2020_June_Heat-Exch_DueDiligenceNOI.docx

DOCX document 31 KB Posted

Attached to
MassDOT NOI Heat Exchange Pump
Solicitation number
BD-20-1030-0P100-0P072-52760
Issued by
Suffolk County, Massachusetts

About this file

This document is a Notice of Intent from the Massachusetts Department of Transportation (MassDOT) regarding its intent to award a contract to Little Engineering Sales & Service of Canton for the purchase of a Maxi-Therm heat exchange pump unit. MassDOT is the owner of the Transportation Building at 10 Park Plaza in Boston and is seeking to improve the efficiency of the building's heating system. Vicinity Energy has offered a substantial financial rebate for the installation of a specific heat exchanger unit, the Maxi-Therm Mod# MCU-1240G-30F-125P. MassDOT is posting this Notice to determine if there are any other interested and qualified entities capable of providing the same or a more competitive solution. Responses must be submitted by 3:00 PM on July 10, 2020 via COMMBUYS.

The estimated cost of the heat exchanger is $190,700, with a supplier rebate of $80,000, resulting in a net cost to MassDOT of $110,700. The heat exchanger must meet specific technical requirements and have a 5-year limited warranty. MassDOT will review any responses received and determine whether to proceed with the Offeror's proposal, withdraw the notice, or accept an offer from another vendor providing a more competitive cost or better value.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Due Diligence Posting of Notice of Intent Massachusetts Department of Transportation 24 June 2020

The Massachusetts Department of Transportation (“Department”) of the Commonwealth of Massachusetts announces its intent to award a contract to Little Engineering Sales & Service of Canton (“Offeror”), pending the results of this Notice of Intent (“Notice”) pursuant to the Commonwealth’s Due Diligence Posting policy.

Project Description: MassDOT is the owner of the Transportation Building at 10 Park Plaza in Boston Massachusetts. The building is heated by the use of steam into a heat exchange system. The building, originally built in 1996, undergoes necessary maintenance and on occasion upgrades in its facilities and systems.

MassDOT receives its steam from Vicinity Energy by agreement. In the interests of improving efficiency in the heating system at the Park Plaza building, Vicinity Energy has offered MassDOT a substantial financial rebate in return for the installation of a Maxi-Therm, Mod# MCU-1240G-30F-125P.

Heat Exchanger Estimated Cost:$190,700.00
Supplier rebate offered for the purchase of this unit$ 80,000.00
Net Cost to MassDOT for the purchase of this unit$110,700.00

Minimum product specifications are provided in Attachment A.

The manufacturer assures delivery of the unit within 14 weeks of placing the order.

Heat exchanger is to be built to the TEMA standards in addition to ASME Code. The exchanger is to have a 5-year limited warranty. Full specifications are attached but include vertical heat exchangers, with carbon steel shell construction, 90/10 CuNi tubes of 3/4” OD x 0.049’’ wall and SS304L tube sheet(s). Steam side to be ASME stamped for 300 psig @375oF, liquid side to be ASME stamped for 300 psig @375oF. Any recommendation of a competitive product must have ANSI 300# flanged connection on steam inlet, condensate outlet and liquid inlet and outlet.

Determination of Other Interested Vendors: The intent of this posting is to determine if there are any other interested and qualified entities capable of completing the anticipated work. Any such entity must submit documentation that they can also provide the same service to the Department at more competitive cost or better value and in a timely fashion.

Response Requirement and Deadline: All Interested Vendors and Offerors interested in responding to this Notice, regardless of prior communications with the Department, must submit a Response to this posting via COMMBUYS (see below) containing evidence of their qualifications, capability, and interest.

All required information must be received by 3:00 PM on 10 July 2020. If interest is generated by this Notice the Department will review any and all Responses and will determine whether they will: (i) withdraw the notice and not accept the Offeror’s offer (and cancel the Notice of Intent) or (ii) accept the offer from the Offeror or (iii) accept an offer from another vendor offering a more competitive cost or better value than the Offeror in their Response.

Additional Terms/Forms Required for Doing Business with the Commonwealth

Names of Standard Forms
Instructions
Instructions for Vendors Responding to Bids Electronically
Read and agree prior to submitting a Response.
RFR - Required Specifications
Read and agree prior to submitting a Response.
Prompt Payment Discount Form
Complete electronically and submit as an attachment to Quote.
Commonwealth Terms & Conditions
Read and agree. Sign and submit original with wet signature upon award, if any.
Contractor Authorized Signatory Listing
Read and agree. Sign and submit original with wet signature upon award, if any.
Authorization for Electronic Funds Transfer
Read and agree. Sign and submit original with wet signature upon award, if any.
Request for Taxpayer Identification Number and Certification (W-9)
Read and agree. Sign and submit original with wet signature upon award, if any.
Standard Contract Form and Instructions
Read and agree. Sign and submit original with wet signature upon award, if any.

