20-0048 Drawings.pdf

PDF 611 KB Posted

Attached to
RF SHIELDED CHAMBERS(UW-MAD)[20-0048]
Solicitation number
20-0048
Issued by
Dane County, Madison City, Wisconsin

About this file

This file is a comprehensive set of architectural, mechanical, plumbing, and electrical drawings for the University of Wisconsin-Madison's project to install three RF shielded chambers in Suite 326 and Corridor 300J of the Primate Center (Building 0526). The project encompasses demolition and remodeling of laboratory and support spaces on the third floor, including the installation of three radiofrequency shielded chambers (designated as rooms 326B, 326C, and 326D) along with associated modifications to room 326 (Lab), room 338, and corridor 300J. The scope of work includes complete room demolition, wall and partition construction, flooring installation with epoxy finishes and heat-welded vinyl, suspended ceiling systems with specified tile and grid specifications, door and hardware installation, and comprehensive updates to all building systems including HVAC, plumbing, and electrical infrastructure. The drawings are dated March 23, 2018, and include detailed specifications for materials, equipment manufacturers and models, equipment schedules, and coordination requirements among multiple trades.

The RF shielded chambers are specified as vendor-supplied and installed equipment with critical attention requirements regarding panel joint coordination, fastener installation, and preservation of conductive surfaces on door frames and thresholds. All new work incorporates specific material requirements including Phoenix OneSteP epoxy flooring in Grey Hound color, Corrim Company fiberglass reinforced polymer doors in Beige finish, Chicago Metallic suspended ceiling systems with Genesis tiles, and various mechanical, plumbing, and electrical components from specified manufacturers including Mott Manufacturing cabinets, Chicago Faucets fixtures, and Vibro-Acoustics sound attenuators. The project requires careful coordination between architectural, mechanical, electrical, and plumbing trades, with particular emphasis on acoustic sealing, RF chamber integrity, cable management through dedicated chases, and compliance with applicable building codes and standards. The University of Wisconsin-Madison directed inquiries to Brad Bauman in Purchasing Services at the specified contact information.

View the file

Other files

File Type Posted
20-0048 RFB.docx DOCX document
20-0048 RFB AMD 1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ARCHITECTURAL SYMBOLS & ABBREVIATIONS

E

EXISTING WALL TO REMAIN

WALL TO BE REMOVED

NEW WALL

EXISTING TO REMAIN

EXISTING TO BE RELOCATED

NEW TO BE INSTALLED

R

N

ROOM

100 ROOM TAG

1 REVISION TAG

KEY NOTE TAG

CALL OUT TAG

ELEVATION TAG

INTERIOR ELEVATION TAG

SECTION TAG

NORTH

NORTH ARROW

FLOOR PLAN VIEW

SCALE

PLAN/DETAIL/SECTION INDICATION

NOTES:

1. SYMBOLS INDICATED HERE AND NOT USED IN THE CONTRACT DOCUMENTS DO NOT APPLY

TO THIS PROJECT. ADDITIONAL SYMBOLS MAY BE INDICATED IN THE CONTRACT

DOCUMENTS.

2. NEW WORK IS SHOWN WITH SOLID HEAVY LINES.

3. EXISTING TO REMAIN IS SHOWN WITH LIGHT LINES.

4. DEMOLISHED WORK IS SHOWN WITH HEAVY DASHED LINES.

& AND

@ AT

Ø ROUND OR DIAMETER

A&E ARCHITECTURAL AND ENGINEERING

AB ANCHOR BOLT/ROD

ABV ABOVE

ACT/ATC ACOUSTIC CEILING TILE

ADA AMERICANS WITH DISABILITIES ACT

AV AUDIO VISUAL

CMU CONCRETE MASONRY UNIT

FF&E FURNITURE, FIXTURES & EQUIPMENT

GWB GYPSUM WALL BOARD

HAZ MAT HAZARDOUS MATERIAL

HM HOLLOW METAL

LVT LUXURY VINYL TILE

SC SOLID CORE

TYP TYPICAL

L ANGLE

LL DOUBLE ANGLE

RCP REFLECTED CEILING PLAN

DEMO DEMOLITION

NOM NOMINAL

VCT VINYL COMPOSITION TILE

R.O. ROUGH OPENING

T.O. TOP OF

FRP FIBERGLASS REINFORCED POYESTER

Scale

UW

Number

Date Issued

Set Type

REVISIONS:

Sh ee t T itle

Pr oje ct Tit le:

Drawn By:

Fa ci lit ie s P la nn in g an d

M an ag em en t

P hy si ca l P la nt

A rc hi te ct s/

E ng in ee rs

N

. M ills

S tre et , M ad is on , W

I 5

U ni ve rs ity o f W is co ns in -M ad is on

Bu ild ing N am e &

N um be r:

U W

B

LD

G

3/

/2

4:

:4

PM

1/4" = 1'-0"

A1

SY

M

B O

LS

A

BB

R

EV

IA

TI

O N

S

03/23/2018

0526 1602

BD

P R

IM

A

TE

C

E N

TE

R

MCLEAN

IN

ST

AL

L

TH

R

EE

R

F

SH

IE

LD

ED

C

H

AM

BE

R

S S

U

IT

E

A

N D

C O

R R

ID

O

R

J

No. Date: By: Description:

300J

CORRIDOR

Room

LAB

CLEAR - GYP BD PARTITIONS (TYP)

9' - 5"CLEAR

9' - 5"

CLEAR

9' - 5"

CL

EA

R

FR

OM

C

OL

UM

N

FA

CE

7'

- 1 0"

A5

A4

LAB

326B

RF CHAMBER

326C

RF CHAMBER

326D

RF CHAMBER

300J

CORRIDOR

5' - 11"

A4

A44

1/2

EX

TE

RI

OR

O F

CH

AM

BE

R

7'

- 9

FR

OM

C

OL

UM

N

FA

CE

1/2

A4

A5

(TYP)

1/2"

(TYP)

1/2"

EXTERIOR OF CHAMBER (TYP)

9' - 4"

3' - 3"

CL OF PANEL

4' - 9"

FA

C

E O

F G

W B

Room

Scale

UW

Number

Date Issued

Set Type

REVISIONS:

Sh ee t T itle

Pr oje ct Tit le:

Drawn By:

Fa ci lit ie s P la nn in g an d

M an ag em en t

P hy si ca l P la nt

A rc hi te ct s/

E ng in

. M ills

S tre et , M ad is on , W

I 5 ve rs ity o f W is co ns in -M ad ing N am e &

N um be r:

U W

B

LD

G

3/

/2

4:

:4

PM

1/4" = 1'-0"

A2

3R D

F

LO

O R

D E

M O

LI

TI

O N

/R E

M O

D E

L P

LA

N

03/23/2018

0526 1602

BD

P R

IM

A

TE

C

E N

TE

R

MCLEAN

IN

S

TA

LL

T H

R E

E R

F S

H

IE

LD

E

D C

H A

M B

E R

S S

U

IT

E

A

N D

C O

R R

ID

O

R

J

REMODEL KEY NOTES

1 PROVIDE AND INSTALL PHOENIX ONESTEP EPOXY FLOORING. FINISH TO BE

NON-SKID/SAFETY. COLOR TO BE GREY HOUND (PT-617).

2 VENDOR SUPPLIED AND INSTALLED MOTT MANUFACTURING DOVE GREY (601008)

METAL BASE CABINETS AND BLACK EPOXY COUNTER TOP WITH 4" BACKSPLASH

AND DARCON D45 EPOXY SINK.

3 PROVIDE AND INSTALL LAB FAUCET - CHICAGO FAUCETS 1100-HA8CP.

COORDINATE WITH PLUMBING.

4 PROVIDE AND INSTALL DECK MOUNTED GUARDIAN G5022 EYEWASH - COORDINATE

WITH PLUMBING.

5 PROVIDE AND INSTALL A 3'-4" X 7'-0" (NOM.) CORRIM COMPANY FRP DOOR INTO THE

EXISTING HOLLOW METAL FRAME. DOOR TO BE BEIGE (NG-74306) WITH A SMOOTH

FINISH. INSTALL A LEVER SET, DOOR CLOSER WITH HOLD OPEN FEATURE AND A

34" X 34" STAINLESS STEEL KICK PLATE ON THE PUSH SIDE. HARDWARE TO BE A

CLASSROOM FUNCTION WITH FINISH 626.

6 CONSTRUCT FULL HEIGHT PARTITION AS PER DETAIL 1/A5. PARTITIONS SHALL BE

ACOUSTICALLY SEALED AROUND PERIMETER.

7 PROVIDE AND INSTALL A 3'-0" X 7'-0" (NOM) CORRIM COMPANY FRP DOOR SET IN A

2" HOLLOW METAL FRAME 3'-0" X 7'-1". DOOR TO BE BEIGE (NG-74306) WITH A

SMOOTH FINISH. INSTALL A LEVER SET, ACOUSTICAL SEALS, SURFACE MOUNTED

AUTOSWEEP, AND A 34" X 34" STAINLESS STEEL KICK PLATE (ON THE PUSH SIDE).

HARDWARE TO BE A PASSAGE SET WITH FINISH 626. SEE DETAIL 2/A5 FOR

ADDITIONAL INFORMATION.

8 PROVIDE AND INSTALL A STAINLESS STEEL RAMP TO MEET ELEVATION OF RF

CHAMBER FLOOR. SEE DETAIL 2/A5.

9 PROVIDE AND INSTALL HEAT WELDED SHEET VINYL FLOORING WITHIN RF BOOTH -

SEE SPECS IN PROJECT FOLDER.

10 PAINT ALL WALLS, WINDOW FRAMES AND GLASS, WITH WHITE EPOXY PAINT.

11 PAINT WALLS WITH BLACK EPOXY PAINT.

12 PROVIDE AND INSTALL A WALL MOUNTED EXAM TABLE @ 42" A.F.F. TO TABLE TOP.

SEE SPECIFICATION IN PROJECT FOLDER.

13 OPEN BLOCK WALL TO ALLOW FOR ELECTRICAL BOX INSTALLATION. COORDINATE

WITH ELECTRICAL.

14 VENDOR SUPPLIED AND INSTALLED RF SHIELDED BOOTH. FASTENERS AT FLOOR

CLEATS TO HAVE ROUND HEADS. CHAMBER DOOR TO BE BLACK.

15 PASS-THRU WAVE GUIDE - Ø3" X 12" ALUMINUM TUBE WITH A PVC ELBOW AT EACH

END. MOUNT AT 6'-10" A.F.F. TO CENTERLINE OF TUBE. CENTER TUBE WITHIN WALL

ASSEMBLIES AND ACOUSTICALLY SEAL IN PLACE. FILL WITH DRY SAND ONCE

CABLES ARE IN PLACE.

