2024_06_26_PerryWorrallCenter_BidSet_NBP.pdf
PDF 2 MB Posted
- Attached to
- 2025-02 PERRY WORRALL COMMUNITY CENTER HVAC
- Solicitation number
- PE-66243-NONST-2024-000000026
- Issued by
- Henry County, Georgia
About this file
This document contains drawings, schedules, and legends related to the replacement of a packaged air conditioning unit at the Perry Worrall Community Center in Perry, Georgia. The project involves the removal of the existing packaged air conditioning unit and associated electrical components, and the installation of a new air handling unit, ductwork, and electrical connections. The drawings detail the demolition work and the new work to be performed, including the routing of supply and return air ducts, the installation of a new gas line, and the replacement of the electrical disconnect serving the air handling unit. The project is being bid by the City of Perry, with a bid set date of June 26, 2024.
The drawings provide technical specifications for the new packaged air conditioning unit, including its capacity, electrical requirements, and features such as a discharge plenum, hot gas reheat, and staged air volume control. No additional details are provided regarding pricing, funding sources, or contract terms.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Ad 2025_02 Packaged AC Replacement _ Worrall .pdf | ||
| 2025_02 Packaged AC Replacement _ Worrall Com.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INDEX OF
DRAWINGS
PROJECT CONSULTANTS
M001
M101
M201
E001
E101
E201
SHEET NO. TITLE
NBP ENGINEERS, INC.
MACON, GEORGIA316 CORPORATE PARKWAY
NBP
ENGINEERS
CONSULTANTS
478-745-1691 www.nbpengineers.com
ABBREVIATIONS, LEGENDS, SCHEDULES, & DETAILS - HVAC
PARTIAL FLOOR PLAN - DEMOLITION - ELECTRICAL
PARTIAL FLOOR PLAN - NEW WORK - ELECTRICAL
NBP Project No.: 23031
Packaged AC Replacement
City of Perry - Perry, Georgia
Perry Worrall Community Center
LARGE SCALE - PARTIAL FLOOR PLAN - DEMOLITION - HVAC
LARGE SCALE - PARTIAL FLOOR PLAN - NEW WORK - HVAC
LEGEND & SCHEDULES - ELECTRICAL
06.26.24 BID SET
SEAL
SCALE:
FILE PATH:
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\23031\23031m001.dgn
AS SHOWN
WSH
LTF
WSH
06.26.24
N B P
P ro je c t
N o
COA Expiration: 6.30.2024
NBP Engineers, Inc. COA#PEF000774
P:\23031\23031m001.dgn
DATE PLOTTED
DGN FILE
25-JUN-2024
23031
P e rr y
W o rr a ll C o m m u n it y
C e n te r
P a c k a g e d
A C
R p la c e m e n t
C it y o f P e rr y
P e rr y G e o rg ia
B
ID
S E
T
M001
A COMPRESSED AIR
AAV AUTOMATIC AIR VENT
AF AIR FOIL
-AFF ABOVE FINISHED FLOOR
AV ACID VENT
AVD AUTOMATIC VOLUME DAMPER
AW ACID WASTE
-AC ABOVE CEILING
AH- AIR HANDLING UNIT
BBD BOILER BLOW DOWN
