2-W Maple Grove Rd and Fivepointville Rd Sanitary Sewer Repairs Project Drawings 4713.005.pdf

PDF 4 MB Posted

Attached to
West Maple Grove Road and Fivepointville Road Sanitary Sewer Repairs Contract No. 26-3
Solicitation number
US.262757
Issued by
Lancaster County, Pennsylvania

About this file

Summary of Project Drawings for West Maple Grove Road and Fivepointville Road Sanitary Sewer Repairs

This document comprises the project drawings for the West Maple Grove Road and Fivepointville Road Sanitary Sewer Repairs project (Contract No. 26-3, Entech Project No. 4713.005) prepared by Entech Engineering for the Northern Lancaster County Authority in Brecknock Township, Lancaster County, Pennsylvania. The project scope includes the replacement of approximately 360 linear feet of existing 8-inch PVC sanitary sewer piping with new SDR-26 PVC pipe across seven designated project areas, replacement of approximately 30 linear feet of 6-inch SDR-26 PVC sanitary sewer lateral, replacement of seven existing manhole composite riser rings, modification of an existing manhole drop connection to convert from external to internal configuration, and PennDOT roadway pavement restoration at multiple locations. The drawings package includes a location/topographical map, general project notes and legend, detailed plans for each of the seven project areas, construction details for sewer connections and manhole modifications, restoration details for both grass and paved areas, and erosion and sedimentation control details. Bids are due electronically via PennBid by 2:00 PM on Wednesday, December 30, 2026, with a mandatory pre-bid conference scheduled for Wednesday, December 2, 2026 at 10:00 AM at 983 Beam Road, Denver, PA 17517. Bidders who fail to attend the mandatory pre-bid conference will not have their bids accepted.

The project imposes multiple contractor responsibilities including compliance with Pennsylvania Act No. 287 regarding underground utility location, traffic control and detour management, shoring device provision and maintenance, use of rubber-tracked excavators or matting to protect road surfaces, maintenance of residential access and utility services throughout construction, temporary bypass pumping operations during construction, and adherence to all erosion and sedimentation control regulations and PennDOT permit conditions. Contractors must also verify existing sewer slopes, match existing surface elevations for manhole grade adjustments, provide adequate restoration of residential yards and garden areas, and notify PennDOT at minimum one week prior to construction start. The drawings indicate seven separate limits of disturbance, each encompassing 0.12 acres, with specific road opening dimensions and restoration requirements varying by project area and road type, including mill and overlay operations for state routes. All project documents are available at no cost through the PennBid Program.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BRECKNOCK

TOWNSHIP

LANCASTER

COUNTY

PROJECT AREA #2

PROJECT AREA #3

PROJECT AREA #1

PROJECT AREA #4

PROJECT AREA #5

PROJECT AREA #6

PROJECT AREA #7

CIVIL LEGEND

LIMIT OF DISTURBANCE

SL PROPOSED SANITARY LATERAL

PROPOSED SANITARY MAINSAN

TEXT PROPOSED TEXT

4713.005

A

B

2 3

C

D

1 2 3

4 5 6

PROJECT NO.

APPROVED BY:

SCALE:

CHECKED BY:

PREPARED BY:

A

B

D

AT

E R

EV

4 5

IS

SU

ED

F

O R

/R

EV

IS

ED

C

AP

PD

D

DRAWING NO.

Entech Engineering - Printed: Nov. 13, 2026 H:\0004713.005\04-CAD\SheetFiles\G-001.dwgLa st

E di te d by : e m ot te r

G-001

NO

RT

HE

RN

L

AN

CA

ST

ER

C

O

UN

TY

A

UT

HO

RI

TY

BR

EC

KN

O

C K

TO

W

N

SH

IP

, L

AN

C

AS

TE

R C

O U

N

TY

, P

EN

N

SY

LV

AN

IA

W M

AP

LE

G

RO

VE

R

OA

D

AN

D

FI

VE

PO

IN

TV

IL

LE

R

OA

D

SE

W

ER

R

EP

AI

RS

AGS

ARA

AS NOTED

/1

2/

A

IN

TE

R N

AL

Q

C

AG

S

/2 0/

B

C

LI

EN

T R

EV

IE

W

AG

S

/1 3/

C

BI

D D

IN

G

AG

S

00 2000' 4000' Scale:1 1" = 2000'

LOCATION / TOPOGRAPHICAL MAP

DR

AW

IN

G

IN

DE

X, G

EN

ER

AL

P

RO

JE

CT

N

O

TE

S, L

EG

EN

D

AN

D

DR

AW

IN

G C

O

NV

EN

TI

O

NS

G

EN

ER

AL

SECTION INDICATOR

DETAIL INDICATOR

ELEVATION INDICATOR

DRAWING CONVENTIONS

?-201

A ?-301

A ?-301

?-501

SCALE:1 1" = 1'-0"

DRAWING TITLE

DRAWING NUMBER

SECTION LETTER

DRAWING NUMBER

ELEVATION LETTER

IDENTIFICATION NUMBER/LETTER

DRAWING TITLE

SHEET KEYNOTE SYMBOL

DRAWING NUMBER

DETAIL NUMBER

TEXT

INDICATES EXIST

CONDITIONS/FEATURES

INDICATES NEW

WORK/FEATURES

A. PROJECT DRAWINGS MUST BE WORKED IN CONJUNCTION WITH THE PROJECT

MANUAL AND SPECIFICATIONS.

B. ALL DIMENSIONS, ELEVATIONS, AND EXISTING CONDITIONS MUST BE CHECKED

AND VERIFIED AT THE PROJECT SITE PRIOR TO CONSTRUCTION.

C. ALL UNDERGROUND UTILITIES SHALL BE LOCATED BY THE CONTRACTOR PRIOR

TO ANY EARTH MOVING ACTIVITIES PURSUANT TO PA ACT NO. 287, AS AMENDED

BY ACT 50 OF 2017. UNDERGROUND UTILITIES MUST BE VERIFIED BY

CONTACTING THE “ONE CALL SYSTEM” AT 1-800-242-1776 OR ONLINE AT

PAONECALL.ORG.

D. CONTRACTOR IS RESPONSIBLE FOR TRAFFIC CONTROL AND DETOURS AS

DEFINED IN THE PROJECT MANUAL.

E. CONTRACTOR SHALL USE, MAINTAIN, AND ALWAYS PROVIDE ADEQUATE

SHORING DEVICES ON SITE. CONTRACTOR SHALL CONFORM TO ALL LOCAL,

STATE, AND FEDERAL REGULATIONS.

F. CONTRACTOR SHALL USE RUBBER TRACKED EXCAVATOR OR PROVIDE 1” THICK

MINIMUM MATTING TO PROTECT PAVED LOCAL MUNICIPAL, STATE, AND PRIVATE

ROAD SURFACES DURING TRENCHING, EXCAVATION, AND GENERAL

CONSTRUCTION OPERATIONS.

G. CONTRACTOR IS RESPONSIBLE TO MAINTAIN ACCESS TO ALL RESIDENCES

THROUGHOUT CONSTRUCTION.

H. CONTRACTOR IS RESPONSIBLE FOR RESTORATION OF RESIDENTIAL YARD AND

GARDEN AREAS.

I. CONTRACTOR IS RESPONSIBLE TO MAINTAIN UTILITY SERVICES TO ALL

RESIDENTS THROUGHOUT CONSTRUCTION.

J. CONTRACTOR SHALL ABIDE BY ALL ISSUED PERMIT CONDITIONS INCLUDING BUT

NOT LIMITED TO EROSION AND SEDIMENTATION CONTROL (CHAPTER 102) AND

THE GENERAL PERMITS (CHAPTER 105).

K. FINAL RESTORATION SHALL BE IN ACCORDANCE WITH THE FINAL ISSUED

PENNDOT HIGHWAY OCCUPANCY PERMITS.