16 COORDINATE PARTITION CONSTRUCTION WITH INTERFERENCE FROM MECHANICAL

DUCT AT THIS LOCATION.

DEMOLITION KEY NOTES

1 DEMO SINK FAUCETS - COORDINATE WITH PLUMBING.

2 DEMO COUNTER TOPS (SUSPECTED ACM) AND BASE CABINETS.

3 REMOVE WALL MOUNTED CABINETS AND RETURN CABINETS IN GOOD CONDITION

TO CARPENTER SHOP STOCK AND DEMO THE REST.

4 DEMO ENTIRE ROOM ENCLOSURE.

5 DEMO FLOOR TILE (SUSPECTED ACM).

6 REMOVE DOOR FROM FRAME AND DISCARD. PREP FRAME FOR NEW FRP DOOR.

7 FROM ALL ROOMS WITHIN THE 326 SUITE, REMOVE ANY REMAINING FURNITURE

AND CONSIGN TO BUILDING MANAGER.

RF CHAMBER NOTES - ATTENTION!

1 RF CHAMBER VENDOR TO COORDINATE PANEL JOINTS WITH ARCHITECTURAL,

MECHANICAL AND ELECTRICAL PENETRATIONS AS NOTED WITHIN THE

CONSTRUCTION DOCUMENTS.

2 DO NOT SPIN-OUT SCREWS WHEN TIGHTENING INTO THE GALVANIZED METAL

PANELS OF THE RF CHAMBER. IF A SCREW SPINS WILST DRAWING, REMOVE

SCREW AND REPLACE WITH THE NEXT LARGER SCREW DIAMETER.

3 DO NOT PAINT WIHTIN THE JAMBS AND HEAD OF THE RF CHAMBER DOOR FRAME.

JAMBS AND HEAD GASKETS MUST REMAIN CONDUCTIVE TO THE DOOR.

4 DO NOT PAINT THE RF CHAMBER DOOR THRESHOLD. THE THRESHOLD MUST

REMAIN CONDUCTIVE TO THE DOOR.

5 DO NOT PAINT THE EDGES OF THE RF CHAMBER DOOR. THE DOOR MUST REMAIN

CONDUCTIVE TO THE FRAME.

NORTH

NORTH

1/4" = 1'-0"

3RD FLOOR DEMO PLAN

1/4" = 1'-0"

3RD FLOOR REMODEL PLAN

9 9 9

No. Date: By: Description:

8 8

14 14

15 15 15 16

OS

H

H

OS JJ JJ JJ

OS

CLG

F

H OS

LAB

300J

CORRIDOR

300J

CORRIDOR

LAB

326C

RF CHAMBER

326D

RF CHAMBER

326B

RF CHAMBER

A.F.F.

CEILING

8' - 2"

A.F.F.

CEILING

7' - 4" A.F.F.

CEILING

7' - 4" A.F.F.

CEILING

7' - 4" Scale

UW

Number

Date Issued

Set Type

REVISIONS:

Sh ee t T itle

Pr oje ct Tit le:

Drawn By:

Fa ci lit ie s P la nn in g an d

M an ag em en t

P hy si ca l P la nt

A rc hi te ct s/

E ng in

. M ills

S tre et , M ad is on , W

I 5 ve rs ity o f W is co ns in -M ad ing N am e &

N um be r:

U W

B

LD

G

3/

/2

4:

:4

PM

1/4" = 1'-0"

A3

3R D

F

LO

O R

C

EI

LI

N

G D

E M

O

LI

TI

O

N /R

E M

O D

EL

P

LA

N

03/23/2018

0526 1602

BD

P R

IM

A

TE

C

E N

TE

R

MCLEAN

IN

S

TA

LL

T H

R E

E R

F S

H

IE

LD

E

D C

H A

M B

E R

S S

U

IT

E

A

N D

C O

R R

ID

O

R

J

DEMOLITION KEY NOTES

1 REMOVE ALL CEILILNG MOUNTED FRAMES ASSOCIATED WITH

THE UPPER CABINETS.

REMODEL KEY NOTES

1 PROVIDE AN INSTALL SUSPENDED CEILNG SYSTEM. TILES: 2X2

GENESIS SMOOTH PRO IN WHITE (74000). GRID: CHICAGO

METALLIC 200 SNAP GRID 15/16" EXPOSED (WHITE 01). INSTALL

HOLD DOWN CLIPS.

2 PROVIDE AN INSTALL SUSPENDED CEILNG SYSTEM. TILES: 2X2

GENESIS SMOOTH PRO IN BLACK (74007). GRID: CHICAGO

METALLIC 200 SNAP GRID 15/16" EXPOSED (BLACK 08). INSTALL

HOLD DOWN CLIPS.

RF CHAMBER NOTES - ATTENTION!

1 RF CHAMBER VENDOR TO COORDINATE PANEL JOINTS WITH ARCHITECTURAL,

MECHANICAL AND ELECTRICAL PENETRATIONS AS NOTED WITHIN THE

CONSTRUCTION DOCUMENTS.

2 DO NOT SPIN-OUT SCREWS WHEN TIGHTENING INTO THE GALVANIZED METAL

PANELS OF THE RF CHAMBER. IF A SCREW SPINS WILST DRAWING, REMOVE

SCREW AND REPLACE WITH THE NEXT LARGER SCREW DIAMETER.

3 DO NOT PAINT WIHTIN THE JAMBS AND HEAD OF THE RF CHAMBER DOOR FRAME.

JAMBS AND HEAD GASKETS MUST REMAIN CONDUCTIVE TO THE DOOR.

4 DO NOT PAINT THE RF CHAMBER DOOR THRESHOLD. THE THRESHOLD MUST

REMAIN CONDUCTIVE TO THE DOOR.

5 DO NOT PAINT THE EDGES OF THE RF CHAMBER DOOR. THE DOOR MUST REMAIN

CONDUCTIVE TO THE FRAME.

NORTH

NORTH

1/4" = 1'-0"

3RD FLOOR DEMO CEILING PLAN

1/4" = 1'-0"

3RD FLOOR REMODEL CEILING PLAN

2 2

DC LIGHTING

CONTROLLER (TYP)

RF LIGHTING FILTER (TYP)

RF POWER FILTER (TYP)

ACCES PANEL FOR PATCH PANEL (TYP)LIGHT SWITCH (TYP)

NOTE: PROVIDE FIRE RETARDANT BLOCKING FOR SURFACE MOUNTED ELECTRICAL EQUIPMENT.

FLEXTRAY (TYP)

PASS-THRU WAVE GUIDE (TYP)

BRUSH PLATE STYLE CABLE PASS-THRU (TYP)

TY

P

3'

- 1

1"

A5

A5

TYP

TYP

2'

- 1

0"

TYP

1" 3' - 0" 2' - 0" 2' - 6" 3' - 0" 1"

10' - 8"

EX

TE

RI

OR

O F

RF

C

HA

MB

ER

8'

- 3

3"

Scale

UW

Number

Date Issued

Set Type

REVISIONS:

Sh ee t T itle

Pr oje ct Tit le:

Drawn By:

Fa ci lit ie s P la nn in g an d

M an ag em en t

P hy si ca l P la nt

A rc hi te ct s/

E ng in

. M ills

S tre et , M ad is on , W

I 5 ve rs ity o f W is co ns in -M ad ing N am e &

N um be r:

U W

B

LD

G

3/

/2

4:

:1

PM

3/8" = 1'-0"

A4

EL

EV

AT

IO

N S

A N

D S

E C

TI

O

N S

03/23/2018

0526 1602

BD

P R

IM

A

TE

C

E N

TE

R

MCLEAN

IN

ST

AL

L

TH

R

EE

R

F

SH

IE

LD

ED

C

H

AM

BE

R

S S

U

IT

E

A

N D

C O

R R

ID

O

R

J

3/8" = 1'-0"1 LONGITUDINAL SECTION THROUGH SHIELDED CHAMBERS

No. Date: By: Description:

3/8" = 1'-0"2 ELEVATION LOOKING SOUTH

3/8" = 1'-0"4 ELEVATION LOOKING WEST

3/8" = 1'-0"3 TRANSVERSE SECTION

TOP OF CHAMBER

SUSPENDED CEILING

WITHIN CHAMBER

FACE OF COLUMN

SUSPENDED

CEILING IN LAB 326

SUSPENDED CEILING LAB 326

GYP. BOARD PARTITION

GYP. BOARD PARTITION

GYP. BOARD PARTITION EXHAUST DUCT

FACE OF BLOCK WALL

RF CHAMBER WALL

SUPPLY DUCT SOUND

ATTENUATOR (TYP)

RF CHAMBER LAB 326

EXHAUST DUCT (TYP)

MRI COMPATIBLE

CAN LIGHT (TYP)

LAY-IN LIGHT

EXHAUST DUCT

SOUND ATTENUATOR

SUPPLY DUCT

SUPPLY DUCT

PASS-THRU WAVE GUIDE

FLEXTRAY

EXHAUST DUCT SOUND

ATTENUATOR (TYP)

PATCH PANEL - BY

VENDOR

RF CHAMBERLAB 326

FINISHED FLOOR - HEAT-WELDED

SHEET VINYL. SEE REMODEL PLAN

KEY NOTES FOR MORE INFORMATION

RF CHAMBER FLOOR SYSTEM - BY VENDOR

RF CHAMBER WALL SYSTEM - BY VENDOR

1/2"

5/8" GYPSUM BOARD (BOTH SIDES)

3-5/8" STEEL STUDS WITH ROCKWOOL

SAFE AND SOUND INSULATION

EPOXY FLOOR WITH INTEGRAL COVE

BASE - SEE PROJECT SPECIFICATIONS 4"

AIR GAP BETWEEN GYPSUM BOARD

PARTITION AND RF CHAMBER WALL

RUBBER TRANSITION. SEE

SPECS IN PROJECT FOLDER.