BE BOTTOM ELEVATION
BOL BOTTOM OF LINE (UNINSULATED)
BOD BOTTOM OF DUCT
BP- BOOSTER PUMP
BTUH BRITISH THERMAL UNIT PER HOUR
-BF BELOW FLOOR
BFP BACK FLOW PREVENTOR
C CONDUIT
CC COOLING COIL
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CR CONDENSER WATER RETURN
CS CONDENSER WATER SUPPLY
CW DOMESTIC COLD WATER
CAB CABINET FAN
CF CENTRIFICAL FAN
CFM CUBIC FEET PER MINUTE
CFP CHEMICAL FEED PUMP
CFT CHEMICAL FEED TANK
CH CABINET HEATER
CHR CHILLER
CL CENTER LINE
CO CLEANOUT
CP CHILLER PUMP
CPHB CHROME PLATED HOSE BIBB
CT COOLING TOWER
CU COPPER
CV- CONVECTOR
Cv VALVE COEFFICIENT
D DRAIN
DDC DIRECT DIGITAL CONTROL
DHW DOMESTIC HOT WATER
DN DOWN
DP DIFFERENTIAL PRESSURE
DS DOWN SPOUT
DSO DOWN SPOUT OVER FLOW
DX DIRECT EXCHANGE
EAD EXHAUST AIR DAMPER
EAT ENTERING AIR TEMPERATURE
EDB ENTERING DRY BULB
EWB ENTERING WET BULB
ESP END SUCTION PUMP
ESP EXTERNAL STATIC PRESSURE
ELL ELBOW
ET EXPANSION TANK
EQT EQUIPMENT TRAP SET
EWT ENTERING WATER TEMPERATURE
EX EXPANSION TANK LINE
EXT EXTERNAL
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
F&BP FACE & BYPASS
FC FAN COIL UNIT
BPD BYPASS DAMPER
EAL EXHAUST AIR LOUVER
ECH ELECTRIC CABINET HEATER
ABBREVIATIONS
FD FLOOR DRAIN
FF FOULING FACTOR
FF- FLY FAN
FF FINISHED FLOOR
FF FINAL FILTER
FFM FIRE FLOW METER
FLEX FLEXIBLE
FM FIRE MAIN
FMS FLOW METER STATION
FOF FUEL OIL FLOW
FOR FUEL OIL RETURN
FOV FUEL OIL VENT
FOP FUEL OIL PUMP
FP FIRE PUMP
FP- FAN POWERED
FPM FEET PER MINUTE
FPS FEET PER SECOND
FRT FLOW RATE TRANSMITTER
FT FEET
G LOW PRESSURE GAS
GA GAUGE
GPM GALLONS PER MINUTE
GT GREASE TRAP
GTH GRAND TOTAL HEAT
H HEIGHT
HC HEATING COIL
HB HOSE BIBB
HBT HORIZONTAL BLOW THROUGH
HD HUB DRAIN
HDT HORIZONTAL DRAW THROUGH
HP HORSEPOWER/HIGH PRESSURE
HPA HIGH PRESSURE AIR
HPG HIGH PRESSURE GAS
HPS HIGH PRESSURE STEAM
HPWS HEAT PUMP WATER SUPPLY
HPWR HEAT PUMP WATER RETURN
HSC HORIZONTAL SPLIT CASE
HWG HOT WATER GENERATOR
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
ILC IN-LINE CENTRIFICAL
IT INTERVAL TIMER
IN INCHES
INV INVERT
JB JUNCTION BOX
L LENGTH
LR LONG RADIUS
LAT LEAVING AIR TEMPERATURE
LCP LOCAL CONTROL PANEL
LDB LEAVING DRY BULB
LN LIQUID NITROGEN
LWB LEAVING WET BULB
LWT LEAVING WATER TEMPERATURE
LPS LOW PRESSURE STEAM
MAV MANUAL AIR VENT
MVD MANUAL VOLUME DAMPER
MAX MAXIMUM
MBH ONE THOUSAND BTUH PER HOUR
MCC MOTOR CONTROL CENTER
MIN MINIMUM
MH MAN HOLE
MP SUMP (MUD) PUMP
MPS MEDIUM PRESSURE STEAM
MPR MEDIUM PRESSURE RETURN
MTS MEDIUM TEMPERATURE SUPPLY
MTR MEDIUM TEMPERATURE RETURN
MUA MAKE-UP AIR
MUW MAKE-UP WATER
MZ MULTIZONE
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OA OUTSIDE AIR
OAD OUTSIDE AIR DAMPER
ODT OUTDOOR TEMPERATURE
PC PUMP CONDENSATE
