20-0048 Drawings.pdf
PDF 611 KB Posted
- Attached to
- RF SHIELDED CHAMBERS(UW-MAD)[20-0048]
- Solicitation number
- 20-0048
- Issued by
- Dane County, Madison City, Wisconsin
About this file
This file is a comprehensive set of architectural, mechanical, plumbing, and electrical drawings for the University of Wisconsin-Madison's project to install three RF shielded chambers in Suite 326 and Corridor 300J of the Primate Center (Building 0526). The project encompasses demolition and remodeling of laboratory and support spaces on the third floor, including the installation of three radiofrequency shielded chambers (designated as rooms 326B, 326C, and 326D) along with associated modifications to room 326 (Lab), room 338, and corridor 300J. The scope of work includes complete room demolition, wall and partition construction, flooring installation with epoxy finishes and heat-welded vinyl, suspended ceiling systems with specified tile and grid specifications, door and hardware installation, and comprehensive updates to all building systems including HVAC, plumbing, and electrical infrastructure. The drawings are dated March 23, 2018, and include detailed specifications for materials, equipment manufacturers and models, equipment schedules, and coordination requirements among multiple trades.
The RF shielded chambers are specified as vendor-supplied and installed equipment with critical attention requirements regarding panel joint coordination, fastener installation, and preservation of conductive surfaces on door frames and thresholds. All new work incorporates specific material requirements including Phoenix OneSteP epoxy flooring in Grey Hound color, Corrim Company fiberglass reinforced polymer doors in Beige finish, Chicago Metallic suspended ceiling systems with Genesis tiles, and various mechanical, plumbing, and electrical components from specified manufacturers including Mott Manufacturing cabinets, Chicago Faucets fixtures, and Vibro-Acoustics sound attenuators. The project requires careful coordination between architectural, mechanical, electrical, and plumbing trades, with particular emphasis on acoustic sealing, RF chamber integrity, cable management through dedicated chases, and compliance with applicable building codes and standards. The University of Wisconsin-Madison directed inquiries to Brad Bauman in Purchasing Services at the specified contact information.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 20-0048 RFB.docx | DOCX document | |
| 20-0048 RFB AMD 1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTURAL SYMBOLS & ABBREVIATIONS
E
EXISTING WALL TO REMAIN
WALL TO BE REMOVED
NEW WALL
EXISTING TO REMAIN
EXISTING TO BE RELOCATED
NEW TO BE INSTALLED
R
N
ROOM
100 ROOM TAG
1 REVISION TAG
KEY NOTE TAG
CALL OUT TAG
ELEVATION TAG
INTERIOR ELEVATION TAG
SECTION TAG
NORTH
NORTH ARROW
FLOOR PLAN VIEW
SCALE
PLAN/DETAIL/SECTION INDICATION
NOTES:
1. SYMBOLS INDICATED HERE AND NOT USED IN THE CONTRACT DOCUMENTS DO NOT APPLY
TO THIS PROJECT. ADDITIONAL SYMBOLS MAY BE INDICATED IN THE CONTRACT
DOCUMENTS.
2. NEW WORK IS SHOWN WITH SOLID HEAVY LINES.
3. EXISTING TO REMAIN IS SHOWN WITH LIGHT LINES.
4. DEMOLISHED WORK IS SHOWN WITH HEAVY DASHED LINES.
& AND
@ AT
Ø ROUND OR DIAMETER
A&E ARCHITECTURAL AND ENGINEERING
AB ANCHOR BOLT/ROD
ABV ABOVE
ACT/ATC ACOUSTIC CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
AV AUDIO VISUAL
CMU CONCRETE MASONRY UNIT
FF&E FURNITURE, FIXTURES & EQUIPMENT
GWB GYPSUM WALL BOARD
HAZ MAT HAZARDOUS MATERIAL
HM HOLLOW METAL
LVT LUXURY VINYL TILE
SC SOLID CORE
TYP TYPICAL
L ANGLE
LL DOUBLE ANGLE
RCP REFLECTED CEILING PLAN
DEMO DEMOLITION
NOM NOMINAL
VCT VINYL COMPOSITION TILE
R.O. ROUGH OPENING
T.O. TOP OF
FRP FIBERGLASS REINFORCED POYESTER
Scale
UW
Number
Date Issued
Set Type
REVISIONS:
Sh ee t T itle
Pr oje ct Tit le:
Drawn By:
Fa ci lit ie s P la nn in g an d
M an ag em en t
P hy si ca l P la nt
A rc hi te ct s/
E ng in ee rs
N
. M ills
S tre et , M ad is on , W
I 5
U ni ve rs ity o f W is co ns in -M ad is on
Bu ild ing N am e &
N um be r:
U W
B
LD
G
3/
/2
4:
:4
PM
1/4" = 1'-0"
A1
SY
M
B O
LS
A
BB
R
EV
IA
TI
O N
S
03/23/2018
0526 1602
BD
P R
IM
A
TE
C
E N
TE
R
MCLEAN
IN
ST
AL
L
TH
R
EE
R
F
SH
IE
LD
ED
C
H
AM
BE
R
S S
U
IT
E
A
N D
C O
R R
ID
O
R
J
No. Date: By: Description:
300J
CORRIDOR
Room
LAB
CLEAR - GYP BD PARTITIONS (TYP)
9' - 5"CLEAR
9' - 5"
CLEAR
9' - 5"
CL
EA
R
FR
OM
C
OL
UM
N
FA
CE
7'
- 1 0"
A5
A4
LAB
326B
RF CHAMBER
326C
RF CHAMBER
326D
RF CHAMBER
300J
CORRIDOR
5' - 11"
A4
A44
1/2
EX
TE
RI
OR
O F
CH
AM
BE
R
7'
- 9
FR
OM
C
OL
UM
N
FA
CE
1/2
A4
A5
(TYP)
1/2"
(TYP)
1/2"
EXTERIOR OF CHAMBER (TYP)
9' - 4"
3' - 3"
CL OF PANEL
4' - 9"
FA
C
E O
F G
W B
Room
Scale
UW
Number
Date Issued
Set Type
REVISIONS:
Sh ee t T itle
Pr oje ct Tit le:
Drawn By:
Fa ci lit ie s P la nn in g an d
M an ag em en t
P hy si ca l P la nt
A rc hi te ct s/
E ng in
. M ills
S tre et , M ad is on , W
I 5 ve rs ity o f W is co ns in -M ad ing N am e &
N um be r:
U W
B
LD
G
3/
/2
4:
:4
PM
1/4" = 1'-0"
A2
3R D
F
LO
O R
D E
M O
LI
TI
O N
/R E
M O
D E
L P
LA
N
03/23/2018
0526 1602
BD
P R
IM
A
TE
C
E N
TE
R
MCLEAN
IN
S
TA
LL
T H
R E
E R
F S
H
IE
LD
E
D C
H A
M B
E R
S S
U
IT
E
A
N D
C O
R R
ID
O
R
J
REMODEL KEY NOTES
1 PROVIDE AND INSTALL PHOENIX ONESTEP EPOXY FLOORING. FINISH TO BE
NON-SKID/SAFETY. COLOR TO BE GREY HOUND (PT-617).
2 VENDOR SUPPLIED AND INSTALLED MOTT MANUFACTURING DOVE GREY (601008)
METAL BASE CABINETS AND BLACK EPOXY COUNTER TOP WITH 4" BACKSPLASH
AND DARCON D45 EPOXY SINK.
3 PROVIDE AND INSTALL LAB FAUCET - CHICAGO FAUCETS 1100-HA8CP.
COORDINATE WITH PLUMBING.
4 PROVIDE AND INSTALL DECK MOUNTED GUARDIAN G5022 EYEWASH - COORDINATE
WITH PLUMBING.
5 PROVIDE AND INSTALL A 3'-4" X 7'-0" (NOM.) CORRIM COMPANY FRP DOOR INTO THE
EXISTING HOLLOW METAL FRAME. DOOR TO BE BEIGE (NG-74306) WITH A SMOOTH
FINISH. INSTALL A LEVER SET, DOOR CLOSER WITH HOLD OPEN FEATURE AND A
34" X 34" STAINLESS STEEL KICK PLATE ON THE PUSH SIDE. HARDWARE TO BE A
CLASSROOM FUNCTION WITH FINISH 626.
6 CONSTRUCT FULL HEIGHT PARTITION AS PER DETAIL 1/A5. PARTITIONS SHALL BE
ACOUSTICALLY SEALED AROUND PERIMETER.
7 PROVIDE AND INSTALL A 3'-0" X 7'-0" (NOM) CORRIM COMPANY FRP DOOR SET IN A
2" HOLLOW METAL FRAME 3'-0" X 7'-1". DOOR TO BE BEIGE (NG-74306) WITH A
SMOOTH FINISH. INSTALL A LEVER SET, ACOUSTICAL SEALS, SURFACE MOUNTED
AUTOSWEEP, AND A 34" X 34" STAINLESS STEEL KICK PLATE (ON THE PUSH SIDE).
HARDWARE TO BE A PASSAGE SET WITH FINISH 626. SEE DETAIL 2/A5 FOR
ADDITIONAL INFORMATION.
8 PROVIDE AND INSTALL A STAINLESS STEEL RAMP TO MEET ELEVATION OF RF
CHAMBER FLOOR. SEE DETAIL 2/A5.
9 PROVIDE AND INSTALL HEAT WELDED SHEET VINYL FLOORING WITHIN RF BOOTH -
SEE SPECS IN PROJECT FOLDER.
10 PAINT ALL WALLS, WINDOW FRAMES AND GLASS, WITH WHITE EPOXY PAINT.
11 PAINT WALLS WITH BLACK EPOXY PAINT.
12 PROVIDE AND INSTALL A WALL MOUNTED EXAM TABLE @ 42" A.F.F. TO TABLE TOP.
SEE SPECIFICATION IN PROJECT FOLDER.
13 OPEN BLOCK WALL TO ALLOW FOR ELECTRICAL BOX INSTALLATION. COORDINATE
WITH ELECTRICAL.
14 VENDOR SUPPLIED AND INSTALLED RF SHIELDED BOOTH. FASTENERS AT FLOOR
CLEATS TO HAVE ROUND HEADS. CHAMBER DOOR TO BE BLACK.