1/2" AIR GAP BETWEEN GWB PARTITION AND

RF CHAMBER WALL

RF CHAMBER DOOR FRAME - BY VENDOR

RF CHAMBER THRESHOLD - BY VENDOR

HEAT WELDED SHEET VINYL FLOORING -

SEE PROJECT SPECIFICATIONS

RF CHAMBER FLOOR - BY VENDOR

SLOPE OF RAMP IS NOT TO

EXTEND BEYOND LAB SIDE OF

DOOR JAMB. SEAL AROUND 3-SIDES

OF RAMP BASE AT FLOOR

HOLLOW METAL DOOR FRAME

SET IN GWB PARTITON

DOOR AT GWB PARTITION

SWEEP

PROVIDE AND INSTALL NON-CONDUCTIVE

GASKETING AT FACE OF RAMP

FASTEN RAMP WITH (3)

COUNTERSUNK STAINLESS STEEL

SCREWS - FILL HOLES WITH SEALANT

1"

PROVIDE SEALANT AT GAP BETWEEN

RAMP AND RF CHAMBER THRESHOLD

GWB J-BEADRF CHAMBER

LAB 326

RF CHAMBER EQUIPMENT CABLE

PATCH PANEL - BY VENDOR

EDGE OF GWB SILL

AIR GAP

STEEL STUD AND GWB PARTITION

W/ACOUSTICAL BATT INSULATION

STEEL STUD - REFER TO ACCESS DOOR

MANUFACTURER'S INSTALLATION

DIRECTIONS TO SIZE R.O.

ACOUSTICAL ACCESS DOOR

ACCESS DOOR FRAME

RF CHAMBER WALL

STEEL STUD EQUIPMENT CABLE

CHASE - NO ACOUSTICAL BATT

INSULATION

EXTERIOR FACE OF RF

CHAMBER WALL

RF CHAMBER LAB 326

ACOUSTICAL ACCESS DOOR

ACCESS DOOR FRAME

GWB - REFER TO ACCESS DOOR

MANUFACTURER'S INSTALLATION

DIRECTIONS TO SIZE R.O.

STEEL STUD EQUIPMENT CABLE CHASE

- NO ACOUSTICAL BATT INSULATION

TOP TRACK

STEEL STUD PARTITION FRAMING

W/ACOUSTICAL BATT INSULATION

RF CHAMBER WALL

RF CHAMBER EQUIPMENT CABLE

PATCH PANEL - BY VENDOR

GWB J-BEAD

GWB L-BEAD

SUSPENDED CEILING TILE -

SEE REFLECTED CEILING

PLAN FOR HEIGHT

FLEXTRAY

3"

T.

O.

G W

B R.

O.

4"

ACOUSTICAL CEILING

TILE WITH IN CHAMBER

AIR GAP

3"

EDGE OF FINISHED

GWB JAMB

FINISHED GWB SILL

SUSPENDED

CEILING TRACK

SUSPENDED

CEILING TRACK

BRUSH STYLE PLATE CABLE PASS-THRU

Scale

UW

Number

Date Issued

Set Type

REVISIONS:

Sh ee t T itle

Pr oje ct Tit le:

Drawn By:

Fa ci lit ie s P la nn in g an d

M an ag em en t

P hy si ca l P la nt

A rc hi te ct s/

E ng in

. M ills

S tre et , M ad is on , W

I 5 ve rs ity o f W is co ns in -M ad ing N am e &

N um be r:

U W

B

LD

G

3/

/2

4:

:2

PM

3" = 1'-0"

A5

D E

TA

IL

S

03/23/2018

0526 1602

BD

P R

IM

A

TE

C

E N

TE

R

MCLEAN

IN

S

TA

LL

T H

R E

E R

F S

H

IE

LD

E

D C

H A

M B

E R

S S

U

IT

E

A

N D

C O

R R

ID

O

R

J

No. Date: By: Description:

3" = 1'-0"1 BASE OF CHAMBER WALL

3" = 1'-0"2 SECTION THROUGH DOOR THRESHOLD

3" = 1'-0"3 DATA CHASE HORIZONTAL SECTION

3" = 1'-0"4 DATA CHASE VERTICAL SECTION

ACOUSTICAL BATT INSULATION -

FROM HEADER FRAMING TO

BOTTOM OF STRUCTURAL DECK

HEADER FRAMING

D

F-CW

CSW

140°

140°

GV

GW

G

OV

OW

PD

V

SS

SHWR

SHWS

SD

OSD

(E)

DOMESTIC COLD WATER-FILTERED

DOMESTIC COLD SOFT WATER

DOMESTIC HOT WATER 140°

DOMESTIC HOT WATER-CIRCULATING

DOMESTIC HOT WATER-CIRCULATING 140°

GREASE VENT

GREASE WASTE

NATURAL GAS

OIL VENT

OIL WASTE

PUMP DISCHARGE

SANITARY VENT

SANITARY SEWER

SOLAR HOT WATER RETURN

SOLAR HOT WATER SUPPLY

STORM DRAINAGE

STORM DRAINAGE-OVERFLOW

EXISTING PIPE TAG

PIPING BEING DEMOLISHED

PG PROPANE GAS

UPRIGHT SPRINKLER HEAD

PENDENT SPRINKLER HEAD

RECESSED SPRINKLER

HEAD

CONCEALED SPRINKLER

HEAD

'D' REPRESENTS DRY SPRINKLER HEAD

SIDEWALL SPRINKLER HEAD

EXTENDED COVERAGE SIDEWALL SPRINKLER HEAD

OBSTRUCTION FROM

DUCTWORK 48" AND GREATER

48x18 SA

DIRECTION OF FLOW

GENERAL PLUMBING SYMBOLS

CWS

CWR CHILLED WATER RETURN

CHILLED WATER SUPPLY

AV

AW

ACID VENT

ACID WASTE

COND COOLING COIL CONDENSATE

PCWS PROCESS COOLING WATER SUPPLY

PCWR PROCESS COOLING WATER RETURN VENT

RWS DRAIN

RWS RECLAIM WATER SUPPLY

RWR RECLAIM WATER RETURN

CA COMPRESSED AIR

IA INSTRUMENT AIR

MW MAKEUP WATER

CLW CLEAR WATER WASTE

NP NON-POTABLE WATER

TW TEMPERED WATER

NP NON-POTABLE WATER

STM ROOF STORM DRAIN PIPE

LCW LAB COLD WATER

LHW LAB HOT WATER

LHWR LAB HOT WATER RETURN

LAB AIRA

LAB CARBON DIOXIDECO2

LAB REVERSE OSMOSISRO

LAB REVERSE OSMOSIS RETURNROR

LAB OXYGENO2

NITROGEN GASN2

HELIUM GASHe

4" RD-1

PLUG/CAP

4"

4"

DRAIN TAG

DRAIN SIZE

FLOOR DRAIN

FIXTURE

DRAIN SIZE

ROOF DRAIN FIXTURE

TYPE (SEE SCHEDULE)

DRAIN TAG

PLUMBING FIXTURE TAG

PLUMBING FIXTURE

PIPE RISE

PIPE DROP

PIPE TEE

REDUCING 45 DEGREE TEE

45 DEGREE TEE

6" FD-2

TYPE (SEE SCHEDULE)

X" V UP THRU FLOOR

4" ORD-1

HYD-2

TYPE (SEE SCHEDULE)

KEYNOTE

CONTINUATION SYMBOL

NUMBER OF SHEET WHERE DETAIL APPEARS

NUMBER OF DETAIL ON SHEET

REVISION NUMBER - SHOWN ON PLANS

ROOM NAME AND NUMBER

POINT WHERE NEW CONNECTS TO EXISTING

EXISTING TO REMAIN IS SHOWN WITH LIGHT LINES.

NEW WORK IS SHOWN WITH SOLID HEAVY LINES.

DEMOLISHED WORK IS SHOWN WITH HEAVY

DASHED LINES.

PLUMBING SYMBOLS

PLUMBING SYMBOLS (CONTINUED)

FIRE PROTECTION SYMBOLS

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GR GRADE

GW GREASE WASTE

HB HOSE BIB

HD HEAD

HORZ HORIZONTAL

HP HORSE POWER

HP HIGH PRESSURE

HW HOT WATER

HYD HYDRANT

ID INDIRCT

IN INCH

INL INLET

INSUL INSULATION

INT INTERIOR

INV INVERT

INWG INCHES WATER GAUGE

JST SPC JOIST SPACE

JT JOINT

LAB LABORATORY

LB POUND

LB/HR POUNDS PER HOUR

LF LINEAL FOOT

LOC LOCATION

LP LOW PRESSURE

LPG LIQUEFIED PETROLEUM GAS

LR LIQUID REFRIGERANT

LS LAWN SPRINKLER

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

MAN MANUAL

MATL MATERIAL

MAV MANUAL AIR VENT

MAX MAXIMUM

MBH ONE THOUSAND BTU PER HOUR

MCF ONE THOUSAND CUBIC FEET

MCW MAKE-UP COLD WATER

MD MOTORIZED DAMPER

MECH MECHANICAL

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MTR MOTOR

N NECK

NC NOISE CRITERIA

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NUMBER

NO NORMALLY OPEN

NOM NOMINAL

NTS NOT TO SCALE

O OXYGEN

OC ON CENTER

OF OVERFLOW

OPNG OPENING

ORD OVERFLOW ROOF DRAIN

PD PRESSURE DROP

PIV POST INDICATOR VALVE

PLBG PLUMBING

PR PAIR

PRELIM PRELIMINARY

PRESS PRESSURE

PRIM PRIMARY

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

PW POTABLE WATER

PWR POWER

RD ROOF DRAIN

REC RECESSED

RED REDUCER

REQD REQUIRED

REV REVERSE

RLA RELIEF AIR

RM ROOM

RPM REVOLUTIONS PER MINUTE

RW RAIN WATER

SF SQUARE FOOT

SAN SANITARY

SCHED SCHEDULE

SECT SECTION

SF SQUARE FOOT

SQ SQUARE

SSD SOIL SUBDRAIN

SS STAINLESS STEEL

STD STANDARD

STRUCT STRUCTURAL

SUCT SUCTION

SUSP SUSPENDED

T THERMOSTAT

TDR TRENCH DRAIN

TEFC TOTALLY ENCLOSED FAN COOLED

TEMP TEMPERATURE

TYP TYPICAL

UG UNDERGROUND

VAC VACUUM

V VENT

VAV VARIABLE AIR VOLUME

VEL VELOCITY

VERT VERTICAL

VOL VOLUME

VTR VENT THROUGH ROOF

W WASTE

WCO WALL CLEAN OUT

WH WALL HYDRANT

AS AIR SEPARATOR

B BOILER

CF CHEMICAL FEEDER

CFP CHEMICAL FEEDER PUMP

CWP CONDENSER WATER PUMP

DB DOMESTIC WATER BOOSTER PUMP

DCP DOMESTIC WATER CIRCULATING PUMP

ET EXPANSION TANK

EWH ELECTRIC WATER HEATER

FP FIRE PUMP

GI GREASE INTERCEPTOR

HX HEAT EXCHANGE

SA SHOCK ABSORBER

SEP SEWAGE EJECTOR PUMP

SP SUMP PUMP

WFMS WATER FLOW MEASURING STATION

WH WATER HEATER

PIPE DROP OFF BOTTOM OF PIPE

PIPE RISE OFF TOP OF PIPE

CLEAN OUT

ABBREVIATIONS (CONTINUED)