PD PRESSURE DROP
PRV PRESSURE REDUCING VALVE
PWF PROPELLER WALL FAN
R REFRIGERANT
RA RETURN AIR
RAD RETURN AIR DAMPER
RAS RELIEF AIR SUPPLY
RP RECIRCULATING PUMP
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
RD ROOF DRAIN
RV RELIEF VALVE
SR SHORT RADIUS
OAL OUTSIDE AIR LOUVER
SAN SANITARY SEWER
SC SILL COCK
SCD SMOKE DAMPER
SD STORM DRAIN
SD SMOKE DETECTOR
SF SQUARE FEET
SDO STORM DRAIN OVERFLOW
SHC SENSIBLE HEAT CAPACITY
SP STAND PIPE
SP SUMP PUMP
SPS STATIC PRESSURE SENSOR
STA STATION
TR TEMPERED WATER RETURN
UG UNDERGROUND
VAC VACUUM PIPING
VDT VERTICAL DRAW THROUGH
VTR VENT THROUGH ROOF
WB WET BULB
O2 OXYGEN
?F DEGREES FAHRENHEIT
?C DEGREES CENTIGRADE
WM WATER METER
WL WATER LINE
WH WATER HEATER
WG WATER GAUGE
W WIDTH
W WASTE
VT VERTICAL TURBINE
VFD VARIABLE FREQUENCY DRIVE
VB VACUUM BREAKER
VAV VARIABLE AIR VOLUME
V VENT
UC UNDERCUT (DOOR - 3/4")
V- VALVE
TOS TOP OF STRUCTURE
TB THRUST BLOCK
T TEMPERED WATER
STR STRAINER
SP STATIC PRESSURE
SP SPRINKLER PIPE
SG SPECIALTY GAS
EUH ELECTRIC UNIT HEATER
RECIRCULATING
DHR DOMESTIC HOT WATER
TRANSMITTER
DPT DIFFERENTIAL PRESSURE
PER MINUTE
SCIM STANDARD CUBIC INCHES
TEMPERATURE
SST SATURATED SUCTION
(UNINSULATED)
TE TOP ELEVATION
(TOWER) PUMP
TP CONDENSER WATER
FSD FIRE/SMOKE DAMPER
EA EXHAUST AIR
MA MIXED AIR
AE ADJUSTABLE AIR EXTRACTOR
RAO RETURN AIR OPENING
AD AREA DRAIN/ACCESS DOOR
SINGLE LINE DUCT LEGEND
DUCT (SUPPLY, RETURN & EXHAUST)
SUPPLY DUCT UP
SUPPLY DUCT DOWN
RETURN OR EXHAUST DUCT UP
RETURN OR EXHAUST DUCT DOWN
DUCT RISE
DUCT DOWN
VOLUME DAMPER (MANUAL UNLESS INDICATED A.V.D.)
TRANSITION
DUCT TAKE-OFF (SEE SPEC. PERTAINING TO DEFLECTROLS)
TRANSITION (FLAT ON TOP)
TRANSITION (FLAT ON BOTTOM)
TRANSITION (TOP OR BOTTOM ONLY)
SUPPLY CEILING DIFFUSER
RETURN OR EXHAUST CEILING GRILLE
SIDEWALL SUPPLY
SIDEWALL RETURN
FLEXIBLE CONNECTION (DUCT)
RELIEF AIR SUPPLY TO TOILET
DUCT SPLIT WITH SPLITTER DAMPER
FLEX. DUCT WITH SCREW ON COLLAR, TAKE-OFF
DUCT WITH DUCT LINER
SQUARE ELBOW WITH TURNING VANES
RADIUS ELBOW (SEE SPECS. PERTAINING TO TURNING VANES)
AUTOMATIC VOLUME DAMPER
DN
R
12\10 SPLIT
OR
OR
SCD
FOB
T OR B
RAS
AVD
FD/SCD
FD
SMOKE CONTROL DAMPER
COMBINATION FIRE/SMOKE CONTROL DAMPER
FIRE DAMPER (FD)
FIRE DAMPER
SPS
SD
COMBINATION STARTER
STARTER
PIPE SLEEVE
CONCENTRIC REDUCER
PIPE ANCHOR
HVAC LEGEND
GATE VALVE WITH
3/4" HOSE END
BALANCE VALVE
THREADED & FLANGED
GLOBE VALVE
CHECK VALVE
3-WAY MIXING VALVE
GATE VALVE
BUTTERFLY VALVE
SOLENOID VALVE
CONTROL VALVE
PLAN VIEW
2-WAY MOTORIZED VALVE
RELIEF VALVE
FLANGED UNION
BRANCH OUT TOP
STRAINER
BRANCH OUT BOTTOM
ELBOW DOWN
ELBOW UP
TEE OUT TOP
BLIND FLANGE
PIPE CAP
AUTOMATIC AIR VENTAAV
FLEX. PIPE CONN.
