2022 Facility Condition Assessment Building 120.pdf
PDF 983 KB Posted
- Solicitation number
- RFQ_QUALIF-0000000010
- Issued by
- King County, Spokane City, Washington
About this file
The document is a 2022 Facility Condition Assessment report prepared by MENG Analysis for the City of Sammamish, focusing on the Central Washington University - Sammamish facility located at 120 228th Ave NE in Sammamish, Washington. The two-story community center, originally constructed in 2008 and purchased by the city in 2015, serves as an extended learning satellite campus for Central Washington University and local high school Running Start students. The 30,807 square foot facility was last renovated in 2020 for a tenant improvement project to lease to the university, with a current replacement value of $10,836,000.
The facility assessment reveals several deficiencies and opportunities across multiple building systems, with a total projected repair cost of approximately $802,000 for the period of 2022-2027. Key areas requiring attention include HVAC system upgrades, roof insulation improvements, exterior wall and window repairs, and site infrastructure enhancements. Additional opportunities for improvement total approximately $1,111,000, including installing LED lighting, networked HVAC controls, electric vehicle charging stations, and a photovoltaic system. The facility has a Facility Condition Index (FCI) of 0.08 and a weighted average condition score of 2.4, indicating moderate maintenance needs. The site is surrounded by forested wetlands and includes utilities such as city water, fire systems, and high-speed fiber-optic data service.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Draft Professional Services Contract.pdf | ||
| RFQ - Building 120 Study.pdf | ||
| Building 120 As-builts.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2022 Facility Condition Assessment
Facility Detail Report
Prepared by MENG Analysis November 30, 2022
City of Sammamish
Central Washington University - Sammamish
Central Washington University - Sammamish
Facility Summary
120 228th Ave NE
Sammamish, WA 98074
Facility Size - Gross S.F. 30,807
Year Of Original Construction 2008
Year Of Last Renovation 2008
Facility Use Type Community Center
Construction Type Medium
Energy Source Gas
# of Floors 2
Historic Register No
Facility Condition Index (FCI) 0.08
Current Replacement Value (CRV) $10,836,000
Total Project Cost Total Project Cost
Present Value
$430,000 $437,000
Beginning Budget Year 2022
Weighted Avg Condition Score 2.4
Opportunities $589,000 N/A
$3,370,315 $4,026,000
Observed Deficiencies 2022 - 2027
Predicted Renewal Budget 2028 - 2041
Escalation 3%
Discount Rate 1.5%
Facility Condition Summary
Constructed in 2008 and previously used by a number of different churches, the facility was purchased by the city in 2015. There was a tenant improvement project in 2020 for lease to Central Washington University as the Sammamish Center which operates as an extended learning (satellite) campus for the university. The two-story structure includes two mansard roof areas surrounding separate low-slope membrane roofs (with multiple past leaks reported) housing mechanical rooftop equipment. Precast wall panels are showing signs of water intrusion, corrosion of reinforcing steel with early stages of spalling at the main entry.
HVAC is rooftop gas-pack units mostly single zone, but two multi-zone with variable volume and temperature (VVT) zone dampers and thermostats.
The large gym unit is failing and planned for replacement in the near future. HVAC controls are standalone (not networked) for each rooftop system and should be upgraded to City-standard networked controls when the rooftop units are replaced. The economizer dampers were all fully closed during the site visit, indicating no ventilation and no free cooling - a building tune-up is suggested to get the rooftop units and controls working properly. A commercial kitchen hood system is installed, but not used, as kitchen appliances are removed. Plumbing includes restrooms, locker rooms, commercial kitchen, janitor sinks, and drinking fountains. Gutter and downspout at perimeter sloped mansard roof, and internal roof and overflow roof drains serving inner low-slope membrane roof. Fire sprinkler and alarm throughout. Power is modern 480V, three-phase with large capacity for future addition to west. Lighting is manually switched and aging fluorescent, except recent upgrade to LED at gym. High-speed fiber-optic data, and other low voltage systems to support the educational program. The elevator is out of service due to failed controls.