15 PASS-THRU WAVE GUIDE - Ø3" X 12" ALUMINUM TUBE WITH A PVC ELBOW AT EACH
END. MOUNT AT 6'-10" A.F.F. TO CENTERLINE OF TUBE. CENTER TUBE WITHIN WALL
ASSEMBLIES AND ACOUSTICALLY SEAL IN PLACE. FILL WITH DRY SAND ONCE
CABLES ARE IN PLACE.
16 COORDINATE PARTITION CONSTRUCTION WITH INTERFERENCE FROM MECHANICAL
DUCT AT THIS LOCATION.
DEMOLITION KEY NOTES
1 DEMO SINK FAUCETS - COORDINATE WITH PLUMBING.
2 DEMO COUNTER TOPS (SUSPECTED ACM) AND BASE CABINETS.
3 REMOVE WALL MOUNTED CABINETS AND RETURN CABINETS IN GOOD CONDITION
TO CARPENTER SHOP STOCK AND DEMO THE REST.
4 DEMO ENTIRE ROOM ENCLOSURE.
5 DEMO FLOOR TILE (SUSPECTED ACM).
6 REMOVE DOOR FROM FRAME AND DISCARD. PREP FRAME FOR NEW FRP DOOR.
7 FROM ALL ROOMS WITHIN THE 326 SUITE, REMOVE ANY REMAINING FURNITURE
AND CONSIGN TO BUILDING MANAGER.
RF CHAMBER NOTES - ATTENTION!
1 RF CHAMBER VENDOR TO COORDINATE PANEL JOINTS WITH ARCHITECTURAL,
MECHANICAL AND ELECTRICAL PENETRATIONS AS NOTED WITHIN THE
CONSTRUCTION DOCUMENTS.
2 DO NOT SPIN-OUT SCREWS WHEN TIGHTENING INTO THE GALVANIZED METAL
PANELS OF THE RF CHAMBER. IF A SCREW SPINS WILST DRAWING, REMOVE
SCREW AND REPLACE WITH THE NEXT LARGER SCREW DIAMETER.
3 DO NOT PAINT WIHTIN THE JAMBS AND HEAD OF THE RF CHAMBER DOOR FRAME.
JAMBS AND HEAD GASKETS MUST REMAIN CONDUCTIVE TO THE DOOR.
4 DO NOT PAINT THE RF CHAMBER DOOR THRESHOLD. THE THRESHOLD MUST
REMAIN CONDUCTIVE TO THE DOOR.
5 DO NOT PAINT THE EDGES OF THE RF CHAMBER DOOR. THE DOOR MUST REMAIN
CONDUCTIVE TO THE FRAME.
NORTH
NORTH
1/4" = 1'-0"
3RD FLOOR DEMO PLAN
1/4" = 1'-0"
3RD FLOOR REMODEL PLAN
9 9 9
No. Date: By: Description:
8 8
14 14
15 15 15 16
OS
H
H
OS JJ JJ JJ
OS
CLG
F
H OS
LAB
300J
CORRIDOR
300J
CORRIDOR
LAB
326C
RF CHAMBER
326D
RF CHAMBER
326B
RF CHAMBER
A.F.F.
CEILING
8' - 2"
A.F.F.
CEILING
7' - 4" A.F.F.
CEILING
7' - 4" A.F.F.
CEILING
7' - 4" Scale
UW
Number
Date Issued
Set Type
REVISIONS:
Sh ee t T itle
Pr oje ct Tit le:
Drawn By:
Fa ci lit ie s P la nn in g an d
M an ag em en t
P hy si ca l P la nt
A rc hi te ct s/
E ng in
. M ills
S tre et , M ad is on , W
I 5 ve rs ity o f W is co ns in -M ad ing N am e &
N um be r:
U W
B
LD
G
3/
/2
4:
:4
PM
1/4" = 1'-0"
A3
3R D
F
LO
O R
C
EI
LI
N
G D
E M
O
LI
TI
O
N /R
E M
O D
EL
P
LA
N
03/23/2018
0526 1602
BD
P R
IM
A
TE
C
E N
TE
R
MCLEAN
IN
S
TA
LL
T H
R E
E R
F S
H
IE
LD
E
D C
H A
M B
E R
S S
U
IT
E
A
N D
C O
R R
ID
O
R
J
DEMOLITION KEY NOTES
1 REMOVE ALL CEILILNG MOUNTED FRAMES ASSOCIATED WITH
THE UPPER CABINETS.
REMODEL KEY NOTES
1 PROVIDE AN INSTALL SUSPENDED CEILNG SYSTEM. TILES: 2X2
GENESIS SMOOTH PRO IN WHITE (74000). GRID: CHICAGO
METALLIC 200 SNAP GRID 15/16" EXPOSED (WHITE 01). INSTALL
HOLD DOWN CLIPS.
2 PROVIDE AN INSTALL SUSPENDED CEILNG SYSTEM. TILES: 2X2
GENESIS SMOOTH PRO IN BLACK (74007). GRID: CHICAGO
METALLIC 200 SNAP GRID 15/16" EXPOSED (BLACK 08). INSTALL
HOLD DOWN CLIPS.
RF CHAMBER NOTES - ATTENTION!
1 RF CHAMBER VENDOR TO COORDINATE PANEL JOINTS WITH ARCHITECTURAL,
MECHANICAL AND ELECTRICAL PENETRATIONS AS NOTED WITHIN THE
CONSTRUCTION DOCUMENTS.
2 DO NOT SPIN-OUT SCREWS WHEN TIGHTENING INTO THE GALVANIZED METAL
PANELS OF THE RF CHAMBER. IF A SCREW SPINS WILST DRAWING, REMOVE
SCREW AND REPLACE WITH THE NEXT LARGER SCREW DIAMETER.
3 DO NOT PAINT WIHTIN THE JAMBS AND HEAD OF THE RF CHAMBER DOOR FRAME.
JAMBS AND HEAD GASKETS MUST REMAIN CONDUCTIVE TO THE DOOR.
4 DO NOT PAINT THE RF CHAMBER DOOR THRESHOLD. THE THRESHOLD MUST
REMAIN CONDUCTIVE TO THE DOOR.
5 DO NOT PAINT THE EDGES OF THE RF CHAMBER DOOR. THE DOOR MUST REMAIN
CONDUCTIVE TO THE FRAME.
NORTH
NORTH
1/4" = 1'-0"
3RD FLOOR DEMO CEILING PLAN
1/4" = 1'-0"
3RD FLOOR REMODEL CEILING PLAN
2 2
DC LIGHTING
CONTROLLER (TYP)
RF LIGHTING FILTER (TYP)
RF POWER FILTER (TYP)
ACCES PANEL FOR PATCH PANEL (TYP)LIGHT SWITCH (TYP)
NOTE: PROVIDE FIRE RETARDANT BLOCKING FOR SURFACE MOUNTED ELECTRICAL EQUIPMENT.
FLEXTRAY (TYP)
PASS-THRU WAVE GUIDE (TYP)
BRUSH PLATE STYLE CABLE PASS-THRU (TYP)
TY
P
3'
- 1
1"
A5
A5
TYP
TYP
2'
- 1
0"
TYP
1" 3' - 0" 2' - 0" 2' - 6" 3' - 0" 1"
10' - 8"
EX
TE
RI
OR
O F
RF
C
HA
MB
ER
8'
- 3
3"
Scale
UW
Number
Date Issued
Set Type
REVISIONS:
Sh ee t T itle
Pr oje ct Tit le:
Drawn By:
Fa ci lit ie s P la nn in g an d
M an ag em en t
P hy si ca l P la nt
A rc hi te ct s/
E ng in
. M ills
S tre et , M ad is on , W
I 5 ve rs ity o f W is co ns in -M ad ing N am e &
N um be r:
U W
B
LD
G
3/
/2
4:
:1
PM
3/8" = 1'-0"
A4
EL
EV
AT
IO
N S
A N
D S
E C
TI
O
N S
03/23/2018
0526 1602
BD
P R
IM
A
TE
C
E N
TE
R
MCLEAN
IN
ST
AL
L
TH
R
EE
R
F
SH
IE
LD
ED
C
H
AM
BE
R
S S
U
IT
E
A
N D
C O
R R
ID
O
R
J
3/8" = 1'-0"1 LONGITUDINAL SECTION THROUGH SHIELDED CHAMBERS
No. Date: By: Description:
3/8" = 1'-0"2 ELEVATION LOOKING SOUTH
3/8" = 1'-0"4 ELEVATION LOOKING WEST
3/8" = 1'-0"3 TRANSVERSE SECTION
TOP OF CHAMBER
SUSPENDED CEILING
WITHIN CHAMBER
FACE OF COLUMN
SUSPENDED
CEILING IN LAB 326
SUSPENDED CEILING LAB 326
GYP. BOARD PARTITION
GYP. BOARD PARTITION
GYP. BOARD PARTITION EXHAUST DUCT
FACE OF BLOCK WALL
RF CHAMBER WALL
SUPPLY DUCT SOUND
ATTENUATOR (TYP)
RF CHAMBER LAB 326
EXHAUST DUCT (TYP)
MRI COMPATIBLE
CAN LIGHT (TYP)
LAY-IN LIGHT
EXHAUST DUCT
SOUND ATTENUATOR
SUPPLY DUCT
SUPPLY DUCT
PASS-THRU WAVE GUIDE
FLEXTRAY
EXHAUST DUCT SOUND
ATTENUATOR (TYP)
PATCH PANEL - BY
VENDOR
RF CHAMBERLAB 326
FINISHED FLOOR - HEAT-WELDED
SHEET VINYL. SEE REMODEL PLAN
KEY NOTES FOR MORE INFORMATION
RF CHAMBER FLOOR SYSTEM - BY VENDOR
RF CHAMBER WALL SYSTEM - BY VENDOR
1/2"
5/8" GYPSUM BOARD (BOTH SIDES)
3-5/8" STEEL STUDS WITH ROCKWOOL
SAFE AND SOUND INSULATION
EPOXY FLOOR WITH INTEGRAL COVE
BASE - SEE PROJECT SPECIFICATIONS 4"
AIR GAP BETWEEN GYPSUM BOARD
PARTITION AND RF CHAMBER WALL
RUBBER TRANSITION. SEE
SPECS IN PROJECT FOLDER.