BACKFLOW PREVENTER
THERMOMETER
TEE OUT BOTTOM
MANUAL AIR VENT
PIPE TEST PLUG
CHILLED WATER FLOW
HEATING WATER FLOW
COLD WATER DOMESTIC
NATURAL GAS
CONDENSER WATER FLOW
DRAIN
CHILLED WATER RETURN
HEATING WATER RETURN
HOT WATER DOMESTIC
G
D
DUCT SIZE FIRST DIMENSION
IS SIDE SHOWN
24\12
DOOR GRILLE
C.F.M.
REFERS TO DETAIL OR
PLAN ON SHEET M-1.THERMOSTAT
INTERVAL TIMER
T
I.T.
1\M-4
DUCT/PLENUM w/LINER
FIRE DAMPER
ELBOW WITH
TURNING VANES
FLEX. DUCT CONN.
TURNING VANES
ELBOW WITHOUT
ADJUSTABLE AIR
EXTRACTOR
INSULATED FLEX. DUCT
INSULATED FLEX. DUCT
c
ECCENTRIC REDUCER
HWS
HWR
CHS
CHR
CONDENSER WATER RETURN
CS
CR
STATIC PRESSURE SENSOR
SMOKE DETECTOR
POINT OF CONNECTION
DUCT SPLIT
THREADED & FLANGED
THREADED & FLANGED
UNION
GAUGE TAPPING
GAUGE WITH TAPPING
THREADED & FLANGED
THREADED & FLANGED
PIPE SOCKET WELL
FLOW INDICATOR BALANCER
M
T G THERMOSTAT w/GROUND
ANNULAR ELEMENT FLOW STATION
M
DAMPER - BLADE VIEW DAMPER - END VIEW
xx{K OR xx/xx}K ROUND OR FLAT OVAL DUCT (K)
DOUBLE WALL INSULATED
ROUND OR FLAT OVAL DUCTxx{ OR xx/xx}
SYMBOL
TOTAL EXT. S.P.
IN H O2 SENSIBLE TOTAL
ENTERING AIRMOTOR
HP
COOLING COIL GAS HEATING COIL
MIN. MAX.
LAYOUT BASIS
F
MANUFACTURER APPROX.
MIN. MIN.
LEAVING AIR
F
MCA/MOP
LBS.
MBH
INPUT
MBH
OUTPUT
WEIGHT
CFM CFM
MBH MBH
NOTES:
MIN. OA
0.75
DB/WB DB/WB
80/67
CARRIER
REMARKS
SUMMER WINTER
DESIGN CONDITIONS
OUTSIDE
INSIDE 75 F DB / 55% RH
93 F DB / 76 F WB
72 F DB
15 F DB
PROVIDE DISCHARGE PLENUM FOR HORIZONTAL DISCHARGE; HOT GAS REHEAT; STAGED AIR VOLUME CONTROL; ECONOMIZER; POWERED EXHAUST.
ELECTRICAL
151 / 175 48FCFN28A 2541 132440059.8/57.82932187.510,000 1,500AHU-1
PACKAGED AIR CONDITIONING UNIT SCHEDULE
A
B
UNIT TYPE
WHERE X = STATIC PRESSURE IN PAN IN INCHES - H2O
A B
ADAPTER
DRAW THRU 2" PLUS X X
AIR HANDLING UNIT DRAIN TRAP
CLEAN OUT
LOOSE CAP
DRAIN PIPE AS SPECIFIED
BLOW THRU 1" MIN. 1.5"X
CONDENSATE DRAIN DRY WELL
GRADE
12" MIN.
OPEN
BACKFILL
FILL PIPE WITH CLEAN GRAVEL,
•" AND LARGER AGGREGATE.
CONDENSATE DRAIN
8" PVC PIPE MIN.