Print Date: 11/29/22
Copyright MENG Analysis 2022
Central Washington University - Sammamish
Facility Summary
120 228th Ave NE
Sammamish, WA 98074
Facility Components
CommentsSystems
O rig in a l
S y s te m
D a te
L a s t
R e n e w a l D a te
Su rveyo r
Sco re
Su rvey D ate 3.0A Substructure
FoundationsA10
Standard FoundationsA1010 3 Concrete footings (possible thickened slab).TRB 09/09/222008 2008
Slab On GradeA1030 3 Concrete slab on grade, no issues reported.TRB 09/09/222008 2008
2.4B Shell
SuperstructureB10
Floor ConstructionB1010 2 Gypcrete on wood deck on TJI wood joists.TRB 09/09/222008 2008
Roof ConstructionB1020 2 Combination of wood deck on stick frame mansard roof forms, steel pan deck on open web steel joists and steel beams. Wood on joists and glulam timbers at low-slope roof area over lobby, wood on timber and glulam beams at north wing vaulted construction. Insulation was noted as fallen away in areas, leaving holes in the thermal envelope below mansard roof framing.
TRB 09/09/222008 2008
Exterior ClosureB20
Exterior WallsB2010 3 Tilt-up concrete panels and stucco finish on cementitious panel pilasters and upper floor. Some diagonal micro cracking of west elevation concrete around openings on north wing. Some moisture intrusion in stucco near west entry. Concrete reinforcing steel corrosion blooms beginning.
TRB 09/09/222008 2008
Exterior WindowsB2020 2 Aluminum storefront system with thermally insulated glazing. One upper west-facing window seal has failed (second floor above the entry, minor maintenance to replace). East window wall reportedly leaks intermittently with water running from the head, down the interior in wind-driven rain conditions (investigate possible source; potential flashing or sealant failure at head of window system).
TRB 09/09/222008 2008
Central Washington University - Sammamish
Facility Summary
120 228th Ave NE
Sammamish, WA 98074
Facility Components
CommentsSystems
O rig in a l
S y s te m D a te
L a s t
R e n e w a l D a te
Su rveyo r
Sco re
Su rvey D ate
2.4B Shell
Exterior ClosureB20
Exterior DoorsB2030 3 Aluminum storefront at primary entries, hollow metal doors and frames (paint fading). Two overhead coiling doors on south elevation.
TRB 09/09/222008 2008
RoofingB30
Roof CoveringsB3010 3 White PVC membrane roofing on low-slope roof well areas, reported having past reoccurring leaks from penetrations and occasional seam failure with leaks needing continual patching. Composition shingle roofing on pitched roof areas with some granule loss occurring. Once the rainy season starts, continue to monitor roof conditions and repair any leaks as minor maintenance.
TRB 09/09/222008 2008
Roof OpeningsB3020 3 Two acrylic skylights over central lobby. Two access hatches with OSHA / L&I safety compliance concerns.
TRB 09/09/222008 2008
ProjectionsB3030 2 Prefinished vented metal soffits at extended eaves.
Soffit at the lower shed roof over storage along gym hangs as low as 6'-8" above sidewalk (head height code compliance issue) and associated downspouts are only 5'-11" off the sidewalk (impact damage evident).
TRB 09/09/222008 2008
2.1C Interiors
Interior ConstructionC10
PartitionsC1010 2 Painted gypsum on stud walls. Demountable glass partition wall added in 2020 at room 114 (see D3040 HVAC Distribution Systems for ventilation air issue).
Plastic laminate toilet partitions.
TRB 09/09/222008 2008
Interior DoorsC1020 3 Solid core wood doors in hollow metal frames. Some doors have begun sticking in frames. It appears that some doors are sagging and need to be adjusted or replaced so doors hang true inside the frames.
TRB 09/09/222008 2008
Central Washington University - Sammamish
Facility Summary
120 228th Ave NE
Sammamish, WA 98074
Facility Components
CommentsSystems
O rig in a l
S y s te m D a te
L a s t
R e n e w a l D a te
Su rveyo r
Sco re
Su rvey D ate
2.1C Interiors
Interior ConstructionC10
FittingsC1030 2 Rubber base, painted metal railings. ADA issues include no guards below grand stair and wall-mounted boxes extend further than allowed by code into the circulation path.
TRB 09/09/222008 2008
StaircasesC20
Stair ConstructionC2010 2 Prefabricated steel stair systems.TRB 09/09/222008 2008
Stair FinishesC2020 2 Carpet.TRB 09/09/222008 2017
Interior FinishesC30
Wall FinishesC3010 2 Painted gypsum, vinyl wall covering, and wainscot with stone image graphic.
TRB 09/09/222008 2017
Floor FinishesC3020 2 Slate-look porcelain tile in central lobby, carpet in classrooms, offices, and second floor, ceramic tile in restroom/lockers/showers, resilient rubber in gym, wood stage, non-slip in prep kitchen.