1/2" AIR GAP BETWEEN GWB PARTITION AND
RF CHAMBER WALL
RF CHAMBER DOOR FRAME - BY VENDOR
RF CHAMBER THRESHOLD - BY VENDOR
HEAT WELDED SHEET VINYL FLOORING -
SEE PROJECT SPECIFICATIONS
RF CHAMBER FLOOR - BY VENDOR
SLOPE OF RAMP IS NOT TO
EXTEND BEYOND LAB SIDE OF
DOOR JAMB. SEAL AROUND 3-SIDES
OF RAMP BASE AT FLOOR
HOLLOW METAL DOOR FRAME
SET IN GWB PARTITON
DOOR AT GWB PARTITION
SWEEP
PROVIDE AND INSTALL NON-CONDUCTIVE
GASKETING AT FACE OF RAMP
FASTEN RAMP WITH (3)
COUNTERSUNK STAINLESS STEEL
SCREWS - FILL HOLES WITH SEALANT
1"
PROVIDE SEALANT AT GAP BETWEEN
RAMP AND RF CHAMBER THRESHOLD
GWB J-BEADRF CHAMBER
LAB 326
RF CHAMBER EQUIPMENT CABLE
PATCH PANEL - BY VENDOR
EDGE OF GWB SILL
AIR GAP
STEEL STUD AND GWB PARTITION
W/ACOUSTICAL BATT INSULATION
STEEL STUD - REFER TO ACCESS DOOR
MANUFACTURER'S INSTALLATION
DIRECTIONS TO SIZE R.O.
ACOUSTICAL ACCESS DOOR
ACCESS DOOR FRAME
RF CHAMBER WALL
STEEL STUD EQUIPMENT CABLE
CHASE - NO ACOUSTICAL BATT
INSULATION
EXTERIOR FACE OF RF
CHAMBER WALL
RF CHAMBER LAB 326
ACOUSTICAL ACCESS DOOR
ACCESS DOOR FRAME
GWB - REFER TO ACCESS DOOR
MANUFACTURER'S INSTALLATION
DIRECTIONS TO SIZE R.O.
STEEL STUD EQUIPMENT CABLE CHASE
- NO ACOUSTICAL BATT INSULATION
TOP TRACK
STEEL STUD PARTITION FRAMING
W/ACOUSTICAL BATT INSULATION
RF CHAMBER WALL
RF CHAMBER EQUIPMENT CABLE
PATCH PANEL - BY VENDOR
GWB J-BEAD
GWB L-BEAD
SUSPENDED CEILING TILE -
SEE REFLECTED CEILING
PLAN FOR HEIGHT
FLEXTRAY
3"
T.
O.
G W
B R.
O.
4"
ACOUSTICAL CEILING
TILE WITH IN CHAMBER
AIR GAP
3"
EDGE OF FINISHED
GWB JAMB
FINISHED GWB SILL
SUSPENDED
CEILING TRACK
SUSPENDED
CEILING TRACK
BRUSH STYLE PLATE CABLE PASS-THRU
Scale
UW
Number
Date Issued
Set Type
REVISIONS:
Sh ee t T itle
Pr oje ct Tit le:
Drawn By:
Fa ci lit ie s P la nn in g an d
M an ag em en t
P hy si ca l P la nt
A rc hi te ct s/
E ng in
. M ills
S tre et , M ad is on , W
I 5 ve rs ity o f W is co ns in -M ad ing N am e &
N um be r:
U W
B
LD
G
3/
/2
4:
:2
PM
3" = 1'-0"
A5
D E
TA
IL
S
03/23/2018
0526 1602
BD
P R
IM
A
TE
C
E N
TE
R
MCLEAN
IN
S
TA
LL
T H
R E
E R
F S
H
IE
LD
E
D C
H A
M B
E R
S S
U
IT
E
A
N D
C O
R R
ID
O
R
J
No. Date: By: Description:
3" = 1'-0"1 BASE OF CHAMBER WALL
3" = 1'-0"2 SECTION THROUGH DOOR THRESHOLD
3" = 1'-0"3 DATA CHASE HORIZONTAL SECTION
3" = 1'-0"4 DATA CHASE VERTICAL SECTION
ACOUSTICAL BATT INSULATION -
FROM HEADER FRAMING TO
BOTTOM OF STRUCTURAL DECK
HEADER FRAMING
D
F-CW
CSW
140°
140°
GV
GW
G
OV
OW
PD
V
SS
SHWR
SHWS
SD
OSD
(E)
DOMESTIC COLD WATER-FILTERED
DOMESTIC COLD SOFT WATER
DOMESTIC HOT WATER 140°
DOMESTIC HOT WATER-CIRCULATING
DOMESTIC HOT WATER-CIRCULATING 140°
GREASE VENT
GREASE WASTE
NATURAL GAS
OIL VENT
OIL WASTE
PUMP DISCHARGE
SANITARY VENT
SANITARY SEWER
SOLAR HOT WATER RETURN
SOLAR HOT WATER SUPPLY
STORM DRAINAGE
STORM DRAINAGE-OVERFLOW
EXISTING PIPE TAG
PIPING BEING DEMOLISHED
PG PROPANE GAS
UPRIGHT SPRINKLER HEAD
PENDENT SPRINKLER HEAD
RECESSED SPRINKLER
HEAD
CONCEALED SPRINKLER
HEAD
'D' REPRESENTS DRY SPRINKLER HEAD
SIDEWALL SPRINKLER HEAD
EXTENDED COVERAGE SIDEWALL SPRINKLER HEAD
OBSTRUCTION FROM
DUCTWORK 48" AND GREATER
48x18 SA
DIRECTION OF FLOW
GENERAL PLUMBING SYMBOLS
CWS
CWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
AV
AW
ACID VENT
ACID WASTE
COND COOLING COIL CONDENSATE
PCWS PROCESS COOLING WATER SUPPLY
PCWR PROCESS COOLING WATER RETURN VENT
RWS DRAIN
RWS RECLAIM WATER SUPPLY
RWR RECLAIM WATER RETURN
CA COMPRESSED AIR
IA INSTRUMENT AIR
MW MAKEUP WATER
CLW CLEAR WATER WASTE
NP NON-POTABLE WATER
TW TEMPERED WATER
NP NON-POTABLE WATER
STM ROOF STORM DRAIN PIPE
LCW LAB COLD WATER
LHW LAB HOT WATER
LHWR LAB HOT WATER RETURN
LAB AIRA
LAB CARBON DIOXIDECO2
LAB REVERSE OSMOSISRO
LAB REVERSE OSMOSIS RETURNROR
LAB OXYGENO2
NITROGEN GASN2
HELIUM GASHe
4" RD-1
PLUG/CAP
4"
4"
DRAIN TAG
DRAIN SIZE
FLOOR DRAIN
FIXTURE
DRAIN SIZE
ROOF DRAIN FIXTURE
TYPE (SEE SCHEDULE)
DRAIN TAG
PLUMBING FIXTURE TAG
PLUMBING FIXTURE
PIPE RISE
PIPE DROP
PIPE TEE
REDUCING 45 DEGREE TEE
45 DEGREE TEE
6" FD-2
TYPE (SEE SCHEDULE)
X" V UP THRU FLOOR
4" ORD-1
HYD-2
TYPE (SEE SCHEDULE)
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
ROOM NAME AND NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
EXISTING TO REMAIN IS SHOWN WITH LIGHT LINES.
NEW WORK IS SHOWN WITH SOLID HEAVY LINES.
DEMOLISHED WORK IS SHOWN WITH HEAVY
DASHED LINES.