& AND

A AIR

ABV ABOVE

ACOUS ACOUSTICAL

AD AREA DRAIN

ADD ADDENDUM

ADDL ADDITIONAL

AFF ABOVE FINISHED FLOOR

AFUE ANNUAL FUEL UTILIZATION EFFICIENCY

AG ABOVE GROUND

ALT ALTERNATE

AP ACCESS PANEL

APPROX APPROXIMATE

ARCH ARCHITECT/ARCHITECTURAL

AV ACID VENT

AW ACID WASTE

AUTO AUTOMATIC

BLDG BUILDING

BLW BELOW

BM BEAM

BO BY OTHER

BOT BOTTOM

BSMT BASEMENT

BTW BETWEEN

CAP CAPACITY

CB CATCH BASIN

CB CATCH BASIN

CCW COUNTER CLOCKWISE

CFCV CONSTANT FLOW CONTROL VALVE

CFM CUBIC FEET PER MINUTE

CHW CIRCULATING HOT WATER

CI CAST IRON

CLG CEILING

CO CLEAN OUT

COL COLUMN

COMB COMBINATION

CONC CONCRETE

CONF CONFERENCE

CONN CONNECT

CONST CONSTRUCTION

CONT CONTINUE/CONTINUATION

CONTR CONTRACT/CONTRACTOR

COORD COORDINATE

CTR CENTER

CUFT CUBIC FEET

CV CHECK VALVE

ABBREVIATIONS

CW COLD WATER

CW CLOCKWISE

D DEGREE

DET DETAIL

DIA DIAMETER

DIAG DIAGONAL

DISCH DISCHARGE

DIV DIVISION

DI DEIONIZED WATER

DMPR DAMPER

DN DOWN

DWG DRAWING

DW DISTILLED WATER

EA EACH

EL ELBOW

ELEC ELECTRICAL

ELEV ELEVATION

EP EXPLOSION PROOF

EQ EQUAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXP EXPANSION

EXPJT EXPANSION JOINT

EXT EXTERIOR

F DEGREES FAHRENHEIT

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FDV FIRE DEPARTMENT VALVE

FHC FIRE HOSE CABINET

FL FLOOR

FLEX FLEXIBLE

FLG FLANGE

FPM FEET PER MINUTE

FRP FIBERGLASS REINFORCED PIPE

FS FULL SIZE

FS FLOOR SINK

FT FOOT/FEET

FTG FOOTING

FUT FUTURE

GA GAGE/GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GENL GENERAL

EQUIPMENT ABBREVIATIONS

GENERAL NOTES

CW DOMESTIC COLD WATER

DOMESTIC HOT WATER

DOMESTIC WATER METER

FLOW MEASURING AND

BALANCING DEVICE

BALL VALVE

CHECK VALVE

THREE WAY VALVE

BUTTERFLY VALVE

MOTORIZED CONTROL

VALVE

PRESSURE REDUCING

VALVE

SOLENOID VALVE

PNEUMATIC

ELECTRIC

THREE WAY MOTORIZED

CONTROL VALVE

FP-DOM-W

FP-D FIRE PROTECTION DRY

COMBINATION FIRE & DOMESTIC

FP-O FIRE PROTECTION OTHER

FP-PA FIRE PROTECTION PRE-ACTION

FP-W FIRE PROTECTION WET

2"

* NOTE *

ALL OF GENERAL NOTES ON THIS

SHEET ARE TO BE APPLIED TO ALL

OTHER MECHANICAL DRAWINGS IN

THIS SET. SYMBOLS INDICATED HERE

AND NOT USED IN THE CONTRACT

DOCUMENTS DO NOT APPLY

TO THIS PROJECT. ADDITIONAL

SYMBOLS MAY BE INDICATED IN THE

CONTRACT DOCUMENTS.

Room

Scale

UW

Number

Date Issued

Set Type

REVISIONS:

Sh ee t T itle

Pr oje ct Tit le:

Drawn By:

Fa ci lit ie s P la nn in g an d

M an ag em en t

P hy si ca l P la nt

A rc hi te ct s/

E ng in

. M ills

S tre et , M ad is on , W

I 5 ve rs ity o f W is co ns in -M ad ing N am e &

N um be r:

U W

B

LD

G

3/

/2

4:

:3

PM

1/8" = 1'-0"

P1

SY

M

B O

LS

A

BB

R

EV

IA

TI

O N

S, G

E N

ER

AL

N O

TE

S

03/23/2018

0526 1602

BD

P R

IM

A

TE

C

E N

TE

R

KRAUS

IN

S

TA

LL

T H

R E

E R

F S

H

IE

LD

E

D C

H A

M B

E R

S S

U

IT

E

A

N D

C O

R R

ID

O

R

J

1 BOLDER TEXT AND GRAPHICS

INDICATE NEW WORK. ALL OTHER

TEXT AND GRAPHICS ARE EXISTING

INFORMATION SHOWN FOR

REFERENCE.

2 INSULATORS SHALL REPAIR OR

REPLACE ALL INCIDENTALLY FOUND

DAMAGED PIPE AND DUCT

INSULATION AND JACKETS IN

PROJECT AREA PER DSF MASTER

SPECIFICATIONS AS NEEDED VIA

MAINTENANCE WORK ORDER.

INSULATION AND JACKETS

DAMAGED DURING OR AS A RESULT

OF PROJECT WORK SHALL BE

REPAIRED OR REPLACED UNDER

PROJECT WORK ORDER.

3 PLUMBING SHOP SHALL CHECK

OPERATION OF ALL VALVES

ASSOCIATED WITH PROJECT.

REPAIR OR REPLACE DAMAGED

VALVES AS NEEDED VIA

MAINTENANCE WORK ORDER.

4 PLUMBING SHOP TO VERIFY ALL

PLUMBING FIXTURES INCLUDING

DRAINS IN PROJECT AREA ARE

FUNCTIONING PROPERLY. REPAIR,

CLEAN OR REPLACE AS REQUIRED

UNDER MAINTENANCE WORK

ORDER.

5 LABEL ALL PIPING, NEW AND

EXISTING, PER DSF MASTER

SPECIFICATIONS.

6 THOROUGHLY CLEAN ITEMS

BEFORE INSTALLATION. CAP PIPE

OPENINGS TO DEFLECT DEBRIS

UNTIL FIXTURES ARE INSTALLED

AND FINAL CONNECTIONS HAVE

BEEN MADE.

7 PROVIDE AND INSTALL PIPING

EQUIPMENT AND MATERIALS IN

ACCORDANCE WITH APPLICABLE

PLUMBING CODE REGULATIONS

AND STANDARDS, AUTHORITIES

HAVING JURISDICTION, AND AS

OTHERWISE RECOMMENDED OR

DIRECTED BY MANUFACTURERS.

3" 3"

3/4"

3/4" CW

3/4" CW

3/4"

3/4" G

2 1/2"

3" SS 3" SS

/2

/2

/2

AIR

GAS

SAN

300J

CORRIDOR

LAB

Room

ROOM

326C ROOM

326D

2" V

3" SS

3" 3"

3/4"

3/4" CW

3/4" CW

3/4"

3/4" G

2 1/2"

Scale

UW

Number

Date Issued

Set Type

REVISIONS:

Sh ee t T itle

Pr oje ct Tit le:

Drawn By:

Fa ci lit ie s P la nn in g an d

M an ag em en t

P hy si ca l P la nt

A rc hi te ct s/

E ng in

. M ills

S tre et , M ad is on , W

I 5 ve rs ity o f W is co ns in -M ad ing N am e &

N um be r:

U W

B

LD

G

3/

/2

4:

:1

PM

1/4" = 1'-0"

P2

3R D

F

LO

O R

P

LU

M B

IN

G

D E

M O

LI

TI

O N

/R E

M O

D E

L P

LA

N

03/23/2018

0526 1602

BD

P R

IM

A

TE

C

E N

TE

R

KRAUS

IN

S

TA

LL

T H

R E

E R

F S

H

IE

LD

E

D C

H A

M B

E R

S S

U

IT

E

A

N D

C O

R R

ID

O

R

J

REMODEL KEY NOTES

1 NEW SINK & FAUCET WITH DECK MOUNTED PULLOUT

EMERGENCY EYEWASH. SEE ARCHITECTURAL DRAWINGS

FOR MANUFACTURER & MODELS. CONNECT HOT WATER,

COLD WATER, WASTE & VENT FROM EXISTING SERVICES.

2 EXISTING PIPING SERVING FLOOR ABOVE SHALL REMAIN

UNLESS NOTED OTHERWISE.

3 CAP PIPING AT WALL OR AT MAIN IN CORRIDOR.

4 INSTALL NEW 3" CAST IRON WASTE PIPING WITH P-TRAP AND

CONNECT TO EXISTING 3" LATERAL MAIN. BOTTOM OF P-TRAP

SHALL BE LOCATED 9'-0" AFF MINIMUM.

5 PROVIDE AND INSTALL NEW 3" CAST IRON P-TRAP WITHOUT

CLEANOUT PLUG.

DEMOLITION KEY NOTES

1 DEMOLISH EXISTING SINK & FAUCET. REMOVE PIPING BACK

TO SUITABLE LOCATION AND CAP. REFER TO REMODEL PLAN

ON THIS SHEET FOR NEW WORK.

2 REMOVE CARBON TANK AND DIONIZER TANK LOCATED IN SINK

CABINET.

3 DEMOLISH PLUMBING SERVICES (GAS & AIR) ON ALL LAB

BENCHES. REMOVE PIPING BACK TO SUITABLE LOCATION &

CAP.

4 FUME HOOD BEING REMOVED. DISCONNECT PLUMBING

SERVICES TO HOOD, REMOVE PIPING BACK TO SUITABLE

LOCATION & CAP.

5 DEMOLISH MISCELLANEOUS UNNECESSARY PLUMBING PIPING

BACK TO SUITABLE LOCATION & CAP.

6 PIPING SERVING FLOOR ABOVE SHALL REMAIN UNLESS

NOTED OTHERWISE.

7 DEMOLISH 3" P-TRAP AND ASSOCIATED PIPING AS REQUIRED

TO ALLOW REPLACEMENT AT A HIGHER ELEVATION. SEE

REMODEL PLAN ON THIS SHEET.