L. CONTRACTOR SHALL NOTIFY PENNDOT AT MINIMUM OF ONE (1) WEEK PRIOR TO

START OF CONSTRUCTION.

M. THE CONTRACTOR IS RESPONSIBLE FOR ALL TEMPORARY BYPASS PUMPING

OPERATIONS DURING CONSTRUCTION.

N. CONTRACTOR TO VERIFY EXISTING SLOPES FOR ALL SANITARY SEWER REPAIRS

TO ENSURE THAT SLOPE IS MAINTAINED.

O. CONTRACTOR TO MATCH EXISTING SURFACE ELEVATIONS FOR ALL SANITARY

SEWER MANHOLE GRADE ADJUSTMENTS.

GENERAL PROJECT NOTES

REFERENCE: USGS 7.5 MINUTE SERIES (TOPOGRAPHIC MAPS) MORGANTOWN AND TERRE HILL, PENNSYLVANIA

1-800-242-1776

(TOLL FREE)

"Pa. Law requires advance notification"

PA ONE CALL FOR DESIGN

COORDINATE PA: 16401187

SERIAL NUMBERS:

20262873043 (FINAL DESIGN)

1-800-242-1776

PE

NN

SY

LV

ANIA ONE CALL SYSTEM

, INC

STOP-CALL BEFORE YOU D

IG

SCALE:2 NONE

VICINITY MAP

DESIGN PA ONE CALL

UTILITY RESPONSE ADDRESS CONTACT INFORMATION PHONE CONTACT PERSON

BRECKNOCK TOWNSHIP LANCASTER COUNTY 1026 DRY TAVERN RD

DENVER, PA. 17517 cmartin@brecknocktownship.us 717-445-5933 CAROL MARTIN

METROPOLITAN EDISON CO/FIRSTENERGY 341 WHITE POND DR

AKRON, OH. 44320 madams@firstenergycorp.com 330-252-4013 MELLYSSA ADAMS

NORTHERN LANCASTER COUNTY AUTHORITY 983 BEAM ROAD

DENVER, PA. 17517 mross@nlcaonline.com 717-445-7553 MATT ROSS

PPL ELECTRIC UTILITIES CORPORATION 4810 LYCOMING MALL

MONTOURSVILLE, PA. 17754 pdseitzer@pplweb.com 570-368-5394 PAMELA SEITZER

PENCOR SERVICES/BLUE RIDGE COMMUNICATION 462 DELAWARE AVE

PALMERTON, PA. 18071-1909 jbuccieri@brctv.com 610-826-9504 JOE BUCCIERI

SERVICE ELECTRIC CABLEVISION INC PO BOX 8

BIRDSBORO, PA. 19508 mike.spayd@secv.com 610-582-5317 MIKE SPAYD

FRONTIER COMMUNICATIONS OF PA INC 300E LAIRD ST

WILKES BARRE, PA. 18702 michael.navich@ftr.com 570-208-3375 MICHAEL NAVICH

DRAWING INDEX

DWG. NO. DRAWING DESCRIPTION/TITLE

GENERAL

G-001 DRAWING INDEX, GENERAL PROJECT NOTES, LEGEND AND DRAWING

CONVENTIONS

G-101 INDEX PLAN

CIVIL

C-101

FIVEPOINTVILLE ROAD SANITARY SEWER REPAIR PLANS

(PROJECT AREAS #1 AND #2)

C-102

W MAPLE GROVE ROAD SANITARY SEWER REPAIR PLAN

(PROJECT AREA #3)

C-103

READING ROAD SANITARY SEWER REPAIR PLANS

(PROJECT AREAS #4 AND #5)

C-104

READING ROAD SANITARY SEWER REPAIR PLANS

(PROJECT AREAS #6 AND # 7)

C-501 CONSTRUCTION DETAILS

C-701 RESTORATION DETAILS

EROSION AND SEDIMENTATION

ES-501 CONTROL DETAILS

NOVEMBER 13, 2026

NORTHERN LANCASTER COUNTY AUTHORITY

W MAPLE GROVE ROAD AND FIVEPOINTVILLE ROAD

SEWER REPAIR PROJECT - CONTRACT NO. 26-3

OFFICE ADDRESS:

983 BEAM ROAD

DENVER, PA. 17517

ISSUED FOR BIDDING

PROJECT SITE

PROJECT SITE

PROJECT SITE

REFERENCE DRAWINGS

1. EXISTING COLLECTION SYSTEM DRAWINGS REFERENCE EBERT

ENGINEERING, INC. "GENERAL PLANS OF SANITARY SEWERS FOR THE

NORTHERN LANCASTER COUNTY AUTHORITY" JOB #063-001 DATED JULY

6, 2012.

G

EN

ER

AL

IN

D

EX

P

LA

N

"PROJECT AREA #1"

DRAWING C-101

PLAN 1

"PROJECT AREA #2"

DRAWING C-101

PLAN 2

"PROJECT AREA #3"

DRAWING C-102

PLAN 1

SCALE:1 1" = 500'

INDEX PLAN

00 500' 1000'

4713.005

A

B

2 3

C

D

1 2 3

4 5 6

PROJECT NO.

APPROVED BY:

SCALE:

CHECKED BY:

PREPARED BY:

A

B

D

AT

E R

EV

4 5

IS

SU

ED

F

O R

/R

EV

IS

ED

C

AP

PD

D

DRAWING NO.

Entech Engineering - Printed: Nov. 13, 2026 H:\0004713.005\04-CAD\SheetFiles\G-101.dwgLa st

E di te d by : m hi es te r

G-101

NO

RT

HE

RN

L

AN

CA

ST

ER

C

O

UN

TY

A

UT

HO

RI

TY

BR

EC

KN

O

C K

TO

W

N

SH

IP

, L

AN

C

AS

TE

R C

O U

N

TY

, P

EN

N

SY

LV

AN

IA

W M

AP

LE

G

RO

VE

R

OA

D

AN

D

FI

VE

PO

IN

TV

IL

LE

R

OA

D

SE

W

ER

R

EP

AI

RS

AGS

ARA

AS NOTED

/1

2/

A

IN

TE

R N

AL

Q

C

AG

S

/2 0/

B

C

LI

EN

T R

EV

IE

W

AG

S

/1 3/

C

BI

D D

IN

G

AG

S

"PROJECT AREA #4"

DRAWING C-103

PLAN 1

"PROJECT AREA #5"

DRAWING C-103

PLAN 2

"PROJECT AREA #7"

DRAWING C-104

PLAN 2

"PROJECT AREA #6"

DRAWING C-104

PLAN 1

4713.005

A

B

2 3

C

D

1 2 3

4 5 6

PROJECT NO.

APPROVED BY:

SCALE:

CHECKED BY:

PREPARED BY:

A

B

D

AT

E R

EV

4 5

IS

SU

ED

F

O R

/R

EV

IS

ED

C

AP

PD

D

DRAWING NO.

Entech Engineering - Printed: Nov. 13, 2026 H:\0004713.005\04-CAD\SheetFiles\C-101.dwgLa st

E di te d by : A

A tti ck

C-101

NO

RT

HE

RN

L

AN

CA

ST

ER

C

O

UN

TY

A

UT

HO

RI

TY

BR

EC

KN

O

C K

TO

W

N

SH

IP

, L

AN

C

AS

TE

R C

O U

N

TY

, P

EN

N

SY

LV

AN

IA

W M

AP

LE

G

RO

VE

R

OA

D

AN

D

FI

VE

PO

IN

TV

IL

LE

R

OA

D

SE

W

ER

R

EP

AI

RS

AGS

ARA

AS NOTED

/1

2/

A

IN

TE

R N

AL

Q

C

AG

S

/2 0/

B

C

LI

EN

T R

EV

IE

W

AG

S

/1 3/

C

BI

D D

IN

G

AG

S

GENERAL PROJECT NOTES

1. REFER TO DRAWING G-001 FOR DRAWING INDEX, GENERAL PROJECT

NOTES, LEGEND AND DRAWING CONVENTIONS.

2. IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR FOR THE

REMOVAL AND DISPOSAL OF THE EXISTING SANITARY SEWER MAIN AND

SANITARY MANHOLES THAT ARE REMOVED FROM SERVICE.

C

IV

IL

FI

VE

PO

IN

TV

IL

LE

R O

AD

S

AN

IT

AR

Y

SE

W

ER

R

EP

AI

R P

LA

N

S (P

R O

JE

C

T

AR

EA

S

#1 A

N D

2)

PROPOSED 8'x8' ROAD OPENING

MANHOLE RISER RINGS TO BE REMOVED

AND REPLACED W/ COMPOSITE RISER

SCALE:1 1" = 30'

SANITARY SEWER REPAIR PLAN

FIVEPOINTVILLE ROAD

PROJECT AREA #1

00 30' 60'

SCALE:2 1" = 30'

SANITARY SEWER REPAIR PLAN

FIVEPOINTVILLE ROAD

PROJECT AREA #2

00 30' 60'

PROPOSED 8'x8' ROAD OPENING

MANHOLE RISER RINGS TO BE REMOVED

AND REPLACED W/ COMPOSITE RISER

FILTER BAG INLET

PROTECTION - TYPE M

ES-501

E&S CONTROL NOTES

1. CONTRACTOR IS RESPONSIBLE TO COMPLY WITH CHAPTER 102

EROSION CONTROL RULES AND REGULATIONS AND FOLLOW GUIDANCE

IN THE PADEP EROSION AND SEDIMENT POLLUTION CONTROL PROGRAM

MANUAL.

2. CONTRACTOR TO LIMIT THE DISTURBED AREA TO THE MINIMUM AMOUNT

POSSIBLE FOR THE INSTALLATION.

3. THE INSTALLATION OF ALL REQUIRED EROSION AND SEDIMENT

CONTROL DEVICES SHALL OCCUR PRIOR TO EARTHMOVING ACTIVITIES.

4. E&S CONTROLS ARE TO REMAIN IN PLACE UNTIL ALL AREAS ARE

PROPERLY STABILIZED WITH A PERMANENT GROUND COVER.

5. PROVIDE TEMPORARY AND PERMANENT SEEDING PER THE

SPECIFICATIONS OF THE PADEP EROSION AND SEDIMENT POLLUTION

CONTROL PROGRAM MANUAL.

6. CONTRACTOR SHALL PREVENT THE TRACKING OF SEDIMENT ONTO

ADJOINING PAVED AREAS AND PUBLIC STREETS BY CONSTRUCTION

VEHICLES. SEDIMENT SHALL BE CLEANED FROM PAVED AREAS DAILY.

7. UNTIL THE SITE IS STABILIZED, ALL EROSION AND SEDIMENT BMPS

SHALL BE MAINTAINED PROPERLY BY THE CONTRACTOR. MAINTENANCE

SHALL INCLUDE INSPECTIONS OF ALL EROSION AND SEDIMENT BMPS

AFTER EACH RUNOFF EVENT AND ON A WEEKLY BASIS. ALL

PREVENTATIVE AND REMEDIAL MAINTENANCE WORK, INCLUDING CLEAN

OUT, REPAIR, REPLACEMENT, RE-GRADING, RESEEDING, RE-MULCHING

AND RE-NETTING MUST BE PERFORMED IMMEDIATELY. IF THE E&S BMPS

FAIL TO PERFORM AS EXPECTED, REPLACEMENT BMPS, OR

MODIFICATIONS OF THOSE INSTALLED WILL BE REQUIRED.

FILTER BAG INLET

PROTECTION - TYPE M

ES-501

SR 1046

SEGMENT 0050

OFFSET 1717

SR 0897

SEGMENT 0350

OFFSET 2967

SR 0897

SEGMENT 0360

OFFSET 0000

SR 1046

SEGMENT 0060

OFFSET 0000

SR 1046

SEGMENT 0050

OFFSET 3309

C-501

C-501

TOTAL LOD: 0.12 ACRES

TOTAL LOD: 0.12 ACRES

C-701

C-701

SAN

2200 2300 2400 2500 2600 2700 2800

0000 0100

4713.005

A

B

2 3

C

D

1 2 3

4 5 6

PROJECT NO.

APPROVED BY:

SCALE:

CHECKED BY:

PREPARED BY:

A

B

D

AT

E R

EV

4 5

IS

SU

ED

F

O R

/R

EV

IS

ED

C

AP

PD

D

DRAWING NO.

Entech Engineering - Printed: Nov. 13, 2026 H:\0004713.005\04-CAD\SheetFiles\C-102.dwgLa st

E di te d by : A

A tti ck

C-102

NO

RT

HE

RN

L

AN

CA

ST

ER

C

O

UN

TY

A

UT

HO

RI

TY

BR

EC

KN

O

C K

TO

W

N

SH

IP

, L

AN

C

AS

TE

R C

O U

N

TY

, P

EN

N

SY

LV

AN

IA

W M

AP

LE

G

RO

VE

R

OA

D

AN

D

FI

VE

PO

IN

TV

IL

LE

R

OA

D

SE

W

ER

R

EP

AI

RS

AGS

ARA

AS NOTED

/1

2/

A

IN

TE

R N

AL

Q

C

AG

S

/2 0/

B

C

LI

EN

T R

EV

IE

W

AG

S

/1 3/

C

BI

D D

IN

G

AG

S

GENERAL PROJECT NOTES

1. REFER TO DRAWING G-001 FOR DRAWING INDEX, GENERAL PROJECT

NOTES, LEGEND AND DRAWING CONVENTIONS.

2. IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR FOR THE

REMOVAL AND DISPOSAL OF THE EXISTING SANITARY SEWER MAIN AND

SANITARY MANHOLES THAT ARE REMOVED FROM SERVICE.

C

IV

IL

W

M

AP

LE

G

R O

VE

R

O

AD

S

AN

IT

AR

Y

SE

W

ER

R

EP

AI

R

P

LA

N (P

R O

JE

C

T

AR

EA

3)

SCALE:1 1" = 30'

SANITARY SEWER REPAIR PLAN

W MAPLE GROVE ROAD

PROJECT AREA #3

00 30' 60'

CUT EXISTING 8" PVC SANITARY

SEWER AND REPLACE WITH 40 LF OF

NEW SDR-26 PVC SANITARY SEWER

PROPOSED 5'x40'

ROAD OPENING

PROPOSED 5'x50'

ROAD OPENING

PROPOSED 5'x25'

ROAD OPENING

CUT EXISTING 8" PVC SANITARY

SEWER AND REPLACE WITH 20 LF OF

NEW SDR-26 PVC SANITARY SEWER

PROPOSED 6" SDR-26 PVC LATERAL (30 LF)

MANHOLE RISER RINGS TO

BE REMOVED AND REPLACED

W/ COMPOSITE RISER

MANHOLE RISER RINGS TO BE REMOVED

AND REPLACED W/ COMPOSITE RISER

CUT EXISTING 8" PVC SANITARY

SEWER AND REPLACE WITH 25 LF OF

NEW SDR-26 PVC SANITARY SEWER

FILTER BAG INLET

PROTECTION - TYPE M

ES-501

E&S CONTROL NOTES

1. CONTRACTOR IS RESPONSIBLE TO COMPLY WITH CHAPTER 102

EROSION CONTROL RULES AND REGULATIONS AND FOLLOW GUIDANCE

IN THE PADEP EROSION AND SEDIMENT POLLUTION CONTROL PROGRAM

MANUAL.

2. CONTRACTOR TO LIMIT THE DISTURBED AREA TO THE MINIMUM AMOUNT

POSSIBLE FOR THE INSTALLATION.