PLUMBING SYMBOLS
PLUMBING SYMBOLS (CONTINUED)
FIRE PROTECTION SYMBOLS
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GR GRADE
GW GREASE WASTE
HB HOSE BIB
HD HEAD
HORZ HORIZONTAL
HP HORSE POWER
HP HIGH PRESSURE
HW HOT WATER
HYD HYDRANT
ID INDIRCT
IN INCH
INL INLET
INSUL INSULATION
INT INTERIOR
INV INVERT
INWG INCHES WATER GAUGE
JST SPC JOIST SPACE
JT JOINT
LAB LABORATORY
LB POUND
LB/HR POUNDS PER HOUR
LF LINEAL FOOT
LOC LOCATION
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LR LIQUID REFRIGERANT
LS LAWN SPRINKLER
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
MAN MANUAL
MATL MATERIAL
MAV MANUAL AIR VENT
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MCW MAKE-UP COLD WATER
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
N NECK
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NOM NOMINAL
NTS NOT TO SCALE
O OXYGEN
OC ON CENTER
OF OVERFLOW
OPNG OPENING
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PIV POST INDICATOR VALVE
PLBG PLUMBING
PR PAIR
PRELIM PRELIMINARY
PRESS PRESSURE
PRIM PRIMARY
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PW POTABLE WATER
PWR POWER
RD ROOF DRAIN
REC RECESSED
RED REDUCER
REQD REQUIRED
REV REVERSE
RLA RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SF SQUARE FOOT
SAN SANITARY
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT
SQ SQUARE
SSD SOIL SUBDRAIN
SS STAINLESS STEEL
STD STANDARD
STRUCT STRUCTURAL
SUCT SUCTION
SUSP SUSPENDED
T THERMOSTAT
TDR TRENCH DRAIN
TEFC TOTALLY ENCLOSED FAN COOLED
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VEL VELOCITY
VERT VERTICAL
VOL VOLUME
VTR VENT THROUGH ROOF
W WASTE
WCO WALL CLEAN OUT
WH WALL HYDRANT
AS AIR SEPARATOR
B BOILER
CF CHEMICAL FEEDER
CFP CHEMICAL FEEDER PUMP
CWP CONDENSER WATER PUMP
DB DOMESTIC WATER BOOSTER PUMP
DCP DOMESTIC WATER CIRCULATING PUMP
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
FP FIRE PUMP
GI GREASE INTERCEPTOR
HX HEAT EXCHANGE
SA SHOCK ABSORBER
SEP SEWAGE EJECTOR PUMP
SP SUMP PUMP
WFMS WATER FLOW MEASURING STATION
WH WATER HEATER
PIPE DROP OFF BOTTOM OF PIPE
PIPE RISE OFF TOP OF PIPE
CLEAN OUT
ABBREVIATIONS (CONTINUED)
& AND
A AIR
ABV ABOVE
ACOUS ACOUSTICAL
AD AREA DRAIN
ADD ADDENDUM
ADDL ADDITIONAL
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
AG ABOVE GROUND
ALT ALTERNATE
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECT/ARCHITECTURAL
AV ACID VENT
AW ACID WASTE
AUTO AUTOMATIC
BLDG BUILDING
BLW BELOW
BM BEAM
BO BY OTHER
BOT BOTTOM
BSMT BASEMENT
BTW BETWEEN
CAP CAPACITY
CB CATCH BASIN
CB CATCH BASIN
CCW COUNTER CLOCKWISE
CFCV CONSTANT FLOW CONTROL VALVE
CFM CUBIC FEET PER MINUTE
CHW CIRCULATING HOT WATER
CI CAST IRON
CLG CEILING
CO CLEAN OUT
COL COLUMN
COMB COMBINATION
CONC CONCRETE
CONF CONFERENCE
CONN CONNECT
CONST CONSTRUCTION
CONT CONTINUE/CONTINUATION
CONTR CONTRACT/CONTRACTOR
COORD COORDINATE
CTR CENTER
CUFT CUBIC FEET
CV CHECK VALVE
ABBREVIATIONS
CW COLD WATER
CW CLOCKWISE
D DEGREE
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DISCH DISCHARGE
DIV DIVISION
DI DEIONIZED WATER
DMPR DAMPER
DN DOWN
DWG DRAWING
DW DISTILLED WATER
EA EACH
EL ELBOW
ELEC ELECTRICAL
ELEV ELEVATION
EP EXPLOSION PROOF
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXP EXPANSION
EXPJT EXPANSION JOINT
EXT EXTERIOR
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FDV FIRE DEPARTMENT VALVE
FHC FIRE HOSE CABINET
FL FLOOR
FLEX FLEXIBLE
FLG FLANGE
FPM FEET PER MINUTE
FRP FIBERGLASS REINFORCED PIPE
FS FULL SIZE
FS FLOOR SINK
FT FOOT/FEET
FTG FOOTING
FUT FUTURE
GA GAGE/GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GENL GENERAL
EQUIPMENT ABBREVIATIONS
GENERAL NOTES
CW DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC WATER METER
FLOW MEASURING AND
BALANCING DEVICE
BALL VALVE
CHECK VALVE
THREE WAY VALVE
BUTTERFLY VALVE
MOTORIZED CONTROL
VALVE
PRESSURE REDUCING
VALVE
SOLENOID VALVE
PNEUMATIC
ELECTRIC
THREE WAY MOTORIZED
CONTROL VALVE
FP-DOM-W
FP-D FIRE PROTECTION DRY
COMBINATION FIRE & DOMESTIC
FP-O FIRE PROTECTION OTHER
FP-PA FIRE PROTECTION PRE-ACTION
FP-W FIRE PROTECTION WET
2"
* NOTE *
ALL OF GENERAL NOTES ON THIS
SHEET ARE TO BE APPLIED TO ALL
OTHER MECHANICAL DRAWINGS IN
THIS SET. SYMBOLS INDICATED HERE
AND NOT USED IN THE CONTRACT
DOCUMENTS DO NOT APPLY
TO THIS PROJECT. ADDITIONAL
SYMBOLS MAY BE INDICATED IN THE
CONTRACT DOCUMENTS.
Room
Scale
UW
Number
Date Issued
Set Type
REVISIONS:
Sh ee t T itle
Pr oje ct Tit le:
Drawn By:
Fa ci lit ie s P la nn in g an d
M an ag em en t
P hy si ca l P la nt
A rc hi te ct s/
E ng in
. M ills
S tre et , M ad is on , W
I 5 ve rs ity o f W is co ns in -M ad ing N am e &
N um be r:
U W
B
LD
G
3/
/2
4:
:3
PM
1/8" = 1'-0"
P1
SY
M
B O
LS
A
BB
R
EV
IA
TI
O N
S, G
E N
ER
AL
N O
TE
S
03/23/2018
0526 1602
BD
P R
IM
A
TE
C
E N
TE
R
KRAUS
IN
S
TA
LL
T H
R E
E R
F S
H
IE
LD
E
D C
H A
M B
E R
S S
U
IT
E
A
N D
C O
R R
ID
O
R
J
1 BOLDER TEXT AND GRAPHICS
INDICATE NEW WORK. ALL OTHER
TEXT AND GRAPHICS ARE EXISTING
INFORMATION SHOWN FOR
REFERENCE.
2 INSULATORS SHALL REPAIR OR
REPLACE ALL INCIDENTALLY FOUND
DAMAGED PIPE AND DUCT
INSULATION AND JACKETS IN
PROJECT AREA PER DSF MASTER
SPECIFICATIONS AS NEEDED VIA
MAINTENANCE WORK ORDER.
INSULATION AND JACKETS
DAMAGED DURING OR AS A RESULT
OF PROJECT WORK SHALL BE
REPAIRED OR REPLACED UNDER
PROJECT WORK ORDER.
3 PLUMBING SHOP SHALL CHECK
OPERATION OF ALL VALVES
ASSOCIATED WITH PROJECT.
REPAIR OR REPLACE DAMAGED
VALVES AS NEEDED VIA
MAINTENANCE WORK ORDER.
4 PLUMBING SHOP TO VERIFY ALL
PLUMBING FIXTURES INCLUDING
DRAINS IN PROJECT AREA ARE
FUNCTIONING PROPERLY. REPAIR,
CLEAN OR REPLACE AS REQUIRED
UNDER MAINTENANCE WORK
ORDER.
5 LABEL ALL PIPING, NEW AND
EXISTING, PER DSF MASTER
SPECIFICATIONS.
6 THOROUGHLY CLEAN ITEMS
BEFORE INSTALLATION. CAP PIPE
OPENINGS TO DEFLECT DEBRIS
UNTIL FIXTURES ARE INSTALLED
AND FINAL CONNECTIONS HAVE
BEEN MADE.
7 PROVIDE AND INSTALL PIPING
EQUIPMENT AND MATERIALS IN
ACCORDANCE WITH APPLICABLE
PLUMBING CODE REGULATIONS
AND STANDARDS, AUTHORITIES
HAVING JURISDICTION, AND AS
OTHERWISE RECOMMENDED OR
DIRECTED BY MANUFACTURERS.
3" 3"
3/4"
3/4" CW
3/4" CW
3/4"
3/4" G
2 1/2"
3" SS 3" SS
/2
/2
/2
AIR
GAS
SAN
300J
CORRIDOR
LAB
Room
ROOM
326C ROOM
326D
2" V
3" SS
3" 3"
3/4"
3/4" CW
3/4" CW
3/4"
3/4" G
2 1/2"
Scale
UW
Number
Date Issued
Set Type
REVISIONS:
Sh ee t T itle
Pr oje ct Tit le:
Drawn By:
Fa ci lit ie s P la nn in g an d
M an ag em en t
P hy si ca l P la nt
A rc hi te ct s/
E ng in
. M ills
S tre et , M ad is on , W
I 5 ve rs ity o f W is co ns in -M ad ing N am e &
N um be r:
U W
B
LD
G
3/
/2
4:
:1
PM
1/4" = 1'-0"
P2
3R D
F
LO
O R
P
LU
M B
IN
G
D E
M O
LI
TI
O N
/R E
M O
D E
L P
LA
N
03/23/2018
0526 1602
BD
P R
IM
A
TE
C
E N
TE
R
KRAUS
IN
S
TA
LL
T H
R E
E R
F S
H
IE
LD
E
D C
H A
M B
E R
S S
U
IT
E
A
N D
C O
R R
ID
O
R
J
REMODEL KEY NOTES
1 NEW SINK & FAUCET WITH DECK MOUNTED PULLOUT
EMERGENCY EYEWASH. SEE ARCHITECTURAL DRAWINGS
FOR MANUFACTURER & MODELS. CONNECT HOT WATER,
COLD WATER, WASTE & VENT FROM EXISTING SERVICES.
2 EXISTING PIPING SERVING FLOOR ABOVE SHALL REMAIN
UNLESS NOTED OTHERWISE.
3 CAP PIPING AT WALL OR AT MAIN IN CORRIDOR.
4 INSTALL NEW 3" CAST IRON WASTE PIPING WITH P-TRAP AND
CONNECT TO EXISTING 3" LATERAL MAIN. BOTTOM OF P-TRAP
SHALL BE LOCATED 9'-0" AFF MINIMUM.
5 PROVIDE AND INSTALL NEW 3" CAST IRON P-TRAP WITHOUT
CLEANOUT PLUG.
DEMOLITION KEY NOTES
1 DEMOLISH EXISTING SINK & FAUCET. REMOVE PIPING BACK
TO SUITABLE LOCATION AND CAP. REFER TO REMODEL PLAN
ON THIS SHEET FOR NEW WORK.
2 REMOVE CARBON TANK AND DIONIZER TANK LOCATED IN SINK
CABINET.
3 DEMOLISH PLUMBING SERVICES (GAS & AIR) ON ALL LAB
BENCHES. REMOVE PIPING BACK TO SUITABLE LOCATION &
CAP.
4 FUME HOOD BEING REMOVED. DISCONNECT PLUMBING
SERVICES TO HOOD, REMOVE PIPING BACK TO SUITABLE
LOCATION & CAP.
5 DEMOLISH MISCELLANEOUS UNNECESSARY PLUMBING PIPING
BACK TO SUITABLE LOCATION & CAP.
6 PIPING SERVING FLOOR ABOVE SHALL REMAIN UNLESS
NOTED OTHERWISE.
7 DEMOLISH 3" P-TRAP AND ASSOCIATED PIPING AS REQUIRED
TO ALLOW REPLACEMENT AT A HIGHER ELEVATION. SEE
REMODEL PLAN ON THIS SHEET.