NOT TO SCALE
DRAIN PAN
SAME SIZE AS THE NIPPLE ON THE DRAIN PAN
DRAIN LINE SHALL BE AT LEAST THE
NOT TO SCALE
& DETAILS - HVAC
SCHEDULES,
LEGENDS,
ABBREVIATIONS,
PER FOOT SLOPE
MINIMUM 1/8 INCH
SLOPE TO DRYWELL AT
M101
SCALE:
= 1'-0
4 0 2 4 8
N
AH-1
& ASSOCIATED DISCHARGE PLENM
REMOVE EXISTING PACKAGED UNIT
SA & RA DUCTS
REMOVE EXISTING
T
THERMOSTAT
EXISTING
REMOVE
EXISTING TO REMAIN
DEMOLITION
LINE LEGEND
GAS PIPING CONNECTION TO HVAC UNIT.
CLOSE VALVE AND REMOVE EXISTING
VALVE ARE TO REMAIN.
EXISTING GAS PIPING AND
LARGE SCALE - PARTIAL FLOOR PLAN - DEMOLITION - HVAC
DEMOLITION - HVAC
FLOOR PLAN -
PARTIAL
LARGE SCALE -
3 4
C
B
A
1 16
COMMUNITY ROOM
1 18
PLATFORM
KITCHEN
STOR.
PANTRY
CRAFTS ROOM 124
RM
SICK
TOIL.
1 17
FOYER
COURTYARD
MECHANICAL
1 19
ELEC.
R A
M P
U
SEAL
SCALE:
FILE PATH:
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\23031\23031m101.dgn
AS SHOWN
WSH
LTF
WSH
06.26.24
KEY-PLAN
NOT TO SCALE
N B P
P ro je c t
N o
AREA OF WORK
COA Expiration: 6.30.2024
NBP Engineers, Inc. COA#PEF000774
P:\23031\23031m101.dgn
DATE PLOTTED
DGN FILE
25-JUN-2024
23031
P e rr a ll C o m m u n it y
C e n te r
P a c k a g p la c e m e n t
BUILDING
C it y o f P e rr y
P e rr y G e o
T
M201
AH-1NEW
SCALE:
= 1'-0
4 0 2 4 8
N
LINE LEGEND
POINT OF CONNECTION
EXISTING TO REMAIN
NEW WORK
THERMOSTAT
NEW
T
R
62/22
60/20 RA
60/20 SA
PROVIDE NEW INSULATED METAL BLANK OFF AROUND DUCT AT WALL.
NOTES:(THIS SHEET ONLY)
STACKED
DUCTS
SA/RA
DISCHARGE CONDENSATE INTO NEW DRY WELL.
PROVIDE DISCHARGE PLENUM.
ROUTE THRU EXISTING OPENING
CONNECTION ON HVAC UNIT. SUPPORT PIPING AT 6' ON CENTER.
CONNECT NEW GAS PIPING AT VALVE. ROUTE GAS PIPING LINE SIZE TO NEW5
G
G
G
G
LARGE SCALE - PARTIAL FLOOR PLAN - NEW WORK - HVAC
CONNECT NEW SA AND RA DUCTS TO EXISTING SA/RA AT EXTERIOR WALL.
NEW WORK - HVAC
FLOOR PLAN -
PARTIAL
LARGE SCALE -
3 4
C
B
A
1 16
COMMUNITY ROOM
1 18
PLATFORM
KITCHEN
STOR.
PANTRY
CRAFTS ROOM 124
RM
SICK
TOIL.
1 17
FOYER
COURTYARD
MECHANICAL
1 19
ELEC.