TRB 09/09/222008 2017
Ceiling FinishesC3030 2 Suspended acoustical tile, gypsum soffits and hard ceilings in wet and utility spaces, stained tongue and groove wood in lobby spine, painted structure in gym.
TRB 09/09/222008 2017
2.4D Services
Vertical TransportationD10
Elevators and LiftsD1010 3 One two-stop 15-hp Thyssenkrupp hydraulic elevator currently out of service due to control failure, but otherwise good; the elevator machinery room has dedicated ductless split-Dx cooling. One mobile stage ADA lift with no issues reported.
DCS 09/09/222008 2008
Central Washington University - Sammamish
Facility Summary
120 228th Ave NE
Sammamish, WA 98074
Facility Components
CommentsSystems
O rig in a l
S y s te m D a te
L a s t
R e n e w a l D a te
Su rveyo r
Sco re
Su rvey D ate
2.4D Services
PlumbingD20
Plumbing FixturesD2010 2 Conventional fixtures with manual trim (faucets and flush valves), including locker room showers and support for commercial kitchen. Dual-height (ADA) drinking fountains, but no filtered water-bottle-fillers -minor maintenance to add in main lobby and/or vending machine area.
DCS 09/09/222008 2008
Domestic Water DistributionD2020 2 City water to copper distribution; high water pressure needs pressure-reducing valve as minor maintenance. Gas-fired domestic hot water heater, with recirculation pump, but heater room hot water piping is missing insulation - minor maintenance to install.
DCS 09/09/222008 2008
Sanitary WasteD2030 3 Economy non-metallic ABS drain, waste, and vent piping, with noise complaints from staff - minor maintenance to wrap offending waste piping with carpet pad. Floor drains with hydraulic trap primers functioning from fixture flush valves.
DCS 09/09/222008 2008
Rain Water DrainageD2040 2 Metal gutter and downspout to storm - minor ongoing maintenance to keep clean, noting access hazard. Internal roof and overflow roof drains all clean, with no issues reported, noting observed interior portions are not insulated to prevent condensation - minor maintenance to add where needed.
DCS 09/09/222008 2008
HVACD30
Energy SupplyD3010 2 Natural gas distribution piping to rooftop HVAC equipment, to domestic hot water heater and commercial kitchen cook line under hood. Minor rust on rooftop gas lines - minor maintenance to clean and preserve.
DCS 09/09/222008 2008
Central Washington University - Sammamish
Facility Summary
120 228th Ave NE
Sammamish, WA 98074
Facility Components
CommentsSystems
O rig in a l
S y s te m D a te
L a s t
R e n e w a l D a te
Su rveyo r
Sco re
Su rvey D ate
2.4D Services
HVACD30
Cooling Generating SystemsD3030 3 Two ductless-split direct-expansion (Dx) refrigerant cooling systems, one for the elevator machine room, the other for the main distribution frame room.
Equipment is aging but functional with five to ten years remaining life with good maintenance. The rooftop refrigerant piping insulation has been damaged and needs replacement as minor maintenance.
DCS 09/09/222008 2008
HVAC Distribution SystemsD3040 2 Rooftop equipment with ductwork both above and below the roof deck; sheet metal and flex duct, with conventional air terminals - grilles, registers, and diffusers, including balancing dampers. Some rooftop duct is oil-canned down, hence with standing water when raining - ongoing maintenance to observe, keep clean, and cold-galvanize to prevent rust. Return air duct is fully-ducted where observed (not ceiling plenum return), which is generally good.
Unpermitted tenant improvement (mechanically) in first floor northeast area - no HVAC for two recently-formed areas with floor-to-ceiling glass walls.
DCS 09/09/222008 2008
Terminal and Package UnitsD3050 3 Rooftop gas-pack units with five to ten years remaining life; multiple pre-filter screens need replacement as minor maintenance. Economizers are not working - tune-up needed. Unclear relief air path for most zones - further investigation needed.
Only two units have on-board relief air path - the gym unit and the larger unit serving the north wing.
The larger gym rooftop unit is failing and needs replacement. Electric wall heater in the riser room.
DCS 09/09/222008 2008
Controls and InstrumentationD3060 4 Standalone controls with programmable thermostats; except two variable volume and temperature (VVT) systems locally networked, but not digitally. Mix or mostly original and some newer thermostats.