8 DEMOLISH EXISTING P-TRAP WITH CLEANOUT PLUG FOR
REPLACEMENT, LATERAL AND VERTICAL PIPING TO REMAIN.
SEE REMODEL PLAN ON THIS SHEET.
NORTH
NORTH
1/4" = 1'-0"
3RD FLOOR PLUMBING DEMO PLAN
1/4" = 1'-0"
3RD FLOOR PLUMBING REMODEL PLAN
No. Date: By: Description:
4 5
(TYP.)8
7 7 7 7
4 4 4 4
(TYP.)
(TYP.)
CO2
CO
H
HS
NO2
O2
TH
TS
T X
SW
S
CWS
CWV
CA
CD
CDR
CTR
CTS
HWR
HWS
STM
16x8
16x8Ø
F
S
M
B
D
C
16Ø
OA
TA
RLA
CWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
COMBINATION WASTE & VENT
COMPRESSED AIR
CONDENSATE DRAINAGE
CONDENSATE RETURN
COOLING TOWER WATER RETURN
COOLING TOWER WATER SUPPLY
HEATING WATER RETURN
HEATING WATER SUPPLY
STEAM
OUTSIDE AIR
RELIEF AIR
TRANSFER AIR
REF-L
REF-S
REFRIGERANT-LIQUID
REFRIGERANT-SUCTION
2"
4" RD-1
CAP
4"
4"
REF-HG REFRIGERANT-HOT GAS
HVAC SYMBOLS (CONTINUED)
GRILLES, REGISTERS, AND
DIFFUSERS TAG
CFM
INLET/OUTLET SIZE
KEYNOTE
CONTINUATION SYMBOL
OVAL DUCT SIZE TAG
(WIDTH / HEIGHT)
SQUARE DUCT SIZE
TAG (WIDTH x HEIGHT)
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL MECHANICAL SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
TYPE (SEE SCHEDULE)
& AND
Ø ROUND
ABV ABOVE
AC AIR CONDITIONING
ACC AIR COOLED CONDENSER
ACCU AIR COOLING CONDENSING UNIT
ACOUS ACOUSTICAL
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
AFMS AIR FLOW MEASURING STATION
AG ABOVE GROUND
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECT/ARCHITECTURAL
AS AIR SEPARATOR
ATU AIR TERMINAL UNIT
AUTO AUTOMATIC
B BOILER
BLDG BUILDING
BLW BELOW
BO BY OTHER
BOT BOTTOM
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CF CABINET FAN
CF CHEMICAL FEEDER
CFCV CONSTANT FLOW CONTROL VALVE
CFM CUBIC FEET PER MINUTE
CFP CHEMICAL FEEDER PUMP
CH CHILLER
CHWP CHILLED WATER PUMP
CLG CEILING
CLG COOLING
COL COLUMN
COMB COMBINATION
CONC CONCRETE
COND CONDENSATE
CONF CONFERENCE
CONN CONNECT
CONST CONSTRUCTION
CONT CONTINUE/CONTINUATION
CONTR CONTRACT/CONTRACTOR
COORD COORDINATE
CRU CONDENSATE RETURN UNIT
CT COOLING TOWER
CTR CENTER
CUH CABINET UNIT HEATER
CUFT CUBIC FEET
CSTV CONSTANT VALVE
CTRLV CONTROL VALVE
CV CHECK VALVE
CW CLOCKWISE
CWP CONDENSER WATER PUMP
D DEGREE
DB DRY BULB
DC DUCT MOUNTED COIL
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DISCH DISCHARGE
DIV DIVISION
DMPR DAMPER
DN DOWN
EAT ENTERING AIR TEMPERATURE
EDC ELECTRIC DUCT COIL
EF EXHAUST FAN
EL ELBOW
ELEC ELECTRICAL
ELEV ELEVATION
EP EXPLOSION PROOF
EQ EQUAL
EQUIP EQUIPMENT
ET EXPANSION TANK
EWT ENTERING WATER TEMPERATURE
EA EXHAUST AIR
EAH EXHAUST HOOD
EXIST EXISTING
EXP EXPANSION
EXPJT EXPANSION JOINT
EXT EXTERIOR
F DEGREES FAHRENHEIT
FCU FAN COIL UNIT
FD FIRE DAMPER
FLEX FLEXIBLE
FLG FLANGE
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
FUT FUTURE
GA GAGE/GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GENL GENERAL
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GR GRADE
GRV GRAVITY ROOF VENTILATOR
H HUMIDIFIER
HB HOSE BIB
HORZ HORIZONTAL
HP HORSE POWER
HP HIH PRESSURE
HPU HEAT PUMP UNIT
HRU HEAT RECOVERY UNIT
HTG HEATING
HTR HEATER
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
ID INDIRECT
ILC INLINE CENTRIFUGAL
IN INCH
INL INLET
INSUL INSULATION
INT INTERIOR
INWG INCHES WATER GAUGE
JST SPC JOIST SPACE
JT JOINT
LAB LABORATORY
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LF LINEAL FOOT
LOC LOCATION
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LR LIQUID REFRIGERANT
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
MA MIXED AIR
MAN MANUAL
MATL MATERIAL
MAV MANUAL AIR VENT
MAX MAXIMUM
MBD MOTORIZED BYPASS DAMPER
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MCW MAKE-UP COLD WATER
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MUA MAKE-UP/AIR
N NECK
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
OC ON CENTER
OF OVERFLOW
PD PRESSURE DROP
PF PROPELLER FAN
PIV POST INDICATOR VALVE
PLBG PLUMBING
PNEU PNEUMATIC
PRELIM PRELIMINARY
PRESS PRESSURE
PRIM PRIMARY
PRV PRESSURE REDUCING VALVE
PRV POWER ROOF VENTILATOR
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
R DUCT RISER
RA RETURN AIR
RC REHEAT COIL
RCP RADIANT CEILING PANEL
RE RETURN/EXHAUST FAN
REC RECESSED
RED REDUCER
REFR REFRIGERATION
RH RELATIVE HUMIDITY
REQD REQUIRED
REV REVERSE
RLA RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RTU ROOFTOP UNIT
SF SQUARE FOOT
SA SUPPLY AIR
SAT SOUND ATTENUATOR
SF SQUARE FOOT
SF SUPPLY FAN
SD SMOKE DAMPER
SLV SLEEVE
SM SURFACE MOUNT
SP STATIC PRESSURE
SPEC SPECIFICATION
SPS STATIC PRESSURE STATION
SQ SQUARE
SR SUCTION REFRIGERANT
SS STAINLESS STEEL
STD STANDARD
STM STEAM
STRUCT STRUCTURAL
SUSP SUSPENDED
T THERMOSTAT
TCP TEMPERATURE CONTROL PANEL
TD TEMPERATURE DROP
TEFC TOTALLY ENCLOSED FAN COOLED
ABBREVIATIONS
FIRE DAMPER
SMOKE DAMPER
MOTORIZED DAMPER
MANUAL BALANCING
DAMPER
BACKDRAFT DAMPER
COMBINATION
FIRE/SMOKE DAMPER
SUPPLY OUTLET RETURN/EXHAUST INLET
RECTANGULAR SUPPLY AIR DUCT RISE
RECTANGULAR RETURN AIR DUCT RISE
MECHANICAL EQUIPMENT
ROUND DUCT SIZE
TAG (DIAMETER)
DOMESTIC WATER METER
FLOW MEASURING AND
BALANCING DEVICE
BALL VALVE
CHECK VALVE
EXISTING TO REMAIN IS SHOWN WITH LIGHT
LINES.
NEW WORK IS SHOWN WITH SOLID HEAVY LINES.
DUCT BEING
DEMOLISHED
PIPING BEING DEMOLISHED
THREE WAY VALVE
BUTTERFLY VALVE
TYPE (SEE SCHEDULE)
ROUND SUPPLY AIR DUCT RISE
ROUND RETURN AIR DUCT RISE
ABOVE GROUND PIPING
PIPE SIZE TAG (DIAMETER)
DROP
DROP
DROP
DROP
DRAIN TAG
DRAIN SIZE
FLOOR DRAIN FIXTURE
DRAIN SIZE
ROOF DRAIN FIXTURE
TYPE (SEE SCHEDULE)
DRAIN TAG
PLUMBING FIXTURE TAG
PLUMBING FIXTURE
PIPE RISE
PIPE DROP
PIPE TEE
REDUCING 45 DEGREE TEE
45 DEGREE TEE
BELOW GROUND PIPING
PIPE INVERT ELEVATION TAG
PIPE SLOPE TAG
GEA GREASE EXHAUST AIR
* NOTE *
ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE
APPLIED TO ALL OTHER MECHANICAL DRAWINGS IN THIS
SET. SYMBOLS INDICATED HERE AND NOT USED IN THE
CONTRACT DOCUMENTS DO NOT APPLY
TO THIS PROJECT. ADDITIONAL SYMBOLS MAY BE
INDICATED IN THE CONTRACT DOCUMENTS.
SEA SMOKE EXHAUST AIR
6" FD-2
TYPE (SEE SCHEDULE)
X" V UP THRU FLOOR
4" ORD-1
HYD-2
TYPE (SEE SCHEDULE)
MOTORIZED CONTROL
VALVE
PRESSURE REDUCING
VALVE
SOLENOID VALVE
THREE WAY MOTORIZED
CONTROL VALVE
DEMOLISHED WORK IS SHOWN WITH HEAVY
DASHED LINES.