R A
M
U
SEAL
SCALE:
FILE PATH:
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\23031\23031m201.dgn
AS SHOWN
WSH
LTF
WSH
06.26.24
KEY-PLAN
NOT TO SCALE
N B P
P ro je c t
N o
AREA OF WORK
COA Expiration: 6.30.2024
NBP Engineers, Inc. COA#PEF000774
P:\23031\23031m201.dgn
DATE PLOTTED
DGN FILE
25-JUN-2024
23031
P e rr a ll C o m m u n it y
C e n te r
P a c k a g p la c e m e n t
BUILDING
C it y o f P e rr y
P e rr y G e o
FILE PATH:
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\23031\23031e001.dgn
AS SHOWN
06.26.24
N B P
P ro je c t
N o
TWT
LTF
TWT
COA Expiration: 6.30.2024
NBP Engineers, Inc. COA#PEF000774
P:\23031\23031e001.dgn
DATE PLOTTED
DGN FILE
25-JUN-2024
23031
P e rr a ll C o m m u n it y
C e n te r
P a c k a g p la c e m e n t
C it y o f P e rr y
P e rr y G e o
E001
CT
TRACK LIGHTS: QUANTITY OF HEADS AS SHOWN EMERGENCY BATTERY PACK-CEILING
EMERGENCY BATTERY PACK-WALL
PANELBOARD-250 VAC OR LESS
SURFACE MOUNTED
PANELBOARD-250 VAC OR LESS
RECESSED
PANELBOARD-OVER 250 VAC
SURFACE MOUNTED
PANELBOARD-OVER 250 VAC
RECESSED
CABLE TRAY
BACKBOARD
CONNECTION TO EQUIPMENT
CAP
CONDUIT DOWN
CONDUIT UP
J
F
BT
C
C
BR
SLAB OR BELOW GRADE
GROUNDING CONDUCTOR- UNDER
U
SP
DP
PE
M
ICM
S
V
S
IC
MM
MC
GG
G
LIGHTING FIXTURES (SYMBOLS VARY BASED ON FIXTURES TYPE)
LIGHTING CONTROL
RECEPTACLES
CIRCUITS
GENERAL EQUIPMENT
FIRE PROTECTION EQUIPMENT
COMMUNICATIONS
LIGHTNING PROTECTION AND GROUNDING
T
JJ
I
UI
I
ELECTRICAL LEGEND
TV
C
G
B
K
LED ON "NORMAL" POWER
CEILING MOUNTED FIXTURE
WALL MOUNTED FIXTURE
EXIT LIGHT (ARROWS AS SHOWN)
LIFE SAFETY EGRESS FIXTURE
CEILING MOUNTED ULTRASONIC OCCUPANCY
SENSOR AND RELAY
CEILING/WALL MOUNTED INFRARED OCCUPANCY
SENSOR AND RELAY
CEILING MOUNTED COMBINATION INFRARED/
ULTRASONIC OCCUPANCY SENSOR AND RELAY -
SWITCHING PHOTOCELL (INTERIOR TYPE) F.C. NOTED
DIMMING PHOTOCELL (INTERIOR TYPE)
EXTERIOR TYPE PHOTO SWITCH
LOW VOLTAGE OVERRIDE SWITCH
INFRARED OCCUPANCY SENSOR
WALL MOUNTED SWITCH
"P" INDICATES PILOT LIGHT
KEYED SWITCH
DIMMER SWITCH
FOUR WAY SWITCH
THREE WAY SWITCH
SINGLE POLE SWITCH
DUPLEX RECEPTACLE - NORMAL
QUAD - NORMAL
GFCI DUPLEX RECEPTACLE - NORMAL
GFCI QUAD - NORMAL
FLOOR DUPLEX RECEPTACLE - NORMAL
FLOOR QUAD - NORMAL
CEILING DUPLEX RECEPTACLE - NORMAL CLOCK OUTLET
WALL/CEILING RACEWAY
CEILING SPECIAL - TYPE NOTED OR SHOWN
SPECIAL - TYPE NOTED OR SHOWN
HORIZONTALLY MOUNTED DUPLEX RECEPTACLE
WEATHER PROOF RECEPTACLE (GFCI)
ELECTRIC WATER COOLER RECEPTACLE(GFCI)
CONDUIT CONCEALED IN CEILING OR WALL
CONDUIT IN GROUND, SLAB, OR UNDER FLOOR
FLEXIBLE RACEWAY
RACEWAY EXPOSED
TRANSFORMER
FRAME AMPS/POLES/NEMA TYPE
FUSE PER MANUFACTURERS RECOMMENDATIONS
ENCLOSED BREAKER-RECESSED IN WALL
ENCLOSED CIRCUIT BREAKER
EMERGENCY PUSHBUTTON