3. THE INSTALLATION OF ALL REQUIRED EROSION AND SEDIMENT

CONTROL DEVICES SHALL OCCUR PRIOR TO EARTHMOVING ACTIVITIES.

4. E&S CONTROLS ARE TO REMAIN IN PLACE UNTIL ALL AREAS ARE

PROPERLY STABILIZED WITH A PERMANENT GROUND COVER.

5. PROVIDE TEMPORARY AND PERMANENT SEEDING PER THE

SPECIFICATIONS OF THE PADEP EROSION AND SEDIMENT POLLUTION

CONTROL PROGRAM MANUAL.

6. CONTRACTOR SHALL PREVENT THE TRACKING OF SEDIMENT ONTO

ADJOINING PAVED AREAS AND PUBLIC STREETS BY CONSTRUCTION

VEHICLES. SEDIMENT SHALL BE CLEANED FROM PAVED AREAS DAILY.

7. UNTIL THE SITE IS STABILIZED, ALL EROSION AND SEDIMENT BMPS

SHALL BE MAINTAINED PROPERLY BY THE CONTRACTOR. MAINTENANCE

SHALL INCLUDE INSPECTIONS OF ALL EROSION AND SEDIMENT BMPS

AFTER EACH RUNOFF EVENT AND ON A WEEKLY BASIS. ALL

PREVENTATIVE AND REMEDIAL MAINTENANCE WORK, INCLUDING CLEAN

OUT, REPAIR, REPLACEMENT, RE-GRADING, RESEEDING, RE-MULCHING

AND RE-NETTING MUST BE PERFORMED IMMEDIATELY. IF THE E&S BMPS

FAIL TO PERFORM AS EXPECTED, REPLACEMENT BMPS, OR

MODIFICATIONS OF THOSE INSTALLED WILL BE REQUIRED.

FILTER BAG INLET

PROTECTION - TYPE C

ES-501

SR 1046

SEGMENT 0100

OFFSET 2828

SR 1046

SEGMENT 0110

OFFSET 0000

C-501

C-501

C-501

C-501

C-501SR 1046

SEGMENT 0100

OFFSET 2259

C-701

C-501

C-701

C-501

C-501

TOTAL LOD: 0.12 ACRES

SHEET KEYNOTES

1. EXISTING LATERAL TO BE RECONNECTED TO NEW SANITARY SEWER

MAIN.

2200 2300

© 2026 Microsoft Corporation © Maxar ©CNES (2026) Distribution Airbus DS © Mapbox

SAN SAN

SAN

18001900200021002200230024002500

00000100

4713.005

A

B

2 3

C

D

1 2 3

4 5 6

PROJECT NO.

APPROVED BY:

SCALE:

CHECKED BY:

PREPARED BY:

A

B

D

AT

E R

EV

4 5

IS

SU

ED

F

O R

/R

EV

IS

ED

C

AP

PD

D

DRAWING NO.

Entech Engineering - Printed: Nov. 13, 2026 H:\0004713.005\04-CAD\SheetFiles\C-103.dwgLa st

E di te d by : A

A tti ck

C-103

NO

RT

HE

RN

L

AN

CA

ST

ER

C

O

UN

TY

A

UT

HO

RI

TY

BR

EC

KN

O

C K

TO

W

N

SH

IP

, L

AN

C

AS

TE

R C

O U

N

TY

, P

EN

N

SY

LV

AN

IA

W M

AP

LE

G

RO

VE

R

OA

D

AN

D

FI

VE

PO

IN

TV

IL

LE

R

OA

D

SE

W

ER

R

EP

AI

RS

AGS

ARA

AS NOTED

/1

2/

A

IN

TE

R N

AL

Q

C

AG

S

/2 0/

B

C

LI

EN

T R

EV

IE

W

AG

S

/1 3/

C

BI

D D

IN

G

AG

S

GENERAL PROJECT NOTES

1. REFER TO DRAWING G-001 FOR DRAWING INDEX, GENERAL PROJECT

NOTES, LEGEND AND DRAWING CONVENTIONS.

2. IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR FOR THE

REMOVAL AND DISPOSAL OF THE EXISTING SANITARY SEWER MAIN AND

SANITARY MANHOLES THAT ARE REMOVED FROM SERVICE.

3. CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE SLOPE OF EXISTING

SEWER PRIOR TO COMPLETING SPOT REPAIRS.

C

IV

IL

R

EA

D

IN

G

R O

AD

S

AN

IT

AR

Y

SE

W

ER

R

EP

AI

R P

LA

N

S (P

R O

JE

C

T

AR

EA

AN

D

5)

SCALE:1 1" = 30'

SANITARY SEWER REPAIR PLAN

READING ROAD (SR 0625 SEG 0160)

PROJECT AREA #4

00 30' 60'

PROPOSED 10'x10' ROAD OPENING MANHOLE RISER RINGS TO BE REMOVED

AND REPLACED W/ COMPOSITE RISER,

REPLACE EXTERIOR MANHOLE DROP

WITH INTERIOR DROP. EXISTING EXTERNAL

DROP MANHOLE TO BE PLUGGED AND

FILLED WITH CONCRETE.

SCALE:2 1" = 30'

SANITARY SEWER REPAIR PLAN

READING ROAD (SR 0625 SEG 0150)

PROJECT AREA #5

00 30' 60'

CUT EXISTING 8" PVC SANITARY

SEWER AND REPLACE WITH 45 LF OF

NEW SDR-26 PVC SANITARY SEWER

CUT EXISTING 8" PVC SANITARY

SEWER AND REPLACE WITH 95 LF OF

NEW SDR-26 PVC SANITARY SEWER

PROPOSED 12'x30' ROAD OPENING

(MILL, BASE PAVE AND REPAIR, AND OVERLAY)

PROPOSED 10'x95' ROAD OPENING

PROPOSED 12'x12' ROAD OPENING

(MILL, BASE PAVE AND REPAIR, AND OVERLAY)

PROPOSED 5'x45' ROAD OPENING

FILTER BAG INLET

PROTECTION - TYPE M

ES-501

E&S CONTROL NOTES

1. CONTRACTOR IS RESPONSIBLE TO COMPLY WITH CHAPTER 102

EROSION CONTROL RULES AND REGULATIONS AND FOLLOW GUIDANCE

IN THE PADEP EROSION AND SEDIMENT POLLUTION CONTROL PROGRAM

MANUAL.

2. CONTRACTOR TO LIMIT THE DISTURBED AREA TO THE MINIMUM AMOUNT

POSSIBLE FOR THE INSTALLATION.

3. THE INSTALLATION OF ALL REQUIRED EROSION AND SEDIMENT

CONTROL DEVICES SHALL OCCUR PRIOR TO EARTHMOVING ACTIVITIES.

4. E&S CONTROLS ARE TO REMAIN IN PLACE UNTIL ALL AREAS ARE

PROPERLY STABILIZED WITH A PERMANENT GROUND COVER.

5. PROVIDE TEMPORARY AND PERMANENT SEEDING PER THE

SPECIFICATIONS OF THE PADEP EROSION AND SEDIMENT POLLUTION

CONTROL PROGRAM MANUAL.

6. CONTRACTOR SHALL PREVENT THE TRACKING OF SEDIMENT ONTO

ADJOINING PAVED AREAS AND PUBLIC STREETS BY CONSTRUCTION

VEHICLES. SEDIMENT SHALL BE CLEANED FROM PAVED AREAS DAILY.

7. UNTIL THE SITE IS STABILIZED, ALL EROSION AND SEDIMENT BMPS

SHALL BE MAINTAINED PROPERLY BY THE CONTRACTOR. MAINTENANCE

SHALL INCLUDE INSPECTIONS OF ALL EROSION AND SEDIMENT BMPS

AFTER EACH RUNOFF EVENT AND ON A WEEKLY BASIS. ALL

PREVENTATIVE AND REMEDIAL MAINTENANCE WORK, INCLUDING CLEAN

OUT, REPAIR, REPLACEMENT, RE-GRADING, RESEEDING, RE-MULCHING

AND RE-NETTING MUST BE PERFORMED IMMEDIATELY. IF THE E&S BMPS

FAIL TO PERFORM AS EXPECTED, REPLACEMENT BMPS, OR

MODIFICATIONS OF THOSE INSTALLED WILL BE REQUIRED.