Response (Quote) Submission Method: Online Quote Submission via COMMBUYS is required. All Interested Vendors and Offerors must submit Quotes online using tools available only to Sellers registered in COMMBUYS. COMMBUYS provides Seller registration functionality at no charge. To register, go to www.COMMBUYS.com and click on the “Register” link on the front page. All Interested Vendors and Offerors who are awarded a contract resulting from this Notice, if any, will be required to maintain an active account during the duration of the Contract, by reviewing their registration information regularly and maintaining its accuracy.

COMMBUYS Quote Submission Training and Instructions: The following resources are provided to assist Interested Vendors and Offerors in submitting Quotes:

· An online job aid on How to Create a Quote;

· Webcast video on How to Find Bids (Solicitations) and Submit Quotes (Responses) through COMMBUYS;

· Instructor-led trainings (ILT) and live webinar sessions on “How to Locate and Respond to Bids” may also be available. Check the OSD Training Courses schedule for Sellers/Business Entities for available locations, dates and times. Note that space is limited and pre-registration for trainings is required to attend. Follow instructions on the course schedule to register.

Any questions or concerns regarding COMMBUYS may be directed to the Help Desk at COMMBUYS@mass.gov or during normal business hours (8am - 5pm ET Monday - Friday) at 1-888-627-8283 or 617-720-3197.

ATTACHMENT A: MINIMUM SPECIFICATIONS – HEAT EXCHANGER

I. STEAM TO LIQUID VERTICAL FLOODED HEAT EXCHANGERS

A. The heat exchanger skid shall be supplied with Simplex heat exchanger mounted on a single skid. Sizing as shown on schedules. Skid shall be provided with single entry points for liquid inlet, liquid outlet, steam inlet and condensate outlet. The skid shall be hydrostatically tested prior to shipping.

B. The basis of operation shall be as follows. The hydronic water is heated in the u-tubes of a vertical heat exchanger designed to be flooded at approximately 15% at full load in order to have a condensate outlet temperature of 200oF or lower, eliminating energy losses due to flash steam.

C. The steam will be supplied directly to the skid; no pressure reducing station or control valves are required. Condensate can be lifted at the outlet of the skid; no condensate pump required.

D. The process is modulated using an electric fail-safe control valve installed on the condensate outlet that exposes the necessary heating surface by flooding the shell of the heat exchanger proportionally to the instantaneous required load. An outlet temperature setpoint stability of +/- 2oF will be achieved at all flow conditions.

E. The Heat Exchanger shall be capable of control with a minimum water side circulation of 15% of design flow at all times during operation. Circulating pumps supplied by others, are to push the liquid to be heated through the heat exchanger.

F.To facilitate the remote start-stop and lead-lagging of the Maxi-Therm systems, a pre-programmed BACnet control panel shall be provided with all the sensors required to perform the optimal sequence of controls. All parameters of the system can be monitored and modified locally or remotely by the building automation system and troubleshooting by the factory is accomplished via Internet using an Ethernet connection. Remote access to the panel by the customer must be permitted for remote troubleshooting.
G.Heat Exchanger shall be sized to operate at full capacity at steam pressures as follows: 125psig
H.Skid shall include and be factory assembled as a minimum:
1.One (1) vertical U-tube heat exchanger, with carbon steel shell construction, 90/10 CuNi or SS304 u-tubes of ½” OD x 0.049’’ wall and SS304 tube sheet. Steam side ASME stamped for 300 psig @375F, liquid side ASME stamped for 300 psig @375F. Heat exchangers design, construction and materials shall conform to the requirements of the Tubular Exchange Manufacturer's Association (TEMA) mechanical standards class c as scheduled on drawing.
2.One (1) stabilizing pump of 1/6 hp, 115/1/60, pre-wired to the control panel
3.One (1) check valve with isolation valves on the pump lines, both in SS
4.Thermometer at liquid inlet and outlet, thermowells included
5.One (1) modulating electric control valve on the condensate outlet, fail safe, pre-wired to the control panel
6.Electric temperature sensors on liquid inlet & outlet, pre-wired to the control panel
7.One (1) pressure transmitter on the steam inlet, pre-wired to the control panel
8.One (1) flow switch on the liquid inlet, pre-wired to the control panel
9.One (1) automated isolation valve on the liquid outlet to allow remote lead-lagging of the systems
10.One (1) over heat security valve on the steam side, high performance butterfly type with electric actuator and battery back-up, pre-wired to the control panel
11.One (1) start-up valve on the steam inlet, on-off and fail closed, pre-wired to the control panel, with union orifice, isolation valves and 100 mesh strainers
12.One (1) NEMA 4 BACnet MSTP control panel with an industrial type programmable PC and touchscreen user interface. The panel is pre-programmed to perform the start-up and shut down procedures as well as alarms managing. The control panel is provided with the sensors required in the sequence of controls. Remote access to the parameters via Internet is accomplished using an Ethernet connection, allowing an easy troubleshooting by the factory. All parameters to be adjustable locally and via the building automation system. Drivers shall be available to communicate with other languages. The panel is factory mounted & tested prior to shipment and is CSA-US approved. Remote access to the panel by the customer must be permitted for remote troubleshooting.
13.One (1) steam trap on the condensate outlet
14.One (1) strainer 100 mesh with blowdown valve on the condensate outlet
15.Manual isolation valves on the liquid, steam and condensate side
16.Liquid & steam piping in carbon steel SCH40 and condensate piping in carbon steel SCH80
17.Heavy duty painted steel frame