COMBINATION STARTER AND DISCONNECT
EXHAUST FAN
MANUAL STARTER AND MOTOR RATED SWITCH
MOTOR
JUNCTION BOX - WALL/CEILING/FLOOR
SURGE SUPPRESSOR
VOICE OUTLET, QUANTITY OF JACKS AS NOTED
DATA OUTLET, QUANTITY OF JACKS AS NOTED
COMBINATION VOICE/DATA OUTLET, QUANTITY OF
VOICE/DATA JACKS AS NOTED
FLOOR VOICE OUTLET, QUANTITY OF JACKS
AS NOTED
FLOOR DATA OUTLET, QUANTITY OF JACKS
AS NOTED
FLOOR COMBINATION VOICE/DATA OUTLET,
QUANTITY OF JACKS AS NOTED
MASTER CLOCK
INTERCOM MASTER STATION
INTERCOM CALL-IN STATION
WALL MOUNTED VOLUME CONTROL
BOX, STUB-UP, AND MODULAR PLATE W/ BLANKS
TELEVISION OUTLET
SPEAKER: CEILING/WALL
MICROPHONE: FLOOR/WALL
FIBER OUTLET
GROUND ROD - C IF CHEMICAL
GROUND CONNECTION (SCHEMATIC)
CONCEALED IN ROOF OR WALLS
GROUNDING CONDUCTOR-
GROUNDING CONDUCTOR- EXPOSED
AIR TERMINAL
GROUNDING PLATE
FACP
FAA
WF
VS
DH
SMOKE DETECTOR/SENSOR - BEAM RECEIVER
SMOKE DETECTOR/SENSOR - BEAM TRANSMITTER
SPEAKER/VISUAL ALARM: CEILING/WALL
VISUAL ALARM: CEILING/WALL
AUDIO/VISUAL ALARM: CEILING/WALL
MANUAL PULL STATION
FIRE ALARM ANNUNCIATOR
FIRE ALARM PANEL
DUCT MOUNTED SMOKE DETECTOR
SMOKE DETECTOR: CEILING / WALL
HEAT DETECTOR: CEILING / WALL
WATER FLOW SWITCH
WATER TAMPER SWITCH
DOOR HOLDER
FIREMAN'S PHONE OUTLET
EWC
WP
H
D
P
I
L
TWO ZONE LOW VOLTAGE SWITCHL2
VACANCY AUTO SHUT OFF
FOUR ZONE LOW VOLTAGE SWITCHL4
DUPLEX RECEPTACLE WITH INTEGRAL USBUSB
TV DUPLEX RECEPTACLETV
AC
ABOVE COUNTER DUPLEX RECEPTACLE (COORDINATE
HEIGHT WITH ARCHITECT)
J-HOOK
SECURITY
C CARD READER
P DOOR POSITION SENSOR
SECURITY CAMERA: CEILING/WALL MOUNTED
ES ELECTRIC STRIKE
C
CABLE TRAY
DUPLEX RECEPTACLE MOUNTED IN RACEWAYR
R DATA OUTLET MOUNTED IN RACEWAY
DUPLEX RECEPTACLE - TAMPER PROOFT
DUPLEX RECEPTACLE - GENERATOR CIRCUIT, RED IN COLOR
QUAD - GENERATOR CIRCUIT, RED IN COLOR
SINGLE ZONE LOW VOLTAGE SWITCHL1
HOMERUN - ONE ARROW PER CIRCUIT
DISCONNECT SWITCH: "F" IF FUSED
F
ELECTRICAL
SCHEDULES -
LEGEND &
FILE PATH:
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\23031\23031e101.dgn
AS SHOWN
06.26.24
N B P
P ro je c t
N o
TWT
LTF
TWT
COA Expiration: 6.30.2024
NBP Engineers, Inc. COA#PEF000774
P:\23031\23031e101.dgn
DATE PLOTTED
DGN FILE
25-JUN-2024
23031
P e rr a ll C o m m u n it y
C e n te r
P a c k a g p la c e m e n t
C it y o f P e rr y
P e rr y G e o
T
1 2 3 4
6 7 8 9 10
E
D
C
1 18
PLATFORM
KITCHEN
STOR.
PANTRY
DINING ROOM
ROOM
MULTI-PURPOSE
O.A.C.
CRAFTS ROOM 124
RM
SICK
TOIL.
COURTYARD
MECHANICAL
1 19
ELEC.
COURTYARD
MECHANICAL
MECH. CHASE
STORAGE
LOCKERS
LOCKERS
GYMNASIUM
E101
PARTIAL FLOOR PLAN - DEMOLITION - ELECTRICAL
SCALE:
= 1'-0
8 0 4 8 16
ELECTRICAL
DEMOLITION -
FLOOR PLAN -
PARTIAL
AH-1
NOTES:(THIS SHEET ONLY)
N
PM
150A/3P CIRCUIT BREAKER SERVING AIR HANDLING UNIT BEING REMOVED.