C-501

C-501 SHEET KEYNOTES

1. CONTRACTOR TO REMOVE AND REPLACE EXISTING GUIDE RAIL TO

FACILITATE INSTALLATION OF NEW RISER RINGS FOR MANHOLE. REFER

TO PENNDOT RC-51M FOR DETAILS OF GUARDRAIL INSTALLATION.

2. EXISTING LATERAL TO BE RECONNECTED TO NEW SANITARY SEWER

MAIN.

C-701

C-701

SR 0625

SEGMENT 0150

OFFSET 2564

SR 0625

SEGMENT 0160

OFFSET 0000

SR 0625

SEGMENT 0150

OFFSET 2141

FILTER BAG INLET

PROTECTION - TYPE M

ES-501

C-701

C-501

C-701

C-501RECONNECT EXISTING 6" SDR-26

SANITARY SEWER LATERAL

C-501

PROPOSED 10'x10' ROAD OPENING MANHOLE RISER RINGS TO BE REMOVED

AND REPLACED W/ COMPOSITE RISER

TOTAL LOD: 0.12 ACRES

TOTAL LOD: 0.12 ACRES

REFER TO SYSTEM DRAWINGS

C-501

C-701

C-701

SAN

010002000300040005000600

SAN SAN

0600070008000900100011001200

SL

SL

4713.005

A

B

2 3

C

D

1 2 3

4 5 6

PROJECT NO.

APPROVED BY:

SCALE:

CHECKED BY:

PREPARED BY:

A

B

D

AT

E R

EV

4 5

IS

SU

ED

F

O R

/R

EV

IS

ED

C

AP

PD

D

DRAWING NO.

Entech Engineering - Printed: Nov. 13, 2026 H:\0004713.005\04-CAD\SheetFiles\C-104.dwgLa st

E di te d by : A

A tti ck

C-104

NO

RT

HE

RN

L

AN

CA

ST

ER

C

O

UN

TY

A

UT

HO

RI

TY

BR

EC

KN

O

C K

TO

W

N

SH

IP

, L

AN

C

AS

TE

R C

O U

N

TY

, P

EN

N

SY

LV

AN

IA

W M

AP

LE

G

RO

VE

R

OA

D

AN

D

FI

VE

PO

IN

TV

IL

LE

R

OA

D

SE

W

ER

R

EP

AI

RS

AGS

ARA

AS NOTED

/1

2/

A

IN

TE

R N

AL

Q

C

AG

S

/2 0/

B

C

LI

EN

T R

EV

IE

W

AG

S

/1 3/

C

BI

D D

IN

G

AG

S

GENERAL PROJECT NOTES

1. REFER TO DRAWING G-001 FOR DRAWING INDEX, GENERAL PROJECT

NOTES, LEGEND AND DRAWING CONVENTIONS.

2. IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR FOR THE

REMOVAL AND DISPOSAL OF THE EXISTING SANITARY SEWER MAIN AND

SANITARY MANHOLES THAT ARE REMOVED FROM SERVICE.

C

IV

IL

R

EA

D

IN

G

R O

AD

S

AN

IT

AR

Y

SE

W

ER

R

EP

AI

R P

LA

N

S (P

R O

JE

C

T

AR

EA

S

#6 A

N D

7)

SCALE:1 1" = 30'

SANITARY SEWER REPAIR PLAN

READING ROAD (SR 0625 SEG 0150)

PROJECT AREA #6

00 30' 60'

CUT EXISTING 8" PVC SANITARY

SEWER AND REPLACE WITH 50 LF OF

NEW SDR-26 PVC SANITARY SEWER

PROPOSED 5'x50' ROAD OPENING PROPOSED 20'x80' ROAD OPENING (MILL, BASE PAVE AND REPAIR, AND OVERLAY) PROPOSED 10'x20' ROAD OPENING

(MILL, BASE PAVE AND REPAIR, AND OVERLAY)

SCALE:2 1" = 30'

SANITARY SEWER REPAIR PLAN

READING ROAD (SR 0625 SEG 0140)

PROJECT AREA #7

00 30' 60'

CUT EXISTING 8" PVC SANITARY

SEWER AND REPLACE WITH 40 LF

OF NEW SDR-26 PVC SANITARY SEWER

CUT EXISTING 8" PVC SANITARY

SEWER AND REPLACE WITH 40 LF

OF NEW SDR-26 PVC SANITARY SEWER

PROPOSED 10'x10' ROAD OPENING

MANHOLE RISER RINGS TO BE REMOVED

AND REPLACED W/ COMPOSITE RISER

PROPOSED 5'x40' ROAD OPENING

PROPOSED 5'x40' ROAD OPENING

FILTER BAG INLET

PROTECTION - TYPE M

FILTER BAG INLET

PROTECTION - TYPE M

FILTER BAG INLET

PROTECTION - TYPE M

ES-501

ES-501

ES-501

E&S CONTROL NOTES

1. CONTRACTOR IS RESPONSIBLE TO COMPLY WITH CHAPTER 102

EROSION CONTROL RULES AND REGULATIONS AND FOLLOW GUIDANCE

IN THE PADEP EROSION AND SEDIMENT POLLUTION CONTROL PROGRAM

MANUAL.

2. CONTRACTOR TO LIMIT THE DISTURBED AREA TO THE MINIMUM AMOUNT

POSSIBLE FOR THE INSTALLATION.

3. THE INSTALLATION OF ALL REQUIRED EROSION AND SEDIMENT

CONTROL DEVICES SHALL OCCUR PRIOR TO EARTHMOVING ACTIVITIES.

4. E&S CONTROLS ARE TO REMAIN IN PLACE UNTIL ALL AREAS ARE

PROPERLY STABILIZED WITH A PERMANENT GROUND COVER.

5. PROVIDE TEMPORARY AND PERMANENT SEEDING PER THE

SPECIFICATIONS OF THE PADEP EROSION AND SEDIMENT POLLUTION

CONTROL PROGRAM MANUAL.

6. CONTRACTOR SHALL PREVENT THE TRACKING OF SEDIMENT ONTO

ADJOINING PAVED AREAS AND PUBLIC STREETS BY CONSTRUCTION

VEHICLES. SEDIMENT SHALL BE CLEANED FROM PAVED AREAS DAILY.

7. UNTIL THE SITE IS STABILIZED, ALL EROSION AND SEDIMENT BMPS

SHALL BE MAINTAINED PROPERLY BY THE CONTRACTOR. MAINTENANCE

SHALL INCLUDE INSPECTIONS OF ALL EROSION AND SEDIMENT BMPS

AFTER EACH RUNOFF EVENT AND ON A WEEKLY BASIS. ALL

PREVENTATIVE AND REMEDIAL MAINTENANCE WORK, INCLUDING CLEAN

OUT, REPAIR, REPLACEMENT, RE-GRADING, RESEEDING, RE-MULCHING

AND RE-NETTING MUST BE PERFORMED IMMEDIATELY. IF THE E&S BMPS

FAIL TO PERFORM AS EXPECTED, REPLACEMENT BMPS, OR

MODIFICATIONS OF THOSE INSTALLED WILL BE REQUIRED.