DCS 09/09/222008 2008
Other HVAC Systems and EquipmentD3090 2 Type 1 kitchen grease hood with rooftop up-blast exhaust fan and make-up air unit; currently not used, but exhaust fan is operable - minor maintenance to return to full service as needed.
DCS 09/09/222008 2008
Central Washington University - Sammamish
Facility Summary
120 228th Ave NE
Sammamish, WA 98074
Facility Components
CommentsSystems
O rig in a l
S y s te m D a te
L a s t
R e n e w a l D a te
Su rveyo r
Sco re
Su rvey D ate
2.4D Services
Fire ProtectionD40
Fire Protection Sprinkler SystemsD4010 2 Six-inch service to three-inch wet and four-inch dry-pipe distribution; base of riser water pressure is 100 psig; with 40 psig air pressure in dry side. The dry pipe system protects the unconditioned mansard attic space.
DCS 09/09/222008 2008
Fire Protection SpecialtiesD4030 2 Fire extinguishers and AEDs in cabinets.DCS 09/09/222008 2008
Other Fire Protection SystemsD4090 2 Commercial kitchen grease hood fire suppression system currently decommissioned - minor maintenance to recommission and return to service as needed.
DCS 09/09/222008 2008
ElectricalD50
Electrical Service and DistributionD5010 2 Square D 480V with 1,600A capacity; no power quality issues reported. Three 480/208V transformers. Multiple distribution panels, including one on the roof powering the rooftop HVAC equipment.
DCS 09/09/222008 2008
Lighting and Branch WiringD5020 3 T8 fluorescent with manual controls in most spaces;
excepting newer LED in gym.
DCS 09/09/222008 2008
Low Voltage CommunicationD5032 2 Newer VoIP phone systems. Abandoned Aiphone intercom system. Abandoned A/V at gym. Newer A/V at classrooms, but speakers are poorly supported and deforming ceiling tiles - minor maintenance to fully support speakers and repair damaged ceiling tiles.
DCS 09/09/222008 2008
Low Voltage Fire AlarmD5037 2 Modern addressable Silent Knight fire alarm control panel with remote annunciator at main entry.
Detection and notification throughout. Place-of-refuge call system at top of each stairwell.
DCS 09/09/222008 2008
Central Washington University - Sammamish
Facility Summary
120 228th Ave NE
Sammamish, WA 98074
Facility Components
CommentsSystems
O rig in a l
S y s te m D a te
L a s t
R e n e w a l D a te
Su rveyo r
Sco re
Su rvey D ate
2.4D Services
ElectricalD50
Low Voltage SecurityD5038 3 Several newer CCTV cameras, with several older abandoned in place. Original General Electric security system abandoned in place - appears readily returned to service with minor maintenance.
DCS 09/09/222008 2008
Low Voltage DataD5039 2 Newer main distribution frame and intermediate distribution frame with high-speed fiber-optic data service and CAT-6 cabling; newer WiFi antennas throughout.
DCS 09/09/222008 2016
Other Electrical SystemsD5090 2 Combination egress and exit signs with on-board battery packs; battery ballast in stairwells.
DCS 09/09/222008 2008
2.7E Equipment and Furnishings
EquipmentE10
Commercial EquipmentE1010 3 Appliances at makeshift kitchenette areas; washer and dryer rough-in, but no appliances.
DCS 09/09/222008 2008
Institutional EquipmentE1020 3 Motorized basketball backboards in gym in good condition. Most commercial kitchen equipment removed.
DCS 09/09/222008 2008
FurnishingsE20
Fixed FurnishingsE2010 2 Composite solid surface bathroom countertops with integral sinks. Wood veneer faced casework and laminate countertops. Window blinds.
TRB 09/09/222008 2008
Score
Budget
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostB1020
Facility: Central Washington University - Sammamish
Roof Construction
Escalation 3%
Discount Rate 1.5%
No fall protection at composite roofing for cleaning and maintenance.
Install fall protection.
Fall Protection
20225 2022 1 $20,000.00 $20,000LS $39,000
Action Type:
Life Safety
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostB1020
Facility: Central Washington University - Sammamish
Roof Construction
Escalation 3%
Discount Rate 1.5%
Gaps in the thermal envelope where insulation has fallen away exposes the conditioned space directly to the exterior underside of the uninsulated mansard roof structure. It also appears that there is insufficient insulation hangars strung below the batts between structural elements.
Inspect the integrity of the entire roof insulation and replace and repair areas where gaps have occurred. Add proper insulation securement to underside of batt insulation.