DIRECTION OF FLOW
CARBON DIOXIDE
SENSOR
CARBON MONOXIDE
SENSOR
HUMIDISTAT
HUMIDITY SENSOR
NITROGEN DIOXIDE
SENSOR
OXYGEN SENSOR
TEMPERATURE &
HUMIDITY SENSOR
MECHANICAL PIPING SYMBOLS
TEMPERATURE
SENSOR
MANUAL SWITCH
SENSOR
THERMOSTAT
ABBREVIATIONS (CONTINUED)
TRANSFER AIR FLOW
ARROW
RECTANGULAR DUCT
TAKE-OFF
ROUND DUCT
TAKE-OFF
ROUND DUCT TAKE-
OFF FROM
RECTANGULAR
MAIN
RECTANGULAR DUCT
TAKE-OFF FROM
ROUND MAIN
DUCT TRANSITION -
CONCENTRIC
DUCT TRANSITION -
ECCENTRIC
RADIUS ELBOW
MITERED ELBOW
DUCT REHEAT COIL
SUPPLY AIR FLOW
ARROW
FLEX DUCT
PIPE DROP OFF BOTTOM OF PIPE
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
US UTILITY SET
UV UNIT VENTILATOR
V VENT
VAV VARIABLE AIR VOLUME
VEL VELOCITY
VENT VENTILATION
VERT VERTICAL
VOL VOLUME
WB WET BULB
WFMS WATER FLOW MEASURING STATION
GENERAL NOTES
HVAC SYMBOLS
P = PNEUMATIC
E = ELECTRIC
PIPE RISE OFF TOP OF PIPE
CD-3
XX-XXX
6-48-2
XXX
NECK SIZE
SLOT LENGTH
NUMBER OF SLOTS
CFM
TYPE (SEE SCHEDULE)
LINEAR DIFFUSER
SA SUPPLY AIR
RA RETURN AIR
EA EXHAUST AIR
5/32" / 12" SLOPE
INV. ELEV:-71' - 1"
ELECTRIC
PNEUMATIC
PLUG
Room
Scale
UW
Number
Date Issued
Set Type
REVISIONS:
Sh ee t T itle
Pr oje ct Tit le:
Drawn By:
Fa ci lit ie s P la nn in g an d
M an ag em en t
P hy si ca l P la nt
A rc hi te ct s/
E ng in
. M ills
S tre et , M ad is on , W
I 5 ve rs ity o f W is co ns in -M ad ing N am e &
N um be r:
U W
B
LD
G
3/
/2
4:
:2
PM
1/8" = 1'-0"
M1
SY
M
B O
LS
A
BB
R
EV
IA
TI
O N
S, G
E N
ER
AL
N O
TE
S
03/23/2018
0526 1602
BD
P R
IM
A
TE
C
E N
TE
R
Author
IN
ST
AL
L
TH
R
EE
R
F
SH
IE
LD
ED
C
H
AM
B
ER
S S
U
IT
E
A
N D
C O
R R
ID
O
R
J
1 BOLDER TEXT AND GRAPHICS INDICATES NEW WORK. ALL
OTHER TEXT AND GRAPHICS IS EXISTING INFORMATION
SHOWN FOR REFERENCE.
2 NEW DUCTWORK SHALL BE INSTALLED PER SMACNA AND ALL
STATE CODES. DUCTWORK SHALL BE SEALED AT ALL JOINTS,
TRANSVERSE AND LONGITUDINAL SEAMS AND CONNECTIONS
IN DUCTWORK. THE REFERENCED DUCTWORK INCLUDES ALL
SUPPLY, EXHAUST, AND RETURN DUCTS. CONCEALED
SUPPLY AIR DUCTWORK SHALL BE INSULATED WITH FLEXIBLE
FIBERGLASS (MIN. 5.0 R). EXPOSED SUPPLY AIR DUCTWORK,
OUTSIDE OF THE ROOM IT SERVES SHALL BE INSULATED WITH
RIGID FIBERGLASS (MIN. 5.0 R) OR SHALL BE DOUBLE-WALL
DUCT WITH MINIMUM 5.0 R INSULATION. EXPOSED SUPPLY
AIR DUCTWORK DOWNSTREAM OF THE REHEAT COIL AND
WITHIN THE ROOM IT SERVES DOES NOT REQUIRE
INSULATION
3 THE MAXIMUM LENGTH FOR EACH SECTION OF FLEXIBLE
DUCT SHALL BE 5'-0". ALL BENDS IN FLEXIBLE DUCT SHALL
HAVE A MINIMUM RADIUS OF 1.5 DUCT DIAMETERS TO DUCT
CENTERLINE.
4 LABEL ALL PIPING NEW AND EXISTING PER DSF MASTER
SPECIFICATIONS.
5 STEAMFITTERS SHALL RECALIBRATE OR REPLACE EXISTING
THERMOSTATS AS APPROPRIATE.
6 BALANCE HVAC AIR AND FLUID SYSTEMS TO QUANTITIES
SHOWN ON PLANS AND/OR SCHEDULES. SEND BALANCE
REPORTS TO ENGINEER AND MAKE AVAILABLE TO THE
DEPARTMENT OF SAFETY & BUILDINGS UPON REQUEST.
7 MAINTENANCE MECHANIC SHALL CLEAN ALL SUPPLY,
RETURN, EXHAUST, TRANSFER AND DOOR GRILLES AS
NEEDED VIA MAINTENANCE WORK ORDER.
8 INSULATION & JACKETS DAMAGED DURING OR AS A RESULT
OF PROJECT WORK SHALL BE REPAIRED OR REPLACED
UNDER PROJECT WORK ORDER.
9 MAINTENANCE MECHANIC TO CLEAN ALL EXISTING COILS AS
NEEDED VIA MAINTENANCE WORK ORDER. SHEETMETAL TO
INSTALL ACCESS DOORS WHERE REQUIRED ON ALL EXISTING
COILS VIA MAINTENANCE WORK ORDER.
10 STEAMFITTERS TO CHECK OPERATION OF CONTROLS
ASSOCIATED WITH REMODEL, UNDER PROJECT WORK ORDER.
T P
TP H T P
TH TH TH
TH
26x20 24x20
14x8
12x8
12x6
12x7
18x8
42x9 42x9 x7 x7
30x14
24x8
52x18 x1
34x18 x1
34x14 x8
26x12
26x12 x8
1 1/2"
3/4"
1 1/2"
3/4"
2"
1 1/4"
3/4"
2"
3/4" 1" 3/4"
2"
3/4"
3/4"
1 1/4"
ROOM
326C
ROOM
326D
CORRIDOR
300J
LAB
Room
26x20 24x20 SA
14x8
12x8
12x6 18x8
42x9 42x9
12x7
30x14 52x18
34x18
34x18
18x14
12x8
1 1/2"
3/4"
1 1/2"
3/4"
2" 1 1/4"
3/4"
2"
3/4" 1" 3/4"
2"
3/4"
3/4"
1 1/4"
34x22 SA 24x12 22x12 22x8
26x18 EA
Ø
Ø x8 x8 x8
8Ø 8Ø 8Ø
10Ø
10Ø x8
10Ø
8Ø 8Ø 8Ø x7 x612 x7
EG-1
22x22
26x12
26x12
CD-66
CD-66
CD-66
CD-9
CD-9
CD-9
EG-1
22x22
EG-1
22x22
1/2"
EG-1
22x22
EG-1
22x22
RC-
RC- RC-300J-1
RC-
D S
A -1
D S
A -1
DSA-1D
S
A -2
D S
A -2
D S
A -2
300J
CORRIDOR
LAB
Room
326C
RF CHAMBER
326D
RF CHAMBER
326B
RF CHAMBER
M3
M3
Scale
UW
Number
Date Issued
Set Type
REVISIONS:
Sh ee t T itle
Pr oje ct Tit le:
Drawn By:
Fa ci lit ie s P la nn in g an d
M an ag em en t
P hy si ca l P la nt
A rc hi te ct s/
E ng in
. M ills
S tre et , M ad is on , W
I 5 ve rs ity o f W is co ns in -M ad ing N am e &
N um be r:
U W
B
LD
G
3/
/2
4:
:3
PM
1/4" = 1'-0"
M2
3R D
F
LO
O R
M E
C H
A N
IC
A
L D
E M
O
LI
TI
O
N /R
E M
O D
E L
P
LA
N
03/23/2018
0526 1602
BD
P R
IM
A
TE
C
E N
TE
R
KRAUS
IN
S
TA
LL
T H
R E
E R
F S
H
IE
LD
E
D C
H A
M B
E R
S S
U
IT
E
A
N D
C O
R R
ID
O
R
J
REMODEL KEY NOTES
1 PROVIDE & INSTALL NEW HOT WATER REHEAT COIL. SEE
SCHEDULE AND DETAILS ON SHEET M3. PROVIDE
ELECTRONIC CONTROL VALVE ON HOT WATER PIPING. VALVE
SHALL FAIL IN LAST POSITION.
2 INSULATE ALL NEW AND EXISTING SUPPLY DUCTWORK
CONCEALED ABOVE CEILINGS AS NOTED IN GENERAL NOTE 2
ON SHEET M1.
3 REPLACE EXISTING PNEUMATIC HOT WATER CONTROL VALVE
WITH ELECTRONIC CONTROL VALVE. VALVE SHALL FAIL IN
LAST POSITION.
4 CONNECT TO EXISTING 34x14 EXHAUST DUCT NEAR WALL.
PROVIDE & INSTALL TRANSITION OFFSETTING OGEE FITTING.
5 INSTALL NEW EXHAUST DUCT AT 8'-6" ABOVE FINISHED
FLOOR. NEW EXHAUST DUCT SHALL BE LOCATED OFF NEW
WALL (±18") TO ALLOW SPACE TO INSTALL MANUAL VOLUME
DAMPER AND COMBINATION TEMPERATURE & HUMIDITY
SENSOR BEFORE EXHAUST BRANCH DUCT GOES THROUGH
NEW GYPSUM WALL.
6 PROVIDE & INSTALL LAY-IN SUPPLY OR EXHAUST GRILLE IN
SUSPENDED CEILING WITHIN RF CHAMBER. PROVIDE
FLEXIBLE DUCT CONNECTION BETWEEN GRILLE AND
HONEYCOMB WAVEGUIDE (PROVIDED BY CHAMBER
MANUFACTURER). PROVIDE & INSTALL SQUARE TO ROUND
TRANSITION TO HONEYCOMB WAVEGUIDE CONNECTION ON
OUTSIDE OF CHAMBER.
7 PROVIDE & INSTALL DUCT SOUND ATTENUATOR (DSA).
INSTALL PER MANUFACTURER RECOMMENDATIONS. SEE
SECTION 3 ON SHEET A4 FOR ORIENTATION OF (SUPPLY &
EXHAUST) DUCT SOUND ATTENUATORS. SEE SCHEDULE ON
SHEET M3.
8 PROVIDE & INSTALL ELECTRONIC TEMPERATURE & HUMIDITY
SENSOR ON DUCT TO CONTROL ROOM.