EXISTING GE SPECTRA SERIES 1000 AMP, 208 VOLT, 3 PHASE PANEL PM. REMOVE EXISTING
CONDUIT MAY NOT STILL BE VIABLE. SO NEW OVERHEAD CONDUIT WILL BE REQUIRED.
ACCESSIBLE. REMOVE ALL CONDUCTORS. THERE IS CONCERN THAT THE EXISTING UNDER SLAB
PANEL PM SHALL BE REMOVED WHERE EXPOSED AND CUT FLUSH WITH SLAB IN AREAS WHERE NOT
REMOVE EXISTING 200 AMP DISCONNECT. EXISTING CONDUIT BETWEEN THE UNIT AND EXISTING
REMOVE ALL EXISTING ELECTRICAL ASSOCIATED WITH AIR HANDLING UNIT BEING REPLACED.
FILE PATH:
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\23031\23031e201.dgn
AS SHOWN
06.26.24
N B P
P ro je c t
N o
TWT
LTF
TWT
COA Expiration: 6.30.2024
NBP Engineers, Inc. COA#PEF000774
P:\23031\23031e201.dgn
DATE PLOTTED
DGN FILE
25-JUN-2024
23031
P e rr a ll C o m m u n it y
C e n te r
P a c k a g p la c e m e n t
C it y o f P e rr y
P e rr y G e o
T
1 2 3 4
6 7 8 9 10
E
D
C
1 18
PLATFORM
KITCHEN
STOR.
PANTRY
DINING ROOM
ROOM
MULTI-PURPOSE
O.A.C.
CRAFTS ROOM 124
RM
SICK
TOIL.
COURTYARD
MECHANICAL
1 19
ELEC.
COURTYARD
MECHANICAL
MECH. CHASE
STORAGE
LOCKERS
LOCKERS
GYMNASIUM
AH-1NEW
E201
SCALE:
= 1'-0
8 0 4 8 16
NOTES:(THIS SHEET ONLY)
PARTIAL FLOOR PLAN - NEW WORK - ELECTRICAL
ELECTRICAL
NEW WORK -
FLOOR PLAN -
PARTIAL
N
RATING.
GE SPECTRA SERIES PANEL PM. NEW BREAKER SHALL MATCH EXISTING PANEL AIC
PROVIDE NEW 175A/3P CIRCUIT BREAKER IN EXISTING 1000 AMP, 208 VOLT, 3 PHASE 2
MATCH SURROUNDING FINISHES.
CONCEALED WHERE POSSIBLE. WHERE NOT CONCEALED PAINT CONDUIT TO
CONNECTIONS TO THE NEW AIR HANDLING UNIT. ALL NEW CONDUIT SHALL BE
NEW CONDUITS UP THROUGH GYMNASIUM AT THE STRUCTURE. MAKE ALL FINAL
CONDUCTORS IN NEW TWO INCH CONDUIT BACK TO EXISTING PANEL PM. ROUTE
THE DISCONNECT THAT WAS REMOVED. PROVIDE NEW 4#3/0 AWG, 1#4G COPPER
NEW 200A/3P/3R HEAVY DUTY RATED FUSED DISCONNECT IN SIMILAR LOCATION AS
PROVIDE NEW 208 VOLT, 3 PHASE POWER TO NEW AIR HANDLING UNIT. PROVIDE A
PM2
| 23031aCov |
| 23031m001 |
| References |
| tb, 23031tb.dgn |
| 23031m101 |
| References |
| afp1, 23031aX1.dgn |
| tb, 23031tb.dgn |
| 23031m201 |
| References |
| afp1, 23031aX1.dgn |
| tb, 23031tb.dgn |
| 23031e001 |
| References |
| tb, 23031tb.dgn |
| 23031e101 |
| References |
| tb, 23031tb.dgn |
| afp, 23031aX1.dgn |
| 23031e201 |
| References |
| tb, 23031tb.dgn |
| afp, 23031aX1.dgn |
| existing, 23031e101.dgn |
| hvac, 23031m201.dgn |