Insulation
20224 2022 5,000 $3.00 $15,000SF $29,000
Action Type:
Energy Efficiency
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostB2010
Facility: Central Washington University - Sammamish
Exterior Walls
Escalation 3%
Discount Rate 1.5%
Areas of moisture intrusion and cracking of cementitious stucco cladding near west entry.
Repair parapet cap flashings and other joint seals to address moisture intrusion. Repair cladding.
Cement Plaster
20254 2022 1 $10,000.00 $10,000LS $20,000
Action Type:
Other
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostB2010
Facility: Central Washington University - Sammamish
Exterior Walls
Escalation 3%
Discount Rate 1.5%
Areas of reinforcing steel and tilt-up panel steel elements corroding and beginning to spall concrete near west entry. Corrosion of exposed steel occurring also at intersection with window head, and back side of exposed parapet wall.
Conduct corrosion removal and repair at panels. Prep and seal reinforcing steel to thwart further future system degradation, patch and seal concrete, and repaint.
Concrete panels
20225 2022 1 $30,000.00 $30,000LS $59,000
Action Type:
Other
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostB2020
Facility: Central Washington University - Sammamish
Exterior Windows
Escalation 3%
Discount Rate 1.5%
East window wall reportedly leaks intermittently during storm events with water running from the head, down the interior of the window wall.
Investigate possible source and repair. There is no eave protection in the center and adjacent gutters terminate at the window wall in this location. There is also no head kick flashing (continuing the drainage plane past the face of the window frame) visibly evident from the ground. Exterior head sealant of the window system may have failed or have gaps. Additional potential leak sources could be wall parapet cap flashing over roof detail; at this location, there is a minimal height roof curb that water could be bypassing during significant storm events if the membrane does not extend up and over the face of the parapet curb, or has other penetrations.
Investigate further for any internal wall water damage.
Aluminum windows
20274 2022 1 $30,000.00 $30,000EA $59,000
Action Type:
Other
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostB2030
Facility: Central Washington University - Sammamish
Exterior Doors
Escalation 3%
Discount Rate 1.5%
Paint oxidized and faded on hollow metal doors and frames.
Repaint doors and frames.
Exterior Doors
20274 2022 1 $5,000.00 $5,000LS $10,000
Action Type:
Other
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostB3020
Facility: Central Washington University - Sammamish
Roof Openings
Escalation 3%
Discount Rate 1.5%
North tall ladder without safety cage, rungs are smooth painted metal and a slip/fall hazard. No fall guard restraint at each access hatch, no fall protection around skylights (installed skylights do not appear to meet rating against fall breakage).
Replace ladders with OSHA- and L&I-compliant systems, including safety cage at tall ladder, handhold extensions, and fall guards with gates at access hatches and surrounding skylights.
Roof Opening - Hatches
20235 2022 1 $10,000.00 $10,000LS $20,000
Action Type:
Life Safety
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostC1030
Facility: Central Washington University - Sammamish
Fittings
Escalation 3%
Discount Rate 1.5%
ADA issues include no guards below grand stair and wall-mounted boxes (e.g. AED and fire extinguisher) extend further than allowed by code into the circulation path.
Install ADA-compliant permanent guards for the visually impaired (railings, benches, panels, or other permanent construction to reduce impact injury to the visually impaired).
Fittings
20225 2022 1 $6,000.00 $6,000LS $12,000
Action Type:
ADA
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostD1010
Facility: Central Washington University - Sammamish
Elevators and Lifts
Escalation 3%
Discount Rate 1.5%
Aged and obsolete elevator controls; controls currently failed with parts on order.
Upgrade control system to current technology.
Elevator
20225 2022 1 $25,000.00 $25,000LS $49,000
Action Type:
ADA
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostD3040
Facility: Central Washington University - Sammamish
HVAC Distribution Systems
Escalation 3%
Discount Rate 1.5%
No HVAC for two recently-formed areas with floor-to-ceiling glass walls.
Design, permit, and construct HVAC system modifications to provide HVAC service to the first floor northeast office area recently walled off by glass.
HVAC distribution
20234 2022 1,500 $10.00 $15,000SF $29,000
Action Type:
Code Issue
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostD3050
Facility: Central Washington University - Sammamish
Terminal and Package Units
Escalation 3%
Discount Rate 1.5%
Two gym rooftop unit compressors are failed and unit is aged.
Replace gym rooftop unit.