C-501

C-501

C-701

C-701

C-701

C-501

C-701

C-5012

C-501

C-701

C-501

RECONNECT EXISTING 6" SDR-26

SANITARY SEWER LATERAL

RECONNECT EXISTING 6" SDR-26

SANITARY SEWER LATERAL

RECONNECT EXISTING 6" SDR-26

SANITARY SEWER LATERAL

RECONNECT EXISTING 6" SDR-26

SANITARY SEWER LATERAL

C-501

C-501

C-501

C-501

PROPOSED 12'x6' ROAD OPENING

(MILL, BASE PAVE AND REPAIR, AND OVERLAY)

C-701

TOTAL LOD: 0.12 ACRES

TOTAL LOD: 0.12 ACRES

PROPOSED 10'x10' ROAD OPENING

(MILL, BASE PAVE AND REPAIR, AND OVERLAY)

C-701

SHEET KEYNOTES

1. EXISTING LATERAL TO BE RECONNECTED TO NEW SANITARY SEWER

MAIN.

4713.005

A

B

2 3

C

D

1 2 3

4 5 6

PROJECT NO.

APPROVED BY:

SCALE:

CHECKED BY:

PREPARED BY:

A

B

D

AT

E R

EV

4 5

IS

SU

ED

F

O R

/R

EV

IS

ED

C

AP

PD

D

DRAWING NO.

Entech Engineering - Printed: Nov. 13, 2026 H:\0004713.005\04-CAD\SheetFiles\C-501.dwgLa st

E di te d by : A

A tti ck

C-501

NO

RT

HE

RN

L

AN

CA

ST

ER

C

O

UN

TY

A

UT

HO

RI

TY

BR

EC

KN

O

C K

TO

W

N

SH

IP

, L

AN

C

AS

TE

R C

O U

N

TY

, P

EN

N

SY

LV

AN

IA

W M

AP

LE

G

RO

VE

R

OA

D

AN

D

FI

VE

PO

IN

TV

IL

LE

R

OA

D

SE

W

ER

R

EP

AI

RS

AGS

ARA

AS NOTED

/1

2/

A

IN

TE

R N

AL

Q

C

AG

S

/2 0/

B

C

LI

EN

T R

EV

IE

W

AG

S

/1 3/

C

BI

D D

IN

G

AG

S

C O

N

ST

R U

C

TI

O N

D

ET

AI

LS

C

IV

IL

STRENGTH OF 3000 PSI AT THE END OF 28 DAYS

NOTE: ALL CONCRETE SHALL HAVE MINIMUM COMPRESSIVE

EXISTING WATER / STORM SEWER

NEW SEWER MAIN

EXIST. GRADE

" M

IN

8" 8"

8"8"

SCALE:3 NONE

EXISTING WATER/STORM SEWER UTILITY DETAIL

NEW SEWER LINE CROSSING UNDER

M

IN

3' -0

M

IN

WHEN VERTICAL SEPARATION IS LESS THAN

18" PROVIDE CONCRETE ENCASEMENT ON

UNDISTURBED GROUND. THE LENGTH OF THE

ENCASEMENT SHALL BE EXTENDED A MINIMUM OF

3 FEET BEYOND THE CENTERLINE OF THE STORM

SEWER (OR OTHER UTILITY) IN BOTH DIRECTIONS

SCALE:5 NONE

TYPICAL CONNECTION TO EXISTING MANHOLE

3'-0"+-

TYP. BOTH SIDES

SDR-26 COUPLING

(TYP. BOTH SIDES)

PROPOSED PVC PIPE PROPOSED PVC PIPE

SCALE:4 NONE

OUTSIDE DROP MANHOLE DETAIL

INSIDE DROP SANITARY EXISTING

NOTES:

1. CORE DRILL 4" LARGER THAN INFLUENT PIPE DIAMETER. PROVIDE A-LOK G3 BOOT SYSTEM.

INFLUENT

PVC PIPE DIA. EQUALS

INFLUENT PIPE DIA. PLUS 2"

STAINLESS STEEL

BANDS (2 MINIMUM)

W (2) A-316 BOLTS AND

ANCHORS@ 48" O.C.

A-LOK BOOT

SYSTEM SEAL (NOTE #1)

INSIDE DROP BOWL

(RELINER/DURAN INC.

OR EQUAL)

90° BEND

COMPOSITE

GRADE RINGS (VARIES,

MIN. 6", MAX. 12")

FILL OUTSIDE DROP

WITH CONCRETE

CONNECT TO EXISTING SANITARY

SEWER W/ SDR-26 COUPLING

SCALE:1 NONE

MANHOLE GRADE ADJUSTMENT DETAIL

PROPOSED SDR-26 PIPE

SCALE:2 NONE

SANITARY SEWER MAIN REPLACEMENT DETAIL

SDR-26 COUPLING

(TYP. BOTH SIDES)

EXISTING SANITARY SEWER

FL

O

W

SECTION

PLAN

SEWER MAIN

WYE

6" PVC BEND(S) AS REQUIRED

6" PVC SEWER LATERAL

6" PVC LATERAL SLOPE 1/4" PER FT. MIN.

6" BEND(S) AS REQUIRED

HOUSE LATERAL (BY OTHERS) WYE

SCALE:6 NONE

SANITARY SEWER LATERAL DETAIL

CONNECT TO EXISTING LATERAL

W/ SHIELDED FLEXIBLE COUPLING

3'

SDR-26 COUPLING

(TYP. BOTH SIDES)

6'-0"

PROVIDE HDPE MANHOLE INSERT

IV

IL

R

ES

TO

R

AT

IO

N

D

ET

AI

LS

4713.005

A

B

2 3

C

D

1 2 3

4 5 6

PROJECT NO.

APPROVED BY:

SCALE:

CHECKED BY:

PREPARED BY:

A

B

D

AT

E R

EV

4 5

IS

SU

ED

F

O R

/R

EV

IS

ED

C

AP

PD

D

DRAWING NO.

Entech Engineering - Printed: Nov. 13, 2026 H:\0004713.005\04-CAD\SheetFiles\C-701.dwgLa st

E di te d by : A

A tti ck

C-701

NO

RT

HE

RN

L

AN

CA

ST

ER

C

O

UN

TY

A

UT

HO

RI

TY

BR

EC

KN

O

C K

TO

W

N

SH

IP

, L

AN

C

AS

TE

R C

O U

N

TY

, P

EN

N

SY

LV

AN

IA

W M

AP

LE

G

RO

VE

R

OA

D

AN

D

FI

VE

PO

IN

TV

IL

LE

R

OA

D

SE

W

ER

R

EP

AI

RS

AGS

ARA

AS NOTED

/1

2/

A

IN

TE

R N

AL

Q

C

AG

S

/2 0/

B

C

LI

EN

T R

EV

IE

W

AG

S

/1 3/

C

BI

D D

IN

G

AG

S

REFER TO TRENCH

RESTORATION DETAILS

6" TOPSOIL AND SEED

ALL DISTURBED AREAS

1'-0"

CUTBACK

(TYP.)

SCALE:1 NONE

FOR GRASS AREAS

SURFACE RESTORATION DETAIL

1'-0"

CUTBACK

(TYP.)

REFER TO TRENCH

RESTORATION DETAILS

SCALE:2 FOR PAVED ROADWAY

SURFACE RESTORATION DETAIL

SAW-CUT FULL DEPTH

EXIST. PAVEMENT

(INITIAL SAW-CUT) (TYP.)

SAW-CUT FULL DEPTH

EXIST. PAVEMENT (TYP.)

1-1/2" SUPERPAVE ASPHALT DESIGN,

9.5MM, PG 64s-22, SRL H, WEARING COURSE

12" WIDE BITUMINOUS

SEAL PG 64s-22 (TYP.)