8 DEMOLISH EXISTING P-TRAP WITH CLEANOUT PLUG FOR

REPLACEMENT, LATERAL AND VERTICAL PIPING TO REMAIN.

SEE REMODEL PLAN ON THIS SHEET.

NORTH

NORTH

1/4" = 1'-0"

3RD FLOOR PLUMBING DEMO PLAN

1/4" = 1'-0"

3RD FLOOR PLUMBING REMODEL PLAN

No. Date: By: Description:

4 5

(TYP.)8

7 7 7 7

4 4 4 4

(TYP.)

(TYP.)

CO2

CO

H

HS

NO2

O2

TH

TS

T X

SW

S

CWS

CWV

CA

CD

CDR

CTR

CTS

HWR

HWS

STM

16x8

16x8Ø

F

S

M

B

D

C

16Ø

OA

TA

RLA

CWR CHILLED WATER RETURN

CHILLED WATER SUPPLY

COMBINATION WASTE & VENT

COMPRESSED AIR

CONDENSATE DRAINAGE

CONDENSATE RETURN

COOLING TOWER WATER RETURN

COOLING TOWER WATER SUPPLY

HEATING WATER RETURN

HEATING WATER SUPPLY

STEAM

OUTSIDE AIR

RELIEF AIR

TRANSFER AIR

REF-L

REF-S

REFRIGERANT-LIQUID

REFRIGERANT-SUCTION

2"

4" RD-1

CAP

4"

4"

REF-HG REFRIGERANT-HOT GAS

HVAC SYMBOLS (CONTINUED)

GRILLES, REGISTERS, AND

DIFFUSERS TAG

CFM

INLET/OUTLET SIZE

KEYNOTE

CONTINUATION SYMBOL

OVAL DUCT SIZE TAG

(WIDTH / HEIGHT)

SQUARE DUCT SIZE

TAG (WIDTH x HEIGHT)

NUMBER OF SHEET WHERE DETAIL APPEARS

NUMBER OF DETAIL ON SHEET

REVISION NUMBER - SHOWN ON PLANS

GENERAL MECHANICAL SYMBOLS

ROOM NAME AND NUMBER

POINT WHERE NEW CONNECTS TO EXISTING

TYPE (SEE SCHEDULE)

& AND

Ø ROUND

ABV ABOVE

AC AIR CONDITIONING

ACC AIR COOLED CONDENSER

ACCU AIR COOLING CONDENSING UNIT

ACOUS ACOUSTICAL

ADD ADDENDUM

AFF ABOVE FINISHED FLOOR

AFUE ANNUAL FUEL UTILIZATION EFFICIENCY

AFMS AIR FLOW MEASURING STATION

AG ABOVE GROUND

AHU AIR HANDLING UNIT

ALT ALTERNATE

ALUM ALUMINUM

AP ACCESS PANEL

APPROX APPROXIMATE

ARCH ARCHITECT/ARCHITECTURAL

AS AIR SEPARATOR

ATU AIR TERMINAL UNIT

AUTO AUTOMATIC

B BOILER

BLDG BUILDING

BLW BELOW

BO BY OTHER

BOT BOTTOM

BTU BRITISH THERMAL UNITS

BTUH BRITISH THERMAL UNITS PER HOUR

CAP CAPACITY

CF CABINET FAN

CF CHEMICAL FEEDER

CFCV CONSTANT FLOW CONTROL VALVE

CFM CUBIC FEET PER MINUTE

CFP CHEMICAL FEEDER PUMP

CH CHILLER

CHWP CHILLED WATER PUMP

CLG CEILING

CLG COOLING

COL COLUMN

COMB COMBINATION

CONC CONCRETE

COND CONDENSATE

CONF CONFERENCE

CONN CONNECT

CONST CONSTRUCTION

CONT CONTINUE/CONTINUATION

CONTR CONTRACT/CONTRACTOR

COORD COORDINATE

CRU CONDENSATE RETURN UNIT

CT COOLING TOWER

CTR CENTER

CUH CABINET UNIT HEATER

CUFT CUBIC FEET

CSTV CONSTANT VALVE

CTRLV CONTROL VALVE

CV CHECK VALVE

CW CLOCKWISE

CWP CONDENSER WATER PUMP

D DEGREE

DB DRY BULB

DC DUCT MOUNTED COIL

DET DETAIL

DIA DIAMETER

DIAG DIAGONAL

DISCH DISCHARGE

DIV DIVISION

DMPR DAMPER

DN DOWN

EAT ENTERING AIR TEMPERATURE

EDC ELECTRIC DUCT COIL

EF EXHAUST FAN

EL ELBOW

ELEC ELECTRICAL

ELEV ELEVATION

EP EXPLOSION PROOF

EQ EQUAL

EQUIP EQUIPMENT

ET EXPANSION TANK

EWT ENTERING WATER TEMPERATURE

EA EXHAUST AIR

EAH EXHAUST HOOD

EXIST EXISTING

EXP EXPANSION

EXPJT EXPANSION JOINT

EXT EXTERIOR

F DEGREES FAHRENHEIT

FCU FAN COIL UNIT

FD FIRE DAMPER

FLEX FLEXIBLE

FLG FLANGE

FO FUEL OIL

FOV FUEL OIL VENT

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FPM FEET PER MINUTE

FS FLOOR SINK

FT FOOT/FEET

FTR FIN TUBE RADIATION

FUT FUTURE

GA GAGE/GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GENL GENERAL

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GR GRADE

GRV GRAVITY ROOF VENTILATOR

H HUMIDIFIER

HB HOSE BIB

HORZ HORIZONTAL

HP HORSE POWER

HP HIH PRESSURE

HPU HEAT PUMP UNIT

HRU HEAT RECOVERY UNIT

HTG HEATING

HTR HEATER

HWP HEATING WATER PUMP

HX HEAT EXCHANGER

ID INDIRECT

ILC INLINE CENTRIFUGAL

IN INCH

INL INLET

INSUL INSULATION

INT INTERIOR

INWG INCHES WATER GAUGE

JST SPC JOIST SPACE

JT JOINT

LAB LABORATORY

LB POUND

LB/HR POUNDS PER HOUR

LAT LEAVING AIR TEMPERATURE

LF LINEAL FOOT

LOC LOCATION

LP LOW PRESSURE

LPG LIQUEFIED PETROLEUM GAS

LR LIQUID REFRIGERANT

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

MA MIXED AIR

MAN MANUAL

MATL MATERIAL

MAV MANUAL AIR VENT

MAX MAXIMUM

MBD MOTORIZED BYPASS DAMPER

MBH ONE THOUSAND BTU PER HOUR

MCF ONE THOUSAND CUBIC FEET

MCW MAKE-UP COLD WATER

MD MOTORIZED DAMPER

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MTR MOTOR

MUA MAKE-UP/AIR

N NECK

NC NOISE CRITERIA

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NOM NOMINAL

NTS NOT TO SCALE

OA OUTSIDE AIR

OC ON CENTER

OF OVERFLOW

PD PRESSURE DROP

PF PROPELLER FAN

PIV POST INDICATOR VALVE

PLBG PLUMBING

PNEU PNEUMATIC

PRELIM PRELIMINARY

PRESS PRESSURE

PRIM PRIMARY

PRV PRESSURE REDUCING VALVE

PRV POWER ROOF VENTILATOR

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

PWR POWER

R DUCT RISER

RA RETURN AIR

RC REHEAT COIL

RCP RADIANT CEILING PANEL

RE RETURN/EXHAUST FAN

REC RECESSED

RED REDUCER

REFR REFRIGERATION

RH RELATIVE HUMIDITY

REQD REQUIRED

REV REVERSE

RLA RELIEF AIR

RM ROOM

RPM REVOLUTIONS PER MINUTE

RTU ROOFTOP UNIT

SF SQUARE FOOT

SA SUPPLY AIR

SAT SOUND ATTENUATOR

SF SQUARE FOOT

SF SUPPLY FAN

SD SMOKE DAMPER

SLV SLEEVE

SM SURFACE MOUNT

SP STATIC PRESSURE

SPEC SPECIFICATION

SPS STATIC PRESSURE STATION

SQ SQUARE

SR SUCTION REFRIGERANT

SS STAINLESS STEEL

STD STANDARD

STM STEAM

STRUCT STRUCTURAL

SUSP SUSPENDED

T THERMOSTAT

TCP TEMPERATURE CONTROL PANEL

TD TEMPERATURE DROP

TEFC TOTALLY ENCLOSED FAN COOLED

ABBREVIATIONS

FIRE DAMPER

SMOKE DAMPER

MOTORIZED DAMPER

MANUAL BALANCING

DAMPER

BACKDRAFT DAMPER

COMBINATION

FIRE/SMOKE DAMPER

SUPPLY OUTLET RETURN/EXHAUST INLET

RECTANGULAR SUPPLY AIR DUCT RISE

RECTANGULAR RETURN AIR DUCT RISE

MECHANICAL EQUIPMENT

ROUND DUCT SIZE

TAG (DIAMETER)

DOMESTIC WATER METER

FLOW MEASURING AND

BALANCING DEVICE

BALL VALVE

CHECK VALVE

EXISTING TO REMAIN IS SHOWN WITH LIGHT

LINES.

NEW WORK IS SHOWN WITH SOLID HEAVY LINES.

DUCT BEING

DEMOLISHED

PIPING BEING DEMOLISHED

THREE WAY VALVE

BUTTERFLY VALVE

TYPE (SEE SCHEDULE)

ROUND SUPPLY AIR DUCT RISE

ROUND RETURN AIR DUCT RISE

ABOVE GROUND PIPING

PIPE SIZE TAG (DIAMETER)

DROP

DROP

DROP

DROP

DRAIN TAG

DRAIN SIZE

FLOOR DRAIN FIXTURE

DRAIN SIZE

ROOF DRAIN FIXTURE

TYPE (SEE SCHEDULE)

DRAIN TAG

PLUMBING FIXTURE TAG

PLUMBING FIXTURE

PIPE RISE

PIPE DROP

PIPE TEE

REDUCING 45 DEGREE TEE

45 DEGREE TEE

BELOW GROUND PIPING

PIPE INVERT ELEVATION TAG

PIPE SLOPE TAG

GEA GREASE EXHAUST AIR

* NOTE *

ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE

APPLIED TO ALL OTHER MECHANICAL DRAWINGS IN THIS

SET. SYMBOLS INDICATED HERE AND NOT USED IN THE

CONTRACT DOCUMENTS DO NOT APPLY

TO THIS PROJECT. ADDITIONAL SYMBOLS MAY BE

INDICATED IN THE CONTRACT DOCUMENTS.