Roof Top Unit
20234 2022 1 $30,000.00 $30,000LS $59,000
Action Type:
Energy Efficiency
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostD3050
Facility: Central Washington University - Sammamish
Terminal and Package Units
Escalation 3%
Discount Rate 1.5%
Economizers not working at all rooftop units - no ventilation air for occupied spaces, and no free cooling during favorable weather.
Service and tune-up rooftop unit economizers to provide code minimum ventilation air and free cooling.
Roof top units
20225 2022 10 $1,500.00 $15,000EA $29,000
Action Type:
Code Issue
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostD3060
Facility: Central Washington University - Sammamish
Controls and Instrumentation
Escalation 3%
Discount Rate 1.5%
Mostly original aging controls.
Replace with current technology thermostats and variable volume and temperature system controls.
Controls
20244 2022 8 $1,000.00 $8,000EA $16,000
Action Type:
Energy Efficiency
Remedial Action:
Deficient Material:
CWU Infrastructure
Facility Summary
120 228th Ave NE
Sammamish, WA 98074
Facility Condition Summary
Purchased in 2015 by the city for $6.1M this 21.54-acre site now houses the two-story Central Washington University Sammamish Center, an extended learning satellite building for the university, that also serves local high school Running Start students. Surrounded by forested wetlands to the north, east, and south, development is generally limited to the west central third of the site. The primary entry and asphalt loop drive off of 228th Avenue NE connects three asphalt parking areas on the north and east sides of the lot, in addition to an entry drive off East Main Street to the south, bisecting two large grassy areas on the east and central thirds of the site (previously earmarked for future building and additional parking lot development).
City water, fire, irrigation, and sewer; onsite storm detention vault to adjacent City storm water pond. Puget Sound Energy power and natural gas.
High-speed fiber-optic data service.
CWU Infrastructure
Facility Summary
120 228th Ave NE
Sammamish, WA 98074
Facility Components
CommentsSystems
O rig in a l
S y s te m
D a te
L a s t
R e n e w a l D a te
Su rveyo r
Sco re
Su rvey D ate G Sitework
Site ImprovementsG20
RoadwaysG2010 3 Asphalt driveway connects main entry, parking lots, fire lane loop, and access road entry from East Main Street, repaired and seal coated in 2018. Clean, prep, and seal asphalt cracks. Apply topcoat seal to extend system life. Fire loop around south face of building is only 11'-2" wide and likely does not meet current fire marshal and apparatus clearance requirements. Some curbs broken, especially at the intersection with the main drive which has a substandard turning radius.
TRB 09/09/222008 2008
Parking LotsG2020 3 Asphalt paving was repaired and seal coated in 2018. Paint (including ADA stall paint) faded.
Asphalt cracking and degradation beginning.
TRB 09/09/222008 2008
Pedestrian PavingG2030 3 Concrete sidewalks.TRB 09/09/222008 2008
Site DevelopmentG2040 3 College monument sign and bicycle racks. Fencing is a combination of some chain link fencing in good condition, but the cedar split rail fencing at the north and south perimeter of wetlands and south entry drive is at end of life.
TRB 09/09/222008 2015
LandscapingG2050 3 Lawn area in front is currently dead (with high water and poor draining soils reportedly become bog-like in the winter). Perimeter landscape plantings (trees and shrubs) in good condition, however need to be pruned away from the building facade. The remaining 80% of the site is natural wetland landscape.
TRB 09/09/222008 2008
CWU Infrastructure
Facility Summary
120 228th Ave NE
Sammamish, WA 98074
Facility Components
CommentsSystems
O rig in a l
S y s te m D a te
L a s t
R e n e w a l D a te
Su rveyo r
Sco re
Su rvey D ate
G Sitework
Site Civil / Mechanical UtilitiesG30
Water SupplyG3010 2 Two-inch city water meter with reduced-pressure backflow preventer in hot box to east. Two-inch irrigation meter with unclear backflow prevention and system abandoned in place, reportedly failed throughout the site with many leaks and not used since City purchased the site in 2016. Ten-inch fire loop through site with multiple fire hydrants and six-inch fire service to the building via large vault with adjacent post-indicator valve and fire department connection. The fire backflow prevention and metering vault is partly flooded with sump pump failure - minor maintenance to service or replace.
Site water pressure is strong at 100 psig. As a low point in the City water distribution system, City water pressure is high and occasionally subject to system-wide over-pressure conditions, resulting in utility relief valves causing localized flooding - noting this is an infrequent occurrence.