I. Items delivered separately to be installed on jobsite by contractor:

1.Two (2) Thermostatic steam traps as drip traps.
2.One (1) Vacuum breaker, stainless steel construction.
3.One (1) Air vent, stainless steel construction.
4.One (1) Maxi-Therm condensate mixer with integrated check valves, required to enable a high-pressure drip trap to discharge in a flooded low-pressure condensate main without water hammer.
J.System to have a limited warranty on parts and performance valid for a period of 18 months after original start-up or 24 months after delivery, whichever comes first. In addition manufacture is to supply a 1 year preventative maintenance contract.
K.The start-up will be performed by the manufacturer or authorized representative.

Vertical heat exchangers, with carbon steel shell construction, 90/10 CuNi tubes of 3/4” OD x 0.049’’ wall and SS304L tube sheet(s). Steam side to be ASME stamped for 300 psig @375oF, liquid side to be ASME stamped for 300 psig @375oF. Heat exchanger shall have ANSI 300# flanged connection on steam inlet, condensate outlet and liquid inlet and outlet. Heat exchanger to be built to the TEMA standards in addition to ASME Code (see comparison on last page) and have a 5-year limited warranty.

ASME Code Only vs TEMA – A Brief Comparison Background ASME Section VIII, Division I is a safety Code that was originally developed in the 1930’s and covers all types of pressure vessels, including tanks, columns, towers, reactors, and Shell & Tube Heat Exchangers (HX). It sets minimum requirements with respect to thickness of components and methods of fabrication and testing for the safe operation of a particular piece of relevant equipment.

The TEMA Standard – which stands for the Tubular Exchangers Manufacturers Association – is a specific set of both safe design standards, as well as supplemental requirements and best practices aimed at not only ensuring the safe operation of a Shell & Tube Heat Exchanger at given conditions, but also that the HX will have a longer life-span than if it were fabricated as “Code Only”. In short, when a HX is fabricated in accordance with the TEMA standards, it is a heavier duty product than Code Only.

Examples Given: A 12” Nominal Shell & U-tube Heat Exchanger, designed for 150 PSIG working pressure, to be used in a typical HVAC Steam to Water application.

· Shell Thickness- Code Only: 0.190”, TEMA Min: 0.375” TEMA is 50% heavier duty

· Tube Thickness- Code Only: 0.035”, TEMA Min: 0.049” TEMA is 30% heavier duty

· Gasket Width – Code Only: Not Addressed, TEMA Min: 0.625” to ensure effective seal

· # Tie-Rods in Tube Bundle to ensure adequate stiffness – Code Only: Not Addressed, TEMA Min: (4) Tie-Rods Summary Obviously, it is not possible to cover all aspects of the differences between a Code Only heat exchanger, and one designed and fabricated to the TEMA standards in just a few short lines. But when specifying a shell & tube heat exchanger, requiring that it be built to the TEMA standards in addition to ASME Code, will ensure that the equipment will be fabricated in accordance with the standard that has achieved worldwide acceptance as the authority on the thermal and mechanical design and fabrication of Shell & Tube Heat Exchangers.

Revised: June 30, 2016