SEA SMOKE EXHAUST AIR

6" FD-2

TYPE (SEE SCHEDULE)

X" V UP THRU FLOOR

4" ORD-1

HYD-2

TYPE (SEE SCHEDULE)

MOTORIZED CONTROL

VALVE

PRESSURE REDUCING

VALVE

SOLENOID VALVE

THREE WAY MOTORIZED

CONTROL VALVE

DEMOLISHED WORK IS SHOWN WITH HEAVY

DASHED LINES.

DIRECTION OF FLOW

CARBON DIOXIDE

SENSOR

CARBON MONOXIDE

SENSOR

HUMIDISTAT

HUMIDITY SENSOR

NITROGEN DIOXIDE

SENSOR

OXYGEN SENSOR

TEMPERATURE &

HUMIDITY SENSOR

MECHANICAL PIPING SYMBOLS

TEMPERATURE

SENSOR

MANUAL SWITCH

SENSOR

THERMOSTAT

ABBREVIATIONS (CONTINUED)

TRANSFER AIR FLOW

ARROW

RECTANGULAR DUCT

TAKE-OFF

ROUND DUCT

TAKE-OFF

ROUND DUCT TAKE-

OFF FROM

RECTANGULAR

MAIN

RECTANGULAR DUCT

TAKE-OFF FROM

ROUND MAIN

DUCT TRANSITION -

CONCENTRIC

DUCT TRANSITION -

ECCENTRIC

RADIUS ELBOW

MITERED ELBOW

DUCT REHEAT COIL

SUPPLY AIR FLOW

ARROW

FLEX DUCT

PIPE DROP OFF BOTTOM OF PIPE

TEMP TEMPERATURE

TYP TYPICAL

UG UNDERGROUND

UH UNIT HEATER

US UTILITY SET

UV UNIT VENTILATOR

V VENT

VAV VARIABLE AIR VOLUME

VEL VELOCITY

VENT VENTILATION

VERT VERTICAL

VOL VOLUME

WB WET BULB

WFMS WATER FLOW MEASURING STATION

GENERAL NOTES

HVAC SYMBOLS

P = PNEUMATIC

E = ELECTRIC

PIPE RISE OFF TOP OF PIPE

CD-3

XX-XXX

6-48-2

XXX

NECK SIZE

SLOT LENGTH

NUMBER OF SLOTS

CFM

TYPE (SEE SCHEDULE)

LINEAR DIFFUSER

SA SUPPLY AIR

RA RETURN AIR

EA EXHAUST AIR

5/32" / 12" SLOPE

INV. ELEV:-71' - 1"

ELECTRIC

PNEUMATIC

PLUG

Room

Scale

UW

Number

Date Issued

Set Type

REVISIONS:

Sh ee t T itle

Pr oje ct Tit le:

Drawn By:

Fa ci lit ie s P la nn in g an d

M an ag em en t

P hy si ca l P la nt

A rc hi te ct s/

E ng in

. M ills

S tre et , M ad is on , W

I 5 ve rs ity o f W is co ns in -M ad ing N am e &

N um be r:

U W

B

LD

G

3/

/2

4:

:2

PM

1/8" = 1'-0"

M1

SY

M

B O

LS

A

BB

R

EV

IA

TI

O N

S, G

E N

ER

AL

N O

TE

S

03/23/2018

0526 1602

BD

P R

IM

A

TE

C

E N

TE

R

Author

IN

ST

AL

L

TH

R

EE

R

F

SH

IE

LD

ED

C

H

AM

B

ER

S S

U

IT

E

A

N D

C O

R R

ID

O

R

J

1 BOLDER TEXT AND GRAPHICS INDICATES NEW WORK. ALL

OTHER TEXT AND GRAPHICS IS EXISTING INFORMATION

SHOWN FOR REFERENCE.

2 NEW DUCTWORK SHALL BE INSTALLED PER SMACNA AND ALL

STATE CODES. DUCTWORK SHALL BE SEALED AT ALL JOINTS,

TRANSVERSE AND LONGITUDINAL SEAMS AND CONNECTIONS

IN DUCTWORK. THE REFERENCED DUCTWORK INCLUDES ALL

SUPPLY, EXHAUST, AND RETURN DUCTS. CONCEALED

SUPPLY AIR DUCTWORK SHALL BE INSULATED WITH FLEXIBLE

FIBERGLASS (MIN. 5.0 R). EXPOSED SUPPLY AIR DUCTWORK,

OUTSIDE OF THE ROOM IT SERVES SHALL BE INSULATED WITH

RIGID FIBERGLASS (MIN. 5.0 R) OR SHALL BE DOUBLE-WALL

DUCT WITH MINIMUM 5.0 R INSULATION. EXPOSED SUPPLY

AIR DUCTWORK DOWNSTREAM OF THE REHEAT COIL AND

WITHIN THE ROOM IT SERVES DOES NOT REQUIRE

INSULATION

3 THE MAXIMUM LENGTH FOR EACH SECTION OF FLEXIBLE

DUCT SHALL BE 5'-0". ALL BENDS IN FLEXIBLE DUCT SHALL

HAVE A MINIMUM RADIUS OF 1.5 DUCT DIAMETERS TO DUCT

CENTERLINE.

4 LABEL ALL PIPING NEW AND EXISTING PER DSF MASTER

SPECIFICATIONS.

5 STEAMFITTERS SHALL RECALIBRATE OR REPLACE EXISTING

THERMOSTATS AS APPROPRIATE.

6 BALANCE HVAC AIR AND FLUID SYSTEMS TO QUANTITIES

SHOWN ON PLANS AND/OR SCHEDULES. SEND BALANCE

REPORTS TO ENGINEER AND MAKE AVAILABLE TO THE

DEPARTMENT OF SAFETY & BUILDINGS UPON REQUEST.

7 MAINTENANCE MECHANIC SHALL CLEAN ALL SUPPLY,

RETURN, EXHAUST, TRANSFER AND DOOR GRILLES AS

NEEDED VIA MAINTENANCE WORK ORDER.

8 INSULATION & JACKETS DAMAGED DURING OR AS A RESULT

OF PROJECT WORK SHALL BE REPAIRED OR REPLACED

UNDER PROJECT WORK ORDER.

9 MAINTENANCE MECHANIC TO CLEAN ALL EXISTING COILS AS

NEEDED VIA MAINTENANCE WORK ORDER. SHEETMETAL TO

INSTALL ACCESS DOORS WHERE REQUIRED ON ALL EXISTING

COILS VIA MAINTENANCE WORK ORDER.

10 STEAMFITTERS TO CHECK OPERATION OF CONTROLS

ASSOCIATED WITH REMODEL, UNDER PROJECT WORK ORDER.

T P

TP H T P

TH TH TH

TH

26x20 24x20

14x8

12x8

12x6

12x7

18x8

42x9 42x9 x7 x7

30x14

24x8

52x18 x1

34x18 x1

34x14 x8

26x12

26x12 x8

1 1/2"

3/4"

1 1/2"

3/4"

2"

1 1/4"

3/4"

2"

3/4" 1" 3/4"

2"

3/4"

3/4"

1 1/4"

ROOM

326C

ROOM

326D

CORRIDOR

300J

LAB

Room

26x20 24x20 SA

14x8

12x8

12x6 18x8

42x9 42x9

12x7

30x14 52x18

34x18

34x18

18x14

12x8

1 1/2"

3/4"

1 1/2"

3/4"

2" 1 1/4"

3/4"

2"

3/4" 1" 3/4"

2"

3/4"

3/4"

1 1/4"

34x22 SA 24x12 22x12 22x8

26x18 EA

Ø

Ø x8 x8 x8

8Ø 8Ø 8Ø

10Ø

10Ø x8

10Ø

8Ø 8Ø 8Ø x7 x612 x7

EG-1

22x22

26x12

26x12

CD-66

CD-66

CD-66

CD-9

CD-9

CD-9

EG-1

22x22

EG-1

22x22

1/2"

EG-1

22x22

EG-1

22x22

RC-

RC- RC-300J-1

RC-

D S

A -1

D S

A -1

DSA-1D

S

A -2

D S

A -2

D S

A -2

300J

CORRIDOR

LAB

Room

326C

RF CHAMBER

326D

RF CHAMBER

326B

RF CHAMBER

M3

M3

Scale

UW

Number

Date Issued

Set Type

REVISIONS:

Sh ee t T itle

Pr oje ct Tit le:

Drawn By:

Fa ci lit ie s P la nn in g an d

M an ag em en t

P hy si ca l P la nt

A rc hi te ct s/

E ng in

. M ills

S tre et , M ad is on , W

I 5 ve rs ity o f W is co ns in -M ad ing N am e &

N um be r:

U W

B

LD

G

3/

/2

4:

:3

PM

1/4" = 1'-0"

M2

3R D

F

LO

O R

M E

C H

A N

IC

A

L D

E M

O

LI

TI

O

N /R

E M

O D

E L

P

LA

N

03/23/2018

0526 1602

BD

P R

IM

A

TE

C

E N

TE

R

KRAUS

IN

S

TA

LL

T H

R E

E R

F S

H

IE

LD

E

D C

H A

M B

E R

S S

U

IT

E

A

N D

C O

R R

ID

O

R

J

REMODEL KEY NOTES

1 PROVIDE & INSTALL NEW HOT WATER REHEAT COIL. SEE

SCHEDULE AND DETAILS ON SHEET M3. PROVIDE

ELECTRONIC CONTROL VALVE ON HOT WATER PIPING. VALVE

SHALL FAIL IN LAST POSITION.

2 INSULATE ALL NEW AND EXISTING SUPPLY DUCTWORK

CONCEALED ABOVE CEILINGS AS NOTED IN GENERAL NOTE 2

ON SHEET M1.

3 REPLACE EXISTING PNEUMATIC HOT WATER CONTROL VALVE

WITH ELECTRONIC CONTROL VALVE. VALVE SHALL FAIL IN

LAST POSITION.

4 CONNECT TO EXISTING 34x14 EXHAUST DUCT NEAR WALL.

PROVIDE & INSTALL TRANSITION OFFSETTING OGEE FITTING.

5 INSTALL NEW EXHAUST DUCT AT 8'-6" ABOVE FINISHED

FLOOR. NEW EXHAUST DUCT SHALL BE LOCATED OFF NEW

WALL (±18") TO ALLOW SPACE TO INSTALL MANUAL VOLUME

DAMPER AND COMBINATION TEMPERATURE & HUMIDITY

SENSOR BEFORE EXHAUST BRANCH DUCT GOES THROUGH

NEW GYPSUM WALL.