DCS 09/09/222008 2008
Sanitary SewerG3020 2 City sewer with no issues reported. The commercial kitchen grease interceptor is located significantly west of the building to make room for the future west building; the interceptor is nearly abandoned in place, as the commercial kitchen is not being used as such - minor maintenance to clean and inspect the interceptor periodically to ensure structural integrity and readiness to return to service in the future if needed.
DCS 09/09/222008 2008
Storm SewerG3030 2 Underground concrete storm water detention vault under far parking lot to northwest with no issues reported; network of catch basins and underground piping conveying storm water to vault, including from building roof drains. The vault should be drained, cleaned, and inspected periodically as minor maintenance. A section of storm drain piping along the pedestrian paving in front of the northwest main entry to the building is damaged, with drain piping exposed above grade - minor maintenance to repair.
DCS 09/09/222008 2008
Fuel DistributionG3060 2 Puget Sound Energy natural gas meter No. 642689 with 1,000 cfh capacity and missing seismic shut-off valve - minor maintenance to install.
DCS 09/09/222008 2008
CWU Infrastructure
Facility Summary
120 228th Ave NE
Sammamish, WA 98074
Facility Components
CommentsSystems
O rig in a l
S y s te m D a te
L a s t
R e n e w a l D a te
Su rveyo r
Sco re
Su rvey D ate
G Sitework
Site Electrical utilitiesG40
Electrical DistributionG4010 2 Power underground to utility 500 kVA, three-phase 480V, pad-mounted transformer southeast of building, with Puget Sound Energy meter No.
P147822968.
DCS 09/09/222008 2008
Site LightingG4020 2 Original metal halide pole lights at parking and roadway areas; building exterior lighting for adjacent pedestrian pathway lighting. Some heads have damaged and/or yellowed lenses - minor maintenance to clean or replace.
DCS 09/09/222008 2008
Site Communications and SecurityG4030 2 High-speed fiber-optic data service; some newer and some older (failed) CCTV cameras - minor maintenance to demolish or replace older cameras with modern cameras. Plain old telephone service for legacy systems.
DCS 09/09/222008 2020
Other Site ConstructionG90
Other Site SystemsG9090 2 Lighted sign at main entry.DCS 09/09/222008 2008
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostG2010
Facility: CWU Infrastructure
Roadways
Escalation 3%
Discount Rate 1.5%
Cracks in need of sealing, surface degradation occurring. Painted directional arrows and instructions contradictory and fading.
Clean, prep, and seal asphalt cracks. Apply topcoat seal to extend system life. Repaint directional arrows, instructions, and fire curbs. Add one-way signage at fire lane loop.
AC Roadway
20244 2022 24,000 $1.50 $36,000SF $71,000
Action Type:
Other
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostG2010
Facility: CWU Infrastructure
Roadways
Escalation 3%
Discount Rate 1.5%
Curbs broken, especially at the intersection with the main drive which has a substandard turning radius.
Demo and replace broken curbs. At fire lane loop intersection with main road, consider road rework to provide a larger turning radius at the intersection with the fire / maintenance loop, and where the north-south leg intersects the north entrance drive to pass fire apparatus, buses, waste collections, and other large vehicles, and thwart future damage to property.
Concrete Curb
20225 2022 1 $10,000.00 $10,000LS $20,000
Action Type:
Life Safety
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostG2020
Facility: CWU Infrastructure
Parking Lots
Escalation 3%
Discount Rate 1.5%
Asphalt cracking and degradation beginning, paint stripes fading, including ADA parking symbols.
Clean, prep, and seal asphalt cracks. Apply topcoat seal to extend system life. Repaint ADA and parking stalls.
AC Paving West
20244 2022 59,000 $1.50 $88,500SF $173,000
Action Type:
Other
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostG2020
Facility: CWU Infrastructure
Parking Lots
Escalation 3%
Discount Rate 1.5%
Some areas of root upheaval in lot. Significant asphalt cracking north of area of underground storm detention. Ground subsidence/settlement suspected.
Remove asphalt at root upheaval, trim roots, and patch and repair. See "AC Paving West" deficiency for topcoat (not included in this price, but needed here). Continue monitoring crack locations for any evidence of further settlement near wetland-end of lot.
Parking Lot Sub Grade
20234 2022 1 $8,000.00 $8,000LS $16,000
Action Type:
Other
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostG2040
Facility: CWU Infrastructure
Site Development
Escalation 3%
Discount Rate 1.5%
Cedar split rail perimeter fencing nearing end of life, broken areas, covered in algae growth.