9 PROVIDE & INSTALL ELECTRONIC TEMPERATURE & HUMIDITY
SENSOR ON WALL TO CONTROL ROOM
10 PROVIDE & INSTALL LAY-IN CEILING DIFFUSER. COORDINATE
LOCATION WITH FLOOR DRAIN P-TRAPS SERVING FLOOR
ABOVE. REFER TO REFLECTED CEILING PLAN ON SHEET A3.
SEE SCHEDULE ON SHEET M3.
11 PROVIDE & INSTALL LAY-IN EXHAUST GRILLE WITH INTEGRAL
2" FILTER. COORDINATE LOCATION WITH FLOOR DRAIN
P-TRAPS SERVING FLOOR ABOVE. REFER TO REFLECTED
CEILING PLAN ON SHEET A3. SEE SCHEDULE ON SHEET M3
DEMOLITION KEY NOTES
1 FUME HOOD TO BE REMOVED. DISCONNECT & DEMOLISH
EXHAUST DUCTWORK BACK TO MAIN. REMOVE AND SALVAGE
FUME HOOD MONITOR TO SHEET METAL SHOP SURPLUS.
2 DEMOLISH EXISTING EXHAUST DUCTWORK AS SHOWN.
REFER TO REMODEL PLAN ON THIS SHEET FOR NEW WORK.
3 CUTOFF EXISTING EXHAUST DUCT NEAR WALL AND PREPARE
FOR NEW DUCT EXTENSION. SEE REMODEL PLAN ON THIS
SHEET.
4 DEMOLISH EXISTING SUPPLY DUCTWORK AS SHOWN. REFER
TO REMODEL PLAN ON THIS SHEET FOR NEW WORK.
5 DEMOLISH EXISTING DUCT MOUNTED SUPPLY DIFFUSER
INCLUDING TAP AND CAP MAIN AIRTIGHT.
6 DEMOLISH EXISTING PNEUMATIC THERMOSTAT AND
ASSOCIATED CONTROL TUBING.
7 DEMOLISH EXISTING PNEUMATIC HUMIDISTAT AND
ASSOCIATED CONTROL TUBING.
NORTH
NORTH
1/4" = 1'-0"
3RD FLOOR MECHANICAL DEMO PLAN
1/4" = 1'-0"
3RD FLOOR MECHANICAL REMODEL PLAN
No. Date: By: Description:
6 6
10 11
33 3
10 11
2 7
SHUT-OFF VALVE
HWS
HWR
REHEAT COIL
CAPPED DRAIN (1/2" BALL VAVLE)
TWO WAY TEMPERATURE CONTROL VALVE
UNION (TYP)MANUAL KEY
TYPE AIR VENT
CALIBRAT
ED
BALANCIN
G VALVE
HOT WATER REHEAT COIL PIPING DETAIL
N.T.S.
DSA-2 26x18 EA
8x12 EA
8Ø EA
326C
RF CHAMBER
LAB
300J
CORRIDOR
DSA-1
6x12 SA
8Ø SA 24x20 SA
REHEAT COIL
326C
RF CHAMBER
300J
CORRIDOR
Scale
UW
Number
Date Issued
Set Type
REVISIONS:
Sh ee t T itle
Pr oje ct Tit le:
Drawn By:
Fa ci lit ie s P la nn in g an d
M an ag em en t
P hy si ca l P la nt
A rc hi te ct s/
E ng in
. M ills
S tre et , M ad is on , W
I 5 ve rs ity o f W is co ns in -M ad ing N am e &
N um be r:
U W
B
LD
G
3/
/2
4:
:3
PM
1/4" = 1'-0"
M3
D
ET
AI
LS
S
C H
ED
U
LE
S
03/23/2018
0526 1602
BD
P R
IM
A
TE
C
E N
TE
R
KRAUS
IN
S
TA
LL
T H
R E
E R
F S
H
IE
LD
E
D C
H A
M B
E R
S S
U
IT
E
A
N D
C O
R R
ID
O
R
J
NOTES:
1. SYSTEM DESIGN BASED ON MANUFACTURER LISTED ABOVE. ANY DEVIATION IN
EQUIPMENT SIZE AND SPECIFICATIONS FROM EQUIPMENT SIZE AND
SPECIFICATIONS
LISTED SHALL BE IDENTIFIED BY EQUIPMENT SUPPLIER.
2. SEE PLAN FOR NECK SIZE AND CFM.
DIFFUSERS, REGISTERS, & GRILLES SCHEDULE
UW PROJECT NO. EQUIPMENT TAG QUANTITY
MANUFACTURE
R MODEL/TYPE MAX. PRESSURE DROP
MAX. NECK
VELOCITY PATTERN FACE SIZE MOUNTING TYPE FINISH DAMPER REMARKS
1602 CD-9 3 PRICE RFD 0.2 1100 2-WAY 24x24 LAY-IN WHITE NO PROVIDE WITH INTEGRAL 2" FILTER RACK 1602 CD-66 3 CARNES RSLAH FILTER 0.1 600 1-WAY 24x24 LAY-IN WHITE NO NO FILTER INSTALLED
No. Date: By: Description:
1602 EG-1 2 CARNES RSLAH FILTER 0.1 400 - 24x24 LAY-IN WHITE NO PROVIDE WITH INTEGRAL 1" FILTER RACK 1602 EG-1 3 CARNES RSLAH FILTER 0.1 400 - 24x24 LAY-IN WHITE NO PROVIDE WITH INTEGRAL 2" FILTER RACK
HOT WATER REHEAT COIL
UW PROJECT
NO.
EQUIPMENT
TAG SERVICE LOCATION MANUFACTURER MODEL/TYPE
AIR FLOW
(cfm)
AIR PRESS. DROP
(in. W.G.)
EAT/LAT
(Deg. F)
CAPACITY
(MBH)
COIL FACE
SIZE (HxW)
FACE AREA
(Sq. Ft.)
FACE
VELOCITY
COIL EWT/LWT
(Deg. F)
WATER FLOW
(gpm)
WATER P.D.
(ft.) REMARKFINS ROW
1602 RC-300J-1 326C 300J HEATCRAFT SD 1 06 12 8
01 06
140 0.05 55 / 87 4.84 6"X12" 0.5 280 8 1 180 0.5 10 -
SOUND ATTENUATOR
UW
PROJECT
NO.
EQUIPMENT
TAG MANUFACTURER MODEL LOCATION SERVICE MATERIAL
TOTAL
CAPACITY
(CFM)
MAX.
VEL.
(FPM)
MAX. PD
("WG)
OVERALL DIMENSION (IN) DYNAMIC INSERTION LOSS / MAXIMUM SELF GENERATED POWER LEVELS
REMARKH / DIA. WIDTH LENGTH 63 125 250 500 1000 2000 4000 8000
1602 DSA-1 VIBRO-ACOUSTICS RNM OVER RF
CHAMBER
SUPPLY GALVANIZED 140 140 0.05 12" 12" 36" 6 / 33 5 / 10 10 / 10 15 / 10 10 / 21 10 / 14 9 / 10 8 / 15 PACKLESS
1602 DSA-2 VIBRO-ACOUSTICS RNM OVER RF
CHAMBER
EXHAUST GALVANIZED 140 140 0.05 12" 12" 36" 6 / 33 5 / 17 10 / 16 15 / 21 10 / 28 10 / 13 9 / 10 8 / 10 PACKLESS
1/4" = 1'-0"1 Section of Exhaust at Chamber 1/4" = 1'-0"2 Section of Supply at Chamber
ELECTRICAL SYMBOLS & ABBREVIATIONS
SC
T
S
QUADRAPLEX ELECTRIC OUTLET
DUPLEX ELECTRIC OUTLET
MULTIPLE PORT VOICE/DATA
VOICE JACK
DATA/DATA JACK
THERMOSTAT
LIGHT SWITCH
WIREMOLD
GAS
SEPARATE CIRCUIT
EXIT SIGN
1X4 LAY-IN FLUORESENT LIGHT FIXTURE
INCANDESCENT LIGHT FIXTURE
FIRE ALARM DEVICE
NOTES:
1. SYMBOLS INDICATED HERE AND NOT USED IN THE CONTRACT DOCUMENTS DO NOT APPLY
TO THIS PROJECT. ADDITIONAL SYMBOLS MAY BE INDICATED IN THE CONTRACT
DOCUMENTS.
2. NEW WORK IS SHOWN WITH SOLID HEAVY LINES.
3. EXISTING TO REMAIN IS SHOWN WITH LIGHT LINES.
4. DEMOLISHED WORK IS SHOWN WITH HEAVY DASHED LINES.
A AMPERES
AFF ABOVE FINISHED FLOOR
ARCH ARCHITECTURAL
ASC ABOVE SUSPENDED CEILING
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
BATS BYPASS AUTOMATIC TRANSFER SWITCH
DC DIRECT CURRENT
DS DAYLIGHT SENSOR
K KELVIN
LAN LOCAL AREA NETWORK
FA FIRE ALARM
BATS BYPASS AUTOMATIC TRANSFER SWITCH
DC DIRECT CURRENT
DS DAYLIGHT SENSOR
K KELVIN
LAN LOCAL AREA NETWORK
FA FIRE ALARM
OS OCCUPANCY SENSOR
S LIGHT SWITCH 3-WAY
S LIGHT SWITCH OCCUPANCY SENSOR
OS
Scale
UW
Number
Date Issued
Set Type
REVISIONS:
Sh ee t T itle
Pr oje ct Tit le:
Drawn By:
Fa ci lit ie s P la nn in g an d
M an ag em en t
P hy si ca l P la nt
A rc hi te ct s/
E ng in
. M ills
S tre et , M ad is on , W
I 5 ve rs ity o f W is co ns in -M ad ing N am e &
N um be r:
U W
B
LD
G
3/
/2
4:
:2
PM
1/4" = 1'-0"
E1
SY
M
BO
LS
A
BB
R
EV
IA
TI
O
N S, G
EN
ER
AL
N O
TE
S
03/23/2018
0526 1602
BD
P R
IM
A
TE
C
E N
TE
R
DREES
IN
ST
AL
L
TH
R
EE
R
F
SH
IE
LD
ED
C
H
AM
BE
R
S S
U
IT
E
A
N D
C O
R R
ID
O
R
J
GENERAL NOTES
1 ADJUST LOCATIONS AND HEIGHTS AS NEEDED.
2 SURFACE MOUNT NEW ELECTRICAL INSTALLATIONS EXCEPT
SURGICAL LIGHT.