2-1/2" MIN. SUPERPAVE ASPHALT DESIGN,

19.0 MM, PG 64s-22, BINDER OR TO A DEPTH

OF EXIST. BINDING COURSE, WHICHEVER

IS GREATER (IF REQUIRED)

5" MIN. SUPERPAVE ASPHALT DESIGN,

25.0 MM, PG 64s-22, BASE OR TO A DEPTH

OF EXIST. BASE COURSE, WHICHEVER

IS GREATER

NOTES:

1. EXISTING PAVEMENT MARKINGS SHALL BE REPLACED IF DISTURBED.

NONE

PENNDOT PAVEMENT RESTORATION NOTES:

1. RESTORE WITH SUPERPAVE (25mm) TO SURFACE AND ALLOW TO SETTLE FOR 90 DAYS.

SUPERPAVE DEPTH OF 6-1/2" OR TO MATCH EXISTING PAVING, WHICHEVER IS GREATER.

2. MILL RESTORED AREA PLUS 1 FOOT TO EACH SIDE OF TRENCH TO 1-1/2" DEPTH.

3. PAVE MILLED AREA WITH 2.0" SPV (9.5mm).

4. SEAL EDGES WITH PG64S-22.

5. PAVEMENT SAWCUTTING SHALL PROVIDE A CLEAN AND NEAT EDGE AT RIGHT ANGLES OF

SURFACE OF PAVEMENT TO REMAIN.

6. ALL BACKFILL WITHIN OR ACROSS THE PENNDOT ROAD MUST BE TESTED FOR 100%

COMPACTION AND 4-INCH LIFTS MUST BE TAMPED.

7. ALL PAVEMENT MARKINGS, WHICH ARE DISTURBED, SHALL BE REPLACED IN KIND WITH

CURRENT PENNDOT STANDARDS AND SPECIFICATIONS.

6" M

IN

TRENCH WIDTH

AA

SH

TO

N

O . 8

M

AT

ER

IA

L

SH

AL

L

M

EE

T

TH

E R

EQ

U

IR

EM

EN

TS

O F

PE

N

N D

O T

PU

BL

IC

AT

IO

N

, 1

P

R O

C

TO

R D

EN

SI

TY

C

O M

PA

C

TE

D

IN

4"

L

IF

TS

, 8

" V

IB

R

AT

O R

Y

PROPOSED PIPE

TEMPORARY AND PERMANENT

PAVEMENT RESTORATION

PERMANENT PAVING

CROSS SECTION AS

REQUIRED BY STATE

OR TOWNSHIP

12"

UTILITY

WARNING TAPE

2A COARSE

AGGREGATE BACKFILL

4' -0

" M

IN

IM

U

M C

O

VE

R

TEMPORARY PERMANENT

TEMPORARY

PAVEMENT 6-1/2"

MIN. SUPERPAVE (25 mm)

12" 12"

SEAL EDGE WITH PG64S-22

(RESTORATION ONLY)

2" WEARING COURSE

SCALE:3 NONE

PAVED AREAS WITHIN PENNDOT RIGHT-OF-WAY

TRENCH RESTORATION DETAIL FOR EXISTING

SPAV, WRG, PG 64S-22, 12.5 MM MIX,

3.0 TO < 10.0 MILLION ESALS,

DEPTH 2.0", SRL-H

O

N

TR

O L

D

ET

AI

LS

ER

O

SI

O

N A

N D

S

ED

IM

EN

TA

TI

O N

2 MIN. (TYP.)

INSTALLATION DETAIL

ISOMETRIC VIEW

PLAN VIEW

SCALE:3 NONE

FILTER BAG INLET PROTECTION - TYPE M INLET

STANDARD CONSTRUCTION DETAIL #4-16

2'

4'

3'

WIDTH LENGTH

FLOW

ELEVATION VIEW FLOW

NOTES:

1. MAXIMUM DRAINAGE AREA= 1/2 ACRE

2. INLET PROTECTION SHALL NOT BE REQUIRED FOR INLET TRIBUTARY TO SEDIMENT BASIN OR TRAP.

BERMS SHALL BE REQUIRED FOR ALL INSTALLATIONS.

3. ROLLED EARTHEN BERM SHALL BE PROVIDED AND MAINTAINED IMMEDIATELY DOWN GRADIENT OF THE PROTECTED INLET UNTIL ROADWAY IS STONED. ROAD SUB-BASE BERM SHALL BE MAINTAINED UNTIL ROADWAY IS PAVED. SIX INCH MINIMUM HEIGHT ASPHALT BERM SHALL BE MAINTAINED UNTIL

ROADWAY SURFACE RECEIVES FINAL COAT.

4. AT A MINIMUM, THE FABRIC SHALL HAVE A MINIMUM GRAB TENSILE STRENGTH OF 120 LBS, A MINIMUM BURST STRENGTH OF 200 PSI, AND A MINIMUM TRAPEZOIDAL TEAR STRENGTH OF 50 LBS. FILTER

BAGS SHALL BE CAPABLE OF TRAPPING ALL PARTICLES NOT PASSING A NO. 40 SIEVE.

5. INLET FILTER BAGS SHALL BE INSPECTED ON A WEEKLY BASIS AND AFTER EACH RUNOFF EVENT.

BAGS SHALL BE EMPTIED AND RINSED OR REPLACED WHEN HALF FULL OR WHEN FLOW CAPACITY

HAS BEEN REDUCED SO AS TO CAUSE FLOODING OR BYPASSING OF THE INLET. DAMAGED OR

CLOGGED BAGS SHALL BE REPLACED. A SUPPLY SHALL BE MAINTAINED ON SITE FOR REPLACEMENT OF BAGS. ALL NEEDED REPAIRS SHALL BE INITIATED IMMEDIATELY AFTER THE INSPECTION. DISPOSE

OF ACCUMULATED SEDIMENT AS WELL AS ALL USE BAGS ACCORDING TO THE PLAN NOTES

6. DO NOT USE ON MAJOR PAVED ROADWAYS WHERE PONDING MAY CAUSE TRAFFIC HAZARDS.

EXPANSION RESTRAINT

(1/4" NYLON ROPE)

2" x 2" x 3/4"

RUBBER BLOCK

1" REBAR FOR

BAG REMOVAL

FROM INLET

REMOVAL

FROM INLET

6" MIN. HEIGHT

BERM

3:1

EARTHEN BERM TO BE STABILIZED

W/ TEMPORARY OR PERMANENT

VEGETATION

2 MIN. : 1STORM

INLET

EXTEND BERM OVER CURB

IF RUN-OFF IS BYPASSING

INLET ON LANDWARD SIDE

GENERAL SHEET NOTES

1. REFER TO DRAWING G-001 FOR DRAWING INDEX, GENERAL PROJECT

NOTES, LEGEND & DRAWING CONVENTIONS.

4713.005

A

B

2 3

C

D

1 2 3

4 5 6

PROJECT NO.

APPROVED BY:

SCALE:

CHECKED BY:

PREPARED BY:

A

B

D

AT

E R

EV

4 5

IS

SU

ED

F

O R

/R

EV

IS

ED

C

AP

PD

D

DRAWING NO.

