the government source that posted it. Updated .