3 LABEL ALL CIRCUITS, RECEPTACLES, JUNCTION BOXES, AND
EQUIPMENT.
4 UPDATE AFFECTED PANEL SCHEDULES.
5 REFEED ANY ELECTRICAL AFFECTECTED BY REMODEL
PORJECT.
6 PLACE ARC FLASH LABEL ON PANELS THAT ARE PART OF THE
PROJECT.
7 TEST FIRE ALARM SYSTEM AS NEEDED DUT TO REMODEL
PROJECT.
8 RESEAL FIRE AND SMOKE WALL PENETRATIONS AS NEEDED.
9 FIELD VERIFY ELECTRICAL CIRCUITS SHOWN ON THE
DRAWINGS.
ENCLOSURE GROUNDING DETAILLIGHTING CONTROLLER
FH
F H
F HFH
3A
M F H
3A
FH
3A-18
3A-18
3A-18 3A-18
3A-5
3A-5
3B-153A-43A-83B-28/30
3A-16
3A-16
3B-4
3B-2 3B-2
3B-4
3A-18 3A-16
3B-6 3B-6
3B-7 3B-9 3A-6 3A-2
3A-5 3B-26
3B-18
3A-16
3A-16 3A-6
3A-5
RF FILTER
LIGHTING
RF FILTER
POWER
RF FILTER
LIGHTING
LIGHTING
CONTROL BOX
RF FILTER
POWER
RF FILTER
POWER
2' - 9" 6' - 8"
8' - 8"
A B
RF FILTER
LIGHTING
LIGHTING
CONTROL BOX
LIGHTING
CONTROL BOX
Scale
UW
Number
Date Issued
Set Type
REVISIONS:
Sh ee t T itle
Pr oje ct Tit le:
Drawn By:
Fa ci lit ie s P la nn in g an d
M an ag em en t
P hy si ca l P la nt
A rc hi te ct s/
E ng in
. M ills
S tre et , M ad is on , W
I 5 ve rs ity o f W is co ns in -M ad ing N am e &
N um be r:
U W
B
LD
G
3/
/2
4:
:2
PM
1/4" = 1'-0"
E2
3R D
F
LO
O R
E
LE
C
TR
IC
A
L D
E M
O
LI
TI
O
N /R
E M
O D
E L
P
LA
N
03/23/2018
0526 1602
BD
P R
IM
A
TE
C
E N
TE
R
DREES
IN
ST
AL
L
TH
R
EE
R
F
SH
IE
LD
ED
C
H
AM
B
ER
S S
U
IT
E
A
N D
C O
R R
ID
O
R
J
REMODEL KEY NOTES
1 REPLACE EXISTING RECEPTACLE WITH A GFCI.
2 INSTALL NEW WALL MOUNTED LIGHT FIXTURE,
MOUNTED AT 72" AFF. WALL WILL BE OPENED TO
ALLOW FOR A RECESSED ELECTRICAL BOX.SEE
PROJECT FILE FOR CUT-SHEET.
3 INSTALL 2 ea DOUBLE DUPLEX RECEPTACLES ON A
DEDICATED CIRCUIT. SURFACE MOUNTED AT 36" AFF
TO THE BOTTOM IN EMT CONDUIT/BOXES. PAINT TO
MATCH.
4 INSTALL A DATA/DATA JACK. SURFACE MOUNT AT 36"
AFF TO THE BOTTOM IN EMT CONDUIT/BOX. PAINT TO
MATCH. INSTALL BRIDLE RINGS ABOVE THE
SUSPENDED CEILING FOR SUPPORTS AS NEEDED.
5 INSTALL 2 ea 120v ELECTRICAL CIRCUITS FOR RF
ENCLOSURE. ONE FOR THE LIGHTING AND ONE FOR
FUTURE RECEPTACLES.
6 INSTALL LIGHTING CONTROL BOX, LIGHT SWITCH, AND
RF FILTER. CONNECT LOAD SIDE TO ENCLOSURE LIGHT
FIXTURES. NECESSARY PARTS ARE SUPPLIED WITH
THE ENCLOSURE.
7 INSTALL A VERTICALLY MOUNTED 4" FLEXTRAY,
SURFACE MOUNT AT 36" AFF TO THE BOTTOM
EXTENDED TO 6" FLEXTRAY.
8 INSTALL A WALL MOUNTED EQUIPMENT GROUNDING
BAR MOUNTED JUST BELOW THE SUSPENDED CEILING
. INSTALL A #6 GROUNDING WIRE FROM THE BAR TO
THE EXISTING EQUIPMENT GROUND LOCATED IN ROOM
333. CONNECT RF FILTERS, AND ENCLOSURES TO
GROUND BAR. REFER TO PDC INSTALLATION MANUAL
FOR DETAILS.
9 INSTALL A QUAD RECEPTACLES MOUNTED AT 42" AFF.
SURFACE MOUNT EMT CONDUIT/BOX. PAINT TO MATCH
WALL COLOR.
10 EQUIPMENT CABLE CHASE - SEE ARCHITECTURAL FOR
ADDITIONAL INFORMATION.
DEMOLITION KEY NOTES
1 DEMO ELECTRICAL RECEPTACLE, BRANCH CIRCUIT WIRING,
AND ASSOCIATED SURFACE MOUNTED BOXES/CONDUIT.
REFEED AND UPSTREAM ELECTRICAL AFFECTED BY
REMODEL PROJECT.
2 DEMO NETWORK JACK, WIRING, AND ASSOCIATED PANDUIT.
3 DEMO LIGHT SWITCH AND ASSOCIATED WIRING.
4 DEMO FIRE ALARM STROBE.
5 DEMO UNDER THE CABINET LIGHT FIXTURE.
6 DEMO TO FUME HOOD. REMOVE ASSOCIATED BRANCH
CIRCUIT WIRING.
7 DEMO IN WALL LIGHT FIXTURE. REMOVE ASSOCIATED
BRANCH CIRCUIT WIRING.
NORTH
NORTH
1/4" = 1'-0"
1602 - 3RD FLOOR ELECTRICAL DEMO PLAN
1/4" = 1'-0"
1602 - 3RD FLOOR ELECTRICAL REMODEL PLAN
1 1
1 1 1 1
No. Date: By: Description:
7 7 7
9 9 9
10 10 10
CLG
F H
T E
F H
3A
FH
H
H
OS JJ JJ JJ
OS
CLG
F
H OS
A/B
A/B A/B A/B A/B A/B
Scale
UW
Number
Date Issued
Set Type
REVISIONS:
Sh ee t T itle
Pr oje ct Tit le:
Drawn By:
Fa ci lit ie s P la nn in g an d
M an ag em en t
P hy si ca l P la nt
A rc hi te ct s/
E ng in
. M ills
S tre et , M ad is on , W
I 5 ve rs ity o f W is co ns in -M ad ing N am e &
N um be r:
U W
B
LD
G
3/
/2
4:
:2
PM
1/4" = 1'-0"
E3
3R D
F
LO
O R
E
LE
C
TR
IC
AL
C
EI
LI
N
G D
EM
O
/R E
M O
D E
L
PL
A N
03/23/2018
0526 1602
BD
P R
IM
A
TE
C
E N
TE
R
DREES
IN
ST
AL
L
TH
R
EE
R
F
SH
IE
LD
ED
C
H
AM
B
ER
S S
U
IT
E
A
N D
C O
R R
ID
O
R
JREMODEL KEY NOTES
1 INSTALL NEW 2x2 LED LIGHT FIXTURE. SEE PROJECT
FILE FOR FIXTURE CUT-SHEET.
2 INSTALL NEW OCCUPANCY SENSOR. CONNECT ALL
SENSORS TOGETHER.
3 REINSTALL PREVIOUSLY REMOVED FIRE ALARM
DETECTOR. RE-PIPE CONDUITS AS NEEDED TO CLEAR
RF ENCLOSURES AS NEEDED.
4 INSTALL A 4"x2" FLEXTRAY MOUNTED 3" BELOW THE
SUSPENDED CEILING TO THE TOP OF THE TRAY.
5 INSTALL 6 ea RECESSED CAN LIGHTS SUPPLIED WITH
THE ENCLOSURE.
6 INSTALL A 2" FLEXTRAY ALONG THE WALL.
DEMOLITION KEY NOTES
1 DEMO AND RECYCLE LIGHT FIXTURE.
2 DEMO FIRE ALARM DEVICE. RETAIN FOR RELOCATION.
NORTH
NORTH
1/4" = 1'-0"
1602 - 3RD FLOOR ELECTRICAL DEMO CEILING PLAN
1/4" = 1'-0"
1602 - 3RD FLOOR ELECTRICAL REMODEL CEILING PLAN
1 1
No. Date: By: Description:
11111
4 4
| Sheets |
| A1 - SYMBOLS & ABBREVIATIONS |
| A2 - 3RD FLOOR DEMOLITION/REMODEL PLAN |
| A3 - 3RD FLOOR CEILING DEMOLITION/REMODEL PLAN |
| A4 - ELEVATIONS AND SECTIONS |
| A5 - DETAILS |
| E1 - SYMBOLS & ABBREVIATIONS, GENERAL NOTES |
| E2 - 3RD FLOOR ELECTRICAL DEMOLITION/REMODEL PLAN |
| E3 - 3RD FLOOR ELECTRICAL CEILING DEMO/REMODEL PLAN |
| M1 - SYMBOLS & ABBREVIATIONS, GENERAL NOTES |
| M2 - 3RD FLOOR MECHANICAL DEMOLITION/REMODEL PLAN |
| M3 - DETAILS & SCHEDULES |
| P1 - SYMBOLS & ABBREVIATIONS, GENERAL NOTES |
| P2 - 3RD FLOOR PLUMBING DEMOLITION/REMODEL PLAN |
File details come from the government source that posted it. Updated .