Replace cedar split rail fencing.
Fencing
20274 2022 1,500 $28.00 $42,000LF $82,000
Action Type:
Other
Remedial Action:
Deficient Material:
Year
Central Washington University - Sammamish
City of Sammamish
Detailed Assessment - Observed Deficiencies
Site:
2022 - 2027
Survey
Year Qty
Unit
Cost
Direct
CostUnit
Marked Up
CostG2050
Facility: CWU Infrastructure
Landscaping
Escalation 3%
Discount Rate 1.5%
Perimeter landscape plantings (trees and shrubs) need to be pruned away from the building facade.
Prune trees away from building and cut shrubs back to extend life and prevent vector path for pests.
Landscaping
20234 2022 1 $5,000.00 $5,000LS $10,000
Action Type:
Other
Remedial Action:
Deficient Material:
Deficiency Repair Cost Markups By System
Site:
Facility System
Total Project Cost
Direct Construction
Cost Contingency
20%
Contractor's
OH & P
20%
Project Soft Cost 36%
Total Project Cost
(Present Value)
2022 - 2027
Escalation 3%
Discount Rate 1.5%
SuperstructureCentral Washington University - Sammamish $68,000$35,000 $18,144$7,000 $8,400 $68,000B10
Exterior Closure $148,000$75,000 $38,880$15,000 $18,000 $153,000B20
Roofing $20,000$10,000 $5,184$2,000 $2,400 $20,000B30
Interior Construction $12,000$6,000 $3,110$1,200 $1,440 $12,000C10
Vertical Transportation $49,000$25,000 $12,960$5,000 $6,000 $49,000D10
HVAC $133,000$68,000 $35,251$13,600 $16,320 $135,000D30
$430,000$219,000 $113,530$43,800 $52,560Facility Total $437,000
Site ImprovementsCWU Infrastructure $372,000$189,500 $98,237$37,900 $45,480 $386,000G20
$372,000$189,500 $98,237$37,900 $45,480Facility Total $386,000
Site Total $802,000$408,500 $211,766$81,700 $98,040 $823,000
Subsystem Opportunity Qty Unit Cost
Total Project Cost
Central Washington University - Sammamish
Unit
City of Sammamish
Opportunity Summary By Subsystem
Site:
Action
Total Site Opportunity Cost: $1,111,000
Direct Cost
HVACSystem:
Central Washington University - SammamishFacility:
$197,000
Cooling Generating SystemsD3030
No ceiling fans. Add ceiling fans. 7.00 $1,500.00 $21,000EA $10,500
Controls and InstrumentationD3060
Local controls; not networked - no remote monitoring or control.
Install City-standard networked controls with remote monitoring and selected control.
30,000.00 $3.00 $176,000SF $90,000
ElectricalSystem:
Central Washington University - SammamishFacility:
$392,000
Lighting and Branch WiringD5020
Fluorescent lighting with manual control.
Upgrade to LED lighting with automatic control.
25,000.00 $8.00 $392,000SF $200,000
Site Civil / Mechanical UtilitiesSystem:
CWU InfrastructureFacility:
$69,000
Storm SewerG3030
Large storm water detention vault under northwest parking lot with large brown turf area between the building and the street to west.
Abandoned irrigation system.
Install an irrigation pump in the detention vault and repair a portion of the irrigation system to maintain the west turf area during summer.
1.00 $35,000.00 $69,000LS $35,000
Print Date: 11/29/22
Page 1 of 2Note: Cost estimates shown include project markups, but exclude escalation.
Subsystem Opportunity Qty Unit Cost
Total Project Cost
Central Washington University - Sammamish
Unit
City of Sammamish
Opportunity Summary By Subsystem
Site:
Action
Total Site Opportunity Cost: $1,111,000
Direct Cost
Site Electrical utilitiesSystem:
CWU InfrastructureFacility:
$453,000
Electrical DistributionG4010
No electric vehicle (EV) charging stations.
Install four double EV charging stations.
4.00 $5,000.00 $39,000EA $20,000
Good south-facing sloped roof in several areas.
Install 25 kW photovoltaic system.
25.00 $7,500.00 $367,000EA $187,500
Site LightingG4020
Original inefficient metal halide lighting at roadways and parking lots.
Replace heads with LED lighting.
16.00 $1,500.00 $47,000EA $24,000
Print Date: 11/29/22
Page 2 of 2Note: Cost estimates shown include project markups, but exclude escalation.