Entech Engineering - Printed: Nov. 13, 2026 H:\0004713.005\04-CAD\SheetFiles\ES-501.dwgLa st

E di te d by : A

A tti ck

ES-501

NO

RT

HE

RN

L

AN

CA

ST

ER

C

O

UN

TY

A

UT

HO

RI

TY

BR

EC

KN

O

C K

TO

W

N

SH

IP

, L

AN

C

AS

TE

R C

O U

N

TY

, P

EN

N

SY

LV

AN

IA

W M

AP

LE

G

RO

VE

R

OA

D

AN

D

FI

VE

PO

IN

TV

IL

LE

R

OA

D

SE

W

ER

R

EP

AI

RS

AGS

ARA

AS NOTED

/1

2/

A

IN

TE

R N

AL

Q

C

AG

S

/2 0/

B

C

LI

EN

T R

EV

IE

W

AG

S

/1 3/

C

BI

D D

IN

G

AG

S

SCALE:1 NONE

PUMPED WATER FILTER BAG

STANDARD CONSTRUCTION DETAIL #3-16

LOW VOLUME FILTER BAGS SHALL BE MADE FROM NON-WOVEN GEOTEXTILE MATERIAL

SEWN WITH HIGH STRENGTH, DOUBLE STITCHED "J" TYPE SEAMS. THEY SHALL BE

CAPABLE OF TRAPPING PARTICLES LARGER THAN 151 MICRONS. HIGH VOLUME FILTER

BAGS SHALL BE MADE FROM WOVEN GEOTEXTILES THAT MEET THE FOLLOWING

STANDARDS:

PROPERTY TEST METHOD MINIMUM STANDARD

AVG. WIDE WIDTH STRENGTH ASTM D-4884 60 lb/in

GRAB TENSILE ASTM D-4632 205 lb

PUNCTURE ASTM D-4833 110 lb

MULLEN BURST ASTM D-3786 350 psi

UV RESISTANCE ASTM D-4355 70%

AOS % RETAINED ASTM D-4751 80 Sieve

NOTES:

1. A SUITABLE MEANS OF ACCESSING THE BAG WITH MACHINERY REQUIRED FOR DISPOSAL PURPOSES SHALL BE PROVIDED. FILTER BAGS SHALL BE REPLACED WHEN THEY BECOME 1/2 FULL OF SEDIMENT.

SPARE BAGS SHALL BE KEPT AVAILABLE FOR REPLACEMENT OF THOSE THAT HAVE FAILED OR ARE FILLED. BAGS SHALL BE PLACED ON STRAPS TO FACILITATE REMOVAL UNLESS BAGS COME WITH

LIFTING STRAPS ALREADY ATTACHED.

2. BAGS SHALL BE LOCATED IN WELL-VEGETATED (GRASSY) AREA, AND DISCHARGE ONTO STABLE, EROSION RESISTANT AREAS. WHERE THIS IS NOT POSSIBLE, A GEOTEXTILE UNDERLAYMENT AND FLOW

PATH SHALL BE PROVIDED. BAGS MAY BE PLACED ON FILTER STONE TO INCREASE DISCHARGE

CAPACITY. BAGS SHALL NOT BE PLACED ON SLOPES GREATER THAN 5%. FOR SLOPES EXCEEDING 5%, CLEAN ROCK OR OTHER NON-ERODIBLE AND NON-POLLUTING MATERIAL MAY BE PLACED UNDER THE

BAG TO REDUCE SLOPE STEEPNESS.

3. NO DOWNSLOPE SEDIMENT BARRIER IS REQUIRED FOR MOST INSTALLATIONS. COMPOST BERM OR COMPOST FILTER SOCK SHALL BE INSTALLED BELOW BAGS LOCATED IN HQ OR EV WATERSHEDS, WITHIN 50 FT. OF ANY RECEIVING SURFACE WATER OR WHERE GRASSY AREA IS NOT AVAILABLE.

4. THE PUMP DISCHARGE HOSE SHALL BE INSERTED INTO BAGS IN THE MANNER SPECIFIED BY THE

MANUFACTURER AND SECURELY CLAMPED. A PIECE OF PVC PIPE IS RECOMMENDED FOR THIS

PURPOSE.

5. THE PUMPING RATE SHALL BE NO GREATER THAN 750 GPM OR 1/2 THE MAXIMUM SPECIFIED BY THE

MANUFACTURER, WHICHEVER IS LESS. PUMP INTAKES SHALL BE FLOATING AND SCREENED.

6. FILTER BAGS SHALL BE INSPECTED DAILY. IF ANY PROBLEM IS DETECTED, PUMPING SHALL CEASE

IMMEDIATELY AND NOT RESUME UNTIL THE PROBLEM IS CORRECTED.

FILTER BAG

FILTER BAG

WELL VEGETATED, GRASSY AREA

PUMP

INTAKE HOSE

CLAMPS

DISCHARGE HOSE

HEAVY DUTY LIFTING STRAPS

(RECOMMENDED)

INTAKE HOSE

CLAMPS

DISCHARGE HOSE

PUMP

WELL VEGETATED, GRASSY AREA

ELEVATION VIEW

PLAN VIEW

COMPOST FILTER

SOCK RING REQUIRED

FOR THIS INSTALLATION

NOTE:

FOR SPECIAL PROTECTION WATERSHED, COMPOST BERM OR COMPOST FILTER SOCK SHALL

BE INSTALLED BELOW BAGS LOCATED IN HQ OR EV WATERSHEDS, WITHIN 50 FT. OF ANY

RECEIVING SURFACE WATER OR WHERE GRASSY AREA IS NOT AVAILABLE.

2 MIN.(TYP.)

1' MIN.

CURB

INSTALLATION DETAIL

ISOMETRIC VIEW

PLAN VIEW

SCALE:2 NONE

FILTER BAG INLET PROTECTION - TYPE C INLET

STANDARD CONSTRUCTION DETAIL #4-15

2'

4'

3'

WIDTH LENGTH

TOP OF CURB

FLOW

ELEVATION VIEW

EXTEND BERM OVER CURB

IF RUNOFF IS BYPASSING

INLET ON LANDWARD SIDE

NOTES:

1. MAXIMUM DRAINAGE AREA= 1/2 ACRE

2. INLET PROTECTION SHALL NOT BE REQUIRED FOR INLET TRIBUTARY TO SEDIMENT BASIN OR

TRAP. BERMS SHALL BE REQUIRED FOR ALL INSTALLATIONS.

3. ROLLED EARTHEN BERM SHALL BE PROVIDED AND MAINTAINED IMMEDIATELY DOWN GRADIENT

OF THE PROTECTED INLET UNTIL ROADWAY IS STONED. ROAD SUB-BASE BERM SHALL BE

MAINTAINED UNTIL ROADWAY IS PAVED. SIX INCH MINIMUM HEIGHT ASPHALT BERM SHALL BE

MAINTAINED UNTIL ROADWAY SURFACE RECEIVES FINAL COAT.

4. AT A MINIMUM, THE FABRIC SHALL HAVE A MINIMUM GRAB TENSILE STRENGTH OF 120 LBS, A

MINIMUM BURST STRENGTH OF 200 PSI, AND A MINIMUM TRAPEZOIDAL TEAR STRENGTH OF 50

LBS. FILTER BAGS SHALL BE CAPABLE OF TRAPPING ALL PARTICLES NOT PASSING A NO. 40

SIEVE.

5. INLET FILTER BAGS SHALL BE INSPECTED ON A WEEKLY BASIS AND AFTER EACH RUNOFF EVENT.

BAGS SHALL BE EMPTIED AND RINSED OR REPLACED WHEN HALF FULL OR WHEN FLOW

CAPACITY HAS BEEN REDUCED SO AS TO CAUSE FLOODING OR BYPASSING OF THE INLET.

DAMAGED OR CLOGGED BAGS SHALL BE REPLACED. A SUPPLY SHALL BE MAINTAINED ON SITE

FOR REPLACEMENT OF BAGS. ALL NEEDED REPAIRS SHALL BE INITIATED IMMEDIATELY AFTER

THE INSPECTION. DISPOSE OF ACCUMULATED SEDIMENT AS WELL AS ALL USE BAGS ACCORDING

TO THE PLAN NOTES

6. DO NOT USE ON MAJOR PAVED ROADWAYS WHERE PONDING MAY CAUSE TRAFFIC HAZARDS.

SANDBAG, FILTER LOG,

COMPOST SOCK OR

FILTER TUBE

EXPANSION RESTRAINT

(1/4" NYLON ROPE)

2" x 2" x 3/4"

RUBBER BLOCK

1" REBAR FOR BAG REMOVAL FROM

INLET REMOVAL FROM INLET

BERM

BERM

STORM

INLET

Sheets and Views
G-001-NLCA
G-101-NLCA
C-101-NLCA
C-102-NLCA
C-103-NLCA
C-104-NLCA
C-501-NLCA
C-701-NLCA
ES-501-24x36

File details come from the government source that posted it. Updated .