6 PROVIDE & INSTALL LAY-IN SUPPLY OR EXHAUST GRILLE IN

SUSPENDED CEILING WITHIN RF CHAMBER. PROVIDE

FLEXIBLE DUCT CONNECTION BETWEEN GRILLE AND

HONEYCOMB WAVEGUIDE (PROVIDED BY CHAMBER

MANUFACTURER). PROVIDE & INSTALL SQUARE TO ROUND

TRANSITION TO HONEYCOMB WAVEGUIDE CONNECTION ON

OUTSIDE OF CHAMBER.

7 PROVIDE & INSTALL DUCT SOUND ATTENUATOR (DSA).

INSTALL PER MANUFACTURER RECOMMENDATIONS. SEE

SECTION 3 ON SHEET A4 FOR ORIENTATION OF (SUPPLY &

EXHAUST) DUCT SOUND ATTENUATORS. SEE SCHEDULE ON

SHEET M3.

8 PROVIDE & INSTALL ELECTRONIC TEMPERATURE & HUMIDITY

SENSOR ON DUCT TO CONTROL ROOM.

9 PROVIDE & INSTALL ELECTRONIC TEMPERATURE & HUMIDITY

SENSOR ON WALL TO CONTROL ROOM

10 PROVIDE & INSTALL LAY-IN CEILING DIFFUSER. COORDINATE

LOCATION WITH FLOOR DRAIN P-TRAPS SERVING FLOOR

ABOVE. REFER TO REFLECTED CEILING PLAN ON SHEET A3.

SEE SCHEDULE ON SHEET M3.

11 PROVIDE & INSTALL LAY-IN EXHAUST GRILLE WITH INTEGRAL

2" FILTER. COORDINATE LOCATION WITH FLOOR DRAIN

P-TRAPS SERVING FLOOR ABOVE. REFER TO REFLECTED

CEILING PLAN ON SHEET A3. SEE SCHEDULE ON SHEET M3

DEMOLITION KEY NOTES

1 FUME HOOD TO BE REMOVED. DISCONNECT & DEMOLISH

EXHAUST DUCTWORK BACK TO MAIN. REMOVE AND SALVAGE

FUME HOOD MONITOR TO SHEET METAL SHOP SURPLUS.

2 DEMOLISH EXISTING EXHAUST DUCTWORK AS SHOWN.

REFER TO REMODEL PLAN ON THIS SHEET FOR NEW WORK.

3 CUTOFF EXISTING EXHAUST DUCT NEAR WALL AND PREPARE

FOR NEW DUCT EXTENSION. SEE REMODEL PLAN ON THIS

SHEET.

4 DEMOLISH EXISTING SUPPLY DUCTWORK AS SHOWN. REFER

TO REMODEL PLAN ON THIS SHEET FOR NEW WORK.

5 DEMOLISH EXISTING DUCT MOUNTED SUPPLY DIFFUSER

INCLUDING TAP AND CAP MAIN AIRTIGHT.

6 DEMOLISH EXISTING PNEUMATIC THERMOSTAT AND

ASSOCIATED CONTROL TUBING.

7 DEMOLISH EXISTING PNEUMATIC HUMIDISTAT AND

ASSOCIATED CONTROL TUBING.

NORTH

NORTH

1/4" = 1'-0"

3RD FLOOR MECHANICAL DEMO PLAN

1/4" = 1'-0"

3RD FLOOR MECHANICAL REMODEL PLAN

No. Date: By: Description:

6 6

10 11

33 3

10 11

2 7

SHUT-OFF VALVE

HWS

HWR

REHEAT COIL

CAPPED DRAIN (1/2" BALL VAVLE)

TWO WAY TEMPERATURE CONTROL VALVE

UNION (TYP)MANUAL KEY

TYPE AIR VENT

CALIBRAT

ED

BALANCIN

G VALVE

HOT WATER REHEAT COIL PIPING DETAIL

N.T.S.

DSA-2 26x18 EA

8x12 EA

8Ø EA

326C

RF CHAMBER

LAB

300J

CORRIDOR

DSA-1

6x12 SA

8Ø SA 24x20 SA

REHEAT COIL

326C

RF CHAMBER

300J

CORRIDOR

Scale

UW

Number

Date Issued

Set Type

REVISIONS:

Sh ee t T itle

Pr oje ct Tit le:

Drawn By:

Fa ci lit ie s P la nn in g an d

M an ag em en t

P hy si ca l P la nt

A rc hi te ct s/

E ng in

. M ills

S tre et , M ad is on , W

I 5 ve rs ity o f W is co ns in -M ad ing N am e &

N um be r:

U W

B

LD

G

3/

/2

4:

:3

PM

1/4" = 1'-0"

M3

D

ET

AI

LS

S

C H

ED

U

LE

S

03/23/2018

0526 1602

BD

P R

IM

A

TE

C

E N

TE

R

KRAUS

IN

S

TA

LL

T H

R E

E R

F S

H

IE

LD

E

D C

H A

M B

E R

S S

U

IT

E

A

N D

C O

R R

ID

O

R

J

NOTES:

1. SYSTEM DESIGN BASED ON MANUFACTURER LISTED ABOVE. ANY DEVIATION IN

EQUIPMENT SIZE AND SPECIFICATIONS FROM EQUIPMENT SIZE AND

SPECIFICATIONS

LISTED SHALL BE IDENTIFIED BY EQUIPMENT SUPPLIER.

2. SEE PLAN FOR NECK SIZE AND CFM.

DIFFUSERS, REGISTERS, & GRILLES SCHEDULE

UW PROJECT NO. EQUIPMENT TAG QUANTITY

MANUFACTURE

R MODEL/TYPE MAX. PRESSURE DROP

MAX. NECK

VELOCITY PATTERN FACE SIZE MOUNTING TYPE FINISH DAMPER REMARKS

1602 CD-9 3 PRICE RFD 0.2 1100 2-WAY 24x24 LAY-IN WHITE NO PROVIDE WITH INTEGRAL 2" FILTER RACK 1602 CD-66 3 CARNES RSLAH FILTER 0.1 600 1-WAY 24x24 LAY-IN WHITE NO NO FILTER INSTALLED

No. Date: By: Description:

1602 EG-1 2 CARNES RSLAH FILTER 0.1 400 - 24x24 LAY-IN WHITE NO PROVIDE WITH INTEGRAL 1" FILTER RACK 1602 EG-1 3 CARNES RSLAH FILTER 0.1 400 - 24x24 LAY-IN WHITE NO PROVIDE WITH INTEGRAL 2" FILTER RACK

HOT WATER REHEAT COIL

UW PROJECT

NO.

EQUIPMENT

TAG SERVICE LOCATION MANUFACTURER MODEL/TYPE

AIR FLOW

(cfm)

AIR PRESS. DROP

(in. W.G.)

EAT/LAT

(Deg. F)

CAPACITY

(MBH)

COIL FACE

SIZE (HxW)

FACE AREA

(Sq. Ft.)

FACE

VELOCITY

COIL EWT/LWT

(Deg. F)

WATER FLOW

(gpm)

WATER P.D.

(ft.) REMARKFINS ROW

1602 RC-300J-1 326C 300J HEATCRAFT SD 1 06 12 8

01 06

140 0.05 55 / 87 4.84 6"X12" 0.5 280 8 1 180 0.5 10 -

SOUND ATTENUATOR

UW

PROJECT

NO.

EQUIPMENT

TAG MANUFACTURER MODEL LOCATION SERVICE MATERIAL

TOTAL

CAPACITY

(CFM)

MAX.

VEL.

(FPM)

MAX. PD

("WG)

OVERALL DIMENSION (IN) DYNAMIC INSERTION LOSS / MAXIMUM SELF GENERATED POWER LEVELS

REMARKH / DIA. WIDTH LENGTH 63 125 250 500 1000 2000 4000 8000

1602 DSA-1 VIBRO-ACOUSTICS RNM OVER RF

CHAMBER

SUPPLY GALVANIZED 140 140 0.05 12" 12" 36" 6 / 33 5 / 10 10 / 10 15 / 10 10 / 21 10 / 14 9 / 10 8 / 15 PACKLESS

1602 DSA-2 VIBRO-ACOUSTICS RNM OVER RF

CHAMBER

EXHAUST GALVANIZED 140 140 0.05 12" 12" 36" 6 / 33 5 / 17 10 / 16 15 / 21 10 / 28 10 / 13 9 / 10 8 / 10 PACKLESS

1/4" = 1'-0"1 Section of Exhaust at Chamber 1/4" = 1'-0"2 Section of Supply at Chamber

ELECTRICAL SYMBOLS & ABBREVIATIONS

SC

T

S

QUADRAPLEX ELECTRIC OUTLET

DUPLEX ELECTRIC OUTLET

MULTIPLE PORT VOICE/DATA

VOICE JACK

DATA/DATA JACK

THERMOSTAT

LIGHT SWITCH

WIREMOLD

GAS

SEPARATE CIRCUIT

EXIT SIGN

1X4 LAY-IN FLUORESENT LIGHT FIXTURE

INCANDESCENT LIGHT FIXTURE

FIRE ALARM DEVICE

NOTES:

1. SYMBOLS INDICATED HERE AND NOT USED IN THE CONTRACT DOCUMENTS DO NOT APPLY

TO THIS PROJECT. ADDITIONAL SYMBOLS MAY BE INDICATED IN THE CONTRACT

DOCUMENTS.

2. NEW WORK IS SHOWN WITH SOLID HEAVY LINES.

3. EXISTING TO REMAIN IS SHOWN WITH LIGHT LINES.

4. DEMOLISHED WORK IS SHOWN WITH HEAVY DASHED LINES.

A AMPERES

AFF ABOVE FINISHED FLOOR

ARCH ARCHITECTURAL

ASC ABOVE SUSPENDED CEILING

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

BATS BYPASS AUTOMATIC TRANSFER SWITCH

DC DIRECT CURRENT

DS DAYLIGHT SENSOR

K KELVIN

LAN LOCAL AREA NETWORK

FA FIRE ALARM

BATS BYPASS AUTOMATIC TRANSFER SWITCH

DC DIRECT CURRENT

DS DAYLIGHT SENSOR

K KELVIN

LAN LOCAL AREA NETWORK

FA FIRE ALARM

OS OCCUPANCY SENSOR

S LIGHT SWITCH 3-WAY

S LIGHT SWITCH OCCUPANCY SENSOR

OS

Scale

UW

Number

Date Issued

Set Type

REVISIONS:

Sh ee t T itle

Pr oje ct Tit le:

Drawn By:

Fa ci lit ie s P la nn in g an d

M an ag em en t

P hy si ca l P la nt

A rc hi te ct s/

E ng in

. M ills

S tre et , M ad is on , W

I 5 ve rs ity o f W is co ns in -M ad ing N am e &

N um be r:

U W

B

LD

G

3/

/2

4:

:2

PM

1/4" = 1'-0"

E1

SY

M

BO

LS

A

BB

R

EV

IA

TI

O

N S, G

EN

ER

AL

N O

TE

S

03/23/2018

0526 1602

BD

P R

IM

A

TE

C

E N

TE

R

DREES

IN

ST

AL

L

TH

R

EE

R

F

SH

IE

LD

ED

C

H

AM

BE

R

S S

U

IT

E

A

N D

C O

R R

ID

O

R

J

GENERAL NOTES

1 ADJUST LOCATIONS AND HEIGHTS AS NEEDED.

2 SURFACE MOUNT NEW ELECTRICAL INSTALLATIONS EXCEPT

SURGICAL LIGHT.

3 LABEL ALL CIRCUITS, RECEPTACLES, JUNCTION BOXES, AND

EQUIPMENT.

4 UPDATE AFFECTED PANEL SCHEDULES.

5 REFEED ANY ELECTRICAL AFFECTECTED BY REMODEL

PORJECT.

6 PLACE ARC FLASH LABEL ON PANELS THAT ARE PART OF THE

PROJECT.

7 TEST FIRE ALARM SYSTEM AS NEEDED DUT TO REMODEL

PROJECT.

8 RESEAL FIRE AND SMOKE WALL PENETRATIONS AS NEEDED.

9 FIELD VERIFY ELECTRICAL CIRCUITS SHOWN ON THE

DRAWINGS.

ENCLOSURE GROUNDING DETAILLIGHTING CONTROLLER

FH

F H

F HFH

3A

M F H

3A

FH

3A-18

3A-18

3A-18 3A-18

3A-5

3A-5

3B-153A-43A-83B-28/30

3A-16

3A-16

3B-4

3B-2 3B-2

3B-4

3A-18 3A-16

3B-6 3B-6

3B-7 3B-9 3A-6 3A-2

3A-5 3B-26

3B-18

3A-16

3A-16 3A-6

3A-5

RF FILTER

LIGHTING

RF FILTER

POWER

RF FILTER

LIGHTING

LIGHTING

CONTROL BOX

RF FILTER

POWER

RF FILTER

POWER

2' - 9" 6' - 8"

8' - 8"

A B

RF FILTER

LIGHTING

LIGHTING

CONTROL BOX

LIGHTING

CONTROL BOX

Scale

UW

Number

Date Issued

Set Type

REVISIONS:

Sh ee t T itle

Pr oje ct Tit le:

Drawn By:

Fa ci lit ie s P la nn in g an d

M an ag em en t

P hy si ca l P la nt

A rc hi te ct s/

E ng in

. M ills

S tre et , M ad is on , W

I 5 ve rs ity o f W is co ns in -M ad ing N am e &

N um be r:

U W

B

LD

G

3/

/2

4:

:2

PM

1/4" = 1'-0"

E2

3R D

F

LO

O R

E

LE

C

TR

IC

A

L D

E M

O

LI

TI

O

N /R

E M

O D

E L

P

LA

N

03/23/2018

0526 1602

BD

P R

IM

A

TE

C

E N

TE

R

DREES

IN

ST

AL

L

TH

R

EE

R

F

SH

IE

LD

ED

C

H

AM

B

ER

S S

U

IT

E

A

N D

C O

R R

ID

O

R

J

REMODEL KEY NOTES

1 REPLACE EXISTING RECEPTACLE WITH A GFCI.

2 INSTALL NEW WALL MOUNTED LIGHT FIXTURE,

MOUNTED AT 72" AFF. WALL WILL BE OPENED TO

ALLOW FOR A RECESSED ELECTRICAL BOX.SEE

PROJECT FILE FOR CUT-SHEET.

3 INSTALL 2 ea DOUBLE DUPLEX RECEPTACLES ON A

DEDICATED CIRCUIT. SURFACE MOUNTED AT 36" AFF

TO THE BOTTOM IN EMT CONDUIT/BOXES. PAINT TO

MATCH.

4 INSTALL A DATA/DATA JACK. SURFACE MOUNT AT 36"

AFF TO THE BOTTOM IN EMT CONDUIT/BOX. PAINT TO

MATCH. INSTALL BRIDLE RINGS ABOVE THE

SUSPENDED CEILING FOR SUPPORTS AS NEEDED.

5 INSTALL 2 ea 120v ELECTRICAL CIRCUITS FOR RF

ENCLOSURE. ONE FOR THE LIGHTING AND ONE FOR

FUTURE RECEPTACLES.

6 INSTALL LIGHTING CONTROL BOX, LIGHT SWITCH, AND

RF FILTER. CONNECT LOAD SIDE TO ENCLOSURE LIGHT

FIXTURES. NECESSARY PARTS ARE SUPPLIED WITH

THE ENCLOSURE.

7 INSTALL A VERTICALLY MOUNTED 4" FLEXTRAY,

SURFACE MOUNT AT 36" AFF TO THE BOTTOM

EXTENDED TO 6" FLEXTRAY.

8 INSTALL A WALL MOUNTED EQUIPMENT GROUNDING

BAR MOUNTED JUST BELOW THE SUSPENDED CEILING

. INSTALL A #6 GROUNDING WIRE FROM THE BAR TO

THE EXISTING EQUIPMENT GROUND LOCATED IN ROOM

333. CONNECT RF FILTERS, AND ENCLOSURES TO

GROUND BAR. REFER TO PDC INSTALLATION MANUAL

FOR DETAILS.

9 INSTALL A QUAD RECEPTACLES MOUNTED AT 42" AFF.

SURFACE MOUNT EMT CONDUIT/BOX. PAINT TO MATCH

WALL COLOR.

10 EQUIPMENT CABLE CHASE - SEE ARCHITECTURAL FOR

ADDITIONAL INFORMATION.

DEMOLITION KEY NOTES

1 DEMO ELECTRICAL RECEPTACLE, BRANCH CIRCUIT WIRING,

AND ASSOCIATED SURFACE MOUNTED BOXES/CONDUIT.

REFEED AND UPSTREAM ELECTRICAL AFFECTED BY

REMODEL PROJECT.

2 DEMO NETWORK JACK, WIRING, AND ASSOCIATED PANDUIT.

3 DEMO LIGHT SWITCH AND ASSOCIATED WIRING.

4 DEMO FIRE ALARM STROBE.

5 DEMO UNDER THE CABINET LIGHT FIXTURE.

6 DEMO TO FUME HOOD. REMOVE ASSOCIATED BRANCH

CIRCUIT WIRING.

7 DEMO IN WALL LIGHT FIXTURE. REMOVE ASSOCIATED

BRANCH CIRCUIT WIRING.

NORTH

NORTH

1/4" = 1'-0"

1602 - 3RD FLOOR ELECTRICAL DEMO PLAN

1/4" = 1'-0"

1602 - 3RD FLOOR ELECTRICAL REMODEL PLAN

1 1

1 1 1 1

No. Date: By: Description:

7 7 7

9 9 9

10 10 10

CLG

F H

T E

F H

3A

FH

H

H

OS JJ JJ JJ

OS

CLG

F

H OS

A/B

A/B A/B A/B A/B A/B

Scale

UW

Number

Date Issued

Set Type

REVISIONS:

Sh ee t T itle

Pr oje ct Tit le:

Drawn By:

Fa ci lit ie s P la nn in g an d

M an ag em en t

P hy si ca l P la nt

A rc hi te ct s/

E ng in

. M ills

S tre et , M ad is on , W

I 5 ve rs ity o f W is co ns in -M ad ing N am e &

N um be r:

U W

B

LD

G

3/

/2

4:

:2

PM

1/4" = 1'-0"

E3

3R D

F

LO

O R

E

LE

C

TR

IC

AL

C

EI

LI

N

G D

EM

O

/R E

M O

D E

L

PL

A N

03/23/2018

0526 1602

BD

P R

IM

A

TE

C

E N

TE

R

DREES

IN

ST

AL

L

TH

R

EE

R

F

SH

IE

LD

ED

C

H

AM

B

ER

S S

U

IT

E

A

N D

C O

R R

ID

O

R

JREMODEL KEY NOTES

1 INSTALL NEW 2x2 LED LIGHT FIXTURE. SEE PROJECT

FILE FOR FIXTURE CUT-SHEET.

2 INSTALL NEW OCCUPANCY SENSOR. CONNECT ALL

SENSORS TOGETHER.

3 REINSTALL PREVIOUSLY REMOVED FIRE ALARM

DETECTOR. RE-PIPE CONDUITS AS NEEDED TO CLEAR

RF ENCLOSURES AS NEEDED.

4 INSTALL A 4"x2" FLEXTRAY MOUNTED 3" BELOW THE

SUSPENDED CEILING TO THE TOP OF THE TRAY.

5 INSTALL 6 ea RECESSED CAN LIGHTS SUPPLIED WITH

THE ENCLOSURE.

6 INSTALL A 2" FLEXTRAY ALONG THE WALL.

DEMOLITION KEY NOTES

1 DEMO AND RECYCLE LIGHT FIXTURE.

2 DEMO FIRE ALARM DEVICE. RETAIN FOR RELOCATION.

NORTH

NORTH

1/4" = 1'-0"

1602 - 3RD FLOOR ELECTRICAL DEMO CEILING PLAN

1/4" = 1'-0"

1602 - 3RD FLOOR ELECTRICAL REMODEL CEILING PLAN

1 1

No. Date: By: Description:

11111

4 4

Sheets
A1 - SYMBOLS & ABBREVIATIONS
A2 - 3RD FLOOR DEMOLITION/REMODEL PLAN
A3 - 3RD FLOOR CEILING DEMOLITION/REMODEL PLAN
A4 - ELEVATIONS AND SECTIONS
A5 - DETAILS
E1 - SYMBOLS & ABBREVIATIONS, GENERAL NOTES
E2 - 3RD FLOOR ELECTRICAL DEMOLITION/REMODEL PLAN
E3 - 3RD FLOOR ELECTRICAL CEILING DEMO/REMODEL PLAN
M1 - SYMBOLS & ABBREVIATIONS, GENERAL NOTES
M2 - 3RD FLOOR MECHANICAL DEMOLITION/REMODEL PLAN
M3 - DETAILS & SCHEDULES
P1 - SYMBOLS & ABBREVIATIONS, GENERAL NOTES
P2 - 3RD FLOOR PLUMBING DEMOLITION/REMODEL PLAN

File details come from the government source that posted it. Updated .